NOTE: REFER TO "TYPICAL COMMUNICATION OUTLET DETAIL" ON DRAWING E4.1 FOR BOX & CONDUIT REQUIREMENTS. CABLING AND TERMINALS WILL BE PROVIDED BY THE OWNER. SYMBOL DESCRIPTION `ljjrkf`^qflkp=ibdbka TELECOMMUNICATIONS OUTLET, MOUNT AT +3'-10"AFF. TELECOMMUNICATIONS OUTLET, MOUNT AT +1'-6"AFF. OWNER PROVIDED TELECOMMUNICATIONS EQUIPMENT RACK. TELECOMMUNICATIONS GROUND BUS BAR, MOUNT AT +1'-6"AFF. TELECOMMUNICATIONS MAIN GROUND BUS BAR, MOUNT AT +1'-6"AFF. TGB TMGB DPS EL RX DOOR POSITION SWITCH. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1 ELECTRIC LOCK. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1 REQUEST TO EXIT. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1 BL CARD READER. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1 EMERGENCY PHONE. PROVIDE RECESSED BOX MOUNT AT +3'-10"AFF WITH 1" EC TO MDF ROOM CR SYMBOL DESCRIPTION cfob=^i^oj=ibdbka FIRE ALARM AUDIO/VISUAL ANNUNCIATOR, MOUNT AT +7'-10"AFF OR 6" BELOW FINISHED CEILING, WHICHEVER IS LOWER. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING. FIRE ALARM VISUAL STROBE ANNUNCIATOR, MOUNT AT +7'-10"AFF OR 6" BELOW FINISHED CEILING, WHICHEVER IS LOWER. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING. FIRE ALARM MANUAL PULL STATION, MOUNT AT +3'-10"AFF. F FIRE ALARM DUCT SMOKE DETECTOR, FURNISH AND CONNECT UNDER DIVISION 28. INSTALL UNDER DIVISION 23. VERIFY LOCATION WITH DIVISION 23 PRIOR TO ROUGH-IN. PROVIDE ACCESSIBLE KEY OPERATED REMOTE TEST SWITCH FOR EACH DETECTOR. SMOKE DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD. HEAT DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD. S H FIRE ALARM TAMPER SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28. TS FIRE ALARM FLOW SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28. FS POST INDICATOR VALVE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28. PV FIRE ALARM PRESSURE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28. PS FIRE ALARM REMOTE INDICATOR, CEILING MOUNT. RI FIRE ALARM MONITOR MODULE. NOT ALL MONITOR MODULES ARE INDICATED ON DRAWINGS. PROVIDE QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED MONITORING FUNCTIONS. M C FIRE ALARM CONTROL MODULE. NOT ALL CONTROL MODULES ARE INDICATED ON DRAWINGS. PROVIDE QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED CONTROL FUNCTIONS. FIRE ALARM SPRINKLER BELL, MOUNT AT +10'-0"AFF. B FIRE ALARM MAGNETIC DOOR HOLDER, WALL MOUNT DEVICE AT 6" BELOW TOP OF DOOR. PROVIDE HINGED MAGNETIC CATCH PLATE ON DOOR TO MATE WITH DEVICE, COORDINATE LOCATION AND LENGTH WITH DIVISION 08. PROVIDE CONCEALED 120-VOLT POWER CONNECTION AND FIRE ALARM CONTROL MODULE IF REQUIRED FOR PROPER OPERATION. FIRE ALARM DOOR HOLDER/CLOSER HARDWARE UNDER DIVISION 08, MONITOR AND CONTROL INTERFACE WITH FIRE ALARM UNDER DIVISION 28. FIRE ALARM/POWER CONNECTION TO DIVISION 23 SMOKE OR FIRE/SMOKE DAMPER. COORDINATE WITH DIVISION 23. REFER TO TYPICAL FIRE/SMOKE DAMPER DIAGRAM. SD M M xx xx dbkbo^i=klqbp A. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER QUALITY. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY OF WORK. B. SUBSCRIPT LETTER BESIDE DEVICE INDICATES THE TYPE AS FOLLOWS: 3R WEATHERPROOF (NEMA 3R) W WALL MOUNT AT +4'-6"AFF P PILOT LIGHT AT THE SWITCH HANDLE WG WIRE GUARD C MOUNT +6" ABOVE COUNTER TOP BACK SPLASH C. FOLLOW MOUNTING HEIGHTS INDICATED IN THE ELECTRICAL LEGEND UNLESS OTHERWISE INDICATED. MEASURE ALL MOUNTING HEIGHTS FROM THE DEVICE CENTER LINE UNLESS OTHERWISE INDICATED. D. VERIFY EXACT FEEDER LOCATIONS FOR MECHANICAL EQUIPMENT. E. EQUIPMENT CONNECTIONS ARE INDICATED IN THEIR APPROXIMATE LOCATIONS. VERIFY EXACT LOCATIONS OF ALL CONNECTIONS WITH OTHER TRADES SUPPLYING EQUIPMENT TO AVOID CONFLICTS AT INSTALLATION. F. LOCATED ALL SWITCHES FOR LOCAL CONTROL OF LIGHTING ON STRIKE SIDE OF SINGLE DOORS UNLESS OTHERWISE INDICATED. G. PROVIDE SPECIFIC BREAKER ARRANGEMENT FOR THE PANEL BOARDS WHEREVER PHYSICALLY POSSIBLE. PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE TYPE WRITTEN PANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. H. ALL CONDUIT RUNS INDICATED ARE DIAGRAMMATIC, COORDINATE ROUTING IN ALL SPACES WITH OTHER TRADES. I. CONDUCTOR CROSS HATCHING IS INDICATED TO CLARIFY BRANCH CIRCUIT AND/OR SWITCHING ARRANGEMENTS. J. ALL PANELBOARDS INDICATED ARE HOUSED IN A SINGLE WIDTH ENCLOSURE, UNO. THE CONTRACTOR SHALL FIELD VERIFY ROOM LAYOUT AND ADJUST ACCORDINGLY, AT NO COST TO THE OWNER, IF PROVIDING ANY ADDTIONAL PANELBOARD ENCLOSURES. K. WHERE POWER AND COMMUNICATION OUTLETS ARE INDICATED IN CLOSE PROXIMITY ON THE DRAWINGS, FIELD COORDINATE THE LOCATIONS TO PLACE THE OUTLETS ADJACENT TO EACH OTHER. L. ALL EXTERIOR RECEPTACLES SHALL BE LABELED "WR" - WEATHER RESISTANT. M. PROVIDE MARKINGS ON CONCRETE SLAB FLOORS IN FRONT OF ELECTRICAL EQUIPMENT PER CPSM 6.16.14 SYMBOL DESCRIPTION ifdeqfkd=ibdbka LIGHT SWITCH, RATED 120/277 VOLTS, 20-AMPS, MOUNT AT +3'-10"AFF. SUBSCRIPT/SUPERSCRIPT LETTERS, NUMBERS, AND SYMBOLS INDICATES SWITCH TYPE AS FOLLOWS: 3 INDICATES 3-WAY LIGHT SWITCH 4 INDICATES 4-WAY LIGHT SWITCH D INDICATES DIMMER SWITCH. P INDICATES PILOT LIGHT, ON WHEN SWITCH IS ON K INDICATES KEY OPERATED LIGHT SWITCH OS INDICATES SWITCH WITH INTEGRAL OCCUPANCY SENSOR OS INDICATES DUAL RELAY INTEGRAL OCCUPANCY SENSOR, WIRED FOR MULTI-LEVEL SWITCHING LOWER CASE LETTER INDICATES LIGHT FIXTURE CONTROL DESIGNATION INDICATES SWITCHES WIRED FOR INBOARD/OUTBOARD SWITCHING. OMNI-DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, CEILING MOUNT. FLUORESCENT LIGHT FIXTURE, CEILING MOUNT. FLUORESCENT LIGHT FIXTURE ON EMERGENCY POWER, CEILING MOUNT. FIXTURE SHALL NOT BE CONTROLLED AND BE ILLUMINATED AT ALL TIMES UNO. LIGHTING FIXTURE. LIGHT FIXTURE ON EMERGENCY POWER, CEILING MOUNT. FIXTURE SHALL NOT BE CONTROLLED AND BE ILLUMINATED AT ALL TIMES UNO. LIGHT FIXTURE, WALL MOUNT, HEIGHT AS INDICATED. EMERGENCY EGRESS LIGHTING FIXTURE, WITH BATTERY PACK, WALL MOUNT AT +8'-0"AFF. EXIT SIGN, CEILING MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN. EXIT SIGN, WALL MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN. LIGHT FIXTURE, POLE MOUNT. 2 SYMBOL DESCRIPTION mltbo=ibdbka APPLIANCE RECEPTACLE, MOUNT AT +1'-6" AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOR EQUIPMENT SERVED. APPLIANCE RECEPTACLE, MOUNT AT +1'-6"AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOR EQUIPMENT SERVED. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE. DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE. DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE. DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF. DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE. GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. PROVIDE NEMA 3R "WHILE IN USE" ENCLOSURE. GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE. GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE. QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE. QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE. CORD REEL OUTLET, CEILING MOUNT. REFER TO DETAIL ON DRAWING E4.1 JUNCTION BOX, CONCEALED ABOVE CEILING, UNO. ENCLOSED CIRCUIT BREAKER, CHARACTERISTICS AS INDICATED. MUSHROOM SWITCH, HEAVY DUTY WITH LEGEND PLATE. MOUNT W/HANDLE AT +3'-10" AFF, UNO. MANUAL MOTOR STARTER, OVERLOAD PROTECTION AS REQUIRED PER NAME PLATE RATINGS, WITH 'ON' INDICATOR PILOT LIGHT. FLUSH MOUNT W/HANDLE AT +3'-10"AFF, UNO. DISCONNECT SWITCH, FUSIBLE OR NON-FUSIBLE AS INDICATED. MOUNT W/HANDLE AT +4'-6"AFF, UNO. MAGNETIC MOTOR STARTER, WITH OVERLOAD RELAYS AS REQUIRED TO SERVE MANUFACTURER REQUIREMENTS OF EQUIPMENT SERVED. PROVIDE WITH HAND-OFF-AUTOMATIC SELECTOR SWITCH AND INDICATOR LIGHTS.. MOUNT W/HANDLE AT +4'-6"AFF, UNO. COMBINATION MAGNETIC STARTER AND DISCONNECT SWITCH. WITH OVERLOAD ELEMENTS AND FUSING AS REQUIRED TO SERVE MANUFACTURER REQUIREMENTS OF EQUIPMENT SERVED. PROVIDE WITH HAND- OFF-AUTOMATIC SELECTOR SWITCH AND INDICATOR LIGHTS.. MOUNT W/HANDLE AT +4'-6"AFF, UNO. EQUIPMENT POWER CONNECTION. MOTOR CONNECTION. POWER FOR ELECTRIC DOOR LOCK CONNECTION. REFER TO DETAIL ON DRAWING E4.1 EMERGENCY GENERATOR. BRANCH CIRCUIT RUN CONCEALED, UNO. DASHED INDICATES CIRCUITRY REQUIRED TO BE RUN BELOW SLAB. STRAIGHT LINEWORK FOR CIRCUITRY INDICATES ON EMERGENCY POWER CIRCUIT. INDICATED FOR CLARITY ONLY, ACTUAL HOMERUN DESIGNATION OVERRIDES THIS SYMBOLOGY. BRANCH CIRCUIT HOME RUN TO PANELBOARD AND CIRCUIT INDICATED. PANELBOARD. TRANSFORMER, PROVIDE CONCRETE HOUSEKEEPING PAD UNLESS NOTED OTHERWISE. RELAY, N/O OR N/C AS INDICATED. RELAY, NORMALLY OPEN. RELAY, NORMALLY CLOSED. J CB E EL G T R FEEDER TAG. REFER TO FEEDER SCHEDULE ON DWG E5.1. XXX CLG INDICATES PARTITION IS A FIRE BARRIER. APPLY FIRE STOP FOR ALL PENETRATION POWER FOR EMERGENCY PHONE. PROVIDE RECESSED BOX ADJACENT TO COMMUNICATION OUTLET. BL POWER FOR VIDEO PROJECTION. PROVIDE CEILING MOUNTED OUTLET AS DIECTED BY THE OWNER. VP SYMBOL DESCRIPTION lkb=ifkb=af^do^j=ibdbka CIRCUIT BREAKER FUSED SWITCH TRANSFORMER TRANSFER SWITCH FEEDER DESIGNATION XXX CURRENT TRANSFORMER CT PT POTENTIAL TRANSFORMER ^o`efqb`qp jlpbibv K`lj TUM=ivkke^sbk=m^oht^vI=prfqb=OMM==sfodfkf^=_b^`eI=sfodfkf^=OPQRO melkb=ETRTF=PSUJOUMM===c^u=ETRTF=PSUJOOPP PROJECT NO: DATE: 01/15/16 NLNNLOMNS=QWQSWMT=mj ibdbkapI ^__obsf^qflkp ^ka=dbkbo^i klqbp g^jbp=j^afplk=rkfsbopfqv rkfsbopfqv=pbosf`bp=^kkbu `ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^ bMKN pq^qb=molgb`q=`labW=ONSJNUNPRJMMM 545116 NOVEMBER 16, 2015 ^__obsf^qflkp 1P SINGLE PHASE 3P THREE PHASE A AMPS ABI ADDITIVE BID ITEM (REFER TO BID FORM) AFF ABOVE FINISHED FLOOR AL ALUMINUM ATS AUTOMATIC TRANSFER SWITCH BFC BELOW FINISHED CEILING BFG BELOW FINISHED GRADE BKR BREAKER BOCT BOTTOM OF CABLE TRAY C CONDUIT CATV COMMUNITY ANTENNA TELEVISION (CABLE) CB CIRCUIT BREAKER CBL CABLE CCTV CLOSED CIRCUIT TELEVISION CKT CIRCUIT CLG CEILING CLR CLEAR CO. COMPANY COMB COMBINATION COMM COMMUNICATIONS CU COPPER DIA DIAMETER DISC DISCONNECT DIV DIVISION DWG DRAWING EBH ELECTRIC BASEBOARD HEATER EC EMPTY CONDUIT ECS EMERGENCY COMMUNICATIONS STATION ELEC ELECTRICAL ELEV ELEVATOR EQ EQUIPMENT ETR EXISTING TO REMAIN EWC ELECTRIC WATER COOLER EX EXISTING EXT EXTERIOR FA FIRE ALARM FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL FAGP FIRE ALARM GRAPHIC PANEL FAXP FIRE ALARM EXTENDER PANEL FFSCP FIRE FIGHTER'S SMOKE CONTROL PANEL FLA FULL LOAD AMPS FPMR FUSE PER MANUFACTURERS REQUIREMENTS/RECOMMENDATIONS FPND FUSE PER NAMEPLATE DATA G GROUND GE GROUND FAULT PROTECTION FOR EQUIPMENT, 6-50mA PER NEC 427.22 (PROVIDE ACCESSORY FOR INDICATED BREAKER) GFCI GROUND FAULT CIRCUIT INTERRUPT GFP GROUND FAULT PROTECTION FOR PERSONNEL, 4-6mA (PROVIDE ACCESSORY FOR INDICATED BREAKER) HC HORIZONTAL CROSS CONNECT HP HORSEPOWER HPS HIGH PRESSURE SODIUM Hz HERTZ IAW IN ACCORDANCE WITH IC INTERMEDIATE CROSS-CONNECT IG ISOLATED GROUND J-BOX JUNCTION BOX KHFSS KITCHEN HOOD FIRE SUPPRESSION SYSTEM KHz KILOHERTZ KVA KILOVOLT AMPS KW KILOWATTS KWH KILOWATT HOURS L LOCKOUT TO PREVENT UNAUTHORIZED SWITCHING (PROVIDE ACCESSORY FOR INDICATED BREAKER) LC ROUTE CIRCUIT TO LOAD VIA LIGHTING CONTACTOR, REFER TO LC SCHEDULE LED LIGHT EMITTING DIODE LTG LIGHTING LTS LIGHTS MAX MAXIMUM MC MAIN CROSS CONNECT MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MH METAL HALIDE MHz MEGAHERTZ MIN MINIMUM ML MAINTENANCE LOCK (PROVIDE ACCESSORY FOR INDICATED BREAKER) MLO MAIN LUG ONLY MNS MASS NOTIFICATION SYSTEM MOCP MAXIMUM OVER CURRENT PROTECTION. MTD MOUNTED N NEUTRAL N/C NORMALLY CLOSED N/O NORMALLY OPEN NO. NUMBER PBD PANELBOARD PD PROTECTIVE DEVICE RCPT RECEPTACLE REC RECEPTACLE SCP SECURITY CONTROL PANEL SEC SECURITY SPD SURGE PROTECTIVE DEVICE SPEC. SPECIFICATION(S) ST SHUNT TRIP, 120V COIL (PROVIDE ACCESSORY FOR INDICATED BREAKER) SW SWITCH SWBD SWITCHBOARD TBB TELECOMMUNICATIONS BONDING BACKBONE TC TELECOMMUNICATIONS CLOSET TELECOM TELECOMMUNICATIONS TGB TELECOMMUNICATIONS GROUNDING BUS BAR TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR TYP TYPICAL UNO UNLESS NOTED (INDICATED) OTHERWISE V VOLTS VFD VARIABLE FREQUENCY DRIVE W WATTS W/ WITH XFER TRANSFER XFMR TRANSFORMER ifdeq=cfuqrob=p`ebarib TYPE DESCRIPTION CATALOG NUMBER LAMP QUANTITY WATTAGE LAMP TYPE VOLTAGE MOUNTING REMARKS A1 2X4 RECESSED INDIRECT 2RTL4 24EN LEPC24 1 49 LED 277 V RECESSED 4800 LUMENS MIN A2 2X4 INDIRECT - STEP DIM 2RTL4 24EN LEPC24 1 49 LED 277 V RECESSED BI LEVEL DIMMING, 4800 LUMENS MIN B2 2X2 INDIRECT - STEP DIM 2RTL2 22EN LEPC22 1 24 LED 277 V RECESSED BI LEVEL DIMMING, 2400 LUMENS MIN C1 2X4 TROFFER 2TL4 GRLED LJT24 1 75 LED 277 V RECESSED 4600 LUMENS MIN D1 2X2 TROFFER 2GTL2 GRLED LJT22 1 37 LED 277 V RECESSED 3000 LUMENS MIN E1 UTILITY FIXTURE STL4 RZNNL3 DCLLED 1 48 LED 277 V PENDANT 4800 LUMENS MIN, 12' MH IN SHOPS, 10'MH ELSEWHERE F1 DAMP LOCATION WL4 S1232 LCL 1 39 LED 277 V SURFACE 4000 LUMENS MIN G1 8" DOWNLIGHT EVO35-29 LED8-DLM30 LF8LED8G4 1 39 LED 277 V RECESSED 3700 LUMENS MIN, DIMMING X1 SINGLE FACE EXIT FIXTURE LES LPDC SE 1 10 LED 277 V UNIVERSAL X2 DOUBLE FACE EXIT FIXTURE LES LPDC SE 1 10 LED 277 V UNIVERSAL Y1 WALL MTD SITE FIXTURE WST LED IST1 LNC2-12LU 1 39 LED 277 V WALL INTERGAL PHOTOCELL, 1600 LUMENS MIN Z1 POLE MTD SITE FIXTURE KAD-LED GLEON CL1-A-60LU 1 109 LED 277 V 4"X25' SQ POLE TYPE 3 DIST., INTERGAL PHOTOCELL, 8000 LUMENS MIN `lab=obcbobkb`bp a) CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL: CPSM, 2014, REV 0 – 10/15/14 b) NATIONAL ELECTRIC CODE/ NPFA 70: NEC, 2011 c) VIRGINIA UNIFORM STATEWIDE BUILDING CODE: VUSBC, 2012 (INCLUDING VECC) d) AMERICANS WITH DISABILITIES ACT: ASAD, SEPTEMBER 15, 2010 e) NATIONAL FIRE ALARM CODE/ NFPA 72, 2007 REVISIONS DATE DESCRIPTION

Transcript of C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff....

Page 1: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

NOTE: REFER TO "TYPICAL COMMUNICATION OUTLET DETAIL" ON DRAWING E4.1 FOR BOX & CONDUIT REQUIREMENTS.CABLING AND TERMINALS WILL BE PROVIDED BY THE OWNER.

SYMBOL DESCRIPTION

`ljjrkf`^qflkp=ibdbka

TELECOMMUNICATIONS OUTLET, MOUNT AT +3'-10"AFF.

TELECOMMUNICATIONS OUTLET, MOUNT AT +1'-6"AFF.

OWNER PROVIDED TELECOMMUNICATIONS EQUIPMENT RACK.

TELECOMMUNICATIONS GROUND BUS BAR, MOUNT AT +1'-6"AFF.

TELECOMMUNICATIONS MAIN GROUND BUS BAR, MOUNT AT +1'-6"AFF.

TGB

TMGB

DPS

EL

RX

DOOR POSITION SWITCH. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1

ELECTRIC LOCK. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1

REQUEST TO EXIT. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1

BL

CARD READER. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1

EMERGENCY PHONE. PROVIDE RECESSED BOX MOUNT AT +3'-10"AFF WITH 1" EC TO MDF ROOM

CR

SYMBOL DESCRIPTION

cfob=^i^oj=ibdbka

FIRE ALARM AUDIO/VISUAL ANNUNCIATOR, MOUNT AT +7'-10"AFF OR 6" BELOW FINISHED CEILING, WHICHEVERIS LOWER. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING.

FIRE ALARM VISUAL STROBE ANNUNCIATOR, MOUNT AT +7'-10"AFF OR 6" BELOW FINISHED CEILING,WHICHEVER IS LOWER. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING.

FIRE ALARM MANUAL PULL STATION, MOUNT AT +3'-10"AFF.F

FIRE ALARM DUCT SMOKE DETECTOR, FURNISH AND CONNECT UNDER DIVISION 28. INSTALL UNDERDIVISION 23. VERIFY LOCATION WITH DIVISION 23 PRIOR TO ROUGH-IN. PROVIDE ACCESSIBLE KEYOPERATED REMOTE TEST SWITCH FOR EACH DETECTOR.

SMOKE DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.

HEAT DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.

S

H

FIRE ALARM TAMPER SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.TS

FIRE ALARM FLOW SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.FS

POST INDICATOR VALVE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.PV

FIRE ALARM PRESSURE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.PS

FIRE ALARM REMOTE INDICATOR, CEILING MOUNT.RI

FIRE ALARM MONITOR MODULE. NOT ALL MONITOR MODULES ARE INDICATED ON DRAWINGS.PROVIDE QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED MONITORINGFUNCTIONS.

M

CFIRE ALARM CONTROL MODULE. NOT ALL CONTROL MODULES ARE INDICATED ON DRAWINGS.PROVIDE QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED CONTROLFUNCTIONS.

FIRE ALARM SPRINKLER BELL, MOUNT AT +10'-0"AFF.B

FIRE ALARM MAGNETIC DOOR HOLDER, WALL MOUNT DEVICE AT 6" BELOW TOP OF DOOR. PROVIDEHINGED MAGNETIC CATCH PLATE ON DOOR TO MATE WITH DEVICE, COORDINATE LOCATION AND LENGTHWITH DIVISION 08. PROVIDE CONCEALED 120-VOLT POWER CONNECTION AND FIRE ALARM CONTROLMODULE IF REQUIRED FOR PROPER OPERATION.

FIRE ALARM DOOR HOLDER/CLOSER HARDWARE UNDER DIVISION 08, MONITOR AND CONTROL INTERFACEWITH FIRE ALARM UNDER DIVISION 28.

FIRE ALARM/POWER CONNECTION TO DIVISION 23 SMOKE OR FIRE/SMOKE DAMPER. COORDINATE WITHDIVISION 23. REFER TO TYPICAL FIRE/SMOKE DAMPER DIAGRAM.

SD

M

M

xx

xx

dbkbo^i=klqbp

A. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IFREQUIRED BY ALL. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER QUALITY.

IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY OF WORK.

B. SUBSCRIPT LETTER BESIDE DEVICE INDICATES THE TYPE AS FOLLOWS:

3R WEATHERPROOF (NEMA 3R)W WALL MOUNT AT +4'-6"AFFP PILOT LIGHT AT THE SWITCH HANDLEWG WIRE GUARDC MOUNT +6" ABOVE COUNTER TOP BACK SPLASH

C. FOLLOW MOUNTING HEIGHTS INDICATED IN THE ELECTRICAL LEGEND UNLESS OTHERWISE INDICATED. MEASUREALL MOUNTING HEIGHTS FROM THE DEVICE CENTER LINE UNLESS OTHERWISE INDICATED.

D. VERIFY EXACT FEEDER LOCATIONS FOR MECHANICAL EQUIPMENT.

E. EQUIPMENT CONNECTIONS ARE INDICATED IN THEIR APPROXIMATE LOCATIONS. VERIFY EXACT LOCATIONS OF ALLCONNECTIONS WITH OTHER TRADES SUPPLYING EQUIPMENT TO AVOID CONFLICTS AT INSTALLATION.

F. LOCATED ALL SWITCHES FOR LOCAL CONTROL OF LIGHTING ON STRIKE SIDE OF SINGLE DOORS UNLESSOTHERWISE INDICATED.

G. PROVIDE SPECIFIC BREAKER ARRANGEMENT FOR THE PANEL BOARDS WHEREVER PHYSICALLY POSSIBLE.PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE TYPE WRITTENPANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT.

H. ALL CONDUIT RUNS INDICATED ARE DIAGRAMMATIC, COORDINATE ROUTING IN ALL SPACES WITH OTHER TRADES.

I. CONDUCTOR CROSS HATCHING IS INDICATED TO CLARIFY BRANCH CIRCUIT AND/OR SWITCHING ARRANGEMENTS.

J. ALL PANELBOARDS INDICATED ARE HOUSED IN A SINGLE WIDTH ENCLOSURE, UNO. THE CONTRACTOR SHALL FIELD VERIFY ROOM LAYOUT AND ADJUST ACCORDINGLY, AT NO COST TO THE OWNER, IF PROVIDING ANY ADDTIONAL PANELBOARD ENCLOSURES.

K. WHERE POWER AND COMMUNICATION OUTLETS ARE INDICATED IN CLOSE PROXIMITY ON THE DRAWINGS, FIELDCOORDINATE THE LOCATIONS TO PLACE THE OUTLETS ADJACENT TO EACH OTHER.

L. ALL EXTERIOR RECEPTACLES SHALL BE LABELED "WR" - WEATHER RESISTANT.

M. PROVIDE MARKINGS ON CONCRETE SLAB FLOORS IN FRONT OF ELECTRICAL EQUIPMENT PER CPSM 6.16.14

SYMBOL DESCRIPTION

ifdeqfkd=ibdbka

LIGHT SWITCH, RATED 120/277 VOLTS, 20-AMPS, MOUNT AT +3'-10"AFF. SUBSCRIPT/SUPERSCRIPT LETTERS,NUMBERS, AND SYMBOLS INDICATES SWITCH TYPE AS FOLLOWS:

3 INDICATES 3-WAY LIGHT SWITCH4 INDICATES 4-WAY LIGHT SWITCHD INDICATES DIMMER SWITCH.P INDICATES PILOT LIGHT, ON WHEN SWITCH IS ONK INDICATES KEY OPERATED LIGHT SWITCHOS INDICATES SWITCH WITH INTEGRAL OCCUPANCY SENSOROS INDICATES DUAL RELAY INTEGRAL OCCUPANCY SENSOR, WIRED FOR MULTI-LEVEL

SWITCHING

LOWER CASE LETTER INDICATES LIGHT FIXTURE CONTROL DESIGNATION

INDICATES SWITCHES WIRED FOR INBOARD/OUTBOARD SWITCHING.

OMNI-DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, CEILING MOUNT.

FLUORESCENT LIGHT FIXTURE, CEILING MOUNT.

FLUORESCENT LIGHT FIXTURE ON EMERGENCY POWER, CEILING MOUNT. FIXTURE SHALL NOT BECONTROLLED AND BE ILLUMINATED AT ALL TIMES UNO.

LIGHTING FIXTURE.

LIGHT FIXTURE ON EMERGENCY POWER, CEILING MOUNT. FIXTURE SHALL NOT BE CONTROLLED AND BEILLUMINATED AT ALL TIMES UNO.

LIGHT FIXTURE, WALL MOUNT, HEIGHT AS INDICATED.

EMERGENCY EGRESS LIGHTING FIXTURE, WITH BATTERY PACK, WALL MOUNT AT +8'-0"AFF.

EXIT SIGN, CEILING MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.

EXIT SIGN, WALL MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.

LIGHT FIXTURE, POLE MOUNT.

2

SYMBOL DESCRIPTION

mltbo=ibdbka

APPLIANCE RECEPTACLE, MOUNT AT +1'-6" AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOREQUIPMENT SERVED.

APPLIANCE RECEPTACLE, MOUNT AT +1'-6"AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOREQUIPMENT SERVED. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDERED DEVICE.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER, PROVIDERED DEVICE.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDERED DEVICE.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. PROVIDE NEMA 3R "WHILE IN USE"ENCLOSURE.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER,PROVIDE RED DEVICE.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER,PROVIDE RED DEVICE.

QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.

QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER,PROVIDE RED DEVICE.

QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.

QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER,PROVIDE RED DEVICE.

CORD REEL OUTLET, CEILING MOUNT. REFER TO DETAIL ON DRAWING E4.1

JUNCTION BOX, CONCEALED ABOVE CEILING, UNO.

ENCLOSED CIRCUIT BREAKER, CHARACTERISTICS AS INDICATED.

MUSHROOM SWITCH, HEAVY DUTY WITH LEGEND PLATE. MOUNT W/HANDLE AT +3'-10" AFF, UNO.

MANUAL MOTOR STARTER, OVERLOAD PROTECTION AS REQUIRED PER NAME PLATE RATINGS, WITH 'ON'INDICATOR PILOT LIGHT. FLUSH MOUNT W/HANDLE AT +3'-10"AFF, UNO.

DISCONNECT SWITCH, FUSIBLE OR NON-FUSIBLE AS INDICATED. MOUNT W/HANDLE AT +4'-6"AFF, UNO.

MAGNETIC MOTOR STARTER, WITH OVERLOAD RELAYS AS REQUIRED TO SERVE MANUFACTURERREQUIREMENTS OF EQUIPMENT SERVED. PROVIDE WITH HAND-OFF-AUTOMATIC SELECTOR SWITCH ANDINDICATOR LIGHTS.. MOUNT W/HANDLE AT +4'-6"AFF, UNO.

COMBINATION MAGNETIC STARTER AND DISCONNECT SWITCH. WITH OVERLOAD ELEMENTS AND FUSINGAS REQUIRED TO SERVE MANUFACTURER REQUIREMENTS OF EQUIPMENT SERVED. PROVIDE WITH HAND-OFF-AUTOMATIC SELECTOR SWITCH AND INDICATOR LIGHTS.. MOUNT W/HANDLE AT +4'-6"AFF, UNO.

EQUIPMENT POWER CONNECTION.

MOTOR CONNECTION.

POWER FOR ELECTRIC DOOR LOCK CONNECTION. REFER TO DETAIL ON DRAWING E4.1

EMERGENCY GENERATOR.

BRANCH CIRCUIT RUN CONCEALED, UNO. DASHED INDICATES CIRCUITRY REQUIRED TO BE RUN BELOWSLAB.

STRAIGHT LINEWORK FOR CIRCUITRY INDICATES ON EMERGENCY POWER CIRCUIT. INDICATED FORCLARITY ONLY, ACTUAL HOMERUN DESIGNATION OVERRIDES THIS SYMBOLOGY.

BRANCH CIRCUIT HOME RUN TO PANELBOARD AND CIRCUIT INDICATED.

PANELBOARD.

TRANSFORMER, PROVIDE CONCRETE HOUSEKEEPING PAD UNLESS NOTED OTHERWISE.

RELAY, N/O OR N/C AS INDICATED.

RELAY, NORMALLY OPEN.

RELAY, NORMALLY CLOSED.

J

CB

E

EL

G

T

R

FEEDER TAG. REFER TO FEEDER SCHEDULE ON DWG E5.1.XXX

CLG

INDICATES PARTITION IS A FIRE BARRIER. APPLY FIRE STOP FOR ALL PENETRATION

POWER FOR EMERGENCY PHONE. PROVIDE RECESSED BOX ADJACENT TO COMMUNICATION OUTLET.BL

POWER FOR VIDEO PROJECTION. PROVIDE CEILING MOUNTED OUTLET AS DIECTED BY THE OWNER.VP

SYMBOL DESCRIPTION

lkb=ifkb=af^do^j=ibdbka

CIRCUIT BREAKER

FUSED SWITCH

TRANSFORMER

TRANSFER SWITCH

FEEDER DESIGNATIONXXX

CURRENT TRANSFORMERCT

PT POTENTIAL TRANSFORMER

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWMT=mj

ibdbkapI

^__obsf^qflkp

^ka=dbkbo^i

klqbp

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bMKN

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

^__obsf^qflkp

1P SINGLE PHASE

3P THREE PHASE

A AMPS

ABI ADDITIVE BID ITEM (REFER TO BID FORM)

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

ATS AUTOMATIC TRANSFER SWITCH

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BKR BREAKER

BOCT BOTTOM OF CABLE TRAY

C CONDUIT

CATV COMMUNITY ANTENNA TELEVISION (CABLE)

CB CIRCUIT BREAKER

CBL CABLE

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CLR CLEAR

CO. COMPANY

COMB COMBINATION

COMM COMMUNICATIONS

CU COPPER

DIA DIAMETER

DISC DISCONNECT

DIV DIVISION

DWG DRAWING

EBH ELECTRIC BASEBOARD HEATER

EC EMPTY CONDUIT

ECS EMERGENCY COMMUNICATIONS STATION

ELEC ELECTRICAL

ELEV ELEVATOR

EQ EQUIPMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EX EXISTING

EXT EXTERIOR

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FAGP FIRE ALARM GRAPHIC PANEL

FAXP FIRE ALARM EXTENDER PANEL

FFSCP FIRE FIGHTER'S SMOKE CONTROL PANEL

FLA FULL LOAD AMPS

FPMR FUSE PER MANUFACTURERS REQUIREMENTS/RECOMMENDATIONS

FPND FUSE PER NAMEPLATE DATA

G GROUND

GE GROUND FAULT PROTECTION FOR EQUIPMENT, 6-50mA PER NEC 427.22 (PROVIDEACCESSORY FOR INDICATED BREAKER)

GFCI GROUND FAULT CIRCUIT INTERRUPT

GFP GROUND FAULT PROTECTION FOR PERSONNEL, 4-6mA (PROVIDE ACCESSORY FORINDICATED BREAKER)

HC HORIZONTAL CROSS CONNECT

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

Hz HERTZ

IAW IN ACCORDANCE WITH

IC INTERMEDIATE CROSS-CONNECT

IG ISOLATED GROUND

J-BOX JUNCTION BOX

KHFSS KITCHEN HOOD FIRE SUPPRESSION SYSTEM

KHz KILOHERTZ

KVA KILOVOLT AMPS

KW KILOWATTS

KWH KILOWATT HOURS

L LOCKOUT TO PREVENT UNAUTHORIZED SWITCHING (PROVIDE ACCESSORY FORINDICATED BREAKER)

LC ROUTE CIRCUIT TO LOAD VIA LIGHTING CONTACTOR, REFER TO LC SCHEDULE

LED LIGHT EMITTING DIODE

LTG LIGHTING

LTS LIGHTS

MAX MAXIMUM

MC MAIN CROSS CONNECT

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MH METAL HALIDE

MHz MEGAHERTZ

MIN MINIMUM

ML MAINTENANCE LOCK (PROVIDE ACCESSORY FOR INDICATED BREAKER)

MLO MAIN LUG ONLY

MNS MASS NOTIFICATION SYSTEM

MOCP MAXIMUM OVER CURRENT PROTECTION.

MTD MOUNTED

N NEUTRAL

N/C NORMALLY CLOSED

N/O NORMALLY OPEN

NO. NUMBER

PBD PANELBOARD

PD PROTECTIVE DEVICE

RCPT RECEPTACLE

REC RECEPTACLE

SCP SECURITY CONTROL PANEL

SEC SECURITY

SPD SURGE PROTECTIVE DEVICE

SPEC. SPECIFICATION(S)

ST SHUNT TRIP, 120V COIL (PROVIDE ACCESSORY FOR INDICATED BREAKER)

SW SWITCH

SWBD SWITCHBOARD

TBB TELECOMMUNICATIONS BONDING BACKBONE

TC TELECOMMUNICATIONS CLOSET

TELECOM TELECOMMUNICATIONS

TGB TELECOMMUNICATIONS GROUNDING BUS BAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR

TYP TYPICAL

UNO UNLESS NOTED (INDICATED) OTHERWISE

V VOLTS

VFD VARIABLE FREQUENCY DRIVE

W WATTS

W/ WITH

XFER TRANSFER

XFMR TRANSFORMER

ifdeq=cfuqrob=p`ebarib

TYPE DESCRIPTION CATALOG NUMBER

LAMPQUANTITY WATTAGE

LAMPTYPE VOLTAGE MOUNTING REMARKS

A1 2X4 RECESSED INDIRECT 2RTL424EN

LEPC24

1 49 LED 277 V RECESSED 4800 LUMENS MIN

A2 2X4 INDIRECT - STEP DIM 2RTL424EN

LEPC24

1 49 LED 277 V RECESSED BI LEVEL DIMMING, 4800 LUMENS MIN

B2 2X2 INDIRECT - STEP DIM 2RTL222EN

LEPC22

1 24 LED 277 V RECESSED BI LEVEL DIMMING, 2400 LUMENS MIN

C1 2X4 TROFFER 2TL4GRLEDLJT24

1 75 LED 277 V RECESSED 4600 LUMENS MIN

D1 2X2 TROFFER 2GTL2GRLEDLJT22

1 37 LED 277 V RECESSED 3000 LUMENS MIN

E1 UTILITY FIXTURE STL4RZNNL3DCLLED

1 48 LED 277 V PENDANT 4800 LUMENS MIN, 12' MH IN SHOPS, 10'MHELSEWHERE

F1 DAMP LOCATION WL4S1232LCL

1 39 LED 277 V SURFACE 4000 LUMENS MIN

G1 8" DOWNLIGHT EVO35-29LED8-DLM30LF8LED8G4

1 39 LED 277 V RECESSED 3700 LUMENS MIN, DIMMING

X1 SINGLE FACE EXIT FIXTURE LESLPDC

SE

1 10 LED 277 V UNIVERSAL

X2 DOUBLE FACE EXIT FIXTURE LESLPDC

SE

1 10 LED 277 V UNIVERSAL

Y1 WALL MTD SITE FIXTURE WST LEDIST1

LNC2-12LU

1 39 LED 277 V WALL INTERGAL PHOTOCELL, 1600 LUMENS MIN

Z1 POLE MTD SITE FIXTURE KAD-LEDGLEON

CL1-A-60LU

1 109 LED 277 V 4"X25' SQ POLE TYPE 3 DIST., INTERGAL PHOTOCELL, 8000LUMENS MIN

`lab=obcbobkb`bp

a) CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL: CPSM, 2014, REV 0 – 10/15/14b) NATIONAL ELECTRIC CODE/ NPFA 70: NEC, 2011c) VIRGINIA UNIFORM STATEWIDE BUILDING CODE: VUSBC, 2012 (INCLUDING VECC)d) AMERICANS WITH DISABILITIES ACT: ASAD, SEPTEMBER 15, 2010e) NATIONAL FIRE ALARM CODE/ NFPA 72, 2007

REVISIONS

DATE DESCRIPTION

Page 2: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

CR

CR

Z1

Z1

Z1

Z1

Z1

Z1

Z1

Z1 Z1

Z1 Z1

Z1

Z1

Z1

Z1

ELECTRICAL PRIMARY DUCTBANK.REFER TO CIVIL PLAN FORCONTINUATION AND TO POWERPLAN FOR DETAILS

APPROXIMATE LOCATION OFELECTRICAL ROOMS

APPROXIMATE LOCATIONOF MDF ROOM

ELECTRICAL SERVICESECONDARY. REFER TO POWERPLAN FOR ADDITIONAL DETAIL

REFER TO CIVIL PLANSFOR DEMOLITION OFLIGHTING IN THIS AREA.

Z1

Z1

Z1

Z1

Z1

H1B-7

H1B-7

H1B-7

H1B-7

H1B-7

GENERATOR DUCTBANK.REFER TO POWER PLAN FORADDITIONAL DETAIL

1

1

1

1

H1B-7

H1B-7

H1B-7

H1B-7

H1B-7

H1B-7

H1B-7

H1B-7 H1B-7

H1B-7 H1B-7

H1B-7

H1B-7

H1B-7

H1B-7

2' -

0"

DIA.

2' - 0"

7' -

6"

3'-6".

3 #3 TIES.

(6) #6 (VERT.) WITH #3 TIES @ 12" O.C.

4000 PSI AIR ENTRAINED CONCRETE (TYP.)

TOP OF CONDUIT MINIMUM 24" BELOWFINISHED GRADE

MIN. 3" CLR.(TYP ALLSIDES)

GALVANIZED ANCHOR BOLTS (BY POLE MFG.)

FINISHED GRADE

3 #3 TIES.ROUND PEDESTAL WITH 1" CHAMFEREDCORNERS

ANCHOR BOLT BASE COVER (BY POLE MFG.)

HAND HOLE W/COVER PLATE ANDSTAINLESS STEELSCREWS

LIGHT POLE

ANCHOR BOLT COVER

REBAR

HAND HOLE

HOT DIPPED GALVANIZEDANCHOR BOLTS

GALVANIZED NUTS

MIN 1" PVC CONDUIT

3".

PROVIDE GROUT BED W/DRAINAGE UNDER BASEPLATE

3".

3".

3".

REPRESENTED BY n

APPLIES TO DRAWINGS E1.0

hbvklqbp

1. PROVIDE #6 WIRE IN 1-1/4" PVC FOR SITE LIGHTING.

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWMV=mj

pfqb=mi^k=J

bib`qof`^i

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bNKM

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

k

1" = 20'-0"

pfqb=mi^k=J=bib`qof`^i

0' 20'10' 40'

1" = 20'-0"

NO SCALE

mlib=_^pb=abq^fi

REVISIONS

DATE DESCRIPTION

Page 3: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

2 OS

2 OS

2O

S 2 OS

2 OS

2O

S

2 OS

2 OS

2 OS

2 OS

2OS

2OS

2OS

2 OS

2OS

2 OS

2OS

2OS

2OS

2 OS

2 OS

2 OS

2OS

2OS

OS OS

OS OS OS OS

OS3

3

3

D

2OS

2OS

3

3

3

3D

33

33

33

33

3

2 OS

2 OS

2 OS

2 OS

2 OS

4

UPUP3

3 3

3

3

3

3

3

3

3

3

OSOS

OS

2OS

2 OS

2OS

2OS

3

3

3

3

3

123

124

122

126 131 133

141

127 130 134

128

129

121

120

119

118 117 116115

114

136

135

137

139

140

145

146

110

142 144

112 111

113101

107

138

125132

103

102

105109 106108

143

A2A2

A2

A2 A2

A2

A2A2

A2 A2

A2A2

A2

A2

A2

A2 A2

A2 A2

A2A2

A2

A2A2A2

G1G1G1

G1G1G1

G1

G1

G1

G1

A2 A2A1

A2A2 A2 A2

A2A2A2 A2

D1

D1

D1

D1

D1

D1 D1 D1 D1

D1

D1

D1

D1

A2 A2

A2 A2

A2A2

A2 A2

A2 A2

A2 A2

A2 A2 A2 A2 A2

A2 A2

A2A2

A2 A2

A2

HX1B-5 HX1B-5

A2

HX1B-5

A2

A2

HX1B-5

D1D1 D1 D1 D1 D1 D1

A2

A2

A2

A2

A2

A2

A1

B2

D1D1 E1E1 E1E1E1E1 E1 E1E1 E1E1

F1 F1

C1

C1

C1

D1

D1

D1

D1

A1 A1 A1 A1

A1 A1 A1 A1

A1 A1 A1 A1

A1 A1 A1 A1

G1 G1G1G1G1

C1

Y1

Y1 Y1 Y1 Y1Y1

Y1Y1

HX1B-4HX1B-4

HX1B-4

HX1B-4 HX1B-4

HX1B-4

HX1B-4HX1B-4

HX1B-4 HX1B-4

HX1B-4HX1B-4

HX1B-4

HX1B-4

HX1B-4

HX1B-4 HX1B-4

HX1B-4 HX1B-4

HX1B-4

HX1B-4

HX1B-4

HX1B-4 HX1B-4HX1B-4

HX1B-4HX1B-4 HX1B-4 HX1B-4

HX1B-4HX1B-4HX1B-4 HX1B-4

HX1B-2

HX1B-2

HX1B-2

HX1B-2

HX1B-2

HX1B-2 HX1B-2HX1B-2 HX1B-2

HX1B-2

HX1B-2

HX1B-2

HX1B-2

HX1B-4 HX1B-4

HX1B-4 HX1B-4

HX1B-4HX1B-4

HX1B-4 HX1B-4

HX1B-5 HX1B-5

HX1B-5 HX1B-5

HX1B-4 HX1B-4 HX1B-4 HX1B-5 HX1B-5

HX1B-5 HX1B-5

HX1B-5HX1B-5

HX1B-5 HX1B-5

HX1B-5 HX1B-5 HX1B-5

HX1B-5

HX1B-2H1B-1 H1B-1 H1B-1 HX1B-2 H1B-1 H1B-1

HX1B-5

HX1B-5

HX1B-5

HX1B-5

HX1B-5

HX1B-5

HX1B-5

HX1B-5

HX1B-5HX1B-5

HX1B-5HX1B-5 H1B-1H1B-1H1B-1H1B-1 H1B-1 H1B-1H1B-1 H1B-1H1B-1

H1B-1 H1B-1

H1B-1

H1B-1

H1B-1

HX1B-1

H1B-1

HX1B-1

HX1B-1

H1B-1 H1B-1 HX1B-2 H1B-1

H1B-1 H1B-1 H1B-1 H1B-1

H1B-1 H1B-1 H1B-1 H1B-1

HX1B-2 H1B-1 H1B-1 HX1B-2

H1B-1 H1B-1H1B-1H1B-1H1B-1

HX1B-3 HX1B-3 HX1B-3 HX1B-3HX1B-3

HX1B-3HX1B-3HX1B-3

A2 A2 A2A2E1HX1B-2

E1HX1B-2

HX1B-2HX1B-2

X1

X1

X1

X1

X1X1 X1

X1

X1

X1

X1

X1

HX1B-4

HX1B-4

HX1B-2

X2

HX1B-2X1

Y1 HX1B-3Y1 HX1B-3 Y1 HX1B-3

PA

RT

A

PA

RT

B

1

HX1B-4

HX1B-2

HX1B-2

HX1B-2

HX1B-2 X1

HX1B-2

HX1B-2D1

C1

C1

C1

HX1B-2

D1

HX1B-1

HX1B-2

HX1B-2

H1B-1

HX1B-2

Y1 HX1B-3

G1

H1B-1 X1X1

Y1 Y1HX1B-3

HX1B-1

HX1B-1

HX1B-2

Y1 HX1B-3

HX1B-2

HX1B-3Y1 Y1 HX1B-3

X1HX1B-2

REPRESENTED BY n

APPLIES TO DRAWINGS E2.1.1

hbvklqbp

1. ALL LIGHTING FIXTURES IN THIS SPACE SHALL BE CONNECTED TO THE DENOTEDCIRCUIT UNO..

2. FIELD ADJUST LIGHTING FIXTURES IN THIS SPACE AS REQUIRED TO COORDINATEWITH OTHER TRADES. MAINTAIN A IN OF 24" FROM THE RADIANT HEATING IN THISSPACE..

3. LIGHTING IN THIS SPACE SHALL NOT BE AUTOMATICALLY CONTROLLED DUE TO RISKOF INJURY POSED BY UNEXPECTED LOSE OF ILLUMINATION..

4. DO NOT LOCATE ANY ELECTRICAL EQUIPMENT OR FIXTURES WITHIN 5' OF THEDOORS OF THE PAINT BOOTH.

150

156

147 148149

152154

153

159

157

161

162

151

158

160

D1

D1

D1

D1

D1 D1 D1 D1

A2

A2

A2

A2

A2

A1 A2

A2

E1E1 E1 E1 E1

E1 E1

E1 E1

E1 E1

A2A2A1

A2A2 A2

C1C1C1

C1C1C1

E1 E1 E1 E1

E1 E1 E1 E1

E1E1 E1 E1 E1

E1

E1 E1 E1 E1

E1E1 E1 E1 E1

E1E1 E1 E1 E1

E1

E1

E1

E1

E1E1 E1 E1 E1

E1E1 E1 E1 E1

E1

E1E1 E1

E1E1 E1

E1E1 E1

E1 E1 E1

E1 E1 E1

E1 E1 E1

E1 E1 E1

E1E1

E1E1

E1E1

E1E1

E1

E1

E1

C1 C1

C1

Y1Y1 Y1 Y1 Y1 Y1Y1

Y1 Y1 Y1

Y1

Y1 Y1

HX1B-1

H1B-1

HX1B-1

HX1B-1

H1B-1 H1B-1 HX1B-1H1B-1

H1B-5

H1B-5

H1B-5

H1B-5

H1B-5

HX1B-1 H1B-5

H1B-5

H1B-5HX1B-1 HX1B-1 H1B-5 HX1B-1

H1B-5 H1B-5

H1B-5 H1B-5

H1B-5 HX1B-1

H1B-5H1B-5HX1B-1

H1B-5H1B-5 H1B-5

H1B-5H1B-5H1B-5

H1B-5HX1B-1H1B-5

H1B-5 H1B-5 HX1B-1 H1B-5

H1B-5 H1B-5 H1B-5

H1B-5

H1B-3H1B-3 H1B-3 H1B-3 H1B-3

H1B-3

H1B-3 HX1B-1 H1B-3 H1B-3

H1B-3H1B-3 H1B-3 H1B-3 H1B-3

HX1B-1H1B-3 H1B-3 H1B-3 HX1B-1

H1B-3

H1B-3

H1B-3

H1B-3

HX1B-1H1B-3 H1B-3 H1B-3 HX1B-1

H1B-3H1B-3 H1B-3 H1B-3 H1B-3

H1B-3

H1B-3H1B-3 HX1B-1

H1B-3HX1B-1 H1B-3

H1B-3H1B-3 HX1B-1

HX1B-1 H1B-3

HX1B-1

H1B-3 H1B-3

H1B-3

H1B-3 H1B-3

H1B-3

HX1B-1 H1B-3

HX1B-1

HX1B-1

HX1B-1HX1B-1H1B-3

HX1B-1

H1B-3

H1B-3

H1B-3

HX1B-3

HX1B-3 HX1B-3 HX1B-3HX1B-3 HX1B-3

HX1B-3HX1B-3 HX1B-3 HX1B-3 HX1B-3 HX1B-3HX1B-3

X1

X1

X1

X1

A2

H1B-5

HX1B-1HX1B-1

X1X1

HX1B-1

X1

X1 X1

X1

X1

Y1 HX1B-3

HX1B-2

E1

E1

E1

E1

H1B-3

H1B-3

H1B-3

H1B-3

Y1

Y1

Y1

HX1B-3

HX1B-3

HX1B-3

E1E1

H1B-5H1B-5

Y1 HX1B-3

E1 HX1B-1

X1X1

HX1B-1

HX1B-1

HX1B-2

HX1B-1

Y1

HX1B-3

X1

1

HX1B-1

Y1 HX1B-3

3

3

3

3

3

4

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWNO=mj

cillo=mi^kp=J

ifdeqfkd

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bOKNKN

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

k

1/8" = 1'-0"

cillo=mi^k=J=m^oq=^=J=ifdeqfkd

k

1/8" = 1'-0"

cillo=mi^k=J=m^oq=_=J=ifdeqfkd

REVISIONS

DATE DESCRIPTION

Page 4: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

VP

E

E

E

E

EL

EL

BL

UPUP

CLG

CLG

CLG

CLG

CLG

CLG

CLG

E

E

EL

EL

BL

S

S

F

S

S

EE E

123

124

122

126 131

133

141

127

130134

128

129

121

120

119

118117

116 115114

136

135

137

139

140

145

146

110

142 144

112 111

113101

107

138

125

132

103

102

105

109

106

108

E2.1.2

2

E2.1.2

1

E2.1.2

4

HM1B

ELECTRICAL PRIMARYDUCTBANK. REFER TO CIVILPLAN FOR CONTINUATION

5' - 0"

5' -

0"

5' - 0"

5' -

0"

5' - 0"

GEN2 GEN1

L1C-3

L1C-3

L1C-3

L1C-33 L1C-33

L1C-29 L1C-29

L1C-1

L1C-5

L1C-5

L1C-9

L1C-9

L1C-17 L1C-17 L1C-21

L1C-14

L1C-18

L1C-18

L1C-37

L1C-39

L1C-22 L1C-22 L1C-26

L1C-32

L1C-32

L1C-35

L1C-31L1C-3

L1C-7

L1C-7

L1C-11

L1C-11

L1C-19 L1C-23

L1B-7

L1C-34

L1C-16

L1C-20

L1C-20

L1C-28L1C-24L1C-24

L1C-39

L1C-35

L1C-31

L1C-39

L1C-34

L1C-3

L1C-7

L1C-7

L1C-7

L1C-7

L1C-11

L1C-11

L1C-11

L1C-11L1C-15

L1C-15 L1C-15

L1C-15 L1C-19

L1C-19

L1C-19

L1C-23

L1B-1

L1C-16L1C-16

L1C-20

L1C-20

L1C-38

L1C-25

L1C-25

L1C-25L1C-25

L1C-27

L1C-2L1C-27

L1C-27

L1C-39L1C-37

L1C-35

L1C-35

L1C-35

L1C-31

L1C-31

L1C-30L1C-30

L1C-30

L1B-33

L1B-33

L1B-2L1B-2L1C-38L1C-38

L1C-38

L1C-41L1C-25

L1B-21 L1B-23

L1C-4L1C-4

L1C-26

L1C-28L1C-24 L1C-28

L1C-28L1C-28L1C-24

L1C-24

L1C-30

L1B-10

L1B-6L1B-6L1B-6L1B-6

L1B-4

L1B-47

L1B-3

L1B-1 L1B-3

L1B-5 L1B-9

L1C-34

L1C-34

L1C-34

L1C-34

L1C-24

L1B-11

L1C-39

L1C-20

L1C-20

L1B-21

L1B-21

L1B-21L1B-23

L1B-23

L1B-23

L1B-35

L1B-19

L1B-19

L1B-4

L1C-41

L1C-41

L1C-41

L1B-33

L1B-13

L1B-13

L1B-13L1B-13

L1B-15

L1B-2

L1C-1

L1C-3

L1C-13L1C-15

L1C-23

L1C-13L1C-15 L1C-19

L1C-19

L1C-38

L1C-38

L1C-35

L1C-39

L1C-6 L1C-8

L1C-10

L1C-12

L1C-10L1C-12

143

L1C-28

L1C-30

L1C-30

L1C-30

L1B-4

L1B-13

L1B-17

104

L1B-2

L1B-25

L1B-27

L1B-31

L1B-29

PA

RT

A

PA

RT

B

L1B-12

5

E2.1.2

PROVIDE SINGLEGENERATOR UNDER BASEBID REFER TO ONE LINEDIAGRAM FOR SIZE

E2.1.3

1

LE1A-9

LE1A-9LE1A-11

ROUTE THE GENERATORDUCTBANK UNDER THESERVICE PRIMARY

150

156

148 149 152 154

153

159

157

161162

151

158

160

UTILITY XFMR

E2.1.2

3

L1BH1B

3

10' -

0"

3' - 0"3' - 0"

L1B-37 L1B-37

L1B-49L1B-39

L1B-41 L1B-53

L1B-55

L1B-49

L1B-51

L1B-51L1B-41

L1B-53L1B-35 L1B-41 L1B-41

L1B-53

L1B-26L1B-26

L1B-26L1B-26

L1B-24 L1B-24

L1B-33

L1B-33

L1B-33 L1B-33

L1B-30L1B-28

L1B-28

L1B-16

L1B-16

L1B-10

L1B-43L1B-16

L1A-1

L1A-29

L1A-31

L1A-31

L1A-33

L1A-35

L1A-35 L1A-33

L1A-33

L1B-6 L1B-8 L1B-8

L1B-8L1B-8L1B-4L1B-4

L1B-35

L1B-35

L1B-35

L1A-29

L1A-31

L1B-33

HM1B-3

L1B-39

L1A-19

L1A-35L1B-45

HM1B-1

L1B-8

DOOR OPERATOR

L1B-12

L1B-14

L1B-14

L1B-24 L1B-24 L1B-24

L1B-18

L1B-20

L1B-22

L1B-53

L1B-55

L1B-53

L1B-53

L1B-28 L1B-28

L1B-30

L1A-1

L1A-3

L1A-5

L1A-2,4,6

30

L1A-8,10,12

L1A-14,16,18

30

L1A-20,22,24

30 L1A-29

L1A-7

L1A-9

L1A-7

L1A-9

L1A-13

L1A-15

L1A-17

L1A-11

L1A-21L1A-23L1A-26,28,30 L1A-25L1A-27L1A-27

L1A-1

DOOR OPERATOR

L1A-39

L1A-39

L1A-39

L1A-39L1A-37

L1A-37

L1A-37

L1A-37

HM1B-5

DOOR OPERATOR

HM1B-7

DOOR OPERATOR

HM1B-9

DOOR OPERATOR

6

E2.1.2

7

E2.1.2

HX1B

33

FAN SUPPLIEDWITH UNIT.FIELD VERIFYELECTRICALREQUIREMENTSBEFOREROUGH-IN

L1B-32

L1B-34

LIGHTS

LIGHTS

3

ELECTRICAL SERVICESECONDARY. REFER TO SITE PLANFOR ROUTING

GENERATOR DUCTBANK.REFER TO SITE PLAN FORROUTING

GROUND EACH PAINTBOOTH ENCLOSURE VIA ANINDIVIDUAL BARE #4 AWG

LE1A-7

LE1A-9

LE1A-9

L1B-46

H1B-15,17,19

H1B-9,11,13

4

REPRESENTED BY n

APPLIES TO DRAWINGS E2.1.2

hbvklqbp

1. PROVIDE 4'X8'X3/4" FIRE RESISTANT PLYWOOD MOUNTED WITH LONG DIMENSION MOUNTEDVERTICALLY ON WALLS AS INDICATED..

2. PROVIDE NEMA 208V/1 PH OUTLET MOUNTED TO THE BACK OF EACH RACK. COORDINATEOUTLET CONFIGURATION WITH THE OWNER PRIOR TO INSTALLATION. DROP POWERCIRCUITRY FROM STRUCTURE ABOVE TO OUTLET VIA EMT CONDUIT. PROVIDE CONDUITSUPPORT AS REQUIRED BY CODE. ALL CONDUCTORS SHALL BE DEDICATED #10 IN 3/4"C TOPANEL..

3. MOUNTED DENOTED PANEL ON THE STUCTURAL WALL AT THIS LOCATION. PROVIDE AMINIMUM OF FOUR 1" EMPTY CONDUIT WITH PULL STRINGS FROM THE PANEL STUBBED TOTHE ACCESSIBLE CEILING. ONCE CONDUIT AND CIRCUITS ARE INSTALLED, INSTALL PARTITIONWALL AS INDICATED ON THE ARCHITECTURAL PLANS AND A RECESSED PANEL COVER..

4. DO NOT LOCATE ANY ELECTRICAL EQUIPMENT OR FIXTURES WITHIN 5' OF THE DOORS OFTHE PAINT BOOTH.

1

SPECIALELECTRONICS

132

FACPL1C-40

L1C-42

SCP

TGB

L1C

ELECTRICAL

125

LABEL AS "LE1C"UNDER ADDITIVEBID OPTION #1

MAIN

MDS

ATS-EATS-XATS-X

HE1A

TE1A

LE1A

CT

MECHANICALROOM

157

ELECTRICAL

160

DIST

L1AL1A-35

L1A-35

L1A-35

T1A

SPACE FORMECHANICAL PIPING

SPACE FORMECHANICAL PIPING

LM1A

TM1A

METER

SPD

1

2

MDF

109

LEMDF-3

LEMDF-1 LEMDF-3

LEMDF-1

L1B-2

LEMDF-2,4

LEMDF-6,8

LEMDF-10,12

30

30

30

LEMDF1

FINISHED GRADE

6"

1'-6"

5"

5"

5" 7" 5"

#3 TIES, @ 18" O.C.

6" SCH 40 PVC CONDUIT(TYP OF 2)

#4 BARS, MIN18" OVERLAP

PROVIDE 3000 PSI CONCRETE UNDER HARDSCAPE, OTHERWISEVDOT #10 SCREENINGS OR APPROVED ENGINEERED FILL.PROVIDE CONDUIT SPACERS EVERY 6'-0"

UNDERGROUND WARNING TAPE

FINISHED GRADE

6"

1'-6"

5"

7"

5" 7" 5"

#3 TIES, @ 18" O.C.

1" SCH 40 PVC CONDUIT(TYP OF 4) FOR POWERAND CONTROLS

#4 BARS, MIN18" OVERLAP

PROVIDE 3000 PSI CONCRETEPROVIDE CONDUIT SPACERS EVERY 6'-0"

UNDERGROUND WARNING TAPE

SCH 40 PVC CONDUIT(TYP OF 2). REFER TOONE LINE DIAGRAM FORSIZE

5"

UNDERGROUND WARNING TAPE

FINISHED GRADE

6"

1'-6"

7"

5"

5" 7" 5"

#3 TIES, @ 18" O.C.

4" SCH 40 PVC CONDUIT(TYP OF 4, TWO SPARE)

#4 BARS, MIN18" OVERLAP

PROVIDE 3000 PSI CONCRETEPROVIDE CONDUIT SPACERS EVERY 6'-0"

5"

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWNV=mj

cillo=mi^kp=J

mltbo

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bOKNKO

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

k

1/8" = 1'-0"

cillo=mi^k=J=m^oq=^=J=mltbo

k

1/8" = 1'-0"

cillo=mi^k=J=m^oq=_=J==mltbo

1/4" = 1'-0"E2.1.2 E2.1.2

bki^odba=mi^k=J=a^q^=olljN

1/4" = 1'-0"E2.1.2 E2.1.2

bki^odba=mi^k=J=bib`qof`^i=olljO

1/4" = 1'-0"E2.1.2 E2.1.2

bki^odba=mi^k=J=bib`qof`^i=olljpP

1/4" = 1'-0"E2.1.2 E2.1.2

bki^odba=mi^k=J=jac=ollj=J=mltboQ

NO SCALEE2.1.2 E2.1.2

bib`qof`^i=pbosf`b=mofj^ovR

NO SCALEE2.1.2 E2.1.2

dbkbo^qlo=ar`q_^khSNO SCALEE2.1.2 E2.1.2

bib`qof`^i=pbosf`b=pb`lka^ovT

REVISIONS

DATE DESCRIPTION

Page 5: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

F

F FF

FF

SSS

S

S

SS

S

VP

SD

EL

CR EL

F

BL

SD

UPUP

F F

F

F

FFFF

F

S

S

S

S

S

S

S

S

S

SD SD

CR

EL

EL

BL

S

OFFICE

123

OFFICE

124

OFFICE

122

OFFICE

126

OFFICE

131

OFFICE

133 OFFICE

141

OFFICE

127

OFFICE

130

OFFICE

134

BREAK ROOM

128

CONFERENCEROOM

129

OFFICE

121

OFFICE

120

OFFICE

119

OFFICE

118OFFICE

117

OFFICE

116

OFFICE

115OFFICE

114

FILE ROOM

136

COPYSUPPLIES

135

OFFICE

137

OFFICE

139

OFFICE

140

OFFICE

145

OFFICE

146

BREAK ROOM

110

OFFICE

142

OFFICE

144

TOILET

112TOILET

111

CORRIDOR

113CORRIDOR

101

COMMONSAREA

107

OPEN OFFICEAREA

138

ELECTRICAL

125

SPECIALELECTRONICS

132

CUSTODIAL

104

WOMENSTOILET &SHOWER

103

MENS TOILET &SHOWER

102

RECYCLE

105MDF

109

CUSTODIALSUPPLIES

106

MECHANICALROOM

108

15

15 15

15 15

15

30

30

15 30

15

15

75

OFFICE

143

15

1530 15

15

30

15

30

15

E2.1.2

1

PA

RT

B

FAAP

E2.1.3

1

PA

RT

B

DPS

RX

DPS

RX

15

15 15

15

75

PAINT SHOP

150

MATERIALSSTORAGE

156

STORAGE

147

SUPERVISOROFFICE

148GENERALOFFICE

149

GENERALOFFICE

152

SUPERVISOROFFICE

154

CARPENTRYSHOP

153

CHEMICALSTORAGE

159

MECHANICALROOM

157

TOOLSTORAGE

161

TRUCK WASHBAY

162

STAGING

151

BLOODBOURNE

(HOUSEKEEPINGLINEN

STORAGE)

158

ELECTRICAL

160

15

15

30

110

75

75

75

30

75

30 1515

75

75

15

7575

FAAP

FIBER MANHOLE.REFER TO CIVILDRAWINGS

FIBER DUCTBANK.REFER TO CIVILDRAWINGS

FIBER DUCTBANK. PROVIDE 4-4"C AMIN OF 2' BELOW THE SLAB FORMFIBER MAHOLE TO MDF ROOM.

PA

RT

AP

AR

T A

DPS

RX

DPS

RX

15

30

15

GROUND EACH PAINTBOOTH ENCLOSURE VIA ANINDIVIDUAL BARE #4 AWG

2

FS

FS

TS

TS

PS

PS

FIELD VERIFY LOCATION

MDF

109

FIBER CONDUIT STUB-UP FROM MANHOLE

12"x4"BOCT: 10' - 0"

RACKS BY OWNER

STATION CABLINGCONDUIT STUB UP

TYP.

TMGB

REPRESENTED BY n

APPLIES TO DRAWINGS E2.1.3

hbvklqbp

1. PROVIDE ROOF PENETRATION WITH WEATHERHEAD PER THE DETAIL ON DRAWING E4.1 FORFUTURE RADIO BOOSTER SYSTEM..

2. DO NOT LOCATE ANY ELECTRICAL EQUIPMENT OR FIXTURES WITHIN 5' OF THE DOORS OFTHE PAINT BOOTH.

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWOM=mj

cillo=mi^kp=J

`ljjrkf`^qflkp

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bOKNKP

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

k

1/8" = 1'-0"

cillo=mi^k=J=m^oq=^=J=`ljjrkf`^qflkp

k

1/8" = 1'-0"

cillo=mi^k=J=m^oq=_=J=`ljjrkf`^qflkp

1/4" = 1'-0"E2.1.2 E2.1.3

bki^odba=mi^k=J=jac==ollj=J=`ljjN

1

REVISIONS

DATE DESCRIPTION

Page 6: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

M

UPUP

M

123

124

122

126

131

133

141

127

130

134

128

129121

120

119

118

117 116 115 114

136

135

137

139

140 145

146

110

142

144

112 111

113 101

107

138

125132

103

102

147

105109106

108

AHU-1

AHU-2

CU-2CU-1

TU1-9

TU1-7TU1-6

TU1-2

FP1-4

TU1-8

TU1-4

TU1-3

TU1-1

FP1-3

FP1-5

FP1-2

FP1-1

TU1-5

xx . .

PA

RT

A

PA

RT

B

UH-5

F-12 F-13

DDCCONTROLPANEL

DSS-1A

DSS-1B

HM1B-38,40,42

HM1B-20,22,24HE1A-2,4,6

HM1B-11

HE1A-8HE1A-8

HE1A-8

HE1A-7

HE1A-8

HE1A-8

HE1A-8

HE1A-8

HE1A-7

HE1A-7

HE1A-7

HE1A-7

HE1A-8

? ? ?

L1B-40

L1C-36 L1C-36

LE1A-3,5

LE1A-3,5

F-1L1B-36

60 30

F-7

HE1A-1,3,5

HM1B-19,21,23

143

LE1A-2

L1B-48

150

156

147 148 149 152 154

153

159

157

161

162

151

158

160

B-1

DC-1

CU-3 CU-4

RH-2 RH-1

TU1-11

TU1-10

TU1-9

F-2

AC-1

UH-1UH-2

UH-3

DC-1ISOLATIONVALVE

CONTROLPANEL

MAINBAS

CONTROLPANEL

UH-4

HM1B-2,4,6

FOR DUST COLLECTION.REFER TO MECOORDINATIONSCHEDULE.

LE1A-1

?

?

? ?

?

F-11

LM1A-20WH2

AHU-3

AHU-4MAU-1

MAU-2

RH-4 RH-3

F-5 F-6 F-8

HM1B-26,28,30 HM1B-32,34,36

HM1B-11

HM1B-11

HM1B-11

LM1A-7

L1B-42,44

LM1A-15LM1A-16

LM1A-17LE1A-6

LM1A-18

HM1B-25,27,29

HM1B-31,33,35HM1B-8,10,12

HM1B-14,16,18

LM1A-9 LM1A-10 LM1A-11

RH-6RH-5

F-4LM1A-8

F-3L1B-38

LM1A-12F-9

LM1A-1LM1A-3LM1A-2 LM1A-4

LM1A-5 LM1A-6

30

3030

P-2

P-1

HE1A-10,12,14

HE1A-9,11,13

LM1A-14

LE1A-4

40

F-10LM1A-13

WH1LM1A-19

LE1A-8

1

.2. REFER TO PLUMBING /ELECTRICAL COORDINATION SCHEDULE ON DRAWING P0.1 FOR

ADDITIONAL REQUIREMENTS.

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWOP=mj

cillo=mi^kp=J

jb`e^kf`^i

mltbo

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bOKNKQ

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

k

1/8" = 1'-0"

cillo=mi^k=J=m^oq=^=J=jb`e^kf`^i=mltbo

k

1/8" = 1'-0"

cillo=mi^k=J=m^oq=_=J=jb`e^kf`^i=mltbo

REVISIONS

DATE DESCRIPTION

Page 7: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

12" LARGER THAN GENERATOR FOOTPRINT

12"

LA

RG

ER

TH

AN

GE

NE

RA

TO

R F

OO

TP

RIN

T12".

CONCRETE PAD REQUIREMENTS

1. THE CONCRETE PAD IS TO BE FURNISHED BY THE CONTRACTOR.ADJUST REQUIREMENT INDICATED HEREIN TO MATCH GENERATORPROVIDER REQUIREMENTS..

2. MINIMUM PAD THICKNESS SHALL BE 12", WITH 3/8" REBAR ON 12"CENTERS, INSTALLED BOTH WAYS THROUGHOUT CONCRETE PAD..

3. CORNERS AND EDGES OF FOUNDATION ARE TO BE BEVELED..

4. THE ELEVATION OF THE PAD TOP SHALL BE APPROXIMATELY 8"ABOVE FINISHED GRADE..

5. THE PAD MUST BE LOCATED SUCH THAT THE MINIMUM CLEARANCEBETWEEN THE PAD AND STRUCTURES IS 3 ' ALONG THE SIDES ANDBACK AND 5' ALONG THE ENDS..

6. IF THE PAD IS LOCATED IN A TRAFFIC AREA, GUARD POSTS MUST BEFURNISHED AND INSTALLED AT THE CORNERS OF THE PAD..

7. REFER TO THE ONELINE DIAGRAM FOR SIZE AND QUANTITY OFSECONDARY CONDUITS..

8. BEFORE POURING CONCRETE, CONTRACTOR SHALL CONTACT THEEQUIPMENT PROVIDER FOR INSPECTION OF FORMS, CONDUITS &REINFORCEMENT..

9. TOP OF PAD SHALL HAVE A FINE BROOMED FINISH UPONCOMPLETION...

10. PROVIDED ANCHORS INTHE PAD AS REQUIRED BY THE EQUIPMENTPROVIDER

SLAB

FINISHED FLOOR

1" CONDUITUNLESS OTHERWISE INDICATED

FLOOR BOXWALL/PARTITION CAVITY

2.5" DEEP 2-GANG OUTLET BOXWITH SINGLE GANG PLASTER RING

WALL/PARTITION FACE

1" CONDUIT MINIMUMSIZE OR AS INDICATED

CONTINUE TO MDFROOM 109

FINISHED CEILING

DOUBLE LOCK NUT& LOCK WASHER

PROVIDE UNISTRUT SUPPORTSANCHORED TO STRUCTUREABOVE CEILING

FINISHED CEILING

DUPLEX OUTLET FLUSHMOUNTED TO CEILING,SUPPORTED BY STRUCTURE,PROVIDE SS COVER PLATE.

PLUG & CORD INTEGRALWITH CORD REEL UNIT

ADJUSTABLE BALL STOP

30' OF 14-3 SJO CORD

INTEGRAL CORD GRIP

(3) 15AGROUNDED PLUGS

MOUNT REEL BRACKETFLUSH WITH CEILING TOUNISTRUT SUPPORTABOVE CEILING.

CORD REEL EQUALTO LUMAPRO 4XP67

CLG

ROOF

3" RIGID STEEL CONDUITTHROUGH ROOF TO SUPPORTFUTURE ANTENNA MAST

FLASH AND SEAL ROOFPENETRATION IAW ROOFMANUFACTURER'SRECOMMENDATIONS

3" SERVICE ENTRANCEWEATHER HEAD FOR ANTENNALEAD-IN CABLE(CABLE BYOTHERS, NIC)

2' -

0"

RIGIDLY SUPPORT CONDUITFROM STRUCTURE

BUSHING

CIELING

VERIFY STRUCTURE AND ROOFCONSTRUCTION RGS CONDUIT ELBOW

PVC CONDUIT

EMT CONDUIT

SLAB

POROUS FILL

EARTH

PVC CONDUIT

EMT CONDUIT

SLAB

POROUS FILL

EARTH

RGS CONDUIT ELBOW

WALL

OS

2

OS

REFER TO PLANS FOR SWITCH TYPE

SINGLE GANG BOX

OCCUPANCY SWITCH

SINGLE GANG COVERPLATE

SINGLE GANG BOX

DUAL RELAYOCCUPANCY SWITCH

SINGLE GANG COVERPLATE

BALLAST #1 ORINPUT #1OF STEP DIMMINGBALLAST

BALLAST #2 ORINPUT #2OF STEP DIMMINGBALLAST

DOUBLE GANG BOX

(2) SWITCHES

DOUBLE GANG COVERPLATE

SINGLE GANG BOXSWITCH

SINGLE GANG COVERPLATE

LINE LOAD LINE

BALLAST #1 ORINPUT #1OF STEP DIMMINGBALLAST

BALLAST #2 ORINPUT #2OF STEP DIMMINGBALLAST

LINE LOAD LINE

REFER TO PLANS FOR SWITCH TYPE

TO PANELS, EQUIPMENT,TRANSFORMERS, ETC.

SWITCHBOARD "MDS"MAIN NEUTRAL BUS

EXOTHERMICCONNECTION

METALUNDERGROUNDWATER MAIN

BUILDING STEEL (IFPROPERLY GROUNDED)

METAL WATER MAINMIN. 10 FT CONTACTWITH EARTH.REMOVABLE

ATTACHMENT POINTMAX. 5' INSIDE OF BLDG.AND ON EACH SIDE OFMAIN WATER VALVE.

MINIMUM 1/2" DIAMETER MIN 20' LENGTH ELECTRICALLYCONDUCTIVE STEEL REBAR, OR, MIN 20' LENGTH #3AWG BAR COPPER CONDUCTOR: ENCASED BY MIN2" CONCRETE IN BUILDING FOUNDATION

CONCRETE ENCASEDELECTRODE

(1)#4/O, 1"C

#3/O BOND

SWITCHBOARD "MDS"MAIN GROUND BUS

(1)#4/O CU GRD1" PVC CONDUIT

(1)#4/O, 1"C

10'

MIN

(1)#4/O, 1"C,TYP.

PRIMARY BONDTO LIGHTNINGPROTECTIONSYSTEM

(3) GROUNDINGRODS

TMGB

TGB

#3/O

PROVIDE (1)#3/O GROUNDINGCONDUCTOR BETWEEN EACHTGB AND NEAREST STRUCTURALSTEEL AND COPPER WATER LINE,TYPICAL.

GEN ATS

DO NOT BONDGROUND ANDNEUTRAL INGENERATOR

PROVIDE #2 BARE TINNED COPPER LOOPDIRECT BURIED AROUND GENERATORPAD WITH (2) GROUND RODSEXOTHERMICALLY BONDED. CONNECTTO GENERATOR GROUNDING TERMINALWITH 2 SEPARATE #2 CONNECTIONS

#3/O

TGB

#4

150 132

109

NEUTRAL

LINE

NEUTRAL

HOT

POWERPACK

LOAD

SUBSTITUTE SWITCHING ARRANGEMENTINDICATED ON THE PLANS.

OUTPUTCOMMON24VDC

OCCUPANCY SENSOR

LOAD

277VLIGHTINGCCT

OS

DUAL RELAYOCCUPANCY SWITCH(PLAN SYMBOL: )

277V NORMAL LIGHTING(REFER TO PLANS FORQUANTITY)

STEP DIMMINGBALLAST

OUTPUT #1

OUTPUT #2

LINE

NEUTRAL

96".

108".

24". 18". 12". 24". 18".

PRIMARY SECONDARY

NO CONDUIT IN THIS AREA

10".

15".

FRONT

12".

CONCRETE PAD REQUIREMENTS FOR PAD MOUNTED TRANSFORMERS1. THE CONCRETE PAD IS TO BE FURNISHED BY THE CONTRACTOR. ADJUST REQUIREMENT INDICATED HEREIN TO MATCH POWER COMPANY REQUIREMENTS

2. MINIMUM PAD THICKNESS SHALL BE 12", WITH 3/8" REBAR ON 12" CENTERS, INSTALLED BOTH WAYS THROUGHOUT CONCRETE PAD.

3. CORNERS AND EDGES OF FOUNDATION ARE TO BE BEVELED.

4. THE ELEVATION OF THE PAD TOP SHALL BE APPROXIMATELY 4" ABOVE FINISHED GRADE.

5. THE PAD MUST BE LOCATED SUCH THAT THE MINIMUM CLEARANCE BETWEEN THE PAD AND STRUCTURES IS 3 ' ALONG THE SIDES AND BACK AND 10' ALONG THE FRONT.

6. IF THE PAD IS LOCATED IN A TRAFFIC AREA, GUARD POSTS MUST BE FURNISHED AND INSTALLED AT THE CORNERS OF THE PAD.

7. REFER TO THE ONELINE DIAGRAM FOR SIZE AND QUANITY OF SECONDARY CONDUITS (MAXIMUN NUMBER =10). ALL BACKFILL IN CONDUIT INSTALLATION AREAS SHALL BE COMPACTED BACK TO AT LEAST 95% TO REDUCE THE RISK OF SETTLING OR CRACKING OF THE PAD.

8. BEFORE POURING CONCRETE, CONTRACTOR SHALL CONTACT THE UTILITY FOR INSPECTION OF FORMS, CONDUITS & REINFORCMENT.

9. TOP OF PAD SHALL HAVE A FINE BROOMED FINISH UPON COMPLETION.

FIRE ALARMDIGITAL

ANNUNCIATORPANEL

FIRE ALARMCONTROL PANEL

(FACP)

2 PHONE LINES UDACT

BATTERYCHARGER

BATTERIES

120V

FIRE ALARMEXTENDERPANEL(FNAC)

NOTIFICATIONAPPLIANCECIRCUITMODULE

BATTERYCHARGER

BATTERIES

120V

EOL

PROVIDE QUANTITIES AS REQUIRED

paqpmpcpp e j ` c

EOL

DPS

EL

CR

EL CR

DPS

FLOOR

3/4"C TO SECURITY CLOSET 132 6'X6'X4" D BOX WITH COVER ON SECURE SIDE OF DOOR

COORDINATE WITH OTHERDIVISIONS TO INSURE THATDOOR FRAMES FOR DOORSWITH ELECTRIC LOCKS ANDPOSITION SWITCHES AREFACTORY FURNISHED WITHAPPROPRIATE HOLES TOALLOW CONDUITCONNECTIONS.

4"X4" FLUSH BOX W 3/4"CONDUIT.

ELECTRIC LOCK.

CIRCUITRY FISHED INDOOR & JAMB

120V INPUT,REFER TOPOWER PLANS

ACCESSIBLE CEILING

3/4" CONDUIT TO DEVICE

RX

RX

EL

1-1/8"

3-1/2"

1/4" THICK ELECTROTINPLATED COPPER BUSBAR

FIBERGLASSBUSHING

3 PAIR 7/16"DIA

15-1/2"

1"8 PAIR 5/16"DIA

5/8"

2"

1"

5/8"

20"

1-1/8" TYP

FIBERGLASSBUSHING

5/16" DIAM,TYPICAL

1/4" THICK ELECTROTINPLATED COPPER BUSBAR

3-1/2"

4"

7/16" DIA(3 PAIR)

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWOR=mj

bib`qof`^i

abq^fip

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bQKN

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

NO SCALE

dbkbo^qlo=m^a=abq^fi

NO SCALE

qbib`ljjrkf`^qflkp=lrqibq=`lkarfq=abq^fi

NO SCALE

`loa=obbi=^ppbj_iv=abq^fi

NO SCALE

tb^qeboeb^a=ollc=mbkbqo^qflk=abq^fi

NO SCALE

ms`=ql=bjq=qo^kpfqflk=abq^fi

NO SCALE

ifdeqfkd=`lkqoli=abq^fiN

NO SCALE

dolrkafkd=pvpqbj=af^do^j

NO SCALE

l``rm^k`v=pbkplo=af^do^j=abq^fi

NO SCALE

lccf`b=ifdeqfkd=^ka=mltbo=`lkqoli=af^do^j

NO SCALE

qo^kpclojbo=m^a=abq^fi

NO SCALE

cfob=^i^oj=ofpbo=af^do^jNO SCALE

cfob=pqlm=abq^fi

NO SCALE

pb`rofqv=bib`qolkf`p=`lkkb`qflk=abq^fi

NO SCALE

qbib`ljjrkf`^qflkp=dolrkafkd=_rp_^o=Eqd_F=abq^fiNO SCALE

qbib`ljjrkf`^qflkp=j^fk=dolrkafkd=_rp_^o=Eqjd_F=abq^fi

REVISIONS

DATE DESCRIPTION

Page 8: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

NO SCALE

PARALLEL SPLICE DETAIL

LIGHTNING PROTECTION CONDUCTOR

ROPE LAY ALUMINUM

(OR SILICONE ADHESIVE - REFER TO DETAIL "B")

UNIVERSAL PARALLEL SPLICER

STAINLESS STEEL FASTENERMOUNT WITH

32 STRAND 17 GAUGE COPPERCONDUCTOR (TO GROUND ROD)

CAST BRONZE CABLE TO ROD CONNECTOR

NOTES:1. P.V.C. INSTALLATION BY ELECTRICAL CONTRACTOR.2. SEALING AROUND P.V.C. PENETRATION BY ROOFING CONTRACTOR.

CAST BRONZE DECK MOUNT

1/2" STAINLESS STEELALL THREAD ROD

1.5" SCHEDULE 40 P.V.C.

CAST ALUMINUM P.V.C. CAP

24 STRAND 14 GAUGE ALUMINUMCONDUCTOR (TO PERIMETER CONDUCTOR)

SEAL EDGES W/ SILICONE SEALANT AND RE-PAINTAFTER ATTACHMENT TO INHIBIT RUST.

CLEAN STEEL CONNECTION POINT FREE OF PAINT ANDDEBRIS PRIOR TO ATTACHMENT.

24 STRAND 14GAUGEALUMINUMCONDUCTOR

CAST ALUMINUMPURLIN STEELBOND CLAMP W/8 SQ. INCHESCONTACT

1.

2.

NOTES: NO SCALE

STEEL CONNECTION DETAIL

NO SCALE

PIPE BONDING DETAIL "E"

NO SCALE

SECONDARY BONDING DETAIL

NO SCALE

VENT BONDING DETAIL

NO SCALE

TEE SPLICE DETAIL

NO SCALE

GROUNDING ELECTRODE DETAIL

ROPE LAYALUMINUMLIGHTNINGPROTECTIONCONDUCTOR

CABLE TO CABLEEXOTHERMICCONNECTION

SOLID SOFTALUMINUMSECONDARYBONDING WIRE

DOWN CONDUCTOR (TRANSITION FROMALUMINUM TO COPPER PRIOR TOCONTACT W/GRADE)

CONCENTRIC STRANDCOPPER GROUNDCONDUCTOR

3/4 " X 10'COPPERWELD GROUND ROD

NOTES:MAKE CONNECTION TO GROUND RODMINIMUM 18" BELOW FINISHED GRADEAND 24" OUT FROM FOUNDATION WALL.

EXOTHERMIC CONNECTION

PVC CONDUIT RUN DOWNCONCEALED INSIDE EXTERIOR WALL

CABLE TO CABLEEXOTHERMICCONNECTION ROPE LAY ALUMINUM LIGHTNING

PROTECTION CONDUCTOR

CAST ALUM. PIPEBONDING CLAMP

ROPE LAY ALUMINUM LIGHTNINGPROTECTION CONDUCTOR

STRAP TYPEALUMINUM VENTBONDING STRAP

ROPE LAY ALUMINUM LIGHTNINGPROTECTION CONDUCTOR

CAST ALUM.SECONDARY BONDINGLUG

ALUMINUM AIR TERMINAL 1/2" X 12" BLUNT-TIP

1. ALIGN AIR TERMINAL PLUMB.

MOUNT BASECAST STL OR ALM ADHESIVE

NOTES:

ALUMINUM CONDUCTOR24 STRAND 14 GAUGE

CONDUCTOR FASTENERALUMINUM ADHESIVE

NO SCALE

ADHESIVE BASE MOUNT

AIR TERMINAL DETAIL "R"

NO SCALE

SIDE MOUNT

AIR TERMINAL DETAIL

ALUMINUM AIR TERMINAL

1/2" X 24" BLUNT-TIP

MOUNT BASECAST STL OR ALM ADHESIVE

ALUMINUM CONDUCTOR

24 STRAND 14 GAUGE

DO NOT PENETRATE METALCOPING ON PARAPET

1/2" X 12" ALUMINUMAIR TERMINAL

ALUMINUM LOOP FASTENERWITH STAINLESS STEEL HEX-HEAD TECH SCREW (TYPICAL)

NO SCALE

GRAVITY VENT OR

FAN BONDING DETAIL

NOTES:1. APPLY SILICONE SEALANT TO UNDERSIDE OF BASE PRIOR TO INSTALLATION ON EXHAUST FAN.2. INTERCONNECT TO MAIN ROOF CONDUCTOR AS INDICATED.3. LOCATE AIR TERMINAL, CABLING, AND FASTENERS TO AVOID OBSTRUCTION OF EQUIPMENT IDENTIFICATION LABEL, COVER OPENING, AND DISCONNECT MEANS.

MALLEABLE ALUMINUMADHESIVE MOUNT BASE

24 STRAND 14GAUGE ALUMINUMCONDUCTOR

NO SCALE

ROOF PENETRATION DETAIL

COLUMNGROUNDING WHENUTILIZED FORDOWN CONDUCTOR

EXOTHERMIC CONNECTION

CONCENTRIC STRANDCOPPER GROUND CONDUCTOR

GROUND ROD

EXOTHERMIC CONNECTION

NO SCALE

COLUMN GROUNDING

GV-1

GV-3

GV-2GV-4

GV-5

9x9 GOOSENECK

8x8 GOOSENECK

30ø EXHAUST STACK,TERMINATE 6' MIN ABOVEROOF SURFACE W/BUTTERFLY DAMPERDISCHARGE ROOF CAP

9x9 GOOSENECK

9x9 GOOSENECK

8x8 GOOSENECK8x8 GOOSENECK

TERMINAL (TYP) CONDUCTOR (TYP)

MAX (TYP)

20' - 0"

MAX (TYP)

50' - 0"

GROUND TO BUILDING STEEL (TYP)

MAX (TYP)

60' - 0"

TERMINAL (TYP)

BOND/SPLICE (TYP)

mi^k=molsfaba=clo=obcbobk`b=lkivK=obcbo==ql=pmb`fcf`^qflk==pb`qflk=OSQNNP=?ifdeqkfkd=molqb`qflk=clo=pqor`qrobp?=clo=obnrfobjbkqp

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWOS=mj

bib`qof`^i

abq^fip

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bQKO

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

k

1" = 10'-0"

ollc=mi^k=J=bib`qof`^i

ifdeqkfkd=molqb`qflk=`^i`ri^qflk

REVISIONS

DATE DESCRIPTION

Page 9: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

qo^kpclojbo=p`ebarib

kVA TYPE PRIMARY SECONDARYGROUNDINGCONDUCTOR

BONDINGCONDUCTOR

15 kVA

30 kVA

45 kVA

75 kVA

112.5 kVA

150 kVA

225 kVA

300 kVA

LINEAR

LINEAR

LINEAR

LINEAR

LINEAR

LINEAR

LINEAR

LINEAR

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

208Y/120V

208Y/120V

208Y/120V

208Y/120V

208Y/120V

208Y/120V

208Y/120V

208Y/120V

#8

#8

#4

#2

#1/O

#3/O

#3/O

#3/O

#8

#8

#4

#2

#1/O

#3/O

#3/O

#3/O

500 kVA LINEAR 480V-3Ø 208Y/120V #3/O #3/O

FEEDERID

# OFSETS

BUILDING WIREQUANTITY & SIZE TYPE

THHN - DRYTYPE THWN - WET

MINIMUMCONDUIT SIZE

`lmmbo=cbbabo=p`ebarib

30 1 3#10,#10 G 3/4"

35 1 3#8,#10 G 3/4"

40 1 3#8,#10 G 3/4"

45 1 3#6,#10 G 1"

50 1 3#6,#10 G 1"

60 1 3#4,#10 G 1"

70 1 3#4,#8 G 1 1/4"

80 1 3#3,#8 G

90 1 3#2,#8 G

100 1 3#1,#8 G

110 1 3#2,#6 G

125 1 3#1,#6 G

150 1 3#1/0,#6 G 2"

175 1 3#2/0,#6 G

200 1 3#3/0,#6 G

225 1 3#4/0,#4 G 2 1/2"

250 1 3-250kCM,#4 G

300 1 3-350kCM,#4 G

350 2 2"

400 1 4"

450 3#4/0,#2 G

500

600 3"

700

800

1000 3

1200 4

1600 4

2000 5

2500 6

1 1/4"

1 1/4"

1 1/4"

1 1/2"

1 1/2"

2"

2"

2 1/2"

2 1/2"

2 1/2"

2 1/2"

2

2

2

2

2

4"

4"

4"

3"

4"

4"

4"

3#2/0,#3 G

3-500kCM,#3 G

3-250kCM,#2 G

3-350kCM,#1 G

3-500kCM,#1/0 G

3-600kCM,#1/0 G

3-500kCM,#2/0 G

3-350kCM,#3/0 G

3-600kCM,#4/0 G

3-600kCM,#250 G

3-600kCM,#350 G

NOTES:1. ELECTRICAL CONTRACTOR TO VERIFY CONDUIT SIZE REQUIRED IF WIRE TYPES OTHER THANTHOSE LISTED ABOVE ARE USED.

2. FEEDER SIZES BASED ON TABLE 310.16, 75º C.

3. SIZES ADJUSTED PER NEC 110.14.

FEEDERID

# OFSETS

BUILDING WIREQUANTITY & SIZE TYPE

THHN - DRYTYPE THWN - WET

MINIMUMCONDUIT SIZE

30Y 1 4#10,#10 G 3/4"

35Y 1 4#8,#10 G 3/4"

40Y 1 4#8,#10 G 3/4"

45Y 1 4#6,#10 G 1"

50Y 1 4#6,#10 G 1"

60Y 1 4#4,#10 G 1"

70Y 1 4#4,#8 G 1 1/4"

80Y 1 4#3,#8 G

90Y 1 4#2,#8 G

100Y 1 4#1,#8 G

110Y 1 4#2,#6 G

125Y 1 4#1,#6 G

150Y 1 4#1/0,#6 G 2"

175Y 1 4#2/0,#6 G

200Y 1 4#3/0,#6 G

225Y 1 4#4/0,#4 G 2 1/2"

250Y 1 4-250kCM,#4 G

300Y 1 4-350kCM,#4 G

350Y 2 2"

400Y 1 4"

450Y 4#4/0,#2 G

500Y

600Y 3"

700Y

800Y

1000Y 3

1200Y 4

1600Y 4

2000Y 5

2500Y 6

1 1/4"

1 1/4"

1 1/4"

1 1/2"

1 1/2"

2"

2"

2 1/2"

2 1/2"

2 1/2"

2 1/2"

2

2

2

2

2

4"

4"

4"

3"

4"

4"

4"

4#2/0,#3 G

4-500kCM,#3 G

4-250kCM,#2 G

4-350kCM,#1 G

4-500kCM,#1/0 G

4-600kCM,#1/0 G

4-500kCM,#2/0 G

4-350kCM,#3/0 G

4-600kCM,#4/0 G

4-600kCM,#250 G

4-600kCM,#3/0 G

POWER COMPANYUNDERGROUND PRIMARY

SPD

M

NEC 700

MAIN DISTRIBUTION SWITCHBOARD MDS

KWH METER,FURNISHED BYPOWER COMPANY ANDINSTALLED BY THECONTRACTOR

POWER COMPANY PADMOUNTED TRANSFORMER480/277V, 3PH, 4W

CTSECTION

ATS-E400A-3P480V,NEMA1,22KAIC,OPENTRANSITION

NEC 700ATS-X100A-3P480V,NEMA1,22KAIC,OPENTRANSITION

NEC 702

NEC 702

CT/PT

CUSTOMERMETER

P/BD H1B

A. PROVIDE A SHORT CIRCUIT AND COORDINATION STUDY PER THE CONTRACT DOCUMENTS. NEC700 SYSTEM (ALL OVERCURRENT PROTECTIVE DEVICES UP AND DOWNSTREAM OF ATS-X)SHALL BE SELECTIVELY COORDINATED TO A MAXIMUM 0.01 SECONDS. SYSTEM IS INDICATEDHERE WITH CIRCUIT BREAKERS. PROVIDE FIXED, ADJUSTABLE AND ELECTRONIC ADJUSTABLEBREAKER AS REQUIRED. FUSES MAY BE USED IF DESIRED OR REQUIRED TO ACHIEVEREQUIRED SELECTIVITY. THE COORDINATION STUDY SHALL DEMONSTRATE REQUIREDSELECTIVITY FOR THE ENTIRE NEC 700 SYSTEM WITHOUT ADJUSTMENT TO THE CONTRACTAMOUNT. EQUIPMENT SHALL NOT BE RELEASED FOR FABRICATION UNTIL THE SHORT CIRCUITAND COORDINATION REPORT IS APPROVED BY THE ARCHITECT. THE CONTRACTOR IS ADVISEDNOT TO ORDER ELECTRICAL EQUIPMENT PRIOR TO SUBMISSION AND APPROVAL OF THECOORDINATION STUDY. THE CONTRACTOR SHALL TAKE FULL RESPONSIBILITY FORMODIFICATION OF ELECTRICAL EQUIPMENT ORDERED PRIOR THE APPROVED COORDINATIONSTUDY..

B. REFER TO TRANSFORMER SCHEDULE FOR BONDING CONDUCTORS SIZES FOR EACHTRANSFORMER..

C. REFER TO PANEL SCHEDULES FOR PANEL CHARACTERISTICS INCLUDING MAIN BREAKERREQUIREMENTS. GROUND PER SERVICE GROUND DETAIL ON THIS DRAWING..

D. SOME PANELS OVERSIZED PER JMU STANDARDS REQUIRING MINIMUM 225A PANELS EXCEPTWHERE COORDINATION CAN ONLY BE ACHIEVED WITH A SMALLER PANEL SIZE

400A100A

MAINBREAKER

DISTRIBUTION

XFMRTE1A,75 KVA

TWO 480V,250 KVA, BI-FUEL(GAS/DIESEL) GENERATORS(500KVA TOTAL CAPACITY)

22

2

M

XFMRT1A,112KVA

P/BD L1A

3 4

100Y 225Y

100Y100Y

2

400Y

400Y 100Y

(2) - 6" EC

800Y

P/BD HE1A

NEC 702

125

1-1/4" EC FORCT/PT LEADS

REPRESENTED BY n

APPLIES TO DRAWINGS Exxx

lkbifkb=hbvklqbp

1. REFER TO THE DUCTBANK DETAILS ON DRAWING E4.1 AND SUBSTITUTE CONDUIT SIZEINDICATED THEREIN..

2. PROVIDE A RED PLAQUE WITH WHITE LETTERING ON THE FRONT OF THIS EQUIPMENT STATING:"THIS PANEL IS CAPABLE OF BEING ENERGIZED FROM MULTIPLE SOURCES. ".

3. PROVIDE DISCONNECTING MEANS LABEL PER NEC ..

4. PROVIDE A SHUNT TRIP MAIN CIRCUIT BREAKER. ALSO PROVIDE A KEY ACTIVATED SWITCH TOOPEN MCB LOCATED ADJACENT TO FIRE ALARM ANNUNCIATOR. KEY SWITCH TO BELOCKNETICS H.D. KEY SWITCH #643-05.

lkb=ifkb=dbkbo^i==klqbpW

1 1

NEC 700P/BD HX1B

2

400Y

175

225Y

P/BD HM1B

P/BD LM1A

NOTE: IF ADDITIVE BID ITEM #01 IS TAKEN, THE BASE BID ONELINE DIAGRAM SHALL NOT BE USED.

400Y

2P/BD LE1A

225Y

2P/BD LEMDF

100Y

2P/BD LE1C

225Y

P/BD L1B

225Y

XFMRTM1A,75KVA

225Y

125

METERING TO INTERFACE TOTHE BAS (TYP). REFER TOSPECIFICATION SECTION 262713

POWER COMPANYUNDERGROUND PRIMARY

SPD

M

NEC 700

MAIN DISTRIBUTION SWITCHBOARD MDS

KWH METER,FURNISHED BYPOWER COMPANY ANDINSTALLED BY THECONTRACTOR

POWER COMPANY PADMOUNTED TRANSFORMER480/277V, 3PH, 4W

CTSECTION

ATS-E400A-3P480V,NEMA1,22KAIC,OPENTRANSITION

NEC 700ATS-X100A-3P480V,NEMA1,22KAIC,OPENTRANSITION

NEC 702

NEC 702

CT/PT

CUSTOMERMETER

P/BD H1B

400A100A

L MAINBREAKER

DISTRIBUTION

XFMRTE1A,75 KVA

480V,100 KVA, NGGENERATOR

22

2

2

M

XFMRT1A,112.5KVA

P/BD L1A

3 4

100Y 225Y

100Y100Y

P/BD LE1A

2

100Y

(2) - 6" EC

800Y

P/BD HE1A

NEC 702

225Y

125

1-1/4" EC FORCT/PT LEADS

REPRESENTED BY n

APPLIES TO DRAWINGS Exxx

lkbifkb=hbvklqbp

1. REFER TO THE DUCTBANK DETAILS ON DRAWING E4.1 AND SUBTITUTE CONDUIT SIZE INDICATEDTHEREIN..

2. PROVIDE A RED PLAQUE WITH WHITE LETTERING ON THE FRONT OF THIS EQUIPMENT STATING:"THIS PANEL IS CAPABLE OF BEING ENERGIZED FROM MULTIPLE SOURCES. ".

3. PROVIDE DISCONNECTING MEANS LABEL PER NEC .. .

4. PROVIDE A SHUNT TRIP MAIN CIRCUIT BREAKER. ALSO PROVIDE A KEY ACTIVATED SWITCH TOOPEN MCB LOCATED ADJACENT TO FIRE ALARM ANNUNCIATOR. KEY SWITCH TO BE LOCKNETICSH.D. KEY SWITCH #643-05.

lkb=ifkb=dbkbo^i==klqbpW

1 1

NEC 700P/BD HX1B

2

400Y

175

225Y

NOTE: IF ADDITIVE BID ITEM #01 IS TAKEN, THIS BASE BID ONELINE DIAGRAM SHALL NOT BE USED.

400Y400Y

400Y

2P/BD LEMDF

100Y

P/BD L1B

225Y

P/BD L1C

225Y

OVERSIZEDFORFUTURE

METERING TO INTERFACE TOTHE BAS (TYP). REFER TOSPECIFICATION SECTION 262713

225Y

P/BD HM1B

A. PROVIDE A SHORT CIRCUIT AND COORDINATION STUDY PER THE CONTRACT DOCUMENTS. NEC700 SYSTEM (ALL OVERCURRENT PROTECTIVE DEVICES UP AND DOWNSTREAM OF ATS-X)SHALL BE SELECTIVELY COORDINATED TO A MAXIMUM 0.01 SECONDS. SYSTEM IS INDICATEDHERE WITH CIRCUIT BREAKERS. PROVIDE FIXED, ADJUSTABLE AND ELECTRONIC ADJUSTABLEBREAKER AS REQUIRED. FUSES MAY BE USED IF DESIRED OR REQUIRED TO ACHIEVEREQUIRED SELECTIVITY. THE COORDINATION STUDY SHALL DEMONSTRATE REQUIREDSELECTIVITY FOR THE ENTIRE NEC 700 SYSTEM WITHOUT ADJUSTMENT TO THE CONTRACTAMOUNT. EQUIPMENT SHALL NOT BE RELEASED FOR FABRICATION UNTIL THE SHORT CIRCUITAND COORDINATION REPORT IS APPROVED BY THE ARCHITECT. THE CONTRACTOR IS ADVISEDNOT TO ORDER ELECTRICAL EQUIPMENT PRIOR TO SUBMISSION AND APPROVAL OF THECOORDINATION STUDY. THE CONTRACTOR SHALL TAKE FULL RESPONSIBILITY FORMODIFICATION OF ELECTRICAL EQUIPMENT ORDERED PRIOR THE APPROVED COORDINATIONSTUDY..

B. REFER TO TRANSFORMER SCHEDULE FOR BONDING CONDUCTORS SIZES FOR EACHTRANSFORMER..

C. REFER TO PANEL SCHEDULES FOR PANEL CHARACTERISTICS INCLUDING MAIN BREAKERREQUIREMENTS. GROUND PER SERVICE GROUND DETAIL ON THIS DRAWING..

D. SOME PANELS OVERSIZED PER JMU STANDARDS REQUIRING MINIMUN 225A PANELS EXCEPTWHERE COORDINATION CAN ONLY BE ACHEIVED WITH A SMALLER PANEL SIZE

P/BD LM1A

XFMRTM1A,75KVA

225Y

125

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWOU=mj

mltbo=lkbJifkb

af^do^j

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bRKN

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

NO SCALE

lkb=ifkb=af^do^j=J=^aafqfsb=_fa=fqbj=@NNO SCALE

lkb=ifkb=af^do^j=J=_^pb=_fa

1. SWITCHBOARD SHALL BE UL SERVICE ENTRANCE RATED2. PROVIDE SPD WITH OVERCURRENT DEVICE, DISCONECTING MEANS & CONDUCTORS, SIZE PER MFR REQUIREMENTS MOUNTED ON TOP OF EQUIPMENT.3. PROVIDE DISCONNECTING MEANS LABEL PER NEC4 .NOT USED5. PROVIDE FACTORY INSTALLED DIGITAL MULTIMETER, PLUS MONITORING CABLE IN CONDUIT TO BAS PICKUP MODULE, COORDINATE WITH DIV 23.6. PROVIDE SIGN PER NEC 700: "LIFE SAFETY STANDBY FROM GENERATOR LOCATED IN EQUIPMENT YARD OUTSIDE, VIA ATS-X"7. PROVIDE SIGN PER NEC 702: "OPTIONAL STANDBY FROM GENERATOR LOCATED IN EQUIPMENT YARD OUTSIDE, VIA ATS-E8. FOR NON-SIMULTANEOUS LOADS, ONLY LARGER OF LOADS IS INCLUDED IN TOTAL.9. PROVIDE INDIVIDUAL METERING AND BAS CABLING FOR THIS CIRCUIT.10. REFER TO PLANS FOR CONDUCTOR AND CONDUIT SIZES.

NOTES:

LARGEST MOTOR 0.00 kVA 0.00 kVA TOTAL DEMAND... 386 A

MISCELLANEOUS 87.10 kVA 87.10 kVA TOTAL CONNECTED... 440 A

KITCHEN 0.00 kVA 0.00 kVA

ELECTRIC HEAT 5.00 kVA 5.00 kVA TOTAL DEMAND KVA: 321 kVA

AC / HEAT PUMP 145.74 kVA 145.74 kVA TOTAL CONNECTED... 366 kVA

RECEPTACLES 109.68 kVA 59.84 kVA

EXTERIOR LIGHTING 4.70 kVA 5.88 kVA

INTERIOR LIGHTING 13.89 kVA 17.36 kVA

LOAD TYPE CONNECTED KVA DEMAND KVA

TOTAL 131.04 kVA 116.61 kVA 114.00 kVA

12 SPARE 0.0 kVA 0.0 kVA 0.0 kVA 3 100 A

11 SPARE 0.0 kVA 0.0 kVA 0.0 kVA 3 225 A

10 LM1A VIA TM1A 5.1 kVA 3.3 kVA 3.3 kVA 3 125 A

9 SPARE 0.0 kVA 0.0 kVA 0.0 kVA 3 400 A

8 SPD 0.0 kVA 0.0 kVA 0.0 kVA 3 100 A 2,10

7 H1B 8.1 kVA 5.3 kVA 4.5 kVA 3 225 A 9,10

6 HM1B 35.4 kVA 32.8 kVA 31.3 kVA 3 225 A 9,10

5 ATS-X 3.0 kVA 4.1 kVA 1.6 kVA 3 100 A 6,9,10

4 ATS-E 41.8 kVA 39.7 kVA 39.8 kVA 3 400 A 7,9,10

3 L1A VIA T1A 37.7 kVA 31.3 kVA 33.5 kVA 3 175 A 9,10

2 MAIN BREAKER 0.0 kVA 0.0 kVA 0.0 kVA 3 800 A 3,5,10

1 CT 0.0 kVA 0.0 kVA 0.0 kVA 3 0 A 1

DEVICE

NO.DESCRIPTION A B C

NUMBER

OF POLESRATING NOTES

NEUTRAL BUS: 800 A

VERTICAL BUS: 800 A CT SECTION: YES BRACING: 22K AMPS...

GROUND BUS: 800 A MAIN SWITCH: 800 A VOLTAGE: 480/277 Wye 3 PH 4 WIRE

HORIZONTAL... 800 A NEMA ENCL: NEMA... FRONT...

SWITCHBOARD SCHEDULE MDS

MISCELLANEOUS 8.00 kVA 100.00% 8.00 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 25 A

AC / HEAT PUMP 0.00 kVA 0.00% 0.00 kVA Total Conn. Current: 22 A

RECEPTACLES 0.00 kVA 0.00% 0.00 kVA Total Est. Demand: 20.4 kVA

EXTERIOR LIGHTING 3.38 kVA 125.00% 4.23 kVA Total Conn. Load: 18.0 kVA

INTERIOR LIGHTING 6.58 kVA 125.00% 8.22 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

30 A 20 A 16 A

8 kVA 5 kVA 4 kVA

41 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 42

39 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 40

37 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 38

35 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 36

33 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 34

31 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 32

29 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 30

27 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 28

25 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 26

23 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 24

21 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 22

19 1.3 0.0 SPACE ONLY -- -- 20

17 1.3 0.0 SPACE ONLY -- -- 18

15

20 A 3 SPRAY BOOTH 150

1.3 0.0 SPACE ONLY -- -- 16

13 1.3 0.0 SPACE ONLY -- -- 14

11 1.3 0.0 SPACE ONLY -- -- 12

9

20 A 3 SPRAY BOOTH 150

1.3 0.0 SPACE ONLY -- -- 10

7 20 A 1 SITE LIGHTING 3.4 0.0 SPACE ONLY -- -- 8

5 20 A 1 LTG 147, 148, 149, 152, 154 1.8 0.0 SPACE ONLY -- -- 6

3 20 A 1 LTG 158 2.7 0.0 SPACE ONLY -- -- 4

1 20 A 1 LTG 107, 108, 106, 105, 101 2.1 0.0 SPACE ONLY -- -- 2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

225 AMP MLO 480/277 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K

PANELBOARD SCHEDULE H1B LOCATION:CORRIDOR101

FED FROM: MDS

MISCELLANEOUS 27.50 kVA 100.00% 27.50 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 125 A

AC / HEAT PUMP 76.26 kVA 100.00% 76.26 kVA Total Conn. Current: 125 A

RECEPTACLES 0.00 kVA 0.00% 0.00 kVA Total Est. Demand: 103.8 kVA

EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 103.8 kVA

INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

135 A 124 A 117 A

37 kVA 34 kVA 33 kVA

41 -- -- SPACE ONLY 0.0 0.8 42

39 -- -- SPACE ONLY 0.0 0.8 40

37 -- -- SPACE ONLY 0.0 0.8

F-7 (ML 3 20 A

38

35 1.1 6.7 36

33 1.1 6.7 34

31

15 A 3 AHU-4 (ML)

1.1 6.7

CU-4 (ML) 3 30 A

32

29 0.8 4.9 30

27 0.8 4.9 28

25

15 A 3 AHU-3 (ML)

0.8 4.9

CU-3 (ML) 3 25 A

26

23 0.0 7.3 24

21 0.0 7.3 22

19

15 A 3 AHU-2 (ML)

2.8 7.3

CU-2 (ML) 3 30 A

20

17 20 A 1 SPARE 0.0 1.3 18

15 20 A 1 SPARE 0.0 1.3 16

13 20 A 1 SPARE 0.0 1.3

MAU-2 (ML) 3 20 A

14

11 20 A 1 TU1-9 THRU TU1-11 0.3 1.3 12

9 20 A 1 GARAGE DOOR 150 2.0 1.3 10

7 20 A 1 GARAGE DOOR 153 2.0 1.3

MAU-1 (ML) 3 20 A

8

5 20 A 1 GARAGE DOOR 161 2.0 5.8 6

3 20 A 1 GARAGE DOOR 162 2.0 5.8 4

1 20 A 1 GARAGE DOOR 162 2.0 5.8

DC-1 (ML) 3 30 A

2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

225 AMP MLO 480/277 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K

PANELBOARD SCHEDULE HM1B LOCATION:MECHANICALROOM 108

FED FROM: MDS

jp_==eN_

=========ejN_

REVISIONS

DATE DESCRIPTION

Page 10: C:acad temp545116-ME WJC-1-9 2014 - Mathers-Team.com · appliance receptacle, mount at +1'-6" aff. provide nema configuration to match plug for equipment served. appliance receptacle,

^o`

efqb`

qpj

lpbib

vK`

lj

TUM=i

vk

ke^

sbk

=m^

oht

^vI=prfqb=O

MM==sfo

dfk

f^=_

b^

`eI=sfo

dfk

f^=O

PQRO

mel

kb=ETRTF=PSUJO

UMM===c

^u=ETRTF=PSUJO

OPP

PROJECT NO: DATE:

01/15/16

NLNNLOMNS=QWQSWPM=mj

bib`qof`^i

p`ebaribp

g^jbp=j

^afplk=rkfsbopfqv

rkfsbopfqv=pbosf`

bp=^

kkbu

`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^

bRKO

pq^

qb=molgb`q=`labW=ONSJNUNPRJMMM

545116 NOVEMBER 16, 2015

MISCELLANEOUS 20.60 kVA 100.00% 20.60 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 105 A

AC / HEAT PUMP 2.22 kVA 100.00% 2.22 kVA Total Conn. Current: 118 A

RECEPTACLES 19.68 kVA 75.41% 14.84 kVA Total Est. Demand: 37.7 kVA

EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 42.5 kVA

INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

146 A 90 A 128 A

17 kVA 11 kVA 15 kVA

83 -- -- SPACE ONLY 0.0 0.0 84

81 -- -- SPACE ONLY 0.0 0.0 82

79 -- -- SPACE ONLY 0.0 0.0

SPARE (FUTURE SPRAYBOOTH) 3 20 A

80

77 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 78

75 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 76

73 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 74

71 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 72

69 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 70

67 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 68

65 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 66

63 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 64

61 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 62

59 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 60

57 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 58

55 20 A 1 REC 152 0.7 0.0 SPARE 1 20 A 56

53 20 A 1 REC 152, 154 1.1 0.0 SPARE 1 20 A 54

51 20 A 1 COMPUTER 154 0.7 0.0 SPARE 1 20 A 52

49 20 A 1 COMPUTER 152 0.7 0.0 SPARE 1 20 A 50

47 20 A 1 EWC 101 (GP) 0.5 0.0 DAMPER 108 (ML) 1 20 A 48

45 20 A 1 EWC 150 (GP) 0.5 0.2 EWC 101 (GP) 1 20 A 46

43 20 A 1 EWC 150 (GP) 0.5 3.5 44

41 20 A 1 REC 149, 148 0.7 3.5AIR COMPRESSOR (ML) 2 40 A

42

39 20 A 1 COMPUTER 149 0.7 0.2 UH -5 (ML) 1 20 A 40

37 20 A 1 COMPUTER 148 0.7 1.0 F-3 (ML) 1 15 A 38

35 20 A 1 REC 147 0.7 1.0 F-1(ML) 1 15 A 36

33 20 A 1 REC 101, 100 0.9 0.5 PAINT BOOTH LIGHTS 1 20 A 34

31 20 A 1 DRYER 103 1.5 0.5 PAINT BOOTH LIGHTS 1 20 A 32

29 20 A 1 DRYER 103 1.5 0.4 MITER SAW 156 1 20 A 30

27 20 A 1 DRYER 102 1.5 0.7 REC 156 1 20 A 28

25 20 A 1 DRYER 102 1.5 0.7 REC 151 1 20 A 26

23 20 A 1 REC 105 0.7 0.9 REC 151 1 20 A 24

21 20 A 1 REC 106 0.7 0.7 COIL REEL REC 150 1 20 A 22

19 20 A 1 REC 108 0.4 0.7 COIL REEL REC 150 1 20 A 20

17 20 A 1 PROJECTOR 107 0.0 0.7 COIL REEL REC 150 1 20 A 18

15 20 A 1 SCREEN 107 0.5 0.5 REC 150 1 20 A 16

13 20 A 1 REC 107 0.9 0.4 REC 150 1 20 A 14

11 20 A 1 REFRIG 110 1.0 0.2 PAINT SHAKER 150 1 20 A 12

9 20 A 1 VENDING 110 (GP) 1.0 0.2 PAINT SHAKER 150 1 20 A 10

7 20 A 1 VENDING 110 (GP) 1.0 0.9 REC EXTERIOR 1 20 A 8

5 20 A 1 VENDING 110 (GP) 1.0 0.9 REC EXTERIOR 1 20 A 6

3 20 A 1 COUNTER REC 110 0.4 0.9 REC EXTERIOR 1 20 A 4

1 20 A 1 COUNTER REC 110 0.4 0.9 REC 101 1 20 A 2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

225 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K

PANELBOARD SCHEDULE L1B LOCATION:CORRIDOR101

FED FROM: L1A

MISCELLANEOUS 2.00 kVA 100.00% 2.00 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 63 A

AC / HEAT PUMP 0.00 kVA 0.00% 0.00 kVA Total Conn. Current: 92 A

RECEPTACLES 31.16 kVA 66.05% 20.58 kVA Total Est. Demand: 22.6 kVA

EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 33.2 kVA

INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

96 A 89 A 92 A

11 kVA 11 kVA 11 kVA

89 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 90

87 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 88

85 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 86

83 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 84

81 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 82

79 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 80

77 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 78

75 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 76

73 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 74

71 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 72

69 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 70

67 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 68

65 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 66

63 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 64

61 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 62

59 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 60

57 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 58

55 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 56

53 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 54

51 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 52

49 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 50

47 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 48

45 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 46

43 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 44

41 20 A 1 REC 136 0.7 1.0 SCP (L) 1 20 A 42

39 20 A 1 REC 133, 134 1.1 1.0 FACP (L) (RED BREAKER) 1 20 A 40

37 20 A 1 COMPUTER 134, 133 0.7 1.1 REC 113 1 20 A 38

35 20 A 1 REC 126, 131 1.1 0.0 F-12 & F13 (ML) 1 15 A 36

33 20 A 1 COMPUTER 126, 131 0.7 1.1 REC 146, 145 1 20 A 34

31 20 A 1 REC 127, 130 1.1 0.7 COMPUTER 145, 146 1 20 A 32

29 20 A 1 COMPUTER 127, 130 0.7 1.3 REC 138 1 20 A 30

27 20 A 1 REC 128 0.5 1.1 REC 143, 144 1 20 A 28

25 20 A 1 REC 129 0.9 0.7 COMPUTER 143,144 1 20 A 26

23 20 A 1 REC 114 0.5 1.1 REC 141, 142 1 20 A 24

21 20 A 1 COMPUTER 114 0.4 0.7 COMPUTER 141, 142 1 20 A 22

19 20 A 1 REC 115, 116 1.1 1.1 REC 139, 140 1 20 A 20

17 20 A 1 COMPUTER 116, 115 0.7 0.7 COMPUTER 139, 140 1 20 A 18

15 20 A 1 REC 118, 117 1.1 0.5 REC 137 1 20 A 16

13 20 A 1 COMPUTER 118, 117 0.7 0.4 COMPUTER 137 1 20 A 14

11 20 A 1 REC 120, 119 1.1 0.4 COUNTER REC 135 1 20 A 12

9 20 A 1 COMPUTER 120, 119 0.7 0.4 COUNTER REC 135 1 20 A 10

7 20 A 1 REC 122, 121 1.1 0.2 COPIER 135 1 20 A 8

5 20 A 1 COMPUTER 122, 121 0.7 1.0 COPIER 135 1 20 A 6

3 20 A 1 REC 124, 123 1.1 0.4 COUNTER REC 128 1 20 A 4

1 20 A 1 COMPUTER 124, 123 0.7 1.0 REF 128 1 20 A 2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

225 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K

PANELBOARD SCHEDULE L1C LOCATION:ELECTRICAL125

FED FROM: L1A

MISCELLANEOUS 15.20 kVA 100.00% 15.20 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 134 A

AC / HEAT PUMP 5.26 kVA 100.00% 5.26 kVA Total Conn. Current: 184 A

RECEPTACLES 45.72 kVA 60.94% 27.86 kVA Total Est. Demand: 48.3 kVA

EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 66.2 kVA

INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

184 A 184 A 184 A

22 kVA 22 kVA 22 kVA

41 15.0 4.0 42

39 15.0 4.4 40

37

0 A 3PANEL LE1C FEED THRU LUGS(SPARE UNDER BASE BID)

15.0 4.4

PANEL LEMDF 3 100 A

38

35 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 36

33 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 34

31 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 32

29 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 30

27 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 28

25 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 26

23 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 24

21 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 22

19 -- -- SPACE ONLY 0.0 0.0 SPARE 1 20 A 20

17 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 18

15 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 16

13 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 14

11 20 A 1 EMERG PHONE (L) 1.0 0.0 SPARE 1 20 A 12

9 20 A 1 EMERG PHONE (L) 0.6 0.0 SPARE 1 20 A 10

7 20 A 1 ELECTRIC LOCK (L) 1.0 0.0 DAMPER 157 (ML) 1 20 A 8

5 1.9 0.2 DC-1 PANEL (ML) 1 20 A 6

325 A 2 DSS-1 (ML)

1.9 0.2 BAS PANEL (L) 1 20 A 4

1 20 A 1 BOILER B-1 (ML) 1.5 0.2 DDC PANEL (L) 1 20 A 2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

225 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K

PANELBOARD SCHEDULE LE1A LOCATION:ELECTRICAL160

FED FROM: TE1A

MISCELLANEOUS 36.40 kVA 100.00% 36.40 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 210 A

AC / HEAT PUMP 2.22 kVA 100.00% 2.22 kVA Total Conn. Current: 285 A

RECEPTACLES 63.96 kVA 57.82% 36.98 kVA Total Est. Demand: 75.6 kVA

EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 102.6 kVA

INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

317 A 261 A 282 A

38 kVA 31 kVA 34 kVA

83 14.8 11.0 84

81 10.8 10.7 82

79

225 A 3 PANEL L1B

16.9 11.4PANEL L1C (SPARE UNDERADDITIVE BID ITEM#1)

3 225 A

80

77 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 78

75 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 76

73 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 74

71 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 72

69 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 70

67 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 68

65 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 66

63 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 64

61 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 62

59 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 60

57 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 58

55 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 56

53 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 54

51 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 52

49 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 50

47 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 48

45 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 46

43 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 44

41 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 42

39 20 A 1 REC 162 0.7 0.0 SPACE ONLY -- -- 40

37 20 A 1 REC 162 0.7 0.0 SPACE ONLY -- -- 38

35 20 A 1 REC 157 0.5 0.0 SPACE ONLY -- -- 36

33 20 A 1 REC 159, 158 0.5 0.0 SPACE ONLY -- -- 34

31 20 A 1 REC 161 0.5 0.0 SPACE ONLY -- -- 32

29 20 A 1 REC 161 0.5 0.7 30

27 20 A 1 SPINDLE SANDER 153 1.6 0.7 28

25 20 A 1 LATHE 153 0.8 0.7

SHAPER 153 3 20 A

26

23 20 A 1 BELT SANDER 153 0.8 0.7 24

21 20 A 1 DRILL PRESS 153 0.8 0.7 22

19 20 A 1 BAND SAW 153 0.8 0.7

LG TABLE SAW 153 3 30 A

20

17 20 A 1 COIL REEL REC 153 0.7 0.7 18

15 20 A 1 COIL REEL REC 153 0.7 0.7 16

13 20 A 1 COIL REEL REC 153 0.7 0.7

LG TABLE SAW 153 3 30 A

14

11 20 A 1 COIL REEL REC 153 0.7 1.0 12

9 20 A 1 MITER SAWS 153 1.0 1.0 10

7 20 A 1 BENCH REC 153 1.0 1.0

JOINER 153 3 30 A

8

5 20 A 1 SM PLANER 153 0.8 0.7 6

3 20 A 1 ROUTER 153 0.8 0.7 4

1 20 A 1 DRUM SANDER 153 1.2 0.7

LG PLANER 153 3 20 A

2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

400 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K

PANELBOARD SCHEDULE L1A LOCATION:ELECTRICAL160

FED FROM: T1A

MISCELLANEOUS 12.00 kVA 100.00% 12.00 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 35 A

AC / HEAT PUMP 0.00 kVA 0.00% 0.00 kVA Total Conn. Current: 35 A

RECEPTACLES 0.72 kVA 100.00% 0.72 kVA Total Est. Demand: 12.7 kVA

EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 12.7 kVA

INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

37 A 37 A 33 A

4 kVA 4 kVA 4 kVA

29 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 30

27 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 28

25 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 26

23 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 24

21 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 22

19 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 20

17 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 18

15 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 16

13 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 14

11 20 A 1 SPARE 0.0 2.0 12

9 20 A 1 SPARE 0.0 2.0RACK 109 2 30 A

10

7 20 A 1 SPARE 0.0 2.0 8

5 20 A 1 SPARE 0.0 2.0RACK 109 2 30 A

6

3 20 A 1 REC 109 0.4 2.0 4

1 20 A 1 REC 109 0.4 2.0RACK 109 2 30 A

2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

100 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K

PANELBOARD SCHEDULE LEMDF LOCATION:MDF &SPECIAL...

FED FROM: LE1A

MISCELLANEOUS 0.00 kVA 0.00% 0.00 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 5.00 kVA 100.00% 5.00 kVA Total Est. Demand... 33 A

AC / HEAT PUMP 6.90 kVA 100.00% 6.90 kVA Total Conn. Current: 33 A

RECEPTACLES 0.00 kVA 0.00% 0.00 kVA Total Est. Demand: 11.9 kVA

EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 11.9 kVA

INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

43 A 28 A 28 A

5 kVA 3 kVA 3 kVA

41 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 42

39 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 40

37 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 38

35 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 36

33 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 34

31 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 32

29 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 30

27 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 28

25 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 26

23 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 24

21 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 22

19 20 A 1 WH-1 (ML) 1.0 1.0 WH-2(ML) 1 20 A 20

17 20 A 1 UH-3 (ML) 0.2 0.2 UH-4 (ML) 1 20 A 18

15 20 A 1 UH-1 (ML) 0.2 0.2 UH-2 (ML) 1 20 A 16

13 15 A 1 F-10 (ML) 0.0 0.1 F-11 (ML) 1 15 A 14

11 20 A 1 F-8 (ML) 1.0 1.0 F-9 (ML) 1 15 A 12

9 20 A 1 F-5 (ML) 1.0 1.0 F-6 (ML) 1 20 A 10

7 20 A 1 F-2 (ML) 1.0 1.0 F-4 (ML) 1 20 A 8

5 20 A 1 RH-2 (ML) 0.5 0.5 RH-1 (ML) 1 20 A 6

3 20 A 1 RH-4 (ML) 0.5 0.5 RH-3 (ML) 1 20 A 4

1 20 A 1 RH-5 (ML) 0.5 0.5 RH-6 (ML) 1 20 A 2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

225 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K

PANELBOARD SCHEDULE LM1A LOCATION:MECHANICALROOM 157

FED FROM: TM1A

iN^==ibN^=ijac

iN_===iN`==ijN^

=ebN_

=euN_

i^_bi=?iN`?=^p=?ibN`?=rkabo=^aafqfsb=_fa=lmqflk=@NUNDER ADDITIVE BID OPTION #1, "LE1C" IS FED FROM "LE1A". REFER TO ONE LINE DIAGRAM

MISCELLANEOUS 15.20 kVA 100.00% 15.20 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 124 A

AC / HEAT PUMP 60.36 kVA 100.00% 60.36 kVA Total Conn. Current: 146 A

RECEPTACLES 45.72 kVA 60.94% 27.86 kVA Total Est. Demand: 103.4 kVA

EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 121.3 kVA

INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

151 A 143 A 144 A

42 kVA 40 kVA 40 kVA

41 -- -- SPACE ONLY 0.0 22.1 42

39 -- -- SPACE ONLY 0.0 22.0 40

37 -- -- SPACE ONLY 0.0 22.1

LE1A VIA TE1A 3 125 A

38

35 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 36

33 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 34

31 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 32

29 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 30

27 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 28

25 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 26

23 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 24

21 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 22

19 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 20

17 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 18

15 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 16

13 0.0 0.0 14

11 0.0 0.0 12

9

20 A 3 PUMP P-1

0.0 0.0

PUMP P-2 3 20 A

10

7 15 A 1 FP-1 - 5 (ML) 1.2 0.8 TU1-1 THRU TU1-8 1 15 A 8

5 3.9 13.8 6

3 3.9 13.8 4

1

20 A 3 AHU-1 (ML)

3.9 13.8

CU-1 (ML) 3 60 A

2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

400 AMP MLO 480/277 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 22K

PANELBOARD SCHEDULE HE1A LOCATION:ELECTRICAL160

FED FROM: ATS-E

MISCELLANEOUS 0.00 kVA 0.00% 0.00 kVA

KITCHEN 0.00 kVA 0.00% 0.00 kVA

ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 13 A

AC / HEAT PUMP 0.00 kVA 0.00% 0.00 kVA Total Conn. Current: 10 A

RECEPTACLES 0.00 kVA 0.00% 0.00 kVA Total Est. Demand: 10.8 kVA

EXTERIOR LIGHTING 1.32 kVA 125.00% 1.65 kVA Total Conn. Load: 8.6 kVA

INTERIOR LIGHTING 7.32 kVA 125.00% 9.14 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.

12 A 16 A 6 A

3 kVA 4 kVA 2 kVA

29 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 30

27 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 28

25 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 26

23 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 24

21 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 22

19 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 20

17 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 18

15 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 16

13 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 14

11 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 12

9 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 10

7 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 8

5 20 A 1 EM 139 -146 1.6 0.0 SPACE ONLY -- -- 6

3 20 A 1 EM EXT LIGHTING 1.3 2.8 EM LTG 119-124 1 20 A 4

1 20 A 1 EM LTG 150 1.9 1.1 EM LTG COORIDOR 1 20 A 2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

100 AMP MLO 480/277 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 22K

PANELBOARD SCHEDULE HX1B LOCATION:CORRIDOR101

FED FROM: ATS-X

REVISIONS

DATE DESCRIPTION