Updated 07/28/2015 Printed 08/24/2017 Page 1 of 1 Project Nos. 45520-H,E
DESIGN AND CONSTRUCTION GROUP
THE GOVERNOR NELSON A. ROCKEFELLER EMPIRE STATE PLAZA ALBANY, NY 12242
ADDENDUM NO. 1 TO PROJECT NO. 45520
HVAC WORK AND ELECTRICAL WORK REPLACE COOLING TOWERS TEN EYCK OFFICE BUILDING
40 NORTH PEARL STREET ALBANY, NY
August 24, 2017 NOTE: This Addendum forms a part of the Contract Documents. Insert it in the Project Manual.
Acknowledge receipt of this Addendum in the space provided on the Bid Form. HVAC WORK SPECIFICATIONS 1. Page 236500-4, Subparagraph 2.02 J.1.: Delete this Subparagraph in its entirety and replace with
the following: “1. Electronic water level control package shall have five (5) stainless steel water level
sensors (one (1) high level, one (1) high level alarm, one (1) low level, one (1) low level alarm and one (1) ground) with a NEMA 4x enclosure mounted in a cleanable Schedule 40 PVC external standpipe with slow closing solenoid valve(s) and "y" strainer(s). Components shall be field mounted. Valves shall be sized for 25 psi minimum to 125 psi maximum pressure. a) Provide electronic level control for basins in each cell allowing for level control
whenever the adjacent cell basin/unit is off line.” 2. Page 236500-4, Subparagraph 2.02 L.5.: Delete this Subparagraph in its entirety and replace
with the following: “5. Units shall be provided with a Vibration Cutout Switch to protect the fan and drive from
damage in the event of excess vibration” HVAC WORK DRAWINGS 3. Revised Drawings: a. Drawing No. M-001, noted “REVISED DRAWING 8/23/17” accompanies this
Addendum and supersedes the same numbered originally issued drawing. ELECTRICAL WORK DRAWINGS 4. Revised Drawings: a. Drawing Nos. E-001 and E-101 noted “REVISED DRAWING 8/23/17” accompany this
Addendum and supersede the same numbered originally issued drawings.
END OF ADDENDUM Margaret F. Larkin Executive Director Design and Construction JRC:jc
EXISTING SWITCHBOARD "NHPR" 1600A, 480/277V, 50,000 AIC
43
40
30
28
24
WIRES CONDUITSIZENO. SIZE NO. SIZE SIZE
CONDUITWIRESTYPE TYPE
CIRCUIT WIRING TABLE
14
8G4
1.25
1 6G3 2
1.25
41 6G
1/02.0
4G28 350
2-3.04 600 4.0
1/0G1
2.7510G
1041
271 8G3 1
1.25
261 8G4 2
1.25
EXISTING400A
CIRCUITBREAKER
43
PANEL "MP1", 400A MCB, 480/277V, 3Ø, 4W,54 POLE, 50,000 AIC 400A
50A
PANEL LP1, 100A MLO, 208/120V,3Ø, 4W, 24 POLE, 10,000AIC
20
26
20 38G6
1.001
30 KVA 480-208/120V
1.7512G
1221
ONE-LINE DIAGRAMSCALE: NOT TO SCALE
291 6G3 1/0
2.0
21 48G6
1.251
35 41 4G
4/02.5
PANEL MP1 SCHEDULE480/277V 3Ø 4W, SURFACE NEMA 1400A MCB, 1-54 POS SECTION
1 -
90/3 COOLING TOWER #1A FAN (40HP)
2 -
90/3 COOLING TOWER #2A FAN (40HP)3 - 4 -
5 - 6 -
7 -
25/3 COOLING TOWER #1A PUMP (10HP)
8 -
25/3 COOLING TOWER #2A PUMP (10HP)9 - 10 -
11 - 12 -
13 -200/
3COOLING TOWER #1A ELECTRIC HEATCONTROL PANEL (60KW)
14 -200/
3COOLING TOWER #2A ELECTRIC HEATCONTROL PANEL (60KW)15 - 16 -
17 - 18 -
19 -
30/3 SPARE
20 -
30/3 SPARE21 - 22 -
23 - 24 -
25 -
90/3 COOLING TOWER #1B FAN (40HP)
26 -
90/3 COOLING TOWER #2B FAN (40HP)27 - 28 -
29 - 30 -
31 -
25/3 COOLING TOWER #1B PUMP (10HP)
32 -
25/3 COOLING TOWER #2B PUMP (10HP)33 - 34 -
35 - 36 -
37 -
30/3 SPARE
38 -
30/3 SPARE39 - 40 -
41 - 42 -
43 -
30/3 SPARE
44 -
30/3 SPARE45 - 46 -
47 - 48 -
49 -
50/3 30KVA XFMR
50 - SPACE
51 - 52 - SPACE
53 - 54 - SPACE
ELECTRICAL LEGENDSYMBOL DESCRIPTION
PANELBOARDS (PLAN VIEW)
(120/208) VOLT PANELBOARD
(277/480) VOLT PANELBOARD
OUTLETS
1'-6" MOUNTING HEIGHT
EQUIPMENT
MOTOR
DISCONNECT SWITCH
MOTOR STARTER, FURNISHED BY H CONTRACT,INSTALLED BY E CONTRACT
ONE-LINE DIAGRAM
CIRCUIT BREAKER
PANELBOARD
TRANSFORMER
M
SWITCH SIZEFUSE SIZE
TRIP/# OF POLEFRAME SIZE
PNL?????????
ELECTRICAL ABBREVIATIONS# NUMBER
AFF ABOVE FINISHED FLOOR
BKR BREAKER
C CONDUIT
CKT CIRCUIT
CLG CEILING
DIA DIAMETER
DN DOWN
DWG DRAWING
E EXISTING
ELEV ELEVATION
ER EXISTING TO REMAIN
FL FLOOR
FS FLOW SWITCH
FT FEET OR FOOT
G GROUND
GFI GROUND FAULT INTERRUPTOR
GRSC GALVANIZED RIGID STEEL CONDUIT
HP HORSEPOWER
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
MTD MOUNTED
NA NOT APPLICABLE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NF NON FUSED
NO NORMALLY OPEN
OC ON CENTER
PR PAIR
SF SQUARE FEET OR SQUARE FOOT
SH SHIELDED
TW TWISTED
TYP TYPICAL
VFD VARIABLE FREQUENCY DRIVE
WP WEATHERPROOF
XFMR TRANSFORMER
PANEL LP1 SCHEDULE208/120V 3Ø 4W, SURFACE NEMA 1100A MCB, 1-24 POS SECTION
1 - 20/1 WATER LEVEL CONTROL PACKAGE CT1 2 - 20/1 WATER LEVEL CONTROL PACKAGE CT2
3 - 20/1 PULSE PURE INTEGRATED PANEL CT1 4 - 20/1 PULSE PURE INTEGRATED PANEL CT2
5 - 20/1 PULSE PURE INTEGRATED PANEL CT1 6 - 20/1 PULSE PURE INTEGRATED PANEL CT2
7 - 20/1 RECEPTACLES 8 - 20/1 SPARE
9 - 20/1 SPARE 10 - 20/1 SPARE
11 - 20/1 SPARE 12 - 20/1 SPARE
13 - 20/1 SPARE 14 - 20/1 SPARE
15 - - SPACE AND BUSSING 16 - - SPACE AND BUSSING
17 - - SPACE AND BUSSING 18 - - SPACE AND BUSSING
19 - - SPACE AND BUSSING 20 - - SPACE AND BUSSING
21 - - SPACE AND BUSSING 22 - - SPACE AND BUSSING
23 - - SPACE AND BUSSING 24 - - SPACE AND BUSSING
PANEL MP1 NHPR
GROUNDING DETAILSCALE: NOT TO SCALE
N
G
BOND
NO
N G
#2 EQUIP GROUNDCONDUCTORNEUTRAL
30KVAXFMR
PANELN
G
TRANSFORMER CONCRETE PAD DETAILSCALE: NOT TO SCALE
4"
#4 BAR (TYPICAL)
#4 DOWEL @ 12"O.C.
4000 PSI CONCRETEST. TROWEL SMOOTH
3/4" CHAMFER2-SIDES
PAD SHOULD BE 3" LARGER IN EACHDIRECTION THAN TRANSFORMER
CT1 CT2
PENTHOUSE
FAN VFDPUMP STARTER
FAN VFDPUMP STARTER
FAN VFDPUMP STARTER
FAN VFDPUMP STARTER
MP1
LP1
30KVA XFMRCONCRETE PAD
NOTE:ROUTING IS DIAGRAMMATIC ONLY.COORDINATE EXACT ROUTING IN FIELD.NOT ALL CONDUITS SHOWN FORCLARITY. CONDUITS NOT SHOWN SHALLFOLLOW SIMILAR PATH TO THOSESHOWN.
4
3
2
1
A B C D E
PENTHOUSE
36x24 P
LO
T S
HE
ET
DESIGN & CONSTRUCTION
Friedman Fisher Associates, P.C.
-45520
PLOT
TED:
8/24
/2017
9:54
:01 A
MSA
VED:
8/24
/2017
9:49
:07 A
MUS
ER: N
ICHO
LAS
DELP
RADO
FILE
: R:\P
ROJE
CTS\
7794
- OG
S TE
N EY
CK B
UILD
ING
COOL
ING
TOW
ER R
EPLA
CEME
NT\_C
AD\77
94 -
E-00
1.DW
G
Engineering and
Land Surveying, P.C.
PLOT
TED:
8/24
/2017
9:54
:02 A
MSA
VED:
8/24
/2017
9:49
:07 A
MUS
ER: N
ICHO
LAS
DELP
RADO
FILE
: R:\P
ROJE
CTS\
7794
- OG
S TE
N EY
CK B
UILD
ING
COOL
ING
TOW
ER R
EPLA
CEME
NT\_C
AD\77
94 -
E-00
1.DW
G
E
CONDUIT ROUTING DETAILSCALE: 1/8" = 1'-0"
REVISEDDRAWING
8/23/17
1
1
1
EXISTING PANEL PP-RTAC-1600A 480/277V
FAN VFDPUMP STARTER
FAN VFDPUMP STARTER
FAN VFDPUMP STARTER
FAN VFDPUMP STARTER
MP1
100ANFNEMA 3R
DISCONNECT SWITCH FOR FAN, ROUTECIRCUIT THROUGH VFD INSIDE ASREQUIRED. PROVIDE WITH "QUICKBREAK" AUXILIARY CONTACT ANDCONTROL WIRING BACK TO VFD
DISCONNECT SWITCH FOR PUMP, ROUTECIRCUIT THROUGH STARTER INSIDE ASREQUIRED.
MP1-1,3,5
MP1-7,9,11
MP1-25,27,29MP1-31,33,35
MP1-2,4,6MP1-8,10,12
MP1-26,28,30
EXISTING SWITCHBOARDNHPR 1600A 480/277V
LP1
30KVA XFMRCONCRETE PAD
GFIWP
LP1-7
CT1 CT2
1
26
COOLING TOWER COOLINGTOWER
COOLINGTOWER COOLING TOWER
2
30ANFNEMA 3R
262 26 2MP1-32,34,36
GFIWP
100ANF NEMA 3R 100A
NF
100ANF NEMA 3R
30ANF NEMA 3R
DISCONNECT SWITCH FOR FAN, ROUTECIRCUIT THROUGH VFD INSIDE ASREQUIRED. PROVIDE WITH "QUICKBREAK" AUXILIARY CONTACT ANDCONTROL WIRING BACK TO VFD
DISCONNECT SWITCH FOR FAN, ROUTECIRCUIT THROUGH VFD INSIDE ASREQUIRED. PROVIDE WITH "QUICKBREAK" AUXILIARY CONTACT ANDCONTROL WIRING BACK TO VFD
26
2
DISCONNECT SWITCH FOR PUMP, ROUTECIRCUIT THROUGH STARTER INSIDE ASREQUIRED.
3
SM
1
LP1
WATER LEVELCONTROLPACKAGE
1LP1
PULSE PUREINTEGRATEDPANEL
S M1LP1WATER LEVELCONTROL PACKAGE
S M1LP1WATER LEVELCONTROL PACKAGE SM
1LP1
WATER LEVELCONTROLPACKAGE
4
4
4
4
16,18,2035
5
MP1-13-15,1735
5J
1
PULSE PUREINTEGRATED PANEL
1LP1
PULSE PURE INTEGRATED PANEL
J1
6
6
6
A B C D E F G H
5
4
3
2
1
5
4
3
2
1
A B C D E F G H
MECHANICALROOM
PENTHOUSE
36x24 P
LO
T S
HE
ET
DESIGN & CONSTRUCTION
Friedman Fisher Associates, P.C.
-45520
PLOT
TED:
8/24
/2017
9:55
:07 A
MSA
VED:
8/24
/2017
9:52
:40 A
MUS
ER: N
ICHO
LAS
DELP
RADO
FILE
: R:\P
ROJE
CTS\
7794
- OG
S TE
N EY
CK B
UILD
ING
COOL
ING
TOW
ER R
EPLA
CEME
NT\_C
AD\77
94-E
-101
.DW
G
NORTH
Engineering and
Land Surveying, P.C.
PLOT
TED:
8/24
/2017
9:55
:08 A
MSA
VED:
8/24
/2017
9:52
:40 A
MUS
ER: N
ICHO
LAS
DELP
RADO
FILE
: R:\P
ROJE
CTS\
7794
- OG
S TE
N EY
CK B
UILD
ING
COOL
ING
TOW
ER R
EPLA
CEME
NT\_C
AD\77
94-E
-101
.DW
G
E
KEYED NOTES
PROVIDE (3) 120V CIRCUITS PER COOLING TOWER TO PANEL LP1.
PROVIDE A 4" HIGH CONCRETE PAD FOR TRANSFORMER. PAD SHALL EXTENDBEYOND EQUIPMENT BY 3" IN ALL DIRECTIONS.PROVIDE UNISTRUT BRACING AS REQUIRED FOR MOUNTING DISCONNECTSWITCHES TO STRUCTURAL STEEL. TYPICAL FOR ALL DISCONNECT SWITCHESSHOWN.PROVIDE 2#12, #12G., 3/4" FROM TO WATER LEVEL CONTROLLER TO THE MAKEUPWATER VALVE. COORDINATE LOCATIONS WITH H-CONTRACT.ELECTRIC HEAT CONTROL PANEL. COORDINATE LOCATION WITH H-CONRTACT.PROVIDE CONDUIT AND WIRE BETWEEN CONTROL PANEL AND EACH HEATER, (2) INEACH CELL. PROVIDE 4#6, #8G., 1.25"C. TO EACH HEATER. COORDINATE HEATERLOCATION WITH H-CONTRACT. PROVIDE CONDUIT AND WIRE BETWEEN CONTROLPANEL AND EACH LOW WATER CUTOFF, (1) IN EACH CELL. PROVIDE 2#12, #12G.,3/4"C TO EACH LOW WATER CUTOFF. PROVIDE CONDUIT AND WIRE BETWEENCONTROL PANEL AND EACH THERMOSTAT, (1) IN EACH CELL. PROVIDE 2#12, #12G.,3/4"C TO EACH THERMOSTAT.
COORDINATE LOCATION WITH H-CONTRACT.
1
2
3
4
5
6
ROOF POWER PLANSCALE: 1/8" = 1'-0"
1 1
2
GENERAL NOTES
1. MOTOR STARTERS AND VFD's ARE FURNISHED BY HVAC CONTRACTOR AND INSTALLEDBY ELECTRICAL CONTRACTOR.
2. ELECTRICAL CONTRACTOR SHALL PROVIDE THE CONDUIT AND WIRING BETWEEN ALLTHE DISCONNECTS SWITCHES AND THE DEVICES BEING SERVED. THIS INCLUDES THECONDUIT AND WIRING BETWEEN THE DISCONNECTS FOR THE SUMP PUMPS, TOWERFANS, WATER LEVEL CONTROLS AND. CONDUIT AND WIRING SIZES SHALL MATCH THESIZES INDICATED UPSTREAM OF EACH RESPECTIVE DISCONNECTS AS INDICATED ONTHE CONTRACT DOCUMENTS.
1
1
1
REVISEDDRAWING
8/23/17
MECHANICAL ABBREVIATIONS# NUMBER
AD ACCESS DOOR
BTU BRITISH THERMAL UNIT
CAP CAPACITY
CFM CUBIC FEET PER MINUTE
CW DOMESTIC COLD WATER PIPE
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DN DOWN
DWG DRAWING
E EXISTING
EFT ENTERING FLUID TEMPERATURE
FT FEET OR FOOT
GA GAUGE OR GAGE
GPM GALLONS PER MINUTE
HD HEAD
HP HORSEPOWER
LBS POUNDS
LFT LEAVING FLUID TEMPERATURE
MAX MAXIMUM
MBH MILLION BTU PER HOUR
MFR MANUFACTURER
MIN MINIMUM
N.I.C. NOT IN CONTRACT
PD PRESSURE DROP
PG PROPYLENE GLYCOL
PRESS PRESSURE
PSI POUND PER SQUARE INCH
QTY QUANTITY
TEMP TEMPERATURE
TYP TYPICAL
VFD VARIABLE FREQUENCY DRIVE
WB WET BULB TEMPERATURE
HVAC SYMBOLS LEGENDSYMBOL DESCRIPTION
GENERAL
CONNECT NEW WORK TO EXISTING
POINT OF DISCONNECT
HVAC SYMBOLS LEGENDVALVES AND PIPING ACCESSORIES
DIRECTION OF FLUID FLOW
PIPE BREAK
PIPE DOWN
PIPE TAKE-OFF FROM BOTTOM
BALANCING VALVE
BUTTERFLY VALVE
3-WAY CONTROL VALVE
FLEXIBLE PIPE CONNECTOR
PUMP
CLEANOUT
3/4" BALL DRAIN VALVE WITH THREADED HOSE END CONNECTION
PIPE MOUNTED TEMPERATURE SENSORT
CT1 CT2
LOCATION OF EXISTING CONTROL PANELS
LOCATION OF VFDs &STARTERS SERVINGCOOLING TOWERS
HEAT PUMP LOOP TEMPERATURE SENSOR
L LEVEL CONTROL SYSTEM
W W L LW W
TT
WATER TREATMENT SYSTEMW
T
L L
(4) 18/8 - 3/4" CONDUIT
18/3 WIRE GAGE / # OF CONDUCTORS
PENTHOUSE
NOTES ALL WIRING AND CONDUIT IS EXPOSED ABOVEROOF AND ROUTED HIGH IN PENTHOUSEMINIMUM CONDUIT SIZE: 3/4"
FAN VFDPUMP STARTERFAN VFDPUMP STARTERFAN VFDPUMP STARTERFAN VFDPUMP STARTER
(4) 18/2 - 3/4" CONDUIT (6) 18/2 - 3/4" CONDUIT22/3 TWISTED SHIELDED - 3/4" CONDUIT
18/2 - 3/4" CONDUIT18/2 - 3/4" CONDUIT
22/3 TWISTED SHIELDED3/4" CONDUIT
18/2 - 3/4" CONDUIT18/2 - 3/4" CONDUIT18/2 - 3/4" CONDUIT
(4) 18/4 - 3/4" CONDUIT
22/3 TWISTED SHIELDED - 3/4" CONDUIT
LEGEND
VIBRATION SWITCHV
VV VV
18/2 - 3/4" CONDUIT 18/2 - 3/4" CONDUIT
(4) 18/2 - 3/4" CONDUIT
36x24 P
LO
T S
HE
ET
DESIGN & CONSTRUCTION
Friedman Fisher Associates, P.C.
-45520
PLOT
TED:
8/24
/2017
9:50
:43 A
MSA
VED:
8/24
/2017
9:48
:40 A
MUS
ER: N
ICHO
LAS
DELP
RADO
FILE
: R:\P
ROJE
CTS\
7794
- OG
S TE
N EY
CK B
UILD
ING
COOL
ING
TOW
ER R
EPLA
CEME
NT\_C
AD\77
94 -
M-00
1.DW
G
Engineering and
Land Surveying, P.C.
PLOT
TED:
8/24
/2017
9:50
:43 A
MSA
VED:
8/24
/2017
9:48
:40 A
MUS
ER: N
ICHO
LAS
DELP
RADO
FILE
: R:\P
ROJE
CTS\
7794
- OG
S TE
N EY
CK B
UILD
ING
COOL
ING
TOW
ER R
EPLA
CEME
NT\_C
AD\77
94 -
M-00
1.DW
G
H
CONTROLS ONE LINE DIAGRAMSCALE: 1/8" = 1'-0"
REVISEDDRAWING
8/23/17
1