GENERAL
1. CODES: ALL CONSTRUCTION SHALL CONFORM TO THEINTERNATIONAL BUILDING CODE, 2012 EDITION AND STANDARDSREFERENCED THEREIN.
2. SAFETY: THE CONTRACTOR IS RESPONSIBLE FOR JOB SAFETY.
3. COORDINATION: THE CONTRACTOR SHALL COORDINATEARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND CIVILWORKS DOCUMENTS WITH THE STRUCTURAL CONTRACTDOCUMENTS. NOTIFICATION SHALL BE MADE, IN WRITING, TO THEARCHITECT OF ANY CONFLICT, DISCREPANCIES, OMISSIONS,AND/OR ANY VARIATIONS NEEDED IN ORDER TO COMPLY WITHCODES.
4. SITE CONDITION VERIFICATION: THE CONTRACTOR SHALL VERIFYEXISTING SITE CONDITIONS, DIMENSIONS, AND ELEVATIONS PRIORTO STARTING WORK. THE ARCHITECT SHALL BE NOTIFIED, INWRITING, OF ANY DISCREPANCIES IN EXISTING SITE CONDITIONS,DIMENSIONS, OR ELEVATIONS TO THOSE SHOWN IN THESTRUCTURAL CONSTRUCTION DOCUMENTS.
5. GENERAL DETAILS: CONSTRUCTION DETAILS NOT FULLY SHOWNOR NOTED SHALL BE SIMILAR TO DETAILS SHOWN FOR SIMILARCONDITIONS.
6. DIMENSIONS: THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS.
7. MEANS OF CONSTRUCTION: THE CONTRACTOR SHALL BERESPONSIBLE FOR MEANS, METHODS, TECHNIQUES, SEQUENCES,AND PROCEDURES OF CONSTRUCTION.
8. MATERIALS AND TESTING: THE CONTRACTOR SHALL BERESPONSIBLE FOR DOCUMENTATION OF ALL MATERIAL PROPERTIES,GRADES, STRENGTHS, ETC. THE CONTRACTOR IS ALSORESPONSIBLE FOR ALL TESTING REQUIRED TO VERIFY MATERIALSTRENGTHS. ALL TEST DATA SHALL BE DOCUMENTED ANDSUBMITTED TO THE ARCHITECT FOR REVIEW AND APPROVAL.
9. BRACING: THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THEDESIGN, CONSTRUCTION, AND ERECTION OF SAFE AND ADEQUATEBRACING, SHORING, TEMPORARY SUPPORTS, ETC. REQUIRED FORSTABILITY OF THE STRUCTURE DURING ALL INTERMEDIATE STAGESOF CONSTRUCTION UNTIL FINAL SUPPORT IS SECURELY ANCHOREDAND/OR CURED.
10.SHOP DRAWINGS: THE CONTRACTOR SHALL SUPPLY THEARCHITECT WITH CHECKED SHOP DRAWINGS BEARING THECONTRACTOR'S STAMP OF APPROVAL AND SIGNATURE. THEREVIEW OF SHOP DRAWINGS BY THE ENGINEER IS ONLY FORGENERAL COMPLIANCE WITH THE STRUCTURAL DRAWINGS ANDSPECIFICATIONS. THIS REVIEW DOES NOT GUARANTEE IN ANY WAYTHAT THE SHOP DRAWINGS ARE CORRECT AND/OR COMPLETE, NORDOES IT INFER THAT THEY SUPERCEDE THE STRUCTURALCONSTRUCTION DOCUMENTS.
11.INSPECTIONS: ANY INSPECTIONS SPECIAL OR OTHERWISE, WHICHARE REQUIRED BY THE BUILDING CODES, LOCAL BUILDINGDEPARTMENTS, OR THESE PLANS, SHALL BE DONE BY ANINDEPENDENT INSPECTION COMPANY. JOB SITE VISITS BY THEENGINEER DO NOT CONSTITUTE, OR SUBSTITUTE INSPECTIONUNLESS SPECIFICALLY CONTRACTED FOR.
12.ALTERATIONS: IN NO CASE SHALL STRUCTURAL ALTERATIONS ORWORK AFFECTING A STRUCTURAL MEMBER BE MADE UNLESSPRIOR APPROVAL IS OBTAINED BY THE STRUCTURAL ENGINEER INWRITING.
STRUCTURAL DESIGN DATA
1. LIVE LOADS:ROOF LIVE LOAD = 20 PSFCOMPRESSOR ROOM MEZZANINE = 150 PSFFLOOR FOR REVISED ELEVATOR FRAMING = 80 PSF
2. DEAD LOADS:ROOF DEAD LOAD = 15 PSFCOMPRESSOR ROOM MEZZANINE = 20 PSFFLOOR FOR REVISED ELEVATOR FRAMING = 20 PSF
3. SNOW LOAD:GROUND SNOW LOAD = 10 PSFSNOW IMPORTANCE FACTOR = 1.0
4. SEISMIC DESIGN DATA:
SEISMIC DESIGN DATA
- RISK CATEGORY = II- IMPORTANCE FACTOR = 1.0- SITE CLASS = D- MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:
S = 0.278S = 0.131
- DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:S = 0.292S = 0.199
- SEISMIC DESIGN CATEGORY = C
S1
DSD1
5. WIND DESIGN DATA:
WIND DESIGN DATA
1. BASIC WIND SPEED = 115 MPH (ULTIMATE)2. RISK CATEGORY = II3. WIND EXPOSURE CATEGORY = B4. INTERNAL PRESSURE COEFFICIENT = 0.18 +/-5. ENCLOSED STRUCTURE
COMPONENTS AND CLADDING LOADS
AREA(SF)
PRESSURE (PSF)
MAXIMUM MINIMUM
ROOFZONE 1
0-1030
100
9.60 -15.48-15.48-15.48
ROOFZONE 2
0-1030
100
-17.90-17.33-16.69
ROOFZONE 3
0-1030
100
-23.95-20.49-16.69
WALLZONE 4
0-10
500
13.0611.7210.56
-15.48-13.99-12.70
WALLZONE 5
0-10
500
-19.11-16.13-13.55
ROOF:
WALLS:
5
5
5
44
5a
a a
a
13.0611.7210.56
* WIND PRESSURES ARE BASED ON ALLOWABLE STRESS DESIGN.* INTERPOLATE FOR OTHER EFFECTIVE WIND AREAS.
100
100
3 32 23 3
3 32 23 3
2 21 12 2
a aaa
a
a
a =3.0'
9.609.609.609.609.609.609.609.60
CONCRETE & REINFORCING STEEL
1. STRENGTH: ALL CONCRETE SHALL HAVE A NORMAL WEIGHT OF145 PCF AND HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTHAS FOLLOWS:
FOUNDATIONS & RETAINING WALLS 3,500 PSI SLABS 4,000 PSI BOARD-FORMED WALLS 4,000 PSI
(GUARD STATION WALLS)
2. SLUMP: THE CONCRETE SLUMP SHALL BE 4" AT THE POINT OFPLACEMENT. THE USE OF WATER-REDUCING ADMIXTURES MAY BEUSED IF AN INCREASED SLUMP IS DESIRED FOR WORKABILITY. THESLUMP SHALL NOT EXCEED 5" WITH THE USE OF NORMAL WATER-REDUCERS & SHALL NOT EXCEED 7" WITH THE USE OF MID-RANGEOR HIGH-RANGE WATER-REDUCERS.
3. JOBSITE SLUMP CONTROL: WATER SHALL NOT BE ADDED TO THEMIX ON SITE UNLESS AN ALLOWABLE AMOUNT OF ADDITIONALWATER IS SPECIFICALLY STATED ON THE DELIVERY TICKET.
4. DOCUMENTATION: THE CONCRETE MIX DESIGN, STRENGTH, ANDALL SPECIFIED TESTING SHALL BE FULLY DOCUMENTED ANDSUBMITTED TO THE ARCHITECT FOR APPROVAL.
5. CURING: CONCRETE SLABS AND WALLS SHALL BE CURED USING ASPRAY-ON CURING COMPOUND APPLIED IMMEDIATLY AFTERFINISHING IS COMPLETED, OR BY COVERING WITH PLASTICSHEETS FOR A MINIMUM OF 7 DAYS. THE CURING COMPOUNDSHALL BE EQUAL TO W.R. GRACE 1150-CLEAR. THE CONTRACTORIS RESPONSIBLE FOR VERIFYING THE CURING COMPOUND ISCOMPATIBLE WITH ALL FLOOR FINISHES.
6. REINFORCEMENT PLACEMENT: ALL REINFORCEMENT SHALL BEBENT COLD. REINFORCEMENT SHALL NOT BE WELDED.REINFORCEMENT SHALL NOT BE WET SET IN CONCRETE.
7. INSERTS: ALL ITEMS TO BE CAST IN CONCRETE SUCH ASREINFORCING, DOWELS, BOLTS, ANCHORS, PIPES, SLEEVES,ETC. SHALL BE SECURELY POSITIONED IN THE FORMS BEFOREPLACING CONCRETE.
8. SECURING REINFORCEMENT: ALL REINFORCING STEEL &EMBEDMENTS SHALL BE SECURELY TIED AND SUFFICIENTLYSUPPORTED TO MAINTAIN THE POSITION WITHIN SPECIFIEDTOLERANCES DURING ALL CONSTRUCTION ACTIVITIES.
9. WEATHER: WEATHER CONDITIONS SHALL NOT BE ACCEPTABLEAS A VALID REASON FOR INCORRECT OR OTHERWISE POORQUALITY OF CONCRETE OR CONCRETE SURFACES.
10.REINFORCEMENT COVER: MINIMUM REINFORCEMENT COVERSHALL BE AS SHOWN IN THIS TABLE:
CONCRETE REINFORCEMENT COVER
CAST AGAINST AND PERMANENTLYEXPOSED TO EARTH:
EXPOSED TO EARTH OR WEATHER:No. 5 AND SMALLER BARSNo. 6 AND LARGER BARS
NOT EXPOSED TO WEATHER OR INCONTACT WITH THE GROUND:
STRUCTURAL SLABS & WALLSBEAMS AND COLUMNS
SLABS ON GRADE:
EXPOSURE CONDITIONMINIMUMCOVER
TOLERANCE(-)
3" 3/8"
1½" 1/4"2" 1/4"
3/4" 1/8"1½" 1/4"
2" 1/4"
11.SPLICING REINFORCEMENT: CONTINUOUS REINFORCEMENT SHALLBE PROVIDED WHEREVER POSSIBLE. REINFORCEMENT SHALL BELAP SPLICED WHEN REQUIRED AS FOLLOWS:
REINFORCEMENT LAP SLICE LENGTHS
#3
BAR SIZE LAP SPLICE LENGTH
#4
#5
#6
#7
#8
#9
22"
29"
36"
43"
63"
72"
81"
12.REINFORCEMENT STANDARD HOOKS: REINFORCEMENT SHALL BEHOOKED AS SHOWN IN THE TABLE BELOW WHEN SPECIFIED IN THEDRAWINGS:
REINFORCEMENT STANDARD HOOKSRADIUS A
#3
BAR SIZE
#4
#5
#6
#7
#8
#9
1.5"
2"
2.5"
3"
3.5"
4"
5.625"
8.5"
11"
14"
16.5"
19.5"
22"
25"
B
2.5"
2.5"
2.5"
3"
3.5"
4"
4.5"
C
4.5"
6"
7.5"
9"
10.5"
12"
13.5"
90° HOOK:RADIUS
C
AB
180° HOOK:
JOINT
STRUCTURAL STEEL
1. CODE: STEEL CONSTRUCTION SHALL BE IN CONFORMANCE WITHTHE TOLERANCES, QUALITY, FABRICATION, AND ERECTION AS SETFORTH IN CHAPTER 22 OF THE INTERNATIONAL BUILDING CODE,2012 AND THE LATEST AMERICAN INSTITUTE OF STEELCONSTRUCTION (AISC) SPECIFICATION.
2. MATERIAL: STRUCTURAL STEEL PLATES, ANGLES, ANDCHANNELS SHALL CONFORM TO ASTM A36. WIDE FLANGESHAPES SHALL CONFORM TO ASTM A992. STRUCTURAL STEELTUBING SHALL CONFORM TO ASTM A500, GRADE B (Fy=46KSI).STRUCTURAL STEEL PIPE SHALL CONFORM TO ASTM A53,GRADE B (Fy=35KSI).
3. SHOP DRAWINGS: THE CONTRACTOR SHALL SUBMIT SHOPDRAWINGS SHOWING ALL MEMBERS, SIZES, LOCATIONS, ANDCONNECTIONS TO THE ARCHITECT/STRUCTURAL ENGINEER FORAPPROVAL PRIOR TO FABRICATION.
4. FOUNDATION ANCHOR RODS: ALL FOUNDATION ANCHOR RODSSHALL BE ASTM F1554, GRADE 55, AND SHALL BE WELDABLE. ALLANCHOR RODS SHALL HAVE TWO HEAVY HEX HEAD NUTS ORHAVE A SINGLE HEAVY HEX NUT TACK WELDED TO THE SHAFT ONTHE END THAT IS ANCHORED IN CONCRETE. ALTERNATIVELY, THEANCHOR RODS MAY HAVE A HEAVY HEX HEAD FACTORY FORGEDTO THE SHAFT.
5. FOUNDATION ANCHOR ROD HOLES: ANCHOR ROD HOLES INBASE PLATES MAY BE OF THE MAXIMUM SIZE AS SPECIFIED INTABLE 14-2 OF THE AISC MANUAL. PLATE WASHERS OF THESPECIFIED MINIMUM SIZE SHALL BE USED WITH OVERSIZEDHOLES.
6. GROUTING: ALL BASE PLATES SHALL BE FULLY GROUTED WITH ANON-SHRINK GROUT THAT MEETS OF EXCEEDS ASTM C 1107,GRADES B AND C.
7. WELDING: ALL WELDING SHALL BE IN ACCORDANCE WITH THEAISC AND EXECUTED BY WELDERS QUALIFIED IN ACCORDANCEWITH THE REQUIREMENTS OF AWS D1.1. ALL WELDS SHALL BEMADE WITH E70XX ELECTRODES. ALL WELDED JOINTS SHALL BEPREQUALIFIED BY AISC.
FOUNDATIONS
1. GEOTECHNICAL REPORT: THE FOUNDATION AND SLAB-ON-GRADEDESIGN WAS BASED ON DESIGN RECOMMENDATIONS CONTAINEDIN THE GEOTECHNICAL REPORT PROVIDED BY PRECISIONENGINEERING CORPORATION (OCTOBER 16, 2017). BASED ONTHESE RECOMMENDATIONS, AN ALLOWABLE NET BEARINGCAPACITY OF 2,500 POUNDS PER SQUARE FOOT WAS USED FORTHE FOUNDATION DESIGN. THE CONTRACTOR SHALL FOLLOW THERECOMMENDED CONSTRUCTION PROCEDURES CONTAINED IN THEGEOTECHNICAL REPORT.
2. OVER-EXCAVATION: OVER-EXCAVATE THE THE EXISTING SOILS ATTHE GUARD STATIONS A MINIMUM OF 1 FOOT BELOW THEBOTTOM OF THE SLAB-ON-GRADE AND FILL WITH COMPACTEDSELECT FILL.
3. SELECT FILL: SELECT FILL MATERIAL SHALL CONSIST OF ADEBRIS FREE, NON-ORGANIC MATERIAL HAVING A LIQUID LIMIT OFLESS THAN 30 PERCENT AND A PLASTICITY INDEX BETWEEN 5PERCENT AND 15 PERCENT. SELECT FILL SHALL BE PLACED INMAXIMUM LOOSE LIFTS OF 8 INCHES AND COMPACTED TO 95PERCENT STANDARD PROCTOR DENSITY (ASTM D-698-91) WITHIN3 PERCENT OF OPTIMUM MOISTURE CONTENT. DENSITY TESTSSHALL BE CONDUCTED FOR EACH LIFT AT A RATE OF ONEDENSITY TEST PER 2,000 SQUARE FEET OF SURFACE AREA PERLIFT.
4. QUESTIONABLE SOILS: SHOULD THE CONTRACTOR ENCOUNTERUNUSUAL SOILS OR QUESTIONABLE SUBSURFACE CONDITIONS,THE STRUCTURAL ENGINEER SHALL BE CONTACTEDIMMEDIATELY.
HELICAL PILES
1. PILE CAPACITY: HELICAL PILE MINIMUM ALLOWABLE CAPACITY:
VERTICAL ALLOWABLE CAPACITY = 25 KIPS
HORIZONTAL ALLOWABLE CAPACITY = 1 KIP (THE PILE MUST BE DESIGNED TO RESIST THE 1 KIP
HORIZONTAL LOAD CONSIDERING A 6.5 FOOT PILECANTILEVER ABOVE GRADE. ALTERNATIVELY, A TIE-BACKPILE MAY BE USED FOR THE HORIZONTAL LOAD. ALL HELICAL PILES FOR LOADING DOCK 1 REQUIRE A TIE-BACK PILE, UNLESS NOTED OTHERWISE.)
TIE-BACK ALLOWABLE CAPACITY = 5 KIPS(FOR LOADING DOCK 1 TIE-BACK PILES)
A FACTOR OF SAFETY EQUAL TO 2.0 IS REQUIREDFOR HELICAL PILES.
2. INSTALLATION LOGS: INTSTALLATION LOGS SHALL BE MAINTAINEDBY THE CONTRACTOR AND SUBMITTED TO THE STRUCTURALENGINEER. THE LOGS SHALL INCLUDE PILE LOCATION, PILE TYPE(INCLUDING LEAD SECTION TYPE, EXTENSION TYPE, AND NUMBEROF EXTENSIONS USED), INSTALLATION DEPTH, INSTALLATIONTORQUE, TYPE OF TORQUE INDICATOR USED, AND COMMENTSPERTAINING TO ANY INTERRUPTIONS, OBSTRUCTIONS, OR OTHERINFORMATION.
3. TORQUE INDICATOR: THE CONTRACTOR SHALL SUBMIT DATAFOR THE TORQUE INDICATOR TO BE USED FOR INSTALLATION ANDCALIBRATION REPORTS THAT HAVE BEEN PERFORMED WITHINONE YEAR OF THE DATE SUBMITTED.
4. CORROSION PROTECTION: HELICAL PILES SHALL BE GALVANIZEDOR HAVE AN EPOXY COATING.
CONCRETE MASONRY
1. CONCRETE MASONRY UNITS: CONCRETE MASONRY UNITS SHALLBE NORMAL WEIGHT OR LIGHTWEIGHT HOLLOW-CORE (ASTM C-331), GRADE N, TYPE II, AND SHALL COMPLY WITH ASTM C 90.CONCRETE MASONRY UNITS SHALL BE CONSTRUCTED IN RUNNINGBOND.
2. STRENGTH: CONCRETE MASONRY UNITS SHALL HAVE A MINIMUMNET AREA COMPRESSIVE STRENGTH OF 1,900 PSI.
3. GROUT: GROUT SHALL HAVE A MINIMUM COMPRESSIVESTRENGTH OF 3,000 PSI AT 28 DAYS AND CONFORM TO ASTM C476.GROUT SHALL HAVE A SLUMP RANGING FROM 8" TO 11".
SLAB-ON-GRADE
1. CRACK FILLING: THE CONTRACTOR SHALL MAKE AN ALLOWANCEFOR FILLING 50 FEET OF 1/8" WIDE CONCRETE CRACKS WITH ANEPOXY CRACK FILLER.
2. CONTRACTION JOINTS: SAWCUT CONTRACTION JOINTS SHALL BEINSTALLED AS SHOWN IN THE DRAWINGS. SAWCUTCONTRACTION JOINTS SHALL BE INSTALLED AS SOON AS THECONCRETE WILL SUPPORT WORKERS AND EQUIPMENT, AND THECUTS CAN BE MADE WITHOUT DAMAGING THE SLAB. ALL JOINTSSHALL BE FILLED WITH A JOINT SEALER. THE CONTRACTORSHALL SUBMIT JOINT FILLER MATERIAL DOCUMENTATION TO THEARCHITECT FOR APPROVAL.
COLD-FORMED STEEL FRAMING
1. DESIGN: THE CONTRACTOR IS RESPONSIBLE FOR THE DESIGN OFCOLD-FORMED FRAMING SYSTEMS.
2. COATING: ALL COLD-FORMED STEEL FRAMING MATERIALS SHALLHAVE A MINIMUM G60 GALVANIZED COATING.
DEFERRED SUBMITTALS
1. DEFERRED SUBMITTALS: DEFERRED SUBMITTALS ARE THEPORTIONS OF THE BUILDING DESIGN THAT ARE NOT SUBMITTEDAT THE TIME OF THE APPLICATION FOR PERMIT AND ARE NOTINCLUDED IN THE STRUCTURAL DRAWINGS. THE CONTRACTOR ISRESPONSIBLE FOR PROVIDING THE DESIGN OF DEFERREDSUBMITTALS. THE FOLLOWING ARE DEFERRED SUBMITALLS:
- COLD-FORMED STEEL FRAMING:PROVIDE SHOP DRAWINGS SHOWING MEMBER SIZES AND ALLCONNECTIONS SEALED BY A MISSISSIPPI PROFESSIONAL ENGINEER
- GUARDRAILS & HANDRAILS:PROVIDE SHOP DRAWINGS SHOWING ALL COMPENTS AND CONNECTIONS FOR GUARDRAIL AND HANDRAIL SYSTEMS SEALED BY A MISSISSIPPI PROFESSIONAL ENGINEER.
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S1.0
STRUCTURALNOTES
2/1/
18
STRUCTURAL NOTES
GENERAL
1. SPECIAL INSPECTIONS: SPECIAL INSPECTIONS SHALL BECOMPLETED PER CHAPTER 17 OF IBC 2012. THE CONTRACTORWILL EMPLOY THE SERVICES OF A SPECIAL INSPECTOR TOPROVIDE INSPECTIONS FOR THE ITEMS LISTED IN THESTATEMENT OF SPECIAL INSPECTIONS. THE SPECIALINSPECTOR SHALL BE APPROVED BY THE ARCHITECT.
2. SPECIAL INSPECTOR: THE SPECIAL INSPECTOR SHALL BE AQUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE,TO INSPECTION OF ITEMS LISTED IN THE STATEMENT OFSPECIAL INSPECTIONS.
3. SCOPE: THE SPECIAL INSPECTION REQUIREMENTS NOTED INTHE STRUCTURAL DOCUMENTS ARE FOR BUILDINGCOMPONENTS THAT ARE WITHIN THE SCOPE OF THESTRUCTURAL ENGINEER. REFER TO OTHER PORTIONS OF THECONSTRUCTION DOCUMENTS FOR OTHER BUILDINGCOMPONENTS.
CONTRACTOR RESPONSIBILITY
1. STATEMENT OF RESPONSIBILITY: THE CONTRACTOR SHALLSUBMIT A STATEMENT OF RESPONSIBILITY TO THE BUILDINGOFFICIAL AND THE OWNER PRIOR TO THE COMMENCEMENT OFWORK ON ANY SYSTEM LISTED IN THE STATEMENT OF SPECIALINSPECTIONS. THE STATEMENT OF RESPONSIBILITY SHALLCONTAIN THE FOLLOWING:
a. ACKNOWLEDGMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL INSPECTIONS
b. ACKNOWLEDGMENT THAT CONTROL WILL BE EXERCISED TO OBTAIN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS APPROVED BY THE BUILDING OFFICIAL
c. PROCEDURES FOR EXERCISING CONTROL WITHIN THE CONTRACTOR'S ORGANIZATION, THE METHOD AND FREQUENCY OF REPORTING AND THE DISTRIBUTION OF THE REPORTS
d. IDENTIFICATION AND QUALIFICATIONS OF THE PERSON EXERCISING SUCH CONTROL AND THEIR POSITION IN THE ORGANIZATION
SPECIAL INSPECTOR RESPONSIBILITY
1. RECORD KEEPING: SPECIAL INSPECTORS SHALL KEEP RECORDSOF INSPECTIONS. THE SPECIAL INSPECTOR SHALL FURNISHINSPECTION REPORTS TO THE BUILDING OFFICIAL, OWNER,ARCHITECT, AND CONTRACTOR. REPORTS SHALL INDICATEWHETHER OR NOT WORK INSPECTED WAS DONE INCONFORMANCE TO APPROVED CONSTRUCTION DOCUMENTS.
2. FINAL REPORT: A FINAL REPORT DOCUMENTING REQUIREDSPECIAL INSPECTIONS AND CORRECTION OF ANYDISCREPANCIES NOTED IN THE INSPECTIONS SHALL BESUBMITTED AT A POINT IN TIME AGREED UPON BY THE PERMITAPPLICANT AND THE BUILDING OFFICIAL PRIOR TO THE STARTOF WORK.
3. DISCREPANCIES: DISCREPANCIES SHALL BE BROUGHT TO THEIMMEDIATE ATTENTION OF THE CONTRACTOR FORCORRECTION. IF THE DISCREPANCIES ARE NOT CORRECTED,THE DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OFTHE BUILDING OFFICIAL, OWNER, AND ARCHITECT PRIOR TO THECOMPLETION OF THAT PHASE OF WORK.
STATEMENT OF SPECIAL INSPECTIONS
1. LATERAL FORCE RESISTING SYSTEM:
- SEISMIC SYSTEM: SPECIAL INSPECTION IS NOT REQUIRED
- WIND SYSTEM: SPECIAL INSPECTION IS NOT REQUIRED
2. SOILS:
CONTRACTOR DUTIES:
A. PROVIDE THE SPECIAL INSPECTOR A COPY OF THE GEOTECHNICAL REPORT.
SPECIAL INSPECTOR DUTIES:
A. PERFORM TESTING AND MONITORING AS RECOMMENDED BY THE GEOTECHNICAL ENGINEER AND GEOTECHNICAL REPORT AND AS INDICATED IN THE DRAWINGS AND SPECIFICATIONS.
(PERIODIC INSPECTION)
B. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER MATERIAL.(PERIODIC INSPECTION)
C. PERFORM CLASSIFICATION AND TESTING OF CONTROLLED FILL MATERIALS. (PERIODIC INSPECTION)
D. VERIFY USE OF PROPER MATERIALS, DENSITIES, AND LIFT THICKNESS DURING PLACEMENT AND COMPACTION OF CONTROLLED FILL. (CONTINUOUS INSPECTION)
E. PRIOR TO PLACEMENT OF CONTROLLED FILL, OBSERVE SUBGRADE AND VERIFY THE SITE HAS BEEN PREPARED PROPERLY. (PERIODIC INSPECTION)
3. STRUCTURAL STEEL / PRE-ENGINEERED METAL BUILDING:
CONTRACTOR DUTIES:
A. SUBMIT THE MANUFACTURER'S CERTIFICATION THAT THE STEEL COMPLIES WITH THE STRUCTURAL CONSTRUCTION
DOCUMENTS:- STRUCTURAL BOLTS, NUTS, AND WASHERS- STRUCTURAL STEEL MEMBERS
B. SUBMIT STRUCTURAL STEEL SHOP DRAWINGS.
C. SUBMIT METAL BUILDING SHOP DRAWINGS(FOR MODIFICATIONS TO THE EXISTING METAL BUILDING).
SPECIAL INSPECTOR DUTIES:
A. PERFORM PERIODIC INSPECTION OF THE STEEL FRAMING TOVERIFY COMPLIANCE WITH THE DETAILS SHOWN ON THE CONSTRUCTION DOCUMENTS, SUCH AS BRACING,STIFFENING, MEMBER LOCATIONS AND PROPER APPLICATIONOF JOINT DETAILS AT EACH CONNECTION.
B. PERFORM PERIODIC INSPECTIONS TO VERIFY COMPLIANCE FOR THE FOLLOWING:
a. MATERIAL VERIFICATION OF STRUCTURAL STEEL, HIGH-STRENGTH BOLTS, NUTS, AND WASHERS.
b. SINGLE PASS FILLET WELDS ≤ 5/16"
C. VISUALLY INSPECT ALL FIELD WELDS IN ACCORDANCEWITH AWS D1.1.
D. VERIFY WELDING PROCEDURES ARE BEING ADHERED TODURING FIELD WELDING.
4. CONCRETE:
CONTRACTOR DUTIES:
A. SUBMIT CONCRETE MIX DESIGN.
B. SUBMIT MANUFACTURER'S CERTIFICATION FOR REINFORCINGSTEEL.
C. SUBMIT REINFORCEMENT SHOP DRAWINGS.
D. SUBMIT A PLAN FOR CURING PROCEDURES.
SPECIAL INSPECTOR DUTIES:
A. MATERIAL TESTING:
a. PERFORM ALL TESTING IN SECTION 033000 OF THE PROJECT SPECIFICATIONS
B. PERFORM PERIODIC INSPECTIONS TO VERIFY COMPLIANCEFOR THE FOLLOWING:
a. FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OFCONCRETE MEMBER BEING FORMED.
b. CONCRETE REINFORCEMENT FOR LOCATION, SIZE, GRADE,AND SPLICE LENGTH.
c. LOCATION OF WALL DOWELS AND OTHER EMBEDMENTS.
d. VERIFY USE OF REQUIRED DESIGN MIX.
e. VERIFY CURING PROCEDURES, TEMPERATURE, AND TECHNIQUES ARE IN COMPLIANCE WITH THE APPROVED
CURING PLAN AND THE SPECIFICATIONS.
5. POST-INSTALLED MECHANICAL AND EPOXY ANCHORS:
CONTRACTOR DUTIES:
A. SUBMIT THE MANUFACTURER'S PRODUCT DATA:
a. GENERAL PRODUCT DATA
b. INSTALLATION INSTRUCTIONS
c. ICC ES REPORT
B. ENSURE PERSONNEL INSTALLING THE ANCHORS HAVE BEEN PROPERLY TRAINED TO INSTALL THE ANCHORS PER THE MANUFACTURER'S SPECIFICATIONS.
SPECIAL INSPECTOR DUTIES:
A. REVIEW PRODUCT DATA, INSTALLATION INSTRUCTIONS, AND ICC ES REPORT AND VERIFY THE ANCHORS ARE IN COMPLIANCE WITH THE CONSTRUCTION DOCUMENTS.
B. PROVIDE CONTINUOUS INSPECTION FOR THE INSTALLATION OF THE FIRST 5 ANCHORS OF EACH TYPE AND VERIFY
COMPLIANCE WITH THE MANUFACTURER'S INSTALLATION SPECIFICATIONS. PROVIDE PERIODIC INSPECTION OF THE REMAINING POST-INSTALLED ANCHORS.
6. COLD-FORMED FRAMING:
CONTRACTOR DUTIES:
A. SUBMIT SHOP DRAWINGS FOR ALL INTERIOR AND EXTERIOR FRAMING SEALED BY A MISSISSIPPI PROFESSIONAL ENGINEER.
SPECIAL INSPECTOR DUTIES:
A. PERIODIC INSPECTIONS TO VERIFY THE FOLLOWING:
a. FRAMING MEMBER SIZE AND MATERIAL GRADE ARE IN COMPLIANCE WITH THE DRAWINGS AND SPECIFICATIONS.
b. FASTENING AND CONNECTIONS ARE IN COMPLIANCE WITH THE DRAWINGS.
7. HELICAL PILES:
CONTRACTOR DUTIES:
A. SUBMIT PRODUCT DATA FOR THE FULL PILE SYSTEM INCLUDING PILE TYPE, LEAD SECTION CONFIGURATION, BRACKET TYPE, ANDALL PILE CONNECTIONS.
B. SUBMIT CERFICIATION FROM A MISSISSIPPI PROFESSIONAL ENGINEER THAT THE HELICAL PILES ARE ACCEPTABLE FOR THE SPECIFIED LOADS.
SPECIAL INSPECTOR DUTIES:
A. CONTINUOUS INSPECTION TO VERIFY THE FOLLOWING:
a. PILE LOCATION
b. PILE TYPE (INCLUDING LEAD SECTION TYPE)
c. BRACKET TYPE
d. CONNECTION OF BRACKET AND SECTIONS OF PILE
e. INSTALLATION DEPTH
f. INSTALLATION TORQUE
g. TYPE OF TORQUE INDICATOR USED
h. COMMENTS PERTAINING TO ANY INTERRUPTIONS OR OBSTRUCTIONS
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S1.1
STRUCTURALQUALITY
ASSURANCE
2/1/
18
STRUCTURAL QUALITY ASSURANCE REQUIREMENTS
ELEVATOR ADDITION PIT INFILL &SLAB REPAIR
3S2.0
2S2.0
1S2.1
COMPRESSOR ROOM ADDITION
1S2.2
1S2.0
LOADING DOCKADDITION 1
TRASH COMPACTORADDITION
LOADING DOCKADDITION 2
1S2.3 2
S2.3
1S2.4
DOOR ADDITIONS
3S2.3
GUARD STATION
1S2.5
2S2.5
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S1.2
OVERALL BUILDINGDIAGRAMS
2/1/
18
1" = 60’−0"
BUILDING 2 DIAGRAM
1" = 60’−0"
BUILDING 3 DIAGRAM 3/16" = 1’−0"
GUARD STATION DIAGRAM
1
S3.0
5' - 9"
7' -
4"
E.B
E.1
E.4
2
S3.0
3"
4' - 0 3/4"
E.A E.C
E.2
E.3
(VERIFY)
(VE
RIF
Y)
3"
(VERIFY)
ALIGN COLUMNS WITH THEELEVATOR GUIDE RAILS
3"
4 1/4"
HELICAL PILE (TYP)
1' -
0"
1' - 0" 1' - 0"
1' -
0"
8" 8"
8"8"
FIELD VERIFY THE LOCATION OFTHESE COLUMN LINES (ALIGNWITH EXISTING FRAMING)
DETAIL/4 S3.1
DETAIL/4 S3.1
DETAIL/5 S3.1
DETAIL/5 S3.1
SUMP PIT PERDETAILVERIFY LOCATION
1
S3.0
E.B
E.1
E.4
2
S3.0
EX
IST
ING
ST
EE
LB
EA
M (
RE
MA
INS
)
EXISTING METAL BUILDINGROOF PURLING TO REMAIN E
XIS
TIN
G S
TE
EL
BE
AM
(R
EM
AIN
S)
EXISTING METAL BUILDINGROOF PURLING TO REMAIN
EXISTING METAL BUILDINGROOF PURLING TO REMAIN
EXISTING METAL BUILDINGROOF PURLING TO REMAIN
EXISTING METAL BUILDINGROOF PURLING TO REMAIN
EXISTING METAL BUILDINGROOF PURLING TO REMAIN
NEW W8X24
NEW W8X24
600S162-43, 33ksiCOLD-FORMED STEELRAFTERS AT 16" O.C.
W8X10 HOIST BEAM BELOW
NE
W W
8X10
NE
W W
8X10
THE NEW BEAM BEARS ON TOPOF THE EXISTING STEEL BEAM(TYP)
1/4TYP. EACH BEARINGLOCATION
DETAIL/3 S3.1
DETAIL/3 S3.1
DETAIL/3 S3.1
DETAIL/3 S3.1
DETAIL/13 S3.1
DETAIL/13 S3.1
DETAIL/13 S3.1
DETAIL/13 S3.1
1
S3.0
E.B
E.1
E.4
2
S3.0
EXISTING W14X22 (REMAINS)
EXISTING W14X22 (REMAINS)
W12
X14
EX
IST
ING
(R
EM
AIN
S)
W12
X14
EX
IST
ING
(R
EM
AIN
S)
EXISTING STEEL JOIST (REMAINS)
E.A E.C
EXISTING CMU WALL
EXISTING FRAMING (REMAINS)
EXISTING FRAMING (REMAINS)
EXISTING W14X22 (REMAINS)
EXISTING STEEL JOIST (REMAINS) EXISTING STEEL JOIST (REMAINS)
NEW HSS8X3X3/8COLUMN
NEW HSS8X3X3/8COLUMN
NEW OPENING FORELEVATOR ADDITION
EXISTING WOOD FLOOR FRAMINGTO REMAIN IN THIS AREA
(NOT SHOWN)
EXISTING STEEL JOIST (REMAINS)
EXISTING WOOD FLOOR FRAMINGTO REMAIN IN THIS AREA
(NOT SHOWN)
NEW HSS3X3X5/16COLUMNS
E.2
E.3
NEW HSS3X3X5/16COLUMNS
CUT OUT THIS SECTION OF STEELBEAM AND STEEL JOIST AFTER THEINSTALLATION OF THE NEW COLUMNSAND THE NEW CONNECTIONS AREFULLY COMPLETED
DETAIL/2 S3.1
DETAIL/2 S3.1
DETAIL/1 S3.1
DETAIL/1 S3.1
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S2.0
ELEVATORADDITION PLANS -
BUILDING 2
2/1/
18
1/2" = 1'-0"S2.01 ELEVATOR ADDITION FOUNDATION PLAN - BUILDING 2
1/2" = 1'-0"S2.03 ELEVATOR ADDITION ROOF FRAMING PLAN - BUILDING 2
1/2" = 1'-0"S2.02 ELEVATOR ADDITION 2ND FLOOR FRAMING PLAN - BUILDING 2
DEMOLISH DAMAGED SLAB AND CONSTRUCTNEW 6" CONCRETE SLAB PER DETAIL
FILL THE EXISTING ELECTRICTRENCH PER DETAIL
FILL THE EXISTINGPIT PER DETAIL
FILL THE EXISTINGPIT PER DETAIL
FILL THE EXISTING ELECTRICTRENCH PER DETAIL
25' -
0"
100' - 0"
37' - 6"
5' -
10"
37' - 6"
5' -
10"
49' - 3"
9' -
4"
2' -
4"
99' - 0"
2' -
4"
231' - 0"
TOTAL AREA = 90 SFTOTAL VOLUME = 1,400 CUBIC FEET
7
S3.1
CJ
CJ
CJ
CONTRACTION JOINTDETAIL
8
S3.1
12' - 6"12' - 6"12' - 6"12' - 6"12' - 6"12' - 6"12' - 6"12' - 6"
12' -
6"
12' -
6" C
J
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CONTRACTION JOINTDETAIL
CJ
CJ
CJ
CJ
CJ
CJ
12' - 3"12' - 3"12' - 3"
9' - 4 1/2"9' - 4 1/2"9' - 4 1/2"
9' - 0"9' - 0"9' - 0"9' - 0"9' - 0"9' - 0"9' - 0"9' - 0"9' - 0"9' - 0"
CONTRACTION JOINTDETAIL(TYP)
CONTRACTION JOINTDETAIL(TYP)
CONTRACTION JOINTDETAIL(TYP)
9' - 0"
TYP
9
S3.1
/6 S3.1
/6 S3.1
/6 S3.1
/6 S3.1
/6 S3.1
/7 S3.1
/9 S3.1
9
S3.1
/8 S3.1
/6 S3.1
/9 S3.1
FILL THE EXISTING ELECTRICTRENCH SIMILAR TO DETAIL /9 S3.1
DEMOLISH THE EXISTING FLOOR DRAIN
FIELD VERIFY ALL DIMENSIONS
ALTERNATE #5
VERIFY THESE VALUES
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S2.1
BUILDING 2 -RENOVATIONS
2/1/
18
1/16" = 1'-0"S2.11 PIT INFILL AND SLAB REPAIR PLAN - BUILDING 2 Copy 1
C.2C.2
C.B
C.B
C.1C.1
C.C
C.C
10' - 10" 10' - 10"
C.A
C.A
ESTIMATED EXISTINGFOUNDATION (FIELD VERIFY)
ANCHOR EACH STAIRSTRINGER TO THE CONCRETESLAB WITH (1) 3/4"Ø x 4½" HILTIKWIK BOLT 3 WEDGE ANCHOR
1' - 0"
ALIGN NEW CMU WALL WITHTHE EXISTING CMU WALL
10
S3.1
12' -
0"
C.3C.3
STOP NEW FOOTING AT THEEXISTING COLUMN FOOTING.FIELD VERIFY LOCATION
8"
8"
1' - 6" 1' - 6"
1' -
0"
1' -
3"
1' -
3"
1' - 3" 1' - 3"
1' - 6" 1' - 6"
3"1'
- 9
"
NEW 16" DEEP FOOTINGREINFORCED WITH(3) #5 BARS IN EACHDIRECTION ON BOTTOM
3"1'
- 9
"
1' - 0"
ADD (1) #5 BAR IN THEDIRECTION OF THECONTINUOUS FOOTINGREINFORCEMENT WITH(3) #5 BARS CROSS BARS
36"x36" #5 90° BARS FOR EACHCONTINUOUS FOOTING BAR ATTHE CORNER
ADD (1) #5 BAR IN THEDIRECTION OF THECONTINUOUS FOOTINGREINFORCEMENT WITH(3) #5 BARS CROSS BARS
1' -
0"
3' -
6"
EXISTING CONSTRUCTION
SEE DETAILFOR BASE PLATE(TYP)
/14 S3.1
SEE DETAIL FORCOLUMN BASE PLATE
/15 S3.1
C.2C.2
C.B
C.B
C.1C.1
C.C
C.C
C.A
C.A
10
S3.1
10' - 10" 10' - 10"1' - 0"
12' -
0"
2' -
5"
2' -
5"
2' -
5"
2' -
5"
2' -
4"
W8X10
W8X10
W8X10
W8X10
W8X10
W8X10 W8X10
W8X10
W8X10
W8X10
W8X10
W8X10
W14
X22
W14
X22
W14
X22
W6X20 W6X20 W6X20
W6X20 W6X20
W6X20
1' -
0"
3' -
6"
C.3C.3
L4X4X3/8
OPEN RISER DIAMONDPLATE STAIR TREADS
MC12X14.3
MC12X14.3
MC
12X
14.3
HSS4X4X3/16
VERIFY
1/4" DIAMOND PLATE STEEL DECKING(CONTINUOUS FOR 2 SPANS MINIMUM)
11
S3.1DEMOLISH THE EXISTING STAIRLANDING FRAMING AND STAIRS
DETAIL/12 S3.1
DETAIL/12 S3.1
DETAIL/12 S3.1
DETAIL/12 S3.1
DETAIL/12 S3.1
DETAIL/12 S3.1
DETAIL/13 S3.1
SEE DETAILFOR CMU WALLLINTEL (TYP)
/18 S3.1
EXISTING CONSTRUCTION
CMU WALL NOTES
1. REINFORCE ALL CMU WALLS WITH HORIZONTAL 9 GAUGELADDER TYPE JOINT REINFORCEMENT @ 16" O.C. & VERTICAL#5 BARS AT 32" O.C.
2. SEE DETAIL 18, S3.1 FOR CMU LINTELS
3. SEE DETAILS 16 & 17 ON S3.1 FOR CMU REINFORCING DETAILS
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S2.2
COMPRESSORROOM ADDITION
2/1/
18
1/4" = 1'-0"S2.21 FOUNDATION PLAN - COMPRESSOR ROOM ADDITION - BUILDING 2
1/4" = 1'-0"S2.22 MEZZANINE FRAMING PLAN - COMPRESSOR ROOM ADDITION - BUILDING 2
3
S3.3
2
S3.3
1
S3.4
ESTIMATED EXISTINGFOUNDATION (FIELD VERIFY)
1
S3.3
14' - 0"
ESTIMATED EXISTINGFOUNDATION (FIELD VERIFY)
NEW RETAINING WALLWITH GUARDRAIL
EXISTING COLUMN
3' - 11"
6' - 2"
3' - 11"
EXISTING COLUMN
(4) HELICAL PILES UNDERPINNINGTHE EXISTING COLUMN FOOTING
(4) HELICAL PILES UNDERPINNINGTHE EXISTING COLUMN FOOTING
NEW RETAINING WALLWITH GUARDRAIL
CONSTRUCTION JOINT BETWEENRETAINING WALL FOOTING AND DOCKWALL FOOTING. INSTALL (6) 3/4"x12"ROUND SMOOTH DOWELS CENTER ONTHE JOINT (3 ON TOP & 3 ON BOTTOM)(TYP. EACH RETAINING WALL)
SEE CIVIL FORWALL LENGTH8"8"
DEMOLISH THE EDGE OF THE EXISTING FOOTINGAS NEEDED FOR THE NEW CONCRETE WALLS(TYP. EACH SIDE OF DOCK)
NOTES:
1. THE NEW LOADING DOCK SHALL BECENTERED BETWEEN THE EXISTINGBUILDING COLUMNS.
2. THE EXISTING OVERHEAD DOORLOCATION SHALL BE MOVED TO BECENTERED ON THE LOADING DOCK.
3. THE CONTRACTOR IS RESPONSIBLE FORPROVIDING THE DESIGN OF THE NEWFRAMING AND CONNECTIONS REQUIREDFOR MOVING THE OVERHEAD DOOR.
4. THE CONTRACTOR SHALL SUBMIT SHOPDRAWINGS FOR THE NEW FRAMING,CONNECTIONS, AND TRIM REQUIREDFOR MOVING THE OVERHEAD DOORLOCATION. THE SHOP DRAWINGS SHALLBE SEALED BY A PROFESSIONALENGINEER LICENSED IN THE STATE OFMISSISSIPPI.
EXISTING FLOOR DRAINDEMOLISH AT NEW DOCK
CUT THE EXISTING SLAB OUTFOR THE INSTALLATION OF THENEW LOADING DOCKS(VERIFY THE EXTENT)C
J
CJ
CONTRACTION JOINTPER DETAIL(TYP)
/6 S3.1
CJCJ
THE CONTRACTOR MUST VERIFY ALL DIMENSIONSWITH THE DOCK LEVELER REQUIREMENTS
EXISTING LOADINGDOCK TO REMAIN
NEW RETAINING WALLWITH GUARDRAIL
EXISTING RETAININGWALL TO REMAIN
DEMOLISH EXISTINGRETAINING WALL ANDFOOTING
EXISTING LOADINGDOCK TO REMAIN
1
S3.4
S3.4 3
INSIDE EDGE OF EXISTINGGRADE BEAM (FIELD VERIFY)
3
S3.2
2
S3.2
SEE CIVIL FORWALL LENGTH
8"
EXISTING STEPSTO REMAIN
1
S3.2
EXISTING FOOTING(VERIFY)
ESTIMATED EXISTING FOOTING.DEMOLISH PORTION EXTENDINGINTO NEW LOADING DOCK AREA
CONSTRUCTION JOINT BETWEENRETAINING WALL FOOTING AND DOCKWALL FOOTING. INSTALL (6) 3/4"x12"ROUND SMOOTH DOWELS CENTER ONTHE JOINT (3 ON TOP & 3 ON BOTTOM)
2
S3.2
CUT THE EXISTING SLAB OUTFOR THE INSTALLATION OFTHE NEW LOADING DOCKS(VERIFY THE EXTENT)
SIMILAR ON EACHSIDE OF NEW DOCKS
HELICAL PILE UNDERPINNING LOCATIONWITH HELICAL PILE TIE-BACK(TYP)
THIS HELICAL PILE LOCATIONDOES NOT REQUIRE A TIE-BACK
CJ
CJ
CJ
CJ
CONTRACTION JOINTPER DETAIL(TYP)
/6 S3.1
CJ
6' -
2"
7' -
10"
6' -
2"
7' -
10"
THE CONTRACTOR MUST VERIFY ALL DIMENSIONSWITH THE DOCK LEVELER REQUIREMENTS
LOADING DOCK ADDITION SEQUENCING:
* THE STRUCTURAL DESIGN WAS BASED ON THE FOLLOWING CONSTRUCTION SEQUENCE.
1. DEMOLISH THE EXISTING SLAB FOR THE INSTALLATION OF THE HELICAL PILES.2. INSTALL THE HELICAL PILES, INCLUDING THE TIE-BACK PILES.3. INSTALL TEMPORARY SHORING AS NEEDED. THE DESIGN AND CONSTRUCTION OF TEMPORARY SHORING IS THE CONTRACTOR'S RESPONSIBILITY.4. DEMOLISH THE EXISTING FOUNDATIONS IN THE AREA OF THE NEW DOCK PITS.5. CONSTRUCT NEW FOOTINGS, WALLS, RETAINING WALLS, AND DOCK SLAB.6. CONSTRUCT NEW EXTERIOR CONCRETE PAVING AND INTERIOR CONCRETE SLAB.7. INSTALL NEW SKIM COAT ON THE NEW AND EXISTING DOCK WALLS.
EXISTING METAL BUILDING WALL GIRT (TYP)
EXISTING METAL BUILDING COLUMN
NEW WALK DOOR
NEW DOOR JAMB
CUT EXISTING WALL GIRT FORNEW WALK DOOR AND CONNECTTO NEW DOOR JAMBS
WALK DOOR ADDITION NOTES:
1. SEE ARCHITECTURAL FOR NEW WALK DOOR LOCATIONS AND SIZES.2. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS.3. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE DESIGN OF THE NEW
FRAMING AND CONNECTIONS REQUIRED FOR THE WALK DOOR ADDITIONS.4. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR THE NEW FRAMING,
CONNECTIONS, AND TRIM REQUIRED FOR THE NEW WALK DOORS. THE SHOPDRAWINGS SHALL BE SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THESTATE OF MISSISSIPPI.
* VERIFY ACTUAL FRAMING CONDITIONS. THIS DETAIL SHOWS AN ESTIMATED CONDITION.
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S2.3
LOADING DOCK &DOOR ADDITION
PLANS
2/1/
18
1/4" = 1'-0"S2.32 LOADING DOCK 2 ADDITION PLAN - BUILDING 3
1/4" = 1'-0"S2.31 LOADING DOCK 1 ADDITION PLAN - BUILDING 3
3/8" = 1'-0"S2.33 WALK DOOR ADDITION DETAIL - BUILDING 3
NEW RETAINING WALL
EXISTING CONCRETE SLAB
38' - 0"
12' -
0"
1' -
6"
3' -
11"
4' -
2"
3' -
11"
4
S3.4
SLOPE 1/8" PER FOOT
1/4" STEEL PLATE
1/4" STEEL PLATE
MATCH ELEVATION OFEXISTING SLAB
10" CONCRETE SLAB-ON-GRADE REINFORCED WITH(2) LAYERS OF #4 BARS AT 18" O.C. IN EACH DIRECTION
1' - 2"
1' - 2"
1' - 2"
1' - 2" 1' - 0"
1' - 0"
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S2.4
TRASH COMPACTORFOUNDATION PLAN -
BUILDING 3
2/1/
18
1/4" = 1'-0"S2.41 TRASH COMPACTOR FOUNDATION PLAN - BUILDING 3
VITREOUS CHINA
MO
RNINGSIDE
K-12636C_LAVATORY
A B
1
2
5" CONCRETE SLABREINFORCE WITH #4 @ 18" O.C. IN
EACH DIRECTION (1½" TOP COVER)
9"9"
9"
9'-61_2" 6'-9"1'-111_
8"
22'-115_8"
19'-115_8"
9" 1'-3"
14'-0
"
9"
12'-6
"
13'-0
"
9"
3"3"
SEE OPPOSITE SIDEFOR ALL DIMENSIONSNOT SHOWN
3"1'
-1"
1'-1
"3"
11 _ 2"
HSS6x6x3/8COLUMN
9" 9"
1'-0" 1'-0"
9"9"
CONCRETE PEDESTAL
GB1 GB2
GB
2
GB1
GB
1
GB
4
GB5
GB5 GB2
GB
3
2'-3"
21 _ 2"
HSS6x6x3/8COLUMN
SIM
SIM
VERIFY ALL DIMENSIONSWITH ARCHITECTURALDRAWINGS - TYPICAL
TAPERED COLUMNSEE 1/SG3.1
TAPERED COLUMNSEE 1/SG3.1
6" BOARD-FORMEDCONCRETE WALL ABOVE(SEE SECTION 033300 OFTHE PROJECTSPECIFICATIONS)
3/4" DIAMETERDIAGONALBRACE(A36 STEEL ROD)
3/4" DIAMETERDIAGONALBRACE(A36 STEEL ROD)
11 _ 2"21 _ 2"
INSTALL 90° CORNERBARS AT ALL GRADEBEAM INTERSECTIONSPER DETAIL 2, S3.7 (TYP)
A
1
2
B
3'-0" 1'-4" 1'-4" 1'-4" 1'-4" 1'-4" 1'-4" 1'-0"
19'-115_8"
12'-6
"
3"
31'-23_4" OUT TO OUT OF TAPERED BEAM
11'-01_8"
HSS6x6x3/8 COLUMN
HSS6x6x3/8 COLUMN
SEE DETAIL FOR PURLIN SPACING
FA
BR
ICA
TE
D P
LAT
E B
EA
M W
ITH
MO
ME
NT
CO
NN
EC
TIO
N A
T E
AC
H E
ND
SEE ARCH DWGS FORROOFING & FINISHEDROOF EDGE DETAILS(TYP)
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
HS
S3
1 / 2x3
1 / 2x3
/ 16
FA
BR
ICA
TE
D P
LAT
E C
HA
NN
EL
L2x2x3/16 ANGLE AT EACH END ANDAT THE CENTER OF THE BEAM
(3 LOCATIONS) CONNECTING PLATEBEAM TO PURLIN(SEE DETAILS)
PL1/8x5"x0'-5" SPACEDAS SHOWN ORCONTINUOUS PLATE
PL1/8x5"x0'-5" SPACEDAS SHOWN ORCONTINUOUS PLATE
(SEE OPPOSITE SIDEFOR DIMENSIONS)
SIM
SIM
3
S3.6
1
S3.6
1
S3.6
1
S3.6
2
S3.6
2
S3.6
2
S3.6
4
S3.6
6
S3.6
5
S3.6
7
S3.6
3
S3.5
S3.5
1
S3.5 2
S3.5
1
S3.5 2
4
S3.5
7
S3.7
7
S3.7
/1 S3.5
8
S3.7
7
S3.7
3
S3.5
9
S3.7
7
S3.7
11
S3.7
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S2.5
GUARD STATIONBUILDING
2/1/
18
3/8" = 1'-0"S2.51 FOUNDATION PLAN - GUARD STATION
3/8" = 1'-0"S2.52 ROOF FRAMING PLAN - GUARD STATION
TOP OF SLAB0' - 0"
TOP OF STEEL10' - 0 3/4"
2' -
0"
4' -
0"
TOP OF STEEL -ELEVATOR COLUMNS23' - 6"
E.B2
S3.0
(FIELD VERIFY)
E.A E.C
(VERIFY)
5' - 9"
3"
4 1/4"
8" 8"SEE DETAILFOR FOUNDATION NOTES
/2 S3.0 SEE DETAILFOR FOUNDATION NOTES
/2 S3.0
HOLD THE TOP HORIZONTAL WALLBAR DOWN 6" TO AVOID COLUMNWEDGE ANCHORS
HOLD THE TOP HORIZONTAL WALLBAR DOWN 6" TO AVOID COLUMNWEDGE ANCHORS
6"X4"X14 GAUGE ANGLE CONNECTEDTO EACH STUD WITH (2) #10 SCREWSAND TO THE STEEL BEAM WITHHILTI X-U PAF AT 12" O.C.
NEW W8X10 BEAM
6"X4"X14 GAUGE ANGLE CONNECTEDTO EACH STUD WITH (2) #10 SCREWSAND TO THE STEEL BEAM WITHHILTI X-U PAF AT 12" O.C.
NEW W8X10 BEAM
6" COLD-FORMED RAFTERS(600S162-43, 33ksi) WITH 5/8"PLYWOOD ROOF SHEATHINGFASTENED TO THE RAFTERS WITH#8 SCREWS AT 6" O.C. AT PANELEDGES AND 12" O.C. IN THE FIELD
5/8" PLYWOOD WALL SHEATHINGFASTENED TO THE STUDS WITH #8SCREWS AT 6" O.C. AT PANELEDGES AND 12" O.C. IN THE FIELD(TYP. EACH SIDE)
NEW W8X10HOIST BEAM
EXISTING STRUCTURE EXISTING STRUCTURE
NEW 3 5/8" COLD-FORMED STUDSAT 16" O.C. (362S162-43, 33ksi)
NEW 6" COLD-FORMED STUDSAT 16" O.C. (600S162-43, 33ksi)
EXISTING FLOOR FRAMINGAND DECKING (REMAINS)
EXISTING FLOOR SHEATHING BEARS ONTHE NEW WALL FASTEN TO THE WALLTRACK WITH #8 SCREWS AT 6" O.C.
EXISTING FLOOR FRAMINGAND DECKING (REMAINS)
NEW 3 5/8" COLD-FORMED STUDSAT 16" O.C. (362S162-43, 33ksi)
NEW 6" COLD-FORMED STUDSAT 16" O.C. (600S162-43, 33ksi)
EXISTING STEEL BEAM(REMAINS)
EXISTING STEEL BEAM(REMAINS)
2" DEEP, 18 GA MIN. DEFLECTION TRACKFASTENED TO THE STEEL BEAM WITHHILTI X-U PAF AT 16" O.C.
INSTALL 2x4 STUD BRACING AT16" O.C. TO SUPPORT THE EDGEOF THE FLOOR SHEATHING
L5X5X3/8 SILL ANGLE ANCHOREDTO CONCRETE WITH 5/8"x5" HILTIHWIK BOLT 3 ANCHORS AT 16" O.C.(VERIFY)
TOP OF SLAB0' - 0"
TOP OF STEEL10' - 0 3/4"
1
S3.0
TOP OF STEEL -ELEVATOR COLUMNS23' - 6"
E.1 E.4
(FIELD VERIFY)
(VERIFY) W8X10 HOIST BEAM
EXISTING STRUCTURE
EXISTING STRUCTURE
EXISTING FLOOR FRAMING TO BEREMOVED AT ELEVATOR OPENING
6"X4"X14 GAUGE ANGLE CONNECTEDTO EACH STUD WITH (2) #10 SCREWSAND TO THE STEEL BEAM WITHHILTI X-U PAF AT 12" O.C.
6"X4"X14 GAUGE ANGLE CONNECTEDTO EACH STUD WITH (2) #10 SCREWSAND TO THE STEEL BEAM WITHHILTI X-U PAF AT 12" O.C.
6" COLD-FORMED RAFTERS(600S162-43, 33ksi) WITH 5/8"PLYWOOD ROOF SHEATHINGFASTENED TO THE RAFTERS WITH#8 SCREWS AT 6" O.C. AT PANELEDGES AND 12" O.C. IN THE FIELD
5/8" PLYWOOD WALL SHEATHINGFASTENED TO THE STUDS WITH #8SCREWS AT 6" O.C. AT PANELEDGES AND 12" O.C. IN THE FIELD(TYP. EACH SIDE)
CONNECT EACH RAFTER TO THE TRACKWITH A CLARKDIETRICH UNI-CLIP(UCEC) WITH (3) #10 SCREWS IN THERAFTER AND TRACK (TYP)
EXISTING FLOOR FRAMINGAND DECKING (REMAINS)
EXISTING FLOOR FRAMINGAND DECKING (REMAINS)
NEW 3 5/8" COLD-FORMED STUDSAT 16" O.C. (362S162-43, 33ksi)
NEW 3 5/8" COLD-FORMED STUDSAT 16" O.C. (362S162-43, 33ksi)
EXISTING FLOOR SHEATHING BEARS ON THE NEW WALLFASTEN TO THE WALL TRACK WITH #8 SCREWS AT 6" O.C.
4' -
0"
EXISTING CONCRETE SLABCUT BACK FORCONSTRUCTION OF THENEW ELEVATOR PIT
EXISTING CONCRETE SLABCUT BACK FORCONSTRUCTION OF THENEW ELEVATOR PIT
3"7' - 4"3"
2' -
0"
8" 8"
8" CONCRETE WALL REINFORCEDWITH VERTICAL #5 BARS AT 12" O.C.AND HORIZONTAL #4 BARS AT 12" O.C.
8" CONCRETE WALL REINFORCEDWITH VERTICAL #5 BARS AT 12" O.C.AND HORIZONTAL #4 BARS AT 12" O.C.
CONTINUOUS BENTONITE WATERSTOPAROUND THE PERIMETER OF THE PIT
REINFORCE FOOTING WITH #5 BARS AT12" O.C. MAXIMUM IN EACH DIRECTIONON TOP & BOTTOM WITH A 90° HOOK ATEACH END OF THE TOP BARS (3" COVER)
VERTICAL WALL REINFORCEMENTTERMINATES IN FOOTING WITH ASTANDARD 90° HOOK (TYP)
WATERPROOFING ON WALL
3/4"x10" ROUND SMOOTH DOWELS AT18" O.C. EMBEDDED 3" IN THE EXISTINGSLAB WITH HILTI HIT-HY 200-A EPOXY
#4 CONTINUOUS
SLOPE THE SOIL BACK AS NEEDED TOCONSTRUCT THE NEW PIT. FILL BACKWITH CONCRETE
4" OF COMPACTED CRUSHEDSTONE AGGREGATE (No. 57 OR 67)
THE CONTRACTOR IS RESPONSIBLE FOR ALLNECESSARY SHORING DURING THECONSTRUCTION OF THE ELEVATOR PIT.
HELICAL PILE (SEE PLAN FOR LOCATIONS)
NEW W8X24 BEAM
NEW W8X24 BEAM
#4 AT 18" O.C.
#4 CONTINUOUS
#4 AT 18" O.C.HOLD THE TOP HORIZONTAL WALLBAR DOWN 6" TO AVOID COLUMNWEDGE ANCHORS
EXISTING STEEL BEAM(REMAINS)
1' - 6"
1' - 6"
VERIFY REQUIREDDIMENSIONS FOR PUMP
L2x2x¼ ON TWO SIDES ANCHOR EACHANGLE TO CONCRETE WITH (2) 1/2"x4"RED HEAD TRUBOLT WEDGE ANCHORS
1¼" DEEP GALVANIZEDSTEEL BAR GRATING
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S3.0
DETAILS
2/1/
18
3/4" = 1'-0"S3.01 ELEVATOR SECTION 1 - BUILDING 2
3/4" = 1'-0"S3.02 ELEVATOR SECTION 2 - BUILDING 2
3/4" = 1'-0"S3.03 ELEVATOR SUMP PIT
NEW HSS3X3X5/16 COLUMN
ADD L2X2X3/16 WEB MEMBERON EACH SIDE AS SHOWN
EXISTING STEEL JOIST
EXISTING JOIST TOBE CUT OUT
1/4
ADD (2) L2X2X1/8 ANGLES FORNEW JOIST SEAT
3/16TYP
NEW ANGLES
JOIST SEAT
TOP &BOTTOM
*THE EXISTING JOIST MUST BE SHORED PRIOR TO CUTTING MEMBERS*
NEW HSS3X3X5/16COLUMN
1/4
PL5/8X6X0'-6"
EXISTING W14X22STEEL BEAM
BEAM TO BECUT OUT
ADD 1/4" STIFFENER PLATEON EACH SIDE OF BEAM WEB
3/16
1/4
SIDE VIEW:END VIEW:
*SHORE THE STEEL BEAM DURING INTERMEDIATE STAGES OF CONSTRUCTION*
6"
1 1/2"
CONTRACTION JOINTSAWCUT UNLESS NOTED ASTOOLED ON THE PLAN
CONTRACTION JOINTS SHALL BE SAWCUT AS SOON ASTHE CONCRETE WILL ADEQUATELY SUPPORT WORKERSAND EQUIPMENT. INSTALL CONTRACTION JOINTS AT AMAXIMUM SPACING OF 16' IN EACH DIRECTION.
4" OF MDOT No. 57 OR 67STONE OR RECYCLEDCONCRETE
6" THICK CONCRETE 4,000PSI MIN. COMP. STRENGTH
#4 BARS AT 18" O.C. IN EACH DIRECTION
10 MIL. VAPORBARRIER
2"
TOP OF SLAB0' - 0"
1' - 4"
1' -
4"
1' - 4"
1' -
4"
6' - 8"
7' -
6"
6" 6"
MINIMUM MINIMUM
6"
NEW SLAB-ON-GRADE REINFORCED WITH #4 BARSAT 18" O.C. IN EACH DIRECTION (2" TOP COVER)
TURN SLAB DOWN AT PERIMETER TO BEAR ONTHE EXISTING CONCRETE AS SHOWN
9' - 4"
EXISTING CONCRETE PIT
FILL PIT WITH COMPACTED SELECT FILL(SEE SPECIFICATIONS)
4" COURSE AGGREGATE LAYERMDOT No. 57 OR No. 67
* THE CONTRACTOR MUST FIELD VERIFY ALL DIMENSIONS FOR EXISTING CONSTRUCTION
TOP OF SLAB0' - 0"
5" 5' - 0" 5"
5' - 10"
NEW SLAB-ON-GRADE REINFORCED WITH #4 BARSAT 18" O.C. IN EACH DIRECTION (2" TOP COVER)
TURN SLAB DOWN AT PERIMETER TO BEAR ONTHE EXISTING CONCRETE AS SHOWN
EXISTING CONCRETE PIT
FILL PIT WITH COMPACTEDSELECT FILL
(SEE SPECIFICATIONS)
4" COURSE AGGREGATE LAYERMDOT No. 57 OR No. 67
* THE CONTRACTOR MUST FIELD VERIFY ALL DIMENSIONS FOR EXISTING CONSTRUCTION
6"
4' -
2"
TOP OF SLAB0' - 0"
NEW SLAB-ON-GRADE REINFORCED WITH (3) #4BARS IN THE LONG DIRECTION AND #4 BARS AT18" O.C. IN THE SHORT DIRECTION (2" TOP COVER)
EXISTING CONCRETE PIT
FILL PIT WITH COMPACTEDSELECT FILL(SEE SPECIFICATIONS)
4" COURSE AGGREGATE LAYERMDOT No. 57 OR No. 67
* THE CONTRACTOR MUST FIELD VERIFY ALL DIMENSIONS FOR EXISTING CONSTRUCTION
2' - 1"
3' -
1"
6"
TOP OF SLAB0' - 0"
C.2
COMPRESSOR ROOM -TOP OF STEEL
9' - 4 1/4"
42" HIGH STEEL TUBE GUARDRAIL (SEE S1.0)
CONTINUOUS L6X6X5/16 ANCHORED TO THE CMU WALLWITH 1/2"Øx4½" HILTI KWIK BOLT 3 WEDGE ANCHORS AT24" O.C. ON THE TOP AND SIDE OF THE WALL AS SHOWN.STAGGER BOLTS ON TOP AND SIDE.GRIND CORNER OF CMU AS NEEDED FOR FLUSH FIT.MITER ANGLE AT WALL CORNER.
8" BOND BEAM WITH (1) CONTINUOUS #5 BAR (GROUT SOLID)
1 1/
2"
2"
3/16 1½ - 163/16 1½ - 16 3/16 1½ - 16
3/16 2 - 12
8" CMU WALL REINFORCED WITH VERTICAL #5BARS AT 32" O.C. AND HORIZONTAL 9 GAUGELADDER TYPE JOINT REINFORCEMENT AT 16" O.C.GROUT ALL REINFORCED CELLS
2' - 6"
6 3/4"
1' - 0"
1' -
4"
CUT OUT EXISTING SLAB FOR NEW FOOTINGREINFORCE WITH (3) CONTINUOUS #5 BARSWITH #4 CROSS BARS AT 30" O.C.
3/4"x12" ROUND SMOOTH DOWELS AT24" O.C. EMBEDDED IN EXISTING SLAB 4"WITH HILTI HIT-HY 200-A EPOXY(EACH SIDE OF FOOTING)
VERTICAL WALL REINFORCEMENT ANCHORS INFOOTING 10" WITH HILTI HIT-HY 200-A EPOXY
(VERIFY - MATCH EXISTING)
C.1
COMPRESSOR ROOM -TOP OF STEEL
9' - 4 1/4"
EXISTING STEEL PLATEDECKING
EXISTING CMU WALL
EXISTING STEEL FRAMINGNOT SHOWN
ANCHOR THE EXISTING STEEL PLATE TOTHE CMU WALL WITH 1/2"Øx4½" HILTI KWIKBOLT 3 WEDGE ANCHORS AT 24" O.C.
BUTT THE NEW STEEL PLATE TOTHE EXISTING STEEL PLATE FORA FLUSH SURFACE 5/8 16
NEW PLATE TO EXISTING EDGE ANGLEGRIND SMOOTH
DEMOLISH THE EXISTING GUARDRAILLOCATED ON TOP OF THIS WALL. REPLACETHE EXISTING EDGE ANGLE AS NEEDED IFDAMAGED DURING RAIL DEMOLITION
(VERIFY - MATCH EXISTING)
3/16 1½ - 163/16 1½ - 16
3/16 1½ - 16
1½ - 24GRIND SMOOTH
COMPRESSOR ROOM -TOP OF STEEL
9' - 4 1/4" (4) 3/4" A325BOLTS
1/4
1 3/4"1 3/4"
2 1/
4"2
1/4"
PL5/8
3/8" STIFFENER PLATE(EACH SIDE OF WEB)
BACKGOUGE TYP.T & B FLANGE
5/16
PL3/8
4 1/2"
1 1/2"
5 1/
2"
1 1/
4"3"
1 1/
4"
PL1/4
(2) 3/4" A325 BOLTS
3/16
COPE THE TOPOF THE BEAM
3 1/2" 3 1/2"
3 1/
4"6
1/4"
4 3/
4"
2" 2"
(4) 5/8"Øx6" HILTI KWIK BOLT 3 WEDGE ANCHORS
3/16
PL1/2
CMU WALL ONTHIS SIDE
3 1/
2"3
1/2"
3 1/2" 3 1/2"
(4) 5/8"Øx4½" HILTI KWIK BOLT 3 WEDGE ANCHORS
PL1/2
5"5"
5" 5"3/16
REINFORCE & GROUT(3) CELLS AT CORNERS
SE
E N
OT
ES
ON
S2.
2
SEE NOTES ON S2.2
CENTER IN WALL
8" BOND BEAM BLOCKS REINFORCEDWITH (1) CONTINUOUS #5 BAR
#5 90° BAR LAP SPLICE ADJACENTBOND BEAM REINFORCEMENT
24"
24"
LINTEL GROUTED SOLID FORTHE FULL DEPTH
LIN
TE
L D
EP
TH
LINTEL BLOCK
MAXIMUMOPENING
WIDTH
LINTELDEPTH
REINFORCEMENT
4'-0" 8" (1) #5 BAR
8'-0" 16" (2) #5 BAR
3/16
EXISTING ROOF PURLIN CUTFOR NEW ELEVATOR
L5x3x1/4x0'-5"
CONNECT THE EXISTING PURLINTO THE ANGLE WITH (6) 1/4"SELF-DRILLING SCREWS
1/2"
SIDE & BOTTOM WITH1/2" RETURN AT TOP
1 3/4" 1 3/4"
6"6"
1/4
PL5/8
(2) 3/4"x6" GALVANIZED HILTI KWIKBOLT 3 WEDGE ANCHORS
1 1/
2"1
1/2"
1 3/4" 1 3/4"
8"8"
1/4
PL5/8
(2) 3/4"x6" GALVANIZED HILTI KWIKBOLT 3 WEDGE ANCHORS
1 1/
2"1
1/2"
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S3.1
DETAILS
2/1/
18
1" = 1'-0"S3.11 STEEL JOIST / COLUMN CONNECTION - ELEVATOR ADDITION
1" = 1'-0"S3.12 STEEL BEAM / COLUMN CONNECTION - ELEVATOR ADDITION
1 1/2" = 1'-0"S3.16 CONCRETE SLAB DETAIL - INTERIOR
1/2" = 1'-0"S3.17 PIT FILL 1
1/2" = 1'-0"S3.18 PIT FILL 2
1/2" = 1'-0"S3.19 PIT FILL 3
1" = 1'-0"S3.110 SECTION AT NEW CMU WALL - COMPRESSOR ROOM ADDITION
1" = 1'-0"S3.111 SECTION AT EXISTING CMU WALL - COMPRESSOR ROOM ADDITION
1" = 1'-0"S3.112 STEEL BEAM / COLUMN MOMENT CONNECTION
1" = 1'-0"S3.113 STEEL BEAM / BEAM CONNECTION
1" = 1'-0"S3.114 BASE PLATE - W6X20
1" = 1'-0"S3.115 BASE PLATE - HSS4X4X3/16
3/4" = 1'-0"S3.116 CMU WALL REINFORCEMENT DETAIL
3/4" = 1'-0"S3.117 CMU WALL BOND BEAM REINFORCEMENT DETAIL
3/4" = 1'-0"S3.118 CMU LINTEL SCHEDULE
1 1/2" = 1'-0"S3.13 PURLIN TO BEAM CONNECTION - ELEVATOR ADDITION
1" = 1'-0"S3.14 BASE PLATE 1
1" = 1'-0"S3.15 BASE PLATE 2
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
3
S3.2
2
S3.2
6"6"
8"8"
CONTINUOUS L3x3x1/4WITH 1/2"x6" HEADEDSTUDS AT 12" O.C.
#5 BARS AT 16" O.C. IN EACHDIRECTION ON TOP & BOTTOM(3" BOTTOM COVER & 2" TOP COVER)
VERTICAL WALL REINFORCEMENTTERMINATES IN FOOTING WITH A 90° HOOK
VERTICAL WALL REINFORCEMENTTERMINATES IN SLAB WITH A 90° HOOK
VERTICAL #5 BARSAT 18" O.C.
HORIZONTAL #4 BARSAT 8" O.C.
#4 BARS AT 18" O.C. IN EACHDIRECTION (2" TOP COVER)
SEE NOTES ONOPPOSITE SIDE
1' -
0"
MIN
IMU
M
3"3"
8' - 0"
DOCK LEVELER(NOT SHOWN)
6"
8"8"
SEE NOTES ONOTHER DOCK
1' -
0"
3"3"
8' - 0"
HELICAL PILES UNDERPINNINGEXISTING FOOTING / GRADE BEAM
EXISTING METALBUILDING COLUMN
EXISTINGFOOTINGBEYOND
EXISTING METALBUILDING STRUCTURE
ESTIMATED EXISTING FOUNDATION(FIELD VERIFY ACTUAL CONDITIONS)
MIN
IMU
M
EXISTING DOCK WALL(FIELD VERIFY)
EXISTING METALBUILDING COLUMN
NEW DOCK WALL FOOTING BEYOND
NEW WALL DOCK WALL TIESINTO EXISTING DOCK WALLWITH 3/4"x12" ROUND SMOOTHDOWELS AT 12" O.C. EMBEDDEDIN EXISTING WALL 4" WITHHILTI HIT-HY 200-A EPOXY
3/4"x12" ROUND SMOOTHDOWELS AT 12" O.C. EMBEDDEDIN EXISTING SLAB 4" WITH HILTIHIT-HY 200-A EPOXY
3/4"x12" ROUND SMOOTH DOWELSAT 12" O.C. EMBEDDED INEXISTING SLAB 4" WITHHILTI HIT-HY 200-A EPOXY
NEW FOOTING TIES INTOEXISTING FOOTING WITH3/4"x12" ROUND SMOOTHDOWELS EMBEDDED INEXISTING FOOTING 4" WITHHILTI HIT-HY 200-A EPOXY(3) DOWELS ON TOP & BOTTOM(6 TOTAL)
EXISTING FOOTING BEYOND
DOCK LEVELER(NOT SHOWN)
6' - 2"6' - 2"
THE CONTRACTOR MUST VERIFY ALL DIMENSIONSWITH THE DOCK LEVELER REQUIREMENTS
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
-5.50'
8' - 3"
10"
8"
3' - 0"
1' -
6"
6"
4' -
0"
2' -
8"
-4.00'
DOCK LEVELER(NOT SHOWN)
CONTINUOUS L3x3x1/4WITH 1/2"x6" HEADEDSTUDS AT 12" O.C. (TYP.AROUND PERIMETER)
CONTINUOUS L3x3x1/4WITH 1/2"x6" HEADEDSTUDS AT 12" O.C.
SITE PAVINGSEE CIVIL
REINFORCE FOOTING WITH (3) #6 BARS ONTOP & BOTTOM WITH #3 TIES AT 24" O.C.(3" COVER)
VERTICAL #5 BARS AT 16" O.C.
HORIZONTAL #4 BARS AT 8" O.C.
VERTICAL WALL REINFORCEMENT DOWELSIN FOOTING WITH A 90° HOOK
3/4" ASPHALTIC EXPANSIONJOINT. SEAL THE TOP OFTHE JOINT WITH CAULK
#5 BARS AT 16" O.C. IN EACHDIRECTION ON TOP & BOTTOM(3" BOTTOM COVER & 2" TOP COVER)
VERTICAL WALLREINFORCEMENTTERMINATES INFOOTING WITH A90° HOOK
VERTICAL WALL REINFORCEMENTTERMINATES IN SLAB WITH A 90° HOOK
VERTICAL #5 BARSAT 18" O.C.
HORIZONTAL #4 BARSAT 8" O.C.
#4 BARS AT 18" O.C. IN EACHDIRECTION (2" TOP COVER)
1' -
8"
1' -
0"
1' -
7 1
/2"
1' - 0"
FLAT AREA
SLOPE 1/2"
7' - 3"
THE CONTRACTOR MUST VERIFY ALL DIMENSIONSWITH THE DOCK LEVELER REQUIREMENTS
VERIFY (SEE CIVIL)
1' - 1"
1
S3.2
TOP OF SLAB0' - 0"
1
S3.2
6"
EXISTING FOUNDATION(VERIFY)
3/4"x12" ROUND SMOOTHDOWELS AT 12" O.C. EMBEDDEDIN EXISTING SLAB 4" WITH HILTIHIT-HY 200-A EPOXY
#4 BARS AT 18" O.C. IN EACHDIRECTION (2" TOP COVER)
48" LONG #4 BARS AT12" O.C. EMBEDDED INEXISTING FOOTING 8"WITH HILTI HIT-HY 200-AEPOXY
HELICAL PILE TIE-BACK
-5.50'
1' -
6"
3' - 0"
1' - 1"
4' -
0"
-4.00'
VERIFY (SEE CIVIL)
HELICAL PILE UNDERPINNINGTHE EXISTING FOUNDATION
FILL THE EXCAVATION WITHCONCRETE AS SHOWN
EXISTING METAL BUILDING
VERTICAL #5 BARS AT 16" O.C.
HORIZONTAL #4 BARS AT 8" O.C.
VERTICAL WALL REINFORCEMENTDOWELS IN FOOTING WITH A 90° HOOK
REINFORCE FOOTING WITH (3) #6 BARS ONTOP & BOTTOM WITH #3 TIES AT 24" O.C.(3" COVER)
SITE PAVINGSEE CIVIL
3/4" ASPHALTIC EXPANSIONJOINT. SEAL THE TOP OFTHE JOINT WITH CAULK
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S3.2
DETAILS
2/1/
18
3/4" = 1'-0"S3.21 LOADING DOCK ADDITION 1, SECTION 1 - BUILDING 3
3/4" = 1'-0"S3.22 LOADING DOCK ADDITION 1, SECTION 2 - BUILDING 3
3/4" = 1'-0"S3.23 LOADING DOCK ADDITION 1, SECTION 3 - BUILDING 3
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
3
S3.3
2
S3.3
6"6"
8"8"
CONTINUOUS L3x3x1/4WITH 1/2"x6" HEADEDSTUDS AT 12" O.C.
#5 BARS AT 16" O.C. INEACH DIRECTION ONTOP & BOTTOM(3" BOTTOM COVER &2" TOP COVER)
VERTICAL WALLREINFORCEMENTTERMINATES INFOOTING WITH A90° HOOK
VERTICAL WALLREINFORCEMENTTERMINATES IN SLABWITH A 90° HOOK
VERTICAL #5 BARSAT 18" O.C.
HORIZONTAL #4 BARSAT 8" O.C.
#4 BARS AT 18" O.C. IN EACHDIRECTION (2" TOP COVER)
SEE NOTES ONOPPOSITE SIDE
1' -
0"
MIN
IMU
M
3" 3"
8' - 0"
DOCK LEVELER(NOT SHOWN)
HELICAL PILESUNDERPINNINGEXISTING FOOTING
NEW DOCK WALL FOOTING BEYOND
HELICAL PILESUNDERPINNINGEXISTING FOOTING
EXISTING METALBUILDING COLUMN3/4"x12" ROUND SMOOTH
DOWELS AT 12" O.C.EMBEDDED IN EXISTINGSLAB 4" WITHHILTI HIT-HY 200-A EPOXY
EXISTING METALBUILDING COLUMN
EXISTING FOUNDATION(FIELD VERIFY)
EXISTING FOUNDATION(FIELD VERIFY)
3/4"x12" ROUND SMOOTH DOWELS AT12" O.C. EMBEDDED IN EXISTING SLAB4" WITH HILTI HIT-HY 200-A EPOXY
NEW WALL DOCK WALL TIES INTOEXISTING FOUNDATION WITH3/4"x12" ROUND SMOOTH DOWELSAT 12" O.C. EMBEDDED INEXISTING FOUNDATION 4" WITHHILTI HIT-HY 200-A EPOXY
NEW WALL DOCK WALL TIES INTOEXISTING FOUNDATION WITH3/4"x12" ROUND SMOOTH DOWELSAT 12" O.C. EMBEDDED INEXISTING FOUNDATION 4" WITHHILTI HIT-HY 200-A EPOXY
THE CONTRACTOR MUST VERIFY ALL DIMENSIONSWITH THE DOCK LEVELER REQUIREMENTS
TOP OF SLAB0' - 0"
REINFORCE FOOTING WITH (3) #6 BARS ONTOP & BOTTOM WITH #3 TIES AT 30" O.C.(3" COVER)
VERTICAL #5 BARS AT 16" O.C.
HORIZONTAL #4 BARS AT 8" O.C.
VERTICAL WALLREINFORCEMENT DOWELS INFOOTING WITH A 90° HOOK
-5.50'
-4.00'1' - 0"
(6) #4 BARSAS SHOWN
3' - 0"
1' -
6"
6" 8"
1
S3.3
TRENCH DRAIN - SEE CIVIL
#4 BARS AT 24" O.C.
3/4" ASPHALTIC EXPANSIONJOINT. SEAL THE TOP OFTHE JOINT WITH CAULK
VERIFY (SEE CIVIL)
4' -
0"
#4 90° DOWELS AT 18" O.C.
18"
18"
WALL PANEL LEDGEMATCH EXISTING
1' - 1"
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
-5.50'
8' - 3"
10"
8"
3' - 0"
1' -
6"
6"
6"
4' -
0"
2' -
8"
-4.00'
DOCK LEVELER(NOT SHOWN)
CONTINUOUS L3x3x1/4WITH 1/2"x6" HEADEDSTUDS AT 12" O.C. (TYP.AROUND PERIMETER)
CONTINUOUS L3x3x1/4WITH 1/2"x6" HEADEDSTUDS AT 12" O.C.
TRENCH DRAIN - SEE CIVIL
1' - 0"
#4 BARS AT 24" O.C.
REINFORCE FOOTING WITH (3) #6 BARS ONTOP & BOTTOM WITH #3 TIES AT 30" O.C.(3" COVER)
VERTICAL #5 BARS AT 16" O.C.
HORIZONTAL #4 BARS AT 8" O.C.
VERTICAL WALL REINFORCEMENT DOWELSIN FOOTING WITH A 90° HOOK
3/4" ASPHALTIC EXPANSIONJOINT. SEAL THE TOP OFTHE JOINT WITH CAULK
#5 BARS AT 16" O.C. IN EACHDIRECTION ON TOP & BOTTOM(3" BOTTOM COVER & 2" TOP COVER)
VERTICAL WALLREINFORCEMENTTERMINATES INFOOTING WITH A90° HOOK
VERTICAL WALL REINFORCEMENTTERMINATES IN SLAB WITH A 90° HOOK
VERTICAL #5 BARSAT 18" O.C.
HORIZONTAL #4 BARSAT 8" O.C.
#4 BARS AT 18" O.C. IN EACHDIRECTION (2" TOP COVER)
1' -
8"
1' -
0"
1' -
7 1
/2"
1' - 0"
FLAT AREA
SLOPE 1/2"
(6) #4 BARSAS SHOWN
VERIFY (SEE CIVIL)
1
S3.3
7' - 3"
1' - 1" 1' - 11"
THE CONTRACTOR MUST VERIFY ALL DIMENSIONSWITH THE DOCK LEVELER REQUIREMENTS
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S3.3
DETAILS
2/1/
18
3/4" = 1'-0"S3.31 LOADING DOCK ADDITION 2, SECTION 1 - BUILDING 3
3/4" = 1'-0"S3.33 LOADING DOCK ADDITION 2, SECTION 3 - BUILDING 3
3/4" = 1'-0"S3.32 LOADING DOCK ADDITION 2, SECTION 2 - BUILDING 3
TOP OF SLAB0' - 0"
SITE PAVEMENTSEE CIVIL
-5.50'
TOP OF FOOTING
FOOTING MAY STEP UP AS THE ELEVATIONINCREASES AWAY FROM THE BUILDING. THETOP OF FOOTING MUST BE AT LEAST 12" BELOWTHE BOTTOM OF PAVING.SEE DETAIL FOR FOOTING STEP
3/4" ASPHALTIC EXPANSION JOINT BOARDWITH THE TOP SEALED WITH CAULK
NEW CONCRETE PAVINGSEE CIVIL
CHAMFER WALLCORNERS
STEEL PIPE SAFETY RAILING
10"
VERTICAL #5 BARS AT 16" O.C.
HORIZONTAL #4 BARS AT 12" O.C.
1' -
6"
4' - 0"REINFORCE WITH (4) CONTINUOUS #5 BARS ONTOP & BOTTOM WITH #5 CROSS BARS AT 30" O.C.(3" COVER)
WALL REINFORCEMENT DOWELSIN FOOTING WITH 90° HOOK
1' - 7" 1' - 7"
/2 S3.4
1' - 6"
2' - 0"
2' - 0"
TYP.
TYP.
VE
RIF
Y
"Z" STEP BAR FOREACH FOOTING BARSAME SIZE AS FOOTINGBARS
TOP OF SLAB0' - 0"
EXISTING WIDE FLANGE STEEL COLUMNS
3
S3.2
2
S3.2
EXISTING GIRTEXISTING GIRT
NEW WALL GIRT AT DOOR HEAD
NEW DOOR JAMB NEW DOOR JAMB EXISTING DOOR
EXISTING PIT WALLFOOTING (FIELD VERIFY)
EXISTING PIT WALLNEW CONCRETE WALLEXTENDS TO EDGE OFBUILDING UNDER THEEXISTING FOOTING
NEW FOOTING
NEW RETAINING WALL
RESURFACE THE NEW AND EXISTINGCONCRETE WALL WITH A MINIMUM 1/8"THICK SKIM COAT FOR A CLEANUNIFORM APPEARANCE (QUIKRETEQUIKWALL OR APPROVED ALTERNATIVE)
OVERHEAD DOOR ADDITION NOTES:
1. SEE ARCHITECTURAL FOR NEW OVERHEAD DOOR LOCATIONS AND SIZES.2. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS.3. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE DESIGN OF THE NEW
FRAMING AND CONNECTIONS REQUIRED FOR THE OVERHEAD DOOR ADDITIONS.4. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR THE NEW FRAMING,
CONNECTIONS, AND TRIM REQUIRED FOR THE NEW OVERHEAD DOORS. THESHOP DRAWINGS SHALL BE SEALED BY A PROFESSIONAL ENGINEER LICENSED INTHE STATE OF MISSISSIPPI.
* VERIFY ACTUAL FRAMING CONDITIONS. THIS DETAIL SHOWS AN ESTIMATED CONDITION.
EXISTING GIRTEXISTING GIRT
1' -
6"
EXISTING BUILDINGFOUNDATION (VERIFY)
2"
3"
10"
6" 6"
#4 BARS @ 18" O.C.IN EACH DIRECTION
(1) #5 BAR CONTINUOUSAROUND THE PERIMETER
TOP #4 BARS TURN DOWNINTO THE SLAB EDGE WITHA 90° HOOK
CONTINUOUS 1/4"x28" STEELPLATE WITH (3) ROWS OF5/8"x4" STUDS AT 30" O.C.
CONCRETE DRAINAGEGUTTER (SEE CIVIL)
MIN
IMU
M
6" OF MDOT No. 57 OR 67 STONEOR RECYCLED CONCRETE
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S3.4
DETAILS
2/1/
18
3/4" = 1'-0"S3.41 LOADING DOCK RETAINING WALL - BUILDING 3
3/4" = 1'-0"S3.42 FOOTING STEP
1/4" = 1'-0"S3.43 LOADING DOCK ADDITION 1 ELEVATION - BUILDING 3
3/4" = 1'-0"S3.44 TRASH COMPACTOR SLAB SECTION - BUILDING 3
A B
11'-01_8"19'-115_
8"
7'-7
3 _ 4"
12'-1
01 _ 4"
31'-23_4" OUT TO OUT OF TAPERED BEAM
4'-0
"3'
-6"
2'-3"
HSS6x6x3/8 COLUMN
TAPERED BEAMDETAIL
TAPEREDCOLUMN
FITTED STIFFENERSALIGNED WITH COLUMN
6" BOARD-FORMEDCONCRETE WALL
8"
3"
2'-6
"
TOP CORNER OFTAPERED FRAME
TOP CORNER OFTAPERED BEAM
COLUMNPEDESTAL
FACE OF TAPEREDCOLUMN
WINDOW WALLSEE ARCH DWGS
SEE ARCHITECTURAL &CIVIL DRAWINGS FORWALKWAYS & PAVING
GRADE BEAM SEEPLAN
CONCRETE FILLBELOW GRADE BEAMSEE DETAIL
BRICK VENEERSEE
ARCHITECTURAL
10"
(3) 1/2 " x 5" HEADED CONCRETEANCHORS WELDED TO THE STEELCOLUMN AND EMBEDDED INCONCRETE WALL (TYP)
2'-8"
41_4"
WORKPOINT
2'-8"2'-8"
2'-8"
2'-33_4"
2'-8"
2'-8"
2'-8"
2'-8"
2'-8"1'-9"
11"1'-11"
1 212'-6"
9" 11'-0" 9"
4'-0
"
14'-0"
9" 9"
∅3/4" DIAGONALBRACES(A36 STEEL ROD)
TAPERED COLUMN
8"2'
-6"
COLUMN PEDESTAL
GRADE BEAM SEEPLAN
SEE ARCH DWGS
SEE ARCH DWGS
ROOF
TAPERED COLUMN
2 112'-6"
1'-0"1'-1"1'-0" 1'-1" 10'-4"
14'-6"
HSS6x6x3/8
8"
9"
2'-6
"
4'-0
"
9"
6" BOARD-FORMED CONCRETE WALL
COLUMN PEDESTAL
CONCRETE SLAB
PLYWOOD ROOFSHEATHING (SEE S1.0)
PURLINS SEE PLAN
FABRICATED BEAM
A
TYPICAL DIAGONAL BRACEEND CONNECTION
EACH END OF DIAGONAL BRACESSHALL BE THREADED AND BEARAGAINST THE COLUMN WEB WITHSLOPED WASHERS, FLAT WASHERS,& HEAVY HEX NUTS (TYP)
4"
3"
12'-1
01 / 4
"
TO
P O
F S
TE
EL
3" 81_2"
1'-2
1 _ 2"
31'-2 3/4"
7'-7
3 _ 4"
11 _ 2"
COLUMN FLANGEPL3/8x6" CONTINUOUS
COLUMN WEBPL1/4 TAPERED CONTINUOUS
HAUNCH STIFFENERPL3/8x6"
TOP & BOTTOM FLANGESPL3/8x6" CONTINUOUS
BEAM WEBPL1/4 TAPERED CONTINUOUS
SEE FOUNDATION DETAILSFOR BASE PLATE & ANCHORROD INFORMATION
CONCRETE PEDESTAL
3"
ALL FLANGES AND WEBS FORTAPERED MEMBERS SHALL
APPEAR TO BE CONTINUOUS(UN-SPLICED)
END PLATEPL3/8x6"x 0'-4"
6'-3
3 _ 4"
3"7"
SLOPED WASHER
COLUMN WEB
FLAT WASHER
HEAVY HEX NUT
3/4" DIAMETER BRACE
TYP3/16
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
/4 S3.5
/1 S3.6
TOP OF SLAB0' - 0"
4
S3.5
TOP OF SLAB0' - 0"
S3.65
S3.710
S3.710
MIRROR
TOP OF SLAB0' - 0"
5
S3.7
6
S3.7
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S3.5
DETAILS
2/1/
18
3/8" = 1'-0"S3.51 SIDE ELEVATION - GUARD STATION
3/8" = 1'-0"S3.52 END ELEVATION - GUARD STATION
3/8" = 1'-0"S3.53 BUILDING SECTION - GUARD STATION
1" = 1'-0"S3.54 STEEL FRAME DETAIL - GUARD STATION
18"
18"
1'-4"
2'-6
"
4'-0
"
BRICK VENEERSEE ARCHITECTURAL
REINFORCE SLAB WITH #4 BARS AT 18" O.C.IN EACH DIRECTION (11/2" TOP COVER)
350S125-43 COLD-FORMED STUDS (3 1/2" DEEP, 18 GA.)AT 16" O.C. WITH 7/16" OSB SHEATHING (SEE S1.0)
(2) #6 TOP & BOT
#3 TIES @ 24" oc
8"
2"
51_2"
DOWN5"
VAPOR BARRIER (SEE ARCH.)10 MIL. MINIMUM
GROUT SOLID BEHIND BRICK VENEER TO HEIGHTOF WEEPHOLES OR EXTERIOR SIDEWALKS &PAVING. SEE ARCH & CIVIL DWGS. - TYPICAL
3/4" ASPHALTIC EXPANSION JOINT BOARDSEALED WITH CAULK AT THE TOP
ALLOWABLE CONSTRUCTION JOINT LOCATION. ROUGHEN SURFACEBEFORE CONCRETE SETS UNLESS NOTED OTHERWISE. CLEAN ANDWET THOROUGHLY BUT REMOVE ALL SURFACE WATER BEFORETOPPING WITH NEW CONCRETE.
#4 90° DOWELS @ 24" O.C.
3"
3" 3"
CONCRETE FILLBELOW GRADE BEAMSEE DETAIL
CONCRETE WALKWAY ORPAVING WHERE SHOWN ONARCH OR CIVIL DWGS. (TYP)
18"
18"
4'-0
"3'
-6"
3" 3"
CONCRETE WALL SEE PLANFOR LOCATION
2'-0
"2"
#4 BARS @ 12" O.C. VERTICAL& 10" O.C. HORIZONTAL
CONTINUOUS BENTONITEWATERSTOP
2"3"
3" 3"
5"
8"
3'-2
"
1'-4"
(2) #6 TOP & BOT
#3 TIES @ 24" oc
CONCRETE FILLBELOW GRADE BEAMSEE DETAIL
REINFORCE SLAB WITH #4 BARS AT 18" O.C.IN EACH DIRECTION (1 1/2" TOP COVER)
VAPOR BARRIER (SEE ARCH.)10 MIL. MINIMUM
#4 90° DOWELS @ 24" O.C.
VERTICAL WALLREINFORCEMENTEMBEDS INFOUNDATION 24"
18"
18"
1'-4"
4'-0
"
BAR CLEARANCE(TYP)
5"
8"
2"3"
3" 3"
2'-6
"
(2) #6 TOP & BOT
#3 TIES @ 24" oc
CONCRETE FILLBELOW GRADE BEAMSEE DETAIL
REINFORCE SLAB WITH #4 BARS AT 18" O.C.IN EACH DIRECTION (1 1/2" TOP COVER)
VAPOR BARRIER (SEE ARCH.)10 MIL. MINIMUM #4 90° DOWELS @ 24" O.C.
BASE PLATE PLANPEDESTAL PLAN
1/4
3'-2
"
1'-6"
TAPERED FRAME COLUMNSEE DETAIL
1'-4
" M
IN
6" 6"
6"6"
8"
(2) #5 "U" BARS
3"
3/4 " DIAGONAL BRACESEE DETAIL
GRADE BEAMSEE PLAN
1'-0"
41 _ 2"
41_2"
1'-0
"
11 _ 2"
9" 9"
41_2"
41 _ 2"
PL3/4(4) 3/4" DIA. ANCHOR RODSEMBEDDED 16" (SEE S1.0)
(3) #3 TIES AT 2" O.C. ATTOP THEN 8" O.C.
GRADE BEAM REINFORCEMENT RUNSCONTINUOUS THROUGH COLUMNPEDESTAL WITH 90° BARS
2"
2" 2"
2"
9" 9"
9"9"
1" CHAMFER ON ALLCORNERS
REINFORCE PEDESTAL WITH(2) VERTICAL #5 "U" BARS
LEVELING NUTS &NON-SHRINK GROUT
CONCRETE FILLBELOW GRADE BEAMSEE DETAIL
BASE PLATE PLAN
5/16
1'-0" 1'-1"
8"
9"
2'-6
"
4'-0
"
3"
1'-4
"
CONTINUOUS GRADEBEAM REINFORCEMENTSEE DETAIL
3"
4"1'
-4"
1'-4
" 3'-6
"
1/2 " x 5" HEADED CONCRETE ANCHORSWELDED TO THE STEEL COLUMN ANDEMBEDDED IN CONCRETE WALL (TYP)
HORIZONTAL #4 BARS @ 12" O.C.PROVIDE 18"x18" 90° BARS AT EACH CORNERFOR ALL HORIZONTAL REINFORCEMENT(VERTICAL REINFORCEMENT NOT SHOWN)
HEADED CONCRETE ANCHOR(SEE NOTE ABOVE)
2'-1"
HSS6x6x3/8 COLUMN
2"
51 _ 2"
31_2" 81_
2"
7"7"
1'-2
"
7"
1'-0"
6" BOARD-FORMED CONCRETE WALL(SEE ARCHITECTURAL FOR FORM LAYOUT)
51 _ 2"
PL3/4(4) 3/4" DIA. ANCHORRODS EMBEDDED 16"(SEE S1.0)
(2) #5 "U" BARS
(3) #3 TIES AT 2" O.C. ATTOP THEN 8" O.C.(AROUND "U" BARS)
CONCRETE FILLBELOW GRADE BEAMSEE DETAIL
PAINT ALL BELOW GRADESTEEL AND BOLTS WITHBASF MasterSeal 615COATING (MIN. (2) COATS) LEVELING NUTS &
NON-SHRINK GROUT
REINFORCE SLAB WITH #4 BARS AT 18" O.C.IN EACH DIRECTION (1 1/2" TOP COVER)
5"
3'-4
"8"
1'-6"
2"
9" 9"
2'-6
"
3"
3" 3"
10"
(2) #6 TOP & BOT
#3 TIES @ 24" O.C.
CONCRETE FILLBELOW GRADE BEAMSEE DETAIL
3'-4
"8"
1'-4"
2"
2'-6
"
3"
3" 3"
10"
(2) #6 TOP & BOT
#3 TIES @ 24" oc
CONCRETE FILLBELOW GRADE BEAMSEE DETAIL
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
/4 S3.5
/2 S3.5
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
TOP OF SLAB0' - 0"
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S3.6
DETAILS
2/1/
18
1" = 1'-0"S3.61 PERIMETER FOUNDATION SECTION AT BRICK (GB1)- GUARD STATION
1" = 1'-0"S3.62 PERIMETER FOUNDATION SECTION AT CONCRETE WALL (GB2) - GUARD STATION
1" = 1'-0"S3.63 INTERIOR GRADE BEAM SECTION (GB3) - GUARD STATION
1" = 1'-0"S3.64 PEDESTAL SECTION - GUARD STATION
1" = 1'-0"S3.65 COLUMN FOOTING SECTION - GUARD STATION
1" = 1'-0"S3.66 GB4 SECTION - GUARD STATION
1" = 1'-0"S3.67 GB5 SECTION - GUARD STATION
3" VARIES
6"
COLUMN WEBPL1/4 CONTINUOUS
COLUMN FLANGEPL3/8x6" CONTINUOUS
TYPICAL BOTHFLANGES3/16
BEAM WEBPL1/4 CONTINUOUS
TOP & BOTTOM FLANGEPL3/8x6" CONTINUOUS
VA
RIE
S
TYPICAL TOP &BOT FLANGE
3" 3"
6"
3/16
1/4 2
2 -183/16
23/16
61_4"
5"
ROOF PURLINS SEE PLAN
BRICK VENEER ALIGNED WITH OUTSIDEEDGE OF STEEL BEAM FLANGE(SEE ARCHITECTURAL DWGS)
VERIFY LOCATION OF OUTSIDE FACE OFROOF EDGE SUPPORT ANGLE WITHARCHITECTURAL DWGS (TYP)EACH SIDE OF
PURLIN TYP
TYPE "A" CONTINUOUS ROOF EDGE SUPPORT:1/4" BENT PLATE WITH 7" HORIZONTAL AND31/2" VERTICAL LEG
ANGLECONNECTION
WELDS TAPERED ROOF BEAM
VA
RIE
S
TY
PIC
AL
350S125-43 COLD-FORMED STUDS(3 1/2" DEEP, 18 GA.) AT 16" O.C. WITH7/16" OSB SHEATHING (SEE S1.0)
INSTALL A DEFLECTION TRACK AT THE TOP OF THE WALL
MINIMUM 3/8" COMPRESSIBLEJOINT BETWEEN BEAM AND BRICK
PL1/8x5"x0'-5" SPACED AT 16" O.C. OR CONTINUOUS PLATE (SEE PLAN)
2"
PLYWOOD ROOFSHEATHING (SEE S1.0)
PLAN AT CORNER
3/16
3/16
61_4"
VERIFY OFFSET DIMENSION WITH ARCH DWGS
3" 81_2"
TYPE "B" CONTINUOUS ROOF EDGESUPPORT: 1/4" BENT PLATE WITH 9"HORIZONTAL LEG AND 31/2"VERTICAL LEG
TAPERED COLUMN
TAPERED BEAM
FULL WIDTH OF BEAM& COLUMN FLANGE
5" LONG ABOVE EACH FRAME.2" LONG @ 18" O.C. BETWEEN FRAMES
END PURLIN CENTERED OVER GRIDLINE & DIAGONAL BRACING BELOW
7" ±
TYPICAL DIAGONAL BRACE
TAPERED FRAME BELOW
MITER ROOF EDGE ANGLES AND FULLY WELDALL CORNER MEMBERS TOP AND BOTTOM TOPROVIDE FOR A SMOOTH, SEAMLESSAPPEARANCE
TYPE "A" EDGE SUPPORT ANGLE
TYPE "B" EDGE SUPPORT ANGLE
1'-2
1 _ 2"
ROOF PURLIN
BRICK VENEERSEE ARCHITECTURAL
350S125-43 COLD-FORMED STUDS(3 1/2" DEEP, 18 GA.) AT 16" O.C. WITH
7/16" OSB SHEATHING (SEE S1.0)
CONNECT STUDS TO THEPURLIN WITH A FRAMING CLIP(SEE COLD-FORMED STEELSHOP DRAWINGS)
3/162 - 6
TAPERED BEAM
PURLINSSEE PLAN
HSS6x6x3/8 COLUMN
FABRICATED PLATE BEAM WITHHEIGHT AND SLOPE OF FLANGESEQUAL TO THE FLANGES OF THETAPERED BEAM. FLANGES SHALLBE PL3/8x5" & WEB SHALL BE PL 1/4
3/8" CONN.PLATE
STIFFENERS FAR SIDE
PLYWOOD ROOFSHEATHING (SEE S1.0)
L2x2x3/16 x0'-8" ANGLE LOCATEDNEAR EACH END OF THE BEAMAND IN THE CENTER OF THE BEAM
(3 LOCATIONS ALONG BEAM)
FABRICATED 3/16" PLATE CHANNEL WITHHEIGHT AND SLOPE EQUAL TO THE FLANGESOF THE TAPERED BEAM. COPE EACH END TOFIT FLUSH WITH THE PLATE BEAM &CONTINUOUSLY FILLET WELD TO THE PLATEBEAM WEB AND FLANGES FOR A SEALEDCONDITION. GRIND WELD SMOOTH.
BEAM SECTION
3/16
1/41/4
1/4
1/4
3/163/16
TYPICAL TYPE "A" ROOFEDGE SUPPORT
HSS6x6x3/8 COLUMN
FULL HEIGHT FITTEDCONNECTION PLATEPL3/8x31/2 WITH (2) 3/4 " BOLTS
(2) PL3/8 FULL HEIGHT FITTEDSTIFFENERS. ALIGN WITH COLUMNWALLS
MA
TC
H T
AP
ER
ED
BE
AM
HE
IGH
TS
LOP
E O
F T
OP
& B
OT
TO
MF
LAN
GE
S W
ILL
VA
RY
TOP & BOTTOMFLANGE - TYP
61_4"
WEB TOFLANGE
5"
5"PLAN AT CORNER
3/16
3/16
51_4"
ROOF PURLIN SEE PLAN
TYPICAL ROOF DECK
TAPERED BEAM SEETYPICAL DETAILS
VERIFY OFFSET DIMENSIONWITH ARCH DWGS.
TYPE "C" CONTINUOUS ROOFEDGE SUPPORT. 1/4" BENTPLATE WITH 9" HORIZONTALLEG AND 31/2" VERTICAL LEG
TAPERED FRAME BELOW
TYPE "A" EDGE SUPPORT ANGLE
TYPE "C" EDGE SUPPORT ANGLE
FULL WIDTH OF BEAMFLANGE - TYPICAL
5" LONG ABOVE EACH TAPEREDBEAM. 2" LONG @ 18" O.C.BETWEEN FRAMES.
ROOF PURLIN
MITER ROOF EDGE ANGLES ANDFULLY WELD ALL CORNER MEMBERSTOP AND BOTTOM TO PROVIDE FOR ASMOOTH, SEAMLESS APPEARANCE
FINISHEDGRADE SEE CIVIL
NEW CONCRETE FOUNDATION
1'-0
"
SEE PLAN
SE
E D
ET
AIL
S
EXISTING SUBGRADE(SEE SPECIFICATIONS)
OVEREXCAVATE EXISTING SOIL ANDPLACE 1 FOOT OF COMPACTEDSELECT FILL BENEATH THE SLAB(SEE SPECIFICATIONS)
CONCRET FILL BELOW GRADE BEAM(MAY BE POURED WITH GRADE BEAM OR BEFORE)
36"x36" #6 "L" BARS TIE ALL GRADE BEAMREINFORCEMENT INTO ADJACENT GRADEBEAM (2 BARS TOP & 2 BARS BOTTOM)
ALL PIPE PENETRATIONS THROUGHCONCRETE BEAMS, FOOTINGS, &SLABS, SHALL BE SLEEVED SO THEREIS A MINIMUM OF 3/4" CLEARANCEAROUND THE PIPE
LOCATE THE PENETRATION AT MID-DEPTHIF IT IS NOT POSSIBLE TO LOCATE IT BELOWTHE BEAM OR FOOTING
ALL PIPES SHALL BE LOCATED BELOWBEAMS AND FOOTINGS WHERE POSSIBLE
#4 BARS (TYP.)
SLAB BLOCKOUT,PENETRATION ORCOLUMN
1 1/2" TYP.
MIN. 24" LONGDIAGONAL #4
12" TYP.
DA
TE
:
RE
VIS
ION
S:
DR
AW
NB
Y:
CH
EC
KE
D B
Y:
SHEET #:
RE
VIS
ION
S
NO
.D
AT
ED
ES
CR
IPT
ION
BY
MIL
WA
UK
EE
ELE
CT
RIC
TO
OL
EX
PA
NS
ION
PH
AS
E II
IG
reen
woo
d, M
S
965 Highway 51, Suite 3 - Madison, MS 39110(601) 898-1295 S3.7
DETAILS
2/1/
18
1" = 1'-0"S3.75 TAPERED COLUMN DETAIL
1" = 1'-0"S3.76 TAPERED BEAM DETAIL
1" = 1'-0"S3.77 WALL SECTION AT STEEL FRAME - GUARD STATION
1" = 1'-0"S3.78 ROOF EDGE SECTION, LOW SIDE - GUARD STATION
1" = 1'-0"S3.79 ROOF FRAMING SECTION - GUARD STATION
1" = 1'-0"S3.710 ROOF FRAMING SECTION 2 - GUARD STATION
1" = 1'-0"S3.711 ROOF FRAMING SECTION 3 - GUARD STATION
3/4" = 1'-0"S3.71 EARTHWORK DETAIL - GUARD STATION
3/8" = 1'-0"S3.72 GRADE BEAM INTERSECTION
3/4" = 1'-0"S3.73 PLUMBING PENETRATION DETAIL
3/4" = 1'-0"S3.74 SLAB PENETRATION DETAIL