Detectomat Katalog 2011
-
Upload
milica-lolic -
Category
Documents
-
view
367 -
download
43
Transcript of Detectomat Katalog 2011
Contents
I 1
II loop3000 21. 3
2. 4
3. 9
4. 12
5. 20
6. 28
7. 39
8. 499. 54
10. 65
11. 7412. 78
13. 84
14. 89
15. 99
16. 124
17. 133
18. 138
19. 141
20. 143
21. Linear heat detectors and accessories 148
22. Smoke Aspiration System and accessories 151
23. Voice Evacuation System - Smoke detect 163
24. Door Control System and accessories 197
25. Testequipment for automatic detectors 218
III Terms & conditions of sale detectomat GmbH 221
Fire Control Panel dc 3400
Fire Control Panel detect 3016 and accessories
Fire Control Panel detect 3004 and accessories
Wireless Fire Alarm Systems
Accessories for Fire Control Panels detect 3004 and detect 3004plus
Accessories for Fire Control Panels detect 3004 and detect 3016
Software and tools
Accessories for detectors
Network components
Addressable automatic detectors loop3000
Addressable manual call points
Smoke alarm detectors and accessories
Conventional Fire Alarm Systems
Infrared-Beam detectors and accessories
Addressable I/O-elements loop3000
Conventional signalling devices
detectomat Fire Detection Systems
Product Overview
Addressable signalling devices loop3000
Flame detectors
Fire Control Panel detect 3004plus and accessories
Ex-proof components and accessories
Introduction detectomat GmbH Germany
I. Introduction detectomat 1
detect 3000 Safety without Compromise
The international detect 3000 system was developed from the consolidation of the JOB-Group in 2003, when detectomat became part of the group and launched it’s detect 3000 system as a fire fighting technology solution.
As a medium sized company and part of the JOB-Group detectomat has the ability to respond quickly to market requirements plus the benefits of the financial security, backing and marketing of an established international company.
The detect 3000 portfolio offers flexible, cost-effective solutions for small, medium and large scale applications including products ranging from detectors to panels and networked systems with visual detect graphic displays.
system features and benefits:
• detect 3000 fire control panels for all applications
• networked detect 3000 systems with visual detect graphic displays
• comprehensive maintenance and service tools I-Check, Easy Check and Loop test
• high system flexibility via loop devices of the profi loop3000
• an extensive variety of designs and colour variations for detector covers and custom designs
In addition to the professional applicationsof the established detect 3000 system, several other interesting products are offered in its portfolio including:
HDv® 3000 smoke detectors for the usein residential / home applications and an extensive range of high performanceconventional detectors in a variety of design styles and colour variations to match contemporary interior designs.
Production hall in Germany
1. Fire Control Panel dc 3400 3
Properties:
System approval S295054 and S208123
EN 54-4:1997/A1:2002/A2:2006VdS approval G208123
Fire Control Panel dc 3400, small housing, compact Art.-no. 32530 - Type dc 3400 SC
18 LED - indicators for status messages1x 24 V / 400 mA monitored line for alarm devices (sounder, flasher)
2 batteries 12 V / up to 12 AhUSB, RS 485
Integrated USB-interface for the easy programming via DCT-software
RS 485-interface for external printer
Description:Microprocessor controlled compact fire control panel for use with the loop3000 fire detection system components approved according EN 54-2/ A1:2006 and and EN 54-4/A1:2003 and A2:2006
1 monitored output 24 V / 400 mA for signaling devices (sounder, flasher, etc.)
Event memory of up to 9999 events
Custumer specific texts for zones or detectors with up to 40 characters
Technical data
Integrated primary switched power supply 150 W according EN 54-4 / A2: 2006
1 output 400 mA for external user
3 potentialfree relay outputs for alarm and fault
2 freely programmable monitored inputs
Clear display and easy operation via 5,7" Touchscreen-Display, 320 x 240 pixel
Integrated 1 loop-interface for the connection up to 126 loop devices of the loop3000 series
12 kg, without batteriesWeight
Light grey RAL 7035ColourMaterialDimensions (H x W x D)
Outputs
Stainless Steel
HumidityProtection class
2 freely programmable monitored inputs0°C to +50°C5 % - 95 % (non-condensing)IP 30
2 integrated languages (German, English)
EN 54-2:1997/A1:2006Standards
300 mm x 400 mm x 135 mm
Input voltagePower supplyEmergency backupInterfacesDisplayLEDs
84 - 264 V AC / 120 - 300 V DC / 47 - 63 Hz
InputsAmbient temperature
Up to 999 programmable zones
Programmable reaction and inspection times
Integrated alarm buffer and 2 detector / 2 zone dependencies
3 relay outputs 30 V / 2A for alarm and fault
32 V DC / 150 W / 3,5 A
5,7" Touchscreen display 320 x 240 pixel, integrated backlight
2. Fire Control Panel detect 3004plus and accessories 4
Properties:
Fire Control Panel detect 3004plus, deep housing, language kit English Art.-no. 32551 - Type detect 3004plus M GB
Event log memory of up to 500 messages
Fire Control Panel detect 3004plus, shallow housing, language kit English Art.-no. 32553 - Type detect 3004plus S GB
2 slots for 2 loop-interfaces for the connection of up to 4 loops each with a maximum of
126 loop3000 devices per loop and a maximum loop length of up to 3.500 m
Description:Microprocessor controlled modular fire control panel for the use with the loop3000 fire detection system components. Approved according to EN54-2 A1:2006, EN54-4 A1:2002, A2:2006 and VdS for the use according to VdE 0833.
to VdS
Connections for a fire brigade interface for controlling the panels outputs, key deposit
Integrated interface connection for up to 63 additional network components
Technical data
Option for 2 conventional interface cards for controlling up to 16 conventional zones
Extinguishing interface for controlling extinguishing and gas suppression systems in accordance
to EN12094
Integrated control of extinguishing systems via the standard extinguishing interface in accordance
Large LCD, 160 x 80 with backlight
Integrated Display and Control Panel according to DIN EN54-2 A1:2006
and transmission units
Integrated RS 232-interface for the DPT programming software and the connection of printers
and other peripheral equipment
3 potential free relays for fire and fault
3 inputs for collective signals
for external devices rated at 24 V DC/800 mA
Integrated power supply 72 W according to EN54 with 1 output
Monitored power supply unit and battery charging according to EN 54-4 A1:2002 and A2:2006
1 external output 24 V/400 mA monitored for sounding/signalling devices
via the MC 3004 monitoring card
Up to 42 T-branches per loop possible
Up to 128 programmable detector zones
Option for customised front logos
Segmented front door allowing the quick assembly of LED indicator modules and printers
Emergency power supply via 2 batteries 12 V/up to 12 Ah (shallow housing) / 26 Ah (deep housing)
Integrated ground fault monitoring
Possibility for complete system redundancy with the CPU and loop interfaces
In accordance to EN61000-6-3 class B for emissions, so suitable for the use in sensitive areas
For more technical details please see next page.
2. Fire Control Panel detect 3004plus and accessories 5
Properties:
tional LED indicator module in the front for indication acc. to EN54-2
Colour Light grey, RAL 7035
Utilization of integrated standard extinguishing interface requires 1 op-
490 mm x 420 mm x 210 mm (deep housing)Weight 12,5 kg, without batteries
Fire Control Panel detect 3004plus, shallow housing, language kit English Art.-no. 32553 - Type detect 3004plus S GB
400 mA RS 232; Bitbus (RS 485 based)
1 output 24 V DC/800 mA for external devices 2 x 12 V/12 Ah (shallow housing) 26 Ah (deep housing)
Simple menu structure in accordance to EN 54-2 A1:2006
Integrated alarm buffer and 2 detector/zone dependencies
Different access levels with password protection
Integrated "one-man-revision mode" with clear protocols and a revision counter
Commissioning and service tool for analyzing and fault finding functions with I-Check software
Technical data
Time controlled changeovers of sensitivity levels of loop3000 detectors by day/night modes
Software controlled disablements for zones and individual detectors via external inputs
Ability to change and edit inspection and reaction times along with all delays
Programming options for different alarm modes
Programming of control logics and time dependent functions for the components of series loop3000
Customized customer texts allowing up to a maximum of 20 characters
5 % - 95 % (non-condensing)Humidity
8 open collector outputs 30 V DC / 90 mAInputsAmbient temperature
Quiescent current Alarm current Interfaces
3 inputs for collective signal
20 LED-display for status signal 1 x 24 V/400 mA monitored for sounding/signalling devicesup to 4 loop 140 mA/3500 m for up to 126 loop3000 elements each3 relays outputs 250 V / 5 A for alarm and fault
24 V DC / 72 W / 3,5
250 mA
Incl. English language kit for control and programming
IP 30Protection class
-5°C to +40°C
Supply voltagePower supply
Emergency supply
230 V AC (-15 %/+10 %)
Fire Control Panel detect 3004plus, deep housing, language kit English Art.-no. 32551 - Type detect 3004plus M GB
System approval S295054
Outputs
Visual diagnostics and remote-control operations via the visualization software visual detect
Display LC-Display 160 x 80 points, backlight
Material Sheet steel Dimensions (H x W x D) 490 mm x 420 mm x 150 mm (shallow housing)
CPD-Number 0786-CPD-20817VdS approval G203068
Standards EN54-2:1997 A1:2006; EN54-4:1997 A1:2002 A2:2006Further approvals EN12094 for 1 area extinguishing systems
international approvals on request General remarks Scope of delivery without loop cards, network interfaces and batteries
2. Fire Control Panel detect 3004plus and accessories 6
Properties:
Connection directly to the CPU-main board via 26 pole ribbon cable (included in the scope of supply)
Inputs
Outputs
20-28 V DC via detect 3004plus supplyOperation voltage
8 x low active
via detect 3004plus supply
8 open collector 90 mA
Emergency current supplyQuiescent currentAlarm current
Dimensions (H x W x D) Weight
-5°C to 40°C5 % - 95 % (non-condensing)160 mm x 75 mm x 25 mm Approx. 140 g
HumidityAmbient temperature
The main relay reacts according to the monitored output of the UEI General remarks
With detect 3004plusVdS approval System approvalFurther approvals
S295054 International approvals on request
Description:Interface-board with defined inputs and outputs for the monitored activation of external dialers for the mounting
into the fire control panels of the series detect 3004plus
Technical data
Integrated protection for the monitored output and the operation voltage
Suitable for all fire control panels of the series detect 3004plus and the remote display control panel
For the triggering of a fire brigade control board, an transmission unit and a key deposit box
in case of mounted UEI-card
Transmission interface for detect 3004plus
Art.-no. 32585 - Type UEI 3004plus
3 x 24 V operation voltage400 mA moitored
Approx. 15 mA (without key deposit box and fire brigade control panel)Approx. 57 mA (without key deposit box and fire brigade control panel)
Switching possibility for the monitoring current of the monitored output from 2 mA to 10 mA
Connection of the swiss fire brigade control panel via 20 pole ribbon cable
2. Fire Control Panel detect 3004plus and accessories 7
Properties:
Properties:
LED - displays of the integrated standard-interface-extinguishing
for the activation, feedback, fault and disconnection
Ambient temperature
Description:Display board for mounting into the fire control panel
detect 3004plus for the indication of different messages of the integrated standard-interface-extinguishing
Technical data
0°C to + 40°C
Extinguishing Display Board for the Fire Control Panel detect 3004plus
Art.-no. 32559 - Type EXT 3004plus
General remarks
Including labelling strips for the identification of different messages
For the mounting into the LED indicator mounting plate (32560) of the detect 3004plus
The display board extinguishing is mounted on the mounting place of the first LED indicator module
To ensure a display for the standard interface extinguishing accordingDimensions (H x W)
Assembly kit is included in the scope of delivery
and is completely controlled by the MC-Card
80 mm x 43 mm
fire control panel detect 3004plusto EN54-2, this display board has to be integrated into the
Mounting Plate for Display Extinguishing Interface and Printer for 3004plus
Art.-no. 32560 - Type CP MP 3004plus
Description:Mounting plate to plug into the front door of the fire control
panel detect 3004plus for the use of LED indicator modules, mount in printers and/or extinguishing display board
there are still 5 additional mounting slots for LED indicator modules
The protocol printer (32558) can easily be integrated into the mounting plate
thanks to a factory provided precut
Technical data
Mounting of up to 6 LED indicator modules (30088)
Including labeling windows for the individual detector zones
In case of the mounting of an extinguishing display board (32559)
Colour RAL 7046 tele greyMaterial Sheet steelDimensions (H x W) 228 mm x 365 mm Weight Approx. 0,7 kg
Standards EN54-2, -17
VdS approval with detect 3004 System approval S295054 Weight Approx. 0,7 kg
2. Fire Control Panel detect 3004plus and accessories 8
Properties:
Properties:
Weight 141 g
Material ABSDimensions (H x W x D) 85 mm x 85 mm x 57 mm
Colour Black
Ambient temperature 0°C to 50 °CHumidity 10-85 % (non-condensing)
Mount in printer for the fire control panel detect 3004plus
Art.-no. 32558 - Type PIP 3004plus
200 mAQuiescent currentAlarm Current
Powered directly from the detect 3004plus fire control panel
57mm paper width
Direct connection to the RS 232 Interface of the fire control panel
32MB of Integrated Buffer Memory
Operation voltage
Printing speed of 50mm/sec
Thermoprint with fixed print heads
204 DPI Resolution
Description:Thermo-printer for the integration to the front plate of the
detect 3004plus fire control panel
Technical data
Interface
General remarks
10 - 32 V DC100 mA
Installation of this printer requires the mounting plate MP 3004
RS 232Print ASCII Standard, international character set
Paper width 57 mm, Paper roll diameter 50 mm
Thermo-paper for PIP 2 and PIP 3004plus, packing unit 5 rolls Art.-no. 30107 - Type EP 5
Description:Thermo-paper, packing unit 5 rolls
Outer diameter: 37mm
Inner diameter (bore) 12,3mm
Technical data
Suitable for mount in printer PIP 2 and PIP 3004plus
Packing unit 5 rolls
Paper width 57mm
3. Fire Control Panel detect 3004 and accessories 9
Properties:
Event log memory of up to 500 messages
Customized customer texts allowing up to a maximum of 20 characters
Programming of control logics and time dependent functions for the components of series loop3000
Emergency power supply via 2 batteries 12 V/ up to 12 Ah (shallow housing)/ 26 Ah (deep housing)
Integrated ground fault monitoring
Possibility for complete system redundancy with the CPU and loop interfaces
Up to 42 T-branches per loop possible
Up to 128 programmable detector zones
Option for customised front logos
Segmented front door allowing the quick assembly of LED indicator modules and printers
Integrated RS 232-interface for the DPT programming software and the connection of printers
and other peripheral equipment
3 potential free relays for fire and fault
3 inputs for collective signals
for external devices rated at 24VDC/800 mA
Integrated power supply 72W according to EN54 with 1 output
1 external output 24 V/400 mA monitored for sounding/signalling devices
Connection option for a fire brigade interface for controlling the panels outputs, key deposit
Integrated interface slot for the connection for up to 63 additional network components
Technical data
Option for 2 conventional interface cards for controlling up to 16 conventional zones
Extinguishing interface option for controlling extinguishing and gas suppression systems
in accordance to EN12094
Option for control of extinguishing systems via the standard extinguishing interface in accordance
4 alphanumeric lines LC-display with backlightt
Integrated display and control panel according to DIN EN 54
and transmission units
Fire Control Panel detect 3004, deep housing, language kit English Art.-no. 32421 - Type detect 3004 M GB
Integrated alarm buffer and 2 detector/zone dependencies
Fire Control Panel detect 3004, shallow housing, language kit English Art.-no. 32424 - Type detect 3004 S GB
2 slots for 2 loop-interfaces for the connection of up to 4 loops with a maximum of
126 loop 3000 devices per loop and a maximum loop length of up to 3500m
Description:Microprocessor controlled modular fire control panel for the use with the loop3000 fire detection system components approved according to EN 54 and VdS for the use according to VdE 0833
to VdS
For more technical details please see next page.
3. Fire Control Panel detect 3004 and accessories 10
Properties:
EN 12094 for 1 area extinguishing systemsinternational approvals on request
General remarks Scope of delivery without loop cards, network interfaces and batteries
G203068System approval S295054
EN 54-4: 1997
230 V AC (-15%/+10%)
Fire Control Panel detect 3004, deep housing, language kit English Art.-no. 32421 - Type detect 3004 M GB
Standards EN 54-2: 1997
4 alphanumeric lines LC-display, backlight
Material Sheet steel 490 mm x 420 mm x 150 mm (shallow housing)
VdS approval
Supply voltagePower supply
Emergency supply
24 V DC / 72 W / 3,5
86 mA
IP 30Protection class
-5°C to +40°C
Quiescent current Alarm current
3 inputs for collective signal
20 LED-display for status signal 1 x 24 V / 400 mA monitored for sounding/signalling devicesup to 4 loop 140 mA / 3500 m for up to 126 loop3000 elements each3 relays outputs 250 V / 5 A for alarm and fault
5-95 % (non-condensing)Humidity
8 open collector outputs 30 V DC / 90 mAInputsAmbient temperature
Technical data
Different access levels with password protection
Visual diagnostics and remote-control operations via the visualization software "Visual detect"
Commissioning and service tool for analyzing and fault finding functions with "I-Check" software
Time controlled changeovers of sensitivity levels of loop3000 detectors by day/night modes
Software controlled disablements for zones and individual detectors via external inputs
Weight 12,5 kg, without batteries
Fire Control Panel detect 3004, shallow housing, language kit English Art.-no. 32424 - Type detect 3004 S GB
146 mA RS 232
1 output 24 V DC/800 mA for external devices 2 x 12 V/12 Ah (shallow housing) 26 Ah (deep housing)
Ability to change and edit inspection and reaction times along with all delays
Programming options for different alarm modes
Incl. English language kit for control and programming
RS485 and Bitbus as option for network
Further approvals
Outputs
Display
Interfaces
Dimensions (H x W x D)
Colour Light grey, RAL 7035
490 mm x 420 mm x 210 mm (deep housing)
3. Fire Control Panel detect 3004 and accessories 11
Properties:
Dimensions (H x W) 75 mm x 159 mm
Transmission interface for detect 3004 unit interface Art.-no. 31242 - Type FIB
Integrated protection for the monitored output and the operation voltage
Connection directly to the CPU-main board via 26 pole ribbon cable (included in the scope of supply)
Description:Interface - board with defined inputs and outputs for the monitored activation of external dialers for the mounting into the fire control panels of the series detect 3004
Display board available under Art.-no. 30090
0°C up to + 40°CAmbient temperature
Technical data
Monitored connection for transmission unit (programmable)
Control unit for transmission unit, main alarm relay and delay
Suitable for all fire control panels of the series detect 3004 and the remote display control panel
For the triggering of a fire brigade control board, an transmission unit and a key deposit box
4. Accessories for Fire Control Panels detect 3004 and detect 3004 plus12
Properties:
to use the latest version of our loop-calculator
Standards EN 54-2, 17For the calculation of the loop structure it is necessary General remarks
1 Loop - interface, active, 140 mA for detect 3004 and detect 3004plus
Art.-no. 32254 - Type DLI 3120P X1 - 1L
1 x RS 2321 Loop 140 mA / 3500 m for up to 126 loop3000 devices
40 mADepending on the loop structure-max. 120 mA
Easy and flexible installation and initialization via automatic and manual addressing
Integrated RS 232-interface for an easy analysis of the loop components,
Description:Microprocessor controlled loop interface for the uninterruptible and short-circuit-proof use with the loop3000 fire detection system components for the connection of 126 fire detection system components on one loop or 2 spurs
Integrated short circuit isolaters on all loop outputs
Up to 42 T-branches per loop possible
Technical data
the preadjustment of functions and commissioning of loop3000
8 integrated freely programmable open-collector-alarm outputs
2 integrated open-collector-alarm outputs for the programming of collecting functions
Supply via fire control panel detect 3004
Connection of loop3000 components in loop structure or spur-structure
2-wire-system-loop with up to 3.500 m loop length, (using wire lead JY(St)Y 2x2x0,8mm)
with detect 3004 VdS approval
5-95 % (non-condensing)HumidityDimensions (H x W x D) Weight
140 mm x 140 mm x 30 mm
Ambient temperature
2 freely programmable monitored inputs2 open collector outputs 30V DC / 90 mA for alarm and fault8 open collector outputs 30 V DC / 90 mA freely programmable-5°C to 40°C
Outputs
Commissioning and service tool for analyzing and fault finding functions with "I-check" software
S295054 System approval
200 g
Supply voltageEmergency supplyNo load currentQuiescent currentAlarm currentInterface
20-28 V DC via detect 3004 supply
alternatively 2 spurs
via detect 3004 supply
Depending on the loop structure-max. 250 mA
4. Accessories for Fire Control Panels detect 3004 and detect 3004 plus13
Properties:
2 Loop - interface, active, 2 x 140 mA for detect 3004 and detect 3004plus
Art.-no. 32098 - Type DLI 3240P X1
20-28 V DC via detect 3004 supply
per loop / alternatively 4 spurs
via detect 3004 supply
Depending on the loop structure-max. 470 mA
Commissioning and service tool for analyzing and fault finding functions with "I-Check" software
Integrated short circuit isolaters on all loop outputs
Up to 42 T-branches per loop possible
Technical data
S295054 System approval
200 g
Supply voltageEmergency supplyNo load currentQuiescent currentAlarm currentInterface
140 mm x 140 mm x 30 mm
2 open collector outputs 30V DC / 90 mA for alarm and fault8 open collector outputs 30 V DC / 90 mA freely programmable-5°C to 40°C
Outputs
2 integrated open-collector-alarm outputs for the programming of collecting functions
Supply via fire control panel detect 3004
with detect 3004 VdS approval
5-95 % (non-condensing)HumidityDimensions (H x W x D) Weight
Ambient temperature
4 freely programmable monitored inputs
2 Loop - interface, active, 2 x 140 mA, redundant for detect 3004 and detect 3004plus
Art.-no. 32312 - Type DLI 3240P X1 - R
the preadjustment of functions and commissioning of loop3000
8 integrated freely programmable open-collector-alarm outputs
Easy and flexible installation and initialization via automatic and manual addressing
Integrated RS 232-interface for an easy analysis of the loop components,
Description:Microprocessor controlled loop interface for the uninterruptible and short-circuit-proof use with the loop3000 fire detection system components for the connection of 2 x 126 fire detection system components on two loops or 4 spurs DLI 3240P X1 - R comes in redundant version with a second processor for increased reliability in the loop (redundancy)
Connection of loop3000 components in loop structure or spur-structure
2-wire-system-loop with up to 3.500 m loop length, (using wire lead JY(St)Y 2x2x0,8mm)
1 x RS 2322 loops with each 140 mA / 3500 m for up to 126 loop3000 devices
40 mADepending on the loop structure-max. 210 mA
to use the latest version of our loop-calculator
Standards EN 54-2, 17For the calculation of the loop structure it is necessary General remarks
4. Accessories for Fire Control Panels detect 3004 and detect 3004 plus14
Properties:
Properties:
Connection of conventional detectors of other manufacturers on requestStandards EN 54-2, 17General remarks
Conventional-Interface, 8 detector zones for detect 3004 and detect 3004plus
Art.-no. 30210 - Type CLI X1
8 open collector outputs 30 V DC / 90 mA freely programmable
Approx. 50 mAApprox. 80 mA
8 integrated freely programmable open-collector-alarm outputs
2 integrated open-collector-alarm outputs for the programming of collecting functions
Description:Microprocessor controlled conventional interface for the uninterruptible and short-circuit-proof use with conventional detectors of the series CT 3000
Technical data
Connection of up to 25 automatic conventional detectors of the series CT 3000
(10 manual call points) per detector zone
with detect 3004 VdS approval
5-95 % (non-condensing)HumidityDimensions (H x W x D) Weight
140 mm x 140 mm x 30 mm
Ambient temperature -5°C to 40°C
Supply via fire control panel detect 3004
S295054 System approval
200 g
Supply voltageEmergency supplyQuiescent currentAlarm currentOutputs
20-28 V DC via detect 3004 supplyvia detect 3004 supply
2 open collector outputs 30 V DC / 90 mA for alarm and fault
Mounting plate for LED indicator module and printer for detect 3004 / detect 3004plus
Art.-no. 30210 - Type CLI X1
Description:Mounting plate for the installation into the front door of the fire control panel detect 3004 in case of use of the LED indicator modules and/or the printer
Technical data
Suitable for all fire control panels of the series detect 3004
and for the remote display and control panel
Mounting of up to 6 pieces LED indicator modules ZM 8 possible
Provides facility for mounting of a built in printer PIP 2Scope of supply including film and labelling strips
Colour Film RAL 7046 telegrey, plaque RAL 7035 light greyMaterial Sheet steelDimensions (H x W) 228 mm x 365 mm
General remarks A subsequent mounting in the fire control panel is possible at any time
Weight Approx. 0,7 kgSystem approval S295054
4. Accessories for Fire Control Panels detect 3004 and detect 3004 plus15
Properties:
Properties:
System approval S295054
HumidityDimensions (H x W x D) Weight
Extension Module for LED indicator 3 - 6 for detect 3004 and detect 3004plus
System approval
Art.-no. 30386 - Type ADB 48
For the extension with LED indicator modules for 16 to 48 zones indication
5-95 % (non-condensing)Ambient temperature
VdS approval
Supply voltageEmergency power supplyQuiescent currentAlarm current
2 modules can be connected directly to the CPU
Suitable for all fire control panels of series detect 3004
8 red LEDs for the indication of alarms of each detector zone
via detect 3004 supply
Possibilty for the labelling of each detector zone in the front of the panel,
by the integration in the front plate MP 3004 (not included in the basic version)
Up to 6 LED indicator modules can be connected in the front of the panel
LED indicator module, 8 detector zones for detect 3004 and detect 3004plus Art.-no. 30088 - Type ZM 8
8 yellow LEDs for the indication of faults of each detector zone
Direct connection to the CPU via a 10 pole ribbon cable (included in delivery)
Description:LED indicator module for the status indication of 8 detector zones with yellow LEDs for fault and red LEDs for alarm for the mounting into the front door of the fire control panel detect 3004
Technical data
Approx. 2 mAPlus approx. 2 mA per LED-activation8 LED indicators red
For the modules 3-6 an adapter board will be necessary (Art-no. 30386)
20-28 V DC via detect 3004 supply
Outputs
Suitable for all fire control panels of series detect 3004
Description:
Extension module for the connection of the 3rd up to the 6th
LED indictor module ZM 8 to the fire control panel of the series detect 3004
8 LED indicators yellow-5 to 40°C
80 mm x 43 mm x 12 mm Approx. 30gwith detect 3004S295054
Standard EN 54-2, 17
Outputs 4 x 10 poles M
Connection directly to the CPU maion board via 14 pole ribbon cable (incl. in the scope of delivery)
Supply voltage 20-28 V DC via detect 3004 supplyEmergency power supply via detect 3004 supply
Technical data
4. Accessories for Fire Control Panels detect 3004 and detect 3004 plus16
Properties:
Standards EN 54-2
Indicator board for transmission unit interface for detect 3004 and detect 3004plus
Art.-no. 30090 - Type TIB
2 LED indicators yellow
Approx. 3 mA per LED-activation4 LED indicators red
1 LED- display yellow for the free switchable input of the UEI 3004plus ( key deposit box - alarm)
1 LED- display green for the free switchable input of the UEI 3004plus (key deposit box unlocked)
Description:Indicator board for the front door of the fire control panel detect 3004 for the status indication of the transmission unit interface
Technical data
1 LED- display yellow for the status indication of the buttom for manual operation
(Transmission unit on-off)
1 LED- display yellow for the status indication of the buttom for manual operation (delay on/off)
Suitable for all fire control panels of series detect 3004 and the Remote and Display Control Panel
3 LED-indicators red for alarm (main alarm, "fire brigade called", "call fire brigade")
5-95 % (non-condensing)HumidityDimensions (H x W x D) Weight
145 mm x 50 mm x 14 mm
Connection directly to the CPU via a 14 pole ribbon cable (included in delivery)
S295054 System approval
Approx. 50g
Supply voltageEmergency supplyAlarm current
20-28 V DC via detect 3004 supply
with detect 3004plusVdS approval
via detect 3004 supply
1 LED indicators green
Ambient temperature -5°C to 40°C
Outputs
4. Accessories for Fire Control Panels detect 3004 and detect 3004 plus17
Properties:
Adjustment possibilities of the pre alarm time of 0-60 sec via DIP - switch
Adjustment possibility for the fllooding time of 0-1270 sec via DIP - switch
Outputs
Standards EN12094-1
with EST 3004 G203068 VdS approval
5-95 % (non-condensing)HumidityDimensions (H x W x D)
Extinguishing control card, 1 extinguishing area for detect 3004 and detect 3004plus
Art.-no. 30111 - Type ETB X1
4 relay contacts
Approx. 50 mA60 mA + to 1 A per control line
Integrated additional signal device lines for the connection of signalling devices
in the extinguishing area (evacuation of the area)
Description:Microprocessor controlled extinguishing control card for the connection of an extinguishing area to the fire control panel detect 3004 approved as extinguishing control accord. to EN 12094
4 integrated relay contacts for pre-alarm, extinguishing activation, emergency stop
and re-flooding function
Technical data
2 lines for the activation of emergency stop and re-flooding function
4 low active-inputs for activation of the extinguishing mimic
via alarm outputs of the loop or conventional card
2 low active inputs for the advanced blockade of the extinguishing function
3 controllable monitored outputs for the control of the main- and area valve
and the re-flooding of the extinguishing area
via detect 3004 supply
Weight140 mm x 140 mm x 20 mm
Ambient temperature -5°C to 40°C
4 monitored control lines (max. 1 A)
Supply and use via internal bus of the fire control panel detect 3004
S295054 System approval
Approx. 210g
Supply voltageEmergency supplyQuiescent currentAlarm current
21-29 V DC via detect 3004
4. Accessories for Fire Control Panels detect 3004 and detect 3004 plus18
Properties:
Properties:
Description:Universal additional casing, design according to size "M" of the fire control panel detect 3004 for the use of additional components
Dimensions (H x W X D)Weight
Additional casing, deep for detect 3004 Art.-no. 31318 - Type UZG 1
RAL 7035 light grey
Built in door lock with simultaneous locking to the panels detect 3004
Colour RAL 7035 light grey
VdS approvalSystem approval
Technical data
Door with 2 built in dummy boards
ColourMaterial
Weight 7,4 kg
Sheet steel
with detect 3004
Standards EN 54-2, 17
Dimensions (H x W X D) 490 mm x 420 mm x 210 mm Material Sheet steel
Assembly frame 19" rack for detect 3004 and detect 3004plus
Art.-no. 30161 - Type RMK 19
S295054
532,6 mm x 482,6 mm x 220 mm 5,25 kg
Description:Assembly frame for the adaption of fire control panels of the series detect 3004 to 19" racks
Technical data
Suitable for all fire control panels of the series detect 3004 and the remote display and control panelDelivery inluding mounting accessories
4. Accessories for Fire Control Panels detect 3004 and detect 3004 plus19
Properties:
Weight EABK-2 25 kgRack units (heigth) 5 HERack units (width) 2 BE
of the breather hole via smoke detectors
with locking activation and automatic triggering in case of fire
Locking activation at rise of temperature and electromagnetic activation
Highest mechanical strenght and chemical resistance
Integrated adjustable mounting system for the installation of the fire control panel detect 3004plus
500 x 620 x 195 mm EABK-2 (H x W x D)
914 x 664 x 496 mm
Protection classColour housingDIN ENDIBT
Outer dimensions ( H x W x D)750 x 500 x 340 mm
Further approvals (DIBT) Z-86. 1-7
Locking via driving plate with 2 point interlocking
Technical data
Housing for the on wall mounting with door stop left side
Removable door with locking option via turning lever
Angle of aperture of the door approx. 180°
Cable sealing for bundly entry (top, down, both sides)
Fire resistance and funtional integrity of more than 30 minutes accoding to F30,
tested according to DIN 4102 part 11 and 12
Fire protection housing, F30 for detect 3004plus
Art.-no. 32441 - Type BSG 3004
4102 part 2Z-86. 1-9
Smoke proof design with surface coating A2 - non combustible, protection class II
With cable cooling part EABK-2 and electromagnetic lock of the ventilation opening EBEL-EM
Description:Fire protection housing F30 as empty housing for the
installation of fire control panels detect 3004plus S or M size
Including mounting strap for wall mounting
Tridimensional adjustable entry systemfor all standard device mounting types
Integrated air cooling system via the backside and ventilation part
Space units 120 PE
Dimensions cable cooling part
116 kgWeightInside dimension ( H x W x D)
IP 42RAL 7035 (Lightgrey)
5. Fire Control Panel detect 3016 and accessories 20
Properties:
Description:Microprocessor controlled modular fire control panel for the use with the loop3000 fire detection system components approved according to EN 54 and VdS for the use according to VdE 0833
for 6 extinguishing areas in accordance to EN12094
Without 19'' rack
Integrated display and control panel according to DIN EN 54
Option for up to 11 slots for extension boards and the connection
Description:Microprocessor controlled modular fire control panel for the use with the loop3000 fire detection system components approved according to EN 54 and VdS for the use according to VdE 0833
key deposit and transmission units
Integrated interface slot for the connection for up to 63 additional network components
with a maximum of 126 loop 3000 devices per loop and a maximum loop lenght of 3500m
Connection option for a fire brigade interface for controlling the panels outputs,
Fire Control Panel detect 3016, wall mounted housing, language kit English Art.-no. 32422 - Type detect 3016 XL GB
Basic version with 5 slots for 2 redundant loop-interfaces for the connection of up to 10 loops
Mounting plate equipped: approx. 16,8kgScope of delivery
Technical data
Dimensions 750 mm x 600 mm x 240 mm
of up to 16 loops with 126 loop3000 devices per loop
Option for 8 conventional interface cards for controlling up to 64 conventional zones
Extinguishing interface option for controlling extinguishing and gas suppression systems
4 alphanumeric lines LC-display with backlight
key deposit and transmission unitsEmergency power supply via 2 batteries 12V / up to 45 Ah
Weight 13,5 kg, without batteries
Dimensions (H x W x D) Front requires 6 HE in 19" FrontWeight Operation front: approx. 2,3 kg
Fire Control Panel detect 3016, 19" front, English language kit Art.-no. 32436 - Type detect 3016 19'' GB
For more technical details please see next page.
5. Fire Control Panel detect 3016 and accessories 21
Properties:
20 LED-display for status signal
Fire Control Panel detect 3016, 19" front, English language kit Art.-no. 32436 - Type detect 3016 19" GB
Approx. 250 mA
1 output 24 V DC/800 mA for external devices 2 x 12 V/ 45 Ah
Integrated power supply 192 W according to EN 54 with
with 2 outputs for external devices rated at 24V DC/ 800mA
Display
Incl. English language kit for control and programming
Technical data
1 external output 24 V / 400 mA monitored for sounding/signalling devices
3 potential free relays for fire and fault
Segmented front door allowing the quick assembly of LED indicator Modules and printers
Integrated RS 232 - interface for the DPT programming software
and the connection of printers and other peripheral equipment
3 inputs for collective signals
Alarm current 2 x RS 232; RS 4 and Bitbus as option for networkInterfaces
Software controlled disablements for zones and individual detectors via external inputs
Ability to change and edit inspection and reaction times along with all delays
Programming options for different alarm modes
Different access levels with password protection
Visual diagnostics and remote-control operations via the visualization software "Visual detect"
Commissioning and service tool for analyzing and fault finding functions with "I-Check" software
Emergency supply
24 V DC / 72 W / 3,5
Approx. 190 mA Quiescent current
230 V AC (-15%/+10%)
Fire Control Panel detect 3016, wall mounted housing, language kit English Art.-no. 32422 - Type detect 3016 XL GB
Inputs 3 inputs for collective signal
4 alphanumeric lines LC-display, backlight
Time controlled changeovers of sensitivity levels of loop3000 detectors by day/night modes
Supply voltagePower supply
1 x 24 V /400 mA monitored for sounding/signalling devicesup to 16 loops 140 mA / 3500 m for up to 126 loop3000 elements each
Ambient temperature -5°C up to +40°C
3 relays outputs 250 V / 5 A for alarm and fault8 open collector outputs 30 V DC / 90 mA
Outputs
Colour Light grey, RAL 7035
Humidity 5-95% (non-condensing)Protection class IP30
Option for customised front logos
Up to 196 programmable detector zones
Possibility for complete system redundancy with redundant CPU and redundant loop interfaces
Additional up to 42 T-branches per loop possible
Event log memory of up to 500 messages
Programming of control logics and time dependent functions for the components of series loop3000
Customized customer texts allowing up to a maximum of 20 characters
Integrated alarm buffer and 2 detector/zone dependencies
For more technical details please see next page.
5. Fire Control Panel detect 3016 and accessories 22
Properties:
Ground fault montoring via module EM (Art.-no. 30927)
Fire Control Panel detect 3016, 19" front, English language kit Art.-no. 32436 - Type detect 3016 19" GB
EN 54-2:1997
S295054EN 12094
General remarks
Technical data
EN 54-4: 1997Standards
Fire Control Panel detect 3016, wall mounted housing, language kit English Art.-no. 32422 - Type detect 3016 XL GB
Scope of delivery without loop cards, network interfaces and batteries
MaterialVdS approval System approval
G203067
EN 12094 for 1 extinguishing systemsFurther approvals
Sheet steel
Conventional-Interface, 8 detector zones, redundant for detect 3016 Art.-no. 30096 - Type CLI X2 - R
Description:Microprocessor controlled conventional interface for the uninterruptible and short-circuit-proof use with conventional detectors of the series CT 3000 with second processor for increased reliability (redundancy)
Supply via fire control panel detect 30162 integrated open-collector-alarm outputs for the programming of collecting functions
Technical data
Connection of up to 25 automatic conventional detectors of the series CT 3000
(10 manual call points) per detector zone
8 integrated freely programmable open-collector-alarm outputs
Supply voltage 20-28 V DC via detect 3016 supplyEmergency supply via detect 3016 supplyQuiescent current Approx. 50 mAAlarm current Approx. 80 mAOutputs 2 open collector outputs 30 V DC / 90 mA for alarm and fault
8 open collector outputs 30 V DC / 90 mA freely programmableAmbient temperature -5°C to 40°CHumidity 5-95 % (non-condensing)Dimensions (H x W x D) 140 mm x 140 mm x 30 mm Weight 200 gVdS approval with detect 3016 System approval S295054 Standards EN 54 - 2, 17General remarks Connection of conventional detectors of other manufacturers on request
5. Fire Control Panel detect 3016 and accessories 23
Properties:
20-28 V DC via detect 3016 supply
alternatively 4 spurs
via detect 3016 supply
Depending on the loop structure-max. 470 mA
Commissioning and service tool for analyzing and fault finding functions with "I-Check" software
S295054 System approval
200 g
Supply voltageEmergency supplyNo load currentQuiescent currentAlarm currentInterface
Ambient temperature
4 freely programmable monitored inputs2 open collector outputs 30V DC / 90 mA for alarm and fault8 open collector outputs 30 V DC / 90 mA freely programmable-5°C to +40°C
Outputs
with detect 3016 VdS approval
5-95 % (non-condensing)HumidityDimensions (H x W x D) Weight
140 mm x 140 mm x 30 mm
Integrated short circuit isolaters on all loop outputs
Up to 42 T-branches per loop possible
Technical data
the preadjustment of functions and commissioning of loop3000
8 integrated freely programmable open-collector-alarm outputs
2 integrated open-collector-alarm outputs for the programming of collecting functions
Supply via fire control panel detect 3016
Connection of loop3000 components in loop structure or spur-structure
2 - wire - system - loop with up to 3.500 m loop length, (using wire lead JY(St)Y 2x2x0,8mm)
2 Loop - interface, active, 2 x 140 mA, redundant for detect 3016 Art.-no. 32099 - Type DLI 3240 X2 - R
1 x RS 2322 Loops 140 mA / 3500 m for up to 126 loop3000 devices
40 mADepending on the loop structure-max. 210 mA
Easy and flexible installation and initialization via automatic and manual addressing
Integrated RS 232-interface for an easy analysis of the loop components,
Description:Microprocessor controlled loop interface for the uninterruptible and short-circuit-proof use with the loop3000 fire detection system components for the connection of 2 x 126 fire detection system components on two loops or 4 spurs
to use the latest version of our loop-calculator
Standards EN 54-2, 17For the calculation of the loop structure it is necessary General remarks
5. Fire Control Panel detect 3016 and accessories 24
Properties:
Properties:
System approval S295054
VdS approval
Standards
Ground circuit module for detect 3016 Art.-no. 30927 - Type EM
Monitoring of the galvanic seperation between ground potential and secondary voltages, e.g.:
with detect 3016
VdS approval with detect 3016Weight 50 g
Supply voltageEmergency power supplyOutputsAmbient temperature
System approval
3 connectors for plug in boards-5°C to +40°C5-95 % (non-condensing)
Extension module, 3 Slots for detect 3016 Art.-no. 30097 - Type ECB
1 slot for output and alarm modules
Connection of the peripherals via integrated screw clamps
Description:Extension module for 3 additional slots for loop interfaces, conventional interfaces or output boards for the use in fire control panels detect 3016
Technical data
Suitable for all fire control panels of series detect 3016
2 slots for loop- and conventional interfaces
Connection directly to the CPU via a 20 pole ribbon cable (included in delivery)
20 - 28 V DC via detect 3016 supply
Humidity
via detect 3016 supply
Description:Plug in module for the detect 3016 fire control panel for monitoring of the galvanic seperation between ground potential and all secondary voltages accord. to EN 54-2,
320 mm x 120 mm x 104 mm Approx. 420g
EN 54-2, 17
Dimensions (H x W x D) Weight
S295054
Emergency current supply via detect 3016
Technical data
Suitable for all fire control panels of the series detect 3016
Outputs OC switching voltage-fault output 29VOC switching current-fault output 100mA
Alarm current 15 mA
General remarks max. 2 extension modules per detect 3016
Quiescent current 7 mA
Line voltage, Loop voltage, Voltages of the outputs, Ground potential of the panelIntegrated mounting possibility onto a DIN rail
Operation voltage 20-28 V DC via detect 3016
Ambient temperature -5°C to 40°CHumidity 5-95% (non-condensing)Material Polyamid PA 6.6Dimensions 59 mm x 20 mm x 60 mm
5. Fire Control Panel detect 3016 and accessories 25
Properties:
Properties:
VdS approval with detect 3016
Standard EN 54-2, 17
Dimensions 400 mm x 483 mm
Provides facility for mounting of a built in printer PIP 2Scope of supply including film and labelling strips; a subsequent mounting is possible at any time
Colour Film RAL 7046 telegrey, plaque RAL 7035 lightgreyMaterial Sheet steel
Technical data
Suitable for all fire control panels of the series detect 3016
Description:Mounting plate for the installation into the front door of the fire control panel detect 3016 in case of use of the LED indicator modules and/or the printer accord. to EN 54-2,17
32 LED indicators yellow-5 to 40°C
108 mm x 194 mm x 34 mm Approx. 130gwith detect 3016S295054
Ambient temperature
Approx. 10 mAPlus approx. 2 mA per LED-activation32 LED indicators red
Suitable for the connection to the Bitbus-LED-Interface (Art-no. 30128)
20-28 V DC via detect 3016 supply
Outputs
LED indicator module, 32 detector zones for detect 3016 Art.-no. 30098 - Type ZM 32
32 yellow LEDs for the indication of faults of each detector zone
Direct connection to the CPU via a 26 pole ribbon cable (included in delivery)
Description:LED indicator module for the status indication of 32 detector zones with yellow LED for fault and red LED for alarm for the mounting into the front door of the fire control panel detect 3016
Technical data
Up to 6 LED indicator modules can be connected in the front of the panel
Suitable for all fire control panels of series detect 3016
32 red LEDs for the indication of alarms of each detector zone
via detect 3016 supply
Possibilty for the labelling of each detector zone in the front of the panel,
by the integration in the front plate MP 3016 (not included in the basic version)
Free programming of LEDs to OC outputs
VdS approval
Supply voltageEmergency power supplyQuiescent currentAlarm current
System approval S295054
HumidityDimensions (H x W x D) Weight
Mounting plate for LED indicator module and printer for detect 3016
System approval
Art.-no. 31947 - Type MP 3016
Mounting of up to 6 pieces LED indicator modules ZM 32 possible
5-95 % (non-condensing)
5. Fire Control Panel detect 3016 and accessories 26
Properties:
Adjustment possibility for the fllooding time of 0-1270 sec via DIP-switch
Outputs
Standards EN12094-1
with EST 3016 G203067 and G207003 VdS approval
5-95 % (non-condensing)HumidityDimensions (H x W x D)
Extinguishing control card, 1 extinguishing area for detect 3016 Art.-no. 40003 - Type ETB X2
4 relay contacts
Approx. 50 mA60 mA + to 1 A per control line
Integrated additional signal device lines for the connection of signalling devices
in the extinguishing area (evacuation of the area)
Description:Microprocessor controlled extinguishing control card for the connection of an extinguishing area to the fire control panel detect 3016 approved as extinguishing control accord. to EN 12094
4 integrated relay contacts for pre-alarm, extinguishing activation, emergency stop
4 monitored control lines (max. 1 A)
and re-flooding function
Technical data
2 lines for the activation of emergency stop and re-flooding function
4 low active-inputs for activation of the extinguishing mimic
via alarm outputs of the loop or conventional card
2 low active inputs for the advanced blockade of the extinguishing function
3 controllable monitored outputs for the control of the main- and area valve
and the re-flooding of the extinguishing area
Adjustment possibilities of the pre alarm time of 0-60 sec via DIP-switch
Weight140 mm x 140 mm x 20 mm
Ambient temperature -5°C to 40°C
Supply and use via internal bus of the fire control panel detect 3004
S295054 System approval
Approx. 220g
Supply voltageEmergency supplyQuiescent currentAlarm current
21 - 29 V DC via detect 3016via detect 3016 supply
5. Fire Control Panel detect 3016 and accessories 27
Properties:
Weight EABK-2 31 kg
High mechanical strenght and stability
500 x 620 x 195 mm EABK-2 (H x W x D)
1024 x 874 x 434 mm
Protection class
Rack units (heigth) 6 HERack units (width) 3 BE
Outer dimensions ( H x W x D)
Tridimensional adjustable entry system for all standard device mounting types
Including mounting strap for wall mounting
Locking via driving plate with 2 point interlocking
Integrated air cooling system with locking activation
Locking activation at rise of temperature
Electromagnetic activation of the breather hole via smoke detectors
High chemical resistance
RAL 7035 (Lightgrey)Colour housingDIN ENDIBT
Smoke proof
With cable cooling part EABK-3 and electromagnetic lock of the ventilation opening EBEL-EM
Housing for the on wall mounting
900 x 750 x 340 mm
Further approvals (DIBT) Z-86. 1-7
Locking option via turning lever
4102 part 2Z-86. 1-9
IP 41
Door stop left side
Fire resistance F30, tested according to DIN 4102 part 2
Functional integrity of more than 30 minutes, according to DIN 4102 part 11
Fire protection housing, F30 for detect 3016 Art.-no. 32442 - Type BSG 3016
Fire load insulation of more than 30 minutes, according to DIN 4102 part 11
Surface coating A2 - non combustible
Description:Fire protection housing F30 as empty housing for the installatin of fire control panels detect 3016
Technical data
Removable door for weight reduction
Angle of aperture of the door approx. 180°
Cable sealing for bundly entry (top, down, both sides)
Space units 216 PE
Dimensions cable cooling part
169 kgWeightInside dimension ( H x W x D)
6. Accessories for Fire Control Panels detect 3004 and detect 3016 28
Properties:
Green
Display 12 LEDs for operation and status signal
ABS
Please consider the dimensioning of the current supply and emergency supply
General remarks
125 mm x 130 mm x 70 mm Dimensions (H x W x D)
the correct wiring of the output lines
Weight Approx. 220 gAt use of low resistance signalling devices (alarm bells) consider
90 mA
4 x 580 mA monitored, short-circuit-proof,
Cascading option of multiple modules of the same type
Operation voltageQuiescent currentAlarm currentInputsOutputs
Module -housing for the easy mounting onto a DIN rail
Possibility for 4 additional monitored and short-circuit-proof outputs
with max. 580 mA line current each
Material
-10°C to 50°CAmbient temperatureHumidityColour
10-85% (non-condensing)
21-37 V DC
Technical data
7 inputs for the control of signal lines
Adjustment possibility for individual or collective control of all signal lines via jumper
24 V supply via supply unit of the fire control panel
Output card Sounder, 4 outputs, monitored, for detect 3004 / 3016 Art.-no. 32066 - Type SC 4
switch for high and low resistant applications
500-2600 mA4 potentialfree
Connection of high and low resistant signalling devices via integrated pole switch
Outputs can be activated to be dependend on the buttom "ext. Warning on/off" of the fire control panel
Description:Output card for a monitored connection of up to 4 additional short-circuit-proof signal lines to the fire control panels of series detect 3004 and detect 3016
12 LED's for indication of operation and status
6. Accessories for Fire Control Panels detect 3004 and detect 3016 29
Properties:
Display 8 LEDs for status signal of the outputs
ABS
and emergency supplyGeneral remarks
125 mm x 175 mm x 60 mmDimensions (H x W x D) Material
-10°C to 50°CAmbient temperature
21-28 V DC58 mA
8 monitored outputs, seperately fused, 400 mA
8 LEDs for indication of status
Operation voltageQuiescent currentAlarm currentInputsOutputs
HumidityColour
10-85% (non-condensing)Green
Description:Control board for a monitored connection and the manual control of up to 8 additional signalling lines to the fire control panels detect 3004 and detect 3016
Cascading option of multiple modules of the same type
Module-housing for the easy mounting onto a DIN rail
Technical data
Outputs can be activated to be dependend on the buttom "ext. Warning on/off" of the fire control panel
Adjustment possibility for individual or collective control of all signal lines
Central function for reset, lamp test etc.
24 V supply via supply unit of the fire control panel
Possibility for 8 additional monitored and seperately fused outputs with max. 400 mA each
8 additional parallel OC outputs (e.g. for the indication of status)
Weight Approx. 310 gPlease consider the dimensioning of the current supply
Alarm control module, 8 outputs, monitored, for detect 3004 / 3016 Art.-no. 30118 - Type SC 8
Quiescent current + current of each signal line16 potentialfree
8 inputs for the parallel switch of the outputs of the control board
(possibility for the manual activation of the outputs)
6. Accessories for Fire Control Panels detect 3004 and detect 3016 30
Properties:
Weight Approx. 300 gPlease consider the dimensioning of the current supply
Relay board, 8 change over contacts for detect 3004 / 3016 Art.-no. 30077 - Type RB 8
30-240 mA (30 mA per relay)8, low active
1 input for the release or the switch off of the functions of the control board (e.g. at "FCP - door open")
Power supply 24V via power supply unit of the fire control panel
Description:Control board for the connection of up to 8 additional external change over contacts for the fire control panels detect 3004 and detect 3016
Technical data
Module-housing for the easy mounting onto a DIN rail
Possibility for 8 additional change over contacts for the control of external circuits of up to 250 V / 5A
8 low-active inputs for the parallel switch of the outputs of the control board
HumidityColour
10-85% (non- condensing)Green
21-28 V DC5 mA
8 change over contacts 250 V / 5 A
8 LEDs for indication of status
Operation voltageQuiescent currentAlarm currentInputsOutputs
Display 8 LEDs for status signal of the outputs
ABS
and emergency supplyGeneral remarks
125 mm x 110 mm x 60 mm Dimensions (H x W x D) Material
-10°C to 50°CAmbient temperature
6. Accessories for Fire Control Panels detect 3004 and detect 3016 31
Properties:
Properties:
Up to 3 AM-modules can be used in the fire control panel detect 3016
General remarks
Ambient temperature -10°C to 50°C
Approx. 165 g
For remote mounting please use adapter module (Art.-no. 30116)
Please consider the dimensioning of the current supply Weight
10-85% (non-condensing)Humidity
21-28 V DC3,5 mA
32 alarm zones
via ribbon cable of the detect 3004 or the adapter plate (Art.-no. 30116)
Operation voltageQuiescent currentAlarm currentInputsOutputs
ColourDimensions (H x W x D)
Green140 mm x 140 mm x 25 mm
Technical data
Easy mounting via 32 pole pin contact bar in the connection board of the detect 3016,
Extension for 32 programmable alarm output areas
Activation via internal I²C-bus or via RS232-Interface of the fire control panel
and emergency supplyUp to 24 outputs usable in the fire control panel detect 3004
Alarm control module, 32 zones, for detect 3004 / detect 3016 Art.-no. 30115 - Type AM
90 - 2880 mA (max. 90 mA per alarm output)RS 232
Remote mounting by connectors (via RS 232)
Power supply 24V via power supply unit of the fire control panel
Description:Microprocessor controlled extension module for 32 additional programmable alarm outputs (OC-Outputs) for the extension of the output matrix of the fire control panels detect 3004 and detect 3016
Connection board for alarm module AM Art.-no. 30116 - Type AM AP
Description:Adapter module for the external use or remote mounting of the alarm module AM outside the fire control panels
Remote mounting by connectors possible
Ambient temperature -10°C to 50°C
Technical data
Module housing for easy mounting on DIN-rail
Terminal block for easy external circuits
Humidity 10-85% (non-condensing)Colour OrangeMaterial ABSDimensions (H x W x D) 88 mm x 175 mm x 70 mm
at the predetermined breaking pointGeneral remarksWeight Approx. 290 g
When using the adapter module please downsize the alarm module
6. Accessories for Fire Control Panels detect 3004 and detect 3016 32
Properties:
Properties:
Weight Approx. 310 g
Material ABSDimensions (H x W x D) 115 mm x 115 mm x 80 mm
Black
Ambient temperature 0°C to 50 °CHumidity 10-85 % (non-condensing)
Mount in printer for the fire control panels detect 3004 / detect 3016 Art.-no. 30106 - Type PIP 2
100 mAQuiescent currentAlarm Current
Powered directly from the fire control panel58 mm paper width
Direct connection to the RS 232 Interface of the fire control panel
8 kB of Integrated Buffer Memory
Operation voltage
Thermoprint with fixed print heads
24 characters per line
Description:Thermo-printer for the integration to the front plate of the fire control panels detect 3004 and detect 3016
Technical data
Interface
21-28 V DC12 mA
to max. 18 Ah
RS 232Print ASCII Standard, international character set
Paper width 58 mm, Paper roll diameter 38 mm
Colour
Inner diameter (bore) 12,3mm
Technical data
Suitable for mount in printer PIP 2 and PIP 3004plus
Packing unit 5 rolls
Paper width 57mm
Installation of this printer requires eithe mounting plate MP 3004 / 3016The use of this printer in the detect 3004 reduces the battery capacity
General remarks
Outer diameter: 37mm
Thermo-paper for PIP 2 and PIP 3004plus, packing unit 5 rolls Art.-no. 30107 - Type EP 5
Description:Thermo-paper, packing unit 5 rolls
6. Accessories for Fire Control Panels detect 3004 and detect 3016 33
Properties:
VdS approval G208156
-5°C to +40°Cmax rel 95 % (non-condensing)IP 30
0786-CPD-20672
GreyABS380 mm x 235 mm x 96 mm 1,5 kg without accumulators
1,5 A according to operation modeFault relay 1A 50Vmax. 2 x 12V / 3Ah (loading capacity up to 12 Ah)
LED - fault display and potential free fault outputs
230 V AC / 50 Hz24 V
Battery capacity
Primary 1,5A synchronized mains adapter Art.-no. 32805 - Type BF 360-24
Controlled output voltage 24 V
Intelligent battery-management
Description:Universal primary synchronized mains adapter for the use as a emergency power supply unit for the detect 3000 range approved according to EN 54 - 4 A1 2002, A2 2006 and VdS for the use according to VdE 0833
Technical data
Primary synchronized switching power supply with electronic overload functions
Integrated low voltage discharge protection
Ambient temperatureHumidity
Dimensions (H x W x D)
Input voltageOutput voltageOutput currentOutput
Protection class
CPD-Number
ColourMaterial
Weight
6. Accessories for Fire Control Panels detect 3004 and detect 3016 34
Properties:
Properties:
9 kg
Primary 5A synchronized mains adapter Art.-no. 32580 - Type 2405STE
Dimensions (H x W x D) 420 mm x 400 mm x 80 mm
Protection classColour
Input voltageOutput voltage
Primary 2A synchronized mains adapter Art.-no. 32579 - Type 2402STE
Controlled output voltage 27,6 V
Intelligent battery-management
Description:Universal primary synchronized mains adapter for the use as a emergency power supply unit for the detect 3000 range approved according to EN 54 - 4 A1 2002, A2 2006 and VdS for the use according to VdE 0833
Technical data
Primary synchronized switching power supply with electronic overload functions
Integrated low voltage discharge protection
Flexible input voltage range 110 to 230 V
LED - fault display and potential free fault outputs
110 V to 230 V AC / 50 Hz27,6 V nominal
Humidity
2 A for Primary 2 A synchronized mains adapter (Art.-no. 32579)5 A for Primary 5 A synchronized mains adapter (Art.-no. 32580)up to 2x 17 Ah
CPD-Number
Weight
Ambient temperature -10°C to +40°C5-75% (non-condensing)IP 20Grey
Sheet steel0786-CPD-20787
Material
Technical data
Additional housing for 2 x 38 Ah accumulators for the connection to the 5 A synchronized mains adapter
Output current
Battery capacity
separate housing is available under Art.-no 32659 Type BATT-BOX
Battery extra housing for Primary 5 A synchronized mains adapter Art.-no. 32659 - Type BATT-BOX
VdS approval G209142
up to 2 x 38 Ah with separate housing for Art.-no. 32580
6. Accessories for Fire Control Panels detect 3004 and detect 3016 35
Properties:
Art.-no. 30155 - Type WP 12 - 12
Quick connector 4,8 or 6,4 mmInternal resistance with 1KHz 13 mOhmMaximum charging current 3,6 ACapacity: 12 AhDimensions (H x W x D): 100 mm x 151 mm x 9 mmWeight: 4,27 kgVdS approval: G103063
Output voltage
Rechargeable accumulator for the emergency power supply for the fire control panels detect 3004 / 3016
Robust encapsulated housing
Accumulator 12 V / 18 Ah Art.-no. 30156 - Type WP 18 - 12
Connectors for screws M5Internal resistance with 1KHz 10 mOhmMaximum charging current 5,4 ACapacity: 18 AhDimensions (H x W x D): 167 mm x 181 mm x 76 mmWeight: 6,28 kgVdS approval: G103064
Ambient temperatureHumidityProtection class
Accumulator 12 V / 7,2 Ah Art.-no. 40056 - Type WP 7.2 - 12
Maintenance-free
Battery charge condition after one month at 20°C 92%
Quick connector 4,8 or 6,4 mmInternal resistance with 1KHz 22 mOhmMaximum charging current 2,16 ACapacity: 7,2 AhDimensions (H x W x D): 94 mm x 151 mm x 65 mmWeight: 2,45 kgVdS approval: G109001
Technical data
Material ABS
Accumulator 12 V / 12 Ah
5-75% (non-condensing)IP 20Grey
Charging voltage 14,4 to 15 V
12 v DC-10°C to +40°C
Colour
6. Accessories for Fire Control Panels detect 3004 and detect 3016 36
Properties:
Art.-no. 30151 - Type WP 45 - 12
Connectors for screws M6,5Internal resistance with 1KHz 6 mOhmMaximum charging current 13,5 ACapacity: 45 AhDimensions (H x W x D): 171 mm x 198 mm x 166 mmWeight: 14,79 kgVdS approval: G105087
Output voltage
Rechargeable accumulator for the emergency power supply for the fire control panels detect 3004 / 3016
Robust encapsulated housing
Accumulator 12 V / 65 Ah Art.-no. 30461 - Type WP 65 - 12
Connectors for screws M6,5Internal resistance with 1KHz 5 mOhmMaximum charging current 19,5 ACapacity: 65 AhDimensions (H x W x D): 174 mm x 350 mm x 166 mmWeight: 23,55 kgVdS approval: G102001
Ambient temperatureHumidityProtection class
Accumulator 12 V / 26 Ah Art.-no. 40001 - Type WP 26 - 12
Maintenance-free
Battery charge condition after one month at 20°C 92%
Connectors for screws M5Internal resistance with 1KHz 8 mOhmMaximum charging current 7,8 ACapacity: 26 AhDimensions (H x W x D): 125 mm x 166 mm x 175 mmWeight: 9,528 kgVdS approval: G103065
Technical data
Material ABS
Accumulator 12 V / 45 Ah
5-75% (non-condensing)IP 20Grey
Charging voltage 14,4 to 15 V
12 v DC-10°C to +40°C
Colour
6. Accessories for Fire Control Panels detect 3004 and detect 3016 37
Properties:
Material
Conductor XT-base Art.-no. 32495 - Type BXT BAS
Maintenance free execution without integrated protective elements
Mounting and earthing via 35 mm DIN rail accord. to EN 60715
Description:Space saving universal base for overvoltage modules without signal interruption for the placement of conductorsA secure earthing of the base is ensured via DIN rail mounting
Technical data
4-pole for all conductor modules suitable
Exchange of modules is possible without signal interruption
YellowPolyamide PA 6.690 mm x 12 mm x 43 mm
Connection via screw clamps up to 4mm² cable diameter
-40°C to +80°CIP 20
Dimensions (H x W x D)
Ambient temperatureProtection classColour
Further approvals CSA, UL
40 gG608001S295054 and S208123System approval
WeightVdS approval
6. Accessories for Fire Control Panels detect 3004 and detect 3016 38
Properties:
Accessories Base BXT BAS (Art.-no. 32495)
Combined conductor module 24V for signal lines
20 kA-40°C to +80°CIP 20
Connection via screw clamps up to 4mm² cable diameter at the base
10 kA2,5 kA
Protection class
Peak current per leadNominal conduct peak currentAmbient temperature
Combined conductor module 48V for loop wires Art.-no. 32496 - Type BXT ML4 BE 48
according to the lightning protection zone concept
Mounting and earthing via base BXT BAS
Description:Space saving combined conductor module for the protection of 4 individual wire leads with a common reference potential and respectively for assymetric interfaces with galvanic isolation against overvoltage suitable for the use as a protection module for all loop wires of the fire control panels detect 3004 and detect 3016; Operation voltage 48V
Technical data
Art.-no. 32497 - Type BXT ML4 BE 48
Description:Space saving combined conductor module for the protection of 2 twin wire leads of symmetric interfaces with input diode, current loop (TTY) and optucoupler-inputs against overvoltage suitable for the use as protection module for all incoming and outgoing signal lines of the system detect 3000Operation voltage 24 V
Peak current total
Integrated monitoring of the conductor module for thermal and electrical overload status-LifeCheck
Conductor of the type 1 P1 is suitable for the interfaces 0A-2 and higher
Combined conductor module 5V for data lines Art.-no. 32498 - Type BXT ML4 BE HF 5
Description:Space saving combined conductor module for the protection of 4 individual wire leads with a common reference potential and high frequency transmission ways without galvanic isolation against overvoltage suitable for the use as a protection module for all incoming and outgoing data cables in the network of the system detect 3000; Operation voltage 5 V
Colour YellowMaterial Polyamide PA 6.6Dimensions (H x W x D) 45 mm x 12 mm x 51 mmStandards IEC 61643-21, UL 497B
Further approvals CAS, UL
VdS approval G608001System approval S295054 and S208123
7. Network components 39
Properties:
Properties:
Art.-no. 30087 - Type CP BBI
Description:Plug in module for a network integration of the fire control panels detect 3004 and detect 3016 in a network of up to 64 participants
Aesthetically pleasing stainless steel housing with lockable front door
Art.-no. 31623 - Type LCD Tableau
Integrated scroll- and acoustics-function with control via control keys
Programming and data copying via fire control panel detect 3004 / 3016
Description:Microprocessor contolled modular Display for the display of messages of the fire control panels series detect 3004 / 3016 and a network
Current consumption
RS 232; Integrated Bitbus Interface
Protection class
General remarks
Humidity-5°C to +40°CAmbient temperature
Display
5-95% (non-condensing)
24 V DC
LCD-Display, language kit English
Approx. 1,8 kgWeight
IP 30Light grey RAL 7035Sheet steel240 mm x 295 mm x 43 mm
Colour housingMaterialDimensions (H x W x D)
Network-Interface, Bitbus
Approx. 60 mA
4-lines alphanumeric LC-Display, backlight
Quiescent currentApprox. 75 mA
InterfacesAlarm current
Integrated module for the connection to a network of fire control panels of series detect 3004 / 3016
Requires external voltage supply of 24 V
Including English language kit for control and programming
Operation voltage
Technical data
4-lines alphanumeric LC-Display with 10 mm character size with backlight
Technical data
Plug in board for direct mounting into the fire control panels detect 3004 and detect 3016
Suitable for a direct connection of 2 network participants with a distance of up to 1.200 m
For up to 64 network participants in one networkVoltage supply via the fire control panel
Operation voltage 24 V DCApprox. 50 mA
Interface Bitbus-InterfaceAmbient temperature -5°C to +40°C
Plug in module for the fire control panel bitbus interface slotThe topology of the network has to be respected when commissioning (b
Humidity 5-95% (non-condensing)Dimensions (H x W x D) 49 mm x 59 mm x 20 mm
7. Network components 40
Remote Display Control Panel, Master, small housing, English language kit Art.-no. 32426 - Type ABF Master SC GB
Dimensions 262 mm x 420 mm x 83 mm
Description:Microprocessor controlled modular remote display control panel for the control of a network of fire control panels of the series detect 3004 and detect 3016
Programming option for Offset assignment for the control of all network participants
Option for an area to area allocation of the LCD displays in the network via programming
Customized customer texts allowing up to a maximum of 20 characters
Weight 6,0 kg
Dimensions (H x W x D) 6 HE
Remote Display Control Panel, Slave, small housing, English language kit Art.-no. 32425 - Type ABF Slave SC GB
Description:Microprocessor controlled modular remote display control panel for the control of a network of fire control panels of the series detect 3004 and detect 3016
Weight
Up to 20 fire control panels can be configured in a network
Remote Display Control Panel, Master or Slave, 19"-front, English language kit Art.-no. 33333 - Type ABF Master or Slave SC GB
Description:Remote Display Control Panel as Master or Slave in 19" version. Please specify upon order.
in the master remote display control panel
mounting plate RDCP-main board approx. 1,9 kg19'' front plate approx. 1,9 kg
For more technical details please see next page.
7. Network components 41
Properties:
Remote Display Control Panel, Master or Slave, 19"-front, English language kit Art.-no. 33333 - Type ABF Master or Slave SC GB
Event log memory of up to 1000 messages
Different access levels with password protection
3 inputs for collective signals
Integrated ground fault monitoring
Option for customised front logos
Technical data
and the connection of printers and other peripheral equipment
4 alphanumeric lines LC-display with backlight
Remote Display Control Panel, Master, small housing, English language kit Art.-no. 32426 - Type ABF Master SC GB
Remote Display Control Panel, Slave, small housing, English language kit Art.-no. 32425 - Type ABF Slave SC GB
HumidityProtection class
Outputs
Inputs
Sheet steelMaterial
IP 30
Operation voltageQuiescent currentAlarm current
Display
5-95% (non-condensing)
Lightgrey RAL 7035Colour
20 LED-display for status signals
-5°C to +40°C
1x 24 V / 400 mA monitored for sounding/signalling devices3 Relays outputs 250 V / 5A for alarm and fault8 open collector outputs 30 V DC / 90 mA3 inputs for collective signal
Ambient temperature
Integrated display and control panel according to DIN EN 54
Integrated module for the connection to a network of fire control panels of the series detect 3004 / 3016
Integrated RS 232-Interface for an easy programming with the dpt-software
Integrated Bitbus-Interface
including English language kit for control and programming
24 V DC
External voltage supply 24 V required
1 external output 24 V / 400 mA monitored for sounding/signalling devices
3 potential free relays for fire and fault
Interfaces
Visual diagnostics and remote-control operations via the visulaization software "Visual detect"
Dimensions (H x W x D) 262 mm x 420 mm x 83 mm Weight 6,0 kg
4 alphanumeric lines LC-DisplayBacklight
146 mARS 232
86 mA
7. Network components 42
Properties:
General remarks The topology of the network has to be considered at comissioning
Interfaces
5 – 95 % (non-condensing)IP 20
Factory provided pre-adjusted transmission speed of 62,5kBit/s
Enables the BITBUS-operation with unlimited message lenght with Baudrates 62,5kBit/s and 375kBit/s
-5°C to +40 °C
Technical data for IPC-BIT900-PCI and USB-BIT
Dimensions (H x W x D)
for aggressive industrial ambient conditions
Network-PC-Interface, PCI-BITBUS Art.-no. 32257 - Type IPC-BIT900-PCI
190 mm x 128 mm x 12 mm
Operated as a slave participant in the Bitbus-network
Description:PC - plug in card for the integration of a PC as a BITBUS-participant in the network of fire control panels of the series detect 3004 and detect 3016
Plug in card for the direct mounting into the PC
Isolated RS485-Interface with SN75LBC176-drivers and substantial protection circuitry
Approx. 185 g
5 V DC via PCInterfaces 2 x RS 485 9 pole Sub D / F and MOperation voltage
Network-PC-Interface, USB-BITBUS Art.-no. 32258 - Type USB-BIT
Isolated RS485-Interface with substantial protection circuitry for aggressive industrial ambient conditions
Operation voltage 5 V DC via PCWithout integrated repeater for the distance extension
Coupling and supply via USB port of the PC
ARM®-based Design with 32-Bit RISC processor and integrated SDLC
Switchable end of line resistors (bus termination)
PC-Interface can be operated together with repeaters in the network
115 mm x 57 mm x 20 mm Weight Approx. 85 g
Dimensions (H x W x D) Weight
RS 485 9 pole SUB D / F
Description:Small and flexible PC - USB -module for the integration of a PC as a BITBUS - participant into the network of fire control panels of the series detect 3004 and detect 3016
HumidityProtection class
Required drivers are provided with the visual detect setup programme
With LED for sender activity (yellow) and user-LED (green),
Ambient temperature
flashing with 1 Hz at standard software
7. Network components 43
Properties:
Weight
Protection class IP 20
The topology of the network has to be considered at comissioning
Network-PC-Interface, Ethernet-BITBUS, IP 65 Art.-no. 32260 - Type ETH-BIT
RS 485 via clamps
50 mA
Description:PC-Ethernet-module for the integration of a PC as a BITBUS - participant in the network of fire control panels of the series detect 3004 and detect 3016 in IP 65 - housing for the assembly in aggressive ambient conditions
Approx. 190 g
Technical data for ETH-BIT R and ETH-BIT
Network-PC-Interface, Ethernet-BITBUS Art.-no. 32259 - Type ETH-BIT R
Ethernet 10/100 Mbits/s via Cat5 Port
Approx. 240 g
Interfaces RS 485 9 pole Sub D / M
Description:PC-Ethernet-module for the integration of a PC as a BITBUS-participant in the network of fire control panels of the series detect 3004 and detect 3016Comes with Din rail housing for an easy mounting on a DIN rail into the fire control panel
Ambient temperature -5°C to 40°C
Dimensions (H x W x D) 140 mm x 118 mm x 45 mm
BITBUS end of line with defined potential
Factory provided pre-adjusted transmission speed of 62,5kBit/s
External 24V supply via the power supply of the fire control panel
Interfaces
Ethernet 10/100 Mbit/s via Cat5 Port
Enables the BITBUS-operation with unlimited message lenght with Baudrates 62,5kBit/s and 375kBit/s
10 and 100 MBit Ethernet via Cat5 LSA - block
32-Bit ARM7 with 2 MByte Flash and 512 kByte supported RAM
General remarks Without integrated repeater for the distance extension
Ambient temperature -40°C to +50°CProtection class IP 65Dimensions (H x W x D) 118 mm x 140 mm x 45 mm
24 v DC (via power supply of the fire control panel)
With LED for sender activity (yellow) and user-LED (green), flashing with 1 Hz at standard software
Current consumptionHumidity
RS 232 via clamps
Weight
5-95% (non-condensing)
Required drivers are provided with the visual detect setup programme
Isolated RS485-Interface with substantial protection circuitry for aggressive industrial ambient conditions
Operation voltage
7. Network components 44
Properties:
The topology of the network has to be considered at comissioning
5-95% (non condensing)IP 3064 mm x 151 mm x 48 mm Approx. 340 g
Connector for current supply included in the scope of deliveryGeneral remarks 900 m at a baud rate of 375kBIT/s (3 repeater)
RS 485 Master via Sub D 9 pole F and MRS 485 Slave via Sub D 9 pole M -5°C to +40°C
With LED for the transmission status (yellow) and for the operating status LED (green)
12-30 V DC100 mA
Operation voltageCurrent consumptionInterfaces
Network-Repeater, BITBUS-RS 485 Art.-no. 32269 - Type BIT RPT
Integrated DC-inverter for the isolation of the input voltage
Integrated load resistance for the slave function
Description:Bidirectional Repeater - Module for the extension of the cable length between fire control panels of the series detect 3004 and detect 3016 in the BITBUS network coming in a protected aluminium housing for wall mounting
Technical data
32-Bit ARM7 with 2 MByte Flash and 512 kByte supported RAM
Isolated RS485-interface with substantial protective circuit for severe industrial conditions
BITBUS cable end with predefined potential
External 24 V supply via power supply of the fire control panel
Enables BITBUS use of up to 1.200 m distance between two nodes at a standard baud rate of 62,5kBit/s
Ambient temperatureHumidityProtection class
13,2 km at baud rate of 62,5kBIT/s (10 repeater)
Dimensions (H x W x D)
Max. length of networkWeight
7. Network components 45
Properties:
General remarks The topology of the network has to be considered at comissioning
Generation of a fault message via LED and an integrated alarm relays in case of failure
5-95% (non-condensing)IP 30
RS 485 via Sub D 9 pole F or 4 pole field bus clampLWL Multimode 50/62,5µm via SC duplex or ST-connectorChange-over contact via 3 pole plug terminal
of the LWL-connection and disruption of the current supply
18-32 V DC
Network-converter, BITBUS - LWL Art.-no. 32479 - Type RS-485 LWL
and ST-connectors
Robust industrial housing made of metall, suitable for the mounting on a DIN rail
Description:Monitored converter module for the use of fibre optics cable run in the BITBUS netzwork of the fire control panels of the series detect 3004 and detect 3016
115 mm x 36 mm x 107 mm Approx. 680 g
Technical data
6 LEDs for operating state, sending and receiving on both sides, fault
Isolated RS485-Interface with substantial protection circuitry for aggressive industrial ambient conditions
Enables BITBUS-operation with unlimited message length with Baudrates of 62,5kBit/s and 375kBit/s
Enables external redundant 24V supply via 2. galvanically isolated supply
Enables BITBUS-operation with fibre optics multimode cable 62,5/125 µm or 50/125 µm
500 mAOperation voltageCurrent consumptionInterfaces
Fault outputHumidityProtection classDimensions (H x W x D) Weight
7. Network components 46
Properties:
General remarks Scope of supply including power supply connection and interface cablesInterface RS 232
Connection diagram of the control board is included at the General remarks
Bitbus Programming Modem Art.-no. 30139 - Type BPM
GreenMaterial ABS
Ribbon cable is included in the delivery of the output modules
Dimensions (H x W x D) Weight
Colour
Overall network programming of the outputs with mapping of corresponding subpanels
Integrated push button for manual reset-function
Red and green LED for the status display
Description:Programming modem for the Bitbus CPU (Art.-no. 30119)
output modules
125 mm x 133 mm x 58 mm Approx. 300 g
Current consumptionInterfaces
Programming with special software and connection of a modem (Art.-no.30136)
5-95% (non-condensing)IP 20
Bitbus - InterfaceRS 232-5°C to +40°C
Module-housing for the easy mounting onto a DIN rail
21-28 V DCApprox. 140 mA
Operation voltage
Network-Output control board, Bitbus Art.-no. 30119 - Type BB CPU
Easy connection of outputs cards via ribbon cable
Option for up to 8 Output cards per Output control board (Art.-no.30120 and Art.-no. 30122)
Description:Microprocessor controlled control board for the direct control of outputs in a network of fire control panels of the series detect 3004 and detect 3016 with up to 64 participants
Technical data
Up to 61 Output control boards in one network
Direct addressing in the network via fixed address
External voltage supply 24 V DC
Control module for the direct control of relay or OC - Output cards in the network
without the use of fire control panels detect 3004 / 3016
Ambient temperatureHumidityProtection class
7. Network components 47
Properties:
32 Open Collector Output card in a network for the use without a fire control panel detect 3004 / 30164 pole terminal block for the possibility of an output supply voltage of 5 or 8V, e.g. for LED-Displays
Quiescent current Approx. 30 mA
Operation voltageAmbient temperatureHumidityProtection classColourMaterialDimensions (H x W x D)
Alarm current
Quiescent current
Technical data for BB 32 OC and BB 16 REL
Overall network programming of the outputs with mapping of corresponding subpanels
Addressing for the recognition by the control module via DIP-switch
Easy connection of outputs cards via ribbon cable, included in the scope of delivery
Up to 8 output cards can be used with one output control board,-
Max. 90 mA per OC-outputOutput 32 Open Collector 24 V DC / 90 mAWeight Approx. 240 g
Approx. 20 mA16 relays output card in a network for the use without a fire control panel detect 3004 / 3016
Network output card, 16 relays, Bitbus Art.-no. 30122 - Type BB 16 REL
Description:16 Relays-output card for the connection to the output control board for the direct control of outputs in a network of fire control panels of series detect 3004 and detect 3016 with up to 64 participants
Network-Output card, 32 Open Collector, Bitbus Art.-no. 30120 - Type BB 32 OC
ABS125 mm x 163 mm x 58 mm
5-95% (non-condensing)IP 20
mixed solutions possible (Art.-no. 30120 and 30122)
Voltage supply via the output control board (ribbon cable)
Description:32 Open Collector-output card for the connection to the output control board for the direct control of outputs in a network of fire control panels of series detect 3004 and detect 3016 with up to 64 participants
Alarm current Max. 90 mA per outputOutput 16 relays, 1 change over contact 30 V DC / 2A
Output control board 30120 required for the connection to the network
Weight Approx. 250 g
General remarks Ribbon cable included in delivery
-5°C to +40°C
Green
Module-housing for the easy mounting onto a DIN rail
Supply via output control board
7. Network components 48
Properties:
Module -housing for an easy mounting onto a DIN rail
21-28 V DC
Weight Approx. 300 g per module
6 x cable connection for CP ZM 323 Relays 30 V/2 A
2 pieces 125 mm x 133 mm x 58 mm
90 mAOperation voltage
Max. 320 mA
Network-LED-Control card, Bitbus Art.-no. 30128 - Type BB LED
Consists of 2 modules with same dimesnions
Easy connection of up to 6 pieces of the 32 LED indicator module ZM32 (Art.-no. 30098)
Description:Microprocessor controlled control card for the direct control of up to 196 LED's in a network of fire control panels of the series detect 3004 and detect 3016 with up to 64 participants
Technical data
via ribbon cable
Up to 61 participants (Control cards) connectable in a network
Direct addressing in the network by a fixed address
Control module for the direct activation of LEDs in a network
without use of the fire control panel detect 3004 / 3016
Quiescent currentAlarm-/operation currentInterfaces
-5°C to +40°C
Bitbus-InterfaceRS 232
Ambient temperature
Dimensions (H x W x D)
Output ext. Load
Humidity
Material
External voltage supply of 24 V DC required
Cross-network programming of the outputs with mapping to the subpanel
Integrated push button for a manual reset function
Red and green LED for the display of the operation status
ABS
5-95% (non-condensing)Protection class IP 20Colour Green
8. Software and tools 49
Properties:
Properties:
Properties:
Technical data
USB converter, 1m Art.-no. 32326 - Type USB 2.0
Description:Converter module from serial interface to USB for the programming of the fire control panels of the series detect 3004 and detect 3016
Length: 1,1 mWeight: Approx. 100 gData rates of up to 1 MB per secsupprts USB 2.0 Standard
Simple connection of serial interfaces to an USB - PortSuitable for Windows 98SE / 2000 /XP / Vista
General remarks
Integrated system access function for the modification and change of data also during operation
(e.g. change of sensitivities, change of mapping, change of module properties etc.)
The programming with I-check software does not replace the
Graphic display of the loop topology with actual addresses and serial numbers of the components
for the use for doumentation and plans
Technical data
Windows-based software tool with graphic display of the loop topology
Comprehensive diagnostic function for support at commissioning and for
Suitable for Windows 98, 2000 and XPprogramming by the dpt-software
Clearly arranged Windows user interface with print and export function (Word, Excel)
CD with installation softwareScope of delivery
PC - connection cable Art.-no. 32310 - Type UPC
Description:Universal connection cable for the programming of the fire control panels of the series detect 3004 and detect 3016
Length: 1,5 mWeight: Approx. 100 gIncluding adapter for both connection options
Technical data
With nullmodem adapter suitable for the programming of the main boardA connection to the DLI-card with serial cable for the loop analysis
via graphic display of actual data like pollution level, smoke concentration, temperature
Diagnostic and programming software for loop3000 Art.-no. 30501 - Type I-Check 3000
the localization of installation faults of existing systems
Analysis of the operating data of all loop3000 components for high service level of the system
Description:Software tool for the components of the loop3000 System for an easy programming of the functions, analysation and diagnostics in case of service and maintenance and for installation and commissioning with graphic user interface with display of the loop topology of the system detect 3000 for the documentation
8. Software and tools 50
Properties:
Scope of delivery
Option for customer specific texts
Integrated time function for the time programming of different functions
for the fire control panels detect 3004 / 3016
CD with installation software
for the fire control panels detect 3004 / 3016
Windows based softwaretool with upload and download function for the programming
of the functions of the fire control panels of the series detect 3004 / 3016 and the
Clearly arranged Windows user interface with print and export function (Word, Excel)
Integrated option for the remote diagnostics via modem
Option for customer specific texts
Integrated time function for the time programming of different functions
Programming and diagnostic software Art.-no. 30136 - Type DPT 3000
network components of the system detect 3000 via a personal computer
Support of all functions of the programming of the system
Description:Software tool for the easy programming of fire control panels of the series detect 3004 and detect 3016 and the network components of the system detect 3000
Technical data
Suitable for Windows 98, 2000 and XP
General remarks After each programming we recommend a function controlof the fire control panel
8. Software and tools 51
Properties:
Scope of delivery 1 transportation suitcase, 3 batteries Type AA, 1 interface cable
Stand-Alone device with up- and downloadfunction for an easy automatic and manual (Scanfunction)
and programming of the components of the loop3000 via a personal computer without
The programming of the automatic detectors can be done directly General remarksvia an integrated base for detector
1 connection cable for modules and manual call points
Automatic switching off function at no use for higher battery lifetime
Battery powered Stand-Alone tool with up and downloadfunction
for an easy manual adressing and programming of the loop3000 components
Acoustic alert at low battery
Four line LC Display with backlight and adjustable brightness for a clear display of all values and data
16 buttom keypad for an easy use and clearly arranged input of data
Update option of the device software via integrated RS232-interface
Diagnostic and programming tool Easy Check Art.-no. 31482 - Type EC 3000
Support for diagnostics and programming functions for all detectors and modules
Easy assignment of customer specific detector data via integrated copy and paste function
Description:Programming tool for the easy manual adressing and programming of the loop3000 components
Technical data
1 Easy check, 1 carrying strap
Test- and programming tool Loop Tester Art.-no. 31625 - Type LT 3000
Description:Programming tool for an easy automatic or manual (Scan-function) adressing and programming of the components of the loop3000 via a PC.
the installation of a fire control panel1 loop or 2 spurs suitable for connection for the complete test of the detectors/modules installationor for the test of subareas (e.g. difficult to access areas)
including reset key for the reset of the loop tester to a defined basic status
Complete support of all diagnostic and programming functions for all detector and module data
Integrated RS 232-Interface for bidirectional data communication
including 230V-voltage supply for the diagnostic tool
Easy programming and diagnostic and input of customer specific data
via diganostic software I-Check 3000Unlimited use of all features of the diagnostic software I-Check
General remarks The programming of the automatic detectors can be done directly via an integrated base for detector
Scope of delivery 1 suitcase, 1 voltage supply, 1 Interface cable1 Loop-tester
8. Software and tools 52
Properties
Art.-no. 32376 - Type VD MS 1
up to 10 workstations connectable with one additional liscense per workingstationNo additional network PC interfaces required due to IP network structure
Management of up to 20 fire control panels per network with one additional liscense per panel
Liscense for the operation of the fire control panel with the visualization software. One liscense per network allows operation by the software.
Liscense for the data interface connection for the integration of the visualization software to superior management systems
Art.-no. 30146 - Type VD CE 1
Management - System - Interface Art.-no. 31654 - Type VD M I
Multi - Server - extension
Art.-no. 30144 - Type VD UE 1
Panel extension - visual detetct Art.-no. 30145 - Type VD PE 1
Operation extension - visual detect
Suitable for Windows 98, 2000 and XP
Extensive logging of all events and messages with option for specific analysis
User extension - visual detect
General remarks After each programming we recommend a function control
Easy, clearly arranged specific programming via flexible surfaces
Visualization software visual detect Basis Art.-no. 30143 - Type VD Basic 11P
Various user levels with extensive user and policy management and an integrated simulation tool
Freely definable alarm management and procedure plans and integrated tool
Description:Software for the bidirectional visualization and remote control of loop3000 networks and the fire control panels detect 3004 and detect 3016
Technical data
Control of up to 3 detect 3000 networks with one additional liscence per network
Extensive help functions integrated
Windowsbased software liscensed as basic version for one fire control panel and one PC
Windows-XP based network compatible software with Client/Server architecture
and print of floor plans (also for fire brigade route cards)
for the automatic execution of procedure plans
Flexible with multilingual version and print-, export- and import function
Highest system security via data encryption and seperate installation and operation access levels
Import of floor plans and programming data of the fire control panel via standard files
(dpt - files for programming data, dwg-files, wmf-files, jpg-files, bmp-files etc. for floor plans)
8. Software and tools 53
Properties:
Liscence dongle
Compact package visual detect Art.-no. 32268 - Type VD smart
Including liscense VD CE 1 for the operation of the fire control panelUSB Interface USB BIT ( Art.-no. 32258)
Modular structure of graphical software for the realization of different applications and extensions
Various user levels with extensive user and policy management and an integrated simulation tool
Description:Package with USB-Interface and Software for the bidirectional visualization and remote control of one fire control panel of the series detect 3004 and detect 3016Compact version for one fire control panel and one PC, no extension possible
Extensive help functions integrated
Import of floor plans and programming data of the fire control panel via standard files
Easy, clearly arranged specific programming via flexible surfaces
Technical data
Freely definable alarm management and procedure plans and
integrated tool for the automatic execution of procedure plans
Flexible with multilingual version and print-, export- and import function
Highest system security via data encryption and seperate installation and operation access levels
Windows based software liscensed as basic version for one fire control panel and one PC
Windows-XP based network compatible software with Client/Server architecture
CD with installation software, software liscence VD smart
(dpt - files for programming data; dwg-files, wmf-files, jpg-files, bmp-files etc. for floor plans)
Extensive logging of all events and messages with option for specific analysis
for 1 fire control panel and 1 PC
and print of floor plans (also for fire brigade route cards)
Scope of supply
9. Addressable automatic detectors loop3000 54
Properties:
Self learning modes for the ambient conditions
Multicolour-LED for alarm (red) and fault (yellow)
Alarm output for the triggering of a LED indicators
Functions completely integrated via loop3000 protocol
Disable and enable modes with individually adjustable sensitivities
Storage of last maintenance date
VdS approval System approval
Protection classColour housing
Dimensions (H x Ø)
S295054, S208123 and S210001
Operation voltageQuiescent currentAlarm currentOC-outputs SensitivityAmbient temperatureHumidity
G208095
Material
Integrated measurement-system and algorithm for condensation recognition (Humitec®)
Intelligent analysis and disruption mode for the elimination of false alarms (e.g. cigarette smoke)
< 20 m/s
0786-CPD-20580
IP 40White (similar to RAL 9003)ABS52 mm x 100 mm
Air speed
CPD - Number
Integrated temperature measurement as rate of rise procedure and maximum value
in accordance to EN54-5 1A
Detector sensitivities automatically calibrated and freely programmable
Fault monitoring of the measurement chamber signal and loop3000-electronics
Description:Intelligent optical and thermal multi sensor detector for loop3000 with 2 optical and 2 thermal sensors and a bidirectional Isolator for earliest fire detection and indication in all environments with difficult ambient conditions, according to EN54-5/-7/-17 and CEA4021Fusion®-Technology for the detection of the smallest smoke particles and fires in the early stage by using the wavelengths of the wide-band white light spectrum
280 μA
5 levels adjustable
Delivery including protective cover for installation phase
15-30 V DC loop powered
Periodic sensor test
Automatic and manual addressing on the loop3000
Integrated Isolator and T-branch option
Technical data
Standards DIN EN 54–7, EN 54-5, CEA 4021, EN 54-17
Multi sensor optical-heat-intelligent, Fusion Art.-no. 32149 - Type PL 3300 OTi Fusion
-10°C to +60°Cmax. 93 % (+/-2%)
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Highest reliability by intelligent combination of thermal and optical sensor signals with via algorithms
Highest reliability by intelligent combination of thermal and optical sensor signals with via algorithms
9. Addressable automatic detectors loop3000 55
Properties:
Self learning modes for the ambient conditions
Multicolour-LED for alarm (red) and fault (yellow)
Alarm output for the triggering of a LED indicators
Functions completely integrated via loop3000 protocol
Disable and enable modes with individually adjustable sensitivities
Storage of last maintenance date
VdS approval System approval
Protection classColour housing
Dimensions (H x Ø)
S295054 and S208123
Operation voltageQuiescent currentAlarm currentOC-outputs SensitivityAmbient temperatureHumidity
G208096
Material
Integrated measurement-system and algorithm for condensation recognition (Humitec®)
Intelligent analysis and disruption mode for the elimination of false alarms (e.g. cigarette smoke)
< 20 m/s
0786-CPD-20580
IP 40White (similar to RAL 9003)ABS52 mm x 100 mm
Air speed
CPD - Number
Integrated temperature measurement as rate of rise procedure and maximum value
in accordance to EN54-5 1A
Detector sensitivities automatically calibrated and freely programmable
Fault monitoring of the measurement chamber signal and loop3000-electronics
Description:Intelligent optical and thermal multi sensor detector for loop3000 with 2 optical and 2 thermal sensors and a bidirectional Isolator for earliest fire detection and indication in all environments with difficult ambient conditions, according to EN54-5/-7/-17 and CEA4021
280 μA
5 levels adjustable
Delivery including protective cover for installation phase
15-30 V DC loop powered
Periodic sensor test
Automatic and manual addressing on the loop3000
Integrated Isolator and T-branch option
Technical data
Standards DIN EN54–7, EN54-5, CEA4021, EN54-17
Multi sensor detector optical-heat-intelligent Art.-no. 32149 - Type PL 3300 OTi
-10°C to +60°Cmax. 93 % (+/-2%)
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Highest reliability by intelligent combination of thermal and optical sensor signals with via algorithms
Highest reliability by intelligent combination of thermal and optical sensor signals with via algorithms
9. Addressable automatic detectors loop3000 56
Properties:
The Carbon Monoxide detector requires calibrating once a year General remarkto ensure the high detection levels is maintained
Alarm output for the triggering of a LED indicators
Functions completely integrated via loop3000 protocol
Disable and enable modes with individually adjustable sensitivities
Standards DIN EN54-5, EN54-17S295054 and S208123
Operation voltage
Multicolour-LED for alarm (red) and fault (yellow)
System approval
Protection classColour housing
Dimensions (H x Ø)
Ambient temperature
CO-Sensor lifetime 5 years
VdS approval G207005
Material
Alarm evaluation with professional CO-sensor technology
Measurement of carbon monoxid with 2 alarm thresholds
< 20 m/s
0786-CPD-20582
IP 40White (similar to RAL 9003)ABS
Alarm current
52 mm x 100 mm
Air speed
CPD - Number
Integrated acoustic indication for CO-pre alarm and CO-alarm
Highest reliability by intelligent combination of thermal and CO sensor via algorithm
Integrated temperature measurement as rate of rise procedure and maximum value
in accordance to EN54-5
Humidity
OC-outputs Sensitivity
Periodic sensor test
Automatic and manual addressing on the loop3000
Integrated Isolator and T-branch option
Technical data
600 μA
CO - Alarm at 30 ppm, heat accord. to EN 54 - 5 1A
Delivery including protective cover for installation phase
15-30 V DC loop poweredQuiescent current
Multisensor carbon monoxide gas and heat, with isolator Art.-no. 30079 - Type PL 3300 COBT
-10°C to +60°Cmax. 93 % (+/-2%)
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Prealarm: 15 ppm in 15 min
Alarm: 30 ppm in 60 min
Description:Intelligent multi sensor detector for the loop3000 series featuring sensor technology for carbon monoxide detection in combination with two thermal detectors and anintegrated Isolator for earliest detection and indication for all environments with difficult ambient conditions, in accordance to EN54-5/-17For the earliest detection of smouldering fires of all kinds including electrical. The PL 3300 COBT continuously monitors the temperature and the CO-concentration.
9. Addressable automatic detectors loop3000 57
Properties:
Standards DIN EN 54–7, EN 54-5, CEA 4021, EN 54-17
Multi sensor detector optical - heat, without isolator Art.-no. 30007 - Type PL 3200 OT
-10°C to +60°Cmax. 93 % (+/-2%)
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Highest reliability by intelligent combination of thermal and optical sensor signals with via algorithms
Exact pollution recognition by an additional independent measuring chamber
Air speed
CPD - Number
Integrated temperature measurement as rate of rise procedure and maximum value
in accordance to EN54-5 1A
Detector sensitivities automatically calibrated and freely programmable
Fault monitoring of the measurement chamber signal and loop3000-electronics
280 μA
5 levels adjustable
Delivery including protective cover for installation phase
15-30 V DC loop powered
< 20 m/s
0786-CPD-20197 (Art.-no. 30007 and 0786-CPD-20198 (Art.-no. 30021)
IP 40White (similar to RAL 9003)ABS52 mm x 100 mm
S295054 and S208123
Operation voltageQuiescent currentAlarm currentOC-outputs SensitivityAmbient temperatureHumidity
G205052 (Art.-no. 30007) and G205051 (Art.-no 30021)
Material
VdS approval System approval
Protection classColour housing
Dimensions (H x Ø)
Multicolour-LED for alarm (red) and fault (yellow)
Alarm output for the triggering of a LED indicators
Functions completely integrated via loop3000 protocol
Disable and enable modes with individually adjustable sensitivities
Storage of last maintenance date
Multi sensor detector optical - heat, with isolator Art.-no. 30021 - Type PL 3300 OT
Article 30021 with integrated Isolator and T-branch option
Self learning modes for the ambient conditions
Description:Optical and thermal multi sensor detector for loop3000 with 2 optical and 2 thermal sensors for earliest fire detection and indication in all environments with difficult ambient conditions according to DIN EN 54-5/7 und CEA 4021(Art.-no. 30021 with bidirectional Isolator)
Periodic sensor test
Automatic and manual addressing on the loop3000
Technical data
9. Addressable automatic detectors loop3000 58
Properties:
Standards DIN EN54–7, EN54-17
Optical smoke detector, without isolator Art.-no. 30009 - Type PL 3200 O
-10°C to +60°Cmax. 93 % (+/-2%)
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Exact pollution recognition by an additional independent measuring chamber
Air speed
S295054 and S208123
CPD - Number
Detector sensitivities automatically calibrated and freely programmable
Fault monitoring of the measurement chamber signal and loop3000-electronics
280 μA
5 levels adjustable
Delivery including protective cover for installation phase
15-30 V DC loop powered
< 20 m/s
0786-CPD-20035 (Art.-no. 30011) and 0786-CPD-20677 (Art.-no. 30009)
Operation voltageQuiescent currentAlarm currentOC-outputs SensitivityAmbient temperatureHumidity
G202002 (Art.-no. 30011) and G202003 (Art.-no. 30009)
Material
VdS approval
White (similar to RAL 9003)ABS44 mm x 100 mm
IP 40
System approval
Protection classColour housing
Dimensions (H x Ø)
Multicolour-LED for alarm (red) and fault (yellow)
Alarm output for the triggering of a LED indicators
Functions completely integrated via loop3000 protocol
Disable and enable modes with individually adjustable sensitivities
Storage of last maintenance date
Optical smoke detector, with isolator Art.-no. 30011 - Type PL 3300 O
Article 30011 with integrated Isolator and T-branch option
Self learning modes for the ambient conditions
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN54-7/-17(Art.-no. 30011 with bidirectional Isolator)
Periodic sensor test
Automatic and manual addressing on the loop3000
Technical data
9. Addressable automatic detectors loop3000 59
Properties:
Test chamber housing for air ducts Art.-No. 31191 - Type LKMG
With integrated isolator and T-branch option
Self learning modes for the ambient conditions
Multicolour-LED for alarm (red) and fault (yellow)
Alarm output for the triggering of a LED indicators
Functions completely integrated via loop3000 protocol
Disable and enable modes with individually adjustable sensitivities
Storage of last maintenance date
System approval
Description:Intelligent optical smoke detector for loop3000 with 2 optical sensors and bidirectional isolator accord. to DIN EN54-7/-17 especially for the use in air ducts and smoke aspiration systems
Periodic sensor test
Automatic and manual addressing on the loop3000
Technical data
Suitable for environments with air streams of 20 m/s
Detector sensitivities automatically calibrated and freely programmable
Fault monitoring of the measurement chamber signal and loop3000-electronics
Intelligent analysis for the elimination of false alarms
Highest reliability by intelligent smoke chamber sensor technology
SensitivityAmbient temperatureHumidity
Material
Protection classColour housing
Air speed
15-30 V DC loop powered
White (similar to RAL 9003)ABS44 mm x 100 mm
20 m/s
Operation voltageQuiescent currentAlarm currentOC-outputs
0786-CPD-20036
IP 40
Standards DIN EN54–7S295054 and S208123
VdS approval CPD - Number
G202107
Dimensions (H x Ø)
Optical smoke detector for air ducts, with isolator Art.-no. 30092 - Type PL 3300 O/K
-10°C to +60°Cmax. 93 % (+/-2%)
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Exact pollution recognition by an additional independent measuring chamber
280 μA
5 levels adjustable
Delivery including protective cover for installation phase
9. Addressable automatic detectors loop3000 60
Properties:
Heat detector with fixed and rate of rise temperature settings, with isolator Art.-no. 30010 - Type PL 3300 T
Article 30010 with integrated Isolator and T-branch option
Description:Heat detector with fixed and rate of rise temperature settings for loop3000 with 1 thermal sensor for earliest fire detection and indication in all environments with difficult ambient conditions according to DIN EN54-5(Art.-no.30010 with bidirectional Isolator according to DIN EN54-17)
Periodic sensor test
Automatic and manual addressing on the loop3000
Technical data
Multicolour-LED for alarm (red) and fault (yellow)
Alarm output for the triggering of a LED indicators
Functions completely integrated via loop3000 protocol
Disable and enable modes with individually adjustable sensitivities
Storage of last maintenance date
System approval
Protection classColour housing
Dimensions (H x Ø)
SensitivityAmbient temperatureHumidity
G203038 (Art.-no.30008) and G203037 (Art.-no.30010)
Material
VdS approval
White (similar to RAL 9003)ABS44 mm x 100 mm
IP 40
Operation voltageQuiescent currentAlarm currentOC-outputs
S295054 and S208123
CPD - Number
and maximum value in accordance to EN54-5 1A
Detector sensitivities automatically calibrated and freely programmable
280 μA
5 levels adjustable
Delivery including protective cover for installation phase
15-30 V DC loop powered
< 20 m/s
0786-CPD-20043 (Art.-no. 30008) and 0786-CPD-20044 (Art.-no.30010)
Standards DIN EN54-5
Heat detector with fixed and rate of rise temperature settings, without isolator Art.-no. 30008 - Type PL 3200 T
-10°C to +60°Cmax. 93 % (+/-2%)
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Integrated temperature measurement as rate of rise procedure
Air speed
9. Addressable automatic detectors loop3000 61
Optical smoke detector, with isolator, mesh design, silver Art.-no. 30488 - Type PL 3301 O silver
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7/-17Silver mesh design
Standards DIN EN 54-7, EN 54-17
Optical smoke detector, with isolator, mesh design, white Art.-no. 30956 - Type PL 3301 O white
Optical smoke detector, with Isolator, mesh design, black Art.-no. 30525 - Type PL 3301 O black
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7/-17Black mesh design
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7/-17White mesh design
Technical data
0786-CPD-20037
42 mm x 95 mmABS, metal mesh
Dimensions (H x Ø)
CPD - Number
S295054, S208123 and S210001G205046
Material
VdS approval System approval
For more technical details please see page 64.
9. Addressable automatic detectors loop3000 62
Standards DIN EN 54-7, EN 54-17
Optical smoke detector, with isolator, round glass-design, white Art.-no. 30567 - Type PL 3305 O white
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7/-17Round glass design, white colour
Technical data
Optical smoke detector, with isolator, round glass design, silver Art.-no. 30568 - Type PL 3305 O silver
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7/-17Round glass design, silver colour
0786-CPD-20041
47 mm x 110 mmGlass, ABS
Optical smoke detector, with isolator, square glass design, white Art.-no. 32289 - Type PL 3306 O white
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7/-17Square glass design, white colour
Dimensions (H x Ø) Material
Technical data
Dimensions (H x W X D) 40 mm x 122 mm x 122 mm
CPD - Number
S295054, S208123 and S210001G204089VdS approval
System approval
Material Glass, ABSStandards DIN EN 54-7, EN 54-17
For more technical details please see page 64.
9. Addressable automatic detectors loop3000 63
Optical smoke detector, with isolator, round flat design, silver Art.-no. 32288 - Type PL 3307 O silver
Optical smoke detector, with Isolator, round flat design, white Art.-no. 32287 - Type PL 3307 O white
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7/-17Round flat design, white colour
Dimensions (H x Ø)
Technical data
Standards DIN EN 54-7, EN 54-17
Technical data
G208147
ABS
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7/-17Round flat design, silver colour
0786-CPD-20575
33 mm x 110 mmABS
Optical smoke detector, with isolator, with individual logo, round design, white Art.-no. 32473 - Type PL 3308 O white
Description:Optical smoke detector for loop3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7/-17Round design, with individual logo, white colour
Standards DIN EN 54-7, EN 54-17
Material
VdS approval System approval
MaterialDimensions (H x Ø) 55 mm x 113 mm
CPD - Number
S295054 and S208123
For more technical details please see page 64.
9. Addressable automatic detectors loop3000 64
Properties:
Optical smoke detector, with isolator, mesh design, silver Art.-no. 30488 - Type PL 3301 O silver
Self learning modes for the ambient conditions
Periodic sensor test
Automatic and manual addressing on the loop3000
Technical data
Optical smoke detector, with Isolator, mesh design, black
Detector sensitivities automatically calibrated and freely programmable
Fault monitoring of the measurement chamber signal and loop3000-electronics
Art.-no. 30525 - Type PL 3301 O black
Multicolour-LED for alarm (red) and fault (yellow)
Alarm output for the triggering of a LED indicators
Functions completely integrated via loop3000 protocol
Disable and enable modes with individually adjustable sensitivities
Storage of last maintenance date
Ambient temperatureHumidity
IP 40Protection classAir speed < 20 m/s
280 μA
5 levels adjustable
Delivery including protective cover for installation phase
15-30 V DC loop poweredOperation voltageQuiescent current
Optical smoke detector, with isolator, mesh design, white Art.-no. 30956 - Type PL 3301 O white
-10°C to +60°Cmax. 93 % (+/-2%)
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Exact pollution recognition by an additional independent measuring chamber
Alarm currentOC-outputs Sensitivity
Optical smoke detector, with isolator, round glass-design, white Art.-no. 30567 - Type PL 3305 O white
Optical smoke detector, with isolator, round glass design, silver Art.-no. 30568 - Type PL 3305 O silver
Optical smoke detector, with isolator, square glass design, white Art.-no. 32289 - Type PL 3306 O white
Optical smoke detector, with Isolator, round flat design, white
Art.-no. 32473 - Type PL 3308 O white
Art.-no. 32287 - Type PL 3307 O white
Optical smoke detector, with isolator, round flat design, silver Art.-no. 32288 - Type PL 3307 O silver
Optical smoke detector, with isolator, with individual logo, round design, white
10. Accessories for detectors 65
Properties:
Detector standard base, white Art.-no. 32242 - Type SDB 3000
Integrated connectors for the connection of one spur for the loop extension (T-branch)
Mounting space for the piezo buzzer ( Art.-no. 32091) and the detector labelling clip (Art.-no. 30479)
Description:Detector Base for all detectors of series CT and loop3000 black colour
Detector standard base, black Art.-no. 30523 - Type SDB 3000 black
Technical data
Integrated connectors for LED indicator (Art.-no. 31193) or piezo buzzer (Art.-no. 32091)
MaterialDimensions (H x Ø)
ABS21 mm x 95 mm
Space for additional connectors Type WAGO 243
Including transparent seal cover to protect the base against contaminents
Description:Detector Base for all detectors of series CT and loop3000white colour
Description:Detector Base for all detectors of series CT and loop3000 silver colour
Detector standard base, silver Art.-no. 30926 - Type SDB 3000 silver
10. Accessories for detectors 66
Properties:
Detector standard base with bridge, white Art.-no. 32241 - Type SDBB 3000
Integrated connectors for the connection of one spur for the loop extension (T-branch)
Mounting space for the piezo buzzer ( Art.-no. 32091) and the detector labelling clip (Art.-no. 30479)
Description:Detector Base with integrated bridge suitable for all detectors of loop3000black colour
Integrated connectors for LED indicator (Art.-no. 31193) or piezo buzzer (Art.-no. 32091)
Space for additional connectors Type WAGO 243
Detector standard base with bridge, black Art.-no. 32083 - Type SDBB 3000 black
MaterialDimensions (H x Ø)
ABS21 mm x 95 mm
Technical data
Integrated connectors for LED indicator (Art.-no. 31193) or piezo buzzer (Art.-no. 32091)
Space for additional connectors Type WAGO 243
Including transparent seal cover to protect the base against contaminents
Description:Detector Base with integrated bridge suitable for all detectors of loop3000white colour
Description:Detector Base with integrated bridge suitable for all detectors of loop3000silver colour
Detector standard base with bridge, silver Art.-no. 32084 - Type SDBB 3000 silver
10. Accessories for detectors 67
Properties
Properties
Pack contains 30 units
Volume
Description:The detector labelling clip is used to display the detector and zone number of the device and is connectable to all detectomat standard bases
Technical data
Plugs directly onto the detector base
Maximum character height of 25 mm
Hexagon socket screw M3Sharp form for fixation into the detector base
ABSMaterial
Approx. 85 dB / 0.3 mWhite (similar RAL 9003)Colour housing
Packing unit 30 pieces
White (similar RAL 9003)
Mechanically compatible to all detectomat standard detector bases
Approx. 85 dB / 0.3 m
8 mm x 45 mm x 35 mm
Detector labelling clip, 30 pcs
Art.-no. 32237 - Type MSSDetector safety screw, VE 30
Description:Immersable set screw for the permanent mounting of detectors of the series CT, HD and PL into the detector base
Dimensions (H x W x D)
Technical data
Direct voltage supply via detector/ loop
Activation by parallel connection to the alarm LED of the detector
VolumeColour housingMaterial
Art.-no. 30479 - Type MBC
Dimensions (H x W x D) M3 x 10 mm
Piezo buzzer Art.-no. 32091 - Type SP
ABS
Local accoustic alarm
Loud accoustic signal due to external and free sound emission
Description:Accoustic piezo alarm buzzer for direct connection to all detectomat detector bases for the local accoustic signalling in occupied areas (e.g hotels, residential homes etc.)
10. Accessories for detectors 68
Properties
in the smoke chamber.
gradient. Overpressure and low pressure (e.g. air conditioned roos)
120 mm110 mm
The design ring is only suitable for ceilings in rooms without pressure
can lead to draughts at the ceiling which could influence the analysis
Designring for detectors PL 3305 O white and CT 3005 O white Colour White RAL 9003
Technical data for DR 45 white and DR45 silver
Design ring for ceiling mounting, white Art.-no. 32070 - Type DR45 white
Description:Architectural modern designed installation set for a deeper installation of detectors of the series loop3000 and CT 3000 in "05 Design" suitable for e.g. suspended ceilings
Designring for detectors PL 3305 O silver and CT 3005 O silver
Easy installation with screw holder
Sheet steel, coated
165 mm
Colour-coordinated with detectors in glass design
Compatible with all detector bases of the loop3000 system and conventional system
White RAL 9003
General remarks
Design ring for ceiling mounting, silver Art.-no. 31684 - Type DR45 silver
Description:Architectural modern designed installation set for a deeper installation of detectors of the series loop3000 and CT 3000 in "05 Design" suitable for e.g. suspended ceilings
Colour
MaterialInstallation holeInner diameterOuter diameter
10. Accessories for detectors 69
Properties
Properties
Weight 40 g
Dimensions (H x Ø) 335 g
Dimensions (H x Ø) 43,5 mm x 105 mmProtection class IP 66
Colour housing White (similar RAL 9003)Material ABS
Base with heater Art.-no. 31875 - Type APS b
White
max. 4 W -30°C to + 60°C
Integrated connectors for LED indicator (Art-no. 31193) or piezo buzzer (Art-no. 32091)
Space for additional connectors Type WAGO 243
Description:Detector base with integrated temperature-controlled heater for all detectomat detectors of series CT and loop3000 for the use in climate critical and humid environments
Without detector base
160 mA
IP 66
Integrated connectors for the connection of one spur for the loop extension (T-branch)24 V DC
2 cable entry points for cable glands M16
Technical data
Integrated temperature-controlled heater for regulated ambient conditions for detectors.
Including Detector base SDB 3000
Protection classColour housing
Technical data
Integrated sealing against condensate and dripping water
Base adapter for surface mounting, IP 66 Art.-no. 32444 - Type DAB 3000
Description:Adapter housing for the installation in finery and for the use in humid environments for all detectomat detector bases
Operation voltage Current consumption Power Ambient temperature
10. Accessories for detectors 70
Properties
Properties
Housing without detector base
Including entry and exit pipe, pipe lenght 210mm
from 300 mm up to 1500 mm
ABS
Suitable for air ducts up to a size of 1500 mmup to 25 m/sAir speed
Air duct sizeProtection classColour housing
Test chamber housing for air ducts Art.-no. 31191 - Type LKMG
200 mm x 110 mm x 92 mm
IP 64Grey
Description:Test chamber housing with pick-up pipe for the use of CT and loop3000 detectors outside of air ducts
MaterialDimensions (H x W x D)
Technical data
General remarks Special lenghts for entry pipes available on request
Parallel Indicator Art.-no. 31193 - Type PA
Description:Intelligent detector parallel indicator for the external optical indication of the installation place of one or more detectors
Technical data
White wall mounting housing, red colour
Aestethical robust wall mounted housing according with IP 30Operation voltage 24 V DCAlarm current 4 mAAmbient temperature -10°C to +50°CWeight Approx. 65 g
System approval S295054, S208123 and S210001
Material ABSDimensions (H x W x D) 84 mm x 84 mm x 35 mmCPD-Number 0786-CPD-20765VdS approval G294052
10. Accessories for detectors 71
Properties
Properties
Dimensions (H x Ø) 160 mm x 120 mmWeight Approx. 140 g
Cable entry from the back required for the detector base, siren and beaconColour WhiteMaterial Steel
like e.g. balls or other objects with a solid metal grid
Installation of the protection cage after the device installation (screw fixation)
Art.-no. 31317 - Type SK
Description:Protective cage for the mechanical protection of detectors of the series CT and loop3000 and sirens and beacons for the application in e.g. sport halls or leisure centers
Technical data
Installation of the protection cage after the detector installation
with three fixation points (screw fixation)
White
Protection of the detector, siren or beacon against foreign objects
Protective cage for detectors, white Art.-no. 32267 - Type SG
75 mm x 150 mm
Description:Protective cage for the mechanical protection of detectors of the series CT and loop3000 for the application in e.g. sport halls or leisure centers
Technical data
Protection of the detector against foreign objects like e.g. balls or other objects with a solid metal grid
Compatible to detectors of the design variants 0, 1 and 2
Steel
Cable entry from the back required for the detector base
Protective cage, white, for detectos, sirens and beacons
ColourMaterialDimensions (H x Ø) Weight Approx. 150 g
10. Accessories for detectors 72
Properties:
Properties:
Properties:
Weight 330 g
Material Sheet steel powder coatedDimensions (H x W x D) 80 mm x 138 mm x 100 mm
Rear cable entry in the detetcor possible
Colour RAL 7035 light grey
Detector folding bracket 0° - 110° Art.-no. 30188 - Type MKK
Description:Detector folding bracket for the mounting of detectors of the series CT and loop3000 at suitable ceilings (e.g. production halls)
Technical data
Steplessly adjustment of an angle from 0° to 110°
Adjustment of the angle via screwRear cable entry in the detector possible
Weight 1.200 g
Colour RAL 7035 light grey
Detector bracket 270 - 480 mm Art.-no. 30187 - Type MKBD
135 mm x 100 mm x 270 mm to 480 mm
Description:Detector bracket for the mounting of detectors of the series CT and loop3000 in false floors and false ceilings.
Technical data
Steplessly variable from 270 to 480 mm
Angle of the detector bracket stepless adjustable from 0° to 110°
Material Sheet steel powder coatedDimensions (H x W x D) 150 mm x 117 mm x 13 mm to 154 mmWeight 430 g
Detector distance console 80 mm Art.-no. 30189 - Type MAK
Rear cable entry in the detector possible
ColourMaterialDimensions (H x W x D)
RAL 7035 light greySheet steel powder coated
Technical data
Mounting distance to the detector base 80 mm
Description:Detector distance console for the split mounting of detectors of the series CT and loop3000 to horizontal ceilings
10. Accessories for detectors 73
Properties:
Properties:
Distance to the wall: 200 mmRear cable entry in the detector possible
Weight 770 g
Colour RAL 7035 light grey
Wall bracket 200 mm Art.-no. 30191 - Type WA 2
Description:Wall bracket for the mounting of detectors of the series CT and loop3000, e.g. for the use with fire protection closures
Technical data
Wall bracket 400 mm Art.-no. 30190 - Type WA 4
50 mm x 100 mm x 400 mm
Description:Wall bracket for the mounting of detectors of the series CT and loop3000, e.g. for the use with fire protection closures
Technical data
Distance to the wall: 400 mm
Weight 390 g
Material Sheet steel powder coatedDimensions (H x W x D) 50 mm x 100 mm x 200 mm
Rear cable entry in the detector possible
ColourMaterialDimensions (H x W x D)
RAL 7035 light greySheet steel powder coated
11. Addressable manual call points 74
Properties
Protection class
Description:Manual Call Point for loop3000 for the manual activation of an alarm with bidirectional Isolator according to DIN EN 54-11, EN 54-17Red plastic housing with imprint "burning house"
ABS
Functions completely integrated via loop3000 protocol
15 to 30 V DC loop powered
Material
Operation voltageQuiescent currentAlarm currentAmbient temperature
89 mm x 89 mm x 51 mm
Technical data
Manual Call Point mechanics for the activation of a manual alarm
Non-destructive activation and reset via mechanics
280 μA
max. 93 % (+/-2%)
Integrated red alarm-LED
Colour housing
Dimensions (H x W x D)
Humidity
CPD-Number 0333-CPD-075280
Manuall Call Point, with Isolator Art.-no. 32433 - Type PL MCP
IP 32Red (RAL 3000)
5 mA-10°C to +60°C
Automatic and manual addressing on the loop3000
Integrated isolator
11. Addressable manual call points 75
Properties
Spare key Art.-no. 40054 - Type HFM SCH M
Standards DIN EN 54-11, EN54-17
Replacement glass, clear Art.-no. 31910 - Type HFM EG
General remarks Suitable for the fitting into extinguishing cabinets
Spare glass (Art.-no. 31910)Spare key metal (Art.-no. 40054)
VdS approval G203021System approval S295054 and S208123
Colour housing Red (RAL 3000)CPD-Number 0786-CPD-20382
Integrated Isolator and T-branch option
Potentialfree alarm output for the activation of e.g. a parallalel indicator
Functions completely integrated via loop3000 protocol
OC-outputs max. 10 mA for parallel indicator
15 to 30 V DC loop powered
Dimensions (H x W x D)
Operation voltageQuiescent currentAlarm current
Ambient temperatureHumidityProtection classColour housing
Description:Manual Call Point for loop3000 for the manual activation of an alarm with bidirectional Isolator and status display viaLED accord. to DIN EN 54-11Red plastic housing with imprint "burning house"
ABS135 mm x 135 mm x 33 mm
Technical data
Push Button mechanics for the activation of a manual alarm
Activation after smash of the front glass and button push
280 μA
max. 93 % (+/-2%)
Integrated red alarm-LED
Material
Accessories
Manual Call Point, with Isolator, with LED, ABS, red Art.-no. 31669 - Type PL 3300 PBDH-ABS-R
IP 42Red (RAL 3000)
280 μA ; 5 mA when alarm-LED is active
-10°C to +60°C
Integrated reset mechanics
Automatic and manual addressing on the loop3000
11. Addressable manual call points 76
Properties
Replacement glass, clear Art.-no. 31910 - Type HFM EG
Manual Call Point, with Isolator, with LED, Aluminium, red Art.-no. 31668 - Type PL 3300 PBDH-ALU-R
IP 42Red (RAL 3000)
280 μA ; 5 mA when alarm-LED is active
-10°C to +60°C
Integrated reset mechanics
Automatic and manual addressing on the loop3000
Description:Manual Call Point for loop3000 for the manual activation of an alarm with bidirectional Isolator and status display viaLED accord. to DIN EN 54-11Red aluminium housing with imprint "burning house"
Aluminium125 mm x 125 mm x 34 mm
Technical data
Push Button mechanics for the activation of a manual alarm
Activation after smash of the front glass and button push
280 μA
max. 93 % (+/-2%)
Integrated red alarm-LED
Dimensions (H x W x D)
Operation voltageQuiescent currentAlarm current
Ambient temperatureHumidityProtection classColour housing
VdS approval G203021System approval
Integrated Isolator and T-branch option
Potentialfree alarm output for the activation of e.g. a parallalel indicator
Functions completely integrated via loop3000 protocol
OC-outputs max. 10 mA for parallel indicator
15 to 30 V DC loop powered
Material
Colour housing Red (RAL 3000)CPD-Number 0786-CPD-20382
Spare glass (Art.-no. 31910)Spare key metal (Art.-no. 40054)
Accessories
Wheatherproof housing (Art.-no. 31091)
S295054 and S208123
Spare key Art.-no. 40054 - Type HFM SCH M
Standards DIN EN 54-11, EN54-17
Wheatherproof housing for PL 3300 PBDH-ALU-R Art.-no. 31091 - Type WG R
General remarks Suitable for a wheatherproof housing
11. Addressable manual call points 77
Properties
Properties
Properties
Art.-no. 40054 - Type HFM SCH M
Dimensions (H x W x DT) 145 mm x 131 mm x 55 mm
Technical data
Replacement glass for manual call points of the series PL and CTClear plain version for the use in all colour varieties
Technical data
Key for opening of all manual call points fo the series PL and CTDie-casting design, metal
Weight Approx. 295 gColour housingMaterial
Replacement glass, clear Art.-no. 31910 - Type HFM EG
Spare key
Aluminium
Sealing and gasket set for a protected cable entry
Description:Wheatherproof housing for aluminium manual call points (Art.-no. 31668 and 31676) to increase the protection class to IP 54
Technical data
Robust aluminium protective housing
-10°C to +60°CAmbient temperatureHumidityProtection class
Wheatherproof housing for manual call points, IP 54, Aluminium, red Art.-no. 31091 - Type WG R
IP 54
Red (RAL 3000)
Including seal and gasket set for the mounting of the housing
max. 93 % (+/-2%)
12. Addressable I/O-elements loop3000 78
Properties:
Weight
CPD-numberVdS approval System approval
Protection classColour housing
Dimensions (H x W x D)
S295054, S208123 and S210001
Operation voltageQuiescent currentAlarm currentOutputInputAmbient temperatureHumidity
G205029
Material
Multicolour-LED for alarm (red) and fault (yellow)
Connecting module with one freely programmable Input and one freely programmable output
Programming of different switching variants of input and output also with time control
460 μA
Automatic and manual addressing on the loop3000
Integrated Isolator and T-branch option
Functions completely integrated via loop3000 protocol
Input- / Output module, single I/O, Relay, with Isolator Art.-no. 30200 - Type IOM 3311
Monitoring of the operating status via loop3000
Independent programming of Input and Output
Description:Intelligent Input- / Output Module for the loop3000 with bidirectional isolator according to DIN EN 54-18 with one monitored input and one potentialfree relay output
Technical data
460 µA ; 5 mA if alarm-LED is activeRelay 1 change over contact 30 V DC / 1ALow active monitored
Aestethical robust wall mounted housing according with IP 54
15 to 30 V DC loop powered
Standards DIN EN 54-18, 17
-10°C to +60°Cmax. 93 % (+/-2%)Approx. 185 g
0786-CPD-20459
IP 54Grey (similar to RAL 7035)ABS93 mm x 93 mm x 55 mm
12. Addressable I/O-elements loop3000 79
Properties:
Accessories Possibility for monitoring of the output with UBW 3311 (Art.-no. 32073)
Integrated Isolator and T-branch option
Functions completely integrated via loop3000 protocol
Multicolour-LED for alarm (red) and fault (yellow)
Programming of different switching variants of input and output also with time control
Standards DIN EN 54-18, 17General remarks The fault input can be used for the monitoring module UBW 3311
-10°C to +60°Cmax. 93 % (+/-2%)
Relay 1 change over contact 30 V DC / 1ALow active monitored
Input- / Output module, single I/O, signalling devices, with isolator Art.-no. 30211 - Type OMS 3301
Connecting module with one freely programmable fault input and
one output for the connection of signalling devices
Description:Intelligent Input- / Output module for the loop3000 for the control of external optical and acoustic signalling devices with bidirectional isolator according to DIN EN 54-18 including one monitored fault input and one potentialfree relay output for signalling devices
Integrated automatic switch function of the output
at "external signal line on/off" signal by the fire control panel
460 μA
Technical data
Monitoring of the operating status via loop3000
Independent programming of Input and Output
Automatic and manual addressing on the loop3000
Aestethical robust wall mounted housing according with IP 54
15 to 30 V DC loop powered
Approx. 190 g
0786-CPD-20460
IP 54Grey (similar to RAL 7035)ABS93 mm x 93 mm x 55 mm
S295054, S208123 and S210001
Operation voltageCurrent consumptionInputOutputAmbient temperatureHumidity
G205030
Material
Weight
CPD-numberVdS approval System approval
Protection classColour housing
Dimensions (H x W x D)
12. Addressable I/O-elements loop3000 80
Properties:
Operation voltageQuiescent currentAlarm current
Ambient temperature
11 mA
Output
WeightProtection class
Humidity
Technical data
Circuit board for the integration in the module housings IOM 3311 and OMS 3301
24V
Monitoring module single Output, for IOM 3311 and OMS 3301 Art.-no. 32073 - Type UBW 3311
Integrated fault output for the connection to the monitored input of the modules IOM and OMS
External voltage supply of 24V
Description:Monitoring module for the use in the modules IOM 3311 and OMS 3301 for the monitored triggering of external optical and acoustic signalling devicesAdd-on module for the direct mounting into the housing of the modules OMS 3301 and IOM 3311
Module for the monitoring of one output line with 24V and up to 1A for broken wire and short circuit
Dimensions (H x W x D) 20 mm x 38 mm x 35 mm
Polarity switchover at activation of the output
Relays-fault output-10°C to +60°C
11 mA24 V / 1 A monitored
max. 93 % (+/-2%)Approx. 50 gNone
12. Addressable I/O-elements loop3000 81
Properties:
Input low active monitored
Output
Standards DIN EN 54-18, 17
-10°C to +60°Cmax. 93 % (+/-2%)Approx. 20 g
0786-CPD-20530
IP 30BlueABS27 mm x 73 mm x 15 mm
380 µA ; 5 mA if alarm-LED is active1 Open Collector 500 mA1 10 mA parallel for LED-status indication
Input- / Output module, single I/O, Open Collector with Isolator Art.-no. 30513 - Type AMD 3311
Programming of different switching variants of input and output also with time control
Monitoring of the operating status via loop3000
Description:Intelligent Input- / Output module mini for the loop3000 with bidirectional isolator for the integration in special detectors and externally connected modules according to DIN EN 54-18 including one monitored input and one open collector output
Technical data
Connecting module with one freely programmable Input and one freely programmable output
Additional parallel alarm output (blinking) for the control of a status indicator (without series resistor)
380 μA
Independent programming of Input and Output
Automatic and manual addressing on the loop3000
Integrated Isolator
Completely encapsulated module for the integrationin special applications with control by the loop3000
15 to 30 V DC loop powered
Functions completely integrated via loop3000 protocol
S295054, S208123 and S210001
Operation voltageQuiescent currentAlarm current
Ambient temperatureHumidity
G205047
Material
Weight
CPD-numberVdS approval System approval
Protection classColour housing
Dimensions (H x W x D)
12. Addressable I/O-elements loop3000 82
Properties:
15 to 30 V DC loop powered
VdS approval System approval
Protection classColour housing
Dimensions (H x W x D)
Functions completely integrated via loop3000 protocol
Completely encapsulated module for the integrationin special applications with control by the loop3000
S295054, S208123 and S210001
Operation voltageCurrent consumption
Ambient temperatureHumidity
G205047
Material
Programming of different switching variants of input and output also with time control
Monitoring of the operating status via loop3000
Independent programming of Input and Output
Integrated Isolator
Input- / Output module, single I/O, signalling devices, with isolator Art.-no. 31640 - Type OMS 3311mini
Connecting module with one freely programmable fault input and
one output for the connection of signalling devices
Description:Intelligent Input- / Output module mini for the loop3000 for the control of external optical and acoustic signalling devices with bidirectional isolator for the integration in externally connected modules according to DIN EN 54-18 including one monitored fault input and one open collector output for signalling devices
Technical data
Integrated automatic switch function of the output at
"external signal line on/off" signal by the fire control panel
Automatic and manual addressing on the loop3000
BlueABS27 mm x 73 mm x 15 mm
1 Open Collector 500 mA1 10 mA parallel for LED-status indication
Input Low active monitored
Output380 μA
Standards DIN EN 54-18, 17
-10°C to +60°Cmax. 93 % (+/-2%)Approx. 20 g
0786-CPD-20530
IP 30Weight
CPD-number
12. Addressable I/O-elements loop3000 83
Properties:
Standards DIN EN 54-18, 17
-10°C to +60°Cmax. 93 % (+/-2%)Approx. 190 g
0786-CPD-20373
IP 54Grey (similar to RAL 7035)ABS93 mm x 93 mm x 55 mm
560 µA; 5 mA if alarm-LED is active1 monitored detector zone with up to 65 mA
Aestethical robust wall mounted housing according with IP 54
15 to 30 V DC loop poweredExternal supply output 12V or 24 V DC
Operation voltage
Input module, 1 conventional zone, with Isolator Art.-no. 30205 - Type TCM 3300
different conventional detectors with different current consumptions and operation voltages
Possibility for parametrization of short-circuit, wire break, prealarm and alarm thresholds
Description:Intelligent Input module for the connection of one conventional detector zone to the loop3000 with bidirectional isolator according to DIN EN 54-18 for the connection of conventional detectors with 12 V or 24 V technology
Technical data
Multicolour-LED for alarm (red) and fault (yellow)
Voltage selection for the detector zone supply via "jumper" on the module board.
External supply of conventional detector zones for the flexible use of
560 μA
Automatic and manual addressing on the loop3000
Integrated Isolator and T-branch option
Functions completely integrated via loop3000 protocol
S295054 and S208123
Quiescent currentAlarm currentInputAmbient temperatureHumidity
G206048
Material
Weight
CPD-numberVdS approval System approval
Protection classColour housing
Dimensions (H x W x D)
13. Addressable signalling devices loop3000 84
Properties:
General remarksStandards
Ambient temperatureHumidity
System approval
280 μA
G208103
Material
Weight
CPD-numberVdS approval
Protection class
loop3000-Sounder, with Isolator, red Art.-no. 31836 - Type LS 3300 R
Monitoring of the operating status via loop3000
Independent programming via autarkic loop address
Description:Intelligent acoustic signalling device for the loop3000 for the external acoustic alarm with bidirectional Isolator according to DIN EN 54-3Wall mounted housingRed colour (Art.-no. 31836)or white colour (Art.-no. 32012)
Technical data
Activation, monitoring and supply via loop3000 protocol
Integrated automatic reset function at signal "external signal line on/off" by the fire control panel
please use the latest loop-calculator version
-10°C to +60°Cmax. 93 % (+/-2%)340 g
0786-CPD-20452
IP 54Red (Art.-no. 31836) or white (Art.-no 32012)ABS100 mm x 101 mm
For the calculation/design of the number of loop3000-signalling devices
loop3000-Sounder, with Isolator, white Art.-no. 32012 - Type LS 3300 W
5 mAmax. 97 dB
Functions completely integrated via loop3000 protocol
Automatic and manual addressing on the loop3000
Integrated isolator
4 different tones adjustable via DIP - switch (including DIN tone)
Volume control via integrated potentiometer
Operation voltage
DIN EN 54–3, 17
Aestethical robust wall mounted housing according with IP 54
15 to 30 V DC loop powered
Integrated dual tone alarm function via seperate activation possible
S295054, S208123 and S210001
Quiescent currentAlarm currentVolume
Colour housing
Dimensions (H x Ø)
13. Addressable signalling devices loop3000 85
Properties:
Alarm currentVolume
VdS approval System approval
Protection classColour housing
Dimensions (H x Ø) Material
Weight
CPD-number
ABS27 mm x 117 mm
For the calculation/design of the number of loop3000-signalling devices
6 mAmax. 85 dB
DIN EN 54-3, 17S295054, S208123 and S210001G208144
Activation, monitoring and supply via loop3000 protocol
Integrated automatic reset function at signal "external signal line on/off" by the fire control panel
For the installation with a detector the detector base has to be ordered seperately and has to be mounted onto the base sounder. For this we recommend the intermediate ring article-no. 32472 (accessories).
please use the latest loop-calculator version
-10°C to +60°Cmax. 93 % (+/-2%)250 g
0786-CPD-20525
IP 54Base sounder in white, covers in red or in white
Integrated dual tone alarm function via seperate activation possible
Operation voltageQuiescent current
loop3000-Base-Sounder, with Isolator Art.-no. 32060 - Type LS 3300 VLC
Monitoring of the operating status via loop3000
Independent programming via autarkic loop address
Description:Intelligent acoustic signalling device for the loop3000 for the external acoustic alarm with bidirectional Isolator according to DIN EN 54-3Suitable as walll mounted sounder version or as sounder base for the detector fixed to the ceiling
Technical data
Accessories:Art.-no. 32067: Cover for loop3000-Base-Sounder, red, Type AD R Art.-no. 32068: Cover for loop3000-Base-Sounder, white, Type AD WArt.-no. 32472: Cover for loop3000-Base-Sounder, white, Type AD Ring
400 μA
Automatic and manual addressing on the loop3000
Integrated isolator
32 different tones adjustable via DIP-switch (including DIN tone)
Functions completely integrated via loop3000 protocolCover plate in red or white colour
15 to 30 V DC loop powered
General remarksStandards
Ambient temperatureHumidity
13. Addressable signalling devices loop3000 86
Properties:
General remarks
Art.-no. 30527 - Type SDM 3300 W
1,28 mA ; via external supply: 9 to 29 mA max. 111 dB
DIN EN 54-3, 17
Aestethical robust wall mounted housing according with IP 54
15 to 30 V DC
Integrated dual tone alarm function via seperate activation possible
please use the latest loop-calculator version
-10°C to +60°Cmax. 93 % (+/-2%)340 gIP 54Red (Art.-no. 30204) or white (Art.-no 30527)ABS93 mm x 93 mm
For the calculation/design of the number of loop3000-signalling devices
loop3000-acoustic signalling device, external supply, with Isolator, red Art.-no. 30204 - Type SDM 3300 R
Monitoring of the operating status via loop3000
Independent programming via autarkic loop address
Description:Intelligent acoustic signalling device for the loop3000 for the external acoustic alarm with bidirectional Isolator according to DIN EN 54-3 with external voltage supply and high sound pressure for the use in noisy ambient conditions, wall mounted housingRed colour (Art.-no. 30204)or white colour (Art.-no. 30527)
Technical data
Activation, monitoring and supply via loop3000 protocol
Integrated automatic reset function at signal "external signal line on/off" by the fire control panel
loop3000-acoustic signalling device, external supply, with Isolator, white
280 μA
Automatic and manual addressing on the loop3000
Integrated Isolator and T-branch option
32 different tones via DIP-switch, including DIN-Tone
Functions completely integrated via loop3000 protocol
Operation voltageQuiescent currentAlarm currentVolume
Standards
Ambient temperatureHumidity
Material
WeightProtection classColour housing
Dimensions (H x Ø)
13. Addressable signalling devices loop3000 87
Properties:
Material
WeightProtection class
Operation voltageQuiescent currentAlarm current
Colour housing
Ambient temperatureHumidity
Dimensions (H x Ø)
400 μA
General remarks
Automatic and manual addressing on the loop3000
Integrated short circuit isolator
Integrated 1 Hz LED-beacon
Functions completely integrated via loop3000 protocol
please use the latest loop-calculator version
-10°C to +60°Cmax. 93 % (+/-2%)
ABS
loop3000-Signalling device optical, with Isolator, white - red Art.-no. 32058 - Type LB 3300 VXB R
Monitoring of the operating status via loop3000
Independent programming via autarkic loop address
Description:Intelligent optical signalling device for the loop3000 for the external alarm with bidirectional Isolator according to DIN EN 54-23Wall mounted housingRed colour (Art.-no. 32058)or orange colour (Art.-no. 32090)
Technical data
Activation, monitoring and supply via loop3000 protocol
Integrated automatic reset function at signal "external signal line on/off" by the fire control panel
80 mm x 98 mmFor the calculation/design of the number of loop3000-signalling devices
loop3000-Signalling device optical, with Isolator, white - orange Art.-no. 32090 - Type LB 3300 VXB O
6 mA
Aestethical robust wall mounted housing according with IP 43
15 to 30 V DC loop powered
145 gIP 43White housing, red cover (Art.-no. 32058); orange cover (Art.-no 32090)
13. Addressable signalling devices loop3000 88
Properties:
6 mA
EN 54-17
Aestethical robust wall mounted housing according with IP 30
15 to 30 V DC
-10°C to +50°Cmax. 93 % (+/-2%)65 gIP 30White housing, red calotteABS84 mm x 84 mm x 35 mm
For the calculation/design of the number of loop3000-signalling devices
loop3000-Parallel-Indicator with Isolator, white-red Art.-no. 32282 - Type PL 3300 PA
Monitoring of the operating status via loop3000
Independent programming via autarkic loop address
Description:Intelligent detector parallel indicator for the loop3000 for the external optical indication of the installation place of one or more detectors with bidirectional IsolatorWhite wall mounting housing, red colour
Technical data
Activation, monitoring and supply via loop3000 protocol
400 μA
Automatic and manual addressing on the loop3000
Integrated Isolator
Functions completely integrated via loop3000 protocol
Operation voltageQuiescent currentAlarm current
Standards
Ambient temperatureHumidity
Material
WeightProtection classColour housing
Dimensions (H x W x D) CPD-number 0786-CPD-20535VdS approval G208141
detector status.
General remarks
System approval S295054, S208123 and S210001
The parallel indicator Art.-no. 31193 can be connected directly to the integrated OC-output of the detector for a direct display of the
please use the latest loop-calculator version
14. Conventional signalling devices 89
Properties:
from 6 mA to 36max 99 dB
Operation voltageAlarm currentVolume
Flat design
12-35 V
Multiple tone sounder, red Art.-no. 32053 - Type VTG-32-SB W
IP 65 model available upon request
-20°C to +70°C220 g
0832-CPD-0255
IP 43Red (Art.-no. 32051) or white (Art.-no 32053)ABS65 mm x 94 mm
DIN EN 54-3G 205137
Material
Multiple tone sounder, red Art.-no. 32051 - Type VTG-32-SB R
Volume and alarm current adjustable via integrated DIP-button
Description:Acoustic multiple tone sounder for an external acoustic alarm accord. to DIN EN 54-3
Technical data
32 different tones (incl. DIN tone) adjustable via DIP button
Wide band signal from 440 to 2900 Hz
General remarksStandards
Ambient temperatureWeight
CPD-numberVdS approval
Protection classColour housing
Dimensions (H x Ø)
14. Conventional signalling devices 90
Properties:
StandardsSystem approval
Ambient temperatureWeight
CPD-numberVdS approval
Protection classColour housing
Dimensions (H x Ø) Material
Multiple tone sounder, red Art.-no. 31689 - Type CS 200 R
Integrated two tone alarm function
Description:Acoustic multiple tone sounder for an external acoustic alarm accord. to DIN EN 54-3
Technical data
32 different tones (incl. DIN tone) adjustable via DIP button
Automatic synchronisation
DIN EN 54-3
-10°C to +55°C240 g
0832-CPD-0523
IP 21CRed (Art.-no. 31689) or white (Art.-no 31690)ABS FR63 mm x 63 mm
S295054, S210001G209123
Flat design
9 - 28 V
Multiple tone sounder, white Art.-no. 31690 - Type CS 200 W
15 mA at DIN tonemax 100 dB, 94 dB at DIN tone
Operation voltageAlarm currentVolume
14. Conventional signalling devices 91
Properties:
Art.-no. 40060 - Type UB w
Flush-mounted base 48mm for IP65, white Art.-no. 31467 - Type PG DG w
Flush-mounted base for IP65, red Art.-no. 40059 - Type UB r
Flush-mounted base 48mm for IP65, red Art.-no. 31468 - Type PG DG r
Flush-mounted base for IP65, white
StandardsSystem approval
Ambient temperatureWeight
CPD-numberVdS approval
Protection classColour housing
Dimensions (H x Ø) Material
Multiple tone sounder, red Art.-no. 31838 - Type ROLP 32 R
Integrated two tone alarm function
Description:Acoustic multiple tone sounder for an external acoustic alarm accord. to DIN EN 54-3
Technical data
32 different tones (incl. DIN tone) adjustable via DIP button
Automatic synchronisation
Volume internally adjustable
DIN EN 54-3
-25°C to +70°C250 g
0832-CPD-0128
IP 54Red (Art.-no. 31838) or white (Art.-no 30198)ABS FR63 mm x 93 mm
S295054, S210001G206019
Flat design
9 - 28 V
Multiple tone sounder, white Art.-no. 30198 - Type ROLP 32 W
3 to 33 mA64 to 111 dB, 99 dB at DIN tone
Operation voltageAlarm currentVolume
Accessories
14. Conventional signalling devices 92
Properties:
General remarks IP 65 model available upon request
IP 42Red
System approvalStandards
ABS FR96 mm x 108 mm x 108 mmG206027S295054, S210001
Multiple tone sounder, red Art.-no. 30216 - Type SYS 120 R
Description:Acoustic multiple tone sounder for an external acoustic alarm accord. to DIN EN 54-3
32 different tones (incl. DIN tone) adjustable via DIP button
Automatic synchronisation
190 to 260 mA, 240 mA at DIN toneOperation voltageAlarm current
Flat design
9 - 28 V
DIN EN 54-3
MaterialDimensions (H x Ø) VdS approval
Protection classColour housing
Integrated two tone alarm function
Volume internally adjustable
88 to 120 dB, 112 dB at DIN tone-25°C to +55°C210 g
VolumeAmbient temperatureWeight
14. Conventional signalling devices 93
Properties:
General remarksStandards
Ambient temperatureHumidityWeight
Accessories:Art.-no. 32067: Cover for loop3000-Base-Sounder, red, Type AD R Art.-no. 32068: Cover for loop3000-Base-Sounder, white, Type AD WArt.-no. 32472: Cover for loop3000-Base-Sounder, white, Type AD Ring
400 μA
Cover plate in red or white colour
15 to 30 V DC loop poweredOperation voltageQuiescent current
Dimensions (H x Ø)
G208144
Material
CPD-number
Base-Sounder Art.-no. 32055 - Type Verso 32
Volume and alarm current adjustable via integrated DIP - button
Flat design
Description:Acoustic multiple tone sounder for an external accoustic alarm accord. to DIN EN 54-3Base design
Technical data
32 different tones (incl. DIN tone) adjustable via DIP button
Wide band signal from 440 to 2900 Hz
For the installation with a detector the detector base has to be ordered seperately and has to be mounted onto the base sounder. For this we recommend the intermediate ring Art.-no. 32472 (accessories).
please use the latest loop-calculator version
-10°C to +60°Cmax. 93 % (+/-2%)250 g
0786-CPD-20525
IP 54Base sounder in white, covers in red or in whiteABS27 mm x 117 mm
For the calculation/design of the number of loop3000-signalling devices
6 mAmax. 85 dB
DIN EN 54–3, 17
Alarm currentVolume
VdS approval System approval
Protection class
S295054, S208123 and S210001
Colour housing
14. Conventional signalling devices 94
Properties:
Properties
System approval S295054, S208123 and S210001VdS approval G294052
Parallel Indicator Art.-no. 31193 - Type PA
Description:Intelligent detector parallel indicator for the external optical indication of the installation place of one or more detectors
Technical data
Aestethical robust wall mounted housing according with IP 30
Dimensions (H x W x D) 84 mm x 84 mm x 35 mm
Alarm current 4 mAAmbient temperature -10°C to +50°C
White wall mounting housing, red colour
Operation voltage
CPD-Number 0786-CPD-20765
Weight Approx. 65 gMaterial ABS
24 V DC
Protection classColour housing
DIN EN 54-3
MaterialDimensions (H x Ø) VdS approval
General remarks Cover plate available upon request
IP 21C
32 different tones (incl. DIN tone) adjustable via DIP button
Automatic synchronisation
8 to 35 mA, 16 mA at DIN toneOperation voltageAlarm current
Base sounder Art.-Nr. 30214 - Type SQ 32 W
Description:Acoustic multiple tone sounder for the external acoustic alarm accord. to DIN EN 54-3
67 to 102 dB, 91 dB at DIN tone-10°C to +55°C210 g
Flat design
10 - 28 V DC
VolumeAmbient temperatureWeight
White
System approvalStandards
ABS FR28 mm x 113 mmG206022S295054, S208123 and S210001
14. Conventional signalling devices 95
Properties:
Flash frequency 1 Hz +/- 20%
Flat design
Accessories: Flush mounted base for IP 65, white, Art.-no. 40060, Type UB w
Flush mounted base for IP 65, red, Art.-no. 40059, Type UB r
Flush mounted base 48 mm for IP 65, white, Art.-no. 31467, Type PG DG w
45 to 185 mA, 80 mA at 24 V10 Cd
Operation voltageAlarm currentEfficacy
Flush mounted base 48 mm for IP 65, red, Art.-no. 31468, Type PG DG r
10 - 60 V DC
Beacon, orange Art.-no. 30220 - Type SOLEX 10 o
Art.-no. 32448 - Type SOLEX 10 b
Beacon, green Art.-no. 32447 - Type SOLEX 10 g
DIN EN 54–23
-25°C to +70°C150 gIP 54Red (Art.-no. 32462) or white (Art.-no 30220, 32447, 32448)Base ABS, lense PC67 mm x 93 mm
S295054, S208123 and S210001G207018
Beacon, red Art.-no. 32462 - Type SOLEX 10 r
High efficiency
Description:Optical Xenon-beacon for an external optical alarm accord. to DIN EN 54-23
Technical data
Huge input voltage range
Automatic synchronisation
Integrated starting current limitation
Beacon, blue
StandardsSystem approval
Ambient temperatureWeight
VdS approval
Protection classColour housing
Dimensions (H x Ø) Material
14. Conventional signalling devices 96
Properties:
Properties:
Material ABSDimensions (H x Ø) 48 mm x 92 mm
-25°C to +70°C
Flush mounted base, red Art.-no. 40059 - Type UB r
Red (Art.-no. 40059) or white (Art.-no. 40060)
Description:Flush-mounted base for the upgrade of the beacons of the serie SOLEX and sirens of the series ROLP to protection class IP 65
Weight 10 g
Colour housing Red (Art.-no. 31468) or white (Art.-no. 31467)Protection class IP 65
Snap on mounting for sirens (ROLP) and beacons (SOLEX)
Ambient temperature -25°C to +70°C
Suitable for PG cable entry
Colour housingMaterial
Technical data
Robust finery-mounted base made of plastic
ABS
Finery mounted base, red Art.-no. 31468 - Type PG DG r
Dimensions (H x Ø) 51 mm x 92 mm
Finery mounted base, white Art.-no. 31467 - Type PG DG w
Description:Finery-mounted base for the upgrade of the beacons of the serie SOLEX and sirens of the series ROLP to protection class IP 65
Flush mounted base, white Art.-no. 40060 - Type UB w
Protection class IP 65
Ambient temperatureWeight
Technical data
Robust flush-mounted base made of plastic
10 g
Snap on mounting for sirens (ROLP) and beacons (SOLEX)
red version
red version
14. Conventional signalling devices 97
Properties:
Material ABS
Beacon, red, IP65 Art.-no. 32057 - Type VXB 1 DB WB RL
Beacon, orange, IP 65 Art.-no. 32200 - Type VXB 1 DB WB AL
Description:Optical LED-signalling device for the external optical alarm
Protection class IP 65
Beacon, red Art.-no. 32056 - Type VXB 1 SB WB RL
145 gIP 43
Beacon, orange Art.-no. 32142 - Type VXB 1 SB WB AL
Light power 0,7 Watt at 5 mA current consumption
Description:Optical LED-signalling device for the external optical alarm
Alarm current
Dimensions (H x Ø) 80 mm x 95 mm
Dimensions (H x Ø) 60 mm x 95 mm
Weight 165 g
20-35 V DC
Colour housing
Operation voltage
0,4 to 0,7 W1 Hz
EfficacyFlash frequencyAmbient temperature
WeightProtection class
White
Technical data for all above beacons
LED - beacon with low current consumption
Flat design
3 to 5 mA
-20°C to +70°C
Light power 0,4 Watt at 3 mA current consumption
red version
red version
14. Conventional signalling devices 98
Properties:
Standards DIN EN 54-3
Sounder/ beacon combination IP 65 Art.-no. 32063 - Type VTB 32 DB W
Description:Combination of optical and acoustic signaling devices for external alarm
Protection class IP 65Dimensions (H x Ø) 107 mm x 94 mm
Sounder/ beacon combination Art.-no. 32062 - Type VTB 32 SB W
233 gIP 43
ABS
Flat design
Description:Combination of optical and acoustic signaling devices for external alarm
Alarm currentVolume
Material
Dimensions (H x Ø) 90 mm x 94 mm
Weight
White
Technical data for above sounder / beacon combinations
32 different tones (incl. DIN tone) adjustable via DIP button
Wide band signal from 440 to 2900 Hz
11 to 37mA
-20°C to +70°C
LED - beacon with low current consumption
18-35 V
Colour housing
Operation voltage
Volume and alarm current adjustable via integrated DIP - button
Adapted to synchronisation
Ambient temperature
WeightProtection class
With high mounting base for a protected outdoor installation
max 109 dB
258 g
15. Conventional Fire Alarm Systems 99
Properties:
Standards EN 54-2: 1997/A1: 2006; EN 54-4: 1997/A2: 2006
Dimensions (H x W x D) 288 mm x 340 mm x 98 mmWeight 2,30 kg (without battery)CPD-number 1293-CPD-0132
Fire Control Panel, 2 Zones, Conventional, English Art.-no. 32638 - Type DCC 2
≥ 110 mA0 to 2 mA
1 x 12 V/7 Ah2 to 10 mA
CT 3000 fire detection components with up to 20 detectors per zone
Integrated power supply accord. to EN 54-4: 1997/A2: 2006
Description:Compact microprocessor controlled fire control panel for the the use with the CT 3000 fire detection system componentsApproved according to EN 54-2: 1997/A1: 2006 and EN 54-4: 1997/A2: 2006
24V DC/300 mA
10 to 110 mA
Different languages available on request
230V AC ± 10%
Independent connection of detector and signalling device zones
Integrated "one-man-revision mode"
2 access levels via key switch
Technical data
with 1 output for external devices rated at 24V DC
2 monitored outputs with 300 mA each for signalling devices
2 potentialfree relay outputs for alarm and fault
Emergency power supply via 1 battery 12V / up to 7 Ah
Clear display and easy operation with LED displays and operation keys
Connection possibility for 2 conventional zones for the use with the
Conventional line broken wire/ fault
-20°C to +60°C
Ambient temperature
Grey (similar to RAL 7035)Colour
21 LEDs for status display, thereof 11 LEDs masked
0 to 95 % (non-condensing)
6 keys for operation2 x 24 V/300 mA monitored for signalling devices2 relay outputs 60 V DC/120 V AC /3A for alarm and fault
Manual control of signalling devices via seperate input
Cabling: - Maximum wire diameter of 2,3 mm
Length: -Max. length of 1,1 km (0,8 mm²) E.G. JY (ST) Y 2 X 2 0,8 mm² -max. length of 3 km (2,3 mm²)
Humidity
Supply voltagePower supplyEmergency supplyQuiescent currentAlarm currentShort circuit
Display
Outputs
Stock temperatureProtection class IP 30
-5°C to +40°C
Material ABS
15. Conventional Fire Alarm Systems 100
Properties:
Standards EN 54-2: 1997/A1: 2006; EN 54-4: 1997/A2: 2006
Dimensions (H x W x D) 288 mm x 340 mm x 98 mmWeight 2,30 kg (without battery)CPD-number 1293-CPD-0132
Fire Control Panel, 4 Zones, Conventional, English Art.-no. 32639 - Type DCC 4
≥ 110 mA0 to 2 mA
1 x 12 V/7 Ah2 to 10 mA
CT 3000 fire detection components with up to 20 detectors per zone
Integrated power supply accord. to EN 54-4: 1997/A2: 2006
Description:Compact microprocessor controlled fire control panel for the the use with the CT 3000 fire detection system componentsApproved according to EN 54-2: 1997/A1: 2006 and EN 54-4: 1997/A2: 2006
24V DC/300 mA
10 to 110 mA
Different languages available on request
230V AC ± 10%
Independent connection of detector and signalling device zones
Integrated "one-man-revision mode"
2 access levels via key switch
Technical data
with 1 output for external devices rated at 24V DC
2 monitored outputs with 300 mA each for signalling devices
2 potentialfree relay outputs for alarm and fault
Emergency power supply via 1 battery 12V / up to 7 Ah
Clear display and easy operation with LED displays and operation keys
Connection possibility for 4 conventional zones for the use with the
Conventional line broken wire/ fault
-20°C to +60°C
Ambient temperature
Grey (similar to RAL 7035)Colour
25 LEDs for status display, thereof 11 LEDs masked
0 to 95 % (non-condensing)
6 keys for operation2 x 24 V/300 mA monitored for signalling devices2 relay outputs 60 V DC/120 V AC /3A for alarm and fault
Manual control of signalling devices via seperate input
Cabling: - Maximum wire diameter of 2,3 mm
Length: -Max. length of 1,1 km (0,8 mm²) E.G. JY (ST) Y 2 X 2 0,8 mm² -max. length of 3 km (2,3 mm²)
Humidity
Supply voltagePower supplyEmergency supplyQuiescent currentAlarm currentShort circuit
Display
Outputs
Stock temperatureProtection class IP 30
-5°C to +40°C
Material ABS
15. Conventional Fire Alarm Systems 101
Properties:
IP 30
-5°C to +40°C
Material ABS
Display
Outputs
Stock temperatureProtection class
Panel network of max. two fire control panels
Cabling: - Maximum wire diameter of 2,3 mm
Maximum zone lenght 2000 m
Humidity
Supply voltagePower supplyEmergency supplyQuiescent currentAlarm currentShort circuitConventional line broken wire/ fault
-20°C to +60°C
Ambient temperature
Grey (similar to RAL 7035)Colour
16 LEDs for status display (+ 8 LEDs in case of extension)
0 to 93 % (non-condensing)
6 keys for operation and programming2 x 24 V/300 mA monitored for signalling devices2 relay outputs 60 V DC/120 V AC /3A for alarm and fault
Independent connection of detector and signalling device zones
Integrated "one-man-revision mode"
Manual control of signalling devices via seperate input
Technical data
Integrated power supply accord. to EN 54-4: 1997/A2: 2006
4 monitored outputs with 300 mA each for signalling devices
2 potentialfree relay outputs for alarm and fault
Emergency power supply via 1 battery 18V / up to 7 Ah
Clear display and easy operation with LED displays and operation keys
Connection possibility for 8 conventional zones for the use with the
24V DC/1 A
10 to 110 mA
Different languages available on request
230V AC ± 10%
Fire Control Panel, 8 - 16 Zones, Conventional, English Art.-no. 32640 - Type DCC 8 plus
≥ 110 mA0 to 2 mA
1 x 12 V/18 Ah2 to 10 mA
CT 3000 fire detection components with up to 20 detectors per zone
Extension option for 8 conventional zones for up to 16 conventional zones for CT 3000 components
Description:Compact microprocessor controlled fire control panel for the the use with the CT 3000 fire detection system componentsApproved according to EN 54-2: 1997/A1: 2006 and EN 54-4: 1997/A2: 2006
CPD-number 1293-CPD-0133Standards EN 54-2: 1997/A1: 2006; EN 54-4: 1997/A2: 2006
Dimensions (H x W x D) Outer dimensions 345 mm x 455 mm x 128 mmWeight 4,26 kg (without battery)
4 zone extension module Art.-no. 32653 Type GE4 alarm zones extension Art.-no. 32654 Type SE 4
Accessories
Relay-module, 8 relays 1 A/12 V Art.-no. 32655 Type RM 8
15. Conventional Fire Alarm Systems 102
Properties:
9 to 33 V DC
Standards DIN EN 54-5 and 7
Multi sensor detector optical - heat, conventional systems Art.-no. 30022 - Type CT 3000 OT
-10°C to +60°Cmax. 93 % (+/-2%)
20 mAmax. 50 mA for LED-indicator or piezo buzzer
Integrated professional smoke detection system with highest reliability for a
Colour housing
52 mm x 100 mm
Air speed
Integrated temperature measurement as rate of rise procedure and maximum value
in accordance to EN 54-5
Intelligent analysis and disruption mode for the elimination of false alarms
Periodic sensor tests of the analyzing chamber
100 μA
60° differential temperature or smoke < 0,15 dB / m
Delivery including protective cover for installation phase
< 20 m/sIP 40White (similar to RAL 9003)ABS
Dimensions (H x Ø)
Operation voltageQuiescent currentAlarm currentOC-outputs SensitivityAmbient temperatureHumidity
Material
Protection class
Integrated locking system for the protection against removal and tamper.
Description:Optical and thermal multi sensor detector for conventional systems for earliest fire detection and indication in all environments with difficult ambient conditions according to DIN EN 54-7 and 5
Alarm output for the triggering of a LED indicators
Multicolour-LED for alarm (red) and fault (yellow)
Technical data
secure alarm verification with 16 fold measurement and intelligent logics
15. Conventional Fire Alarm Systems 103
Properties:
Integrated locking system for the protection against removal and tamper
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7
Alarm output for the triggering of a LED indicators
Multicolour-LED for alarm (red) and fault (yellow)
Technical data
Dimensions (H x Ø)
Operation voltageQuiescent currentAlarm currentOC-outputs SensitivityAmbient temperatureHumidity
IP 40White (similar to RAL 9003)ABS
Protection classColour housing
44 mm x 100 mm
Air speed
Intelligent analysis and disruption mode for the elimination of false alarms
Periodic sensor tests of the analyzing chamber
100 μA
60° differential temperature or smoke < 0,15 dB / m
Delivery including protective cover for installation phase
9 to 33 V DC
Material
< 20 m/s
Standards DIN EN 54-5 and 7
Optical smoke detector, conventional system Art.-no. 30015 - Type CT 3000 O
-10°C to +60°Cmax. 93 % (+/-2%)
20 mAmax. 50 mA for LED-indicator or piezo buzzer
Integrated professional smoke detection system with highest reliability for a
secure alarm verification with 16 fold measurement and intelligent logics
System approval S295054, S208123 and S210001
CPD-Number 0786-CPD-20042VdS approval G203036
15. Conventional Fire Alarm Systems 104
Properties:
Heat detector with fixed & rate of rise temperature settings for conventional systems Art.-no. 30014 - Type CT 3000 T
-10°C to +60°Cmax. 93 % (+/-2%)
20 mAmax. 50 mA for LED-indicator or piezo buzzer
80 μA
Integrated locking system for the protection against removal and tamper
Differential temperature
Delivery including protective cover for installation phase
Standards DIN EN 54-552 mm x 100 mm
Air speed
Dimensions (H x Ø) Material
< 20 m/sIP 40White (similar to RAL 9003)ABS
Protection classColour housing
OC-outputs SensitivityAmbient temperature
9 to 33 V DCOperation voltageQuiescent current
Humidity
Description:Heat detector with fixed and rate of rise temperature settings for conventional systems for earliest fire detection and indication in all environments with difficult ambient conditions according to DIN EN 54-5
Alarm output for the triggering of a LED indicators
Multicolour-LED for alarm (red) and fault (yellow)
Technical data
Integrated temperature measurement as rate of rise procedure and maximum value
in accordance to EN 54-5
Periodic sensor tests of the analyzing chamber
Alarm current
15. Conventional Fire Alarm Systems 105
Properties:
System approval S295054, S208123 and S210001
CPD-Number 0786-CPD-20308VdS approval G 206097
Standards DIN EN 54-5
Optical smoke detector for air ducts, conventional system Art.-no. 30977 - Type CT 3000 O/K
-10°C to +60°Cmax. 93 % (+/-2%)
20 mAmax. 50 mA for LED-indicator or piezo buzzer
Integrated professional smoke detection system with highest reliability for a
secure alarm verification with 16 fold measurement and intelligent logics
Intelligent analysis and disruption mode for the elimination of false alarms
Periodic sensor tests of the analyzing chamber
100 μA
60° differential temperature or smoke < 0,15 dB / m
Delivery including protective cover for installation phase
9 to 33 V DCQuiescent currentAlarm currentOC-outputs Sensitivity
ABS
Protection classColour housing
44 mm x 100 mmMaterial
Ambient temperatureHumidity
IP 40White (similar to RAL 9003)
Air speed 20 m/s
Test chamber housing for air ducts Art.-No. 31191 - Type LKMG
Integrated locking system for the protection against removal and tamper
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7 especially for the use in air ducts and smoke aspiration systems
Alarm output for the triggering of a LED indicators
Multicolour-LED for alarm (red) and fault (yellow)
Technical data
Dimensions (H x Ø)
Operation voltage
15. Conventional Fire Alarm Systems 106
Optical smoke detector, conventional system, mesh design, white Art.-no. 31929 - Type CT 3001 O white
Optical smoke detector, conventional system, mesh design, black Art.-no. 31926 - Type CT 3001 O black
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7Mesh design, white colour
Optical smoke detector, conventional system, mesh design, silver Art.-no. 31589 - Type CT 3001 O silver
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7Mesh design, silver colour
42 mm x 95 mmDimensions (H x Ø)
Standards DIN EN 54-7
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7Mesh design, black colour
Technical data
Material ABS, metal mesh
For more technical details please see page 109.
15. Conventional Fire Alarm Systems 107
Material Glass, ABSStandards DIN EN 54–7
Technical data
Dimensions (H x W x D) 44 mm x 122 mm x 122 mm
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7Round glass design, silver colour
47 mm x 110 mmGlass, ABS
Optical smoke detetctor, conventional system, square glass design, white Art.-no. 32470 - Type CT 3006 O white
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7Square glass design, white colour
Dimensions (H x Ø) MaterialStandards DIN EN 54–7
Technical data
Optical smoke detector, conventional system, round glass-design, silver Art.-no. 30552 - Type CT 3005 O silver
Optical smoke detector, conventional system, round glass-design, white Art.-no. 30551 - Type CT 3005 O white
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7Round glass design, white colour
For more technical details please see page 109.
15. Conventional Fire Alarm Systems 108
Optical smoke detector, conventional system, round flat design, white Art.-no. 32468 - Type CT 3007 O white
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7Round flat design, white colour
Optical smoke detector, conventional system, flat design, silver colour Art.-no. 32469 - Type CT 3007 O silver
Material
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7Round flat design, silver colour
33 mm x 110 mm ABS
Dimensions (H x Ø)
Standards DIN EN 54-7
Technical data
For more technical details please see page 109.
15. Conventional Fire alarm systems 109
Properties:
Art.-no. 31926 - Type CT 3001 O black
Multicolour-LED for alarm (red) and fault (yellow)
Integrated locking system for the protection against removal and tamper
Optical smoke detector, conventional system, mesh design, silver Art.-No. 31589 - Type CT 3001 O silver
Periodic sensor tests of the smoke chamber
Alarm output for the triggering of a LED indicators
Technical data
Optical smoke detector, conventional system, mesh design, black
secure alarm verification with 16 fold measurement and intelligent logics
Intelligent analysis and disruption mode for the elimination of false alarms
Ambient temperatureHumidity
IP 40Protection classAir speed < 20 m/s
100 μA
< 0,15 dB / m
Delivery including protective cover for installation phase
9 to 33 V DCOperation voltageQuiescent current
Optical smoke detector, conventional system, mesh design, white Art.-no. 31929 - Type CT 3001 O white
-10°C to +60°Cmax. 93 % (+/-2%)
20 mAmax. 50 mA for LED-indicator or piezo buzzer
Integrated professional smoke detection system with highest reliability for a
Alarm currentOC-outputs Sensitivity
Optical smoke detector, conventional system, round glass-design, white Art.-no. 30551 - Type CT 3005 O white
Optical smoke detector, conventional system, round glass-design, silver Art.-no. 30552 - Type CT 3005 O silver
Optical smoke detector, conventional system, flat design, silver colour Art.-no. 32469 - Type CT 3007 O silver
Optical smoke detetctor, conventional system, square glass design, white Art.-no. 32470 - Type CT 3006 O white
Optical smoke detector, conventional system, round flat design, white Art.-no. 32468 - Type CT 3007 O white
15. Conventional Fire Alarm Systems 110
Properties:
Detector standard base, white Art.-no. 32242 - Type SDB 3000
Integrated connectors for the connection of one spur for the loop extension (T-branch)
Mounting space for the piezo buzzer ( Art.-no. 32091) and the detector labelling clip (Art.-no. 30479)
Description:Detector Base for all detectors of series CT and loop3000 black colour
Detector standard base, black Art.-no. 30523 - Type SDB 3000 black
Technical data
Integrated connectors for LED indicator (Art.-no. 31193) or piezo buzzer (Art.-no. 32091)
MaterialDimensions (H x Ø)
ABS21 mm x 95 mm
Space for additional connectors Type WAGO 243
Including transparent seal cover to protect the base against contaminents
Description:Detector Base for all detectors of series CT and loop3000white colour
Description:Detector Base for all detectors of series CT and loop3000 silver colour
Detector standard base, silver Art.-no. 30926 - Type SDB 3000 silver
15. Conventional Fire Alarm Systems 111
Properties:
System approval S295054, S208123, S210001
White (Art.-no. 30469), silver (Art.-no. 32086) or black (Art.-no. 32085)ABS21 mm x 95 mmApprox. 60 gG207011
MaterialDimensions (H x Ø) Weight
Compatible to all detetcors of series CT 3000
Suitable for the connection to 24 V-systems
Description:Detector base with integrated relay for triggering of external devices or displays via potential free change over contact for all detectors of series CT 3000Available in white, silver or black colour
Technical data
Triggering of the relays at alarm and removal of detector
Triggering of the relay only at alarm is possible
Detector relay base for CT detectors, white, 24 V-version Art.-no. 30469 - Type DRB 3000 white
Ambient temperatureColour housing
Space for additional connectors Type WAGO 243
Mounting space for the detector labelling clip (Art.-no. 30479)
0,4 mA1 change over contact 30 V / 1A
Including transparent seal cover to protect the base against contaminents
18 to 30 V DC22 mA
VdS approval
Detector relay base for CT-detectors, silver, 24 V-version Art.-no. 32086 - Type DRB 3000 silver
Detector relay base for CT-detectors, black, 24 V-version Art.-no. 32085 - Type DRB 3000 black
Operation voltageQuiescent currentAlarm current
-10°C to +60°COutputs
15. Conventional Fire Alarm Systems 112
Properties:
Weight Approx. 60 g
White (Art.-no. 32265), silver (Art.-no. 32266)ABS21 mm x 95 mm
MaterialDimensions (H x Ø)
0,7 mA1 change over contact 30 V / 1A
Including transparent seal cover to protect the base against contaminents
10 to 15 V DC6 mA
Operation voltageQuiescent currentAlarm current
Detector relay base for CT detectors, white, 12 V-version Art.-no. 32265 - Type DRB 400 white
Compatible to all detetcors of series CT 3000
Suitable for the connection to 12 V-systems
Description:Detector base with integrated relay for triggering of external devices or displays via potential free change over contact for all detectors of series CT 3000Available in white, silver
Technical data
Detector relay base for CT-detectors, silver, 12 V-version Art.-no. 32266 - Type DRB 400 silver
Space for additional connectors Type WAGO 243
Mounting space for the detector labelling clip (Art.-no. 30479)
Triggering of the relays at alarm and removal of detector
Triggering of the relay only at alarm is possible
-10°C to +60°COutputsAmbient temperatureColour housing
15. Conventional Fire Alarm Systems 113
Properties
Properties
Art.-no. 30479 - Type MBC
Dimensions (H x W x D) M3 x 10 mm
Piezo buzzer Art.-no. 32091 - Type SP
ABS
Local accoustic alarm
Loud accoustic signal due to external and free sound emission
Description:Accoustic piezo alarm buzzer for direct connection to all detectomat detector bases for the local accoustic signalling in occupied areas (e.g hotels, residential homes etc.)
Dimensions (H x W x D)
Technical data
Direct voltage supply via detector/ loop
Activation by parallel connection to the alarm LED of the detector
VolumeColour housingMaterial
Packing unit 30 pieces
White (similar RAL 9003)
Mechanically compatible to all detectomat standard detector bases
Approx. 85 dB / 0.3 m
8 mm x 45 mm x 35 mm
Detector labelling clip, 30 pcs
Art.-no. 32237 - Type MSSDetector safety screw, VE 30
Description:Immersable set screw for the permanent mounting of detectors of the series CT, HD and PL into the detector base
Hexagon socket screw M3Sharp form for fixation into the detector base
ABSMaterial
Approx. 85 dB / 0.3 mWhite (similar RAL 9003)Colour housing
Pack contains 30 unitsVolume
Description:The detector labelling clip is used to display the detector and zone number of the device and is connectable to all detectomat standard bases
Technical data
Plugs directly onto the detector base
Maximum character height of 25 mm
15. Conventional Fire Alarm Systems 114
Properties
in the smoke chamber.
gradient. Overpressure and low pressure (e.g. air conditioned roos)
120 mm110 mm
The design ring is only suitable for ceilings in rooms without pressure
can lead to draughts at the ceiling which could influence the analysis
Designring for detectors PL 3305 O white and CT 3005 O white Colour White RAL 9003
Technical data for DR 45 white and DR45 silver
Design ring for ceiling mounting, white Art.-no. 32070 - Type DR45 white
Description:Architectural modern designed installation set for a deeper installation of detectors of the series loop 3000 and CT 3000 in "05 Design" suitable for e.g. suspended ceilings
Designring for detectors PL 3305 O silver and CT 3005 O silver
Easy installation with screw holder
Sheet steel, coated
165 mm
Colour-coordinated with detectors in glass design
Compatible with all detector bases of the loop 3000 system and conventional system
White RAL 9003
General remarks
Design ring for ceiling mounting, silver Art.-no. 31684 - Type DR45 silver
Description:Architectural modern designed installation set for a deeper installation of detectors of the series loop 3000 and CT 3000 in "05 Design" suitable for e.g. suspended ceilings
Colour
MaterialInstallation holeInner diameterOuter diameter
15. Conventional Fire Alarm Systems 115
Properties
Properties
Weight 40 g
Dimensions (H x Ø) 335 g
Dimensions (H x Ø) 43,5 mm x 105 mmProtection class IP 66
Colour housing White (similar RAL 9003)Material ABS
Base with heater Art.-no. 31875 - Type APS b
White
max. 4 W -30°C to + 60°C
Integrated connectors for LED indicator (Art-no. 31193) or piezo buzzer (Art-no. 32091)
Space for additional connectors Type WAGO 243
Description:Detector base with integrated temperature-controlled heater for all detectomat detectors of series CT and loop3000 for the use in climate critical and humid environments
Without detector base
160 mA
IP 66
Integrated connectors for the connection of one spur for the loop extension (T-branch)24 V DC
2 cable entry points for cable glands M16
Technical data
Integrated temperature-controlled heater for regulated ambient conditions for detectors.
Including Detector base SDB 3000
Protection classColour housing
Technical data
Integrated sealing against condensate and dripping water
Base adapter for surface mounting, IP 66 Art.-no. 32444 - Type DAB 3000
Description:Adapter housing for the installation in finery and for the use in humid environments for all detectomat detector bases
Operation voltage Current consumption Power Ambient temperature
15. Conventional Fire Alarm Systems 116
Properties
Properties
Dimensions (H x Ø) 160 mm x 120 mmWeight Approx. 140 g
Cable entry from the back required for the detector base, siren and beaconColour WhiteMaterial Steel
like e.g. balls or other objects with a solid metal grid
Installation of the protection cage after the device installation (screw fixation)
Art.-no. 31317 - Type SK
Description:Protective cage for the mechanical protection of detectors of the series CT and loop3000 and sirens and beacons for the application in e.g. sport halls or leisure centers
Technical data
Installation of the protection cage after the detector installation
with three fixation points (screw fixation)
White
Protection of the detector, siren or beacon against foreign objects
Protective cage, white, for detectos, sirens and beacons
ColourMaterialDimensions (H x Ø) Weight Approx. 150 g
Protective cage for detectors, white Art.-no. 32267 - Type SG
75 mm x 150 mm
Description:Protective cage for the mechanical protection of detectors of the series CT and loop3000 for the application in e.g. sport halls or leisure centers
Technical data
Protection of the detector against foreign objects like e.g. balls or other objects with a solid metal grid
Compatible to detectors of the design variants 0, 1 and 2
Steel
Cable entry from the back required for the detector base
15. Conventional Fire Alarm Systems 117
Properties:
Properties:
Properties:
Weight 330 g
Material Sheet steel powder coatedDimensions (H x W x D) 80 mm x 138 mm x 100 mm
Rear cable entry in the detetcor possible
Colour RAL 7035 light grey
Detector folding bracket 0° - 110° Art.-no. 30188 - Type MKK
Description:Detector folding bracket for the mounting of detectors of the series CT and loop3000 at suitable ceilings (e.g. production halls)
Technical data
Steplessly adjustment of an angle from 0° to 110°
Adjustment of the angle via screwRear cable entry in the detector possible
Weight 1.200 g
Colour RAL 7035 light grey
Detector bracket 270 - 480 mm Art.-no. 30187 - Type MKBD
135 mm x 100 mm x 270 mm to 480 mm
Description:Detector bracket for the mounting of detectors of the series CT and loop3000 in false floors and false ceilings
Technical data
Steplessly variable from 270 to 480 mm
Angle of the detector bracket stepless adjustable from 0° to 110°Rear cable entry in the detector possible
Colour
Material Sheet steel powder coatedDimensions (H x W x D) 150 mm x 117 mm x 13 mm to 154 mmWeight 430 g
Detector distance console 80 mm Art.-no. 30189 - Type MAK
MaterialDimensions (H x W x D)
RAL 7035 light greySheet steel powder coated
Technical data
Mounting distance to the detector base 80 mm
Description:Detector distance console for the split mounting of detectors of the series CT and loop3000 to horizontal ceilings
15. Conventional Fire Alarm Systems 118
Properties:
Properties:
Dimensions (H x W x D)
RAL 7035 light greySheet steel powder coated
Weight 390 g
Material Sheet steel powder coatedDimensions (H x W x D) 50 mm x 100 mm x 200 mm
Colour
Wall bracket 400 mm Art.-no. 30190 - Type WA 4
50 mm x 100 mm x 400 mm
Description:Wall bracket for the mounting of detectors of the series CT and loop3000, e.g. for the use with fire protection closures
Technical data
Distance to the wall: 400 mmRear cable entry in the detector possible
ColourMaterial
Weight 770 g
RAL 7035 light grey
Wall bracket 200 mm Art.-no. 30191 - Type WA 2
Description:Wall bracket for the mounting of detectors of the series CT and loop3000, e.g. for the use with fire protection closures
Technical data
Distance to the wall: 200 mmRear cable entry in the detector possible
15. Conventional Fire Alarm Systems 119
Properties
Standards DIN EN 54-11
Manual call point, Conventional system, without LED Art.-no. 32082 - Type SBDH ABS - R
IP 42Red (RAL 3000)
27 mA-10°C to +60°C
88 mm x 88 mm x 54 mm
Technical data
Description:Push button detector for conventional system for the manual activation of an alarm accord. to DIN EN 54-11In a red plastic case with label symbol "burning house"
ABS
up to 30 V DC
Material
Spring buttom detector mechanics for the activation of a manual alarm
max. 93 % (+/-2%)
Non-destructive activation and reset via mechanics
Colour housing
Dimensions (H x W x D)
Operation voltageAlarm currentAmbient temperatureHumidityProtection class
15. Conventional Fire Alarm Systems 120
Properties
Accessories
Manual Call Point, conventional system, ABS, red Art.-no. 31675 - Type CT 3000 PBDH-ABS-R
IP 42Red (RAL 3000)
27 mA-10°C to +60°C
Integrated reset mechanics (operation from inside)
Integrated red alarm-LED
Description:Manual Call Point for conventional systems for the manual activation of an alarm and status display via LED accord. to DIN EN 54-11Red plastic housing with imprint "burning house"
ABS135 mm x 135 mm x 33 mm
Technical data
Push Button mechanics for the activation of a manual alarm
Activation after smash of the front glass and button push
max. 93 % (+/-2%)
Lockable plastic housing
Material
12 to 24 V DC
Dimensions (H x W x D)
Operation voltageAlarm currentAmbient temperatureHumidityProtection classColour housing
Colour housing Red (RAL 3000)CPD-Number 0786-CPD-20526VdS approval G296033System approval S295054, S208123 and S210001
Spare key Art.-no. 40054 - Type HFM SCH M
Standards DIN EN 54-11
Replacement glass, clear Art.-no. 31910 - Type HFM EG
General remarks A plastic key comes with every 10 manual call points
Spare glass (Art.-no. 31910)Spare key metal (Art.-no. 40054)
15. Conventional Fire Alarm Systems 121
Properties
Wheatherproof housing (Art.-no. 31091)
System approval S295054, S208123 and S210001
Spare key
Art.-no. 31910 - Type HFM EG
Art.-no. 40054 - Type HFM SCH M
Standards DIN EN 54-11
Wheatherproof housing for CT 3000 PBDH-ALU-R Art.-no. 31091 - Type WG R
Suitable for a wheatherproof housing
Spare glass (Art.-no. 31910)
A metal key comes with every 10 manual call pointsGeneral remarks
Replacement glass, clear
Colour housing
12 to 24 V DC
Spare key metal (Art.-no. 40054)
Colour housing Red (RAL 3000)CPD-Number 0786-CPD-20350
Accessories
VdS approval G202034
Alarm currentAmbient temperatureHumidityProtection class
Aluminium125 mm x 125 mm x 34 mm
Technical data
Push Button mechanics for the activation of a manual alarm
Activation after smash of the front glass and button push
max. 93 % (+/-2%)
Lockable aluminium housing
MaterialDimensions (H x W x D)
Operation voltage
Manual Call Point, with LED, conventional system, Aluminium, red Art.-no. 31676 - Type CT 3000 PBDH-ALU-R
IP 42Red (RAL 3000)
27 mA-10°C to +60°C
Integrated reset mechanics (operation from inside)
Integrated red alarm-LED
Description:Manual Call Point for conventional systems for the manual activation of an alarm and status display via LED accord. to DIN EN 54-11Red aluminium housing with imprint "burning house"
15. Conventional Fire Alarm Systems 122
Properties
Properties
Properties
Wheatherproof housing for manual call points, IP 54, Aluminium, red Art.-no. 31091 - Type WG R
IP 54
Red (RAL 3000)
Including seal and gasket set for the mounting of the housing
max. 93 % (+/-2%)
Aluminium
Sealing and gasket set for a protected cable entry
Description:Wheatherproof housing for aluminium manual call points (Art.-no. 31668 and 31676) to increase the protection class to IP 54
Technical data
Robust aluminium protective housing
-10°C to +60°CAmbient temperatureHumidityProtection class
Technical data
Key for opening of all manual call points fo the series PL and CTDie-casting design, metal
Weight Approx. 295 gColour housingMaterial
Replacement glass, clear Art.-no. 31910 - Type HFM EG
Spare key Art.-no. 40054 - Type HFM SCH M
Dimensions (H x W x DT) 145 mm x 131 mm x 55 mm
Technical data
Replacement glass for manual call points of the series PL and CTClear plain version for the use in all colour varieties
15. Conventional Fire Alarm Systems 123
Properties
Manual Call Point, conventional system, IP 66, red Art.-no. 31083 - Type CT 3000 PBD-IP66-R
IP 66Red (RAL 3000)
Approx. 30 mA-35°C to +60°C
Integrated reset mechanics (operation from inside)
Description:Manual Call Point for conventional systems for the manual activation of an alarm accord. to DIN EN 54-11Red housing with imprint "burning house"in water and dust proof protection class IP66
PC135 mm x 135 mm x 61 mm
Technical data
Push Button mechanics for the activation of a manual alarm
Flame and UV resistant plastic housing
Material
12 to 28 V DC
Dimensions (H x W x D)
Operation voltageAlarm currentAmbient temperatureProtection classColour housing
Weight 475 gCPD-Number 0786-CPD-20309
Standards DIN EN 54-11
VdS approval G206113System approval S295054, S208123 and S210001
16. Wireless Fire Alarm Systems 124
Properties:
Integrated power supply and emergency battery set for the backup of
the power supply in case of power failure
Emergency supply with 8 batteries Mignon LR6
External input for 12V-supply
Protection classColour
DisplayOutputs
Ambient temperature
170 mm x 170 mm x 55 mm Dimensions (H x W x D)
Grey
Supply voltagePower supplyEmergency supply
Alarm currentRadio frequency
IP 30
ABSMaterial
10 mW ERP
5-95 % (non-condensing)
LC-Display, backlight, 15 LEDs - for status indication4 relays outputs 30 V AC / 1 A, SUB - D plug type connector, 9 polesinternal acoustic signal (85 db/ 1m)0°C to +60 °C
Radio transmission power
Humidity
Control of all alarm and status messages with plausibiity check
4 potentialfree output relays, freely programmable, SUB-D plug type connector
Different access levels with password protection
Technical data
9 status-LEDs
Individual identification of all radio devices with addresses
Monitoring of the radio devices relating to individual battery condition, fault,
radio transmission and life-signal
Integrated display with backlight
Connection of up to 100 radio devices
12 V DC
(4 relays in quiescent current operation)
Comprehensive service and analysis mode
230 V AC / 50 Hz (+/-10%)
Nominal current
Radio / Wireless Fire Control Panel Art.-no. 32487 - Type SRC 3000
max 160 mA depending on mode of operation433,42 MHz (ISM-band)
8 x Mignon LR6 for approx. 60 hours35 m A (LED operation) up to 120 mA
Enables the connection of up to 3 repeaters for extension of the transmission path
6 alarm zones with LEDs
Description:Microprocessor controlled radio fire control panel for the bidirectional wireless communication with life cycle monitoring for up to 100 radio devices for dry heated roomsOption for relay connection cable (Art.-no. 32294) and12 V connection cable for external supply (Art.-no. 32327)
General remarks Scope of delivery including 8 Mignon LR6
Relay-connection cable for SRC 3000, Art.-no. 32294, Type F.BZWeight 800 g
12 V connection cable for external supply, Art.-no. 32327, Type AKOptional accessories
16. Wireless Fire Alarm Systems 125
Properties:
Adhesive pad (Art.-no. 32587)Standards EN 14604
Accessories Anti tamper pin (Art.-no. 32301)Anti tamper screws (Art.-no. 50437)
Smoke alarm, optical home detector, wireless link module, wired network Art.-no. 30458 - Type HDv® 3000 O
IP 40White (similar to RAL 9003)
under normal temperatures (15-25°C), Test accord. to DIN 14676max. 95 % (+/-2%)
Intelligent analysis and disruption mode for the elimination of false alarms
Inspected pollution resistance, integrated pollution recognition and fault indication
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LIncludes a lithium battery for the long term operation
Intelligent technology for smoke measurement under variations in temperature,
Integrated professional smoke measuring chamber with the highest reliability
for secure alarm verifications via 16 fold measurements and intelligent logics
Approx. 10 years, when used as Stand-Alone-Detector
Integrated interface for wireless link modules for the additional functionality of the smoke detection as part of a linked system
-10°C to +60°CBattery lifetimeAmbient temperature
Technical data
in the cases of contaminated environments
Periodic sensor tests of the smoke chamber
Pre-alarm for condensation, consequently suitable for the use in kitchens and bathrooms
Dimensions (H x Ø) Weight
no additional cost intensive heat sensor required
Easy activation of the test-function via LED-mechanism
Complies with industrial standards in accordance to IPC 2
< 20m/sHumidityAir speed
Suitable for use in applications with demanding requirements
e.g. vehicles in accordance to EN 14604 Annex L
CPD-NumberVdS approval
ABS52 mm x 100 mmApprox. 160g0786-CPD-20302 and 0786-CPD-20681G202042
Material
Includes an alkaline battery for the long term operation
Special designed housing for optimal smoke entry and acoustic alarm signal transmission
Integrated Piezo-buzzer for a loud acoustic alarm (> 85dB)
Integrated LED displaying alarm and fault conditions
Integrated locking system for the protection against removal and tamper.
Indication of maintenance and service via optical and acoustic signals
Protection ClassHousing colour
Suitable for a number of different fixing methods
Easy mounting of the detectors in the base using Click-In-Technology
16. Wireless Fire Alarm Systems 126
Properties:
Properties:
Alarm current 18 mA (radio reception) to 35 mA (transmission)Radio frequency 433,42 MHz (ISM-band)
Emergency supply via TMQuiescent current 36 µA
Radio plug in module for optical detector / alarm Art.-no. 32488 - Type SRC 3000 FMO
LED0°C to +55 °C
36 µA18 mA (radio reception) to 35 mA (transmission)
Enables the activation of the back up alarm of all devices of the system
Micro switch for the teach in function with display of the signal strength at the panel display
Description:Microprocessorcontrolled radio module for the bidirection al radio communication with life time cycle monitoring for the integration to the optical smoke detector / alarm of the
series HDv® 3000 suitable for dry, heated rooms
via HDv® 3000
433,42 MHz (ISM-band)
Monitoring relating to individual battery condition, fault, radio transmission and life-signal
9 V DC
Radio frequency
Operation voltage
Emergency supplyQuiescent currentAlarm current
Technical data
Integrated switchable acoustic signal for the receipt of alarms
Individual identification of all radio devices with addresses
Transmission of all alarm and status messages with plausibility check
Bidirectional data exchange with the radio wireless fire control panel SRC 3000
Integrated switchable acoustic signal for the receipt of alarmsIndividual identification of all radio devices with addresses
Operation voltage 9 V DC
Transmission of all alarm and status messages with plausibility check
Bidirectional data exchange with the radio wireless fire control panel SRC 3000
Enables the activation of the back up alarm of all devices of the system
Micro switch for the teach in function with display of the signal strength at the panel display
DisplayAmbient temperature
Technical data
General remarks Suitable for the HDv® 3000 O and design variants
Radio plug in module for heat detector / alarm Art.-no. 32489 - Type SRC 3000 FMT
Description:Microprocessorcontrolled radio module for the bidirection al radio communication with life time cycle monitoring for the integration to the heat detector / alarm TM suitable for dry heated rooms
General remarks Suitable for the TM detector
Display LEDAmbient temperature 0°C to +55 °C
16. Wireless Fire Alarm Systems 127
Properties:
9 V DC
Alarm currentOutputResponse sensitivity
max. 20 mA4 Relais 50 V / 0,5 A
Heat detector with fixed temperature settings, Stand alone Art.-no. 31957 - Type TM
Integrated interface for wireless link modules for the additional functionality of the detection
as part of a linked system
Integrated temperature measurement as maximum value
Alarm temperature 60°C
Integrated Piezo-alarm for a loud acoustic alarm (> 85dB)
Periodic sensor test with signaling of a sensor defect
Technical data
Dimensions (H x Ø) 70 mm x 80 mm
0°C to +60°Cmax. 80 % (+/-2%)IP 20WhiteABS
Protection class
Ambient temperatureHumidity
Colour housingMaterial
Description:Battery supplied stand alone heat detector with maximum value response sensitivity as conventional detctor for earliest fire detectioon and indication in all environments with difficult ambient conditions
max. 16 μA
Integrated LED for alarm and fault messages
Display of maintenance and service via optical and acoustic signals
Operation voltageQuiescent current
60°C
Scope of supply including batteries and fixing material
16. Wireless Fire Alarm Systems 128
Properties:
Quiescent currentAlarm currentRadio frequencyDisplay
6 V DC
Dimensions (H x W x D)
IP 42BlueABS120 mm x 120 mm x 31 mm
Protection classColour housingMaterial
Ambient temperature
Integrated switchable acoustic signal for the receipt of alarms
Technical data
Integrated warning signal for low battery
Transmission of all alarm and status messages with plausibility check
Bidirectional data exchange with the radio wireless fire control panel SRC 3000
Enables the activation of the back up alarm of all devices of the system
Integrated Piezo - alarm for a loud acoustic alarm (> 85dB)
Operation voltageEmergency supply
Scope of delivery including batteries
Description:Manual call point with integrated microprocessorcontrolled wireless radio module for the bidirectional radio communication with life time cycle monitoring suitable for dry, heated rooms
Integrated LED for alarm and fault messages
Display of maintenance and service via optical and acoustic signals
Micro switch for the teach in function with display of the signal strength at the panel display
Radio manual call point Art.-no. 32490 - Type SRC 3000 HM
LED0°C to +55°C
40 µA40 mA433,42 MHz (ISM-band)
Individual identification of all radio devices with addresses
Monitoring relating to individual battery condition, fault, radio transmission and life-signal
16. Wireless Fire Alarm Systems 129
Properties:
Dimensions (H x W x D) Dimensions (H x W x D)
Radio push button detector, manual call point Art.-no. 32491 - Type SRC 3000 MCP
0°C to +55°CIP 42
7,5 µA40 mA
Enables the activation of the back up alarm of all devices of the system
Micro switch for the teach in function with display of the signal strength at the panel display
Description:Push button detector with integrated microprocessorcontrolled wireless radio module for the bidirectional radio communication with life time cycle monitoring suitable for dry, heated rooms
RedABS
Technical data
Integrated warning signal for low battery
433,42 MHz (ISM- band)
Scope of delivery including batteries
9 V DC
Individual identification of all radio devices with addresses
Material
Operation voltageEmergency supplyQuiescent currentAlarm currentRadio frequencyAmbient temperatureProtection class
Transmission of all alarm and status messages with plausibility check
Bidirectional data exchange with the radio wireless fire control panel SRC 3000
Colour housing
16. Wireless Fire Alarm Systems 130
Properties:
Ambient temperature
Quiescent currentAlarm current
Radio frequencyDisplay
Volume
Dimensions (H x W x D)
IP 65BlueBase ABS, lense PC93 mm x 121 mm
Protection classColour housingMaterial
Integrated warning signal for low battery
Transmission of all alarm and status messages with plausibility check
Bidirectional data exchange with the radio wireless fire control panel SRC 3000
Operation voltageEmergency supply
Scope of delivery including batteries
6 V DC
Display of maintenance and service via optical and acoustic signals
Micro switch for the teach in function with display of the signal strength at the panel display
Integrated switchable acoustic signal for the receipt of alarms
Technical data
0°C to +55°C
45 µA150 mA
433,42 MHz (ISM-band)
0,7 J101 dB (adjustable to a lower value)
Wireless sounder / beacon combination Art.-no. 32492 - Type SRC 3000 SB
LED
Red XENON beacon with 0,7 J energy according to EN 54-23
32 tone sirene with 101 dB, synchronized
Luminous intensity
Individual identification of all radio devices with addresses
Monitoring relating to individual battery condition, fault, radio transmission and life-signal
Description:Sounder / beacon combination with integrated microprocessorcontrolled wireless radio module for the bidirectional radio communication with life time cycle monitoring suitable for dry, heated rooms
16. Wireless Fire Alarm Systems 131
Properties:
Dimensions (H x W x D) 158 mm x 195 mm x 45 mm
433,42 MHz (ISM-band)5 LEDs-status indication
Colour housing
9 V (for 8 hours)max. 35 mA
Description:Repeater for the extension of the transmission path between the SRC 3000 and the devices with integrated microprocessorcontrolled radio module for the bidirectional wireless communication with life cycle monitoring
Individual identification of all radio devices with addresses
Technical data
12 V DC
Connection of up to 10 devices per repeater
Connection of up to 3 repeaters per SRC 3000 system
Display of the actual radio signal strength at the programming
Wireless radio repeater Art.-no. 32493 - Type SRC 3000 R
max. 70 mA
Scope of delivery including batteries and power supply
230 V AC via AC adaptor plug
Bidirectional data exchange with the radio wireless fire control panel SRC 3000
Enables the activation of the back up alarm of all devices of the system
Integrated emergency supply battery
Integrated LED for alarm and fault messages
Display of maintenance and service via optical and acoustic signals
Transmission of all alarm and status messages with plausibility check
Display
Material
0°C to +60 °CIP 20GreyABS
Monitoring relating to individual battery condition, fault, radio transmission and life-signal
Ambient temperatureProtection class
Alarm currentRadio frequency
Supply voltageOperation voltageEmergency supplyQuiescent current
16. Wireless Fire Alarm Systems 132
Properties:
Radio frequencyAmbient temperatureProtection class
Radio reset module Art.-no. 32503 - Type SRC 3000 FRM
Description:Resetmodule for the external reset of the SRC 3000 with integrated microprocessorcontrolled wireless radio module for the bidirectional radio communication with life time cycle monitoring
Enables the control with an impulse of 2 - 10 sec.
Integrated warning signal for low battery
433,42 MHz (ISM - band)
Scope of delivery including batteries
9 V DC
Enables the activation of the back up alarm of all devices of the system
Micro switch for the teach in function with display of the signal strength at the panel display
Operation voltageEmergency supplyQuiescent current
Radio input module Art.-no. 32494 - Type SRC 3000 IM
Individual identification of all radio devices with addresses
Monitoring relating to individual battery condition, fault, radio transmission and life-signal
1 input as connection option for a potential free contact
Display of the actual radio signal strength at the programming
Transmission of all alarm and status messages with plausibility check
Bidirectional data exchange with the radio wireless fire control panel SRC 3000
Technical data
max 35 µA25 mA
Description:Input module with integrated microprocessorcontrolled wireless radio module for the bidirectional radio communication with life time cycle monitoring sutable for dry heated rooms
Alarm current
Dimensions (H x W x D) 92 mm x 57 mm x 30 mm
0°C to +60 °CIP 42GreyABS
Colour housingMaterial
17. Smoke alarm detectors and accessories 133
Properties:
Indication of maintenance and service via optical and acoustic signals
Protection ClassHousing colour
Suitable for a number of different fixing methods
Up to 40 smoke detectors of the HD range can be linked together to increase the alarm area
CPD-NumberVdS approval
ABS52 mm x 100 mmApprox. 160g0786-CPD-20302 and 0786-CPD-20681G202042
MaterialDimensions (H x Ø) Weight
no additional cost intensive heat sensor required
Easy activation of the test-function via LED-mechanism
Complies with industrial standards in accordance to IPC 2
< 20m/sHumidityAir speed
Suitable for use in applications with demanding requirements
e.g. vehicles in accordance to EN 14604 Annex L
Easy mounting of the detectors in the base using Click-In-Technology
Technical data
in the cases of contaminated environments
Periodic sensor tests of the smoke chamber
Pre-alarm for condensation, consequently suitable for the use in kitchens and bathrooms
Includes an alkaline battery for the long term operation
Special designed housing for optimal smoke entry and acoustic alarm signal transmission
Integrated Piezo-buzzer for a loud acoustic alarm (> 85dB)
Integrated LED displaying alarm and fault conditions
Integrated locking system for the protection against removal and tamper.
Approx. 10 years, when used as Stand-Alone-Detector
Integrated interface for wireless link modules for the additional functionality of the smoke detection as part of a linked system
-10°C to +60°CBattery lifetimeAmbient temperature
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LIncludes a lithium battery for the long term operation
Intelligent technology for smoke measurement under variations in temperature,
Integrated professional smoke measuring chamber with the highest reliability
for secure alarm verifications via 16 fold measurements and intelligent logics
Accessories Anti tamper pin (Art.-no. 32301); Anti tamper screws (Art.-no. 50437)
Smoke alarm, optical home detector, wireless link module, wired network Art.-no. 30458 - Type HDv® 3000 O
IP 40White (similar to RAL 9003)
under normal temperatures (15-25°C), Test accord. to DIN 14676max. 95 % (+/-2%)
Intelligent analysis and disruption mode for the elimination of false alarms
Inspected pollution resistance, integrated pollution recognition and fault indication
Adhesive pad (Art.-no. 32587)Standards EN 14604
17. Smoke alarm detectors and accessories 134
Dimensions (H x Ø)
CPD - NumberApprox. 140 g
G202054
Material
VdS approval
Weight0786-CPD-20303
42 mm x 95 mmABS, Aluminium
Standards EN 14604
Smoke alarm, optical home detector, wireless link module, mesh design, white Art.-no. 30023 - Type HD 3001 O white
Smoke alarm, optical home detector, wireless link module, mesh design, black Art.-no. 30123 - Type HD 3001 O black
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LIncludes a lithium battery for the long term operationBlack mesh design
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LIncludes a lithium battery for the long term operationWhite mesh design
Technical data
Smoke alarm, optical home detector, wireless link module, mesh design, silver Art.-no. 30024 - Type HD 3001 silver
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LIncludes a lithium battery for the long term operationSilver mesh design
Properties and general technical data similar to HDv® 3000 O.
17. Smoke alarm detectors and accessories 135
Standards EN 14604
Smoke alarm, optical home detector, wireless link module, glass design white Art.-no. 32015 - Type HD 3005 O white
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LIncludes a lithium battery for the long term operationGlass design white
Technical data
Smoke alarm, optical home detector, wireless link module, glass design silver Art.-no. 32004 - Type HD 3005 O silver
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LIncludes a lithium battery for the long term operationGlass design silver
Approx. 320 g
56 mm x 110 mmGlass, ABS
Smoke alarm, optical home detector, wireless link module square glass design white Art.-no. 32292 - Type HD 3006 O white
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LIncludes a lithium battery for the long term operationSquare glass design white
Dimensions (H x Ø) Material
Technical data
Dimensions (W x D) 122 mm x 122 mm
Weight
G2040910786-CPD-20307CPD - Number
VdS approval
Material Glass, ABSStandards EN 14604
Properties and general technical data similar to HDv® 3000 O.
17. Smoke alarm detectors and accessories 136
Lithium battery for home smoke detectors Art.-no. 30528 - Type Batterie LI 9V/ 1.2 Ah
Monitoring plomb Art.-no. 32301 - Type SP 100
Screw for detector Art.-no. 32237 - Type MSS
Smoke alarm, optical home detector, wireless link module, flat design white Art.-no. 32290 - Type HD 3007 O white
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LIncludes a lithium battery for the long term operationRound flat design, white colour
Dimensions (H x Ø)
Technical data
Standards EN 14604
Technical data
0786-CPD-20859
ABSApprox. 320g
56 mm x 110 mmABS
Smoke alarm, optical home detector, wireless link module, flat design with logo Art.-no. 32325 - Type HD 3008 O white
Description:Intelligent stand alone smoke detector for early detection giving a local acoustic alarm in private and domestic applications in accordance to EN 14604 for the use in applications with demanding requirements e.g. caravan- and camper vans again in accordance to EN 14604 Annex LRound design, with individual logo, white colour
Standards EN 14604
Material
CPD - NumberVdS approval
MaterialDimensions (H x Ø) 56 mm x 110 mm
Weight
G208084
Properties and general technical data similar to HDv® 3000 O.
17. Smoke alarm detectors and accessories 137
Properties:
Properties:
Ambient temperature 0°C to 55°CGeneral remarks Suitable for HDv® 3000 O and design variants
Frequency 868 MHz (ISM-band)Display LED
Quiescent current 36 µAAlarm current up to 37 mA
Wireless interlink module for smoke alarms Art.-no. 30933 - Type FM 868
Description:Microprocessor controlled bidirectional wireless module with fault monitoring and alarm transmission to interlink smoke alarms in cascaded networks suitable for dry, heated rooms
Ambient temperatureProtection classHumidityColour
Technical data
IP 20
54 mm x 22 mm x 22 mm
Supply of the module via battery of the smoke alarm
-10°C to +60°C
External voltage supply for the connected device required
Extension module for all smoke alarms of the series HDv 3000 and HD 3000
without integral battery for the connection of external devices
Easy and fast assembly plug in module for the smoke alarm
Connection of external devices to the change over contact
Description:Relay output module for the parallel control of external alarm devices in case of fire, e.g. additional devices for handicapped and hearing impaired persons
Relay module for smoke alarms Art.-no. 30942 - Type RM
5-95 % (non-condensing)Green
Bidirectional data exchange to othe wireless interlink modules
Enables the activation of the back up alarm of all devices of the system
Dimensions (H x W x D ) WeightOutput
Technical data
Approx. 10 g1 change over relay 30 V DC / 2 A
Emergency supply
by using the relay moduleGeneral remarks
Wireless interlink option for up to 40 smoke alarms without using a fire control panel
9 V DCvia HDv® 3000 O
Integrated repeater function for the for the extension of the transmission path to other network devicesMonitoring relating to individual battery condition, fault, radio transmission and life-signal
Operation voltage
The lifetime of the battery of the smoke alarm is reduced
18. Infrared-Beam detectors and accessories 138
Properties:
Standards DIN EN 54-12
Infrared Beam detector Art.-no. 31095 - Type FR 2000
IP 50Grey
22 mA2 x 30 V DC/1A
Range 5-100 m
Control width: max. 13m
Control height: max. 12m
Description:Infrared beam detector for the detection of light and dark beam with sender, receiver and separate analyser
Technical data
Detection of light and dark smoke
14 mA
-20°C to + 55°C
Connection to the loop 3000 via IOM 3311
11,5 to 28 V DCOperation voltageQuiescent currentAlarm currentOutput relayAmbient temperature
Control area: 1300 m²
Monitored area and mounting accord. to DIN VDE 0833
Potential free relays for alarm and fault
Three sensitivities: 25%, 35% and 50%
Protection classColour housing
Dimensions (H x W x D)
GreySheet steel2,14 kg265mm x 210mm x 85mm
Colour frontMaterialWeight
18. Infrared-Beam detectors and accessories 139
Properties:
Art.-no. 32471 - Type EP 01
Ambient temperatureProtection classColour housing
Extension prism for FR 50 RV, FR 100 RV, FR 5000
Standards DIN EN 54-12
-30°C to + 55°C
Operation voltageQuiescent currentAlarm currentOutput relay
Dimensions (H x W x D)
ABS0,67 kg117mm x 210mm x 120mm
MaterialWeight
Infrared Beam detector Art.-no. 31861 - Type FR 50 RV
IP 50Grey
15 mA2 x 30 V DC/1A
Monitored area and mounting accord. to DIN VDE 0833
Potential free relays for alarm and fault
Infrared Beam detector Art.-no. 31486 - Type FR 100 RV
Description:Infrared beam detector for the detection of light and dark beam with sender and receiver in a single housingFR 50 RV:incl. one prismrange 5-100mweight 0,67 kgFR 100 RV:incl. four prismrange 50-100mweight 0,98 kg
Technical data
4 mA
Connection to the loop 3000 via IOM 3311
10,2 to 30 V DC
Three sensitivities: 25%, 35% and 50%
Detection of light and dark smoke
18. Infrared-Beam detectors and accessories 140
Properties:
Description:Infrared beam detector with automatic adjustment by an infrared sender and receiver unit including a reflection prism. The Fireray 5000 requires 1 prism for the range of 8-50 m and 4 prism for the range of 50-100 m
Technical data
8 to 12 mA
For the distance range of 100m three additional prism (Art.-no. 32471) are required in addition to the basic package.
14 to 28 V DC
Connection to the loop 3000 via IOM 3311
Adjustment of the sensitivity with thresholdd values in the range of 10% to 60%
Connection to the loop 3000 via IOM 3311
Adjustment of the delay times individually for fire and fault from 2 to 30 seconds
Automatic compensation for moving buildings
Infrared Beam detector Art.-no. 32476 - Type FR 5000
IP 54Grey / black
48 to 52 mA-10°C to 55°C
Adjustment of the system to the local conditions
Automatic adjustment of the beam detector can be activated or deactivated
LCD display with optical menue navigation in the display for an easy operation
Modular design
Dimensions (H x W x D)1,67 kg135mm x 134 mm x 134mm
Weight
rel. 93% (non-condensing)
Operation voltageQuiescent currentAlarm / Operation currentAmbient temperature
Art.-no. 32471 - Type EP 01
HumidityProtection classColour housing
Extension prism for FR 50 RV, FR 100 RV, FR 5000
Standards DIN EN 54-12
19. Flame detectors 141
Properties:
Hazardous area proof: EX: 538 Ex II 2 GD, ATEX 132195, FM 3260
Scope of supply: detector, magnet and mounting bracket
Sensitivity
Humidity max. 95% - (for short time up to 100% condensing air)
550 mA
N-Heptane: 0,1 m² in 15 m distance: < 15 seconds
Recommended cable: shielded cable with 0,5 mm² up to 2,5 mm²
18 V up to 30 V DC
EX
Protection classColour housing
Operation voltageAlarm / operation currentInterfacesPotential free relays
Ambient temperature
Material housingDimensions (H x W x D)
538 Ex II 2 GD, ATEX 132195, FM 3260
IP 66RedCooperfree Aluminium or stainless steel 316119 mm x 122 mm x 246 mm
Modular housing design
Technical data
Fast response time (40 ms)
Visual range angle 90°
Multicolour LED for status display of operation, fault and alarm
Mounting bracket vibration-free according to MIL
Automatic, optical self test
Microprocessor controlled heated optics
Description:Infrared flame detector for a secure detection of e.g. hydrocarbon fires in industrial applications like turbine, petrochemistry, automotive industry, projects with high pollution
Event memory
Maintenance mode via magnet
Standards DIN EN 54-10; Cl. 1-3
Infrared Flame detector Art.-no. 32075 - Type X9800
Methan: 30 inch flame in 10,5 5 distance: < 10 seconds-40°C to +75°C
RS-485 Modbus output, 4-20 mAAlarm, Fault, additional alarm
Reliable detection even in case of simultaneous faults
Detection of a N-Heptane fire of 0,1 m² size at a distance of up to 15 m
19. Flame detectors 142
Properties:
Technical data
Including service interface and event memoryIncluding mounting base and mounting bracket
General remarks
Max. cable length
Standards
Colour housingMaterial housing
Operation voltageQuiescent currentAlarm / operation currentAmbient temperatureProtection classCovering range
Approx. 0,25 mA
Covering area
Up to 8 FMX 5000 UV-flame detectors can be connected to one
WeightDimensions (H x Ø)
700 m with 0,5 mm² cable
DIN EN 54-10; Cl. 1
Red / silverAluminium die casting0,8 kg
7,6 V up to 30 V DC
Covering range up to 50 m; Covering area up to 676 m²
Parametrization for different applications via DIP switch
Monitoring of the optical window against pollution (UV-range)
Function control and analysis of the measured values with microcontroller;
faults can be displayed at the detector or at a separate line
Multicolour LED for alarm (red) and fault (yellow)
Recomended cable: IY (St) Y 2x2x0,8 mm²
The ultraviolet light of the optical spectrum is analysed
Robust housing suitable for the application in rough industrial environment
High reliability against false alarms, like e.g. lightning or strong solar irradiation
High sensitivity
Description:Conventional ultraviolet flame detector for the detection of open flames (e.g. fire with gas, oil products, plastic, wood, metal)
Ultraviolet Flame detector Art.-no. 32272 - Type FMX 5000 UV
conventional interface CP CLI or to one conventional module TCM 3000
up to 50 mup to 676 m²
Approx. 15 mA-20°C to +80°CIP 67
100 mm x 50 mm
20. Ex-proof components and accessories 143
Properties:
Quiescent currentAmbient temperature
Power on time
HumidityProtection class
Specially for areas where a fire involves high temperatures in an early stage of fire
Integrated professional smoke detection and temperature measurement
< 20 sec.
Optional flashing LED for the indication of the normal operation status
Self learning modes for the ambient conditions
For the use in explosive areas the Ex-barrier EX-B1 (Art.-no. 31174) has to be used
Colour housingMaterial
Detector base for this EX detector is Art.-no. 32247
Operation voltage 14 to 28 V DC
Fast commissioning
Sensor protection and measurement chamber design reducing the entry of dust and false alarms
Sensor with high reliability and reduction of false alarms
Algorithm for separation of temporarily abnormal values
EX Multi sensor detector optical heat, conventional systems Art.-no. 32244 - Type MSM Ex Orbis IS
WhitePolycarbonate
-40°C up to +60°Cmax. 98%
High sensitivity for fast burning flaming fires (including liquid fires)
Resistant against pressure and wind
Description:Optical and thermal multi sensor detector for conventional systems in Ex-proof designDimensions (H x Ø): 60 mm (with base) x 100 mmWeight: Approx. 0,1 kgStandard: DIN EN 54-7; Cl. A1
ATEX BAS06, ATEX 0007X
EX Heat detector, conventional system Art.-no. 32245 - Type WM Ex 50 Orbis IS
Description:Heat detector for conventional systems in Ex-proof designDimensions (H x Ø): 50 mm (with base) x 100 mmWeight: Approx. 0,085 kgStandard: DIN EN 54-5; Cl. A1
Rate of rise detector- triggering temperature 50°CTechnical data for MSM Ex Orbis IS and WM Ex 50 Orbis IS
85 µA / 24 V
IP 23 D
20. Ex-proof components and accessories 144
Properties:
Dimensions (H x Ø) WeightPower on time
Operation voltageQuiescent currentAmbient temperatureHumidityProtection classColour housingMaterial
Good performance with white and black smoke
ATEX
EX detector base for Orbis detectors, conventional systems Art.-no. 32247 - Type MS Ex Orbis IS
50 mm (with base) x 100 mm0,105 kg< 20 sec.BAS06, ATEX 0007X
Standards DIN EN 54-7; Cl. A1
IP 23 D
Detector base for this EX detector is Art.-no. 32247
14 to 28 V DC
Self learning modes for the ambient conditions
Extra confirmation for smoke before alarm activation
For the use in explosive areas the Ex-barrier EX-B1 (Art.-no. 31174) has to be used.
Fast commissioning
Description:Optical smoke detector for conventional systems in Ex-proof design
85 µA / 24 V
Technical data
Sensor protection and measurement chamber design reducing the entry of parts and false alarms
Sensor with high reliability and reduction of false alarms
Algorithm for separation of temporarily abnormal values
Optional flashing LED for the indication of the normal operation status
Multisensor for early smoke detection and fast burning flaming fires
Technical data
Material Polycarbonate
EX optical detector, conventional systems Art.-no. 32246 - Type OM Ex Orbis IS
WhitePolycarbonate
-40°C up to +60°Cmax. 98%
Resistant against pressure and wind
Description:Detector base for all Orbis detectors in Ex-proof design for a fast and easy installation
ATEX BAS06, ATEX 0007X
Dimensions (H x Ø) 23 mm x 100 mmWeight 0,005 kg
Colour White
20. Ex-proof components and accessories 145
Properties:
Properties:
Ambient temperatureColour housingMaterialDimensions (H x W x D)
Technical data
-10°C up to +60°C
93mm x 20mm x 110mm
Top hat rail mounting
6 mA
Reverse voltage protection
GreenABS
Quiescent current
Description:EX-barrier for EX-detectors of the series Orbis for 1 EX-detector zone
EX-barrier for EX-detectors, conventional systems Art.-no. 31174 - Type Ex-B1
Weight 0,09 kg
Housing for modules Art.-no. 30218 - Type M 1
Description:Housing for Ex-barriers, protocol interfaces, overload protection components and modules for top hat rail mounting
Technical data
Reverse voltage protectionTop hat rail mounting
Protection class IP 65Colour housing GreyMaterial ABSDimensions (H x W x D) 220 mm x 125 mm x 162 mm
20. Ex-proof components and accessories 146
Properties:
Properties:
Operation voltageVolumeAmbient temperatureHumidityProtection classColour housingMaterial
Art.-no. 32307 - Type Z 728
Dimensions (H x W X D)WeightATEX-No.
EX-barrier for EX-multiple tone sounder, conventional system
Technical data
135mm x 130mm x 130mm0,75 kg04ATEX2301X, II1GEExiaIICT4
Ex zone 0, 1 or 2; Categories 1G, 2G or 3G, Temperature class T4
Technical data
Mounting option for 35 mm DIN rail according to DIN EN 50022Self-opening clamps, max wire dimension 2 x 2,5 mm²
Categories 1G, 2G and 3G (zones 0,1 and 2)
24 V DC
Operation in hazardous areas from 10 to 28 V DC supply via a Zener barrier or galvanic isolation
Shock-resistant housing
Suitable for outdoor use
Description:EX-barrier for the EX Multiple tone sounder IS-A105N (Art.-no. 32306)
Operation voltage 24 V DC
Max. 112 dB +/- 3 dB
IP 65
Standards DIN EN 50020The EX sounder operates only directly at the signal line outputs of the General remarks
detect 3004 and detect 3016 and at the SC8-card (Art.-no. 30118). Within an ATEX-area the Zenerbarrier Z728 (Art.-no. 32307) is required.
Ambient temperature -20°C up to +60°C
Incl. DIN tone = 106 dB (A) at 1 m+/- 3 dB (DIN tone 9: 1200/500 Hz @ 1 Hz)
32 different alarm sounds (adjustable via DIP-switch)
Up to 3 tones can be activated externally to realize different signals
Sound pressure level reduction with potentiometer by up to 15 dB (A)
Flame red, similiar to RAL 3000ABS, self-extinguishing similar UL 94 VO
-40°C up to +60°C90% at +50°C
Description:EX Multiple tone sounder for conventional systems in Ex-proof design for hazardous explosive areas
EX Multiple tone sounder, conventional systems Art.-no. 32306 - Type IS-A 105N
ATEX-No. BAS01ATEX7005X
Colour housing GreenMaterial ABS
20. Ex-proof components and accessories 147
Properties:
Properties:
Operation voltageAmbient temperatureProtection classColour housingMaterialDimensions (H x W x D)Weight
Technical data
-20°C up to +60°C
ABS
Scope of supply: Manual Call point, 2 screws, 2 wall anchors, 1 blind plug (M20 x 1,5)
12 to 28 V DC
Operation current: nominal current = 0,1 A; Short circuit current = 4,5 A
Connecting terminal: 0,08-2,5 mm²
Cable entry: 2 x M20 x 1,5 (Ø 6-12 mm)
Type of protection: II2G Ex emb IIC T6, II2D Ex tD A21 IP6X T80°C
For explosive areas Group II, category 2GD (Zones 1,2,21&22)
No ex-barrier required
Dust and water proof housing with IP 66
Thin colourless front glass easy to replace
Description:EX Manual call point for conventional systems in Ex-proof design for hazardous areas where gas an dust can cause an explosive atmosphere
EX Manual call point, conventional systems Art.-no. 31170 - Type HFM Ex DC21 R
145mm x 135mm x 71mm0,5 kg
IP 66Red
ATEX BAS02, ATEX 1729
EX-beacon red Art.-no. 31222 - Type BE 24 R Eex
EX-beacon yellow Art.-no. 31223 - Type BE 24 Y Eex
Description:Red (Art.-no. 31222) or yellow (Art.-no. 31223) Beacon for conventional systems in Ex-proof design for hazardous areas
Technical data
Yellow aluminium housing and red (Art.-no. 31222) or yellow (Art.-no. 31223) calotte
High light performance
Stainless steel protection for the calotteFlash energy: 15 Joule
Operation voltage 24 V DCAlarm / operation current 1,0 AAmbient temperature -20°C to +40°CColour housing YellowMaterial AluminiumDimensions (H x Ø) 243 mm x 110 mmWeight 2,1 kgATEX II 2G Eex de IIC T6
red version
21. Linear heat detectors and accessories 148
Properties:
Properties:
Weigth 0,37 kg
Grey (similar to RAL 7035)105 mm x 105 mm x 65 mmDimensions (H x W x D)
-25°C to 50°C
Description:Linear heat sensor cable detector for the earliest detection of fire or overheating in critical environments
Test key for simultation, alarm, fault and LED test
Connection to the loop 3000 via IOM 3311
Technical data
Application e.g.: garages, tunnels, parking houses, escalator, conveyors, cable ducts,
cold store, high voltage plants, recycling plants etc.
For the connection of up to 300 m sensor cable
Linear heat cable detector Art.-no. 32315 - Type LWM 1
IP 65
Suitable for the use in Ex zones (Zone 1 and Zone 2; Zone 21 and Zone 22)
10 to 30 V DC
Adjustment of the sensitivity of the linear heat cable detector via 16 stage DIP-switch
with free adjustment of fiexed and rate of rise temperature
Three potential free relays contacts for the connection to the fire control panel
via IOM 3311 module, 2 alarm relays, 1 fault relay
Monitoring of wire break and short circuit
Connection of cables being resistant against mechanical, chemical and biological influences
Ambient temperatureProtection classColour housing
Suitable for detection in classes A1, A2, B and C
Operation voltageQuiescent currentPotential free relays
28 mA (at 24 V)2 x 30 V / 1 A DC
Technical data
Suitable for cables up to 6 mmPacking unit: 100 pieces
Fastening clamp Art.-no. 31620 - Type SK-LS
Description:Fastening clamp for an easy fast mounting of the sensor cable
21. Linear heat detectors and accessories 149
Properties:
Properties:
Properties:
Description:Linear heat sensor cable for the connection to the LWM1 linear heat cable detector for the use in humid conditions and non aggressive atmosphere
Linear heat cable LWM1, blue Art.-no. 32316 - Type SKB
Technical data
Tensile strength 1000 N
Not for outdoor use; limited resistanc against UV-light
3,15 mmTensile strength 100 N
Technical data
Sensor cable with nylon cover and steel netting mesh
Diameter 5,8 mm
Suitable for the outdoor use
UV-resistant
Linear heat cable LWM1, black with steel netting mesh Art.-no. 32318 - Type SKSS
Description:Linear heat sensor cable with nylon cover and steel nettingmesh for the connection to the LWM1 linear heat cable detector for the use in ambients with acids and alkalis and in strong mechanical conditions resistant against biological and chemical influences
Tensile strength 100 N +
Suitable for the outdoor use
UV-resistant
Diameter
Technical data
Sensorcable with nylon cover
Diameter 4,8 mm
Linear heat cable LWM1, black Art.-no. 32317 - Type SKS
Description:Linear heat sensor cable with nylon cover for the connection to the LWM1 linear heat cable detector for the use in ambients with acids and alkalis
21. Linear heat detectors and accessories 150
Properties:
Properties:
Protection classColour housing Dimensions (H x W x D)
Operation voltageQuiescent currentPotential free relays
Linear heat cable detector Art.-no. 30503 - Type SKM-03.01
IP 65
Monitoring of wire break and short circuit
24 V DC
External 24 V supply required
Potential free alarm and fault output
Connection to the loop3000 via IOM 3311
Technical data
Application e.g.: garages, tunnels, parking houses, escalator, conveyors, cable ducts,
2 x 30 V / 1 A DC-25°C to 50°C
Description:Linear heat sensor cable detector for the earliest detection of fire or overheating in critical environments
cold store, high voltage plants, recycling plants etc.
For the connection of up to 300 m sensor cable
Connection of cables being resistant against mechanical, chemical and biological influences
Ambient temperature
28 mA
Weigth 0,27 kg
Grey / White110 mm x 110 mm x 66 mm
Linear heat cable SKM KRT red Art.-no. 30980 - Type SKM KRT
Linear heat cable SKM KRT black Art.-no. 30981 - Type KSW
Description:Linear heat sensor cable for the connection to the SKM-03 linear heat cable detector for the use in normal conditions and non aggressive atmosphere
Diameter: 3,25 mmTensile strength: < 200 N
Description:Linear heat sensor cable for the connection to the SKM-03 linear heat cable detector for the use in aggressive conditions
Diameter: 4,0 mmTensile strength: <200 N
Resistant against acids and alkalisNylon Cover
22. Smoke Aspiration Systems and accessories 151
Properties:
General remarks Software for the design of projects available on request
HSSD-2 smoke aspiration detector with display Art.-no. 31114 - Type HSSD-2 M
-10°C to +60°CMax. 90 % (non-condensing)
5 potential free relays for info, pre-alarm, fire 1, fire 2, fault
via intelligent teach in modes
Intelligent laser sensor technology with consideration of ambient conditions for fast detection
Laser dust discrimination and elimination system
Automatic day-/night mode for the adjustment from and to temporally different ambient conditions
Integrated fast learn for the automatic configuration of the system
Technical data
450 mA at 24 V DC at fan speed 8
in difficult environments
Integrated potential free relays outputs for alarm and fault
Special integrated technology for the elimination of influences by pollution (dust etc.)
Integrated dust filter
4 sampling pipes, up to 250m maxium length:
- Total pipe lenght 200m with up to 100 sampling holes
0,0003 µm to 10 µm
Functions completely integrated via loop3000 protocol
21,6 - 26,4 V DC
Highest reliability by optimal adjustment of the alarm threshold via intelligent algorithm
for the fire detection
Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3,
External voltage supply required
- Total pipe lenght 250m with up to 80 sampling holes
1 recirculation pipe for the compensation of the intrasystem pressure gradient
Integrated RS485-interface for the network of up to 127 participants
Description:Intelligent active Laser-smoke aspiration detector for ealiest detection of fires in sensitive and extreme contaminated e.g. EDP-control room, hospital operating room, storage area, incineration plant etc.
Integrated LC-Display with 2x16 characters, arrow keys control panel
Integrated automatic adjustment of the detector to the ambient conditions
IP 503/4"
Operation voltageCurrent supplyOutputsParticle sensitivity rangeAmbient temperature
Protection classPipe diameter
Humidity
Light greyCast aluminium/ABS
5,2 kg
MaterialDimensions (H x W x D)
Colour housing
S295054 and S208123System approval
372 mm x 427 mm x 95 mm
DIN EN 54-20Standards
G203024WeightVdS approval
22. Smoke Aspiration Systems and accessories 152
Properties:
Properties:
Properties:
Properties:
HSSD-2 command unit with power supply unit
MaterialDimensions (H x W x D) Weight 5,2 kg
G203024VdS approval
Protection classColour housing
DIN EN 54-20StandardsGeneral remarks Software for the design of projects available on request
Cast aluminium/ABS372 mm x 427 mm x 95 mm
System approval S295054 and S208123
IP 50Light grey
-10°C to +60°C
Description:Command module: Ability to setup, change and view any smoke aspiration system on the network
External voltage supply required
Integrated RS485-interface for the network of up to 127 participants
250 mA at 24 V DC
Max. 90 % (non-condensing)Humidity
HSSD-2 command unit Art.-no. 31117 - Type HSSD-2 S
Technical data
Integrated LC-Display with 2x16 characters, arrow keys control panel
Integrated potential free relays outputs for alarm and fault
21,6 - 26,4 V DC
Ambient temperature
Technical data
230V AC
HSSD-2 smoke aspiration detector without display Art.-no. 31867 - Type HSSD-2 MOD
Similar to HSSD-2 but with command module
Operation voltageCurrent supply
Similar to HSSD-2 but without display
Art.-no. 31116 - Type HSSD-2 SNTechnical data
Similar to HSSD-2 S but with power supply unitInternal uninterruptable 24V power supply and battery charging
HSSD-2 smoke aspiration detector with display and command unit Art.-no. 31115 - Type HSSD-2 MS
Command module: Ability to setup, change and view any smoke aspiration system on the network
Technical data
Operation voltage
22. Smoke Aspiration Systems and accessories 153
Properties:
Accessories Relays-board (Art.-no. 32236) with 5 potential free relays outputs
Micra 100 with mounting base Art.-no. 31476 - Type Micra 100
-10°C to +60°CMax. 90 % (non-condensing)
Measurement range (%Obs/m) 0,03% to 25%
via intelligent teach in modes
Intelligent laser sensor technology with consideration of ambient conditions for fast detection
Laser dust discrimination and elimination system
Technical data
400 mA at 24 V DC
in difficult environments
External voltage supply required
Special integrated technology for the elimination of influences by pollution (dust etc.)
Integrated dust filter
2 sampling pipes, up to 100 m maxium length:
- Total pipe lenght 100 m with up to 25 sampling holes
Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3,
Functions completely integrated via loop3000 protocol
- Total pipe lenght 2 x 50 m with up to 25 sampling holes
1 recirculation pipe for the compensation of the intrasystem pressure gradient
Integrated RS485-interface for the network of up to 127 participants
Automatic day-/night mode for the adjustment from and to temporally different ambient conditions
Integrated fast learn for the automatic configuration of the system
Description:Intelligent active Laser-smoke aspiration detector for ealiest detection of fires in sensitive and extreme contaminated environments e.g. EDP-control room, hospital operating room, storage area, incineration plant etc.
Integrated automatic adjustment of the detector to the ambient conditions
General remarks Software for the design of projects available on request
0,0003 µm to 10 µm
Including mounting base and connection flange for the recirculation pipe21,6 - 26,4 V DC
Highest reliability by optimal adjustment of the alarm threshold via intelligent algorithm
for the fire detection
IP 503/4"
Operation voltageCurrent supplyMeasurement rangeParticle sensitivity rangeAmbient temperature
Protection classPipe diameter
Humidity
DIN EN 54-20StandardsWeight
Light greyCast aluminium/ABS
3,7 kg
MaterialDimensions (H x W x D)
Colour housing
200 mm x 293 mm x 83 mm
22. Smoke Aspiration Systems and accessories 154
Properties:
DIN EN 54-20Standards
WeightVdS approval G207078System approval S295054 and S208123
Light greyCast aluminium/ABS
1,01 kg
MaterialDimensions (H x W x D)
Colour housing
175 mm x 135 mm x 83 mm
IP 503/4"
Operation voltageCurrent supplyMeasurement rangeParticle sensitivity rangeAmbient temperature
Protection classPipe diameter
Humidity
Description:Intelligent active Laser-smoke aspiration detector for ealiest detection of fires in sensitive and extreme contaminated environments e.g. EDP-control room, hospital operating room, storage area, incineration plant etc.
Integrated automatic adjustment of the detector to the ambient conditions
General remarks Software for the design of projects available on request
0,0003 µm to 10 µm
Including mounting base and connection flange for the recirculation pipe21,6 - 26,4 V DC
Highest reliability by optimal adjustment of the alarm threshold via intelligent algorithm
for the fire detection
1 recirculation pipe for the compensation of the intrasystem pressure gradient
Integrated RS485-interface for the network of up to 127 participants
Automatic day-/night mode for the adjustment from and to temporally different ambient conditions
Integrated fast learn for the automatic configuration of the system
Technical data
250 mA at 24 V DC
in difficult environments
External voltage supply required
Special integrated technology for the elimination of influences by pollution (dust etc.)
Integrated dust filter
2 sampling pipes, up to 50 m maxium length:
- Total pipe lenght 50 m with up to 10 sampling holes (25 m at highest sensitivity)
Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3,
Functions completely integrated via loop3000 protocol
Accessories Relays-board (Art.-no. 32236) with 5 potential free relays outputs
Micra 25 with mounting base Art.-no. 31118 - Type Micra 25
-10°C to +60°CMax. 90 % (non-condensing)
Measurement range (%Obs/m) 0,03% to 25%
via intelligent teach in modes
Intelligent laser sensor technology with consideration of ambient conditions for fast detection
Laser dust discrimination and elimination system
22. Smoke Aspiration Systems and accessories 155
Properties:
Properties:
Properties:
Ambient temperatureOutputs
Integrated relays card with 5 potential free relays outputs, 4 outputs for alarm, 1 output for fault
Technical data
5 relays contacts 0,4 A / 24 V
Micra 25 with mounting base and relays card Art.-no. 32313 - Type Micra 25 REC
Technical data
Similar to Micra 100 but with relays card
- Indication for the battery capacity
Mounting as plug in module on the main board
5 potential free relays for the connection to a fire control panel
(2 x alarm, 1 x pre-alarm, 1 x info-alarm, 1 x fault)
Compatible to all Micra smoke aspiration detectors
-10°C to +60°C
Relay board Art.-no. 32236 - Type REC
3 free Inputs for the programming of functions like e.g.
- Reset of the detector,
Description:Relays board for the connection of the smoke aspiration detector to a fire control panel
Technical data
- Reduction of the detector sensitivity,
Similar to Micra 25 but with relays cardIntegrated relays card with 5 potential free relays outputs, 4 outputs for alarm, 1 output for fault
Dimensions (H x W x D) 68 mm x 100 mm x 25 mm
Micra 100 with mounting base and relays card Art.-no. 32330 - Type Micra 100 REC
22. Smoke Aspiration Systems and accessories 156
Properties:
Pipe diameter
Air filter replacement for HSSD-2 Art.-no. 31255 - Type ELF HSSD-2
Air filter replacement for Micra
Material
Description:Air filter replacement for all smoke apiration detectors of series HSSD-2
Technical data
Compatible to HSSD-2 and Micra smoke aspiration detectors
Integrated self regulating heating element 60-200W
230V 60-200W
Sheet steel, zinc-plated
Protected ceramic terminal block and cable entries
-10°C to +60°C
Air heater box Art.-no. 32350 - Type LEB
264 mm x 140 mm x 160 mm3/4"
4 rearward and 2 below placed pipe holes
Description:Air heater box for the preheating of the aspirated air of the smoke aspiration detector. The preheating ensures the operation of the smoke aspiration detector in between the admissible values.Further the air heater box can be used to avoid humidity or condensation influences at the detection in case of high humidity or low temperatures.
Ambient temperatureHeaterDimensions (H x W x D)
Recommended use with HSSD-2Temperature control of the aspirated aistream available upon request
General remarks
Description:Air filter replacement for all smoke aspiration detectors of series Micra
Art.-no. 31256 - Type ELF Micra
Description:Air filter replacement for all smoke aspiration detectors of series HSSD-1
Air filter replacement for HSSD-1 Art.-no. 31253 - Type ELF HSSD-1
22. Smoke Aspiration Systems and accessories 157
Bend 90° Art.-no. 31136 - Type B90
3/4" / 27 mm x 41mm
Description:Bend 90° for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Dimensions ( Ø x L) 3/4" / 27 mm x 144 mm
Art.-no. 31138 - Type VM
Description:Connection sleeve for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Description:Angle 45° for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Dimensions ( Ø x L) 3/4" / 27 mm x 62 mm
Dimensions ( Ø x L x D) 3/4" / 27 mm x 65 mm x 50
Dimensions ( Ø x L)
Connection sleeve
T-piece Art.-no. 31140 - Type TA
Description:T-piece for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Pipe Art.-no. 31133 - Type AR
Description:Non-halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Dimensions ( Ø x L) 3/4" / 27 mm x 3000 mm
Angle 45° Art.-no. 31135 - Type W45
For more technical details please see next page.
22. Smoke Aspiration Systems and accessories 158
Properties:
Description:End cap for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Dimensions ( Ø x L) 3/4" / 27 mm x 30 mm
Dimensions ( Ø x L) 3/4" / 27 mm x 53 mm
End cap Art.-no. 31143 - Type EK
Technical data for 3/4" pipe system (page 157 and 158)
Low coefficient of thermal expansion extension due to the special ABS version
Reducer adapter Art.-no. 31150 - Type RA
Description:Reducer for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range to suit 25mm DIN nominal size
Special adhesive (Art.-no. 31147)
High resistance against chemicals and aggressive ambient conditions
Fastening clip (Art.no. 31145) for pipeAccessories
Material ABS, non-halogen
Pipe diameter 3/4"Colour Red
Screw joint Art.-no. 31141 - Type VG
ABS-detergent (Art.-no. 31148)
Resistant against strong mechanical loads
Description:Screw joint for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range for creation of connection holes for the cleaning and blowing out of the installed pipe system
Dimensions ( Ø x L) 3/4" / 27 mm x 217mm3/4" to 25mm adaptation
High flexibility and bending properties
No electrostatic chargingThe pipe system has to be securely fixed at all junctions.
General remarks
All sampling holes have to be drilled in accordance to the guidelinesof the systems vendor and have to be marked with warning labels.
22. Smoke Aspiration Systems and accessories 159
Properties:
Properties:
Properties:
Colour GreySize M8
Suspension 60mm (Art-no. 31146)Flange nut (Art.-no. 31960)
Accessories
Description:Flange nut for the mounting clip for pipes onto the suspension
Flange nut for mounting clipAccessories Flange nut (Art.-no. 31960)Dimensions ( L) Max. 115 mm
Technical data
Enables the direct assembly of the mounting clip for pipes onto the suspension threaded pin
Art.-no. 31960 - Type FM
Mounting clip for pipe Art.-no. 31145 - Type BC
ABS, non-halogen
Resistant against strong mechanical loads
Description:Mounting clip for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Dimensions (H x W x D) 55 mm x 45 mm x 20 mm
Technical data
For an easy fixation of pipes
Low coefficient of thermal expansion extension due to the special ABS version
Red
High resistance against chemicals and aggressive ambient conditions
3/4" Pipe diameterColourMaterial
Colour GreyMaterial Steel
Distance
Technical data
For the adjustment of uneven surfaces and suspension of the pipe
up to 60 mm
Suspension for mounting clip Art.-no. 31146 - Type AB
Description:Suspension for the mounting clip for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range for the fixation of mounting clips on uneven surfaces.
Material SteelDimensions (H x W x D) 20 mm x 10 mm x 2 mm
22. Smoke Aspiration Systems and accessories 160
Properties:
End piece for the connection of a 10mm hose pipe
T-hose pipe-adapter Art.-no. 31153 - Type TKA
Dimensions ( Ø x L x T) 3/4" / 27 mm x 41 mm x 58 mm
End adapter for hose pipe Art.-no. 31154 - Type EKA
Description:End-adapter for the connection of a hose pipe to the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range.The aspirating holes can be placed 8m away with the hose pipe.
Description:Adapter for the connection of a hose pipe to the non halogen pipe system for all smoke aspiration detectors from the series HSSD-2 and Micra range.The aspirating holes can be placed 8m away with the hose pipe.
ABS-detergent (Art.-no. 31148)
High resistance against chemicals and aggressive ambient conditions
Special adhesive (Art.-no. 31147) Accessories
Material ABS, non-halogen
Pipe diameter
T-piece for connection of 10mm hose pipe
Dimensions ( Ø x L) 3/4" / 27 mm x 55 mm
3/4"Colour Red, black
Technical data for TKA and EKA
Low coefficient of thermal expansion extension due to the special ABS version
Resistant against strong mechanical loads
22. Smoke Aspiration Systems and accessories 161
Properties:
Dimensions ( Ø ) 10 mm
ABS-detergent (Art.-no. 31148)Special adhesive (Art.-no. 31147) Accessories
ABS, non-halogen
Resistant against strong mechanical loads
Description:Hose pipe for the out of line place of an aspirating hole for the non halogen pipe system for all smoke aspiration detectors from the series HSSD-2 and Micra range.The aspirating holes can be placed 8m away with the hose pipe.
Plug in piece Art.-no. 31613 - Type SK
Description:Plug in piece for the connection of the 10 mm hose pipe attached to the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Dimensions ( Ø x L) 10 mm x 20 mm
10 mm
Hose pipe, red Art.-no. 31151 - Type KR
Colour White
White
Technical data for KR, KW and SK
Low coefficient of thermal expansion extension due to the special ABS version
High flexibility and bending properties
Pipe diameter
Colour
Material
Colour
Hose pipe, white Art.-no. 31152 - Type KW
Description:Hose pipe for the out of line place of an aspirating hole for the non halogen pipe system for all smoke aspiration detectors from the series HSSD-2 and Micra range.The aspirating holes can be placed 8m away with the hose pipe.
Red
High resistance against chemicals and aggressive ambient conditions
22. Smoke Aspiration Systems and accessories 162
End piece for hose pipe Art.-no. 31156 - Type FK
ABS, non-halogen
Description:End piece with clamp fastening for connection to the 10 mm hose pipe attached to the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Dimensions ( Ø x L) 65 mm x 40 mm
33 mm x 73 mmTechnical data for FK and KK
Smoke generator Art.-no. 31539 - Type AX 18
Description:Pyroctechnical smoke generator for the funtion test for all smoke aspiration detectors from the series HSSD-2 and Micra range
Including 5 smoke cartridgesSmoking time per cartridge: approx. 4 minSmoke volume per cartridge: approx. 17 m³
Smoke pen Art.-no. 32334 - Type RS
Description:Smoke pen for the test and function control suitable for all smoke aspiration detectors of the series HSSD-2 and Micra
Including 6 smoke cartridges
Warning decal for sampling holes, 100pcs Art.-no. 31149 - Type WA
Description:Warning decal for the marking of the samplig holes for the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
Packing unit 100 pieces
White10mm
Accessories Special adhesive (Art.-no. 31147)
Pipe diameterColourMaterial
ABS-detergent (Art.-no. 31148)
Dimensions ( Ø x L)
End piece for hose pipe Art.-no. 31155 - Type KK
Description:End piece with clamp fastening for connection to the 10 mm hose pipe attached to the non halogen pipe for all smoke aspiration detectors from the series HSSD-2 and Micra range
23. Voice Evacuation System - Sound detect 163
Approx. 4,2 kg
Networking via redundant optical cable ring
Networking via redundant optical cable ring
Description:PCT 1244 L system control unit for the Pantura EVAC-System for the management of up to 12 paging stations and 4 audio-inputs and 4 audio outputs
Integrated audio matrix with 12 connections for paging stations, 4 audio inputs for external auxiliaries and 4 audio outputs for the processing in the speaker matrix
Output level Line-OutWeight
Optical (50 or 62,5 µm): ca. 2000 m
Description:PCT 1244 LFO system control unit for the Pantura EVAC-system for the management of up to 12 paging stations and 4 audio-inputs and 4 audio-outputs with an integrated fibre optic interface for an optional redundant Network (Loop) with a second system controller
Integrated audio matrix with 12 connections for paging stations, 4 audio inputs for external auxiliaries
and 4 audio outputs for the processing in the speaker matrix
System controller Pantura 622 L Art.-no. 32407 - Type SD-PCT 622 L
Description:PCT 622 L system control unit for the Pantura EVAC-system for the management of up to 6 paging stations and 2 audio-inputs and 2 audio-outputs
Weight Approx. 4,2 kg
System controller Pantura 1244 LFO, Fibre optic interface for network Art.-no. 32410 - Type SD-PCT 1244 LFO
Output level Line-Out Optical (50 or 62,5 µm): ca. 2000 m
Weight Approx. 3,7 kg
System controller Pantura 1244 L Art.-no. 32409 - Type SD-PCT 1244 L
Description:PCT 622 LFO system control unit for the Pantura EVAC-system for the management of up to 6 paging stations and 2 audio-inputs and 2 audio outputs with an integrated fibre optic interface
Output level Line-Out +6 to +8dBu
Integrated audio matrix with 6 connections for paging stations, 2 audio inputs for external auxiliaries and 2 audio outputs for the processing in the speaker matrix
Integrated audio matrix with 6 connections for paging stations, 2 audio inputs for external auxiliaries
and 2 audio outputs for the processing in the speaker matrix
Output level Line-Out +6 to +8dBuWeight Approx. 3,7 kg
System controller Pantura 622 LFO, Fibre optic interface for network Art.-no. 32408 - Type SD-PCT 622 LFO
For more technical details please see next page.
23. Voice Evacuation System - Sound detect 164
Properties:
Operation voltagePower consumption with unloaded interfacesInput-/ Outputlevel Paging stations
-5°C to +40°C
Material Metal
Mounting 19"-fittingColour housing Silver grey
Permanent monitoring of all audio and control paths, processors, memories, paging stations,
decentralized modules, active error interface and the display for individual error messages
Control and management of up to 30 speaker Matrix SD-PMT 32
Technical data for system controllers Pantura
Intelligent voice management for an optimal routing of the corresponding audio signals
Internal flash memory (128MB) for wave-files for different voice recordings or alarm signals
with a maximum duration of 9 minutes
Scaleable audio memory for voice messages and evacuation signals
Slave clocks supply voltage 12 to 60 V DC
System controller Pantura 622 L
25 to 30 W+6 to +8dBu
Interface connection for the fire control panels of the system detect 3000 via 8 independent and freely
programmable inputs
System controller Pantua 622 LFO, Fibre optic interface for networkSystem controller Pantura 1244 L
System controller Pantura 1244 LFO, Fibre optic interface for network
Position -12dBu: -12 to -8dBu
Remote access via LAN or ISDN
Integrated Ethernet-interfaces
Incl. USB or Parallel Interface for the connection of a printer
Shallow design (1HE) and 19"-fitting
Input level Line-In
Factory provided serial number for addressing in the system
18 to 36 V DC
Position +6dBu: +6 to +8dB
Dimensions (H, W, D) 44,4 mm (1HE) x 483 mm (19") x 240 mm
Control inputsInput voltage
Low: -30 to +5 V DCHigh: +10 to +30 V DC
Amient temperatureHumidity 90%, (non-condensing)
Slave clocks output current Approx. 800 mA
Management of up to 240 speaker lines, 256 paging zones and 120 power amplifiers per controller
Dynamic power management of all amplifier channels
Integrated real time clock for time and calendar functions and system messages
Optional time synchronisation via DCF 77 or GPS signals
Built in master clock for management of different varying slave clocks
User friendly and high performance PC programming software with integrated online-help
for an easy programming of the system via Ethernet interface
Password protected access rights via programming software P-Control
23. Voice Evacuation System - Sound detect 165
Properties:
Max. 30 speaker matrix per system controller
Shallow design (1HE) and 19"-fitting
Intelligent amplifier operation according to power requirement
Permanent monitoring of broken wire, short-cicuit and ground fault of all speaker lines
Impedance measurement by 20kHz pilot tone
Non reactive switch off of short-circuit speaker lines
Mounting 19"-fitting
Weight Approx. 3,85 kg
Colour housing Silver greyMaterial MetalDimensions (H, W, D) 44,4 mm (1HE) x 483 mm (19") x 240 mm
Humidity 90%, non-condensing
Bus load Max. 0,5 ULPower consumption Max. 21 W
Speaker Matrix 100V, 32 speaker lines Art.-no. 32411 - Type SD-PMT 32
-7 to -0,2 V0,2 to 12 V
0,05 to 7 A RMS; 0,07 to 10 A Pk0,05 to 7 A RMS; 0,07 to 10 A Pk
Integrated multichannel unit for the distribution of signals to the speaker lines.
4 simultaneous audio signals will be distributed to 8 speaker lines;
Description:Speaker Matrix for the activating, switching and monitoring of 100 V speakers or speaker lines. 32 individual outputs (100V) are grouped into 4 terminal blocks, which could be connected seperately to amplifiers
0 to 100 V RMS; 0 to 141 V Pk
0 to 550 KOhm
Factory provided serial number for addressing in the system
18 to 36 V DC
Permanent monitoring of all amplifiers/ amplifier signals and automatic adjustment
of the signal routing at amplifier fault
Dedicated spare amplifier in single channel systems
Technical data
2 simultaneous audio signals will be distributed to 16 speaker lines;
1audio signal will be distributed to 32 speaker lines
Entire management and control by the system controler SD-PCT via data bus P-DATA
Integrated emergency switch via external activation of the line relais
Signal distribution matrix (100 V) with 4 independent signal inputs
8 line-relais / 8 signal outputs per signal input allowing 32 signal outputs / speaker lines
-0,15 to 0,25 mA-6 to 6 mA
Min. 1,5 V
0,2 to 2 µs
[UDATA + - UDATA -], RL = 54 Ohm
Slew rate
Operation voltageInput voltage differentialInput current amplifierOutput current conductorMeasurement ground fault resistanceInput voltage LOW UDATA + - UDATA -
Input voltage HIGH UDATA + - UDATA -
Input current -7V < UIn < + 12 V
CL = 50pF per wire to Common, RL = 54 Ohm (Data+ to Data-)
Input current -60V < UIn < + 60 VOutput voltage
23. Voice Evacuation System - Sound detect 166
Dimensions (H x W x D) Approx. 60 mm x 203 mm x 205 mmWeight Approx. 1,85 kg
A change over mode enables the assignement of two seperate functions to each keyCurrent consumption Full load at 9 V = max. 1,8 A; full load at 36 V = 0,5 APower consumption Approx. 18 W
Approx. 60 mm x 298 mm x 205 mmWeight Approx. 2,40 kg
Paging station with 47 buttons, freely configurable, incl. Speaker Art.-no. 32414 - Type SD-PPS 47
Description:The paging station SD-PPS 47 consists of 47 freely configurable keys for the activation/deactivation of speaker lines, zones, switching functions etc.. The keys can be freely assigned and labelled and can be fully illuminated (red, yellow, green) to signal the switching status. One monitored microphone and one speaker are factory-provided for the paging station
Description:The paging station SD-PPS 63 consists of 63 freely configurable keys for the activation/deactivation of speaker lines, zones, switching functions etc.. The keys can be freely assigned and labelled and can be fully illuminated (red, yellow, green) to signal the switching status. One monitored microphone and one speaker are factory-provided for the paging station
Keypad with 63 freely programmable, fully illuminated LED keys (red, yellow, green)
Keypad with 47 freely programmable, fully illuminated LED keys (red, yellow, green)Current consumption Full load at 9 V = max. 2,1 A; full load at 36 V = 0,6 A
Paging station with 63 buttons, freely configurable, incl. Speaker
Power consumption Approx. 22 WDimensions (H x W x D)
Paging station with 31 buttons, freely configurable, incl. Speaker Art.-no. 32413 - Type SD-PPS 31
Description:The paging station SD-PPS 31 consists of 31 freely configurable keys for the activation/deactivation of speaker lines, zones, switching functions etc.. The keys can be freely assigned and labelled and can be fully illuminated (red, yellow, green) to signal the switching status. A change over mode enables the assignement of two seperate functions to each key. One monitored microphone and one speaker are factory-provided for the paging station.
Keypad with 31 freely programmable, fully illuminated LED keys (red, yellow, green)
Dimensions (H x W x D) Approx. 60 mm x 392 mm x 205 mmWeight Approx. 2,95 kg
Current consumption Full load at 9 V = max. 2,3 A; full load at 36 V = 0,6 APower consumption Approx. 22 W
Art.-no. 32415 - Type SD-PPS 63
For more technical details please see next page.
23. Voice Evacuation System - Sound detect 167
Properties:
Paging station with 63 buttons, freely configurable, incl. Speaker Art.-no. 32415 - Type SD-PPS 63
Paging station with 31 buttons, freely configurable, incl. Speaker Art.-no. 32413 - Type SD-PPS 31
Paging station with 47 buttons, freely configurable, incl. Speaker Art.-no. 32414 - Type SD-PPS 47
Colour housingMaterial
THD & Noise (1 dB under Limiter-threshold 100Hz-20kHz) Max. 0,5 %
Microphone:Frequency response (100 Hz-20 kHz)
Min. 70 dBSignal- to-noise ratio (RMS unvalued)
Including elegant microphone
Configuration of all display functions possible
Metal
-3 to 0 dB
Operation voltageAmbient temperatureHumidityConnection
Technical data for paging stations
direct call buttom, group key, control key, alarm start, alarm interruption, play track,
auxiliary input selection, volume control, audio monitor, system status monitoring, priorty change,
special functions and lamp test freely programmable
Grey
-5°C to +40°C
Labelling of each key by removeable key cap and seperate labels
Several key functions e.g. paging area pre selection, call button with or without chime, delete key,
90%, non-condensing
Factory provided serial number for addressing in the system
9 to 36 V DC
Microphone amplifier with integrated limiter
Integrated loudspeaker for monitoring and control
Permanent monitoring of the acoustic microphone and the paging station control
Pa = 950mW) -0,5 to +0,5 dBTHD&Noise (Pa=950mW, RL=80 Ohm) Max. 0,7 %
Load impedance Min. 8 Ohm
Load impedance Min. 150 OhmOutput impedance Max. 100 OhmPower amplifier:Frequency response (100 Hz-20 kHz
and the data communication
Connection of the paging station to the system controller for the microphone signal,
voltage supply, data communication via P-DATA Bus
Nominal output level +6 dButhreshold to clipping limit Min. 20 dBHeadroom Limiter
Connection cable with D-Sub connector 15-poles
Signal- to-noise ratio (RMS unvalued) Min. 80 dBInput level +6 dBu
Output power (THD < 1%, RL = 8 Ohm) Min. 1 W
CMRR input Min. 70 dBInput impedance 2,2 kOhm
23. Voice Evacuation System - Sound detect 168
Properties:
Technical data
Weight Approx. 0,13 kg
90%, non-condensing
6 mA
0 to 0,7 V DC
Dimensions (H x W x D)
5 to 36 V DC
Black
Bus Optocoupler input-module, 8 freely configurable potential free inputs Art.-no. 32555 - Type SD-PDM 80
Description:The bus optocoupler input module SD-PDM 80 comes with 8 freely configurable optocoupler inputs, which can be individually used for different controls (e.g. connection of the fire control panels detect 3004 and detect 3016)
Each optocoupler-input can be individually configurated as voltage input or as
input for a potential free contact
Supply voltage
Bus participant
Wide input voltage range
Current consumption Max. 20 mA
All inputs are protected against reverse polarity by integrated inverse-polarity protection
12 to 36 V DC
Approx. 35 mm x 98 mm x 88 mm
Optocoupler input current (Ue = 5…36V)Input voltage optocoupler HIGHInput voltage optocoupler LOWHumidityConnectionColour housingMaterial ABS
23. Voice Evacuation System - Sound detect 169
Properties:
Approx. 35 mm x 98 mm x 88 mm
HumidityConnection
18 to 36 V DCSupply voltage
Relay switching current
Material
90%, non-condensingBus particpantBlackABS
Relay switching voltage
Weight Approx. 0,16 kg
Current consumption
48 V
Colour housing
6,5 A
UB = 18 V, no load: 33mA
UB = 36 V, all relays operated; 65 mA
Dimensions (H x W x D)
Bus Relay output module, 8 freely configurable relays Art.-no. 32556 - Type SD-PDM 08
UB =18 V, all relays operated: 110 mAUB = 36 V, no load: 35 mA
Description:The bus relay output module SD-PDM 08 provides 8 freely configurable relay contacts for general control tasks
Technical data
Each relay can be individually configured as closed (NO) or open dry contact (NC).
With common power inlet on UEXT each relay can be individually set to normally open contact voltage output (NO) or normally closed contact voltage output (NC)
23. Voice Evacuation System - Sound detect 170
Properties:
Load current (per output)HumidityConnectionColour housing
Supply voltageSupply voltage outputsCurrent consumptionCurrent consumption output driver
Input wiring is possible via potential free contacts
Technical data
Connection of external loads via switching outputs (Lx)
All switching outputs are short-circuit-proof against the positve and the negative wire supply
Material
Combined module, 3 inputs, 6 transistor outputs, freely configurable Art.-no. 32557 - Type SD-PDM 36 S
Isolated voltage supply of the switching outputs and the bus supply
Description:The combined module SD-PDM 36 S comes with 3 freely configurable inputs and 6 freely configurable transistor outputs. It is a module for controlling six DC consumers and for interrogation of three potential free contacts
9 to 25 V DC
or alternatively via (NPN ) transistor output of an op-coupler
12 to 36 V DC
Max. 30 mAOpen load = 24 mA, allowable full load = 2,1 A350 mA90%, non-condensing
ABSBlackBus participant
Dimensions (H x W x D) Approx. 35 mm x 98 mm x 88 mmWeight Approx. 0,13 kg
23. Voice Evacuation System - Sound detect 171
Properties:
Dimensions
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1mCeiling cut-outDispersion angle (-10dB)MountingConnection Plug-in connection
RAL 9010 whiteMetalMaterial200 mm x 65 mm
Description:Ceiling speaker in elegant design with 165mm full range speaker for a high efficiency and excellent sound in all fields of application
64-19.385 Hz
170 mm
Different colours available on request
6/3/1,5 W
Technical data
Spring clamps for a fast, reliable and easy mounting.
Shock resistant housing for the use in difficult environments
Colour housing
Weight 0,875 kg
Ceiling speaker, powder coated metal, one piece, shallow Art.-no. 32392 - Type SD-DL-E 06-165/T
180° (H) / 180° (V)Spring clamps
94,9 dB105,3 dB
UV-resistant colour
23. Voice Evacuation System - Sound detect 172
Properties:
Weight 1,3 kg
Metal ceiling speaker, powder coated material, deep version Art.-no. 32528 - Type SD-DL 06-165/T
180° (H) / 180° (V)Spring clamps
97,9 dB105,7 dB
UV-resistant colour
220 mm x 100 mm
Description:Ceiling speaker in elegant design with 165mm full range speaker for a high efficiency and excellent sound in all fields of application
100-16.000 Hz
-20°C to +80°C
Different colours available on request
6/3/1,5 W
Technical data
Spring clamps for a fast, reliable and easy mounting.
Shock resistant housing for the use in difficult environments
Dimensions
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperatureDispersion angle (-10dB)MountingConnectionColour housingMaterial
Suitable for the installation in a fire dome to avoid the stack effect at suspended ceilings.
No smoke/ fire will be passing above suspended ceiling in case that
the speaker membrane is burned.
Ceiling cut-out 197 mm
Plug-in connectionRAL 9010 whiteMetal
23. Voice Evacuation System - Sound detect 173
Properties:
Material
Equipped with ceramic terminal, thermo fuse and a temperature resistant cable
to ensure an increased safety in case of fire
Including fire dome to avoid the stack effect at suspended ceilings. No smoke/ fire will
Ceiling cut-out 197 mm
Plug-in connectionRAL 9010 white (fire dome - black)Metal
Dimensions speaker
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperatureDispersion angle (-10dB)MountingConnectionColour housing
220 mm x 100 mm
Description:Ceiling speaker in elegant design with 165mm full range speaker for a high efficiency and excellent sound in all fields of application according to British Standard BS 5839 part 8
100-16.000 Hz
-20°C to +80°C
Different colours available on request
6/3/1,5 W
Technical data
Spring clamps for a fast, reliable and easy mounting.
Shock resistant housing for the use in difficult environments
be passing above suspended ceiling in case that the speaker mebrane is burned.
General remarks The fire dome can not be used as built in dome for concrete ceilings.
Ceiling speaker, powder coated metal, deep version, 165 mm speaker incl. fire dome, BS 5839
Art.-no. 32393 - Type SD-DL 06-165/T BS 5839
180° (H) / 180° (V)Spring clamps
97,9 dB105,7 dB
UV-resistant colour
Weight speaker + fire dome 1,6 kgDimensions fire dome 162 mm x 61 mm
23. Voice Evacuation System - Sound detect 174
Properties:
Weight 1,05 kg
smoke/ fire will be passing above suspended ceiling in case that the speaker mebrane is burned.
232 mm x 63 mm
Description:Ceiling speaker in elegant design with 165mm full range speaker for a high efficiency and excellent sound in all fields of application suitable for the installation in a fire dome, built in dome for concrete ceilings or electroacoustical housing
200-16.000 Hz
-20°C to +150 °C
Different colours available on request
6/3/1,5 W
General remarks The fire dome is not included in the delivery.
Ceiling speaker, ball proofed, 165 mm speaker, excl. fire dome Art.-no. 32538 - Type SD-DL-F 06-165/T
180° (H) / 180° (V)Spring clamps
96,9 dB104,7 dB
UV-resistant colour
Colour housing
Technical data
Spring clamps for a fast, reliable and easy mounting.
Certified fire protection class B2 accord. to DIN 4102, part 8 of the building part test
Dimensions
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperatureDispersion angle (-10dB)MountingConnection
and DIN 4102, part 1 of the B2-test for building material
Material
Plug-in connectionRAL 9010 whiteMetal
Shock resistant and ball proof housing (according to DIN 18032 part 3)
for the use in difficult environments
Suitable for the installation in a fire dome to avoid the stack effect at suspended ceilings. No
Ceiling cut-out 200 mm
23. Voice Evacuation System - Sound detect 175
Properties:
Metal
Ceiling cut-out 200 mm
Plug-in connectionRAL 9010 white
Dimensions
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperatureDispersion angle (-10dB)MountingConnection
Material232 mm x 104 mm
Description:Ceiling speaker in elegant design with 165mm full range speaker for a high efficiency and excellent sound in all fields of application suitable for the installation in a fire dome, built in dome for concrete ceilings or electroacoustical housing according to British Standard BS 5839 part 8
200-16.000 Hz
-20°C to +150 °C
Different colours available on request
6/3/1,5 W
Technical data
Spring clamps for a fast, reliable and easy mounting.
Certified fire protection class B2 accord. to DIN 4102, part 8 of the building part test
Weight 1,79 kg
Ceiling speaker, ball proofed, 165 mm speaker, incl. fire dome, BS 5839 Art.-no. 32394 - Type SD-DL-FF 06-165/T BS 5839
180° (H) / 180° (V)Spring clamps
96,9 dB104,7 dB
UV-resistant colour
Colour housing
Equipped with ceramic terminal, thermo fuse and a temperature resistant cable to ensure
an increased safety in case of fire
smoke/ fire will be passing above suspended ceiling in case that the speaker mebrane is burned.
and DIN 4102, part 1 of the B2-test for building material
Shock resistant and ball proof housing (according to DIN 18032 part 3)
for the use in difficult environments
Including fire dome to avoid the stack effect at suspended ceilings. No
23. Voice Evacuation System - Sound detect 176
Properties:
Weight 1,8 kg
smoke/ fire will be passing above suspended ceiling in case that the speaker mebrane is burned.
267 mm x 100 mm
Description:Ceiling speaker in elegant design with 200 mm full range speaker for a high efficiency and excellent sound in all fields of application
100-19.000 Hz
-20°C to +80 °C
Different colours available on request
10/6/3/1,5 W
General remarks The fire dome is not included in the delivery.
Ceiling speaker, powder coated metal, ball proofed, 200 mm speaker, excl. fire dome Art.-no. 32539 - Type SD-DL 10-200/T
178° (H) / 178° (V)Spring clamps
94,5 dB104,5 dB
UV-resistant colour
Colour housing
Technical data
Spring clamps for a fast, reliable and easy mounting.
Certified fire protection class B2 accord. to DIN 4102, part 8 of the building part test
Dimensions
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperatureDispersion angle (-10dB)MountingConnection
and DIN 4102, part 1 of the B2-test for building material
Material
Plug-in connectionRAL 9010 whiteMetal
Shock resistant and ball proof housing (according to DIN 18032 part 3)
for the use in difficult environments
Suitable for the installation in a fire dome to avoid the stack effect at suspended ceilings. No
Ceiling cut-out 238 mm
23. Voice Evacuation System - Sound detect 177
Properties:
Dimensions fire dome 267 mm x 100 mm
Equipped with ceramic terminal, thermo fuse and a temperature resistant cable to ensure
an increased safety in case of fire
Including fire dome to avoid the stack effect at suspended ceilings. No
smoke/ fire will be passing above suspended ceiling in case that the speaker mebrane is burned.
Shock resistant and ball proof housing (according to DIN 18032 part 3)
for the use in difficult environments
Suitable for the installation in a fire dome to avoid the stack effect at suspended ceilings. No
Ceiling cut-out 238 mm
MountingConnection
and DIN 4102, part 1 of the B2-test for building material
Material
Plug-in connectionRAL 9010 whiteMetal
Technical data
Spring clamps for a fast, reliable and easy mounting.
Certified fire protection class B2 accord. to DIN 4102, part 8 of the building part test
Dimensions speaker
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperatureDispersion angle (-10dB)
General remarks The fire dome can not be used as built in dome for concrete ceilings.
Ceiling speaker, powder coated metal, ball proofed, 200 mm speaker, incl. fire dome, BS 5839
Art.-no. 32395 - Type SD-DL 10-200/T BS 5839
178° (H) / 178° (V)Spring clamps
94,5 dB104,5 dB
UV-resistant colour
Colour housing
Weight 2,37 kg
smoke/ fire will be passing above suspended ceiling in case that the speaker mebrane is burned.
267 mm x 100 mm
Description:Ceiling speaker in elegant design with 200 mm full range speaker for a high efficiency and excellent sound in all fields of application suitable for the installation in a fire dome, built in dome for concrete ceilings or electroacoustical housing according to British Standard BS 5839 part 8
100-19.000 Hz
-20°C to +80 °C
Different colours available on request
10/6/3/1,5 W
23. Voice Evacuation System - Sound detect 178
Properties:
Colour housingMaterial
Suitable for the installation in a fire dome to avoid the stack effect at suspended ceilings.
No smoke/ fire will be passing above suspended ceiling in case that
the speaker membrane is burned.
Ceiling cut-out 215 mm
Plug-in connectionRAL 9010 whiteMetal
Ambient temperatureDispersion angle (-10dB)MountingConnection
Description:Ceiling speaker in elegant design with two autonomous speaker and transformators and a supply via two seperated (A/B) lines. The redundant speaker system ensures at a failure of one line the continous sound supply to the evacuation area according to VDE 0833-4. The A and also the B-line is available in any installation position to avoid failure situations.
149-18.896 Hz
-20°C to +150°C
Different colours available on request
6/3/1,5 W
Technical data
Spring clamps for a fast, reliable and easy mounting.
Shock resistant housing for the use in difficult environments
High-quality metal housing, easy to install, with white metal mounting frame
Power
for concrete ceilings.
Ceiling speaker, 2 speaker, AB-wiring Art.-no. 32548 - Type SD-DL-EN 06-100/T
180° (H) / 180° (V)Spring clamps
94,5 dB110,0 dB
UV-resistant colour
and a front cover with fine perforation for high sound transmission
Weight 1,5 kgGeneral remarks The additional available fire dome can not be used as built in dome
245 mm x 65 mmDimensions
Frequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
23. Voice Evacuation System - Sound detect 179
Properties:
smoke/ fire will be passing above suspended ceiling in case that the speaker mebrane is burned.
210 mm x 80 mm
Description:Surface-mounted speaker in elegant design with a high quality 200 mm full range speaker for high efficiency and excellent sound in all fields of application. It can be installed onto walls and ceilings where built-in versions are not possible according to British Standard BS 5839 part 8
200-17.400 Hz
-20°C to +80 °C
Different colours available on request
10/6/3/1,5 W
Technical data
Spring clamps for a fast, reliable and easy mounting.
Weight 1,69 kg
Surface-mounted ceiling speaker, powder-coated metal,200 mm chassis, BS 5839 Art.-no. 32396 - Type SD-DL-A 10-200/T BS 5839
180°Screws
95,9 dB108,7 dB
UV-resistant colour
Colour housing
Dimensions
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1mAmbient temperatureDispersion angle (-10dB)
Material Metal
Mounting
and DIN 4102, part 1 of the B2-test for building material
Equipped with ceramic terminal, thermo fuse and a temperature resistant cable to ensure
an increased safety in case of fire
Shock resistant and ball proof housing (according to DIN 18032 part 3)
for the use in difficult environments
Suitable for the installation in a fire dome to avoid the stack effect at suspended ceilings. No
Certified fire protection class B2 accord. to DIN 4102, part 8 of the building part test
RAL 9010 white
23. Voice Evacuation System - Sound detect 180
Properties:
Protection class IP 54
Weight 1,8 kg
Colour housing
252 mm x 192 mm x 82 mm
Spring clamps on the rear plate for a fast, reliable and easy mounting.
6/3/1,5 W
Technical data
Surface-mounted cabinet speaker, MDF-wood housing Art.-no. 32397 - Type SD-WA 06-165/T
180° (H) / 180° (V)
Screws/Spring clamps
97,5 dB105,3 dB
UV-resistant colour
Description:Surface-mounted cabinet speaker 100 V with powerful 165 mm-full range speaker in high-quality, film coated MDF-wood housing for a non-resonance sound suitable for various installations e.g. in schools, public places or hospitals
125-15.000 Hz
-20°C to +150 °C
Dimensions
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1mAmbient temperatureDispersion angle (-10dB)
MountingConnection
Material
Shock resistant housing for the use in difficult environments
Plug-in connectionWhiteMDF-wood
Equipped with ceramic terminal, thermo fuse and a temperature resistant cable to ensure an increased safety in case of fire
Surface-mounted cabinet speaker, MDF-wood housing, BS 5839 Art.-no. 32398 - Type SD-WA 06-165/T BS 5839
Description:Surface-mounted cabinet speaker 100 V with powerful 165 mm-full range speaker in high-quality, film coated MDF-wood housing for a non-resonance sound suitable for various installations e.g. in schools, public places or hospitals according to British Standard BS 5839 part 8
23. Voice Evacuation System - Sound detect 181
Properties:
Description:Surface-mounted cabinet speaker (100 V) in elegant design with two autonomous speaker and transformators and a supply via two seperated (A/B) lines. The redundant speaker system ensures at a failure of one line the continous sound supply to the evacuation area according to VDE 0833-4. The A and also the B-line is available in any installation position to avoid failure situations.
230-18.379 Hz
-20°C to +120 °C
Spring clamps on the rear plate for a fast, reliable and easy mounting.
2 x 6/3/1,5 W
Technical data
PowerFrequency rangeSound pressure level SPL 1W/1m
Weight 2,1 kg
Surface-mounted cabinet speaker, MDF-wood housing, 2 speaker, AB-wiring Art.-no. 32549 - Type SD-WA-EN 06-100/T
150° (H) / 150° (V)Screws/Spring clamps
97,8 dB112,8 dB
UV-resistant colour
Colour housingMDF-wood
IP 54Sound pressure level SPL Pmax/1m
Ambient temperatureDispersion angle (-10dB)
Material
MountingConnection
Shock resistant housing for the use in difficult environments
Protection class
Plug-in connectionWhite
23. Voice Evacuation System - Sound detect 182
Properties:
Weight 1,35 in kg
Colour housing
140 mm x 195 mmMaterial ABS-plastic
Sound Projector, BS 5839 Art.-no. 32399 - Type SD-DA-P 20-130/T BS 5839
360° (H) / 360° (V) Mounting bracket
99,5 dB112,5 dB
Description:Stable and reliable soundprojectors 100 V for evacuation in floors and corridoors because of its good speech intelligibility according to British Standard BS 5839 part 8
150-20.000 Hz
-20°C to +150 °C
UV-resistant colour
Dimensions
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1mAmbient temperatureDispersion angle (-10dB)Mounting
Equipped with ceramic terminal, thermo fuse and a temperature resistant cable to ensure
5-wire cable, length 1mRAL 9010 white
Technical data
an increased safety in case of fire
Shock resistant housing for the use in difficult environments
20/10/5/2,5 W
Connection
23. Voice Evacuation System - Sound detect 183
Properties:
is included in the delivery
Protection class IP 66 for reliability under challenging environments
The rust-proof U-bracket made of V2A allowing a flexible and quick mounting
Weight 1,4 kg
Colour housing
142 mm x 210 mm
10 / 5 / 2,5 / 1,25 W
Dimensions
Power
Horn speaker, 10 Watt, wheaterproof Art.-no. 32400 - Type SD-DK 10T
140° (H) / 140° (V)V2A-bracket
102,4 dB112,4 dB
Description:Wheatherproof, reliable and UV resistant 10 Watt horn speaker (100 V) for outdoor use in robust ABS housing
400-10.000 Hz
-50°C to +100°C
Flexible power adjustments (DK10: 20 Ohm) can easily be made on the back of the horn speaker.
Technical data
Shock resistant ABS-housing accord. to UL 94-VO for enduring stability.
Enormous sound pressure, high wheather-resistance and broad frequency range
for industrial use (workshops, outdoor use, swimming pools etc.)
Frequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperature
ABS-housing
Protection class IP 66
2-wire cable, lenght 1mRAL 7035 light grey
Dispersion angle (-10dB)MountingConnection
Material
23. Voice Evacuation System - Sound detect 184
Properties:
ABS-housing
Protection class IP 66
2-wire cable, lenght 1mRAL 7035 light grey
Dispersion angle (-10dB)MountingConnection
Material
Frequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperature
Technical data
Shock resistant ABS-housing accord. to UL 94-VO for enduring stability.
Enormous sound pressure, high wheather-resistance and broad frequency range
for industrial use (workshops, outdoor use, swimming pools etc.)
Horn speaker, 15 Watt, wheaterproof Art.-no. 32401 - Type SD-DK 15T
140° (H) / 140° (V)V2A-bracket
107,3 dB119,1 dB
Description:Wheatherproof, reliable and UV resistant 15 Watt horn speaker (100 V) for outdoor use in robust ABS housing
300-12.500 Hz
-50°C to +100°C
Flexible power adjustments (DK15: 20 Ohm) can easily be made on the back of the horn speaker.is included in the delivery
Protection class IP 66 for reliability under challenging environments
The rust-proof U-bracket made of V2A allowing a flexible and quick mounting
Weight 1,9 kg
Colour housing
208,5 mm x 271,5 mm
15 / 7,5 / 3,75 / 1,87 W
Dimensions
Power
23. Voice Evacuation System - Sound detect 185
Properties:
is included in the delivery
Protection class IP 66 for reliability under challenging environments
The rust-proof U-bracket made of V2A allowing a flexible and quick mounting
Weight 2,6 kg
Colour housing
238 mm x 302 mm
30/20/10/5 W
Dimensions
Power
Horn speaker, 30 Watt, wheaterproof Art.-no. 32402 - Type SD-DK 30T
130° (H) / 130° (V)V2A-bracket
110,1 dB124,9 dB
Description:Wheatherproof, reliable and UV resistant 30 Watt horn speaker (100 V) for outdoor use in robust ABS housing
300-6.000 Hz
-50°C to +100°C
Flexible power adjustments (DK30: 20 Ohm) can easily be made on the back of the horn speaker.
Technical data
Shock resistant ABS-housing accord. to UL 94-VO for enduring stability.
Enormous sound pressure, high wheather-resistance and broad frequency range
for industrial use (workshops, outdoor use, swimming pools etc.)
Frequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperature
ABS-housing
Protection class IP 66
2-wire cable, lenght 1mRAL 7035 light grey
Dispersion angle (-10dB)MountingConnection
Material
23. Voice Evacuation System - Sound detect 186
Properties:
Including wall mounting brackets for an easy mounting
Water proof product with stainless steel and plastic coating
for the use in difficult environments
Weight 2,1 kg
Colour housing
344 mm x 100 mm x 92 mm
10/6/3/1,5 W
Dimensions
Power
Sound column, wheaterproof Art.-no. 32403 - Type SD-TS-C 10-300/T
232° (H) / 140° (V)Wall mounting
93,3 dB103,3 dB
Description:Wheatherproof sound column (100 V) for outdoor use made out off shock-resistant, ball proof aluminium
150-18.000 Hz
-30°C to +100°C
Ball joint as option for a flexible mounting
Technical data
Shock resistant and ball proof housing (according to DIN 18032 part 3)
Impregnated for environments with high humidity
Sound column, wheaterproof, BS 5839 Art.-no. 32405 - Type SD-TS-C 10-300/T BS5839
Description:Wheatherproof sound column (100 V) for outdoor use made out off shock-resistant, ball proof aluminium according to British Standard BS 5839 part 8
Frequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperature
Aluminium
Protection class IP 66
5-wire cable, length 1mRAL 9006
Dispersion angle (-10dB)MountingConnection
Material
23. Voice Evacuation System - Sound detect 187
Properties:
Aluminium
Protection class IP 66
5-wire cable, length 1mRAL 9006
Dispersion angle (-10dB)MountingConnection
Material
Frequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1m
Ambient temperature
Technical data
Shock resistant and ball proof housing (according to DIN 18032 part 3)
Impregnated for environments with high humidity
Sound column, 8 full range speaker, wheatherproof, BS 5839 Art.-no. 32406 - Type SD-TS-C 50-1000/T BS5839
Description:Wheatherproof sound column (100 V) for outdoor use made out off shock-resistant, ball proof aluminium with 8 full range speaker according to British Standard BS 5839 part 8
8 full range speaker as standard
Sound column, 8 full range speaker wheaterproof Art.-no. 32404 - Type SD-TS-C 50-1000/T
244° (H) / 62° (V)Swivel joint
93,7 dB110,7 dB
Description:Wheatherproof sound column (100 V) for outdoor use made out off shock-resistant, ball proof aluminium with 8 full range speaker
150-17.000 Hz
-30°C to +100°C
Ball joint as option for a flexible mountingIncluding wall mounting brackets for an easy mounting
Water proof product with stainless steel and plastic coating
for the use in difficult environments
Weight 5,7 kg
Colour housing
971 mm x 100 mm x 92 mm
50/30/15/7,5 W
Dimensions
Power
23. Voice Evacuation System - Sound detect 188
Properties:
Material
Weight
Supply voltageBattery voltageFrequency response
OutputsDistortion factorColour housing
Inputs
Rated load-carrying capacity
100 V and 8 Ohm; Speech: 100 V; Line output: 1 V, 600 OhmLess than 1% at 1kHz, nominal powerBlackMetal
50 ~20.000 Hz +/-3 dB
Shallow design (2HE) and19"-fitting
115 V/230 V AC , 50/60 Hz
Technical data for SD-AMP 120 and SD-AMP 240
Including 24V adapter for the emergency supply
Including one potentiometer at the amplifier front for the levelling out of the amplifier
Integrated remote control input for a remote activation of the amplifier
Flexibility provided by symmetric and asymmetric inputs for each
amplifier channel (XLR, Cinch, Jack )
of speakers and the Speaker Matrix PMT 32 (32411) respectively
Description:The Power amplifier SD-AMP 120 amplifies the audio signal coming from the system controller (PCT) to a 100 V signal which is being routed by the Speaker Matrix (PMT 32) to the according speaker lines
24 V DC (MAX 10% deviation)
Approx. 10 kg
Rated load-carrying capacityPower consumption
Power amplifier 240 Watt Art.-no. 32562 - Type SD-AMP 240
Description:The Power amplifier SD-AMP 240 amplifies the audio signal coming from the system controller (PCT) to a 100 V signal which is being routed by the Speaker Matrix (PMT 32) to the according speaker lines
Dimensions (H x W x D) Approx. 88 mm (2HE) x 483 mm (19") x 300 mm
Approx. 13 kg
Power amplifier 120 Watt Art.-no. 32561 - Type SD-AMP 120
Line input: 1 V, 47 kOhm, symmetric, asymmetric, balanced, unbalanced
180 W / 120 W400 W
The amplifier comes with a 100 V-respectively an 8 Ohm output for the connection
360 W / 240 WPower consumption 760 WWeight
23. Voice Evacuation System - Sound detect 189
Properties:
Dimensions (H x W x D)Weight
Supply voltageBattery voltage
Dimensions (H x W x D)
Including one potentiometer at the amplifier front for the levelling out of the amplifier
Integrated remote control input for a remote activation of the amplifier
Flexibility provided by symmetric and asymmetric inputs for each
amplifier channel (XLR, Cinch, Jack )
of speakers and the Speaker Matrix PMT 32 (32411) respectively
Frequency response
OutputsDistortion factorColour housing
Inputs
100 V and 8 Ohm; Speech: 100 V; Line output: 1 V, 600 OhmLess than 1% at 1kHz, nominal powerBlack
Approx. 133 mm (3HE) x 483 mm (19") x 385 mm
Approx. 133 mm (3HE) x 483 mm (19") x 380 mm
50 ~20.000 Hz +/-3 dB
Shallow design (2HE) and19"-fitting
115 V/230 V AC , 50/60 Hz
Technical data for SD-AMP 480 and SD-AMP 4 x 120
Including 24V adapter for the emergency supply
Description:The Power amplifier SD-AMP 480 amplifies the audio signal coming from the system controller (PCT) to a 100 V signal which is being routed by the Speaker Matrix (PMT 32) to the according speaker lines
24 V DC (MAX 10% deviation)
Approx. 24 kg
Rated load-carrying capacityPower consumption
4-Channel-Power amplifier, 4 x 120 Watt Art.-no. 32564 - Type SD-AMP 4x120
Description:The 4-Channel-Power-amplifier SD-AMP 4x120 comes with four independently amplifier channels. Each channel amplifies the audio signal coming from the system controller (PCT) to a 100V signal which is being routed by the speaker matrix (PMT 32) to the according speaker
Material Metal
Approx. 25,5 kg
Power amplifier 480 Watt Art.-no. 32563 - Type SD-AMP 480
Line input: 1 V, 47 kOhm, symmetric, asymmetric, balanced, unbalanced
720 W / 480 W1100 W
The amplifier comes with a 100 V-respectively an 8 Ohm output for the connection
Weight
Rated load-carrying capacity 4 x 180 W / 120 WPower consumption 1100 W
23. Voice Evacuation System - Sound detect 190
Properties:
Properties:
OutputsColour housingMaterialDimensions (H x W x D)
Black
Shallow design and 19" fitting
230 V AC , 50/60 Hz
Technical data
sleep-function up to 90 min, 10 station memories FM, 10 station memories AM and stereo play
The Rac-CD/MP3-Module (right module part) includes a programming function, a repeat mode,
a volume control and an auto-reverse-function
Supply voltageCurrent consumptionAmbient temperature
Player with CD/MP3 and Tuner module
Metal, ABSApprox. 44 mm (1HE) x 483 mm (19") x 266 mm
0°C to +40°CChinch-outputs (asymmetric) for each module, antenna terminal
The unit comes with an USB-input and a SD-card reader and is compatible with CD, CD-R and MP3
The RAC-Tuner-Module (left module part) has an integrated volume control,
Description:High quality, reliable audio player for any industrial applications. The RAC 02 CD/MP3-Tuner comes with a CD/MP3- and a Tuner Module
45VA = 0,2A at 230 V AC; 0,9 A at 24 V DC
Supply voltage 230 V AC , 50/60 Hz
Weight Approx. 3,8 kg
Player and recording module with CD/MP3 and MP3-record/player module (DIGI)
Description:High quality, reliable audio player and recorder for any industrial applications. The RAC 02 CD/MP3 (DIGI) comes with a CD/MP3- and a MP3-Record/Player module
Technical data
The Rac-CD/MP3-Module (right module part) includes a programming function, a repeat mode,
Shallow design and 19" fitting
a volume control and an auto-reverse-function
The unit comes with an USB-input and a SD-card reader and is compatible with CD, CD-R and MP3
The RAC-Tuner-Module (left module part) has an integrated 128MB Flash Memory
(120 min recording time), memory card reader (SD) up to 1GB, 2 microphone inputs (Chinch),
Current consumption 45VA = 0,2A at 230 V AC; 0,9 A at 24 V DCAmbient temperature 0°C to +40°C
Dimensions (H x W x D) Approx. 44 mm (1HE) x 483 mm (19") x 266 mm
Outputs Chinch-outputs (asymmetric) for each module, antenna terminalColour housing Black
Weight Approx. 4,5 kg
Art.-no. 32566 - Type SD-RAC 02 with CD/MP3 and MP3-Record/Player (DIGI)
Art.-no. 32565 - Type SD-RAC 02 with CD/MP3 and Tuner Module
2 headphone jacks (chinch) and USB-Port (1.1)
The unit includes MP3 and WAV file management, 6 different repeat functions, level volume control,
recording volume control and supports digital MP3 recording with 44,1 KHz, 128 kbps
Driver software included, compatible to WIN98, WIN2000 and WIN XP
Material Metal, ABS
23. Voice Evacuation System - Sound detect 191
Properties:
Properties:
Material ABSDimensions Approx. 81 mm x 81 mm x 56 mm
Programme 6Colour housing Pure white
Technical data
Selection of 6 different programme sources with a rotary switch
Integrated 24 V-priority override relayShallow design (2HE) and 19" fitting
Programme selector uP, 6 programmes Art.-no. 32572 - Type SD-PW 6 RUP
Description:Programme selector SD-PW 6 RUP for the selection of 6 different programme sources
Approx. 88 mm (2HE) x 483 mm (19") x 41 mm
PowerFrequency rangeSound pressure level SPL 1W/1mSound pressure level SPL Pmax/1mDispersion angle (-10dB)Colour housingMaterialDimensions (H x W x D)
Description:The KL-PW-677 control speaker with programme selector is the best choice for the enduring monitoring of public address systems. The integrated 6W power speaker and the programme selector allow the individually monitoring and control of 6 different programme sources.
70-17.000 Hz
180°
Shallow design (2HE) and 19" fitting
6/3/1,5 W
Technical data
Integrated 6 W speaker with a 77mm full range speaker,
a 100 V-transformer and a wired potentiometer
Weight 1,3 kg
Control speaker with programme selector Art.-no. 32567 - Type SD-KL-PW-677
BlackMetal
83,9 dB91,7 dB
Including programme selector for the selection of 6 different programme sources
The programm selector is equipped with a 24V priority override relay.
23. Voice Evacuation System - Sound detect 192
Properties:
Dimensions Approx. 81 mm x 81 mm x 56 mm
Dimensions Approx. 81 mm x 81 mm x 56 mmSuitable up to a power of 12 W
Volume control uP, 12 Watt Art.-no. 32569 - Type SD-LS 12 RUP
Description:Volume control 12 Watt (in wall) for area volume control of one speaker line (100 V)
Material ABS
Volume control uP, 50 Watt Art.-no. 32570 - Type SD-LS 50 RUP
Description:Volume control 50 Watt (in wall) for area volume control of one speaker line (100 V)
Suitable up to a power of 50 W
Volume control uP, 100 WattPower 50 W
Volume control uP, 6 Watt Art.-no. 32568 - Type SD-LS 06 RUP
Integrated 24 V-mandatory signalling relay
The volume control in »Fail to safe« version bridges the mandatory signalling relay
Description:Volume control 6 Watt (in wall) for area volume control of one speaker line (100 V)
Technical data for volume control
Approx. 81 mm x 81 mm x 74 mmDimensions
Power
Power
Volume control including masking frame,
12 W
Suitable up to a power of 6 W
Approx. 81 mm x 81 mm x 74 mm
Art.-no. 32571 - Type SD-LS 100 RUP
Description:Volume control 100 Watt (in wall) for area volume control of one speaker line (100 V)
Suitable up to a power of 100 W
6 W
Colour housing
DimensionsPower
of the volume control in case that the voltage of the mandatory signal declines
from 24 V to 0 V. In this case the volume control is supplied with full power
12-step continuously rotating attenuation switch with a zero position without remaining volume
100 W
Pure white
plate and rotary switch, colour pure white (GIRA STANDARD 55)
23. Voice Evacuation System - Sound detect 193
Properties:
Programmes (Programme selector)Colour housingMaterial
Suitable up to a power of 6 W
Integrated 24 V-mandatory signalling relay
The volume control in »Fail to safe« version bridges the mandatory signalling relay
of the volume control in case that the voltage of the mandatory signal declines from 24 V to 0 V.
Volume control and programme selector including masking frame, plate and rotary switches,
colour pure white (GIRA STANDARD 55)
Power (Volume control)
In this case the volume control is supplied with full power.
Programme selector:
Selection of 6 different Programme sources with a rotary switch
Technical data
Description:Volume control 6 W and programme selector combination (in wall) for area volume control and programme selection (up to 6 different programme sources) for one speaker line (100 V)
6
Integrated 24 V-priority override relay
6 W
Volume control-Programme selector combination, 12 Watt, 6 programmes Art.-no. 32574 - Type SD-LS-PW 12 RUP
Description:Volume control 12 W and programme selector combination (in wall) for area volume control and programme selection (up to 6 different programme sources) for one speaker line (100 V)
Suitable up to a power of 12 WPower (Volume control) 12 W
Dimensions Approx. 81 mm x 81 mm x 56 mm
Volume control-Programme selector combination, 6 Watt, 6 programmes Art.-no. 32573 - Type SD-LS-PW 06 RUP
Pure whiteABS
Volume control:
12-step continuously rotating attenuation switch with a zero position without remaining volume
23. Voice Evacuation System - Sound detect 194
Properties:
Properties:
Dimensions Approx. 81 mm x 81 mm x 45 mmWeight 0,1 kg
Material ABS
Operation voltageFrequency rangeInputsOutputsColour housingMaterialDimensions
Outputs 50 OhmColour housing Pure white
Technical data
Including 18V phantom power by default for the SD - MI-VO
The phantom power can be disabled through the removal of two resistors
Inputs 50 kOhm
Pure white
rotary switch and XLR socket, colour pure white (GIRA STANDARD 55)
18-30 V
Microphone pre-amplifier including masking frame, plate,
Microphone pre-amplifier, adjustable, including 18 V phantom power Art.-no. 32575 - Type SD-MI-VO
at the back of the circuit board
Description:Adjustable microphone pre-amplifier for the use in professional ELA acoustic irraduation equipment
Description:Adjustable line pre-amplifier for the use in professional ELA acoustic irraduation equipment
Technical data
Including 18V phantom power by default for the SD - MI-VOOperation voltage 18-30 VFrequency range 40~20.000 Hz
0,1 kg
Line pre-amplifier, adjustable Art.-no. 32576 - Type SD-TO-VO
40~20.000 Hz
Weight
ABSApprox. 81 mm x 81 mm x 45 mm
4,4 kOhm50 Ohm
23. Voice Evacuation System - Sound detect 195
Properties:
OutputsColour housingMaterialDimensions
(2 Cinch, 2 XLR) and an electonically balanced output with terminal connectors
Operation voltageFrequency rangeInputs
Description:The flush mounted mixer pre-amplifier SD - UP-MX 04 combines a lot of features on a small spot for the use in professional ELA acoustic irraduation equipment
Mic: 150-20.000 Hz; AUX: 30-20.0000 Hz
Alu anodised
Matching built-in housing available on request
22-30 V AC
Technical data
Seperate limiters for microphone channels and a phantom powering for
condenser microphones can be internally switched on
The flush mounted mixer pre-amplifier comes with two icrophone and two line-inputs
Weight 0,35 kg
Mixer pre-amplifier Art.-no. 32577 - Type SD-UP-MX 04
AluminiumApprox. 205 mm x 150 mm x 40 mm
Mic: -60dBu, AUX: -10dBu / 35 kOhm+6dBu / 150 Ohm
High quality design with an aluminium anodise front plate with engraved inscription
Installation in tables, desks and furniture possible in flush mounted version
23. Voice Evacuation System - Sound detect 196
Properties:
MaterialDimensions
Frequency range
Colour housing
Outputs
Pre Out: 600ohm, 1V; Tape Out: 350 mV, 4,7KohmBlackMetalApprox. 43 mm x 483 mm x 230 mm
- Serial mode: channel 1 has the highest priority, channel 7 the lowest
Equipped with 6 XLR-microphone inputs (switchable to LINE-operation)
and a channel for Tuner/AUX/CD
Master Out: 600ohm, 1V, balanced (XLR), 1V unbalanced (Cinch);
Including 24 V emergency power source connector
The number of channels can be extended from 8 to 16 by connection of
two SD- Pre-Amp 08 via a master/slave DIN socket
Mains/ Battery voltage
Technical data
Seperated limiters for microphone channels and a phantom powering for condenser microphones
can be internally switched on
Three different priorities are available:
Description:The 8 channel pre-amplifier SD-PRE-AMP 08 combines a lot of features for the use in professional ELA acoustic irraduation equipment
24 V DC (MAX 10% deviation)
CD: 500mV, 47kOhm; Tuner: 200mV, 47kOhm; AUX: 200mV, 47kOhm;
Including control input for the built in chime, which is masking the background music
24 V / 230 V AC 50 / 60Hz
Inputs
- Block before: The first activated channel gains the highest priority (channel 1-6)
- Block behind: The last activated channel gains the highest priority (channel 1-6)
Pre-amplifier including external power supply and 19“-mounting brackets
Weight 3,2 kg
Pre-amplifier, 8 channels Art.-no. 32578 - Type SD-PRE-AMP 08
Tel: 0.1~1V, 600ohm adjustable; Power in: 1V, 47Kohm, Paging MIC IN: suitable M-E 01
50~20.000 Hz +/-3dBMic (XLR, DIN): 1mV, 250ohm balanced; Line (XLR): 200mV, 47kOhm;
Including connectivity option to a phone system via seperate input
Three different priority settings for the signals can be easily set by jumpers for each individual project
24. Door Control System and accessories 197
Properties:
DIBT-Number Z-6.5-1646
Door control panel Art.-no. 30410 - Type TSZ 0400
IP 42RAL 9002 greywhite
800 mA1 Relay switch over 30 V/1 A for magnetic clamp
Integrated reset function
External load output for sirens and beacons
Description:Door control panel for the control of fire protection closures and doors
50 Hz ± 10 %
0°C to +40°C
Suitable for applications in EX-zones
230 V AC
Technical data
Up to 3 panels cascadable with control linkage
Status indication for alarm, fault and normal operation via LED
Connection of up to 10 detectors and 12 magnetic clamps
Current supply for the connected detectors and magnetic clamps
Alarm analysis and control
ABS185 mm x 233 mm x 93 mm
Operation voltageFrequencyOutput ext. LoadsPotential free relayAmbient temperatureProtection class
24 Vmax. 800 mA680 g
Output currentWeight
Colour housingMaterialDimensions (H x W x D)Output voltage
24. Door Control System and accessories 198
Properties:
Technical data
Alarm output for the triggering of a LED indicators
Multicolour-LED for alarm- (red) and fault (yellow)
Standards DIN EN 54-7
Max. 93 % (+/-2%)
20 mAmax. 50 mA for LED-indicator or piezo buzzer
-10°C to +60°C
G203036
Optical smoke detector, conventional system, base, DIBT Art.-no. 32255 - Type CT 3000 O incl. SDB DIBT
Description:Optical smoke detector with base for conventional systems with an optical measurement method for ealiest fire detection and indication for the connection to the door control panel TSZ 400
Integrated locking system for the protection against removal and tamper
Integrated professional smoke detection system with highest reliability for a secure
alarm verification with 16 fold measurement and intelligent logics
< 20 m/s
Intelligent analysis and disruption mode for the elimination of false alarms
Periodic sensor tests of the smoke chamber
9 to 33 V DC
44 mm x 100 mm
100 μA
< 0,15 dB / m
Delivery including protective cover for installation phase
Air speedIP 40White (similar to RAL 9003)ABS
Z-6.5-1646
Operation voltageQuiescent currentAlarm currentOC-outputs SensitivityAmbient temperatureHumidity
0786-CPD-20042
Material
VdS approval CPD- NumberDIBT-Number
Protection classColour housing
Dimensions (H x Ø)
24. Door Control System and accessories 199
Properties:
DIBT-Number
Protection classColour housing
Dimensions (H x Ø) Material
Air speed
VdS approval CPD- Number
according to DIBT Z-6.5-1976 with 24 V via a potential free change-over contact
Z-6.5-1646
Operation voltageQuiescent currentAlarm currentOutputsSensitivityAmbient temperatureHumidity
0786-CPD-20042
ABS44 mm x 100 mm
100 μA
< 0,15 dB / m
Integrated locking system for the protection against removal and tamper
Integrated professional smoke detection system with highest reliability for a secure
alarm verification with 16 fold measurement and intelligent logics
Including white relays base with integrated relay board for the triggering of door controls
Intelligent analysis and disruption mode for the elimination of false alarms
Periodic sensor tests of the smoke chamber
9 to 33 V DC
Optical smoke detector, conventional system, relay base, DIBT Art.-no. 32291 - Type CT 3000 O incl. DRB DIBT
Description:Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to DIN EN 54-7Including relay base DRB 3000 for 24 V for the triggering of power supplies of door controls according to DIBT Z-6.5-1976
Technical data
Alarm output for the triggering of a LED indicators
Multicolour-LED for alarm- (red) and fault (yellow)
Standards DIN EN 54-7
Max. 93 % (+/-2%)
20 mARelay 1 change-over contact 30 V / 1A in the base
-10°C to +60°C
< 20 m/s
G203036
IP 40White (similar to RAL 9003)
24. Door Control System and accessories 200
Properties:
Weight 1.200 g
24 V DC +- 10 %
Description:Power supply for door holders with electronic stabilized output voltage 24V at 800 mA output current
Current consumptionOutput currentProtection classColour housing
Operation voltage
Dimensions (H x W x D)
Power supply 800 mA, DIBT Art.-no. 30412 - Type E 800
Current consumptionOutput current
100 mA
160 mm x 105 mm x 55 mm
Dimensions (H x W x D) Weight
Electronic stabilized output voltage of 24V provided by a 230V AC input voltage
Integrated electronic adjustment control for the compensation of variability in the supply voltage
-10°C to +40°C
Robust stainless steel gousing with cable entry at the bottom side
230 V AC +-10 %, 50 HzOutput voltage
117 mm x 82 mm x 51 mm750 g
Z-6.5-1976
200 mA800 mAIP 20White
Technical data for power supply
Ambient temperature
Integrated circuitry against short circuit at the output side
Integrated Status-LED for the display of the operation status
Primary side protected with fuse 0,1 A
Only suitable for the mounting in dry roomsWarms up during operation - please consider sufficient aeration
General remarksDIBT-Number
Stainless steelMaterial
Power supply 450 mA, DIBT Art.-no. 30411 - Type E 450
IP 30Silver
450 mA
Description:Power supply for door holders with electronic stabilized output voltage 24V at 450 mA output current
Protection classColour housing
24. Door Control System and accessories 201
Properties:
Manual release switch uP for door controls Art.-no. 30418 - Type HT uP
Description:Manual release switch for the manual activation of door controls in surface mounting design
Ambient temperatureColour housingMaterial
Dimensions (H x W x D) Weight
Technical data for manual release
Robust housing suitable for the surface mounting
Red rocker switch with inscription "Tür schließen"
Red rocker, white corpus
76 g
Dimensions (H x W x D) 80 mm x 80 mm x 25 mmWeight 93 g
General remarks Attention for mounting: Do not hide the manual switch by an open door.
Manual release switch aP for door controls Art.-no. 30417 - Type HT aP
ABS
63 mm x 63 mm x 37 mm
Description:Manual release switch for the manual activation of door controls in surface mounting design
Manual activation of the release switch gives way to a fire door
-20°C to +60°C
24. Door Control System and accessories 202
Properties:
Colour housingMaterialDiameter
100 g
HeightPower-on timeHolding force
Magnetic clamp, wall fastening, 700 N, DIBT Art.-no. 30422 - Type EM GD 60 K 70
Integrated spark turn off diode for the protection in case of overvoltage
Description:Magnetic clamp for wall mounting with plastic foot for the application with door control systems
Technical data
Integrated release button for the manual interruption
Robust plastic housing with hidden cable entry for a protected connection
-20°C to +60°CIP 40Black
Integrated reverse voltage protection
24 V DC ± 10 %67 mA (1,6 W)
Operation voltageAlarm-/ operation currentAmbient temperatureProtection class
DIBT-Number Z-6.5-1976
Steel82 mm (magnet Ø 60 mm)
RemanenceWeight
70mm100%700 N0 N
24. Door Control System and accessories 203
Properties:
Ambient temperatureProtection classColour housing
Integrated release button for manual interruption
Integrated spark turn off diode for the protection in case of overvoltage
Operation voltageAlarm-/ operation current
MaterialDiameter
RemanenceWeight
Dimensions (H x Ø)Power-on timeHolding force
DIBT-Number Z-6.5-1976
107 mm x 96 mm100%700 N0 N760 g
Technical data
Rotary head for floor and ceiling mounting, with out change of the electrical connections
Length 175 mm, 90° pivoting, Length in pivoted status 137 mm
A magnetic clamp, which keeps a fire door open, has to be activated General remarks
67 mA (1,6 W)
Light grey
Integrated reverse voltage protection
24 V DC ± 10 %
Installation of a manual release switch next to the door is necessary.by a manual release switch, which is not hidden by an open door.
Magnetic clamp, rotary head, 700 N, 175 mm, DIBT Art.-no. 30423 - Type EM GD 60 S 175
Steel96 mm (magnet Ø 60 mm)
-20°C to +60°CIP 40
Robust plastic housing with hidden cable entry for a protected connection
Description:Magnetic clamp for universal mouning onto walls, ceilings and floors for the application in door control systems
24. Door Control System and accessories 204
Properties:
by a manual release switch, which is not hidden by an open door.
Magnetic clamp, rotary head, 700 N, 325 mm, DIBT Art.-no. 30424 - Type EM GD 60 S 325
Steel96 mm (magnet Ø 60 mm)
-20°C to +60°CIP 40
Robust plastic housing with hidden cable entry for a protected connection
Description:Magnetic clamp for universal mouning onto walls, ceilings and floors for the application with door control systems
Technical data
Rotary head for floor and ceiling mounting, with out change of the electrical connections
Length 325 mm, 90° pivoting, Lenght in pivoted status 287 mm
A magnetic clamp, which keeps a fire door open, has to be activated General remarks
67 mA (1,6 W)
Light grey
Integrated reverse voltage protection
24 V DC ± 10 %
Installation of a manual release switch next to the door is necessary.
DIBT-Number Z-6.5-1976
257 mm x 96 mm100%700 N0 N770 g
MaterialDiameter
RemanenceWeight
Dimensions (H x Ø)Power-on timeHolding force
Ambient temperatureProtection classColour housing
Integrated release button for manual interruption
Integrated spark turn off diode for the protection in case of overvoltage
Operation voltageAlarm-/ operation current
24. Door Control System and accessories 205
Properties:
by a manual release switch, which is not hidden by an open door.
Magnetic clamp, rotary head, 700 N, 475 mm, DIBT Art.-no. 30425 - Type EM GD 60 S 475
Steel96 mm (magnet Ø 60 mm)
-20°C to +60°CIP 40
Robust plastic housing with hidden cable entry for a protected connection
Description:Magnetic clamp for universal mouning onto walls, ceilings and floors for the application with door control systems
Technical data
Rotary head for floor and ceiling mounting, with out change of the electrical connections
Length 475 mm, 90° pivoting, Length in pivoted status 437 mm
A magnetic clamp, which keeps a fire door open, has to be activated General remarks
67 mA (1,6 W)
Light grey
Integrated reverse voltage protection
24 V DC ± 10 %
Installation of a manual release switch next to the door is necessary.
DIBT-Number Z-6.5-1976
407 mm x 96 mm100%700 N0 N1.200 g
MaterialDiameter
RemanenceWeight
Dimensions (H x Ø)Power-on timeHolding force
Ambient temperatureProtection classColour housing
Integrated release button for manual interruption
Integrated spark turn off diode for the protection in case of overvoltage
Operation voltageAlarm-/ operation current
24. Door Control System and accessories 206
Properties:
Magnetic clamp for wall mounting, 700 N, DIBT Art.-no. 30428 - Type EM GD 60 F 26
Steel(Magnet Ø 60 mm)
-20°C to +60°CIP 20
Description:Magnetic clamp for wall mounting for the use with door control systems
Technical data
Integrated spark turn off diode for the protection in case of overvoltage
Reverse voltage protection
General remarks
67 mA (1,6 W)
Zinccoated
Robust housing with zinccoated surface
24 V DC ± 15 %
Cover available upon requestDIBT-Number Z-6.5-1976
93 mm x 65 mm x 26 mm100%700 N0 N1.200 g
MaterialDiameter
RemanenceWeight
Dimensions (H x Ø)Power-on timeHolding force
Ambient temperatureProtection classColour housing
Operation voltageAlarm-/ operation current
24. Door Control System and accessories 207
Properties:
Integrated spark turn off diode for the protection in case of overvoltage
Ambient temperatureProtection classColour housing
Operation voltageAlarm-/ operation current
MaterialDiameter
RemanenceWeight
Dimensions (H x Ø)Power-on timeHolding force
100%700 N0 N500 g
Robust plastic housing with hidden cable entry for a protected connection
General remarks
67 mA (1,6 W)
White
Integrated reverse voltage protection
24 V DC ± 10 %
The terminal clamp is located on the base plate of the magnetDIBT-Number Z-6.5-1976
102 mm x 70 mm x 25 mm
Magnetic clamp in plastic housing, 700 N, DIBT Art.-no. 30430 - Type EM GD 60 F 26 T
Plastic(Magnet Ø 60 mm)
-20°C to +60°CIP 20
Description:Magnetic clamp in plastic housing with integrated disruption button for the application with door control systems
Technical data
Integrated release button for a manual disruption
24. Door Control System and accessories 208
Properties:
RemanenceHolding force
Alarm-/ operation current
MaterialDiameter
DIBT-Number Z-6.5-1976
100 mm x 165 mm x 107 mm100%700 N0 N1.900 gWeight
Dimensions (H x Ø)Power-on time
mechanical impact or foreign objects on the floor
67 mA (1,6 W)
Black
Integrated reverse voltage protection
24 V DC ± 10 %
Integrated spark turn off diode for the protection in case of overvoltage
Ambient temperatureProtection classColour housing
Operation voltage
Magnetic clamp, floor mounting, 700 N, DIBT Art.-no. 30434 - Type EM GD 60 FB
Aluminium3 x 9 mm (mounting holes for the floor mounting)
-20°C to +60°CIP 40
Description:Magnetic clamp for the floor mounting with aluminium cast housing for the application with door control
Technical data
Design in solid aluminium cast housing and resistant against any
24. Door Control System and accessories 209
Properties:
Magnetic clamp, wall mounting, 600 N, DIBT Art.-no. 32508 - Type EM GD 50 F 26
Steel(Magnet Ø 50 mm)
-20°C to +60°CIP 20
Description:Magnetic clamp for wall mounting for the application with door control systems
Technical data
Integrated spark turn off diode for the protection against overvoltage
Integrated reverse voltage protection
67 mA (1,6 W)
Zinc
Robust housing with zinc coated surface
24 V DC ± 10 %
Ambient temperatureProtection classColour housing
Operation voltageAlarm-/ operation current
DIBT-Number Z-6.5-1976
83 mm x 55 mm x 26 mm100%600 N0 N402 g
MaterialDiameter
RemanenceWeight
Dimensions (H x Ø)Power-on timeHolding force
24. Door Control System and accessories 210
Properties:
Magnetic clamp wall mounting 1450 N, DIBT Art.-no. 32510 - Type EM GD 70 F 39
Steel(Magnet Ø 70 mm)
-20°C to +60°CIP 20
Description:Magnetic clamp for wall mounting for the use in door control systems
Technical data
Integrated spark turn off diode for the protection in case of overvoltage
Reverse voltage protection
General remarks
71 mA
Zinccoated
Robust housing with zinccoated surface
24 V DC ±10 %
Cover available upon requestDIBT-Number Z-6.5-1976
103 mm x 75 mm x 39 mm100%1.450 N0 N1.074 g
MaterialDiameter
RemanenceWeight
Dimensions (H x Ø)Power-on timeHolding force
Ambient temperatureProtection classColour housing
Operation voltageAlarm-/ operation current
24. Door Control System and accessories 211
Properties:
the explosive area in explosionproof design.
General remarks
to a junction box, which is provided by the customer and which is installed outside of the explosive area or which is installed inside
Please consider the remarks for explosionproof components
ATEX-Number ExII2GEExemIIT6
Explosionproof magnetic clamps with connection cable are connected
Ambient temperatureProtection classColour housing
RemanenceWeight
Dimensions (H x W x D)Power-on time 100%
1.450 N0 N
Operation voltageAlarm-/ operation current
MaterialDiameter
Magetic clamp, wall mounting, 1450 N, DIBT Art.-no. 30436 - Type EM GD 70 Ex
Steel(Magnet Ø 70 mm)
-20°C to +40°CIP 66
Integrated spark turn off diode for the protection in case of overvoltage
70 mA (1,7 W)
Zinc
Description:Magnetic clamp for wall mounting in explosionproof design for the application with door control
Technical data
Including connection cable of 2m
DIBT-Number Z-6.5-1976
110 mm x 75 mm x 43 mm
1.260 g
Integrated reverse voltage protection
24 V DC ±20 %
Holding force
24. Door Control System and accessories 212
Properties:
Properties:
Anchor plate with rubber bearing Art.-no. 30437 - Type AP GD 60 G 16
64 mm (anchor plate)
Description:The anchor plates provides a magnetic contact between a magnetic clamp and a fire door
Technical data
Elastic connection piece for an adjustment of an angle up to 10 °
Steel, Zinccoated
Zinc coated anchor plate
Colour housing
Art.-no. 30438 - Type AP GD 60 W 50
Material
WeightDimensions (H x W x D)
Anchor plate with angle joint
pole face of the magnet to utilize its holding force.
65 mm x 65 mm x 16 mm280 g The anchor plate requires at minimum the same diameter like the General remarks
Description:The anchor plate provides a magnetic contact between the magnetic clamp and the fire door.Suitable for the adjustment of angles of inclination of up to 60°
Technical data
Elastic connection piece for an adjustment of an angle up to 10 °Zinc coated anchor plate
Colour housing BlackMaterial SteelDiameter 64 mm (anchor plate)Dimensions (H x W x D) 60 mm x 60 mm x 51 mm
General remarks The anchor plate requires at minimum the same diameter like the pole face of the magnet to utilize its holding force.
Weight 230 g
24. Door Control System and accessories 213
Properties:
Properties:
General remarks The anchor plate requires at minimum the same diameter like the pole face of the magnet to utilize its holding force.
Dimensions (H x W x D) 55 mm x 55 mm x 16 mmWeight 197g
Zinc coated anchor plate
Material Steel, ZinccoatedDiameter 54 mm (anchor plate)
Description:The anchor plates provide a magnetic contact between a magnetic clamp and a fire door.
Technical data
Elastic connection piece for the adjustment of an angle up to 10 °
Anchor plate with rubber bearing
pole face of the magnet to utilize its holding force.
64 mm (anchor plate)
350 g The anchor plate requires at minimum the same diameter like the General remarks
Zinc coated anchor plate
Colour housing
Art.-no. 32511 - Type AP GD 50 G16
Dimensions (H x Ø) 82 mm x 80 mmHolding force 100 N at 200 mm spring deflexion
Material
Weight
Diameter
Anchor plate with telescope damper Art.-no. 30439 - Type AP GD 60 T 80
Steel
Description:Anchor plate with telescope damping for providing a magnetic contact between the magnetic clamp and a fire door.Suitable for the installation on heavy doors and gates, where an absorption of the impact is necessary.
Technical data
Fibre-glass reinforced black robust plastic housing for heavy mechanical loads
Zinc coated anchor plate
Flexible support of the anchor plate for an adjustment of an angle up to 10°
Black
24. Door Control System and accessories 214
Properties:
Properties:
Anchor plate with rubber bearing Art.-no. 32512 - Type AP GD 70 G 20
74 mm (anchor plate)
Description:The anchor plates provide a magnetic contact between a magnetic clamp and a fire door
Technical data
Elastic connection piece for the adjustment of an angle up to 10 °
Steel, Zinccoated
Zinc coated anchor plate
Material
Art.-no. 32513 - Type AP GD 70 W 54
Weight 518 g
DiameterDimensions (H x W x D)
Anchor plate with angle joint
pole face of the magnet to utilize its holding force.
75 mm x 75 mm x 20 mm
The anchor plate requires at minimum the same diameter like the General remarks
Description:The anchor plate provides a magnetic contact between the magnetic clamp and the fire door.Suitable for the adjustment of angles of inclination of up to 60°
Technical data
Angle joint with a slewing range of up to max. 60° in both directionsZinc coated anchor plate
Colour housing BlackMaterial SteelDiameter 74 mm (anchor plate)Dimensions (H x W x D) 60 mm x 60 mm x 54 mm
General remarks The anchor plate requires at minimum the same diameter like the pole face of the magnet to utilize its holding force.
Weight 395 g
24. Door Control System and accessories 215
Properties:
The anchor plate requires at minimum the same diameter like the pole face of the magnet to utilize its holding force.
General remarks
Anchor plate with angle joint Art.-no. 30441 - Type AP GD 50 W 50
51 mm (anchor plate)60 mm x 60 mm x 51 mm
Description:The anchor plate provides a magnetic contact between the magnetic clamp and the fire door.Suitable for the adjustment of angles of inclination of up to 60°
Weight
Technical data
Angle joint with a slewing range of up to max. 60° in both directions
Steel
184 g
Zinc coated anchor plate
BlackColour housingMaterialDiameterDimensions (H x W x D)
24. Door Control System and accessories 216
Set 398, magnetic clamp 500 N and anchor plate Art.-no. 32507 - Type Set GD 50 398
Description:Set 398 consisting of: magnetic clamp and anchor plate with rubber bearing for the application with door control systemsSet includes: 1 pcs 30430 and 32511
Set 331, magnetic clamp 500 N and anchor plate Art.-no. 32506 - Type Set GD 50 331
Description:Set 331 consisting of: magnetic clamp in plastic housing 500 N, Ø 49,5 mm and anchor plate with rubber bearing.Suitable for the application with door control and fire protection closuresSet includes: 1 pcs 30430 and 32511
Set 330 Magnetic clamp 500 N and anchor plate Art.-no. 32505 - Type Set GD 50 330
Description:Set 330 consisting of: magnetic clamp in plastic housing 500 N, Ø 49,5 mm and anchor plate with angle joint.Suitable for the application with door control and fire protection closuresSet includes: 1 pcs 30430 and 30441
24. Door Control System and accessories 217
Properties:
Properties:
The distance from the ceiling to the top edge of the wall opening is more than 5 m
of the wall opening and at cantilever arm.Wall mounted detectors are installed min. 3,5 m above the top edge
Weight 612 g
Smoke detector distance bracket for wall mounting: 0,5 m Art.-no. 32438 - Type RA 0,5
Description:The mounting angle enables an easy mounting of the detectors at walls
Technical data
Mounting angle with a lenght of minimum 500 mm
White (RAL 9010)Colour housingMaterialDimensions
Floor mounting / wall mounting for magnetic clamps EM GD 50 F and EM GD 60 F Art.-no. 32509 - Type BWA
(Magnet Ø 60 mm)
Description:Floor mounting / wall mounting spacer for an easy and fast mounting of the magnetic clamps EM GD 50 F and EMG 60 F
Technical data
Rotary head, pivoting range up to 180°
Adjustable in height and length of up to 70 mm
Sheet steel
Incl. 4 screws for the fixation of the magnetic clamps
25. Testequipment for automatic detectors 218
Heat, smoke and CO-detector tester, complete Art.-no. 32336 - Type Testifire 2001-001 Kit
Description:Cordless test set for heat detectors, smoke detectors and CO detectors including:1 cordless combi test cap 1001-011 test capsule TS3-001 smoke capsule2 battery bars Solo 760-0011 battery chargerTest capsule TC3-001 CO capsuleWeight: 4,7 kg
Heat and smoke detector tester, complete Art.-no. 32335 - Type Testifire 1001-001 Kit
Description:Cordless test set for heat detectors and smoke detectors including:1 cordless combi test cap 1001-011 test capsule TS3-001 smoke capsule2 battery bars Solo 760-0011 battery chargerWeight: 1,5 kg
Replacement smoke capsule TS3-001 Art.-no. 32337 - Type Testifire TS3-001
Description:Box with 6 capsules for the test of smoke detectors
Replacement smoke capsule TC3-001 Art.-no. 32338 - Type Testifire TC3-001
Description:Box with 6 capsules for the test of CO-detectors
25. Testequipment for automatic detectors 219
Properties:
Heat detector tester, complete Art.-no. 30398 - Type SOLO 461
Description:Cordless test set for heat detectors including:1 cordless heat detector test cap2 Batteries1 battery chargerWeight: 2,05 kg
Smoke detector test set Art.-no. 31956 - Type SOLO 812
Description:Test and detector exchange kit including the following:1 glass fiber telescopic extension pole, length 4,5 m2 glass fiber extension poles, length 1,13 m1 universal removal tool for the exchange of detectors1 aerosol smoke dispenser1 protective carrying/storage bag Weight: 4,7 kg
Aerosol smoke dispenser Art.-no. 14008 - Type SOLO 330
Description:Smoke dispenser for the release of smoke test aerosol for the activation of optical detectorsWeight: 0,75 kg
Technical data
Clear test cap for the visual control of the detector LED during smoke test
Spring loaded mechanism for effective, economic areosol releaseTest cap sensitive to pressure - ideal for suspended / false ceilings
25. Testequipment for automatic detectors 220
Testaerosol 250 ml Art.-no. 31845 - Type TA 250
Description:Non flammable testaerosol for ionisation and optical smoke detectorsArt.-no.: 31845 250 ml bottleArt.-no.: 32262: 35 ml bottleClean, non greasy, fast evaporatingNon flammable non self-sparkingAmbient temperature: 0°C up to +40°C
Testaerosol 35 ml Art.-no. 32262 - Type TA 35
Telescope pole Art.-no. 14006 - Type SOLO 100
Description:4 section glass fibre telescope pole extandable to 4,5 mWeight: 1,86 kg
Detector exchange tool Art.-no. 14007 - Type SOLO 200
Description:Detector removal tool for an easy replacement of detectorsWeight: 1,47 kg
Extension pole Art.-no. 30193 - Type SOLO 101
Description:Glass fibre extension pole; 1,13 mmax. 2 pieces per telescope pole
Bag Art.-no. 14010 - Type SOLO 610
Description:Carrying /Storage bag for test equipmentIntegrated bag for telescope polesBlack synthetic materialWith carrying strapDimensions (H x W x D): 460 mm x 45 mm x 180 mmWeight: 3,44 kg