Com Power Pfc05en (Web)

download Com Power Pfc05en (Web)

of 20

Transcript of Com Power Pfc05en (Web)

  • 8/10/2019 Com Power Pfc05en (Web)

    1/20

    About

    Power Factor Correction

    Solutions for

    Energy Efficiency

    For internal distribution only

  • 8/10/2019 Com Power Pfc05en (Web)

    2/20

    Power Factor Correction:true solution for improving

    Energy Efficiencyfor our customers

    PFC Line of Business

    550 people

    6 industrial facilities

    60 business specialists

    in the world

    2

  • 8/10/2019 Com Power Pfc05en (Web)

    3/20

    3

    Summary

    What is Power Factor Correction?

    Customer benefits

    Offer panorama

    They have trusted us

    Revelant documents and links

    Contacts

    4

    6

    8

    16

    19

    20

  • 8/10/2019 Com Power Pfc05en (Web)

    4/20

    What is Power Factor Correction?

    Definition of Power Factor

    The active power P (kW)is the real power transmitted to loads such as motors, lamps, heaters,

    computers. The electrical active power is transformed into mechanical power, heat or light.

    In a circuit where the applied r.m.s. voltage is Vrms and the circulating r.m.s. current is Irms, the

    apparent power S (kVA)is: S = Vrms

    x Irms

    The apparent power is the basis for electrical equipment rating.

    The Power Factor is the ratio of the active power P (kW) to the apparent power S (kVA).

    =P(kW)

    S(kVA)

    Reactive power

    /

    Harmonics

    Active Power

    (kW)

    Apparent power

    (kVA)

    Power Factor is deteriorated by:

    reactive power(when voltage

    and current are phase-shifted)

    harmonics(when voltage or

    current are distorted)

    4

  • 8/10/2019 Com Power Pfc05en (Web)

    5/20

    Power Factor Correction

    In electrical networks, reactive power and harmonics result in increased line currents for a given active

    power transmitted to loads. The principle of Power Factor Correctionis to reduce the apparent Power

    S(kVA) for a given active Power P(kW).

    Power Quality auditsand installation of Power Monitoring systemsare the preliminary steps to be

    proposed to customers. This will provide a full knowledge of the electrical installation characteristics in

    terms of Power Factor and Harmonic distortion. Compensation of reactive power/energy or harmonicmitigation will be selected accordingly.

    Compensation of reactive power/energy

    Generally, the electricity bill includes components related to active and reactive power absorbed over

    time (active and reactive energy).

    Compensation of reactive energy is typically achieved by producing reactive energy close to the

    consuming loads, through connection of capacitor banks to the network. Then, only the active energy

    has to be supplied by the energy supplier.

    Harmonic mitigation

    Operation of active harmonic filter is identical to a noise-cancellation headset:

    The active filter injects currents on the network, eliminating the distortion

    Power losses and disturbances are reduced

    Reactive energy supplied and

    billed by the energy provider.

    00,51

    1,5

    2

    -0,5-1

    -1,5-2

    0

    0,51

    1,5

    2

    -0,5-1

    -1,5

    -2

    + =

    = =

    00,5

    11,5

    2

    -0,5-1

    -1,5

    -2

    00,51

    1,5

    2

    -0,5

    -1-1,5-2

    00,51

    1,5

    2

    -0,5

    -1-1,5-2

    00,5

    11,5

    2

    -0,5-1

    -1,5

    -2

    Before After

    Power

    generation

    Active energy

    Reactive energy

    Transmission

    network

    Active energy

    Reactive energyMotor

    Power

    generation

    Transmission

    networkMotor

    Active energy Active energy

    Reactive energy

    Capacitor

    The reactive power is supplied

    by capacitors. No billing of

    reactive power by the energy

    supplier.

    Harmonicgenerators

    Activefilter

    ResultMV

    Harmonic

    M

    Harmonicgenerators

    Activefilter

    5

  • 8/10/2019 Com Power Pfc05en (Web)

    6/20

    Customer benefits

    Save on the electricity bill: reduce Opex

    Eliminating penalties on reactive energy and decreasing kVA demand,

    Reducing power losses generated in the transformers and conductors

    of the installation, thus reducing CO2 emission.

    Example:

    Loss reduction in a 630 kVA transformer

    PW = 6,500 W with an initial Power Factor = 0.7.

    With power factor correction, we obtain a final Power Factor = 0.98. The losses

    become: 3,316 W, i.e. a reduction of 49%.

    Increase available power

    Allowing a better use of electrical equipment. Example: The power

    available at the secondary of a MV/LV transformer can be increased by

    fitting Power Factor Correction equipment on the low voltage side.

    The table opposite shows the increased available power at the

    transformer output through improvement of the Power Factor from 0.7

    to 1.

    Reduce installation size: reduce Capex

    Installing power factor correction equipment allows

    conductor cross-section to be reduced, since less current is

    absorbed by the compensated installation for the same

    active power.

    The opposite table shows the multiplying factor for theconductor cross-section with different power factor values.

    Power

    factor

    Increased

    available

    power

    0.7 0 %

    0.8 +14 %

    0.85 +21 %

    0.90 + 28 %

    0.95 +36 %

    1 +43 %

    Power

    factor

    Cable cross

    section

    multiplying

    factor

    1 1

    0.95 1.05

    0.9 1.1

    0.85 1.17

    0.8 1.25

    0.7 1.43

    6

  • 8/10/2019 Com Power Pfc05en (Web)

    7/20

    Improve Power Quality

    Harmonics are responsible of different nuisances:

    Deterioration of the supply voltage quality,

    Stress of the electrical network and potential equipment damage,

    Disruption of normal operation and increased operating costs,

    Overheating of transformers, motors and cables, thermal tripping of protective devices

    and logic faults of digital devices,

    Reduction of equipment life span by elevated operating temperature.

    Active Harmonic Filtersprovide the best technical and cost effective solution.

    Equipment such as welders, induction furnaces, lifts, crushers are generating:

    Rapid and frequent load variations,

    Fast and large voltage fluctuations at the users level,

    Light flicker and disturbances of sensitive equipment.

    Electronicor Hybrid Var Compensators, based on Active Harmonic Filter technology, can

    solve this problem.

    Provide voltage support on weak grids

    Renewable energy generators such as wind turbines, solar panels and small hydrogenerators are generally connected on weak grids,

    Voltage support is requested by the Utilities in order to avoid large voltage fluctuations.

    In all these situations, the best result is obtained with fast and continuous reactive energy

    compensation.

    Improve electricity availability and business performance

    Power Factor Correction equipments provide solutions for an optimized use of Electricity:

    Increased reliability and equipment lifetime,

    Reduced risks of outage,

    Increased productivity & quality.

    7

  • 8/10/2019 Com Power Pfc05en (Web)

    8/20

    Offer panorama

    LV metallic capacitors

    VarplusCan / VarplusBox

    VarplusCan

    Construction Extruded aluminium can

    Voltage 230 V - 690 V 400 V - 690 V 400 V - 600 Vrange

    Power range 1 50 kvar 5 15 kvar 6.5 100 kvar 6.5 25 kvar(three-phase)

    Overcurrent 1.5 x IN 1.8 x IN 2.5 x IN 1.8 x IN 2.5 x IN

    Mean life Up to 100,000 h Up to 130,000 h Up to 160,000 h Up to 130,000 h Up to 160,000 hexpectancy

    Safety Self-healing + pressure-sensitive disconnector + discharge device

    Dielectric Metallized polypropylene Double metallized paper Metallized polypropylene Double metallized paperfilm with Zn/Al alloy + Polypropylene film film with Zn/Al alloy + Polypropylene film

    Ambient -25- Max 55C/Class D -25- Max 70C -25- Max 55C/Class D -25- Max 70Ctemperature

    PE90132

    PE90131

    PE90130

    +

    PE90131

    SDuty HDuty Energy HarmonicHDuty HarmonicEnergy

    8

  • 8/10/2019 Com Power Pfc05en (Web)

    9/20

    VarplusBox

    Steel sheet enclosure

    380 V - 690 V 380 V - 690 V

    2.5 100 kvar 6.5 100 kvar

    1.5 x IN 1.8 x IN 2.5 x IN 1.8 x IN 2.5 x IN

    Up to 100,000 h Up to 130,000 h Up to 160,000 h Up to 130,000 h Up to 160,000 h

    Self-healing + pressure-sensitive disconnector + discharge device

    Metallized polypropylene Double metallized paper Metallized polypropylene Double metallized paperfilm with Zn/Al alloy + Polypropylene film film with Zn/Al alloy + Polypropylene film

    -25- Max 55C/Class D -25- Max 70C -25- Max 55C/Class D -25- Max 70C

    PE90135

    PE90136

    +

    +

    PE90154

    PE90164

    PE90137

    PE

    90134

    PE90135

    SDuty HDuty Energy HarmonicHDuty Harmonic Energy

    9

  • 8/10/2019 Com Power Pfc05en (Web)

    10/20

    Service voltage (V) 230 to 690/50Hz 240 to 600 / 60Hz

    Rated voltage (V) Up to 690V

    kvar range 2.5 to 20

    Protection system HQ protection system built into each single phase element:

    - high current fault protection by HRC cartridge fuse

    - low current fault protection by combination of single

    phase internal overpressure device with the HRC fuse

    Installation All positions are convenient except vertical one with

    connecting terminals upside down

    Temperature class D (+55 C)

    Overcurrent + 30 % permanently

    Harmonics Up to 50% non-linear loads with detuned reactor

    LV plastic capacitors / modules / capacitor banks

    Varplus2 capacitors

    Varpact modules

    Varset capacitor banks

    Service voltage 400V / 50Hz

    kvar range 12.5 to 120

    Connection Cable / busbar

    Configuration Single / double

    Harmonics Classic:15% non-linear loadsComfort:15 to 25% non-linear loads

    Harmony:25 to 50% non-linear loads

    Temperature max: 40 C around the capacitor bank (electrical room)

    Installation Horizontal or vertical

    Options Circuit breaker

    Service voltage 400V / 50Hz

    kvar range 7.5 to 1200

    Harmonics Classic: 15% non-linear loads

    Comfort:15 to 25% non-linear loads

    Harmony:25 to 50% non-linear loads

    Enclosure Wall-mounted or free-standing

    Protection IP31

    Temperature max: 40 C around the capacitor bank (electrical room)

    Options Circuit breaker

    Transient-free switching (VarsetFast)

    10

  • 8/10/2019 Com Power Pfc05en (Web)

    11/20

    Power Factor Controllers

    The Varlogic controllers permanently

    monitor the reactive power of the

    installation and control the connection

    and disconnection of capacitor steps

    in order to obtain the targeted power

    factor

    Benefits

    Permanent monitoring of the network and equipment;

    Providing information on equipment status;

    Alarm signals transmitted in case of anomaly;

    Communication by Modbus protocol (Varlogic NRC12)

    Simplicity

    Simplified programming and possibility of intelligent self

    set-up,

    Ergonomic layout on control buttons.

    User-friendlinessThe large display allows:

    Direct viewing of installation electrical information and

    capacitor stage condition;

    Direct reading of set-up configuration;

    Intuitive browsing in the various menus (indications,

    commissioning, configuration);

    Alarm indication.

    Performance Access to a wealth of network and capacitor bank data;

    New control algorithm designed to reduce the number of

    switching operations and quickly attain the targeted power

    factor.

    Simplified installation and set-up

    Quick and simple mounting and wiring;

    Insensitive to current transformer polarity and phase

    rotation polarity;

    A special menu allows controller self-configuration.

    Monitoring and protection

    Alarms

    Should an anomaly occur on the network or the capacitor

    bank, alarms are indicated on the screen and alarm contact

    closure is initiated;

    The alarm message is maintained on the screen once the

    fault clears until it is manually removed.

    Protection If necessary, the capacitor steps are automatically

    disconnected to protect the equipment.

    Varlogic RT6/8/12

    Varlogic NR6/12

    Varlogic NRC12

    11

  • 8/10/2019 Com Power Pfc05en (Web)

    12/20

    Harmonic Active Filters

    The right choice for each needSchneider Electric is specialised in harmonic mitigation objectives and is therefore offering a broad

    range of solutions for every demand.We propose solutions which maximize the savings when balanced with the cost of the harmonic

    mitigation equipment to get a reasonable Return On Investment (ROI). We propose two different

    ranges of active filters: AccuSine SWP and AccuSine PCS which cover a large extent of customer

    needs. Their main characteristics are summarized below.

    AccuSine SWP AccuSine PCS

    UPS, Air handling system

    UPS, ground power systems

    HVAC, Lifts

    HVAC, Lifts

    Drilling, extraction pumps

    Port cranes

    Pumps, UV treatment

    Welders, handling equipment

    Crushers, conveyors

    Pumps, fans, winch

    Cable cars, ski lifts

    Three or four wire connection (3 phase or 3 phase +

    Neutral) 400V supply, other voltages possible with transformers

    Units from 20A to 120A, with possible parallel operation

    up to 480 A

    Cancellation up to the 25th harmonic.

    Neutral harmonic correction at 3 times unit rating.

    Three wire connection

    From 230 V to 480 V supply (higher voltage level possible withtransformer).

    Filtering at network level, units from 50 A to 300 A, with possi-

    ble parallel operation up to 3000 A.

    Cancellation up to the 50th harmonic.

    PE90051

    PE90052

    64568

    12

  • 8/10/2019 Com Power Pfc05en (Web)

    13/20

    MV capacitors

    Description

    A medium-voltagePropivar NGcapacitor takes the form of a metalenclosure with terminals on top. This enclosure contains a set of

    capacitor elements. Wired in series-parallel groups, they can form

    unit elements of high power for high network voltages.

    CompositionThe capacitor elements forming the Propivar capacitors are made of:

    aluminium sheet armatures,

    polypropylene films,

    a PCB, chlorine-free dielectric fluid.

    Main characteristicsPropivar capacitors have a long service life increased by their thermal

    resistance and their low losses, their chemical stability and their

    resistance to over-voltage and over-current.

    Wide temperature range

    Chemical stability

    High over-voltage and over-current resistance

    Other caracteristics

    Operating frequency 50 Hz or 60 Hz

    Temperature range -25 to +50C

    Average loss factor at 20C after

    stabilization

    0.16 W/kvar with internal fuses

    0.12 W/kvar without internal fuse

    Maximum nominal reactive power Three-phase capacitor 600 kvar

    Double-phase capacitor 800 kvar

    Single-phase capacitor 1000 kvar

    Single-phase Propivar NG

    13

  • 8/10/2019 Com Power Pfc05en (Web)

    14/20

    Industrial application

    Applications Motor compensation Industrial compensation Industrial compensationFixed bank Automatic bank Automatic bank

    Reference CP214 CP214SAH* CP253 CP253SAH*

    Three-lines diagrams

    Maximum voltage Up to 12 kV Up to 12kV Up to 12 kV

    Connection mode Three-phase capacitors with delta connection Three-phase capacitors Three-phase capacitorsup to 900 kvar, up to 900 kvar,single-phase capacitors single-phase capacitorswith double star with double star

    connection above connection above

    Type of protection HRC fuses (**) HRC fuses HRC fuses

    Maximum power**** 2 x 450, i.e. 900 kvar Up to 4500 kvar Up to 4000 kvar

    Comments

    * SAH: Detuning Reactor

    ** HRC: High Rupturing Capacity

    *** CT: Current Transformer

    **** For larger power rating, please contact us

    CP 214 CP 227SAH CP 253 CP 254

    PE90107

    PB1

    01996_

    SE

    PB1

    02003_

    SE

    PB1

    02001_

    SE

    DE90082

    DE90082

    DE90082

    DE90082

    MV capacitor banks

    Up to 900kvar: with 3-phase

    capacitors. Above 900kvar:

    single-phasecapacitors with

    double star conection

    14

  • 8/10/2019 Com Power Pfc05en (Web)

    15/20

    All applications Energy application

    Global compensation Distribution system Distribution system Distribution Fixed bank Large sites Fixed bank and Transport system Automatic bank Fixed bank

    CP227 CP254 CP229 CP230

    Up to 36kV From 12 to 36 kV Up to 36 kV Above 36 kV

    Single-phase capacitors with double star connection Single-phase capacitorswith double star

    or H connection

    Unbalance by CT*** Unbalance by CT*** and relayand relay

    12 x 600, i.e. 7200 kvar 12 x 480, i.e. 5760 kvar Please contact us Please contact us

    SAH* on request SAH* on request SAH* on request SAH* on request

    CP 229 CP 230

    PE90108

    PE90084

    DE90082

    DE90082

    DE90082

    DE90082

    15

  • 8/10/2019 Com Power Pfc05en (Web)

    16/20

    They have trusted us

    LV capacitor bank

    Customer: Ministry of Electricity & Water, Kuwait

    Stakes

    With increasing load, MEW needed immediate measures for reducing energy consumption. MEW was

    facing problems of transformer and switchgear failures, in an overloaded distribution network.

    A solution was investigated, without any change in the electricity tariff which is amongst the lowest in

    the world. Till a recent past, there was no regulation for reactive energy compensation.

    HVAC and lighting constitutes to more than 80% of energy comsumption

    Schneider Electric solution

    MEW was keen in installing LV PFC equipment because it would allow:

    approx. 15 - 20% kVA capacity release, approx. 20 - 25% reduction in tranformer losses.

    The equipment is for 240 LV Capacitor Banks + 20 Active Harmonic Filters to be installed in 50 - 75

    Substations.

    Each capacitor bank includes Power Quality Metering and remote monitoring using PowerLogic ION

    7650 meters.

    Capacitor banks are fitted with air conditioning systems for outdoor application. Capacitor banks are

    rated for a 50C ambient temperature.

    16

  • 8/10/2019 Com Power Pfc05en (Web)

    17/20

    Schneider Electric solution

    In order to improve distribution network quality by decreasing reactive energy losses, a reliable

    automatic capacitor bank solution for the 20 kV and 25 kV networks was proposed. Fixed and

    automatic capacitor banks between 4 and 6 Mvar have been delivered to ENDESA.

    MV capacitor bank

    Customer: ENDESA, Spain

    Stakes

    ENDESA manages and operates part of the MV distribution network in Spain. The ENDESA Group

    produces 47% of Spains electricity and controls 43% of the distribution in the country.

    Electricity supply quality and supply continuity must be irreproachable. Improvement of distribution

    network quality depends on decreasing reactive energy losses.

    Each capacitor bank includes:

    12 or 18 capacitor units with internal fuses connected in

    double star

    3 inrush current reactors

    1 unbalanced CT protection

    1 earthing switch for the protection of people

    1 SF1 switch + 2 overcurrent protection transformers

    (automatic capacitor banks only).

    17

  • 8/10/2019 Com Power Pfc05en (Web)

    18/20

    Active filterMetro-cable, Medellin, Colombia.

    Stakes

    The Medellin Metro-cable is driven by two 535kW motors, with two 960kW variable speed controllers.

    These electronic devices are responsible for harmonic distortion and poor power factor.

    Before implementation of correction equipment, the measurement results give:

    Power factor: 0.65 to 0.74

    Total Demand Distortion: 33 to 52%

    Voltage distortion THDu: 5.6 to 6.1%

    Harmonic current limits specified by the Utility are exceeded for harmonics 5, 7, 11, 13.

    Schneider Electric Solution

    For compliance to the Utility regulations and improvement of the Power Factor, active filters have been

    selected as the most efficient and flexible solution. Two Accusine PCS Active Harmonic Filters, ratedat 300A each have been implemented.

    The following table illustrates the resulting improvement,

    for the same operating point:

    Without filter With filter

    Line current (A) 332.8 156

    Current Harmonic distortion (%) 43.7 7

    Power Factor 0.66 0.99

    Full compliance with Utility regulations is obtained, and power losses

    are reduced by 45%.

    18

  • 8/10/2019 Com Power Pfc05en (Web)

    19/20

    Relevant documents published by Schneider Electric

    Expert Guide n6:Capacitor protection

    Expert Guide n4:Harmonic detection & filtering

    Technical Guide 152:Harmonic disturbances in networks, and their treatment

    Technical Guide 202: The singularities of the third harmonic

    Panel Builders Guide

    Reactive Energy Management LV components - Catalogue 2011(PFCED310003EN)

    Power Factor Correction and harmonic filtering solutions - MV Catalogue 2010 (CFIED205098EN)

    AccuSine - Harmonic filtering and reactive power compensation - Catalogue 2011 (AMTED109015EN)

    Harmonic Mitigation Solutions Handbook (SLTED109014EN)

    White paper:Controlling the Impact of Power Factor and Harmonics on Energy Efficiency

    Relevant websites

    http://www.schneider-electric.com

    http://www.electrical-installation.org/wiki/Main_Page

    https://www.solution-toolbox.schneider-electric.com/segment-solutions

    http://engineering.electrical-equipment.org

    e-learning

    Energy University training course: Power Factor & Harmonics

    19

  • 8/10/2019 Com Power Pfc05en (Web)

    20/20

    Contacts

    R. HENRIGeneral Sales Management

    +33 4 50 66 95 20

    [email protected]

    S. RATELEurope, Russia

    +33 4 50 66 95 31

    [email protected]

    P. RICHARDSouth America, Africa

    +34 934 84 32 83

    [email protected]

    M.T. NIGENFrance, Nordic Baltic+33 4 50 66 95 27

    [email protected]

    T. LE GUILLOUAsia Pacific

    +86 10 84 34 66 99

    [email protected]

    As standards, specications and designs develop from time to time, always ask for comrmation

    of the information given in this publication.

    Production and design: Schneider Electric

    Pictures: Schneider Electric

    Schneider Electric Industries SAS

    Head Ofce35 rue Joseph Monier

    CS 30323

    F - 92506 Rueil-Malmaison Cedex

    RCS Nanterre 954 503 439

    Capital social 896 313 776

    This document has been printed on ecological paper

    SchneiderElectricIndustriesS

    AS

    -Allrightsreserved

    Medium Voltage

    West Chester, Ohio - USA

    Low VoltageEst Haven, Connecticut - USA

    Rectiphase

    Pringy - France

    SSAM

    Shanga - China

    SalemOregon - USA

    SE PFC IndiaBangalore

    R. BOLDUCCanada, Middle East

    +1 613 247 7171

    [email protected]

    M. TETIUSA, Mexico, South Africa

    +1 905 364 3006

    [email protected]

    S. RAGHAVANIndia, Thailand

    +91 80 39 10 20 38

    [email protected]

    H. BOULOSUSA, Mexico, South Africa

    +1 905 364 [email protected]