Cat® C18 DIESEL GENERATOR SETS
LEHE1772-04 1/2
Standby & Prime: 60Hz
PACKAGE PERFORMANCE
Image shown might not reflect actual configuration
Engine Model Cat® C18 ATAAC™ In-line 6, 4-cycle diesel
Bore x Stroke 145mm x 183mm (5.7in x 7.2in)
Displacement 18.13 L (1106.3 in³)
Compression Ratio 14:1
Aspiration Turbocharged Air-to-Air Aftercooled
Fuel Injection System Electronic Unit Injection
Governor Electronic ADEM™ A4
Model Standby Prime Emission Strategy
C18 750 ekW, 938 kVA 680 ekW, 850 kVA EPA TIER II
Performance Standby Prime
Frequency 60 Hz
Genset Power Rating 938 kVA 850 kVA
Genset power rating with fan @ 0.8 power factor 750 ekW 680 ekW
Emissions EPA TIER II
Performance Number EM3842 EM3843
Fuel Consumption
100% load with fan, L/hr (gal/hr) 205.5 (54.2) 188.5 (49.7)
75% load with fan, L/hr (gal/hr) 164.3 (43.4) 146.3 (38.6)
50% load with fan, L/hr (gal/hr) 108.9 (28.7) 100.3 (26.5)
25% load with fan, L/hr (gal/hr) 63.5 (16.7) 59.4 (15.6)
Cooling System1
Radiator air flow restriction (system), kPa (in. Water) 0.12 (0.48) 0.12 (0.48)
Radiator air flow, m3/min (cfm) 900 (31783) 900 (31783)
Engine coolant capacity, L (gal) 20.8 (5.5) 20.8 (5.5)
Radiator coolant capacity, L (gal) 77 (20.3) 77 (20.3)
Total coolant capacity, L (gal) 97.8 (25.8) 97.8 (25.8)
Inlet Air
Combustion air inlet flow rate, m³/min (cfm) 67.3 (2376) 65.6 (2316)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 49 (120) 49 (120)
Exhaust System
Exhaust stack gas temperature, °C (°F) 452.9 (847.2) 432.9 (811.2)
Exhaust gas flow rate, m³/min (cfm) 170.7 (6028) 161 (5686)
Exhaust system backpressure (maximum allowable) kPa (in. water) 10.0 (40.0) 10.0 (40.0)
Heat Rejection
Heat rejection to jacket water, kW (Btu/min) 225 (12795) 208 (11828)
Heat rejection to exhaust (total) kW (Btu/min) 714 (40604) 664 (37761)
Heat rejection to aftercooler, kW (Btu/min) 272 (15468) 253 (14387)
Heat rejection to atmosphere from engine, kW (Btu/min) 142 (8075) 123 (6995)
Cat® C18 DIESEL GENERATOR SETS
Emissions (Nominal)2 Standby Prime
NOx, mg/Nm³ (g/hp-hr) 2468 (5.42) 2213 (4.91)
CO, mg/Nm³ (g/hp-hr) 100.1 (0.22) 75.6 (0.17)
HC, mg/Nm³ (g/hp-hr) 23.5 (0.06) 24.1 (0.06)
PM, mg/Nm³ (g/hp-hr) 11.7 (0.03) 10.6 (0.03)
WEIGHTS & DIMENSIONS
APPLICABLE CODES AND STANDARDS:AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22, NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC. Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for availability.
STANDBY: Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
PRIME: Output available with varying load for an unlimited time. Average power output is 70% of the prime power rating. Typical peak demand is 100% of prime rated ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year
RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions.
DEFINITIONS AND CONDITIONS1 For ambient and altitude capabilities consult your Cat dealer. Air flow restriction
(system) is added to existing restriction from factory.2 Emissions data measurement procedures are consistent with those described
in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.
3 UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.
LEHE1772-04 (05/20)
www.Cat.com/electricpowerAll rights reserved.
Materials and specifications are subject to change without notice.The International System of Units (SI) is used in this publication.© 2020 Caterpillar. All Rights Reserved. CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow”, the “Power Edge” and
Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission
Dim “A” mm (in) Dim “B” mm (in) Dim “C” mm (in) Dry Weight kg (lb)
3512 (138) 1746 (69) 2322 (92) 4863 (10721)
C
A
2/2
B
Alternator3
Voltages 208V 220V 240V 480V 600V
Motor starting capability @ 30% Voltage Dip 1917 skVA 2129 skVA 2501 skVA 2512 skVA 2512 skVA
Current 2602.2 amps 2460.3 amps 2512 amps 1127.6 amps 902.1 amps
Frame Size LC7224N LC7224L LC7224L LC7224L LC7224L
Excitation AREP AREP AREP AREP AREP
Temperature Rise 130 °C 130 °C 130 °C 105 °C 130 °C
1
Attachment
EMCP 4.2B GENERATOR SET CONTROLLER
The Cat® EMCP 4.2B offers fully featured power metering, protective relaying and engine and generator control and monitoring. Engine and generator controls, diagnostics, and operating information are accessible via the control panel keypads; diagnostics from the EMCP 4 optional modules can be viewed and reset through the EMCP 4.2B.
• Wide range of system expansion attachments, designed specifically to work with the EMCP 4
• Flexible packaging options for easy
and cost effective installation
World wide product support
• Cat dealers provide extensive pre and post sale support
• Cat dealers have over 1,600 dealer branch stores operating in 200 countries
• A 33 x 132 pixel, 3.8 inch, white backlit graphical
display denotes text alarm/event descriptions,
set points, engine and generator monitoring, and
is visible in all lighting conditions.
• Textual display with support for 26 languages
• Advanced engine monitoring is available on systems with an ADEM™ controller.
• Integration with the CDVR and IVR provides enhanced system performance
• Fully featured power metering, protective relaying, engine and generator parameter viewing, and expanded AC metering are all integrated into this controller.
• Real-time clock allows for date and time stamping of diagnostics and events in the control’s logs as well as service maintenance reminders based on engine operating hours or calendar days. Up to 40 diagnostic events are stored in the non-volatile memory
LEHE1208-01
Features
• Ability to view and reset diagnostics on EMCP
4 optional modules via the control panel
removes the need for a separate service tool
for troubleshooting
• Set points and software stored in non-volatile
memory, preventing loss during a power
outage
• Five levels of security allow for configurable
operator privileges
• Programmable security levels for groups of
setpoints.
• Programmable kW Relays (3)
• Programmable weekly exerciser timer• Dealer configurable resistive maps• Default overview screen• Real (kW) Load histogram• Auto mains failure• Programmable logic functionality• Selectable units
o Temperature: °C or °Fo Pressure: psi, kPa, baro Fuel Consumption: Liter/hr or Gal/hr
(U.S. or U.K.)
Full range of attachments Features
Pi cture shown may not reflect actual configuration
2
Attachment
Standard Features
• Voltage (L-L, L-N)
• Current (Phase)
• Average Volt, Amp, Frequency
• kW, kVAr, kVA (Average, Phase, %)
• Power Factor (Average, Phase)
• kW-hr, kVAr-hr (total)
• Excitation voltage and current (with
CDVR)
• Desired Voltage, Excitation Command, Operating Mode (with IVR)
• Generator stator and bearing temp (with optional module)
• kW load histogram
Generator Protection
• Generator phase sequence
• Over/Under voltage (27/59)
• Over/Under frequency (81 O/U)
• Reverse Power (kW) (32)
• Reverse Reactive Power (kVAr) (32RV)
• Overcurrent (50/51)
• Thermal Damage Curve
Engine Monitoring
• Coolant temperature
• Oil pressure
• Engine speed (RPM)
• Battery voltage
• Run hours
• Crank attempt and successful start counter
• Enhanced engine monitoring (with electronic engines)
Engine Protection
• Control switch not in auto (alarm)
• High coolant temp (alarm and shutdown)
• Low coolant temp (alarm)
• Low coolant level (alarm)
• High engine oil temp (alarm and shutdown)
• Low, high, and weak battery voltage
• Overspeed
• Overcrank
• Low Oil Pressure
Control
• Run / Auto / Stop control
• Speed and voltage adjust
• Local and remote emergency stop
• Remote start/stop
• Cycle crank
Inputs & Outputs
• Two dedicated digital inputs
• Three analog inputs
• Six programmable digital inputs
• Eight relay out
• Two programmable digital outputs
Communications
• Primary and accessory CAN data links
• RS-485 annunciator data link
• Modbus RTU (RS-485 Half duplex)
Language Support
Environmental
LEHE1208-01
Arabic, Bulgarian, Czech, Chinese, Danish, Dutch, English, Estonian, Finnish, French, German, Greek, Hungarian, Italian, Icelandic, Japanese, Latvian, Lithuanian, Norwegian, Polish, Portuguese, Romanian, Russian, Spanish, Swedish, Turkish
• Control module operating temperature:
-40°C to 70°C
• Display operating temperature: -20°C to 70°C
• Humidity: 100% condensing 30°C to 60°C
• Storage temperature: -40°C to 85°C
• Vibration: Random profile, 24-1000 Hz, 4.3G rms
Standards• UL Recognized• CSA C22.2 No.100,14, 94• Complies with all necessary standards for CE
Certificationo 98/37/EC Machinery Directiveo BS EN 60204-1 Safety of Machinery
89/336/EEC EMC Directiveo BS EN 50081-1 Emissions Standardo BS EN 50082-2 Immunity Standard
73/23/EEC Low Voltage Directiveo EN 50178 LVD Standard
• IEC529, IEC60034-5, IEC61131-3• MIL STND 461
ATTACHMENTS
ULCERT
UL 2200 LISTING
ELECTRICAL OPTIONS
The table below shows electrical options that meet UL requirements:
MECHANICAL OPTIONS
Mechanical options do not require UL Listing and, therefore, are not affected. The exceptions to this are:
FUEL TANKS
If a fuel tank is ordered with the unit, it must be UL Listed. Two versions are available: 24 hour integral (FCUL2) and 24/48 hour sub-base (FSBT)
ENCLOSURES
Factory installed enclosures meet UL requirements. Weatherproof and sound attenuated versions are available.
Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission. www.Cat-ElectricPower.com
©2013 Caterpillar All Rights Reserved
LEHEXXXXXX (01/13) Printed in U.S.A.
INCLUDES THE FOLLOWING:
ALTERNATOR
Alternator insulation system is UL Recognized (UL 1446). PMG and AREP alternators are available. Automatic voltage regulators are UL Recognized.
WIRE HARNESS
AC, DC, and power harnesses are made with UL Listed wire and UL Listed terminals.
CONTROL PANEL
Control panels are comprised of UL Listed and UL Recognized components. EMCP is UL Recognized.
CIRCUIT BREAKER
Output circuit breaker is 100% rated and UL Listed.
TESTING
All UL Listed sets are designed and rigorously tested in accordance with UL Standard for Safety, UL 2200.
LABELING
Labeling meets UL requirements.
EBH Battery Heater
EOS Lube Oil Sump Heater
WCA1 Low Coolant Level Shutdown
WSS1 Low Coolant Temperature Alarm
AH1H Anti-Condensation Heater
WHH Coolant Heater
GOVE5 Electronic Governor (Fully Adjustable)
FSS1 Critical Low Fuel Level Shutdown
FSS2 Low Fuel Level Alarm
FSS5 Critical High Fuel Alarm
PBC5UL UL Listed Battery Charger
PBC10NU NFPA Battery Charger, UL Listed
UL Listing is available on all diesel fuelled generator sets up to 175 kW at 60 Hz, 600 vac maximum.
LEHE0410-00 (01/13)
Enclosures
LEHE0465-09 1/7
C13/C15/C18 SOUND ATTENUATED ENCLOSURESUS Sourced Diesel Generator Set 350 - 750 ekW 60 Hz
FeaturesRobust/Highly Corrosion Resistant Construction• Factory installed on skid base• Environmentally friendly, polyester powder baked paint• 14 gauge steel• Interior zinc plated fasteners• Exterior stainless steel fasteners• Internally mounted exhaust silencing system• Designed and tested to comply with UL 2200 Listed generator set
package• Compression door latches providing solid door seal
Excellent Access• Large cable entry area for installation ease• Accommodates side mounted single or multiple breakers• Three doors on both sides• Vertically hinged allow 180° opening rotation and retention with
door stays• Lube oil and coolant drains piped to the exterior of the enclosure
base• Radiator fill cover
Security and Safety• Lockable access doors which give full access to control panel and
breaker• Cooling fan and battery charging alternator fully guarded• Fuel fill, oil fill and battery can only be reached via lockable access• Externally mounted emergency stop button• Designed for spreader bar lifting to ensure safety• Stub-up area is rodent proof
TransportabilityThese enclosures are of extremely rugged construction to withstand outdoor exposure and rough handling common on many construction sites.
Options• Enclosure constructed with 14 gauge steel• Enclosure constructed with 12 gauge aluminum (5052 grade)• Caterpillar yellow or white paint• Control panel viewing window• UL Listed integral fuel tank with 670, 400, and 300 gallon
capacities• UL Listed sub base fuel tank with 660, 1000, 1900, and 2200
gallon capacities.• Seismic certification per applicable building codes: IBC 2000, IBC
2003, IBC 2006, IBC 2009, IBC 2012, IBC 2015 CBC 2007, CBC 2010• IBC Certification for 150 mph wind loading• AC/DC lighting package• 5 kW Canopy space heater to facilitate compliance with NFPA 110• Motorized louvers and gravity discharge damper• 125A Load Center• GFCI outlets*Not available with aluminum enclosures.
Picture shown may not reflect actual configuration
Enclosures
LEHE0465-09 2/7
Level 1 Sound Attenuated Enclosure (Steel) Sound Levels
Sound Attenuated Enclosure (Aluminum) Sound Levels
Model Standby eKWCooling Air Flow Rate Ambient Capability* Sound Pressure Levels
(dBA) at 7m (23 ft)
m3/s cfm ˚C ˚F 100% Load
C13350 8.5 18010 57 135 74
400 8.5 18010 56 133 75
C15
350 10.4 22072 59 138 73
400 10.4 22072 51 124 73
450 10.4 22072 46 115 74
500 12.5 26415 48 118 75
C18
550 8.1 17234 45 113 75
600 8.1 17234 43 109 75
650 12.7 26909 51 123 75
700 12.7 26909 48 118 75
750 12.7 26909 48 118 75
Model Standby eKWCooling Air Flow Rate Ambient Capability* Sound Pressure Levels
(dBA) at 7m (23 ft)
m3/s cfm ˚C ˚F 100% Load
C13350 8.5 - 57 135 75
400 8.5 - 56 133 75
C15
350 10.4 22072 59 138 72
400 10.4 22072 51 124 73
450 10.4 22072 46 115 74
500 12.5 26415 48 118 75
C18
550 8.1 17234 45 113 76
600 8.1 17234 43 109 76
650 12.7 26909 51 123 76
700 12.7 26909 48 118 76
750 12.7 26909 48 118 76
Enclosures
LEHE0465-09 3/7
Level 2 Sound Attenuated Enclosure (Steel) Sound Levels
Component Weights to Calculate Package Weight
Sound Attenuated Enclosure on Skid Base
Model Standby eKWCooling Air Flow Rate Ambient Capability* Sound Pressure Levels
(dBA) at 7m (23 ft)
m3/s cfm ˚C ˚F 100% Load
C13350 7.2 15256 50 122 70
400 7.2 15256 50 122 70
C15
350 10.4 22071 50 122 72
400 10.4 22071 50 122 72
450 10.4 22071 50 122 72
500 12.5 26415 50 122 72
Model Standby eKW
Narrow Skid Base Wide Skid Base Sound Attenuated Enclosure (Steel)
Sound Attenuated Enclosure (Aluminum)
kg lb kg lb kg lb kg lb
C13350
253 578 579 1276 1245 2745 765 1687400
C15
350
273 602 465 1025 1245 2745 765 1687400
450
500
C18
550301 664 466 1027 1301 2868 817 1801
600
650
286 630 637 1404 1393 3071 887 1955700
750
Model Standby eKWLength “L” Width “W” Height “H”
mm in mm in mm in
C13350
4948 194.8 2014 79.3 2320 91.3400
C15
350
4948 194.8 2014 79.3 2320 91.3400
450
500
C18
5505183 204.0 2014 79.3 2262 89.0
600
650
5230 205.9 2315 91.1 2253 88.7700
750
*Cooling system performance at sea level. Consult your Cat® dealer for site specific ambient and altitude capabilities.Note: Sound level measurements are subject to instrumentation, installation and manufacturing variability, as well as ambient site conditions.
Enclosures
LEHE0465-09 4/7
Sound Attenuated Enclosure on a UL Listed Integral Fuel Tank Base
Model Standby eKWLength “L” Width “W” Height “H”
mm in mm in mm in
C13350
5461 215.0 2014 79.3 2743 108.0400
C15
350
4948 194.8 2014 79.3 2619 103.0400
450
500
C18
5505187 204.2 2014 79.3 2561 101.0
600
650
6977 274.7 2315 91.1 2675 105.3700
750
ATTACHMENTS
Picture shown may not represent actual package
C13 / C15 / C18 Integral and Sub-Base Fuel Tanks
US Sourced Diesel Generator Set
350 - 750 ekW 60 Hz
Features
• UL Listed for United States (UL 142) and Canada (CAN/ULC S601)• Facilitates compliance with NFPA 30 code, NFPA 37 and 110 standards and CSA C282 code• Dual wall• Lockable fuel fill cap, 4" (101.6 mm) NPT• Low fuel level warning standard, customer configurable warning or shutdown• Primary tank leak detection switch in containment basin• Tank design provides capacity for thermal expansion of fuel• Fuel supply dip tube is positioned so as not to pick up fuel sediment• Fuel return and supply dip tube is separated by an internal baffle to prevent immediate re-supply of
heated return fuel• Pressure washed with an iron phosphate solution• Interior tank surfaces coated with a solvent-based thin-film rust preventative• Heavy gauge steel gussets with internal lifting rings• Primary and secondary tanks are leak tested at 20.7 kPa (3 psi) minimum• Compatible with open packages and enclosures• Gloss black polyester alkyd enamel exterior paint• Welded steel containment basin (minimum of 110% of primary tank capacity)• Direct reading fuel gauge with variable electrical output• Emergency vents on primary and secondary tanks are sized in accordance with NFPA 30
Sub Base • The sub-base fuel tank mounts below the generator set wide base
Integral • Integral diesel fuel tank is incorporated into the generator set base frame• Robust base design includes linear vibration isolators between tank base and engine generator
Options • Audio/visual fuel level alarm panel• 5 gal (18.9 L) spill containment• 5 gal (18.9 L) spill containment with fuel fill drop tube with in 6" (152 mm) from bottom of tank• 5 gal (18.9 L) spill containment with overfill prevention valve and fuel fill drop tube with in 6" (152 mm)
from bottom of tank• ULC Listed 7.5 gal (28.4 L) spill containment with vent extensions, vent whistle, and drop tube facilitating
compliance with CSA 8139-09• ULC Listed 7.5 gal (28.4 L) spill containment with overfill prevention valve, vent extensions, vent whistle
and drop tube facilitating compliance with CSA 8139-09LEHE0467-08 Page 1 of 5
ATTACHMENTS
Integral & Sub-Base Fuel Tank Base Useable Capacities with
Fuel Tank Dimensions & Weights
Integral - Width (W) 2014 mm (79.3 in)
Sub-base - Width (W) 2056 mm (81.0 in)
Integral* - Width(W) 2315 mm (91.2 in)
Sub-base*-Width(W) 2357 mm (92.7in)
Open Set & Weather Protective Enclosure
C13 Tank
Design
Feature
Code
Total
Capacity
Useable
Capacity
Tank Only
Overall Package Height
with Tank
Dry Weight Height 'H' Length 'L' Open Enclosure
Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in
Integral FTDW013 2646 699 2540 671 1569 3450 762 30.0 5461 215 2552 100.5 2743 108.0
Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 2763 108.8 2955 116.3
Sub-Base FTDW006 6980 1844 6818 1801 2228 4483 889 35.0 6184 243.5 3017 118.8 3209 126.3
Sub-Base FTDW007 8339 2203 8244 2178 2150 5052 889 35.0 7074 278.5 2291 117.8 3789 149.2
Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 2763 108.8 2955 116.3
C15 Tank
Design
Feature
Code
Total
Capacity
Useable
Capacity
Tank Only
Overall Package Height
with Tank
Dry Weight Height 'H' Length 'L' Open Enclosure
Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in
Integral FTDW002 1283 339 1262 333 1015 2237 635 25.0 3814 150.1 2426 95.5 2619 103.0
Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 2763 108.8 2955 116.3
Sub-Base FTDW006 6980 1844 6818 1801 2228 4912 889 35.0 6184 243.5 3017 118.8 3209 126.3
Sub-Base FTDW008 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 2763 108.8 2955 116.3
C18 Tank
Design
Feature
Code
Total
Capacity
Useable
Capacity
Tank Only
Overall Package Height
with Tank
Dry Weight Height 'H' Length 'L' Open Enclosure
Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in
Integral FTDW004 1446 382 1422 376 1015 2237 635 25.0 3814 150.1 2426 95.5 2560 100.8
Integral* FTDW030 2498 660 2377 628 1681 3703 762 30.0 4995 196.6 2670 105.1 2675 105.3
Integral* FTDW031 5175 1367 4997 1320 2046 4510 762 30.0 6737 265.3 2670 105.1 2675 105.3
Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 2763 108.8 2955 116.3
Sub-Base FTDW007 8339 2203 8244 2178 2150 4134 889 35.0 7074 278.5 2291 117.8 3159 124.4
Sub-Base FTDW008 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 2739 107.9 2905 114.4
Sub-Base* FTDW032 10228 2702 10112 2640 2638 5816 889 35.0 7368 290 3127 123.1 3132 123.3
LEHE0467-08 Page 2 of 5
ATTACHMENTS
Integral & Sub-Base Fuel Tank Base Useable Capacities with
Fuel Tank Dimensions & Weights
Integral - Width(W) 2014 mm (79.3 in)
Sub-base - Width(W) 2056 mm (81 in)
Integral* - Width(W) 2315 mm (91.2 in)
Sub-base*-Width(W) 2357 mm (92.7in)
Sound Attenuated Enclosure
C13 Tank
Design
Feature
Code
Total
Capacity
Useable
Capacity
Tank Only
Overall Package Height
with Tank
Dry Weight Height 'H' Length 'L' Open Enclosure
Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in
Integral FTDW013 2646 699 2540 671 1569 3450 762 30.0 5461 215.0 NA NA 2743 108.0
Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 NA NA 2955 116.3
Sub-Base FTDW006 6980 1844 6818 1801 2033 4483 889 35.0 6184 243.5 NA NA 3209 126.3
Sub-Base FTDW007 8339 2203 8244 2178 2292 5052 889 35.0 7074 278.5 NA NA 3209 126.3
Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 NA NA 2955 116.3
C15 Tank
Design
Feature
Code
Total
Capacity
Useable
Capacity
Tank Only
Overall Package Height
with Tank
Dry Weight Height 'H' Length 'L' Open Enclosure
Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in
Integral FTDW001 1283 339 1262 333 1015 2237 639 25.0 4746 186.9 NA NA 2619 103.0
Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 NA NA 2955 116.3
Sub-Base FTDW006 6980 1844 6818 1801 2228 4912 889 35.0 6184 243.5 NA NA 3209 126.3
Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 NA NA 2955 116.3
C18 Tank
Design
Feature
Code
Total
Capacity
Useable
Capacity
Tank Only
Overall Package Height
with Tank
Dry Weight Height 'H' Length 'L' Open Enclosure
Liter Gallon Liter Gallon kg lb mm in mm in mm in mm in
Integral FTDW003 1446 382 1422 376 1015 2237 635 25.0 3814 150.1 NA NA 2560 100.8
Integral* FTDW030 2498 660 2381 629 1681 3703 762 30.0 4995 196.6 2670 105.1
2675 105.3
Integral* FTDW031 5175 1367 4997 1320 2046 4510 762 30.0 6737 265.3 NA NA 2675 105.3
Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 NA NA 2905 114.3
Sub-Base FTDW007 8339 2203 8244 2178 2150 4134 889 35.0 7074 278.5 NA NA 3209 126.3
Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 NA NA 2905 114.3
Sub-Base* FTDW032 10228 2702 9994 2640 2638 5816 889 35.0 7368 290 NA NA 3132 123.3
LEHE0467-08 Page 3 of 5
ATTACHMENTS
The heights listed above do not include lumber used during manufacturing and shipping.
Estimated Run Times (Hours) at 100% Load
C13 Tank
Design Feature Code
Standby Ratings (ekW) Prime Ratings (ekW)
400 350 – – 350 320 – –
Integral FTDW013 24 27 - - 25 29 - -
Sub-Base FTDW005 36 41 - - 38 43 - -
Sub-Base FTDW006 65 72 - - 72 77 - -
Sub-Base FTDW007 77 87 - - 81 93 - -
Sub-Base FTDW011 23 25 - - 24 27 - -
C15 Tank
Design Feature Code
Standby Ratings (ekW) Prime Ratings (ekW)
500 450 400 350 455 410 365 320
Integral FTDW001 / FTDW002 9 9 11 11 10 10 11 12
Sub-Base FTDW005 28 29 32 36 30 31 35 38
Sub-Base FTDW006 50 52 57 63 54 56 62 67
Sub-Base FTDW008 / FTDW011 17 18 20 22 19 20 22 24
C18 Tank
Design Feature Code
Standby Ratings (ekW) Prime Ratings (ekW)
750 700 650 600 550 680 635 600 545 500
Integral FTDW003 / FTDW004 - - - 8 9 - - - 9 10
Integral* FTDW030 11 12 13 - - 12 13 14 - -
Integral* FTDW031 24 25 27 - - 26 27 29 33 36
Sub-Base FTDW005 - - - 24 25 - - - 25 27
Sub-Base FTDW007 - - - 51 54 - - - 54 59
Sub-Base FTDW008 / FTDW011 - - - 15 16 - - - 16 17
Sub-Base* FTDW032 49 51 54 - - 53 55 58 - -
LEHE0467-08 Page 4 of 5
ATTACHMENTS
Tanks with full electrical stub-up area include removable end channel. Tanks with RH stub-up include stub- up area directly below the circuit breaker or power terminal strips. Dimensions include weather-protective enclosure exhaust system.
Dual wall sub-base tanks are UL Listed and constructed in accordance with UL Standard for Safety UL 142, Steel Aboveground Tanks for Flammable and Combustible Liquids and Canada CAN/ULC S601, Standard for Shop Fabricated Steel Aboveground Horizontal Tanks for Flammable and Combustible Liquids.
Fuel tanks and applicable options facilitate compliance with the following United States NFPA Code and Standards:
NFPA 30: Flammable and Combustible Liquids Code
NFPA 37: Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines
NFPA 110: Standard for Emergency and Standby Power Systems
Fuel tanks and applicable options facilitate compliance with the following Canadian Standard and Code:
CSA C282 - Emergency Electrical Power Supply for Buildings
CSA B139-09 - Installation Code for Oil-Burning Equipment
The following sub-base fuel tanks meet Chicago code for containment and labelling:
FTDW005
FTDW008
FTDW011
LEHE0467-08 (03/20)
www.cat.com/electricpower ©2020 Caterpillar
All rights reserved.
LEHE0942-01 Page 1 of 2
Construction robuste et durable
C9 ACERT™, C13 ACERT, C15 ACERT, C18 ACERT Circuit Breakers
Circuit Breakers
Manually Operated Circuit Breakers
Current(A) Frame
Number of Poles
Interrupting Ratings (kA rms) TripUnits
(Lugs) Cable Size Range / Phase Auxiliary Options240V 480V 600V
250 T4N 3 65 25 18
Electronic LS/I
(S or I)or
LSI
(1) 6 AWG – 350 kcmil 1 Form C + 1 Bell Alarm
250VAC/VDC
Shunt Trip 24VDC
400 T5N 3 65 25 18 (2) 3/0 – 250 kcmil
600 T6N 3 65 35 20 (3) 2/0 – 400 kcmil
800 T6N 3 65 35 20 (3) 2/0 – 400 kcmil
1 Form C + 1 Bell Alarm 400VAC / 250VDC
Shunt Trip 24VDC1200 T7S 3 65 50 25 (4) 4/0 – 500 kcmil
1600 R 3 65 35 18
Electronic LSI
BUS BARForm C (1NO + 1NC)
Shunt Trip 24VDC2000 R 3 65 35 18 BUS BAR
2500 R 3 65 35 18 BUS BAR
Electrically Operated Circuit Breakers
Current(A) Frame
Number of Poles
Interrupting Ratings (kA rms) TripUnits
(Lugs) Cable Size Range / Phase Auxiliary Options240V 480V 600V
800 T7M-S 3 65 50 25Electronic
LSI
(4) 4/0 – 500kcmil
2 Form C + 1 BellAlarm 24VDC
1200 T7M-S 3 65 50 25 (4) 4/0 – 500 kcmil
2 Form C + 1 BellAlarm 24VDC
Circuit Breakers
LEHE0942-01 (04/16)
Materials and specifications are subject to change without notice.CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,
the “Power Edge” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
www.Cat-ElectricPower.com©2016 Caterpillar
All rights reserved.
Single Breaker Options (250 – 2500A)
Model Current (A) Operation
C9 ACERT™ 250 Manually Operated
C9 ACERT 400 Manually Operated
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 600 Manually Operated
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 800 Manually Operated or Electrically Operated
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 1200 Manually Operated or Electrically Operated
C13 ACERT, C15 ACERT, C18 ACERT 1600 Manually Operated
C15 ACERT, C18 ACERT 2000 Manually Operated
C18 ACERT 2500 Manually Operated
Multiple Breaker Options
Model
Main Breaker Box Auxiliary Box
1st Breaker (Amps)
2nd Breaker (Amps)
Breaker(Amps)
ManuallyOperated
ManuallyOperated Manually Operated
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 250
250, 400, 600, 800, or 1200
3rd Breaker:250 or 400
(Not available if1st & 2nd Breaker = 1200A)
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 400
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 600
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 800
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 1200
C13 ACERT, C15 ACERT, C18 ACERT 1600
Not Available2nd Breaker:250 or 400
C15 ACERT, C18 ACERT 2000
C18 ACERT 2500
LEHE0141-05 Page 1 of 2
Battery Charger
Features ● Electronicallycurrentlimitedat105%ofrated
output● Alarmsystem● Digitaldisplay● Lightningandvoltagetransientprotection● Protectionofconnectedequipmentagainst
loaddumpprotection● Constantvoltage,currentlimited,4-rate
automaticequalization● IP20housing● Temperaturecompensation● Onboardtemperaturesensorwithremoteport● AutoAClinecompensation● Outputregulatedbysensedbatteryvoltage
Standards● C-ULlistedtoUL1236● NFPA70,NFPA110● CSA22.2No107certified● CEDOCtoEN60335● IBCSeismicCertification
UL 10 AmpBattery ChargerThisbatterychargeroffersaccurate,automaticchargingoflead-acidandnickelcadmiumbatteries.Theoutputvoltageautomaticallyadjuststochanginginput,load,batteryandambientconditions.Thispreventsbatteryover-chargingandconsequentlossofbatteryelectrolyte.
StandardfeaturesincludeAClinecompensation,precisionvoltageregulation,currentlimiting,automatic2-ratecharging,voltmeterandammeter,temperaturecompensationandULListing.
Theuserinterfaceiseasytounderstandwithdigitalmetering,NFPA110alarmsandabatteryfaultalarm.
ImageShownmaynotReflectActualPackage.
Battery Charger
Informationcontainedinthispublicationmaybeconsideredconfidential.Discretionisrecommendedwhendistributing.Materialsandspecificationsaresubjecttochangewithoutnotice.
CAT,CATERPILLAR,LET’SDOTHEWORK,theirrespectivelogos,“CaterpillarYellow,”the“PowerEdge”andCat“ModernHex”tradedressaswellascorporateandproductidentityusedherein,aretrademarks
ofCaterpillarandmaynotbeusedwithoutpermission.
www.cat,com/electricpower©2019CaterpillarAllrightsreserved.
Specifications Inputsupply 110 – 120 V
208 – 240 V
ACandDCfuses 2inputand2output)
Outputvoltage 24V
Outputamps 10
Frequency 50/60Hz
Operatingtemperature -20°C(-4°F)to+60°C(140°F)
HousingconstructedofrustproofanodizedAluminum
Dimensions
Width Depth Height Weight
195mm(7.66in) 165mm(6.5in) 318mm(12.5in) 10.4kg(23lb)
NFPA110alarmpackageasfollows:
● ACon Greenled(indication)● ACfail RedledandformCcontact(2A)● Floatmode LED● Fastcharge LED● Tempcompactive LED● Lowbatteryvolts RedledandFormCconta● HighBatteryVolts RedledandFormCconta● Chargerfail RedledandFormCconta● Batteryfault RedledandFormCconta● Batterydisconnected● Batterypolarityreversed● Mismatchedchargerbatteryvoltage● Openorhighresistancechargertobatteryconnection● Openbatterycellorexcessiveinternalresistance
Feature Codes:BTC1024BTC1028BTC1035BTC1025BTC1032
LEHE0141-05 (02/19)
ATTAC
LEHE0
FEATURE
FACTORY
Comple
Isolatedextreme
Optimizfor max
Remoteoptimize100° F (
Automavia a depanel.
Supplie
Compat
All parts
Incoloy
Ima
CHMENT
0297-01
ES
INSTALLED
ete with silicon
d tank heater e limits to gua
zed location oimum coolant
e pilot thermosed power cyc(37.8°C)
atically disconedicated heate
d with UL rec
tible with Cat®
s are servicea
heater eleme
age Shown may n
TS
ne hoses
vibration andarantee durab
f the heater ot flow
stat located ole efficiency i
nected whener relay locate
cognized com® ELC and all
able and field
ent for longer
not Reflect Actua
shock testedbility
on the genset
on the engine s factory set t
engine is runed in the cont
ponents
l chemicals
replaceable
service life
al Package
d to
base
forto
nningtrol
Ro1
Ar
S
C1He
Factostartimetaremosilicocommheatemaxi
Remote pilot optimized pow100° F (37.8°
Automaticallyrunnune cont
Rating
Frequency
Phase
Amps
Feature Code
SPECIFICAT
15 and eater
ory installed jing capability
al heater with ote engine moone hoses andmon connectier and thermomum coolant
thermostat lower cycle effic°C
y disconnectetrol panel
Unit Spe
208
2250
50/60 Hz
1
10.82
IONS
C18 Ja
acket water h. The system an integral hi
ounted controd heater contion point in thostat locationt flow and hea
ocated on the ciency is facto
ed when the e
ecifications
Design Vo
220
2520
z 50/60 H
1
11.45
JWH005JWH005JWHD03
acket W
heater for incrincludes a ta
igh limit thermol thermostat, trol relay wirehe control pan is optimized ating power e
engine for ory set to
engine is
ltage
240
3000
Hz 50/60 H
1
12.5
585932
Water
reased cold-ank-stylemostat and a
durabled to a
nel. The for
efficiency.
0
Hz
C15 and C18 Jacket Water Heater . Factory installed jacket water heater for increased
cold-starting capability. The system includes a tank-
style metal heater with an integral high limit
thermostat and a remote engine mounted control
thermostat, durable silicone hoses and heater control
relay wired to a common connection point in the
control panel. The heater and thermostat location is
optimized for maximum coolant flow and heating
power efficiency.
ATTACHMENTS
LEHE0297-01 2
WIRING DIAGRAMS
Wiring diagram reference for 240V Line to Neutral power connection
Wiring diagram reference for 240V or 208V Line to Line and 120V Line to Neutral power connection (Note: Including Optional Space Heater and Battery Charger)
ATTACHMENTS
LEHE0297-01 3
HEATER OPERATION
The heater uses compliant components to UL and CSA, and is both CSA and UL approved.
When the generator set is not running, the heater is automatically connected to the AC supply through a power relay mounted in the control panel. Upon receiving a start signal, the AC supply is automatically disconnected by the power relay and automatically reconnected when the start signal is removed and the engine has stopped.
Pilot thermostat located on the engine precisely monitors and controls the engine coolant temperature and is wired to energize and de-energize heater power cycles.
A high-limit thermostat is built into the heater to regulate the output temperature to within safe limits.
HEATER DETAIL
Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
www.Cat-ElectricPower.com
LEHE0297-01 (05/13) ©2013 Caterpillar All Rights Reserved.
Printed in U.S.A.
G E N E R A T O R S
www.cat-ElectricPower.comMarket: N. America
Information contained in this publication may be considered confidential. © 2005 Caterpillar LEHE4017 (01-05) Discretion is recommended when distributing. All Rights Reserved.
Materials and specifications are subject to change without notice. Printed in U.S.A.
GENERATOR ANTI-CONDENSATIONHEATER AH1H
Appropriate when the generator set is to be sited ina low ambient and/or high humidity environment,the heater maintains the AC generator at a suitabletemperature to prevent winding corrosion dueto condensation.
The heater itself is powered by a 110/120 volt(VAC 120) or 208/240 volt (VAC 240) AC auxiliarysupply protected by a fuse inside the main controlpanel. When the generator set is not running theheater is automatically connected to the AC supplythrough a power relay mounted in the controlpanel. Upon receiving a start signal the AC supplyis automatically disconnected by the power relayand automatically reconnected when the startsignal is removed and the engine has stopped.
SELF5709
Effective with sales to the first user on or after August 1, 2016
CATERPILLAR LIMITED WARRANTYIndustrial, Petroleum, Locomotive, and Agriculture Engine Products and Electric Power
Generation ProductsWorldwide
Caterpillar Inc. or any of its subsidiaries (“Caterpillar”) warrants new and
remanufactured engines and new and rebuild electric power generation
products sold by it (including any products of other manufacturers
packaged and sold by Caterpillar), to be free from defects in material
and workmanship.
This warranty does not apply engines sold for use in on-highway vehicle or
marine applications; engines in machines manufactured by or for Caterpillar;
C175, 3500 and 3600 series engines used in locomotive applications; 3000
Family engines, C0.5 through C4.4 and ACERT™ (C6.6, C7, C7.1, C9,
C9.3, C11, C13, C15, C18, C27, and C32) engines used in industrial, mobile
agriculture and locomotive applications; or Cat®
batteries; or Electric Power
Generation Products manufactured or assembled in India. These products
are covered by other Caterpillar warranties.
This warranty is subject to the following:
Warranty Period
• For industrial engines, engines in a petroleum applications
or Petroleum Power Systems (excluding petroleum fire
pump application), or engines in a Locomotive application, or
Uninterruptible Power Supply (UPS) systems, the warranty period
is 12 months after date of delivery to the first user.
• For engines used in petroleum fire pump and mobile agriculture
applications the warranty period is 24 months after date of delivery
to the first user.
• For controls only (EPIC), configurable and custom switchgear
products, and automatic transfer switch products, the warranty
period is 24 months after date of delivery to the first user.
• For new CG132, CG170 and CG260 series power generation
products the warranty period is 24 months/16,000 hours, whichever
comes first, after date of delivery to first user.
• For electric power generation products other than CG132, CG170
and CG260 series in prime or continuous applications the warranty
period is 12 months. For standby applications the warranty period
is 24 months/1000 hours. For emergency standby applications the
warranty period is 24 months/400 hours. All terms begin after date
of delivery to the first user.
• For Caterpillar rebuild electric power generation products the
warranty period is 12 months, but not to exceed 24 months
from shipment of rebuilt electric power generation product from
Caterpillar.
• For all other applications the warranty period is 12 months after
date of delivery to the first user.
Caterpillar Responsibilities
If a defect in material or workmanship is found during the warranty
period, Caterpillar will, during normal working hours and at a place of
business of a Cat dealer or other source approved by Caterpillar:
• Provide (at Caterpillar’s choice) new, Remanufactured, or
Caterpillar approved repaired parts or assembled components
needed to correct the defect.
Note: New, remanufactured, or Caterpillar approved repaired parts or
assembled components provided under the terms of this warranty
are warranted for the remainder of the warranty period applicable
to the product in which installed as if such parts were original
components of that product. Items replaced under this warranty
become the property of Caterpillar.
• Replace lubricating oil, filters, coolant, and other service items
made unusable by the defect.
• Provide reasonable and customary labor needed to correct
the defect, including labor to disconnect the product from and
reconnect the product to its attached equipment, mounting, and
support systems, if required.
For new 3114, 3116, and 3126 engines and, new and Caterpillar rebuild
electric power generation products (which includes the following: any
new products of other manufacturers packaged and sold by Caterpillar)
• Provide travel labor, up to four hours round trip, if in the opinion
of Caterpillar, the product cannot reasonably be transported to
a place of business of a Cat dealer or other source approved by
Caterpillar (travel labor in excess of four hours round trip, and any
meals, mileage, lodging, etc. is the user’s responsibility).
For all other products:
• Provide reasonable travel expenses for authorized mechanics,
including meals, mileage, and lodging, when Caterpillar chooses
to make the repair on-site.
User Responsibilities
The user is responsible for:
• Providing proof of the delivery date to the first user.
• Labor costs, except as stated under “Caterpillar Responsibilities,”
including costs beyond those required to disconnect the product
from and reconnect the product to its attached equipment,
mounting, and support systems.
• Travel or transporting costs, except as stated under “Caterpillar
Responsibilities.”
• Premium or overtime labor costs.
• Parts shipping charges in excess of those that are usual and
customary.
• Local taxes, if applicable.
• Costs to investigate complaints, unless the problem is caused by a
defect in Caterpillar material or workmanship.
• Giving timely notice of a warrantable failure and promptly making
the product available for repair.
• Performance of the required maintenance (including use of proper
fuel, oil, lubricants, and coolant) and items replaced due to normal
wear and tear.
• Allowing Caterpillar access to all electronically stored data.
Limitations
Caterpillar is not responsible for:
• Failures resulting from any use or installation that Caterpillar
judges improper.
• Failures resulting from attachments, accessory items, and parts
not sold or approved by Caterpillar.
• Failures resulting from abuse, neglect, and/or improper repair.
• Failures resulting from user’s delay in making the product available
after being notified of a potential product problem.
• Failures resulting from unauthorized repairs or adjustments, and
unauthorized fuel setting changes.
• Damage to parts, fixtures, housings, attachments, and accessory
items that are not part of the engine, Cat Selective Catalytic
Reduction System or electric power generation product (including
any products of other manufacturers packaged and sold by
Caterpillar).
• Repair of components sold by Caterpillar that is warranted directly
to the user by their respective manufacturer. Depending on type of
application, certain exclusions may apply. Consult your Cat dealer
for more information.
(Continued on reverse side…)
SELF5709
This warranty covers every major component of the products. Claims under this warranty should be submitted to a
place of business of a Cat dealer or other source approved by Caterpillar. For further information concerning either
the location to submit claims or Caterpillar as the issuer of this warranty, write Caterpillar Inc., 100 N. E. Adams St.,
Peoria, IL USA 61629.
Caterpillar’s obligations under this Limited Warranty are subject to, and shall not apply in contravention of, the laws,
rules, regulations, directives, ordinances, orders, or statutes of the United States, or of any other applicable jurisdiction,
without recourse or liability with respect to Caterpillar.
A) For products operating outside of Australia, Fiji, Nauru, New Caledonia, New Zealand, Papua New Guinea, the Solomon Islands and Tahiti, the following is applicable:
NEITHER THE FOREGOING EXPRESS WARRANTY NOR ANY OTHER WARRANTY BY CATERPILLAR,
EXPRESS OR IMPLIED, IS APPLICABLE TO ANY ITEM CATERPILLAR SELLS THAT IS WARRANTED DIRECTLY
TO THE USER BY ITS MANUFACTURER.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED,
INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE,
EXCEPT CATERPILLAR EMISSION-RELATED COMPONENTS WARRANTIES FOR NEW ENGINES, WHERE
APPLICABLE. REMEDIES UNDER THIS WARRANTY ARE LIMITED TO THE PROVISION OF MATERIAL AND
SERVICES, AS SPECIFIED HEREIN.
CATERPILLAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.
CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON ITS PART
OR ON THE PART OF ANY OF ITS EMPLOYEES, AGENTS OR REPRESENTATIVES IN RESPECT OF THE
MANUFACTURE OR SUPPLY OF GOODS OR THE PROVISION OF SERVICES RELATING TO THE GOODS.
IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE INTERNATIONAL SALE
OF GOODS IS EXCLUDED IN ITS ENTIRETY.
For personal or family use engines or electric power generation products, operating in the USA, its territories and
possessions, some states do not allow limitations on how long an implied warranty may last nor allow the exclusion
or limitation of incidental or consequential damages. Therefore, the previously expressed exclusion may not apply to
you. This warranty gives you specific legal rights and you may also have other rights, which vary by jurisdiction. To
find the location of the nearest Cat dealer or other authorized repair facility, call (800) 447-4986. If you have questions
concerning this warranty or its applications, call or write:
In USA and Canada: Caterpillar Inc., Engine Division, P. O. Box 610, Mossville, IL 61552-0610, Attention: Customer
Service Manager, Telephone (800) 447-4986. Outside the USA and Canada: Contact your Cat dealer.
B) For products operating in Australia, Fiji, Nauru, New Caledonia, New Zealand, Papua New Guinea, the Solomon Islands and Tahiti, the following is applicable:
THIS WARRANTY IS IN ADDITION TO WARRANTIES AND CONDITIONS IMPLIED BY STATUTE AND OTHER
STATUTORY RIGHTS AND OBLIGATIONS THAT BY ANY APPLICABLE LAW CANNOT BE EXCLUDED,
RESTRICTED OR MODIFIED (“MANDATORY RIGHTS”). ALL OTHER WARRANTIES OR CONDITIONS, EXPRESS
OR IMPLIED (BY STATUTE OR OTHERWISE), ARE EXCLUDED. WITHOUT LIMITING THE FOREGOING
PROVISIONS OF THIS PARAGRAPH, WHERE A PRODUCT IS SUPPLIED FOR BUSINESS PURPOSES, THE
CONSUMER GUARANTEES UNDER THE CONSUMER GUARANTEES ACT 1993 (NZ) WILL NOT APPLY.
NEITHER THIS WARRANTY NOR ANY OTHER CONDITION OR WARRANTY BY CATERPILLAR, EXPRESS
OR IMPLIED (SUBJECT ONLY TO THE MANDATORY RIGHTS), IS APPLICABLE TO ANY ITEM CATERPILLAR
SELLS THAT IS WARRANTED DIRECTLY TO THE USER BY ITS MANUFACTURER.
IF THE MANDATORY RIGHTS MAKE CATERPILLAR LIABLE IN CONNECTION WITH SERVICES OR GOODS,
THEN TO THE EXTENT PERMITTED UNDER THE MANDATORY RIGHTS, THAT LIABILITY SHALL BE LIMITED
AT CATERPILLAR’S OPTION TO (a) IN THE CASE OF SERVICES, THE SUPPLY OF THE SERVICES AGAIN OR
THE PAYMENT OF THE COST OF HAVING THE SERVICES SUPPLIED AGAIN AND (b) IN THE CASE OF GOODS,
THE REPAIR OR REPLACEMENT OF THE GOODS, THE SUPPLY OF EQUIVALENT GOODS, THE PAYMENT OF
THE COST OF SUCH REPAIR OR REPLACEMENT OR THE ACQUISITION OF EQUIVALENT GOODS.
CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON ITS PART
OR ON THE PART OF ANY OF ITS EMPLOYEES, AGENTS OR REPRESENTATIVES IN RESPECT OF THE
MANUFACTURE OR SUPPLY OF GOODS OR THE PROVISION OF SERVICES RELATING TO THE GOODS.
CATERPILLAR IS NOT LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES UNLESS IMPOSED UNDER
MANDATORY RIGHTS.
IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE INTERNATIONAL SALE
OF GOODS IS EXCLUDED IN ITS ENTIRETY.
C) For products supplied in Australia:
IF THE PRODUCTS TO WHICH THIS WARRANTY APPLIES ARE:
I. PRODUCTS OF A KIND ORDINARILY ACQUIRED FOR PERSONAL, DOMESTIC OR HOUSEHOLD USE
OR CONSUMPTION; OR
II. PRODUCTS THAT COST AUD 40,000 OR LESS,
WHERE THOSE PRODUCTS WERE NOT ACQUIRED FOR THE PURPOSE OF RE-SUPPLY OR FOR THE
PURPOSE OF USING THEM UP OR TRANSFORMING THEM IN THE COURSE OF PRODUCTION OR
MANUFACTURE OR IN THE COURSE OF REPAIRING OTHER GOODS OR FIXTURES, THEN THIS SECTION
C APPLIES.
THE FOLLOWING MANDATORY TEXT IS INCLUDED PURSUANT TO THE AUSTRALIAN CONSUMER LAW
AND INCLUDES REFERENCES TO RIGHTS THE USER MAY HAVE AGAINST THE DIRECT SUPPLIER OF
THE PRODUCTS: OUR GOODS COME WITH GUARANTEES THAT CANNOT BE EXCLUDED UNDER THE
AUSTRALIAN CONSUMER LAW. YOU ARE ENTITLED TO A REPLACEMENT OR REFUND FOR A MAJOR
FAILURE AND COMPENSATION FOR ANY OTHER REASONABLY FORESEEABLE LOSS OR DAMAGE. YOU
ARE ALSO ENTITLED TO HAVE THE GOODS REPAIRED OR REPLACED IF THE GOODS FAIL TO BE OF
ACCEPTABLE QUALITY AND THE FAILURE DOES NOT AMOUNT TO A MAJOR FAILURE. THE INCLUSION
OF THIS TEXT DOES NOT CONSTITUTE ANY REPRESENTATION OR ACCEPTANCE BY CATERPILLAR OF
LIABILITY TO THE USER OR ANY OTHER PERSON IN ADDITION TO THAT WHICH CATERPILLAR MAY HAVE
UNDER THE AUSTRALIAN CONSUMER LAW.
TO THE EXTENT THE PRODUCTS FALL WITHIN THIS SECTION C BUT ARE NOT OF A KIND ORDINARILY
ACQUIRED FOR PERSONAL, DOMESTIC OR HOUSEHOLD USE OR CONSUMPTION, CATERPILLAR LIMITS
ITS LIABILITY TO THE EXTENT IT IS PERMITTED TO DO SO UNDER THE AUSTRALIAN CONSUMER LAW
TO, AT ITS OPTION, THE REPAIR OR REPLACEMENT OF THE PRODUCTS, THE SUPPLY OF EQUIVALENT
PRODUCTS, OR THE PAYMENT OF THE COST OF SUCH REPAIR OR REPLACEMENT OR THE ACQUISITION
OF EQUIVALENT PRODUCTS.
THE WARRANTY SET OUT IN THIS DOCUMENT IS GIVEN BY CATERPILLAR INC. OR ANY OF ITS
SUBSIDIARIES, 100 N. E. ADAMS ST, PEORIA, IL USA 61629, TELEPHONE 1 309 675 1000, THE USER IS
RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH MAKING A CLAIM UNDER THE WARRANTY SET
OUT IN THIS DOCUMENT, EXCEPT AS EXPRESSLY STATED OTHERWISE IN THIS DOCUMENT, AND THE
USER IS REFERRED TO THE BALANCE OF THE DOCUMENT TERMS CONCERNING CLAIM PROCEDURES,
CATERPILLAR RESPONSIBILITIES AND USER RESPONSIBILITIES.
TO THE EXTENT PERMISSIBLE BY LAW, THE TERMS SET OUT IN THE REMAINDER OF THIS WARRANTY
DOCUMENT (INCLUDING SECTION B) CONTINUE TO APPLY TO PRODUCTS TO WHICH THIS SECTION C
APPLIES.
©2016 Caterpillar All Rights Reserved.