E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch...

15
NOTE: ALL SYMBOLS LISTED MAY NOT APPEAR ON THE DRAWINGS 4'-0" (1219mm) 4'-0" (1219mm) 4'-0" (1219mm) 4'-0" (1219mm) THREE WAY SWITCH SINGLE POLE SWITCH SINGLE POLE SWITCH - LOWERCASE SUBSCRIPT INDICATES ITEM CONTROLLED COORDINATE IN FIELD 1'-6" (457mm) UON 1'-6" (457mm) UON 1'-6" (457mm) UON 1'-6" (457mm) UON DUPLEX RECEPTACLE - NEMA 5-20R PROTECTION OCCUPANCY SENSOR SWITCH TWO DUPLEX RECEPTACLE - NEMA 5-20R DUPLEX RECEPTACLE NEMA 5-20R WITH INTEGRAL GROUND FAULT SPECIAL RECEPTACLE - NEMA CONFIGURATION AS NOTED J M SD SOC S3 Sa S TRANSFORMER T SWITCH SIZE, LOWER NUMERAL DENOTES FUSE SIZE - 3 POLE, UON FUSED SAFETY DISCONNECT SWITCH - UPPER NUMERAL DENOTES MOTOR CONNECTION PANELBOARD, BRANCH JUNCTION BOX PANELBOARD, DISTRIBUTION 30/15 4'-0" (1219mm) LP-10,12 HOMERUN TO PANELBOARD. NUMERALS AND LETTERS ADJACENT TO ARROW HEAD(S) INDICATE ASSIGNED PANEL AND CIRCUIT(S) NUMBERS(S). SEE PANEL SCHEDULE(S) FOR CIRCUIT WIRE AND CONDUIT SIZES/QUANTITIES. NUMERAL SUBSCRIPT INDICATES CANDELA POWER COMBINATION FIRE ALARM AUDIO/VISUAL APPLIANCE - WALL MOUNTED, INDICATES CANDELA POWER. FIRE ALARM VISUAL APPLIANCE - WALL MOUNTED, NUMERAL SUBSCRIPT FIRE ALARM MANUAL STATION FIRE ALARM AUDIO ALARM - WALL MOUNTED V F AV A 15 15 EXISTING TO REMAIN EXISTING TO BE REMOVED PLAN REFERENCE NOTE SYMBOL NEW WORK X DATA/TELEPHONE OUTLET - SEE DETAIL 6 ON SHEET E501 PANEL, SWITCHBOARD, OR BUSDUCT - SEE ONE-LINE DIAGRAM FOR EXACT SPECIFICATION ELECTRICAL CONDUIT - SEE ONE-LINE DIAGRAM FOR EXACT SPECIFICATION CIRCUIT BREAKER FUSED DISCONNECT SAFETY SWITCH, 3 POLE UON TRANSFORMER EQUIPMENT ENCLOSURE - SEE ONE-LINE DIAGRAM FOR EXACT SPECIFICATION X X G A. GENERAL 1. THE CONTRACTOR SHALL COMPLY WITH ALL THE LATEST LAWS, ORDINANCES, RULES AND REGULATIONS OF ALL LOCAL AND STATE GOVERNMENTAL AUTHORITIES, THE RULES OF THE NATIONAL FIRE PROTECTION ASSOCIATION AS INTERPRETED BY THE ENFORCING AUTHORITY HAVING JURISDICTION AND OF THE PUBLIC UTILITIES HAVING CONNECTION WITH ANY OF THE SYSTEMS HEREIN SPECIFIED. 2. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND INSPECTIONS REQUIRED BY ANY OF THE FOREGOING AUTHORITIES, AND PAY FOR ALL OTHER COSTS IN CONNECTION WITH THE WORK. ALL CERTIFICATES SHALL BE IN DUPLICATE AND SHALL BE DELIVERED TO THE OWNER. 3. THE SITE, LOCATION AND ROUTING OF SYSTEMS INDICATED TO HAVE NEW CONNECTIONS MADE TO THEM ARE SHOWN AS ACCURATELY AS FIELD CONDITIONS WOULD PERMIT. BIDDERS SHALL VISIT THE SITE AND THOROUGHLY EXAMINE THE CONTRACT DRAWINGS. BIDDERS WHO DO NOT VISIT THE SITE MAY BE UNILATERALLY NOT PERMITTED TO SUBMIT A BID IF THE OWNER SO DESIGNATES. ALL EXISTING CONDITIONS SHALL BE EXAMINED AND THEIR EXACT LOCATIONS VERIFIED. THE CONTRACTOR SHALL REPORT TO THE ARCHITECT, ENGINEER AND OWNER BEFORE SUBMITTING A BID, ANY CONDITIONS WHICH MIGHT MAKE INSTALLATION OF REQUIRED EQUIPMENT A PROBLEM. NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO INVESTIGATE CONDITIONS OR MISUNDERSTANDINGS OF THE CONTRACTUAL REQUIREMENTS. 4. THE CONTRACTOR SHALL REMOVE ALL EQUIPMENT NOT INDICATED TO BE REUSED TO A DESIGNATED LOCATION AT THE PROJECT SITE. AFTER THE EQUIPMENT HAS BEEN ASSEMBLED FOR THE OWNER'S INSPECTION AND POSSIBLE RETENTION, ALL EQUIPMENT NOT TO BE RETAINED BY THE OWNER SHALL BE REMOVED FROM THE SITE BY THE CONTRACTOR. ALL BUILDING SYSTEMS SHALL REMAIN IN SERVICE UNLESS INDICATED OTHERWISE. ALL OUTAGES OR INTERRUPTIONS SHALL BE KEPT TO MINIMUM DURATION. NOTIFY THE OWNER 15 BUSINESS DAYS IN ADVANCE OF ANY OUTAGE OR INTERRUPTION. 5. THE CONTRACTOR SHALL INSTALL AND CONNECT ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH THE BEST ENGINEERING PRACTICE AND, UNLESS OTHERWISE SHOWN OR SPECIFIED, FOLLOW THE MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS AND FURNISH AND INSTALL ALL REQUIRED AUXILIARY ITEMS COMPLETE. 6. DRAWINGS SHALL BE CONSIDERED DIAGRAMMATIC AND FOR BIDDING PURPOSES ONLY. WHILE THE DRAWINGS ARE GENERALLY TO SCALE AND ARE AS ACCURATE AS THE SCALE WILL PERMIT, ALL IMPORTANT DIMENSIONS SHALL BE DETERMINED IN THE FIELD. 7. COORDINATE WITH ALL TRADES TO AVOID INTERFERENCE AMONG MECHANICAL, ELECTRICAL, ARCHITECTURAL AND STRUCTURAL ITEMS. PROVIDE ALL NECESSARY OFFSETS AND FITTINGS IN CIRCUITRY AND OTHER ITEMS REQUIRED TO INSTALL THE WORK WITHOUT INTERFERENCES. 8. THE CONTRACTOR SHALL TEST ALL EQUIPMENT INSTALLED UNDER THIS CONTRACT AND DEMONSTRATE TO THE OWNER ITS PROPER OPERATIONS. ALL NEW EQUIPMENT SHALL BE MOUNTED VIBRATION FREE. 9. ALL EQUIPMENT AND WORKMANSHIP SHALL BE GUARANTEED IN FULL FROM ALL DEFECTS FOR ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THIS WORK. 10. ALL EQUIPMENT INSTALLED SHALL BE NEW AND SHALL CONFORM IN ALL RESPECTS TO THE LATEST APPROVED STANDARDS OF IEEE, ANSI, NEMA AND UNDERWRITERS LABORATORIES, INC., (UNLESS INDICATED OTHERWISE). 11. THE CONTRACTOR SHALL REPAIR ALL WALL, CEILING, FLOOR, OR ROOF OPENINGS WHICH ARE CREATED BY DEMOLITION OR PENETRATION. THE REPAIRS SHALL BE WITH MATERIALS AND FINISHES TO MATCH EXISTING. ALL FIRE RATED PENETRATIONS SHALL BE SEALED WITH SUITABLE MATERIALS TO PRESERVE FIRE RATED INTEGRITY. 12. DEFINITIONS a. "PROVIDE" UNDER THIS CONTRACT IS DEFINED AS FURNISH AND INSTALL. b. "CONCEALED" UNDER THIS CONTRACT IS DEFINED AS HIDDEN BY ARCHITECTURAL WALLS AND CEILINGS. c. "EXPOSED" UNDER THIS CONTRACT IS DEFINED AS VISIBLE TO VIEW. d. "INDICATED" UNDER THIS CONTRACT IS DEFINED AS SHOWN IN THE CONTRACT DOCUMENTS. 13. UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL THOROUGHLY CLEAN THE CONTRACT AREA AND ALL OTHER AREAS USED FOR STORAGE, STAGING, ETC. 14. THE CONTRACTOR SHALL NOTIFY THE OWNER WHEN THE PROJECT IS APPROXIMATELY 75% COMPLETED IN ORDER TO SCHEDULE A PRE-FINAL REVIEW OF CONSTRUCTION. NO WORK SHALL BE CONCEALED BY CEILINGS, WALLS, ETC. FINAL REVIEW SHALL BE SCHEDULED AT 100% COMPLETION. ALL PUNCH LIST ITEMS MUST BE ACCOMPLISHED PRIOR TO FINAL ACCEPTANCE. 15. THE CONTRACTOR SHALL PREPARE A COMPREHENSIVE METHOD OF PROCEDURE AND SUBMIT IT TO THE OWNER WITH SHOP DRAWINGS FOR REVIEW. THE SUBMITTAL SHALL ITEMIZE METHODS OF PROCEDURE FOR ALL POTENTIAL EMERGENCY SITUATIONS AND SHALL INCLUDE A LIST OF PERSONS REPRESENTING THE OWNER AND THE CONTRACTOR ALONG WITH DAYTIME AND EMERGENCY PHONE NUMBERS AND PAGER NUMBERS WHO SHALL BE CONTACTED IN THE EVENT OF AN EMERGENCY. THIS LIST SHALL BE DISTRIBUTED TO THE OWNER'S REPRESENTATIVE AND THE CONTRACTORS SUPERINTENDENT OR FOREMAN AT THE SITE. EMERGENCY SITUATIONS SHALL INCLUDE BUT NOT BE LIMITED TO POWER OUTAGES, CHILLED AND CONDENSER WATER SYSTEM RUPTURES, AUTOMATIC TEMPERATURE CONTROL OUTAGES AND OWNER'S EQUIPMENT DAMAGE. THE COMPREHENSIVE METHOD OF PROCEDURE SHALL BE APPROVED BY THE OWNER PRIOR TO COMMENCEMENT OF ANY WORK. 16. THE USE OF POWDER DRIVEN FASTENERS OR IMPACT TOOLS SHALL NOT BE PERMITTED. 17. ALL WORK SHALL BE PERFORMED DURING NORMAL WORKING HOURS MONDAY THROUGH FRIDAY - 7:00 A.M. TO 5:00 P.M. WORK PERFORMED OUTSIDE OF NORMAL WORKING HOURS WILL BE REIMBURSED AT PREMIUM RATES AND SHALL BE NEGOTIATED WITH THE OWNER PRIOR TO THE CONSTRUCTION PHASE. 18. PROVIDE TEMPORARY SERVICE FOR LIGHTING AND POWER EQUIPMENT (DRILLS, SAW, ETC.). VERIFY TEMPORARY REQUIREMENTS WITH GENERAL CONTRACTOR. TEMPORARY LIGHTING AND POWER SHALL MEET OSHA REQUIREMENTS AND LOCAL CODE. TEMPORARY POWER SHALL BE 120 VOLTS. 19. UNLESS SPECIFICALLY NOTED ON THE DEMOLITION PLANS, REMOVE ALL LIGHTING, SWITCHES, RECEPTACLES AND CLOCK OUTLETS AND ASSOCIATED CIRCUITRY INDICATED. CIRCUITRY TO BE REMOVED SHALL BE ALL CONDUCTORS AND ANY EXPOSED RACEWAYS INCLUDING WIREMOLD AND ALL RACEWAY THAT BECOMES EXPOSED UPON REMOVAL OF WALLS AND CEILINGS. NOT ALL DEVICES TO BE REMOVED ARE SHOWN ON PLANS. 20. UNLESS SPECIFICALLY NOTED ON THE PLANS, ALL CIRCUITRY, EQUIPMENT, DEVICES, ETC., NOT NOTED AS EXISTING TO REMAIN OR TO BE RELOCATED, SHALL BE NEW. THE CONTRACTOR MAY REUSE ALL EXISTING CIRCUITRY AS FIELD CONDITIONS PERMIT. REMOVE ALL DEVICES AND CIRCUITRY NOT BEING REUSED. CIRCUITRY TO BE REMOVED SHALL BE REMOVED BACK TO THE SOURCE AND ALL HOLES SHALL BE REPAIRED TO CONFORM TO FINISHED SURFACE. ALL CIRCUITS ARE TO REMAIN IN SERVICE UPON COMPLETION OF THIS PROJECT WHICH ARE COORDINATED WITH THE OWNER. 21. PROTECT ADJACENT MATERIALS INDICATED TO REMAIN. INSTALL AND MAINTAIN DUST AND NOISE BARRIERS TO KEEP DIRT, DUST, AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS. REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE. 22. LOCATE, IDENTIFY AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREA AND SERVING OTHER AREAS OUTSIDE THE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY SERVICES FOR AFFECTED AREAS. 23. FINAL TESTING: AT THE TIME OF FINAL INSPECTION AND TESTS, ALL CONNECTIONS AT PANELBOARDS, DEVICES AND EQUIPMENT AND ALL SPLICES MUST BE COMPLETED. EACH BRANCH CIRCUIT AND ITS RESPECTIVE CONNECTED EQUIPMENT MUST TEST FREE OF SHORT CIRCUITS. UPON COMPLETION OF THE WORK, CLEAN AND POLISH ALL EXPOSED SURFACES IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. FIRE ALARM ANNUNCIATOR PANEL FLA HP GFI HOA (ER) FA FACP FAAP EMER ELEC (E) FULL LOAD AMPS GROUND FAULT INTERRUPTER HANDS OFF AUTOMATIC HORSEPOWER GROUND EXISTING TO REMAIN RELOCATED EQUIPMENT FIRE ALARM CONTROL PANEL FIRE ALARM EMERGENCY ELECTRIC AFF CKT CT CLG AWG CB AIC ABOVE FINISHED FLOOR CURRENT TRANSFORMER AMERICAN WIRE GAGE CIRCUIT BREAKERS CIRCUIT CEILING CONDUIT AMPS INTERRUPTING CAPACITY AMPS KILOVOLT AMPERE MAIN CIRCUIT BREAKER MAIN LUGS ONLY MAIN DISTRIBUTION PANEL LIGHTING LTG MLO MCB MIN MDP MINIMUM KVA KW KILOWATTS G NOT TO SCALE EQUIPMENT TO BE RELOCATED WEATHERPROOF UNLESS OTHERWISE NOTED WP W V UON WATTS VOLTS T SW TELE TYP NTS (R) PBO TRANSFORMER SWITCH TELEPHONE TYPICAL PROVIDED BY OTHERS NATIONAL ELECTRIC CODE NEC (N) NEW PH PHASE REMOVE (X) TRANSFORMER XFMR C A VA VOLT-AMPS ATS AUTOMATIC TRANSFER SWITCH MECHANICAL EQUIPMENT. REFERENCE MECHANICAL DRAWINGS XXX-# CABLE TRAY DIVISION 26 - ELECTRICAL GENERAL NOTES DIVISION 26 - ELECTRICAL ABBREVIATIONS DIVISION 26 - ELECTRICAL SYMBOLS PLAN SYMBOLS WIRING DEVICES EQUIPMENT ONE-LINE DIAGRAM FIRE ALARM 120-277V CEILING OCCUPANCY SENSOR 12' (3658mm) RADIUS 120-277V WALL - SWITCH HEIGHT 1. SENSORSWITCH 2. LEGRAND 3. LEVITON OCCUPANCY SENSOR SWITCH DESCRIPTION MFR. CATALOG NO. MOUNTING REMARKS VOLTS SOC OS PROVIDE WITH MOUNTING HARDWARE AND POWER PACK. SET TO 30 MINUTE TIMER PROVIDE WITH MOUNTING HARDWARE AND POWER PACK. SET TO 30 MINUTE TIMER EMERGENCY EXIT SIGN SYMBOL DESCRIPTION MANUFACTURER MODEL NUMBER LAMP TYPE # MOUNTING VOLTS NOTES COOPER 1 EUXR-6 1W LED CEILING MVOLT NOTES: 1. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUDE: a. HUBBELL LES-C-S-R-X-N-A. b. LITHONIA LRP-1-RC-120/277 2. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUDE: a. HUBBELL LCAT14-35MLG-EU b. COOPER 14GR-LD5-24-F1-UNV-L830-CD-1 3. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUED: a. SYLVANIA 2A/025UNV835/22GWH b. HUBBELL LCAT22-935MLG-EU 4. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUED: a. SYLVANIA 2A/035UNV835/24GWH b. HUBBELL LCAT24-35MLG-EU 5. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUDE: a. HUBBELL MPS4-4-35XW-CN-E-U b. SYLVANIA 1A/035UNV835/48/SWH 6. LIGHT FIXTURE IS THE BASIS OF DESIGN. ADDITIONAL MANUFACTURERS ARE, BUT NOT LIMITED TO HUBBELL AND SYLVANIA 7. ALTERNATE MAUNFACTURERS a. FINELIGHT UC-E-22-S b. UCLD-24IN-30K-90CRI-SWR-WH 8. LIGHT FIXTURE IS THE BASIS OF DESIGN. ADDITIONAL MANUFACTURERS ARE AVAILABLE. 9. TUNABLE WHITE LIGHT FIXTURE IS THE BASIS OF DESIGN. ADDITIONAL MANUFACTURERS ARE, BUT NOT LIMITED TO SYLVANIA AND HE WILLIAMS. LIGHTING FIXTURE SCHEDULE 305mm X 1220mm LED TROFFER LITHONIA 1 BLT4-20L-ADP-277 -LP835 35W LED CEILING 610mm X 610mm LED TROFFER LITHONIA 1 2BLT2-20L-ADP-277 -LDP835 26W LED CEILING 610mm X 1120mm LED TROFFER LITHONIA 1 2BLT4-30L-ADP-277 -LP835 31W LED CEILING OCCUPANCY SENSOR SCHEDULE CR CARD READER 1 2 3 4 WSX-PDT DSW-301-W-U OSSMT-GDW 1. SENSORSWITCH 2. LEGRAND 3. HUBBELL CMR-PDT-9 DT-355-U OMNIDT500BP1277 ISOLATED GROUND IG 4'-0" (1219mm) 1220mm STRIP LED LITHONIA 1 ZL1D-L48-3000LM-FST -MVOLT-35K-80CRI 30W LED PENDANT 5 1220mm WALL LED LITHONIA 1 WL4-30L-EZ1-LP835 29W LED WALL 6 RCP REES SYSTEM CONTROL PANEL 4'-0" (1219mm) 1'-6" (457mm) UON DOUBLE WIRED QUAD RECEPTACLE - SEE DETAIL 5 SHEET E-501 C SURFACE METAL RACEWAY EXISTING FACP FS SP AV S SD TS F PRIOR TO THE START OF ANY WORK THE CONTRACTOR SHALL PERFORM A TEST PER NFPA 72 AND VERIFY THE EXISTING FIRE ALARM SYSTEM IS IN GOOD WORKING CONDITION. THE RESULTS OF THIS TEST SHALL BE SUBMITTED TO THE OWNER, ARCHITECT, AND ENGINEER FOR RECORD. ANY REPAIRS REQUIRED TO MAKE THE FIRE ALARM SYSTEM OPERATIONAL SHALL BE PROVIDED TO THE OWNER UNDER A SEPERATE LINE ITEM PRICE FOR APPROVAL. COMMENCEMENT OF ANY REPAIR WORK WITHOUT AUTHORIZATION BY OWNER WILL BE DONE AT THE CONTRACTOR'S EXPENSE. THIS PROJECT INVOLVES THE INSTALLATION OF NEW FIRE ALARM DEVICES TO EXTEND THE SERVICE OF THE EXISTING BASE BUILDING FIRE ALARM SYSTEM TO PROTECT THE AREA OF WORK INDICATED. THE EXTENSION OF SYSTEM WILL EMPLOY THE USE OF STYLE "Y" INDICATING APPLIANCE CIRCUITS PER THE MANUFACTURERS REQUIREMENTS. NEW INITIATING DEVICES SHALL BE INSTALLED AND CONNECTED ON EXISTING INITIATING DEVICE CIRCUITS SERVED BY THE EXISTING FIRE ALARM CONTROL PANEL AS PER MANUFACTURERS REQUIREMENTS. THE CONTRACTOR SHALL PROVIDE ADDITIONAL NOTIFICATION CIRCUITS TO ACCOMMODATE THE ADA APPROVED AUDIBLE AND VISUAL SIGNALING DEVICES IN QUANTITIES AND TYPES AS INDICATED. ALL INTERCONNECTIONS TO THE EXISTING FIRE ALARM SYSTEM SHALL BE CONNECTED SO AS TO PROVIDE U.L. REQUIRED SUPERVISION OF ALL WIRING. ADDITIONALLY, SHOULD THE NEW EQUIPMENT BECOME INOPERATIVE FOR ANY REASON, THE EXISTING FIRE ALARM SYSTEM SHALL ENTER TROUBLE MODE. THE CONTRACTOR SHALL PROVIDE ALL DEVICES, WIRING, EXPANDER PANELS, ETC., AS REQUIRED FOR A COMPLETE, CODE COMPLIANT AND OPERATIONAL FIRE ALARM SYSTEM. THIS RISER DIAGRAM IS TYPICAL ONLY. REFER TO FLOOR PLANS FOR EXACT QUANTITY AND LOCATIONS OF DEVICES. ALL FIRE ALARM SYSTEM WIRING SHALL BE INSTALLED IN EMT. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND PLAN DRAWINGS TO AHJ FOR APPROVAL. ALL DEVICES SHALL BE COMPATIBLE WITH THE EXISTING FACP. VISUAL DEVICES SHALL HAVE SELECTABLE 15, 30, 75 AND 110CD RATINGS. ALL FIRE ALARM STROBES SHALL SYNCRONIZE. PROVIDE SYNCRONIZATION MODULES AS REQUIRED. TEST AND RE-CERTIFY SYSTEM PER NFPA 72. ALL WORK SHALL COMPLY WITH THE LOCAL FIRE ALARM CODES. CONTRACTOR SHALL UPDATE EXISTING FACP/EXPANDER CALCULATIONS FOR BATTERY AND LINE VOLTAGE DROPS. MANUFACTURER IS SIEMENS. LOCATED IN THE CRC, B2 LEVEL ELECTRICAL ROOM B2-5753. EXISTING POWER EXTENDER. EXISTING VOICE EVAC TO ADDITIONAL SPEAKERS TO ADDITIONAL NOTIFICATION DEVICES TO ADDITIONAL INITIATING DEVICES (E) (E) (E) (E) (N) (E) (R) 15 1 2 3 4 5 6 7 8 9 10 11 1 FIRE ALARM PARTIAL RISER DIAGRAM SCALE: NO SCALE AV (R) 15 V (E) 15 AV (E) 15 UNDER CABINET LIGHTING H.E. WILLIAMS 1 1SF-4-L12/835-DMA- DRV-UNV 12.5W LED SURFACE 7 DIMMER SWITCH WARNING LIGHT/ALARM GUARDIAN 1 AP280-235 13.2W LED WALL 8 120 610mm X 610mm LED TROFFER LITHONIA 1 2BLT2-TUWH-RHYR- 20L-ADP 26W LED CEILING 9 A MVOLT MVOLT MVOLT MVOLT MVOLT MVOLT MVOLT FIRE ALARM SPEAKER - CEILING MOUNTED UON SP 4'-0" (1219mm) 6" (152 mm) BELOW DROP CEILING. 6" (152 mm) BELOW DROP CEILING. 6" (152 mm) BELOW DROP CEILING. COORDINATE FINAL MOUNTING HEIGHT WITH MANUFACTURER COORDINATE FINAL MOUNTING HEIGHT WITH MANUFACTURER COORDINATE FINAL MOUNTING HEIGHT WITH MANUFACTURER DRAWN BY CHECKED BY DRAWING NO. MEP ENGINEERS PROPERTY OF THE UNITED STATES GOVERNMENT FOR OFFICIAL USE ONLY DO NOT REMOVE THIS NOTICE PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED DESIGNED BY FILE NAME OFFICE OF RESEARCH FACILITIES DRAWING PROJECT BUILDING CONTRACTORS REVISIONS SEAL A/E Name and LOGO SUBMISSION SUB. DATE PROJ. MGR. WRK REQ. NO. PROJ. OFFICER SPB TASK NO. STATE/ZIP OTHER CITY BUILDING NO. STREET NAME BUILDING NO. FACILITY CODE 9000 ROCKVILLE PIKE BETHESDA MD 20892 PRIME A/E SUB A/E CONS. WORK CONSTR. CON. CONS. CONTR. A/E TASK NO. A/E CON. NO. PROJEC T TITLE DRAWIN G TITLE HERA LABORATORY PLANNERS NIH HHSN292201400002I 20251 Century Blvd. Suite 120 Germantown, MD 20874 877.871.4229 t. www.cfrengineering.com HERA PROJECT NO: PROJECT MANAGER / LABORATORY PLANNER Health, Education and Research Associates, Inc. ARCHITECT HERA Studio of Pennsylvania, LLC 7315 Wisconsin Ave., Suite 400W Bethesda, MD 20814 301.789.8017 t. 314.289.6167 f. www.herainc.com STRUCTURAL ENGINEER 604 S. King Street, Suite 101 Leesburg, VA 20175 703.385.5556 t. www.ares.engineering 10/15/2018 6:44:47 PM NHLBI SUITE B2-3701 - ELECTRON MICROSCOPY CORE 03/20/2020 ISSUED FOR CONSTRUCTION 10 CRC 51 C105883 A. BHASIN CFR ENGINEERING #14341.51 MARK DATE DESCRIPTION OM/RS ID/PS ID/PS T. GRIFFITH E-001 GENERAL NOTES, ABBREVIATIONS, SYMBOLS, DETAILS, & SCHEDULES - ELECTRICAL

Transcript of E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch...

Page 1: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

NOTE: ALL SYMBOLS LISTED MAY NOT APPEAR ON THE DRAWINGS

4'-0" (1219mm)

4'-0" (1219mm)

4'-0" (1219mm)

4'-0" (1219mm)

THREE WAY SWITCH

SINGLE POLE SWITCH

SINGLE POLE SWITCH - LOWERCASE SUBSCRIPT INDICATES ITEM CONTROLLED

COORDINATE

IN FIELD

1'-6" (457mm) UON

1'-6" (457mm) UON

1'-6" (457mm) UON

1'-6" (457mm) UONDUPLEX RECEPTACLE - NEMA 5-20R

PROTECTION

OCCUPANCY SENSOR SWITCH

TWO DUPLEX RECEPTACLE - NEMA 5-20R

DUPLEX RECEPTACLE NEMA 5-20R WITH INTEGRAL GROUND FAULT

SPECIAL RECEPTACLE - NEMA CONFIGURATION AS NOTED

J

M

SD

SOC

S3

Sa

S

TRANSFORMERT

SWITCH SIZE, LOWER NUMERAL DENOTES FUSE SIZE - 3 POLE, UON

FUSED SAFETY DISCONNECT SWITCH - UPPER NUMERAL DENOTES

MOTOR CONNECTION

PANELBOARD, BRANCH

JUNCTION BOX

PANELBOARD, DISTRIBUTION

30/15

4'-0" (1219mm)

LP-10,12

HOMERUN TO PANELBOARD. NUMERALS AND LETTERS ADJACENT TO ARROW HEAD(S) INDICATE

ASSIGNED PANEL AND CIRCUIT(S) NUMBERS(S). SEE PANEL SCHEDULE(S) FOR CIRCUIT WIRE AND

CONDUIT SIZES/QUANTITIES.

NUMERAL SUBSCRIPT INDICATES CANDELA POWER

COMBINATION FIRE ALARM AUDIO/VISUAL APPLIANCE - WALL MOUNTED,

INDICATES CANDELA POWER.

FIRE ALARM VISUAL APPLIANCE - WALL MOUNTED, NUMERAL SUBSCRIPT

FIRE ALARM MANUAL STATION

FIRE ALARM AUDIO ALARM - WALL MOUNTED

V

F

AV

A

15

15

EXISTING TO REMAIN

EXISTING TO BE REMOVED

PLAN REFERENCE NOTE SYMBOL

NEW WORK

X

DATA/TELEPHONE OUTLET - SEE DETAIL 6 ON SHEET E501

PANEL, SWITCHBOARD, OR BUSDUCT - SEE ONE-LINE DIAGRAM FOR EXACT SPECIFICATION

ELECTRICAL CONDUIT - SEE ONE-LINE DIAGRAM FOR EXACT SPECIFICATION

CIRCUIT BREAKER

FUSED DISCONNECT SAFETY SWITCH, 3 POLE UON

TRANSFORMER

EQUIPMENT ENCLOSURE - SEE ONE-LINE DIAGRAM FOR EXACT SPECIFICATION

XX

G

A. GENERAL

1. THE CONTRACTOR SHALL COMPLY WITH ALL THE LATEST LAWS, ORDINANCES, RULES AND REGULATIONS OF

ALL LOCAL AND STATE GOVERNMENTAL AUTHORITIES, THE RULES OF THE NATIONAL FIRE PROTECTION

ASSOCIATION AS INTERPRETED BY THE ENFORCING AUTHORITY HAVING JURISDICTION AND OF THE PUBLIC

UTILITIES HAVING CONNECTION WITH ANY OF THE SYSTEMS HEREIN SPECIFIED.

2. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND INSPECTIONS REQUIRED BY ANY OF THE

FOREGOING AUTHORITIES, AND PAY FOR ALL OTHER COSTS IN CONNECTION WITH THE WORK. ALL

CERTIFICATES SHALL BE IN DUPLICATE AND SHALL BE DELIVERED TO THE OWNER.

3. THE SITE, LOCATION AND ROUTING OF SYSTEMS INDICATED TO HAVE NEW CONNECTIONS MADE TO THEM

ARE SHOWN AS ACCURATELY AS FIELD CONDITIONS WOULD PERMIT. BIDDERS SHALL VISIT THE SITE AND

THOROUGHLY EXAMINE THE CONTRACT DRAWINGS. BIDDERS WHO DO NOT VISIT THE SITE MAY BE

UNILATERALLY NOT PERMITTED TO SUBMIT A BID IF THE OWNER SO DESIGNATES. ALL EXISTING CONDITIONS

SHALL BE EXAMINED AND THEIR EXACT LOCATIONS VERIFIED. THE CONTRACTOR SHALL REPORT TO THE

ARCHITECT, ENGINEER AND OWNER BEFORE SUBMITTING A BID, ANY CONDITIONS WHICH MIGHT MAKE

INSTALLATION OF REQUIRED EQUIPMENT A PROBLEM. NO CONSIDERATION OR ALLOWANCE WILL BE

GRANTED FOR FAILURE TO INVESTIGATE CONDITIONS OR MISUNDERSTANDINGS OF THE CONTRACTUAL

REQUIREMENTS.

4. THE CONTRACTOR SHALL REMOVE ALL EQUIPMENT NOT INDICATED TO BE REUSED TO A DESIGNATED

LOCATION AT THE PROJECT SITE. AFTER THE EQUIPMENT HAS BEEN ASSEMBLED FOR THE OWNER'S

INSPECTION AND POSSIBLE RETENTION, ALL EQUIPMENT NOT TO BE RETAINED BY THE OWNER SHALL BE

REMOVED FROM THE SITE BY THE CONTRACTOR. ALL BUILDING SYSTEMS SHALL REMAIN IN SERVICE

UNLESS INDICATED OTHERWISE. ALL OUTAGES OR INTERRUPTIONS SHALL BE KEPT TO MINIMUM DURATION.

NOTIFY THE OWNER 15 BUSINESS DAYS IN ADVANCE OF ANY OUTAGE OR INTERRUPTION.

5. THE CONTRACTOR SHALL INSTALL AND CONNECT ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH

THE BEST ENGINEERING PRACTICE AND, UNLESS OTHERWISE SHOWN OR SPECIFIED, FOLLOW THE

MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS AND FURNISH AND INSTALL ALL REQUIRED

AUXILIARY ITEMS COMPLETE.

6. DRAWINGS SHALL BE CONSIDERED DIAGRAMMATIC AND FOR BIDDING PURPOSES ONLY. WHILE THE

DRAWINGS ARE GENERALLY TO SCALE AND ARE AS ACCURATE AS THE SCALE WILL PERMIT, ALL IMPORTANT

DIMENSIONS SHALL BE DETERMINED IN THE FIELD.

7. COORDINATE WITH ALL TRADES TO AVOID INTERFERENCE AMONG MECHANICAL, ELECTRICAL,

ARCHITECTURAL AND STRUCTURAL ITEMS. PROVIDE ALL NECESSARY OFFSETS AND FITTINGS IN CIRCUITRY

AND OTHER ITEMS REQUIRED TO INSTALL THE WORK WITHOUT INTERFERENCES.

8. THE CONTRACTOR SHALL TEST ALL EQUIPMENT INSTALLED UNDER THIS CONTRACT AND DEMONSTRATE TO

THE OWNER ITS PROPER OPERATIONS. ALL NEW EQUIPMENT SHALL BE MOUNTED VIBRATION FREE.

9. ALL EQUIPMENT AND WORKMANSHIP SHALL BE GUARANTEED IN FULL FROM ALL DEFECTS FOR ONE (1) YEAR

FROM THE DATE OF FINAL ACCEPTANCE OF THIS WORK.

10. ALL EQUIPMENT INSTALLED SHALL BE NEW AND SHALL CONFORM IN ALL RESPECTS TO THE LATEST

APPROVED STANDARDS OF IEEE, ANSI, NEMA AND UNDERWRITERS LABORATORIES, INC., (UNLESS INDICATED

OTHERWISE).

11. THE CONTRACTOR SHALL REPAIR ALL WALL, CEILING, FLOOR, OR ROOF OPENINGS WHICH ARE CREATED BY

DEMOLITION OR PENETRATION. THE REPAIRS SHALL BE WITH MATERIALS AND FINISHES TO MATCH EXISTING.

ALL FIRE RATED PENETRATIONS SHALL BE SEALED WITH SUITABLE MATERIALS TO PRESERVE FIRE RATED

INTEGRITY.

12. DEFINITIONS

a. "PROVIDE" UNDER THIS CONTRACT IS DEFINED AS FURNISH AND INSTALL.

b. "CONCEALED" UNDER THIS CONTRACT IS DEFINED AS HIDDEN BY ARCHITECTURAL WALLS AND CEILINGS.

c. "EXPOSED" UNDER THIS CONTRACT IS DEFINED AS VISIBLE TO VIEW.

d. "INDICATED" UNDER THIS CONTRACT IS DEFINED AS SHOWN IN THE CONTRACT DOCUMENTS.

13. UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL THOROUGHLY CLEAN THE CONTRACT AREA

AND ALL OTHER AREAS USED FOR STORAGE, STAGING, ETC.

14. THE CONTRACTOR SHALL NOTIFY THE OWNER WHEN THE PROJECT IS APPROXIMATELY 75% COMPLETED IN

ORDER TO SCHEDULE A PRE-FINAL REVIEW OF CONSTRUCTION. NO WORK SHALL BE CONCEALED BY

CEILINGS, WALLS, ETC. FINAL REVIEW SHALL BE SCHEDULED AT 100% COMPLETION. ALL PUNCH LIST ITEMS

MUST BE ACCOMPLISHED PRIOR TO FINAL ACCEPTANCE.

15. THE CONTRACTOR SHALL PREPARE A COMPREHENSIVE METHOD OF PROCEDURE AND SUBMIT IT TO THE

OWNER WITH SHOP DRAWINGS FOR REVIEW. THE SUBMITTAL SHALL ITEMIZE METHODS OF PROCEDURE FOR

ALL POTENTIAL EMERGENCY SITUATIONS AND SHALL INCLUDE A LIST OF PERSONS REPRESENTING THE

OWNER AND THE CONTRACTOR ALONG WITH DAYTIME AND EMERGENCY PHONE NUMBERS AND PAGER

NUMBERS WHO SHALL BE CONTACTED IN THE EVENT OF AN EMERGENCY. THIS LIST SHALL BE DISTRIBUTED

TO THE OWNER'S REPRESENTATIVE AND THE CONTRACTORS SUPERINTENDENT OR FOREMAN AT THE SITE.

EMERGENCY SITUATIONS SHALL INCLUDE BUT NOT BE LIMITED TO POWER OUTAGES, CHILLED AND

CONDENSER WATER SYSTEM RUPTURES, AUTOMATIC TEMPERATURE CONTROL OUTAGES AND OWNER'S

EQUIPMENT DAMAGE. THE COMPREHENSIVE METHOD OF PROCEDURE SHALL BE APPROVED BY THE OWNER

PRIOR TO COMMENCEMENT OF ANY WORK.

16. THE USE OF POWDER DRIVEN FASTENERS OR IMPACT TOOLS SHALL NOT BE PERMITTED.

17. ALL WORK SHALL BE PERFORMED DURING NORMAL WORKING HOURS MONDAY THROUGH FRIDAY - 7:00 A.M.

TO 5:00 P.M. WORK PERFORMED OUTSIDE OF NORMAL WORKING HOURS WILL BE REIMBURSED AT PREMIUM

RATES AND SHALL BE NEGOTIATED WITH THE OWNER PRIOR TO THE CONSTRUCTION PHASE.

18. PROVIDE TEMPORARY SERVICE FOR LIGHTING AND POWER EQUIPMENT (DRILLS, SAW, ETC.). VERIFY

TEMPORARY REQUIREMENTS WITH GENERAL CONTRACTOR. TEMPORARY LIGHTING AND POWER SHALL

MEET OSHA REQUIREMENTS AND LOCAL CODE. TEMPORARY POWER SHALL BE 120 VOLTS.

19. UNLESS SPECIFICALLY NOTED ON THE DEMOLITION PLANS, REMOVE ALL LIGHTING, SWITCHES,

RECEPTACLES AND CLOCK OUTLETS AND ASSOCIATED CIRCUITRY INDICATED. CIRCUITRY TO BE REMOVED

SHALL BE ALL CONDUCTORS AND ANY EXPOSED RACEWAYS INCLUDING WIREMOLD AND ALL RACEWAY THAT

BECOMES EXPOSED UPON REMOVAL OF WALLS AND CEILINGS. NOT ALL DEVICES TO BE REMOVED ARE

SHOWN ON PLANS.

20. UNLESS SPECIFICALLY NOTED ON THE PLANS, ALL CIRCUITRY, EQUIPMENT, DEVICES, ETC., NOT NOTED AS

EXISTING TO REMAIN OR TO BE RELOCATED, SHALL BE NEW. THE CONTRACTOR MAY REUSE ALL EXISTING

CIRCUITRY AS FIELD CONDITIONS PERMIT. REMOVE ALL DEVICES AND CIRCUITRY NOT BEING REUSED.

CIRCUITRY TO BE REMOVED SHALL BE REMOVED BACK TO THE SOURCE AND ALL HOLES SHALL BE REPAIRED

TO CONFORM TO FINISHED SURFACE. ALL CIRCUITS ARE TO REMAIN IN SERVICE UPON COMPLETION OF THIS

PROJECT WHICH ARE COORDINATED WITH THE OWNER.

21. PROTECT ADJACENT MATERIALS INDICATED TO REMAIN. INSTALL AND MAINTAIN DUST AND NOISE BARRIERS

TO KEEP DIRT, DUST, AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS. REMOVE PROTECTION

AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE.

22. LOCATE, IDENTIFY AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREA AND

SERVING OTHER AREAS OUTSIDE THE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE

DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY SERVICES FOR

AFFECTED AREAS.

23. FINAL TESTING: AT THE TIME OF FINAL INSPECTION AND TESTS, ALL CONNECTIONS AT PANELBOARDS,

DEVICES AND EQUIPMENT AND ALL SPLICES MUST BE COMPLETED. EACH BRANCH CIRCUIT AND ITS

RESPECTIVE CONNECTED EQUIPMENT MUST TEST FREE OF SHORT CIRCUITS. UPON COMPLETION OF THE

WORK, CLEAN AND POLISH ALL EXPOSED SURFACES IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

FIRE ALARM ANNUNCIATOR PANEL

FLA

HP

GFI

HOA

(ER)

FA

FACP

FAAP

EMER

ELEC

(E)

FULL LOAD AMPS

GROUND FAULT INTERRUPTER

HANDS OFF AUTOMATIC

HORSEPOWER

GROUND

EXISTING TO REMAIN

RELOCATED EQUIPMENT

FIRE ALARM CONTROL PANEL

FIRE ALARM

EMERGENCY

ELECTRIC

AFF

CKT

CT

CLG

AWG

CB

AIC

ABOVE FINISHED FLOOR

CURRENT TRANSFORMER

AMERICAN WIRE GAGE

CIRCUIT BREAKERS

CIRCUIT

CEILING

CONDUIT

AMPS INTERRUPTING CAPACITY

AMPS

KILOVOLT AMPERE

MAIN CIRCUIT BREAKER

MAIN LUGS ONLY

MAIN DISTRIBUTION PANEL

LIGHTING LTG

MLO

MCB

MIN

MDP

MINIMUM

KVA

KW KILOWATTS

G

NOT TO SCALE

EQUIPMENT TO BE RELOCATED

WEATHERPROOF

UNLESS OTHERWISE NOTED

WP

W

V

UON

WATTS

VOLTS

T

SW

TELE

TYP

NTS

(R)

PBO

TRANSFORMER

SWITCH

TELEPHONE

TYPICAL

PROVIDED BY OTHERS

NATIONAL ELECTRIC CODENEC

(N) NEW

PH PHASE

REMOVE(X)

TRANSFORMERXFMR

C

A

VA VOLT-AMPS

ATS AUTOMATIC TRANSFER SWITCH

MECHANICAL EQUIPMENT. REFERENCE MECHANICAL DRAWINGSXXX-#

CABLE TRAY

DIVISION 26 - ELECTRICAL GENERAL NOTES DIVISION 26 - ELECTRICAL ABBREVIATIONS

DIVISION 26 - ELECTRICAL SYMBOLS

PLAN SYMBOLS

WIRING DEVICES

EQUIPMENT

ONE-LINE DIAGRAM

FIRE ALARM

120-277V

CEILING

OCCUPANCY SENSOR

12' (3658mm) RADIUS

120-277V

WALL - SWITCH

HEIGHT

1. SENSORSWITCH

2. LEGRAND

3. LEVITON

OCCUPANCY

SENSOR SWITCH

DESCRIPTION MFR. CATALOG NO. MOUNTING REMARKSVOLTS

SOC

OS

PROVIDE WITH MOUNTING

HARDWARE AND POWER PACK. SET

TO 30 MINUTE TIMER

PROVIDE WITH MOUNTING

HARDWARE AND POWER PACK. SET

TO 30 MINUTE TIMER

EMERGENCY EXIT SIGN

SYMBOL DESCRIPTION MANUFACTURER MODEL NUMBER

LAMP

TYPE#

MOUNTING VOLTS NOTES

COOPER 1EUXR-6

1W LED CEILING MVOLT

NOTES:

1. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUDE:

a. HUBBELL LES-C-S-R-X-N-A.

b. LITHONIA LRP-1-RC-120/277

2. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUDE:

a. HUBBELL LCAT14-35MLG-EU

b. COOPER 14GR-LD5-24-F1-UNV-L830-CD-1

3. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUED:

a. SYLVANIA 2A/025UNV835/22GWH

b. HUBBELL LCAT22-935MLG-EU

4. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUED:

a. SYLVANIA 2A/035UNV835/24GWH

b. HUBBELL LCAT24-35MLG-EU

5. ADDITIONAL ACCEPTABLE LIGHT FIXTURES INCLUDE:

a. HUBBELL MPS4-4-35XW-CN-E-U

b. SYLVANIA 1A/035UNV835/48/SWH

6. LIGHT FIXTURE IS THE BASIS OF DESIGN. ADDITIONAL MANUFACTURERS ARE, BUT NOT LIMITED TO HUBBELL

AND SYLVANIA

7. ALTERNATE MAUNFACTURERS

a. FINELIGHT UC-E-22-S

b. UCLD-24IN-30K-90CRI-SWR-WH

8. LIGHT FIXTURE IS THE BASIS OF DESIGN. ADDITIONAL MANUFACTURERS ARE AVAILABLE.

9. TUNABLE WHITE LIGHT FIXTURE IS THE BASIS OF DESIGN. ADDITIONAL MANUFACTURERS ARE, BUT NOT

LIMITED TO SYLVANIA AND HE WILLIAMS.

LIGHTING FIXTURE SCHEDULE

305mm X 1220mm

LED TROFFER

LITHONIA 1

BLT4-20L-ADP-277

-LP835

35W LED CEILING

610mm X 610mm

LED TROFFER

LITHONIA 1

2BLT2-20L-ADP-277

-LDP835

26W LED CEILING

610mm X 1120mm

LED TROFFER

LITHONIA 1

2BLT4-30L-ADP-277

-LP835

31W LED CEILING

OCCUPANCY SENSOR SCHEDULE

CRCARD READER

1

2

3

4

WSX-PDT

DSW-301-W-U

OSSMT-GDW

1. SENSORSWITCH

2. LEGRAND

3. HUBBELL

CMR-PDT-9

DT-355-U

OMNIDT500BP1277

ISOLATED GROUNDIG

4'-0" (1219mm)

1220mm

STRIP LED

LITHONIA 1

ZL1D-L48-3000LM-FST

-MVOLT-35K-80CRI

30W LED PENDANT 5

1220mm

WALL LED

LITHONIA 1WL4-30L-EZ1-LP835

29W LED WALL 6

RCPREES SYSTEM CONTROL PANEL

4'-0" (1219mm)

1'-6" (457mm) UON

DOUBLE WIRED QUAD RECEPTACLE - SEE DETAIL 5 SHEET E-501

C

SURFACE METAL RACEWAY

EXISTING

FACP

FS

SP

AV

SSDTSF

PRIOR TO THE START OF ANY WORK THE CONTRACTOR SHALL PERFORM A TEST PER NFPA

72 AND VERIFY THE EXISTING FIRE ALARM SYSTEM IS IN GOOD WORKING CONDITION. THE

RESULTS OF THIS TEST SHALL BE SUBMITTED TO THE OWNER, ARCHITECT, AND ENGINEER

FOR RECORD. ANY REPAIRS REQUIRED TO MAKE THE FIRE ALARM SYSTEM OPERATIONAL

SHALL BE PROVIDED TO THE OWNER UNDER A SEPERATE LINE ITEM PRICE FOR APPROVAL.

COMMENCEMENT OF ANY REPAIR WORK WITHOUT AUTHORIZATION BY OWNER WILL BE

DONE AT THE CONTRACTOR'S EXPENSE.

THIS PROJECT INVOLVES THE INSTALLATION OF NEW FIRE ALARM DEVICES TO EXTEND

THE SERVICE OF THE EXISTING BASE BUILDING FIRE ALARM SYSTEM TO PROTECT THE

AREA OF WORK INDICATED. THE EXTENSION OF SYSTEM WILL EMPLOY THE USE OF STYLE

"Y" INDICATING APPLIANCE CIRCUITS PER THE MANUFACTURERS REQUIREMENTS.

NEW INITIATING DEVICES SHALL BE INSTALLED AND CONNECTED ON EXISTING INITIATING

DEVICE CIRCUITS SERVED BY THE EXISTING FIRE ALARM CONTROL PANEL AS PER

MANUFACTURERS REQUIREMENTS. THE CONTRACTOR SHALL PROVIDE ADDITIONAL

NOTIFICATION CIRCUITS TO ACCOMMODATE THE ADA APPROVED AUDIBLE AND VISUAL

SIGNALING DEVICES IN QUANTITIES AND TYPES AS INDICATED.

ALL INTERCONNECTIONS TO THE EXISTING FIRE ALARM SYSTEM SHALL BE CONNECTED SO

AS TO PROVIDE U.L. REQUIRED SUPERVISION OF ALL WIRING. ADDITIONALLY, SHOULD THE

NEW EQUIPMENT BECOME INOPERATIVE FOR ANY REASON, THE EXISTING FIRE ALARM

SYSTEM SHALL ENTER TROUBLE MODE.

THE CONTRACTOR SHALL PROVIDE ALL DEVICES, WIRING, EXPANDER PANELS, ETC., AS

REQUIRED FOR A COMPLETE, CODE COMPLIANT AND OPERATIONAL FIRE ALARM SYSTEM.

THIS RISER DIAGRAM IS TYPICAL ONLY. REFER TO FLOOR PLANS FOR EXACT QUANTITY

AND LOCATIONS OF DEVICES.

ALL FIRE ALARM SYSTEM WIRING SHALL BE INSTALLED IN EMT.

CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND PLAN DRAWINGS TO AHJ FOR

APPROVAL.

ALL DEVICES SHALL BE COMPATIBLE WITH THE EXISTING FACP. VISUAL DEVICES SHALL

HAVE SELECTABLE 15, 30, 75 AND 110CD RATINGS. ALL FIRE ALARM STROBES SHALL

SYNCRONIZE. PROVIDE SYNCRONIZATION MODULES AS REQUIRED.

TEST AND RE-CERTIFY SYSTEM PER NFPA 72. ALL WORK SHALL COMPLY WITH THE LOCAL

FIRE ALARM CODES.

CONTRACTOR SHALL UPDATE EXISTING FACP/EXPANDER CALCULATIONS FOR BATTERY

AND LINE VOLTAGE DROPS.

MANUFACTURER IS SIEMENS. LOCATED

IN THE CRC, B2 LEVEL ELECTRICAL

ROOM B2-5753.

EXISTING

POWER

EXTENDER.

EXISTING

VOICE

EVAC

TO ADDITIONAL

SPEAKERS

TO ADDITIONAL

NOTIFICATION

DEVICES

TO ADDITIONAL

INITIATING

DEVICES

(E)(E) (E)

(E)

(N)

(E)

(R)

15

1

2

3

4

5

6

7

8

9

10

11

1

FIRE ALARM PARTIAL RISER DIAGRAM

SCALE: NO SCALE

AV

(R)

15

V

(E)

15

AV

(E)

15

UNDER CABINET LIGHTING H.E. WILLIAMS 1

1SF-4-L12/835-DMA-

DRV-UNV

12.5W

LED

SURFACE 7

DIMMER SWITCH

WARNING LIGHT/ALARM GUARDIAN 1AP280-235

13.2W

LED

WALL 8120

610mm X 610mm

LED TROFFER

LITHONIA 1

2BLT2-TUWH-RHYR-

20L-ADP

26W LED CEILING 9

A

MVOLT

MVOLT

MVOLT

MVOLT

MVOLT

MVOLT

MVOLT

FIRE ALARM SPEAKER - CEILING MOUNTED UONSP

4'-0" (1219mm)

6" (152 mm) BELOW DROP CEILING.

6" (152 mm) BELOW DROP CEILING.

6" (152 mm) BELOW DROP CEILING.

COORDINATE FINAL MOUNTING HEIGHT WITH MANUFACTURER

COORDINATE FINAL MOUNTING HEIGHT WITH MANUFACTURER

COORDINATE FINAL MOUNTING HEIGHT WITH MANUFACTURER

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-001

GE

NE

RA

L N

OT

ES

,

AB

BR

EV

IA

TIO

NS

, S

YM

BO

LS

,

DE

TA

IL

S, &

S

CH

ED

UL

ES

-

EL

EC

TR

IC

AL

Page 2: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

DISCONNECT & REMOVE EXISTING PANELBOARD. REMOVE CONDUIT AND CONDUCTORS BACK TO

PANEL LDPB2FA.

DISCONNECT AND REMOVE EXISTING CARD READER.

DISCONNECT AND REMOVE EXISTING FUME HOOD.

JUNCTION BOX FOR EXISTING MANIFOLD.

DISCONNECT AND REMOVE EXISTING FCU.

APPROXIMATE ENTRY LOCATION OF EXISTING 2 - 4" CONDUITS FOR IT. CONDUITS ARE FED FROM IT

ROOM B2-3623.

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

2. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHOW INTENT OF DEMOLITION WORK TO BE

DONE. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, EQUIPMENT AND LABOR REQUIRED FOR

A COMPLETE DEMOLITION.

3. UNLESS SPECIFICALLY INDICATED OTHERWISE, REMOVE ALL EXISTING ELECTRICAL EQUIPMENT,

LIGHTING FIXTURES, DEVICES, FEEDERS AND BRANCH CIRCUITRY WHERE EQUIPMENT IS

INDICATED TO BE REMOVED. REMOVE WIRING AND CONDUIT/CABLE BACK TO NEXT REMAINING

ACTIVE OUTLET OR BACK TO SOURCE.

4. ANY SHUTDOWN OF POWER SERVICES SHALL BE COMPLETED AT TIMES OUTSIDE OF NORMAL

WORKING HOURS AS APPROVED BY THE OWNER. PROVIDE A MINIMUM OF 15 BUSINESS DAYS

ADVANCED NOTICE PRIOR TO ANY SHUTDOWN.

5. EXISTING EQUIPMENT INDICATED TO REMAIN ARE TO REMAIN ACTIVE THROUGHOUT

CONSTRUCTION. PROVIDE TEMPORARY FEEDERS IF REQUIRED TO MAINTAIN SERVICE.

6. PROVIDE TEMPORARY SERVICE AS DIRECTED FOR LIGHTING AND POWER EQUIPMENT (DRILLS,

SAWS, ETC.). VERIFY TEMPORARY REQUIREMENTS WITH GENERAL CONTRACTOR. TEMPORARY

LIGHTING AND POWER SHALL MEET OSHA REQUIREMENTS AND LOCAL CODES.

7. LOCATE, IDENTIFY AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREA

AND SERVING OTHER AREAS OUTSIDE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS

OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY

SERVICES FOR AFFECTED AREAS.

8. ADVANCE NOTICE SHALL BE GIVEN TO OWNER BEFORE COMMENCEMENT OF WORK ON ANY

ELECTRICAL CIRCUITRY, WHETHER OR NOT AN OUTAGE IS REQUIRED.

9. PROTECT ADJACENT MATERIALS INDICATED TO REMAIN. INSTALL AND MAINTAIN DUST AND NOISE

BARRIERS TO KEEP DIRT, DUST AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS.

REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE.

10. ALL EXISTING DEVICES MAY NOT BE SHOWN ON PLANS. REMOVE ALL DEVICES ON WALLS SHOWN

TO BE DEMOLISHED.

11. REMOVE ALL DATA/COMMUNICATIONS AND CATV WIRING AND DEVICES WHERE INDICATED.

12. COORDINATE REMOVAL OF DATA/TELEPHONE OUTLETS WITH OWNER AND CIT PRIOR TO

BEGINNING WORK

DEMOLITION GENERAL NOTES

DEMOLITION PLAN NOTES

1

2

3

4

5

6

SURGERY SUITE

B2-3761

RECOVERY

B2-3751

F. LOCKERS

B2-3743

M. LOCKERS

B2-3741

SURGERY CORE

B2-3745

TOILET

B2-3731

LAB

B2-3721

PREP ROOM

B2-3747

INSTRUMENT

ROOM

B2-3753

CORRIDOR

B2-3701

BREAK AREA

B2-3749

CYCLOTRON

ACCESS

B2-3755

MULTI-PURPOSE

LAB

B2-3725

OFFICE

B2-3737

ELECTRICAL

ROOM

B2-5753

OXYGEN

MANIFOLD

B2-3727A

STAIR

S3-7

MECHANICAL

ROOM

B2-5731

HOUSEKEEPING

B2-3733

CORRIDOR

B2-3727

AREA OF WORK

(X)

(X)

PANEL

LPB2FC

PANEL

LPB2FB

1

1

J

J

J

J

J

J

CR

CR

(X) (X)

(X)

(X)

(X)

(X)

(X)

J J

(E)

T T

(E)

(E)

(E)

3

3

CR

PANEL

LSHDPB2FA

(E)

PANEL

SBLPB2FB

(E)

PANEL

HPB2FB

(E)

PANEL

LPB2FD

(E)

PANEL

LDPB2FA

(E)

PANEL

HDPB2FA

(E)

T

(E)

112.5KVA

XFMR

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X) (X)

(X)

(X)

(X)

(X)

(X)(X)(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

J

J

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X) (X)

(X)

(X)

(X)

(X)(X)

(X)

(X)

(X)

J

(X)

J

(X)

J

J

J

(X)

J

(X)

J

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)(X)

(X)

(X)

(X)

(X)

(X)

4

2

2

FACP(E)

(E)

4

J

(X)

5

6

1

PARTIAL B2 LEVEL PLAN - DEMO - POWER

SCALE: 1:50

S.6

T

U

V

W

W.8

W.9

Y

Y.5

Z

BB

CC

D2 B8D1F19F18F17F16

PROJECT

AREA

CO

RR

B2B

100

N

B2 LEVEL

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

KEY PLAN

0M 2M

1:50

1M1M

500MM

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

ED-101

PA

RT

IA

L B

2 F

LO

OR

P

LA

N -

DE

MO

- P

OW

ER

Page 3: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

DISCONNECT AND REMOVE CAV MECHANICAL EQUIPMENT.

APPROXIMATE LOCATION OF 13.8KV FEEDERS RUNNING THROUGH SPACE. FEEDERS ARE EXISTING

TO REMAIN.

DISCONNECT AND REMOVE EXISTING RECEPTACLE. SALVAGE EXISTING CIRCUIT FOR USE IN NEW

WORK.

DEMOLITION PLAN NOTES

1

2

3

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

2. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHOW INTENT OF DEMOLITION WORK TO BE

DONE. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, EQUIPMENT AND LABOR REQUIRED FOR

A COMPLETE DEMOLITION.

3. UNLESS SPECIFICALLY INDICATED OTHERWISE, REMOVE ALL EXISTING ELECTRICAL EQUIPMENT,

LIGHTING FIXTURES, DEVICES, FEEDERS AND BRANCH CIRCUITRY WHERE EQUIPMENT IS

INDICATED TO BE REMOVED. REMOVE WIRING AND CONDUIT/CABLE BACK TO NEXT REMAINING

ACTIVE OUTLET OR BACK TO SOURCE.

4. ANY SHUTDOWN OF POWER SERVICES SHALL BE COMPLETED AT TIMES OUTSIDE OF NORMAL

WORKING HOURS AS APPROVED BY THE OWNER. PROVIDE A MINIMUM OF 15 BUSINESS DAYS

ADVANCED NOTICE PRIOR TO ANY SHUTDOWN.

5. EXISTING EQUIPMENT INDICATED TO REMAIN ARE TO REMAIN ACTIVE THROUGHOUT

CONSTRUCTION. PROVIDE TEMPORARY FEEDERS IF REQUIRED TO MAINTAIN SERVICE.

6. PROVIDE TEMPORARY SERVICE AS DIRECTED FOR LIGHTING AND POWER EQUIPMENT (DRILLS,

SAWS, ETC.). VERIFY TEMPORARY REQUIREMENTS WITH GENERAL CONTRACTOR. TEMPORARY

LIGHTING AND POWER SHALL MEET OSHA REQUIREMENTS AND LOCAL CODES.

7. LOCATE, IDENTIFY AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREA

AND SERVING OTHER AREAS OUTSIDE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS

OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY

SERVICES FOR AFFECTED AREAS.

8. ADVANCE NOTICE SHALL BE GIVEN TO OWNER BEFORE COMMENCEMENT OF WORK ON ANY

ELECTRICAL CIRCUITRY, WHETHER OR NOT AN OUTAGE IS REQUIRED.

9. PROTECT ADJACENT MATERIALS INDICATED TO REMAIN. INSTALL AND MAINTAIN DUST AND NOISE

BARRIERS TO KEEP DIRT, DUST AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS.

REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE.

10. ALL EXISTING DEVICES MAY NOT BE SHOWN ON PLANS. REMOVE ALL DEVICES ON WALLS SHOWN

TO BE DEMOLISHED.

11. REMOVE ALL DATA/COMMUNICATIONS AND CATV WIRING AND DEVICES WHERE INDICATED.

12. COORDINATE REMOVAL OF DATA/TELEPHONE OUTLETS WITH OWNER AND CIT PRIOR TO

BEGINNING WORK

DEMOLITION GENERAL NOTES

D2 B8D1F19F18F17F16.1F16F15.7

T

U

V

V.3

W

W.8

W.9

Y

Y.5

Z

BB

CC

AREA OF WORK

(X)

(X)

(E)

(E)

(E)

2

3

3

J

J

JJ

J

J

(X)

JJ

JJ

(X)(X)

(X)(X)

(X)

(X)

(X)

(X)(X)

1

11

11

1

1

1

11

1

PARTIAL B2 INTERSTITIAL LEVEL PLAN - DEMO - POWER

SCALE: 1:50

PROJECT

AREA

CO

RR

B2B

100

N

B2 LEVEL

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

KEY PLAN

0M 2M

1:50

1M1M

500MM

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

ED-102

PA

RT

IA

L B

1 IN

TE

RS

TIT

IA

L

FL

OO

R P

LA

N - D

EM

O -

PO

WE

R

AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
Page 4: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

DISCONNECT AND REMOVE ALL EXISTING LIGHTING FIXTURES WITHIN AREA OF WORK UNLESS

OTHERWISE NOTED. SALVAGE CIRCUITS FOR CONNECTION UNDER NEW WORK.

DISCONNECT AND REMOVE ALL EXISTING FIRE ALARM DEVICES IN AREA OF WORK BACK TO NEXT

REMAINING FIRE ALARM DEVICE. SALVAGE CIRCUIT FOR CONNECTION UNDER NEW WORK.

APPROXIMATE ENTRY LOCATION OF EXISTING 2 - 4" CONDUITS FOR IT. CONDUITS ARE FED FROM IT

ROOM B2-3623.

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

2. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHOW INTENT OF DEMOLITION WORK TO BE

DONE. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, EQUIPMENT AND LABOR REQUIRED FOR

A COMPLETE DEMOLITION.

3. UNLESS SPECIFICALLY INDICATED OTHERWISE, REMOVE ALL EXISTING ELECTRICAL EQUIPMENT,

LIGHTING FIXTURES, DEVICES, FEEDERS AND BRANCH CIRCUITRY WHERE EQUIPMENT IS

INDICATED TO BE REMOVED. REMOVE WIRING AND CONDUIT/CABLE BACK TO NEXT REMAINING

ACTIVE OUTLET OR BACK TO SOURCE.

4. ANY SHUTDOWN OF POWER SERVICES SHALL BE COMPLETED AT TIMES OUTSIDE OF NORMAL

WORKING HOURS AS APPROVED BY THE OWNER. PROVIDE A MINIMUM OF 15 BUSINESS DAYS

ADVANCED NOTICE PRIOR TO ANY SHUTDOWN.

5. EXISTING EQUIPMENT INDICATED TO REMAIN ARE TO REMAIN ACTIVE THROUGHOUT

CONSTRUCTION. PROVIDE TEMPORARY FEEDERS IF REQUIRED TO MAINTAIN SERVICE.

6. PROVIDE TEMPORARY SERVICE AS DIRECTED FOR LIGHTING AND POWER EQUIPMENT (DRILLS,

SAWS, ETC.). VERIFY TEMPORARY REQUIREMENTS WITH GENERAL CONTRACTOR. TEMPORARY

LIGHTING AND POWER SHALL MEET OSHA REQUIREMENTS AND LOCAL CODES.

7. LOCATE, IDENTIFY AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREA

AND SERVING OTHER AREAS OUTSIDE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS

OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY

SERVICES FOR AFFECTED AREAS.

8. ADVANCE NOTICE SHALL BE GIVEN TO OWNER BEFORE COMMENCEMENT OF WORK ON ANY

ELECTRICAL CIRCUITRY, WHETHER OR NOT AN OUTAGE IS REQUIRED.

9. PROTECT ADJACENT MATERIALS INDICATED TO REMAIN. INSTALL AND MAINTAIN DUST AND NOISE

BARRIERS TO KEEP DIRT, DUST AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS.

REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE.

10. EXISTING LIGHT FIXTURES TO BE REUSED AND RELOCATED SHALL BE CLEANED, RE-LAMPED, AND

REPAIRED.

11. COORDINATE REMOVAL OF DATA/TELEPHONE OUTLETS WITH OWNER AND CIT PRIOR TO

BEGINNING WORK

DEMOLITION GENERAL NOTES

DEMOLITION PLAN NOTES

1

2

3

D2 B8D1F19F18F17F16

ELECTRICAL

ROOM

B2-5753

OXYGEN

MANIFOLD

B2-3727A

STAIR

S3-7

MECHANICAL

ROOM

B2-5731

SURGERY SUITE

B2-3761

RECOVERY

B2-3751

F. LOCKERS

B2-3743

M. LOCKERS

B2-3741

SURGERY CORE

B2-3745

TOILET

B2-3731

LAB

B2-3721

PREP ROOM

B2-3747

INSTRUMENT

ROOM

B2-3753

CORRIDOR

B2-3701

BREAK AREA

B2-3749

CYCLOTRON

ACCESS

B2-3755

MULTI-PURPOSE

LAB

B2-3725

OFFICE

B2-3737

HOUSEKEEPING

B2-3733

CORRIDOR

B2-3727

AREA OF WORK

1

S(X)

1

2

2

S(E)

(E)

(E)

AV

F

AV

AV

AV

AV

AV

AVAV

AV

AV

AV

AV

AV

AV

OS

OS

SP

SP

SPSP

SP

SP

SP AV

3

1

PARTIAL B2 LEVEL PLAN - DEMO - LIGHTING & FIRE ALARM

SCALE: 1:50

T

U

V

W

W.8

W.9

Y

Y.5

Z

BB

CC

S.6

PROJECT

AREA

CO

RR

B2B

100

N

B2 LEVEL

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

KEY PLAN

0M 2M

1:50

1M1M

500MM

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

ED-201

PA

RT

IA

L B

2 F

LO

OR

P

LA

N -

DE

MO

- L

IG

HT

IN

G &

F

IR

E

AL

AR

M

Page 5: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE. SALVAGE EXISTING CONDUIT AND

CONDUCTORS FOR USE IN NEW WORK.

DISCONNECT AND REMOVE EXISTING EMERGENCY LIGHT FIXTURE. SALVAGE EXISTING CONDUIT

AND CONDUCTORS FOR USE IN NEW WORK.

APPROXIMATE LOCATION OF 13.8KV FEEDERS RUNNING THROUGH SPACE. FEEDERS ARE EXISTING

TO REMAIN.

DISCONNECT AND REMOVE EXISTING RECEPTACLE. SALVAGE EXISTING CIRCUIT FOR USE IN NEW

WORK.

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

2. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHOW INTENT OF DEMOLITION WORK TO BE

DONE. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, EQUIPMENT AND LABOR REQUIRED FOR

A COMPLETE DEMOLITION.

3. UNLESS SPECIFICALLY INDICATED OTHERWISE, REMOVE ALL EXISTING ELECTRICAL EQUIPMENT,

LIGHTING FIXTURES, DEVICES, FEEDERS AND BRANCH CIRCUITRY WHERE EQUIPMENT IS

INDICATED TO BE REMOVED. REMOVE WIRING AND CONDUIT/CABLE BACK TO NEXT REMAINING

ACTIVE OUTLET OR BACK TO SOURCE.

4. ANY SHUTDOWN OF POWER SERVICES SHALL BE COMPLETED AT TIMES OUTSIDE OF NORMAL

WORKING HOURS AS APPROVED BY THE OWNER. PROVIDE A MINIMUM OF 15 BUSINESS DAYS

ADVANCED NOTICE PRIOR TO ANY SHUTDOWN.

5. EXISTING EQUIPMENT INDICATED TO REMAIN ARE TO REMAIN ACTIVE THROUGHOUT

CONSTRUCTION. PROVIDE TEMPORARY FEEDERS IF REQUIRED TO MAINTAIN SERVICE.

6. PROVIDE TEMPORARY SERVICE AS DIRECTED FOR LIGHTING AND POWER EQUIPMENT (DRILLS,

SAWS, ETC.). VERIFY TEMPORARY REQUIREMENTS WITH GENERAL CONTRACTOR. TEMPORARY

LIGHTING AND POWER SHALL MEET OSHA REQUIREMENTS AND LOCAL CODES.

7. LOCATE, IDENTIFY AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREA

AND SERVING OTHER AREAS OUTSIDE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS

OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY

SERVICES FOR AFFECTED AREAS.

8. ADVANCE NOTICE SHALL BE GIVEN TO OWNER BEFORE COMMENCEMENT OF WORK ON ANY

ELECTRICAL CIRCUITRY, WHETHER OR NOT AN OUTAGE IS REQUIRED.

9. PROTECT ADJACENT MATERIALS INDICATED TO REMAIN. INSTALL AND MAINTAIN DUST AND NOISE

BARRIERS TO KEEP DIRT, DUST AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS.

REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE.

10. ALL EXISTING DEVICES MAY NOT BE SHOWN ON PLANS. REMOVE ALL DEVICES ON WALLS SHOWN

TO BE DEMOLISHED.

11. REMOVE ALL DATA/COMMUNICATIONS AND CATV WIRING AND DEVICES WHERE INDICATED.

12. REMOVE ALL FIRE ALARM WIRING AND DEVICES UNLESS OTHERWISE NOTED.

13. COORDINATE REMOVAL OF DATA/TELEPHONE OUTLETS WITH OWNER AND CIT PRIOR TO

BEGINNING WORK

DEMOLITION GENERAL NOTES

DEMOLITION PLAN NOTES

1

2

3

4

D2 B8D1F19F18F17F16.1F16F15.7

T

U

V

V.3

W

W.8

W.9

Y

Y.5

Z

BB

CC

AREA OF WORK

S(X)

F

(X)

(X)

(X)

AV

(X)

110

(X)

(X)

(X)(X)

AV

(E)

110

(X)

(X)

AV

(E)

15

(X)

(X)

(X) (X)

(X)

(E)

(E)

(E)

1

1

1

1

1

12

2

2

2

2

3

S(E

)

4

4

1

PARTIAL B2 INTERSTITIAL LEVEL PLAN - DEMO - LIGHTING & FIRE ALARM

SCALE: 1:50

PROJECT

AREA

CO

RR

B2B

100

N

B2 LEVEL

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

KEY PLAN

0M 2M

1:50

1M1M

500MM

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

ED-202

PA

RT

IA

L B

1 IN

TE

RS

TIT

IA

L

FL

OO

R P

LA

N - D

EM

O -

LIG

HT

IN

G &

F

IR

E A

LA

RM

AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
Page 6: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

2. ALL EQUIPMENT SHOWN SHALL BE NEW UON.

3. REFERENCE SHEET E-601 & E-602 FOR PANEL SCHEDULES AND ONE LINE DIAGRAM.

4. ALL NEW LOW-VOLTAGE WIRING MUST BE IN CONDUIT PER THE DRM. GREENFIELD IS APPROVED.

5. ENSURE ALL EQUIPMENT WITHIN 6FT (1829MM) OF EMERGENCY SHOWER IS WEATHERPROOF PER

NIH DRM 10.5.3.B.13.

NEW WORK GENERAL NOTES

1

2

PROVIDE ELECTRICAL CONNECTION TO NEW SURFACE METAL RACEWAY. CONNECT

RECEPTACLES TO ALTERNATING CIRCUITS WITH NO MORE THAN FOUR (4) RECEPTACLES PER

CIRCUIT.

PROVIDE NEW EQUIPMENT GROUNDING BAR. SEE DETAIL 9 ON SHEET E-501. PROVIDE

INDIVIDUAL GROUND FEED BACK TO MAIN GROUNDING BAR IN MAIN ELECTRICAL VAULT.

PROVIDE ELECTRICAL CONNECTION TO 2.5KVA, 208V:230V BUCK-BOOST TRANSFORMER.

PROVIDE DATA PORT FOR REES SYSTEM. RUN 3/4" CONDUIT FROM DATA PORT BACK TO REES

CONTROL PANEL LOCATED IN ROOM B2-3721.

PROVIDE ELECTRICAL CONNECTION TO ELECTRON MICROSCOPE.

REES SYSTEM CONTROL PANEL.

PROVIDE ELECTRICAL CONNECTION TO NEW FUME HOOD.

JUNCTION BOX FOR GAS MANIFOLD.

PROVIDE NEW RECEPTACLE FOR AUTOMATIC CHANGE OVER MANIFOLD(CACM). MOUNT

RECEPTACLE AT 48"(1219MM) AFF.

THIS AREA SHALL MEET LOW EMI REQUIREMENTS AS DEFINED BY THE EMI DESIGNER.

COORDINATE ANY ADDITIONAL ITEMS WITH THE EMI DESIGNER.

DEDICATED RECEPTACLE FOR BIOSAFETY CABINET.

APPROXIMATE ENTRY LOCATION OF EXISTING 2 - 4" CONDUITS FOR IT. CONDUITS ARE FED FROM

IT ROOM B2-3623.

PROVIDE NEW CABLE TRAY. PROPERLY GROUND CABLE TRAY TO INCOMING IT CONDUITS.

PROVIDE ELECTRICAL CONNECTION TO NEW EMS PANEL.

PROVIDE ELECTRICAL CONNECTION TO NEW BAS PANEL. COORDINATE WITH NIH CIT. CIT TO

PROVIDE FACNET DROP FOR NEW BAS PANEL. SEE MECHANICAL DRAWINGS FOR MORE

INFORMATION

3

NEW WORK PLAN NOTES

4

5

6

7

8

9

LOW EMI REQUIREMENTS

1. ALL ELECTRICAL CIRCUITS RATED BELOW 100A SHOULD BE INSTALLED IN EMT CONDUIT.

2. LIGHTING SHALL BE LED TYPE. NO PULSE-WIDTH MODULATION (PWM) BALLASTS OR PWM DIMMING

IS ALLOWED.

3. LIGHTING FIXTURES SHALL BE SERVED BY A DEDICATED CIRCUIT WITH A DEDICATED NEUTRAL.

10

11

12

13

CABLE MANAGEMENT SYSTEM REQUIREMENTS

1. CABLE MANAGEMENT SYSTEM OR CABLE TRAY SHALL BE COMPRISED OF A CONTINUOUS RIGID

WELDED STEEL WIRE MESH CABLE MANAGEMENT SYSTEM WITH CONTINUOUS SAFETY EDGE WIRE

WELDED TO THE TOP OF THE TRAY, AND WIRE MESH WELDED AT ALL INTERSECTIONS. THE CABLE

TRAY SYSTEM SHALL BE OF A “BASKET” TYPE CONSTRUCTION, RIGID TYPE CABLE TRAY WILL NOT

BE ACCEPTED.

2. CABLE MANAGEMENT SYSTEM FINISH SHALL BE ELECTROPLATED ZINC GALVANIZING (STANDARD

STOCK FINISH) FOR MOST INDOOR APPLICATIONS AND SHALL BE USED OUTDOORS IN MILD

ENVIRONMENTS ONLY. HOT DIP GALVANIZING IS SHALL BE USED FOR OUTDOOR APPLICATIONS OR

ENVIRONMENTS WHERE INCREASED CORROSION RESISTANCE IS REQUIRED/DESIRED.

3. CABLE MANAGEMENT SYSTEMS SIZING SHALL BE NO SMALLER THAN 100 MM (4 IN.) DEEP X 455 MM

(18 IN) WIDE. THE FINAL DETERMINATION OF DEPTH, WIDTH AND LAYOUT DESIGN SHALL BE

COORDINATED WITH AND APPROVED BY CIT. CABLE TRAY SHALL HAVE A MINIMUM OF 150 MM (6 IN.)

OF CLEARANCE ON ALL SIDES FOR ACCESS BY THE CABLING CONTRACTOR.

4. THE CABLE MANAGEMENT SYSTEM SHALL BE INSTALLED USING HARDWARE, SPLICE CONNECTORS,

SUPPORT COMPONENTS AND ACCESSORIES FURNISHED BY THE MANUFACTURER. ALL TURNS AND

“WATERFALLS” SHALL BE OF MANUFACTURED PRODUCTS. ALL CUTTING OF THE CABLE

MANAGEMENT SYSTEM SHALL BE PERFORMED USING MANUFACTURER RECOMMENDED CUTTING

TECHNIQUES AND CUTTING TOOLS.

14

15

CO2 MANIFOLD

B2-3727A

D2 B8D1F19F18F17F16 D4

T

U

V

W

W.8

W.9

Y

Y.5

Z

BB

CC

FH-5C

FH-5B

FH

-5

A

AREA OF WORK

LPB2FC-9

LPB2FB-2,4

LPB2FB-2,4

LPB2FB-11,13

J

LPB2FB-1 LPB2FB-3

J

J

J

J

J

J

J

J

J

CR

J

+1118

G

(N)

(N)

(N)

(N)

LPB2FC-39

LPB2FC-39

LPB2FC-39

LPB2FC-39

J J

(E)

(E)

PANEL

LPB2FB

PANEL

LPB2FC

PANEL

LSHDPB2FA

(E)

PANEL

SBLPB2FB

(E)

PANEL

HPB2FB

(E)

PANEL

LPB2FD

(E)

PANEL

LDPB2FA

(E)

PANEL

HDPB2FA

(E)

T

(E)

112.5KVA

XFMR

+1118

+1118

SBLPB2FB-17

SBLPB2FB-17

LPB2FB-9,7

LPB2FB-9,7

LPB2FB-9

LPB2FB-9

+1067

+1067

+1067

LPB2FB-10

LPB2FB-12

GG

+1067

LPB2FC-14,

16, 18

LPB2FC-8,10,12

LPB2FC-26,28,30

LPB2FC-20,22,24

LPB2FB-2,4

LPB2FB-2

LPB2FB-6,8

LPB2FB-6,8

LPB2FC-1,3,5

L15-20

(N) (N)

FACP(E)

LPB2FB-2

+1118

LPB2FB-9

LPB2FB-6

LPB2FB-10

+1829

+1829

+1016

LPB2FC-2,4,6

+1936

+1524

+1524

(E)

LPB2FB-14

LPB2FB-16

LPB2FB-16

LPB2FB-18

+1524

+1524

LPB2FC-32

L6-15

+1118

+1118

+1118

+1118

+1118

LPB2FC-7

LPB2FC-7

LPB2FC-9

LPB2FC-11

LPB2FC-9

G

G

G

LPB2FC-11

LPB2FC-11

+1118

30

SBLPB2FB-19

30

SBLPBF2B-21

30

SBLPBF2B-20

+1118

+1936

LPB2FC-13

+1118

+1118

+1118

+1118

+1118

LPB2FC-46

LPB2FC-46

LPB2FC-46

LPB2FC-48LPB2FC-50

LPB2FC-58

LPB2FC-58

LPB2FC-60

G

G

G

CC

1

1

1

1

1

LPB2FC-52,54,56

1

C

C

C

LPBF2C-62

LPBF2C-62

+1067

+1067

LPB2FC-64

LPB2FC-61

22

J

60/40

LPB2FB-15,17

LPB2FB-20,22

LPB2FB-24

L6-20

60/30

L6-30

LPB2FB-26,28

LPB2FB-24

2 2

60/30

L6-30

LPB2FB-30,32

LPB2FC-66

LPB2FC-66

60/30

L6-30

LPB2FB-34,36

T

3

LPB2FB-37

LPB2FC-70 LPB2FC-68

RC

P

4

4

LPB2FB-39

LPB2FB-39

LPB2FB-41

LPB2FB-41

LPB2FB-38

LPB2FB-38

LPB2FB-40

LPB2FB-40

LPB2FB-40

LPB2FB-40

LPB2FB-40

FUTURE EM

B2-3711

FIB SEM

B2-3710

EM EQUIP

B2-3713

TEM

B2-3715

EM EQUIP

B2-3712

FIB SEM 02

B2-3714

CRYO CUTTING

B2-3716

CUTTING

B2-3717

MICROSCOPY

B2-3719

OFFICE

B2-3721

ENTRY

VESTIBULE

B2-3723

PREP LAB

B2-3725

SHARED OFFICE

B2-3722

CYCLOTRON

ACCESS

B2-3722A

TISSUE CULTURE

B2-3737

CORRIDOR

B2-3723A

6

7

7

7

14

16

18

14

8

10

12

8

26 28 30

20222420

52 54

56

2

4

62

4

6464

61 61 61

5

LPB2FB-40

LPB2FB-40

T T(E)(E)

CR

(N)

LPB2FB-24

LPB2FC-66

8

8

LPB2FB-40

LPB2FC-63

LPB2FC-63

LPB2FB-43

LPB2FB-43

9

9

(E)

MAIN

GROUNDING

BAR

2

10

11 11

LPB2FB-21

LPB2FB-19

12

(N)

13

(N)

(N)

(N)

(N)

(N)

J

J

14

15

SBLPB2FB-22

SBLPB2FB-24

1

PARTIAL B2 FLOOR PLAN - NEW WORK - POWER

SCALE: 1:50

PROJECT

AREA

CO

RR

B2B

100

N

B2 LEVEL

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

KEY PLAN

0M 2M

1:50

1M1M

500MM

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-101

PA

RT

IA

L B

2 F

LO

OR

P

LA

N -

NE

W W

OR

K - P

OW

ER

Page 7: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

2. ALL EQUIPMENT SHOWN SHALL BE NEW UON.

3. REFERENCE SHEET E-601 & E-602FOR PANEL SCHEDULES AND ONE LINE DIAGRAM.

4. MECHANICAL EQUIPMENT TO BE LOCATED IN THE INTERSTITIAL SPACE ABOVE.

1

2

PROVIDE ELECTRICAL CONNECTION FOR NEW DUCT HEATER.

PROVIDE ELECTRICAL CONNECTION FOR NEW FAN COIL UNIT.

PROVIDE ELECTRICAL CONNECTION FOR NEW DEHUMIDIFIER.

APPROXIMATE ROUTING OF EXISTING 13.2KV FEEDERS.

DEDICATED RECEPTACLE FOR PUMP CP-A. MOUNT ABOVE DROP CEILING. COORDINATE FINAL

MOUNTING HEIGHT WITH MECHANICAL CONTRACTOR.

3

NEW WORK PLAN NOTES

NEW WORK GENERAL NOTES

4

5

AREA OF WORK

FCU-2

DH-2

FCU-1

DH-1

FCU-3

DH-3

EDH-3

EDH-2

EDH-5

EDH-1

EDH-6

EDH-4

J

30/20

J

30/15

J

30/15

J

30/15

J

30/20

J

30/15

J

30/15

J

30/15

J

30/15

J

30/15

J

30/15

J

30/20

LPB2FC-15,17,19

LPB2FC-21,23,25

LPB2FC-27,29,31

LPB2FC-42,44

LPB2FC-34,36

LPB2FC-38,40

HPB2FB-7,9,11

HPB2FB-13,15,17

HPB2FB-14,16,18

HPB2FB-19,21,23

HPB2FB-20,22,24

HPB2FB-25,27,29

1

1

1

1

1

1

2

2

2

3

3

3

4

5

LPB2FC-65

1

PARTIAL B2 INTERSTITIAL FLOOR PLAN - NEW WORK - MECHANICAL POWER

SCALE: 1:50

PROJECT

AREA

CO

RR

B2B

100

N

B2 LEVEL

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

KEY PLAN

0M 2M

1:50

1M1M

500MM

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-102

PA

RT

IA

L B

1 IN

TE

RS

TIT

IA

L

FL

OO

R P

LA

N - N

EW

W

OR

K -

ME

CH

AN

IC

AL

P

OW

ER

Page 8: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

2. ALL EQUIPMENT SHOWN SHALL BE NEW UON.

3. REFERENCE SHEET E-601 FOR PANEL SCHEDULES AND ONE LINE DIAGRAM.

4. SEE SHEET E-101 FOR PANEL LOCATION.

5. SWITCHES CONTROL LIGHTING IN SAME ROOM UON.

6. NEW FA DEVICES SHALL BE CONNECTED TO EXISTING FA CIRCUIT SALVAGED DURING DEMOLITION.

7. FOR LIGHT FIXTURE AND OCCUPANCY SCHEDULES SEE SHEET E-001.

1

2

CONNECT LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT SALVAGED DURING DEMOLITION.

NORMAL LIGHTING CIRCUIT IS FED FROM PANEL HDB2FB CKT 2.

EMERGENCY LIGHTING FIXTURE. CONNECT TO EMERGENCY LIGHTING CIRCUIT SALVAGED

DURING DEMOLITION. EMERGENCY LIGHTING CIRCUIT IS FED FROM PANEL LSHPB2FA, FED FROM

EXISTING EMERGENCY GENERATOR AND ATS. SEE DETAIL 4 ON SHEET E-502.

EMERGENCY EXIT SIGN. CONNECT TO EMERGENCY LIGHTING CIRCUIT SALVAGED DURING

DEMOLITION. CONNECT EXIT SIGN AHEAD OF ALL LOCAL SWITCHING.

THIS AREA SHALL MEET LOW EMI REQUIREMENTS AS DEFINED BY THE EMI DESIGNER.

COORDINATE ANY ADDITIONAL ITEMS WITH THE EMI DESIGNER. SEE SHEET E101 FOR EMI

REQUIREMENTS.

CONNECT NEW GAS WARNING LIGHT TO CIRCUIT 42 IN PANEL LPB2FB

PROVIDE TUNABLE WHITE WALL SWITCHES AS RECOMMENDED BY LIGHT MANUFACTURER.

SWITCHES SHALL CONTROL CCT LEVEL AND ON/OFF FOR LIGHT FIXTURES.

CONNECT LIGHT FIXTURE TO NORMAL LIGHTING CIRCUIT IS FED FROM PANEL HPB2FB CKT 6.

EMERGENCY LIGHTING FIXTURE. CONNECT TO AVAILABLE EMERGENCY LIGHTING CIRCUIT FED

FROM PANEL LSHPB2FA, FED FROM EXISTING EMERGENCY GENERATOR AND ATS. SEE DETAIL 4

ON SHEET E-502. CIRCUIT SHALL NOT EXCEED 16AMPS.

CONNECT UNDERCABINET LIGHT FIXTURE TO 120V CIRCUIT FEEDING SURFACE METAL RACEWAY.

SEE DETAIL 2 ON SHEET 502.

3

NEW WORK PLAN NOTES

NEW WORK GENERAL NOTES

EXISTING NORMAL LIGHTING FIXTURE LOAD:

1'X4' FIXTURES: 17 X (32W X 2 LAMPS) = 1,088W

2'X4' FIXTURES: 4 X (32W X 3 LAMPS) = 384W

2'X2' FIXTURES: 3 X (31W X 2 LAMPS) = 186W

50W DOWNLIGHTS 6 X 50W = 300W

52W DOWNLIGHTS 38 X 52W = 1,976W

24W DOWNLIGHTS 12 X 24W = 288W

TOTAL REMOVED NORMAL LIGHTING LOAD = 4,222W

EXISTING EMERGENCY LIGHTING LOADS:

1'X4' FIXTURES: 18 X (32W X 2 LAMPS) = 1,152W

2'X4' FIXTURES: 2 X (32W X 3 LAMPS) = 192W

2'X2' FIXTURES: 1 X (31W X 2 LAMPS) = 62W

50W DOWNLIGHTS 2 X 50W = 100W

52W DOWNLIGHTS 9 X 52W = 468W

24W DOWNLIGHTS 3 X 24W = 72W

TOTAL REMOVED EMERGENCY LIGHTING LOAD = 2,046W

NEW NORMAL LIGHTING LOAD:

1'X4' LED FIXTURE: 23 X 35W = 805W

2'X2' LED FIXTURE: 28 X 26W = 728W

2'X4' LED FIXTURE: 2 X 31W = 62W

TOTAL NEW NORMAL LIGHTING LOAD = 1,700W

NEW EMERGENCY LIGHTING LOAD:

1'X4' LED FIXTURE: 8 X 35W = 280W

2'X2' LED FIXTURE: 8 X 26W = 208W

2'X4' LED FIXTURE: 1 X 31W = 31W

TOTAL NEW EMERGENCY LIGHTING LOAD = 554W

NEW LIGHTING LOADS ARE LESS THAN EXISTING

LIGHTING LOAD CALCULATION

4

5

6

7

8

9

D2 B8D1F19F18F17F16 D4

T

U

V

V.3

W

W.8

W.9

Y

Y.5

Z

BB

CC

AREA OF WORK

SOC

OS

SO

C

SO

C

(E)

SOC

SD

p

SDr

SD

m

OS

Sa

S3c

Sb

a a

a

b b b

a,b

S3d

S3c

S3d

d d

c c c c

c c c

d

d

OS

OS

e e

f

e e f

f

e

f

Sf

g

h

h

g

Sg

Sh

g,h

3

3

3

3

3

121

1

1

1

2

2 1

11

1 2 1 11 21

1

11

2

1 1 1

1 2 1

3

1

1

2 1

11

SDq

1 1

21

87

7 7

7 8

77

7 7

87

7 8

77

7 7

77

77

7 7

7

7

7 1

1

2

8

1

2

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

AV

15

V

15

AV

15

FUTURE EM

B2-3711

FIB SEM

B2-3710

EM EQUIP

B2-3713

TEM

B2-3715

EM EQUIP

B2-3712

FIB SEM 02

B2-3714

CRYO CUTTING

B2-3716

CUTTING

B2-3717

MICROSCOPY

B2-3719

OFFICE

B2-3721

ENTRY

VESTIBULE

B2-3723

PREP LAB

B2-3725

SHARED OFFICE

B2-3722

CYCLOTRON

ACCESS

B2-3722A

TISSUE CULTURE

B2-3737

CO2 MANIFOLD

B2-3727A

(E) S(E)

LPB2FC-41

LPB2FC-41

LPB2FC-41

LPB2FC-41

87

SDs

SDj

SDk

SDh

S3e

S3e

mp

m m

mm

p p

pp

AV

15

3

CORRIDOR

B2-3723A

9 9 9

9 9 9

9 9 9 9

9 9

9 9 9 9 9

9 9 9 9

9

9

9

9

9

9

9

9

9

9

9

9

9

9

9 9

h h h

j

j

k

kk

kk

q q

qq

q

q

r

rr

r

s s

s s

5

5

5

5

5

A A A

A A A

A

A

A

A

A

A

A

A A

AA

6

6

6

6

6

6

4

1

PARTIAL B2-LEVEL FLOOR PLAN - NEW WORK - LIGHTING & FIRE ALARM

1:50

PROJECT

AREA

CO

RR

B2B

100

N

B2 LEVEL

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

KEY PLAN

0M 2M

1:50

1M1M

500MM

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-201

PA

RT

IA

L B

2 F

LO

OR

P

LA

N -

NE

W W

OR

K - L

IG

HT

IN

G &

FIR

E A

LA

RM

Page 9: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

Calculation Summary

Label CalcType UnitsAvg Max

Min Avg/Min Max/Min

Corridor_Workplane IlluminanceFc 24.86 29.9 17.6 1.41 1.70

Cryo Cutting_Workplane IlluminanceFc 26.32 38.4 16.9 1.56 2.27

Cutting_Workplane IlluminanceFc 35.15 47.1 19.9 1.77 2.37

EM Equip 1_Workplane IlluminanceFc 39.08 48.4 28.4 1.38 1.70

EM Equip 2_Workplane IlluminanceFc 41.18 47.8 32.7 1.26 1.46

Entry Vestibule_Workplane IlluminanceFc 34.11 49.5 9.9 3.45 5.00

Future EM_Workplane IlluminanceFc 22.42 30.3 9.8 2.29 3.09

Microscopy_Workplane IlluminanceFc 47.70 62.4 24.3 1.96 2.57

Office_Workplane IlluminanceFc 40.82 45.9 32.3 1.26 1.42

Prep Lab_Workplane IlluminanceFc 31.47 53.2 11.0 2.86 4.84

SEM Suite_Workplane IlluminanceFc 34.19 45.5 14.1 2.42 3.23

Shared Office_Workplane IlluminanceFc 37.69 47.0 16.0 2.36 2.94

TEM_Workplane IlluminanceFc 23.72 31.1 16.2 1.46 1.92

Tissue Culture_Workplane IlluminanceFc 35.96 53.8 20.4 1.76 2.64

Calculation Summary

Label CalcType UnitsAvg Max

Min Avg/Min Max/Min

Corridor_Workplane IlluminanceFc 24.84 29.9 17.6 1.41 1.70

Cryo Cutting_Workplane IlluminanceFc 40.69 112 17.4 2.34 6.42

Cutting_Workplane IlluminanceFc 55.94 123 23.1 2.42 5.30

EM Equip 1_Workplane IlluminanceFc 39.26 48.6 28.5 1.38 1.71

EM Equip 2_Workplane IlluminanceFc 41.38 48.0 32.8 1.26 1.46

Entry Vestibule_Workplane IlluminanceFc 34.16 49.6 9.8 3.49 5.06

Future EM_Workplane IlluminanceFc 28.50 101 9.9 2.88 10.18

Microscopy_Workplane IlluminanceFc 64.32 120 26.3 2.45 4.58

Office_Workplane IlluminanceFc 40.75 45.8 32.3 1.26 1.42

Prep Lab_Workplane IlluminanceFc 38.20 113 11.4 3.35 9.92

SEM Suite_Workplane IlluminanceFc 34.30 45.5 14.1 2.43 3.23

Shared Office_Workplane IlluminanceFc 37.88 47.2 16.2 2.34 2.91

TEM_Workplane IlluminanceFc 28.16 112 16.4 1.72 6.83

Tissue Culture_Workplane IlluminanceFc 38.95 74.8 20.7 1.88 3.61

LIGHTING CALCULATION WITHOUT UNDERCABINET LIGHTING

LIGHTING CALCULATION WITH UNDERCABINET LIGHTING

D2 B8D1F19F18F17F16

AREA OF WORK

FUTURE EM

B2-3711

FIB SEM

B2-3710

EM EQUIP

B2-3713

TEM

B2-3715

EM EQUIP

B2-3712

FIB SEM 02

B2-3714

CRYO CUTTING

B2-3716

CUTTING

B2-3717

MICROSCOPY

B2-3719

OFFICE

B2-3721

ENTRY

VESTIBULE

B2-3723

PREP LAB

B2-3725

SHARED OFFICE

B2-3722

CYCLOTRON

ACCESS

B2-3722A

TISSUE CULTURE

B2-3737

CO2 MANIFOLD

B2-3727A

CORRIDOR

B2-3723A

17.6 23.4 24.5 22.4 23.0 26.1 26.0 23.2 23.5 26.3 26.1 23.0 22.8 24.8 22.9

20.1 27.0 28.2 25.2 25.9 29.9 29.7 26.0 26.2 29.9 29.7 25.9 25.8 29.0 27.5

17.6 23.5 24.7 22.6 23.1 26.1 26.1 23.3 23.3 26.0 25.9 23.0 23.0 25.2 23.8

16.9 25.3 31.5 26.3 16.9

19.8 30.4 38.2 31.3 19.9

20.7 30.8 37.7 31.5 20.7

20.2 30.5 38.4 31.5 20.1

17.0 25.8 32.4 26.9 17.2

22.9 31.5 34.2 33.2 33.9 30.3 21.8

28.8 40.9 44.0 41.8 44.2 39.7 27.4

30.8 43.0 46.7 45.0 47.1 42.5 29.8

30.3 42.8 46.4 44.4 46.7 42.4 29.6

27.0 38.0 41.2 39.2 41.2 37.5 26.3

20.4 27.4 30.0 29.4 29.8 26.9 19.9

30.3 37.7 40.0 37.4 29.8

35.7 44.3 46.9 43.8 35.1

37.0 45.7 48.4 45.2 36.4

36.9 45.6 48.3 45.1 36.2

34.7 43.1 45.8 42.8 34.3

28.6 35.6 37.9 35.4 28.4

33.1 37.8 37.7 32.7

39.8 45.3 45.2 39.4

41.8 47.6 47.4 41.4

42.0 47.8 47.6 41.4

40.5 46.3 46.2 40.1

34.2 39.4 39.4 34.2

32.9 35.1 31.4 30.5 33.4 32.0 24.3

42.7 45.1 38.7 37.3 42.3 41.0 30.4

47.0 49.5 42.4 40.4 45.5 44.1 32.5

46.3 48.9 41.7 38.8 43.0 41.1 29.8

42.1 44.4 38.0 33.4 34.6 32.0 23.0 14.5

40.5 42.3 35.2 27.7 23.8 21.0 16.4 11.9

41.8 43.5

39.7 40.2

38.4 39.1

39.4 40.4

36.4 37.6

9.9 18.4 34.0 35.6

12.4 22.3 32.9 34.8

12.0 18.9 26.6 28.2

9.8 13.6 17.0 18.8 16.0 23.1 23.0 19.6

11.4 16.1 22.0 26.1 26.7 26.4 27.7 28.0 24.2

12.3 17.5 24.2 29.0 29.4 28.8 30.0 30.3 26.0

12.4 17.6 24.4 29.1 29.5 28.8 30.0 30.2 26.0

11.6 16.3 22.4 26.7 27.0 26.5 27.6 27.7 23.9

10.0 13.9 18.5 21.8 22.4 22.1 22.8 22.6 19.4

38.8 49.1 50.2 50.5 50.2 40.6

46.3 57.3 58.3 58.8 59.1 47.9

46.8 58.9 60.4 61.7 62.4 50.8

44.0 55.1 57.6 60.3 62.0 50.6

40.0 49.4 52.4 56.0 57.8 47.3

38.1 47.2 48.0 48.4 49.0 40.1

32.9 40.8 40.3 37.4 35.2

24.3 28.8 30.1 25.1

33.4 41.3 41.1 41.2 40.9 32.3

36.6 45.2 45.2 45.1 44.9 36.1

36.1 44.1 44.9 44.9 43.9 35.7

36.7 45.5 45.8 45.9 45.5 36.5

33.6 42.1 42.3 42.2 42.0 33.5

14.5 19.1 23.7 24.6 19.9 14.2

21.3 27.6 36.0 37.6 28.2 18.5

30.9 38.1 46.4 46.9 34.4 22.0

28.3 40.3 47.7 53.2 51.8 37.6 23.9

27.7 39.4 46.9 53.0 51.9 37.8 24.3

21.1 29.3 37.6 48.6 48.8 35.9 23.3

19.9 28.6 41.2 41.9 32.4 20.4

14.1 18.2 35.3 38.0 30.0 18.6 22.3 25.2 25.8 25.5 24.3 22.0 18.2 13.4

19.6 29.3 35.7 38.4 43.8 42.6 39.3 32.3 33.8 36.2 37.9 38.3 37.7 36.1 32.9 26.8 18.3

23.8 36.9 45.1 50.0 50.7 49.3 45.0 40.3 42.4 46.3 48.6 49.0 48.4 46.5 42.7 34.4 21.7

21.9 32.6 39.8 44.1 44.6 43.4 39.8 36.3 39.1 41.8 43.7 44.2 43.7 41.9 38.2 30.9 20.2

16.4 22.4 27.4 30.0 30.6 30.0 28.2 26.7 27.5 28.7 29.8 30.1 29.7 28.3 25.6 21.0 15.2

12.0 15.8 19.0 20.8 21.2 21.0 20.4 19.9 19.7 19.5 20.1 20.2 19.8 18.8 17.0 14.2 11.0

19.7 23.8 25.9 26.2 25.4 22.7 18.0

24.8 30.1 32.7 33.1 32.2 28.5 22.6

28.7 35.2 38.1 38.5 37.6 33.1 26.0

31.4 38.3 41.5 41.9 40.7 35.9 28.1

32.9 40.0 43.2 43.5 42.3 37.1 29.2

33.5 40.4 43.6 43.9 42.4 37.1 29.6

33.8 40.7 43.8 44.1 42.4 36.7 27.8 14.1

34.4 41.6 44.7 44.9 43.2 37.1 27.8 18.7

34.7 42.0 45.2 45.5 43.8 37.8 28.2 14.9

34.3 41.5 44.7 45.0 43.5 38.1 30.2

33.0 40.0 43.1 43.4 42.1 37.2 29.1

31.1 37.6 40.5 40.9 39.7 35.2 27.8

29.0 35.2 38.0 38.3 37.3 33.2 26.2

26.0 31.7 34.2 34.5 33.8 30.0 23.4

21.4 26.1 28.2 28.6 27.9 24.9 19.3

28.1 34.7 35.6 36.7 38.6 36.9 36.0 35.6 28.9

34.0 42.5 43.2 44.1 46.7 44.1 42.7 42.8 34.8

34.6 43.0 44.2 45.0 47.0 44.7 43.1 42.2 34.8

34.8 43.2 44.4 45.2 46.9 44.5 42.9 42.1 34.6

34.0 43.1 43.9 44.7 46.5 43.1 41.4 41.4 33.9

27.5 35.0 36.6 38.3 37.6 34.7 33.5 33.1 27.5

16.0 23.1 23.3 23.0 19.3

17.7 21.0 20.7 18.0 16.2 17.0 20.6 24.5 22.9

21.1 25.2 24.8 21.5 19.6 20.9 25.4 30.4 28.1

22.6 27.2 27.1 24.3 23.6 26.0 28.7 29.8 26.0

22.3 26.9 27.3 25.5 26.9 31.1 30.8 25.9 20.4

20.3 24.5 25.0 24.0 26.4 30.7 28.9 22.1

16.6 19.9 20.6 19.7 23.7 22.2 17.2

21.4 27.5 32.0 34.3 34.0 31.3 26.4 20.4

28.1 37.0 43.8 47.0 46.7 42.9 35.6 26.6

31.4 42.2 50.2 53.8 53.6 49.3 40.7 29.8

28.7 37.9 44.8 48.0 47.8 44.2 36.8 27.5

22.1 28.5 33.2 35.5 35.3 32.8 27.8 21.4

1

PARTIAL B2-LEVEL FLOOR PLAN - LIGHTING CALCULATION

1:50

T

U

V

W

W.8

W.9

Y

Y.5

Z

BB

CC

PROJECT

AREA

CO

RR

B2B

100

N

B2 LEVEL

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

KEY PLAN

0M 2M

1:50

1M1M

500MM

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-201A

PA

RT

IA

L B

2 F

LO

OR

P

LA

N -

LIG

HT

IN

G C

AL

CU

LA

TIO

N

Page 10: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

2. ALL EQUIPMENT SHOWN SHALL BE NEW UON.

3. REFERENCE SHEET E-601 FOR PANEL SCHEDULES AND ONE LINE DIAGRAM.

4. SEE SHEET E-101 FOR PANEL LOCATION.

5. SWITCHES CONTROL LIGHTING IN SAME ROOM UON.

6. NEW FA DEVICES SHALL BE CONNECTED TO EXISTING FA CIRCUIT SALVAGED DURING DEMOLITION.

7. LIGHT FIXTURE AND OCCUPANCY SCHEDULES SEE SHEET E-001.

1

2

CONNECT LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT SALVAGED DURING DEMOLITION.

NORMAL LIGHTING CIRCUIT IS FED FROM PANEL HDB2FB CKT 5.

EMERGENCY LIGHTING FIXTURE. CONNECT TO EMERGENCY LIGHTING CIRCUIT SALVAGED

DURING DEMOLITION. EMERGENCY LIGHTING CIRCUIT IS FED FROM PANEL LSHPB2FA CKT 8, FED

FROM EXISTING EMERGENCY GENERATOR AND ATS. PROVIDE INTEGRAL EMERGENCY LIGHTING

BYPASS CONTROL THAT IS UL 924 COMPLIANT. BASIS OF DESIGN BODINE BLCD-208 OR EQUAL.

EMERGENCY EXIT SIGN. CONNECT TO EMERGENCY LIGHTING CIRCUIT SALVAGED DURING

DEMOLITION. CONNECT EXIT SIGN AHEAD OF ALL LOCAL SWITCHING.

APPROXIMATE ROUTING OF EXISTING 13.2KV FEEDERS.

CONNECT RECEPTACLE TO CIRCUIT SALVAGED DURING DEMOLITION.

3

NEW WORK PLAN NOTES

NEW WORK GENERAL NOTES

4

5

D2 B8D1F19F18F17F16

AREA OF WORK

AV

(E)

110

AV

(E)

15

(E)

(E)

(E)

1(N)

1

12

2

3

3

(N)

(N)

(N)(N)

(N)

(N)

F

AV

30

(N)

AV

30

(N)

(N)

(N)

(N)(N)

(N)

2

1

11

(N)

1

S

S(E

)

4

3

(N)

5

5

(N)

(N)

(N)

1

1

PARTIAL B2 LEVEL PLAN - NEW WORK - POWER

SCALE: 1:50

T

U

V

W

W.8

W.9

Y

Y.5

Z

BB

CC

PROJECT

AREA

CO

RR

B2B

100

N

B2 LEVEL

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

KEY PLAN

0M 2M

1:50

1M1M

500MM

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-202

PA

RT

IA

L B

1 IN

TE

RS

TIT

IA

L

FL

OO

R P

LA

N - N

EW

W

OR

K -

EL

EC

TR

IC

AL

Page 11: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

PROVIDE A LABEL FOR EACH RECEPTACLE TO INDICATE PANEL AND

CIRCUIT BREAKER NO. SUPPLYING THE DEVICE. PROVIDE PRESSURE

SENSITIVE, LABEL WITH BLACK LETTERING ON CLEAR BACKGROUND.

LETTERING HEIGHT IS 1/8" (3.175mm).

RP3W7-13

1/8"

(3.175mm)

2

RECEPTACLE LABELING DETAIL

SCALE: NOT TO SCALE

1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES OR SPECIAL CONDITIONS.

2. PROVIDE WIRING AND CONDUIT BETWEEN ALL OUTLETS/FIXTURES INDICATED WITH CIRCUIT

NUMBERS AND PANEL DESIGNATIONS.

3. ALL SWITCH CONTROLS SHALL BE PROVIDED WITH WIRING AND CONDUIT AS REQUIRED.

4. ALTHOUGH ALL BRANCH CIRCUIT WIRING AND CONDUIT IS NOT SHOWN, IT IS THE INTENT OF

THESE DOCUMENTS THAT A COMPLETE BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED.

5. BRANCH CIRCUIT WIRING IS INDICATED ON THE DRAWINGS IN ACCORDANCE FOR BOTH

LIGHTING AND POWER.

6. LIGHT SWITCH CONTROLS LIGHTS IN THE SAME ROOM UON.

HP-4a

PANEL

DESIGNATION

SWITCH

DESIGNATION

CIRCUIT #

1

BRANCH CIRCUIT WIRING NOTES

SCALE: NOT TO SCALE

NOTE: CONNECT AHEAD OF LOCAL SWITCH UON.

3

OCCUPANCY SENSOR WIRING DIAGRAM

SCALE : NO SCALE

L

A

O

D

Neutral

Neutral

Hot

Load

Line

Neutral

Ground

Terminals

Sensor Using

Occupancy

Voltage

Any Line

OFF SWITCH

NOTE: MAXIMUM NUMBER OF SENSORS PER POWER PACK

DEPENDS ON THE MODEL OF SENSOR. SEE THE PRODUCT DATA

SHEET TO DETERMINE THE SPECIFIC CURRENT CONSUMPTION

OF EACH SENSOR.

Any

24VDC

Ceiling/Wall

Sensor

Any

24VDC

Ceiling/Wall

Sensor

Control Output

Common

+24VDC

Neutral

HotBlk

Wht

Power

Pack

Red

Red

Local

Off

Switch

L

o

a

d

Control Output

Common

+24VDC

NOTE: CONNECT AHEAD OF LOCAL SWITCH UON.

4

MULTIPLE OCCUPANCY SENSOR DIAGRAM

SCALE : NO SCALE

BOND CONDUIT TO

NEAREST CABLE TRAY

VIA #6 AWG

4-11/16" (119mm)W x

4-11/16" (119mm)H x 2-1/8"

(54mm) DEEP BACKBOX

PROVIDE WITH 4-11/16"

(119mm) DOUBLE GANG

MUD RING

TO TELE. CLOSET. SEE

PLAN #2, SHEET E1.01

FOR DESTINATION

CABLE TRAY

1 1/4" (29mm) EMT

CONDUIT

10 BASE T CATEGORY(5),

4 TWISTED PAIRS, 24 AWG

FLUSH WALL PLATE, PBO

PLASTIC LABEL

(TYPICAL)

CPSI

LAN

NOTES:

1. CONDUIT BENDS SHALL BE NO LESS THAN 90°.

2. NO MORE THAN TWO 90° BENDS IN THE CONDUIT RUN SHALL BE

PERMITTED WITHOUT A 1900 BOX.

3. ALL WORK AREA OUTLET LOCATIONS ARE TO REMAIN ACCESSIBLE AT

ALL TIMES AND NOT BLOCKED BY FURNITURE, FILE CABINETS, ETC.

4. CONDUIT "DAISY CHAINING" IS NOT PERMITTED.

5. PROVIDE EACH CONDUIT PATHWAY WITH A PULL STRING.

6. CLEARANCES BETWEEN TELECOMMUNICATION/DATA CABLING AND

ELECTRICAL WIRING/FIXTURES SHALL BE A MINIMUM OF 6 INCHES TO

AVOID ELECTRICAL MAGNETIC INTERFERENCE.

6

DATA WIRING DIAGRAM

SCALE: NOT TO SCALE

RIGHT SIDE COMPUTER

RECEPTACLE

LEFT SIDE CONVENIENCE

RECEPTACLE

1. PROVIDE WIRING AND CONDUIT BETWEEN ALL OUTLETS/FIXTURES INDICATED WITH CIRCUIT

NUMBERS AND PANEL DESIGNATIONS.

2. ALTHOUGH ALL BRANCH CIRCUIT WIRING AND CONDUIT IS NOT SHOWN, IT IS THE INTENT OF

THESE DOCUMENTS THAT A COMPLETE BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED.

3. BRANCH CIRCUIT WIRING IS INDICATED ON THE DRAWINGS IN ACCORDANCE FOR DOUBLED

WIRED QUAD RECEPTACLE.

4. CONTRACTOR TO RUN COMPUTER AND CONVENIENCE RECEPTACLE CIRCUIT IN SAME CONDUIT

FOR DOUBLE WIRED QUAD RECEPTACLE ONLY.

CONVENIENCE RECEPTACLE

CIRCUIT #

COMPUTER RECEPTACLE

CIRCUIT #

C

PNL-X,Y

PANEL

DESIGNATION

CONV PNL-X COMP PNL-Y

5

DOUBLE WIRED QUAD RECEPTACLE DETAIL

SCALE: NOT TO SCALE

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-501

DE

TA

IL

S - E

LE

CT

RIC

AL

Page 12: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

7/16" (11mm) DIA.

NEWTON P.N. A-6056

WALL MOUNTED BRACKET

4"

4" (102mm)

5/8" (16mm) LOCKWASHER

NEWTON P.N. 3015-8

3/8" (10mm) DIA.

NEWTON P.N. 3061-4

2-3/4" (70mm) INSULATER

5/8" (16mm) DIA.

1/4" (6mm)

5/8" (16mm) LOCKWASHER

NEWTON P.N. 3015-8

12" (305mm)

THREAD (TYP)

5/8" (16mm)-11 CONTINUOUS

EVERY 12" (305mm)

3

GROUND BAR DETAIL

SCALE : NO SCALE

#6 GROUND

1/2" (13mm)-BOLT AND NUT

DRILL AND BOLT NEAREST

STEEL COLUMN.

3/4" (19mm)CONDUIT EMT

TERMINATE TO 3/4" HOLE

ON DOOR SIDE OF FRAME, 4"

FROM SIDE OF FRAME.

3/4" (19mm)CONDUIT EMT

SINGLE GANG CONSTRUCTION

BOX MOUNTED 42" (1067mm) CENTERLINE

ABOVE FLOOR, 6" (152mm) CENTERLINE

FROM DOOR FRAME MOUNTED

ON UNSECURED SIDE OF DOOR.

3/4" (19mm)CONDUIT

RUN CONDUIT TO MIDDLE

HINGE ON DOOR FRAME

POWER TRANSFER HINGE

G, F, R

GFR

TO SECURITY PANEL

PUBLIC SIDE

SECURED SIDE

CEILING

4.

POWER TRANSFER HINGE

18AWG-4C UNSHIELDED PLENUM

G

F

22AWG-4C UNSHIELDED PLENUM

TYPE

DEVICE LEGEND

CABLE LEGEND

3.

M

L

1.

P

SWITCH, MAGNETIC

AUTOMATIC MONITORING

PROXIMITY, PROXIMITY

CARD ACCESS READER

R

18AWG-6C 0/A SHIELD PLENUM

AWG - CONDUCTORS

2.

LOCKSET

ELECTRIC LOCK, MORTISE

JB

L

P

M

NOTES:

1. DOOR WILL BE HELD CLOSED BY ELECTRIFIED MORTISE LOCK.

2. DOOR SHALL BE COMPLIANT WITH NFPA 101 SECTION 7.2.1.5.6

3. SECURITY CABLING AND DEVICES SHALL BE INSTALLED BY A SECURITY CONTRACTOR TRAINED AND CERTIFIED BY THE HARDWARE MANUFACTURER

TO PERFORM WORK ON NIH SECURITY SYSTEMS.

4. CONTRACTOR TO CONTACT NIH DIVISION OF PERSONNEL SECURITY AND ACCESS CONTROL (DPSAC) TO LOCATED THE NEAREST SECURITY PANEL

WITH AVAILABLE CAPACITY TO SUPPORT THE PROJECT PRIOR TO INSTALLING ANY SECURITY CONDUIT OR CABLING.

JUNCTION BOX TO BE INSTALLED ABOVE

CEILING ON SECURED SIDE OF WALL

1

NIH DOOR SECURITY DETAIL

SCALE: NO SCALE

NORMAL VOLTAGE SENSE

TO EMERGENCY

LIGHTING

FIXTURES

NOTES:

NORMAL

LIGHTING

CIRCUIT

TO NORMAL

LIGHTING

FIXTURES

EMERGENCY

LIGHTING

CIRCUIT

LOCAL SWITCH OR POWERPACK

4

EMERGENCY LIGHTING WIRING DIAGRAM

SCALE : NO SCALE

UL1008

TRANSFER DEVICE

1. PROVIDE ADDITIONAL CONTROL WIRING AS INDICATED BY MANUFACTURER WIRING DIAGRAMS WHERE APPLICABLE

FOR 0-10V, 2-WIRE, AND 3-WIRE DIMMING APPLICATIONS.

2. ONLY ONE RELAY REQUIRED PER ZONE PER ROOM.

3. PLANS INDICATE EMERGENCY CIRCUIT PROVIDED FOR EMERGENCY FIXTURES. PER THIS DETAIL, ALSO PROVIDE

NORMAL POWER TO CONTROL DEVICE FOR EMERGENCY FIXTURES. PROVIDE NORMAL POWER FROM NORMAL POWER

CIRCUIT FEEDING FIXTURES WITHIN THE SAME CONTROL ZONE AS NOTED ON PLANS.

4. EMERGENCY FIXTURES SHALL DIM WITH NORMAL FIXTURES IN THE SAME ZONE.

BASIS OF DESIGN: BODINE

SURFACE MOUNTED

RACEWAY ENTRANCE

JUNCTION BOX

CONNECT TO

ALTERNATE

PHASES

(TYPICAL)

CIRCUIT

BREAKER,

1P, 20A,

120V, 10,000

AIC UON

(TYPICAL)

SURFACE

METAL

RACEWAY

(SMR)

TOGGLE SWITCH

FOR UNDERSHELF

LIGHTING FIXTURES

TO OTHER

FIXTURES

DUPLEX GROUNDING TYPE

RECEPTACLE, 125 VOLTS, 20

AMPS NEMA 5 -20R (USE GFI

TYPE WHERE INDICATED).

INCOMING 4 #6, #10G

FEEDER CONDUCTORS

IN 1 1/4" CONDUIT.

FEEDER CONDUCTORS

TO BE RUN

CONTINUOUSLY

THROUGHOUT SMR.

BOND EQUIP GROUND

CONDUCTOR TO EACH

SMR BASE SECTION,

INCLUDING FITTINGS

2

NOT TO SCALE

WIRING DIAGRAM AT RACEWAY

G

N

C

B

A

N

G

A, B OR C

1. MAXIMUM 4 DUPLEX RECEPTACLES ON ANY SINGLE POLE, 20A SMR CIRCUIT BREAKER.

2. LIGHTING FIXTURES SHALL BE CONNECTED IN SERIES AND HARDWIRED TO A SINGLE CIRCUIT.

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-502

DE

TA

IL

S - E

LE

CT

RIC

AL

Page 13: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

1 DEMO AND REMOVE EXISTING CONDUIT AND CONDUCTORS BACK TO PANEL LDPB2FA.

PLAN NOTES

NEW WORK GENERAL NOTES

SEE SCHEDULE

(N) PANEL "LPB2FB", B2 LVL

225A

SEE SCHEDULE

(N) PANEL "LPB2FC", B2 LVL

225A

PANEL "LDPB2FA", B2 LVL

400A, 208/120V, 3Ø, 4W.

225A

400A

225A

UPSTREAM 208/120V

SUPPLY

2

PARTIAL ONE-LINE DIAGRAM - NEW WORK

NOTE: ALL EQUIPMENT SHOWN IS EXISTING UON

CONDUCTOR SIZE

PER NEC TABLE 310.16 AND NEC TABLE 250.122

CONDUIT SIZE

PER NEC ANNEX C

TABLE C.1

SYMBOL

225N 2 1/2"4 - #4/0 AND A #4 GND

NOTE:

1. IF N IS NOT IN SYMBOL, REDUCE SYSTEM FROM 4 WIRE SYSTEM TO 3 WIRE SYSTEM GROUND

CONDUCTOR AND CONDUIT SHALL REMAIN THE SAME.

2. FEEDERS HAVE BEEN SIZED AS COPPER CONDUCTORS.

225N225N

FEEDER SCHEDULE

PANEL "LPB2FB", B2 LVL

225A (X)

PANEL "LPB2FC", B2 LVL

225A (X)

PANEL "LDPB2FA", B2 LVL

400A, 208/120V, 3Ø, 4W.

225A

400A

225A

UPSTREAM 208/120V

SUPPLY

1

PARTIAL ONE-LINE DIAGRAM - DEMO

NOTE: ALL EQUIPMENT SHOWN IS EXISTING UON

1 1

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-601

PA

NE

L S

CH

ED

UL

ES

&

PA

RT

IA

L O

NE

-L

IN

E D

IA

GR

AM

- E

LE

CT

RIC

AL

Page 14: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

1

PARTIAL ONE-LINE DIAGRAM - EMERGENCY

NOTE: ALL EQUIPMENT SHOWN IS EXISTING UON

PANEL "SBLPB2FB", B2 LVL

SEE SCHEDULE

100A

PANEL "SBLDP2FA", 800A,

208/120V, 3Ø, 4W, 65kA.

100A

800A

UPSTREAM 208/120V

SUPPLY

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

NEW WORK GENERAL NOTES

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-602

PA

NE

L S

CH

ED

UL

ES

&

PA

RT

IA

L O

NE

-L

IN

E D

IA

GR

AM

- E

LE

CT

RIC

AL

Page 15: E-001 · switch size, lower numeral denotes fuse size - 3 pole, uon fused safety disconnect switch - upper numeral denotes motor connection panelboard, branch junction box panelboard,

1

PARTIAL ONE-LINE DIAGRAM

NOTE: ALL EQUIPMENT SHOWN IS EXISTING UON

PANEL "HPB2FB", B2 LVL

SEE SCHEDULE

100A

PANEL "HDPB2FA", 400A,

480/277V, 3Ø, 4W, 65kA.

100A

400A

UPSTREAM 208/120V

SUPPLY

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN OBTAINED FROM RECORD DRAWINGS

WHEN AVAILABLE AND GENERAL FIELD SURVEY AND MAY NOT INDICATE ACTUAL EXISTING

CONDITIONS IN DETAIL AND DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING

EXACT EXISTING CONDITIONS PRIOR TO THE FABRICATION OR ORDER OF EQUIPMENT OR

PERFORMANCE OF ANY WORK. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER IN

WRITING IF EXISTING CONDITIONS ARE DISCOVERED THAT PREVENT THE EXECUTION OF WORK.

THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL DIRECTION IS PROVIDED.

NEW WORK GENERAL NOTES

PANEL "HPB2FB", B2 LVL

SEE SCHEDULE

100A

225A

480:208/120V

112.5KVA

XFMR

DRAWN BY

CHECKED BY

DRAWING NO.

MEP ENGINEERS

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY DOCUMENTS WHEN NO LONGER

NEEDED

DESIGNED BY

FILE NAME

OFFICE OF

RESEARCH FACILITIES

DR

AW

IN

GP

RO

JE

CT

BU

IL

DIN

GC

ON

TR

AC

TO

RS

RE

VIS

IO

NS

SE

AL

A/E

N

am

e a

nd

L

OG

O

SUBMISSION

SUB. DATE

PROJ. MGR.

WRK REQ. NO.

PROJ. OFFICER

SPB TASK NO.

STATE/ZIP

OTHER

CITY

BUILDING NO.

STREET

NAME

BUILDING NO.

FACILITY CODE

9000 ROCKVILLE PIKE

BETHESDA

MD 20892

PRIME A/E

SUB A/E

CONS. WORK

CONSTR. CON.

CONS. CONTR.

A/E TASK NO.

A/E CON. NO.

PR

OJE

C

T T

IT

LE

DR

AW

IN

G T

IT

LE

HERA LABORATORY PLANNERS

NIH

HHSN292201400002I

20251 Century Blvd. Suite 120

Germantown, MD 20874

877.871.4229 t.

www.cfrengineering.com

HERA PROJECT NO:

PROJECT MANAGER / LABORATORY PLANNER

Health, Education and Research Associates, Inc.

ARCHITECT

HERA Studio of Pennsylvania, LLC

7315 Wisconsin Ave., Suite 400W

Bethesda, MD 20814

301.789.8017 t. 314.289.6167 f.

www.herainc.com

STRUCTURAL ENGINEER

604 S. King Street, Suite 101

Leesburg, VA 20175

703.385.5556 t.

www.ares.engineering

10

/1

5/2

01

8 6

:4

4:4

7 P

M

NH

LB

I S

UIT

E B

2-3701 -

EL

EC

TR

ON

M

IC

RO

SC

OP

Y

CO

RE

03/20/2020

ISSUED FOR CONSTRUCTION

10 CRC

51

C105883

A. BHASIN

CFR ENGINEERING

#14341.51

MARK DATEDESCRIPTION

OM/RS

ID/PS

ID/PS

T. GRIFFITH

E-603

PA

NE

L S

CH

ED

UL

ES

&

PA

RT

IA

L O

NE

-L

IN

E D

IA

GR

AM

- E

LE

CT

RIC

AL