Butikskylsystem medkoldioxid som kldmedium
Sveriges Energi- & Kylcentrum
13 december 2006
-
8/6/2019 CO2 Projektmote SEK 13dec06
2/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
3/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
4/4714/12/2006 Manustai Likitthammanit, Master Student, KTH 4
Projektvillkor
Projektet r beviljat medel fr perioden jan06 jul07 40/60 finansiering (fas 1: 50/50)
Total budget 4 997 tkr (1 999/2 998) (fas 1: 4 367/(2 183/ 2 183))
Mindre pengar i projektet och mer att motfinansiera!
Redovisning sker NU!
-
8/6/2019 CO2 Projektmote SEK 13dec06
5/4714/12/2006 Manustai Likitthammanit, Master Student, KTH 5
Fortsttning p projektet?
?
-
8/6/2019 CO2 Projektmote SEK 13dec06
6/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
7/4714/12/2006 Manustai Likitthammanit, Master Student, KTH 7
Overview
Objective Current Situation
Refrigeration Systems in IUC
The conditions in the IUC lab Working System NH3/CO2 Cascade
Results of NH3/CO2 Cascade System
Working System R404A DX system
Results of R404A DX System
Comparison of two systems NH3 Speed Compressor Test
Discussion and Conclusion
Transcritical CO2 components
-
8/6/2019 CO2 Projektmote SEK 13dec06
8/4714/12/2006 Manustai Likitthammanit, Master Student, KTH 8
Objective
Installation, test, and investigation of Transcritical CO2system. (main part)
To test and investigate NH3/CO2 cascade and R404A DXrefrigeration system and then compare with transcritical CO2system in term of performance and cost
To test and investigate two different speed (on-off andfrequency speed) of both CO2 compressor and NH3compressor in NH3/CO2 cascade refrigeration system in term
of performance
-
8/6/2019 CO2 Projektmote SEK 13dec06
9/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
10/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 10
Currently Situation
Transcritical CO2 system installing
-
8/6/2019 CO2 Projektmote SEK 13dec06
11/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 11
Refrigeration Systems in IUCRefrigeration Systems in IUC
NH3/CO2 cascade refrigeration system
-
8/6/2019 CO2 Projektmote SEK 13dec06
12/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 12
Refrigeration Systems in IUCRefrigeration Systems in IUC
R404A Direct Expansion refrigeration system
-
8/6/2019 CO2 Projektmote SEK 13dec06
13/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
14/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
15/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 15
The Conditions in IUC Lab
Different Ambient Temperature (15, 20, 25, 30 C)
-
8/6/2019 CO2 Projektmote SEK 13dec06
16/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 16
Working System NH3/CO2 CascadeWorking System NH3/CO2 Cascade
Thermosyphon Arrangement
-
8/6/2019 CO2 Projektmote SEK 13dec06
17/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 17
The Result of NH3/CO2 Cascade System
T_Evap_Freezing(-32--33 C)
T_Evap_Medium (-8C)T_NH3_Evap (-10.5)
T_CO2_Cond (-8.5 C)Temperature Diff (2 C)
-
8/6/2019 CO2 Projektmote SEK 13dec06
18/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
19/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
20/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
21/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 21
The Result of NH3/CO2 Cascade System
-
8/6/2019 CO2 Projektmote SEK 13dec06
22/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
23/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
24/47
Th R lt f R404A DX t
-
8/6/2019 CO2 Projektmote SEK 13dec06
25/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 25
The Result of R404A DX system
Chiller No1 had no stable operation at 15, 20, 25 C of cooling water temperature
-
8/6/2019 CO2 Projektmote SEK 13dec06
26/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
27/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
28/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
29/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
30/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
31/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
32/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
33/47
NH3 Speed Compressor Test
-
8/6/2019 CO2 Projektmote SEK 13dec06
34/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 34
NH3 Speed Compressor Test
The conditions were still set the same as the pervious test.
4 hours for test in each ambient temperature
On-OFF control Frequency control
-
8/6/2019 CO2 Projektmote SEK 13dec06
35/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
36/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
37/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
38/47
Transcritical CO2 System
-
8/6/2019 CO2 Projektmote SEK 13dec06
39/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 39
Discharge 2nd stage
Discharge 1st stage Suction 2nd stage
Suction 1st stage
Dorin semi-hermetic compressor
- 2900 rpm of compressor speed
- 10.3 m3/h of swept volume
- resist against pressure of 100 barin suction and 163 bar in discharge
- Frequency control
Two stages CO2 compressor
-
8/6/2019 CO2 Projektmote SEK 13dec06
40/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
41/47
-
8/6/2019 CO2 Projektmote SEK 13dec06
42/47
Transcritical CO2 System
-
8/6/2019 CO2 Projektmote SEK 13dec06
43/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 43
Internal Heat Exchanger
- Shell and tube heat exchanger
- stand pressure up to 200 bar
- 5 kW of capacity- Temperature drop 0.3 C
- Pressure drop 30 kPa or 0.3 bar
To expansionvalve
To suction
compressor
From gas cooler
From
accumulator
Transcritical CO2 System
-
8/6/2019 CO2 Projektmote SEK 13dec06
44/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 44
Danfoss Expansion Valve
- Pressure control
- Expansion
- ON / OFF
Maximum working pressure: PS 140 bar
Volume Flow = 0,6 4,6 [m3/h]
Hermetic sealed coupling
For further information: Contact Danfoss Industrial Refrigeration
ICMT
Transcritical CO2 System
-
8/6/2019 CO2 Projektmote SEK 13dec06
45/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 45
CO2 Inlet Water Outlet
Water Inlet
CO2 OutletSuper Max Heat Exchanger
- 27 kW of capacity
- 80 plates in heat exchanger
- 70 bar of design pressure
- 40 C of design temperature
- 4.8 m2 of Area
Cascade Condenser
Transcritical CO2 System
-
8/6/2019 CO2 Projektmote SEK 13dec06
46/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 46
CO2 liquid and vaporinlet
CO2 vaporoutlet
Suction Accumulator
- a pressure up to 200 bar
- around 3 liters
- separator CO2 vapor andliquid
1 mm of hole (remove oil from CO2)
-
8/6/2019 CO2 Projektmote SEK 13dec06
47/47
14/12/2006 Manustai Likitthammanit, Master Student, KTH 47