Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L...

36
Effective July 2010 Supersedes IL 33-FHC-3 Dated 04/02 Instruction Leaflet IL 33-FHC-4 Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Transcript of Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L...

Page 1: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Effective July 2010Supersedes IL 33-FHC-3 Dated 04/02Instruction Leaflet IL 33-FHC-4

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Page 2: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

2 EATON CORPORATION www.eaton.com

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

Description

Introduction .......................................................... 5Step 1: General Breaker Preparation .............. 6Step 2: Removing the Original Components

and Preparing the Breaker forRetrofitting ............................................ 7

Step 3: Installing the Sensors and SensorHarness (Partial) ................................... 8

Step 4: Preparing the Aux. CT Assembly ...... 11Step 5: Installing the Breaker

Mounted CPT ...................................... 13Step 6: Installing the Trip Finger .................... 19Step 7: Installing the DTA ............................... 21Step 8: Installing the Aux. CT Module

Assembly and the Trip Unit ............... 24Step 9: Installing the External Harness

and Final Wiring .................................. 27Step 10: Testing the Breaker ............................ 29Step 11: Mounting the Cell Harness ................ 30Step 12: Installing the Retrofitted Breaker

in the Cell ............................................ 30

Figures

1. Overview: Original Components Removedfrom the Breaker and Saved forReinstallation. ................................................ 7

2. Hood Assembly, Arc Chutes, Flash Barrier,Interphase Barriers, and Side Barriers Re-moved from the Breaker. ............................... 7

3. Charging Handle, Face Plate, and FloatingTrim Removed from the Breaker. .................... 8

4. Overview: Sensors Installed in the Breaker. 8

CONTENTS

5. Finger Clusters Removed from the BottomLoad Terminals (Electrically Operated). ......... 8

6. Lower Molding and Load TerminalsRemoved from the Breaker. ........................... 9

7. Sensor and Spacers Installed on a Jumper. .. 9 8. Sensors, Load Terminals, and Lower

Molding Installed on the Breaker. ................ 10 9. Finger Clusters Reinstalled on the Load

Terminals (Electrically Operated). ................ 10

10. Sensor Harness Connected to theSensors. ...................................................... 10

11. Routing of the Sensor Harness. ................... 11

12. Overview: Aux. CT Assembly and PTModule Ready for Installation. ..................... 11

13. Glass Poly Barrier Mounted to theAux. CT Module. .......................................... 11

14. PT Module Mounted to the Aux. CTModule Assembly. ....................................... 12

15. Aux. CT Module Assembly Placedon the Breaker Frame. ................................. 12

16. PT Wires Connected to the Jumper Bolts. .. 12

17. PT Wires Secured to the Sensor Harness. .. 1318. Overview: Breaker Mounted CPT

Installed in the Breaker. ............................... 13

19. Fuse Clips and Spade ConnectorRemoved from the CPT ............................... 13

20. CPT Module Installed on the MountingBracket. ....................................................... 14

21. Drilling Plan “A”. .......................................... 1422. Drilling Plan “B” ........................................... 14

23. Load and Line Sides of the HV Wires. ....... 1424. HV and CPT Wires Connected to the CPT

Module. ....................................................... 15

Digitrip Retrofit Systemfor Federal Pioneer 25 H-2& H-L 50 / 65 H-2 & H-LBreakers

Page 3: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

EATON CORPORATION www.eaton.com 3

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

25. Finger-Safe Covers Installed on the CPTModule. ....................................................... 16

26. Microswitch Mounted to the AuxiliarySwitch Mounting Bracket. .......................... 16

27. CPT Assembly Installed in the Breaker. .... 1628. Auxiliary Switch and CPT Assemblies

Installed in the Breaker. .............................. 16

29. Correct Engagement of the AuxiliarySwitch Arm. ................................................ 17

30. Correct Orientation of the HV WireRing Terminals. ........................................... 17

31. HV Wires Connected to Side SecuredFinger Clusters. .......................................... 18

32. HV Wires Connected to Top SecuredFinger Clusters. .......................................... 18

33. HV Fuses and Wires Secured Away fromMoving Breaker........................................... 18

34. CPT Voltage Labels supplied with theCPT Kit. ....................................................... 19

35. Overview: Trip Finger Installed in theBreaker - Long Trip Shaft. .......................... 19

36. Short Trip Shaft. .......................................... 1937. Trip Finger to be used with a Long Trip

Shaft (Style Number 9A10093G05). ........... 20

38. Trip Finger to be used with a Short TripShaft (Style Number 9A10093G06). ........... 20

39. Original Trip Finger Removed from anElectrically Operated Breaker with ShortTrip Shaft. .................................................... 20

40. Trip Finger Installed on a Long Trip Shaft. . 2041. Trip Finger Installed on a Short Trip Shaft. 2042. Overview: DTA Installed in the Breaker. .... 21

43. Drilling Plan “C”........................................... 2144. Drilling Plan “D” .......................................... 2145. Hardware to Remove from the

DTA Trip Shaft. ........................................... 2146. DTA Mounted to the Bottom Front

Breaker Channel. ........................................ 22

47. Slow Close Handle Engaged in theClosing Link. ............................................... 22

48. Reset “L” Bracket Installed on theDTA Shaft. ................................................... 22

49. Proper Cage Height Adjustment. .............. 2350. Proper Air Gap Adjustment. ....................... 23

51. Routing and Securing of the Originaland New Wiring........................................... 23

52. Overview: Aux. CT Assembly and TripUnit Installed on the Breaker. ..................... 24

53. Original Components Reinstalled on theBreaker. ....................................................... 24

54. Drilling Plan “E”. .......................................... 24

55. Aux. CT Module Mounting BracketsInstalled on the Breaker. ............................. 25

56. Aux. CT Module Assembly Installedon the Breaker and Preliminary Routingof the Sensor Harness, DTA Wires, andCPT Wires. .................................................. 25

57. DTA Wires Connected to the Aux. CTModule Terminal Block. .............................. 25

58. Sensor Harness Connected to the Aux.CT Module Terminal Block. ........................ 26

59. Support Clips and Sensor Harness GroundWire Connected to the Aux. CT Module. ... 26

60. Rating Plug and Aux. CT HarnessInstalled. ...................................................... 26

61. Overview: External Harness Installedon the Breaker. ........................................... 27

62. 510 Basic Kit External Harness ShortingPlug. ............................................................ 27

63. External Harness Wires Connected tothe Auxiliary Switch. ................................... 28

64. External Harness Connections at theTrip Unit. ...................................................... 28

65. External Harness Secured to the Side ofthe Breaker. ................................................. 28

66. Retrofit Components .................................. 35

Tables

1. Available Retrofit Kits ................................... 5

2. Sensor Taps Rating .................................... 10 3. CPT High Voltage Taps for Standard

and Special Order CPTs .............................. 15

4. CPT Low Voltage Taps for Standardand Special Order CPTs .............................. 15

5. Torque Values for General Mountingand Screw Size Conversion ........................ 34

6. Torque Values for Copper BUSConnectors .................................................. 34

Page 4: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

4

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Eaton CoRPoRatIon www.eaton.com

WARNINGPOWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE SIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY FEATURES INTENDED TO PROVIDE SAFE AND PROPER OPERATING SEQUENCES. TO PROVIDE MAXIMUM PROTECTION FOR PERSONNEL ASSOCIATED WITH THE INSTALLATION, OPERATION, AND MAINTENANCE OF THESE BREAKERS, THE FOLLOWING PRACTICES MUST BE FOLLOWED. FAILURE TO FOLLOW THESE PRACTICES MAY RESULT IN DEATH, PERSONAL INJURY, OR PROPERTY DAMAGE.

Safety Precautions

• Periodic testing of this device is required (see Step 10 Testing the Breaker for test procedures).

• Only qualified persons, as defined in the National Electric Code, who are familiar with the installation and maintenance of power circuit breakers and their associated switchgear assemblies should perform any work associated with these breakers.

• Completely read and understand all instructions before attempting any installation, operation, maintenance, or modification of these breakers.

• Always turn off and lock out the power source feeding the breaker prior to attempting any installation, maintenance, or modi-fication of the breaker. Do not use the circuit breaker as the sole means for isolating a high voltage circuit. Follow all lockout and tagging rules of the National Electric Code and all other applicable codes, regulations, and work rules.

• Do not work on a closed breaker or a breaker with the closing springs charged. Trip (open) the breaker and be sure the stored energy springs are discharged before performing any work. The breaker may trip open or the charging springs may discharge, causing crushing or cutting injuries.

• For drawout breakers, trip (open), and then remove the breaker to a well-lit work area before beginning work.

• Do not perform any maintenance: including breaker charging, clos-ing, tripping, or any other function which could cause significant movement of the breaker while it is on the extension rails. Doing so may cause the breaker to slip from the rails and fall, potentially causing severe personal injury to those in the vicinity.

• Do not leave the breaker in an intermediate position in the switch-gear cell. Always leave it in the connected, disconnected, or (optional) test position. Failure to do so could lead to improper positioning of the breaker and flashover, causing death, serious personal injury, and / or property damage.

• Do not defeat any safety interlock. Such interlocks are intended to protect personnel and equipment from damage due to flash-over and exposed contacts. Defeating an interlock could lead to death, severe personal injury, and / or property damage

Page 5: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

5

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Eaton CoRPoRatIon www.eaton.com

Section 1: IntroductionEaton Digitrip Retrofit Kits are available in a number of configurations that provide a wide range of features. The Digitrip System starts with the 510 Basic Kit that offers true RMS sensing, overcurrent protection, and self-testing features. Advanced Digitrip Retrofit Kits feature zone interlocking, digital alphanumeric displays, remote alarm signals, PowerNet communications, energy monitoring capabilities, power factors, and harmonic content measurements.

Table 1 provides a quick reference of the components supplied with each level of Retrofit Kit. Before beginning the Retrofit process, take a minute to review the information contained in Table 1. It is important that the Retrofitter understands which level of Retrofit Kit is to be installed and which components are included with the Kit.

The instructions contained in this manual cover the installation of all levels of Retrofit Kit. If the Kit you are installing does not contain a certain component, skip the instructions for that component and proceed to the next.

Throughout the Retrofit process, refer to the Torque Tables at the back of this manual for specific torque values.

If you have any questions concerning the Retrofit Kit and / or the Retrofit process, contact Eaton at: 1-800-937-5487.

Table 1. Available Retrofit Kits

Components 510 Basic510 with Zone Interlock 610 810 910

Trip Unit

Rating Plug

Auxiliary Current

Transformer

(CT) Module

Auxiliary

CT Harness

Sensors

Sensor Harness

Direct Trip Actuator (DTA)

Mounting Brackets and Hardware

External Harness Plug 1 Connector Harness 2 Connector Harness 3 Connector Harness 4 Connector Harness

Cell Harness

Breaker Mounted Control Power Transformer (CPT

Potential Transformer (PT) Module

Auxiliary Switch

Page 6: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

6 EATON CORPORATION www.eaton.com

STEP 1: GENERAL BREAKERPREPARATION

Before attempting to remove the Breaker from theCell or perform any Retrofit Operation, be sure toread and understand the Safety Precautions sec-tion of this manual. In addition, be sure to read andunderstand the Instructions for the Application ofDigitrip RMS Retrofit Kits on Power Circuit Break-ers (Retrofit Application Data - Publication AD 33-855), supplied with the Digitrip Retrofit Kit.

DO NOT ATTEMPT TO INSTALL OR PER-FORM MAINTENANCE ON EQUIPMENTWHILE IT IS ENERGIZED. SEVERE PER-SONAL INJURY OR DEATH CAN RESULTFROM CONTACT WITH ENERGIZED EQUIP-MENT. VERIFY THAT NO VOLTAGE ISPRESENT BEFORE PROCEEDING.

A. Trip the Breaker and remove it from the Cell.Move the Breaker to a clean, well-lit work area.

NOTE: It is the responsibility of the Retrofitter toinsure that the Breaker and all originalcomponents are in good condition. Visu-ally inspect all Breaker components forsigns of damage or wear. If any signs ofdamage or wear are detected for compo-nents not included in the Retrofit Kit,secure the necessary replacement partsbefore beginning the Retrofit Process.

The force necessary to trip the Breakershould not exceed three (3) lbs.

NOTE: It is the responsibility of the Retrofitter toinsure that the proper, manufacturer’srecommended crimping tools and termi-nals are used for each type of connector.It is also the responsibility of the Retrofitterto insure that all wire preparations, con-nections, strippings, terminations, andwiring techniques are performed accordingto the latest IEEE, NEC, and / or NEMAindustry standards, specifications, codes,and guidelines.

To begin the Retrofit Process, refer to the compo-nents list at the end of this manual. Layout thecomponents and hardware according to the stepsoutlined. The parts bags are labeled with thecorresponding step number. The components andhardware will be used to complete each step in theRetrofit Process.

WARNING

Page 7: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 7

STEP 2: REMOVING THE ORIGINAL COMPO-NENTS AND PREPARING THEBREAKER FOR RETROFITTING

Fig. 1 Overview: Original Components Removedfrom the Breaker and Saved forReinstallation.

NOTE: Throughout this Retrofit, an electricallyoperated Breaker was used for the supportphotographs. Where the components and/ or procedures differ between the electri-cally and mechanically operated Breakers,photos of both are supplied for clarity.

NOTE: The Breakers Retrofitted in the creation ofthis IL had 21" wide Frames. If theBreaker being Retrofitted is either narroweror wider, exact locations for drilling anymounting holes must be confirmed beforedrilling. The locations may not match theDrilling Plans contained in this IL.

HOODASSEMBLYARC

CHUTESFLASHBARRIER

ARCCHUTEHOLDERS

MOUNTINGKNOBS

INTERPHASEBARRIERS

SIDE BARRIERS

Refer to the Federal Pioneer 25 H-2 & H-L or 50 /65 H-2 & H-L Instruction Manual, originally sup-plied with the Breaker, to perform the followingprocedures.

A. Remove and discard the original Trip Unit andall associated wiring and mounting hardware.

B. Remove and save the Hood Assembly.

C. Remove the Mounting Knobs and Arc ChuteHolders securing the Arc Chutes to the Breaker.Remove and save the Arc Chutes, the Holders,and the Mounting Knobs.

D. Remove and save the two (2) Side Barriers.

E. Remove the mounting hardware securing theFlash Barrier to the Breaker. Remove and savethe Flash Barrier and the mounting hardware.

F. Remove and save the Phase 1 & 2 and Phase 2& 3 Interphase Barriers.

Fig. 2 Hood Assembly, Arc Chutes, Flash Barrier,Interphase Barriers, and Side BarriersRemoved from the Breaker.

NOTE: Removing the Charging Handle, BreakerFace Plate, and the Floating Trim detailedin Steps “G” and “H” below, are notmandatory for the Retrofit. However,removing these components will provideadditional access to the internal Breakermechanisms during the Retrofit.

Page 8: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

8 EATON CORPORATION www.eaton.com

STEP 3: INSTALLING THE SENSORS ANDSENSOR HARNESS (PARTIAL)

Fig. 4 Overview: Sensors Installed in theBreaker.

Refer to the Federal Pioneer 25 H-2 & H-L or 50 /65 H-2 & H-L Instruction Manual, originally sup-plied with the Breaker, to perform the followingprocedures.

A. Remove the hardware securing the FingerClusters (Drawout Contacts) to the bottomLoad Terminals. Remove and save the FingerClusters and mounting hardware.

B. Raise the rear of the Breaker approximately four(4) inches to provide clearance for the follow-ing steps.

Fig. 5 Finger Clusters Removed from the BottomLoad Terminals (Electrically Operated).

G. Remove and save the Charging Handle.

H. Remove the hardware securing the BreakerFace Plate to the Breaker. Remove and savethe Face Plate, Floating Trim, and mountinghardware.

Fig. 3 Charging Handle, Face Plate, and FloatingTrim Removed from the Breaker.

Page 9: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 9

C. Loosen the six (6) bolts and nuts securing therear Lower Molding and Load Terminals to theJumpers.

D Remove and save the mounting hardwaresecuring the Lower Molding to the right and leftsides of the Breaker.

E. While “spreading” the sides of the Breaker,remove the Lower Molding and Load Terminalsfrom the Breaker. Note that as you are remov-ing the Lower Molding, the Load Terminals willfall free.

F. Remove the original Sensors from the Jump-ers. Scrap the original Sensors and all associ-ated wiring.

Fig. 6 Lower Molding and Load Terminals Re-moved from the Breaker.

G. Install a new Sensor and two (2) spacers, asshown, on each Jumper. Note that the Sen-sors must be installed with the terminalstowards the inside of the Breaker. The combi-nation of the Sensors and spacers create a“friction fit” to hold the Sensors in place.

Fig. 7 Sensor and Spacers Installed on a Jumper.

H. To reinstall the Lower Molding, align the LoadTerminals with the holes in the Lower Molding.Insert the bolts into the Lower Molding andLoad Terminals and thread two (2) to three(3) turns to keep the Load Terminals in place.

Insert the right side of the Lower Molding intoposition with the right side of the Breaker(when viewed from the rear). While “spread-ing” the left side of the Breaker, push the leftside of the Lower Molding into place.

Page 10: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

10 EATON CORPORATION www.eaton.com

I. Using the original mounting hardware re-moved in Step 3-D, secure the Lower Moldingto the Breaker.

J. Tighten the six (6) original bolts and nuts untilthe Load Terminals are securely mated to theJumpers.

For Kits Supplied with a PT Module Only:Leave one (1) nut loose on each Load Terminal.These will be used later in the Retrofit Processto secure the PT Wires.

Fig. 8 Sensors, Load Terminals, and LowerMolding Installed on the Breaker.

K. Using the original mounting hardware, reinstallthe bottom Finger Clusters on the LoadTerminals in their original positions.

L. Remove what was used to elevate the back ofthe Breaker and return the Breaker to its restposition.

M. Working from the front of the Breaker, connectthe ring terminals of the Sensor Harness to theSensor Terminals. Refer to Section 12 of theApplication Data, supplied with the Retrofit Kit,for detailed wiring specifications.

For FP 25 H-2 & H-L and 50 / 65 H-2 & H-LRetrofits, the following conventions apply.

Table 2 Sensor Taps RatingFP 25 H-2 & H-L

Sensor Style No. Terminal Com. Amps

8188A79H01 X1-X2 = 400 A

X1-X3 = 800 A

8188A81H01 X1-X2 = 300 A

X1-X3 = 600 A

8184A45H01 X1-X2 = 200 A

FP 50 / 65 H-2 & H-L

Sensor Style No. Terminal Com. Amps

9A10020H01 X1 - X2 = 800 AX1 - X3 = 1,600 A

9A10021H01 X1 - X2 = 1,200 AX1 - X3 = 2,000 A

Fig. 9 Finger Clusters Reinstalled on the LoadTerminals (Electrically Operated).

Fig. 10 Sensor Harness Connected to theSensors.

Page 11: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 11

Fig. 11 Routing of the Sensor Harness.

STEP 4: PREPARING THE AUX. CT ASSEMBLY

Fig. 12 Overview: Aux. CT Assembly and PTModule Ready for Installation.

A. Align the Glass Poly Barrier with the existingholes in the back of the Aux. CT Module asshown. Secure the Barrier to the Aux. CTModule using the using the (2) .190-32 × .375"screws, (2) lock washers, and (2) flat washerssupplied.

Fig. 13 Glass Poly Barrier Mounted to the Aux.CT Module.

For Kits Supplied with a PT Module Only.

B. Align the PT Module with the existing holes inthe Glass Poly Barrier as shown. Secure the PTModule to the Glass Poly Barrier using the(2) .138-32 × .500" screws, (4) flat washers,(2) lock washers, and (2) nuts supplied.

N. Route the Sensor Harness along the back ofthe Breaker towards the left side. Use theself-adhesive mounting pads and wire tiessupplied to secure the Sensor Harness awayfrom any moving parts within the Breaker.

Page 12: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

12 EATON CORPORATION www.eaton.com

Fig. 14 PT Module Mounted to the Aux. CTModule Assembly.

NOTE: To ease installation, the PT Wires will beconnected to the Jumpers in the followingsteps. To accomplish this, the Aux. CTModule Assembly must be set on the topof the Breaker Frame. Until the Aux. CTModule Assembly is mounted later in theRetrofit Process, care must be taken toinsure that the Aux. CT Module Assemblyis not “knocked off” the Breaker.

C. Set the Aux. CT Module Assembly on the topof the Breaker Frame.

Fig. 15 Aux. CT Module Assembly Placed on theBreaker Frame.

D. Route the PT Wires through the cut-out in thetop and middle Breaker Frames, down towardsthe bottom left rear corner of the Breaker.

E. The PT Wires are marked for connection toPhases 1, 2, and 3 with corresponding num-bers.

NOTE: Before cutting the PT Wires, verify thePhase Convention used on the BreakerApplication.

Route the PT Wires to a position suitable forattachment to the bolts that secure the LoadTerminals to the Jumpers. These were leftloose in Step 3. Move the PT Wire markers toa position where they will still be attached tothe wires after cutting. Cut the wires to theappropriate length, strip each wire 0.250", andinstall a 0.500" ring terminal on each wire.Remove the nuts and washers from theJumper bolts left loose in Step 3-J. Using thehardware just removed, connect the PT Wiresto the Jumpers.

Fig. 16 PT Wires Connected to the Jumper Bolts.

F. Use the wire ties supplied to secure the PTWires to the Sensor Harness running along theinside of the left Breaker Frame.

Page 13: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 13

Fig. 17 PT Wires Secured to the Sensor Har-ness.

For Kits Supplied with a Breaker Mounted CPT and/ or Auxiliary Switch Only.

STEP 5: INSTALLING THE BREAKERMOUNTED CPT

Fig. 18 Overview: Breaker Mounted CPT In-stalled in the Breaker.

A. Remove and save the (2) .190 - 32 × .250"screws securing the fuse clips and male spadeconnector installed on the CPT. Discard thefuse clips and spade connector, then reinstallthe screws in the CPT Terminals.

Fig. 19 Fuse Clips and Spade Connector Re-moved from the CPT

Page 14: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

14 EATON CORPORATION www.eaton.com

B. Align the CPT Module with the holes in theCPT Mounting Bracket as shown. Note thatwhen viewed from the angled end of theMounting Bracket, the “X” Terminals should betowards the left edge of the Mounting Bracket.Secure the CPT Module to the CPT MountingBracket using the (4) .190-32 × .500" screws,(8) flat washers, (4) lock washers, and (4) nutssupplied.

Fig. 22 Drilling Plan “B”

NOTE: The Load Side HV Wires are longer thannecessary and are cut during the follow-ing step. Before cutting the wires, besure that sufficient length is left so thatthe HV Wire Fuses are accessible andthat the connections can be made to thecorrect “H” terminals on the CPT.

Fig. 20 CPT Module Installed on the MountingBracket.

C. Using Drilling Plan “A” for H-2 Breakers, orDrilling Plan B for H-L Breakers, drill two(2) 0.281" diameter holes in the bottom frontBreaker Channel. Note that it may be neces-sary to temporarily remove the fuse box orexisting wire ties and mounting pad in order todrill the Breaker Channel.

Fig. 21 Drilling Plan “A”.

Fig. 23 Load and Line Sides of the HV Wires.

LINE SIDE LOAD SIDE

“X”TERMINALS

0.281 DIA. - (2)

0.63

1.25 4.75

DRILL MOUNTING HOLES INTO CHANNELON BOTTOM / FRONT OF BREAKER

0.281 DIA. - (2)

0.63

1.25 2.75

DRILL MOUNTING HOLES INTO CHANNELON BOTTOM / FRONT OF BREAKER

Page 15: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 15

G. After the HV and CPT Wires have been con-nected to the proper terminals of the CPT,install the “A” and “B” Finger-Safe Covers overthe CPT Terminals as shown. Secure theFinger-Safe Covers to the CPT using the(4) .098 - 28 × .375" screws supplied with theCPT Kit. Torque the screws to 8 - 10 in./lbs.

NOTE: The “C” and “D” Finger-Safe Coverssupplied with the CPT Kit are not used inthis application and should be discarded.

Table 3 CPT High Voltage Taps for Standardand Special Order CPTs

Standard CPT (Style #9A10037G01 & G02)

Voltage Required CPT Terminals Used

480 Volt Circuit H1 & H4

240 Volt Circuit H2 & H4

208 Volt Circuit H3 & H4

Special Order 575 Volt CPT (Style #9A10037G03 & G04)

575 Volt Circuit H1 & H4

460 Volt Circuit H2 & H4

230 Volt Circuit H3 & H4

D. Set the CPT Assembly in front of the bottomfront Breaker Channel, near the holes drilled inStep C. Position the HV Fuses along the rightside of the Breaker, roughly half way betweenthe front and back of the Breaker.

E. Mark and cut the Load Side of each HV Wireto an appropriate length for connection to the“H” terminals of the CPT. Strip an appropriatelength of insulation from the Load Side HVWires and attach a 0.138" ring terminal toeach. Attach the HV Wires to the CPT termi-nals to achieve the required voltage(see Table 3).

NOTE: The terminals to which the Load Side HVwires are connected determine the volt-age of the CPT. Verify that the line volt-age of the circuit matches the CPTvoltage BEFORE putting the Breaker intoservice.

Table 4 CPT Low Voltage Taps for Standardand Special Order CPTs(After Removing Fuse Clips)

Standard CPT (Style #9A10037G01 & G02)

120 Voltage Required CPT Terminals Used

Secondary Circuit X1 & X2

Special Order 575 Volt CPT(Style #9A10037G03 & G04)

Secondary Circuit X1 & X2

Fig. 24 HV and CPT Wires Connected to theCPT Module.

F. Connect the CPT Wires to the appropriate “X”terminals of the CPT Module as shown. SeeTable 4 for Tap information. Temporarily routethe CPT Wires towards the left side of theBreaker. These will be routed and connectedalong with the Sensor Harness later in theRetrofit Process.

Page 16: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

16 EATON CORPORATION www.eaton.com

Fig. 26 Microswitch Mounted to the AuxiliarySwitch Mounting Bracket.

I. Align the CPT Assembly, as shown, with theholes drilled in the bottom front BreakerChannel in Step 5-C. Secure the CPT Assem-bly to the bottom front Breaker Channel usingthe (2) .250-20 × .750" bolts, (4) flat washers,(2) lock washers, and (2) nuts supplied.

Fig. 28 Auxiliary Switch and CPT AssembliesInstalled in the Breaker.

As the Auxiliary Switch Assembly is beinginstalled in the Breaker, insure that the AuxiliarySwitch Arm engages the Closing Link as shown.

Fig. 25 Finger-Safe Covers Installed on the CPTModule.

H. For Kits Supplied with an Auxiliary Switch Only:For H-2 Breakers cut 2.88" off the MicroswitchArm. For H-L Breakers cut 0.88" off theMicroswitch Arm. Align the Microswitch, asshown, with the existing holes in the AuxiliarySwitch Mounting Bracket. Secure theMicroswitch to the Mounting Bracket using the(2) .138-32 × 1.00" screws, (4) flat washers,(2) lock washers, and (2) nuts supplied.

Fig. 27 CPT Assembly Installed in the Breaker.

For Kits Supplied with an Auxiliary Switch Only:The hardware and holes used to secure CPTAssembly to the Breaker are also used tosecure the Auxiliary Switch Assembly. TheAuxiliary Switch Mounting Bracket should beplaced behind the CPT Mounting Bracket, asshown.

Page 17: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 17

The HV Wires from the CPT MUST BEATTACHED to the Line Side of the Breaker.If it is determined that the power flow forthe Breaker application is opposite thenormal convention, the HV Wires must beattached to the Bottom Load Terminals. Inthe case of the Line Side being the BottomLoad Terminals, the bolts that secure theLoad Terminals to the Jumpers can beused for HV Wire attachment.

NOTE: The Line Side HV Wires are longer thannecessary and are cut during the followingsteps. Before cutting the wires, be surethat sufficient length is left so that the HVWire Fuses are accessible and that theconnections can be made to the correctLoad Terminals.

J. Route the HV Line Side Wires up towards theappropriate Top Load Terminals. Cut each HVWire to an appropriate length, then strip .250"from each wire.

NOTE: There are two distinct types of FingerClusters that were used on FP 25 H-2 &H-L and 50 / 65 H-2 & H-L Breakers.Finger Clusters that are secured to the

Fig. 30 Correct Orientation of the HV Wire RingTerminals.

Using the original bolts and the (2) new 0.250"washers supplied, secure the HV Wires to theFinger Clusters and Load Terminals.

Fig. 29 Correct Engagement of the AuxiliarySwitch Arm.

NOTE: The power convention of Circuit Breakersis normally Top to Bottom, meaning the TopLoad Terminals (Breaker Stabs) are on theLine Side of the Breaker and the BottomLoad Terminals are on the Load Side.

Load Terminals from the sides; and FingerClusters that are secured to the LoadTerminals from the top. The followingprocedures detail HV Wire connection forboth applications.

K. For Finger Clusters Secured to the LoadTerminals from the Sides: Crimp a 0.312" ringterminal to each HV Wire. Completely removethe mounting hardware from one side of theappropriate Finger Clusters. Loosen thehardware on the opposite sides of each FingerCluster. Slide the HV Wire ring terminalsbetween the Finger Clusters and the LoadTerminals as shown.

Page 18: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

18 EATON CORPORATION www.eaton.com

Fig. 32 HV Wires Connected to Top SecuredFinger Clusters.

M. Use the nylon wire ties and self adhesive padssupplied to keep the HV Fuses and Wiresaway from any moving parts.

N. Install the appropriate CPT Voltage Label in aclearly visible location on the Breaker FacePlate.

Fig. 33 HV Fuses and Wires Secured Away fromMoving Breaker.

Fig. 31 HV Wires Connected to Side SecuredFinger Clusters.

L. For Finger Clusters Secured to the Load Termi-nals from the Top: Crimp a 0.500" ring terminalto each HV Wire. Completely remove one ofthe two bolts securing the appropriate FingerClusters to the Load Terminals. Align the HVring terminals with the Finger Cluster MountingHoles. Using the original mounting hardware,secure the HV Wires to the appropriate FingerClusters.

Page 19: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 19

STEP 6: INSTALLING THE TRIP FINGER

Fig. 35 Overview: Trip Finger Installed in theBreaker - Long Trip Shaft.

NOTE: FP 25 H-2 & H-L and 50 / 65 H-2 & H-LBreakers were equipped with two differ-ent Trip Shafts: a long Trip Shaft (asshown in Figure 35) or a short Trip Shaft(as shown in Figure 36). If the Breakerbeing Retrofitted has a long Trip Shaft,use the new Trip Finger with the StyleNumber 9A10093G05. If the Breakerbeing Retrofitted has a short Trip Shaft,use the new Trip Finger with the StyleNumber 9A10093G06.

Fig. 36 Short Trip Shaft.

Fig. 34 CPT Voltage Labels supplied with theCPT Kit.

208VCONTROL POWER TRANSF. TAPS

H1–H4=480V H2–H4=240VH3–H4=208V

WARNINGTHIS BREAKER CONTAINS A 50VA

CONTROL POWER TRANSFORMER FOR TRIP UNIT DISPLAY. IF BREAKERIS USED ON A LINE VOLTAGE OTHERTHAN SHOWN. THE CPT TAPS MUST BE CHANGED BEFORE ENERGIZING.FAILURE TO DO SO WILL RESULT IN

DAMAGE TO THE TRIP UNIT AND / ORCONTROL POWER TRANSFORMER

NP# 9A10039H04

240VCONTROL POWER TRANSF. TAPS

H1–H4=480V H2–H4=240VH3–H4=208V

WARNINGTHIS BREAKER CONTAINS A 50VA

CONTROL POWER TRANSFORMER FOR TRIP UNIT DISPLAY. IF BREAKERIS USED ON A LINE VOLTAGE OTHERTHAN SHOWN. THE CPT TAPS MUST BE CHANGED BEFORE ENERGIZING.FAILURE TO DO SO WILL RESULT IN

DAMAGE TO THE TRIP UNIT AND / ORCONTROL POWER TRANSFORMER

NP# 9A10039H03

480VCONTROL POWER TRANSF. TAPS

H1–H4=480V H2–H4=240VH3–H4=208V

WARNINGTHIS BREAKER CONTAINS A 50VA

CONTROL POWER TRANSFORMER FOR TRIP UNIT DISPLAY. IF BREAKERIS USED ON A LINE VOLTAGE OTHERTHAN SHOWN. THE CPT TAPS MUST BE CHANGED BEFORE ENERGIZING.FAILURE TO DO SO WILL RESULT IN

DAMAGE TO THE TRIP UNIT AND / ORCONTROL POWER TRANSFORMER

NP# 9A10039H02

575VCONTROL POWER TRANSF. TAPS

H1–H4=575V

WARNINGTHIS BREAKER CONTAINS A 50VA

CONTROL POWER TRANSFORMER FOR TRIP UNIT DISPLAY. IF BREAKERIS USED ON A LINE VOLTAGE OTHERTHAN SHOWN. THE CPT TAPS MUST BE CHANGED BEFORE ENERGIZING.FAILURE TO DO SO WILL RESULT IN

DAMAGE TO THE TRIP UNIT AND / ORCONTROL POWER TRANSFORMER

NP# 9A10039H01

Page 20: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

20 EATON CORPORATION www.eaton.com

For Breakers Equipped with a Short Trip ShaftOnly: Align the hole in the Trip Finger with theexisting hole near the end of the Trip Shaft.Secure the Trip Finger to the Trip Shaft usingthe (1) .190-32 × 1.25" screw, (2) flat washers,(1) lock washer, and (1) nut supplied.

Fig. 39 Original Trip Finger Removed from anElectrically Operated Breaker with ShortTrip Shaft.

B. For Breakers Equipped with a Long Trip ShaftOnly: Align the inner hole in the Trip Fingerwith the existing hole near the end of the TripShaft. Secure the Trip Finger to the Trip Shaftusing the (2) .190-32 × 1.25" screws, (4) flat

Fig. 40 Trip Finger Installed on a Long Trip Shaft.

Fig. 41 Trip Finger Installed on a Short Trip Shaft.

Fig. 37 Trip Finger to be used with a Long TripShaft (Style Number 9A10093G05).

Fig. 38 Trip Finger to be used with a Short TripShaft (Style Number 9A10093G06).

A. For Breakers with a Short Trip Shaft Only:Remove and scrap the existing Trip Finger andmounting hardware.

washers, (2) lock washers, and (2) nuts sup-plied. Note that the screw that “pinches” theTrip Finger together should not be over tight-ened.

Page 21: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 21

STEP 7: INSTALLING THE DTA

Fig. 42 Overview: DTA Installed in the Breaker.

A. If existing holes do not already exist, usingDrilling Plan “C” for H-2 Breakers or DrillingPlan “D” for H-L Breakers, drill two (2) 0.281"diameter holes in the bottom front BreakerChannel. Note that it may be necessary totemporarily remove the existing wire ties andmounting pad in order to drill the BreakerChannel.

ON BOTTOM / FRONT OF BREAKERDRILL MOUNTING HOLES INTO CHANNEL

0.281 DIA. - (2)

0.63

1.883.75

Fig. 43 Drilling Plan “C”.

NUTWASHER (1)

Fig. 45 Hardware to Remove from the DTA TripShaft.

C. Align the DTA, as shown, with the existingholes or the holes drilled in Step 7-A. Securethe DTA to the bottom front Breaker Channelusing the (2) .250-20 × .625" bolts, (4) flatwashers, (2) lock washers, and (2) nuts sup-plied.

B. Remove the nut and one (1) wide flat washerfrom the end of the DTA Reset Shaft.

ON BOTTOM / FRONT OF BREAKERDRILL MOUNTING HOLES INTO CHANNEL

0.281 DIA. - (2)

0.63

1.883.56

Fig. 44 Drilling Plan “D”.

Page 22: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

22 EATON CORPORATION www.eaton.com

NOTE: For the following procedures, it is recom-mended that the Retrofitter have both theBreaker’s Slow Close Handle and anappropriate block of wood available.

D. Using the Slow Close Handle, slightly movethe Closing Link forward towards the “Closed”position. Place a block of wood between oneof the Closing Links and the inner BreakerFrame. Slowly move the Slow Close Handletowards the back of the Breaker until thewood block is engaged.

Fig. 47 Slow Close Handle Engaged in theClosing Link.

E. Align the slot in the “L” Bracket with the DTAReset Shaft. Using the (1) .375-16 × 1.00"shoulder bolt, (3) flat washers, and (1) nutsupplied, loosely mount the Reset “L” Bracket,as shown, to the Closing Link. Note that extraflat washer is to be installed between the “L”Bracket and the Closing Link. On H-L Break-ers, an additional flat washer may be neededbetween the “L” Bracket and closing link toprovide proper vertical alignment.

Tighten the nut, then back it off three (3) tofour (4) turns. Apply Loc-Tite® 243 to thethreads of the bolt, fully tighten the nut, thenback the nut off one-half to one turn to allowthe “L” Bracket to pivot.

F. Using the wide flat washer and nut removed inStep 7-B, secure the “L” Bracket to the DTAReset Shaft.

Fig. 48 Reset “L” Bracket Installed on the DTAShaft.

Fig. 46 DTA Mounted to the Bottom Front BreakerChannel.

Page 23: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 23

I. “Close” the Breaker.

NOTE: Throughout the Trip System Setupprocedure, be sure to keep hands andfingers away from any moving partswithin the Breaker. Failure to do so couldresult in serious injury.

J. Back-off the DTA Trip Disk. Apply Loc-Tite243 to the threads of the DTA Shaft. Turn theDTA Trip Disk until a gap of 0.070 to 0.100 isachieved between the top of the Disk and thebottom of the Trip Finger.

CAGEHEIGHT 0.875"

Fig. 49 Proper Cage Height Adjustment.

Fig. 50 Proper Air Gap Adjustment.

K. Return the Breaker to the “Open” position.

L. Using the self-adhesive mounting pads andwire ties supplied, secure the original wiring tothe Breaker Channel.

M. Route the DTA Wires, the Sensor Harness, andif applicable the CPT wires as shown towardsthe top of the Breaker. Use the wire tiessupplied to secure and bundle the wires tokeep them clear of any moving parts within theBreaker.

DTATRIPDISK

TRIP FINGER

GAP0.070"TO0.100"

Fig. 51 Routing and Securing of the Original andNew Wiring.

G. Again using the Slow Close Handle, releasethe pressure on the Closing Link and removethe wood block. Return the Breaker to thefully “Open” position.

H. Back-off the nuts on the DTA Reset Shaft.Apply Loc-Tite 243 to the threads of the ResetShaft. Adjust the nut below the “L” Bracket onthe Reset Shaft until a cage height of 0.875" isachieved. Fully tighten the nut securing theReset “L” Bracket to the Reset Shaft.

Page 24: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

24 EATON CORPORATION www.eaton.com

STEP 8: INSTALLING THE AUX. CT MODULEASSEMBLY AND THE TRIP UNIT

Fig. 52 Overview: Aux. CT Assembly and TripUnit Installed on the Breaker.

NOTE: For Steps 8-A through 8-E, the originalcomponents removed and saved duringStep 2 will be reinstalled. Refer to theFederal Pioneer 25 H-2 & H-L or 50 / 65H-2 & H-L Instruction Manual, originallysupplied with the Breaker, to perform thereinstallations.

A. Reinstall the Phase 1 & 2 and Phase 2 & 3Interphase Barriers.

B. Using the original hardware, reinstall the FlashBarrier.

C. Reinstall the Side Barriers.

D. Reinstall the Arc Chutes, the Arc Chute Hold-ers, and the Mounting Knobs.

E. Reinstall the Hood Assembly.

Fig. 53 Original Components Reinstalled on theBreaker.

F. Remove and scrap the existing hardware fromthe top, front right corner of the Breaker andnear the top, left rear corner of the Face PlateBox.

NOTE: If no holes exist at these locations, useDrilling Plan “E” to drill two (2) 0.281"holes in the top Breaker Frame.

Fig. 54 Drilling Plan “E”.

10.25 1.50

21.00

0.50

TOP VEIW OF BREAKER

0.281 DIA. - (2)

Page 25: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 25

G. Align the right and left Aux. CT Module Mount-ing Brackets, as shown, with the holes fromwhich the hardware was just removed. Securethe Aux. CT Module Mounting Brackets to theBreaker using the (2) .250-20 × .625" bolts,(2) lock washers, and (2) flat washers supplied.If the existing holes are not threaded, or if theholes were drilled during this process, use theadditional (2) 0.250-20 nuts and (2) flat wash-ers supplied to secure the Aux. CT ModuleMounting Brackets.

Fig. 55 Aux. CT Module Mounting BracketsInstalled on the Breaker.

H. Align the Aux. CT Module Assembly with theholes in the Aux. CT Module Mounting Brack-ets. Secure the Aux. CT Module Assembly tothe Brackets using the (4) .190-32 × .500" flathead screws.

I. Route the Sensor Harness and the DTA Wirestowards the Aux. CT Module Terminal Block.

For Kits Supplied with a Breaker Mounted CPTOnly: Route the CPT wires across the top ofthe Aux. CT Module, against the bottom of theGlass Poly Barrier. If necessary, use the self-adhesive mounting pad and wire tie suppliedto hold the CPT Wires in place.

Fig. 56 Aux. CT Module Assembly Installed on theBreaker and Preliminary Routing of theSensor Harness, DTA Wires, and CPTWires.

J. Remove and save the Aux. CT Module Termi-nal Block Cover and mounting hardware.

K. Connect the “+” DTA Wire to the “OP” terminalof the 7-Point Terminal Block and the un-marked wire to the “ON” terminal.

Fig. 57 DTA Wires Connected to the Aux. CTModule Terminal Block.

Page 26: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

26 EATON CORPORATION www.eaton.com

L. Connect the Sensor Harness to the properterminals of the 7-Point Terminal Block. Refer toSection 12 of the Retrofit Application Data,supplied with the Retrofit Kit, for detailedwiring specifications.

Note that the Sensor Harness Ground Wire(with ring terminal) will be connected later in theRetrofit Process.

Fig. 58 Sensor Harness Connected to the Aux.CT Module Terminal Block.

M. Reinstall the 7-Point Terminal Cover.

N. Mount the Trip Unit to the top of the Aux. CTModule as shown using the (2) .190-32 × 4.00"screws, (2) lock washers, (2) flat washers, and(2) spacers supplied. Note that the brassspacers are positioned between the top of theAux. CT Module and the bottom rear of the TripUnit. Do not fully tighten the screws at thistime.

O. Mount the left and right Trip Unit Support Clipsto the sides of the Aux. CT Module and intothe bottom front slots in the Trip Unit asshown. Secure using the (4) .190-32 × .500"screws, (4) lock washers, and (4) flat washerssupplied. Use one of the left Support ClipMounting Screws to secure the Sensor Har-ness Ground Wire to the Aux. CT Module.

Secure the Trip Unit by tightening the 4.00"screws installed in Step 8-N.

Fig. 59 Support Clips and Sensor HarnessGround Wire Connected to the Aux. CTModule.

P. Remove the Trip Unit Cover and install theRating Plug supplied with the Retrofit Kit.Reinstall the Cover.

Q. Install the Aux. CT Harness between the TripUnit and the Aux. CT Module.

Fig. 60 Rating Plug and Aux. CT Harness In-stalled.

Page 27: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 27

R. Use the self-adhesive mounting pads and wireties supplied to secure the Sensor Harness,DTA Wires and if applicable, the PT Wires andCPT Wires away from any moving parts withinthe Breaker.

S. Install the Digitrip Retrofit Label on the top ofthe Trip Unit.

STEP 9: INSTALLING THE EXTERNAL HAR-NESS AND FINAL WIRING

Fig. 61 Overview: External Harness Installed onthe Breaker.

A. Connect the External Harness to the Trip Unit.

NOTE: For 510 Basic Kits, the External Harnessis the shorting plug pictured below. It isto be plugged into the right side of theTrip Unit.

Fig. 62 510 Basic Kit External Harness ShortingPlug.

B. For Kits Supplied with a PT Module Only: Plugthe connector from the PT Module into itsreceptacle on the External Harness.

Page 28: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

28 EATON CORPORATION www.eaton.com

C. For Kits Supplied with an Auxiliary Switch Only:Route the two (2) wires (with ring terminals)from the External Harness, down through theBreaker to the Auxiliary Switch. Connect one(1) wire to the normally “Open” terminal andthe other wire to the “Common” terminal of theAuxiliary Switch.

Fig. 63 External Harness Wires Connected to theAuxiliary Switch.

D. For Kits Supplied with a Breaker Mounted CPTOnly: Remove the External Harness pluginstalled in the bottom rear socket of the TripUnit. Insert the black plug of the CPT Harnessinto the same receptacle in the Trip Unit.Reinsert the External Harness Plug just re-moved into the female receptacle on the CPTHarness.

Fig. 64 External Harness Connections at the TripUnit.

E. Secure the External Harness to the rightBreaker Frame using the self-adhesive mount-ing pad and wire tie supplied.

Fig. 65 External Harness Secured to the Side ofthe Breaker.

F. Use the self-adhesive mounting pads and wireties supplied to dress all wires and harnessesto keep them away from any moving partswithin the Breaker.

G. If the Breaker Face Plate, Floating Trim, andCharging Handle were removed during theRetrofit, reinstall them using the original mount-ing hardware.

Page 29: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 29

STEP 10: TESTING THE BREAKER

A. Measure the force necessary to trip theBreaker at where the Trip Finger impacts theDTA Adjusting Disk. The force necessary totrip the Breaker MUST NOT EXCEED 3 lbs.

B. The Retrofit must be tested using primaryinjection. Refer to Section 8 of the Instructionsfor the Application of Digitrip RMS Retrofit Kitson Power Circuit Breakers (Publication AD 33-855), supplied with the Retrofit Kit, for detailedtesting procedures and specifications. Fortest information specific to the Trip Unit, referto the IL publication supplied with the RetrofitKit (see the Pick List for the IL number).

C. While Section 8 of the Instructions for theApplication of Digitrip RMS Retrofit Kits onPower Circuit Breakers provides the informa-tion necessary for testing the Breaker, pleasekeep the following notes in mind when review-ing other sections of the publication.

Confirm that the PowerNet communicationwiring is correct by following the proce-dures detailed in Section 7.4 of the Instruc-tions for the Application of Digitrip RMSRetrofit Kits on Power Circuit Breakers.Note that for 810 and 910 Kits, the imped-ance between COM 1 and COM 2 should bebetween one (1) and three (3) ohms.

When testing is complete, disconnect theExternal Harness from the Cell Harness.Final External Harness connection will beperformed later in the Retrofit Process.

CAUTION

WHEN ALL TESTING IS COMPLETE, THE TRIPUNIT MUST BE RESET. FAILURE TO DO SOMAY CAUSE THE BATTERY IN THE RATINGPLUG TO RUN DOWN.

NOTES:

1. For All Kits Other Than 510 Basic: If testingthe Breaker with Short Delay or GroundFault functions, be sure to either plug in theCell Harness Assembly or use the ZoneInterlock Shorting Plug. Failure to do somay result in shorter than expected triptimes.

2. For 810 and 910 Kits Only: Without any powerapplied to the system (neither the 120 voltpower supply nor the Aux. Power Moduleconnected), plug the External Harness into theCell Harness and check the impedance be-tween COM 1 and COM 2. The impedanceshould be between one (1) and three (3) ohms.If the impedance is not within this range, tracethe wiring and examine each connection toassure its integrity.

Page 30: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

30 EATON CORPORATION www.eaton.com

STEP 11: MOUNTING THE CELL HARNESS

A. The Cell Harness is to be mounted in theBreaker Cell. The connector end is to bemounted on the left side of the Cell, in alocation suitable for connection with theExternal Harness. The Terminal Blocks can bemounted anywhere space is available in theCell as long as connection to the ExternalHarness can be made.

B. Route the Cell Harness wiring to keep it awayfrom any moving parts within the Cell Housing.

STEP 12: INSTALLING THE RETROFITTEDBREAKER IN THE CELL

WARNING

DO NOT LEAVE THE BREAKER IN AN INTER-MEDIATE POSITION IN THE SWITCHGEARCELL. ALWAYS LEAVE IT IN THE CONNECTED,DISCONNECTED, OR (OPTIONAL) TEST POSI-TION. FAILURE TO DO SO COULD LEAD TOIMPROPER POSITIONING OF THE BREAKERAND FLASHOVER, CAUSING DEATH, SERIOUSPERSONAL INJURY, AND / OR PROPERTYDAMAGE.

NOTE: It is the responsibility of the Retrofitter toinsure proper Breaker / Cell fit. Whenracking the Breaker into the Connectedposition, the Retrofitter MUST FOLLOWBOTH the manufacturer’s instructions andthe customer’s safety standards andprocedures for racking a Breaker into theConnected position.

A. With the Breaker in the Open position and thesprings discharged, slowly rack the Breakerinto the Connected position, making surethere is no interference or binding. TheBreaker should rack smoothly and withoutmechanical interference between any Breakerand Cell parts. The Retrofitter will feel someresistance when the primary fingers connectonto the stabs of the Cell. This is normal.

However, if any unusual resistance is detectedthat could be abnormal interference betweenthe Breaker and Cell parts, stop immediatelyand move the Breaker out of the Connectedposition. Examine what is causing the interfer-ence and correct the situation.

Page 31: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 31

Digitrip Retrofit Kit Installation Components for Federal Pioneer 25 H-2 & H-L and 50 / 65 H-2& H-L Breaker RMS/R RetrofitsStep Description Qty. CommentStep 3 Sensor See Pick List 3

Sensor Mounting Parts 9A10093G04 1Spacer 6

Sensor Harness Parts 9A10093G07 1Sensor Harness See Pick List 1Mounting Pad - 1", Self Adhesive 6Wire Tie Nylon 16

Step 4 Aux. CT Module 6503C59G__ 1Trip Unit Mounting Parts 9A10093G10 1

Trip Unit Barrier 1Aux. CT Mounting Bracket R. H. 1Aux. CT Mounting Bracket L. H. 1Support Clip RH 1Support Clip LH 1.250-20 × .625 Lng. Bolt Stl. 2.250 Flat Washer Stl. 4.250 Lock Washer Stl. 2.250-20 Nut Hex Stl. 2.190-32 × 4.00 Lng. Screw Fil. 2.190-32 × .500 Lng. Screw F. H. 4.190-32 × .500 Lng. Screw P. H. 4.190-32 x .375 Lng. Screw P. H. 2.190 Flat Washer Stl. 8.190 Lock Washer Stl. 8Spacer Brass 2Label Digitrip Retrofit 1

PT Module 6502C82G01 1Ring Terminal (.190, .250, .312, .375, .500 -Each Size) 3

PT Module Mounting Parts 9A10093G11 1.138-32 × .500 Lng. Screw P. H. 2.138 Flat Washer Stl. 4.138 Lock Washer Stl. 2.138-32 Nut Hex Stl. 2

Wire Tie Nylon From Step 3Step 5 Breaker Mounted CPT Kit See Pick List 1

MTE Transformer 1HV Fused Wires 2CPT Wires 1

Mounting Hardware Kit 1.190-32 × .750 Lng. Screw Fil. 4.190-32 × .375 Lng. Screw Fil. 2.190 Flat Washer Stl. 10.190 Lock Washer Stl. 6.190-32 Nut Hex Stl. 4Ring Terminal (.138, .190, .250, .312, .375, .500 -Each Size) 2

Comm. Only

CPT Only

Page 32: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Instruction Leaflet IL 33-FHC-4Effective July 2010

32 EATON CORPORATION www.eaton.com

Digitrip Retrofit Kit Installation Components for Federal Pioneer 25 H-2 & H-L and 50 / 65 H-2& H-L Breaker RMS/R RetrofitsStep Description Qty. Comment

Wire Tie Nylon 12Warning Label (208, 240, 480, & 575 Volt - Each) 1

Finger-Safe Cover Kit FSK4 1Cover (A, B, C, & D Each) 1.098-28 × .375 Lng. Screw Fil. 4

CPT Mounting Parts 9A10093G20 1CPT Mounting Bracket 1.250-20 × .750 Lng. Bolt Stl. 2.250 Flat Washer Stl. 6.250 Lock Washer Stl. 2.250-20 Nut Hex Stl. 2.190-32 × .500 Lng. Screw F. H. 4.190 Flat Washer Stl. 8.190 Lock Washer Stl. 4.190-32 Nut Hex Stl. 4

Auxiliary Switch Kit 9A10093G02 1Microswitch 1Auxiliary Switch Mounting Bracket 1.250-20 × .750 Lng. Bolt Stl. 2.250 Flat Washer Stl. 4.250 Lock Washer Stl. 2.250-20 Nut Hex Stl. 2.138-32 × 1.00 Lng. Screw Fil. 2.138 Flat Washer Stl. 4.138 Lock Washer Stl. 2.138-32 Nut Hex Stl. 2

Mounting Pad - 1", Self AdhesiveWire Tie Nylon

Step 6 Trip Finger Parts (Long Trip Shaft) 9A10093G05 1Trip Finger 1.190-32 × 1.25 Lng. Screw Fil. 2.190 Flat Washer Stl. 4.190 Lock Washer Stl. 2.190-32 Nut Hex Stl. 2

Trip Finger Parts (Short Trip Shaft) 9A10093G06 1Trip Finger 1.190-32 × 1.25 Lng. Screw P.H. 1.190 Flat Washer Stl. 2.190 Lock Washer Stl. 2.190-32 Nut Hex Stl. 1

Step 7 DTA Assembly 9A10093G__ 1DTA Mounting Parts 9A10093G08 1

.250-20 × .625 Lng. Bolt Stl. 2

.250 Flat Washer Stl. 4

.250 Lock Washer Stl. 2

Step 5(cont.)

CPT Only

From Step 3

Comm. Only

Page 33: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 33

Digitrip Retrofit Kit Installation Components for Federal Pioneer 25 H-2 & H-L and 50 / 65 H-2& H-L Breaker RMS/R RetrofitsStep Description Qty. Comment

.250-20 Nut Hex Stl. 2Loc-Tite® 243 1

Reset Parts 9A10093G09 1L Bracket Reset 1.375-16 × 1.00 HEX BOLT 1.375-16 HEX NUT 1.375 FLAT WASHER 4Loc-Tite® 243 1

Mounting Pad - 1", Self AdhesiveWire Tie Nylon

Step 8 Aux. CT Mounting Bracket R. H. 1Aux. CT Mounting Bracket L. H. 1Support Clip R. H. 1Support Clip L. H. 1.250-20 × .625 Lng. Bolt Stl. 2.250 Flat Washer Stl. 4.250 Lock Washer Stl. 2.190-32 × 4.00 Lng. Screw Fil. 2.190-32 × .500 Lng. Screw F. H. 4.190-32 × .500 Lng. Screw P. H. 4.190-32 × .375 Lng. Screw P. H. 2.190 Flat Washer Stl. 8.190 Lock Washer Stl. 8Spacer Brass 2Label Digitrip Retrofit 1Auxiliary CT Harness 6502C84G01 1Mounting Pad - 1", Self AdhesiveWire Tie Nylon

Step 9 External Harness 6502C83G__ 1 Except 510 BasicMounting Pad - 1", Self AdhesiveWire Tie Nylon

Step 11 Cell Harness See Pick List 1

NOTE: Due to the wide variety of Breakers and the multiple functions of the Retrofit components, someexcess hardware may remain when the Retrofit is complete.

Step 7(cont.)

From Step 4

From Step 3

From Step 3

From Step 3

Page 34: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

34

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Eaton CoRPoRatIon www.eaton.com

Table 5: Torque Values for General Mounting and Screw Size Conversion

Decimal Size (in) Standard Size Torque (in-lbs) Torque (ft-lbs)

.112 4.40 10 0.8

.138 6.32 18 1.5

.164 8.32 36 3.0

.190 10.32 46 3.8

.250 1/4-20 100 8.3

.312 5/16-18 206 17.2

.375 3/8-16 356 29.7

.438 7/16-14 572 47.7

.500 1/2-13 856 71.3

Table 6: Torque Values for Copper BUS Connectors

Decimal Size (in) Standard Size Torque (in-lbs) Torque (ft-lbs)

.250 1/4-20 60 5

.312 5/16-18 144 12

.375 3/8-16 240 20

.500 1/2-13 600 50

Page 35: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

EATON CORPORATION www.eaton.com 35

A. SensorsB. Trip UnitC. Aux. CT ModuleD. Direct Trip Actuator (DTA)E. CPT TransformerF. Rating PlugG. HV WiresH. Aux. CT Harness

I. Sensor HarnessJ. External HarnessK. Cell Terminal BlockL. Aux. SwitchM. PT ModuleN. CPT HarnessO. Trip Finger(s)

Fig. 66 Retrofit Components

AB

C

D

H

I

J

KL

M

N

O

G

F

E

Page 36: Digitrip Retrofit System for Federal Pioneer 25 H-2 & H-L ...pub/@electrical/documents/content/il33-fhc.pdf · 2 EATON CORPORATION Digitrip Retrofit System for Federal Pioneer 25

Instruction Leaflet IL 33-FHC-4Effective July 2010

Digitrip Retrofit System for Federal Pioneer25 H-2 & H-L and 50/65 H-2 & H-L Breakers

Eaton CorporationElectrical Group1000 Cherrington ParkwayMoon Township, PA 15108United States877-ETN-CARE (877-386-2273)Eaton.com

© 2010 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. IL 33-FHC-4 / TBG000376Part No. IL33-FHCH04July 2010

PowerChain Management is a registered trademark of Eaton Corporation.

All other trademarks are property of their respective owners.

The instructions for installation, testing, maintenance, or repair herein are provided for the use of the product in general commercial applications and may not be appropriate for use in nuclear applica-tions. Additional instructions may be available upon specific request to replace, amend, or supplement these instructions to qualify them for use with the product in safety-related applications in a nuclear facility.

The information, recommendations, descriptions, and safety nota-tions in this document are based on Eaton’s experience and judg-ment with respect to Retrofitting of Power Breakers. This instruction-al literature is published solely for information purposes and should not be considered all-inclusive. If further information is required, you should consult an authorized Eaton sales representative.

The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract. The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton.

NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or conse-quential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its cus-tomers resulting from the use of the information, recommendations and description contained herein.