Page 1 of 8 DATA SHEET E85001-0135 Not to be used for installation purposes. Issue 1.3 EDWARDS ® Catalog u Small Building Fire alarm Solutions 12-18-17 LIFE SAFETY & INCIDENT MANAGEMENT LIFE SAFETY & INCIDENT MANAGEMENT Overview EDWARDS brand intelligent life safety systems offer the power of high-end intelligent processing in configurations that deliver uncomplicated solutions for small to mid-sized applications. With intelligent detection, electronic addressing, automatic device mapping, optional Ethernet ® connectivity, and a full line of easily- configured option cards and modules, these flexible systems offer versatility that benefits building owners and contractors alike. The iO64 provides one Class A or Class B intelligent device loop that supports up to 64 device addresses, and two Class B Notifi- cation Appliance Circuits (NACs). Optional Class A device wiring is available with the use of a module. The iO1000 provides one Class A or Class B intelligent device loop that supports up to 250 device addresses. Loop controller modules may be added in combination to expand total system capacity in 250-point increments to up to 1,000 device addresses. The iO1000 panel includes four NACs that may be wired for either Class A or Class B operation. The RZI16-2 module adds even more capacity to iO installations by adding up to 16 conventional device circuits and two additional notification appliance circuits. This makes them an ideal retrofit solution that can accommodate new intelligent detectors, as well as existing conventional devices. iO Series supports a wide range of high-end features, including: • Signature Series intelligent modules, detectors, and bases • R-Series remote annunciators • SIGA-REL Releasing Modules • Fully integrated CO detection using Signature Series detec- tors with or without audible signaling Features Auto-programming speeds installation time Supports Signature Series intelligent modules and detectors Combines the Signature intelligent releasing module with Signature multisensor detectors for reliable fire suppression Form C contacts for alarm and trouble, Form A for supervisory Electronic addressing with automatic device mapping Optional Ethernet port for diagnostics, programming and a variety of system reports Two programmable switches with LEDs and custom labeling Supports Genesis horn silence over two wires, and UL 1971-compliant strobe synchronization Class B or Class A wiring Ground fault detection by module Supports up to eight serial annunciators, (LCD, LED-only, and graphic interface) Can use existing wiring for most retrofit applications Upload/download remotely or locally Two-level maintenance alert reporting Pre-alarm and alarm verification by point • Adjustable detector sensitivity 4 x 20 character backlit LCD display Optional earthquake hardening: seismic Importance Factor 1.5 • Standalone operation • Alarm ON command manually activates alarm condition Intelligent Fire Alarm Systems iO64, iO1000 7165-1657: 0244 S3000 COA 6227

Transcript of Data Sheet E85005-0135 -- iO Series Intelligent Fire Alarm...

Page 1: Data Sheet E85005-0135 -- iO Series Intelligent Fire Alarm ...lambdatech.co.in/downloads/Edwards-compressed.pdf · Page 1 of 8 DATA SHEET E85001-0135 Not to be used for installation

Page 1 of 8 D A T A S H E E T E85001-0135 Not to be used for installation purposes. Issue 1.3

EDWARDS® Catalog u Small Building Fire alarm Solutions

12-18-17

L I F E S A F E T Y & I N C I D E N T M A N A G E M E N TL I F E S A F E T Y & I N C I D E N T M A N A G E M E N T

OverviewEDWARDS brand intelligent life safety systems offer the power of high-end intelligent processing in configurations that deliver uncomplicated solutions for small to mid-sized applications. With intelligent detection, electronic addressing, automatic device mapping, optional Ethernet® connectivity, and a full line of easily-configured option cards and modules, these flexible systems offer versatility that benefits building owners and contractors alike.

The iO64 provides one Class A or Class B intelligent device loop that supports up to 64 device addresses, and two Class B Notifi-cation Ap pliance Circuits (NACs). Optional Class A device wiring is available with the use of a module.

The iO1000 provides one Class A or Class B intelligent device loop that supports up to 250 device addresses. Loop controller modules may be added in combination to expand total system capacity in 250-point increments to up to 1,000 device addresses. The iO1000 panel includes four NACs that may be wired for either Class A or Class B operation.

The RZI16-2 module adds even more capacity to iO installations by adding up to 16 conventional device circuits and two additional notification appliance circuits. This makes them an ideal retrofit solution that can accommodate new intelligent detectors, as well as existing conventional devices.

iO Series supports a wide range of high-end features, including:

• Signature Series intelligent modules, detectors, and bases

• R-Series remote annunciators

• SIGA-REL Releasing Modules

• Fully integrated CO detection using Signature Series detec-tors with or without audible signaling

Features• Auto-programming speeds installation time

• Supports Signature Series intelligent modules and detectors

• Combines the Signature intelligent releasing module with Signature multisensor detectors for reliable fire suppression

• Form C contacts for alarm and trouble, Form A for supervisory

• Electronic addressing with automatic device mapping

• Optional Ethernet port for diagnostics, programming and a variety of system reports

• Two programmable switches with LEDs and custom labeling

• Supports Genesis horn silence over two wires, and UL 1971-compliant strobe synchronization

• Class B or Class A wiring

• Ground fault detection by module

• Supports up to eight serial annunciators, (LCD, LED-only, and graphic interface)

• Can use existing wiring for most retrofit applications

• Upload/download remotely or locally

• Two-level maintenance alert reporting

• Pre-alarm and alarm verification by point

• Adjustable detector sensitivity

• 4 x 20 character backlit LCD display

• Optional earthquake hardening: seismic Importance Factor 1.5

• Standalone operation

• Alarm ON command manually activates alarm condition

Intelligent Fire Alarm SystemsiO64, iO1000

7165-1657: 0244

S3000

COA 6227

Page 2: Data Sheet E85005-0135 -- iO Series Intelligent Fire Alarm ...lambdatech.co.in/downloads/Edwards-compressed.pdf · Page 1 of 8 DATA SHEET E85001-0135 Not to be used for installation

Page 2 of 8 D A T A S H E E T E85001-0135 Not to be used for installation purposes. Issue 1.3

ApplicationEDWARDS iO Series life safety systems are powerful intelligent solu-tions for small to mid-sized buildings. Advanced intelligent technol-ogy delivers the benefits of flexible system installation, while clean and easy-to-operate user interfaces make panel operation and system maintenance quick and intuitive.

The smart choiceSignature Series electronic addressing eliminates the tedium of setting dipswitches, and automatic device mapping ensures that each device resides on the system at its correct location. Mean-while, innovative programming allows the designer to customize the system to precisely suit the needs of the building owner.

Reliability you can count onThe inherent fault-tolerant characteristics of Analog/Addressable Technology boosts the reliability of EDWARDS fire alarm systems. When combined with iO Series smoke and heat detectors, these systems deliver a level of dependability not previously available for small to mid-sized applications. All EDWARDS systems are built to exacting reliability benchmarks.

Clear-cut remote annunciationRemote annunciation is a strong suit of the iO Series fire alarm systems. Up to eight annunciators can be installed on a single system. Compatible annunciators include a range of LED and LCD models that provide zone or point annunciation, as well as com-mon control capabilities. iO control panels also supports graphic annunciation with optional RA Graphic Annunciator interface mod-ules. Each interface provides common control and 32 LEDs.

Flexibility built right inTwo fully-programmable front panel switch/LED combinations provide an added measure of flexibility. Their slide-in labels take the mystery out of custom applications, and present a clean finished appearance.

Dimensions

(1) Surface Mounting Holes

(2) Semi-flush mounting Holes

(3) Backbox with Door Attached

(4) Backbox with door and trim kit attached.

Panel dimensions, in (cm)Model D1* D2 D3 D4 D5* D6 D7 D8 D9

iO100028.0(71.1)

3.85(9.8)

9.0(22.8)

22.0(55.8)

15.75(40.0)

10.25(26.0)

4.4 (11.1)

28.2 (71.6)

2.7 (6.8)

iO6421.5(54.6)

3.85(9.8)

7.5 (19.0)

15.5(39.4)

14.25(36.2)

10.25(26.0)

4.5 (11.4)

21.7 (55.1)

2.7 (6.8)

* Add 1-1/2 in. (3.81 cm) to D1 and D5 dimensions for trim kit. The trim kit provides 0.75 inches (1.9 cm) of trim to the top, bottom, and sides of the backbox.

Programming and remote diagnosticsEDWARDS iO Series life safety systems are simple to set up, yet offer advanced programming features that put these small building panels into a class of their own. The auto programming feature quickly gets the panel operational using factory default settings. Basic zone and point settings can be programmed through the front panel interface, so the system is up and running in no time.

For more advanced system configuration and correlation groups programming, iO Series systems interface to a PC running com-patible iO-CU software. This option offers full system configuration in the familiar Windows® operating environment. Connection is made to a laptop through the panel’s optional RS-232 communi-cations port, which can also be used to connect a system printer.

Among the many innovative features of iO Series control panels is the optional network card. This module provides a standard 10/100 Base T Ethernet® network connection that permits access to the control panel from any remote location with the correct communications protocols. The connection can be used to download to the panel from the iO-CU, or upload and view system reports using the iO-CU.

Available system reports include: Correlation groups, Device de-tails, Device maintenance, History, Internal status, System configu-ration, System status, Walk test, Dialer, and CO runtime.

Perfect for retrofitsEDWARDS iO Series control panels are particularly well-suited to retrofit applications. All connections are made over standard wiring – no shielded cable required. This means that in most situations existing wiring can be used to upgrade a legacy control panel to iO technology without the expense or disruption of rewiring the en-tire building. iO control panels also support the ingenious RZI16-2 Zone Module, which adds up to 16 conventional circuits and two NACs. This combination easily accommodates new intelligent detection alongside existing conventional circuits, making it an superior solution in the retrofit market.

Scalable IP and Cellular CommunicationsSeveral popular third-party IP/Cellular communicators have been tested with the iO control panels and are compatibility listed to UL864. The IP/Cellular communicators meet NFPA72 2013 edition requirements for sole or secondary transmission paths. Using IP/Cellular communicators can reduce the cost of ownership by eliminating POTS lines. Please see the iO control panel compat-ibility documentation part number 3102353-EN for a full list of compatible communicators.

Signals with a differenceiO system NACs are configurable to fully support the advanced signaling technology of EDWARDS Genesis and Enhanced Integ-rity notification appliances. These devices offer precision synchro-nization of strobes to UL 1971 standards. For Genesis devices, enabling this feature allows horns to be silenced while strobes on the same two-wire circuit continue to flash until the panel is reset.

A complete line of accessoriesiO Series life safety systems are supported by a complete line of analog/addressable detectors, modules and related equipment. Consult the Ordering Information section for details.

Page 3: Data Sheet E85005-0135 -- iO Series Intelligent Fire Alarm ...lambdatech.co.in/downloads/Edwards-compressed.pdf · Page 1 of 8 DATA SHEET E85001-0135 Not to be used for installation

Page 3 of 8 D A T A S H E E T E85001-0135 Not to be used for installation purposes. Issue 1.3

Each iO64 panel ships with one Signature loop controller that sup-ports 64 devices of any type. This panel’s device capacity cannot be expanded.

System Layout

iO1000

iO64

Panel Layout

Four Class B or two optional Class A NACs

Up to 20,000 feet of wiring per loop

Four Class B or two optional Class A NACs

Optional 10 A or 6.5 A Booster

Up to eight remote annunciators

Up to 125 sensors and 125 modules per loop

Ethernet (SA-ETH)

DACT/Dialer (SA-DACT)

RS-232 (SA-232)

Relays: Two Form C, one Form A

Standard Loop: 250 points (one expansion slot)

iO-SDC1 Expander Loop: 250 points (one expansion slot)

iO-SDC2 Expander, Loop 1 of 2: 250 points

iO-SDC2 Expander, Loop 2 of 2: 250 points

Any combination of two single- or dual Signature loop modules

(one expansion slot)

Sixteen Conventional IDCs, two additional NACs with RZI16-2 module

Ethernet (SA-ETH)

DACT/Dialer (SA-DACT)

RS-232 (SA-232)

Relays: Two Form C, one Form A

Up to 20,000 feet of wiring.

Two Class B or two optional Class A NACs

Optional 10 A or 6.5 A Booster Power Supply

Up to eight remote annunciators

Loop supports up to 64 intelligent devices of any type.

Each iO1000 panel has room for up to two Signature loop control-ler modules in any combination of single or dual 250-device loops. iO1000 loops support 125 detectors and 125 modules.

00:00:00 01/01/07

,

1

2

3

4

5

6

78

9

10

11

12

13

1 Transformer2 Main AC wiring block & fuse holder3 RS-232 card connector (J3)4 Dialer card connection (J8)5 Ethernet card connector (J1)6 Main circuit board7 Panel backbox enclosure8 Operator interface9 SLC card connector (J7)

10 Class A card connector (J2)11 Tie wrap mounts12 LED expander connector (J6)13 Standby batteries

Page 4: Data Sheet E85005-0135 -- iO Series Intelligent Fire Alarm ...lambdatech.co.in/downloads/Edwards-compressed.pdf · Page 1 of 8 DATA SHEET E85001-0135 Not to be used for installation

Page 4 of 8 D A T A S H E E T E85001-0135 Not to be used for installation purposes. Issue 1.3

Annunciator loop (TB4)The control panel provides a connection for up to eight serially driven and supervised remote annunciators.

Circuit specifications

Device loops Class B (Style Y) or Class A (Style Z)Circuit voltage 2.55 VCircuit current 30 mA maxCircuit impedance

Up to 8 annunciators or 4000 feet

+ –TB4

+ –Channel 1 Channel 2

CH1 (+) INCH1 (-) IN

CH2 (+) INCH2 (-) IN

Annunciator

+ –TB4

+ –Channel 1 Channel 2

CH1 (+) INCH1 (-) IN

CH2 (+) INCH2 (-) IN

Annunciator

Terminal wiring location

+ –TB4

+ –Channel 1 Channel 2

CH1 (+) INCH1 (-) IN

CH2 (+) INCH2 (-) IN

Annunciator

+ –TB4

+ –Channel 1 Channel 2

CH1 (+) INCH1 (-) IN

CH2 (+) INCH2 (-) IN

Annunciator

Terminal wiring location

Class B Class A

Alarm, trouble, and supervisory relay (TB3)The trouble relay is normally-open, held closed, and opens on any trouble event or when the panel is de-energized. The supervisory relay is normally-open, and closes on any supervisory event. The alarm relay changes over on any alarm event.

Relay specifications

Alarm Trouble SupervisoryType Form C Form AVoltage 24 VDC at 1 A resistive 24 VDC at 1 A resistive

Relay circuits can only be connected to power-limited sources.

Auxiliary & smoke power outputs (TB3)The control panel provides two auxiliary power outputs that can be used for powering ancillary equipment such as remote annunciators and two wire smoke detectors. Aux 2 can be software selected to operate continuously. The circuit is supervised for shorts and grounds.

Circuit specificationsCircuit voltage range

21.9 to 28.3 V

Resettable circuit (Aux power 2)

24 VDC nominal at 500 mA

Continuous circuit (Aux power 1)

24 VDC nominal at 500 mA. Use this circuit for powering two-wire smoke detectors.

Note: Any current above 0.5 amp connected to both Aux 1 and 2 will reduce the total available NAC power by that amount.

Notification appliance circuits (TB2)iO1000 control panels come equipped with four notification ap-pliance circuits. iO64 control panels come with two NACs. Each circuit can be individually configured for continuous, temporal, synchronized, and coded output.

Specifications iO1000 iO64

Circuit Type 4 Class B or 2 Class A 2 Class B or 2 Class A with SA-CLA module

Voltage 24 VFWRCurrent 6.0 A total, 2.5 A max.

per circuit at 120/230 VAC 60 Hz.

5.0 A total, 2.5 A max. per circuit at 230 VAC

50 Hz.

3.75 A total, 2.5 A max. per circuit at 120/230

VAC 60 Hz.3.0 A total, 2.5 A max. per circuit at 230 VAC

50 Hz.Impedance 26 Ω total, 0.35 µF maxEOLR 15 K Ω, ½ WSynchronization Supported system-wide

+NAC1 -

NAC2+

NAC2 -

NAC1+

EOLR

TB2

+

+ +

Class B wiring

Class B wiring

TB2

TB6

EOLR

NAC3 -

NAC4+

NAC4 -

NAC3+

EOLR

NAC1 -

NAC2+

NAC2 -

NAC1+

+ +

+ +

+ +

+ +

Class A wiring

TB2

TB6

NAC1 -

NAC2+

NAC2 -

NAC1+

+ +

+ +

+

+

- -

- -

- -

- -

- -

- -

- -

- -

-

-

+NAC1 -

NAC2+

NAC2 -

NAC1+

EOLR

TB2

+

+ +

Class B wiring

Class B wiring

TB2

TB6

EOLR

NAC3 -

NAC4+

NAC4 -

NAC3+

EOLR

NAC1 -

NAC2+

NAC2 -

NAC1+

+ +

+ +

+ +

+ +

Class A wiring

TB2

TB6

NAC1 -

NAC2+

NAC2 -

NAC1+

+ +

+ +

+

+

- -

- -

- -

- -

- -

- -

- -

- -

-

-

Marking indicates output signal polarity when the circuit is active. Polarity reverses when the circuit is not active. Wire notification appliances accordingly. Notification appliance polarity shown in active state.

Wiring & Configuration

Signature device loopThe system provides one Signature device loop circuit with a total capacity of 125 detectors and 125 module addresses. The loop circuit is supervised for opens, shorts, and grounds.

Circuit specifications

iO1000 iO64

Device loops One Class B or A loop, supporting 125 detectors and 125

modules. Expandable to four loops.

One Class B or A loop, supporting 64 devices of

any kind.

Communication line voltage

Maximum 20 V peak-to-peak

Circuit current 0.5 A maxCircuit impedance

66Ω total, 0.5 µF, max

Isolators 64 maximumSignal Synchronization

Supported on a system-wide basis (all device loops) when using a SIGA-CC1S or SIGA-MCC1S module and Genesis or Enhanced Integrity notification ap-

pliances.

Loop 1 SEC

Loop card

+

Loop 1 PRI

+

+ +

Loop

device

Loop

device

Data Line

Class B wiring

Class A wiring

Loop 1 SEC+

Loop 1 PRI

+

+ +

Loop

device

Loop

deviceLoop card

Data Line

-

-

- -

-

-

- -

Loop 1 SEC

Loop card

+

Loop 1 PRI

+

+ +

Loop

device

Loop

device

Data Line

Class B wiring

Class A wiring

Loop 1 SEC+

Loop 1 PRI

+

+ +

Loop

device

Loop

deviceLoop card

Data Line

-

-

- -

-

-

- -

SLC A

SLC B

SLC A

SLC B

TB3

(1)NO

NC

NC

NO

NO

(4)

(3)

(2)

(1) Trouble

(2) Supervisory

(3) Alarm

(4) Smoke/Aux

Page 5: Data Sheet E85005-0135 -- iO Series Intelligent Fire Alarm ...lambdatech.co.in/downloads/Edwards-compressed.pdf · Page 1 of 8 DATA SHEET E85001-0135 Not to be used for installation

Page 5 of 8 D A T A S H E E T E85001-0135 Not to be used for installation purposes. Issue 1.3

Single and Dual Loop Controller CardsThe iO-SDC1 is a single loop controller card that can be used with the iO64 as a replacement for the standard 64-point loop, or with the iO1000 as a 250-point expansion module.

The iO-SDC2 is a 500-point dual loop controller card for the iO1000 that provides two SLC circuits, each with 125 detector addresses and 125 module addresses.

Specifications iO-SDC1 iO-SDC2

Device Addresses iO1000: one loop, 250 device addresses

iO64: 64 addresses

iO1000: two loops, 500 device addresses

Wiring Class B or Class AOperating Voltage 24 VDCOperating Current (fully loaded loop)

Standby: 55 mAAlarm: 80 mA

Standby: 45 mAAlarm: 70 mA

Note: These ratings do not include the use of two-wire smoke modules.

Communication Line Voltage

Max. 20.6 V peak-to-peak

Terminal Rating 12 to 18 AWG (0.75 to 2.5 mm2)Circuit Current 0.5 A max.Max total loop resistance

66 Ω

Max total loop capacitance

0.5 μF

Isolators 64 isolators maximum per loop (total bothisolator bases and modules)

Ground Fault Impedance

0 to 5 kΩ

Operating Environment

32 to 120°F (0 to 49°C)0 to 93% noncondensing at 90°F (32°C)

RZI16-2 Remote Zone Interface Module

The RZI16-2 Addressable Remote Zone Interface Module is an addressable device that provides connections for sixteen Class B Initiating Device Circuits and two Class B Supervised Output Circuits. The inputs and outputs can be configured individually for several device types.

It requires 18 consecutive addresses on the Signaling Line Circuit (SLC). Addresses are assigned electronically. There are no address switches to set.

The RZI16-2 incorporates two 8-segment DIP switches that are used to select the Alarm or Supervisory default device type for each of the 16 IDC circuits. The module also includes one 4-seg-ment DIP switch used to select the default Relay or NAC output device type. Device types other than the default are accomplished through programming.

RZI16-2 Specifications

Voltage 24V/Aux nominal: Supervisory current: Alarm Current 24V/Aux minimum: 24V/Aux maximum: NAC1, NAC2 nominal:

24 VDC250 mA at 24 VDC nominal1000 mA18.4 VDC26.4 VDC24 VDC

Current Standby current for 4.7 k EOL (U.S.) Standby current for 3.9 k EOL (Canada) Alarm current at nominal voltage

4.8 mA/ circuit 5.7 mA/ circuit 31.1 mA/ circuit

Relay outputs Quantity Type Rating (pilot duty)

2 Programmable 24 VDC at 2.5 A

Input circuit wiring resistance

25 Ω per wire

Initiating device circuits Quantity EOL resistor Zone voltage

Alarm current Alarm impedance range Trouble impedance range

16 4.7 kΩ (U.S.); 3.9 kΩ Canada 22.78 V for 4.7 kΩ (U.S.) 22.08 V for 3.9 kΩ (Canada) 31.1 mA/ channel at nominal voltage < 680 Ω > 5.55 kΩ

Supervised output circuits EOL resistor Quantity Short circuit detection Open circuit detection Contact ratings

15 kΩ 2< 2.6 kΩ > 61.9 kΩ 24 VDC at 2.5 A (5 A for two NACs)

Compatible cabinets MFC(A), iO1000, APS

SA-ETH Ethernet Interface Card

Network cable

Ethernet card

To network

connection

SA-ETH wiring The SA-ETH card provides a standard 10/100 Base T Ether-net network connection for connecting to an intranet, a local network, or the Internet. The card can be used to download configuration programming from the iO-CU to the panel.

The Ethernet card is installed on the plastic assembly and con-nects to the main circuit board via a ribbon cable.

SA-ETH specificationsEthernet 10/100 Base TOperating environment

TemperatureHumidity

32 to 120°F (0 to 49°C)0 to 93% RH, noncondensing at 90°F (32°C)

Option Cards

EDWARDS iO Series panels are supported by a complete line of modules and related equipment that enhance performance and extend system capabilities. Option cards plug directly into the control panel main circuit board or are connected to it with a ribbon cable. After installation, terminals remain accessible. The cabinet provides ample room for wire routing, keeping wiring neat at all times.

Page 6: Data Sheet E85005-0135 -- iO Series Intelligent Fire Alarm ...lambdatech.co.in/downloads/Edwards-compressed.pdf · Page 1 of 8 DATA SHEET E85001-0135 Not to be used for installation

Page 6 of 8 D A T A S H E E T E85001-0135 Not to be used for installation purposes. Issue 1.3

SA-232 RS-232 interface

GND (black wire)

TXD (white wire)

RXD (red wire)

SA-232 wiringThe SA-232 card provides an RS-232 in-terface with iO panels. It can be used for connecting a printer to the control panel to print system events. The card also can be used for connecting a computer to download a configuration program from the iO-CU to the control panel.

The RS-232 card is installed on the plas-tic assembly and connects to the main circuit board via a ribbon cable.

SA-232 specificationsOperating voltage Standard EIA-232Terminal rating 12 to18 AWG (0.75 to 2.5 sq mm)Operating environment

TemperatureHumidity

32 to 120°F (0 to 49°C)0 to 93% RH, noncondensing at 90°F (32°C)

SA-DACT DialerThe SA-DACT provides communications between the control panel and the central station over a telephone line system. It transmits system status changes (events) to a compatible digital alarm communicator receiver over the public switched telephone network. The dialer is capable of single, dual, or split reporting of events to two different account and telephone numbers. The modem feature of the SA-DACT can also be used for uploading and downloading panel configuration, history, and current status to a PC running the iO-CU.

Phone line 1

Phone line 2To wallphone jack

Phone cables(supplied) RJ31 jacks

SA-DACTwiring

The dialer phone lines connect to connectors on the dialer’s main circuit board. Phone line 1 connects to connector J4 and phone line 2 connects to connector J1.

The SA-DACT queues mes-sages and transmits them based on priority (alarm, supervisory, trouble, and monitor). Activations are transmitted before restora-tions.

The SA-DACT is installed on the plastic assembly and connects to the main circuit board via a ribbon cable.

SA-DACT specificationsPhone line type One or two loop-start lines on a public,

switched networkPhone line connector RJ-31/38X (C31/38X)Communication formats Contact ID (SIA DC-05)Operating environment

TemperatureHumidity

32 to 120°F (0 to 49°C)0 to 93% RH, noncondensing at 90°F (32°C)

Compatible DACRsReceiver Models FormatsAdemco 685 Contact IDFBII CP220 Contact IDOsborne-Hoffman OH 2000 Contact IDBosch D6600 Contact IDSilent Knight 9800 Contact IDSur-Gard SG-MLR1, MLR2 Contact ID

SA-CLA Class A Module (iO64 only)The SA-CLA card provides Class A capability for NAC wiring. Its terminal block provides the wiring connection for NAC return wiring. The card is required for annunciator Class A wiring even though this wiring does not return to the SA-CLA card. The SA-CLA is compatible with iO64 control panels only. iO1000 panels are Class A Ready. The SA-CLA is installed directly to the control panel circuit board using its plastic standoffs and plug connection.

SA-CLA specificationsOperating voltage 24 VFWROperating current 3.75 A FWR total at 120/230 VAC 60 Hz

3.0 A FWR total at 230 VAC 50 Hz 2.5 A max per circuit

Circuit impedance 26 ohms, 0.35uFTerminal rating 12 to18 AWG (0.75 to 2.5 sq mm)Operating environment

TemperatureHumidity

32 to 120°F (0 to 49°C)0 to 93% RH, noncondensing at 90°F (32°C)

D16L-iO LED Display Expander (iO1000 only)The D16L-iO LED Display Expanders provide LED annunciation for up to 16 zones. It provides two LEDs for each zone. Two D16L-iO LED display expanders can be installed in each iO1000 panel.

(1) LED 1

(2) LED 2

(3) LED Expander 1

(4) LED Expander 2

(5) Alarm/non-alarm and trouble zone LEDs

Page 7: Data Sheet E85005-0135 -- iO Series Intelligent Fire Alarm ...lambdatech.co.in/downloads/Edwards-compressed.pdf · Page 1 of 8 DATA SHEET E85001-0135 Not to be used for installation

Page 7 of 8 D A T A S H E E T E85001-0135 Not to be used for installation purposes. Issue 1.3

SpecificationsiO64 iO1000

Device loops 1 loop Class B or Class A (Styles 4, 6, 7) supporting up to 64 device addresses (any combination of detectors and modules)

Maximum T-taps: 63 (each device can be on its own branch)

1 loop, expandable to 4, Class A or B (Styles 4, 6, 7), each loop supporting up to 250 device addresses (125 detectors and 125 modules max.). Addresses 1 to 125 are for detectors and addresses 126 to 250 are for modules

Maximum T-taps/loop: 124

Notification appliance circuits

2 Class B (Style Y), Class A (Style Z) optional

3.75 A FWR total at 120/230 VAC 60 Hz

3.0 A FWR total at 230 VAC 50 Hz

2.5 A FWR each max. per circuit

4 Class B (Style Y) or 2 Class A (Style Z)

6.0 A FWR total at 120/230 VAC 60 Hz

5.0 A FWR total at 230 VAC 50 Hz

2.5 A FWR each max. per circuit

Primary power 120 VAC, 60 Hz, 1.3 A max.

230 VAC, 50-60 Hz, 0.62 A max.

120 VAC, 60 Hz, 2.0 A max.

230 VAC, 50-60 Hz, 0.97 A max.

Base panel current standby 155 mA 172 mA

Base panel current alarm 204 mA 267 mA

Input zones 16 max. 32 max.

Remote annunciator 8 drops max., RS-485 Class B, Class A is optional

Data line length: 4,000 ft. (1,219 m)

8 drops max., RS-485 Class A or B

Data line length: 4,000 ft. (1,219 m)

Operating voltage 24 VDC panel

Auxiliary power output circuit

Aux power 1: 500 mA, 24 VDC

Aux power 2: 500 mA, 24 VDC (1 A possible if you reduce total available NAC power by 500 mA)

Output: 28.3 to 21.9 VDC, special application

Note: For a list of compatible devices, see the iO64 and iO1000 Series Compatibility List (P/N 3102353-EN)

Loop circuit Maximum loop resistance: 66 Ω

Maximum loop capacitance: 0.5 µF

Communication line voltage: Maximum 20.6 V peak-to-peak

Operating current (fully loaded loop) Stand by: 55 mA/45 mA

Alarm: 125 mA/115 mA (not including two-wire smoke modules)

Circuit current: 0.5 A max. Style 4, 6, and 7 wiring

Max. resistance between isolators: Limited only by overall wire run lengths

64 isolators maximum per loop (total both isolator bases and modules)

Batteries Type: Sealed lead acid

Voltage: 24 VDC

Charging current: 2.47 A max. Amp hour capacity: 26 Ah

Standby operation: 24 hour or 60 hour

Placement: Up to two 10 Ah batteries will fit in the iO64 control panel cabinet and two 18 Ah batteries will fit in the iO1000 control panel cabinet. If larger batteries are required, use an EDWARDS battery cabinet.

SA-DACT dialer Phone line type: One or two loop-start lines on a public, switched network

Phone line connector: RJ-31/38X (C31/38X)

Communication formats: Contact ID (SIA DC-05)

Operating current Standby/Alarm: 41 mA Max.: 100 mA

FCC registration number: GESAL01BSADACT

Industry Canada Registration number: 3944A-SADACT

Ringer equivalence number: 0.1B

Ground fault impedance 0 to 5 kΩ

Alarm contact Form C N.O. 24 VDC at 1 A (resistive load)

Trouble contact Form C 24 VDC at 1 A (resistive load)

Supervisory contact Form A N.O. 24 VDC at 1 A (resistive load)

Environmental Temperature: 0 to 49°C (32 to 120°F) Relative humidity: 0 to 93% noncondensing

Terminal rating All terminals rated for 12 to 18 AWG (0.75 to 2.5 mm²)

Page 8: Data Sheet E85005-0135 -- iO Series Intelligent Fire Alarm ...lambdatech.co.in/downloads/Edwards-compressed.pdf · Page 1 of 8 DATA SHEET E85001-0135 Not to be used for installation

Page 8 of 8 D A T A S H E E T E85001-0135 Not to be used for installation purposes. Issue 1.3

12-18-17

L IFE SAFETY & INCIDENT MANAGEMENT

Contact us...

Email: [email protected]: edwards-fire.com

1016 Corporate Park Drive Mebane, NC 27302

EDWARDS is a registered mark in the United States and other countries.

© 2018 United Technologies Corporation. All rights reserved.

Ordering InformationPart Description

iO1000 Fire Alarm SystemsIO1000G Four loop system with one 250-point loop installed. 110v, gray door.IO1000G-2 Four loop system with one 250-point loop installed. 230v, gray door.IO1000G-2-PG Four loop system with one 250-point loop installed. 230v, gray door, Portuguese.IO1000G-2-SP Four loop system with one 250-point loop installed. 230v, gray door, Spanish.IO1000G-CA Four loop system, one 250-point loop installed. 110v, gray door, LED strips, Canada. IO1000GD Four loop system, one 250-point loop installed. 110v, gray door, with dialer.IO1000G-F Four loop system, one 250-point loop. 110v, gray door, LED strips, French Canada.IO1000G-PG Four loop system with one 250-point loop installed. 110v, gray door, Portuguese.IO1000G-SP Four loop system with one 250-point loop installed. 110v, gray door, Spanish.IO1000R Four loop system with one 250-point loop installed. 110v, red door.IO1000R-2 Four loop system with one 250-point loop installed. 230v, red door.IO1000RD Four loop system, one 250-point loop installed. 110v, red door, with dialer.SA-TRIM2 iO1000 Flush mount trim, black.

iO64 Fire Alarm SystemsIO64G One loop system with one 64-point loop installed. 110v, gray door.IO64G-2 One loop system with one 64-point loop installed. 230v, gray door.IO64G-2-PG One loop system with one 64-point loop installed. 230v, gray door, Portuguese.IO64G-2-SP One loop system with one 64-point loop installed. 230v, gray door, Spanish.IO64GD One loop system, one 64-point loop installed. 110v, gray door, with dialer.IO64GL One loop system, one 64-point loop installed. 110v, gray door, English Canada.IO64GL-F One loop system, one 64-point loop installed. 110v, gray door, French Canada.IO64G-PG One loop system with one 64-point loop installed. 110v, gray door, Portuguese.IO64G-SP One loop system with one 64-point loop installed. 110v, gray door, Spanish.IO64R One loop system with one 64-point loop installed. 110v, red door.IO64R-2 One loop system with one 64-point loop installed. 230v, red door.IO64RD One loop system, one 64-point loop installed. 110v, red door, with dialer.SA-TRIM1 iO64 Flush mount trim, black

Option CardsiO-SDC1 Expansion module, one 250-device loop.iO-SDC2 Expansion module, two 250-device loops, 500 devices total. For iO1000 only.RZI16-2 Remote Zone Interface Module. 16 Class B IDCs, 2 Class B Output. Includes bracket.SA-DACT Dual Line Dialer/Modem, supports Contact ID, mounts in cabinet on base plate.SA-232 RS-232 Serial Port for connection to printers & computers, mounts in cabinet.SA-ETH Ethernet Port, Slave, mounts in cabinet on base plate.SA-CLA Class A adapter module. Provides Class A capacity on NACs. Mounts in cabinet on

main board. iO64 systems only.D16L-iO-2 LED Annunciator module, 16 X 2-LED zones (4 programmable for sup). Mounts in

cabinet to right of LCD display for zones 17-32. For iO1000 only.D16L-iO-1 LED Annunciator module, 16 X 2-LED zones (4 programmable for sup). Mounts in

cabinet to left of LCD display for zones 1-16. For iO1000 only.D8RY-iO-2 Canada only: LED Annunciator module, two LEDs per zone, 16 zones (4 alarm only,

8 supervisory only, 4 alarm or supervisory). Mounts in cabinet. For iO1000 only.D8RY-iO-1 Canada only: LED Annunciator module, two LEDs per zone, 16 zones (4 alarm only,

8 supervisory only, 4 alarm or supervisory). Mounts in cabinet. For iO1000 only.

AccessoriesCTM City Tie Module. 2-gang. Connection to a local energy fire alarm box.MFC-A Multifunction Fire Cabinet, 8" x 14" x 3.5" - red.SIGA-REL Releasing ModulePT-1S System PrinterBC-1 Battery Cabinet. 14.0" x 18.25" x 7.25". Holds two 12V24A batteries.BC-1R Battery Cabinet - Red. 14.0" x 18.25" x 7.25". Holds two 12V24A batteries.BC-1EQ Seismic hardening Kit for iO series panels. Includes battery hardening for

BC-1 enclosure and components to harden panel internal components.

Programming ToolsiO-CU IO Series configuration and diagnostics utility.260097 RS232 cable, 4 conductor, DB9 PC interface