SINGLE SECTION DIGITAL AXLE COUNTER
MAINTAINENCE OF SSDAC
Presented bySandeep AggarwalTechnical Manager
Central Electronics Ltd.
MAINTENANCE OF SSDAC VERIFY SYSTEM HAS BEEN COMMISSIONED AS PER PRE
COMMISSIONING CHECKLIST & IS PROPERLY SIGNED BY CEL MOVEMENT OF TROLLEY’S HAS BEEN TESTED DURING PARALLEL
WORKING TRAINING PROVIDED TO STAFF SYSTEM PERFORMANCE SHALL BE SENT TO CEL REGULARLY. CONDUCT REGULAR TRAINING SESSIONS AT CEL OR YOUR
TRAINING INSTITUTES BY CEL STAFF.
MEASURE THE Tx COIL (21 KHz & 23 KHz) AND Rx COIL (21 KHz & 23 KHz) SIGNAL LEVELS. THEY SHOULD BE WITHIN LIMITS
MEASURE THE OUTPUT SIGNALS OF CARDS AT THE TEST POINTS PROVIDED ON CARDS
CHECK AND MEASURE THE INPUT POWER SUPPLY TO SSDAC
RESET BOX SHOULD BE INSPECTED FOR ITS PROPER FUNCTIONING
ALL CABLE CONNECTIONS ON THE CT BOARD OF APPARATUS AT LOCATION BOXEX SHOULD BE CHECKED
MAINTAINENCE OF SSDAC (CONTD …)
MAINTENANCE SCHEDULE (MONTHLY)
MAINTAINENCE OF SSDAC (CONTD …)
MAINTENANCE LOG SHEET FOR SSDAC
Kindly check the page 6 of 7 of pre commissioning checklist issued by RDSO
ALL EARTH CONNECTIONS SHOULD BE EXAMINED MONTHLY FOR CONNECTIONS AND SOLDERED JOINTS TO BE IN PROPER CONDITION
ARMOR OF QUAD CABLE SHOULD BE PROPERLY EARTH RESISTANCE OF EVERY EARTH SHOULD BE MEASURED ON
YEARLY BASIS. INSTALLATIONS NEAR SSP & FEEDER POINTS MAY BE
PROPERLY EARTHED
MAINTAINENCE OF SSDAC (CONTD …)
MAINTENANCE & TESTING OF MAINTENANCE FREE EARTHS
RECOMMENDED TOOLKIT
(1 set of tool kit to be purchased separately for every 10 sets of SSDAC systems)
1 Portable data analyzer for downloading event logger data for analysis and report generation.
2 Pure sine wave Digital multimeter make Fluke model 187/ Rishabh model 28S / Kusum Meco model 859CF or Equivalent
3 Train simulator, Model TS 267P CEL make
4 Extender card (Card No. 557)
5 Dummy wheel (as per Drg No. L007750A3, D14)
6 Ring spanner 17-19,24-26
7 Open end spanner 17-19, 24-26
8 Socket spanner with handle
9 Torque wrench (Jaicom JPR65 or equivalent, 88NM)
10 Screw Driver No. 902, 935
11 Marking jig for drilling (Drg No. F008300, on D29& D29A)
RECOMMENDED SPARES
The following spares are to be procured separately for 5 nos. of Single Section Digital Axle Counter working in field1 SCC 1&2 cards (Card 1 & 2) 2 Nos
2 MLB 1&2 cards (Card 3 & 4) 2 Nos
3 Modem card (Card 6) 1 No
4 Relay driver (Card 7) 1 No
5 Event Logger Card (Card 5) 2 Nos
6 DC-DC converter (Card 8) 1 No
7 Axle detectors (AD711) 21 KHz/23KHz (TX coil) 1 No
8 Axle detectors (AD711) 21 KHz/ 23 KHz (Rx coil) 1 No
9 Reset box RB-259 1 No
10 Vital Relay Box with Relay 24V, 1000 ohm, Q type 1 No
11 Surge voltage protection device box (SV-121) 1 No
DO’S & DON’TDO’S The inter connection drawings are to be followed for connecting the Transmitter &
Receiver coils. Tx1 is 21 KHz, Tx2 is 23 KHz & Rx1 and Rx2 coils are 21 KHz & 23 KHz, respectively.
Ensure that Receiver and Transmitter coil cables have been laid in different pipes. Ensure that both the TX coils & Rx coils are having proper alignment on Rail. Ensure that packing of sleepers with ballast on both sides of Axle detector is
proper. Check that metal sheaths of the outdoor cable are connected to earth at both ends The recommended cables for wiring of the system at site should be used. The steady Battery voltage 24V should be maintained. The cable connections should not be connected loosely. The M.S Circular connectors of SSDAC are checked and maintained firmly. The SSDAC & Reset box is provided with sealing arrangement. They should be
sealed at site. Resetting should be done only after ensuring that there is no train in the section
DON’T Don’t install the Axle detectors near the rail joint (should be more than
6 sleepers away). Don’t install the Axle detectors where the rail is badly worn out. Don’t cut or join the Transmitter / Receiver cables supplied along with
the coil. It would result in change of frequency of signal. Don’t lay the TX and RX coil cables in the same pipe. Don’t use any other outdoor cable other than the recommended
cables. Avoid installing the Axle detectors on curve of rail / too much slope of
rail to the possible extent. Don’t remove the cards from SSDAC units under power ON condition
of system. Remove card if necessary after Switching OFF the power to the unit.
TROUBLE SHOOTING OF SSDAC
FAMILIARITY WITH ERROR CODES
10 20
40 80
1 2
4 8
5 6
7 8
1 2
3 4
FRONT VIEW VALUE GIVEN TO LED’s
LSB
MSB
LSB
MSB
COUNT RELATED ERRORS ERRORS RELATED TO WRONG TRAIN MOVEMENT VITAL RELAY RELATED ERRORS HARDWARE SYNCHRONIZATION RELATED ERRORS POWER INTERRUPTION & COMMUNICATION RELATED
ERRORS
TROUBLESHOOTING OF SSDAC (CONTD …)
CLASSIFICATION OF ERROR CODES
COUNT RELATED ERRORS Error code 0x33, 0x34 & 0x35: the remote unit’s error code is checked
and diagnosed Error code 0x36 & 0x37: the Tx/Rx coils and SCC card are to be
checked
TROUBLESHOOTING OF SSDAC (CONTD …)
ERROR DUE TO WRONG WHEEL MOVEMENT Error 0x38 & 0x43: output of coil and SCC cards should be checked. Error 0x44, 0x45, 0x46, 0x47 & 0x48: comes due to formation of non-
overlap pulse. Any movement of trolley in the section should be checked.
VITAL RELAY RELATED ERRORS Error 0x15, 0x50, 0x51, 0x52 & 0x53: the VR should be checked for
proper insertion.
TROUBLESHOOTING OF SSDAC (CONTD …)
POWER & COMMUNICATION RELATED ERRORS Error 0x30: link between the two SSDAC units should be checked. Error 0x40, 0x41, 0x42: the communication media between the local and
remote units should be checked for noise or other interfering element. Surge Devices to be checked
Error 0x3F, 0x7F: reset operation for the local and/or remote unit should be proper
Error 0x80: remote unit should be checked and analyzed for error HARDWARE SYNCHRONIZATION RELATED ERRORS
Error 0x60, 0x62: Reset the system. If problem persists, MLB cards should be replaced
TROUBLESHOOTING OF SSDAC (CONTD …)
IN CASE OF LIGHTNING, THE SVPD DEVICES SHOULD BE CHECKED FOR PROPER WORKING
POWER LINE & RESET LINE SURGE MODULES ARE INDICATIVE TYPE SURGE DEVICES.
MODEM LINE DEVICES ARE NON INDICATIVE TYPE THE DAMAGED MODULE(S), IF FOUND SHOULD BE REPLACED
WITH FRESH MODULE(S) OF SIMILAR TYPE. CONTACT CEL FOR PART NOS
TROUBLESHOOTING OF SSDAC (CONTD …)
PRESENTATION CD INCLUDES
COPY OF SLIDES SSDAC INTRODUCTION SSDAC – MANITENANCE SSDAC - IMPROVEMENTS
INSTALLATION MANUALS OF BOTH AMPLITUDE & PHASE TYPE SSDAC
PRECOMMISSIONING CHECKLIST APPROVED BY RDSO