(DRUPS) and its integration in "Uptime Institute Tier"
Transcript of (DRUPS) and its integration in "Uptime Institute Tier"
![Page 1: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/1.jpg)
IT & INFRASTRUCTURE DATACENTERS CONGRESS
Brussels, 13th of October 2016
Yves Jansen
![Page 2: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/2.jpg)
DIESEL ROTARY UPS (DRUPS) AND ITS INTERGRATION IN
« UPTIME INSTITUTE TIER » ARCHITECTURE BASED DATA
CENTRES
![Page 3: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/3.jpg)
EURO‐DIESEL SADRUPS : NO‐BREAK KSTIER STANDARDNO‐BREAK KS AND THE TIER STANDARD
![Page 4: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/4.jpg)
HQ EURO‐DIESEL SA, Belgium, Liege
EURO‐DIESEL SA
Holland
Belgium
Established in 1989
HQ Liège, Belgium
Consolidated revenue : 103 million EUR
Total number of employees : 250
Subsidiaries in Germany, UK, France, USA, Singapore, Brazil, Middle East, United Arab Emirates, Turkey, Mexico and Russia
Worldwide distributor network
Focus on power quality solutions: DRUPS
France
The Netherlands
Belgium
Luxemburg
BrusselsLiège
![Page 5: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/5.jpg)
World Largest DRUPS Testing Facility
• 6300 M²
• Production capacity > 200 systems
• 18 Test stands
• Indoor enclosure assembly
• 50 & 60 Hz testing
• Load banks > 18 MW
• Load banks & recordings, software operated
The Facility built in 2009:
![Page 6: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/6.jpg)
Power Quality
![Page 7: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/7.jpg)
Building a NO‐BREAK KS® System
![Page 8: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/8.jpg)
Stato‐Alternator Side View
ACCU‐ROTOR < 3000 RPM
MAIN SHAFT 1500 OR 1800 RPM
![Page 9: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/9.jpg)
100 kVA to 2750 kVA (50Hz); 3000 kVA (60Hz)
![Page 10: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/10.jpg)
NO‐BREAK KS® Conditioning Mode
![Page 11: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/11.jpg)
NO‐BREAK KS® Conditioning Mode
•Voltage regulator •Harmonics filter•Improvement of Power factor•Elimination of Microcuts
![Page 12: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/12.jpg)
NO‐BREAK KS® Independent Mode
![Page 13: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/13.jpg)
NO‐BREAK KS® SYSTEM CONFIGURATIONS
FOR DATA CENTRES
![Page 14: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/14.jpg)
UPTIME Institute Tier Standard: Topology
• The functionality
• The capacity
• The availability ( or performance)
Tier Standard Topology is an objective basis for comparing:
of a particular site infrastructure design topology against other sites
![Page 15: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/15.jpg)
UPTIME Institute Tier Standard: Topology
• The functionality
• The capacity
• The availability ( or performance)
Tier Standard Topology is an objective basis for comparing:
of a particular site infrastructure design topology against other sites
Tier Standard describes criteria four differentiate classifications of site infrastructure
![Page 16: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/16.jpg)
System Configurations for Data Centres
Tier I
Active Capacity Components to Support the IT Load N
Distribution Paths 1
Concurrently Maintainable No
Fault Tolerance No
Compartmentalization No
Diesel Engine Function Engine Limited on Consecutive Hours of Operation
Uptime Institute Design Criteria
![Page 17: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/17.jpg)
System Configurations for Data Centres
Tier I Tier II
Active Capacity Components to Support the IT Load N N+1
Distribution Paths 1 1
Concurrently Maintainable No No
Fault Tolerance No No
Compartmentalization No No
Diesel Engine Function Engine Limited on Consecutive Hours of Operation
Engine Limited on Consecutive Hours of Operation
Uptime Institute Design Criteria
![Page 18: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/18.jpg)
System Configurations for Data Centres
Tier I Tier II Tier III
Active Capacity Components to Support the IT Load N N+1 N+1
Distribution Paths 1 1 1 Active and 1 Alternative Path
Concurrently Maintainable No No Yes
Fault Tolerance No No No
Compartmentalization No No No
Diesel Engine Function Engine Limited on Consecutive Hours of Operation
Engine Limited on Consecutive Hours of Operation
Engine NO Limit on Consecutive Hours of Operation
Uptime Institute Design Criteria
![Page 19: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/19.jpg)
System Configurations for Data Centres
Tier I Tier II Tier III Tier IV
Active Capacity Components to Support the IT Load N N+1 N+1 N: After a failure
Distribution Paths 1 1 1 Active and 1 Alternative Path 2 Simultaneously Active
Concurrently Maintainable No No Yes Yes
Fault Tolerance No No No Yes
Compartmentalization No No No Yes
Diesel Engine Function Engine Limited on Consecutive Hours of Operation
Engine Limited on Consecutive Hours of Operation
Engine NO Limit on Consecutive Hours of Operation
Engine NO Limit on Consecutive Hours of Operation
Uptime Institute Design Criteria
![Page 20: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/20.jpg)
NO‐BREAK KS® Single System – Tier I design
• Active capacity element to support active load : N
• Distribution path: 1
• Concurrently Maintainable: NO
• Fault Tolerant: NOTIER 1
![Page 21: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/21.jpg)
NO‐BREAK KS® LV Parallel – Tier II Design
TIER 2
Critical load
• Active capacity :
• Distribution path:
• Concurrently Maintainable:
• Fault Tolerant:
N+1
1
NO
NO
![Page 22: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/22.jpg)
NO‐BREAK KS® LV Parallel – Tier II Design
TIER 2
Critical load
• Active capacity :
• Distribution path:
• Concurrently Maintainable:
• Fault Tolerant:
N+1
2
NO
NO
![Page 23: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/23.jpg)
NO‐BREAK KS® LV Parallel – Tier III Design
TIER 3
Critical load
• Active capacity :
• Distribution path:
• Concurrently Maintainable:
• Fault Tolerant:
N+1
2
YES
NO
![Page 24: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/24.jpg)
NO‐BREAK KS® LV Parallel – Tier III Design
TIER 3
Critical load
• Active capacity :
• Distribution path:
• Concurrently Maintainable:
• Fault Tolerant:
N+1
2
YES
NO
![Page 25: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/25.jpg)
NO‐BREAK KS® LV Parallel – Tier 3 Design
TIER 3
Critical load
• Active capacity :
• Distribution path:
• Concurrently Maintainable:
• Fault Tolerant:
N+N
2
YES
YES
subject to interpretation TIER 4
![Page 26: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/26.jpg)
NO‐BREAK KS® LV Parallel – Tier IV Design
2 NO-BREAK KS ® of 1000 kVA+ 2 NO-BREAK KS ® of 2000 kVA
ECMWF READING UK:
![Page 27: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/27.jpg)
NO‐BREAK KS® LV Parallel – Tier IV Design
TIER 4
Critical load
• Active capacity :
• Distribution path:
• Concurrently Maintainable:
• Fault Tolerant:
N+N
2 Active
YES
YES
![Page 28: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/28.jpg)
NO‐BREAK KS® LV Parallel – Tier IV Design
TIER 4
PROXIMUS GAM EVERE :
PROXIMUS MECHELEN:
PROXIMUS SURFHOUSE EVERE:
4+4 NO-BREAK KS ® of 1000 kVA
2+2 NO-BREAK KS ® of 1600 kVA
2+2 NO-BREAK KS ® of 1000 kVA
![Page 29: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/29.jpg)
NO‐BREAK KS® MV Parallel – Tier IV Design
TIER 4
PROXIMUS MACHELEN: 5+5 NO-BREAK KS ® of 1700 kVA
![Page 30: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/30.jpg)
NO‐BREAK KS® LV Parallel – Tier IV Design
TIER 4
Critical load
50%
• Active capacity :
• Distribution path:
• Concurrently Maintainable:
• Fault Tolerant:
N+N
2 Active
YES
YES
50%
Load repartition
![Page 31: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/31.jpg)
NO‐BREAK KS® Distributed Redundant
66% 66% 66%
Load repartition
![Page 32: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/32.jpg)
NO‐BREAK KS® Distributed Redundant
TIER 4
• Active capacity element to support active load : N+N
• Distribution path: 2 active
• Concurrently Maintainable: YES
• Fault Tolerant: YES
![Page 33: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/33.jpg)
SOME OF OUR MAJOR REFERENCESIN DATA CENTRES
![Page 34: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/34.jpg)
NO‐BREAK KS®5 16 x 2500 kVA, 400V
Etisalat Data Centre, Khalifa City A, Abu Dhabi, UAE
![Page 35: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/35.jpg)
NO‐BREAK KS®5 10 x 1600 kVA, 415 V
Meeza Data Center, Qatar
![Page 36: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/36.jpg)
NO‐BREAK KS®5 SB 18 X 1650 kVA, 400V
Standard Bank of South Africa , Samrand, Midrand
![Page 37: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/37.jpg)
NO‐BREAK KS®5SB 2 x 2500 kVA, 13.8 kV
Telus Modular data center, Rimouski , Canada
![Page 38: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/38.jpg)
Ascenty Data Center, Jundiaí, Brazil
NO‐BREAK KS®5SB 9 x 1700 kVA, 13,8 kV
![Page 39: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/39.jpg)
Ascenty Data Center, Hortolândia, Brazil
NO‐BREAK KS®5SB 9 x 1700 kVA, 480 V
![Page 40: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/40.jpg)
KEPPEL DATAHUB T27, Singapore
NO‐BREAK KS®5 6 x 2000 kVA, 415V
![Page 41: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/41.jpg)
Cisco Systems TX‐DC2, Dallas, USA
NO‐BREAK KS®5 SB 8 x 2100 kW, 4.16 kV
![Page 42: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/42.jpg)
NO‐BREAK KS®5 SB 16 x 2500 kVA, 400V
Natixis, France
![Page 43: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/43.jpg)
Global Switch, London, UK
NO‐BREAK KS®5 26 x 2000 kVA, 11 kV
![Page 44: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/44.jpg)
NO‐BREAK KS®5 8 x 2250 kVA, 11 kV
Global Switch, Sydney, Australia
![Page 45: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/45.jpg)
Global Switch, Hong Kong
NO‐BREAK KS®7 12 x 2625 kVA, 11 kV
![Page 46: (DRUPS) and its integration in "Uptime Institute Tier"](https://reader033.fdocuments.in/reader033/viewer/2022042605/585ccef81a28abed2190a1d8/html5/thumbnails/46.jpg)
For More Information • Please See Us ......
Thank You For Your Attention • With Compliments
Speaker • EURO‐DIESEL SA