DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical Engineering University of Sarajevo Bosnia & Herzegovina Amra Omeragic, Head of Investment Planning, Elektroprenos B&H, Bosnia & Herzegovina

Transcript of DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC...

Page 1: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

DEVELOPMENT OF THE KNOWLEDGE BASE

FOR OPERATION AND MAINTENANCE THE

EQUIPMENT WITH POLYMERIC INSULATION

Kemo Sokolija, Professor, Faculty of Electrical Engineering

University of Sarajevo

Bosnia & Herzegovina

Amra Omeragic, Head of Investment Planning, Elektroprenos B&H, Bosnia &

Herzegovina

Page 2: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

2

CONTENT

1. INTRODUCTION 3

2. MODIFICATION OF OUR “TECHNICAL SPECIFICATION FOR CPIs” BASED ON OURS AND THE OTHER’S EXPERIENCES 15

3. ELABORATION OF THE PRELIMINARY POLLUTION MAP 17

4. CONDITION MONITORING OF CPIs INSTALLED IN TEST STATIONS 23

5. DATA BASE FOR OBSERVATION OF CPI’s BEHAVIOUR 35

6. ESTIMATION OF LONG-TERM PERFORMANCES OF CPIs 38

7. PERSONAL EDUCATION 41

8. CONCLUSIONS 43

Page 3: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

1. INTRODUCTION

Page 4: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

4

INSULATORS USED FOR TLs AND SWITCHGEARS ARE NOTIMMORTAL

EVEN THEN ARE PRODUCED USING '‘DEAD'' MATERIALS

INSULATORS WITH MATERIALS WHICH ARE NOT

CHEMICAL INERT – POLYMERS CAN BE MORE SUBJECT TO AGEING

INSULATORS ARE LIVE ELEMENTS OF EES

HAVE OWN WORKING LIFETIME DEPENDINGFROM A FEW INFLUENCE FACTORS

CHOICE (material, design, ...)

HANDLING OBSERVATION DURING OPERATION MAINTENANCE

NEW APPROACH TO

BUYING (more cheaper) INSTALL AND CAN CONSIDER THAT THEY WILL BE IN FUNCTION

'‘FOR EVER''

OLD APPROACH TO

EL.TENSIONS

CLIMATIC IMPACT

AIR POLLUTION

BAD QUALITY

BAD CHOICE

Page 5: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

5

INSULATORS HAVE THEIR LIFE TIME

WHEN WE MAKE A CHOICE FOR A SPECIFIC APPLICATION

WE MUST TAKE INTO ACCOUNT

LONG LIFE CYCLE COSTS:

PURCHASE

MAINTENANCE

OUTAGE (NON-DELIVERED POWER)

HOWEVER, EVEN TODAY,

FOLLOWING ON OLD APPROACH WAKE,

THERE ARE PLANTY OF THEM SEEING

NOTHING MORE

THAN BARE PURCHASE COSTS

!?

ENGINEERS MUST LONG FOR THE

OPTIMUM

TO INCLUDE

TOTAL OPERATING AMBIENT

REQUIRED PERFORMANCES

EXPECTED LONG LIFE CYCLES COSTS

Page 6: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

6

ONE OF THE STARTING POINTS OF THE

NEW APPROACH ARE

LONG LIFE CYCLE COSTS

EXPECTED LIFE TIME MUST BE PUT

INTO THE FOCUS

POLYMERIC INSULATION SUBJECT TO AGEING

UNCERTAINTY REGARDING EXPECTED LIFE TIME

WHY CP INSULATION ?

THE MAIN LIMITING FACTOR IN EXTENSIVE

APPLICATION OF CPIs

Page 7: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

7

IT IS A QUESTION OF PREJUDICE !!!

THE AGEING PROBLEM IS NOT DISTINCTIVE TRAIT

OF CPIs

CONVENTIONAL INSULATORS ARE ALSO SUBJECTED TO

AGEING

IF NOT PORCELAIN PARTS, METAL PARTS WILL DEFINITLY AGE

BEING “KILLED” ONE IS SUPOSED TO BE OUT OF FUNCTION

EARTHQUAKES, HURRICANES

IF ENVIRONMENTAL CONDITIONS CHANGE

DRAMATICALY THEY WILL BE

“RUN OVER BY TIME”

WHY ?

Page 8: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

8

LOWER PURCHASE COSTS

LOWER WEIGHT

LOWER MAINTENANCE COSTS

TO USE CPIs IS SOMETIMES

MORE ECONOMICALY EFFICIENT

EVEN MORE THEIR REAL LIFE TIME IS

TWO, FIVE OR THEN TIMES

SHORTER THEN THAT OF THEIR CONVENTIONAL PATERNS

FROM THE OTHER SIDE

Page 9: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

9

ALTHOUGH PORCELAIN STILL HOLDS THE MAJORITY

CONSUPTION IN HV INSULATORS,

CONSERVATIVE POWER INDUSTRY CHANGES

UNDER FOLLOWING ADVANTAGES OF CPIs:

1. LIGHT WEIGHT MORE ECONOMIC DESIGN OF THE TOWERS OR ENABLING TO UPGRADE THE VOLTAGE OF EXISTING SYSTEM;

2. MUCH BETTER PERFORMANCE IN PRESENCE OF HEAVY POLLUTION, SPECIALLY SILICON RUBBER;

3. HIGHER MECHANICAL STRENGH TO WEIGHT RATIO LONGER SPANS OF TOWERS;

4. CAN WITHSTAND SEVERE GUNSHOT DAMAGE WITHOUT IMMEDIATE FAILURE;

5. REDUCTION IN MAINTENANCE COSTS IN HEAVILY POLLUTED CONDITIONS;

6. REDUCTION IN THE PURCHASE PRICE, TRANSPORTATION AND INSTALLATION COSTS

Page 10: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

10

THE MAJOR DISADVANTAGES CPIs ARE:

1. LIMITED LONG-TERM SERVICE EXPERIENCE

2. UNCERTAIN LIFETIME

3. DIFFICULTIES IN DEFECTING FAULTY INSULATORS AS WELL AS MONITORING IN SERVICE

BESIDES

MANUFACTURERS MARKED CPIs AS A PRODUCT

WHICH DID NOT NEEDED TO BE HANDLED CAREFULLY

CPIs WERE USED AS TOOLS BEEING DESTROYED

BY UNPROPER HANDLING

Page 11: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

11

ALTHOUGH NATURAL WEATHERING HAS BEEN SHOWN

TO CAUSE CPIs AGEING, THERE IS A GREAT EXPERIENCE SHOWING:

THE LIFETIME OF CPIs HAS BEEN MORE

RELATED TO DESIGN WEAKNESSES AND

POUR QUALITY CONTROL DURING MANUFACTURING.

GREAT EFFORTS HAVE BEEN MADE

IN ORDER TO OBTAIN AN OPTIMAL MIX OF

GOOD PROPERTIES OF THE MATERIALS USED FOR CPIs

AND TO RESOLVE DIFFERENT DESIGN PROBLEMS

HOWEVER, WE MUST SAY:

NOT ALL PRODUCTS WE COULD FING TODAY ON THE

MARKET HAVE REACHED REQUIRED

QUALITY LEVEL EVEN THEY HAVE PASSED

REQUIRED STANDARD TESTS.

Page 12: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

12

HOW TO MAKE DIFFERENCE BETWEEN GOOD AND A BAD PRODUCT ?

IF ONE WISH TO LEARN SWIMING HE/SHE MUST

GO INTO THE WATER !!!

THE ONLY SURE METHOD OF DISTINGUISHING

GOOD FROM BAD IS TO ACCES THEIR

BEHAVIORING IN REAL SERVICE CONDITIONS.

THAT WAS THE IDEA WHICH OUR UTILITY

(TODAY “ELEKTROPRIJENOS BiH”),

IN COLABORATION WITH UNIVERSITY OF SARAJEVO,

ENDEAVOR TO REALISE DURING LAST YEARS.

WE DID NOT PROCEEDED IN A WAY:

AFTER BEING INSTALL CPIs ARE LEFT TO THEIR DESTINATION

HOPEING THEY WILL BEHAVE A GOOD BEHAVIOUR IN SERVICE

TAKE CARE OF INSTALLED CPIs

AND TAKING INTO ACCOUNT COLLECTED

KNOWLEDGE

IMPROVE OUR BEHAVIOUR IN THIS TECHNOLOGY

OUR AIM WAS AND REMAIND THE SAME:

Page 13: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

13

THE STUDY WORK PRESENTED HERE IS RESULT

OF OUR NEED TO SINTHETISE

OUR’S AND THE EXPERIENCES OF OTHER UTILITIES

IN ORDER TO FORM A BASE FOR THE

NEW KNOWLEDGE DEVELOPMENT

..... AND TO TRACE THE WAYS LEADING TOWARDS THE DEFINED TARGET

THE RESULTS OF THIS STUDY WORK ARE:

1. SINTHESIS OF PREVIOUS EXPERIENCES

2. PRELIMINARY POLLUTION MAP OF THE REGION

3. ANALYSIS OF THE RESULTS OF PREVIOUS MONITORING OF CPIs

4. THE PROPOSAL OF THE ORGANISATION OF DATA BASE ON CPIs

BEHAVIOUR IN SERVICE

5. SPECIFICATION OF THE PROCEDURES FOR CPIS MONITORING

6. PROGRAM OF STAFF TRAINING

Page 14: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

14

WHAT WAS THE AIMS OF THIS STUDY WORK?

TO DEFINE LONG-TERM PROGRAM WHICH WILL ENABLE THATJP ELEKTROPRIVREDA BiH

DEVELOP THE KNOWLEDGE BASE NEEDED FOR A NEW APPROACH THAT

CHOICE (materials, design, production process)

HANDLING in all phases before putting into operation

OBSERVATION DURING EXPLOITATION

OF EQUIPMENT WITH POLYMERIC INSULATION BE ESTABLISHED ON

K N O W L E D G E

Page 15: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

2. MODIFICATION OF OUR“TECHNICAL SPECIFICATION

FOR COMPOSITE INSULATORS”BASED ON OURS AND

THE OTHER’S EXPERIENCES

Page 16: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

16

On the base of worldwide experiences and studying of papers regarding one of the most important failure mechanism on CPI – brittle fracture– it is made possible to us that suggest following modifications in document ''Technical specification for composite insulators'':

(f) Regarding moulding line parallel to insulator axis, stay on decision that is prefered design where the one does not exist. But, it does not mean that the insulators, which had moulding line parallel to insulator axis and producer was removed it in finish phase, are «handicaped». Because of that formulation of this point should be: «Insulator designs on which does not exist noticeable tracks of moulding line parallel to insulator axis are prefered.».

(a)Explicite define that only CPIs with silicone rubber housing can be installed in the network.

(b)Explicite define that minimal thickness of rubber on the sheat has to be 3,0 mm.

(c) Beside formulation «it is prefered insulator with ECR core», explicite define that CPIs with ECR core can be installed in the network only.

(d)Exclude possibility of insulator choice with underribes on sheds.

(e)Exclude following «it is prefered insulator design where the metal fittings are not covered by housing material».

Page 17: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

3. ELABORATION OF THE

PRELIMINARY POLLUTION

MAP

Page 18: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

18

System requirementsEnvironment conditions

Insulator parameters

Application Level and type of pollution

Type

Withstand voltages Fog, dew, rain… Material

Reliability, availability, maintenance

Wind Profile

Costs Temperature, humidity

Leakage distance

Installing position, distances,…

Heigh above sea level Diameter

Vandalism

Earthquakes Flashover distanceThunderstorms

Table 3.1. Categories of input data and parameters

Table 3.1. gives the categories of input data and their parameters to beconsidered resolving the problem of insulators choice

Page 19: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

19

MSCD

CHOICE AND DIMENSIONING

LEGEND:approach Aapproach Bapproach CMSCD – minimal specific creepage distance

SYSTEM’S REQUIREMENTS

EXISTING EXPERIENCE IN EXPLOITATION

AND/OR RESULTS OF NEW INVESTIGATIONS

IN REAL EXPLOITATION CONDITIONS

RESULTS OF EXISTING AND/OR

NEW INVESTIGATIONS IN

LABORATORY’S CONDITIONS

CORRECTION FACTORS

ESTABLISHMENT OF POLLUTION

LEVEL

INSULATOR PARAMETERS

ENVIRONMENT CONDITIONS

Fig. 3.1. Three approachs to the choice and the dimensioning

Since, insulators performances are determined by the means of complex dynamic interaction between environment conditions and insulators parameters, approach A should be used whenever possible; that can not be correctly done using existing laboratory tests – Approach B.

Approach C makes possible these interactions to be taken into account using empirically determined corection factors.Although it is simply and cheap, this approach has restrictions which could have negative impact on system requirements: reliability, availability, maintenance.

The Fig. 3.1. gives three possible approachs used for choice of insulators for specific application on specific site, on the base of three categories of input data.

Page 20: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

20

We could not make the proper choice of insulators for our lines and substations because we have not had a document unambiguously prescribing to which IEC zone (pollution level) allocate location of interest.

Our engineers used the approach based on its subjective judgement and imprecisely defined pollution levels in IEC documents.

So we decided to establish a preliminary pollution map.

Page 21: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

21

Into the topographic map of the theritory we inserted all our lines and substations, as well as the all existing pollution sources.

Using the definitions of the pollution levels according IEC documents, we assigned the corresponding pollution levels and adequate minimal creepage distance for all the facilities of the company.

Special attention was dedicated to our specific climate conditions (fog, drizzle, rain); impact of the great cities is specially treated.

3.1. Procedure used for the preparation of the preliminary pollution map

The topographic configuration of the ground is also taken into consideration, as well as the impact of the main roads and wind directions.

The proper care is also taken regarding the future capital projects to be realised (highway, industry).

Page 22: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

22

Before we have established the preliminary pollution map our utility usualy prescribed MCD of 20 mm/kV, sometimes also 16 mm/kV in its tenders.

The results obtained analising pollution sources and other relevant issues during the preparation of the preliminary pollution map showed that in some substations 110 kV we must applied 31 mm/kV, as well as at many parts of our power lines; the same we have found regarding the existing substations and power lines where we need 25 mm/kV.

To establish the real state it is necessary to prepare a “real pollution map” on the base of measuring of ESDD and NSDD. The list of the 18 locations where we need to install measuring equipment is also the result of our considerations during the preparation of the preliminary map.

Page 23: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

4. CONDITION MONITORING

OF CPIs INSTALLED IN TEST STATIONS

Page 24: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

24

4.1. Visual inspection

Today, this technique is the most applicable. Technicians being in charge of the visual inspection have to possess a great experience regarding design, materials and behaviour of CPIs, and be well familiar with diferent types of deteriorations, damages and faults which could be happened on this type of insulators.

Tipical signs of deterioration (acceptable ageing) of CPIs are:

– small splitting of material on sheds or sheat of insulator.

– appearance of chalking on insulator surface;

– change of insulator surface color;

– appearance of microcrack on insulator surface;

– appearance of corrosion on metal fittings;

– light surface erosion of sheds or sheat of insulator;

– small peeling between some components;

Page 25: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

25

As the result of progressiv ageing and/or environment impact, or wrong handling with CPIs, damages, which have a negative impact on performances and life time of insulators, can be appear:

– direct exposure of FGR to environment conditions;

– branching off different insulator parts which could cause important decreasing of creepage distance or thickness of housing on sheat;

– surface erosion which caused important material removing on insulator sheat;

– branching off of sealing from the metal fittings;

– destroying of metal fittings caused by electric arc over insulator surface;

– punctures of sheds or sheat of insulator;

– cutting/cracks of housing which cause important reduction of creepage distance or thickness of the housing on sheat;

– tracking – forming of conductive paths on insulator surface;

– damages caused by animals.

Page 26: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

26

4.2 Results of visual inspections in JP Elektroprivreda BiH

In order to systematicly monitor behaviour of different type of insulators (design, material, producer) which are installed in transmission network, according to CIS Program (Composite Insulator Status Program), addopted by STRI, the three test stations are formed where the insulators of different producers are installed – Table 4.1.

Table 4.1. CPIs installed on three test stations

Test station (TS)

Insulator type (producer)

Housing materialPollution level

(IEC 60815)Year of installation

Kakanj – TS 1E1, SE1, S2, S3,

S5, S6

E1 – EPDM*)

SE1 – SIL ALLOYS1 – S6 – SIR

IIIE1, SE1, S2 – 1998.

S3 – S6 – 2002.

Hadzici – TS 2E1, SE1, S2, S3,

S5– '' – II

E1, SE1, S2 – 1998.S3, S4, S5 – 2000.

Pratace – TS 3 E1, SE1, S6 – '' – I E1, SE1, S6 – 1998.

(*) EPDM – etilen propilen dien monomerSE1 – silicone alloySIR – silicone rubber

Page 27: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

27

The main data cocerning those insulators are given in the Table 4.2.

Table 4.2. The main data of the insulators installed in the test stations

Insulators given in Table 4.1. E1 SE1 S2

Housing material EPDM Silicone alloy Silicone rubber

Date of installation November 1998. November 1998. November 1998.

Position horizontal horizontal horizontal

Max. System voltage (kV) 123 123 123

Nominal system voltage (kV) 110 110 110

Corona rings NO NO NO

Arcing horns NO NO NO

Flashover distance (mm) 879 930 887

Creepage distance (mm) 2700 2320 2717

Specific creepage distance (mm/kV) 21,95 18,86 22,09

Alternating sheds YES NO NO

Number of sheds 16 15 24 – 19 –

Diameter of sheds (mm) 105 90 94 – 129 –

Diameter of sheat (mm) 26 25 20

Distance between sheds (mm) 55 39 40

Page 28: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

28

The complete review of the results of our observations of different types of CPIs which are installed in the test stations in the period 1999–2009 is not presented here because of its extensiveness.The results have been sent to STRI (in the framework of CIS Program). It is important to note that the same tipes of the insulators are installed (type E1 and SE1 in huge number) in transmission network of BiH.

According to the results of observation it is concluded that there is not any insulator on test station which has had changes that could be characterised as a damage. Also, there is not any insulator which sustained a failure.

Regarding the hydrophobicity of insulator surface, it was obviously confirmed the fact that only insulators based on sillicone rubber were keeping their hydrophobicity even after long time exposure to atmospheric impacts. Insulators with EPDM housing, during the time have lost this characteristic (Fig. 4.1.(a)) and has not been able to recovery it, as it was the case for silicone insulators -Fig.4.1.(c).

Page 29: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

29

Fig. 4.1. Hydrophobicity of insulators surface after four years of operation (test station Hadzici):

(a) (b)

(c)

(a) insulator E1; (b) insulator SE1; (c) insulator S2

Page 30: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

30

However, it could be interesting to discuss the observations of the insulators with the housing made using so cold silicone alloy.

It is very reasonable question why they in their formulations use silicione at all when those insulators immediately (after one year of operation-Fig 4.1. (b)) loose their very modest starting hydrophobicity.

These observations can not, of course, refer at once to conclusion that insulators with silicone alloy are more inferior product, because neither the hidrophobicity is the only one important factor of housing material, nor the material is the only one stipulate factor which determine performances of CPIs.

However,existence or non-existence of the hydrophobicity itself as a first defense line has definitely one very important reflection on the process of housing deterioration caused by surface discharges.

Page 31: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

31

In that sense, behaviour of insulator type E1, specially SE1 is very indicative. As it is shown on picture 4.2. and 4.3., after four years of operation in real environment conditions, those insulators have a serious changes on housing. However, those changes are still signs of acceptable ageing.

On such behaviour of insulators type E1 and type SE1, their design has an important impact. Since that test stations are located on areas which belong to the III pollution level (Kakanj), and II pollution level (Hadzici), it can be concluded that creepage distances of insulators 18,86 mm/kV (insulator SE1) and 21,95 mm/kV (insulator E1) are not adequate. Insulator SE1 is not corectly dimensioned for both locations, and insulator E1 for location Kakanj.

Fig. 4.2. Appearance of deterioration on insulators after four years of operation (Kakanj (a) and Hadzici (b))

(a) (b)

(a) color changing on insulator SE1; (b) color changing on insulator E1

Page 32: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

32

Fig. 4.3. Deterioration on insulators after four years of exploitation:

(a)

(b)

a) changes of surface on insulator SE1;

b) changes of surface on insulator E1

Page 33: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

33

4.3 Application of special equipment for visual inspection

There is a logical question: “What is the activity of discharges on the surface of a insulator which could be considered as allowed?”

The answer is: “No sort of discharges which are in contact with the insulator housing or with sealing between metal parts and housing.”

It is aside the question to replace immediately or not the insulator in the case of unacceptable discharges registrated. This question is not jet answered!

Until such correlation does not exist IR – thermography could be considered as a complementary technique for visual inspection of CPIs.

So we use this technique extensively.

Page 34: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

34

Since the human eye, as well as standard night vision cameras, are not sensitive on the part of spectrum where the main part energy of unacceptable discharges is located (300-380 nm) and since the glass used in standard lenses do not transmit this part of the spectrum, we have not been able to detect those partial discharges visually until few years ago when special cameras equipped with quartz’s lenses were developed.

These instruments can be very efficient for detection of discharges in dry conditions, when any visual corona discharges should not be on insulator’s surface. Drawback of night vision technique is the fact that discharges which we want to detect on this way – discharges on insulator surface caused by leakage current – have a specific and sporadic nature; they do not happen only during the night.

Thanks to techological progress, after only a few years, from the situation when we could not see anything what is happening on insulator surface, today we are in position that can see everything during the day light. The special instruments, which it make possible, are developed and have world wide application today.

Following the experiencies of other utilities we will be very ready to use this inspection technique very soon.

Page 35: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

5. DATA BASE FOR OBSERVATION OF

CPI’s BEHAVIOUR

Page 36: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

36

General survey of the data base

Data base Izolatori (Fig.5.1.) represents a program package developed whith the purpose of monitoring, registration and strage of all information regarding the changes noticed during the CPIs inspection on the lines and substations of Elektroprivreda BiH.

Data base includs: the characterisctics of all types of CPIs installed; the time and the places of CPIs instalation; information regarding conditions and behaviour of CPIs during the inpections; information regarding regisrated damages/faults.

Fig. 5.1. Starting “window” of application

Page 37: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

37

The application is realised as related data base in ACCESS 2000 (Access 9) for WINDOWS 98/2000/XP, what mean that it can be installed and used on PCs where the WINDOWS 98/2000/XP and MS Access 2000/2003 (XP) are installed.

In technical appearance, the system is outlined as back end – front end data base. Term back end – front end mean that program has two files at least. In one file (back end) there are only tables with data, till in the other file (front end) there are other objects for work and control of data base, as forms, reports, moduls in program language Visual Basic

System can be implemented as: - centralized or - distributed.

Page 38: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

6. ESTIMATION OF LONG – TERMPERFORMANCES

OF CPIs

Page 39: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

39

Those informations can be obtained using visual inspections and other diagnostic procedures in operation, as well as conducting laboratory tests on insulators removed from lines.

The laboratory tests should be chosen in the way that they can describe basic insulators’ characteristics (electrical and mechanical).

When the CPIs are new, they have extraordinary electrical characteristics. Observations made on CPIs after their long term operation under working conditions show that, depending of chosen housing material and specific design, CPIs can be deteriored or damaged.

So the information regarding CPIs ageing are very important for electric utilities in order to keep required system relaibility.

Page 40: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

40

The Table 6.1. showes testing procedures steps, which are necessary strictly follow to ensure a reprodicibility and repeatibility of examinations and to make possible comparation of basic insulators characteristics. On that way the results of surface characteristics measurements can be compared with results of laboratory testings of electrical characteristics and with results of visual inspections.

Table 6.1. Steps of testing procedures

Test No. Test type Standard

1. Visual inspection

2.2.1.2.2.2.3.2.4.2.5.2.6.

Surface insulator’s characteristicsHydrophobicity classificationZinc galvanization on fittingsPollution level (ESDD and NSDD)Surface changes on polymerHardness of polymer housing materialRoughness of insulator surface

STRI Guide 92/1IEC 60 383–1IEC 60507IR spectroscopyISO 868ISO 4287

3.3.1.3.2.3.3.

Electrical characteristics of insulatorAtmospheric withstand voltage test - dryIndustrial withstand voltage test 50 Hz - wetVoltage test of corona beginning

IEC 60060–1IEC 60060–1IEC 60060–1

4.4.1.4.2.

Internal insulator integrityTest of housing material peelingTest of sealing for interface housing/fitting

CT–AR 51.00.28104IEC 61109

5.5.1.5.2.

Mechanical characteristics of insulatorsRoutine test and verification of SMLTest of extreme durability on strain

IEC 61109IEC 61109

Page 41: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

7. PERSONAL EDUCATION

Page 42: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

42

Our utility has organised the program of education of the human resources in charge of selection, inspection, comissioning, stocking and installing of CPIs.

For that purpose we have prepared a special handbook.

The program is being realised using different forms: courses, workshops and practical training.

The following aspects are treated in he framework of the education program:

selection of design and material;

comissioning in the factory, stock, transport and handling, installation;

visual inspection: identification of detorations, damages and failures;

causes of detorations and damages;

using of special instruments and methods for CPIs monitoring and

diagnostics.

Page 43: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

8. CONCLUSIONS

Page 44: DEVELOPMENT OF THE KNOWLEDGE BASE FOR OPERATION AND MAINTENANCE THE EQUIPMENT WITH POLYMERIC INSULATION Kemo Sokolija, Professor, Faculty of Electrical.

44

CONCLUSIONS

After almost four decades of research, development and continuous improvements in production of CPIs, it is clearly that this product expirienced its full ripeness.

Design, materials and technology of production reached the levels which could be able to ensure a product of high quality.

At the same time, polymer housing has almost comletely changed porcelain housing for MV surge arresters, and it is more and more used in production of other equipment.

Basic shortages in application of CPIs are connected to insufficient experiences of their long term performances. These factors are consequence of weaking their electrical, probably also mechanical performances during the time.

JP Elektroprivreda BiH has made decision to take such approach to CPIs which means to take care about installed CPIs, and to improve its own relation to this technology on the base of acquired experiences.