Duct Design
Presented by
Dave Janquart
![Page 2: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/2.jpg)
Overview of Topics
• Duct design
• Duct insulation
• SMACNA Standards
![Page 3: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/3.jpg)
Factors Influencing Duct Design
• Equipment Losses
• Air Velocity
• Duct Material
• Duct Size & Shape
• Length of Duct
![Page 4: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/4.jpg)
Friction Losses
FURNACE
NO SCALE
SUPPLY
FAN
COIL
OR
FURN
ACE
R.A.
BOX
FILTER
S.P. 0.07
RE
TU
RN
AIR
RAG CONT
G35W
S.P. 0.045
SAG CONT 32W
S.P. 0.04A coil
.25” sp
![Page 5: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/5.jpg)
Air Distribution System
Components
• Supply fan
• Supply Ductwork
• Transition fittings
• Discharge grills
• Return grills
• Return ductwork
![Page 6: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/6.jpg)
Calculate Air System Pressure
Losses
• The air pressure losses from both the supply and return duct systems plus the loss through external a/c coil is often referred to as the external static pressure.
• Manufacturers generally publish fan ratings based on external static pressure (internal losses due to coils, filters, etc. are usually accounted for in the cataloged fan ratings).
![Page 7: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/7.jpg)
Air Velocity in Duct Design
• As Air Velocity Increases Noise Increases
• Increasing Air Velocity Causes More
Turbulence
• Recommended Velocity 700-900 FPM
![Page 8: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/8.jpg)
Duct Material Roughness
– Duct material roughness refers to the inside surface of
the duct material.
– The rougher the surface, the higher the friction loss.
– Most duct sizing tables use the roughness factor for
smooth, galvanized sheet metal as the reference value.
– The back side of the Duct Calculator has a conversion
table for converting the material roughness from
smooth sheet metal to other materials.
![Page 9: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/9.jpg)
Select Duct Material (sheet metal,
fiberglass, flex)• Decide which duct construction material to
use.
• Common choices: fiberglass duct board, galvanized sheet metal, “flex” vinyl coated with helical wire core.
• Each material has advantages.
– First cost (price & ease of installation)
– Performance (friction loss, fan energy)
– Acoustic properties
– Thermal properties (heat gain & loss; internal/external insulation)
![Page 10: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/10.jpg)
Round vs. Rectangular Duct
of Equal Friction Rate
40.7 in.
3 ft.
3 ft.
2 ft.
4-1/2 ft.
1-1/2 ft.6 ft.
1 ft. 9 ft.
9.0 ft2
9.0 ft2
9.0 ft2
9.03 ft2 10.65 ft.
Ratio ofPerimeter
to Area
EquivalentRound Duct
Frictionat
15,000 CFMPerimeter
1.18:1 40.7 in. .07 in. / 100 ft.
1.33:112 ft. 39.4 in. .086 in. / 100 ft.
13 ft. 1.45:1 38.7 in. .095 in. / 100 ft.
15 ft. 1.67:1 37.2 in. .113 in. / 100 ft.
20 ft. 2.22:1 34.5 in. .156 in. / 100 ft.
Figure 8
![Page 11: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/11.jpg)
Fitting Influences
• Selection of the proper fittings is critical
![Page 12: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/12.jpg)
![Page 13: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/13.jpg)
![Page 14: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/14.jpg)
Design Friction Rate
• When sizing a duct system the designer will usually choose a design friction rate.
• This is the desired friction loss in inches w.g. per 100 ft. of equivalent length (in. w.g./100 ft. E.L.) of duct.
• The design friction rate is generally determined based on the velocity of the air in the first section of ductwork.
• Most designers use a design friction rate somewhere between 0.08 and 0.10 in. w.g. per 100 ft. E.L.
![Page 15: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/15.jpg)
![Page 16: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/16.jpg)
Determining Friction Rate/100 ft.
• Equipment pressure drop
• Duct pressure drop
• Terminal device pressure drop
![Page 17: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/17.jpg)
Terminal Device Pressure Drop
• Pressure loss for supply air grill
• Pressure loss for return air grill
![Page 18: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/18.jpg)
Friction Losses
FURNACE
NO SCALE
SUPPLY
FAN
COIL
OR
FURN
ACE
R.A.
BOX
FILTER
S.P. 0.07
RE
TU
RN
AIR
RAG CONT
G35W
S.P. 0.045
SAG CONT 32W
S.P. 0.04A coil
.25” sp
![Page 19: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/19.jpg)
Equal Friction Method
• Same friction loss per foot of ductwork
• Most commonly used method
• Accomplished by use of a Ductulator
• Requires less balancing
– Important to have balance dampers at each
outlet
• Results in reasonable duct sizes
![Page 20: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/20.jpg)
Velocity Scale
Velocity
Pressure
Airflow
(CFM)
Friction
Loss
Round Duct
Diameter
Equivalent
Rectangular
Duct SizesFigure 7
Duct Calculator
![Page 21: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/21.jpg)
Duct Calculator
![Page 22: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/22.jpg)
Duct Calculator (Reverse)
![Page 23: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/23.jpg)
Recommended & Maximum
Duct Velocity Ranges
Design toward smaller end of range for quieter systems
and toward larger end of range to minimize duct sizes.
![Page 24: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/24.jpg)
Things to Consider
• Aspect ratio no more than 3:1
• Residential 2 times # of 6” RD take offs
plus 2” for ducts that are 8” high
• .5 cfm per Sq Ft
• No more than100 cfm per 6” RD
![Page 25: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/25.jpg)
Round vs. Rectangular Duct
of Equal Friction Rate
40.7 in.
3 ft.
3 ft.
2 ft.
4-1/2 ft.
1-1/2 ft.6 ft.
1 ft. 9 ft.
9.0 ft2
9.0 ft2
9.0 ft2
9.03 ft2 10.65 ft.
Ratio ofPerimeter
to Area
EquivalentRound Duct
Frictionat
15,000 CFMPerimeter
1.18:1 40.7 in. .07 in. / 100 ft.
1.33:112 ft. 39.4 in. .086 in. / 100 ft.
13 ft. 1.45:1 38.7 in. .095 in. / 100 ft.
15 ft. 1.67:1 37.2 in. .113 in. / 100 ft.
20 ft. 2.22:1 34.5 in. .156 in. / 100 ft.
Figure 8
![Page 26: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/26.jpg)
![Page 27: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/27.jpg)
![Page 28: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/28.jpg)
![Page 29: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/29.jpg)
![Page 30: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/30.jpg)
![Page 31: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/31.jpg)
GAS
DRYER
(N.I.C.)
WASHER
(N.I.C.)
120 SQ FT
160 SQ FT
60 SQ FT
120 SQ FT
450 SQ FT
90 SQ FT
120 SQ FT
50 SQ FT
190 SQ FT
50 SF
90 SQ FT
![Page 32: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/32.jpg)
GAS
DRYER
(N.I.C.)
WASHER
(N.I.C.)
120 SQ FT
160 SQ FT
60 SQ FT
120 SQ FT
450 SQ FT
90 SQ FT
120 SQ FT
50 SQ FT
190 SQ FT
50 SF
90 SQ FT
95 CFM
45 CFM
25CFM
45 CFM
60 CFM225 CFM
25 CFM
60 CFM
80 CFM
30 CFM
60 CFM
![Page 33: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/33.jpg)
GAS
DRYER
(N.I.C.)
WASHER
(N.I.C.)
120 SQ FT
160 SQ FT
60 SQ FT
120 SQ FT
450 SQ FT
90 SQ FT
120 SQ FT
50 SQ FT
190 SQ FT
50 SF
90 SQ FT
95 CFM
45 CFM
25CFM
45 CFM
60 CFM225 CFM
25 CFM
60 CFM
80 CFM
30 CFM
60 CFM
![Page 34: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/34.jpg)
GAS
DRYER
(N.I.C.)
WASHER
(N.I.C.)
120 SQ FT
160 SQ FT
60 SQ FT
120 SQ FT
450 SQ FT
90 SQ FT
120 SQ FT
50 SQ FT
190 SQ FT
50 SF
90 SQ FT
95 CFM
45 CFM
25CFM
45 CFM
60 CFM225 CFM
25 CFM
60 CFM
80 CFM
30 CFM
60 CFM
![Page 35: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/35.jpg)
GAS
DRYER
(N.I.C.)
WASHER
(N.I.C.)
120 SQ FT
160 SQ FT
60 SQ FT
120 SQ FT
450 SQ FT
90 SQ FT
120 SQ FT
50 SQ FT
190 SQ FT
50 SF
90 SQ FT
95 CFM
45 CFM
25CFM
45 CFM
60 CFM
225 CFM
25 CFM
60 CFM
80 CFM
30 CFM
60 CFM12/8
18/8
8/8
8/8
![Page 36: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/36.jpg)
GASDRYER
(N.I.C.)
WASHER(N.I.C.)
120 SQ FT
160 SQ FT
60 SQ FT
120 SQ FT
450 SQ FT
90 SQ FT
120 SQ FT
50 SQ FT
190 SQ FT
50 SF
90 SQ FT
95 CFM
45 CFM
25CFM
45 CFM
60 CFM225 CFM
25 CFM
60 CFM
80 CFM
30 CFM
60 CFM8/8
12/8
8/8
![Page 37: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/37.jpg)
Select and Adjust Fan
• The total static pressure is the pressure that the fan
must overcome to deliver the required amount of air.
This total amount is also used to select the required fan
motor size or fan speed.
• Perform air balance next. Per Comm 23.18
• Measured airflow values should be compared against
the required values.
• Adjust fan and balancing dampers as necessary to
deliver the correct amount of air to each zone.
![Page 38: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/38.jpg)
![Page 39: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/39.jpg)
![Page 40: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/40.jpg)
Duct Insulation
• 22.17 UDC Duct system insulation. (1)
except as provided in sub. (4), all heating
and cooling duct systems, or portions
thereof, that are located in unheated or
uncooled spaces respectively, shall be
provided with insulation with a thermal
resistance of at least R-5.
![Page 41: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/41.jpg)
Duct Insulation cont.
• R-4.2 and R-6 are common industry
standards for insulated flex
• R-5 and R-8 are common industry standards
for duct wrap
![Page 42: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/42.jpg)
Installation of Underground
Ducts SMACNA Standards
![Page 43: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/43.jpg)
Installation of Underground
Ducts cont.
![Page 44: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/44.jpg)
Installation of Underground
Ducts cont.
• 23.08 UDC supply air ducts shall be
insulated with a moistureproof material
having a resistance value of a least R-5.
![Page 45: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/45.jpg)
Underground Duct cont.
![Page 46: Duct design](https://reader034.fdocuments.in/reader034/viewer/2022052215/55695258d8b42ad3278b49ad/html5/thumbnails/46.jpg)
Underground Ducts cont.
• Uninsulated duct will require 152 btuh per linear foot of duct for heating
• 1” insulated duct will require 91 btuh per linear foot of duct for heating (40% less energy)
• 2” insulated duct will require 74 btuh per linear foot of duct for heating (51% less energy)