NOTE: REFER TO "TYPICAL COMMUNICATION OUTLET DETAIL" ON DRAWING E4.1 FOR BOX & CONDUIT REQUIREMENTS.CABLING AND TERMINALS WILL BE PROVIDED BY THE OWNER.
SYMBOL DESCRIPTION
`ljjrkf`^qflkp=ibdbka
TELECOMMUNICATIONS OUTLET, MOUNT AT +3'-10"AFF.
TELECOMMUNICATIONS OUTLET, MOUNT AT +1'-6"AFF.
OWNER PROVIDED TELECOMMUNICATIONS EQUIPMENT RACK.
TELECOMMUNICATIONS GROUND BUS BAR, MOUNT AT +1'-6"AFF.
TELECOMMUNICATIONS MAIN GROUND BUS BAR, MOUNT AT +1'-6"AFF.
TGB
TMGB
DPS
EL
RX
DOOR POSITION SWITCH. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1
ELECTRIC LOCK. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1
REQUEST TO EXIT. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1
BL
CARD READER. REFER TO SECURITY ELECTRONICS DETAIL ON DRAWING E4.1
EMERGENCY PHONE. PROVIDE RECESSED BOX MOUNT AT +3'-10"AFF WITH 1" EC TO MDF ROOM
CR
SYMBOL DESCRIPTION
cfob=^i^oj=ibdbka
FIRE ALARM AUDIO/VISUAL ANNUNCIATOR, MOUNT AT +7'-10"AFF OR 6" BELOW FINISHED CEILING, WHICHEVERIS LOWER. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING.
FIRE ALARM VISUAL STROBE ANNUNCIATOR, MOUNT AT +7'-10"AFF OR 6" BELOW FINISHED CEILING,WHICHEVER IS LOWER. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING.
FIRE ALARM MANUAL PULL STATION, MOUNT AT +3'-10"AFF.F
FIRE ALARM DUCT SMOKE DETECTOR, FURNISH AND CONNECT UNDER DIVISION 28. INSTALL UNDERDIVISION 23. VERIFY LOCATION WITH DIVISION 23 PRIOR TO ROUGH-IN. PROVIDE ACCESSIBLE KEYOPERATED REMOTE TEST SWITCH FOR EACH DETECTOR.
SMOKE DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.
HEAT DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.
S
H
FIRE ALARM TAMPER SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.TS
FIRE ALARM FLOW SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.FS
POST INDICATOR VALVE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.PV
FIRE ALARM PRESSURE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.PS
FIRE ALARM REMOTE INDICATOR, CEILING MOUNT.RI
FIRE ALARM MONITOR MODULE. NOT ALL MONITOR MODULES ARE INDICATED ON DRAWINGS.PROVIDE QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED MONITORINGFUNCTIONS.
M
CFIRE ALARM CONTROL MODULE. NOT ALL CONTROL MODULES ARE INDICATED ON DRAWINGS.PROVIDE QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED CONTROLFUNCTIONS.
FIRE ALARM SPRINKLER BELL, MOUNT AT +10'-0"AFF.B
FIRE ALARM MAGNETIC DOOR HOLDER, WALL MOUNT DEVICE AT 6" BELOW TOP OF DOOR. PROVIDEHINGED MAGNETIC CATCH PLATE ON DOOR TO MATE WITH DEVICE, COORDINATE LOCATION AND LENGTHWITH DIVISION 08. PROVIDE CONCEALED 120-VOLT POWER CONNECTION AND FIRE ALARM CONTROLMODULE IF REQUIRED FOR PROPER OPERATION.
FIRE ALARM DOOR HOLDER/CLOSER HARDWARE UNDER DIVISION 08, MONITOR AND CONTROL INTERFACEWITH FIRE ALARM UNDER DIVISION 28.
FIRE ALARM/POWER CONNECTION TO DIVISION 23 SMOKE OR FIRE/SMOKE DAMPER. COORDINATE WITHDIVISION 23. REFER TO TYPICAL FIRE/SMOKE DAMPER DIAGRAM.
SD
M
M
xx
xx
dbkbo^i=klqbp
A. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IFREQUIRED BY ALL. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER QUALITY.
IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY OF WORK.
B. SUBSCRIPT LETTER BESIDE DEVICE INDICATES THE TYPE AS FOLLOWS:
3R WEATHERPROOF (NEMA 3R)W WALL MOUNT AT +4'-6"AFFP PILOT LIGHT AT THE SWITCH HANDLEWG WIRE GUARDC MOUNT +6" ABOVE COUNTER TOP BACK SPLASH
C. FOLLOW MOUNTING HEIGHTS INDICATED IN THE ELECTRICAL LEGEND UNLESS OTHERWISE INDICATED. MEASUREALL MOUNTING HEIGHTS FROM THE DEVICE CENTER LINE UNLESS OTHERWISE INDICATED.
D. VERIFY EXACT FEEDER LOCATIONS FOR MECHANICAL EQUIPMENT.
E. EQUIPMENT CONNECTIONS ARE INDICATED IN THEIR APPROXIMATE LOCATIONS. VERIFY EXACT LOCATIONS OF ALLCONNECTIONS WITH OTHER TRADES SUPPLYING EQUIPMENT TO AVOID CONFLICTS AT INSTALLATION.
F. LOCATED ALL SWITCHES FOR LOCAL CONTROL OF LIGHTING ON STRIKE SIDE OF SINGLE DOORS UNLESSOTHERWISE INDICATED.
G. PROVIDE SPECIFIC BREAKER ARRANGEMENT FOR THE PANEL BOARDS WHEREVER PHYSICALLY POSSIBLE.PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE TYPE WRITTENPANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT.
H. ALL CONDUIT RUNS INDICATED ARE DIAGRAMMATIC, COORDINATE ROUTING IN ALL SPACES WITH OTHER TRADES.
I. CONDUCTOR CROSS HATCHING IS INDICATED TO CLARIFY BRANCH CIRCUIT AND/OR SWITCHING ARRANGEMENTS.
J. ALL PANELBOARDS INDICATED ARE HOUSED IN A SINGLE WIDTH ENCLOSURE, UNO. THE CONTRACTOR SHALL FIELD VERIFY ROOM LAYOUT AND ADJUST ACCORDINGLY, AT NO COST TO THE OWNER, IF PROVIDING ANY ADDTIONAL PANELBOARD ENCLOSURES.
K. WHERE POWER AND COMMUNICATION OUTLETS ARE INDICATED IN CLOSE PROXIMITY ON THE DRAWINGS, FIELDCOORDINATE THE LOCATIONS TO PLACE THE OUTLETS ADJACENT TO EACH OTHER.
L. ALL EXTERIOR RECEPTACLES SHALL BE LABELED "WR" - WEATHER RESISTANT.
M. PROVIDE MARKINGS ON CONCRETE SLAB FLOORS IN FRONT OF ELECTRICAL EQUIPMENT PER CPSM 6.16.14
SYMBOL DESCRIPTION
ifdeqfkd=ibdbka
LIGHT SWITCH, RATED 120/277 VOLTS, 20-AMPS, MOUNT AT +3'-10"AFF. SUBSCRIPT/SUPERSCRIPT LETTERS,NUMBERS, AND SYMBOLS INDICATES SWITCH TYPE AS FOLLOWS:
3 INDICATES 3-WAY LIGHT SWITCH4 INDICATES 4-WAY LIGHT SWITCHD INDICATES DIMMER SWITCH.P INDICATES PILOT LIGHT, ON WHEN SWITCH IS ONK INDICATES KEY OPERATED LIGHT SWITCHOS INDICATES SWITCH WITH INTEGRAL OCCUPANCY SENSOROS INDICATES DUAL RELAY INTEGRAL OCCUPANCY SENSOR, WIRED FOR MULTI-LEVEL
SWITCHING
LOWER CASE LETTER INDICATES LIGHT FIXTURE CONTROL DESIGNATION
INDICATES SWITCHES WIRED FOR INBOARD/OUTBOARD SWITCHING.
OMNI-DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, CEILING MOUNT.
FLUORESCENT LIGHT FIXTURE, CEILING MOUNT.
FLUORESCENT LIGHT FIXTURE ON EMERGENCY POWER, CEILING MOUNT. FIXTURE SHALL NOT BECONTROLLED AND BE ILLUMINATED AT ALL TIMES UNO.
LIGHTING FIXTURE.
LIGHT FIXTURE ON EMERGENCY POWER, CEILING MOUNT. FIXTURE SHALL NOT BE CONTROLLED AND BEILLUMINATED AT ALL TIMES UNO.
LIGHT FIXTURE, WALL MOUNT, HEIGHT AS INDICATED.
EMERGENCY EGRESS LIGHTING FIXTURE, WITH BATTERY PACK, WALL MOUNT AT +8'-0"AFF.
EXIT SIGN, CEILING MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.
EXIT SIGN, WALL MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.
LIGHT FIXTURE, POLE MOUNT.
2
SYMBOL DESCRIPTION
mltbo=ibdbka
APPLIANCE RECEPTACLE, MOUNT AT +1'-6" AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOREQUIPMENT SERVED.
APPLIANCE RECEPTACLE, MOUNT AT +1'-6"AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOREQUIPMENT SERVED. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDERED DEVICE.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER, PROVIDERED DEVICE.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDERED DEVICE.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. PROVIDE NEMA 3R "WHILE IN USE"ENCLOSURE.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER,PROVIDE RED DEVICE.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER,PROVIDE RED DEVICE.
QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.
QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER,PROVIDE RED DEVICE.
QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.
QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER,PROVIDE RED DEVICE.
CORD REEL OUTLET, CEILING MOUNT. REFER TO DETAIL ON DRAWING E4.1
JUNCTION BOX, CONCEALED ABOVE CEILING, UNO.
ENCLOSED CIRCUIT BREAKER, CHARACTERISTICS AS INDICATED.
MUSHROOM SWITCH, HEAVY DUTY WITH LEGEND PLATE. MOUNT W/HANDLE AT +3'-10" AFF, UNO.
MANUAL MOTOR STARTER, OVERLOAD PROTECTION AS REQUIRED PER NAME PLATE RATINGS, WITH 'ON'INDICATOR PILOT LIGHT. FLUSH MOUNT W/HANDLE AT +3'-10"AFF, UNO.
DISCONNECT SWITCH, FUSIBLE OR NON-FUSIBLE AS INDICATED. MOUNT W/HANDLE AT +4'-6"AFF, UNO.
MAGNETIC MOTOR STARTER, WITH OVERLOAD RELAYS AS REQUIRED TO SERVE MANUFACTURERREQUIREMENTS OF EQUIPMENT SERVED. PROVIDE WITH HAND-OFF-AUTOMATIC SELECTOR SWITCH ANDINDICATOR LIGHTS.. MOUNT W/HANDLE AT +4'-6"AFF, UNO.
COMBINATION MAGNETIC STARTER AND DISCONNECT SWITCH. WITH OVERLOAD ELEMENTS AND FUSINGAS REQUIRED TO SERVE MANUFACTURER REQUIREMENTS OF EQUIPMENT SERVED. PROVIDE WITH HAND-OFF-AUTOMATIC SELECTOR SWITCH AND INDICATOR LIGHTS.. MOUNT W/HANDLE AT +4'-6"AFF, UNO.
EQUIPMENT POWER CONNECTION.
MOTOR CONNECTION.
POWER FOR ELECTRIC DOOR LOCK CONNECTION. REFER TO DETAIL ON DRAWING E4.1
EMERGENCY GENERATOR.
BRANCH CIRCUIT RUN CONCEALED, UNO. DASHED INDICATES CIRCUITRY REQUIRED TO BE RUN BELOWSLAB.
STRAIGHT LINEWORK FOR CIRCUITRY INDICATES ON EMERGENCY POWER CIRCUIT. INDICATED FORCLARITY ONLY, ACTUAL HOMERUN DESIGNATION OVERRIDES THIS SYMBOLOGY.
BRANCH CIRCUIT HOME RUN TO PANELBOARD AND CIRCUIT INDICATED.
PANELBOARD.
TRANSFORMER, PROVIDE CONCRETE HOUSEKEEPING PAD UNLESS NOTED OTHERWISE.
RELAY, N/O OR N/C AS INDICATED.
RELAY, NORMALLY OPEN.
RELAY, NORMALLY CLOSED.
J
CB
E
EL
G
T
R
FEEDER TAG. REFER TO FEEDER SCHEDULE ON DWG E5.1.XXX
CLG
INDICATES PARTITION IS A FIRE BARRIER. APPLY FIRE STOP FOR ALL PENETRATION
POWER FOR EMERGENCY PHONE. PROVIDE RECESSED BOX ADJACENT TO COMMUNICATION OUTLET.BL
POWER FOR VIDEO PROJECTION. PROVIDE CEILING MOUNTED OUTLET AS DIECTED BY THE OWNER.VP
SYMBOL DESCRIPTION
lkb=ifkb=af^do^j=ibdbka
CIRCUIT BREAKER
FUSED SWITCH
TRANSFORMER
TRANSFER SWITCH
FEEDER DESIGNATIONXXX
CURRENT TRANSFORMERCT
PT POTENTIAL TRANSFORMER
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWMT=mj
ibdbkapI
^__obsf^qflkp
^ka=dbkbo^i
klqbp
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bMKN
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
^__obsf^qflkp
1P SINGLE PHASE
3P THREE PHASE
A AMPS
ABI ADDITIVE BID ITEM (REFER TO BID FORM)
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
ATS AUTOMATIC TRANSFER SWITCH
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BKR BREAKER
BOCT BOTTOM OF CABLE TRAY
C CONDUIT
CATV COMMUNITY ANTENNA TELEVISION (CABLE)
CB CIRCUIT BREAKER
CBL CABLE
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CLR CLEAR
CO. COMPANY
COMB COMBINATION
COMM COMMUNICATIONS
CU COPPER
DIA DIAMETER
DISC DISCONNECT
DIV DIVISION
DWG DRAWING
EBH ELECTRIC BASEBOARD HEATER
EC EMPTY CONDUIT
ECS EMERGENCY COMMUNICATIONS STATION
ELEC ELECTRICAL
ELEV ELEVATOR
EQ EQUIPMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EX EXISTING
EXT EXTERIOR
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FAGP FIRE ALARM GRAPHIC PANEL
FAXP FIRE ALARM EXTENDER PANEL
FFSCP FIRE FIGHTER'S SMOKE CONTROL PANEL
FLA FULL LOAD AMPS
FPMR FUSE PER MANUFACTURERS REQUIREMENTS/RECOMMENDATIONS
FPND FUSE PER NAMEPLATE DATA
G GROUND
GE GROUND FAULT PROTECTION FOR EQUIPMENT, 6-50mA PER NEC 427.22 (PROVIDEACCESSORY FOR INDICATED BREAKER)
GFCI GROUND FAULT CIRCUIT INTERRUPT
GFP GROUND FAULT PROTECTION FOR PERSONNEL, 4-6mA (PROVIDE ACCESSORY FORINDICATED BREAKER)
HC HORIZONTAL CROSS CONNECT
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
Hz HERTZ
IAW IN ACCORDANCE WITH
IC INTERMEDIATE CROSS-CONNECT
IG ISOLATED GROUND
J-BOX JUNCTION BOX
KHFSS KITCHEN HOOD FIRE SUPPRESSION SYSTEM
KHz KILOHERTZ
KVA KILOVOLT AMPS
KW KILOWATTS
KWH KILOWATT HOURS
L LOCKOUT TO PREVENT UNAUTHORIZED SWITCHING (PROVIDE ACCESSORY FORINDICATED BREAKER)
LC ROUTE CIRCUIT TO LOAD VIA LIGHTING CONTACTOR, REFER TO LC SCHEDULE
LED LIGHT EMITTING DIODE
LTG LIGHTING
LTS LIGHTS
MAX MAXIMUM
MC MAIN CROSS CONNECT
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MH METAL HALIDE
MHz MEGAHERTZ
MIN MINIMUM
ML MAINTENANCE LOCK (PROVIDE ACCESSORY FOR INDICATED BREAKER)
MLO MAIN LUG ONLY
MNS MASS NOTIFICATION SYSTEM
MOCP MAXIMUM OVER CURRENT PROTECTION.
MTD MOUNTED
N NEUTRAL
N/C NORMALLY CLOSED
N/O NORMALLY OPEN
NO. NUMBER
PBD PANELBOARD
PD PROTECTIVE DEVICE
RCPT RECEPTACLE
REC RECEPTACLE
SCP SECURITY CONTROL PANEL
SEC SECURITY
SPD SURGE PROTECTIVE DEVICE
SPEC. SPECIFICATION(S)
ST SHUNT TRIP, 120V COIL (PROVIDE ACCESSORY FOR INDICATED BREAKER)
SW SWITCH
SWBD SWITCHBOARD
TBB TELECOMMUNICATIONS BONDING BACKBONE
TC TELECOMMUNICATIONS CLOSET
TELECOM TELECOMMUNICATIONS
TGB TELECOMMUNICATIONS GROUNDING BUS BAR
TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR
TYP TYPICAL
UNO UNLESS NOTED (INDICATED) OTHERWISE
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W WATTS
W/ WITH
XFER TRANSFER
XFMR TRANSFORMER
ifdeq=cfuqrob=p`ebarib
TYPE DESCRIPTION CATALOG NUMBER
LAMPQUANTITY WATTAGE
LAMPTYPE VOLTAGE MOUNTING REMARKS
A1 2X4 RECESSED INDIRECT 2RTL424EN
LEPC24
1 49 LED 277 V RECESSED 4800 LUMENS MIN
A2 2X4 INDIRECT - STEP DIM 2RTL424EN
LEPC24
1 49 LED 277 V RECESSED BI LEVEL DIMMING, 4800 LUMENS MIN
B2 2X2 INDIRECT - STEP DIM 2RTL222EN
LEPC22
1 24 LED 277 V RECESSED BI LEVEL DIMMING, 2400 LUMENS MIN
C1 2X4 TROFFER 2TL4GRLEDLJT24
1 75 LED 277 V RECESSED 4600 LUMENS MIN
D1 2X2 TROFFER 2GTL2GRLEDLJT22
1 37 LED 277 V RECESSED 3000 LUMENS MIN
E1 UTILITY FIXTURE STL4RZNNL3DCLLED
1 48 LED 277 V PENDANT 4800 LUMENS MIN, 12' MH IN SHOPS, 10'MHELSEWHERE
F1 DAMP LOCATION WL4S1232LCL
1 39 LED 277 V SURFACE 4000 LUMENS MIN
G1 8" DOWNLIGHT EVO35-29LED8-DLM30LF8LED8G4
1 39 LED 277 V RECESSED 3700 LUMENS MIN, DIMMING
X1 SINGLE FACE EXIT FIXTURE LESLPDC
SE
1 10 LED 277 V UNIVERSAL
X2 DOUBLE FACE EXIT FIXTURE LESLPDC
SE
1 10 LED 277 V UNIVERSAL
Y1 WALL MTD SITE FIXTURE WST LEDIST1
LNC2-12LU
1 39 LED 277 V WALL INTERGAL PHOTOCELL, 1600 LUMENS MIN
Z1 POLE MTD SITE FIXTURE KAD-LEDGLEON
CL1-A-60LU
1 109 LED 277 V 4"X25' SQ POLE TYPE 3 DIST., INTERGAL PHOTOCELL, 8000LUMENS MIN
`lab=obcbobkb`bp
a) CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL: CPSM, 2014, REV 0 – 10/15/14b) NATIONAL ELECTRIC CODE/ NPFA 70: NEC, 2011c) VIRGINIA UNIFORM STATEWIDE BUILDING CODE: VUSBC, 2012 (INCLUDING VECC)d) AMERICANS WITH DISABILITIES ACT: ASAD, SEPTEMBER 15, 2010e) NATIONAL FIRE ALARM CODE/ NFPA 72, 2007
REVISIONS
DATE DESCRIPTION
CR
CR
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1 Z1
Z1 Z1
Z1
Z1
Z1
Z1
ELECTRICAL PRIMARY DUCTBANK.REFER TO CIVIL PLAN FORCONTINUATION AND TO POWERPLAN FOR DETAILS
APPROXIMATE LOCATION OFELECTRICAL ROOMS
APPROXIMATE LOCATIONOF MDF ROOM
ELECTRICAL SERVICESECONDARY. REFER TO POWERPLAN FOR ADDITIONAL DETAIL
REFER TO CIVIL PLANSFOR DEMOLITION OFLIGHTING IN THIS AREA.
Z1
Z1
Z1
Z1
Z1
H1B-7
H1B-7
H1B-7
H1B-7
H1B-7
GENERATOR DUCTBANK.REFER TO POWER PLAN FORADDITIONAL DETAIL
1
1
1
1
H1B-7
H1B-7
H1B-7
H1B-7
H1B-7
H1B-7
H1B-7
H1B-7 H1B-7
H1B-7 H1B-7
H1B-7
H1B-7
H1B-7
H1B-7
2' -
0"
DIA.
2' - 0"
7' -
6"
3'-6".
3 #3 TIES.
(6) #6 (VERT.) WITH #3 TIES @ 12" O.C.
4000 PSI AIR ENTRAINED CONCRETE (TYP.)
TOP OF CONDUIT MINIMUM 24" BELOWFINISHED GRADE
MIN. 3" CLR.(TYP ALLSIDES)
GALVANIZED ANCHOR BOLTS (BY POLE MFG.)
FINISHED GRADE
3 #3 TIES.ROUND PEDESTAL WITH 1" CHAMFEREDCORNERS
ANCHOR BOLT BASE COVER (BY POLE MFG.)
HAND HOLE W/COVER PLATE ANDSTAINLESS STEELSCREWS
LIGHT POLE
ANCHOR BOLT COVER
REBAR
HAND HOLE
HOT DIPPED GALVANIZEDANCHOR BOLTS
GALVANIZED NUTS
MIN 1" PVC CONDUIT
3".
PROVIDE GROUT BED W/DRAINAGE UNDER BASEPLATE
3".
3".
3".
REPRESENTED BY n
APPLIES TO DRAWINGS E1.0
hbvklqbp
1. PROVIDE #6 WIRE IN 1-1/4" PVC FOR SITE LIGHTING.
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWMV=mj
pfqb=mi^k=J
bib`qof`^i
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bNKM
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
k
1" = 20'-0"
pfqb=mi^k=J=bib`qof`^i
0' 20'10' 40'
1" = 20'-0"
NO SCALE
mlib=_^pb=abq^fi
REVISIONS
DATE DESCRIPTION
2 OS
2 OS
2O
S 2 OS
2 OS
2O
S
2 OS
2 OS
2 OS
2 OS
2OS
2OS
2OS
2 OS
2OS
2 OS
2OS
2OS
2OS
2 OS
2 OS
2 OS
2OS
2OS
OS OS
OS OS OS OS
OS3
3
3
D
2OS
2OS
3
3
3
3D
33
33
33
33
3
2 OS
2 OS
2 OS
2 OS
2 OS
4
UPUP3
3 3
3
3
3
3
3
3
3
3
OSOS
OS
2OS
2 OS
2OS
2OS
3
3
3
3
3
123
124
122
126 131 133
141
127 130 134
128
129
121
120
119
118 117 116115
114
136
135
137
139
140
145
146
110
142 144
112 111
113101
107
138
125132
103
102
105109 106108
143
A2A2
A2
A2 A2
A2
A2A2
A2 A2
A2A2
A2
A2
A2
A2 A2
A2 A2
A2A2
A2
A2A2A2
G1G1G1
G1G1G1
G1
G1
G1
G1
A2 A2A1
A2A2 A2 A2
A2A2A2 A2
D1
D1
D1
D1
D1
D1 D1 D1 D1
D1
D1
D1
D1
A2 A2
A2 A2
A2A2
A2 A2
A2 A2
A2 A2
A2 A2 A2 A2 A2
A2 A2
A2A2
A2 A2
A2
HX1B-5 HX1B-5
A2
HX1B-5
A2
A2
HX1B-5
D1D1 D1 D1 D1 D1 D1
A2
A2
A2
A2
A2
A2
A1
B2
D1D1 E1E1 E1E1E1E1 E1 E1E1 E1E1
F1 F1
C1
C1
C1
D1
D1
D1
D1
A1 A1 A1 A1
A1 A1 A1 A1
A1 A1 A1 A1
A1 A1 A1 A1
G1 G1G1G1G1
C1
Y1
Y1 Y1 Y1 Y1Y1
Y1Y1
HX1B-4HX1B-4
HX1B-4
HX1B-4 HX1B-4
HX1B-4
HX1B-4HX1B-4
HX1B-4 HX1B-4
HX1B-4HX1B-4
HX1B-4
HX1B-4
HX1B-4
HX1B-4 HX1B-4
HX1B-4 HX1B-4
HX1B-4
HX1B-4
HX1B-4
HX1B-4 HX1B-4HX1B-4
HX1B-4HX1B-4 HX1B-4 HX1B-4
HX1B-4HX1B-4HX1B-4 HX1B-4
HX1B-2
HX1B-2
HX1B-2
HX1B-2
HX1B-2
HX1B-2 HX1B-2HX1B-2 HX1B-2
HX1B-2
HX1B-2
HX1B-2
HX1B-2
HX1B-4 HX1B-4
HX1B-4 HX1B-4
HX1B-4HX1B-4
HX1B-4 HX1B-4
HX1B-5 HX1B-5
HX1B-5 HX1B-5
HX1B-4 HX1B-4 HX1B-4 HX1B-5 HX1B-5
HX1B-5 HX1B-5
HX1B-5HX1B-5
HX1B-5 HX1B-5
HX1B-5 HX1B-5 HX1B-5
HX1B-5
HX1B-2H1B-1 H1B-1 H1B-1 HX1B-2 H1B-1 H1B-1
HX1B-5
HX1B-5
HX1B-5
HX1B-5
HX1B-5
HX1B-5
HX1B-5
HX1B-5
HX1B-5HX1B-5
HX1B-5HX1B-5 H1B-1H1B-1H1B-1H1B-1 H1B-1 H1B-1H1B-1 H1B-1H1B-1
H1B-1 H1B-1
H1B-1
H1B-1
H1B-1
HX1B-1
H1B-1
HX1B-1
HX1B-1
H1B-1 H1B-1 HX1B-2 H1B-1
H1B-1 H1B-1 H1B-1 H1B-1
H1B-1 H1B-1 H1B-1 H1B-1
HX1B-2 H1B-1 H1B-1 HX1B-2
H1B-1 H1B-1H1B-1H1B-1H1B-1
HX1B-3 HX1B-3 HX1B-3 HX1B-3HX1B-3
HX1B-3HX1B-3HX1B-3
A2 A2 A2A2E1HX1B-2
E1HX1B-2
HX1B-2HX1B-2
X1
X1
X1
X1
X1X1 X1
X1
X1
X1
X1
X1
HX1B-4
HX1B-4
HX1B-2
X2
HX1B-2X1
Y1 HX1B-3Y1 HX1B-3 Y1 HX1B-3
PA
RT
A
PA
RT
B
1
HX1B-4
HX1B-2
HX1B-2
HX1B-2
HX1B-2 X1
HX1B-2
HX1B-2D1
C1
C1
C1
HX1B-2
D1
HX1B-1
HX1B-2
HX1B-2
H1B-1
HX1B-2
Y1 HX1B-3
G1
H1B-1 X1X1
Y1 Y1HX1B-3
HX1B-1
HX1B-1
HX1B-2
Y1 HX1B-3
HX1B-2
HX1B-3Y1 Y1 HX1B-3
X1HX1B-2
REPRESENTED BY n
APPLIES TO DRAWINGS E2.1.1
hbvklqbp
1. ALL LIGHTING FIXTURES IN THIS SPACE SHALL BE CONNECTED TO THE DENOTEDCIRCUIT UNO..
2. FIELD ADJUST LIGHTING FIXTURES IN THIS SPACE AS REQUIRED TO COORDINATEWITH OTHER TRADES. MAINTAIN A IN OF 24" FROM THE RADIANT HEATING IN THISSPACE..
3. LIGHTING IN THIS SPACE SHALL NOT BE AUTOMATICALLY CONTROLLED DUE TO RISKOF INJURY POSED BY UNEXPECTED LOSE OF ILLUMINATION..
4. DO NOT LOCATE ANY ELECTRICAL EQUIPMENT OR FIXTURES WITHIN 5' OF THEDOORS OF THE PAINT BOOTH.
150
156
147 148149
152154
153
159
157
161
162
151
158
160
D1
D1
D1
D1
D1 D1 D1 D1
A2
A2
A2
A2
A2
A1 A2
A2
E1E1 E1 E1 E1
E1 E1
E1 E1
E1 E1
A2A2A1
A2A2 A2
C1C1C1
C1C1C1
E1 E1 E1 E1
E1 E1 E1 E1
E1E1 E1 E1 E1
E1
E1 E1 E1 E1
E1E1 E1 E1 E1
E1E1 E1 E1 E1
E1
E1
E1
E1
E1E1 E1 E1 E1
E1E1 E1 E1 E1
E1
E1E1 E1
E1E1 E1
E1E1 E1
E1 E1 E1
E1 E1 E1
E1 E1 E1
E1 E1 E1
E1E1
E1E1
E1E1
E1E1
E1
E1
E1
C1 C1
C1
Y1Y1 Y1 Y1 Y1 Y1Y1
Y1 Y1 Y1
Y1
Y1 Y1
HX1B-1
H1B-1
HX1B-1
HX1B-1
H1B-1 H1B-1 HX1B-1H1B-1
H1B-5
H1B-5
H1B-5
H1B-5
H1B-5
HX1B-1 H1B-5
H1B-5
H1B-5HX1B-1 HX1B-1 H1B-5 HX1B-1
H1B-5 H1B-5
H1B-5 H1B-5
H1B-5 HX1B-1
H1B-5H1B-5HX1B-1
H1B-5H1B-5 H1B-5
H1B-5H1B-5H1B-5
H1B-5HX1B-1H1B-5
H1B-5 H1B-5 HX1B-1 H1B-5
H1B-5 H1B-5 H1B-5
H1B-5
H1B-3H1B-3 H1B-3 H1B-3 H1B-3
H1B-3
H1B-3 HX1B-1 H1B-3 H1B-3
H1B-3H1B-3 H1B-3 H1B-3 H1B-3
HX1B-1H1B-3 H1B-3 H1B-3 HX1B-1
H1B-3
H1B-3
H1B-3
H1B-3
HX1B-1H1B-3 H1B-3 H1B-3 HX1B-1
H1B-3H1B-3 H1B-3 H1B-3 H1B-3
H1B-3
H1B-3H1B-3 HX1B-1
H1B-3HX1B-1 H1B-3
H1B-3H1B-3 HX1B-1
HX1B-1 H1B-3
HX1B-1
H1B-3 H1B-3
H1B-3
H1B-3 H1B-3
H1B-3
HX1B-1 H1B-3
HX1B-1
HX1B-1
HX1B-1HX1B-1H1B-3
HX1B-1
H1B-3
H1B-3
H1B-3
HX1B-3
HX1B-3 HX1B-3 HX1B-3HX1B-3 HX1B-3
HX1B-3HX1B-3 HX1B-3 HX1B-3 HX1B-3 HX1B-3HX1B-3
X1
X1
X1
X1
A2
H1B-5
HX1B-1HX1B-1
X1X1
HX1B-1
X1
X1 X1
X1
X1
Y1 HX1B-3
HX1B-2
E1
E1
E1
E1
H1B-3
H1B-3
H1B-3
H1B-3
Y1
Y1
Y1
HX1B-3
HX1B-3
HX1B-3
E1E1
H1B-5H1B-5
Y1 HX1B-3
E1 HX1B-1
X1X1
HX1B-1
HX1B-1
HX1B-2
HX1B-1
Y1
HX1B-3
X1
1
HX1B-1
Y1 HX1B-3
3
3
3
3
3
4
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWNO=mj
cillo=mi^kp=J
ifdeqfkd
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bOKNKN
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
k
1/8" = 1'-0"
cillo=mi^k=J=m^oq=^=J=ifdeqfkd
k
1/8" = 1'-0"
cillo=mi^k=J=m^oq=_=J=ifdeqfkd
REVISIONS
DATE DESCRIPTION
VP
E
E
E
E
EL
EL
BL
UPUP
CLG
CLG
CLG
CLG
CLG
CLG
CLG
E
E
EL
EL
BL
S
S
F
S
S
EE E
123
124
122
126 131
133
141
127
130134
128
129
121
120
119
118117
116 115114
136
135
137
139
140
145
146
110
142 144
112 111
113101
107
138
125
132
103
102
105
109
106
108
E2.1.2
2
E2.1.2
1
E2.1.2
4
HM1B
ELECTRICAL PRIMARYDUCTBANK. REFER TO CIVILPLAN FOR CONTINUATION
5' - 0"
5' -
0"
5' - 0"
5' -
0"
5' - 0"
GEN2 GEN1
L1C-3
L1C-3
L1C-3
L1C-33 L1C-33
L1C-29 L1C-29
L1C-1
L1C-5
L1C-5
L1C-9
L1C-9
L1C-17 L1C-17 L1C-21
L1C-14
L1C-18
L1C-18
L1C-37
L1C-39
L1C-22 L1C-22 L1C-26
L1C-32
L1C-32
L1C-35
L1C-31L1C-3
L1C-7
L1C-7
L1C-11
L1C-11
L1C-19 L1C-23
L1B-7
L1C-34
L1C-16
L1C-20
L1C-20
L1C-28L1C-24L1C-24
L1C-39
L1C-35
L1C-31
L1C-39
L1C-34
L1C-3
L1C-7
L1C-7
L1C-7
L1C-7
L1C-11
L1C-11
L1C-11
L1C-11L1C-15
L1C-15 L1C-15
L1C-15 L1C-19
L1C-19
L1C-19
L1C-23
L1B-1
L1C-16L1C-16
L1C-20
L1C-20
L1C-38
L1C-25
L1C-25
L1C-25L1C-25
L1C-27
L1C-2L1C-27
L1C-27
L1C-39L1C-37
L1C-35
L1C-35
L1C-35
L1C-31
L1C-31
L1C-30L1C-30
L1C-30
L1B-33
L1B-33
L1B-2L1B-2L1C-38L1C-38
L1C-38
L1C-41L1C-25
L1B-21 L1B-23
L1C-4L1C-4
L1C-26
L1C-28L1C-24 L1C-28
L1C-28L1C-28L1C-24
L1C-24
L1C-30
L1B-10
L1B-6L1B-6L1B-6L1B-6
L1B-4
L1B-47
L1B-3
L1B-1 L1B-3
L1B-5 L1B-9
L1C-34
L1C-34
L1C-34
L1C-34
L1C-24
L1B-11
L1C-39
L1C-20
L1C-20
L1B-21
L1B-21
L1B-21L1B-23
L1B-23
L1B-23
L1B-35
L1B-19
L1B-19
L1B-4
L1C-41
L1C-41
L1C-41
L1B-33
L1B-13
L1B-13
L1B-13L1B-13
L1B-15
L1B-2
L1C-1
L1C-3
L1C-13L1C-15
L1C-23
L1C-13L1C-15 L1C-19
L1C-19
L1C-38
L1C-38
L1C-35
L1C-39
L1C-6 L1C-8
L1C-10
L1C-12
L1C-10L1C-12
143
L1C-28
L1C-30
L1C-30
L1C-30
L1B-4
L1B-13
L1B-17
104
L1B-2
L1B-25
L1B-27
L1B-31
L1B-29
PA
RT
A
PA
RT
B
L1B-12
5
E2.1.2
PROVIDE SINGLEGENERATOR UNDER BASEBID REFER TO ONE LINEDIAGRAM FOR SIZE
E2.1.3
1
LE1A-9
LE1A-9LE1A-11
ROUTE THE GENERATORDUCTBANK UNDER THESERVICE PRIMARY
150
156
148 149 152 154
153
159
157
161162
151
158
160
UTILITY XFMR
E2.1.2
3
L1BH1B
3
10' -
0"
3' - 0"3' - 0"
L1B-37 L1B-37
L1B-49L1B-39
L1B-41 L1B-53
L1B-55
L1B-49
L1B-51
L1B-51L1B-41
L1B-53L1B-35 L1B-41 L1B-41
L1B-53
L1B-26L1B-26
L1B-26L1B-26
L1B-24 L1B-24
L1B-33
L1B-33
L1B-33 L1B-33
L1B-30L1B-28
L1B-28
L1B-16
L1B-16
L1B-10
L1B-43L1B-16
L1A-1
L1A-29
L1A-31
L1A-31
L1A-33
L1A-35
L1A-35 L1A-33
L1A-33
L1B-6 L1B-8 L1B-8
L1B-8L1B-8L1B-4L1B-4
L1B-35
L1B-35
L1B-35
L1A-29
L1A-31
L1B-33
HM1B-3
L1B-39
L1A-19
L1A-35L1B-45
HM1B-1
L1B-8
DOOR OPERATOR
L1B-12
L1B-14
L1B-14
L1B-24 L1B-24 L1B-24
L1B-18
L1B-20
L1B-22
L1B-53
L1B-55
L1B-53
L1B-53
L1B-28 L1B-28
L1B-30
L1A-1
L1A-3
L1A-5
L1A-2,4,6
30
L1A-8,10,12
L1A-14,16,18
30
L1A-20,22,24
30 L1A-29
L1A-7
L1A-9
L1A-7
L1A-9
L1A-13
L1A-15
L1A-17
L1A-11
L1A-21L1A-23L1A-26,28,30 L1A-25L1A-27L1A-27
L1A-1
DOOR OPERATOR
L1A-39
L1A-39
L1A-39
L1A-39L1A-37
L1A-37
L1A-37
L1A-37
HM1B-5
DOOR OPERATOR
HM1B-7
DOOR OPERATOR
HM1B-9
DOOR OPERATOR
6
E2.1.2
7
E2.1.2
HX1B
33
FAN SUPPLIEDWITH UNIT.FIELD VERIFYELECTRICALREQUIREMENTSBEFOREROUGH-IN
L1B-32
L1B-34
LIGHTS
LIGHTS
3
ELECTRICAL SERVICESECONDARY. REFER TO SITE PLANFOR ROUTING
GENERATOR DUCTBANK.REFER TO SITE PLAN FORROUTING
GROUND EACH PAINTBOOTH ENCLOSURE VIA ANINDIVIDUAL BARE #4 AWG
LE1A-7
LE1A-9
LE1A-9
L1B-46
H1B-15,17,19
H1B-9,11,13
4
REPRESENTED BY n
APPLIES TO DRAWINGS E2.1.2
hbvklqbp
1. PROVIDE 4'X8'X3/4" FIRE RESISTANT PLYWOOD MOUNTED WITH LONG DIMENSION MOUNTEDVERTICALLY ON WALLS AS INDICATED..
2. PROVIDE NEMA 208V/1 PH OUTLET MOUNTED TO THE BACK OF EACH RACK. COORDINATEOUTLET CONFIGURATION WITH THE OWNER PRIOR TO INSTALLATION. DROP POWERCIRCUITRY FROM STRUCTURE ABOVE TO OUTLET VIA EMT CONDUIT. PROVIDE CONDUITSUPPORT AS REQUIRED BY CODE. ALL CONDUCTORS SHALL BE DEDICATED #10 IN 3/4"C TOPANEL..
3. MOUNTED DENOTED PANEL ON THE STUCTURAL WALL AT THIS LOCATION. PROVIDE AMINIMUM OF FOUR 1" EMPTY CONDUIT WITH PULL STRINGS FROM THE PANEL STUBBED TOTHE ACCESSIBLE CEILING. ONCE CONDUIT AND CIRCUITS ARE INSTALLED, INSTALL PARTITIONWALL AS INDICATED ON THE ARCHITECTURAL PLANS AND A RECESSED PANEL COVER..
4. DO NOT LOCATE ANY ELECTRICAL EQUIPMENT OR FIXTURES WITHIN 5' OF THE DOORS OFTHE PAINT BOOTH.
1
SPECIALELECTRONICS
132
FACPL1C-40
L1C-42
SCP
TGB
L1C
ELECTRICAL
125
LABEL AS "LE1C"UNDER ADDITIVEBID OPTION #1
MAIN
MDS
ATS-EATS-XATS-X
HE1A
TE1A
LE1A
CT
MECHANICALROOM
157
ELECTRICAL
160
DIST
L1AL1A-35
L1A-35
L1A-35
T1A
SPACE FORMECHANICAL PIPING
SPACE FORMECHANICAL PIPING
LM1A
TM1A
METER
SPD
1
2
MDF
109
LEMDF-3
LEMDF-1 LEMDF-3
LEMDF-1
L1B-2
LEMDF-2,4
LEMDF-6,8
LEMDF-10,12
30
30
30
LEMDF1
FINISHED GRADE
6"
1'-6"
5"
5"
5" 7" 5"
#3 TIES, @ 18" O.C.
6" SCH 40 PVC CONDUIT(TYP OF 2)
#4 BARS, MIN18" OVERLAP
PROVIDE 3000 PSI CONCRETE UNDER HARDSCAPE, OTHERWISEVDOT #10 SCREENINGS OR APPROVED ENGINEERED FILL.PROVIDE CONDUIT SPACERS EVERY 6'-0"
UNDERGROUND WARNING TAPE
FINISHED GRADE
6"
1'-6"
5"
7"
5" 7" 5"
#3 TIES, @ 18" O.C.
1" SCH 40 PVC CONDUIT(TYP OF 4) FOR POWERAND CONTROLS
#4 BARS, MIN18" OVERLAP
PROVIDE 3000 PSI CONCRETEPROVIDE CONDUIT SPACERS EVERY 6'-0"
UNDERGROUND WARNING TAPE
SCH 40 PVC CONDUIT(TYP OF 2). REFER TOONE LINE DIAGRAM FORSIZE
5"
UNDERGROUND WARNING TAPE
FINISHED GRADE
6"
1'-6"
7"
5"
5" 7" 5"
#3 TIES, @ 18" O.C.
4" SCH 40 PVC CONDUIT(TYP OF 4, TWO SPARE)
#4 BARS, MIN18" OVERLAP
PROVIDE 3000 PSI CONCRETEPROVIDE CONDUIT SPACERS EVERY 6'-0"
5"
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWNV=mj
cillo=mi^kp=J
mltbo
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bOKNKO
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
k
1/8" = 1'-0"
cillo=mi^k=J=m^oq=^=J=mltbo
k
1/8" = 1'-0"
cillo=mi^k=J=m^oq=_=J==mltbo
1/4" = 1'-0"E2.1.2 E2.1.2
bki^odba=mi^k=J=a^q^=olljN
1/4" = 1'-0"E2.1.2 E2.1.2
bki^odba=mi^k=J=bib`qof`^i=olljO
1/4" = 1'-0"E2.1.2 E2.1.2
bki^odba=mi^k=J=bib`qof`^i=olljpP
1/4" = 1'-0"E2.1.2 E2.1.2
bki^odba=mi^k=J=jac=ollj=J=mltboQ
NO SCALEE2.1.2 E2.1.2
bib`qof`^i=pbosf`b=mofj^ovR
NO SCALEE2.1.2 E2.1.2
dbkbo^qlo=ar`q_^khSNO SCALEE2.1.2 E2.1.2
bib`qof`^i=pbosf`b=pb`lka^ovT
REVISIONS
DATE DESCRIPTION
F
F FF
FF
SSS
S
S
SS
S
VP
SD
EL
CR EL
F
BL
SD
UPUP
F F
F
F
FFFF
F
S
S
S
S
S
S
S
S
S
SD SD
CR
EL
EL
BL
S
OFFICE
123
OFFICE
124
OFFICE
122
OFFICE
126
OFFICE
131
OFFICE
133 OFFICE
141
OFFICE
127
OFFICE
130
OFFICE
134
BREAK ROOM
128
CONFERENCEROOM
129
OFFICE
121
OFFICE
120
OFFICE
119
OFFICE
118OFFICE
117
OFFICE
116
OFFICE
115OFFICE
114
FILE ROOM
136
COPYSUPPLIES
135
OFFICE
137
OFFICE
139
OFFICE
140
OFFICE
145
OFFICE
146
BREAK ROOM
110
OFFICE
142
OFFICE
144
TOILET
112TOILET
111
CORRIDOR
113CORRIDOR
101
COMMONSAREA
107
OPEN OFFICEAREA
138
ELECTRICAL
125
SPECIALELECTRONICS
132
CUSTODIAL
104
WOMENSTOILET &SHOWER
103
MENS TOILET &SHOWER
102
RECYCLE
105MDF
109
CUSTODIALSUPPLIES
106
MECHANICALROOM
108
15
15 15
15 15
15
30
30
15 30
15
15
75
OFFICE
143
15
1530 15
15
30
15
30
15
E2.1.2
1
PA
RT
B
FAAP
E2.1.3
1
PA
RT
B
DPS
RX
DPS
RX
15
15 15
15
75
PAINT SHOP
150
MATERIALSSTORAGE
156
STORAGE
147
SUPERVISOROFFICE
148GENERALOFFICE
149
GENERALOFFICE
152
SUPERVISOROFFICE
154
CARPENTRYSHOP
153
CHEMICALSTORAGE
159
MECHANICALROOM
157
TOOLSTORAGE
161
TRUCK WASHBAY
162
STAGING
151
BLOODBOURNE
(HOUSEKEEPINGLINEN
STORAGE)
158
ELECTRICAL
160
15
15
30
110
75
75
75
30
75
30 1515
75
75
15
7575
FAAP
FIBER MANHOLE.REFER TO CIVILDRAWINGS
FIBER DUCTBANK.REFER TO CIVILDRAWINGS
FIBER DUCTBANK. PROVIDE 4-4"C AMIN OF 2' BELOW THE SLAB FORMFIBER MAHOLE TO MDF ROOM.
PA
RT
AP
AR
T A
DPS
RX
DPS
RX
15
30
15
GROUND EACH PAINTBOOTH ENCLOSURE VIA ANINDIVIDUAL BARE #4 AWG
2
FS
FS
TS
TS
PS
PS
FIELD VERIFY LOCATION
MDF
109
FIBER CONDUIT STUB-UP FROM MANHOLE
12"x4"BOCT: 10' - 0"
RACKS BY OWNER
STATION CABLINGCONDUIT STUB UP
TYP.
TMGB
REPRESENTED BY n
APPLIES TO DRAWINGS E2.1.3
hbvklqbp
1. PROVIDE ROOF PENETRATION WITH WEATHERHEAD PER THE DETAIL ON DRAWING E4.1 FORFUTURE RADIO BOOSTER SYSTEM..
2. DO NOT LOCATE ANY ELECTRICAL EQUIPMENT OR FIXTURES WITHIN 5' OF THE DOORS OFTHE PAINT BOOTH.
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWOM=mj
cillo=mi^kp=J
`ljjrkf`^qflkp
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bOKNKP
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
k
1/8" = 1'-0"
cillo=mi^k=J=m^oq=^=J=`ljjrkf`^qflkp
k
1/8" = 1'-0"
cillo=mi^k=J=m^oq=_=J=`ljjrkf`^qflkp
1/4" = 1'-0"E2.1.2 E2.1.3
bki^odba=mi^k=J=jac==ollj=J=`ljjN
1
REVISIONS
DATE DESCRIPTION
M
UPUP
M
123
124
122
126
131
133
141
127
130
134
128
129121
120
119
118
117 116 115 114
136
135
137
139
140 145
146
110
142
144
112 111
113 101
107
138
125132
103
102
147
105109106
108
AHU-1
AHU-2
CU-2CU-1
TU1-9
TU1-7TU1-6
TU1-2
FP1-4
TU1-8
TU1-4
TU1-3
TU1-1
FP1-3
FP1-5
FP1-2
FP1-1
TU1-5
xx . .
PA
RT
A
PA
RT
B
UH-5
F-12 F-13
DDCCONTROLPANEL
DSS-1A
DSS-1B
HM1B-38,40,42
HM1B-20,22,24HE1A-2,4,6
HM1B-11
HE1A-8HE1A-8
HE1A-8
HE1A-7
HE1A-8
HE1A-8
HE1A-8
HE1A-8
HE1A-7
HE1A-7
HE1A-7
HE1A-7
HE1A-8
? ? ?
L1B-40
L1C-36 L1C-36
LE1A-3,5
LE1A-3,5
F-1L1B-36
60 30
F-7
HE1A-1,3,5
HM1B-19,21,23
143
LE1A-2
L1B-48
150
156
147 148 149 152 154
153
159
157
161
162
151
158
160
B-1
DC-1
CU-3 CU-4
RH-2 RH-1
TU1-11
TU1-10
TU1-9
F-2
AC-1
UH-1UH-2
UH-3
DC-1ISOLATIONVALVE
CONTROLPANEL
MAINBAS
CONTROLPANEL
UH-4
HM1B-2,4,6
FOR DUST COLLECTION.REFER TO MECOORDINATIONSCHEDULE.
LE1A-1
?
?
? ?
?
F-11
LM1A-20WH2
AHU-3
AHU-4MAU-1
MAU-2
RH-4 RH-3
F-5 F-6 F-8
HM1B-26,28,30 HM1B-32,34,36
HM1B-11
HM1B-11
HM1B-11
LM1A-7
L1B-42,44
LM1A-15LM1A-16
LM1A-17LE1A-6
LM1A-18
HM1B-25,27,29
HM1B-31,33,35HM1B-8,10,12
HM1B-14,16,18
LM1A-9 LM1A-10 LM1A-11
RH-6RH-5
F-4LM1A-8
F-3L1B-38
LM1A-12F-9
LM1A-1LM1A-3LM1A-2 LM1A-4
LM1A-5 LM1A-6
30
3030
P-2
P-1
HE1A-10,12,14
HE1A-9,11,13
LM1A-14
LE1A-4
40
F-10LM1A-13
WH1LM1A-19
LE1A-8
1
.2. REFER TO PLUMBING /ELECTRICAL COORDINATION SCHEDULE ON DRAWING P0.1 FOR
ADDITIONAL REQUIREMENTS.
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWOP=mj
cillo=mi^kp=J
jb`e^kf`^i
mltbo
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bOKNKQ
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
k
1/8" = 1'-0"
cillo=mi^k=J=m^oq=^=J=jb`e^kf`^i=mltbo
k
1/8" = 1'-0"
cillo=mi^k=J=m^oq=_=J=jb`e^kf`^i=mltbo
REVISIONS
DATE DESCRIPTION
12" LARGER THAN GENERATOR FOOTPRINT
12"
LA
RG
ER
TH
AN
GE
NE
RA
TO
R F
OO
TP
RIN
T12".
CONCRETE PAD REQUIREMENTS
1. THE CONCRETE PAD IS TO BE FURNISHED BY THE CONTRACTOR.ADJUST REQUIREMENT INDICATED HEREIN TO MATCH GENERATORPROVIDER REQUIREMENTS..
2. MINIMUM PAD THICKNESS SHALL BE 12", WITH 3/8" REBAR ON 12"CENTERS, INSTALLED BOTH WAYS THROUGHOUT CONCRETE PAD..
3. CORNERS AND EDGES OF FOUNDATION ARE TO BE BEVELED..
4. THE ELEVATION OF THE PAD TOP SHALL BE APPROXIMATELY 8"ABOVE FINISHED GRADE..
5. THE PAD MUST BE LOCATED SUCH THAT THE MINIMUM CLEARANCEBETWEEN THE PAD AND STRUCTURES IS 3 ' ALONG THE SIDES ANDBACK AND 5' ALONG THE ENDS..
6. IF THE PAD IS LOCATED IN A TRAFFIC AREA, GUARD POSTS MUST BEFURNISHED AND INSTALLED AT THE CORNERS OF THE PAD..
7. REFER TO THE ONELINE DIAGRAM FOR SIZE AND QUANTITY OFSECONDARY CONDUITS..
8. BEFORE POURING CONCRETE, CONTRACTOR SHALL CONTACT THEEQUIPMENT PROVIDER FOR INSPECTION OF FORMS, CONDUITS &REINFORCEMENT..
9. TOP OF PAD SHALL HAVE A FINE BROOMED FINISH UPONCOMPLETION...
10. PROVIDED ANCHORS INTHE PAD AS REQUIRED BY THE EQUIPMENTPROVIDER
SLAB
FINISHED FLOOR
1" CONDUITUNLESS OTHERWISE INDICATED
FLOOR BOXWALL/PARTITION CAVITY
2.5" DEEP 2-GANG OUTLET BOXWITH SINGLE GANG PLASTER RING
WALL/PARTITION FACE
1" CONDUIT MINIMUMSIZE OR AS INDICATED
CONTINUE TO MDFROOM 109
FINISHED CEILING
DOUBLE LOCK NUT& LOCK WASHER
PROVIDE UNISTRUT SUPPORTSANCHORED TO STRUCTUREABOVE CEILING
FINISHED CEILING
DUPLEX OUTLET FLUSHMOUNTED TO CEILING,SUPPORTED BY STRUCTURE,PROVIDE SS COVER PLATE.
PLUG & CORD INTEGRALWITH CORD REEL UNIT
ADJUSTABLE BALL STOP
30' OF 14-3 SJO CORD
INTEGRAL CORD GRIP
(3) 15AGROUNDED PLUGS
MOUNT REEL BRACKETFLUSH WITH CEILING TOUNISTRUT SUPPORTABOVE CEILING.
CORD REEL EQUALTO LUMAPRO 4XP67
CLG
ROOF
3" RIGID STEEL CONDUITTHROUGH ROOF TO SUPPORTFUTURE ANTENNA MAST
FLASH AND SEAL ROOFPENETRATION IAW ROOFMANUFACTURER'SRECOMMENDATIONS
3" SERVICE ENTRANCEWEATHER HEAD FOR ANTENNALEAD-IN CABLE(CABLE BYOTHERS, NIC)
2' -
0"
RIGIDLY SUPPORT CONDUITFROM STRUCTURE
BUSHING
CIELING
VERIFY STRUCTURE AND ROOFCONSTRUCTION RGS CONDUIT ELBOW
PVC CONDUIT
EMT CONDUIT
SLAB
POROUS FILL
EARTH
PVC CONDUIT
EMT CONDUIT
SLAB
POROUS FILL
EARTH
RGS CONDUIT ELBOW
WALL
OS
2
OS
REFER TO PLANS FOR SWITCH TYPE
SINGLE GANG BOX
OCCUPANCY SWITCH
SINGLE GANG COVERPLATE
SINGLE GANG BOX
DUAL RELAYOCCUPANCY SWITCH
SINGLE GANG COVERPLATE
BALLAST #1 ORINPUT #1OF STEP DIMMINGBALLAST
BALLAST #2 ORINPUT #2OF STEP DIMMINGBALLAST
DOUBLE GANG BOX
(2) SWITCHES
DOUBLE GANG COVERPLATE
SINGLE GANG BOXSWITCH
SINGLE GANG COVERPLATE
LINE LOAD LINE
BALLAST #1 ORINPUT #1OF STEP DIMMINGBALLAST
BALLAST #2 ORINPUT #2OF STEP DIMMINGBALLAST
LINE LOAD LINE
REFER TO PLANS FOR SWITCH TYPE
TO PANELS, EQUIPMENT,TRANSFORMERS, ETC.
SWITCHBOARD "MDS"MAIN NEUTRAL BUS
EXOTHERMICCONNECTION
METALUNDERGROUNDWATER MAIN
BUILDING STEEL (IFPROPERLY GROUNDED)
METAL WATER MAINMIN. 10 FT CONTACTWITH EARTH.REMOVABLE
ATTACHMENT POINTMAX. 5' INSIDE OF BLDG.AND ON EACH SIDE OFMAIN WATER VALVE.
MINIMUM 1/2" DIAMETER MIN 20' LENGTH ELECTRICALLYCONDUCTIVE STEEL REBAR, OR, MIN 20' LENGTH #3AWG BAR COPPER CONDUCTOR: ENCASED BY MIN2" CONCRETE IN BUILDING FOUNDATION
CONCRETE ENCASEDELECTRODE
(1)#4/O, 1"C
#3/O BOND
SWITCHBOARD "MDS"MAIN GROUND BUS
(1)#4/O CU GRD1" PVC CONDUIT
(1)#4/O, 1"C
10'
MIN
(1)#4/O, 1"C,TYP.
PRIMARY BONDTO LIGHTNINGPROTECTIONSYSTEM
(3) GROUNDINGRODS
TMGB
TGB
#3/O
PROVIDE (1)#3/O GROUNDINGCONDUCTOR BETWEEN EACHTGB AND NEAREST STRUCTURALSTEEL AND COPPER WATER LINE,TYPICAL.
GEN ATS
DO NOT BONDGROUND ANDNEUTRAL INGENERATOR
PROVIDE #2 BARE TINNED COPPER LOOPDIRECT BURIED AROUND GENERATORPAD WITH (2) GROUND RODSEXOTHERMICALLY BONDED. CONNECTTO GENERATOR GROUNDING TERMINALWITH 2 SEPARATE #2 CONNECTIONS
#3/O
TGB
#4
150 132
109
NEUTRAL
LINE
NEUTRAL
HOT
POWERPACK
LOAD
SUBSTITUTE SWITCHING ARRANGEMENTINDICATED ON THE PLANS.
OUTPUTCOMMON24VDC
OCCUPANCY SENSOR
LOAD
277VLIGHTINGCCT
OS
DUAL RELAYOCCUPANCY SWITCH(PLAN SYMBOL: )
277V NORMAL LIGHTING(REFER TO PLANS FORQUANTITY)
STEP DIMMINGBALLAST
OUTPUT #1
OUTPUT #2
LINE
NEUTRAL
96".
108".
24". 18". 12". 24". 18".
PRIMARY SECONDARY
NO CONDUIT IN THIS AREA
10".
15".
FRONT
12".
CONCRETE PAD REQUIREMENTS FOR PAD MOUNTED TRANSFORMERS1. THE CONCRETE PAD IS TO BE FURNISHED BY THE CONTRACTOR. ADJUST REQUIREMENT INDICATED HEREIN TO MATCH POWER COMPANY REQUIREMENTS
2. MINIMUM PAD THICKNESS SHALL BE 12", WITH 3/8" REBAR ON 12" CENTERS, INSTALLED BOTH WAYS THROUGHOUT CONCRETE PAD.
3. CORNERS AND EDGES OF FOUNDATION ARE TO BE BEVELED.
4. THE ELEVATION OF THE PAD TOP SHALL BE APPROXIMATELY 4" ABOVE FINISHED GRADE.
5. THE PAD MUST BE LOCATED SUCH THAT THE MINIMUM CLEARANCE BETWEEN THE PAD AND STRUCTURES IS 3 ' ALONG THE SIDES AND BACK AND 10' ALONG THE FRONT.
6. IF THE PAD IS LOCATED IN A TRAFFIC AREA, GUARD POSTS MUST BE FURNISHED AND INSTALLED AT THE CORNERS OF THE PAD.
7. REFER TO THE ONELINE DIAGRAM FOR SIZE AND QUANITY OF SECONDARY CONDUITS (MAXIMUN NUMBER =10). ALL BACKFILL IN CONDUIT INSTALLATION AREAS SHALL BE COMPACTED BACK TO AT LEAST 95% TO REDUCE THE RISK OF SETTLING OR CRACKING OF THE PAD.
8. BEFORE POURING CONCRETE, CONTRACTOR SHALL CONTACT THE UTILITY FOR INSPECTION OF FORMS, CONDUITS & REINFORCMENT.
9. TOP OF PAD SHALL HAVE A FINE BROOMED FINISH UPON COMPLETION.
FIRE ALARMDIGITAL
ANNUNCIATORPANEL
FIRE ALARMCONTROL PANEL
(FACP)
2 PHONE LINES UDACT
BATTERYCHARGER
BATTERIES
120V
FIRE ALARMEXTENDERPANEL(FNAC)
NOTIFICATIONAPPLIANCECIRCUITMODULE
BATTERYCHARGER
BATTERIES
120V
EOL
PROVIDE QUANTITIES AS REQUIRED
paqpmpcpp e j ` c
EOL
DPS
EL
CR
EL CR
DPS
FLOOR
3/4"C TO SECURITY CLOSET 132 6'X6'X4" D BOX WITH COVER ON SECURE SIDE OF DOOR
COORDINATE WITH OTHERDIVISIONS TO INSURE THATDOOR FRAMES FOR DOORSWITH ELECTRIC LOCKS ANDPOSITION SWITCHES AREFACTORY FURNISHED WITHAPPROPRIATE HOLES TOALLOW CONDUITCONNECTIONS.
4"X4" FLUSH BOX W 3/4"CONDUIT.
ELECTRIC LOCK.
CIRCUITRY FISHED INDOOR & JAMB
120V INPUT,REFER TOPOWER PLANS
ACCESSIBLE CEILING
3/4" CONDUIT TO DEVICE
RX
RX
EL
1-1/8"
3-1/2"
1/4" THICK ELECTROTINPLATED COPPER BUSBAR
FIBERGLASSBUSHING
3 PAIR 7/16"DIA
15-1/2"
1"8 PAIR 5/16"DIA
5/8"
2"
1"
5/8"
20"
1-1/8" TYP
FIBERGLASSBUSHING
5/16" DIAM,TYPICAL
1/4" THICK ELECTROTINPLATED COPPER BUSBAR
3-1/2"
4"
7/16" DIA(3 PAIR)
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWOR=mj
bib`qof`^i
abq^fip
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bQKN
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
NO SCALE
dbkbo^qlo=m^a=abq^fi
NO SCALE
qbib`ljjrkf`^qflkp=lrqibq=`lkarfq=abq^fi
NO SCALE
`loa=obbi=^ppbj_iv=abq^fi
NO SCALE
tb^qeboeb^a=ollc=mbkbqo^qflk=abq^fi
NO SCALE
ms`=ql=bjq=qo^kpfqflk=abq^fi
NO SCALE
ifdeqfkd=`lkqoli=abq^fiN
NO SCALE
dolrkafkd=pvpqbj=af^do^j
NO SCALE
l``rm^k`v=pbkplo=af^do^j=abq^fi
NO SCALE
lccf`b=ifdeqfkd=^ka=mltbo=`lkqoli=af^do^j
NO SCALE
qo^kpclojbo=m^a=abq^fi
NO SCALE
cfob=^i^oj=ofpbo=af^do^jNO SCALE
cfob=pqlm=abq^fi
NO SCALE
pb`rofqv=bib`qolkf`p=`lkkb`qflk=abq^fi
NO SCALE
qbib`ljjrkf`^qflkp=dolrkafkd=_rp_^o=Eqd_F=abq^fiNO SCALE
qbib`ljjrkf`^qflkp=j^fk=dolrkafkd=_rp_^o=Eqjd_F=abq^fi
REVISIONS
DATE DESCRIPTION
NO SCALE
PARALLEL SPLICE DETAIL
LIGHTNING PROTECTION CONDUCTOR
ROPE LAY ALUMINUM
(OR SILICONE ADHESIVE - REFER TO DETAIL "B")
UNIVERSAL PARALLEL SPLICER
STAINLESS STEEL FASTENERMOUNT WITH
32 STRAND 17 GAUGE COPPERCONDUCTOR (TO GROUND ROD)
CAST BRONZE CABLE TO ROD CONNECTOR
NOTES:1. P.V.C. INSTALLATION BY ELECTRICAL CONTRACTOR.2. SEALING AROUND P.V.C. PENETRATION BY ROOFING CONTRACTOR.
CAST BRONZE DECK MOUNT
1/2" STAINLESS STEELALL THREAD ROD
1.5" SCHEDULE 40 P.V.C.
CAST ALUMINUM P.V.C. CAP
24 STRAND 14 GAUGE ALUMINUMCONDUCTOR (TO PERIMETER CONDUCTOR)
SEAL EDGES W/ SILICONE SEALANT AND RE-PAINTAFTER ATTACHMENT TO INHIBIT RUST.
CLEAN STEEL CONNECTION POINT FREE OF PAINT ANDDEBRIS PRIOR TO ATTACHMENT.
24 STRAND 14GAUGEALUMINUMCONDUCTOR
CAST ALUMINUMPURLIN STEELBOND CLAMP W/8 SQ. INCHESCONTACT
1.
2.
NOTES: NO SCALE
STEEL CONNECTION DETAIL
NO SCALE
PIPE BONDING DETAIL "E"
NO SCALE
SECONDARY BONDING DETAIL
NO SCALE
VENT BONDING DETAIL
NO SCALE
TEE SPLICE DETAIL
NO SCALE
GROUNDING ELECTRODE DETAIL
ROPE LAYALUMINUMLIGHTNINGPROTECTIONCONDUCTOR
CABLE TO CABLEEXOTHERMICCONNECTION
SOLID SOFTALUMINUMSECONDARYBONDING WIRE
DOWN CONDUCTOR (TRANSITION FROMALUMINUM TO COPPER PRIOR TOCONTACT W/GRADE)
CONCENTRIC STRANDCOPPER GROUNDCONDUCTOR
3/4 " X 10'COPPERWELD GROUND ROD
NOTES:MAKE CONNECTION TO GROUND RODMINIMUM 18" BELOW FINISHED GRADEAND 24" OUT FROM FOUNDATION WALL.
EXOTHERMIC CONNECTION
PVC CONDUIT RUN DOWNCONCEALED INSIDE EXTERIOR WALL
CABLE TO CABLEEXOTHERMICCONNECTION ROPE LAY ALUMINUM LIGHTNING
PROTECTION CONDUCTOR
CAST ALUM. PIPEBONDING CLAMP
ROPE LAY ALUMINUM LIGHTNINGPROTECTION CONDUCTOR
STRAP TYPEALUMINUM VENTBONDING STRAP
ROPE LAY ALUMINUM LIGHTNINGPROTECTION CONDUCTOR
CAST ALUM.SECONDARY BONDINGLUG
ALUMINUM AIR TERMINAL 1/2" X 12" BLUNT-TIP
1. ALIGN AIR TERMINAL PLUMB.
MOUNT BASECAST STL OR ALM ADHESIVE
NOTES:
ALUMINUM CONDUCTOR24 STRAND 14 GAUGE
CONDUCTOR FASTENERALUMINUM ADHESIVE
NO SCALE
ADHESIVE BASE MOUNT
AIR TERMINAL DETAIL "R"
NO SCALE
SIDE MOUNT
AIR TERMINAL DETAIL
ALUMINUM AIR TERMINAL
1/2" X 24" BLUNT-TIP
MOUNT BASECAST STL OR ALM ADHESIVE
ALUMINUM CONDUCTOR
24 STRAND 14 GAUGE
DO NOT PENETRATE METALCOPING ON PARAPET
1/2" X 12" ALUMINUMAIR TERMINAL
ALUMINUM LOOP FASTENERWITH STAINLESS STEEL HEX-HEAD TECH SCREW (TYPICAL)
NO SCALE
GRAVITY VENT OR
FAN BONDING DETAIL
NOTES:1. APPLY SILICONE SEALANT TO UNDERSIDE OF BASE PRIOR TO INSTALLATION ON EXHAUST FAN.2. INTERCONNECT TO MAIN ROOF CONDUCTOR AS INDICATED.3. LOCATE AIR TERMINAL, CABLING, AND FASTENERS TO AVOID OBSTRUCTION OF EQUIPMENT IDENTIFICATION LABEL, COVER OPENING, AND DISCONNECT MEANS.
MALLEABLE ALUMINUMADHESIVE MOUNT BASE
24 STRAND 14GAUGE ALUMINUMCONDUCTOR
NO SCALE
ROOF PENETRATION DETAIL
COLUMNGROUNDING WHENUTILIZED FORDOWN CONDUCTOR
EXOTHERMIC CONNECTION
CONCENTRIC STRANDCOPPER GROUND CONDUCTOR
GROUND ROD
EXOTHERMIC CONNECTION
NO SCALE
COLUMN GROUNDING
GV-1
GV-3
GV-2GV-4
GV-5
9x9 GOOSENECK
8x8 GOOSENECK
30ø EXHAUST STACK,TERMINATE 6' MIN ABOVEROOF SURFACE W/BUTTERFLY DAMPERDISCHARGE ROOF CAP
9x9 GOOSENECK
9x9 GOOSENECK
8x8 GOOSENECK8x8 GOOSENECK
TERMINAL (TYP) CONDUCTOR (TYP)
MAX (TYP)
20' - 0"
MAX (TYP)
50' - 0"
GROUND TO BUILDING STEEL (TYP)
MAX (TYP)
60' - 0"
TERMINAL (TYP)
BOND/SPLICE (TYP)
mi^k=molsfaba=clo=obcbobk`b=lkivK=obcbo==ql=pmb`fcf`^qflk==pb`qflk=OSQNNP=?ifdeqkfkd=molqb`qflk=clo=pqor`qrobp?=clo=obnrfobjbkqp
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWOS=mj
bib`qof`^i
abq^fip
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bQKO
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
k
1" = 10'-0"
ollc=mi^k=J=bib`qof`^i
ifdeqkfkd=molqb`qflk=`^i`ri^qflk
REVISIONS
DATE DESCRIPTION
qo^kpclojbo=p`ebarib
kVA TYPE PRIMARY SECONDARYGROUNDINGCONDUCTOR
BONDINGCONDUCTOR
15 kVA
30 kVA
45 kVA
75 kVA
112.5 kVA
150 kVA
225 kVA
300 kVA
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
208Y/120V
208Y/120V
208Y/120V
208Y/120V
208Y/120V
208Y/120V
208Y/120V
208Y/120V
#8
#8
#4
#2
#1/O
#3/O
#3/O
#3/O
#8
#8
#4
#2
#1/O
#3/O
#3/O
#3/O
500 kVA LINEAR 480V-3Ø 208Y/120V #3/O #3/O
FEEDERID
# OFSETS
BUILDING WIREQUANTITY & SIZE TYPE
THHN - DRYTYPE THWN - WET
MINIMUMCONDUIT SIZE
`lmmbo=cbbabo=p`ebarib
30 1 3#10,#10 G 3/4"
35 1 3#8,#10 G 3/4"
40 1 3#8,#10 G 3/4"
45 1 3#6,#10 G 1"
50 1 3#6,#10 G 1"
60 1 3#4,#10 G 1"
70 1 3#4,#8 G 1 1/4"
80 1 3#3,#8 G
90 1 3#2,#8 G
100 1 3#1,#8 G
110 1 3#2,#6 G
125 1 3#1,#6 G
150 1 3#1/0,#6 G 2"
175 1 3#2/0,#6 G
200 1 3#3/0,#6 G
225 1 3#4/0,#4 G 2 1/2"
250 1 3-250kCM,#4 G
300 1 3-350kCM,#4 G
350 2 2"
400 1 4"
450 3#4/0,#2 G
500
600 3"
700
800
1000 3
1200 4
1600 4
2000 5
2500 6
1 1/4"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
2"
2"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
2
2
2
2
2
4"
4"
4"
3"
4"
4"
4"
3#2/0,#3 G
3-500kCM,#3 G
3-250kCM,#2 G
3-350kCM,#1 G
3-500kCM,#1/0 G
3-600kCM,#1/0 G
3-500kCM,#2/0 G
3-350kCM,#3/0 G
3-600kCM,#4/0 G
3-600kCM,#250 G
3-600kCM,#350 G
NOTES:1. ELECTRICAL CONTRACTOR TO VERIFY CONDUIT SIZE REQUIRED IF WIRE TYPES OTHER THANTHOSE LISTED ABOVE ARE USED.
2. FEEDER SIZES BASED ON TABLE 310.16, 75º C.
3. SIZES ADJUSTED PER NEC 110.14.
FEEDERID
# OFSETS
BUILDING WIREQUANTITY & SIZE TYPE
THHN - DRYTYPE THWN - WET
MINIMUMCONDUIT SIZE
30Y 1 4#10,#10 G 3/4"
35Y 1 4#8,#10 G 3/4"
40Y 1 4#8,#10 G 3/4"
45Y 1 4#6,#10 G 1"
50Y 1 4#6,#10 G 1"
60Y 1 4#4,#10 G 1"
70Y 1 4#4,#8 G 1 1/4"
80Y 1 4#3,#8 G
90Y 1 4#2,#8 G
100Y 1 4#1,#8 G
110Y 1 4#2,#6 G
125Y 1 4#1,#6 G
150Y 1 4#1/0,#6 G 2"
175Y 1 4#2/0,#6 G
200Y 1 4#3/0,#6 G
225Y 1 4#4/0,#4 G 2 1/2"
250Y 1 4-250kCM,#4 G
300Y 1 4-350kCM,#4 G
350Y 2 2"
400Y 1 4"
450Y 4#4/0,#2 G
500Y
600Y 3"
700Y
800Y
1000Y 3
1200Y 4
1600Y 4
2000Y 5
2500Y 6
1 1/4"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
2"
2"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
2
2
2
2
2
4"
4"
4"
3"
4"
4"
4"
4#2/0,#3 G
4-500kCM,#3 G
4-250kCM,#2 G
4-350kCM,#1 G
4-500kCM,#1/0 G
4-600kCM,#1/0 G
4-500kCM,#2/0 G
4-350kCM,#3/0 G
4-600kCM,#4/0 G
4-600kCM,#250 G
4-600kCM,#3/0 G
POWER COMPANYUNDERGROUND PRIMARY
SPD
M
NEC 700
MAIN DISTRIBUTION SWITCHBOARD MDS
KWH METER,FURNISHED BYPOWER COMPANY ANDINSTALLED BY THECONTRACTOR
POWER COMPANY PADMOUNTED TRANSFORMER480/277V, 3PH, 4W
CTSECTION
ATS-E400A-3P480V,NEMA1,22KAIC,OPENTRANSITION
NEC 700ATS-X100A-3P480V,NEMA1,22KAIC,OPENTRANSITION
NEC 702
NEC 702
CT/PT
CUSTOMERMETER
P/BD H1B
A. PROVIDE A SHORT CIRCUIT AND COORDINATION STUDY PER THE CONTRACT DOCUMENTS. NEC700 SYSTEM (ALL OVERCURRENT PROTECTIVE DEVICES UP AND DOWNSTREAM OF ATS-X)SHALL BE SELECTIVELY COORDINATED TO A MAXIMUM 0.01 SECONDS. SYSTEM IS INDICATEDHERE WITH CIRCUIT BREAKERS. PROVIDE FIXED, ADJUSTABLE AND ELECTRONIC ADJUSTABLEBREAKER AS REQUIRED. FUSES MAY BE USED IF DESIRED OR REQUIRED TO ACHIEVEREQUIRED SELECTIVITY. THE COORDINATION STUDY SHALL DEMONSTRATE REQUIREDSELECTIVITY FOR THE ENTIRE NEC 700 SYSTEM WITHOUT ADJUSTMENT TO THE CONTRACTAMOUNT. EQUIPMENT SHALL NOT BE RELEASED FOR FABRICATION UNTIL THE SHORT CIRCUITAND COORDINATION REPORT IS APPROVED BY THE ARCHITECT. THE CONTRACTOR IS ADVISEDNOT TO ORDER ELECTRICAL EQUIPMENT PRIOR TO SUBMISSION AND APPROVAL OF THECOORDINATION STUDY. THE CONTRACTOR SHALL TAKE FULL RESPONSIBILITY FORMODIFICATION OF ELECTRICAL EQUIPMENT ORDERED PRIOR THE APPROVED COORDINATIONSTUDY..
B. REFER TO TRANSFORMER SCHEDULE FOR BONDING CONDUCTORS SIZES FOR EACHTRANSFORMER..
C. REFER TO PANEL SCHEDULES FOR PANEL CHARACTERISTICS INCLUDING MAIN BREAKERREQUIREMENTS. GROUND PER SERVICE GROUND DETAIL ON THIS DRAWING..
D. SOME PANELS OVERSIZED PER JMU STANDARDS REQUIRING MINIMUM 225A PANELS EXCEPTWHERE COORDINATION CAN ONLY BE ACHIEVED WITH A SMALLER PANEL SIZE
400A100A
MAINBREAKER
DISTRIBUTION
XFMRTE1A,75 KVA
TWO 480V,250 KVA, BI-FUEL(GAS/DIESEL) GENERATORS(500KVA TOTAL CAPACITY)
22
2
M
XFMRT1A,112KVA
P/BD L1A
3 4
100Y 225Y
100Y100Y
2
400Y
400Y 100Y
(2) - 6" EC
800Y
P/BD HE1A
NEC 702
125
1-1/4" EC FORCT/PT LEADS
REPRESENTED BY n
APPLIES TO DRAWINGS Exxx
lkbifkb=hbvklqbp
1. REFER TO THE DUCTBANK DETAILS ON DRAWING E4.1 AND SUBSTITUTE CONDUIT SIZEINDICATED THEREIN..
2. PROVIDE A RED PLAQUE WITH WHITE LETTERING ON THE FRONT OF THIS EQUIPMENT STATING:"THIS PANEL IS CAPABLE OF BEING ENERGIZED FROM MULTIPLE SOURCES. ".
3. PROVIDE DISCONNECTING MEANS LABEL PER NEC ..
4. PROVIDE A SHUNT TRIP MAIN CIRCUIT BREAKER. ALSO PROVIDE A KEY ACTIVATED SWITCH TOOPEN MCB LOCATED ADJACENT TO FIRE ALARM ANNUNCIATOR. KEY SWITCH TO BELOCKNETICS H.D. KEY SWITCH #643-05.
lkb=ifkb=dbkbo^i==klqbpW
1 1
NEC 700P/BD HX1B
2
400Y
175
225Y
P/BD HM1B
P/BD LM1A
NOTE: IF ADDITIVE BID ITEM #01 IS TAKEN, THE BASE BID ONELINE DIAGRAM SHALL NOT BE USED.
400Y
2P/BD LE1A
225Y
2P/BD LEMDF
100Y
2P/BD LE1C
225Y
P/BD L1B
225Y
XFMRTM1A,75KVA
225Y
125
METERING TO INTERFACE TOTHE BAS (TYP). REFER TOSPECIFICATION SECTION 262713
POWER COMPANYUNDERGROUND PRIMARY
SPD
M
NEC 700
MAIN DISTRIBUTION SWITCHBOARD MDS
KWH METER,FURNISHED BYPOWER COMPANY ANDINSTALLED BY THECONTRACTOR
POWER COMPANY PADMOUNTED TRANSFORMER480/277V, 3PH, 4W
CTSECTION
ATS-E400A-3P480V,NEMA1,22KAIC,OPENTRANSITION
NEC 700ATS-X100A-3P480V,NEMA1,22KAIC,OPENTRANSITION
NEC 702
NEC 702
CT/PT
CUSTOMERMETER
P/BD H1B
400A100A
L MAINBREAKER
DISTRIBUTION
XFMRTE1A,75 KVA
480V,100 KVA, NGGENERATOR
22
2
2
M
XFMRT1A,112.5KVA
P/BD L1A
3 4
100Y 225Y
100Y100Y
P/BD LE1A
2
100Y
(2) - 6" EC
800Y
P/BD HE1A
NEC 702
225Y
125
1-1/4" EC FORCT/PT LEADS
REPRESENTED BY n
APPLIES TO DRAWINGS Exxx
lkbifkb=hbvklqbp
1. REFER TO THE DUCTBANK DETAILS ON DRAWING E4.1 AND SUBTITUTE CONDUIT SIZE INDICATEDTHEREIN..
2. PROVIDE A RED PLAQUE WITH WHITE LETTERING ON THE FRONT OF THIS EQUIPMENT STATING:"THIS PANEL IS CAPABLE OF BEING ENERGIZED FROM MULTIPLE SOURCES. ".
3. PROVIDE DISCONNECTING MEANS LABEL PER NEC .. .
4. PROVIDE A SHUNT TRIP MAIN CIRCUIT BREAKER. ALSO PROVIDE A KEY ACTIVATED SWITCH TOOPEN MCB LOCATED ADJACENT TO FIRE ALARM ANNUNCIATOR. KEY SWITCH TO BE LOCKNETICSH.D. KEY SWITCH #643-05.
lkb=ifkb=dbkbo^i==klqbpW
1 1
NEC 700P/BD HX1B
2
400Y
175
225Y
NOTE: IF ADDITIVE BID ITEM #01 IS TAKEN, THIS BASE BID ONELINE DIAGRAM SHALL NOT BE USED.
400Y400Y
400Y
2P/BD LEMDF
100Y
P/BD L1B
225Y
P/BD L1C
225Y
OVERSIZEDFORFUTURE
METERING TO INTERFACE TOTHE BAS (TYP). REFER TOSPECIFICATION SECTION 262713
225Y
P/BD HM1B
A. PROVIDE A SHORT CIRCUIT AND COORDINATION STUDY PER THE CONTRACT DOCUMENTS. NEC700 SYSTEM (ALL OVERCURRENT PROTECTIVE DEVICES UP AND DOWNSTREAM OF ATS-X)SHALL BE SELECTIVELY COORDINATED TO A MAXIMUM 0.01 SECONDS. SYSTEM IS INDICATEDHERE WITH CIRCUIT BREAKERS. PROVIDE FIXED, ADJUSTABLE AND ELECTRONIC ADJUSTABLEBREAKER AS REQUIRED. FUSES MAY BE USED IF DESIRED OR REQUIRED TO ACHIEVEREQUIRED SELECTIVITY. THE COORDINATION STUDY SHALL DEMONSTRATE REQUIREDSELECTIVITY FOR THE ENTIRE NEC 700 SYSTEM WITHOUT ADJUSTMENT TO THE CONTRACTAMOUNT. EQUIPMENT SHALL NOT BE RELEASED FOR FABRICATION UNTIL THE SHORT CIRCUITAND COORDINATION REPORT IS APPROVED BY THE ARCHITECT. THE CONTRACTOR IS ADVISEDNOT TO ORDER ELECTRICAL EQUIPMENT PRIOR TO SUBMISSION AND APPROVAL OF THECOORDINATION STUDY. THE CONTRACTOR SHALL TAKE FULL RESPONSIBILITY FORMODIFICATION OF ELECTRICAL EQUIPMENT ORDERED PRIOR THE APPROVED COORDINATIONSTUDY..
B. REFER TO TRANSFORMER SCHEDULE FOR BONDING CONDUCTORS SIZES FOR EACHTRANSFORMER..
C. REFER TO PANEL SCHEDULES FOR PANEL CHARACTERISTICS INCLUDING MAIN BREAKERREQUIREMENTS. GROUND PER SERVICE GROUND DETAIL ON THIS DRAWING..
D. SOME PANELS OVERSIZED PER JMU STANDARDS REQUIRING MINIMUN 225A PANELS EXCEPTWHERE COORDINATION CAN ONLY BE ACHEIVED WITH A SMALLER PANEL SIZE
P/BD LM1A
XFMRTM1A,75KVA
225Y
125
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWOU=mj
mltbo=lkbJifkb
af^do^j
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bRKN
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
NO SCALE
lkb=ifkb=af^do^j=J=^aafqfsb=_fa=fqbj=@NNO SCALE
lkb=ifkb=af^do^j=J=_^pb=_fa
1. SWITCHBOARD SHALL BE UL SERVICE ENTRANCE RATED2. PROVIDE SPD WITH OVERCURRENT DEVICE, DISCONECTING MEANS & CONDUCTORS, SIZE PER MFR REQUIREMENTS MOUNTED ON TOP OF EQUIPMENT.3. PROVIDE DISCONNECTING MEANS LABEL PER NEC4 .NOT USED5. PROVIDE FACTORY INSTALLED DIGITAL MULTIMETER, PLUS MONITORING CABLE IN CONDUIT TO BAS PICKUP MODULE, COORDINATE WITH DIV 23.6. PROVIDE SIGN PER NEC 700: "LIFE SAFETY STANDBY FROM GENERATOR LOCATED IN EQUIPMENT YARD OUTSIDE, VIA ATS-X"7. PROVIDE SIGN PER NEC 702: "OPTIONAL STANDBY FROM GENERATOR LOCATED IN EQUIPMENT YARD OUTSIDE, VIA ATS-E8. FOR NON-SIMULTANEOUS LOADS, ONLY LARGER OF LOADS IS INCLUDED IN TOTAL.9. PROVIDE INDIVIDUAL METERING AND BAS CABLING FOR THIS CIRCUIT.10. REFER TO PLANS FOR CONDUCTOR AND CONDUIT SIZES.
NOTES:
LARGEST MOTOR 0.00 kVA 0.00 kVA TOTAL DEMAND... 386 A
MISCELLANEOUS 87.10 kVA 87.10 kVA TOTAL CONNECTED... 440 A
KITCHEN 0.00 kVA 0.00 kVA
ELECTRIC HEAT 5.00 kVA 5.00 kVA TOTAL DEMAND KVA: 321 kVA
AC / HEAT PUMP 145.74 kVA 145.74 kVA TOTAL CONNECTED... 366 kVA
RECEPTACLES 109.68 kVA 59.84 kVA
EXTERIOR LIGHTING 4.70 kVA 5.88 kVA
INTERIOR LIGHTING 13.89 kVA 17.36 kVA
LOAD TYPE CONNECTED KVA DEMAND KVA
TOTAL 131.04 kVA 116.61 kVA 114.00 kVA
12 SPARE 0.0 kVA 0.0 kVA 0.0 kVA 3 100 A
11 SPARE 0.0 kVA 0.0 kVA 0.0 kVA 3 225 A
10 LM1A VIA TM1A 5.1 kVA 3.3 kVA 3.3 kVA 3 125 A
9 SPARE 0.0 kVA 0.0 kVA 0.0 kVA 3 400 A
8 SPD 0.0 kVA 0.0 kVA 0.0 kVA 3 100 A 2,10
7 H1B 8.1 kVA 5.3 kVA 4.5 kVA 3 225 A 9,10
6 HM1B 35.4 kVA 32.8 kVA 31.3 kVA 3 225 A 9,10
5 ATS-X 3.0 kVA 4.1 kVA 1.6 kVA 3 100 A 6,9,10
4 ATS-E 41.8 kVA 39.7 kVA 39.8 kVA 3 400 A 7,9,10
3 L1A VIA T1A 37.7 kVA 31.3 kVA 33.5 kVA 3 175 A 9,10
2 MAIN BREAKER 0.0 kVA 0.0 kVA 0.0 kVA 3 800 A 3,5,10
1 CT 0.0 kVA 0.0 kVA 0.0 kVA 3 0 A 1
DEVICE
NO.DESCRIPTION A B C
NUMBER
OF POLESRATING NOTES
NEUTRAL BUS: 800 A
VERTICAL BUS: 800 A CT SECTION: YES BRACING: 22K AMPS...
GROUND BUS: 800 A MAIN SWITCH: 800 A VOLTAGE: 480/277 Wye 3 PH 4 WIRE
HORIZONTAL... 800 A NEMA ENCL: NEMA... FRONT...
SWITCHBOARD SCHEDULE MDS
MISCELLANEOUS 8.00 kVA 100.00% 8.00 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 25 A
AC / HEAT PUMP 0.00 kVA 0.00% 0.00 kVA Total Conn. Current: 22 A
RECEPTACLES 0.00 kVA 0.00% 0.00 kVA Total Est. Demand: 20.4 kVA
EXTERIOR LIGHTING 3.38 kVA 125.00% 4.23 kVA Total Conn. Load: 18.0 kVA
INTERIOR LIGHTING 6.58 kVA 125.00% 8.22 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
30 A 20 A 16 A
8 kVA 5 kVA 4 kVA
41 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 42
39 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 40
37 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 38
35 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 36
33 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 34
31 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 32
29 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 30
27 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 28
25 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 26
23 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 24
21 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 22
19 1.3 0.0 SPACE ONLY -- -- 20
17 1.3 0.0 SPACE ONLY -- -- 18
15
20 A 3 SPRAY BOOTH 150
1.3 0.0 SPACE ONLY -- -- 16
13 1.3 0.0 SPACE ONLY -- -- 14
11 1.3 0.0 SPACE ONLY -- -- 12
9
20 A 3 SPRAY BOOTH 150
1.3 0.0 SPACE ONLY -- -- 10
7 20 A 1 SITE LIGHTING 3.4 0.0 SPACE ONLY -- -- 8
5 20 A 1 LTG 147, 148, 149, 152, 154 1.8 0.0 SPACE ONLY -- -- 6
3 20 A 1 LTG 158 2.7 0.0 SPACE ONLY -- -- 4
1 20 A 1 LTG 107, 108, 106, 105, 101 2.1 0.0 SPACE ONLY -- -- 2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
225 AMP MLO 480/277 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K
PANELBOARD SCHEDULE H1B LOCATION:CORRIDOR101
FED FROM: MDS
MISCELLANEOUS 27.50 kVA 100.00% 27.50 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 125 A
AC / HEAT PUMP 76.26 kVA 100.00% 76.26 kVA Total Conn. Current: 125 A
RECEPTACLES 0.00 kVA 0.00% 0.00 kVA Total Est. Demand: 103.8 kVA
EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 103.8 kVA
INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
135 A 124 A 117 A
37 kVA 34 kVA 33 kVA
41 -- -- SPACE ONLY 0.0 0.8 42
39 -- -- SPACE ONLY 0.0 0.8 40
37 -- -- SPACE ONLY 0.0 0.8
F-7 (ML 3 20 A
38
35 1.1 6.7 36
33 1.1 6.7 34
31
15 A 3 AHU-4 (ML)
1.1 6.7
CU-4 (ML) 3 30 A
32
29 0.8 4.9 30
27 0.8 4.9 28
25
15 A 3 AHU-3 (ML)
0.8 4.9
CU-3 (ML) 3 25 A
26
23 0.0 7.3 24
21 0.0 7.3 22
19
15 A 3 AHU-2 (ML)
2.8 7.3
CU-2 (ML) 3 30 A
20
17 20 A 1 SPARE 0.0 1.3 18
15 20 A 1 SPARE 0.0 1.3 16
13 20 A 1 SPARE 0.0 1.3
MAU-2 (ML) 3 20 A
14
11 20 A 1 TU1-9 THRU TU1-11 0.3 1.3 12
9 20 A 1 GARAGE DOOR 150 2.0 1.3 10
7 20 A 1 GARAGE DOOR 153 2.0 1.3
MAU-1 (ML) 3 20 A
8
5 20 A 1 GARAGE DOOR 161 2.0 5.8 6
3 20 A 1 GARAGE DOOR 162 2.0 5.8 4
1 20 A 1 GARAGE DOOR 162 2.0 5.8
DC-1 (ML) 3 30 A
2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
225 AMP MLO 480/277 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K
PANELBOARD SCHEDULE HM1B LOCATION:MECHANICALROOM 108
FED FROM: MDS
jp_==eN_
=========ejN_
REVISIONS
DATE DESCRIPTION
^o`
efqb`
qpj
lpbib
vK`
lj
TUM=i
vk
ke^
sbk
=m^
oht
^vI=prfqb=O
MM==sfo
dfk
f^=_
b^
`eI=sfo
dfk
f^=O
PQRO
mel
kb=ETRTF=PSUJO
UMM===c
^u=ETRTF=PSUJO
OPP
PROJECT NO: DATE:
01/15/16
NLNNLOMNS=QWQSWPM=mj
bib`qof`^i
p`ebaribp
g^jbp=j
^afplk=rkfsbopfqv
rkfsbopfqv=pbosf`
bp=^
kkbu
`ebp^mb^hb=^sbkrbI=e^oofplk_rod==s^
bRKO
pq^
qb=molgb`q=`labW=ONSJNUNPRJMMM
545116 NOVEMBER 16, 2015
MISCELLANEOUS 20.60 kVA 100.00% 20.60 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 105 A
AC / HEAT PUMP 2.22 kVA 100.00% 2.22 kVA Total Conn. Current: 118 A
RECEPTACLES 19.68 kVA 75.41% 14.84 kVA Total Est. Demand: 37.7 kVA
EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 42.5 kVA
INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
146 A 90 A 128 A
17 kVA 11 kVA 15 kVA
83 -- -- SPACE ONLY 0.0 0.0 84
81 -- -- SPACE ONLY 0.0 0.0 82
79 -- -- SPACE ONLY 0.0 0.0
SPARE (FUTURE SPRAYBOOTH) 3 20 A
80
77 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 78
75 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 76
73 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 74
71 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 72
69 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 70
67 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 68
65 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 66
63 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 64
61 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 62
59 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 60
57 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 58
55 20 A 1 REC 152 0.7 0.0 SPARE 1 20 A 56
53 20 A 1 REC 152, 154 1.1 0.0 SPARE 1 20 A 54
51 20 A 1 COMPUTER 154 0.7 0.0 SPARE 1 20 A 52
49 20 A 1 COMPUTER 152 0.7 0.0 SPARE 1 20 A 50
47 20 A 1 EWC 101 (GP) 0.5 0.0 DAMPER 108 (ML) 1 20 A 48
45 20 A 1 EWC 150 (GP) 0.5 0.2 EWC 101 (GP) 1 20 A 46
43 20 A 1 EWC 150 (GP) 0.5 3.5 44
41 20 A 1 REC 149, 148 0.7 3.5AIR COMPRESSOR (ML) 2 40 A
42
39 20 A 1 COMPUTER 149 0.7 0.2 UH -5 (ML) 1 20 A 40
37 20 A 1 COMPUTER 148 0.7 1.0 F-3 (ML) 1 15 A 38
35 20 A 1 REC 147 0.7 1.0 F-1(ML) 1 15 A 36
33 20 A 1 REC 101, 100 0.9 0.5 PAINT BOOTH LIGHTS 1 20 A 34
31 20 A 1 DRYER 103 1.5 0.5 PAINT BOOTH LIGHTS 1 20 A 32
29 20 A 1 DRYER 103 1.5 0.4 MITER SAW 156 1 20 A 30
27 20 A 1 DRYER 102 1.5 0.7 REC 156 1 20 A 28
25 20 A 1 DRYER 102 1.5 0.7 REC 151 1 20 A 26
23 20 A 1 REC 105 0.7 0.9 REC 151 1 20 A 24
21 20 A 1 REC 106 0.7 0.7 COIL REEL REC 150 1 20 A 22
19 20 A 1 REC 108 0.4 0.7 COIL REEL REC 150 1 20 A 20
17 20 A 1 PROJECTOR 107 0.0 0.7 COIL REEL REC 150 1 20 A 18
15 20 A 1 SCREEN 107 0.5 0.5 REC 150 1 20 A 16
13 20 A 1 REC 107 0.9 0.4 REC 150 1 20 A 14
11 20 A 1 REFRIG 110 1.0 0.2 PAINT SHAKER 150 1 20 A 12
9 20 A 1 VENDING 110 (GP) 1.0 0.2 PAINT SHAKER 150 1 20 A 10
7 20 A 1 VENDING 110 (GP) 1.0 0.9 REC EXTERIOR 1 20 A 8
5 20 A 1 VENDING 110 (GP) 1.0 0.9 REC EXTERIOR 1 20 A 6
3 20 A 1 COUNTER REC 110 0.4 0.9 REC EXTERIOR 1 20 A 4
1 20 A 1 COUNTER REC 110 0.4 0.9 REC 101 1 20 A 2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
225 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K
PANELBOARD SCHEDULE L1B LOCATION:CORRIDOR101
FED FROM: L1A
MISCELLANEOUS 2.00 kVA 100.00% 2.00 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 63 A
AC / HEAT PUMP 0.00 kVA 0.00% 0.00 kVA Total Conn. Current: 92 A
RECEPTACLES 31.16 kVA 66.05% 20.58 kVA Total Est. Demand: 22.6 kVA
EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 33.2 kVA
INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
96 A 89 A 92 A
11 kVA 11 kVA 11 kVA
89 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 90
87 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 88
85 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 86
83 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 84
81 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 82
79 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 80
77 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 78
75 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 76
73 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 74
71 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 72
69 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 70
67 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 68
65 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 66
63 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 64
61 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 62
59 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 60
57 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 58
55 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 56
53 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 54
51 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 52
49 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 50
47 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 48
45 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 46
43 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 44
41 20 A 1 REC 136 0.7 1.0 SCP (L) 1 20 A 42
39 20 A 1 REC 133, 134 1.1 1.0 FACP (L) (RED BREAKER) 1 20 A 40
37 20 A 1 COMPUTER 134, 133 0.7 1.1 REC 113 1 20 A 38
35 20 A 1 REC 126, 131 1.1 0.0 F-12 & F13 (ML) 1 15 A 36
33 20 A 1 COMPUTER 126, 131 0.7 1.1 REC 146, 145 1 20 A 34
31 20 A 1 REC 127, 130 1.1 0.7 COMPUTER 145, 146 1 20 A 32
29 20 A 1 COMPUTER 127, 130 0.7 1.3 REC 138 1 20 A 30
27 20 A 1 REC 128 0.5 1.1 REC 143, 144 1 20 A 28
25 20 A 1 REC 129 0.9 0.7 COMPUTER 143,144 1 20 A 26
23 20 A 1 REC 114 0.5 1.1 REC 141, 142 1 20 A 24
21 20 A 1 COMPUTER 114 0.4 0.7 COMPUTER 141, 142 1 20 A 22
19 20 A 1 REC 115, 116 1.1 1.1 REC 139, 140 1 20 A 20
17 20 A 1 COMPUTER 116, 115 0.7 0.7 COMPUTER 139, 140 1 20 A 18
15 20 A 1 REC 118, 117 1.1 0.5 REC 137 1 20 A 16
13 20 A 1 COMPUTER 118, 117 0.7 0.4 COMPUTER 137 1 20 A 14
11 20 A 1 REC 120, 119 1.1 0.4 COUNTER REC 135 1 20 A 12
9 20 A 1 COMPUTER 120, 119 0.7 0.4 COUNTER REC 135 1 20 A 10
7 20 A 1 REC 122, 121 1.1 0.2 COPIER 135 1 20 A 8
5 20 A 1 COMPUTER 122, 121 0.7 1.0 COPIER 135 1 20 A 6
3 20 A 1 REC 124, 123 1.1 0.4 COUNTER REC 128 1 20 A 4
1 20 A 1 COMPUTER 124, 123 0.7 1.0 REF 128 1 20 A 2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
225 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K
PANELBOARD SCHEDULE L1C LOCATION:ELECTRICAL125
FED FROM: L1A
MISCELLANEOUS 15.20 kVA 100.00% 15.20 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 134 A
AC / HEAT PUMP 5.26 kVA 100.00% 5.26 kVA Total Conn. Current: 184 A
RECEPTACLES 45.72 kVA 60.94% 27.86 kVA Total Est. Demand: 48.3 kVA
EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 66.2 kVA
INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
184 A 184 A 184 A
22 kVA 22 kVA 22 kVA
41 15.0 4.0 42
39 15.0 4.4 40
37
0 A 3PANEL LE1C FEED THRU LUGS(SPARE UNDER BASE BID)
15.0 4.4
PANEL LEMDF 3 100 A
38
35 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 36
33 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 34
31 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 32
29 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 30
27 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 28
25 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 26
23 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 24
21 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 22
19 -- -- SPACE ONLY 0.0 0.0 SPARE 1 20 A 20
17 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 18
15 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 16
13 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 14
11 20 A 1 EMERG PHONE (L) 1.0 0.0 SPARE 1 20 A 12
9 20 A 1 EMERG PHONE (L) 0.6 0.0 SPARE 1 20 A 10
7 20 A 1 ELECTRIC LOCK (L) 1.0 0.0 DAMPER 157 (ML) 1 20 A 8
5 1.9 0.2 DC-1 PANEL (ML) 1 20 A 6
325 A 2 DSS-1 (ML)
1.9 0.2 BAS PANEL (L) 1 20 A 4
1 20 A 1 BOILER B-1 (ML) 1.5 0.2 DDC PANEL (L) 1 20 A 2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
225 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K
PANELBOARD SCHEDULE LE1A LOCATION:ELECTRICAL160
FED FROM: TE1A
MISCELLANEOUS 36.40 kVA 100.00% 36.40 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 210 A
AC / HEAT PUMP 2.22 kVA 100.00% 2.22 kVA Total Conn. Current: 285 A
RECEPTACLES 63.96 kVA 57.82% 36.98 kVA Total Est. Demand: 75.6 kVA
EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 102.6 kVA
INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
317 A 261 A 282 A
38 kVA 31 kVA 34 kVA
83 14.8 11.0 84
81 10.8 10.7 82
79
225 A 3 PANEL L1B
16.9 11.4PANEL L1C (SPARE UNDERADDITIVE BID ITEM#1)
3 225 A
80
77 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 78
75 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 76
73 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 74
71 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 72
69 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 70
67 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 68
65 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 66
63 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 64
61 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 62
59 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 60
57 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 58
55 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 56
53 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 54
51 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 52
49 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 50
47 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 48
45 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 46
43 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 44
41 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 42
39 20 A 1 REC 162 0.7 0.0 SPACE ONLY -- -- 40
37 20 A 1 REC 162 0.7 0.0 SPACE ONLY -- -- 38
35 20 A 1 REC 157 0.5 0.0 SPACE ONLY -- -- 36
33 20 A 1 REC 159, 158 0.5 0.0 SPACE ONLY -- -- 34
31 20 A 1 REC 161 0.5 0.0 SPACE ONLY -- -- 32
29 20 A 1 REC 161 0.5 0.7 30
27 20 A 1 SPINDLE SANDER 153 1.6 0.7 28
25 20 A 1 LATHE 153 0.8 0.7
SHAPER 153 3 20 A
26
23 20 A 1 BELT SANDER 153 0.8 0.7 24
21 20 A 1 DRILL PRESS 153 0.8 0.7 22
19 20 A 1 BAND SAW 153 0.8 0.7
LG TABLE SAW 153 3 30 A
20
17 20 A 1 COIL REEL REC 153 0.7 0.7 18
15 20 A 1 COIL REEL REC 153 0.7 0.7 16
13 20 A 1 COIL REEL REC 153 0.7 0.7
LG TABLE SAW 153 3 30 A
14
11 20 A 1 COIL REEL REC 153 0.7 1.0 12
9 20 A 1 MITER SAWS 153 1.0 1.0 10
7 20 A 1 BENCH REC 153 1.0 1.0
JOINER 153 3 30 A
8
5 20 A 1 SM PLANER 153 0.8 0.7 6
3 20 A 1 ROUTER 153 0.8 0.7 4
1 20 A 1 DRUM SANDER 153 1.2 0.7
LG PLANER 153 3 20 A
2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
400 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K
PANELBOARD SCHEDULE L1A LOCATION:ELECTRICAL160
FED FROM: T1A
MISCELLANEOUS 12.00 kVA 100.00% 12.00 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 35 A
AC / HEAT PUMP 0.00 kVA 0.00% 0.00 kVA Total Conn. Current: 35 A
RECEPTACLES 0.72 kVA 100.00% 0.72 kVA Total Est. Demand: 12.7 kVA
EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 12.7 kVA
INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
37 A 37 A 33 A
4 kVA 4 kVA 4 kVA
29 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 30
27 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 28
25 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 26
23 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 24
21 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 22
19 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 20
17 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 18
15 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 16
13 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 14
11 20 A 1 SPARE 0.0 2.0 12
9 20 A 1 SPARE 0.0 2.0RACK 109 2 30 A
10
7 20 A 1 SPARE 0.0 2.0 8
5 20 A 1 SPARE 0.0 2.0RACK 109 2 30 A
6
3 20 A 1 REC 109 0.4 2.0 4
1 20 A 1 REC 109 0.4 2.0RACK 109 2 30 A
2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
100 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K
PANELBOARD SCHEDULE LEMDF LOCATION:MDF &SPECIAL...
FED FROM: LE1A
MISCELLANEOUS 0.00 kVA 0.00% 0.00 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 5.00 kVA 100.00% 5.00 kVA Total Est. Demand... 33 A
AC / HEAT PUMP 6.90 kVA 100.00% 6.90 kVA Total Conn. Current: 33 A
RECEPTACLES 0.00 kVA 0.00% 0.00 kVA Total Est. Demand: 11.9 kVA
EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 11.9 kVA
INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
43 A 28 A 28 A
5 kVA 3 kVA 3 kVA
41 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 42
39 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 40
37 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 38
35 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 36
33 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 34
31 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 32
29 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 30
27 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 28
25 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 26
23 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 24
21 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 22
19 20 A 1 WH-1 (ML) 1.0 1.0 WH-2(ML) 1 20 A 20
17 20 A 1 UH-3 (ML) 0.2 0.2 UH-4 (ML) 1 20 A 18
15 20 A 1 UH-1 (ML) 0.2 0.2 UH-2 (ML) 1 20 A 16
13 15 A 1 F-10 (ML) 0.0 0.1 F-11 (ML) 1 15 A 14
11 20 A 1 F-8 (ML) 1.0 1.0 F-9 (ML) 1 15 A 12
9 20 A 1 F-5 (ML) 1.0 1.0 F-6 (ML) 1 20 A 10
7 20 A 1 F-2 (ML) 1.0 1.0 F-4 (ML) 1 20 A 8
5 20 A 1 RH-2 (ML) 0.5 0.5 RH-1 (ML) 1 20 A 6
3 20 A 1 RH-4 (ML) 0.5 0.5 RH-3 (ML) 1 20 A 4
1 20 A 1 RH-5 (ML) 0.5 0.5 RH-6 (ML) 1 20 A 2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
225 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 10K
PANELBOARD SCHEDULE LM1A LOCATION:MECHANICALROOM 157
FED FROM: TM1A
iN^==ibN^=ijac
iN_===iN`==ijN^
=ebN_
=euN_
i^_bi=?iN`?=^p=?ibN`?=rkabo=^aafqfsb=_fa=lmqflk=@NUNDER ADDITIVE BID OPTION #1, "LE1C" IS FED FROM "LE1A". REFER TO ONE LINE DIAGRAM
MISCELLANEOUS 15.20 kVA 100.00% 15.20 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 124 A
AC / HEAT PUMP 60.36 kVA 100.00% 60.36 kVA Total Conn. Current: 146 A
RECEPTACLES 45.72 kVA 60.94% 27.86 kVA Total Est. Demand: 103.4 kVA
EXTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA Total Conn. Load: 121.3 kVA
INTERIOR LIGHTING 0.00 kVA 0.00% 0.00 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
151 A 143 A 144 A
42 kVA 40 kVA 40 kVA
41 -- -- SPACE ONLY 0.0 22.1 42
39 -- -- SPACE ONLY 0.0 22.0 40
37 -- -- SPACE ONLY 0.0 22.1
LE1A VIA TE1A 3 125 A
38
35 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 36
33 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 34
31 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 32
29 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 30
27 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 28
25 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 26
23 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 24
21 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 22
19 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 20
17 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 18
15 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 16
13 0.0 0.0 14
11 0.0 0.0 12
9
20 A 3 PUMP P-1
0.0 0.0
PUMP P-2 3 20 A
10
7 15 A 1 FP-1 - 5 (ML) 1.2 0.8 TU1-1 THRU TU1-8 1 15 A 8
5 3.9 13.8 6
3 3.9 13.8 4
1
20 A 3 AHU-1 (ML)
3.9 13.8
CU-1 (ML) 3 60 A
2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
400 AMP MLO 480/277 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 22K
PANELBOARD SCHEDULE HE1A LOCATION:ELECTRICAL160
FED FROM: ATS-E
MISCELLANEOUS 0.00 kVA 0.00% 0.00 kVA
KITCHEN 0.00 kVA 0.00% 0.00 kVA
ELECTRIC HEAT 0.00 kVA 0.00% 0.00 kVA Total Est. Demand... 13 A
AC / HEAT PUMP 0.00 kVA 0.00% 0.00 kVA Total Conn. Current: 10 A
RECEPTACLES 0.00 kVA 0.00% 0.00 kVA Total Est. Demand: 10.8 kVA
EXTERIOR LIGHTING 1.32 kVA 125.00% 1.65 kVA Total Conn. Load: 8.6 kVA
INTERIOR LIGHTING 7.32 kVA 125.00% 9.14 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
(GE) = PROVIDE GFCI BREAKER FOR EQUIPMENT, 6-50mA PER 2008 NEC 427.22. DED. NEUTRAL.(GP) = PROVIDE GFCI BREAKER FOR PERSONNEL, 4-6mA PER 2008 NEC 210.8. DED. NEUTRAL.(L) = PROVIDE LOCKOUT BREAKER TO PREVENT UNAUTHORIZED SWITCHING.(LC) = ROUTE TO LOAD VIA LIGHTING CONTACTOR, REF DETAIL ON DWG E4.X.(ML) = PROVIDE BREAKER WITH MAINTENANCE LOCKOUT, LOCKABLE OFF.
12 A 16 A 6 A
3 kVA 4 kVA 2 kVA
29 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 30
27 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 28
25 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 26
23 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 24
21 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 22
19 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 20
17 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 18
15 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 16
13 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 14
11 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 12
9 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 10
7 20 A 1 SPARE 0.0 0.0 SPACE ONLY -- -- 8
5 20 A 1 EM 139 -146 1.6 0.0 SPACE ONLY -- -- 6
3 20 A 1 EM EXT LIGHTING 1.3 2.8 EM LTG 119-124 1 20 A 4
1 20 A 1 EM LTG 150 1.9 1.1 EM LTG COORIDOR 1 20 A 2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
100 AMP MLO 480/277 Wye 3 PH 4 W MOUNT: Surface PANEL ASSEMBLY RATED (KAIC): 22K
PANELBOARD SCHEDULE HX1B LOCATION:CORRIDOR101
FED FROM: ATS-X
REVISIONS
DATE DESCRIPTION