COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER...
-
Upload
corinne-mader -
Category
Documents
-
view
213 -
download
1
Transcript of COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER...
![Page 1: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/1.jpg)
COPPER PIPE SIZING PROGRAMProVersion
![Page 2: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/2.jpg)
PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline)
ENTER START PRESSURE say 40m=392.4 kPa
ENTER NUMBER OF DWELLINGS
LENGTH TO WORST CASE
HEIGHT DIFFERENCE between start and end locations
ANSWERS
Keep clicking anywhere to proceed
392.4
30
12
15
3.0
10
40 m
15
Min residual head
10
32
1.937
0
1.94
![Page 3: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/3.jpg)
CHECK WITH CODE
ANSWERS
40 m
15
10
RESIDUAL HEAD IS 10mPressure Drop = start – Ht. diff – residual
= 40 – 15 – 10 = 15m
Pressure Drop 15 m
392.4
30
12
15
3.0
10
32
1.937
0
1.94
![Page 4: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/4.jpg)
392.4
30
12
15
3.0
10
32
1.937
0
1.94
CHECK WITH CODE Pressure Drop = 15m
From Code table 3.2, flow from 12 dwellings = 1.94 L/s
From table C1 the closest higher flow for length 30m is 2.02 L/s.This gives the required pipe size = 32mm
![Page 5: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/5.jpg)
392.4
30
12
15
3.0
10
32
1.937
0
1.94
A table is also produced showing the capacities of each pipe section
![Page 6: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/6.jpg)
32
1.937
0
1.94
A table is also produced showing the capacities of each pipe sectionFrom previous: Pressure Drop = 15mSize from previous = 32.
Length = 30
Agrees with resultsFlow = 2.02
CODE
![Page 7: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/7.jpg)
Ability to enter fixtures as well as dwellings
22
10
10
5
5
1.25
Flow is calculated
Flow is transferred to main screen
Flow is totalledFixed Flows ie Hose Reels can be added
![Page 8: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/8.jpg)
If the pressure is too low, pump duty is calculated
Use this pressure as the start pressure to calculate pipe sizes when using the pump.
![Page 9: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/9.jpg)
HOW TO SIZE A LARGE JOBDraw a diagrammatic
Level 2
Level 1
Ground
Name all the fixtures
CWR 1
Roof
3530
2124
3030
65
110
170
230 400
Name all the fixturesSum the Loading Units from the table given in the notes section)Enter the Parameters & press calculate
WC Sk
To other parts of the project
To Street main or Pump
392.4
30
12
15
3.0
10
32
1.937
0
1.94
![Page 10: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/10.jpg)
SCROLL DOWN TO THE RESULTS TABLE
32
1.937
0
1.94
Level 2
Level 1
Ground
CWR 1
Roof
3530
2124
3030
65
110
170
700 870
WC Sk
To other parts of the project
To Street main or Pump
Read off the required size for each pipe section, using the LU’sChoose the size that can carry the given LU’s or more (never less)
Draw the size on the diagramatic
2525
32
40
50
![Page 11: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/11.jpg)
ADVANTAGES OVER THE CODE
QUICKER AND EASIER
THIS PROGRAM PRODUCES A TABLE FOR EVERY POSSIBLE PRESSURE DROP WITH NO UPPER LIMIT
THE CODE PRESSURE DROP TABLES ARE IN INCREMENTS OF UP TO 5M, AND ONLY GO UP TO 35M
THE INDEX LENGTH IS ALSO INCREMENTED BY 5M
THIS PROGRAM PRODUCES A TABLE FOR EVERY POSSIBLE INDEX LENGTH
THE ADVANTAGE OF THIS IS THAT THERE IS NO NEED TO INTERPOLATE BETWEEN THE FIGURES IN THE TABLES, OR ACCEPT A POSSIBLY LARGER SIZE THAN REQUIRED.
![Page 12: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/12.jpg)
Further Information and Notes
![Page 13: COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.](https://reader038.fdocuments.in/reader038/viewer/2022110304/5519b75a55034660578b4835/html5/thumbnails/13.jpg)