DTS Dimming Bypass Module - hubbellcdn€¦ · OVERVIEW The DTS is a dimming bypass module used...

9
DTS Dimming Bypass Module INTRODUCTION © 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com Page 1/9 Rev. 08/21/19 COL-DTS-IMP Integration Guide OVERVIEW The DTS is a dimming bypass module used with an inverter or generator in emergency systems. The DTS works by constantly sensing for the presence of utility power. When utility power is no longer sensed (during a power outage), the DTS will bypass any dimming or controls integral to or networked with the fixture. Fixtures that can be dimmed must return to an undimmed (or pre-determined) state with loss of utility power, to meet UL924 requirements. LUMINAIRE USE The DTS cannot be used in conjunction with GTD, ATSD or ELL14/40 (Emergency Battery Pack) options. Each luminaire has different restrictions of use, please check individual specification sheets for compatibility. The DTS is available only as a factory-installed option. EMERGENCY CIRCUITS While the DTS is UL924 listed, it is not used to transfer power. The transfer of power must happen through a UL1008 module, (such as an AETS – Automatic Emergency Transfer Switch), to meet building code. The DTS is to be used in conjunction with an emergency AC power supply, such as an inverter or generator. These systems are designed/specified by qualified professionals. CONNECTIONS FROM FIXTURE TO BUILDING SYSTEM The following 10 cases are outlined in the included wiring diagram package if further information is needed. The following outlines key connections to perform when installing new fixtures, as well as wiring internal to the fixture.

Transcript of DTS Dimming Bypass Module - hubbellcdn€¦ · OVERVIEW The DTS is a dimming bypass module used...

DTS Dimming Bypass ModuleINTRODUCTION

© 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 1/9 Rev. 08/21/19COL-DTS-IMP

Integration Guide

OVERVIEWThe DTS is a dimming bypass module used with an inverter or generator in emergency systems. The DTS works by constantly sensing for the presence of utility power. When utility power is no longer sensed (during a power outage), the DTS will bypass any dimming or controls integral to or networked with the fixture. Fixtures that can be dimmed must return to an undimmed (or pre-determined) state with loss of utility power, to meet UL924 requirements.

LUMINAIRE USEThe DTS cannot be used in conjunction with GTD, ATSD or ELL14/40 (Emergency Battery Pack) options. Each luminaire has different restrictions of use, please check individual specification sheets for compatibility. The DTS is available only as a factory-installed option.

EMERGENCY CIRCUITSWhile the DTS is UL924 listed, it is not used to transfer power. The transfer of power must happen through a UL1008 module, (such as an AETS – Automatic Emergency Transfer Switch), to meet building code. The DTS is to be used in conjunction with an emergency AC power supply, such as an inverter or generator.

These systems are designed/specified by qualified professionals.

CONNECTIONS FROM FIXTURE TO BUILDING SYSTEMThe following 10 cases are outlined in the included wiring diagram package if further information is needed. The following outlines key connections to perform when installing new fixtures, as well as wiring internal to the fixture.

© 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 2/9 Rev. 08/21/19COL-DTS-IMP

DTS Dimming Bypass ModuleSYSTEM LAYOUT EXAMPLES

Integration Guide

Utility Power

Un-Switched

Emergency Line

Switched

Switched

Transfer Switch (AETS) (UL1008 Device)

1

2

3

4

Luminaire with In-Fixture Control

Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

Refer to wiring diagrams for speci�c cases

EmergencyAC Power

SITUATION 1: NORMAL UNDIMMED OPERATION• Each luminare has in-fixture control and is not dimmed• Luminaires 3 & 4 are also emergency enabled with DTS modules

EXAMPLE OF BASIC SYSTEM LAYOUT

Emergency Line

Switched

50% Dim

50% Dim

Utility Power

Un-Switched

Switched

Transfer Switch (AETS) (UL1008 Device)

1

2

3

4

Luminaire with In-Fixture Control

Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

EmergencyAC Power

Emergency Line

Switched

Utility Power

(Resumes to undimmed state)

Un-Switched

Switched

Transfer Switch (AETS) (UL1008 Device)

1

2

3

4

Luminaire with In-Fixture Control

Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

EmergencyAC Power

Below are 3 situations of a system layout using a DTS module*Specific layouts may vary

SITUATION 1 (below)Normal Undimmed Operation

SITUATION 2 (pg. 3)Dimmed Operation

SITUATION 3 (pg. 4)Emergency Operation

Utility Power

Un-Switched

Emergency Line

Switched

Switched

Transfer Switch (AETS) (UL1008 Device)

1

2

3

4

Luminaire with In-Fixture Control

Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

Refer to wiring diagrams for speci�c cases

EmergencyAC Power

© 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 3/9 Rev. 08/21/19COL-DTS-IMP

DTS Dimming Bypass ModuleSYSTEM LAYOUT EXAMPLES

Integration Guide

Emergency Line

Switched

50% Dim

50% Dim

Utility Power

Un-Switched

Switched

Transfer Switch (AETS) (UL1008 Device)

1

2

3

4

Luminaire with In-Fixture Control

Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

EmergencyAC Power

SITUATION 2: NORMAL UTILITY POWER OPERATION, INDIVIDUAL DIMMING CONTROL• Luminaires 1 & 3 are in a dimmed state by user choice

© 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 4/9 Rev. 08/21/19COL-DTS-IMP

DTS Dimming Bypass ModuleSYSTEM LAYOUT EXAMPLES

Integration Guide

Emergency Line

Switched

Utility Power

(Resumes to undimmed state)

Un-Switched

Switched

Transfer Switch (AETS) (UL1008 Device)

1

2

3

4

Luminaire with In-Fixture Control

Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

DTS Enabled Luminaire with In-Fixture Control

EmergencyAC Power

SITUATION 3: LOSS OF UTILITY POWER• Transfer switch will transfer power from utility to emergency power source• Luminaires 1 & 2 lose power • DTS opens dimming circuits in luminaires 3 & 4 which then resume their undimmed state to meet

UL924 requirements

DTS Dimming Bypass ModuleWIRING DIAGRAMS

© 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 5/9 Rev. 08/21/19COL-DTS-IMP

Integration Guide

DTS/NXFM-O/I

DRIVER

WHITE

WHITEBLACK

REDBLUE

GRAY

ORANGE

VIOLET

SMALL YELLOW (CAPPED)

TO LED BOARD(S)

GND

WHITE/BLUE

YELLOW

BLUE

BLACK

WHITE/BLUE

TO EMERGENCY

NXFM-O

RED

REDWHITE

BLACK

FERRITE CHOKE

1 LOOPOF WHT & BLK WIRE AROUND CHOKE

TO UTILITY

TO EMERGENCY

VIOLET

KEYColor Connects WithWhite/Blue Emergency NeutralBlue Emergency LineBlack Utility line (Unswitched Hot)White Utility Neutral

CASE 2: DTS WITH INTERNAL NXFM-O OR NXFM-I

DTS

DRIVER

WHITE

WHITEBLACK

RED

REDBLUE

GRAYVIOLET

VIOLET

ORANGE

SMALL YELLOW (CAPPED)

TO LED BOARD(S)

TO DIMMING

GND

TO UTILITY

WHITE/BLUE

YELLOW

BLUE

WHITE/BLUE

TO EMERGENCY

TO EMERGENCY

BLACK

KEY

Color Connects WithWhite/Blue Emergency NeutralBlue Emergency LineBlack Utility line (Unswitched Hot)White Utility NeutralRed Switched HotViolet Dimming Gray Dimming

CASE 1: DTS WITH EXTERNAL DIMMING CONTROL

DTS Dimming Bypass ModuleWIRING DIAGRAMS

© 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 6/9 Rev. 08/21/19COL-DTS-IMP

Integration Guide

DTS/CTC

DRIVER

WHITE

WHITEBLACK

BLACK

REDBLUE

GRAYVIOLET

VIOLET

ORANGE

SMALL YELLOW (CAPPED)

TO DIMMING

GND

TO UTILITY

WHITE/BLUE

YELLOW

BLUE

RED

WHITE/BLUE

TO EMERGENCY

TO EMERGENCY

NEGPOSNEGPOS

CH1 NEGCH2 NEGCH1 POSCH2 POS

LED0-10V

DRIVER

CTCREDBLUE

WHITE/BLUE

TO LED BOARD(S)

VIOLETGRAY

TO CTC DIMMING

KEY

Color Connects WithWhite/Blue Emergency NeutralBlue Emergency LineBlack Utility line (Unswitched Hot)White Utility NeutralRed Switched HotViolet Dimming Gray Dimming

CASE 4: DTS WITH INTERNAL CTC MODULE FOR SpectraSync™

DTS/NXFM-LV

WHITERED

VIOLET

SMALL YELLOW (CAPPED)

TO UTILITY

WHITE/BLUE

BLUE

BLACK

WHITE/BLUE

WHI

TE

TO EMERGENCYDIM 1+DIM 2+

COM+12V

NHG

+-

+- DIM

LED

AUX

YELLOW

GND

GRA

Y

YEL L

OW

ORA

NGE

VIOLET

GRA

Y

RED

BLUEBLUE

TO LED BOARD(S)

BLACK

NXCBL-I TO:NXSMP SENSOR AND/ORNXRM-H RADIO MODULE AND/ORNXDSP/NXFSP SMART PORT

KEY

Color Connects With

White/Blue Emergency Neutral

Blue Emergency LineBlack Utility line (Unswitched Hot)White Utility NeutralRed Switched Hot

CASE 3: DTS WITH INTERNAL NXFM-LV

DTS Dimming Bypass ModuleWIRING DIAGRAMS

© 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 7/9 Rev. 08/21/19COL-DTS-IMP

Integration Guide

WHITE BLACKVIOLET

ORANGE

SMALL YELLOW (CAPPED)

TO UTILITY

WHITE/BLUE

BLUE

YELLOW

RED

WHITE/BLUE

N

+- E2

L

E1

WHI

TEBL

UE

E1 LABELE2 LABEL

VIOLET

VIOLET

GRAY

CAP INSIDE FIXTURE

CAP INSIDE FIXTURE

CAP INSIDE FIXTURE

REDBLUE

TO LED BOARD(S)

BLUE

TO EMERGENCY

TO DIMMING

DTS LUTRON H/5 SERIES

KEY

Color Connects With

White/Blue Emergency NeutralBlue Emergency LineBlack Utility line (Unswitched Hot)White Utility NeutralRed Switched HotViolet Dimming Gray Dimming

CASE 6: DTS WITH LUTRON H SERIES DRIVER OR LUTRON 5 SERIES DRIVER

DTS/NX/CTC

DRIVER

WHITE

WHITEBLACK

GRAY

ORANGE

VIOLET

SMALL YELLOW (CAPPED)

GND

WHITE/BLUE

YELLOW

BLUE

BLACK

WHITE/BLUE

TO EMERGENCY

NXFM-O

RED

REDWHITE

BLACK

FERRITE CHOKE

1 LOOPOF WHT & BLK WIRE AROUND CHOKE

TO UTILITY

TO EMERGENCY

RED

NEGPOSNEGPOS

CH1 NEGCH2 NEGCH1 POSCH2 POS

LED0-10V

DRIVER

CTCREDBLUE

WHITE/BLUE

TO LED BOARD(S)

VIOLET

VIOLET/WHITE

GRAYGRAY

BLUE

KEY

Color Connects WithWhite/Blue Emergency NeutralBlue Emergency LineBlack Utility line (Unswitched Hot)White Utility Neutral

CASE 5: DTS WITH INTERNAL CTC AND NXFM-O OR NXFM-I FOR SpectraSync™ USED WITH NX

DTS Dimming Bypass ModuleWIRING DIAGRAMS

© 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 8/9 Rev. 08/21/19COL-DTS-IMP

Integration Guide

DTS/ODPG

WHITERED

VIOLET

TO UTILITY

WHITE/BLUE

BLUE

BLACK

WHITE/BLUE

WHI

TE

YELLOW

GND

RED

ORANGECAP INSIDE FIXTURE

NHG

+- LED

+-

SRSRBLUE

TO LED BOARD(S)

BROWN

BROWN

VIOLET

SMAL

L YE

LLO

W

VIOLET

BRO

WN

TO EMERGENCY

KEY

Color Connects With

White/Blue Emergency NeutralBlue Emergency LineBlack Utility line (Unswitched Hot)White Utility NeutralRed Switched Hot

CASE 8: DTS WITH INDIVIDUAL FIXTURE ODPG SENSOR

DTS/LVR/LVS

WHITERED

VIOLET

TO UTILITY

WHITE/BLUE

BLUE

BLACK

WHITE/BLUE

WHI

TE

TO EMERGENCYYELLOW

GND

RED

ORANGECAP INSIDE FIXTURE

NHG

+- LED

+-

SRSRBLUE

TO LED BOARD(S)

BROWN

BROWN

VIOLET

SMAL

L YE

LLO

W

VIOLET

BLUE

BLUE

KEY

Color Connects With

White/Blue Emergency NeutralBlue Emergency LineBlack Utility line (Unswitched Hot)White Utility NeutralRed Switched Hot

CASE 7: DTS WITH INDIVIDUAL FIXTURE LVR OR LVS SENSOR

DTS Dimming Bypass ModuleWIRING DIAGRAMS

© 2019 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com

Page 9/9 Rev. 08/21/19COL-DTS-IMP

Integration Guide

CASE 10: DTS/NXFM-0/I WITH FLEX

KEY

Color Connects With

Violet Emergency NeutralGray Emergency LineBlack Utility line (Unswitched Hot)White Utility NeutralGreen Ground

CASE 9: DTS WITH FLEX

DRIVER

WHITE

WHITEBLACK

REDBLUE

GRAY

ORANGE

VIOLET

SMALL YELLOW (CAPPED)

TO LED BOARD(S)

WHITE/BLUE

YELLOW

BLUE

BLACK

WHITE/BLUE

TO EMERGENCY

NXFM-O

RED

REDWHITE

BLACK

FERRITE CHOKE

1 LOOPOF WHT & BLK WIRE AROUND CHOKE

TO UTILITY

TO EMERGENCY

VIOLET

5-WIRE

F LEX

GREEN

VIOLET

WHITE

BLACK

GRAY

GND

GROUND TO HOUSING

6- WIRE FLEX KEY

Color Connects With

Black Utility Line (Unswitched Hot)White Utility NeutralRed Switched HotViolet DimmingGray DimmingGreen Ground

3-WIRE FLEX KEY

Color Connects With

White Emergency NeutralBlack Emergency LineGreen Ground

DRIVER

WHITE

WHITEBLACK

RED

REDBLUE

GRAYVIOLET

VIOLET

ORANGE

SMALL YELLOW (CAPPED)

TO LED BOARD(S)

TO UTILITY

WHITE/BLUE

YELLOW

BLUE

WHITE/BLUE

BLACK

6-WIRE

FL EX

3-WIRE

FL EX

BLAC

KW

HITE

GND

TO EMERGENCY

GRAYVIOLET

BLACK REDWHITE

GND

GND

GROUND TO HOUSING