Rotor DC Current Measurement by Using Current Transformers Authors: Z. Gajić, ABB Sweden D. Trišić, Drinsko-Limske HE, Serbia S.Roxenborg, ABB Sweden Presented by Roger Hedding

description

DC Current Measurement

Transcript of DC Current Measurement

Page 1: DC Current Measurement

Rotor DC Current Measurement by Using Current Transformers

Authors:Z. Gajić, ABB SwedenD. Trišić, Drinsko-Limske HE, SerbiaS.Roxenborg, ABB Sweden

Presented by Roger Hedding

Page 2: DC Current Measurement

Objectives

Information about typical excitation systems

Static excitation What is the role of an excitation

system New measurement principle for

rotor DC current Information about the trial

installation Show some captured recordings DC current use for the protection Conclusions

Page 3: DC Current Measurement

Power Station

CONTROL ROOM

CONTROL SYSTEMS

STEP UP TRANSFORMER

HV SYSTEM

STARPOINTCUBICLE

HV- SUBSTATION

TURBINEGOVERNOR

STATIC STARTER

SYNCHRONIZATION

1

1

Power Island

GEXCITATIONTRANS-FORMERTURBINE

MV SWITCHGEAR

PT’sCT’sSA’s

AUXILIARYTRANS-FORMER

MVDRIVES

LV SWITCHGEAR

EXCITATION SYSTEM

UNITPROTECTION

Page 4: DC Current Measurement

Two main types of excitation system

Page 5: DC Current Measurement

AVR

Regulation & Control Electronics

Excitation transformer

Converter

De-excitation

DC-breaker*

Field flashing

AC-breaker*

*AC- or DC breaker

Main Components Static Excitation Systems

Page 6: DC Current Measurement

Static Excitation System “Inside View”

ULVPh-Ph

Page 7: DC Current Measurement

Thyristor Controlled Rectifier

Note that phases are marked with letters R, S, T instead of A, B, C

Page 8: DC Current Measurement

Static excitation System

AVR

Excitation Transformer

Converter

ACCB

PT

CTController

Field Discharge

Provide variable DC current with short time overload capability

Control terminal voltage with suitable accuracy

Ensure stable operation with network and / or other machines

Contribute to transient stability subsequent to a fault

Communicate with the power plant control system

Keep machine within allowed operating range on P-Q diagram

Page 9: DC Current Measurement

HPP Bajina Bašta (Low Lake)

Page 10: DC Current Measurement

View of RHE from the dam

Page 11: DC Current Measurement

HPP Bajina Bašta (Upper Lake)

Page 12: DC Current Measurement

Overall Single Line Diagram of the Plant

315MVA11kV

100MVA15,75kV

0,2km 220kV OHL

Hydro Power Plant

220kV S/S Zaugline

8km, 220kV OHL (4 off)

Page 13: DC Current Measurement

Generator/Pump Unit Data

Turbine Francis 428.6rpm

Synchronous Machine 315MW pf=0.95 11kV; 50Hz

Unit Transformer 2*160MVA 242kV/11kV Yd5

Page 14: DC Current Measurement

Special Things about this Installation

Operating Modes Generator Motor (Pump) Electrical braking Synchronous start

(i.e. Back-to-Back)

Page 15: DC Current Measurement

Single Line Diagram of Machine Used in Trial Installation

Page 16: DC Current Measurement

Excitation System Three-Line-Diagram

Page 17: DC Current Measurement

Traditional Possibilities to measure DC current

Resistive Shunt Hall-effect sensor

Typically not possible to be used by the numerical protection relays

Primary connections

Connections to transducer

Page 18: DC Current Measurement

Required CT Connections for DC Current Measurement

100/5

1500/5

1400kVA11kV/0,55kV

Yd1

Page 19: DC Current Measurement

How the DC Current is Calculated ?

When HV CTs are used: IA, IB, IC are measured By using properties of

excitation transformer re-calculate Ia, Ib, Ic first

Then use formulas to the right

When LV CTs are used: Ia, Ib, Ic are measured Calculate instantaneous

DC current by using the following formula:

Calculate equivalent RMS value of the DC current by using the following formula:

Page 20: DC Current Measurement

Recordings from the Trial Installation

100/5

1500/5

1400kVA11kV/0,55kV

Yd1

IR_HV, IS_HV, IT_HV

IR_LV, IS_LV, IT_LV

HV_DC_I

LV_DC_I

R, S, T <=> A, B, C

Page 21: DC Current Measurement

Filed Record No 1

Page 22: DC Current Measurement

Filed Record No 2

Page 23: DC Current Measurement

Filed Record No 3

Page 24: DC Current Measurement

Filed Record No 4

Page 25: DC Current Measurement

Filed Record No 5

Page 26: DC Current Measurement

DC Current Value on the built-in HMI, via Comms, etc.

Page 27: DC Current Measurement

Conclusion

Patented DC current measurement in the numerical IED will improve the synchronous generator protection and monitoring.

Current based protection for the rotor winding can be done in an easy way (e.g. thermal overload).

Possible to record and monitor the rotor winding DC current together with Stator U and I in the same COMTRADE file!

Page 28: DC Current Measurement

Practical Advise

When more than one power source is used for the excitation equipment supply, use the CT located just in front of the six-pulse rectifier bridge in order to measure DC current under all operating conditions of the machine

5

2

3

6

4

1

7

89

220kV Transmission Network

Page 29: DC Current Measurement

Questions

Page 30: DC Current Measurement

Recording from Another Machine

8 10 12 1440-

20-

0

20

40 IAIBIC

W1 Current Waveforms

Time [cycles]

Cur

rent

[Am

ps P

rimar

y]

8 10 12 14

200

400

600

800HV_side

DC Current Integrated Value

Time [cycles]

DC

Cur

rent

[Am

pere

s]