DOCUMENTAÇÃO TÉCNICA AC SANYO

223
FILE NO. 1 Section 2 3 4 5 TECHNICAL DATA & SERVICE MANUAL 0.8180.219.2 11/02 SPW-XR253GH56 / SPW-CR253EHL5 SPW-XR253GH56 / SPW-CR253EL5 SPW-XR253GH56 / SPW-CR253EHL8 SPW-XR253GH56 / SPW-CR253EL8 SPW-XR363GH56 / SPW-CR363EHL8 SPW-XR363GH56 / SPW-CR363EL8 SPW-XR483GH56 / SPW-CR483EHL8 SPW-XR483GH56 / SPW-CR483EL8 SPW-UR253GHN56 / SPW-CR253EHL5 SPW-UR253GHN56 / SPW-CR253EL5 SPW-UR253GHN56 / SPW-CR253EHL8 SPW-UR253GHN56 / SPW-CR253EL8 SPW-UR363GHN56 / SPW-CR363EHL8 SPW-UR363GHN56 / SPW-CR363EL8 SPW-UR483GHN56 / SPW-CR483EHL8 SPW-UR483GHN56 / SPW-CR483EL8 SPW-TR253GH56 / SPW-CR253EHL5 SPW-TR253GH56 / SPW-CR253EL5 SPW-TR253GH56 / SPW-CR253EHL8 SPW-TR253GH56 / SPW-CR253EL8 SPW-TR363GH56 / SPW-CR363EHL8 SPW-TR363GH56 / SPW-CR363EL8 SPW-TR483GH56 / SPW-CR483EHL8 SPW-TR483GH56 / SPW-CR483EL8 SPW-DR253GH56 / SPW-CR253EHL5 SPW-DR253GH56 / SPW-CR253EL5 SPW-DR253GH56 / SPW-CR253EHL8 SPW-DR253GH56 / SPW-CR253EL8 SPW-DR363GH56 / SPW-CR363EHL8 SPW-DR363GH56 / SPW-CR363EL8 SPW-DR483GH56 / SPW-CR483EHL8 SPW-DR483GH56 / SPW-CR483EL8 SPLIT SYSTEM AIR CONDITIONER OUTDOOR MODEL No. PRODUCT CODE No. SPW-CR253EHL5 854 015 40 SPW-CR253EL5 854 015 57 SPW-CR253EHL8 854 015 41 SPW-CR253EL8 854 015 46 SPW-CR363EHL8 854 015 42 SPW-CR363EL8 854 015 47 SPW-CR483EHL8 854 015 43 SPW-CR483EL8 854 015 48 INDOOR MODEL No. PRODUCT CODE No. SPW-XR253GH56 854 014 17 SPW-XR363GH56 854 014 18 SPW-XR483GH56 854 014 19 SPW-TR253GH56 854 014 31 SPW-TR363GH56 854 014 32 SPW-TR483GH56 854 014 33 SPW-UR253GHN56 854 015 85 SPW-UR363GHN56 854 015 86 SPW-UR483GHN56 854 015 87 SPW-DR253GH56 854 014 34 SPW-DR363GH56 854 014 35 SPW-DR483GH56 854 014 36 Indoor Unit Outdoor Unit SPW-CR253EHL5, SPW-CR253EHL8 SPW-CR253EL5 , SPW-CR253EL8 SPW-CR363EHL8, SPW-CR483EHL8 SPW-CR363EL8 , SPW-CR483EL8 SPW-XR253GH56 SPW-UR253GHN56 SPW-DR253GH56 SPW-DR363GH56 SPW-DR483GH56 SPW-TR253GH56 SPW-TR363GH56 SPW-TR483GH56 SPW-XR363GH56 SPW-XR483GH56 SPW-UR363GHN56 SPW-UR483GHN56

Transcript of DOCUMENTAÇÃO TÉCNICA AC SANYO

Page 1: DOCUMENTAÇÃO TÉCNICA AC SANYO

FILE NO.

1

Section

2

3

4

5

TECHNICAL DATA&

SERVICE MANUAL

0.8180.219.2 11/02

SPW-XR253GH56 ⁄ SPW-CR253EHL5SPW-XR253GH56 ⁄ SPW-CR253EL5SPW-XR253GH56 ⁄ SPW-CR253EHL8SPW-XR253GH56 ⁄ SPW-CR253EL8SPW-XR363GH56 ⁄ SPW-CR363EHL8SPW-XR363GH56 ⁄ SPW-CR363EL8SPW-XR483GH56 ⁄ SPW-CR483EHL8SPW-XR483GH56 ⁄ SPW-CR483EL8

SPW-UR253GHN56 ⁄ SPW-CR253EHL5SPW-UR253GHN56 ⁄ SPW-CR253EL5SPW-UR253GHN56 ⁄ SPW-CR253EHL8SPW-UR253GHN56 ⁄ SPW-CR253EL8SPW-UR363GHN56 ⁄ SPW-CR363EHL8SPW-UR363GHN56 ⁄ SPW-CR363EL8SPW-UR483GHN56 ⁄ SPW-CR483EHL8SPW-UR483GHN56 ⁄ SPW-CR483EL8

SPW-TR253GH56 ⁄ SPW-CR253EHL5SPW-TR253GH56 ⁄ SPW-CR253EL5SPW-TR253GH56 ⁄ SPW-CR253EHL8SPW-TR253GH56 ⁄ SPW-CR253EL8SPW-TR363GH56 ⁄ SPW-CR363EHL8SPW-TR363GH56 ⁄ SPW-CR363EL8SPW-TR483GH56 ⁄ SPW-CR483EHL8SPW-TR483GH56 ⁄ SPW-CR483EL8

SPW-DR253GH56 ⁄ SPW-CR253EHL5SPW-DR253GH56 ⁄ SPW-CR253EL5SPW-DR253GH56 ⁄ SPW-CR253EHL8SPW-DR253GH56 ⁄ SPW-CR253EL8SPW-DR363GH56 ⁄ SPW-CR363EHL8SPW-DR363GH56 ⁄ SPW-CR363EL8SPW-DR483GH56 ⁄ SPW-CR483EHL8SPW-DR483GH56 ⁄ SPW-CR483EL8

SPLIT SYSTEM AIR CONDITIONER OUTDOOR MODEL No. PRODUCT CODE No.

SPW-CR253EHL5 854 015 40

SPW-CR253EL5 854 015 57

SPW-CR253EHL8 854 015 41

SPW-CR253EL8 854 015 46

SPW-CR363EHL8 854 015 42

SPW-CR363EL8 854 015 47

SPW-CR483EHL8 854 015 43

SPW-CR483EL8 854 015 48

INDOOR MODEL No. PRODUCT CODE No.

SPW-XR253GH56 854 014 17

SPW-XR363GH56 854 014 18

SPW-XR483GH56 854 014 19

SPW-TR253GH56 854 014 31

SPW-TR363GH56 854 014 32

SPW-TR483GH56 854 014 33

SPW-UR253GHN56 854 015 85

SPW-UR363GHN56 854 015 86

SPW-UR483GHN56 854 015 87

SPW-DR253GH56 854 014 34

SPW-DR363GH56 854 014 35

SPW-DR483GH56 854 014 36

Indoor Unit Outdoor Unit

SPW-CR253EHL5, SPW-CR253EHL8SPW-CR253EL5 , SPW-CR253EL8

SPW-CR363EHL8, SPW-CR483EHL8SPW-CR363EL8 , SPW-CR483EL8

SPW-XR253GH56

SPW-UR253GHN56 SPW-DR253GH56SPW-DR363GH56SPW-DR483GH56

SPW-TR253GH56SPW-TR363GH56SPW-TR483GH56

SPW-XR363GH56SPW-XR483GH56

SPW-UR363GHN56SPW-UR483GHN56

Page 2: DOCUMENTAÇÃO TÉCNICA AC SANYO

iSM830080

Please Read Before Starting

This air conditioning system meets strict safety andoperating standards. As the installer or service person, itis an important part of your job to install or service thesystem so it operates safely and efficiently.

For safe installation and trouble-free operation, youmust :

Carefully read this instruction booklet before beginning.

Follow each installation or repair step exactly as shown.

Observe all local, state, and national electrical codes.

Pay close attention to all warning and caution noticesgiven in this manual.

This symbol refers to ahazard or unsafe practicewhich can result in severepersonal injury or death.

This symbol refers to ahazard or unsafe practicewhich can result in personalinjury or product or propertydamage.

If Necessary, Get HelpThese instructions are all you need for most installationsites and maintenance conditions. If you require help for aspecial problem, contact our sales/service outlet or yourcertified dealer for additional instructions.

In Case of Improper InstallationThe manufacturer shall in no way be responsible forimproper installation or maintenance service, includingfailure to follow the instructions in this document.

SPECIAL PRECAUTIONS

When Wiring……………………………………………………………………

ELECTRICAL SHOCK CAN CAUSESEVERE PERSONAL INJURY OR DEATH.ONLY A QUALIFIED, EXPERIENCEDELECTRICIAN SHOULD ATTEMPT TOWIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring andtubing are completed or reconnected and checked.

• Highly dangerous electrical voltages are used in thissystem. Carefully refer to the wiring diagram and theseinstructions when wiring. Improper connections andinadequate grounding can cause accidental injury ordeath .

• Ground the unit following local electrical codes.

• Connect all wiring tightly. Loose wiring may causeoverheating at connection points and a possible firehazard.

When Transporting……………………………………………………………………

Be careful when picking up and moving the indoor andoutdoor units. Get a partner to help, and bend your kneeswhen lifting to reduce strain on your back. Sharp edges orthin aluminum fins on the air conditioner can cut yourfingers.

Important

CAUTION

When Installing……………………………………………………………………

…In a RoomProperly insulate any tubing run inside a room to prevent“sweating” that can cause dripping and water damage towalls and floors.

…In Moist or Uneven LocationsUse a raised concrete pad or concrete blocks to provide asolid, level foundation for the outdoor unit. This preventswater damage and abnormal vibration.

…In an area with High WindsSecurely anchor the outdoor unit down with bolts and ametal frame. Provide a suitable air baffle.

…In a Snowy Area (for Heat Pump-type Sys-tems)Install the outdoor unit on a raised platform that is higherthan drifting snow. Provide snow vents.

When Connecting Refrigerant Tubing……………………………………………………………………

• Ventilate the room well, in the event that refrigerant gasleaks during the installation. Be careful not to allowcontact of the refrigerant gas with a flame as this willcause the generation of poisonous gas.

• Keep all tubing runs as short as possible.

• Use the flare method for connecting tubing.

• Apply refrigerant lubricant to the matching surfaces ofthe flare and union tubes before connecting them, thentighten the nut with a torque wrench for a leak-freeconnection.

• Check carefully for leaks before starting the test run.

NOTEDepending on the system type, liquid and gas lines maybe either narrow or wide. Therefore, to avoid confusion therefrigerant tubing for your particular model is specified aseither “narrow” or “wide” rather than as “liquid” or “gas”.

When Servicing……………………………………………………………………

• Turn the power OFF at the main power box (mains)before opening the unit to check or repair electricalparts and wiring.

• Keep your fingers and clothing away from any movingparts.

• Clean up the site when installation is finished. Checkthat no metal scraps or bits of wiring have been leftinside the unit.

CAUTION

• Ventilate any enclosed areas when installing or testingthe refrigeration system. Contact of refrigerant gas withfire or heat can produce poisonous gas.

• Confirm after installation that no refrigerant gas isleaking. If the gas comes in contact with a burningstove, gas water heater, electric room heater or otherheat source, it can cause the generation of poisonousgas.

Page 3: DOCUMENTAÇÃO TÉCNICA AC SANYO

iiSM830080

WHO SHOULD USE THIS MANUAL

This service manual is made to assist the service technician apply his knowledge andtraining to this model air conditioner. This manual is written both for experienced servicepersons and those who are new to air conditioning service. To help those with lessexperience or who are new to this kind of unit we have included more explanations ofbasic procedures in simple language than is usual in some service manuals. The experi-enced technician will of course find he knows many of these things already and can godirectly to the procedures and information he needs; the less experienced technician willbetter understand what to do even before he arrives on the job, and therefore be betterable to work by himself as well as assist the more experienced technician.

TABLE OF CONTENTS

1. SPECIFICATIONS ............................................................................................ I - 11-1 Unit Specifications ..................................................................................... I - 21-2 Major Component Specifications ............................................................... I - 34

(A) Indoor Units.......................................................................................... I - 34(B) Outdoor Units ....................................................................................... I - 46

1-3 Other Component Specifications ............................................................... I - 521-4 Dimensional Data ...................................................................................... I - 60

(A) Indoor Units.......................................................................................... I - 60(B) Outdoor Units ....................................................................................... I - 67

1-5 Refrigerant Flow Diagram .......................................................................... I - 691-6 Operating Range ....................................................................................... I - 721-7 Cooling Capacity........................................................................................ I - 731-8 Noise Criterion Curves............................................................................... I - 901-9 Indoor Fan Performance ............................................................................ I - 951-10 Air throw Distance Chart ............................................................................ I - 971-11 Installation Instructions .............................................................................. I - 99

2. PROCESSES AND FUNCTIONS ...................................................................... II - 12-1 Room Temperature Control ...................................................................... II - 2

(A) Cooling ................................................................................................ II - 2(B) Heating................................................................................................ II - 3

2-2 Cold Draft Prevention (Heating Cycle) ...................................................... II - 42-3 Automatic Fan Speed (Indoor Unit) .......................................................... II - 5

(A) Cooling ................................................................................................ II - 5(B) Heating................................................................................................ II - 5

2-4 Outdoor Fan Speed Control ...................................................................... II - 6(A) Cooling ................................................................................................ II - 6(B) Heating................................................................................................ II - 6

2-5 Freeze Prevention (Cooling) ..................................................................... II - 72-6 Condensing Temperature Control (Cooling) ............................................. II - 8

Page 4: DOCUMENTAÇÃO TÉCNICA AC SANYO

iiiSM830080

2-7 Overload Protection (Heating) .................................................................. II - 92-8 Discharge Temperature Control (Cooling and Heating) ........................... II - 102-9 Auto. Mode for Automatic Heating/Cooling Switching .............................. II - 112-10 Defrosting Control, Outdoor Heat Exchanger Coil (Heating) .................... II - 122-11 4-Way Valve, Solenoid Control ................................................................. II - 13

(A) Normal Control Mode .......................................................................... II - 13(B) AUTO Control Mode ........................................................................... II - 14

2-12 Automatic Restart after Power Interruption ............................................... II - 142-13 Electronic Expansion Control Valve.......................................................... II - 152-14 Compressor Discharge Gas Temperature ................................................ II - 15

(A) Cooling ................................................................................................ II - 15(B) Heating (Except During Defrosting) .................................................... II - 15

2-15 Compressor Current Detection Circuit ...................................................... II - 162-16 Dehumidifying Operation .......................................................................... II - 172-17 Auto-flap Control ....................................................................................... II - 182-18 Controlled by Electronic Expansion Valve ................................................ II - 192-19 Voltage Detection Control ......................................................................... II - 20

3. ELECTRICAL DATA ........................................................................................ III - 13-1 Indoor Unit (Electric Wiring Diagram, Schematic Diagram) ..................... III - 23-2 Outdoor Unit (Electric Wiring Diagram, Schematic Diagram) .................. III - 14

4. SERVICE PROCEDURES ............................................................................... IV - 14-1 Troubleshooting ...................................................................................... IV - 24-2 Checking the Electrical Components ...................................................... IV - 36

5. APPENDIX ....................................................................................................... V - 15-1 P.C.B. ...................................................................................................... V - 2

Page 5: DOCUMENTAÇÃO TÉCNICA AC SANYO

ivSM830080

WHAT IS IN THIS MANUALIntroduction: Read Me First!

This manual will help you understand and service the air conditioner. To help you find the information youneed, we have divided it into 5 main sections. Each section is divided into chapters with charts, tables andexplanations to help you find and repair problems.

Section 1: Specifications, tells you about the physical and electrical make up of the unit, aswell as its heating and cooling capacities. Look in this section to find the correct values forcomponents and functions.

Section 2: Processes and Functions, explains each different part of the cooling andheating cycle, and how each control function reacts to changing conditions to keep the roomat the set temperature range.

Section 3: Electrical Data , which has fold-out schematic and wiring diagrams so you canfind the parts you need to check when something is wrong, and see how they should beconnected.

Section 4: Service Procedures, has two main parts, a diagnostic chapter to help you findthe specific component to replace or adjust, and a chapter with specific procedures andvalues to guide you in checking the electrical components in the unit.

HOW TO USE THIS MANUAL

You can use this manual both as a reference to find specific information about the capacity, functions andconstruction of this unit, and as a source of information to help you set up and maintain the unit.When this unit is not working properly, and the cause is not known, you can use the procedures inSection 3: Servicing Procedures to find the problem, fix it, and restore the unit to its proper functioning.

This air conditioner has many helpful self diagnostic features to help you identify problem areas quickly.

So you will be ready when a problem happens, we suggest you look this manual over and become familiarwith it by following these steps:

1. Look at the TABLE OF CONTENTS to get an idea of what is in this manual and where tofind it.

2. Look at the chapter about TROUBLE SHOOTING , so you are familiar with the way the flowcharts work. They are designed to guide you quickly through the possible causes for eachkind of problem that is likely to happen to the Unit. Particularly read the introduction to thissection, and the parts about the self-diagnosis and error codes which show on the display.

3. Look at the chapter about CHECKING ELECTRICAL COMPONENTS. You already knowabout most of these procedures. This chapter gives you the specific values and methods forthese components. If you don’t know some of these procedures, you can easily learn themhere.

4. Read the Instruction Manual! The Instruction Manual is included here because it helps youhelp the user to set the temperature controls properly and know how to take care of anysimple problems that may happen, as well as know when to call for service. The InstructionManual also has illustrations, care, and installation information not found in the rest of theservice manual. It is short, and if you read it carefully, you will be able to answer thecustomers questions easily, and also know the most efficient ways for setting times andtemperatures.

Please use this manual to make your work easier, keep the air conditioner functioning well, and keep yourcustomers satisfied.

Page 6: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 1SM830080

1. SPECIFICATIONS

1-1 Unit Specifications ................................................................................. I - 24-Way Air Discharge Semi-concealed Type ........................................... I - 2Ceiling Mounted Type .............................................................................. I - 10Concealed Duct Type .............................................................................. I - 18Concealed Duct High Static Pressure Type ............................................ I - 26

1-2 Major Component Specifications ............................................................. I - 34(A) Indoor Units ........................................................................................ I - 34(B) Outdoor Units ..................................................................................... I - 46

1-3 Other Component Specifications ............................................................. I - 524-Way Air Discharge Semi-concealed Type ........................................... I - 52Ceiling Mounted Type .............................................................................. I - 53Concealed Duct High Static Pressure Type ............................................ I - 54Concealed Duct Type .............................................................................. I - 55Outdoor Units........................................................................................... I - 56

1-4 Dimensional Data .................................................................................... I - 60(A) Indoor Units ........................................................................................ I - 60

4-Way Air Discharge Semi-concealed Type....................................... I - 60Ceiling Mounted Type ........................................................................ I - 62Concealed Duct Type ......................................................................... I - 63Concealed Duct High Static Pressure Type ....................................... I - 66

(B) Outdoor Units ..................................................................................... I - 671-5 Refrigerant Flow Operating Range .......................................................... I - 691-6 Operating Range ..................................................................................... I - 721-7 Cooling Capacity ...................................................................................... I - 731-8 Noise Criterion Curves............................................................................. I - 901-9 Indoor Fan Performance .......................................................................... I - 951-10 Air throw Distance Chart .......................................................................... I - 971-11 Installation Instructions ............................................................................ I - 99

Tubing Length .......................................................................................... I - 99Selecting the Installation Site................................................................... I -100Electrical Wiring ....................................................................................... I -104Electrical Characteristics ......................................................................... I -107

Page 7: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 2SM830080

1-1 Unit Specifications

4-Way Air Discharge Semi-concealed Type

MODEL No. Indoor Unit SPW-XR253GH56Outdoor Unit SPW-CR253EL5

POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 HzPERFORMANCE Cooling

Capacity kW 7.3BTU / h 25,000

Air circulation (Hi / Me / Lo) m3/h 1,140 / 1,020 / 840Moisture removal (High) Liters/h 3.6

ELECTRICAL RATINGSVoltage rating V 220 230 240Available voltage range V 198 – 264Running amperes* A 13.32 13.46 13.58Max. running amperes** A 14.66 14.72 14.76Power input kW 2.81 2.93 3C.O.P W / W 2.6 2.49 2.43Max. starting amperes A 69 72 75

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-5PS3EWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 37 / 35 / 31

Outdoor - Hi dB - A 52Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit (Include panel) Outdoor unitUnit dimensions Height mm (in.) 328 (12 - 29 / 32) 735 (28 - 30 / 32)

Width mm (in.) 860 (33 - 27 / 32) 940 (37 )Depth mm (in.) 860 (33 - 27 / 32) 340 (13 - 12 / 32)

Package dimensions Body : SPW-X253GH56 Panel : PNR-X253GHA Outdoor unitHeight mm (in.) 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32)Width mm (in.) 824 (32 - 14 / 32) 967 (38 - 2 / 32) 1,016 (40 )Depth mm (in.) 833 (32 - 25 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 30 (66) 69 ( 152)Shipping weight kg (lb.) 27 ( 60 ) 8 ( 18) 75 ( 165 )Shipping volume m3 (cu. ft) 0.195 ( 6.9 ) 0.1 ( 3.5) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 8: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 3SM830080

1-1 Unit Specifications

4-Way Air Discharge Semi-concealed Type

MODEL No. Indoor Unit SPW-XR253GH56Outdoor Unit SPW-CR253EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 7.3BTU / h 25,000

Air circulation (Hi / Me / Lo) m3/h 1,140 / 1,020 / 840Moisture removal (High) Liters/h 3.6

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 4.82 4.78 4.73Max. running amperes** A 5.67 5.68 5.69Power input kW 2.76 2.79 2.82C.O.P W / W 2.64 2.62 2.59Max. starting amperes A 27 29 30

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-5PS3EWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 37 / 35 / 31

Outdoor - Hi dB - A 52Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit (Include panel) Outdoor unitUnit dimensions Height mm (in.) 328 (12 - 29 / 32) 735 (28 - 30 / 32)

Width mm (in.) 860 (33 - 27 / 32) 940 (37 )Depth mm (in.) 860 (33 - 27 / 32) 340 (13 - 12 / 32)

Package dimensions Body : SPW-XR253GH56 Panel : PNR-X253GHA Outdoor unitHeight mm (in.) 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32)Width mm (in.) 824 (32 - 14 / 32) 967 (38 - 2 / 32) 1,016 (40 )Depth mm (in.) 833 (32 - 25 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 30 (66) 69 ( 152)Shipping weight kg (lb.) 27 ( 60) 8 ( 18) 75 ( 165)Shipping volume m3 (cu. ft) 0.195 ( 6.9) 0.1 ( 3.5) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 9: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 4SM830080

1-1 Unit Specifications

4-Way Air Discharge Semi-concealed Type

MODEL No. Indoor Unit SPW-XR363GH56Outdoor Unit SPW-CR363EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 10.6BTU / h 36,000

Air circulation (Hi / Me / Lo) m3/h 1,920 / 1,680 / 1,320Moisture removal (High) Liters/h 4.6

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 7.01 7.02 7.05Max. running amperes** A 7.86 7.87 7.9Power input kW 3.92 3.97 4.02C.O.P W / W 2.7 2.67 2.64Max. starting amperes A 47 49 50

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-5PS3EWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 43 / 40 / 36

Outdoor - Hi dB - A 53Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.0

DIMENSIONS & WEIGHT Indoor unit (Include panel) Outdoor unitUnit dimensions Height mm (in.) 358 (14 - 3 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,150 (45 - 9 / 32) 940 (37 )Depth mm (in.) 860 (33 - 27 / 32) 340 (13 - 12 / 32)

Package dimensions Body : SPW-XR363GH56 Panel : PNR-X483GHA Outdoor unitHeight mm (in.) 316 (12 - 14 / 32) 104 ( 4 - 3 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,114 (43 - 27 / 32) 1,257 (49 - 16 / 32) 1,016 (40 )Depth mm (in.) 860 (33 - 27 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 38 (84) 104 ( 229)Shipping weight kg (lb.) 32 ( 71 ) 10 ( 22) 111 ( 245 )Shipping volume m3 (cu. ft) 0.303 (10.7) 0.131 ( 4.6) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 10: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 5SM830080

1-1 Unit Specifications

4-Way Air Discharge Semi-concealed Type

MODEL No. Indoor Unit SPW-XR483GH56Outdoor Unit SPW-CR483EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 12.6BTU / h 43,000

Air circulation (Hi / Me / Lo) m3/h 1,920 / 1,680 / 1,320Moisture removal (High) Liters/h 6.3

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 8.35 8.35 8.37Max. running amperes** A 9.47 9.47 9.49Power input kW 4.6 4.64 4.67C.O.P W / W 2.74 2.72 2.70Max. starting amperes A 53 56 58

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-5PS3EWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 43 / 40 / 36

Outdoor - Hi dB - A 55Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.5

DIMENSIONS & WEIGHT Indoor unit (Include panel) Outdoor unitUnit dimensions Height mm (in.) 358 (14 - 3 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,150 (45 - 9 / 32) 940 (37 )Depth mm (in.) 860 (33 - 27 / 32) 340 (13 - 12 / 32)

Package dimensions Body : SPW-XR483GH56 Panel : PNR-X483GHA Outdoor unitHeight mm (in.) 316 (12 - 14 / 32) 104 ( 4 - 3 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,114 (43 - 27 / 32) 1,257 (49 -16 / 32) 1,016 (40 )Depth mm (in.) 860 (33 - 27 / 32) 999 (39 -11 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 38 (84) 106 ( 234)Shipping weight kg (lb.) 32 ( 71 ) 10 ( 22) 113 ( 249 )Shipping volume m3 (cu. ft) 0.303 (10.7) 0.131 ( 4.6) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 11: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 6SM830080

1-1 Unit Specifications

4-Way Air Discharge Semi-concealed Type

MODEL No. Indoor Unit SPW-XR253GH56Outdoor Unit SPW-CR253EHL5

POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 HzPERFORMANCE Cooling Heating

Capacity kW 7.3 8.6BTU / h 25,000 29,300

Air circulation (Hi / Me / Lo) m3/h 1,140 / 1,020 / 840Moisture removal (High) Liters/h 3.6 —

ELECTRICAL RATINGSVoltage rating V 220 230 240 220 230 240Available voltage range V 198 – 264 198 – 264Running amperes* A 13.32 13.46 13.58 14.69 14.64 14.57Max. running amperes** A 14.66 14.72 14.76 16.59 16.94 16.27Power input kW 2.81 2.93 3 3.07 3.14 3.21C.O.P W / W 2.6 2.49 2.43 2.8 2.74 2.68Max. starting amperes A 69 72 75 69 72 75

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-SH80TGWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 37 / 35 / 31

Outdoor - Hi dB - A 52Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit (Include panel) Outdoor unitUnit dimensions Height mm (in.) 328 (12 - 29 / 32) 735 (28 - 30 / 32)

Width mm (in.) 860 (33 - 27 / 32) 940 (37 )Depth mm (in.) 860 (33 - 27 / 32) 340 (13 - 12 / 32)

Package dimensions Body : SPW-XR253GH56 Panel : PNR-X253GHA Outdoor unitHeight mm (in.) 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32)Width mm (in.) 824 (32 - 14 / 32) 967 (38 - 2 / 32) 1,016 (40 )Depth mm (in.) 833 (32 - 25 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 30 (66) 71 ( 157)Shipping weight kg (lb.) 27 ( 60 ) 8 ( 18) 77 ( 170 )Shipping volume m3 (cu. ft) 0.195 ( 6.9 ) 0.1 ( 3.5) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 12: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 7SM830080

1-1 Unit Specifications

4-Way Air Discharge Semi-concealed Type

MODEL No. Indoor Unit SPW-XR253GH56Outdoor Unit SPW-CR253EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 7.3 8.6BTU / h 25,000 29,300

Air circulation (Hi / Me / Lo) m3/h 1,140 / 1,020 / 840Moisture removal (High) Liters/h 3.6 —

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 4.82 4.78 4.73 5.31 5.21 5.12Max. running amperes** A 5.67 5.68 5.69 5.41 5.32 5.22Power input kW 2.76 2.79 2.82 3 3.03 3.06C.O.P W / W 2.64 2.62 2.59 2.87 2.84 2.81Max. starting amperes A 27 29 30 27 29 30

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-SH80TGWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 37 / 35 / 31

Outdoor - Hi dB - A 52Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit (Include panel) Outdoor unitUnit dimensions Height mm (in.) 328 (12 - 29 / 32) 735 (28 - 30 / 32)

Width mm (in.) 860 (33 - 27 / 32) 940 (37 )Depth mm (in.) 860 (33 - 27 / 32) 340 (13 - 12 / 32)

Package dimensions Body : SPW-XR253GH56 Panel : PNR-X253GHA Outdoor unitHeight mm (in.) 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32)Width mm (in.) 824 (32 - 14 / 32) 967 (38 - 2 / 32) 1,016 (40 )Depth mm (in.) 833 (32 - 25 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 30 (66) 71 ( 157)Shipping weight kg (lb.) 27 ( 60 ) 8 ( 18) 77 ( 170 )Shipping volume m3 (cu. ft) 0.195 ( 6.9 ) 0.1 ( 3.5) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 13: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 8SM830080

1-1 Unit Specifications

4-Way Air Discharge Semi-concealed Type

MODEL No. Indoor Unit SPW-XR363GH56Outdoor Unit SPW-CR363EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 10.6 12.5BTU / h 36,000 42,700

Air circulation (Hi / Me / Lo) m3/h 1,920 / 1,680 / 1,320Moisture removal (High) Liters/h 4.6 —

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 7.01 7.02 7.05 7.58 7.6 7.64Max. running amperes** A 7.86 7.87 7.9 7.98 8 8.04Power input kW 3.92 3.97 4.02 4.26 4.3 4.33C.O.P W / W 2.7 2.67 2.64 2.93 2.91 2.89Max. starting amperes A 47 49 50 47 49 50

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-SH80TGWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 43 / 40 / 36

Outdoor - Hi dB - A 53Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.0

DIMENSIONS & WEIGHT Indoor unit (Include panel) Outdoor unitUnit dimensions Height mm (in.) 358 (14 - 3 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,150 (45 - 9 / 32) 940 (37 )Depth mm (in.) 860 (33 - 27 / 32) 340 (13 - 12 / 32)

Package dimensions Body : SPW-XR363GH56 Panel : PNR-X483GHA Outdoor unitHeight mm (in.) 316 (12 - 14 / 32) 104 ( 4 - 3 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,114 (43 - 27 / 32) 1,257 (49 -16 / 32) 1,016 (40 )Depth mm (in.) 860 (33 - 27 / 32) 999 (39 -11 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 38 (84) 106 ( 234)Shipping weight kg (lb.) 32 ( 71 ) 10 ( 22) 113 ( 249 )Shipping volume m3 (cu. ft) 0.303 (10.7) 0.131 ( 4.6) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 14: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 9SM830080

1-1 Unit Specifications

4-Way Air Discharge Semi-concealed Type

MODEL No. Indoor Unit SPW-XR483GH56Outdoor Unit SPW-CR483EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 12.6 15.3BTU / h 43,000 52,200

Air circulation (Hi / Me / Lo) m3/h 1,920 / 1,680 / 1,320Moisture removal (High) Liters/h 6.3 —

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 8.35 8.35 8.37 9.48 9.49 9.52Max. running amperes** A 9.47 9.47 9.49 9.99 10 10.02Power input kW 4.6 4.64 4.67 5.46 5.5 5.53C.O.P W / W 2.74 2.72 2.7 2.8 2.78 2.77Max. starting amperes A 53 56 58 53 56 58

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-SH80TGWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 25 cm above drain connection (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 43 / 40 / 36

Outdoor - Hi dB - A 55Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.5

DIMENSIONS & WEIGHT Indoor unit (Include panel) Outdoor unitUnit dimensions Height mm (in.) 358 (14 - 3 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,150 (45 - 9 / 32) 940 (37 )Depth mm (in.) 860 (33 -27 / 32) 340 (13 - 12 / 32)

Package dimensions Body : SPW-XR483GH56 Panel : PNR-X483GHA Outdoor unitHeight mm (in.) 316 (12 - 14 / 32) 104 ( 4 - 3 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,114 (43 - 27 / 32) 1,257 (49 -16 / 32) 1,016 (40 )Depth mm (in.) 860 (33 - 27 / 32) 999 (39 -11 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 38 (84) 108 ( 238)Shipping weight kg (lb.) 32 ( 71 ) 10 ( 22) 115 ( 254 )Shipping volume m3 (cu. ft) 0.303 (10.7) 0.131 ( 4.6) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 15: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 10SM830080

1-1 Unit Specifications

Ceiling Mounted Type

MODEL No. Indoor Unit SPW-TR253GH56Outdoor Unit SPW-CR253EL5

POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 HzPERFORMANCE Cooling

Capacity kW 7.3BTU / h 25,000

Air circulation (Hi / Me / Lo) m3/h 1,080 / 960 / 840Moisture removal (High) Liters/h 3.5

ELECTRICAL RATINGSVoltage rating V 220 230 240Available voltage range V 198 – 264Running amperes* A 13.15 13.27 13.38Max. running amperes** A 14.49 14.53 14.56Power input kW 2.77 2.89 2.95Power factor % 95.7 94.7 91.9C.O.P W / W 2.64 2.53 2.47Max. starting amperes A 69 72 75

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-5PS3EWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (20A, OD26 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 39 / 37 / 34

Outdoor - Hi dB - A 52Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 190 ( 7 - 15 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,300 (51 - 6 / 32) 940 (37 )Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 266 (10 - 15 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,403 (55 - 8 / 32) 1,016 (40 )Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 26 ( 57 ) 69 ( 152 )Shipping weight kg (lb.) 32 ( 71 ) 75 ( 165 )Shipping volume m3 (cu. ft) 0.294 (10.4) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 16: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 11SM830080

1-1 Unit Specifications

Ceiling Mounted Type

MODEL No. Indoor Unit SPW-TR253GH56Outdoor Unit SPW-CR253EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 7.3BTU / h 25,000

Air circulation (Hi / Me / Lo) m3/h 1,080 / 960 / 840Moisture removal (High) Liters/h 3.5

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 4.77 4.72 4.67Max. running amperes** A 5.62 5.63 5.64Power input kW 2.72 2.75 2.77Power factor % 86.6 84.1 82.5C.O.P W / W 2.68 2.65 2.64Max. starting amperes A 27 29 30

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-5PS3EWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (20A, OD26 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 39 / 37 / 34

Outdoor - Hi dB - A 52Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 190 ( 7 - 15 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,300 (51 - 6 / 32) 940 (37 )Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 266 (10 - 15 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,403 (55 - 8 / 32) 1,016 (40 )Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 26 ( 57 ) 69 ( 152 )Shipping weight kg (lb.) 32 ( 71 ) 75 ( 165 )Shipping volume m3 (cu. ft) 0.294 (10.4) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 17: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 12SM830080

1-1 Unit Specifications

Ceiling Mounted Type

MODEL No. Indoor Unit SPW-TR363GH56Outdoor Unit SPW-CR363EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 10.6BTU / h 36,000

Air circulation (Hi / Me / Lo) m3/h 1,800 / 1,560 / 1,200Moisture removal (High) Liters/h 4.7

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 7.01 7.02 7.06Max. running amperes** A 7.86 7.88 7.91Power input kW 3.92 3.97 4.02Power factor % 85 81.6 79.2C.O.P W / W 2.7 2.67 2.64Max. starting amperes A 47 49 50

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-5PS3EWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (20A, OD26 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 42 / 40 / 35

Outdoor - Hi dB - A 53Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.0

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 240 ( 9 - 14 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,575 (62 ) 940 (37 )Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 317 (12 - 15 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,678 (66 - 2 / 32) 1,016 (40 )Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 38 ( 84 ) 104 ( 229 )Shipping weight kg (lb.) 44 ( 97 ) 111 ( 245 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 18: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 13SM830080

1-1 Unit Specifications

Ceiling Mounted Type

MODEL No. Indoor Unit SPW-TR483GH56Outdoor Unit SPW-CR483EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 12.6BTU / h 43,000

Air circulation (Hi / Me / Lo) m3/h 1,920 / 1,680 / 1,320Moisture removal (High) Liters/h 5.9

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 8.35 8.35 8.38Max. running amperes** A 9.47 9.48 9.5Power input kW 4.6 4.64 4.67Power factor % 83.7 80.2 80.4C.O.P W / W 2.74 2.72 2.7Max. starting amperes A 53 56 58

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-5PS3EWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (20A, OD26 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 44 / 41 / 37

Outdoor - Hi dB - A 55Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.5

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 240 ( 9 - 14 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,575 (62 ) 940 (37 )Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 317 (12 - 15 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,678 (66 - 2 / 32) 1,016 (40 )Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 38 ( 84 ) 106 ( 234 )Shipping weight kg (lb.) 44 ( 97 ) 113 ( 249 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 19: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 14SM830080

1-1 Unit Specifications

Ceiling Mounted Type

MODEL No. Indoor Unit SPW-TR253GH56Outdoor Unit SPW-CR253EHL5

POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 HzPERFORMANCE Cooling Heating

Capacity kW 7.3 8.6BTU / h 25,000 29,300

Air circulation (Hi / Me / Lo) m3/h 1,080 / 960 / 840Moisture removal (High) Liters/h 3.5 —

ELECTRICAL RATINGSVoltage rating V 220 230 240 220 230 240Available voltage range V 198 – 264 198 – 264Running amperes* A 13.15 13.27 13.38 14.65 14.58 14.49Max. running amperes** A 14.49 14.53 14.56 16.55 16.38 16.19Power input kW 2.77 2.89 2.95 3.06 3.13 3.19Power factor % 95.7 94.7 91.9 94.9 93.3 91.7C.O.P W / W 2.64 2.53 2.47 2.81 2.75 2.7Max. starting amperes A 69 72 75 69 72 75

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-SH80TGWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (20A, OD26 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 39 / 37 / 34

Outdoor - Hi dB - A 52Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 190 ( 7 - 15 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,300 (51 - 6 / 32) 940 (37 )Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 266 (10 - 15 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,403 (55 - 8 / 32) 1,016 (40 )Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 26 ( 57 ) 71 ( 157 )Shipping weight kg (lb.) 32 ( 71 ) 77 ( 170 )Shipping volume m3 (cu. ft) 0.294 (10.4) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 20: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 15SM830080

1-1 Unit Specifications

Ceiling Mounted Type

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

MODEL No. Indoor Unit SPW-TR253GH56Outdoor Unit SPW-CR253EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 7.3 8.6BTU / h 25,000 29,300

Air circulation (Hi / Me / Lo) m3/h 1,080 / 960 / 840Moisture removal (High) Liters/h 3.5 —

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 4.77 4.72 4.67 4.9 4.8 4.7Max. running amperes** A 5.62 5.63 5.64 5.7 5.5 5.3Power input kW 2.72 2.75 2.77 2.81 2.82 2.85Power factor % 86.6 84.1 82.5 87.1 84.8 84.4C.O.P W / W 2.68 2.65 2.64 3.06 3.05 3.02Max. starting amperes A 27 29 30 27 29 30

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-SH80TGWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (20A, OD26 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 39 / 37 / 34

Outdoor - Hi dB - A 52Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 190 ( 7 - 15 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,300 (51 - 6 / 32) 940 (37 )Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 266 (10 - 15 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,403 (55 - 8 / 32) 1,016 (40 )Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 26 ( 57 ) 71 ( 157 )Shipping weight kg (lb.) 32 ( 71 ) 77 ( 170 )Shipping volume m3 (cu. ft) 0.294 (10.4) 0.349 (12.3)

Page 21: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 16SM830080

1-1 Unit Specifications

Ceiling Mounted Type

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

MODEL No. Indoor Unit SPW-TR363GH56Outdoor Unit SPW-CR363EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 10.6 12.5BTU / h 36,000 42,700

Air circulation (Hi / Me / Lo) m3/h 1,800 / 1,560 / 1,200Moisture removal (High) Liters/h 4.7 —

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 7.01 7.02 7.06 7.64 7.65 7.68Max. running amperes** A 7.86 7.88 7.91 8.04 8.05 8.09Power input kW 3.92 3.97 4.02 4.3 4.34 4.37Power factor % 85 81.6 79.2 85.5 81.9 79.2C.O.P W / W 2.7 2.67 2.64 2.91 2.88 2.86Max. starting amperes A 47 49 50 47 49 50

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-SH80TGWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (20A, OD26 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 42 / 40 / 35

Outdoor - Hi dB - A 53Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.0

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 240 ( 9 - 14 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,575 (62 ) 940 (37 )Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 317 (12 - 15 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,678 (66 - 2 / 32) 1,016 (40 )Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 38 ( 84 ) 106 ( 234 )Shipping weight kg (lb.) 44 ( 97 ) 113 ( 249 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.56 (19.8)

Page 22: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 17SM830080

1-1 Unit Specifications

Ceiling Mounted Type

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

MODEL No. Indoor Unit SPW-TR483GH56Outdoor Unit SPW-CR483EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 12.6 15.3BTU / h 43,000 52,200

Air circulation (Hi / Me / Lo) m3/h 1,920 / 1,680 / 1,320Moisture removal (High) Liters/h 5.9 —

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 8.35 8.35 8.38 9.54 9.54 9.56Max. running amperes** A 9.47 9.48 9.5 10.05 10.05 10.07Power input kW 4.6 4.64 4.67 5.5 5.54 5.57Power factor % 83.7 80.2 77.5 87.6 83.8 81.1C.O.P W / W 2.74 2.72 2.7 2.78 2.76 2.75Max. starting amperes A 53 56 58 53 56 58

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hours ON/OFF 24-hours & ProgramFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) Automatic (Remote control)Air filter Washable, easy access, long life (2,500 hr)Remote controller (Option) Wired : RCS-SH80TG Wireless : RCS-SH80TGWLRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (20A, OD26 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 44 / 41 / 37

Outdoor - Hi dB - A 55Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.5

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 240 ( 9 - 14 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,575 (62 ) 940 (37 )Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 317 (12 - 15 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,678 (66 - 2 / 32) 1,016 (40 )Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 38 ( 84 ) 108 ( 238 )Shipping weight kg (lb.) 44 ( 97 ) 115 ( 254 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.56 (19.8)

Page 23: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 18SM830080

1-1 Unit Specifications

Concealed Duct High Static Pressure Type

MODEL No. Indoor Unit SPW-DR253GH56Outdoor Unit SPW-CR253EL5

POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 HzPERFORMANCE Cooling

Capacity kW 7.3BTU / h 25,000

Air circulation (Hi / Me / Lo) m3/h 1,380 / 1,320 / 1,260Moisture removal (High) Liters/h 3.1External static pressure (High) mmAq(Pa) 19 (186) : at shipment

ELECTRICAL RATINGSVoltage rating V 220 230 240Available voltage range V 198 – 264Running amperes* A 15.01 15.14 15.26Max. running amperes** A 16.35 16.4 16.44Power input kW 3.16 3.3 3.38Power factor % 95.7 94.8 92.3C.O.P W / W 2.31 2.21 2.16Max. starting amperes A 71 74 77

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 44 / 43 / 42

Outdoor - Hi dB - A 52Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 420 (16 - 17 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,065 (41 - 30 / 32) 940 (37 )Depth mm (in.) 620 (24 - 13 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 513 (20 - 6 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,148 (45 - 6 / 32) 1,016 (40 )Depth mm (in.) 713 (28 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 47 ( 104 ) 69 ( 152 )Shipping weight kg (lb.) 61 ( 134 ) 75 ( 165 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 24: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 19SM830080

1-1 Unit Specifications

Concealed Duct High Static Pressure Type

MODEL No. Indoor Unit SPW-DR253GH56Outdoor Unit SPW-CR253EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 7.3BTU / h 25,000

Air circulation (Hi / Me / Lo) m3/h 1,380 / 1,320 / 1,260Moisture removal (High) Liters/h 3.1External static pressure (High) mmAq(Pa) 19 (186) : at shipment

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 5.3 5.24 5.19Max. running amperes** A 6.15 6.14 6.14Power input kW 3.11 3.16 3.2Power factor % 89.2 87 85.8C.O.P W / W 2.35 2.31 2.28Max. starting amperes A 29 31 32

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 44 / 43 / 42

Outdoor - Hi dB - A 52Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 420 (16 - 17 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,065 (41 - 30 / 32) 940 (37 )Depth mm (in.) 620 (24 - 13 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 513 (20 - 6 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,148 (45 - 6 / 32) 1,016 (40 )Depth mm (in.) 713 (28 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 47 ( 104 ) 69 ( 152 )Shipping weight kg (lb.) 61 ( 134 ) 75 ( 165 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 25: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 20SM830080

1-1 Unit Specifications

Concealed Duct High Static Pressure Type

MODEL No. Indoor Unit SPW-DR363GH56Outdoor Unit SPW-CR363EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 10.6BTU / h 36,000

Air circulation (Hi / Me / Lo) m3/h 1,800 / 1,680 / 1,500Moisture removal (High) Liters/h 4.4External static pressure (High) mmAq(Pa) 18 (176) : at shipment

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 7.43 7.43 7.45Max. running amperes** A 8.29 8.28 8.31Power input kW 4.24 4.31 4.37Power factor % 86.7 83.7 81.6C.O.P W / W 2.5 2.46 2.43Max. starting amperes A 49 51 52

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 45 / 44 / 42

Outdoor - Hi dB - A 53Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.0

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 420 (16 - 17 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,065 (41 - 30 / 32) 940 (37 )Depth mm (in.) 620 (24 - 13 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 513 (20 - 6 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,148 (45 - 6 / 32) 1,016 (40 )Depth mm (in.) 713 (28 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 50 ( 110 ) 104 ( 229 )Shipping weight kg (lb.) 64 ( 141 ) 111 ( 245 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 26: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 21SM830080

1-1 Unit Specifications

Concealed Duct High Static Pressure Type

MODEL No. Indoor Unit SPW-DR483GH56Outdoor Unit SPW-CR483EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 12.6BTU / h 43,000

Air circulation (Hi / Me / Lo) m3/h 2,160 / 2,100 / 1,980Moisture removal (High) Liters/h 5.4External static pressure (High) mmAq(Pa) 17 (167) : at shipment

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 8.87 8.89 8.92Max. running amperes** A 10.02 10.03 10.06Power input kW 5 5.09 5.16Power factor % 85.6 82.6 80.5C.O.P W / W 2.52 2.48 2.44Max. starting amperes A 55 58 60

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 47 / 46 / 44

Outdoor - Hi dB - A 55Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.5

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 450 (17 - 23 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,065 (41 - 30 / 32) 940 (37 )Depth mm (in.) 620 (24 - 13 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 513 (20 - 6 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,148 (45 - 6 / 32) 1,016 (40 )Depth mm (in.) 713 (28 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 54 ( 119 ) 106 ( 234 )Shipping weight kg (lb.) 69 ( 152 ) 113 ( 249 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 27: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 22SM830080

1-1 Unit Specifications

Concealed Duct High Static Pressure Type

MODEL No. Indoor Unit SPW-DR253GH56Outdoor Unit SPW-CR253EHL5

POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 HzPERFORMANCE Cooling Heating

Capacity kW 7.3 8.6BTU / h 25,000 29,300

Air circulation (Hi / Me / Lo) m3/h 1,380 / 1,320 / 1,260Moisture removal (High) Liters/h 3.1 —External static pressure (High) mmAq(Pa) 19 (186) : at shipment

ELECTRICAL RATINGSVoltage rating V 220 230 240 220 230 240Available voltage range V 198 – 264 198 – 264Running amperes* A 15.01 15.14 15.26 16.61 16.54 16.46Max. running amperes** A 16.35 16.4 16.44 18.51 18.34 18.16Power input kW 3.16 3.3 3.38 3.47 3.56 3.64Power factor % 95.7 94.8 92.3 95 93.6 92.1C.O.P W / W 2.31 2.21 2.16 2.48 2.42 2.36Max. starting amperes A 71 74 77 71 74 77

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 44 / 43 / 42

Outdoor - Hi dB - A 52Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 420 (16 - 17 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,065 (41 - 30 / 32) 940 (37 )Depth mm (in.) 620 (24 - 13 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 513 (20 - 6 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,148 (45 - 6 / 32) 1,016 (40 )Depth mm (in.) 713 (28 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 47 ( 104 ) 71 ( 157 )Shipping weight kg (lb.) 61 ( 134 ) 77 ( 170 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 28: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 23SM830080

1-1 Unit Specifications

Concealed Duct High Static Pressure Type

MODEL No. Indoor Unit SPW-DR253GH56Outdoor Unit SPW-CR253EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 7.3 8.6BTU / h 25,000 29,300

Air circulation (Hi / Me / Lo) m3/h 1,380 / 1,320 / 1,260Moisture removal (High) Liters/h 3.1 —External static pressure (High) mmAq(Pa) 19 (186) : at shipment

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 5.3 5.24 5.19 5.6 5.4 5.4Max. running amperes** A 6.15 6.14 6.14 6.4 6.1 5.9Power input kW 3.11 3.16 3.2 3.22 3.25 3.3Power factor % 89.2 87 85.8 87.4 86.9 85C.O.P W / W 2.35 2.31 2.28 2.67 2.65 2.61Max. starting amperes A 29 31 32 29 31 32

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 44 / 43 / 42

Outdoor - Hi dB - A 52Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 420 (16 - 17 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,065 (41 - 30 / 32) 940 (37 )Depth mm (in.) 620 (24 - 13 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 513 (20 - 6 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,148 (45 - 6 / 32) 1,016 (40 )Depth mm (in.) 713 (28 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 47 ( 104 ) 71 ( 157 )Shipping weight kg (lb.) 61 ( 134 ) 77 ( 170 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 29: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 24SM830080

1-1 Unit Specifications

Concealed Duct High Static Pressure Type

MODEL No. Indoor Unit SPW-DR363GH56Outdoor Unit SPW-CR363EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 10.6 12.5BTU / h 36,000 42,700

Air circulation (Hi / Me / Lo) m3/h 1,800 / 1,680 / 1,500Moisture removal (High) Liters/h 4.4 —External static pressure (High) mmAq(Pa) 18 (176) : at shipment

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 7.43 7.43 7.45 8.09 8.08 8.1Max. running amperes** A 8.29 8.28 8.31 8.49 8.48 8.51Power input kW 4.24 4.31 4.37 4.64 4.7 4.74Power factor % 86.7 83.7 81.6 87.1 84 81.4C.O.P W / W 2.5 2.46 2.43 2.69 2.66 2.64Max. starting amperes A 49 51 52 49 51 52

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 45 / 44 / 42

Outdoor - Hi dB - A 53Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.0

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 420 (16 - 17 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,065 (41 - 30 / 32) 940 (37 )Depth mm (in.) 620 (24 - 13 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 513 (20 - 6 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,148 (45 - 6 / 32) 1,016 (40 )Depth mm (in.) 713 (28 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 50 ( 110 ) 106 ( 234 )Shipping weight kg (lb.) 64 ( 141 ) 113 ( 249 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 30: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 25SM830080

1-1 Unit Specifications

Concealed Duct High Static Pressure Type

MODEL No. Indoor Unit SPW-DR483GH56Outdoor Unit SPW-CR483EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 12.6 15.3BTU / h 43,000 52,200

Air circulation (Hi / Me / Lo) m3/h 2,160 / 2,100 / 1,980Moisture removal (High) Liters/h 5.4 —External static pressure (High) mmAq(Pa) 17 (167) : at shipment

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 8.87 8.89 8.92 10.11 10.12 10.15Max. running amperes** A 10.02 10.03 10.06 10.62 10.63 10.66Power input kW 5 5.09 5.16 5.92 6.01 6.08Power factor % 85.6 82.6 80.5 89 85.7 83.3C.O.P W / W 2.52 2.48 2.44 2.58 2.55 2.52Max. starting amperes A 55 58 60 55 58 60

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) No (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 47 / 46 / 44

Outdoor - Hi dB - A 55Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.5

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 450 (17 - 23 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,065 (41 - 30 / 32) 940 (37 )Depth mm (in.) 620 (24 - 13 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 513 (20 - 6 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,148 (45 - 6 / 32) 1,016 (40 )Depth mm (in.) 713 (28 - 2 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 54 ( 119 ) 108 ( 238 )Shipping weight kg (lb.) 69 ( 152 ) 115 ( 254 )Shipping volume m3 (cu. ft) 0.42 (14.8) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Heating:ARating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 31: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 26SM830080

1-1 Unit Specifications

Concealed Duct Type

MODEL No. Indoor Unit SPW-UR253GHN56Outdoor Unit SPW-CR253EL5

POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 HzPERFORMANCE Cooling

Capacity kW 7.3BTU / h 25,000

Air circulation (Hi / Me / Lo) m3/h 1,080 / 900 / 780Moisture removal (High) Liters/h 3.5External static pressure (High) mmAq(Pa) 5.1 (50) : at shipment, 9.4 (92) : using the booster cable

ELECTRICAL RATINGSVoltage rating VAC 220 230 240Available voltage range VAC 198 – 264Running amperes* A 14.65 14.6 14.54Max. running amperes** A 15.65 15.5 15.44Power input kW 3.01 3.14 3.21Power factor % 93.4 93.5 92C.O.P W / W 2.43 2.32 2.27Max. starting amperes A 69 72 75

FEATURESControls / Thermostat control MicroprocessorTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 34 / 30 / 27, (38 / 34 / 30 : using the booster cable)

Outdoor - Hi dB - A 52Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 310 (12 - 7 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,000 (39 - 12 / 32) 940 (37 )Depth mm (in.) 630 (24 - 26 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 358 (14 - 3 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,191 (46 - 28 / 32) 1,016 (40 )Depth mm (in.) 783 (30 - 26 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 32 ( 71 ) 69 ( 152 )Shipping weight kg (lb.) 37 ( 82 ) 75 ( 165 )Shipping volume m3 (cu. ft) 0.334 (11.8) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 32: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 27SM830080

1-1 Unit Specifications

Concealed Duct Type

MODEL No. Indoor Unit SPW-UR253GHN56Outdoor Unit SPW-CR253EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 7.3BTU / h 25,000

Air circulation (Hi / Me / Lo) m3/h 1,080 / 900 / 780Moisture removal (High) Liters/h 3.5External static pressure (High) mmAq(Pa) 5.1 (50) : at shipment, 9.4 (92) : using the booster cable

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 5.14 5.05 5.00Max. running amperes** A 5.74 5.75 5.76Power input kW 2.96 3.00 3.03Power factor % 87.5 85.7 84.3C.O.P W / W 2.47 2.43 2.41Max. starting amperes A 27 29 30

FEATURESControls / Thermostat control MicroprocessorTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 34 / 30 / 27, (38 / 34 / 30 : using the booster cable)

Outdoor - Hi dB - A 52Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 310 (12 - 7 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,000 (39 - 12 / 32) 940 (37 )Depth mm (in.) 630 (24 - 26 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 358 (14 - 3 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,191 (46 - 28 / 32) 1,016 (40 )Depth mm (in.) 783 (30 - 26 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 32 ( 71 ) 69 ( 152 )Shipping weight kg (lb.) 37 ( 82 ) 75 ( 165 )Shipping volume m3 (cu. ft) 0.334 (11.8) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

Page 33: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 28SM830080

1-1 Unit Specifications

Concealed Duct Type

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

MODEL No. Indoor Unit SPW-UR363GHN56Outdoor Unit SPW-CR363EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 10.6BTU / h 36,000

Air circulation (Hi / Me / Lo) m3/h 1,800 / 1,560 / 1,260Moisture removal (High) Liters/h 4.2External static pressure (High) mmAq(Pa) 8.1 (79) : at shipment, 12.4 (122) : using the booster cable

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 7.15 7.16 7.19Max. running amperes** A 8.01 8.02 8.04Power input kW 4.03 4.09 4.14Power factor % 85.6 82.5 80.1C.O.P W / W 2.63 2.59 2.56Max. starting amperes A 47 49 50

FEATURESControls / Thermostat control MicroprocessorTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 38 / 33 / 31, (42 / 38 / 33 : using the booster cable)

Outdoor - Hi dB - A 53Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.0

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 310 (12 - 7 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,480 (58 - 9 / 32) 940 (37 )Depth mm (in.) 630 (24 - 26 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 358 (14 - 3 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,671 (65 - 25 / 32) 1,016 (40 )Depth mm (in.) 783 (30 - 26 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 47 ( 104 ) 104 ( 229 )Shipping weight kg (lb.) 52 ( 115 ) 111 ( 245 )Shipping volume m3 (cu. ft) 0.468 (16.5) 0.56 (19.8)

Page 34: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 29SM830080

1-1 Unit Specifications

Concealed Duct Type

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DB

MODEL No. Indoor Unit SPW-UR483GHN56Outdoor Unit SPW-CR483EL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling

Capacity kW 12.6BTU / h 43,000

Air circulation (Hi / Me / Lo) m3/h 1,980 / 1,800 / 1,500Moisture removal (High) Liters/h 5.4External static pressure (High) mmAq(Pa) 8.0 (78) : at shipment, 11.5 (113) : using the booster cable

ELECTRICAL RATINGSVoltage rating V 380 400 415Available voltage range V 342 – 456Running amperes* A 8.49 8.49 8.51Max. running amperes** A 9.62 9.62 9.63Power input kW 4.71 4.76 4.79Power factor % 84.3 80.9 78.3C.O.P W / W 2.68 2.65 2.63Max. starting amperes A 53 56 58

FEATURESControls / Thermostat control MicroprocessorTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 40 / 37 / 33, (44 / 40 / 37 : using the booster cable)

Outdoor - Hi dB - A 55Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.5

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 310 (12 - 7 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,480 (58 - 9 / 32) 940 (37 )Depth mm (in.) 630 (24 - 26 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 358 (14 - 3 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,671 (65 - 25 / 32) 1,016 (40 )Depth mm (in.) 783 (30 - 26 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 47 ( 104 ) 106 ( 234 )Shipping weight kg (lb.) 52 ( 115 ) 113 ( 249 )Shipping volume m3 (cu. ft) 0.468 (16.5) 0.56 (19.8)

Page 35: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 30SM830080

1-1 Unit Specifications

Concealed Duct Type

MODEL No. Indoor Unit SPW-UR253GHN56Outdoor Unit SPW-CR253EHL5

POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 HzPERFORMANCE Cooling Heating

Capacity kW 7.3 8.6BTU / h 25,000 29,300

Air circulation (Hi / Me / Lo) m3/h 1,080 / 900 / 780Moisture removal (High) Liters/h 3.5 —External static pressure (High) mmAq(Pa) 5.1 (50) : at shipment, 9.4 (92) : using the booster cable

ELECTRICAL RATINGSVoltage rating V 220 230 240 220 230 240Available voltage range V 198 – 264 198 – 264Running amperes* A 14.65 14.6 14.54 15.6 15.45 15.39Max. running amperes** A 15.65 15.5 15.44 17.4 17.15 16.99Power input kW 3.01 3.14 3.21 3.25 3.32 3.4Power factor % 93.4 93.5 92 94.7 93.4 92.1C.O.P W / W 2.43 2.32 2.27 2.65 2.59 2.53Max. starting amperes A 69 72 75 69 72 75

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 34 / 30 / 27, (38 / 34 / 30 : using the booster cable)

Outdoor - Hi dB - A 52Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 310 (12 - 7 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,000 (39 - 12 / 32) 940 (37 )Depth mm (in.) 630 (24 - 26 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 358 (14 - 3 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,191 (46 - 28 / 32) 1,016 (40 )Depth mm (in.) 783 (30 - 26 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 32 ( 71 ) 71 ( 157 )Shipping weight kg (lb.) 37 ( 82 ) 77 ( 170 )Shipping volume m3 (cu. ft) 0.334 (11.8) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DBHeating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 36: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 31SM830080

1-1 Unit Specifications

Concealed Duct Type

MODEL No. Indoor Unit SPW-UR253GHN56Outdoor Unit SPW-CR253EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 7.3 8.6BTU / h 25,000 29,300

Air circulation (Hi / Me / Lo) m3/h 1,080 / 900 / 780Moisture removal (High) Liters/h 3.5 —External static pressure (High) mmAq(Pa) 5.1 (50) : at shipment, 9.4 (92) : using the booster cable

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 5.14 5.05 5 5.42 5.33 5.24Max. running amperes** A 5.74 5.75 5.76 5.53 5.43 5.34Power input kW 2.96 3.00 3.03 3.09 3.12 3.16Power factor % 87.5 85.7 84.3 86.6 84.5 83.9C.O.P W / W 2.47 2.43 2.41 2.78 2.76 2.72Max. starting amperes A 27 29 30 27 29 30

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm)Compressor Rotary (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 34 / 30 / 27, (38 / 34 / 30 : using the booster cable)

Outdoor - Hi dB - A 52Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)outer diameter Wide tube mm (in.) 15.88 (5 / 8)Refrigerant amount at shipment kg R407C - 3.2

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 310 (12 - 7 / 32) 735 (28 - 30 / 32)

Width mm (in.) 1,000 (39 - 12 / 32) 940 (37 )Depth mm (in.) 630 (24 - 26 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 358 (14 - 3 / 32) 826 (32 - 17 / 32)Width mm (in.) 1,191 (46 - 28 / 32) 1,016 (40 )Depth mm (in.) 783 (30 - 26 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 32 ( 71 ) 71 ( 157 )Shipping weight kg (lb.) 37 ( 82 ) 77 ( 170 )Shipping volume m3 (cu. ft) 0.334 (11.8) 0.349 (12.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DBHeating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 37: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 32SM830080

1-1 Unit Specifications

Concealed Duct Type

MODEL No. Indoor Unit SPW-UR363GHN56Outdoor Unit SPW-CR363EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 10.6 12.5BTU / h 36,000 42,700

Air circulation (Hi / Me / Lo) m3/h 1,800 / 1,560 / 1,260Moisture removal (High) Liters/h 4.2 —External static pressure (High) mmAq(Pa) 8.1 (79) : at shipment, 12.4 (122) : using the booster cable

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 7.15 7.16 7.19 7.79 7.8 7.83Max. running amperes** A 8.01 8.02 8.04 8.19 8.20 8.23Power input kW 4.03 4.09 4.14 4.42 4.47 4.50Power factor % 85.6 82.5 80.1 86.2 82.7 80C.O.P W / W 2.63 2.59 2.56 2.83 2.8 2.78Max. starting amperes A 47 49 50 47 49 50

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 38 / 33 / 31, (42 / 38 / 33 : using the booster cable)

Outdoor - Hi dB - A 53Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.0

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 310 (12 - 7 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,480 (58 - 9 / 32) 940 (37 )Depth mm (in.) 630 (24 - 26 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 358 (14 - 3 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,671 (65 - 25 / 32) 1,016 (40 )Depth mm (in.) 783 (30 - 26 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 47 (104) 106 ( 234 )Shipping weight kg (lb.) 52 ( 115 ) 113 ( 249 )Shipping volume m3 (cu. ft) 0.468 (16.5) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DBHeating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 38: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 33SM830080

1-1 Unit Specifications

Concealed Duct Type

MODEL No. Indoor Unit SPW-UR483GHN56Outdoor Unit SPW-CR483EHL8

POWER SOURCE 380 - 400 - 415 V / 3N / 50 HzPERFORMANCE Cooling Heating

Capacity kW 12.6 15.3BTU / h 43,000 52,200

Air circulation (Hi / Me / Lo) m3/h 1,980 / 1,800 / 1,500Moisture removal (High) Liters/h 5.4 —External static pressure (High) mmAq(Pa) 8.0 (78) : at shipment, 11.5 (113) : using the booster cable

ELECTRICAL RATINGSVoltage rating V 380 400 415 380 400 415Available voltage range V 342 – 456 342 – 456Running amperes* A 8.49 8.49 8.51 9.69 9.69 9.71Max. running amperes** A 9.62 9.62 9.63 10.20 10.20 10.21Power input kW 4.71 4.76 4.79 5.62 5.66 5.70Power factor % 84.3 80.9 78.3 88.1 84.3 81.7C.O.P W / W 2.68 2.65 2.63 2.72 2.7 2.68Max. starting amperes A 53 56 58 53 56 58

FEATURESControls / Thermostat control Microprocessor / I.C. thermostatTimer ON / OFF 72-hoursFan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)Airflow direction (Indoor) —Air filter Field supplyRemote controller (Option) Wired : RCS-SH80TGRefrigerant control Electronic expansion valveDrain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm)Compressor Scroll (Sanyo)Operation sound Indoor - Hi/Me/Lo dB - A 40 / 37 / 33, (44 / 40 / 37 : using the booster cable)

Outdoor - Hi dB - A 55Color (Approximate value) Indoor —

Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GLREFRIGERANT TUBING

Limit of tubing length m (ft.) 50 (164 )Limit of tubing length at shipment m (ft.) 30 ( 98 )Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)between the two units Outdoor unit is lower than indoor unit : 30 (98)Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)outer diameter Wide tube mm (in.) 19.05 (3 / 4)Refrigerant amount at shipment kg R407C - 4.5

DIMENSIONS & WEIGHT Indoor unit Outdoor unitUnit dimensions Height mm (in.) 310 (12 - 7 / 32) 1,235 (48 - 20 / 32)

Width mm (in.) 1,480 (58 - 9 / 32) 940 (37 )Depth mm (in.) 630 (24 - 26 / 32) 340 (13 - 12 / 32)

Package dimensions Height mm (in.) 358 (14 - 3 / 32) 1,326 (52 - 7 / 32)Width mm (in.) 1,671 (65 - 25 / 32) 1,016 (40 )Depth mm (in.) 783 (30 - 26 / 32) 416 (16 - 12 / 32)

Net weight kg (lb.) 47 ( 104 ) 108 ( 238 )Shipping weight kg (lb.) 52 ( 115 ) 115 ( 254 )Shipping volume m3 (cu. ft) 0.468 (16.5) 0.56 (19.8)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Cooling:

Rating conditions (*): Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DBFull load conditions (**): Indoor air temperature 32 °C DB / 23 °C WB, Outdoor air temperature 43 °C DBHeating:Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WBFull load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB

Page 39: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 34SM830080

1-2 Major Component Specifications

(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type

MODEL No. SPW-XR253GH56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Turbo (1 … ø 490)

Fan motor

Model…Nominal output W SFG6X-41A5P … 40 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 6 … 470

Coil resistance Ω BRN – WHT : 114.0 ORG – YEL : 66.4(Ambient temperature 20°C) WHT – VLT : 23.9 WHT – PNK : 77.4

VLT – ORG : 12.4 YEL – BLK : 82.1

Safety device

Operating temperature Open °C 130 ± 8

Close °C ( 79 ± 15 )

Run capacitor VAC, µF 440 V , 4 µF

Electronic expansion valve

Coil DKV-MOZS582E0

Coil resistance (at 20°C) Ω ORG – GRY : 46, YEL – GRY : 46RED – GRY : 46, BLK – GRY : 46

Valve body IKV-24D12

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 2 … 1.5

Face area m2 0.295

Panel

Model No. PNR-X253GHA

Dew proof heater 240 V, 26 W

Auto louver motor M2LB24ZA12

Auto louver motor…Rated V, W, rpm. 240 VAC, 3W, 2.5 rpm

Coil resistance (at 25 °C) Ω 15.620 Ω ± 15 %

Drain Pump WP20SL - 21

Rated VAC, W AC230 V, 50 Hz, 14.7 W

Total head & capacity 400 mm, 600 cc/min

Page 40: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 35SM830080

1-2 Major Component Specifications

(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type

MODEL No. SPW-XR363GH56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Turbo (1 … ø 490)

Fan motor

Model…Nominal output W SFG6X-61A3P…60 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 6 … 530

Coil resistance Ω BRN – WHT : 71.1 ORG – YEL : 22.7(Ambient temperature 20°C) WHT – VLT : 8.7 VLT – PNK : 43.2

VLT – ORG : 13.3 YEL – BLK : 126.7

Safety device

Operating temperature Open °C 130 ± 8

Close °C ( 79 ± 15 )

Run capacitor VAC, µF 440 V , 6 µF

Electronic expansion valve

Coil EKV-MOZS584E0

Coil resistance (at 20°C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body HKV-30D16

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 2…1.5

Face area m2 0.479

Panel

Model No. PNR-X483GHA

Dew proof heater 240 V, 31 W

Auto louver motor M2LB24ZA12

Auto louver motor…Rated V, W, rpm. 240 VAC, 3W, 2.5 rpm

Coil resistance (at 25 °C) Ω 15.620 Ω ± 15 %

Drain Pump WP20SL - 21

Rated VAC, W AC230 V, 50 Hz, 14.7 W

Total head & capacity 400 mm, 600 cc/min

Page 41: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 36SM830080

1-2 Major Component Specifications

(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type

MODEL No. SPW-XR483GH56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Turbo (1 … ø 490)

Fan motor

Model…Nominal output W SFG6X-61A3P…60 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 6 … 530

Coil resistance Ω BRN – WHT : 71.1 ORG – YEL : 22.7(Ambient temperature 20°C) WHT – VLT : 8.7 VLT – PNK : 43.2

VLT – ORG : 13.3 YEL – BLK : 126.7

Safety device

Operating temperature Open °C 130 ± 8

Close °C ( 79 ± 15 )

Run capacitor VAC, µF 440 V , 6 µF

Electronic expansion valve

Coil EKV-MOZS584E0

Coil resistance (at 20°C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body HKV-30D16

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 2…1.5

Face area m2 0.479

Panel

Model No. PNR-X483GHA

Dew proof heater 240 V, 31 W

Auto louver motor M2LB24ZA12

Auto louver motor…Rated V, W, rpm. 240 VAC, 3W, 2.5 rpm

Coil resistance (at 25 °C) Ω 15.620 Ω ± 15 %

Drain Pump WP20SL - 21

Rated VAC, W 230 V, 50 Hz, 14.7 W

Total head & capacity 400 mm, 600 cc/min

Page 42: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 37SM830080

1-2 Major Component Specifications

(A) Indoor Units : Ceiling Mounted Type

MODEL No. SPW-TR253GH56

Source 220 - 230 - 240 V / 1 phase / 50 Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Centrifugal (4 … ø 130)

Fan motor

Model…Nominal output W SR4X-51A6P … 50 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,172

Coil resistance Ω BRN – WHT : 111.0 ORG – YEL : 16.7(Ambient temperature 20 °C) WHT – VLT : 35.4 YEL – BLK : 136.6

VLT – ORG : 13.4 BLK – PNK : 23.9

Safety device

Operating temperature Open °C 130 ± 8

Close °C ( 79 ± 15 )

Run capacitor VAC, µF 440 V, 1.5 µF

Electronic expansion valve

Coil DKV - MOZS582E0

Coil resistance (at 20 °C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body IKV-24D12

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 3 … 1.7

Face area m2 0.168

Auto louver motor MT8 - 3C

Auto louver motor…Rated VAC, Hz, W, rpm. 220 – 240 V, 50 Hz, 3 W, 3.3 rpm.

Coil resistance (at 25 °C) Ω 16.430 Ω ± 8 %

Page 43: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 38SM830080

1-2 Major Component Specifications

(A) Indoor Units : Ceiling Mounted Type

MODEL No. SPW-TR363GH56

Source 220 - 230 - 240 V / 1 phase / 50 Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Centrifugal (4 … ø 150)

Fan motor

Model…Nominal output W KFG4X-101C6P…100 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 4…1,015

Coil resistance Ω BRN – WHT : 61.05 ORG – YEL : 13.23(Ambient temperature 20 °C) WHT – VLT : 9.955 YEL – BLK : 19.25

VLT – ORG : 9.576 BLK – PNK : 10.81

Safety device

Operating temperature Open °C 130 ± 8

Close °C ( 79 ± 15 )

Run capacitor VAC, µF 440 V, 4.0 µF

Electronic expansion valve

Coil EKV - MOZS584E0

Coil resistance (at 20 °C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body HKV - 30D16

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 3 … 1.7

Face area m2 0.326

Auto louver motor MT8 - 3C

Auto louver motor…Rated VAC, Hz, W, rpm. 220 – 240 V, 50 Hz, 3 W, 3.3 rpm.

Coil resistance (at 25 °C) Ω 16.430 Ω ± 8 %

Page 44: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 39SM830080

1-2 Major Component Specifications

(A) Indoor Units : Ceiling Mounted Type

MODEL No. SPW-TR483GH56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Centrifugal (4…ø150)

Fan motor

Model…Nominal output W KFG4X-101C6P…100 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 4…1,070

Coil resistance Ω BRN – WHT : 61.05 ORG – YEL : 13.23(Ambient temperature 20°C) WHT – VLT : 9.955 YEL – BLK : 19.25

VLT – ORG : 9.576 BLK – PNK : 10.81

Safety device

Operating temperature Open °C 130 ± 8

Close °C ( 79 ± 15 )

Run capacitor VAC, µF 440 V, 5.0 µF

Electronic expansion valve

Coil EKV - MOZS584E0

Coil resistance (at 20°C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body HKV - 30D16

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 3…1.7

Face area m2 0.326

Auto louver motor MT8 - 3C

Auto louver motor…Rated VAC, Hz, W, rpm. 220 – 240 V, 50Hz, 3 W, 3.3 rpm.

Coil resistance (at 25°C) Ω 16.430 Ω ± 8 %

Page 45: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 40SM830080

1-2 Major Component Specifications

(A) Indoor Units : Concealed Duct High Static Pressure Type

MODEL No. SPW-DR253GH56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Centrifugal (1 … ø 220)

Fan motor

Model…Nominal output W KFC4X-201B5P … 200 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,004

Coil resistance Ω BRN – WHT : 13.75 ORG – YEL : 2.21(Ambient temperature 20°C) WHT – VLT : 4.47 YEL – BLK : 10.33

VLT – ORG : 1.20 BLK – PNK : 12.90

Safety device

Operating temperature Open °C 130 ± 5

Close °C ( 115 ± 5 )

Run capacitor VAC, µF 440 V, 5.0 µF

Electronic expansion valve

Coil DKV-MOZS550E0

Coil resistance (at 20°C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body IKV-24D12

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 3 … 2.0

Face area m2 0.233

Page 46: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 41SM830080

1-2 Major Component Specifications

(A) Indoor Units : Concealed Duct High Static Pressure Type

MODEL No. SPW-DR363GH56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Centrifugal (1 … ø 220)

Fan motor

Model…Nominal output W KFC4X-201B5P … 200 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,134

Coil resistance Ω BRN – WHT : 13.75 ORG – YEL : 2.21(Ambient temperature 20°C) WHT – VLT : 4.47 YEL – BLK : 10.33

VLT – ORG : 1.20 BLK – PNK : 12.90

Safety device

Operating temperature Open °C 130 ± 5

Close °C ( 79 ± 15 )

Run capacitor VAC, µF 440 V, 7.0 µF

Electronic expansion valve

Coil EKV-MOZS559E0

Coil resistance (at 20°C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body HKV-30D16

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 4 … 2.0

Face area m2 0.273

Page 47: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 42SM830080

1-2 Major Component Specifications

(A) Indoor Units : Concealed Duct High Static Pressure Type

MODEL No. SPW-DR483GH56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Centrifugal (1 … ø 250)

Fan motor

Model…Nominal output W KFC4Q-401A5P … 400 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,077

Coil resistance Ω BRN – WHT : 11.05 ORG – YEL : 4.57(Ambient temperature 20°C) WHT – VLT : 1.80 YEL – PNK : 7.70

VLT – ORG : 1.00

Safety device

Operating temperature Open °C 130 ± 5

Close °C ( 79 ± 15 )

Run capacitor VAC, µF 440 V, 7 µF x 2

Electronic expansion valve

Coil EKV-MOZS559E0

Coil resistance (at 20°C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body HKV-30D16

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 4 … 2.0

Face area m2 0.273

Page 48: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 43SM830080

1-2 Major Component Specifications

(A) Indoor Units : Concealed Duct Type

MODEL No. SPW-UR253GHN56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Centrifugal (2 … ø 190)

Fan motor

Model…Nominal output W KFC4X-71B5P … 70 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,063

Coil resistance Ω BRN – WHT : 74.72 ORG – YEL : 9.588(Ambient temperature 20°C) WHT – VLT : 19.14 YEL – BLK : 10.52

VLT – ORG : 10.52 BLK – PNK : 21.72

Safety device

Operating temperature Open °C 130 ± 5

Close °C ( 115 ± 5 )

Run capacitor VAC, µF 440 VAC, 5 µF

Electronic expansion valve

Coil DKV-MOZS697E0

Coil resistance (at 20°C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body IKV-24D12

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 3 … 1.7

Face area m2 0.189

Drain pump PJV-1,422

Rated VAC, W AC 230 V, 50 Hz, 12 W

Total head & capacity 500 mm, 400 cc/min

Page 49: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 44SM830080

1-2 Major Component Specifications

(A) Indoor Units : Concealed Duct Type

MODEL No. SPW-UR363GHN56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Centrifugal (3 … ø 190)

Fan motor

Model…Nominal output W KFC4X-141A5P…160 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,207

Coil resistance Ω BRN – WHT : 25.79(Ambient temperature 20°C) WHT – VLT : 5.086

VLT – ORG : 8.626ORG – YEL : 5.792YEL – BLK : 6.746PNK – VLT : 6.361

Safety device

Operating temperature Open °C 130 ± 5

Close °C ( 115 ± 5 )

Run capacitor VAC, µF 440 VAC, 8 µF

Electronic expansion valve

Coil EKV-MOZS698E0

Coil resistance (at 20°C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body HKV-30D16

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 3 … 2.0

Face area m2 0.308

Drain pump PJV-1,422

Rated VAC, W AC 230 V, 50 Hz, 12 W

Total head & capacity 500 mm, 400 cc/min

Page 50: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 45SM830080

1-2 Major Component Specifications

(A) Indoor Units : Concealed Duct Type

MODEL No. SPW-UR483GHN56

Source 220 - 230 - 240 V / 1 phase / 50Hz

Controller P.C.B. Ass’y CR-X253GH (Microprocessor)

Fan (Number…diameter) mm Centrifugal (3 … ø 190)

Fan motor

Model…Nominal output W KFC4X-141A5P…160 W

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole…r.p.m. (230 V, High) rpm. 4 … 1,207

Coil resistance Ω BRN – WHT : 25.79(Ambient temperature 20°C) WHT – VLT : 5.086

VLT – ORG : 8.626ORG – YEL : 5.792YEL – BLK : 6.746ORG – VLT : 6.361

Safety device

Operating temperature Open °C 130 ± 5

Close °C ( 115 ± 5 )

Run capacitor VAC, µF 440 VAC, 8 µF

Electronic expansion valve

Coil EKV-MOZS698E0

Coil resistance (at 20°C) Ω ORG – GRY : 46 , YEL – GRY : 46RED – GRY : 46 , BLK – GRY : 46

Valve body HKV-30D16

Heat exchanger

Coil Aluminum plate fin / Copper tube

Rows…fin pitch mm 3 … 2.0

Face area m2 0.308

Drain pump PJV-1,422

Rated VAC, W AC 230 V, 50 Hz, 12 W

Total head & capacity 500 mm, 400 cc/min

Page 51: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 46SM830080

1-2 Major Component Specifications

(B) Outdoor Unit

MODEL No. SPW-CR253EL5

Source 220 - 230 - 240 V / 1 phase / 50 Hz

Controller P.C.B. Ass'y CR - CR253GHL5 (Microprocessor)

Control circuit fuse 250 V, 3.15 A

Compressor Rotary (Hermetic)

Model ..... number C - RN220H5B

Source 220 - 240 V / 1 phase / 50 Hz

Nominal output W 2200

Compressor oil cc 1500

Coil resistance Ω C – R : 0.76 , R – S : 3.52(Ambient temperature 25 °C) C – S : 2.76

Safety devices

Overload relay models Internal type

Operating temperature Open °C 160 ± 5

Close °C 87 ± 11

Crank case heater 240V, 25 W

Refrigerant amount at shipment kg R407C - 3.2

High pressure switch ACB - 1TB07

Set pressure OFF kg/cm2 32 (3.2 MPa)

ON kg/cm2 24 ± 2.0 (2.4 ± 0.2 MPa)

Fan Propeller

Number...diameter mm 1 ..... ø460

Air circulation (Hi) m3/h 2800

Fan speeds 3 (AUTO)

Fan motor

Model KFC6T - 91C5P

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole ..... rpm (230V, High / Med. / Low) 6...772 / 376 / 252

Nominal output W 70

Coil resistance Ω WHT – BRN : 127.3 , VLT – YEL : 15.0(Ambient temperature 20°C) WHT – VLT : 56.7 , YEL – PNK : 7.2

Safety device Internal type

Operating temperature Open °C 130 ± 8

Close °C 79 ± 15

Run capacitor VAC, µF 440 V, 6 µF

Heat exchange

Coil Aluminium plate fin / Copper tube

Rows ..... fin pitch mm 2 ..... 1.8

Face area m2 0.616

+ 0– 1.5

+ 0– 0.15

Page 52: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 47SM830080

1-2 Major Component Specifications

(B) Outdoor Unit

MODEL No. SPW-CR253EHL5

Source 220 - 230 - 240 V / 1 phase / 50 Hz

Controller P.C.B. Ass'y CR - CR253GHL5 (Microprocessor)

Control circuit fuse 250 V, 3.15 A

Compressor Rotary (Hermetic)

Model ..... number C - RN220H5B

Source 220 - 240 V / 1 phase / 50 Hz

Nominal output W 2200

Compressor oil cc 1500

Coil resistance Ω C – R : 0.76 , R – S : 3.52(Ambient temperature 25 °C) C – S : 2.76

Safety devices

Overload relay models Internal type

Operating temperature Open °C 160 ± 5

Close °C 87 ± 11

Crank case heater 240V, 25 W

Refrigerant amount at shipment kg R407C - 3.2

High pressure switch ACB - 1TB07

Set pressure OFF kg/cm2 32 (3.2 MPa)

ON kg/cm2 24 ± 2.0 (2.4 ± 0.2 MPa)

Fan Propeller

Number...diameter mm 1 ..... ø460

Air circulation (Hi) m3/h 2800

Fan speeds 3 (AUTO)

Fan motor

Model KFC6T - 91C5P

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole ..... rpm (230V, High / Med. / Low) 6...772 / 376 / 252

Nominal output W 70

Coil resistance Ω WHT – BRN : 127.3 , VLT – YEL : 15.0(Ambient temperature 20°C) WHT – VLT : 56.7 , YEL – PNK : 7.2

Safety device Internal type

Operating temperature Open °C 130 ± 8

Close °C 79 ± 15

Run capacitor VAC, µF 440 V, 6 µF

Heat exchange

Coil Aluminium plate fin / Copper tube

Rows ..... fin pitch mm 2 ..... 1.8

Face area m2 0.616

+ 0– 1.5

+ 0– 0.15

Page 53: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 48SM830080

1-2 Major Component Specifications

(B) Outdoor Unit

MODEL No. SPW-CR253EL8

Source 380 - 400 - 415 V / 3 phase / 50 Hz

Controller P.C.B. Ass'y CR - CR483GHL8 (Microprocessor)

Control circuit fuse 250 V, 3.15 A

Compressor Rotary (Hermetic)

Model ..... number C - RN223H8D

Source 380 - 400 - 415 V / 3 phase / 50 Hz

Nominal output W 2400

Compressor oil cc 1350

Coil resistance Ω T – R : 5.77 , R – S : 5.66(Ambient temperature 25 °C) S – T : 5.38

Safety devices

Overload relay models Internal type

Operating temperature Open °C 120 ± 5

Close °C 98 ± 11

Crank case heater 240V, 25 W

Refrigerant amount at shipment kg R407C - 3.2

High pressure switch ACB - 1TB07

Set pressure OFF kg/cm2 32 (3.2 MPa)

ON kg/cm2 24 ± 2.0 (2.4 ± 0.2 MPa)

Fan Propeller

Number...diameter mm 1 ..... ø460

Air circulation (Hi) m3/h 2800

Fan speeds 3 (AUTO)

Fan motor

Model KFC6T - 91C5P

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole ..... rpm (230V, High / Med. / Low) 6...772 / 376 / 252

Nominal output W 70

Coil resistance Ω WHT – BRN : 127.3 , VLT – YEL : 15.0(Ambient temperature 20°C) WHT – VLT : 56.7 , YEL – PNK : 7.2

Safety device Internal type

Operating temperature Open °C 130 ± 8

Close °C 79 ± 15

Run capacitor VAC, µF 440 V, 6 µF

Heat exchange

Coil Aluminium plate fin / Copper tube

Rows ..... fin pitch mm 2 ..... 1.8

Face area m2 0.616

+ 0– 1.5

+ 0– 0.15

Page 54: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 49SM830080

1-2 Major Component Specifications

(B) Outdoor Unit

MODEL No. SPW-CR253EHL8

Source 380 - 400 - 415 V / 3 phase / 50 Hz

Controller P.C.B. Ass'y CR - CR483GHL8 (Microprocessor)

Control circuit fuse 250 V, 3.15 A

Compressor Rotary (Hermetic)

Model ..... number C - RN223H8D

Source 380 - 400 - 415 V / 3 phase / 50 Hz

Nominal output W 2400

Compressor oil cc 1350

Coil resistance Ω T – R : 5.77 , R – S : 5.66(Ambient temperature 25 °C) S – T : 5.38

Safety devices

Overload relay models Internal type

Operating temperature Open °C 120 ± 5

Close °C 98 ± 11

Crank case heater 240V, 25 W

Refrigerant amount at shipment kg R407C - 3.2

High pressure switch ACB - 1TB07

Set pressure OFF kg/cm2 32 (3.2 MPa)

ON kg/cm2 24 ± 2.0 (2.4 ± 0.2 MPa)

Fan Propeller

Number...diameter mm 1 ..... ø460

Air circulation (Hi) m3/h 2800

Fan speeds 3 (AUTO)

Fan motor

Model KFC6T - 91C5P

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole ..... rpm (230V, High / Med. / Low) 6...772 / 376 / 252

Nominal output W 70

Coil resistance Ω WHT – BRN : 127.3 , VLT – YEL : 15.0(Ambient temperature 20°C) WHT – VLT : 56.7 , YEL – PNK : 7.2

Safety device Internal type

Operating temperature Open °C 130 ± 8

Close °C 79 ± 15

Run capacitor VAC, µF 440 V, 6 µF

Heat exchange

Coil Aluminium plate fin / Copper tube

Rows ..... fin pitch mm 2 ..... 1.8

Face area m2 0.616

+ 0– 1.5

+ 0– 0.15

Page 55: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 50SM830080

1-2 Major Component Specifications

(B) Outdoor Unit

MODEL No. SPW-CR363EL8 SPW-CR483EL8

Source 380 - 400 - 415 V / 3 phase / 50 Hz

Controller P.C.B. Ass'y CR - CR483GHL8 (Microprocessor)

Control circuit fuse 250 V, 3.15 A

Compressor Scroll (Hermetic)

Model ..... number C - SBN303H8A C - SBN373H8A

Source 380 - 400 - 415 V / 3 phase / 50 Hz

Nominal output W 2,400 3,700

Compressor oil cc 1,700 1,700

Coil resistance Ω T – R : 3.177 , R – S : 3.177 T – R : 2.806 , R – S : 2.806(Ambient temperature 25 °C) S – T : 2.966 S – T : 2.651

Crank case heater 240 V, 32 W 240 V, 32 W

Safety devices

Overload relay models Internal type

Operating temperature Open °C 155 ± 5 145 ± 5

Close °C 61 ± 9 61 ± 9

Refrigerant amount at shipment kg R407C - 4.0 R407C - 4.5

High pressure switch ACB - 1TB07

Set pressure OFF kg/cm2 32 (3.2 Mpa)

ON kg/cm2 24 ± 2.0 (2.4 ± 0.2 Mpa)

Low pressure switch LCB - JA89

Set pressure OFF kg/cm2 0.5 ± 0.3 (0.05 ± 0.03 Mpa)

ON kg/cm2 1.5 ± 0.3 (0.15 ± 0.03 Mpa)

Fan Propeller

Number...diameter mm 2 ..... ø460

Air circulation m3/h 5040

Fan speeds 3 (AUTO)

Fan motor

Model KFC6T - 91C5P × 2

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole ..... rpm (230V, High / Med. / Low) 6...772 / 376 / 252

Nominal output W 70 W × 2

Coil resistance Ω BRN – WHT : 127.3 , VLT – YEL : 15.0(Ambient temperature 20°C) WHT – VLT : 56.7 , YEL – PNK : 7.2

Safety device Internal type

Operating temperature Open °C 130 ± 8

Close °C 79 ± 15

Run capacitor VAC, µF 440 V, 6 µF × 2

Heat exchange

Coil Aluminium plate fin / Copper tube

Rows ..... fin pitch mm 2 ..... 2.0 2 ..... 1.8

Face area m2 1.08

+ 0– 1.5

+ 0– 0.15

Page 56: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 51SM830080

1-2 Major Component Specifications

(B) Outdoor Unit

MODEL No. SPW-CR363EHL8 SPW-CR483EHL8

Source 380 - 400 - 415 V / 3 phase / 50 Hz

Controller P.C.B. Ass'y CR - CR483GHL8 (Microprocessor)

Control circuit fuse 250 V, 3.15 A

Compressor Scroll (Hermetic)

Model ..... number C - SBN303H8A C - SBN373H8A

Source 380 - 400 - 415 V / 3 phase / 50 Hz

Nominal output W 2,400 3,700

Compressor oil cc 1,700 1,700

Coil resistance Ω T – R : 3.177 , R – S : 3.177 T – R : 2.806 , R – S : 2.806(Ambient temperature 25 °C) S – T : 2.966 S – T : 2.651

Crank case heater 240 V, 32 W 240 V, 32 W

Safety devices

Overload relay models Internal type

Operating temperature Open °C 155 ± 5 145 ± 5

Close °C 61 ± 9 61 ± 9

Refrigerant amount at shipment kg R407C - 4.0 R407C - 4.5

High pressure switch ACB - 1TB07

Set pressure OFF kg/cm2 32 (3.2 Mpa)

ON kg/cm2 24 ± 2.0 (2.4 ± 0.2 Mpa)

Low pressure switch LCB - JA89

Set pressure OFF kg/cm2 0.5 ± 0.3 (0.05 ± 0.03 Mpa)

ON kg/cm2 1.5 ± 0.3 (0.15 ± 0.03 Mpa)

Fan Propeller

Number...diameter mm 2 ..... ø460

Air circulation m3/h 5040

Fan speeds 3 (AUTO)

Fan motor

Model KFC6T - 91C5P × 2

Source 220 - 230 - 240 V / 1 phase / 50 Hz

No. of pole ..... rpm (230V, High / Med. / Low) 6...772 / 376 / 252

Nominal output W 70 W × 2

Coil resistance Ω BRN – WHT : 127.3 , VLT – YEL : 15.0(Ambient temperature 20°C) WHT – VLT : 56.7 , YEL – PNK : 7.2

Safety device Internal type

Operating temperature Open °C 130 ± 8

Close °C 79 ± 15

Run capacitor VAC, µF 440 V, 6 µF × 2

Heat exchange

Coil Aluminium plate fin / Copper tube

Rows ..... fin pitch mm 2 ..... 2.0 2 ..... 1.8

Face area m2 1.08

+ 0– 1.5

+ 0– 0.15

Page 57: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 52SM830080

1-3 Other Component Specifications

4-Way Air Discharge Semi-concealed Type

MODEL NO. Indoor Unit SPW-XR253 ~ 483GH56

Power Transformer ATR-II215TA

Rated

Primary VAC, Hz 230 V, 50 Hz

Secondary 10.2 V 1.4 A

14 V 0.5 A

Coil resistance Ω WHT – WHT : 84 , BRN – BRN : 0.7

RED – RED : 2.7

Thermal cut off temperature ˚ C 145

Thermistor (Coil sensor) : TH2, 3, 4 PB3M-41E-S4 , PBC-41E-S25 , PBC-41E-S26 , PBC-41E-S36

Resistance KΩ -10 ˚C : 23.7 ± 5 % , 20 ˚C : 6.5 ± 5 %-5 ˚C : 18.8 ± 5 % , 30 ˚C : 4.4 ± 5 %0 ˚C : 15.0 ± 5 % , 40 ˚C : 3.1 ± 5 %5 ˚C : 12.1 ± 5 % , 45 ˚C : 2.6 ± 5 %

10 ˚C : 9.7 ± 5 %

Thermistor (Room sensor) : TH1 KTEC-35-S6

Resistance KΩ 0 ˚C :16.5 ± 5 % , 40 ˚C : 2.7 ± 5 %5 ˚C :12.8 ± 5 % , 45 ˚C : 2.2 ± 5 %

10 ˚C :10.0 ± 5 % , 50 ˚C : 1.8 ± 5 %20 ˚C : 6.3 ± 5 % , 55 ˚C : 1.5 ± 5 %30 ˚C : 4.0 ± 5 %

Electronic expansion valve

Valve body IKV-24D12 (SPW-XR253GH56)HKV-30D16 (SPW-XR363 · 483GH56)

Coil DKV-MOZS582E0 (SPW-XR253GH56)EKV-MOZS584E0 (SPW-XR363 · 483GH56)

Drain pump WP20SL-21

Rated 230 V, 14.7 W

Float switch FS-0218-102 (SPW-XR253GH56)FS-0218-103 (SPW-XR363 · 483GH56)

Rated (Contact rated) DC 12 V, 25 W

Page 58: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 53SM830080

1-3 Other Component Specifications

Ceiling Mounted Type

MODEL NO. Indoor Unit SPW-TR253 ~ 483GH56

Power Transformer ATR-II215TB

Rated

Primary VAC, Hz 230 V, 50 Hz

Secondary 10.2 V 1.4 A

14 V 0.5 A

Coil resistance Ω WHT –WHT : 110 , BRN – BRN : 0.5

RED – RED : 2.3

Thermal cut off temperature ˚ C 145

Thermistor (Coil sensor) : TH2, 3, 4 PB3M-41E-S6 , PBC-41E-S14 , PBC-41E-S25

Resistance KΩ -10 ˚C : 23.7 ± 5 % , 20 ˚C : 6.5 ± 5 %-5 ˚C : 18.8 ± 5 % , 30 ˚C : 4.4 ± 5 %0 ˚C : 15.0 ± 5 % , 40 ˚C : 3.1 ± 5 %5 ˚C : 12.1 ± 5 % , 45 ˚C : 2.6 ± 5 %

10 ˚C : 9.7 ± 5 %

Thermistor (Room sensor) : TH1 KTEC-35-S6

Resistance KΩ 0 ˚C :16.5 ± 5 % , 40 ˚C : 2.7 ± 5 %5 ˚C :12.8 ± 5 % , 45 ˚C : 2.2 ± 5 %

10 ˚C :10.0 ± 5 % , 50 ˚C : 1.8 ± 5 %20 ˚C : 6.3 ± 5 % , 55 ˚C : 1.5 ± 5 %30 ˚C : 4.0 ± 5 %

Electronic expansion valve

Valve body IKV-24D12 (SPW-TR253GH56)HKV-30D16 (SPW-TR363 · 483GH56)

Coil DKV-MOZS582E0 (SPW-TR253GH56)EKV-MOZS584E0 (SPW-TR363 · 483GH56)

Page 59: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 54SM830080

1-3 Other Component Specifications

Concealed Duct High Static Pressure Type

MODEL NO. Indoor Unit SPW-DR253 ~ 483GH56

Power Transformer ATR-II215TB

Rated

Primary VAC, Hz 230 V, 50 Hz

Secondary 10.2 V 1.4 A

14 V 0.5 A

Coil resistance Ω WHT –WHT : 110 , BRN – BRN : 0.5

RED – RED : 2.3

Thermal cut off temperature ˚ C 145

Thermistor (Coil sensor) : TH2, 3, 4 PBC-41E-S36 , PBC-41E-S25

Resistance KΩ -10 ˚C : 23.7 ± 5 % , 20 ˚C : 6.5 ± 5 %-5 ˚C : 18.8 ± 5 % , 30 ˚C : 4.4 ± 5 %0 ˚C : 15.0 ± 5 % , 40 ˚C : 3.1 ± 5 %5 ˚C : 12.1 ± 5 % , 45 ˚C : 2.6 ± 5 %

10 ˚C : 9.7 ± 5 %

Thermistor (Room sensor) : TH1, 5 KTEC-35-S85

Resistance KΩ 0 ˚C :16.5 ± 5 % , 40 ˚C : 2.7 ± 5 %5 ˚C :12.8 ± 5 % , 45 ˚C : 2.2 ± 5 %

10 ˚C :10.0 ± 5 % , 50 ˚C : 1.8 ± 5 %20 ˚C : 6.3 ± 5 % , 55 ˚C : 1.5 ± 5 %30 ˚C : 4.0 ± 5 %

Electronic expansion valve

Valve body IKV-24D12 (SPW-DR253GH56)HKV-30D16 (SPW-DR363 · 483GH56)

Coil DKV-MOZS550E0 (SPW-DR253GH56)EKV-MOZS559E0 (SPW-DR363 · 483GH56)

Float switch FS-0218-103

Rated (Contact rated) DC 12 V, 25 W

Page 60: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 55SM830080

1-3 Other Component Specifications

Concealed Duct Type

MODEL NO. Indoor Unit SPW-UR253 ~ 483GHN56

Power Transformer ATR-II215TB

Rated

Primary VAC, Hz 230 V, 50 Hz

Secondary 10.2 V 1.4 A

14 V 0.5 A

Coil resistance Ω WHT –WHT : 110 , BRN – BRN : 0.5

RED – RED : 2.3

Thermal cut off temperature ˚ C 145

Thermistor (Coil sensor) : TH2, 3, 4 PBC-41E-S36 , PBC-41E-S25

Resistance KΩ -10 ˚C : 23.7 ± 5 % , 20 ˚C : 6.5 ± 5 %-5 ˚C : 18.8 ± 5 % , 30 ˚C : 4.4 ± 5 %0 ˚C : 15.0 ± 5 % , 40 ˚C : 3.1 ± 5 %5 ˚C : 12.1 ± 5 % , 45 ˚C : 2.6 ± 5 %

10 ˚C : 9.7 ± 5 %

Thermistor (Room sensor) : TH1, 5 KTEC-35-S6, KTEC-35-S85

Resistance KΩ 0 ˚C :16.5 ± 5 % , 40 ˚C : 2.7 ± 5 %5 ˚C :12.8 ± 5 % , 45 ˚C : 2.2 ± 5 %

10 ˚C :10.0 ± 5 % , 50 ˚C : 1.8 ± 5 %20 ˚C : 6.3 ± 5 % , 55 ˚C : 1.5 ± 5 %30 ˚C : 4.0 ± 5 %

Electronic expansion valve

Valve body IKV-24D12 (SPW-UR253GHN56)HKV-30D16 (SPW-UR363 · 483GHN56)

Coil DKV-MOZS697E0 (SPW-UR253GHN56)EKV-MOZS698E0 (SPW-UR363 · 483GHN56)

Drain pump PTV-1422

Rated AC 230 V, 12 W

Float switch FS-0218-103

Rated (Contact rated) DC 12 V, 25 W

Page 61: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 56SM830080

1-3 Other Component Specifications

Outdoor Unit

MODEL NO. Outdoor Unit SPW-CR253EL5, SPW-CR253EL8

Power Transformer ATR - I65B

Rated

Primary VAC, Hz 230 V, 50 Hz

Secondary 14 V, 0.4 A

Coil resistance Ω WHT – WHT : 300 , BRN – BRN : 2.2

Thermal cut off temperature °C 145

Thermistor (Coil sensor) : TH7 PBC - 41E - S4

Coil resistance kΩ –10 °C : 23.7 , 10 °C : 9.7– 5 °C : 18.8 , 20 °C : 6.5

0 °C : 15.0 , 30 °C : 4.45 °C : 12.1 , 40 °C : 3.1

45 °C : 2.6

Thermistor (Discharge gas sensor) : TH8 PTC - 51H - S1

Coil resistance kΩ 60 °C : 13.8 , 90 °C : 5.170 °C : 9.7 , 100 °C : 3.875 °C : 8.2 , 110 °C : 2.880 °C : 7.0 , 120 °C : 2.285 °C : 5.9 , 130 °C : 1.7

Relay (Comp. Magnetic Contactor) FC - 1SZ607

Coil rated VAC 220 - 240 V

Contact rating VAC, A 440 V, 13 A

Coil resistance (at 25 °C) Ω —

Solenoid coil or 4 way valve

4 way valve —

Solenoid coil —

Page 62: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 57SM830080

1-3 Other Component Specifications

Outdoor Unit

MODEL NO. Outdoor Unit SPW-CR253EHL5, SPW-CR253EHL8

Power Transformer ATR - I65B

Rated

Primary VAC, Hz 230 V, 50 Hz

Secondary 14 V, 0.4 A

Coil resistance Ω WHT – WHT : 300 , BRN – BRN : 2.2

Thermal cut off temperature °C 145

Thermistor (Coil sensor) : TH6, 7 PBC - 41E - S26 , PBC - 41E - S4

Coil resistance kΩ –10 °C : 23.7 , 10 °C : 9.7– 5 °C : 18.8 , 20 °C : 6.5

0 °C : 15.0 , 30 °C : 4.45 °C : 12.1 , 40 °C : 3.1

45 °C : 2.6

Thermistor (Discharge gas sensor) : TH8 PTC - 51H - S1

Coil resistance kΩ 60 °C : 13.8 , 90 °C : 5.170 °C : 9.7 , 100 °C : 3.875 °C : 8.2 , 110 °C : 2.880 °C : 7.0 , 120 °C : 2.285 °C : 5.9 , 130 °C : 1.7

Relay (Comp. Magnetic Contactor) FC - 1SZ607

Coil rated VAC 220 - 240 V

Contact rating VAC, A 440 V, 13 A

Coil resistance (at 25 °C) Ω —

Solenoid coil or 4 way valve

4 way valve CHV - 0201

Solenoid coil CHV - 01AJ504D1

Page 63: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 58SM830080

1-3 Other Component Specifications

Outdoor Unit

MODEL NO. Outdoor Unit SPW-CR363EL8, SPW-CR483EL8

Power Transformer ATR - I65B

Rated

Primary VAC, Hz 230 V, 50 Hz

Secondary 14 V, 0.4 A

Coil resistance Ω WHT – WHT : 300 , BRN – BRN : 2.2

Thermal cut off temperature °C 145

Thermistor (Coil sensor) : TH7 PBC - 41E - S4

Coil resistance kΩ –10 °C : 23.7 , 10 °C : 9.7– 5 °C : 18.8 , 20 °C : 6.5

0 °C : 15.0 , 30 °C : 4.45 °C : 12.1 , 40 °C : 3.1

45 °C : 2.6

Thermistor (Discharge gas sensor) : TH8 PTC - 51H - S1

Coil resistance kΩ 60 °C : 13.8 , 90 °C : 5.170 °C : 9.7 , 100 °C : 3.875 °C : 8.2 , 110 °C : 2.880 °C : 7.0 , 120 °C : 2.285 °C : 5.9 , 130 °C : 1.7

Relay (Comp. Magnetic Contactor) FC - 1SZ607

Coil rated VAC 220 - 240 V

Contact rating VAC, A 440 V, 13 A

Coil resistance (at 25 °C) Ω —

Solenoid coil or 4 way valve

4 way valve —

Solenoid coil —

Page 64: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 59SM830080

1-3 Other Component Specifications

Outdoor Unit

MODEL NO. Outdoor Unit SPW-CR363EHL8 SPW-CR483EHL8

Power Transformer ATR - I65B

Rated

Primary VAC, Hz 230 V, 50 Hz

Secondary 14 V, 0.4 A

Coil resistance Ω WHT – WHT : 300 , BRN – BRN : 2.2

Thermal cut off temperature °C 145

Thermistor (Coil sensor) : TH6, 7 PBC - 41E - S36 , PBC - 41E - S4

Coil resistance kΩ –10 °C : 23.7 , 10 °C : 9.7– 5 °C : 18.8 , 20 °C : 6.5

0 °C : 15.0 , 30 °C : 4.45 °C : 12.1 , 40 °C : 3.1

45 °C : 2.6

Thermistor (Discharge gas sensor) : TH8 PTC - 51H - S1

Coil resistance kΩ 60 °C : 13.8 , 90 °C : 5.170 °C : 9.7 , 100 °C : 3.875 °C : 8.2 , 110 °C : 2.880 °C : 7.0 , 120 °C : 2.285 °C : 5.9 , 130 °C : 1.7

Relay (Comp. Magnetic Contactor) FC - 1SZ607

Coil rated VAC 220 - 240 V

Contact rating VAC, A 440 V, 13 A

Coil resistance (at 25 °C) Ω —

Solenoid coil or 4 way valve

4 way valve CHV - 0301 CHV - 0401

Solenoid coil CHV - 01AJ504D1

Page 65: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 60SM830080

860

10076

0

500

500

298 30205

165

1212

48

860

820

(Cei

ling

open

ing)

820 (Ceiling opening)

61

730

(Sus

pent

ion

bolt

pitc

h)

Pan

el c

ente

r

590 (Suspention bolt pitch)

345

35

Air intake grilleAir outletRefrigerant liquid line [ø 9.52 (In case of 25 type, use the tube connector.)] Refrigerant gas line ø 12.7: 12 type, ø 15.88: 18, 25 typeDrain connectionPower supply entryFor discharge ductHumidifier (option) mounting holeSuspension bolt mounting

342 15

X-v

iew

1488_X_I

125

207

100

205

61

760

50 150255

207

9

9

1-4 Dimensional Data

(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type25 Type

Page 66: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 61SM830080

1150

1050

790

500328 30

218125

860

1110

(C

eilin

g op

enin

g)

820 (Ceiling opening)

61

1020

(S

uspe

ntio

n bo

lt pi

tch)

Pan

el c

ente

r

590 (Suspention bolt pitch)

490

40

Air intake grilleAir outletRefrigerant liquid line (ø9.52)Refrigerant gas line (ø19.05) Drain connectionPower supply entryFor discharge ductHumidifier (option) mounting holeSuspension bolt mounting

X-v

iew

0183_X_I

218

145

35

21060

760

70 165285

210

100

100

9

9

342 15

12

48

12

1-4 Dimensional Data

(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type36, 48 Type

Page 67: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 62SM830080

Drain connectionDrain connection for left sideRefrigerant liquid line (ø9.52)Refrigerant gas line (18, 25 type: ø15.88 / 36, 48 type: ø19.05)Hole for rear side refrigerant tubingHole for through-the-wall refrigerant tubing (ø100 hole)Hole for upper side refrigerant tubing (Knockout hole)Hole for right side refrigerant tubing (Knockout hole)Hole for left side drain connection (Knockout hole)Hole for power supply cord (Knockout hole ø40)Hole for remote controller wiring

1394_X_S

Dimension : mm

Air intake

Air outlet

500

or m

ore

Hole for wall-through piping (View from front)

17081

N

214A

670

280

280

B

D32

016

0E

L M

K

F

G H

2816

0

53

JI

146

183

103

251

141

35C (Suspension bolt hole pitch)

89

147

71132

280

86

Front (Service space)(Service space)

Holes in the rear unit (View from front)

(Sus

pens

ion

bolt

hole

pitc

h)

250or more

250or more

A B C D E F G H I J K L M N

25 type 1,300 1,280 1,230 147 101 64 134 147 116 83 120 95 147 190

36, 48 type 1,575 1,555 1,505 197 151 114 184 197 121 80 170 140 197 240

1-4 Dimensional Data

(A) Indoor Units : Ceiling Mounted Type25, 36, 48 Type

Page 68: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 63SM830080

1-4 Dimensional Data

(A) Indoor Units : Concealed Duct Type25 Type

Refrigerant liquid line ø9.52 (narrow tube)(Use the tube connector)Refrigerant gas line ø15.88 (wide tube)Upper drain port (O.D. 32 mm)Bottom drain port (O.D. 26 mm)Suspension lugPower supply outlet (2-ø30)Fresh air intake port (ø150)Flange for the flexible air outlet duct (ø200)Tube cover Electrical component boxFlange for the air intake duct(Option or field supply)

9

10

11

1731_U_I

(Suspension bolt pitch)

16-ø

3.3

(Hol

e)

962

(A

ir ou

tlet d

uct f

lang

e)

900

1000

1080

(S

uspe

nsio

n bo

lt pi

tch)

(150

)

40

290

290

272

75 65

9018

0

3131

185

580 25

115

19

Insp

ectio

n ac

cess

(450

× 4

50)

(Fie

ld s

uppl

y)

10

285

7013

0

2521

0

310

25 175 35

190

85

25

7030

160

6302510

11 24260(Air outlet

duct flange)

Page 69: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 64SM830080

1-4 Dimensional Data

(A) Indoor Units : Concealed Duct Type36, 48 Type

Refrigerant liquid line ø9.52 (narrow tube)Refrigerant gas line ø19.05 (wide tube)Upper drain port (O.D. 32 mm)Bottom drain port (O.D. 26 mm)Suspension lugPower supply outlet (2-ø30)Fresh air intake port (ø150)Flange for the flexible air outlet duct (ø200)Tube cover Electrical component boxFlange for the air intake duct(Option or field supply)

9

10

11

1732_U_I

(Suspension bolt pitch)

18-ø

3.3

(Hol

e)

1442

(A

ir ou

tlet d

uct f

lang

e)

230

P ×

6 =

138

0

1480

1560

(S

uspe

nsio

n bo

lt pi

tch)

(150

)

40

335

335

335

310

75 65

9023

0

3131

185

580 25

115

19

Insp

ectio

n ac

cess

(450

× 4

50)

(Fie

ld s

uppl

y)

10

285

7013

0

2521

0

310

25 175 35

190

85

25

7030

160

6302510

11 24260(Air outlet

duct flange)

Page 70: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 65SM830080

1-4 Dimensional Data

7 Flange for the air intake duct (Field supply)

: For Concealed Duct Type

2-ø

3.3

1018

31

FG

HG

F9

E

D

B (

O.D

.)

A25

(Hol

e)

C-ø

3.3

(Hol

e)

I-ø

6(H

ole)

210

305

260 (O.D.) 23

200458 45

25

25

10

1766_U_I

A B C D E F G H I

9, 12, 18 type 698 662 4 200 3 × 200P = 600 170 – 340 12

25 type 998 962 6 180 5 × 180P = 900 120 245 (245 × 1) 250 16

36, 48 type 1,478 1,442 7 230 6 × 230P = 1,380 120 490 (245 × 2) 240 20

(mm)

Page 71: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 66SM830080

A

310

100 100

300

B

50

55

25

500

7035

940

35 15

81

80 290

(Suspension bolt pitch)

130

23 C 55

0184_D_I

60 90

20

40 55

7 ×

100

= 7

00

4 ×

100

= 4

00

500

980

(Sus

pens

ion

bolt

pitc

h)

4-ø

20 H

ole

for

susp

ensi

on b

olt)

Dra

in p

an

793

940

4846

16 -

ø3.

2

Ele

ctric

box

22 -

ø3.

2 (H

ole

for

full

circ

umfe

renc

e)

(Hol

e fo

r fu

ll ci

rcum

fere

nce)

(274)

100

1010

15

10

620

5555 100100

Refrigerant liquid line [ø 9.52 (In case of 25 type, use the tube connector.)] Refrigerant gas line (ø 19.05)Power supply entryDrain connection (20 A / VP20) Duct connection for suctionDuct connection for discharge

25, 36 type

48 type

A

420

450

B

395

425

C

68

98

1-4 Dimensional Data

(A) Indoor Units : Concealed Duct High Static Pressure Type25, 36, 48 Type

Page 72: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 67SM830080

735

280

307

940

Dimension : mm

Hole for anchor bolt (4-ø13)Refrigerant tube joint (narrow tube) Flare connection 1/4 in (6.35 mm)Refrigerant tube joint (wide tube) Flare connection 5/8 in (15.88 mm)Refrigerant tubing inletPower supply inlet

0411_C_S

400

380

1030

50 50

340

110660170

1-4 Dimensional Data

(B) Outdoor Units : SPW-CR253EHL5, SPW-CR253EL5SPW-CR253EHL8, SPW-CR253EL8

Page 73: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 68SM830080

1-4 Dimensional Data

(B) Outdoor Units : SPW-CR363EHL8, SPW-CR363EL8SPW-CR483EHL8, SPW-CR483EL8

1235

580

607

940

Dimension : mm

Hole for anchor bolt (4-ø13)Refrigerant tube joint (narrow tube) Flare connection 3/8 in (9.52 mm)Refrigerant tube joint (wide tube) Flare connection 3/4 in (19.05 mm)Refrigerant tubing inletPower supply inlet

1553_C_S

400

380

1030

50 50

340

110660170

Page 74: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 69SM830080

HP

Highpressureswitch

CompressorAccumulator

Accumulator

EC

P

Heat exchanger

EC

P

Heat exchanger

Distributor

Electronicref.controlvalve

Strainer

Liquid linenipple

Liquid lineservicevalve

O.D.ø6.35mm(1/4")

O.D.ø15.88mm(5/8")

Gas linenipple

Gas lineservicevalve

Distributor

Cooling Cycle

Strainer

M

1549_C_S

1-5 Refrigerant Flow Diagram

Outdoor Units : SPW-CR253EL5SPW-CR253EL8

Indoor Unit : 25 Type

Page 75: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 70SM830080

HP

High pressureswitch

Compressor

Accumulator

EC

P

Heat exchanger

EC

P

Heat exchanger

Distributor

Electronicref.controlvalve

Strainer

Liquid linenipple

Liquid lineservicevalve

O.D.ø9.52mm(3/8")

O.D.ø19.05mm(3/4")

Gas linenipple

Gas lineservicevalve

Distributor

Cooling Cycle

Strainer

M

1550_C_S

LP

Low pressure switch

1-5 Refrigerant Flow Diagram

Outdoor Units : SPW-CR363EL8SPW-CR483EL8

Indoor Units : 36, 48 Type

Page 76: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 71SM830080

HPHighpressureswitch

CompressorAccumulator

Accumulator

EC

P

Heat exchanger

4-way valveEC

P

Heat exchanger

Distributor

Electronicref.controlvalve

Strainer

Liquid linenipple

Liquid lineservicevalve

O.D.ø6.35mm(1/4")

O.D.ø15.88mm(5/8")

Gas linenipple

Gas lineservicevalve

Distributor

Sub-heat exchanger

Cooling CycleHeating Cycle

Strainer

M

1551_C_S

Muffler

1-5 Refrigerant Flow Diagram

Outdoor Units : SPW-CR253EHL5SPW-CR253EHL8

Indoor Unit : 25 Type

Page 77: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 72SM830080

HP

LP

High pressureswitch

Compressor Low pressure switchAccumulator

EC

P

Heat exchanger

4-way valveEC

P

Heat exchanger

Distributor

Electronicref.controlvalve

Strainer

Liquid linenipple

Liquid lineservicevalve

O.D.ø9.52mm(3/8")

O.D.ø19.05mm(3/4")

Gas linenipple

Gas lineservicevalve

Distributor

Sub-heat exchanger

Cooling CycleHeating Cycle

Strainer

M

Muffler

1552_C_S

Temperature Indoor air intake temp. Outdoor air intake temp.

CoolingMaximum 35°C DB / 23°C WB 43 °C DB

Minimum 18°C DB / 14°C WB -15 °C DB

HeatingMaximum 27°C DB / — WB 21 °C DB / 15.5°C WB

Minimum 15°C DB / — WB -15 °C DB / — WB

1-5 Refrigerant Flow Diagram

Outdoor Units : SPW-CR363EHL8SPW-CR483EHL8

Indoor Units : 36, 48 Type

1-6 Operating Range

Page 78: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 73SM830080

1-7 Cooling Capacity

Indoor Unit : SPW-XR253GH56 Outdoor Unit : SPW-CR253EHL5SPW-CR253EL5

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1140 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 7.37 7.03 6.67 6.26 5.81CI 2.22 2.37 2.55 2.49 2.45

21 SHC 4.66 4.47 4.28 4.06 3.8315 23 SHC 5.21 5.03 4.83 4.61 4.39

25 SHC 5.77 5.58 5.39 5.17 4.9427 SHC 6.33 6.14 5.95 5.73 5.529 SHC 6.88 6.7 6.51 6.26 5.8131 SHC 7.37 7.03 6.67 6.26 5.81

TC 7.61 7.31 6.96 6.59 6.18CI 2.28 2.44 2.62 2.57 2.52

21 SHC 3.93 3.78 3.6 3.42 3.2317 23 SHC 4.49 4.34 4.16 3.98 3.78

25 SHC 5.05 4.89 4.72 4.54 4.3427 SHC 5.6 5.45 5.28 5.09 4.929 SHC 6.16 6.01 5.83 5.65 5.4631 SHC 6.72 6.56 6.39 6.21 6.01

TC 7.88 7.6 # 7.3 6.94 6.54CI 2.35 2.52 2.7 2.66 2.62

21 SHC 3.21 3.08 2.94 2.77 2.619 23 SHC 3.76 3.63 3.49 3.33 3.16

25 SHC 4.32 4.19 4.05 3.89 3.7127 SHC 4.88 4.75 4.61 4.45 4.2729 SHC 5.44 5.31 5.17 5 4.8331 SHC 5.99 5.86 5.72 5.56 5.39

TC 8.14 7.85 7.56 7.21 6.86CI 2.41 2.59 2.78 2.74 2.7

23 SHC 3.03 2.91 2.78 2.64 2.521 25 SHC 3.59 3.47 3.34 3.2 3.05

27 SHC 4.15 4.03 3.9 3.75 3.6129 SHC 4.7 4.58 4.46 4.31 4.1731 SHC 5.26 5.14 5.01 4.87 4.73

TC 8.42 8.17 7.88 7.59 7.24CI 2.48 2.65 2.85 2.82 2.78

23 25 SHC 2.86 2.76 2.65 2.54 2.4127 SHC 3.42 3.32 3.21 3.1 2.9729 SHC 3.97 3.88 3.77 3.65 3.5231 SHC 4.53 4.44 4.32 4.21 4.08

TC 8.76 8.45 8.2 7.91 7.61CI 2.56 2.74 2.91 2.9 2.88

25 27 SHC 2.71 2.6 2.51 2.41 2.329 SHC 3.27 3.15 3.06 2.97 2.8631 SHC 3.82 3.71 3.62 3.52 3.42

Page 79: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 74SM830080

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1140 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 7.37 7.03 6.67 6.26 5.81CI 2.07 2.22 2.38 2.49 2.62

21 SHC 4.66 4.47 4.28 4.06 3.8315 23 SHC 5.21 5.03 4.83 4.61 4.39

25 SHC 5.77 5.58 5.39 5.17 4.9427 SHC 6.33 6.14 5.95 5.73 5.529 SHC 6.88 6.7 6.51 6.26 5.8131 SHC 7.37 7.03 6.67 6.26 5.81

TC 7.61 7.31 6.96 6.59 6.18CI 2.13 2.28 2.44 2.57 2.69

21 SHC 3.93 3.78 3.6 3.42 3.2317 23 SHC 4.49 4.34 4.16 3.98 3.78

25 SHC 5.05 4.89 4.72 4.54 4.3427 SHC 5.6 5.45 5.28 5.09 4.929 SHC 6.16 6.01 5.83 5.65 5.4631 SHC 6.72 6.56 6.39 6.21 6.01

TC 7.88 7.6 # 7.3 6.94 6.54CI 2.19 2.35 2.52 2.65 2.77

21 SHC 3.21 3.08 2.94 2.77 2.619 23 SHC 3.76 3.63 3.49 3.33 3.16

25 SHC 4.32 4.19 4.05 3.89 3.7127 SHC 4.88 4.75 4.61 4.45 4.2729 SHC 5.44 5.31 5.17 5 4.8331 SHC 5.99 5.86 5.72 5.56 5.39

TC 8.14 7.85 7.56 7.21 6.86CI 2.25 2.41 2.59 2.72 2.85

23 SHC 3.03 2.91 2.78 2.64 2.521 25 SHC 3.59 3.47 3.34 3.2 3.05

27 SHC 4.15 4.03 3.9 3.75 3.6129 SHC 4.7 4.58 4.46 4.31 4.1731 SHC 5.26 5.14 5.01 4.87 4.73

TC 8.42 8.17 7.88 7.59 7.24CI 2.31 2.48 2.66 2.79 2.93

23 25 SHC 2.86 2.76 2.65 2.54 2.4127 SHC 3.42 3.32 3.21 3.1 2.9729 SHC 3.97 3.88 3.77 3.65 3.5231 SHC 4.53 4.44 4.32 4.21 4.08

TC 8.76 8.45 8.2 7.91 7.61CI 2.39 2.56 2.71 2.87 3.02

25 27 SHC 2.71 2.6 2.51 2.41 2.329 SHC 3.27 3.15 3.06 2.97 2.8631 SHC 3.82 3.71 3.62 3.52 3.42

1-7 Cooling Capacity

Indoor Unit : SPW-XR253GH56 Outdoor Unit : SPW-CR253EHL8SPW-CR253EL8

Page 80: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 75SM830080

1-7 Cooling Capacity

Indoor Unit : SPW-XR363GH56 Outdoor Unit : SPW-CR363EHL8SPW-CR363EL8

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 10.6 kW AIR FLOW RATE : 1920 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 10.7 10.21 9.69 9.08 8.44CI 2.89 3.09 3.31 3.38 3.46

21 SHC 6.95 6.69 6.43 6.13 5.8115 23 SHC 7.88 7.62 7.36 7.06 6.74

25 SHC 8.81 8.56 8.3 7.99 7.6827 SHC 9.74 9.49 9.23 8.93 8.4429 SHC 10.67 10.21 9.69 9.08 8.4431 SHC 10.7 10.21 9.69 9.08 8.44

TC 11.06 10.61 10.11 9.57 8.98CI 2.96 3.17 3.4 3.48 3.56

21 SHC 5.78 5.57 5.33 5.09 4.8117 23 SHC 6.71 6.5 6.27 6.02 5.74

25 SHC 7.65 7.43 7.2 6.95 6.6727 SHC 8.58 8.37 8.13 7.88 7.6129 SHC 9.51 9.3 9.06 8.81 8.5431 SHC 10.44 10.23 9.99 9.57 8.98

TC 11.45 11.03 # 10.6 10.07 9.5CI 3.05 3.27 3.51 3.59 3.68

21 SHC 4.61 4.43 4.24 4.01 3.7719 23 SHC 5.55 5.36 5.17 4.94 4.7

25 SHC 6.48 6.29 6.11 5.88 5.6427 SHC 7.41 7.23 7.04 6.81 6.5729 SHC 8.34 8.16 7.97 7.74 7.531 SHC 9.28 9.09 8.9 8.67 8.43

TC 11.82 11.41 10.97 10.47 9.96CI 3.14 3.36 3.61 3.7 3.79

23 SHC 4.37 4.2 4.02 3.83 3.6321 25 SHC 5.3 5.13 4.96 4.76 4.56

27 SHC 6.23 6.06 5.89 5.69 5.4929 SHC 7.16 6.99 6.82 6.62 6.4231 SHC 8.09 7.93 7.75 7.56 7.36

TC 12.22 11.86 11.45 11.02 10.52CI 3.22 3.45 3.7 3.8 3.89

23 25 SHC 4.12 3.99 3.84 3.68 3.527 SHC 5.06 4.92 4.77 4.61 4.4329 SHC 5.99 5.85 5.7 5.55 5.3731 SHC 6.92 6.79 6.63 6.48 6.3

TC 12.72 12.27 11.9 11.49 11.05CI 3.33 3.56 3.78 3.9 4.02

25 27 SHC 3.9 3.75 3.63 3.5 3.3529 SHC 4.84 4.69 4.56 4.43 4.2831 SHC 5.77 5.62 5.49 5.36 5.21

Page 81: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 76SM830080

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 12.6 kW AIR FLOW RATE : 1920 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 12.71 12.13 11.52 10.8 10.03CI 3.42 3.66 3.93 4.14 4.38

21 SHC 8.04 7.72 7.38 7 6.615 23 SHC 8.97 8.65 8.31 7.93 7.54

25 SHC 9.9 9.58 9.25 8.86 8.4727 SHC 10.84 10.51 10.18 9.8 9.429 SHC 11.77 11.45 11.11 10.73 10.0331 SHC 12.7 12.13 11.52 10.8 10.03

TC 13.14 12.61 12.02 11.38 10.67CI 3.51 3.76 4.04 4.26 4.49

21 SHC 6.83 6.55 6.25 5.94 5.617 23 SHC 7.76 7.49 7.19 6.87 6.53

25 SHC 8.69 8.42 8.12 7.8 7.4627 SHC 9.62 9.35 9.05 8.74 8.3929 SHC 10.56 10.28 9.98 9.67 9.3331 SHC 11.49 11.21 10.92 10.6 10.26

TC 13.61 13.12 # 12.6 11.97 11.29CI 3.62 3.88 4.16 4.4 4.63

21 SHC 5.61 5.37 5.14 4.85 4.5419 23 SHC 6.54 6.31 6.07 5.78 5.47

25 SHC 7.48 7.24 7 6.71 6.4127 SHC 8.41 8.17 7.93 7.65 7.3429 SHC 9.34 9.1 8.87 8.58 8.2731 SHC 10.27 10.04 9.8 9.51 9.2

TC 14.05 13.56 13.04 12.45 11.84CI 3.72 3.99 4.28 4.52 4.76

23 SHC 5.31 5.09 4.87 4.62 4.3721 25 SHC 6.24 6.02 5.81 5.56 5.31

27 SHC 7.17 6.96 6.74 6.49 6.2429 SHC 8.1 7.89 7.67 7.42 7.1731 SHC 9.04 8.82 8.6 8.35 8.1

TC 14.53 14.1 13.61 13.1 12.5CI 3.82 4.09 4.39 4.64 4.89

23 25 SHC 5.01 4.84 4.65 4.45 4.2227 SHC 5.94 5.77 5.58 5.39 5.1629 SHC 6.88 6.71 6.51 6.32 6.0931 SHC 7.81 7.64 7.45 7.25 7.02

TC 15.12 14.59 14.15 13.66 13.13CI 3.94 4.22 4.48 4.76 5.04

25 27 SHC 4.75 4.56 4.4 4.23 4.0529 SHC 5.68 5.49 5.33 5.16 4.9831 SHC 6.61 6.42 6.26 6.09 5.91

1-7 Cooling Capacity

Indoor Unit : SPW-XR483GH56 Outdoor Unit : SPW-CR483EHL8SPW-CR483EL8

Page 82: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 77SM830080

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1080 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 7.37 7.03 6.67 6.26 5.81CI 2.22 2.37 2.55 2.49 2.45

21 SHC 4.74 4.56 4.37 4.15 3.9315 23 SHC 5.31 5.12 4.93 4.72 4.49

25 SHC 5.87 5.69 5.5 5.28 5.0627 SHC 6.44 6.25 6.06 5.85 5.6229 SHC 7 6.82 6.63 6.26 5.8131 SHC 7.37 7.03 6.67 6.26 5.81

TC 7.61 7.31 6.96 6.59 6.18CI 2.28 2.44 2.62 2.57 2.52

21 SHC 4.02 3.87 3.7 3.52 3.3217 23 SHC 4.58 4.43 4.26 4.08 3.89

25 SHC 5.15 5 4.83 4.65 4.4527 SHC 5.71 5.56 5.39 5.21 5.0229 SHC 6.28 6.13 5.95 5.78 5.5831 SHC 6.84 6.69 6.52 6.34 6.15

TC 7.88 7.6 # 7.3 6.94 6.54CI 2.35 2.52 2.7 2.66 2.62

21 SHC 3.29 3.16 3.03 2.87 2.6919 23 SHC 3.86 3.73 3.59 3.43 3.26

25 SHC 4.42 4.29 4.16 4 3.8227 SHC 4.99 4.86 4.72 4.56 4.3929 SHC 5.55 5.42 5.29 5.13 4.9531 SHC 6.12 5.99 5.85 5.69 5.52

TC 8.14 7.85 7.56 7.21 6.86CI 2.41 2.59 2.78 2.74 2.7

23 SHC 3.12 3.01 2.88 2.74 2.621 25 SHC 3.69 3.57 3.44 3.3 3.16

27 SHC 4.25 4.14 4.01 3.87 3.7329 SHC 4.82 4.7 4.57 4.43 4.2931 SHC 5.38 5.27 5.14 5 4.86

TC 8.42 8.17 7.88 7.59 7.24CI 2.48 2.65 2.85 2.82 2.78

23 25 SHC 2.96 2.87 2.75 2.64 2.5227 SHC 3.52 3.43 3.32 3.21 3.0829 SHC 4.09 3.99 3.88 3.77 3.6531 SHC 4.65 4.56 4.45 4.34 4.21

TC 8.76 8.45 8.2 7.91 7.61CI 2.56 2.74 2.91 2.9 2.88

25 27 SHC 2.81 2.7 2.62 2.52 2.4129 SHC 3.38 3.27 3.18 3.08 2.9831 SHC 3.94 3.83 3.74 3.65 3.54

1-7 Cooling Capacity

Indoor Unit : SPW-TR253GH56 Outdoor Unit : SPW-CR253EHL5SPW-CR253EL5

Page 83: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 78SM830080

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1080 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 7.37 7.03 6.67 6.26 5.81CI 2.22 2.37 2.55 2.49 2.45

21 SHC 4.74 4.56 4.37 4.15 3.9315 23 SHC 5.31 5.12 4.93 4.72 4.49

25 SHC 5.87 5.69 5.5 5.28 5.0627 SHC 6.44 6.25 6.06 5.85 5.6229 SHC 7 6.82 6.63 6.26 5.8131 SHC 7.37 7.03 6.67 6.26 5.81

TC 7.61 7.31 6.96 6.59 6.18CI 2.28 2.44 2.62 2.57 2.52

21 SHC 4.02 3.87 3.7 3.52 3.3217 23 SHC 4.58 4.43 4.26 4.08 3.89

25 SHC 5.15 5 4.83 4.65 4.4527 SHC 5.71 5.56 5.39 5.21 5.0229 SHC 6.28 6.13 5.95 5.78 5.5831 SHC 6.84 6.69 6.52 6.34 6.15

TC 7.88 7.6 # 7.3 6.94 6.54CI 2.35 2.52 2.7 2.66 2.62

21 SHC 3.29 3.16 3.03 2.87 2.6919 23 SHC 3.86 3.73 3.59 3.43 3.26

25 SHC 4.42 4.29 4.16 4 3.8227 SHC 4.99 4.86 4.72 4.56 4.3929 SHC 5.55 5.42 5.29 5.13 4.9531 SHC 6.12 5.99 5.85 5.69 5.52

TC 8.14 7.85 7.56 7.21 6.86CI 2.41 2.59 2.78 2.74 2.7

23 SHC 3.12 3.01 2.88 2.74 2.621 25 SHC 3.69 3.57 3.44 3.3 3.16

27 SHC 4.25 4.14 4.01 3.87 3.7329 SHC 4.82 4.7 4.57 4.43 4.2931 SHC 5.38 5.27 5.14 5 4.86

TC 8.42 8.17 7.88 7.59 7.24CI 2.48 2.65 2.85 2.82 2.78

23 25 SHC 2.96 2.87 2.75 2.64 2.5227 SHC 3.52 3.43 3.32 3.21 3.0829 SHC 4.09 3.99 3.88 3.77 3.6531 SHC 4.65 4.56 4.45 4.34 4.21

TC 8.76 8.45 8.2 7.91 7.61CI 2.56 2.74 2.91 2.9 2.88

25 27 SHC 2.81 2.7 2.62 2.52 2.4129 SHC 3.38 3.27 3.18 3.08 2.9831 SHC 3.94 3.83 3.74 3.65 3.54

1-7 Cooling Capacity

Indoor Unit : SPW-TR253GH56 Outdoor Unit : SPW-CR253EHL8SPW-CR253EL8

Page 84: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 79SM830080

1-7 Cooling Capacity

Indoor Unit : SPW-TR363GH56 Outdoor Unit : SPW-CR363EHL8SPW-CR363EL8

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 10.6 kW AIR FLOW RATE : 1800 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 10.7 10.21 9.69 9.08 8.44CI 2.89 3.09 3.31 3.38 3.46

21 SHC 7 6.75 6.49 6.2 5.8815 23 SHC 7.97 7.72 7.46 7.16 6.85

25 SHC 8.94 8.69 8.43 8.13 7.8227 SHC 9.91 9.66 9.4 9.08 8.4429 SHC 10.7 10.21 9.69 9.08 8.4431 SHC 10.7 10.21 9.69 9.08 8.44

TC 11.06 10.61 10.11 9.57 8.98CI 2.96 3.17 3.4 3.48 3.56

21 SHC 5.8 5.59 5.36 5.12 4.8417 23 SHC 6.77 6.56 6.33 6.08 5.81

25 SHC 7.74 7.53 7.3 7.05 6.7827 SHC 8.71 8.5 8.26 8.02 7.7529 SHC 9.67 9.47 9.23 8.99 8.7231 SHC 10.64 10.43 10.11 9.57 8.98

TC 11.45 11.03 # 10.6 10.07 9.5CI 3.05 3.27 3.51 3.59 3.68

21 SHC 4.6 4.42 4.23 4.01 3.7719 23 SHC 5.57 5.39 5.2 4.97 4.74

25 SHC 6.54 6.35 6.17 5.94 5.727 SHC 7.5 7.32 7.14 6.91 6.6729 SHC 8.47 8.29 8.11 7.88 7.6431 SHC 9.44 9.26 9.07 8.85 8.61

TC 11.82 11.41 10.97 10.47 9.96CI 3.14 3.36 3.61 3.7 3.79

23 SHC 4.35 4.18 4.01 3.82 3.6221 25 SHC 5.32 5.15 4.98 4.79 4.59

27 SHC 6.29 6.12 5.95 5.76 5.5629 SHC 7.26 7.09 6.92 6.72 6.5331 SHC 8.22 8.06 7.89 7.69 7.5

TC 12.22 11.86 11.45 11.02 10.52CI 3.22 3.45 3.7 3.8 3.89

23 25 SHC 4.11 3.98 3.83 3.67 3.527 SHC 5.08 4.95 4.8 4.64 4.4729 SHC 6.05 5.92 5.76 5.61 5.4331 SHC 7.02 6.88 6.73 6.58 6.4

TC 12.72 12.27 11.9 11.49 11.05CI 3.33 3.56 3.78 3.9 4.02

25 27 SHC 3.89 3.74 3.62 3.49 3.3429 SHC 4.86 4.71 4.59 4.46 4.3131 SHC 5.83 5.68 5.56 5.42 5.28

Page 85: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 80SM830080

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 12.6 kW AIR FLOW RATE : 1920 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 12.71 12.13 11.52 10.8 10.03CI 3.42 3.66 3.93 4.14 4.38

21 SHC 8.17 7.86 7.53 7.16 6.7815 23 SHC 9.19 8.88 8.55 8.19 7.8

25 SHC 10.21 9.9 9.58 9.21 8.8227 SHC 11.23 10.92 10.6 10.23 9.8429 SHC 12.25 11.94 11.52 10.8 10.0331 SHC 12.71 12.13 11.52 10.8 10.03

TC 13.14 12.61 12.02 11.38 10.67CI 3.51 3.76 4.04 4.26 4.49

21 SHC 6.87 6.61 6.32 6.01 5.6817 23 SHC 7.89 7.63 7.34 7.03 6.7

25 SHC 8.91 8.65 8.36 8.06 7.7327 SHC 9.93 9.67 9.38 9.08 8.7529 SHC 10.95 10.69 10.4 10.1 9.7731 SHC 11.97 11.71 11.42 11.12 10.67

TC 13.61 13.12 # 12.6 11.97 11.29CI 3.62 3.88 4.16 4.4 4.63

21 SHC 5.57 5.34 5.11 4.84 4.5419 23 SHC 6.59 6.36 6.13 5.86 5.56

25 SHC 7.61 7.38 7.15 6.88 6.5827 SHC 8.63 8.4 8.18 7.9 7.629 SHC 9.65 9.43 9.2 8.92 8.6231 SHC 10.67 10.45 10.22 9.94 9.64

TC 14.05 13.56 13.04 12.45 11.84CI 3.72 3.99 4.28 4.52 4.76

23 SHC 5.27 5.06 4.85 4.61 4.3721 25 SHC 6.29 6.08 5.87 5.63 5.39

27 SHC 7.31 7.11 6.9 6.66 6.4129 SHC 8.34 8.13 7.92 7.68 7.4431 SHC 9.36 9.15 8.94 8.7 8.46

TC 14.53 14.1 13.61 13.1 12.5CI 3.82 4.09 4.39 4.64 4.89

23 25 SHC 4.98 4.82 4.63 4.44 4.2227 SHC 6 5.84 5.65 5.46 5.2429 SHC 7.02 6.86 6.68 6.49 6.2631 SHC 8.04 7.88 7.7 7.51 7.29

TC 15.12 14.59 14.15 13.66 13.13CI 3.94 4.22 4.48 4.76 5.04

25 27 SHC 4.72 4.54 4.39 4.22 4.0529 SHC 5.74 5.56 5.41 5.24 5.0731 SHC 6.77 6.58 6.43 6.26 6.09

1-7 Cooling Capacity

Indoor Unit : SPW-TR483GH56 Outdoor Unit : SPW-CR483EHL8SPW-CR483EL8

Page 86: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 81SM830080

1-7 Cooling Capacity

Indoor Unit : SPW-UR253GHN56 Outdoor Unit : SPW-CR253EHL5SPW-CR253EL5

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1080 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 7.37 7.03 6.67 6.26 5.81CI 2.35 2.51 2.69 2.63 2.58

21 SHC 4.86 4.68 4.5 4.28 4.0615 23 SHC 5.44 5.26 5.07 4.86 4.64

25 SHC 6.02 5.84 5.65 5.44 5.2227 SHC 6.59 6.41 6.23 6.02 5.829 SHC 7.17 6.99 6.67 6.26 5.8131 SHC 7.37 7.03 6.67 6.26 5.81

TC 7.61 7.31 6.96 6.59 6.18CI 2.41 2.58 2.76 2.71 2.65

21 SHC 4.13 3.99 3.82 3.64 3.4617 23 SHC 4.71 4.56 4.4 4.22 4.03

25 SHC 5.29 5.14 4.97 4.8 4.6127 SHC 5.87 5.72 5.55 5.38 5.1929 SHC 6.44 6.3 6.13 5.95 5.7631 SHC 7.02 6.87 6.71 6.53 6.18

TC 7.88 7.6 # 7.3 6.94 6.54CI 2.48 2.66 2.85 2.8 2.75

21 SHC 3.41 3.28 3.15 2.99 2.8219 23 SHC 3.98 3.86 3.72 3.57 3.4

25 SHC 4.56 4.44 4.3 4.14 3.9727 SHC 5.14 5.01 4.88 4.72 4.5529 SHC 5.72 5.59 5.46 5.3 5.1331 SHC 6.29 6.17 6.03 5.88 5.71

TC 8.14 7.85 7.56 7.21 6.86CI 2.55 2.73 2.93 2.89 2.84

23 SHC 3.25 3.13 3.01 2.87 2.7321 25 SHC 3.82 3.71 3.59 3.45 3.31

27 SHC 4.4 4.29 4.16 4.02 3.8829 SHC 4.98 4.86 4.74 4.6 4.4631 SHC 5.56 5.44 5.32 5.18 5.04

TC 8.42 8.17 7.88 7.59 7.24CI 2.62 2.8 3.01 2.97 2.93

23 25 SHC 3.09 3 2.89 2.78 2.6627 SHC 3.67 3.58 3.47 3.36 3.2329 SHC 4.25 4.15 4.04 3.94 3.8131 SHC 4.82 4.73 4.62 4.51 4.39

TC 8.76 8.45 8.2 7.91 7.61CI 2.7 2.89 3.07 3.05 3.03

25 27 SHC 2.95 2.85 2.76 2.67 2.5629 SHC 3.53 3.42 3.34 3.24 3.1431 SHC 4.11 4 3.91 3.82 3.72

Page 87: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 82SM830080

1-7 Cooling Capacity

Indoor Unit : SPW-UR253GHN56 Outdoor Unit : SPW-CR253EHL8SPW-CR253EL8

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1080 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 7.37 7.03 6.67 6.26 5.81CI 2.2 2.35 2.52 2.55 2.6

21 SHC 4.86 4.68 4.5 4.28 4.0615 23 SHC 5.44 5.26 5.07 4.86 4.64

25 SHC 6.02 5.84 5.65 5.44 5.2227 SHC 6.59 6.41 6.23 6.02 5.829 SHC 7.17 6.99 6.67 6.26 5.8131 SHC 7.37 7.03 6.67 6.26 5.81

TC 7.61 7.31 6.96 6.59 6.18CI 2.25 2.41 2.59 2.63 2.67

21 SHC 4.13 3.99 3.82 3.64 3.4617 23 SHC 4.71 4.56 4.4 4.22 4.03

25 SHC 5.29 5.14 4.97 4.8 4.6127 SHC 5.87 5.72 5.55 5.38 5.1929 SHC 6.44 6.3 6.13 5.95 5.7631 SHC 7.02 6.87 6.71 6.53 6.18

TC 7.88 7.6 # 7.3 6.94 6.54CI 2.32 2.49 2.67 2.71 2.76

21 SHC 3.41 3.28 3.15 2.99 2.8219 23 SHC 3.98 3.86 3.72 3.57 3.4

25 SHC 4.56 4.44 4.3 4.14 3.9727 SHC 5.14 5.01 4.88 4.72 4.5529 SHC 5.72 5.59 5.46 5.3 5.1331 SHC 6.29 6.17 6.03 5.88 5.71

TC 8.14 7.85 7.56 7.21 6.86CI 2.39 2.56 2.74 2.79 2.84

23 SHC 3.25 3.13 3.01 2.87 2.7321 25 SHC 3.82 3.71 3.59 3.45 3.31

27 SHC 4.4 4.29 4.16 4.02 3.8829 SHC 4.98 4.86 4.74 4.6 4.4631 SHC 5.56 5.44 5.32 5.18 5.04

TC 8.42 8.17 7.88 7.59 7.24CI 2.45 2.62 2.82 2.87 2.92

23 25 SHC 3.09 3 2.89 2.78 2.6627 SHC 3.67 3.58 3.47 3.36 3.2329 SHC 4.25 4.15 4.04 3.94 3.8131 SHC 4.82 4.73 4.62 4.51 4.39

TC 8.76 8.45 8.2 7.91 7.61CI 2.53 2.71 2.87 2.95 3.02

25 27 SHC 2.95 2.85 2.76 2.67 2.5629 SHC 3.53 3.42 3.34 3.24 3.1431 SHC 4.11 4 3.91 3.82 3.72

Page 88: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 83SM830080

1-7 Cooling Capacity

Indoor Unit : SPW-UR363GHN56 Outdoor Unit : SPW-CR363EHL8SPW-CR363EL8

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 10.6 kW AIR FLOW RATE : 1800 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 10.7 10.21 9.69 9.08 8.44CI 2.89 3.09 3.31 3.38 3.46

21 SHC 7.48 7.24 6.99 6.71 6.4115 23 SHC 8.53 8.29 8.04 7.76 7.46

25 SHC 9.58 9.34 9.1 8.81 8.4427 SHC 10.63 10.21 9.69 9.08 8.4429 SHC 10.7 10.21 9.69 9.08 8.4431 SHC 10.7 10.21 9.69 9.08 8.44

TC 11.06 10.61 10.11 9.57 8.98CI 2.96 3.17 3.4 3.48 3.56

21 SHC 6.22 6.02 5.8 5.56 5.317 23 SHC 7.27 7.07 6.85 6.61 6.35

25 SHC 8.32 8.12 7.9 7.67 7.427 SHC 9.37 9.17 8.95 8.72 8.4629 SHC 10.42 10.23 10 9.57 8.9831 SHC 11.06 10.61 10.11 9.57 8.98

TC 11.45 11.03 # 10.6 10.07 9.5CI 3.05 3.27 3.51 3.59 3.68

21 SHC 4.96 4.79 4.61 4.39 4.1619 23 SHC 6.01 5.84 5.66 5.44 5.21

25 SHC 7.06 6.89 6.71 6.49 6.2727 SHC 8.11 7.94 7.76 7.55 7.3229 SHC 9.17 8.99 8.81 8.6 8.3731 SHC 10.22 10.04 9.86 9.65 9.42

TC 11.82 11.41 10.97 10.47 9.96CI 3.14 3.36 3.61 3.7 3.79

23 SHC 4.74 4.58 4.41 4.23 4.0421 25 SHC 5.79 5.63 5.47 5.28 5.09

27 SHC 6.84 6.68 6.52 6.33 6.1429 SHC 7.89 7.73 7.57 7.38 7.1931 SHC 8.94 8.78 8.62 8.43 8.24

TC 12.22 11.86 11.45 11.02 10.52CI 3.22 3.45 3.7 3.8 3.89

23 25 SHC 4.52 4.39 4.25 4.1 3.9327 SHC 5.57 5.45 5.3 5.15 4.9829 SHC 6.62 6.5 6.35 6.2 6.0331 SHC 7.67 7.55 7.4 7.26 7.09

TC 12.72 12.27 11.9 11.49 11.05CI 3.33 3.56 3.78 3.9 4.02

25 27 SHC 4.32 4.18 4.06 3.94 3.829 SHC 5.37 5.23 5.12 4.99 4.8531 SHC 6.43 6.28 6.17 6.04 5.9

Page 89: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 84SM830080

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 12.6 kW AIR FLOW RATE : 1980 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 12.71 12.13 11.52 10.8 10.03CI 3.42 3.66 3.93 4.14 4.38

21 SHC 8.68 8.39 8.09 7.74 7.3815 23 SHC 9.83 9.53 9.23 8.88 8.52

25 SHC 10.97 10.68 10.37 10.02 9.6627 SHC 12.11 11.82 11.51 10.8 10.0329 SHC 12.71 12.13 11.52 10.8 10.0331 SHC 12.71 12.13 11.52 10.8 10.03

TC 13.14 12.61 12.02 11.38 10.67CI 3.51 3.76 4.04 4.26 4.49

21 SHC 7.3 7.05 6.78 6.49 6.1817 23 SHC 8.44 8.19 7.92 7.63 7.32

25 SHC 9.58 9.33 9.06 8.77 8.4627 SHC 10.72 10.47 10.2 9.92 9.629 SHC 11.86 11.62 11.34 11.06 10.6731 SHC 13.01 12.61 12.02 11.38 10.67

TC 13.61 13.12 # 12.6 11.97 11.29CI 3.62 3.88 4.16 4.4 4.63

21 SHC 5.9 5.69 5.47 5.21 4.9319 23 SHC 7.05 6.83 6.62 6.35 6.07

25 SHC 8.19 7.97 7.76 7.5 7.2127 SHC 9.33 9.12 8.9 8.64 8.3629 SHC 10.47 10.26 10.04 9.78 9.531 SHC 11.61 11.4 11.18 10.92 10.64

TC 14.05 13.56 13.04 12.45 11.84CI 3.72 3.99 4.28 4.52 4.76

23 SHC 5.64 5.44 5.24 5.01 4.7921 25 SHC 6.78 6.58 6.38 6.16 5.93

27 SHC 7.92 7.72 7.53 7.3 7.0729 SHC 9.06 8.87 8.67 8.44 8.2131 SHC 10.2 10.01 9.81 9.58 9.35

TC 14.53 14.1 13.61 13.1 12.5CI 3.82 4.09 4.39 4.64 4.89

23 25 SHC 5.37 5.22 5.05 4.87 4.6627 SHC 6.52 6.36 6.19 6.01 5.829 SHC 7.66 7.5 7.33 7.15 6.9431 SHC 8.8 8.65 8.47 8.29 8.08

TC 15.12 14.59 14.15 13.66 13.13CI 3.94 4.22 4.48 4.76 5.04

25 27 SHC 5.14 4.97 4.82 4.67 4.529 SHC 6.28 6.11 5.96 5.81 5.6431 SHC 7.43 7.25 7.11 6.95 6.78

1-7 Cooling Capacity

Indoor Unit : SPW-UR483GHN56 Outdoor Unit : SPW-CR483EHL8SPW-CR483EL8

Page 90: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 85SM830080

1-7 Cooling Capacity

Indoor Unit : SPW-DR253GH56 Outdoor Unit : SPW-CR253EHL5SPW-CR253EL5

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1380 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 7.37 7.03 6.67 6.26 5.81CI 2.22 2.37 2.55 2.49 2.45

21 SHC 4.19 4.01 3.82 3.61 3.3915 23 SHC 4.92 4.75 4.56 4.34 4.12

25 SHC 5.66 5.48 5.29 5.07 4.8527 SHC 6.39 6.21 6.02 5.81 5.5829 SHC 7.12 6.94 6.67 6.26 5.8131 SHC 7.37 7.03 6.67 6.26 5.81

TC 7.61 7.31 6.96 6.59 6.18CI 2.28 2.44 2.62 2.57 2.52

21 SHC 3.23 3.09 2.92 2.74 2.5517 23 SHC 3.97 3.82 3.65 3.47 3.28

25 SHC 4.7 4.55 4.38 4.21 4.0227 SHC 5.43 5.29 5.12 4.94 4.7529 SHC 6.17 6.02 5.85 5.67 5.4831 SHC 6.9 6.75 6.58 6.41 6.18

TC 7.88 7.6 # 7.3 6.94 6.54CI 2.35 2.52 2.7 2.66 2.62

21 SHC 2.28 2.15 2.02 1.86 1.6919 23 SHC 3.01 2.89 2.75 2.59 2.42

25 SHC 3.75 3.62 3.49 3.33 3.1627 SHC 4.48 4.35 4.22 4.06 3.8929 SHC 5.21 5.09 4.95 4.79 4.6231 SHC 5.94 5.82 5.68 5.53 5.35

TC 8.14 7.85 7.56 7.21 6.86CI 2.41 2.59 2.78 2.74 2.7

23 SHC 2.05 1.94 1.81 1.67 1.5321 25 SHC 2.78 2.67 2.55 2.41 2.27

27 SHC 3.52 3.4 3.28 3.14 329 SHC 4.25 4.14 4.01 3.87 3.7331 SHC 4.98 4.87 4.75 4.61 4.47

TC 8.42 8.17 7.88 7.59 7.24CI 2.48 2.65 2.85 2.82 2.78

23 25 SHC 1.83 1.74 1.63 1.52 1.427 SHC 2.56 2.47 2.36 2.26 2.1329 SHC 3.3 3.21 3.1 2.99 2.8631 SHC 4.03 3.94 3.83 3.72 3.6

TC 8.76 8.45 8.2 7.91 7.61CI 2.56 2.74 2.91 2.9 2.88

25 27 SHC 1.63 1.53 1.44 1.35 1.2429 SHC 2.37 2.26 2.17 2.08 1.9831 SHC 3.1 2.99 2.91 2.81 2.71

Page 91: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 86SM830080

1-7 Cooling Capacity

Indoor Unit : SPW-DR253GH56 Outdoor Unit : SPW-CR253EHL8SPW-CR253EL8

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1380 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 7.37 7.03 6.67 6.26 5.81CI 2.07 2.22 2.38 2.49 2.62

21 SHC 4.19 4.01 3.82 3.61 3.3915 23 SHC 4.92 4.75 4.56 4.34 4.12

25 SHC 5.66 5.48 5.29 5.07 4.8527 SHC 6.39 6.21 6.02 5.81 5.5829 SHC 7.12 6.94 6.67 6.26 5.8131 SHC 7.37 7.03 6.67 6.26 5.81

TC 7.61 7.31 6.96 6.59 6.18CI 2.13 2.28 2.44 2.57 2.69

21 SHC 3.23 3.09 2.92 2.74 2.5517 23 SHC 3.97 3.82 3.65 3.47 3.28

25 SHC 4.7 4.55 4.38 4.21 4.0227 SHC 5.43 5.29 5.12 4.94 4.7529 SHC 6.17 6.02 5.85 5.67 5.4831 SHC 6.9 6.75 6.58 6.41 6.18

TC 7.88 7.6 # 7.3 6.94 6.54CI 2.19 2.35 2.52 2.65 2.77

21 SHC 2.28 2.15 2.02 1.86 1.6919 23 SHC 3.01 2.89 2.75 2.59 2.42

25 SHC 3.75 3.62 3.49 3.33 3.1627 SHC 4.48 4.35 4.22 4.06 3.8929 SHC 5.21 5.09 4.95 4.79 4.6231 SHC 5.94 5.82 5.68 5.53 5.35

TC 8.14 7.85 7.56 7.21 6.86CI 2.25 2.41 2.59 2.72 2.85

23 SHC 2.05 1.94 1.81 1.67 1.5321 25 SHC 2.78 2.67 2.55 2.41 2.27

27 SHC 3.52 3.4 3.28 3.14 329 SHC 4.25 4.14 4.01 3.87 3.7331 SHC 4.98 4.87 4.75 4.61 4.47

TC 8.42 8.17 7.88 7.59 7.24CI 2.31 2.48 2.66 2.79 2.93

23 25 SHC 1.83 1.74 1.63 1.52 1.427 SHC 2.56 2.47 2.36 2.26 2.1329 SHC 3.3 3.21 3.1 2.99 2.8631 SHC 4.03 3.94 3.83 3.72 3.6

TC 8.76 8.45 8.2 7.91 7.61CI 2.39 2.56 2.71 2.87 3.02

25 27 SHC 1.63 1.53 1.44 1.35 1.2429 SHC 2.37 2.26 2.17 2.08 1.9831 SHC 3.1 2.99 2.91 2.81 2.71

Page 92: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 87SM830080

1-7 Cooling Capacity

Indoor Unit : SPW-DR363GH56 Outdoor Unit : SPW-CR363EHL8SPW-CR363EL8

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 10.6 kW AIR FLOW RATE : 1800 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 10.7 10.21 9.69 9.08 8.44CI 2.89 3.09 3.31 3.38 3.46

21 SHC 6.42 6.17 5.91 5.6 5.2815 23 SHC 7.46 7.2 6.94 6.63 6.31

25 SHC 8.49 8.24 7.97 7.67 7.3527 SHC 9.53 9.27 9.01 8.7 8.3829 SHC 10.56 10.21 9.69 9.08 8.4431 SHC 10.7 10.21 9.69 9.08 8.44

TC 11.06 10.61 10.11 9.57 8.98CI 2.96 3.17 3.4 3.48 3.56

21 SHC 5.1 4.89 4.65 4.4 4.1217 23 SHC 6.14 5.92 5.69 5.43 5.16

25 SHC 7.17 6.96 6.72 6.47 6.1927 SHC 8.21 7.99 7.75 7.5 7.2229 SHC 9.24 9.03 8.79 8.54 8.2631 SHC 10.27 10.06 9.82 9.57 8.98

TC 11.45 11.03 # 10.6 10.07 9.5CI 3.05 3.27 3.51 3.59 3.68

21 SHC 3.78 3.59 3.4 3.17 2.9319 23 SHC 4.81 4.63 4.44 4.21 3.96

25 SHC 5.85 5.66 5.47 5.24 527 SHC 6.88 6.7 6.51 6.28 6.0329 SHC 7.92 7.73 7.54 7.31 7.0731 SHC 8.95 8.77 8.58 8.35 8.1

TC 11.82 11.41 10.97 10.47 9.96CI 3.14 3.36 3.61 3.7 3.79

23 SHC 3.48 3.31 3.14 2.94 2.7421 25 SHC 4.51 4.34 4.17 3.97 3.77

27 SHC 5.55 5.38 5.21 5.01 4.8129 SHC 6.58 6.41 6.24 6.04 5.8431 SHC 7.62 7.45 7.27 7.08 6.87

TC 12.22 11.86 11.45 11.02 10.52CI 3.22 3.45 3.7 3.8 3.89

23 25 SHC 3.19 3.06 2.9 2.75 2.5727 SHC 4.22 4.09 3.94 3.78 3.629 SHC 5.26 5.12 4.97 4.81 4.6331 SHC 6.29 6.16 6.01 5.85 5.67

TC 12.72 12.27 11.9 11.49 11.05CI 3.33 3.56 3.78 3.9 4.02

25 27 SHC 2.92 2.77 2.65 2.51 2.3729 SHC 3.96 3.81 3.68 3.55 3.431 SHC 4.99 4.84 4.72 4.58 4.43

Page 93: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 88SM830080

TC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CI : Compressor Input (kW)

Rating conditions are: Outdoor Ambient Temp. 35 °C DB: Indoor Unit Entering Air Temp. 27 °C DB / 19 °C WB

RATING CAPACITY : 12.6 kW AIR FLOW RATE : 2160 CMHEVAPORATOR CONDENSERENT. TEMP. °C AMBIENT TEMP °CWB DB 25 30 35 40 45

TC 12.71 12.13 11.52 10.8 10.03CI 3.42 3.66 3.93 4.14 4.38

21 SHC 7.65 7.35 7.03 6.66 6.2815 23 SHC 8.86 8.55 8.24 7.87 7.49

25 SHC 10.07 9.76 9.44 9.08 8.6927 SHC 11.27 10.97 10.65 10.28 9.929 SHC 12.48 12.13 11.52 10.8 10.0331 SHC 12.71 12.13 11.52 10.8 10.03

TC 13.14 12.61 12.02 11.38 10.67CI 3.51 3.76 4.04 4.26 4.49

21 SHC 6.11 5.85 5.57 5.27 4.9417 23 SHC 7.32 7.06 6.77 6.47 6.14

25 SHC 8.52 8.26 7.98 7.68 7.3527 SHC 9.73 9.47 9.19 8.88 8.5629 SHC 10.94 10.68 10.39 10.09 9.7631 SHC 12.14 11.88 11.6 11.3 10.67

TC 13.61 13.12 # 12.6 11.97 11.29CI 3.62 3.88 4.16 4.4 4.63

21 SHC 4.56 4.34 4.11 3.84 3.5519 23 SHC 5.77 5.54 5.32 5.05 4.75

25 SHC 6.97 6.75 6.53 6.25 5.9627 SHC 8.18 7.96 7.73 7.46 7.1729 SHC 9.39 9.16 8.94 8.67 8.3731 SHC 10.59 10.37 10.15 9.87 9.58

TC 14.05 13.56 13.04 12.45 11.84CI 3.72 3.99 4.28 4.52 4.76

23 SHC 4.21 4 3.8 3.56 3.3221 25 SHC 5.41 5.21 5 4.77 4.53

27 SHC 6.62 6.42 6.21 5.97 5.7429 SHC 7.83 7.62 7.42 7.18 6.9431 SHC 9.03 8.83 8.62 8.39 8.15

TC 14.53 14.1 13.61 13.1 12.5CI 3.82 4.09 4.39 4.64 4.89

23 25 SHC 3.86 3.7 3.52 3.34 3.1227 SHC 5.07 4.91 4.73 4.54 4.3229 SHC 6.28 6.12 5.94 5.75 5.5331 SHC 7.48 7.32 7.14 6.95 6.74

TC 15.12 14.59 14.15 13.66 13.13CI 3.94 4.22 4.48 4.76 5.04

25 27 SHC 3.55 3.37 3.22 3.06 2.8929 SHC 4.76 4.58 4.43 4.27 4.131 SHC 5.97 5.79 5.64 5.47 5.3

1-7 Cooling Capacity

Indoor Unit : SPW-DR483GH56 Outdoor Unit : SPW-CR483EHL8SPW-CR483EL8

Page 94: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 89SM830080

Heating Capacity

15˚C20˚C25˚C

140

120

100

80

60

%

25˚C

20˚C

15˚C

140

120

100

80

60

%

–15 –10 –5 0 5 10 15

Com

p. m

otor

pow

er in

put r

atio

Hea

ting

capa

city

rat

io

Outdoor temperature ˚C WB

Indoor temperature ˚C DB

Indoor temperature ˚C DB

0413_M_S

NOTE1. Above characteristics are based on:

1) Tubing length is 7 meters.2) Air flow speed is high speed.

2. Minimum outdoor ambient temperature: –15°C WB3. Above characteristics indicate instantaneous capacity. Integrated capacity is instantaneous

capacity less the effect of frost on the outdoor coil and the drop of performance during defrostcycle.

Page 95: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 90SM830080

1-8 Noise Criterion Curves

4-Way Air Discharge Semi-concealed TypeMODEL : SPW-XR253GH56

SOUND LEVEL : HIGH 37 dB(A), NC 30

LOW 31 dB(A), NC 22

CONDITION : Center, Under the unit 1.5 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

MODEL : SPW-XR363GH56 , XR483GH56

SOUND LEVEL : HIGH 43 dB(A), NC 36

LOW 36 dB(A), NC 24

CONDITION : Center, Under the unit 1.5 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

60

50

40

30

20

10OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0 d

B =

0.0

002

µbar

)

63 125 250 500 1000 2000 4000 8000

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

BAND CENTER FREQUENCIES, Hz

NC-20

NC-40

NC-50

NC-30

0275_X_I

60

50

40

30

20

10OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0 d

B =

0.0

002

µbar

)

63 125 250 500 1000 2000 4000 8000

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

BAND CENTER FREQUENCIES, Hz

NC-20

NC-40

NC-50

NC-30

0274_X_I

REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the valuesshown in this graph because of the conditions of operation, the structure of the building, the backgroundnoise and other factors.

2. The test results were obtained from an anechoic room.

To evaluate “Noise level” the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used.Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and selectthe maximum value (vertical axis) among them.

NOTE

Page 96: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 91SM830080

1-8 Noise Criterion Curves

Ceiling Mounted Type

MODEL : SPW-TR253GH56

SOUND LEVEL : HIGH 39 dB(A), NC 34

LOW 34 dB(A), NC 26

CONDITION : Distance 1 m, Under the unit 1 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

60

50

40

30

20

10OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0 d

B =

0.0

002

µbar

)

63 125 250 500 1000 2000 4000 8000

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

BAND CENTER FREQUENCIES, Hz

NC-20

NC-40

NC-50

NC-30

1221_X_I

MODEL : SPW-TR363GH56

SOUND LEVEL : HIGH 42 dB(A), NC 36

LOW 35 dB(A), NC 28

CONDITION : Distance 1 m, Under the unit 1 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

60

50

40

30

20

10OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0 d

B =

0.0

002

µbar

)

63 125 250 500 1000 2000 4000 8000

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

BAND CENTER FREQUENCIES, Hz

NC-40

NC-50

NC-30

1222_X_I

NC-20

MODEL : SPW-TR483GH56

SOUND LEVEL : HIGH 44 dB(A), NC 38

LOW 37 dB(A), NC 31

CONDITION : Distance 1 m, Under the unit 1 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

1223_X_I

60

50

40

30

20

10OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0 d

B =

0.0

002

µbar

)

63 125 250 500 1000 2000 4000 8000

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

BAND CENTER FREQUENCIES, Hz

NC-40

NC-50

NC-30

NC-20

Page 97: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 92SM830080

1-8 Noise Criterion Curves

Concealed Duct Type

MODEL : SPW-UR253GHN56

SOUND LEVEL : HIGH 34 dB(A), NC 22 / LOW 27 dB(A), NC 18

CONDITION : Under the unit 1.5 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

MODEL : SPW-UR363GHN56

SOUND LEVEL : HIGH 38 dB(A), NC 30 / LOW 31 dB(A), NC 21

CONDITION : Under the unit 1.5 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

1761_U_I

60

50

40

30

20

10

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

63 125 250 500 1000 2000 4000 8000BAND CENTER FREQUENCIES, HzO

CT

AV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B(0

dB

= 0

.000

2 µb

ar)

NC-50

NC-40

NC-30

NC-20

1762_U_I

60

50

40

30

20

10

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

63 125 250 500 1000 2000 4000 8000BAND CENTER FREQUENCIES, HzO

CT

AV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B(0

dB

= 0

.000

2 µb

ar)

NC-50

NC-40

NC-30

NC-20

MODEL : SPW-UR483GHN56

SOUND LEVEL : HIGH 40 dB(A), NC 33 / LOW 33 dB(A), NC 25

CONDITION : Under the unit 1.5 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

1763_U_I

60

50

40

30

20

10

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

63 125 250 500 1000 2000 4000 8000BAND CENTER FREQUENCIES, HzO

CT

AV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B(0

dB

= 0

.000

2 µb

ar)

NC-50

NC-40

NC-30

NC-20

REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the valuesshown in this graph because of the conditions of operation, the structure of the building, the backgroundnoise and other factors.

2. The test results were obtained from an anechoic room.

To evaluate “Noise level” the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used.Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and selectthe maximum value (vertical axis) among them.

NOTE

Page 98: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 93SM830080

1-8 Noise Criterion Curves

Concealed Duct High Static Pressure TypeMODEL : SPW-DR253GH56

SOUND LEVEL : HIGH 44 dB(A), NC 38

CONDITION : Under the unit 1.5 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

MODEL : SPW-DR363GH56

SOUND LEVEL : HIGH 45 dB(A), NC 39

CONDITION : Under the unit 1.5 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

MODEL : SPW-DR483GH56

SOUND LEVEL : HIGH 47 dB(A), NC 42

CONDITION : Under the unit 1.5 m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

0313_D_I

90

80

70

60

50

40

30

20

10

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

63 125 250 500 1000 2000 4000 8000BAND CENTER FREQUENCIES, Hz

OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0 d

B =

0.0

002

µbar

)

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

0314_D_I

90

80

70

60

50

40

30

20

10

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

63 125 250 500 1000 2000 4000 8000BAND CENTER FREQUENCIES, Hz

OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0 d

B =

0.0

002

µbar

)

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

0315_D_I

90

80

70

60

50

40

30

20

10

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

63 125 250 500 1000 2000 4000 8000BAND CENTER FREQUENCIES, Hz

OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0 d

B =

0.0

002

µbar

)

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

REMARKS: 1. Value obtained in the actual placewhere the unit is installed may beslightly higher than the values shown inthis graph because of the conditions ofoperation, the structure of the building,the background noise and other factors.

2. The test results were obtained from ananechoic room.

To evaluate “Noise level” the maximum number of themeasured OCTAVE BAND SOUND PRESSURE LEVELis used. Read the number on each BAND CENTERFREQUENCIES (horizontal axis) ranging from 63 Hz to8000 Hz and select the maximum value (vertical axis)among them.

NOTE

Page 99: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 94SM830080

MODEL : SPW-CR253EH5, CR253EH8

SPW-C253EH5, C253EH8

SOUND LEVEL : 52 dB(A), NC 44

CONDITION : Distance 1m, Height 1m

SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz

380 - 400 - 415V, 3 Phase, 50 Hz

MODEL : SPW-CR363EH8

SPW-C363EH8

SOUND LEVEL : 53 dB(A), NC 45

CONDITION : Distance 1m, Height 1m

SOURCE : 380 - 400 - 415 V, 3 Phase, 50 Hz

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

0597_C_S

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0dB

=0.

0002

µba

r)

BAND CENTER FREQUENCIES, Hz

NC-70

NC-50

NC-60

NC-40

NC-30

NC-20

OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0dB

=0.

0002

µba

r)

BAND CAENTER FREQUENCIES, Hz0598_C_S

90

80

70

60

50

40

30

20

1060 125 250 500 1000 2000 4000 8000

APPROXIMATETHRESHOLD OFCONTINUOUSNOISE

MODEL : SPW-CR483EH8

SPW-C483EH8

SOUND LEVEL : 55 dB(A), NC 47

CONDITION : Distance 1m, Height 1m

SOURCE : 380 - 400 - 415V, 3 Phase, 50 Hz

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

0599_C_SBAND CENTER FREQUENCIES, Hz

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

NC-70

NC-50

NC-20

NC-60

NC-40

NC-30

OC

TA

VE

BA

ND

SO

UN

D P

RE

SS

UR

E L

EV

EL,

dB

(0dB

=0.

0002

µba

r)

REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the valuesshown in this graph because of the conditions of operation, the structure of the building, the backgroundnoise and other factors.

2. The test results were obtained from an anechoic room.

To evaluate “Noise level” the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used.Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and selectthe maximum value (vertical axis) among them.

NOTE

1-8 Noise Criterion Curves

Outdoor Units

Page 100: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 95SM830080

1-9 Indoor Fan Performance

Concealed Duct TypeIf external static pressure is too great (due to longextension of ducts, for example), the air flow volumemay drop too low at each air outlet. This problem maybe solved by increasing the fan speed using thefollowing procedure:

(1) Remove 2 screws on the electrical componentbox and remove the cover plate.

(2) Disconnect the fan motor sockets in the box.

(3) Take out the booster cable (sockets at both ends)clamped in the box.

(4) Securely connect the booster cable socketsbetween the disconnected fan motor sockets instep 2 as shown in the Fig. 1-1.

(5) Place the cable neatly in the box and reinstall thecover plate.

Booster cable

Booster cable

Electrical component box

(At shipment) (Connected booster cable)1743_M_I

Fan motor socket

Fan motor

Fig. 1-1

Indoor Fan Performance

20

Air Flow Volume (m3/minute)

Ext

erna

l Sta

tic P

ress

ure

0

50

0

5

10

15150

10

Lim

it lin

eLi

mit

line

HT

H

L

100

1746_U_I

M

(mm

Aq)

(Pa)

30 40

Air Flow Volume (m3/minute)

Ext

erna

l Sta

tic P

ress

ure

0

50

0

5

10

15150

20

Lim

it lin

e

Lim

it lin

e

L

100

1748_U_I

M

H

(mm

Aq)

(Pa)

HT

30

Air Flow Volume (m3/minute)

Ext

erna

l Sta

tic P

ress

ure

0

50

0

5

10

15150

20

Lim

it lin

e

HT

L

100

1747_U_I

M

H

Lim

it lin

e (mm

Aq)

(Pa)

HT : Using the booster cable

H : At shipment

NOTE

SPW-UR253GHN56 SPW-UR483GHN56SPW-UR363GHN56

Fig. 1-2

How to read the diagramThe vertical axis is the external static pressure (Pa) while the horizontal axis represents the AIR FLOW (m3/minute). Thecharacteristic curves for “HT”, “H”, “M” and “L” fan speed control are shown.The nameplate values are shown based on the “H” air flow. For the 25 type, the air flow is 18 m3/minute, while theexternal static pressure is 49 Pa at “H” position. If external static pressure is too great (due to long extension of duct, forexample), the air flow volume may drop too low at each air outlet.This problem may be solved by increasing the fan speed as explained above.

Page 101: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 96SM830080

Ext

erna

l Sta

tic P

ress

ure

(mm

Aq)

Limit line

Lim

it lin

e

H

H,M

ML

0848_D_I

300

5

10

15

20

25

35 40

(Pa)

50

100

150

200

Air Flow (m3/minute)

Ext

erna

l Sta

tic P

ress

ure

(mm

Aq)

Limit line

Lim

it lin

e

H

H

M

M

L

0847_D_I

250

5

10

15

20

25

30 35

(Pa)

50

100

150

200

Air Flow (m3/minute)

Ext

erna

l Sta

tic P

ress

ure

(mm

Aq)

Limit line

Lim

it lin

e

H

H

M

ML

0846_D_I

Air Flow (m3/minute)

200

5

10

15

20

25

25 30

(Pa)

50

100

150

200

SPW-DR253GH56 SPW-DR363GH56 SPW-DR483GH56

How to Read the Diagram

The vertical axis is the EXTERNAL STATIC PRESSURE (mmAq) while the horizontal axis represents the AIRFLOW (m3/minute). The characteristic curve for the “H”, “Med”, and “Lo” fan speed control.The name plate values are shown based on the “H” air flow. Therefore in the case of the 25 type the flow is 23 m3/minute, while the EXTERNAL STATIC PRESSURE is 19 mmAq at “H” position. If the external static pressure is toogreat (due to long extention of duct, for example), the air flow volume may drop too low at each air outlet.

1-9 Indoor Fan Performance

Concealed Duct High Static Pressure Type

Page 102: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 97SM830080

1-10 Air throw Distance Chart

4-Way Air Discharge Semi-concealed Type

Model: 25 Type

Model: 36, 48 Type

0 1 2 3 4 5 60

1

2

3

4

HORIZONTAL DISTANCE (m)

AX

IS A

IR V

ELO

CIT

Y (

m/s

)V

ER

TIC

AL

DIS

TAN

CE

(m

)

AXIS AIR VELOCITY

0276_X_I

0 1 2 3 4 5 60

1

2

3

4

HORIZONTAL DISTANCE (m)

AX

IS A

IR V

ELO

CIT

Y (

m/s

)V

ER

TIC

AL

DIS

TAN

CE

(m

)

AXIS AIR VELOCITY

0277_X_I

: LOUVER ANGLE 20˚ in Cooling mode: LOUVER ANGLE 60˚ in Heating mode

Condition Fan Speed : HiRoom air temp. : 27 ˚C DB in cooling mode

20 ˚C DB in heating mode

Page 103: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 98SM830080

1-10 Air throw Distance Chart

Ceiling Mounted Type

0 1 2 3 4 5 6 7 8 9 100

1

2

3

4

5

HORIZONTAL DISTANCE (m)

AX

IS A

IR V

ELO

CIT

Y (

m/s

)V

ER

TIC

AL

DIS

TAN

CE

(m

)

1225_T_I

AXIS AIR VELOCITY

Model: 25 Type

0 1 2 3 4 5 6 7 8 9 100

1

2

3

4

5

HORIZONTAL DISTANCE (m)

AX

IS A

IR V

ELO

CIT

Y (

m/s

)V

ER

TIC

AL

DIS

TAN

CE

(m

)

1226_T_I

AXIS AIR VELOCITY

Model: 36 Type

Model: 48 Type

0 1 2 3 4 5 6 7 8 9 100

1

2

3

4

5

HORIZONTAL DISTANCE (m)

AX

IS A

IR V

ELO

CIT

Y (

m/s

)V

ER

TIC

AL

DIS

TAN

CE

(m

)

1227_T_I

AXIS AIR VELOCITY

FAN SPEED

HEATINGCOOLING

ROOM AIR TEMP.

LOUVER ANGLE

HIGHHIGH

20˚27˚

54˚– 7˚

: COOLING

: HEATING

Page 104: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 99SM830080

1-11 Installation Instructions

Tubing Length

(A) Single type Refrigerant tubing between the indoor and

outdoor units should be kept as short aspossible.

The length of the refrigerant tubes betweenthe indoor and outdoor units are limited by theelevation difference between the two units.During tubing work, try to make both thetubing length (L) and the difference in eleva-tion (H) as short as possible. Refer to Table1-1 for the details.

Tubing length (L)INDOORUNIT

OUTDOORUNIT

Elevation difference (H)

0419_M_I

Installation Example 1

Limit of elevationdifference betweenthe two units

Table 1-1 (R407C Models)

No additional charge of compressor oil is necessary.*1 If total tubing length becomes 30 to 50 m, charge additional refrigerant (R407C) by a) 45 or b) 50 g/m.

Model s SPW-CR253E(H)L5SPW-CR363E(H)L8 SPW-CR483E(H)L8

Tubing Dat a CR253E(H)L8Tubing size Narrow tube mm (in.) 6.35 (1/4) 9.52 (3/8) 9.52 (3/8)outer diameter Wide tube mm (in.) 15.88 (5/8) 19.05 (3/4) 19.05 (3/4)Limit of tubing length (m) 50 50 50

Outdoor unit is placed50 50 50

upper (m)Outdoor unit is placed

30 30 30lower (m)

Max. allowable tubing length at shipment (m) 30 30 30Required additional refrigerant *1 (g/m) a) 45 b) 50 b) 50Refrigerant charged at shipment (kg) 3.2 4.0 4.5

Page 105: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 100SM830080

NOTE

Indoor Unit

AVOID:

areas where leakage of flammable gas may beexpected.

places where large amounts of oil mist exist.

direct sunlight

locations where nearby heat sources may affectperformance of the unit.

locations where nearby external air may enter theroom directly. This may cause “sweating” on theair discharge ports, causing them to spray or drip.

locations where the remote controller will besplashed with water or affected by dampness orhumidity.

installing the remote controller behind curtains orfurniture.

DO:

select an appropriate position from which everycorner of the room can be uniformly cooled.

select a location where the ceiling is strongenough to support the weight of the unit.

select a location where tubing and drain pipehave the shortest run to the outside.

allow room for operation and maintenance aswell as unrestricted air flow around the unit.

install the unit within the maximum elevationdifference (H) above or below the outdoor unitand within a total tubing length (L) from theoutdoor unit as detailed in Table 1-1.

allow room for mounting the remote controllerabout 1 m off the floor, in an area that is not indirect sunlight nor in the flow of cool air from theindoor unit.

Air delivery will be degraded if the distance from thefloor to the ceiling is greater than 3 m.

1-11 Installation Instructions

Selecting the Installation Site

Ceiling-Mounted Type

2-Way, 4-Way Semi-Concealed Type

0021_X_I

1m

1m 1m

1m

1m

1-Way Semi-Concealed Type

Wall-Mounted Type

5 cm min.

5 cm min.

1 m

min

.

Airintake

Airdischarge

Obstacle

Ceiling

Wall

Wall

0022_AS_I

15 cm min.

Front View0023_K_I

15 cmmin

15 cmmin

0020_T_I

25 cm min.Front view

The rear of the indoor unit can be installed flushagainst the wall.

30 cm min.

Air intake

Airdischarge

Side view

NOTE

25 cm min.

Ceiling

Wall

NOTE

Page 106: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 101SM830080

Outdoor Unit

AVOID:

heat sources, exhaust fans, etc. (Fig. 1-3)

damp, humid or uneven locations.

DO:

choose a place as cool as possible.

choose a place that is well ventilated and outsideair temperature does not exceed maximum 45 ˚Cconstantly.

allow enough room around the unit for air intake /exhaust and possible maintenance. (Fig. 1-4)

provide a solid base; about 15 cm above groundlevel to reduce humidity and possiblewater damage in unit and decreaseservice life. (Fig. 1-5)

use lag bolts or equal to bolt down unit,reducing vibration and noise.

In case of multiple installations

provide a solid base (concrete block, 10 × 40 cmbeams or equal), a minimum of 15 cm aboveground level to reduce humidity and protect the unitagainst possible water damage and decreasedservice life. (Fig. 1-5)

use lug bolts or equal to bolt down unit, reducingvibration and noise.

Unit spacing if air discharge chamber is not used. Unit spacing when air discharge chamber is used.

Min. 1m Min. 1mMin. 1.5m

Min. 30cm

Min. 3.5m

Min. 20cm

Min. 1m Min. 20cm Min. 1m

Min. 35cm

Min. 35cm

Min. 30cm

Min. 30cm

Airdischargechamber

If you would like to make the separation smaller on the airdischarge side, use an air discharge chamber.You can install any number of units side-by -side.

Only up to 3 units can be installed side-by-side under the above conditions. The next group must be spaced at least 30 cm away from the first group.

0424_C_I

1-11 Installation Instructions

Selecting the Installation Site

Air inAir in

Airdischarge

Anchor bolts(4 pieces) Min. 15cm

0425_C_IFig. 1-5

Min.2 m

Min.2 m

Obstacle above

Ground

Obs

tacl

e

Airdis-charge

0486_C_IFig. 1-4

Table 1-2 AAAAA DimensionsModel Min. (cm)

25 type 1036, 48 type 20

Min.1 cm Min.

1 cm

Min.50 cm

A

1548_C_I

Out-doorunit

Heat source

Hot air

Exhaust fan

0591_C_I

Fig. 1-3

Page 107: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 102SM830080

Air Discharge Chamber for Top Discharge

Be sure to install the air discharge chamber in the filedwhen: it is difficult to keep a space of min. 50 cm between

the air discharge outlet and the obstacle. the air discharge outlet is facing to the sidewalk and

discharged hot air annoys the passers.Refer to Fig. 1-6.

Installing the Unit in Heavy Snow Areas

In positions with strong wind, snow-proof ductingshould likewise be fitted and direct exposure to thewind should be avoided as much as possible.

Countermeasures against snow and wind in regionswith snow and strong wind, the following problemsmay occur when the outdoor unit is not provided with aplatform and snow-proof ducting.

a) The outdoor fan may not run and damage of theunit may be caused.

b) There may be no air flow.c) The tubing may freeze and burst.d) The condenser pressure may drop because of

strong wind, and the indoor unit may freeze.

Precautions for Installation in Heavy SnowAreas

(1) The platform should be higher than the max.snow depth. (Fig. 1-7)

(2) The two fixing feet of the outdoor unit should beused for the platform, and the platform should beinstalled beneath the air intake side of outdoorunit.

(3) The platform foundation must be firmer and theunit must be secured with anchor bolts.

(4) In case of installation on a roof subject to strongwind, countermeasures must be taken to preventthe unit from being blown over.

Dimensions of Snow / Wind-proof Ducting andRefrigerant Tubing Space for Installation

1-11 Installation Instructions

Selecting the Installation Site

Duct

Duct

Outdoor Unit

Min. 100

300

Min. 100 300 Unit: mm 0489_C_I

Example of Installation

0490_C_I

AirIntake

Platform (foundation)

Higher than themaximumsnow depth

Duct

About 1/2 of theunit height

AirIntake

Duct

OutdoorUnit

0488_C_IFig. 1-9

Fig. 1-7 Fig. 1-80487_C_I

Without snow-proof ducting(Low platform)

Without snow-proof ducting(High platform)

In regions with snow fall, the outdoor unit should beprovided with a platform and snow-proof duct.

Fig. 1-6

Air discharge

0426_C_I

Page 108: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 103SM830080

1-11 Installation Instructions

Selecting the Installation Site

Wind Shield for “ EHL”, “ EL” Model

It is recommended to install wind shields for coolingoperation in low outdoor temperature condition.(Fig. 1-10)

GeneralWhen the outdoor unit is installed in a position ex-posed to strong wind (like seasonal winds with low airtemperature in winter), wind shield must be installedon the outdoor unit.

This unit is designed so that the fan of the outdoor unitruns at low speed when the air conditioner is operatedat low outdoor air temperatures. When the outdoor unitis exposed to strong wind, the system pressure dropsbecause of the freeze protector.

For outer dimensions of wind shield, please seeFig. 1-11.

Important

Fig. 1-10

Wind shield(air discharge side)

Front

0935_C_I

1546_C_I

3 - ø40 hole

6 - ø6 hole

250

549

24

132

570

13

596

554

13125025027

554

1545_C_I

3 - ø60 hole

8 - ø6 hole

450

100

250

250

1116

132

567

131

300

592

For 253 typeFor 363, 483 type

Recommended outer dimensions of wind shield(field supply)

Fig. 1-11

Page 109: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 104SM830080

General Precautions on Wiring

(1) Before wiring, confirm the rated voltage of the unitas shown on its nameplate, then carry out thewiring closely following the wiring diagram.

(2) Provide a power outlet to be used exclusivelyfor each unit, and a power supply disconnectand circuit breaker for overcurrent protectionshould be provided in the exclusive line.

(3) To prevent possible hazards due to insulationfailure, the unit must be grounded.

(4) Each wiring connection must be done in accor-dance with the wiring system diagram. Wrongwiring may cause the unit to misoperate orbecome damaged.

(5) Do not allow wiring to touch the refrigerant tubing,compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring canbe very dangerous. The manufacturer will acceptno responsibility for any damage or misoperationthat occurs as a result of such unauthorizedchanges.

1-11 Installation Instructions

Electrical Wiring

Recommended Wire Length and Wire Diameter for Power Supply System

* AWG = American Wire Gauge(1) Single Type (One indoor unit / one outdoor unit)

(A) Power Supply (B) Inter-unit wiring Power Supply Terminal Base

Capacity Max. Wire4 mm2 2.5 mm2 Diameter

SPW-CR253E(H)L8 97 m 50 m 15 A 25 A 5.5 mm2 (AWG#10)

SPW-CR363E(H)L8 60 m 50 m 20 A 25 A 5.5 mm2 (AWG#10)

SPW-CR483E(H)L8 54 m 50 m 25 A 25 A 5.5 mm2 (AWG#10)

SPW-CR253E(H)L5 17 m 50 m 40 A 50 A 14 mm2 (AWG#10)

Time DelayFuse orCircuitCapacity

R407Cmodels

Type

(7) Regulations on wire diameters differ from locality tolocality. For field wiring rules, please refer to yourLOCAL ELECTRICAL CODES before beginning.

You must insure that installation complies with allrelevant rules and regulations.

(8) To prevent malfunction of the air conditionercaused by electrical noise, care must be takenwhen wiring as follows:

The remote control wiring and the inter-unitcontrol wiring should be wired apart from theinter-unit power wiring.

Use shielded wires for inter-unit control wiringbetween units and ground the shielded on bothsides.

(9) If the power supply cord of this appliance is dam-aged, it must be replaced by a repair shop ap-pointed by the manufacture, because specialpurpose tools are required.

Page 110: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 105SM830080

1-11 Installation Instructions

Electrical Wiring

• Indoor Unit

(F) Power Supply Power Supply Terminal Base

Capacity Max. Wire2.5 mm2 Diameter

X, S, AS, T, U, SL 245 m 15 A 50 A 14 mm2 (AWG#6)

K 588 m 15 A 25 A 5.5 mm2 (AWG#10)

D 89 m 15 A 50 A 14 mm2 (AWG#6)

Time DelayFuse orCircuitCapacity

Type

NOTE1) Refer to the Wiring System Diagrams (Ref. next

page) for the meaning of “A”, “B”, “C”, “D”, “E”,and “F” in the above tables.

2) Inter-Unit Control Wiring (c) has no polarity.But for other wiring, respect polarity.Be sure to connect as shown in the Wiring Sys-tem Diagram.

3) The basic connection diagram of the indoor unitshows the 8P terminal board, so the terminalboards in your equipment may differ from thediagram.

4) In accordance with conformity of EC Directive No.89/336/EEC, when connecting power supply, itshould be considered guidance showing below.

* Do not share a common installation group withother equipment.

* Be sure that supply network impedance issufficiently low (IZSYSI [ RΩ).It may be necessary to consult the powersupply authority before connection of the airconditioner to a low-voltage public network.

1(L)2(N)Power supply U1

Inter-unitcontrol wiring

U2Remote controller

8P terminal board

0511_M_I

R1R2 R31 2 U1 U2 R1 R2 R3

1(L)2(N) 4 51 2 3 4 5

1 2 3Power supply

Inter-unitcontrol wiring

Remote controller

5P terminal board + 3P terminal board

0512_M_I

Only for K type

Control Wiring

(C) Inter-Unit Control Wiring (D) Remote Control Wiring (E) Control Wiring For Group Control0.75 mm2 (AWG#18) 0.75 mm2 (AWG#18) 0.75 mm2 (AWG#18)Use Shielded Wiring

Max. 1000 m Max. 500 m Max. 500 m

Models RΩ Remarks25 type (3 phase) — Not necessary to consider supply network impedance36 type (3 phase) 0.192 Conforms to the local code48 type (3 phase) 0.167 Ditto25 type (1 phase) 0.126 Ditto

R407C Models

Page 111: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 106SM830080

Wiring System Diagrams(1) Basic wiring diagram for standard control

1 Single type (one indoor unit)1-1. 3-phase outdoor unit

1-2. Single-phase outdoor unit

2 Use shielded wires for inter-unit controlwiring (c) and ground the shielded on bothsides.

1

2

U1

U2

R1

R2

R3

1

2

3

1

2

3

1

2

4

L1

L2

L3

N

Indoor Unit

Inter-unitpower wiring(Line voltage)

Inter-unitcontrol wiring(Low voltage)

RED

WHT

BLK

Remote controller

Outdoor Unit

Ground

Ground(Option)

B

D

A 0499_M_I

Power supply

R.C. Address on the PCB: 0 (S2, BLK)(0: Factory shipped state)

380 - 415 V - 3 N 50 Hz

L1

L2

L3

N

1

2

0

C

1

2

U1

U2

1

2

R1

R2

R3

1

2

3

1

2

4

L

N

Indoor Unit

Inter-unitpower wiring(Line voltage)

Inter-unitcontrol wiring(Low voltage)

RED

WHT

BLK

Remote controller

Outdoor Unit

Ground

Ground

D

B

A

0500_M_I

Power supply

R.C. Address on the PCB: 0 (S2, BLK)(0: Factory shipped state)

220 - 240 V 50 Hz

L

N

0

1

2

3

C

Shielded wire

0160_M_I

1-11 Installation Instructions

Electrical Wiring

Page 112: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 107SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-XR253GH5 6 Outdoor Unit : SPW-CR253EHL5SPW-CR253EL5

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz

Rating conditionsA 0.6 / 0.63 0.62 / 0.65 12.1 / 12.3 13.32 / 13.58

kW 130 / 150 0.13 / 0.15 2.55 / 2.7 2.81 / 3.0

Full load conditionsA 0.6 / 0.63 0.62 / 0.65 13.44 / 13.48 14.66 / 14.76

kW 130 / 150 0.13 / 0.15 2.8 / 2.88 3.06 / 3.18

Starting amperes A 1 / 1 1 / 1 67 / 73 69 / 75

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz

Rating conditionsA 0.37 / 0.42 0.62 / 0.65 13.7 / 13.5 14.69 / 14.57

kW 80 / 100 0.13 / 0.15 2.86 / 2.96 3.07 / 3.21

Full load conditionsA 0.37 / 0.42 0.62 / 0.65 15.6 / 15.2 16.59 / 16.27

kW 80 / 100 0.13 / 0.15 3.25 / 3.29 3.46 / 3.54

Starting amperes A 1 / 1 1 / 1 67 / 73 69 / 75

Page 113: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 108SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-XR253GH5 6 Outdoor Unit : SPW-CR253EHL8SPW-CR253EL8

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.6 / 0.63 0.62 / 0.65 4.45 / 4.35 4.82 / 4.73

kW 130 / 150 0.13 / 0.15 2.5 / 2.52 2.76 / 2.82

Full load conditionsA 0.6 / 0.63 0.62 / 0.65 5.3 / 5.32 5.67 / 5.69

kW 130 / 150 0.13 / 0.15 2.98 / 3.02 3.24 / 3.32

Starting amperes A 1 / 1 1 / 1 25 / 28 27 / 30

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.37 / 0.42 0.62 / 0.65 5 / 4.8 5.31 / 5.12

kW 80 / 100 0.13 / 0.15 2.79 / 2.81 3 / 3.06

Full load conditionsA 0.37 / 0.42 0.62 / 0.65 5.1 / 4.9 5.41 / 5.22

kW 80 / 100 0.13 / 0.15 2.87 / 2.89 3.08 / 3.14

Starting amperes A 1 / 1 1 / 1 25 / 28 27 / 30

Page 114: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 109SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-XR363GH5 6 Outdoor Unit : SPW-CR363EHL8SPW-CR363EL8

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.92 / 0.93 1.24 / 1.31 6.35 / 6.39 7.01 / 7.05

kW 200 / 220 0.26 / 0.29 3.46 / 3.51 3.92 / 4.02

Full load conditionsA 0.92 / 0.93 1.24 / 1.31 7.2 / 7.24 7.86 / 7.9

kW 200 / 220 0.26 / 0.29 3.98 / 4.02 4.44 / 4.53

Starting amperes A 2 / 2 3 / 3 42 / 45 47 / 50

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.65 / 0.68 1.24 / 1.31 7 / 7.04 7.58 / 7.64

kW 140 / 160 0.26 / 0.29 3.86 / 3.88 4.26 / 4.33

Full load conditionsA 0.65 / 0.68 1.24 / 1.31 7.4 / 7.44 7.98 / 8.04

kW 140 / 160 0.26 / 0.29 4.08 / 7.12 4.48 / 4.57

Starting amperes A 2 / 2 3 / 3 42 / 45 47 / 50

Page 115: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 110SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-XR483GH5 6 Outdoor Unit : SPW-CR483EHL8SPW-CR483EL8

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.92 / 0.93 1.24 / 1.31 7.7 / 7.72 8.35 / 8.37

kW 200 / 220 0.26 / 0.29 4.14 / 4.16 4.6 / 4.67

Full load conditionsA 0.92 / 0.93 1.24 / 1.31 8.8 / 8.82 9.47 / 9.49

kW 200 / 220 0.26 / 0.29 5 / 5.04 5.46 / 5.55

Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.65 / 0.68 1.24 / 1.31 8.89 / 8.91 9.48 / 9.52

kW 140 / 160 0.26 / 0.29 5.06 / 5.08 5.46 / 5.53

Full load conditionsA 0.65 / 0.68 1.24 / 1.31 9.4 / 9.41 9.99 / 10.02

kW 140 / 160 0.26 / 0.29 5.38 / 5.42 5.78 / 5.87

Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58

Page 116: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 111SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-TR253GH5 6 Outdoor Unit : SPW-CR253EHL5SPW-CR253EL5

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz

Rating conditionsA 0.43 / 0.43 0.62 / 0.65 12.1 / 12.3 13.15 / 13.38

kW 90 / 100 0.13 / 0.15 2.55 / 2.7 2.77 / 2.95

Full load conditionsA 0.43 / 0.43 0.62 / 0.65 13.44 / 13.48 14.49 / 14.56

kW 90 / 100 0.13 / 0.15 2.8 / 2.88 3.02 / 3.13

Starting amperes A 1 / 1 1 / 1 67 / 73 69 / 75

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz

Rating conditionsA 0.33 / 0.34 0.62 / 0.65 13.7 / 13.5 14.65 / 14.49

kW 70 / 80 0.13 / 0.15 2.86 / 2.96 3.06 / 3.19

Full load conditionsA 0.33 / 0.34 0.62 / 0.65 15.6 / 15.2 16.55 / 16.19

kW 70 / 80 0.13 / 0.15 3.25 / 3.29 3.45 / 3.52

Starting amperes A 1 / 1 1 / 1 67 / 73 69 / 75

Page 117: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 112SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-TR253GH5 6 Outdoor Unit : SPW-CR253EHL8SPW-CR253EL8

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.43 / 0.43 0.62 / 0.65 4.45 / 4.35 4.77 / 4.67

kW 90 / 100 0.13 / 0.15 2.5 / 2.52 2.72 / 2.77

Full load conditionsA 0.43 / 0.43 0.62 / 0.65 5.3 / 5.32 5.62 / 5.64

kW 90 / 100 0.13 / 0.15 2.98 / 3.02 3.2 / 3.27

Starting amperes A 1 / 1 1 / 1 25 / 28 27 / 30

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.33 / 0.34 0.62 / 0.65 5 / 4.8 5.29 / 5.1

kW 70 / 80 0.13 / 0.15 2.79 / 2.81 2.99 / 3.04

Full load conditionsA 0.33 / 0.34 0.62 / 0.65 5.1 / 4.9 5.39 / 5.2

kW 70 / 80 0.13 / 0.15 2.87 / 2.89 3.07 / 3.12

Starting amperes A 1 / 1 1 / 1 25 / 28 27 / 30

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 118: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 113SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-TR363GH5 6 Outdoor Unit : SPW-CR363EHL8SPW-CR363EL8

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.95 / 0.98 1.24 / 1.31 6.35 / 6.39 7.01 / 7.06

kW 200 / 220 0.26 / 0.29 3.46 / 3.51 3.92 / 4.02

Full load conditionsA 0.95 / 0.98 1.24 / 1.31 7.2 / 7.24 7.86 / 7.91

kW 200 / 220 0.26 / 0.29 3.98 / 4.02 4.44 / 4.53

Starting amperes A 2 / 2 3 / 3 42 / 45 47 / 50

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.86 / 0.9 1.24 / 1.31 7 / 7.04 7.64 / 7.68

kW 180 / 200 0.26 / 0.29 3.86 / 3.88 4.3 / 4.37

Full load conditionsA 0.86 / 0.9 1.24 / 1.31 7.4 / 7.44 8.04 / 8.09

kW 180 / 200 0.26 / 0.29 4.08 / 7.12 4.52 / 4.61

Starting amperes A 2 / 2 3 / 3 42 / 45 47 / 50

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 119: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 114SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-TR483GH5 6 Outdoor Unit : SPW-CR483EHL8SPW-CR483EL8

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.95 / 0.98 1.24 / 1.31 7.7 / 7.72 8.35 / 8.38

kW 200 / 220 0.26 / 0.29 4.14 / 4.16 4.6 / 4.67

Full load conditionsA 0.95 / 0.98 1.24 / 1.31 8.8 / 8.82 9.47 / 9.5

kW 200 / 220 0.26 / 0.29 5 / 5.04 5.46 / 5.55

Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.86 / 0.9 1.24 / 1.31 8.89 / 8.91 9.54 / 9.56

kW 180 / 200 0.26 / 0.29 5.06 / 5.08 5.5 / 5.57

Full load conditionsA 0.86 / 0.9 1.24 / 1.31 9.4 / 9.41 10.05 / 10.07

kW 180 / 200 0.26 / 0.29 5.38 / 5.42 5.82 / 5.91

Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 120: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 115SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-UR253GHN5 6 Outdoor Unit : SPW-CR253EHL5SPW-CR253EL5

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz

Rating conditionsA 0.84 / 0.9 0.62 / 0.65 12.1 / 12.3 13.56 / 13.85

kW 180 / 210 0.13 / 0.15 2.55 / 2.7 2.86 / 3.06

Full load conditionsA 0.84 / 0.9 0.62 / 0.65 13.44 / 13.48 14.9 / 15.03

kW 180 / 210 0.13 / 0.15 2.8 / 2.88 3.11 / 3.24

Starting amperes A 1 / 1 1 / 1 67 / 73 69 / 75

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz

Rating conditionsA 0.84 / 0.9 0.62 / 0.65 13.7 / 13.5 15.16 / 15.05

kW 180 / 210 0.13 / 0.15 2.86 / 2.96 3.17 / 3.32

Full load conditionsA 0.84 / 0.9 0.62 / 0.65 15.6 / 15.2 17.06 / 16.75

kW 180 / 210 0.13 / 0.15 3.25 / 3.29 3.56 / 3.65

Starting amperes A 1 / 1 1 / 1 67 / 73 69 / 75

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 121: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 116SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-UR253GHN5 6 Outdoor Unit : SPW-CR253EHL8SPW-CR253EL8

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.84 / 0.9 0.62 / 0.65 4.45 / 4.35 4.89 / 4.8

kW 180 / 210 0.13 / 0.15 2.5 / 2.52 2.81 / 2.88

Full load conditionsA 0.84 / 0.9 0.62 / 0.65 5.3 / 5.32 5.74 / 5.76

kW 180 / 210 0.13 / 0.15 2.98 / 3.02 3.29 / 3.38

Starting amperes A 1 / 1 1 / 1 25 / 28 27 / 30

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 0.84 / 0.9 0.62 / 0.65 5 / 4.8 5.44 / 5.25

kW 180 / 210 0.13 / 0.15 2.79 / 2.81 3.1 / 3.17

Full load conditionsA 0.84 / 0.9 0.62 / 0.65 5.1 / 4.9 5.54 / 5.35

kW 180 / 210 0.13 / 0.15 2.87 / 2.89 3.18 / 3.25

Starting amperes A 1 / 1 1 / 1 25 / 28 27 / 30

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 122: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 117SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-UR363GHN5 6 Outdoor Unit : SPW-CR363EHL8SPW-CR363EL8

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 1.43 / 1.54 1.24 / 1.31 6.35 / 6.39 7.13 / 7.19

kW 290 / 340 0.26 / 0.29 3.46 / 3.51 4.01 / 4.14

Full load conditionsA 1.43 / 1.54 1.24 / 1.31 7.2 / 7.24 7.99 / 8.05

kW 290 / 340 0.26 / 0.29 3.98 / 4.02 4.53 / 4.65

Starting amperes A 2 / 2 3 / 3 42 / 45 47 / 50

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 1.43 / 1.54 1.24 / 1.31 7 / 7.04 7.79 / 7.84

kW 290 / 340 0.26 / 0.29 3.86 / 3.88 4.41 / 4.51

Full load conditionsA 1.43 / 1.54 1.24 / 1.31 7.4 / 7.44 8.19 / 8.25

kW 290 / 340 0.26 / 0.29 4.08 / 7.12 4.63 / 4.75

Starting amperes A 2 / 2 3 / 3 42 / 45 47 / 50

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 123: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 118SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-UR483GHN5 6 Outdoor Unit : SPW-CR483EHL8SPW-CR483EL8

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 1.48 / 1.58 1.24 / 1.31 7.7 / 7.72 8.5 / 8.53

kW 310 / 360 0.26 / 0.29 4.14 / 4.16 4.71 / 4.81

Full load conditionsA 1.48 / 1.58 1.24 / 1.31 8.8 / 8.82 9.62 / 9.66

kW 310 / 360 0.26 / 0.29 5 / 5.04 5.57 / 5.69

Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 1.48 / 1.58 1.24 / 1.31 8.89 / 8.91 9.71 / 9.75

kW 310 / 360 0.26 / 0.29 5.06 / 5.08 5.63 / 5.73

Full load conditionsA 1.48 / 1.58 1.24 / 1.31 9.4 / 9.41 10.23 / 10.25

kW 310 / 360 0.26 / 0.29 5.38 / 5.42 5.95 / 6.07

Starting amperes A 2 / 2 3 / 3 48 / 53 53 / 58

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 124: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 119SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-DR253GH5 6 Outdoor Unit : SPW-CR253EHL5SPW-CR253EL5

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz

Rating conditionsA 2.29 / 2.31 0.62 / 0.65 12.1 / 12.3 15.01 / 15.26

kW 480 / 530 0.13 / 0.15 2.55 / 2.7 3.16 / 3.38

Full load conditionsA 2.29 / 2.31 0.62 / 0.65 13.44 / 13.48 16.35 / 16.44

kW 480 / 530 0.13 / 0.15 2.8 / 2.88 3.41 / 3.56

Starting amperes A 3 / 3 1 / 1 67 / 73 71 / 77

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz

Rating conditionsA 2.29 / 2.31 0.62 / 0.65 13.7 / 13.5 16.61 / 16.46

kW 480 / 530 0.13 / 0.15 2.86 / 2.96 3.47 / 3.64

Full load conditionsA 2.29 / 2.31 0.62 / 0.65 15.6 / 15.2 18.51 / 18.16

kW 480 / 530 0.13 / 0.15 3.25 / 3.29 3.86 / 3.97

Starting amperes A 3 / 3 1 / 1 67 / 73 71 / 77

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 125: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 120SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-DR253GH5 6 Outdoor Unit : SPW-CR253EHL8SPW-CR253EL8

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 2.29 / 2.31 0.62 / 0.65 4.45 / 4.35 5.3 / 5.19

kW 480 / 530 0.13 / 0.15 2.5 / 2.52 3.11 / 3.2

Full load conditionsA 2.29 / 2.31 0.62 / 0.65 5.3 / 5.32 6.15 / 6.14

kW 480 / 530 0.13 / 0.15 2.98 / 3.02 3.59 / 3.7

Starting amperes A 3 / 3 1 / 1 25 / 28 29 / 32

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 2.29 / 2.31 0.62 / 0.65 5 / 4.8 5.85 / 5.64

kW 480 / 530 0.13 / 0.15 2.79 / 2.81 3.4 / 3.49

Full load conditionsA 2.29 / 2.31 0.62 / 0.65 5.1 / 4.9 5.95 / 5.74

kW 480 / 530 0.13 / 0.15 2.87 / 2.89 3.48 / 3.57

Starting amperes A 3 / 3 1 / 1 25 / 28 29 / 32

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 126: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

2

3

4

5

I - 121SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-DR363GH5 6 Outdoor Unit : SPW-CR363EHL8SPW-CR363EL8

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 2.46 / 2.47 1.24 / 1.31 6.35 / 6.39 7.43 / 7.45

kW 520 / 570 0.26 / 0.29 3.46 / 3.51 4.24 / 4.37

Full load conditionsA 2.46 / 2.47 1.24 / 1.31 7.2 / 7.24 8.29 / 8.31

kW 520 / 570 0.26 / 0.29 3.98 / 4.02 4.76 / 4.88

Starting amperes A 4 / 4 3 / 3 42 / 45 49 / 52

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 2.46 / 2.47 1.24 / 1.31 7 / 7.04 8.09 / 8.1

kW 520 / 570 0.26 / 0.29 3.86 / 3.88 4.64 / 4.74

Full load conditionsA 2.46 / 2.47 1.24 / 1.31 7.4 / 7.44 8.49 / 8.51

kW 520 / 570 0.26 / 0.29 4.08 / 7.12 4.86 / 4.98

Starting amperes A 4 / 4 3 / 3 42 / 45 49 / 52

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 127: DOCUMENTAÇÃO TÉCNICA AC SANYO

1. Specifications

1

12

3

4

5

I - 122SM830080

1-11 Installation Instructions

Electrical Characteristics

Indoor Unit : SPW-DR483GH5 6 Outdoor Unit : SPW-CR483EHL8SPW-CR483EL8

Cooling

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 2.8 / 3 1.24 / 1.31 7.7 / 7.72 8.87 / 8.92

kW 600 / 710 0.26 / 0.29 4.14 / 4.16 5 / 5.16

Full load conditionsA 2.8 / 3 1.24 / 1.31 8.8 / 8.82 10.02 / 10.06

kW 600 / 710 0.26 / 0.29 5 / 5.04 5.86 / 6.04

Starting amperes A 4 / 4 3 / 3 48 / 53 55 / 60

Heating (Heat pump only)

Indoor Unit Outdoor UnitComplete Unit

Fan Motor Fan Motor Compressor

Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz

Rating conditionsA 2.8 / 3 1.24 / 1.31 8.89 / 8.91 10.11 / 10.15

kW 600 / 710 0.26 / 0.29 5.06 / 5.08 5.92 / 6.08

Full load conditionsA 2.8 / 3 1.24 / 1.31 9.4 / 9.41 10.62 / 10.66

kW 600 / 710 0.26 / 0.29 5.38 / 5.42 6.24 / 6.42

Starting amperes A 4 / 4 3 / 3 48 / 53 55 / 60

Cooling:

Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB

Outdoor Air Temperature 35°C DB

Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB

Outdoor Air Temperature 43°C DB

Heating:

Rating Conditions : Indoor Air Temperature 20°C DB

Outdoor Air Temperature 7°C DB / 6°C WB

Full Load Conditions : Indoor Air Temperature 24°C DB

Outdoor Air Temperature 21°C DB / 15.5°C WB

Page 128: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 1SM830080

2. PROCESSES AND FUNCTIONS

2-1 Room Temperature Control ...................................................................... II - 2(A) Cooling ................................................................................................ II - 2(B) Heating ................................................................................................ II - 3

2-2 Cold Draft Prevention (Heating Cycle) ...................................................... II - 42-3 Automatic Fan Speed (Indoor Unit) .......................................................... II - 5

(A) Cooling ................................................................................................ II - 5(B) Heating ................................................................................................ II - 5

2-4 Outdoor Fan Speed Control ...................................................................... II - 6(A) Cooling ................................................................................................ II - 6(B) Heating ................................................................................................ II - 6

2-5 Freeze Prevention (Cooling) ..................................................................... II - 72-6 Condensing Temperature Control (Cooling) ............................................. II - 82-7 Overload Protection (Heating) .................................................................. II - 92-8 Discharge Temperature Control (Cooling and Heating) ........................... II - 102-9 Auto. Mode for Automatic Heating/Cooling Switching .............................. II - 112-10 Defrosting Control, Outdoor Heat Exchanger Coil (Heating) .................... II - 122-11 4-Way Valve, Solenoid Control ................................................................. II - 13

(A) Normal Control Mode .......................................................................... II - 13(B) AUTO Control Mode ............................................................................ II - 14

2-12 Automatic Restart after Power Interruption ............................................... II - 142-13 Electronic Expansion Control Valve.......................................................... II - 152-14 Compressor Discharge Gas Temperature ................................................ II - 15

(A) Cooling ................................................................................................ II - 15(B) Heating (Except During Defrosting) ..................................................... II - 15

2-15 Compressor Current Detection Circuit ...................................................... II - 162-16 Dehumidifying Operation .......................................................................... II - 172-17 Auto-flap Control .......................................................................................II - 182-18 Controlled by Electronic Expansion Valve ................................................ II - 192-19 Voltage Detection Control ......................................................................... II - 20

Page 129: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 2SM830080

2-1 Room Temperature Control

The unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF.This process is controlled by the thermostat located in the indoor unit.The figures on this and the next page show how each part of the system performs as theroom temperature changes and the thermostat activates the compressor to start (thermoON) or stop (thermo OFF ). Fig. 1 shows about the cooling cycle, and Fig. 2 shows aboutthe heating cycle.

(A) Cooling

Fig. 1

(THERMO. OFF)

(THERMO. ON)

ROOM TEMP.

THERMO. ON

5 MINUTESMORE THAN5 MINUTES 3 MINUTES

T+1°C

T–1°CSET TEMP. T°C

COMPRESSOR

OUTDOOR FAN(H, M or L)

INDOOR FAN

OFF OFF

OFF OFF1

1. Refer to 2-4 Outdoor Fan Speed Control

MORE THAN3 MINUTES

MORE THAN5 MINUTES

ON ON ON

ON ON ON

SET SPEED

OFF OFF

OFF OFF

ON ON ON

ON ON ON

DRAIN PUMP

DEW PROOFHEATER

BODY SENSOR

1573_X_S

THERMO. OFF

Chart Summary and Explanations

Once the compressor starts , it keeps running for 5 minutes.

Once the compressor stops , it will not start running again for 3 minutes.

If you change the operation mode (HEAT, DRY, COOL, or FAN) during the cooling cycle,the control circuit stops the compressor for 3 minutes.

For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,the compressor is not controlled by the room sensor.

Thermo ON: When room temperature rises 1°C (2°C when set on body sensor) abovethe set temperature T˚, (T˚+1°C or T˚+2°C when set on body sensor):

Compressor ON

Thermo OFF : When the room temperature is –1°C below the set temperature T˚:

Compressor OFF

Page 130: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 3SM830080

(B) Heating

Chart Summary and Explanations

Once the compressor starts, it keeps running for 5 minutes.

Once the compressor stops, it will not start running again for 3 minutes.

If you change the operation mode (HEAT, DRY, COOL or FAN) during the heating cycle,the control circuit stops the compressor for 3 minutes.

For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,the compressor is not controlled by the room sensor.

When set on remote control sensorThermo ON: When room temperature is –1°C below the set temperature T˚.

Compressor ONThermo OFF: When the room temperature is 1°C above the set temperature T˚, (T˚+1°C)

Compressor OFFWhen set on body sensor

NOTE: In case of Body sensor, operating temperature is shifted to setting temperature +4°C .

Fig. 2

THERMO. ON THERMO. ON

+1°C

OFF OFF2

1. Refer to 2-4 Outdoor Fan Speed Control

OFF SET SPEED

ON ON ON

ON (REVERSING CYCLE)

ON

TEMP.OPERATION

REMOTE CONTROL SENSOR

(Only for wireless remote controller)

BODY SENSOR

OFF

OFF

SET SPEEDSET SPEED

3 SECONDS

ON OFF ON

MORE THAN3 MINUTES

OFFONOFF

ON OFF ONOFFOFF ON

3 MINUTESMORE THAN5 MINUTES5 MINUTES

THERMO. ON

THERMO. ONTHERMO. ONTHERMO. ON

2. Refer to 2-2 Cold Draft Prevention (Heating)

BUTTON

COIL (4-WAY)SOLENOIDE2TEMP.COILEXCH.INDOOR HEAT

STANDBY

2INDOOR FAN

1OUTDOOR FAN(H, M or L)

COMPRESSOR

SET. +1°C

SET. –1°C

–1°CSET TEMP.+4°C SHIFT

THERMO. OFF THERMO. OFF

OFF

(31°C)

27°C

25°C

1574_X_S

THERMO. OFF THERMO. OFF

LL LLLLL L

SETTING TEMP.

SET TEMP.

Page 131: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 4SM830080

2-2 Cold Draft Prevention (Heating Cycle)

The cold draft prevention function controls indoor fan speed so a strong draft of cold airwill not blow out before the indoor heat exchange coils have warmed up.

STANDBY shows on the remote controller when the indoor fan speed is LL(very low) or OFF. This condition occurs in the following 3 cases:• During Thermo OFF (refer to 2-1 B). Room Temperature Control, Heating)

• During the defrosting operation (refer to 2-10 Defrosting Control, Heating)

• Until either the coil temperature E2 reaches 27°C or when a maximum of 6minutes has past.

The indoor fan motor operates in L instead of LL for 3 seconds as it starts togive the fan an initial boost.

Chart Summary and Explanations

The main idea of this chart is to show that the indoor fan speed increases and gets closer tothe set fan speed as the coil temperature E2 rises.

The indoor unit’s coil temperature is taken from sensor E2 located in the middle of the indoorheat exchange coil.

The dotted line shows that the indoor fan motor is OFF. When the temperature at sensor E2falls below 10°C, the indoor fan motor stops running.

Fig. 3

33

31

27

25

10

SETFANSPEED

AUTO OR H

M

L LL LL/OFF LL L L L

LL LL/OFF LL L M M

LL LL/OFF LL L M H

MAX. 6 MINUTES

“STANDBY”INDICATOR

INDOOR UNITCOIL TEMP.

E2 (°C)

LL= Very low speedL= Low speed

M= Medium speedH= High speed

“STANDBY” APPEARS

0673_X_S

Page 132: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 5SM830080

Chart Explanations and notes

When the fan speed changes, it keeps the speed step for at least 1 minute, even if thetemperature changes to another speed step during the time.

(B) Heating

Fig. 5

Chart Explanations and notes

When the fan speed changes, it keeps the speed step for at least 3 minutes, even if thetemperature changes to another speed step during the time.

Fig. 4

2-3 Automatic Fan Speed (Indoor Unit)

(A) Cooling

By pressing the FAN SPEED button on the remote controller, the fan speed can be set atone of four steps: AUTO., HI., MED., or LO. When set at AUTO. the indoor unit fan speedwill be automatically adjusted to the room temperature as the two charts shown below.

INDOOR FANSPEED

LH

M MH

0433_M_S

ROOM TEMP.(deg)

SET TEMP.

+3

+2

+1

HM

: High: Middle

LLL

: Low: Very low

INDOOR FANSPEED H

LM MH

0434_M_S

ROOM TEMP. (deg)

SET TEMP.

–2

–4

HM

: High: Middle

LLL

: Low: Very low

Page 133: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 6SM830080

2-4 Outdoor Fan Speed Control

To optimize performance in air conditioner, the outdoor fan speed is selected automaticallyaccording to the outdoor temperature.

Note that in both Cooling and Heating modes, the fan comes on at first athigh speed (H mode) for 5 seconds. Since outdoor conditions sometimesmake it difficult for the fan to start, this sudden surge of power may benecessary.

The outdoor fan operates in H mode for 3 minutes after the compressor stops(excluding defrosting operation period).

Charts below show how the outdoor fan speed changes with the change inoutdoor temperature.

(A) Cooling

Outdoor fanmotor (FMo)

25°C or more H

less than 25°C M

less than 19°C L

25

H

14

M

H

Outdoor coil Outdoor fantemperature [C2] motor (FMo)

14°C or more M

less than 14°C H

(B) Heating

Fig. 6

Fig. 7

19

M

L

* This is supposed to be coil temp [C2] whenoperating outdoor fan without running comp.

*Outdoor Airtemperature

OU

TD

OO

R A

IR T

EM

PE

RA

TU

RE

(°C

)O

UT

DO

OR

CO

IL T

EM

PE

RA

TU

RE

(°C

)

Page 134: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 7SM830080

2-5 Freeze Prevention (Cooling)

Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reducesthe efficiency of the unit, and frost build up on the coil blocks cool air circulation from theindoor unit's fan.

Note: Freeze prevention is controlled by the temperature at the indoor heatexchanger coil as sensed by either sensor E1 (located at the entranceof the coil) or sensor E2 (located on the middle of the coil). Freezeprevention cycle is controlled by the lower temperature sensed at eitherof the two sensors.

Chart Explanations and notes

This chart shows when the electronic expansion valve opens to regulate the temperatureof the indoor unit coil to prevent freezing.

If the refrigerant control is not effective and the temperature continues to drop and staysbelow 0°C for 2 minutes continuously, the control circuit stops the compressor. Thecompressor does not start again until the temperature rises above 1°C.The compressor stops for 3 minutes minimum.

Note: • When low fan speed is selected and the air conditioner is in coolingoperation at a low outdoor temperature of less than 10°C, the airconditioner may automatically switch to medium fan speed.

• Cut the jumper wire (JP11) on the outdoor P.C.B. when the aboveFMI control (LM) is not needed.

Fig. 8

(°C)

INDOOR UNIT COIL TEMP.

ELECTRONICEXPANSION

VALVE SIGNAL

MIN. VALUE OF EITHER E1 OR E2

13

–0.5

0

–0.5

COMPRESSOR

CONTINUOUS DETECTION FOR 2 MINUTES

MINIMUM 3 MINUTESON ON

1563_M_S

OPEN (+60 step/30 sec)OPEN (+60 step/30 sec)

FMI CONTROL L ML M

Page 135: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 8SM830080

2-6 Condensing Temperature Control (Cooling)

Condensing temperature is controlled by the outdoor heat exchanger coil temperature assensed by sensor C2.

Chart Explanations and notes

This chart shows how the outdoor fan speed and the electronic refrigerant control valvereact to coil temperature to control condensing temperature.

Sensor C2 is located in the middle of the outdoor unit heat exchange coil.

When C2 rises above 60°C the electronic control valve opens 50steps / 30 seconds, andthe outdoor for speed increases by one step. The outdoor fan speed doese not change for 5minits.

When C2 falls below 40°C, the outdoor fan speed decreases by one step.

60

40

57

(°C)

C2

FMO

ELECTRONIC CONTROL VALVE

1906_M_I

H, L or LL

+50 step/30 sec

+50 step/30 sec

H or LH

LLL

Fig. 9

Page 136: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 9SM830080

Chart Explanations and notes

This chart shows how the outdoor fan speed and the electronic refrigerant control valvereact to coil temperature to keep the indoor heat exchanger coil from overloading.

When sensor E2 rises above 60°C the electronic refrigerant control valve opens at 50 steps/30 seconds until E2 falls below 59°C.

Sensor E2 is located in the middle of the indoor unit heat exchange unit.

When sensor E2 rises above 62°C, the control circuit stops the outdoor fan motor till thetemp. drops to 55°C

Fuzzy control controls the electronic refrigerant control valve.

Fig. 10

2-7 Overload Protection (Heating)

This function prevents the air conditioner from overloading.

(°C)

ELECTRONIC EXPANSION VALVE

INDOOR UNIT COIL TEMP. (E2)

64

61

60

59

55

53

OUTDOOR FMSTART UP

COMPENSATIONOFF

OPEN

H or M H L

1565_M_S

FUZZY CONTROLFUZZY CONTROL

OVERLOADPROTECTION OVERLOAD PROTECTION

OPEN

H or M

Page 137: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 10SM830080

Chart Summary and Explanations

Discharge temperature is sensed by TH8 (discharge gas sensor).

When the temperature rises above 95°C the electronic refrigerant control valve opens at 50steps/30 seconds until the temperature falls below 93°C .

During HEATING operation, when the temperature rises above 105°C , the control circuitstops the outdoor fan motor until the temperature falls below 90°C. Please note that thiscontrol does not function during COOLING operation.

For both COOLING and HEATING modes, if the temperature reaches 115°C (135°C for 48type) the operation shuts down and alarm P3 appears on the remote controller.

The outdoor fan speed is controlled on discharge temp. at heating mode.

Fig. 11

2-9 Auto. Mode for Automatic Heating/Cooling Switching

When the AUTO mode is selected, the microprocessor calculates the differencebetween the set temperature and the room temperature, and automaticallyswitches to the COOLING or HEATING mode to maintain the desiredtemperature.

Room temp. ] Set temp. COOLINGRoom temp. < Set temp. HEATING

This means that if the room temperature is higher or equal to the settemperature, COOLING operation starts. If the room temperature is lower thanthe set temperature, HEATING operation starts.

2-8 Discharge Temperature Control (Cooling and Heating)

This function prevents the compressor motor from burn out by overheating.

OUTDOOR FAN SPEED

DISCHARGE GAS TEMP. (°C)

115

105

95

93

90

85

COMPRESSOR

ELECTRONIC EXPANSION VALVE (DISCHARGE TEMP.)

TRIP IS OPERATED.

H or M L

1566_M_S

OPENOPEN

H or M

ON

Page 138: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 11SM830080

Fig. 12

Chart summary and Explanations

This chart shows how the Operation Mode (COOLING or HEATING) is determined by themicroprocessor taking the room temperature into consideration. It also shows thetemperature points at which the cooling or heating mode is switched, when the AUTO modeis selected.

After operation starts, the set temperature shifts automatically by +2 deg. at cooling and by -2 deg. at heating. For example, if cooling is selected, the set temperature changes from20° C to 22° C.(The display of the remote controller remains 20° C.)

The change of the operation mode (heating to cooling, cooling to heating) by the change ofthe room temperature during the operation is as follows.

Heating to Cooling; Room temp. ≥ Shifted temp + 0.5 deg.

Cooling to Heating; Room temp. ≤ Shifted temp -1.0deg.

For example, if the room temperature rises above 22.5 °C (=22+0.5) during the coolingoperation at the room temperature 20° C set by the remote controller, the operationchanges to cooling. When the room temperature lowers below 17° C (=18-1.0) thereafter,the operation changes to heating again.

In heating operation, using the body sensor, room temperature control is designed so thatroom air temp. is sensed as 4 deg. lower than suctioned air at indoor unit taking intoaccount of the temperature gap between upper part and lower part of the room.

Within 10 minutes after the compressor turns OFF, the operation does not change tocooling (heating), even when the room temperature changes from C to A (A to C).

When switching from cooling (heating) to heating (cooling), the actuation of the 4 way valvewill delay about 30-50 seconds after the compressor turns ON.

COOLING SELECTION TEMP. +2.5 deg

SHIFT SET TEMP. +2 deg

REMOTE CONTROLLED SET TEMP.

SHIFT SET TEMP. –2 deg

HEATING SELECTION TEMP. –3 deg

HEATING COOLING HEATING0440_M_S

A

B

C

2-9 Auto. Mode for Automatic Heating/Cooling Switching

Page 139: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 12SM830080

During the defrost cycle, STANDBY appears on the remote controller.

*......Cold Draft Prevention may operate occasionally

Time Chart for Defrosting

Fig. 14

Fig. 13

COMPRESSOR

OFF OR LLOFF OR LL

Release ofDefrosting

DefrostingStart

SOLENOID COIL(4 WAY VALVE)

OUTDOOR FAN(H or M)

INDOOR FAN (SET SPEED)

“STANDBY”INDICATOR

MAX. 9 MINUTES 1 MINUTE1 MINUTE

ON ON

ON

ON

ON

ON

ON

“STANDBY” APPEARS

1575_M_S

2-10 Defrosting Control, Outdoor Heat Exchanger Coil (Heating)

When the outdoor temperature is low, frost may form on the outdoor heat exchanger coil.When this occurred, the defrosting system operates. The microprocessor in the outdoorunit monitors the relationship between the temperature of the outdoor heat exchanger coiland the outdoor temperature so it can defrost when necessary.

Occurs either when the temperature of C1 (the outdoorheat exchanger coil) has reached 10°C or above,or when the maximum defrosting time (9 minutes)has elapsed.

Refer to time chart.*Minimum continuous operating time by defrosting is 48 minutes (= 15 + 8 + 25).

Release of defrosting

Defrosting

Stand by time for defros: 25 minutes

Flow of Defrosting

Heating operation

No counting time for detecting frost : 15 minutes

Detecting the frost

OUTDOOR COILTEMP. C1 (°C)

Y “RELEASE OFDEFROSTING”RANGE10

-13.7 10

OUTDOOR AIR TEMP.(°C)X

-3

-8

The area below the heavy line is the frost detection area.

-20

Either continuous 8 minutes or cumulative 60 minutes are required to detect frost in the “Frosting” range.

0441_M_S

Page 140: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 13SM830080

2-11 4-Way Valve, Solenoid Control

The basic function of the 4-way valve is to direct the refrigerant in the correct directionaccording to the Operation Mode (COOLING or HEATING) selected.The following two charts show conditions of the controls and functions listed in the lefthand column when the solenoid is ON or OFF. Chart (A) on this page shows therelationships when the temperature control is in NORMAL mode, and Chart (B) on thenext page shows the relationships when the remote controller is set to AUTO mode.

(A) Normal Control Mode

Fig. 15

Chart Summary and Explanations

For the first 3 minutes after power is applied, the 4–way valve remains OFF and thecompressor will not operate, even if the ON button is pushed.

If the 4–way valve is turned OFF with the compressor operating, the air conditioneroperates in COOLING mode. See Table below.

If the 4–way valve is turned ON with the compressor operating, the air conditioner operatesin HEATING mode. See Table below.

Operation Mode4-way valve

Compressorsolenoid

COOLING OFFON

HEATING ON

OFFOFFOFF

OFF

OFF

3 MINUTES

OFF

TURN ONTURN OFF

THERMO OFFTHERMO ON

THERMO OFFTHERMO ON

22

2

1 111

OFFSOLENOID COIL(4-WAY VALVE)

COMPRESSOR

COOLMODEBUTTON HEAT

OPERATIONBUTTON

POWER SOURCE

1. . . More than 5 minutes 2. . . More than 3 minutes

ONON

HEAT

ON ON ON

HEAT

COOL

ON

ON

ON

ON

0443_M_S

Page 141: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 14SM830080

(B) AUTO Control Mode

When the Compressor has stopped while in AUTO mode, the 4-way valve switches on(heating) or off (cooling) within 1 minute according to the following conditions:

Fig. 16

2-12 Automatic Restart after Power Interruption

This air conditionner has a power failure recovery function.

Compressor has stopped under the operation of

“AUTO mode” condition.

4-way valve delays its switching for 30 – 50 secondsafter compressor has been

turned ON.

0446_M_S

Fig. 17

SOLENOID COIL(4-WAY VALVE)

COMPRESSOR

COOLAUTOMODECONTROL HEAT

OFF OFF

OFF

OFFPOWER SOURCE

OPERATIONBUTTON

OFF

MORE THAN 10 MINUTES(THERMO. OFF)

MORE THAN 10 MINUTES(THERMO. OFF)

3 MINUTES

THERMO. OFFTHERMO. ON

MORE THAN30 – 50 SECONDS

MORE THAN3 MINUTES

OFFOFF

MORE THAN30 – 50 SECONDS

ON ON ON ON

ON

HEAT

COOL

ON

ON

ON

HEAT

0445_M_S

Page 142: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 15SM830080

2-13 Electronic Expansion Valve

This valve allows very precise and smooth control of the amount of refrigerant flow inthe system. Since the valve is operated by a step motor, the control circuits canopen or close it in very exact amounts, so the degree of heating or cooling can bechanged by just a little, or changed very quickly or slowly.

(Completely close …… 0 step)

(Full open................ 480 step)

Fuzzy ControlFuzzy Control is a controlling system to control electronic refrigerant control valveusing fuzzy logic. It regulates the functions of heating and cooling, as well as someof the processes inside the unit, by taking account of many different conditions oftemperature, fan speed, etc. These control circuits work automatically to send justthe right amount of refrigerant through the Electronic Expansion Valve .

2-14 Compressor Discharge Gas Temperature

ModelMin. open

Max. open Standard conditionHEAT COOL

25 type 100 step 120 step 100 – 200

36 type 85 step 85 step 480 step 100 – 200

48 type 85 step 85 step 100 – 200

(A) Cooling

Indoor temp. (˚C) 20 – 25 26 – 28 29 – 32

Outdoor temp. (°C) 13 or below 14 – 16 27 – 35 36 – 43

Compressor dischargegas temp. (°C) 40 – 80 40 – 90 60 – 100 70 – 105

(B) Heating (Except During Defrosting)

Indoor temp. (°C) 18 – 21 22 – 25 26 – 30

Outdoor temp. (°C) 0 or below 1 – 10 0 or below 1 – 10 11 – 21 0 or below 1 – 10 11 – 21

Compressor dischargegas temp. (°C) 40 – 80 50 – 90 40 – 90 50 – 100 60 – 105 50 – 90 60 – 100 70 – 105

Operate the unit at least 30 minutes to stabilize the discharge temperature.

The above discharge temperature was measured with a 15m tubing length.The temperature may vary with tubing length.

Page 143: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 16SM830080

2-15 Compressor Current Detection Circuit

The Compressor Current Detection Circuit detects the compressor current and,depending on the current range, can stop the compressor motor so it will not bedamaged by overcurrent.

Overcurrent can be caused by several factors, particularly mechanical seizing ofthe compressor or liquid backflow. Either of these conditions can hold thecompressor to run, and thus drawing so much current that the motor can burnout.

Chart Summary and Explanations

Overload Protection

• When the detected current is 1.17 – 1.4 times greater than the rated current value (Is) and continuesfor 30 seconds, both compressor and outdoor fan stop (Thermostat OFF).

• After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, if thecondition mentioned above repeats twice within 30 minutes , the remote controller displays the alarmmessage H01, compressor overload .

Locked Compressor Cut-off

• When the detected current is 1.4 times greater than the rated current value (ls) and continues for 2seconds , both compressor and outdoor fan stop (Thermostat OFF).

• After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, if thecondition mentioned above repeats twice , the remote controller displays the alarm message H02,compressor locked .

Failure of Compressor Current Detection

• When the Compressor Current Detection Circuit fails to detect the compressor current within 2seconds after compressor starts , both compressor and outdoor fan stop (Thermostat OFF).

• After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, whenthe circuit fails to detect the current twice in a row, the remote controller displays alarm message H03,Failure of compressor Current Detection.

Fig. 18

Outdoor ModelRated Current Value Overload Protection Locked Compressor Cut-off

ls (A) ls x 1.17 (A) Is x 1.4 (A)

SPW-CR253E(H)L5 23.1 27.0 32.3

SPW-CR253E(H)L8 7.1 8.31 9.94

SPW-CR363E(H)L8 10.3 12.05 14.42

SPW-CR483E(H)L8 13.6 15.9 19.0

Locked Comp. Cut-off Range

Overload Protection Range

Normal Operation Range

Comp. Amps.(A)

Is 1.17

Is 1.4

IsRated Currentvalue

+

+

0447_M_S

Page 144: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 17SM830080

2-16 Dehumidifying Operation

Dehumidifying operation uses the cooling cycle to remove moisture from the air, but byrunning an indoor fan at a low speed, to dehumidify without greatly lowering roomtemperature. In this mode, the microprocessor automatically controls the ON-OFFoperation between +2 deg. and -2 deg. of the set temperature.

The indoor fan speed is automatically set to L and cannot be adjusted to M or H.

When the set temperature is either 18 or 19°C, the set temperature is considered the sameas 20°C.

Room temperature is monitored every 8 minutes when it is in the B range to select the bestoperation mode.

Fig. 19

Fig. 20

A range: When the room temperature is in this range, cooling operation starts. However, whenthe temperature is below 18°C, the cooling operation does not start.

B range: When the room temperature is in this range, the air conditioner automatically repeatsthe dehumidifying cycle of 5 minutes ON, 3 minutes OFF – see Fig. 20 for details.

C range: When the room temperature is in this range, the microprocessor shuts off the airconditioner.

AROOM TEMP.(DEG)

B

C

SET TEMP.

0448_M_S

+2deg

–2deg

ROOM TEMP

5 MINUTES 3 MINUTES

AREA

A

B

C

OFF

OFF

OFF

OFF

INDOOR FAN

OUTDOOR FAN

COMPRESSOR

T+2°C (T+1°C)SET TEMP. T°C

T–2°C (T–1°C)

L

ON

ON ON

ON

ON

ON

Body sensor 0449_M_S

Page 145: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 18SM830080

(1) When the unit is stopped, the Auto-flap returns to F5 position.(2) When the airflow direction is set (an optional setting), the auto and Swing settings will

be released. To return the mode to auto-flap control, change the operation mode.(3) Once Auto-flap is set, the flap position will be input in the memory.(4) When the operation mode is changed, the unit starts to search flap position. (if a

search action for sensing flap position is not succeeded in one minute, only the swingis operated.)

2-17 Auto-flap Control (Indoor Unit : 4-Way Air Discharge Semi-Concealed TypeCeiling-Mounted Type)

Auto flap can control the air flow in 5 steps.

Fig. 21

Operation modeFlap position

Automatic setting Optional setting

Cooling/dehumidifying F2 F1 • F2 • F3 • Swing

Fan F2 F1 • F2 • F3 • F4 • F5 • Swing

Heating F4 F1 • F2 • F3 • F4 • F5 • Swing

Standby for heatingF2 (The flap returns to the original position after

release of the standby mode.)

1328_M_I

F1

F5

60°

Heating F1~F5Cooling F1~F3

F2

F3

F4

Page 146: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

2

3

4

5

II - 19SM830080

2-18 Controlled by Electronic Expansion Valve

The circulation volume of the refrigerant is controlled by a pulse type electronic controlvalve.When the power is switched ON, the opening degree of the electronic control valve iscontrolled between 90 and 480 steps after setting the initial step at the time when thethermostat is ON.

Contents and Order of control

Even though the operation is performed every 30 seconds, the control of discharge gastemperature, high load prevention, outdoor unit coil temperature and freeze preventionactivates when it occurs.

(1) Refrigerant flow distribution control

At the control of flexible combination (a plural number of indoor units are set), the openingdegree of the electronic control valve is controlled by the indoor unit coil temperature.

Cooling: indoor unit coil E2 temperature (located at the middle of coil)Heating: indoor unit coil E1 temperature (located at the outlet of coil)

(2) Fuzzy control (optimal refrigerant flow rate control)

By outputting the fuzzy estimation result corresponding to the fuzzy input variables (theindoor unit coil temp., the deviation between the actual discharge gas temp. and the targetdischarge gas temperature calculated from the outdoor unit coil temperature and thechange thereof), the electronic refrigerant valve is controlled so that the unit can performits maximum ability in accordance with the indoor and outdoor temperature conditions atthe operation.

0451_M_S

Outdoor unit coil temperature control

Freeze prevention control

Refrigerant flow distribution control

* Repeat control in accordance with the priority order.

Discharge gas temperature control

Start

*

Cooling

Discharge gas target temperature control (Fuzzy control)

High load prevention control

Heating start up control

Refrigerant flow distribution control

Discharge gas temperature control

Start

*

Heating

Discharge gas target temperature control (Fuzzy control)

Page 147: DOCUMENTAÇÃO TÉCNICA AC SANYO

2. Processes and functions

1

12

3

4

5

II - 20SM830080

2-19 Voltage Detection Control

When the power voltage falls below 160 V (voltage between N phase and each phase) orrises above 260 V, the “P2” alarm is issued to protect the compressor and electricalcomponents.

Page 148: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 1SM830080

3

3. ELECTRICAL DATA

3-1 Indoor Units (Electric Wiring Diagram, Schematic Diagram) ................. III - 24-Way Air Discharge Semi-concealed Type ........................................... III - 2Ceiling Mounted Type .............................................................................. III - 4Concealed Duct Type .............................................................................. III - 6Concealed Duct High Static Pressure Type ............................................ III - 12

3-2 Outdoor Units (Electric Wiring Diagram, Schematic Diagram) ................ III - 16

Page 149: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

12

3

4

5

III - 2SM830080

3-1 Indoor Units

11111 4-Way Air Discharge Semi-concealed Type : SPW-XR253GH56, SPW-XR363GH56,SPW-XR483GH56

TH

1T

H2

TH

3

31

21

21

21

TH

4

31

21

DP

DP

H

32 PS

1

LSW

Con

nect

or8P

(RE

D)

Con

nect

or9P

(WH

T)

31 F

S

45

3

31

21

21

23

13

14

13

13

13

13

14

33

17

52

31

12

34

56

78

12

34

56

78

12

34

56

78

91

S P2

34

56

78

9

1Pow

erS

uppl

y

Uni

tC

ontr

ol

Line

Ter

min

alP

late

(8P

)

• E

lect

ric W

iring

Dia

gram

W 8

54-2

-526

8-47

0-00

-3 (

X)

To

Rem

ote

Con

trol

Sw

itch

AC

230V

TR

1

RC

1

23

U1

U2

R1

R2

R3

GRN/YEL

GRN/YELGR

N/Y

EL

GR

N/Y

EL

49F

I

BLKBLK

BLKBLK

ORGREDYELBLKGRY

BLKBLK

BLKBLK

BLKBLK

BRNBRN

BRNORG

PNKGRY

ORGYEL

BRN

BLK

BLU

BRN

PNK

BRNREDRED

RED

RED

YELORGVLTWHTGRYGRY

ORG

PNKBRNBLK

YELWHTBLKBRNGRYPNK

WHT

WHT

WHT

GRYGRY

WHT

WHT

BLKBLU

VLT

YEL

FM

I

PNKBRNBRN

LM

MO

V

(BR

N)

Coi

l E3

(BLK

)C

oil E

2(R

ED

)C

oil E

1(Y

EL)

Roo

m T

emp

Co

ntr

olle

r (C

R-X

253G

H)

T6

(WH

T)

DP

(B

LU)

FS

(R

ED

)ER

RN

1(B

LK)

NR

VC

C(W

HT

)R

N2(

WH

T)

NR

RN

3(W

HT

)N

HL

LL FM

(W

HT

)H

HD

PH

(BLU

)LM

(GR

N)

LS(W

HT

)T

20(G

RY

)S

G1

SG

2O

C(B

LU)

SG

12V

GR

C(B

LU)

PN

L(G

RN

)

LN

Page 150: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 3SM830080

• Schematic Diagram

S 854-2-5268-470-00-3 (X)

FMI

2

1

3

1

2

1

2

1

2

1

5

6

8

7

3

1

3

1

2

1

234

5

1234

1TR1

T20

AC230V

8P-U2

8P-U1

To Outdoor Unit

Indoor Coil

Indoor Coil

Indoor Coil

Room Thermistor

TH4

TH3E3

TH2E2

TH1

FS

LSW

8P-R1

CR-X253GHController

8P-R2

8P-R3

E1

23

1

23

1

3

1

1

11R

8

9

3

4

3

3

LM

N N

RC1

2X

1X

3X

RY1

RY2

2

1

3

DPH

21

143

DP

1317531

6 7543

LL L HHH HT

DP

RY2 49FI

T20

RCS

F1(5A)

1X

2X

3X 3X

8P-1(L)

8P-2(N)

RY1

DPH LMLL L HHH R

MOV

Symbols Description

FMI

49FI

RC1

F1

LM

TR1

1X-3X

RY1-RY2

MOV

RCS

TH1

TH2

Indoor Fan Motor

Indoor Motor Thermal Protector

Running Capacitor

Fuse

Auto Louver Motor

Power Transformer

Auxiliary Relay

Auxiliary Relay

Motor Operated Valve

Remote Control Switch

Room Thermistor

Thermistor (Indoor Coil E1)

Symbols Description

TH3

TH4

CR-X253GH

DP

DPH

LSW

FS

Thermistor (Indoor Coil E2)

Thermistor (Indoor Coil E3)

Indoor Controller

Terminal Plate

Connector

Terminal

Drain Pump

Dew Proof Heater

Limit Switch

Float Switch

VCC

SGRC12V

G

T6

PNL

LS

FS

RN2

LM

DP.DPH

DC12V

OCSG1SG2

3-1 Indoor Units

11111 4-Way Air Discharge Semi-concealed Type : SPW-XR253GH56, SPW-XR363GH56,SPW-XR483GH56

Page 151: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

12

3

4

5

III - 4SM830080

3-1 Indoor Units

22222 Ceiling Mounted Type : SPW-TR253GH56, SPW-TR363GH56, SPW-TR483GH56

LM

Con

nect

or9P

(WH

T)

21

31

31

43

31

75

12

34

56

78

1PS

PS2

34

56

78

9 9

W 8

54-2

-526

8-66

5-00

-0 (

TR

)

AC

230V

TR

1

GRN/YEL

GR

N/Y

EL

49F

I

ORGYEL

BRNBRNREDRED

YELORGVLTWHTGRY

Con

nect

or2P

(BLK

)1 1

2 2

BLK

GRY

PNKBRNBLK

WHTWHT

GRYGRY

31

BLKBLK

WHTVLT

FM

I

23

1

Co

ntr

olle

r (C

R-X

253G

H)

E

VC

C(W

HT

)R

N2(

WH

T)

RN

3(W

HT

)F

M(W

HT

)T

20(G

RY

)F

S (

RE

D)

21

43

5

REDORG

BLKGRY

YEL

(WH

T)

T6

PN

L (G

RN

)

MO

V

31

21

23

1

1Pow

erS

uppl

y

Uni

tC

ontr

ol

Line

Ter

min

alP

late

(8P

)

To

Rem

ote

Con

trol

Sw

itch

23

U1

U2

R1

R2

R3

GR

N/Y

EL

BLK

BLU

BRN

PNK

RED

RED

WHT

RN

1(B

LU)

OC

(BLU

)R

C(B

LU)

LN

Con

nect

or4P

(WH

T)

Con

nect

or2P

(WH

T)

31

LSW

BLKWHTGRY

PNK

WHTBLK

PNKGRY

21

21

43

43

SP

P

LM (

GR

N)

LS (

WH

T)

31

BLUWHT

DP

(B

LU)

31 2

1

TH

1T

H2

TH

3

31

TH

4

21

21

21

BLKBLK

BLKBLK

BLKBLK

BRNBRN

(BR

N)

Coi

l E3

(BLK

)C

oil E

2(R

ED

)C

oil E

1(Y

EL)

Roo

m T

emp

41

RC

1

PNKBRNBRN

ORG

• E

lect

ric W

iring

Dia

gram

Page 152: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 5SM830080

• Schematic Diagram

S 854-2-5268-665-00-0 (TR)

FMI

2

1

3

1

2

1

2

1

2

13

1

3

4

2

1

3

1

3

2

1

23

4

5

1

234

1

TR1

AC230V

8P-U2

8P-U1

Indoor Coil

Indoor Coil

Indoor Coil

Room Thermistor

E3

E2

TH1

TH2

TH3

TH4

LSW

8P-R1

CR-X253GHController

8P-R2

8P-R3

E1

23

1

23

1

3

T20

1

1

11

R

8

9

3

2

1

3

LM

N N

RC1

2X

1X

3X

RY1

RY2

2

121

343

17531

6 7543

LL L HHH HT

DP

RY2 49FI

T20

RCS

F1(5A)

1X

2X

3X

8P-1(L)

8P-2(N)

RY1

LMLL L HHH

MOV

Symbols Description

FMI

MOV

49FI

RC1

TR1

LM

LSW

TH1

TH2

TH3

Indoor Fan Motor

Motor Operated Valve

Indoor Motor Thermal Protector

Running Capacitor

Power Transformer

Auto Louver Motor

Limit Switch

Room Thermistor

Thermistor (Indoor Coil E1)

Thermistor (Indoor Coil E2)

Symbols Description

TH4

F1

1X-3X

RY1-RY2

CR

RCS

Thermistor (Indoor Coil E3)

Fuse

Auxiliary Relay

Auxiliary Relay

Indoor Controller

Remote Control Switch

Terminal Plate

Connector

Terminal

VCC

SGRC12V

SG1OC

SG2

G

T6

PNL

LS

FS

LM

RN2

DC12V

DP

To Outdoor Unit

3-1 Indoor Units

22222 Ceiling Mounted Type : SPW-TR253GH56, SPW-TR363GH56, SPW-TR483GH56

Page 153: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

12

3

4

5

III - 6SM830080

3-1 Indoor Units

33333 Concealed Duct High Static Pressure Type : SPW-DR253GH56

TH

1T

H2

TH

3

31

TH

4

21

21

21

21

Con

nect

or9P

(WH

T)

Con

nect

or2P

(BLK

)C

onne

ctor

2P(B

LK)

MO

V

31 F

S

45

3

31

21

21

23

13

14

13

14

33

17

5

12

34

56

78

91

PS2

34

56

78

9

1Pow

erS

uppl

y

Uni

tC

ontr

ol

Line

Ter

min

alP

late

(8P

)

• E

lect

ric W

iring

Dia

gram

W 8

54-2

-526

8-69

3-00

-0 (

DR

)

To

Rem

ote

Con

trol

Sw

itch

AC

230V

TR

1

RC

1

23

U1

U2

R1

R2

R3

GRN/YEL

GR

N/Y

EL

GR

N/Y

EL

49F

I

BLKBLK

BLK

ORGREDYELBLKGRY

BLKBLK

BLKBLK

BLKBLK

BRNBRN

ORGYEL

BRN

BLK

BLU

BRN

PNK

BRNREDRED

RED

RED

YELORGVLTWHTGRYGRY

PNKBRNBLK

WHT

WHT

WHT

GRYGRY

BLKBLK

WHTVLT

FM

I

21

45

32

14

5S C

onne

ctor

5P(W

HT

)

P3

ORGRED

BLKBLK B

LK

YELBLKGRY

21

21

SP2

12

1SP

PNKBRNBRN

23

1

ORG

31

WHTBLU

21

Con

nect

or2P

(WH

T)

P

(BR

N)

Coi

l E3

TH

5

(BLK

)C

oil E

2(R

ED

)C

oil E

1(Y

EL)

Roo

m T

emp

T6

(WH

T)

FS

(R

ED

)ER

RN

1(B

LK)

NR

VC

C(W

HT

)R

N2(

WH

T)

NR

RN

3(W

HT

)N

HL

LL FM

(W

HT

)H

HT

20(G

RY

)

21

Dis

char

geA

ir (G

RN

)S

G1

SG

2O

C(B

LU)

SG

12V

GR

C(B

LU)

PN

L (G

RN

)D

P (

BLU

)

Co

ntr

olle

r (C

R-X

253G

H)

Page 154: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 7SM830080

• Schematic Diagram

S 854-2-5268-693-00-0 (DR)

FMI

2

1

3

1

2

1

2

1

2

1

2

1

2

1

3

1

2345

1234

1TR1

AC230V

8P-U2

8P-U1

To Outdoor Unit

Indoor Coil

Indoor Coil

Indoor Coil

Room Thermistor

TH4

2

1Discharge Air

TH5

TH3E3

TH2E2

TH1

FS

8P-R1

CR-X253GHController

8P-R2

8P-R3

E1

23

1

23

1

3

T20

1

11R

8

9

3

2345

1

N N

RC1

2X

1X

3X

RY2

1

221

143

317531

6 7543

LL L HHH HT

DP

RY2 49FI

T20

RCS

F1(5A)

1X

2X

3X 3X

8P-1

8P-2

LL L HHH R

MOV

Symbols Description

FMI

49FI

RC1

F1

TR1

1X-3X

RY2

MOV

RCS

TH1

TH2

TH3

Indoor Fan Motor

Indoor Motor Thermal Protector

Running Capacitor

Fuse

Power Transformer

Auxiliary Relay

Auxiliary Relay

Motor Operated Valve

Remote Control Switch

Room Thermistor

Thermistor (Indoor Coil E1)

Thermistor (Indoor Coil E2)

Symbols Description

TH4

TH5

CR-X253GH

FS

Thermistor (Indoor Coil E3)

Thermistor (Discharge Air)

Indoor Controller

Terminal Plate

Connector

Terminal

Float Switch

2

1

VCC

SGRC12V

G

T6

FS

RN2

DP

DC12V

OCSG1SG2

PNL

3-1 Indoor Units

33333 Concealed Duct High Static Pressure Type : SPW-DR253GH56

Page 155: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

12

3

4

5

III - 8SM830080

3-1 Indoor Units

44444 Concealed Duct High Static Pressure Type : SPW-DR363GH56

TH

1T

H2

TH

3

31

TH

4

21

21

21

21

Con

nect

or9P

(WH

T)

Con

nect

or2P

(BLK

)C

onne

ctor

2P(B

LK)

MO

V

31 F

S

45

3

31

21

21

23

13

14

13

14

33

17

5

12

34

56

78

91

PS2

34

56

78

9

1Pow

erS

uppl

y

Uni

tC

ontr

ol

Line

Ter

min

alP

late

(8P

)

• E

lect

ric W

iring

Dia

gram

W 8

54-2

-526

8-69

4-00

-0 (

DR

)

To

Rem

ote

Con

trol

Sw

itch

AC

230V

TR

1

RC

1

23

U1

U2

R1

R2

R3

GRN/YEL

GR

N/Y

EL

GR

N/Y

EL

49F

I

BLKBLK

BLK

ORGREDYELBLKGRY

BLKBLK

BLKBLK

BLKBLK

BRNBRN

ORGYEL

BRN

BLK

BLU

BRN

PNK

BRNREDRED

RED

RED

YELORGVLTWHTGRYGRY

PNKBRNBLK

WHT

WHT

WHT

GRYGRY

WHTVLT

FM

I

21

45

32

14

5S C

onne

ctor

5P(W

HT

)

P3

ORGRED

BLKBLK B

LK

YELBLKGRY

21

21

SP2

12

1SP

PNKBRNBRN

23

1

ORG

31 WHT

BLU

21

Con

nect

or2P

(WH

T)

P

(BR

N)

Coi

l E3

(BLK

)C

oil E

2(R

ED

)C

oil E

1(Y

EL)

Roo

m T

emp

Co

ntr

olle

r (C

R-X

253G

H)

T6

(WH

T)

FS

(R

ED

)ER

RN

1(B

LK)

NR

VC

C(W

HT

)R

N2(

WH

T)

NR

RN

3(W

HT

)N

HL

LL FM

(W

HT

)H

HT

20(G

RY

)S

G1

SG

2O

C(B

LU)

SG

12V

GR

C(B

LU)

PN

L (G

RN

)D

P (

BLU

)

BLKBLK

TH

5

21

Dis

char

geA

ir (G

RN

)

Page 156: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 9SM830080

• Schematic Diagram

S 854-2-5268-694-00-0 (DR)

FMI

2

1

3

1

2

1

2

1

2

1

2

1

2

1

3

23

4

5

1234

TR1

AC230V

8P-U2

8P-U1

Indoor Coil

Indoor Coil

Indoor Coil

Room Thermistor

TH4

E3

E2

TH1

TH2

TH3

FS

8P-R1

CR-X253GHController

8P-R2

8P-R3

E1

23

1

23

1

3

T20

1

1

11

R

8

9

3

23

4

5

1

N N

RC1

2X

1X

3X

RY2

1

221

143

317531

7 5643

LL L HTHH H

DP

RY2 49FI

T20

RCS

F1(5A)

1X

2X

3X 3X

8P-1

8P-1

LL L HHH R

MOV

Symbols Description

FMI

49FI

RC1

F1

TR1

1X-3X

RY2

MOV

RCS

TH1

TH2

TH3

Indoor Fan Motor

Indoor Motor Thermal Protector

Running Capacitor

Fuse

Power Transformer

Auxiliary Relay

Auxiliary Relay

Motor Operated Valve

Remote Control Switch

Room Thermistor

Thermistor (Indoor Coil E1)

Thermistor (Indoor Coil E2)

Symbols Description

TH4

TH5

CR-X253GH

FS

Thermistor (Indoor Coil E3)

Thermistor (Discharge Air)

Indoor Controller

Terminal Plate

Connector

Terminal

Float Switch

2

1

1

VCC

SGRC12V

G

T6

FS

RN2

DP

DC12V

OCSG1SG2

PNL

To Outdoor Unit

2

1Discharge Air

TH5

3-1 Indoor Units

44444 Concealed Duct High Static Pressure Type : SPW-DR363GH56

Page 157: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

12

3

4

5

III - 10SM830080

3-1 Indoor Units

55555 Concealed Duct High Static Pressure Type : SPW-DR483GH56

Con

nect

or2P

(BLK

)C

onne

ctor

2P(B

LK)

MO

VF

SBLKBLK

BLK

ORGREDYELBLKGRY

21

45

32

14

5S C

onne

ctor

5P(W

HT

)

P3

ORGRED

BLKBLK B

LK

YELBLKGRY

21

21

SP2

12

1SP

23

1

ORG

WHTBLU

21

Con

nect

or2P

(WH

T)

P

TH

1T

H2

TH

3

31

TH

4

21

21

21

31

21

21

23

13

14

3

1Pow

erS

uppl

y

Uni

tC

ontr

ol

Line

Ter

min

alP

late

(8P

)

• E

lect

ric W

iring

Dia

gram

W 8

54-2

-526

8-69

5-00

-0 (

DR

)

To

Rem

ote

Con

trol

Sw

itch

AC

230V

TR

1

RC

22

3U

1U

2R

1R

2R

3

GRN/YEL

GR

N/Y

EL

49F

I

BLKBLK

BLKBLK

BLKBLK

BRNBRN

BRN

BLK

BLU

BRN

PNK

BRNREDRED

RED

RED

Con

nect

or8P

(WH

T)

12

34

56

78

1PS

23

45

67

8

YELORGVLTWHTGRYGRY

PNKBRN

Con

nect

or6P

(WH

T)

1

SP

1

YE

LO

RG

VLT

WH

T

PN

KB

RN

WHT

WHT

WHT

FM

I

PNK

BRN

RC

1

BRN

23

1

ORG

7 83

14

2

65

2Z

7 83

14

2

65

1Z

7 83

14

2

65

4Z

7 83

14

2

65

3Z

31

GRYGRY

BR

NB

RN

PN

K

PN

K

BR

N

PN

KP

NK

22

33

44

55

66

41

31

75

BR

N

YE

LO

RG

VLT

WH

T

PN

KB

RN

YE

LO

RG

VLT

WH

T

PN

K

PN

K

BR

N

RE

DF

0

21

45

33

13

1

GRN/YEL

(BR

N)

Coi

l E3

(BLK

)C

oil E

2

21

TH

5BLKBLK

Dis

char

geA

ir (G

RN

)(R

ED

)C

oil E

1(Y

EL)

Roo

m T

emp

Co

ntr

olle

r (C

R-X

253G

H)

ERR

N1(

BLK

)N

RV

CC

(WH

T)

RN

2(W

HT

)N

SG

1S

G2

OC

(BLU

)S

G12

VG

RC

(BLU

)T

20(G

RY

)R

RN

3(W

HT

)N

LLL F

M (

WH

T)

T6

(WH

T)

DP

(B

LU)

FS

(R

ED

)P

NL

(GR

N)

HH

H

Page 158: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 11SM830080

3-1 Indoor Units

55555 Concealed Duct Type : SPW-DR483GH56

2

1

2

1 FS

• Schematic Diagram

S 854-2-5268-695-00-0 (DR)

FMI

2

1

3

1

2

12

1

2

1

3

1

2

1

2345

1234

1TR1

AC230V

8P-U2

8P-U1

To Outdoor Unit

Indoor Coil

Indoor Coil

Indoor Coil

Room Thermistor

TH4

TH3E3

TH2E2

TH1

8P-R1

CR-X253GHController

8P-R2

8P-R3

E1

23

1

23

1

3

T20

1

11

R

8

3

2345

1

N N

RC2RC1

2X

1X

3X

RY2

1

1

2

21

143

1Z3Z

2Z4Z

375316543

6543

LL L H HH

DP

RY249FI

T20

RCS

F1(5A)

1X

2X

3X

8P-1

8P-2

LL

4Z

L HHH

3Z 2Z 1Z9

F0(6.3A)

MOV

Symbols Description

FMI

49FI

RC1, 2

F0, 1

TR1

1X-3X

RY2

MOV

RCS

TH1

TH2

TH3

Indoor Fan Motor

Indoor Motor Thermal Protector

Running Capacitor

Fuse

Power Transformer

Auxiliary Relay

Auxiliary Relay

Motor Operated Valve

Remote Control Switch

Room Thermistor

Thermistor (Indoor Coil E1)

Thermistor (Indoor Coil E2)

Symbols Description

TH4

TH5

CR-X253GH

FS

1Z-4Z

Thermistor (Indoor Coil E3)

Thermistor (Discharge Air)

Indoor Controller

Terminal Plate

Connector

Terminal

Float Switch

Auxiliary Relay

2VCC

SGRC12V

G

T6

PNL

FS

RN2

DP

DC12V

OCSG1SG2

2

1Discharge Air

TH5

Page 159: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

12

3

4

5

III - 12SM830080

3-1 Indoor Units

66666 Concealed Duct Type : SPW-UR253GH56, SPW-UR363GH56, SPW-UR483GH56

TH

1T

H2

TH

3

31

TH

4

21

21

21

31

21

Con

nect

or9P

(WH

T)

MO

V

31 F

S

45

3

31

21

21

23

13

14

13

14

33

17

5

12

34

56

78

91

P S2

34

56

78

9

1Pow

erS

uppl

y

Uni

tC

ontr

ol

Line

Ter

min

alP

late

(8P

)

• E

lect

ric W

iring

Dia

gram

W 8

54-2

-526

8-84

3-00

-0 (

UR

93G

HN

56)

To

Rem

ote

Con

trol

Sw

itch

AC

230V

TR

1

RC

1

23

U1

U2

R1

R2

R3

GRN/YEL

GR

N/Y

EL

GR

N/Y

EL

49F

I

BLKBLK

BLKBLK

BLKBLK

BRNBRN

YELORG

BRN

PNK

BRN

REDRED

RED

REDBRN

YELORGVLTWHTGRYGRY

PNKBRNBLK

WHTWHT

WHTBLK

GRYGRY

WHTVLT

FM

I

ORGRED

BLKBLK

BLUBLU

YELBLKGRY

DP

PNKBRNBRN

23

1

ORGG

RN

/YE

L

(BR

N)

Coi

l E3

(BLK

)C

oil E

2(R

ED

)C

oil E

1(Y

EL)

Roo

m T

emp

Co

ntr

olle

r (C

R-X

253G

H)

T6

(WH

T)

DP

(B

LU)

FS

(R

ED

)ER

RN

1(B

LK)

NR

VC

C(W

HT

)R

N2(

WH

T)

NR

RN

3(W

HT

)N

HL

LL FM

(W

HT

)H

HT

20(G

RY

)S

G1

SG

2O

C(B

LU)

SG

12V

GR

C(B

LU)

PN

L (G

RN

)

BLU

LN

21T

H5 BLK

BLK

Dis

char

geA

ir (G

RN

)

Page 160: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 13SM830080

3-1 Indoor Units

66666 Concealed Duct Type : SPW-UR253GH56, SPW-UR363GH56, SPW-UR483GH56

• Schematic Diagram

S 854-2-5268-843-00-0 (UR93GHN56)

FMI

2

1

3

1

2

1

2

1

2

1

3

1

2

1

2345

1234

1TR1

AC230V

8P-U2

8P-U1

To Outdoor Unit

Indoor Coil

Indoor Coil

Indoor Coil

Room Thermistor

TH4

TH3

E3

2

1Discharge Air

TH5

TH2

E2

TH1

FS

8P-R1

CR-X253GHController

8P-R2

8P-R3

E1

23

1

23

1

3

T20

1

11R

8

9

3

N N

RC1

2X

1X

3X

RY2

3

21

143

DP

1317531

6 7543

LL L HHH HT

DP

RY2 49FI

T20

RCS

F1(5A)

1X

2X

3X 3X

8P-1(L)

8P-2(N)

DPHLL L HHH R

MOV

Symbols Description

FMI

49FI

RC1

F1

FS

TR1

1X-3X

RY2

MOV

RCS

TH1

TH2

Indoor Fan Motor

Indoor Motor Thermal Protector

Running Capacitor

Fuse

Float Switch

Power Transformer

Auxiliary Relay

Auxiliary Relay

Motor Operated Valve

Remote Control Switch

Room Thermistor

Thermistor (Indoor Coil E1)

Symbols Description

TH3

TH4

TH5

CR-X253GH

DP

Thermistor (Indoor Coil E2)

Thermistor (Indoor Coil E3)

Thermistor (Discharge Air)

Indoor Controller

Terminal Plate

Connector

Terminal

Drain Pump

VCC

SGRC12V

G

T6

PNL

FS

RN2

DP.DPH

DC12V

OCSG1SG2

Page 161: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

12

3

4

5

III - 14SM830080

3-2 Outdoor Units

11111 SPW-CR253EHL5, SPW-CR253EL5

1

• E

lect

ric W

iring

Dia

gram

23

4N

LT

H6

TH

7

TH

8212121

31

63P

H

31

31

35

79

13

11

3

BLK

BLK

BLK

BLK

WH

T

WH

T

TR

AC

230V

AC

14V

FM

OC

M

RC

PNK

BRNGRY

GRYWHTVLTYEL

CT

BA

UV

W32

RS

T31

21

21

SP

21

21

SP

Con

nect

or

2P (

RE

D)

CH

21

21

43

43

65

65

87

8P

Con

nect

or8P

(W

HT

)

Con

nect

or2P

(Y

EL)

RC

2

S7

BRNBRN

BRNYEL

CS

R

BLK

WHT

RED

GRN/YELPow

er S

uppl

yT

o In

door

Uni

tT

erm

inal

Pla

te (

6P)

Ter

min

alP

late

(2P

)

2 1

Par

ts s

urro

unde

d by

cha

in li

ne

a

re u

sed

for

heat

pum

p m

odel

W 8

54-2

-526

8-77

8-00

-0 (

CR

253E

HL5

)

BR

N

GR

N/Y

EL

RE

D

BLK

BLK

BLU

PN

K

OR

GG

RY

BRN

BRN

GRY

BLKWHTVLT

YEL

PNK

RED

BRN

BLUBLU

BRN

BLUBLU

BRN

WHT

WHT

WHT

GR

N/Y

EL

49F

O

WH

T

RE

DR

ED

WHT WHT

RED

GR

N/Y

EL

21

12

52C

20S

C1

(BLK

)

2P(W

HT

)V

CC

3P(R

ED

)63

PH

3P(Y

EL)

20S

3P(W

HT

)R

S9P

(WH

T)

CN

263P

(BLK

)52

C3P

(WH

T)

CT

1

CN

22P

(B

LU)

N L1 EL

Co

ntr

olle

r (C

R-C

R25

3GH

L5)

(RE

D)

C2

Dis

char

geG

as (

GR

N)

Page 162: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 15SM830080

3-2 Outdoor Units

11111 SPW-CR253EHL5, SPW-CR253EL5

• Schematic Diagram

FMO

2

1

3

1

1

2

2

1

2

1

2

1

3

1

TR

AC 230V

AC 14V

TH8

TH7

TH6

2P-22P-1

3

7

3

1

4

RC2

RY4

RY5

RY6

RY3

N

RY2

21

1

52C

20S

1 9

2

1

3 3

1

765

53

H LM

49FO

RY3

63PH-1

RY2RY4

RY5 RY6

H M L 20S 52C

CH

2

1

52C

Symbols Description

CM

FMO

52C

49FO

63PH

CT

RC,RC2

TR

CH

20S

F1

TH6

TH7

TH8

Compressor Motor

Outdoor Fan Motor

Compressor Motor Magnetic Contactor

Outdoor Fan Motor Thermal Protector

High Pressure Switch

Current Transmitter

Running Capacitor

Power Transformer

Crank Case Heater

Four Way Valve

Fuse

Thermistor (Outdoor Coil C1)

Thermistor (Outdoor Coil C2)

Thermistor (Discharge Gas)

Symbols Description

CR-CR253EHL5

RY2~6

Outdoor Controller

Auxiliary Relay

Terminal Plate

Terminal

Connector

63PH

49FO

49C

CM

52C

C RS

RC

-2

-3

-4

-L

-N

CT

CR-CR253GHL5Controller

TerminalPlate (6P)

L1 F1(3.15A)

CN2

FM1

DC12V

FM2

52C

20S

RS

VCC

OutdoorCoil C1

OutdoorCoil C2

Dischargegas

CT1

N

Parts surrounded by chain line are used for heat pump model.

S 854-2-5268-778-00-0 (CR253EHL5)

Page 163: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

12

3

4

5

III - 16SM830080

3-2 Outdoor Units

22222 SPW-CR253EHL8, SPW-CR253EL8

1

• E

lect

ric W

iring

Dia

gram

23

45

67

8T

H6

TH

7

TH

8212121

31

63P

H

31

31

35

79

13

11

3

BLK

BLK

BLK

BLK

WH

T

WH

T

TR

AC

230V

AC

14V

FM

OC

MPNK

BRNGRY

GRYWHTVLTYEL

CT

BA

UV

W32

RS

T31

21

21

SP

21

21

SP

Con

nect

or

2P (

RE

D)

CH

21

21

43

43

65

65

87

8P

Con

nect

or8P

(W

HT

)

Con

nect

or2P

(Y

EL)

RC

2

S7

BRNBRN

BRNYEL

RS

T

BLU

GRY

GRY

WHT

RED

GRN/YELPow

er S

uppl

yT

o In

door

Uni

tT

erm

inal

Pla

te (

8P)

Ter

min

alP

late

(2P

)

52C

2 1

WH

T

BR

NB

LU

GR

N/Y

EL

RE

D

BLK

BLK

BLU

PN

K

OR

GG

RY

BRN

BRN

GRY

WHTVLT

PNK

RED

BRN

BLUBLU

BRN

BLUBLU

BRN

WHT

WHT

WHT

GR

N/Y

EL

49F

O

BR

N

RE

DR

ED

WHT

BLU

RED

GR

N/Y

EL

21

49C

12

L1L2

L3N

20S

3P(R

ED

)63

PH

3P(Y

EL)

20S

3P(B

LK)

52C

9P(W

HT

)C

N26

3P(W

HT

)C

T1

3P(W

HT

)R

S2P

(WH

T)

(BLK

)C

1

(RE

D)

C2

Dis

char

geG

as (

GR

N)

CN

22P

(B

LU)

L1 EL2L3N

VC

C

Co

ntr

olle

r (C

R-C

R48

3GH

L8)

YEL

L

Par

ts s

urro

unde

d by

cha

in li

ne

a

re u

sed

for

heat

pum

p m

odel

W 8

54-2

-526

8-77

9-00

-0 (

CR

253E

HL8

)

Page 164: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 17SM830080

3-2 Outdoor Units

22222 SPW-CR253GHL8, SPW-CR253EL8

• Schematic Diagram

FMO

2

1

3

1

1

2

2

1

2

1

2

1

3

1

TR

AC 230V

AC 14V

TH8

TH7

TH6

2P-22P-1

37

3

1

4

RC2

RY4

RY5

RY3

L2

RY2

21

1

52C

20S

1 9

2

1

3 3

1

765

53

H LM

49FO

49C

RY3

63PH-1

RY2RY4

RY5

H M 20S 52C

CH

2

1

52C

F2(3.15A)

Symbols Description

CM

FMO

52C

49C

49FO

63PH

CT

RC2

TR

CH

20S

F1,2

TH6

TH7

TH8

Compressor Motor

Outdoor Fan Motor

Compressor Motor Magnetic Contactor

Compressor Motor Termal Protector

Outdoor Fan Motor Thermal Protector

High Pressure Switch

Current Transmitter

Running Capacitor

Power Transformer

Crank Case Heater

Four Way Valve

Fuse

Thermistor (Outdoor Coil C1)

Thermistor (Outdoor Coil C2)

Thermistor (Discharge Gas)

Symbols Description

CR-CR483EHL8

RY2~6

Outdoor Controller

Auxiliary Relay

Terminal Plate

Terminal

Connector

63PH

49FO

49C

CM

52C

R TS

L3 N

-2

-3

-4

-5

-6

L1

-7L3

-8N

L2

CT

CR-CR483GHL8Controller

TerminalPlate (8P)

L1 F1(3.15A)

FM1

DC12V

FM2

RY6

52C

20S

CN2

RS

VCC

OutdoorCoil C1

OutdoorCoil C2

Dischargegas

CT1

N L3 L2

RY6

L

Parts surrounded by chain line are used for heat pump model

S 854-2-5268-779-00-0 (CR253EHL8)

Page 165: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

12

3

4

5

III - 18SM830080

3-2 Outdoor Units

33333 SPW-CR363EHL8, SPW-CR363EL8, SPW-CR483EHL8, SPW-CR483EL8

1

• E

lect

ric W

iring

Dia

gram

23

45

67

8T

H6

TH

7

TH

8212121

31

63P

H

31

31

35

79

13

11

3

BLK

BLK

BLK

BLK

WH

T

WH

T

TR

AC

230V

AC

14V

FM

O2

CM

PNK

BRNGRY

GRYWHTVLTYEL

CT

BA

UV

W32

RS

T31

21

21

SP

21

21

SP

Con

nect

or

2P (

RE

D)

CH

21

21

43

43

65

65

87

8P

Con

nect

or8P

(W

HT

)

Con

nect

or2P

(Y

EL)

RC

3

S7

BRNBRN

BRNYEL

UV

W

BLU

WHT

RED

GRN/YELPow

er S

uppl

yT

o In

door

Uni

tT

erm

inal

Pla

te (

8P)

L1L2

L3N

Ter

min

alP

late

(2P

)

52C

2 1

WH

T

BR

NB

LU

GR

N/Y

EL

RE

D

BLK

BLK

BLU

PN

K

OR

GG

RY

BRN

BR

N

WHTGRY

VLT

YEL

PNK

RED

BRN

BLUBLU

BRN

WHTVLT

BLUBLU

BRN

WHT

WHT

WHT

GR

N/Y

EL

49F

O2

FM

O1

PNK

BRNGRY

GRYWHTVLTYEL

21

21

43

43

65

65

87

8P

Con

nect

or8P

(W

HT

)

RC

2

S7

BLK

BLK

GRYGRY

WHTVLT

YEL

RED

GR

N/Y

EL

49F

O1

BR

N

RE

DR

ED

WHT

BLU

RED

GR

N/Y

EL

21

12

20S

Co

ntr

olle

r (C

R-C

R48

3GH

L8)

3P(R

ED

)63

PH

31

63P

L

REDRED

3P(G

RN

)63

PL

3P(Y

EL)

20S

3P(B

LK)

52C

9P(W

HT

)C

N26

3P(W

HT

)C

T1

3P(W

HT

)R

S2P

(WH

T)

(BLK

)C

1

(RE

D)

C2

Dis

char

geG

as (

GR

N)

CN

22P

(B

LU)

L1 EL2L3N

VC

C

L

Par

ts s

urro

unde

d by

cha

in li

ne

a

re u

sed

for

heat

pum

p m

odel

W 8

54-2

-526

8-78

7-00

-1 (

CR

363E

HL8

)

YEL

Page 166: DOCUMENTAÇÃO TÉCNICA AC SANYO

3. Electrical data

1

2

3

4

5

III - 19SM830080

3-2 Outdoor Units

33333 SPW-CR363EHL8, SPW-CR363EL8, SPW-CR483EHL8, SPW-CR483EL8

• Schematic Diagram

FMO2

2

1

3

1

1

2

2

1

2

1

2

1

3

1

TR

AC 230V

AC 14V

TH8

TH7

TH6

2P-22P-1

37

3

1

4

4

RC3

RY4

RY5

RY6

RY3

L2

RY2

21

1

52C20S

1 9

2

1

3 3

1

765

53

H LM

FMO1

RC2

21

765H LM

49FO1

49FO2

RY3

63PH

L1 F1(3.15A)

-1

RY2RY4

RY5

H M L 20S 52C

1

3

63PL

63PL

F2(3.15A)

Symbols Description

CM

FMO1,2

52C

49FO1,2

63PH

63PL

CT

RC2,3

TR

CH

20S

F1,2

TH6

TH7

TH8

Compressor Motor

Outdoor Fan Motor

Compressor Motor Magnetic Contactor

Outdoor Fan Motor Thermal Protector

High Pressure Switch

Low Pressure Switch

Current Transmitter

Running Capacitor

Power Transformer

Crank Case Heater

Four Way Valve

Fuse

Thermistor (Outdoor Coil C1)

Thermistor (Outdoor Coil C2)

Thermistor (Discharge Gas)

Symbols Description

CR-CR483EHL8

RY2~6

Outdoor Controller

Auxiliary Relay

Terminal Plate

Terminal

Connector

63PH

49FO

49C

CM

52C

U WV

L3 N

-2

-3

-4

-5

-6

L1

-7L3

-8N

L2

CT

CR-CR483GHL8Controller

TerminalPlate (8P)

3FM1

DC12V

FM2

52C

20S

CN2

RS

VCC

OutdoorCoil C1

OutdoorCoil C2

Dischargegas

CT1

N L3 L2

CH

2

1

52C ∗

RY6

Parts surrounded by chain line are used for heat pump model

S 854-2-5268-787-00-1 (CR363EHL8)

Page 167: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 1SM830080

4. SERVICE PROCEDURES

4-1 Troubleshooting ...................................................................................... IV - 2(1) Check before and after Troubleshooting.......................................... IV - 3(2) General Troubleshooting Flow Chart: Diagnosis and Remedy ........ IV - 5(3) Meanings of alarm messages .......................................................... IV - 7(4) LED Indication on the Outdoor Unit’s P.C.B. Ass’y.......................... IV - 9(5) Symptoms and parts to inspect........................................................ IV - 10(6) Procedures When a Specific Component Does Not Work............... IV - 20(7) Service Functions of Remote Controller .......................................... IV - 22

4-2 Checking the Electrical Components ...................................................... IV - 36(1) Measurement of Insulation Resistance ............................................ IV - 36(2) Measurement of Insulation Resistance for Electrical parts .............. IV - 37(3) Checking the Protective Devices ..................................................... IV - 38(4) Checking the Electrical Parts ........................................................... IV - 39(5) Sensor and Solenoid Layout Diagram ............................................. IV - 42(6) Thermistor Characteristic Curve ...................................................... IV - 47(7) P.C.B. Setting .................................................................................. IV - 48(8) R.C Address Setting Method ........................................................... IV - 49(9) Automatic Address Setting Method.................................................. IV - 50

(10) Displaying Indoor / Outdoor Unit Combination Numbers ................. IV - 50(11) Items to Check Prior to Test Run ..................................................... IV - 51(12) Test Run Procedure ......................................................................... IV - 52

Page 168: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 2SM830080

4-1 Troubleshooting

This section explains:

This unit is made to be trouble free, and not need much service. However, with time,moving parts wear out, electronic components break down, and sometimes misusedamages the unit.The purpose of this section is to help you when the unit is not working properly.Sometimes your experience will tell you right away where to look for a problem, and whenyou find it you will know how to fix it at once.Often, however, all you have is a symptom like “poor cooling” or “outside fan doesn’tcome on.” Now you must find out the cause of the problem, and then how to fix it. Thissection provides several ways to help you go from the symptom to the cause and then thesolution.The first chart, General Troubleshooting Flow Chart is divided into two sections: Poorheating and Poor Cooling. Under each heading you will find the main things that can gowrong and cause either of these problems. Sometimes you can start with this chart andfind the problem right away, but often you will come here for more suggestions after youhave looked at the error code on the remote control unit display. This chart gives you the"big picture" of problems and solutions.The other main tool we explain here is the use of the Alarm Messages . When a certainpart fails or a safety device has shut the unit down, any alpha-numeric codes appears onthe display to guide you to the problem.By understanding the code you can often go right to the problem area and then, with thismanual and your knowledge of air conditioning, find the solution.

What the LED codes mean

What the remote control unit display screen messages mean

How to use the flow charts to find and solve problems

How to use the self-diagnostic tests to find parts that aren’t working right

Page 169: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 3SM830080

(1)-1 Check before and after Troubleshooting (SPW-CR253 EHL5)

Many problems may happen because of wiring or power supply problems, so you shouldcheck these areas first. Problems here can cause false results in some of the other tests,and so should be corrected first.

11111. Check power supply wiring Check the power supply wires are correctly connected between terminal

No. 1 & 2 on the 3P terminal plates in the indoor unit and the outdoor unit.

22222. Check inter-unit wiring Check that inter-unit control wiring (DC low voltage) is correctly connected

between the indoor unit and outdoor unit.

Power Supply: 50 Hz, single-phase, 220-230-240 V

33333. Check power supply Check that voltage is within the specified range (±10% of the rating). Check that power is being supplied.

If the following troubleshooting must be done with power being supplied,be careful not to touch any uninsulated live part that can cause ELECTRICSHOCK.

44444. Check the lead wires and connectors in indoor and outdoor units. Check that the sheath of lead wires is not damaged. Check that the lead wires are firmly connected at the terminal plate. Check that the wiring is correct.

Fig. 22

1

2

U1

U2

1

2

R1

R2

R3

1

2

3

1

2

4

L

N

Indoor Unit

Inter-unitpower wiring(Line voltage)

Inter-unitcontrol wiring(Low voltage)

RED

WHT

BLK

Remote controller

Outdoor Unit

Ground

Ground

D

B

A

0500_M_I

Power supply

R.C. Address on the PCB: 0 (S2, BLK)(0: Factory shipped state)

220 - 240 V 50 Hz

L

N

0

1

2

3

C

Page 170: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 4SM830080

Power Supply: 50 Hz, 3-phase, 380-400-415 V

1

2

U1

U2

R1

R2

R3

1

2

3

1

2

3

1

2

4

L1

L2

L3

N

Indoor Unit

Inter-unitpower wiring(Line voltage)

Inter-unitcontrol wiring(Low voltage)

RED

WHT

BLK

Remote controller

Outdoor Unit

Ground

Ground(Option)

B

D

A 0499_M_I

Power supply

R.C. Address on the PCB: 0 (S2, BLK)(0: Factory shipped state)

380 - 415 V - 3 N 50 Hz

L1

L2

L3

N

1

2

0

C

(1)-2 Check before and after Troubleshooting (SPW-CR253 EHL8, CR363EHL8, CR483EHL8)

Many problems may happen because of wiring or power supply problems, so you shouldcheck these areas first. Problems here can cause false results in some of the other tests,and so should be corrected first.

11111. Check power supply wiring Check that power supply wires are correctly connected to terminal No.5

through No.8 on the 8P terminal plate in the outdoor unit. Check the power supply wires are correctly connected between terminal

No.1 and 2 on the 3P terminal plate in the indoor unit and terminal No.1and 2 on the 8P terminal plate in the outdoor unit.

22222. Check inter-unit wiring

Check that inter-unit control wiring (DC low voltage) is correctly connectedbetween the indoor unit and outdoor unit.

33333. Check power supply Check that voltage is within the specified range (±10% of the rating). Check that power is being supplied.

If the following troubleshooting must be done with power being supplied,be careful not to touch any uninsulated live part that can cause ELECTRICSHOCK.

44444. Check the lead wires and connectors in indoor and outdoor units. Check that the sheath of lead wires is not damaged. Check that the lead wires are firmly connected at the terminal plate. Check that the wiring is correct.

Fig. 23

Page 171: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 5SM830080

(2) General Troubleshooting Flow Chart: Diagnosis and Remedy

When you have found a major problem, such as refrigerant not flowing in the system orreduced air circulation, come to this section and find the box listing the problem.Connected to the box are the main causes of the problem and their remedies. To find outwhich malfunction is happening in your case, check the remote controller for an AlarmMessage, and follow the steps in section 3).

(A) Cooling

Poor cooling

Is setting temp.suitable ?

Change the setting temp.

Is cooling loadtoo heavy ?

Review cooling load estimate.

4-way valve isdefective.

Replace the 4-way valve.

Refrigerant shortage

Charge refrigerant gas.

Refrigerant flowfailure

Electronic refrigerantcontrol valve is defective.

Service valves are notfully open.

Replace the compressor.Compressor is defective.

Open the valves fully.

Air filteris clogged.

Clean the filter.Not enough aircirculation

Is fan speedset to LOW ?

Set the fan speed toeither MEDIUM or HIGH.

Refrigerant tubes betweenindoor and outdoor units are not insulated.

Insulate wide and narrowtubes separately.

Replace the valve.

a. Cooling

0458_M_I

Page 172: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 6SM830080

(B) Heating

Poor heating

Is setting temp.suitable ?

Change the setting temp.

Is heating loadtoo large ?

Review heating loadestimate.

4-way valve isdefective.

Replace the valve.

Refrigerant shortage

Charge with refrigerant.

Refrigerant flowfailure

Electronic refrigerant control valve is defective.

Service valves are notfully open.

Replace the compressor.Compressor is defective.

Open the valves fully.

Air filteris clogged.

Clean the filter.Not enoughair circulation

Is fan speedset to LOW ?

Set the fan speed toeither MEDIUM or HIGH.

Refrigerant tubes between indoor and outdoor units are not insulated.

Insulate wide and narrowtubes separately.

Replace the valve.

4-way valve isdefective.

Replace the valve.Cold air isdischarged.

“ STANDBY ” is displayed.

Cold draft preventionis not working.

Replace indoor P.C.B. Ass'y.

Indoor coil sensor E2 isdefective.

Replace the sensor.

b. Heating

0459_M_I

Page 173: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 7SM830080

(3) Meanings of alarm messages

If an error occurred in the air conditioner, the error condition is presented by indicating theerror code in the wired remote controller display or by the combination of lamp statuses foroperation, timer and heat stand-by (OFF status and flashing status).

Remote controller is detectingunusual signal from indoor unit.

Wired remotecontrollerdisplay

Wireless remotecontrollerdisplay

Possible causes of troubles

Improper setting of indoor unit orremote controller.

Indoor unit is detecting unusualsignal from signal option.

Improper setting of indoor unit orremote controller.

Indoor unit is detecting unusualsignal from outdoor unit.

Outdoor unit is detectingunusual signal from indoor unit.

Auto. address setting is notcorrect.

Indoor unit is detecting unusualsignal from another indoor unit.

Improper setting of indoor unit orremote controller.

•S

eria

l com

mun

icat

ion

erro

rs •

Mis

-set

ting

•M

is-s

ettin

g

Operation lampand heat stand-by lamp flash atthe same time.

O: Operationlamp

v: Timer lamp

O: Heat stand-by lamp

• Indoor unit is detecting unusual signal from the remote controller or group control. (No serial communications signal)

Heat stand-by

lamp flashes

v:Operationlamp

v: Timer lamp

O: Heat stand-by lamp

Operationlamp flashes

O: Operationlamp

v: Timer lamp

v:Heat stand-by lamp

Error receiving of serial communications signal.

Error transmitting of serial communications signal.

Indoor unit address setting is duplicated.

Remote controller address (RCU.ADR) is duplicated.

Error receiving of serial communications signal.

When using flexible combination control, main indoor unit addresssetting is duplicated. (judged by outdoor unit.)

Error receiving of serial communications signal.

Error transmitting of serial communications signal

Error receiving of serial communications signal.

(Confirmation error of unit numbers included)

Error transmitting of serial communications signal.

No. of judged indoor units or total capacity of indoor units is small.

No. of judged indoor units or total capacity of indoor units is large.

Error receiving of serial communications signal.

Model setting of indoor unit is not matching the outdoor unit.

When using group control, main indoor unit address setting is duplicated.(judged by indoor unit.)

Improper wiring between indoor units.(There is a group connection wiring in case of individual control.)

Capacity code of indoor unit is not set.

Improper wiring of group control wiring.

E01

E02

E03

E08

E09

E11

E14

E04

E05

E06

E07

E15

E16

E18

L02

L03

L07

L09

L11

P09

P01

P10

P02

P03

P04

P05

P31

Thermal protector in indoor fan motor is activated.

Float switch is activated.

• Thermal protector in outdoor fan motor is activated.• PC or AC Compressor thermal protector is activated.• Power supply voltage is unusual. (The voltage is more than

260 V or less than 160 V between L and N phase.)

Discharge gas temperature of PC comp. is unusual.

High pressure switch is activated.

Negative phase or voltage drops.

Other indooor unit is warning.

Improper wiring connections of ceiling panel.

Protective device in indoor unitis activated.

Protective device in outdoor unitis activated.

Operation lampand heat stand-bylamp flashalternately.

O: Operationlamp

v: Timer lamp

O: Heat stand-by lamp

v: Operationlamp

O: Timer lampO: Heat stand-

by lamp

•A

ctiv

atio

n of

pro

tect

ive

devi

ce

Page 174: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 8SM830080

Wired remotecontrollerdisplay

Wireless remotecontrollerdisplay

Possible causes of troubles

•T

herm

isto

r fa

ilure

Operation lampand heat stand-bylamp flashalternately.O: Operation

lamp

O: Timer lamp

v:Heat stand-by lamp

Indoor thermistor is eitheropen or short.

Outdoor thermistor is eitheropen or short.

Indoor coil temp. (E1 = TH2) cannot be detected.

Indoor coil temp. (E2 = TH3) cannot be detected.

Indoor room temperature cannot be detected.

Discharge gas temp.A (PC compressor=TH0A) cannot be detected.

Outdoor coil liquid temp. (C1 = TH0E) cannot be detected.

Outdoor coil gas temp. (C2 = TH0C) cannot be detected.

v:Operationlamp

O: Timer lamp

v:Heat stand-by lamp

Protective device forcompressor is activated.

PC compressor motor is overloaded.

PC compressor motor is locked.

Compressor current detection circuit is defective.

Low-pressure protector is activated.(Low pressure switch or low pressure prevention.)

Standard comp. contactor (Mg SW)is chattering.

F01

F02

F10

F04

F06

F07

H01

H02

H03

H06

H18

•F

ault

with

com

pres

sor

and

its c

ircui

t

O: flashes

v: OFF

Page 175: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 9SM830080

(4) LED Indication on the Outdoor Unit’s P.C.B. Ass’y

If something goes wrong with the outdoor unit, LED lamps on the outdoor P.C.B. Ass’ylight up to show the cause of the trouble, in addition to the Alarm message on the remotecontroller.

* REFRIGERANT SHORTAGENote particularly that a shortage of refrigerant is only shown by the outdoor P.C.B.Ass’y LEDs and the Alarm Message does not appear on the Indoor Remote Controller .The compressor keeps running even when the refrigerant is less, so when you find theLED indication on the outdoor P.C.B. Ass’y , stop the air conditioner immediately toavoid the compressor damage.

Fig. 24

LED 2 onP.C. board

Remotecontroller

LED 1 onP.C. board Possible cause of trouble

v v No message

v V E06, E07, L04

v * No message

V v P02

V V P04, P05

V * F04~F09

* v H01, H02

* V H04, H05

* * E15, E16

* *

Flash at the same time

“SETTING”flashes.Flash alternately

0654_C_I

LED 1LED 2

Normal

Outdoor unit serial communication signal is abnormal.

Outdoor unit address is duplicated.

Other outdoor units are performing auto address and

detecting refrigerant shortage.

FMo • CM thermal protection is in operation.

Power supply voltage is abnormal.

High voltage SW activates

Negative phase protector activates.

Sensor is abnormal. (Open or short)

Abnormal compressor current value is detected.

Scroll thermal protection failure is detected.

Auto address failure

Auto address is in operation.

NOTE v: LED lamps OFF V: LED lamps ON (lights up) * : LED lamps ON (flashes)

CAUTION

Page 176: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 10SM830080

(5) Symptoms and parts to inspect

1) Symptom: LCD on the remote controller does not display and remote controller doesnot operate.

No

No

No

No

No

No NoNo

No

No

Yes

Yes

Yes

Yes

Yes

Yes

YesYes

Yes

Yes

Start

Replace the indoor unit PCB.

Is there 12 V DC between 2 and 3 of the remote controller?

Replace the remote controller.

Repair the remote controller wiring.

Has the indoor unit PCB fuse blown?

Check and repair the power breaker etc.

Replace the indoor unit’spower transformer.

Is the 220-240 V ACcircuit shorted?

Replace or repair.

Replace the indoor unit PCB.

Is there 220-240 V AC between R and S of the indoor PCB?

Is the LED (D80) on the indoor unit PCB lit?

Is there 12 V DC between R2 and R3 on the 8P terminal plate of the indoor unit?

Is the primary side of the indoor power transformer shorted?

Is there 220-240 V AC between U1 and U2 of the 8P terminal plate?

Are the connections for the 4P connector for the indoor unit’s PCB power trans-former good?

Is there 15 V AC between 1 and 2 of the 4P connector for the indoor unit’s power transformer?

Miswiring of power supply wires andindoor/outdoor control lines

Correct the connections

Replace the indoor unit power transformer.

Correct the wiring. Remove the socket connected to the OC plug on the PCB and connect to the EMG plug instead.

0332_M_I

Page 177: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 11SM830080

2) Symptom: LCD on the remote controller displays “CHECK E01”.(Unusual communication between remote controller and indoor unit.)

3) Symptom: LCD on the remote controller displays “CHECK E02”. (Unusualcommunication between remote controller and indoor unit)

OK

No

NG

Yes

0334_M_I

Start

Repair the wiring.

Replace the remote controller.

Is the No. 1 line wire (red) for the remote controller connected to another line (2 or 3) or are No. 1 and No. 3 (black) wired reversed?

Remote controller judges itself with self-diagnostic functions.(To avoid misjudgment, always remove the No. 1 line of the remote controller wiring from the indoor unit terminal plate.)

Replace the indoor unit PCB.

OK

No

No

No

Yes

Yes

Yes

NG

1905_M_I

Start

Remote controller judges itself with self-diagnostic functions

Replace the remote controller.

Correct the wiring.

Correct the setting.

Open the forced OPR pin.

Is there an open or a contact defect in the No. 1 line of the remote controller?

Is the setting for the non-volatile memory IC on the indoor unit PCB inappropriate?

No

Yes YesIs there 220 -240 V AC between U1 and U2 of 8 P terminal plate?

Mis-wiring between the power supply line and indoor/ outdoor unit operation lines.

Correct the wiring, and pull out the socket connected to the OC plug to replace with the EMG plug.

Is the indoor unit PCB’s forced OPR pin shorted?

Replace the indoor unit PCB.

Page 178: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 12SM830080

4) Symptom: LCD on the remote controller is displaying “CHECK E04”. (Unusualcommunication between the indoor and outdoor units.)

5) Symptom: LCD on the remote controller is displaying “CHECK E05”. (Unusualcommunication between the indoor and outdoor units)

0336_M_I

Start

Indoor unit PCB transmission/reception circuit defect

Replace the indoor unit PCB.

Yes

No No

Yes

No

Yes

0335_M_I

Start

Is the contact good at the 2P connector for indoor serial communications on the outdoor unit PCB?

Is the contact good at the 2P connector for indoor serial communications on the outdoor unit PCB?

Correct the connections.

NoCorrect the connections.

Replace the indoor unit PCB.

Replace the indoor unit PCB. Indoor/outdoor unit control lines are cut off

Correct the wiring.

Cut the breaker, remove the indoor/outdoor unit control lines connected to U1 and U2 ofthe outdoor unit 8P terminal plate. After shorting the test pin (CN11) on the outdoor unit PCB, switch the breaker on. Do the LEDs (red, × 2) on the PCB flash?

Cut the breaker and remove the indoor/outdoor unit control lines connected to U1 and U2 of the indoor unit 8P terminal plate. After shorting the test pin (CN2) on the indoor unit PCB, switch the breaker on. Does the LED (red) on the PCB light up?

Page 179: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 13SM830080

6) Symptom: LCD on the remote controller is displaying “CHECK E06”. (Unusualcommunication between the indoor and outdoor units)

* See the section of INSTALLATION INSTRUCTION concerning with flexiblecombination system.

7) Symptom: LCD on the remote controller is displaying “CHECK E08”. (Duplicateindoor unit address setting)

No

Yes

0339_M_I

Start

Replace the remote controller.

Correct the setting.*Are there two remote controllers

(master-slave) installed with both remote controllers set as masters?

* See the section of INSTALLATION INSTRUCTION concerning with controllingremote controller switches when there are two remote controllers.

8) Symptom: LCD on the remote controller is displaying “CHECK E09”. (Duplicatesetting of RCU address switch of remote controllers)

No

Yes

1903_M_I

Start

Correct wiring.

Influenced by external noise

Is there a cut line or contact defect between an indoor and outdoor unit’s control line?

No

Yes

1904_M_I

Start

Influenced by external noise

Correct the setting. Is the setting for the non-volatile memory IC on the indoor unit PCB inappropriate? (Are there two units with the same address?)

* See the section of INSTALLATION INSTRUCTION concerning with flexiblecombination system.

Page 180: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 14SM830080

9) Symptom: LCD on the remote controller displays “CHECK P01”. (Indoor fanprotection thermostat operation warning)

No

No

No

Yes

Yes

Yes

0340_M_I

Start

Is there 220-240 V AC between S4 and T20-3 on the indoor unit PCB?

Is there 220-240 V AC between T20-3 and S4 after T20-1 and T20-3 on the indoor unit PCB shorted?

Is the indoor fan wire winding protection thermostat (49FI) off?

Replace the indoor fan.

Correct the connection

Replace the indoor unit PCB.

Page 181: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 15SM830080

10) Symptom: LCD on the remote controller displays “CHECK P02”. (Compressor /outdoor fan protection thermostat operation warning / power supplyvoltage abnormality)

Yes

Yes

No

Yes

No

No

0342_M_I

Start

Is the outdoor fan wire winding protection thermostat (49FO) off?

Replace the outdoor fan.

Is there connector contact defect?

Replace the outdoor unit PCB.

Correct the connection

Yes

No

No

No

Replace the outdoor unit PCB. Is there 220-240 V AC between CN19-9 and CN19-1 on the outdoor unit PCB?

YesReplace the outdoor unit PCB. Is the high voltage switch

(63 PH) off?

YesReplace the fuse. Is the fuse on the outdoor unit

PCB blown (F1 and F2)?

Is the compressor protection thermostat (49C) off except 48 type?

• No refrigerant• High load• 4-way valve defect• Clogged refrigerant circuit• Electronic refrigerant control valve defect (indoor unit)

Yes

No Check the power breaker etc. and repair.

Is the power supply to the outdoor unit normal? (Voltage / defective phase?)

Page 182: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 16SM830080

11) Symptoms: LCD on the remote controller displays “CHECK P03”.(Alarm for unusual discharge temp. of compressor)

12) Symptom: LCD on the remote controller displays “CHECK P04”. (High-pressureswitch activation warning)

0343_M_I

Start

Unusual discharge gas temperature

• Refrigerant shortage• Clogged refrigerant circuit• Electronic refrigerant control

valve defect (indoor unit)

No Yes

NoYes

0344_M_I

Start

Are there connection defects in the wiring?

High-pressure switch defect

Repair the wiring.The system does not operate again.

High-pressure switch activation

(Both cooling and heating)• Electronic refrigerant control valve

defect • Refrigerant over-charged

(Cooling)• Outdoor unit, heat exchanger dirty,

clogged• Outdoor unit air short• Outdoor fan stopped

(Heating)• Outdoor unit air short• Indoor unit, heat exchanger dirty,

clogged• Large pipe side service valve

closed• Indoor fan stop• Air filter clogged

Page 183: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 17SM830080

13) Symptom: LCD on the remote controller displays “CHECK P05”. (Negative phasedetection operation warning)

Yes

No

No

No

Yes

Yes

0345_M_I

Start

Check the power breaker etc. and repair

No problem

Correct the connection

Replace the outdoor PCB

Is the power supply to the outdoor unit normal?(Voltage defective phase?)

Does the outdoor unit operate whentwo of the three phases are changed?(Actuation of negative phase protector)

Is there a contact defect in the 3P connector?

No

YesReplace the fuse.Is the fuse (F1, F2) on the indoor

unit PCB blown?

14) Symptom: LCD on the remote controller displays “CHECK E15”.

No

No

No

Yes

Yes

Yes

0646_M_S

Start

Repair the wiring.

Select an indoor unit which matches with the outdoor capacity.

Check the contact.

Perform the same as “CHECK E04”.

When the group of the units are installed, is there any mis-cross between interunit control wiring and refrigerant tubing?

Are the total capacities of indoor units to that of outdoor units less than 93%?

Are there no contact failure betweenoutdoor and indoor units?

Page 184: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 18SM830080

15) Symptom: LCD on the remote controller displays “CHECK E16”.

No

No

No

Yes

Yes

0647_M_S

Start

Repair the wiring.When the group of the units are installed, is there any mis-cross between inter unit control wiring and refrigerant tubing?

Confirm less than 5 indoor units are connected.

Select indoor units which match with the outdoor capacity.

Are the total capacities of indoor units to that of outdoor units more than 107%?

16) “Check P9” is displayed on the remote control unit.

Yes

Yes

0649_M_S

Start

Connect firmly.Is 15P connector socket (RED)being attached to panel connected firmly with 15P plug?

Replace P.C.B. Ass’y in the indoor unit.

Page 185: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 19SM830080

17) Symptom: LCD on the remote controller displays “CHECK H01, H02, H03”. (PCcompressor current detection)

* Please check the related part described in the following chart after confirming thecode setting (S4) of the outdoor unit’s capacity on the PCB in the outdoor unit.

18) Check the indoor unit (When the alarm of communication failure is not activated)¶ If the electronic control valve failure occurred in Flexible Combination system

(simultaneous operation system), one indoor unit would not be operated normally,then the other units won’t be operated either. Due to this, try to detect the troubledunit and correct it.

Normal

No

Failure in the electroniccontrol valve activation.

No

Replace the sensor.

Operate the unit incooling mode.(30 minutes after its operation)

• Cooled air comes out.• Is the temperature of each indoor coil sensor almost the same? (Refer to the sensor temperature display function of the remote controller.)

• Does each indoor coil sensor detect the temperature correctly? (Is there any leakage from the pipe of the temperature detection section?)

Yes

Yes

0460_M_I

0346_M_I

“CHECK H02” display

Compressor lock detection

• Insufficient voltage• Comp. motor magnetic contactor defect• Refrigerant over-charged

Start

Compressor lock

“CHECK H01” display

Compressor overload detection

• L3 phase wire disconnected• Comp. motor magnetic contactor defect• Outdoor unit PCB defect

“CHECK H03” display

Compressor current detection circuit defect

Page 186: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 20SM830080

(6) Procedures When a Specific Component Does Not Work

1) Indoor fan does not operate.

3) Flap does not operate, when you press FAN AIM button. (When you press SWEEPbutton, flap operates.)

2) Flaps in indoor unit’s air outlet does not operate, when you press SWEEP button.

No

Yes

Is fan motor capacitornormal ?

Is there voltage outputof P.C.B. Ass'y for fanmotor ?

• Check resistance of fan motor winding.

Replace the fan motor.

Replace the capacitor.

Replace the P.C.B. Ass'yin the indoor unit.

No

Yes

Out

0650_M_S

Is 15P connector socket (RED)attached to panelconnected firmly with 15P plug ?

No

Yes

Replace P.C.B. Ass'y in theindoor unit.

Yes

NoReplace the motor.

Connect firmly.

Check the louver motor resistance.Is auto louver motor normal?

0651_M_S

Is 15P connector socket (RED)attached to panelconnected firmly with 15P plug ?

No

Yes

Replace P.C.B. Ass'y in theindoor unit.

Yes

NoReplace the switch.

Connect firmly.

Does limit switch actuate?

0652_M_S

Page 187: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 21SM830080

4) Compressor motor does not operate.

5) Outdoor fan does not operate.

No

Yes

No

Yes

Is fan motor capacitor normal ?

NoIs there voltage output of

P.C.B. Ass’y for fan motor ?

Yes

Check resistance of fan motor

winding.

NG

Replace the fan motor.

Replace the relays.

Replace the capacitor.

Replace P.C.B. Ass’y

in the outdoor unit.

Are auxiliary relays (1Y, 2Y)

normal ?

0462_M_I

No

Yes

Does compressor motor magnetic

contactor (52C) actuate ?

Replace the compressor

motor magnetic contactor.

Check resistance of compressor

motor winding.

Replace the compressor.

NG

0461_M_I

Page 188: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 22SM830080

(7) Service Functions of Remote ControllerFrom the remote controller you can control both the operation and settings of the unit aswell as perform several useful service checks. This section explains how to use theremote controller on the following items from (A) to (J).

(A) Set service check switches.

(B) Use the test run procedure.

(C) Check the sensor temperature readings.

(D) Find out about past service problems.

(E) Check the remote controller itself for correct operation.

(F) Excute the auto. address operation.

(G) Confirm and change the indoor unit address.

(H) Change the shift temperature in heating mode

( I ) Set the indoor unit address.

(J) Change the period of the filter timer

(A) Set service check switches

The service check switch (RCU.CK) is located on the back of the remote controller’sP.C.B. Ass’y as follows :

The followings are the correct switch settings for ordinary use of the unit. Only change thesettings temporarily for making service checks. When you finish the settings, be sure toreturn them to the standard settings shown here.

RCU.CK switch - Refer to section (E) “ Checking the remote controller forcorrect operation ”(Remote Control Unit, Check)

RCU.ADR switch - Keep the switch OFF all the time except in case of sub remotecontroller(Remote Control Unit, Address)

ON

OF

F

RC

U. A

DR

switc

h

ON

OF

FR

CU

. CK

switc

h

0354_M_I

Page 189: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 23SM830080

(B) Use the test run procedure

The purpose of the test run function is to let you control the operation of the unitdirectly without turning the unit on or off by thermostat. As indicated in the followingprocedure, be sure to stop test run operation when you finish the procedure, or theair conditioner may be damaged.

To protect the air conditioner from overloading, the outdoor unit will not startrunning for 3 minutes after power is applied or the unit is turned OFF.

a Press the TEST / CHK button atthe bottom right on the remotecontroller.

b Press the ON / OFF operationbutton to start the test run.

c Press the MODE button to selecteither COOLING or HEATINGmode.

d When the test run starts, “TEST”shows on the remote controller’sdisplay.

e During the test run, the airconditioner runs continuouslyand the thermostat does notcontrol the system.

f After the test run, be sure topress theTEST / CHK button once againto finish this mode and makesure “TEST” is not shown on thedisplay.

The TEST RUN button is used only for servicing the air conditioner. Do not press thisbutton in normal operation, or the system may be damaged.

CAUTION

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

TEST

°CTIMER SET

A

TEST / CHK

Alarm message

TEST RUN / CHECK button

ON / OFF operationbutton

1152_THS_I

Page 190: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 24SM830080

(C) Check the sensor temperature readings

The air conditioner has thermo sensors which are used to control the unit.

Each sensor has an address which is made up of the indoor unit address, and thesensor address. The indoor unit address is used only when several units arehooked up to one remote controller (group control). If there is only one unit, madeup of one indoor and one outdoor unit, then only the sensor address should be putin, as shown in the procedure below.

Follow this procedure to display the temperature of each sensor:

a On the remote controller, press both TEST / CHK and CL buttons at the same time formore than 4 seconds.

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

UNIT No.

No.CODE

SET TEMP.

°CTIMER SET

AIM

SWEEP

A

SETTING

TEST / CHK

0356_M_I

b The UNIT No., the address and temperature of the sensors instead of its usualinformation will flash on the display.

Following example shows the UNIT No. (Indoor unit address) is fixed at 01– 01. In case of group control, select the UNIT NO. (Indoor unit address) which you want

to check with UNIT button. Each time you press the , (SET TEMP.) button you can select a different

sensor, and the display shows the sensor address and temperature as shownbelow.

0357_M_I

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

UNIT No.

No.CODE

TIMER SET

DATA

MONITOR

SETTING

TEST / CHK

UNIT No. (Indoor unit address)

Sensor address

Sensor temperature °C

NOTE

Do not press TIMER SET button during the procedure.

Page 191: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 25SM830080

Refer to the table below for the relationship between the sensor address and the locationof the sensor.

In case there are no sensor equipped with the unit, “- - -” is shown on the display.

C Resetting the remote controller display to previous mode.

To reset the display, press TEST / CHK button, then the remote controller willreturn to previous mode.

(D) Find out about past service problems

The remote controller can memorize the max. 4 most recent alarm messages , so youcan see problems the unit has had, if any. Knowing what has already occurred and beenfixed helps you to know what to check at present.

This function is usable even if the unit is not working.

To display the past error codes, follow the procedure below.

Procedure:

a On the remote controller, press both TEST / CHK and SET buttons at the same timefor more than 4 seconds.

b Once in this mode, display changes from the normal display to service check displayas shown in the table below:

(È)NORMAL DISPLAYDisplay Change

SERVICE CHECK DISPLAY

Set temp. È Code No.

UNIT No. È UNIT No. (Indoor unit address)

Hours, Minutes È Alarm Message

NOTE

Location of Sensor (Themistor): ˚C

Relationship between the sensor address and the location of sensor

Sensor Address(CODE No.)

Indoor Unit 01 —02 TH1 Indoor air suction Temp.03 TH2 Indoor coil Temp. (E1)04 TH3 Indoor coil Temp. (E2)05 TH4 Indoor coil Temp. (E3)06 TH5 Indoor discharge air Temp.*07 —08 —09 —

Outdoor Unit 0A TH8 Discharge gas Temp. A0B —0C —0D TH7 Outdoor coil liquid Temp. (C2)0E TH6 Outdoor coil liquid Temp. (C1)0F —10 —11 —12 —13 —14 —

* Only for unit which has a discharge air temp. sensor (U or D type)

Page 192: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 26SM830080

This picture shows the service check display.

For example, if the last four alarm messages were, in order of occurrence from oldest tomost recent, P01, P02, P04, and most recently E01, then the display will be shown asbelow when you press button four times. The 5th time you press button you canrepeat the display, then the first message will be shown again.

c. A maximum of 4 alarm messages can be accessed by pressing either SET TEMPbutton or as follows.

SERVICE

R.C. No.

CHECK

UNIT No.

No.CODE

0358_M_I

CODE No.

No.

UNIT No.1–1

Alarm message

RefrigerantCircuit No.

0359_M_I

Present

Past

Present

Past

MODE

FAN SPEED

SET TEMP.

NOTE Pressing CL (Clear) button will clear all the service history.

... accessed in order of “Past È Present”.

... accessed in order of “Present È Past”.

0360_M_I

SERVICE

R.C. No.

CHECK

UNIT No.

No.CODE

SERVICE

R.C. No.

CHECK

UNIT No.

No.CODE

SERVICE

R.C. No.

CHECK

UNIT No.

No.CODE

SERVICE

R.C. No.

CHECK

UNIT No.

No.CODE

SERVICE

R.C. No.

CHECK

UNIT No.

No.CODE

If there are no alarm messages, the display shows:

Alarm message

1 2 3 4

Page 193: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 27SM830080

Never press CL (clear) button unless you want to erase the accessed data in memory.Follow the procedure below only when erasing is necessary.

To erase accessed data, press the CL button.

When erasing is finished,“----” mark appears on the controller’s display.

After checking the alarm messages, be sure to press the TEST / CHK button.

(E) Check the remote controller itself for correct operation

The remote controller has a self-diagnostic function to check if it works properly. Use thisprocedure to find out if the remote controller itself is in trouble.

a Turn ON the RCU.CK switch on the back of the P.C.B. Ass’y in the remote controller.See section (A) for exact location.

b The appearance of the display will tell you whether or not the remote controller isworking correctly or not.

Normal condition – All displays appear for 10 seconds, then disappear.

Unusual condition – All displays flash ON and OFF for 10 seconds, thendisappear.

After checking the panel, be sure to set the RCU.CK switch to this original OFFposition.

Important

CAUTION

CAUTION

Page 194: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 28SM830080

(F) Execute the auto. address operation

Auto. address operation is executed by pressing the A. ADD (S1) button of outdoorunit’s PCB usually.For your convenience it can be executed by remote controller also.

a Press the TEST / CHK and ( ) buttons at the same time for more than 4seconds.

b Set CODE No. A1 with , (SET TEMP) button.

c Select R.C. No. which you want to execute the auto. address operation with UNITbutton.

d Press the SET button. The auto. address operation will start. CODE No. changes fromflashing to ON state.

e If an error occurs during operation, the alarm message will be displayed. Check andremove the cause. If you want to stop the operation, press the CL button then the unitstands in waiting mode (Press the SET button again.)

f If the automatic address operation finishes, the display will disappear.

g Execute the operation of the other R.C. line in the same way by following the abovesteps c to d .

h Complete the automatic address operation by pressing the TEST / CHK button.

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C.

No.CODE

TIMER SET

SETTING

TEST / CHK

0361_M_I

In this mode, the auto. addressoperation is executed at each R.C.(Refrigerant Circuit) line one by one.

Page 195: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 29SM830080

(G) Confirm and change the indoor unit address

The purpose of the above function is to let you confirm the indoor unit addressafter the auto. address operation, and change the indoor unit address if it isneeded.

a Press the TEST / CHK and ( ) buttons at the same time for more than 4seconds.

b Select the R.C. No. which you want to change with the UNIT (up) orFLAP (down) buttons.

c Press the SET button (to confirm the R.C. No.).The smallest registered indoor No. and the selected R.C. No. will bedisplayed. Ex:

R.C. No. 3 is selected.Indoor No. 2 is the smallest indoor No. ofthe R.C. No. 3.

d Select the indoor No. which you want to change with UNIT button. Once in this mode,the fan motor of selected indoor unit will turn on and let you confirm the indoorunit address.

0362_M_I

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C.

No.CODE

TIMER SET

SETTING

TEST / CHK

SET DATA

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

TIMER SET

DATA

SETTING

TEST / CHK

0363_M_I

Page 196: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 30SM830080

e Set the required new indoor unit’s No. by pressing the , ( ) button.

f Press the SET button.UNIT No, SET DATA (0008) and SETTING changes from flashing to ON state.

g If you made a mistake, press the CL button.

h Finally, press the TEST / CHK button.

i If you want to change the indoor unit address of the other R.C. No., follow the step ato h in the same way.

* In this case, UNIT No. 3 – 6 (current)≠

3 – 8 (NEW : after pressing theTEST / CHK button)

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

No.CODE

TIMER SET

DATA

SETTING

TEST / CHK

0364_M_I

Ex: UNIT No. 3-6: currently registered indoor unit address

Required new indoor No.8: SET DATA

Page 197: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 31SM830080

(H) Change the shift temperature in heating mode

If the indoor unit is installed at high location (ex. ceiling level), the thermostat tends to turnoff at heating mode because of the hot air temperature around ceiling level. In order to solvethe problem, the shift temp. (valid while heating only) is set when shipped from factory.

If the shift temp. is not enough (ex. the indoor unit is installed at position higher than 3 m),the shift temp. can be set with remote controller from +1 to +10 deg. manually as follows:

a Press the TEST / CHK button for more than 4 seconds.

b In case of group control, if you want to change all units in group control collectively,proceed next step remaining ALL displayed.If you want to change a unit individually, select the indoor unit address (UNIT No.) withUNIT button.

c Select the CODE No. 06 with , (SET TEMP) button.

d Choose the shift temp with , ( ) button.

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

TIMER SET

DATA

SETTING

TEST / CHK

0365_M_I

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

SET TEMP.

TIMER SET

DATA

SETTING

TEST / CHK

0366_M_I

e Press the SET button.CODE No. 06, SET DATA and SETTING change from flashing to ON state.

f If you made a mistake, press the CL button.

g Finally, press the TEST / CHK button.

EX:UNIT No. 1–6CODE No. 06Shift temp. +5 deg

Page 198: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 32SM830080

( I ) Set the indoor unit address

This function is usable if the auto. address operation is not available.Indoor unit address can be set one by one by remote controller.

1) In case of group control, branch wiring for group control should be removedtemporarily.

2) In case of remote controllerless system, remote controller should be connectedwith the indoor unit temporarily.

a Short the two terminals of DISP PIN on indoor unit PCB.(DISP PIN : Refer to P. VI–2)

b Press the TEST / CHK , SET and CL buttons at the same time for more than 4seconds.

c Set the CODE No. 12 to set the No. of R. C. with the , (SET TEMP) button.

NOTE

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

TIMER SET

DATA

SETTING

TEST / CHK

0367_M_I

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

TIMER SET

DATA

SETTING

TEST / CHK

0368_M_I

Page 199: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 33SM830080

d Set the No. of R. C. which you want to set with , ( ) button.

e Press the SET button.UNIT No., CODE No. 12, SETTING and SET DATA (0002) change from flashing to ON state.

f Select the CODE No. 13 to set the indoor unit No. with the , (SET TEMP) button.

g Set the indoor unit No. which you want to set with the , ( ) button.

Ex. Indoor unit No. 4 will be set.In this example, indoor unit address(UNIT No.) will be set 2–4.

Ex. No. of R. C. will be set 2.

h Press the SET button.UNIT No., CODE No. 13, SETTING and SET DATA (0004) change from flashing to ONstate.

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

TIMER SET

DATA

SETTING

TEST / CHK

0369_M_I

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

TIMER SET

DATA

SETTING

TEST / CHK

0370_M_I

Page 200: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 34SM830080

i Select the code No. 14 to set group setting with the , (SET TEMP) button.

j Set the No. of group setting as shown below with the , ( ) button.

Nos. of group setting.0 : Standard system (except group

control)1 : Main indoor unit in case of group

control2 : Sub indoor unit in case of group

control99: No setting (at factory shipment)

k Press the SET button.UNIT No., CODE No. 14, SETTING and SET DATA change from flashing to ON state.

l If you made a mistake, press the CL button so that setting returns to the initial state.

m Press the TEST / CHK button to finish this mode.The display is disappeared.

n Confirm the indoor unit address (UNIT No.) with the UNIT button after pressing the ON/ OFF button.

o Finally, remove the short circuit of DISP PIN.And in case of group control, be sure to restore the branch wiring to its original wiring.In case of remote controller–less system, remove the remote controller.

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

TIMER SET

DATA

SETTING

TEST / CHK

0371_M_I

Page 201: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 35SM830080

(J) Change the period of the filter timer

If the period of filter timer is not suitable (for example in case of dirty environment),the period can be shortened to half as follows:

a Press the TEST / CHK button for more than 4 seconds.

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

TIMER SET

DATA

SETTING

TEST / CHK

0213_M_I

b In case of group control, if you want to change all units in group control collectively,proceed next step remaining “ALL” displayed.If you want to change a unit individually, select the indoor unit address (UNIT No.) withUNIT button.

c Select the CODE No. 02 with , (SET TEMP) button.

d Change the No. from 0 to 1 with , ( ) button.

e Press the SET button.CODE No. 06, SET DATA and SETTING change from flashing to ON state.

f If you made a mistake, press the CL button.

g Finally, press the TEST / CHK button.

SET CL

MODE

FAN SPEED

ONOFF

••

SET TEMP.

UNIT

FLAP

AIR FLOW

R.C. No.

SET

UNIT No.

No.CODE

SET TEMP.

TIMER SET

DATA

SETTING

TEST / CHK

0214_M_I

EX:UNIT No. 1–6CODE No. 02T type 150 hr → 75 hr

Page 202: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 36SM830080

4-2 Checking the Electrical Components

(1) Measurement of InsulationResistance

• The insulation is in good condition if theresistance exceeds 1 MΩ.

1 Power Supply Wires

Clamp the earthed wire of the Power Supplywires with a lead clip of the insulation resis-tance tester and measure the resistance byplacing a probe on either of the power wires.(Fig. 25 )

Then measure the resistance between the earthedwire and the other power wire. (Fig. 25)

2 Indoor Unit

Clamp an aluminum plate fin or copper tubewith the lead clip of the insulation resistancetester and measure the resistance by placinga probe on high voltage terminal on theterminal plate (Fig. 26 )

See Fig. 22 .

3 Outdoor Unit (SPW-CR253 EHL5)

Clamp a metallic part of the unit with the leadclip of the insulation resistance tester andmeasure the resistance by placing a probe on1 and then 2 on the 8 or 6P terminal plate.(Fig. 26 )

See Fig. 22 .

3 Outdoor Unit (SPW-CR253 EHL8,SPW-CR363GHL8, SPW-CR483EHL8)

Clamp a metallic part of the unit with the leadclip of the insulation resistance tester andmeasure the resistance by placing a probe on5 and then 6, and then 7 on the 8P terminalplate. (Fig. 26 )

See Fig. 23 .

Fig. 25

Fig. 26

Coppertube ormetallic part

Clip

Insulationtester

Probe

Terminal plate

0639_X_S

Earthed wire

Clip

Probe

Insulationtester

0638_X_S

Page 203: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 37SM830080

(2) Measurement of InsulationResistance for Electrical parts

• Disconnect the connector of the desiredelectric part from terminal plate, P.C.B.Ass’y, etc. (Fig. 27 )

• Similary, disconnect the lead wires fromcompressor, capacitor, etc. (Fig. 28 )

• Measure the resistance in the samemanner as illustrated on the right.

Refer to Electrical Wiring Diagram.

NOTEIf the probe does not enter the hole becausethe hole is too narrow, use a probe with athinner pin.

Fig. 27

Coppertube ormetallic part

Clip

Insulationtester

Probe

0640_X_S

Fig. 28

From fan motor,compressor and otherparts.

Clip

Probe

Insulationtester

Metallicpart

0641_X_S

Page 204: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 38SM830080

(3) Checking the Protective Devices

• Disconnect the connector, which consists of P (plug) and S (socket) whenyou want to check the protective device.

• Then check continuity among plug’s (and/or socket’s) terminal as in Fig. 29 .

• Normality of the protective device can be judged by the following table.The Protective Device is proved normal if there is a continuity betweenterminals.

1 Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit

• Disconnect 9P connector (WHT) which leads to the indoor fan motor (FMI).

• Check the socket’s terminals between No. 8 (GRY lead wire) and No. 9(GRY lead wire).

2 Compressor motor thermal protector (49C) . . . . . . Outdoor unit

• Only for the SPW-C253EH8 and SPW-C363EH8. Disconnect the 8Pconnector (white), and the 9P connector (white) on the P.C. board, andcheck 8P (white) plug’s No. 4 (GRY lead wire) and socket’s No. 9 (GRY leadwire) on the P.C.board.

3 Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit

• Disconnect 8P connector(s) (WHT) which lead(s) to the outdoor fan motor(FMO).

• Check socket’s terminal between No. 3 (GRY lead wire) and No.4 (GRY leadwire).

4 High pressure switch (63PH) . . . . . . Outdoor unit

• Disconnect the socket (63PH) of 3P (red) connecting to the P.C. board, andcheck both sides (1 (white), 3 (red)).

Fig. 29

Ω

socket

Multimeter

0642_X_S

Page 205: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 39SM830080

(4) Checking the Electrical Parts

1 Power transformer (TR1) ................. Indoor unit *Measure the coil resistance.

• Primary ; Measure the resistance between No.1 and No.3(WHT lead wires) terminals of 3P (WHT) socketconnected to power transformer.

• Secondary 14V ; Measure the resistance between No.1 and No.2(RED lead wires).

10V ; Measure the resistance between No.3 and No.4(BRN lead wires).

Refer to “1-3 Other component specifications”.

2 Power transformer (TR) ............ Outdoor unit *Measure the coil resistance.

• Primary ; Measure the resistance between No.1 and No.3(WHT lead wires) terminals of 3P(WHT) socket jointedto power transformer.

• Secondary 14 V ; Measure the resistance between No.1 and No.2(BRN lead wires).

Refer to “1-3 Other component specifications”.

3 Indoor fan motor (FMI) ............... Indoor unit *Measure the coil resistance.

• Measure the resistance between each terminal of 9P (WHT) socketconnected to the indoor fan motor.

Refer to “1–2–(A) Major component specifications”.

4 Outdoor fan motor (FMO) ........... Outdoor unit *Measure the coil resistance.

• Measure the resistance in the same manner as explained above 3.

Refer to “1–2–(B)Major component specifications”.

5 Fan motor capacitor ............ Both in indoor and outdoor unit• Remove the lead wires from the capacitor terminals,

and then place a probe on the capacitor terminals asshown in Fig. 30 . Observe the deflection of the pointer,setting the resistance measuring range of the multimeterto the maximum value.

• The capacitor is “good” if the pointer bounces to a greatextent and then gradually returns to its original position.

NOTEThe range of deflection and the deflection time differaccording to the capacity of the capacitor.

Fig. 30

Multimeter

Fan motorCapacitor

0643_X_S

Page 206: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 40SM830080

6 Solenoid coil of the electronic refrigerant *Measure the coil resistance.

control valve (ERCV) ………… Indoor unit

• Measure the resistance between No. 5 (GRY lead wire) and other terminals(another color of lead wires) of 5P (WHT) plug connected to the solenoid coil.

Refer to “1-2-(A) Major component specifications”.

7 Compressor motor (CM) ……… Outdoor unit *Measure the coil resistance.

• In case of triple -phase compressor

Measure the resistance between “R” (RED lead wire) and “S” (WHT leadwire) terminals, “R” and “T” (BLU lead wire) terminals and “S” and “T”terminals on the compressor motor magnetic contactor.

• In case of single -phase compressor

Remove the cover of compressor terminal and measure the resistancebetween terminals.

Refer to “1-2 Major component specifications”.

8 Compressor motor magnetic contactor (52C) ………… Outdoor unit

MODEL

Push button onthe magneticcontactor

no press

press

• Measure the resistance between A (ORG lead wire) and B (GRY lead wire)terminals on the compressor motor magnetic contactor.

Refer to “1-3 Other component specifications”.

• Check the continuity between contactors.

9 Solenoid coil of 4-way valve (20S) … Outdoor unit

*Measure the coil resistance.

• Measure the resistance between No.1 (BLU lead wire) and No.2 (BLU leadwire) terminals of 2P (YEL) socket connected to the solenoid coil.

Refer “1-3 Other component specifications”.

FMCA–1S / FC–1SZ607

Pair of terminals

R – U S – V T – W 31 – 32

–––– –––– –––– YES

YES YES YES ––––

Page 207: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 41SM830080

0 Fuse on indoor and outdoor P.C.B. Ass’y …. Both in indoor and outdoor unit*Check the continuity.

• Remove the P.C.B. Ass’y from the electrical component box. Then pull outthe fuse from the P.C.B. Ass’y. (Fig. 31 )

• Then check the continuity of the fuse by using the multimeter. (Fig. 32 )

Fig. 32

Fuses

Indoor P.C.B. Ass’y0644_X_S

Fuses

Outdoor P.C.B. Ass’y0653_X_S

Fig. 31

Fuse

0645_X_S

Page 208: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 42SM830080

(5) Sensor and Solenoid Layout Diagram

Indoor Unit• SPW-XR253GH56

TH3 (E2), (BLK)

TH2 (E1), (RED)

Electronic expansion valve

TH4 (E3), (BRN)

1251_X_I

TH2 (E1), (RED)

TH3 (E2), (BLK)

Electronic expansion valve

TH4 (E3), (BRN)1250_X_I

• SPW-XR363GH56• SPW-XR483GH56

Page 209: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 43SM830080

• SPW-TR363GH56, SPW-TR483GH56

TH3 (E2), (BLK)

TH4 (E3), (BRN)

1219_THS_I

TH2 (E1), (RED)

Electronic expansion valve

TH4 (E3), (BRN)

TH3 (E2), (BLK)

1218_THS_I

TH2 (E1), (RED)

Electronic expansion valve

Indoor Unit• SPW-TR253GH56

Page 210: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 44SM830080

Heat exch

TH5 (Discharge Air)

1264_C_I

TH3 (E2), (BLK)

TH2 (E1), (RED)

Electronic expansion valve

TH4 (E3), (BRN)

1257_U_I

TH3 (E2), (BLK)

TH2 (E1), (RED)

Electronic expansion valve

TH4 (E3), (BRN)

1258_U_I

Indoor Unit• SPW-DR253GH56 • SPW-DR363GH56

• SPW-DR483GH56

• SPW-UR253GHN56 • SPW-UR363GHN56• SPW-UR483GHN56

TH3 (E2), (BLK)

TH2 (E1), (RED)

Electronic expansion valve

TH4 (E3), (BRN)

1255_D_I

TH3 (E2), (BLK)

TH2 (E1), (RED)

Electronic expansion valve

TH4 (E3), (BRN)

1256_D_I

TH5 (GRN), (Discharge Air)

Fan motor

Fan

1263_C_I

Page 211: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 45SM830080

• SPW-CR363EHL8

0585_C_S

TH6 (C1), (BLK)

TH7 (C2), (RED)

TH6, 7, 8

CM

CH

TH8 (GRN)( Discharge gas)

63PH

20S

0584_C_S

0583_C_S

TH6 (C1), (BLK)

20S TH7 (C2), (RED)

TH6, 7, 820S, 63PH

CM

CH

TH8 (GRN)( Discharge gas)

0582_C_S

Outdoor Units• SPW-CR253EHL5, SPW-CR253EHL8

Page 212: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 46SM830080

0585_C_S

TH6 (C1), (BLK)

TH7 (C2), (RED)

TH6, 7, 8

CM

CH

TH8 (GRN)( Discharge gas)

63PH

20S

0586_C_S

Outdoor Units• SPW-CR483EHL8

Page 213: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 47SM830080

(1) Room temp. sensor : TH1 (KTEC-35)TH5 (KTEC-35)

(2) Indoor heat exch.coil sensor : TH2(E1), TH3(E2),

TH4(E3)Outdoor heatexch. coil sensor : TH6(C1), TH7(C2)

(3) Compressor discharge gas temp. sensor : TH8 (PTC-51H)

( PBC-41E) ( PB3M-41E)

Res

ista

nce

(kn

)

10 15 20 25 30 35 40

10

9

8

7

6

5

4

3

2

1

Temperature (°C)0374_M_I

–20 –15 –10 –5 0 5 10 15 200

5

10

15

20

25

30

35

40

Temperature (°C)

Res

ista

nce

(kn

)

0375_M_I

80 90 100 110 120 130

1

2

3

4

5

6

7

Temperature (°C)

Res

ista

nce

(kn

)

0376_M_I

(6) Thermistor Characteristic Curve

Page 214: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 48SM830080

(7) P.C.B. Setting

Setting of outdoor control PCB

(A) Standard control (single outdoor unit)In case of single outdoor unit installation, even if in case of twin, triple or quartet type(2, 3 or 4 indoor units), no setting necessary.Keep factory shipment state (R.C. address is set in “0”).

In this case, auto. address operation takes place automatically for the first time whenthe power is switched on. This takes about a few minutes.

(B) Group control (Multiple outdoor units)In case of group control (up to 8 indoor units can be connected with one remote con-troller), before turning the power supply on set the R.C. address with S2, S3 on theoutdoor control PCB.

R.C. address: Refrigerant circuit address 1 ~ 30.

Regarding the example of R.C. address for group control, please refer to page 53 andsec. 12-3 (page 87).

(C) Central control (when using the system controller)In case of central control (when using the system controller,that is, when linking out-door units in a network),(a) Before turning the power supply on, set the R.C. address with S2, S3 on the

outdoor control PCB.(b) Remove the short plug (CN4, 2P Black) from all outdoor units except any one of

outdoor unit.

Regarding the example of R.C. address for central control and the position of CN4,please refer to page 54 and sec. 12-3(page 87).

Setting of indoor control PCBNo setting necessary.Each indoor unit address (UNIT No.: R.C. – No.) is decided after auto. address operation.

Indoor unit No.Refrigerant Circuit No. (R.C. address)

Manual setting for indoor unit address can be performed also by remote controller.

Page 215: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 49SM830080

(8) R.C. Address Setting Method

Outdoor unit R.C. address setting methodIn case of group control or central control, set the R.C. address to 1, 2, 3, ... according tothe No. of outdoor units.

R.C. addressR.C. address R.C. address

(S3 2P dip switch, green) (S2 Rotary switch, Black)

00 auto addressBoth OFF Set to 0

02 (In case of No. 2 outdoor unit) Both OFF Set to 2

03 (In case of No. 3 outdoor unit) Both OFF Set to 3

11 (In case of No. 11 outdoor unit) 10’s digit ON Set to 1

21 (In case of No. 21 outdoor unit) 20’s digit ON Set to 1

30 (In case of No. 30 outdoor unit) 20’s digit ON Set to 0

(“0” when shipped from factory)

1

ON

10 position

20 position

ON side

: S2

: S3

OFF side

Refrigerant circuit address (2P DIP switch, green or Blue)

Refrigerant circuit address (black)

Refrigerant circuit address (factory setting = 0)

Outdoor control PCB

1576_C_I2

0

A. ADD (S1):Automatic address setting start buttonUsed for central control (link system) and group control (Normally, not used)

CN4 (2P Black)

1

ON ON side

OFF side2

1

ON ON side

OFF side2

1

ON ON side

OFF side2

1

ON ON side

OFF side2

1

ON ON side

OFF side2

1

ON ON side

OFF side2

10’s digit and

0

0

1

1

32

Page 216: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 50SM830080

(9) Automatic Address Setting Method

— For group control and central control withmultiple outdoor units —

Carry out automatic address setting withthe remote controller.(1) All auto. address operation

1 Press the TEST / CHK and ( )buttons at the same time for morethan 4 seconds.

2 Press the SET button after confirm-ing the CODE No. AA (CODE No.AA: All Auto. address operation).

After addresses are automatically setin order for the outdoor units fromNo. 1 to No. 30, the system returnsto the normal stopped state.

(2) Individual auto. address operation foreach refrigerant circuit1 To select each refrigerant circuit

individually and set addresses auto-matically, press the TEST / CHK and

( ) buttons at the same time formore than 4 seconds, then press the

, (SET TEMP) button once toset CODE No. A1.(CODE No. A1: Auto. address opera-tion)

2 Select R.C. No. which you want toexecute the auto. address operationwith UNIT button.

3 Press the SET button. The auto.address operation will start. CODENo. changes from flashing to ONstate.

4 If the error is happened during theoperation, the alarm message willdisplay. Check and remove thecause. If you want to interrupt theoperation, press the CL button thenthe unit stands in waiting mode(Press the SET button).

5 If the auto. address operation fin-ishes, the display will disappear.

6 Execute the operation of the otherR.C. line in the same way by follow-ing the above steps 2 to 3.

7 Complete the auto. address op-eration by pressing the TEST /CHK button.

Required time for auto. address operation:In case of group control : a few minutes

for each R.C.In case of central control : max. about 20

min. for eachR.C.

NOTE

(10) Displaying Indoor / Outdoor UnitCombination Numbers

Display the indoor / outdoor unit addressafter automatic address setting.(1) When installing multiple units, match

the indoor unit address numbers andthe outdoor R.C. address numbersand display them at an easy-to-checklocation (near the nameplate) with anoil-based magic marker or other indel-ible marker so that the individualindoor and outdoor unit combinationscan be checked.

Example:Outdoor Unit 1 – Indoor Units 1-1, 1-

2, 1-3, ....Outdoor Unit 2 – Indoor Units 2-1, 2-

2, 2-3, ....

(2) This is necessary for maintenance.Always label these.*Check indoor unit address with theremote controller. Press the TEST /CHK button for at least 4 seconds andcheck the indoor unit address with theUNIT button. (Each time you pressthe UNIT button, the address changes1-1, 1-2, ... 2-1, 2-2, ...) The fan foronly the selected indoor unit turns onat high speed, so check which indoorunit runs and label the indoor unitaddress.(If there is 1 outdoor unit, the ad-dresses are 1-1, 1-2, ...)

When you press the TEST / CHKbutton again, the system returns tonormal remote control mode.

Page 217: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

2

3

4

5

IV - 51SM830080

(11) Items to Check Prior to Test Run

(1) Turn on the power supply switch more than 5 hours before in order to charge the crankcase heater.

(2) Fully open the outdoor service valve after making the leak inspection of field connectedtubing, vacuuming, and gas charging if necessary.

(3) Check the capacity code and model code setting.* The factory setting is as shown in the table. Double check it.* The capacity code is set by S4 (green, 4P DIP switch) on outdoor control PCB.The model code is set by S5 (black, 2P DIP switch) on outdoor control PCB.

1

ON ON side

1577_C_I

OFF side

S4 (green or Blue) capacity code(4P DIP switch)

2 3 4

1

ON ON side

OFF side

S5 (black) model code(2P DIP switch)

2

S5. Model code• R407 Models: SPW-CR type

No. Outdoor PCBModel No. 1 2 3 425 type (1 phase) ON ON ON OFF25 type (3 phase) ON ON ON OFF36 type (3 phase) OFF ON OFF ON48 type (3 phase) OFF OFF ON ON

No. Outdoor PCBModel No. 1 2SPW-CR253EHL5 OFF ONSPW-CR253EHL8 OFF OFFSPW-CR363EHL8 OFF OFFSPW-CR483EHL8 OFF OFF

S4. Capacity code

No. Outdoor PCBModel No. 1 2SPW-CR253EL5 ON ONSPW-CR253EL8 ON OFFSPW-CR363EL8 ON OFFSPW-CR483EL8 ON OFF

S5. Model code

Page 218: DOCUMENTAÇÃO TÉCNICA AC SANYO

4. Service procedures

1

12

3

4

5

IV - 52SM830080

(12) Test Run Procedure

1) One of CN4 of all linked outdoor units shold be short.

2) In case of using system controller, zone registration is required after finishing Test run.Regarding the zone registration, please refer to Installation Instructions attached withsystem controller.

NOTE

Set the outdoor unit R.C. address.Turn on power supply switch.

Execute auto. address operation with the remote controller.

Press A. ADD (S1) buttonor

Execute auto. address operation with the remote controller.

Press A. ADD (S1) buttonor

CN4: Open (*)Set the outdoor unit R.C. address.Turn on power supply switch.

Go nextR.C. line

Go nextR.C. line

Check according the self-diagnostics function table, and if there is a location to correct, correct it.

Note: Check the indoor side drain water.

Recheck the test items before test operation.

Check the indoor and outdoor unit combination (wiring).

Return the remote controller to normal.

Display the combination number.

Set the remote controller to test operation.

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes Yes

Group control for multiple outdoor

units?

Central control for multiple outdoor

units?

Finish allR.C. line?

Finish allR.C. line?

Single type?(One indoor unit and one remote controller for one

outdoor unit)

No

No Multiple indoor units for one outdoor

units?

Turn on power supply for indoor units side first Then turn on power supply for outdoor unit side.

No

No

Is operation possible?

1579_M_I

Multiple remotecontrol?

Turn on RCU address SWof sub remote control unit

Yes

No

Start

End

Page 219: DOCUMENTAÇÃO TÉCNICA AC SANYO

5. Appendix

1

2

3

4

5

V - 1SM830080

5

5. APPENDIX

5-1 P.C.B. ..................................................................................................... V - 2

Page 220: DOCUMENTAÇÃO TÉCNICA AC SANYO

5. Appendix

1

12

3

4

5

V - 2SM830080

5-1 P.C.B.

Outdoor Unit Control P.C.B. : SPW-CR253EHL8 , SPW-CR363EHL8, SPW-CR483EHL8SPW-CR253EL8 , SPW-CR363EL8 , SPW-CR483EL8

CR

-CR

483GH

L8

JP11

JP8

JP7

JP2

JP1

1554_C_S

CN1 : VCC

CN26 (WHT)

CN27

S2 (BLK) : R.C. Address

LED1 : Message lampLED2 : Message lamp

S3 : R.C. Address

S4 : Capacity code

S5 : Model code

CN11 (YEL) : TEST

CN13 (BLK) : C1 (Used for Heatpump Type only)

CN14 (RED) : C2

CN15 (GRN) : DISCH

S1 : A. ADD

CN10

CN23 (BLK) : 52C

CN52CN53

CN51

CN12 (WHT) : CT1

CN3 (BNR)

CN2 (BLU)

CN4 (BLK)

CN22 (YEL) : 20S(Used for Heatpump

Type only)

CN33

CN32

CN31

CN30

CN54 : N1 CN25 (GRN) : 63PL (Used for 36, 48 Type only)

CN24 (RED) : 63PH

CN20 (WHT) : RS

CN34 (GRN/YEL)

F3 : Fuse 125V / 0.5A

F2 : Fuse 250V / 3.15A

F1 : Fuse 250V / 3.15A

LED POW D13

CN6CN7 (RED) : CHECK

CN8 CK.L

CN9 : CK.H

Page 221: DOCUMENTAÇÃO TÉCNICA AC SANYO

5. Appendix

1

2

3

4

5

V - 3SM830080

5-1 P.C.B.

Outdoor Unit Control P.C.B. : SPW-CR253EHL5, SPW-CR253EL5

CR

-CR

253GH

L5

JP11

JP8

JP7

JP2

JP1

1578_C_S

CN1 : VCC

CN26 (WHT)

CN27

S2 (BLK) : R.C. Address

LED1 : Message lampLED2 : Message lamp

S3 : R.C. Address

S4 : Capacity code

S5 : Model code

CN11 (YEL) : TEST

CN13 (BLK) : C1 (Used for Heatpump Type only)

CN14 (RED) : C2

CN15 (GRN) : DISCH

S1 : A. ADD

CN10

CN23 (BLK) : 52C

CN52CN53

CN51

CN12 (WHT) : CT1

CN3 (BNR)

CN2 (BLU)

CN4 (BLK)

CN22 (YEL) : 20S(Used for Heatpump

Type only)

CN33

CN30

CN54 : N1CN24 (RED) : 63PH

CN20 (WHT) : RS

CN34 (GRN/YEL)

F3 : Fuse 125V / 0.5A

F1 : Fuse 250V / 3.15A

LED POW D13

CN6CN7 (RED) : CHECK

CN8 CK.L

CN9 : CK.H

Page 222: DOCUMENTAÇÃO TÉCNICA AC SANYO

5. Appendix

1

12

3

4

5

V - 4SM830080

When replacing the indoor unit P.C.B. for service, remove the *E2P-ROM of the original P.C.B. then attach itto the new P.C.B. since the original E2P-ROM has it's own data (ex. indoor unit address) to identify the unit.

Note when replacing the indoor unit P.C.B.

5-1 P.C.B.

Indoor Unit Control P.C.B. (CR-X253GH)

1208_THS_I

Shipment state: Pulse signalJumper cut: Static signal

JP1 (Jumper wire): For sellecting the signal of T10.

CN5 (WHT) : FORCED OPR

CN3 (WHT) : TEST PIN

CN2 (WHT) : CHECK PIN

CN1 (WHT) : DISP PIN

CN33 (YEL) : ROOM TEMP

CN31 (RED) : COIL E1

CN32 (BLK) : COIL E2

CN30 (BRN) : COIL E3

CN6 (RED) EXCT: Forced thermostat OFF input terminal

CN71 (YEL) T10: External input and output terminal

CN34 (GRN) : DISCHARGE

CN83 (WHT) : FMI

CN79 (RED) : HU1

CN85 (BLU) : DPH

CN76 (BLK) : OP1

CN78 (BLU) : DP

CN84 (WHT) : RN3

CN81 (GRY) : T20

CN80 (RED) : 26H

D80 (RED): Power lamp

CR-X253GH

CN42 (BLU) : For wireless remote controller

CN43(BLU)

HU

(BLK

)C

N36

T18 (R

ED

)C

N72

CN

10 (YE

L)C

N7

CN

34

CN35 (GRN) : PNL CN41 (BLU) : Wired remote controller

CN9 (RED) : FS

CN8 (WHT) : LS

CN73 (BLK) : RN1

F3 : Fuse 125V / 0.5A

F1 : Fuse 250V / 5A

CN40 (BLU) : OC

CN44 (BRN) : EMG

CN70 (WHT) : T6

CN75 (WHT) : VCC

CN74 (WHT) : RN2

CN77 (GRN) : LM

E2P-ROM

AIR TEMP

Page 223: DOCUMENTAÇÃO TÉCNICA AC SANYO

SANYO Electric Air Conditioning Co., Ltd.Tochigi, Japan

G1100 G 500 Printed in Japan

• The specifications, designs, and information in this brochure are subject to change without notice.