Unit with hermetic scroll type compressor andpropeller fans
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with hermetic scroll type compressor andpropeller fans
Cooling capacity [1]
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
Cooling capacity [1]
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of fans - External Secti on Fans
No. & Type of Compressors
Dimensions
2 0, 7 2 5, 7 28 ,1 33 ,9 37 ,6 4 3, 5 5 2, 7 5 6,9 6 3,0 7 8,3 9 3,5 1 01 ,5 1 19 ,1 1 31 ,6 1 40 ,3 1 51 ,1
35, 0 40, 6 44, 2 52, 1 56, 4 61, 2 77, 8 90, 9 104,4 119,2 132,0 141,1148, 1
40, 9 47, 1 52, 3 60, 2 66, 2 72, 3 86, 7 100,9 115,4 129,8 148,0 155,8166, 4
220 275 280 380 400 485 580 585 590 1347 1473 1548 1666 1695 1746 1789
60 59 59 60 60 60 60 60 60 72 74 75 77 77 77 77
2 Scroll 3 Scroll 4 Scroll
1 Axial 2 Axial 4 Axial 6 Axial 2 Axial 3 Axial
1435 1530 1530 1563 1563 1563 2098 2098 2098 3250 3250 3250 3250 3250 3250 3250
6 78 6 78 6 78 1 10 7 1 10 7 1 10 7 1 10 7 1 10 7 1 10 7 1 09 5 1 09 5 1 095 1 095 1 09 5 1 09 5 1 09 5
1000 1530 1530 1570 1570 1570 1570 1570 1570 2030 2030 2030 2030 2030 2030 2030
4,4 5,6 6,8 8,0 10,0 12,0 14,4 16,0 18,6 21,3 26,5 31,3
4,7 5,8 7,1 8,2 10,2 11,7 14,6 16,1 19,6 21,9 27,4 33,1
5,5 6,9 8,2 9,7 12,0 14,2 17,1 19,2 23,2 27,6 30,0 36,2
94 94 102 102 136 136 182 182 175 215 270 275
53 55 55 56 58 60 60 60 60 61 60 61
1 Scroll
1 Axial 2 Axial 1 Axial 2 Axial
895 895 895 895 1040 1040 1325 1325 1435 1435 1530 1530
359 359 359 359 411 411 555 555 678 678 678 678
895 895 1095 1095 1175 1175 1225 1225 1000 1000 1530 1530
Regulation
• a series of units installed to operate in
the same circuit communicate with
each other to optimise the management
of the various components.
Remote control management
• a personal computer can be used to
manage all the functions of the unit and
display all the operating parameters.
This allows preventive remote service
and the diagnosis of any malfunctions.
Air cooled water chiller for
outdoor installation
8 2 ÷ 6 0 4
WSAT Air to water heat pump for
outdoor installation
WSAN
®
WSAT - WSAN82 102 122 142 162 182 202 222 242 292 323 404 464 524 564 604
data refer to the following conditions:[1] evaporator water = 12/7°C; room temperature = 35°C;[2] evaporator air intake = 6.1°C WB; condenser water outlet temperature 45°C;
[3] The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to adistance of 1m from the external surface of the units operating in an open field.
Ready to install
• the unit does not require an external
hydronic assembly, as it is already fitted
as standard with a pump.
Setting Logic
• in systems with widely varying loads,
the reduced load phases are managed
intelligently so as to minimise energy
consumption.
Possible Configurations
Unit for production of chilled water to
-8°C
Partial recovery of condensing heat,
up to 25%
Total condensing heat recovery
Built-in free-cooling system
Standard
B
D
R
FC
S
11
H Y D R O N I C
Sizes
DIVISION
R407C
R22
CLIVET is an active member of the
EUROVENT certification program.
Wsat R407C
Wsan R22
Wsan R22
Length
Depth
Height
kW
kW
kW
Kg
dB(A)
mm
mm
mm
CLIVET is an active member of the
EUROVENT certification program.
Can be installed anywhere
• the compact overall dimensions,
together with the minimum functional
clearances, make it extremely easy to
find the right location.
• quiet operation.
• construction materials with excellent
weather resistance.
WSANWSAT Air to water heat pump for
outdoor installation
Air cooled water chiller for
outdoor installation
®
data refer to the following conditions:[1] evaporator water = 12/7°C; room temperature = 35°C;[2] evaporator air intake = 6.1°C WB; condenser water outlet temperature 45°C;
[3] The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure levelrefers to a distance of 1m from the external surface of the units operating in an open field.10
Everything you need from a chiller
• integrated frost prevention systems.
• high energy efficiency: above average
COP.
Time is precious
• unit ready for operation, only requires
the water and electrical connections.
• management of the pumps and storage
tanks in the unit.
• hydronic assembly and storage
integrated into the unit.
Possible Configurations
Operation with chilled fluid, outlet
temperature to -7°C
Possibility of automatic set point
modification
Serial communication module to interface
with the most modern supervisor systems
DIVISION
1 7 ÷ 1 2 1
H Y D R O N I C
R407C
R22
HYDRONIC SPLIT SYSTEM PACKAGED
WSAT - WSAN 17 21 25 31 41 51 61 71 81 91 101 121
Wsat R407C
Wsan R22
Wsan R22
Length
Depth
Height
kW
kW
kW
Kg
dB(A)
mm
mm
mm
Sizes
Low speed axial fan
directly coupled byelectrical motor
Hermetic compressor
Scroll type
Tandem Compressors
Scroll type
Braze welded plate
exchanger
ST
LN
Configuration:
Standard
Low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 2/15
Unit with semi-hermetic screw compressor andpropeller fans
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with semi-hermetic screw compressorand propeller fans
Cooling capacity [1]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
810,6 855,1 912,7 963,1 1013,61064,0 1112,91181,0 1234,81285,4 1334,71383,9 1482,3
6705 7046 7327 7762 8631 8800 8969 10175 10586 10765 10929 11096 11272
85 85 85 85 86 86 86 87 87 87 87 87 87
3 Single Screw 4 Single Screw
16 Axial 17 Axial 18 Axial 23 Axial 24 Axial
7918 7918 8938 8938 9840 9840 9840 11790 11790 11790 11790 11790 11790
2326 2326 2326 2326 2326 2326 2326 2326 2326 2326 2326 2326 2326
2443 2443 2443 2443 2443 2443 2443 2443 2443 2443 2443 2443 2443
Control Logic
• analyses the thermal requirements of the
system, optimising the compressor starts
and stops.
Regulation
• the sophisticated electronics used control
not only of the normal unit operating
parameters, but also the environmental
conditions, thus activating the defrosts
only when strictly required. This allows
more regular operation and significant
energy savings.
Air cooled water chiller for
outdoor installation
3 . 3 9 0 ÷ 4 . 7 2 0
WSAT
®
WSAT3.390 3.410 3.430 3.450 3.480 3.510 3.540 4.580 4.600 4.630 4.660 4.690 4.720
data refer to the following conditions[1] evaporator water = 12/7°C; room temperature = 35°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to adistance of 1m from the external surface of the units operating in an open field.
Energy saving
• part or all of the normally-lost condensing
energy can be recovered, for the
production of hot water for a variety of
uses.
• continuous and instant optimisation of
fan operation for maximum energy
savings.
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 15%
Total condensing heat recovery
Built-in free-cooling system
Standard
B
D
R
FC
S
13
H Y D R O N I C
Sizes
DIVISION
R407C
R22
CLIVET is an active member of the
EUROVENT certification program.
Wsat R407C
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
CLIVET is an active member of the
EUROVENT certification program.
• outside air heat exchangers with
innovative shape, especially designed to
guarantee maximum efficiency and
continuity over time.
Time is precious
• the careful design allows the unit to be
handled, positioned and connected on
site with extreme simplicity.
WSANWSAT Air to water heat pump for
outdoor installation
Air cooled water chiller for
outdoor installation
®
data refer to the following conditions:[1] evaporator water = 12/7°C; room temperature = 35°C;[2] evaporator air intake = 6.1°C WB; condenser water outlet temperature 45°C;
[3] The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure levelrefers to a distance of 1m from the external surface of the units operating in an open field.12
Suitable for any kind of installation
• for renovations and all cases where
space is limited, the compact
dimensions of the unit simplify
installation.
• for installations in particularly aggressive
environments, the air-side exchangers
can be made using special materials or
coatings that increase resistance to
corrosive agents.
High efficiency
• uprated heat exchangers can be
requested in the event of high outside
temperatures or to increase energy
efficiency in all conditions.
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 15%
Total condensing heat recovery
Built-in free-cooling system
Standard
DIVISION
2 . 9 0 ÷ 2 . 3 6 0
H Y D R O N I C
R407C
R22
Single screw compressor
with satellites
Microprocessor control
panel
S ingle s crew compre ss or Bra ze we lded plate
exchanger
HYDRONIC SPLIT SYSTEM PACKAGED
Cooling capacity [1]
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
194,2 237,0 260,7 277,0 297,4 339,5 367,2 416,3 482,5 538,2 592,1 642,7 691,9 741,1
205,2 237,6 260,9 291,7 320,5 353,2 379,6 438,8
284,2 324,1 362,6 397,4 429,9 467,1 501,1 570,3
2706 2941 3166 3250 3295 3595 3681 3891 4315 4491 5070 5539 5689 5840
81 81 82 82 82 82 83 83 83 83 84 84 84 84
2 Single Screw
4 Axial 5 Axial 6 Axial 7 Axial 8 Axial 9 Axial 10 Axial 11 Axial 12 Axial
3950 3950 3950 3950 3950 3950 3950 3950 4880 4880 5900 5900 5900 5900
2040 2040 2040 2040 2040 2326 2326 2326 2326 2326 2326 2326 2326 2326
2104 2104 2104 2104 2104 2443 2443 2443 2443 2443 2443 2443 2443 2443
WSAT - WSAN
Wsat R407C
Wsan R22
Wsan R22
Length
Depth
Height
kW
kW
kW
Kg
dB(A)
mm
mm
mm
Sizes
B
D
R
FC
S
2 .9 0 2 .10 0 2 .1 10 2 .1 25 2. 14 0 2 .1 55 2 .17 0 2. 20 0 2 .2 30 2 .2 60 2 .2 80 2 .30 0 2. 33 0 2 .3 60
ST
SC
LN
EN
Configuration:
Standard
Sound-proof compressorenclosures
Low noise
Extremely low noise
ST
SC
LN
EN
Configuration:
Standard
Sound-proof compressorenclosures
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 3/15
Unit with semi-hermetic screw compressor andpropeller fans
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with semi-hermetic screw compressor andpropeller fans
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
206,5 240,3 273,4 298,5 321,8 381,3 436,1 461,9 491,8
2920 3170 3336 3446 3562 4239 4638 4749 5019
79 79 80 81 81 82 82 82 82
2 Single Screw
4 Axial 5 Axial 6 Axial 7 Axial 8 Axial
3950 3950 3950 3950 3950 4880 4880 4880 4880
2040 2040 2040 2040 2040 2326 2326 2326 2326
2104 2104 2104 2104 2104 2443 2443 2443 2443
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
541,5 593,7 619,2 688,7 715,0 741,2 817,4 872,2 898,0 927,9 953,7 983,6
6485 6875 7255 7526 7645 7765 9307 9705 9816 10086 10197 10467
83 83 84 84 84 84 85 85 85 85 85 85
3 Single Screw 4 Single Screw
12 Axial 13 Axial 14 Axial 15 Axial 16 Axial
7918 7918 7918 7918 7918 7918 9750 9750 9750 9750 9750 9750
2326 2326 2326 2326 2326 2326 2326 2326 2326 2326 2326 2326
2443 2443 2443 2443 2443 2443 2443 2443 2443 2443 2443 2443
Low noise Level
• wherever silent operation is required, the
units can be configured for reduced
noise emissions and transmission of
vibrations to the support structures.
Control Logic
• the unit dynamically modulates the
temperature of the chilled fluid according
to the outside temperature, thus
optimising energy efficiency.
Can be installed anywhere
• the special structure with base made
from thick galvanised steel plate section
bars ensures uniform weight distribution.
Air cooled water chiller for
outdoor installation
3 . 2 6 0 ÷ 4 . 4 8 0
WSAT
®
WSAT3.260 3.280 3.300 3.320 3.340 3.360 4.380 4.400 4.420 4.440 4.460 4.480
data refer to the following conditions[1] evaporator water = 12/7°C; room temperature = 35°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
High efficiency
• outside air heat exchangers with
innovative shape, especially designed to
guarantee maximum efficiency and
continuity over time.
Energy saving
• part or all of the normally-lost
condensing energy can be recovered,
for the production of hot water for a
variety of uses.
Possible Configurations
unit for production of chilled
water to -8°C
partial recovery of condensing
heat, up to 15%
total condensing heat recovery
built-in free-cooling system
standard
B
D
R
FC
S
15
H Y D R O N I C
Sizes
DIVISION
R134a
CLIVET is an active member of the
EUROVENT certification program.
Wsat R134a
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
CLIVET is an active member of the
EUROVENT certification program.
Energy savings
• in systems with widely varying loads,
the reduced load phases are managed
intelligently so as to minimise energy
consumption.
Maximum respect for the environment
• with the ecological refrigerant the unit
complies with the strictest pollution
control and environmental protection
standards.
WSAT Air cooled water chiller for
outdoor installation
®
data refer to the following conditions[1] evaporator water = 12/7°C; room temperature = 35°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.14
Control logic
• a series of units installed to operate in
the same circuit communicate with
each other to optimise the management
of the various components.
Suitable for any kind of installation
• for renovations and all cases where
space is limited, the compact
dimensions of the unit simplify
installation.
Reliability and build quality
• guaranteed quality of all the
components installed.
DIVISION
2 . 9 0 ÷ 2 . 2 4 0
H Y D R O N I C
R134a
HYDRONIC SPLIT SYSTEM PACKAGED
WSAT 2.90 2.110 2.130 2.145 2.160 2.180 2.200 2.220 2.240
Wsat R134a
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
Sizes
Possible Configurations
unit for production of chilled
water to -8°C
partial recovery of condensing
heat, up to 15%
total condensing heat recovery
built-in free-cooling system
standard
Axial fan with profiled
blades
Microprocessor control
panel
Single screw compressor
with satellites
B
D
R
FC
S
Shell and tube heat
exchanger
ST
SC
LN
EN
Configuration:
Standard
Sound-proof compressorenclosures
Low noise
Extremely low noise
ST
SC
LN
EN
Configuration:
Standard
Sound-proof compressorenclosures
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 4/15
Unit with semi-hermetic reciprocating compressorand propeller fans
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with semi-hermetic double screw compressorand propeller fans
Cooling capacity [1]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
299,4 319,9 338,1 361,9 382,8 422,6 485,6 510,7 535,8 574,9 613,9
3402 3509 3603 3645 3658 4319 5001 5104 5202 5470 5577
82 83 84
2 Double Screw
6 Axial 7 Axial 8 Axial 10 Axial 12 Axial
3950 3950 3950 3950 3950 3950 4880 4880 4880 5900 5900
2040 2040 2040 2040 2040 2326 2326 2326 2326 2326 2326
2104 2104 2104 2104 2104 2443 2443 2443 2443 2443 2443
Cooling capacity [1]
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
No. & Type of fans - External Section Fans
Dimensions
Wrat and Wran R22 up to size 2.120
High efficiency
• uprated heat exchangers can be
requested in the event of high outside
temperatures or to increase energy
efficiency in all conditions.
Suitable for any kind of installation
• for renovations and all cases where
space is limited, the compact
dimensions of the unit simplify
installation.
Air cooled water chiller for
outdoor installation
2 . 7 0 ÷ 2 . 1 4 0
WRAT Air to water heat pump for
outdoor installation
WRAN
®
WRAN - WRAT
data refer to the following conditions[1] evaporator water = 12/7°C; room temperature = 35°C;[2] evaporator air intake = 10°C WB (R.H. = 80%); condenser water outlet temperature 40/45°C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
Regulation
• a series of units installed to operate in
the same circuit communicate with
each other to optimise the management
of the various components.
Control logic
• in systems with widely varying loads,
the reduced load phases are managed
intelligently so as to minimise energy
consumption.
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 25%
Total condensing heat recovery
Built-in free-cooling system
Standard
B
D
R
FC
S
17
H Y D R O N I C
Sizes
DIVISION
R407C
R22
CLIVET is an active member of the
EUROVENT certification program.
Wrat R407C
Wrat R22
Wran R22
Length
Depth
Height
kW
kW
kW
Kg
dB(A)
mm
mm
mm
CLIVET is an active member of the
EUROVENT certification program.
Reliability and build quality
• twin-screw compressor for maximum
sturdiness and reliability over time.
• the use of plate exchangers, specifically
designed for use with ecological gas and
with perfectly opposing flows, optimises
the heat exchange of the water on the
utility side.
WDAT Air cooled water chiller for
outdoor installation
®
data refer to the following conditions[1] evaporator water = 12/7°C; room temperature = 35°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.16
Control Logic
• analyses the thermal requirements of the
system, optimising the compressor
starts and stops.Remote control management
• a personal computer can be used to
manage all the functions of the unit and
display all the operating parameters.
This allows preventive remote service
and the diagnosis of any malfunctions.
Can be installed anywhere
• for installations in particularly aggressive
environments, the air-side exchangers
can be made using special materials or
coatings that increase resistance to
corrosive agents.
DIVISION
2 . 1 4 0 ÷ 2 . 2 8 0
H Y D R O N I C
R407C
R22
HYDRONIC SPLIT SYSTEM PACKAGED
WDAT 2.140 2.150 2.160 2.170 2.180 2.200 2.220 2.235 2.250 2.265 2.280
Wdat R407C
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
Sizes
Double screw
compressor rotors
Reciprocating
compressor
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 15%
Total condensing heat recovery
Built-in free-cooling system
Standard
B
D
R
FC
S
138,6 154,0 167,2 186,4 202,2 226,4 246,5 272,5 286,8
163,7 179,8 192,5 215,2 234,2 257,0 272,8
202,6 222,9 243,2 272,1 293,2 320,4 347,6
1890 1982 2066 2203 2410 2402 2463 2487 2492
81 83 85
2 Reciprocating
4 Axial
2950 2950 2950 2950 2950 2950 2950 2950 2950
2040 2040 2040 2040 2040 2040 2040 2040 2040
2113 2113 2113 2113 2113 2113 2113 2113 2113
2.70 2.75 2.80 2.90 2.100 2.110 2.120 2.130 2.140
Double screw
compressor rotors
Axial fan with profiled
blades
ST
SC
LN
EN
Configuration:
Standard
Sound-proof compressorenclosures
Low noise
Extremely low noise
ST
SC
LN
EN
Configuration:
Standard
Sound-proof compressorenclosures
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 5/15
Unit with hermetic scroll type compressorand centrifugal fans
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with semi-hermetic reciprocating compressorand propeller fans
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 15%
Total condensing heat recovery
Standard
Cooling capacity [1]
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
Everything you need from a chiller
• fan inverter to optimise energy
consumption.
• high energy efficiency: above averageCOP.
Time is precious
• all the static pressure requirements are
satisfied by the use of a wide range of
motors.
• unit ready for operation, only requires
the water and electrical connections.
• management of the pumps in the unit.
Air cooled water chiller for
indoor installation
2 1 ÷ 1 2 1
WRA Air to water heat pump
for indoor installation
WRN
®
WRN - WRA
data refer to the following conditions[1] evaporator water = 12/7°C; ambient air temperature = 30°C;[2] evaporator air intake = 6.1°C WB; condenser water outlet temperature 45°C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
Can be installed anywhere
• can be installed in ceilings, garages,
service rooms and basements, without
having to modify the existing structures.• fitted for connection to various types of
ducting.
• soundproofed panelling that guarantees
reduced noise levels.
Possible Configurations
Remote control
Serial communication module to interface
with the most modern supervisor systems
Operation with chilled fluid, outlet
temperature to -7°C
19
H Y D R O N I C
Sizes
DIVISION
R407C
R22
CLIVET is an active member of the
EUROVENT certification program.
Wra R407C
Wrn R22
Wrn R22
Length
Depth
Height
kW
kW
kW
Kg
dB(A)
mm
mm
mm
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
CLIVET is an active member of the
EUROVENT certification program.
Reliability and build quality
• outside air heat exchangers with
innovative shape, especially designed to
guarantee maximum efficiency andcontinuity over time guaranteed quality of
all the components installed.
Energy saving
• part or all of the normally-lost condensing
energy can be recovered, for the
production of hot water for a variety of
uses.
WRANWRAT Air to water heat pump for
outdoor installation
Air cooled water chiller for
outdoor installation
®
data refer to the following conditions[1] evaporator water = 12/7°C; room temperature = 35°C;[2] evaporator air intake = 10°C WB (R.H. = 80%); condenser water outlet temperature 40/45°C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.18
Low noise Level
• wherever silent operation is required,
the units can be configured for
reduced noise emissions andtransmission of vibrations to the
support structures.
Control Logic
• the unit dynamically modulates the
temperature of the chilled fluid
according to the outside temperature,
thus optimising energy efficiency.
Can be installed anywhere
• the special structure with base made
from thick galvanised steel plate
section bars ensures uniform weight
distribution.
DIVISION
4 . 1 4 0 ÷ 4 . 2 4 0
H Y D R O N I C
R22
HYDRONIC SPLIT SYSTEM PACKAGED
WRAT - WRAN
Wrat R22
Wran R22
Length
Depth
Height
kW
kW
Kg
dB(A)
mm
mm
mm
Sizes
Reciprocating compressor
B
D
R
S
321,0 381,6 428,3 473,4 514,0 546,4
405,2 486,4 544,2 586,4 640,8 695,2
3397 3596 3974 4333 4400 4416
86 86 86 86 88 89
4 Reciprocating
8 Axial
5900 5900 5900 5900 5900 5900
2040 2040 2040 2040 2040 2040
2113 2113 2113 2113 2113 2113
4.140 4.160 4.180 4.200 4.220 4.240
Axial fan with profiledblades
5,7 6,7 7,8 11,8 15,5 21,0 25,0 30,0
5,9 7,1 8,5 12,4 17,2 22,7 26,3 32,1
6,8 8,0 9,4 14,0 19,1 27,0 29,5 35,6
97 123 125 170 329 347 400 420
57 59 60 65 61 60 60 62
1 Scroll
1 Centrifugal
790 935 935 1165 1517 1517 1780 1780
538 630 630 703 758 758 846 846
648 648 648 723 1130 1130 1205 1205
21 25 31 51 71 91 101 121
Fan Inverter to optimise
energy consumption
Hermetic compressor
Scroll type
Shell and tube heat
exchanger
STSC
LN
EN
Configuration:
Standard
Sound-proof compressorenclosures
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 6/15
Unit with semi-hermetic reciprocatingcompressor and centrifugal fans
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with hermetic scroll typecompressor and centrifugal fans
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
Low noise Level
• wherever silent operation is required,
the units can be configured for reduced
noise emissions and transmission of vibrations to the support structures.
Control Logic
• a series of units installed to operate in
the same circuit communicate with
each other to optimise the management
of the various components.
Air cooled water chiller for
indoor installation
2 . 7 0 ÷ 2 . 1 2 0
WRA
®
WRA
data refer to the following conditions[1] evaporator water = 12/7°C; ambient air temperature = 35°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
Can be installed anywhere
• the special structure with base made
from thick galvanised steel plate section
bars ensures uniform weight distribution.Reliability and build quality
• outside air heat exchangers with
innovative shape, especially designed to
guarantee maximum efficiency and
continuity over time.
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 15%
Total condensing heat recovery
Standard
B
D
R
S
21
H Y D R O N I C
Sizes
DIVISION
R407C
R22
CLIVET is an active member of the
EUROVENT certification program.
Wra R407C
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
Cooling capacity [1]
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
No. & Type of fans - External Secti on Fans
Dimensions
CLIVET is an active member of the
EUROVENT certification program.
Suitable for any kind of installation
• for renovations and all cases where
space is limited, the compact
dimensions of the unit simplifyinstallation.The wide range of
motor/drive possibilities makes the unit
easily adaptable to any type of air
discharge ducting.
Time is precious
• the careful design allows the unit to be
handled, positioned and connected on
site with extreme simplicity.
WRNWRA Air to water heat pump for
indoor installation
Air cooled water chiller for
indoor installation
®
data refer to the following conditions[1] evaporator water = 12/7°C; ambient air temperature = 35°C;[2] evaporator air intake = 7°C WB (R.H. = 85%); condenser water outlet temperature 40/45°C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.20
Control Logic
• analyses the thermal requirements of the
system, optimising the compressor starts
and stops.• the unit dynamically modulates the
temperature of the chilled fluid according
to the outside temperature, thus
optimising energy efficiency.
• in systems with widely varying loads, the
reduced load phases are managed
intelligently so as to minimise energy
consumption.
DIVISION
1 4 2 ÷ 6 0 4
H Y D R O N I C
R407C
R22
HYDRONIC SPLIT SYSTEM PACKAGED
WRA - WRN
Wra R407C
Wrn R22
Wrn R22
Length
Depth
Height
kW
kW
kW
Kg
dB(A)
mm
mm
mm
Sizes
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 25%
Standard
B
D
S
Reciprocating
compressor
Hermetic compressor
Scroll type
31,0 42,0 50,0 60,0 72,1 81,5 93,5 99,9 109,1 111,4 121,4 137,3 143,6
34,7 45,4 52,0 64,3 75,7 86,6 96,0 110,1 104,8 115,2 124,3 139,3 147,8
38,0 49,0 58,0 68,0 91,4 102,8 116,7 139,5 124,1 139,6 152,6 169,8 182,4
629 670 760 772 920 950 1050 1070 1500 1550 1580 1675 1700
62 60 61 62 59 64 66 66 61 61 61 63 64
2 Scroll 2 Reciprocating 2 Tandem Scroll
1 Centrifugal 2 Centrifugal 3 Centrifugal
2230 2230 2230 2230 2478 2478 2478 2478 3308 3308 3308 3308 3308
978 978 978 978 974 974 974 974 1152 1152 1152 1152 1152
1430 1430 1705 1705 1672 1672 1672 1672 2275 2275 2275 2275 2275
142 182 202 242 292 322 362 422 404 464 524 564 604
140,0 151,2 160,0 186,1 195,1 213,7 226,0
2068 2128 2155 2390 2489 2619 2635
74 75 76 76 77 79 80
2 Reciprocating
4 Centrifugal
4400 4400 4400 4400 4400 4400 4400
1140 1140 1140 1140 1140 1140 1140
2270 2270 2270 2270 2270 2270 2270
2.70 2.75 2.80 2.90 2.100 2.110 2.120
Fan Inverter to optimise
energy consumption
ST
SC
Configuration:
Standard
Sound-proof compressorenclosures
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 7/15
Unit with hermetic scroll type compressor
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with hermetic scroll type compressor
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
Dimensions
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
Dimensions
Water cooled water chiller
for indoor installation
1 0 2 ÷ 4 2 2
WRHWater to water heat pump
reversible on the refrigerant circuit
for indoor installation
WRHN
®
WRHN - WRH
data refer to the following conditions:[1] evaporator water = 12/7°C; condenser water = 16/30°C;[2] evaporator water = 12/7°C; condenser water outlet temperature 45°C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
Everything you need from a chiller
• high energy efficiency: above average
COP.• management of the pumps and storage
tanks in the unit.
Time is precious
• reversal on the refrigerant circuit = time
saving.
• reversal on the refrigerant circuit = less
components in the water circuit.
Can be installed anywhere
• quiet operation
• the compact overall dimensions,
together with the minimum functional
clearances, make it extremely easy to
find the right location.
Possible Configurations
Version available with reversal on the water
circuit (WRH-H)
Remote control
Operation with chilled fluid, outlet
temperature to -7°C
Possibility of automatic set point
modification
Serial communication module to interface
with the most modern supervisor systems
23
H Y D R O N I C
Sizes
DIVISION
R407C
R22
CLIVET is an active member of the
EUROVENT certification program.
Wrh R407C
Wrhn R407C
Length
Depth
Height
kW
kW
Kg
dB(A)
mm
mm
mm
5,4 6,7 8,1 9,3 12,0 14,3 17,2 19,0 20,8 24,8 29,2 35,6
6,2 7,8 9,4 10,9 15,6 16,5 19,6 22,0 24,5 29,3 34,1 41,8
86 89 94 96 102 104 107 109 129 129 134 140
49 49 49 49 50 50 50 50 59 59 60 62
1 Scroll
402 402 402 402 402 402 402 402 402 402 402 402
487 487 487 487 602 602 602 602 602 602 602 602
790 790 790 790 790 790 790 790 915 915 915 915
CLIVET is an active member of the
EUROVENT certification program.
• reversal on the refrigerant circuit = less
components in the water circuit.
Can be installed anywhere• can be installed anywhere, such as
simply the under the sink.
• quiet operation.
• the compact overall dimensions, together
with the minimum functional clearances,
make it extremely easy to find the right
location.
WRHNWRHWater to water heat pump
reversible on the refrigerant circuit
for indoor installation
Water cooled water chiller
for indoor installation
®
data refer to the following conditions:[1] evaporator water = 12/7°C; condenser water = 16/30°C;[2] evaporator water = 12/7°C; condenser water outlet temperature 45°C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.22
Everything you need from a chiller
• high energy efficiency: above average
COP.
• management of the pumps and storagetanks in the unit.
• units for geothermal applications.
Time is precious
• water pump and expansion vessel fitted
in version P.
• reversal on the refrigerant circuit = time
savings.
Possible Configurations
Version available with reversal on the water
circuit (WRH-H)
Operation with chilled fluid, outlet
temperature to -7°C
Possibility of automatic set point
modification
Serial communication module to interface
with the most modern supervisor systems
Remote control
DIVISION
1 7 ÷ 1 2 1
H Y D R O N I C
R407C
R22
HYDRONIC SPLIT SYSTEM PACKAGED
WRH - WRHN 17 21 25 31 41 51 61 71 81 91 101 121
Wrh R407C
Wrhn R407C
Length
Depth
Height
kW
kW
Kg
dB(A)
mm
mm
mm
Sizes
Hermetic compressor
Scroll type
Braze welded plate
exchanger
Electronic
microprocessor control
Hermetic compressor
Scroll type
28,6 38,1 42,3 49,5 58,4 64,8 71,5 93,2 108,0 123,4 148,1
33,0 44,0 48,6 58,6 68,2 75,9 83,7
180 200 248 250 260 266 271 450 490 520 580
53 53 62 62 63 64 65 66 66 66 66
2 Scroll
802 802 802 802 802 802 802 1062 1062 1062 1062
602 602 602 602 602 602 602 580 580 580 580
790 790 915 915 915 915 915 1538 1538 1538 1538
102 142 162 182 202 222 242 292 322 362 422
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 8/15
Unit with semi-hermetic screw type compressor
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with semi-hermetic screw type compressor
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
Dimensions
Control Logic
• a series of units installed to operate in
the same circuit communicate with
each other to optimise the managementof the various components.
Suitable for any kind of installation
• for renovations and all cases where
space is limited, the compact
dimensions of the unit simplify
installation.
High efficiency
• new generation water exchangers for
eliminating the heat with solutions
Water cooled water chiller
for indoor installation
3 . 3 9 0 ÷ 4 . 7 2 0
WSHWater to water heat pump
(reversible water circuit) for indoor
installation
WSHH
®
WSHH - WSH
data refer to the following conditions:[1] size 3.390÷3.540; evaporator water = 13/7 °C; condenser water = 30/35 °C;
size 4.560÷4.720; evaporator water = 12/7 °C; condenser water = 29/35 °C;[2] size 3.390÷3.540; condenser water = 40/45 °C; evaporator water = 13/7 °C;
size 4.560÷4.720; condenser water = 39/45 °C; evaporator water = 12/7 °C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
designed to obtain maximum efficiency
over time.
Maximum respect for the environment
• with the ecological refrigerant the unitcomplies with the strictest pollution
control and environmental protection
standards.
Energy saving
• part or all of the normally-lost
condensing energy can be recovered, for
the production of hot water for a variety
of uses.
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of the condensing
heat up to 10%
Total condensing heat recovery
Water to water heat pump with
reversal on the water circuit
Standard
B
D
R
H
S
25
H Y D R O N I C
Sizes
DIVISION
R407C
R22
CLIVET is an active member of the
EUROVENT certification program.
Wsh R407C
Wshh R407C
Length
Depth
Height
kW
kW
Kg
dB(A)
mm
mm
mm
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
Dimensions
CLIVET is an active member of the
EUROVENT certification program.
Reliability and build quality
• the use of plate exchangers, specifically
designed for use with ecological gas
and with perfectly opposing flows,optimises the heat exchange of the
water on the utility side.
Energy saving
• in systems with widely varying loads,
the reduced load phases are managed
intelligently so as to minimise energy
consumption.
WSHHWSHWater to water heat pump
(reversible water circuit) for indoor
installation
Water cooled water chiller
for indoor installation
®
data refer to the following conditions:[1] evaporator water = 12/7°C; condenser water = 30/35°C;[2] evaporator water = 12/7°C; condenser water outlet temperature 40/45°C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.24
Low noise Level
• wherever silent operation is required,
the units can be configured for reduced
noise emissions and transmission of vibrations to the support structures.
Control Logic
• the unit dynamically modulates the
temperature of the chilled fluid
according to the outside temperature,
thus optimising energy efficiency.
Suitable for any kind of installation
• the condensing heat can be rejected by
water to waste (well) or a closed circuit
(tower), to suit a variety of systems
needs.
DIVISION
2 . 9 0 ÷ 2 . 3 6 0
H Y D R O N I C
R407C
R22
HYDRONIC SPLIT SYSTEM PACKAGED
WSH - WSHH
Wsh R407C
Wshh R407C
Length
Depth
Height
kW
kW
Kg
dB(A)
mm
mm
mm
Sizes
Single screw compressor
with satellites
Braze welded plate
exchanger
240,2 289,2 324,1 345,0 386,6 407,7 436,3 490,9 578,2 659,8 730,8 801,9 838,3 874,8
285,0 337,3 377,5 403,5 458,3 482,6 516,5 587,0 688,6 783,2 864,4 945,6 1006,51067,5
1531 1696 1829 1878 1931 2279 2294 2397 2447 2587 2900 3226 3272 3318
74 74 75 76 77 77 77 78 78 79 79 79 80 80
2 Single Screw
3620 3620 3620 3620 3620 3780 3780 3780 3780 4150 4150 4150 4150 4150
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000
2 .9 0 2 .10 0 2 .1 10 2 .1 25 2. 14 0 2 .1 55 2 .17 0 2. 20 0 2 .2 30 2 .2 60 2 .2 80 2 .30 0 2. 33 0 2 .3 60
866,0 938,91000,41080,51130,71180,91231,21321,51381,41455,31503,41561,01609,01666,8
1063,91143,01213,71304,11378,31452,41526,51590,01660,41742,91815,01896,81968,82050,6
3759 4324 4664 5004 5045 5086 5127 6443 6740 7008 7040 7072 7104 7136
80 80 80 80 81 81 81 82 82 82 83 83 83 83
3 Single Screw 4 Single Screw
4300 4300 4300 4300 4300 4300 4300 4600 4600 4600 4600 4600 4600 4600
1815 1815 1815 1815 1815 1815 1815 2340 2340 2340 2340 2340 2340 2340
2150 2250 2250 2300 2300 2300 2300 1900 1900 1900 1900 1900 1900 1900
3 .390 3 .410 3 .430 3 .450 3 .480 3 .510 3 .540 4 ,560 4 ,580 4 .600 4 .630 4 .660 4 .690 4 .720
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of the condensing
heat up to 10%
Total condensing heat recovery
Water to water heat pump
with reversal on the water circuit
Standard
B
D
R
H
S
S in gl e s cr ew co mp re ss or S he ll an d t ub e h ea t
exchanger
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 9/15
Unit with semi-hermetic screw type compressor
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with semi-hermetic screw type compressor
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
Dimensions
6 19 ,0 6 80, 0 7 54 ,5 7 81 ,9 8 16 ,7 8 44, 8 94 6, 3 1 012 ,6 10 38 ,5 1 06 4,4 1 10 7, 6 1 15 0, 8
697,9 768,0 845,1 877,1 915,3 948,1 1060, 8 1132, 4 1165, 6 1198, 8 1247, 1 1295, 5
3958 4169 4604 4632 4661 4689 6319 6516 6551 6572 6602 6628
77 77 77 78 78 78 79 79 80 80 80 80
3 Single Screw 4 Single Screw
4300 4300 4300 4300 4300 4300 4650 4650 4650 4650 4650 4650
1815 1815 1815 1815 1815 1815 2340 2340 2340 2340 2340 2340
2150 2150 2200 2200 2200 2200 1700 1700 1700 1700 1700 1700
Low noise Level
• wherever silent operation is required, the
units can be configured for reduced
noise emissions and transmission of vibrations to the support structures.
Control Logic
• the unit dynamically modulates the
temperature of the chilled fluid according
to the outside temperature, thus
optimising energy efficiency.
Suitable for any kind of installation
• the condensing heat can be rejected by
water to waste (well) or a closed circuit
(tower), to suit a variety of systems
needs.
Water cooled water chiller
for indoor installation
3 . 2 6 0 ÷ 4 . 4 8 0
WSHWater to water heat pump
(reversible water circuit) for
indoor installation
WSHH
®
WSHH - WSH
data refer to the following conditions:[1] evaporator water = 12/7°C; condenser water = 30/35°C;[2] condenser water = 40/45°C; evaporator water = 10/5°C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
Maximum respect for the environment
• with the ecological refrigerant the unit
complies with the strictest pollution
control and environmental protectionstandards.
High efficiency
• part or all of the normally-lost
condensing energy can be recovered,
for the production of hot water for a
variety of uses.
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of the condensing
heat up to 10%
Water to water heat pump with
reversal on the water circuit
Total condensing heat recovery
Standard
B
D
H
R
S
27
H Y D R O N I C
Sizes
DIVISION
R134a
CLIVET is an active member of the
EUROVENT certification program.
Wsh R134a
Wshh R134a
Length
Depth
Height
Kw
Kw
Kg
dB(A)
mm
mm
mm
CLIVET is an active member of the
EUROVENT certification program.
Reliability and build quality
• exclusive single-screw compressors
with avant-garde technology offering
excellent performance.Everything you need from a chiller
• our units stand out on the market for
their excellent performance and
competitive costs.
Time is precious
• the careful design allows the unit to be
handled, positioned and connected on
site with extreme simplicity.
WSHHWSHWater to water heat pump
(reversible water circuit) for
indoor installation
Water cooled water chiller
for indoor installation
®
data refer to the following conditions:[1] evaporator water = 12/7 °C; condenser water = 30/35 °C;[2] evaporator water = 10/5 °C; condenser water = 40/45 °C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.26
Control Logic
• analyses the thermal requirements of
the system, optimising the compressor
starts and stops.• in systems with widely varying loads,
the reduced load phases are managed
intelligently so as to minimise energy
consumption.
Can be installed anywhere
• the special structure with base made
from thick galvanised steel plate section
bars ensures uniform weight
distribution.
DIVISION
2 . 9 0 ÷ 2 . 2 4 0
H Y D R O N I C
R134a
HYDRONIC SPLIT SYSTEM PACKAGED
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of the
condensing heat up to 10%
Water to water heat pump with
reversal on the water circuit
Total condensing heat recovery
Standard
B
D
H
R
S
Shell and tube heat
exchanger
3.260 3.280 3.300 3.320 3.340 3.360 4.380 4.400 4.420 4.440 4.460 4.480
Single screw compressor
with satellites
S in gl e s cr ew co mp re ss or S he ll an d t ub e h ea t
exchanger
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
Dimensions
WSH - WSHH
Wsh R134a
Wshh R134a
Length
Depth
Height
kW
kW
Kg
dB(A)
mm
mm
mm
Sizes
238,6 281,5 313,3 344,5 381,0 440,0 506,3 532,2 575,4
270,1 316,4 355,1 386,8 424,8 494,6 566,2 599,4 647,8
1791 1940 2033 2152 2327 2808 3241 3251 3335
71 73 73 75 75 76 77 77 77
2 Single Screw
3200 3400 3700 3700 3700 4600 4600 4600 4600
895 1000 1000 1000 1000 1200 1200 1200 1200
1300 1500 1500 1500 1500 1800 1800 1800 1800
2.90 2.110 2.130 2.145 2.160 2.180 2.200 2.220 2.240
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 10/15
Unit with hermetic scroll type compressor
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with semi-hermetic reciprocating type compressor
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
Dimensions
Discrete
• compact dimensions.
• quiet operation.
Everything you need from a chiller
• our units stand out on the market for
their excellent performance and
competitive costs.
Condenserless water
chiller for indoor installation
with remote condenser
1 7 ÷ 1 2 1
ME
®
ME
data refer to the following conditions:[1] evaporator water = 12/7°C; condensing temperature = 50°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
Extremely versatile
• hydronic assembly installed in the unit.
Possible Configurations
Operation with chilled fluid, outlet
temperature to -7°C
Remote control
Serial communication module to interface
with the most modern supervisor systems
29
H Y D R O N I C
Sizes
DIVISION
R407C
R22
CLIVET is an active member of the
EUROVENT certification program.
Me R407C
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
Cooling capacity [1]
Heating capacity [2]
Shipping weight
Sound pressure level [3]
No. & Type of Compressors
Dimensions
CLIVET is an active member of the
EUROVENT certification program.
High efficiency
• new generation water exchangers for
eliminating the heat with solutions
designed to obtain maximum efficiencyover time.
Time is precious
• the careful design allows the unit to be
handled, positioned and connected on
site with extreme simplicity.
WRHHWRHWater to water heat pump
(reversible water circuit) for
indoor installation
Water cooled water chiller
for indoor installation
®
data refer to the following conditions:[1] condenser water = 12/7°C; evaporator water = 30/35°C;[2] condenser water = 40/45°C; evaporator water = 12/7°C;
[3] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.28
Control Logic
• a series of units installed to operate in
the same circuit communicate with
each other to optimise the managementof the various components.
• in systems with widely varying loads,
the reduced load phases are managed
intelligently so as to minimise energy
consumption.
Suitable for any kind of installation
• for renovations and all cases where
space is limited, the compact
dimensions of the unit simplify
installation.
DIVISION
2 . 7 0 ÷ 2 . 1 4 0
H Y D R O N I C
R407C
HYDRONIC SPLIT SYSTEM PACKAGED
WRH - WRHH
Wrh R407C
Wrhh R407C
Length
Depth
Height
kW
kW
Kg
dB(A)
mm
mm
mm
Sizes
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensingheat, up to 15%
Water to water heat pump withreversal on the water circuit
Total condensing heat recovery
Standard
B
D
H
R
S
178,8 200,8 218,9 238,2 256,5 292,0 317,2 349,1 364,6
213,8 239,1 260,0 277,5 299,2 345,6 376,2 417,4 443,0
1139 1182 1213 1369 1480 1515 1559 1575 1573
80 80 80 81 81 81 81 84 86
2 Reciprocating
2750 2750 2750 2750 2750 2750 2750 2750 2750
770 770 770 770 770 770 770 770 770
1360 1360 1360 1360 1360 1360 1360 1360 1360
2.70 2.75 2.80 2.90 2.100 2.110 2.120 2.130 2.140
5,0 6,2 7,6 8,7 11,2 13,4 15,9 17,8 19,5 23,4 27,2 33,5
77 80 85 87 91 92 93 93 113 113 113 119
49 49 49 49 50 50 50 50 59 59 60 62
1 Scroll
402 402 402 402 402 402 402 402 402 402 402 402
487 487 487 487 602 602 602 602 602 602 602 602
790 790 790 790 790 790 790 790 915 915 915 915
17 21 25 31 41 51 61 71 81 91 101 121
Braze welded plate
exchanger
Reciprocating
compressor
Hermetic compressor
Scroll type
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 11/15
Unit with semi-hermetic screw type compressor
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with hermetic scroll type compressor
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
Dimensions
Control Logic
• analyses the thermal requirements of
the system, optimising the compressor
starts and stops.Can be installed anywhere
• the special structure with base made
from thick galvanised steel plate section
bars ensures uniform weight
distribution.
Reliability and build quality
• exclusive single-screw compressors
with avant-garde technology offering
excellent performance.
Condenserless water
chiller for indoor installation
with remote condenser
2 . 9 0 ÷ 2 . 3 6 0
MSE
®
MSE
data refer to the following conditions:[1] evaporator water = 12/7°C; condensing temperature = 45°C;[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers
to a distance of 1m from the external surface of the units operating in an open field.
High efficiency
• the use of plate exchangers, specifically
designed for use with ecological gas
and with perfectly opposing flows,optimises the heat exchange of the
water on the utility side.
Energy saving
• part or all of the normally-lost
condensing energy can be recovered,
for the production of hot water for a
variety of uses.
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 15%
Standard
B
D
S
31
H Y D R O N I C
Sizes
DIVISION
R407C
R22
CLIVET is an active member of the
EUROVENT certification program.
Mse R407C
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
Dimensions
CLIVET is an active member of the
EUROVENT certification program.MECondenserless water chiller
for indoor installation with
remote condenser
®
data refer to the following conditions:[1] evaporator water = 12/7°C; condensing temperature = 50°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.30
Discrete
• compact dimensions.
• quiet operation.
Possible Configurations
Solution to optimize the installation
Operation with chilled fluid, outlet
temperature to -7°C
Remote control
Serial communication module to interface
with the most modern supervisor systems
DIVISION
1 0 2 ÷ 4 2 2
H Y D R O N I C
R407C
R22
HYDRONIC SPLIT SYSTEM PACKAGED
ME
Me R407C
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
Sizes
25,7 34,2 37,5 45,1 52,5 58,5 64,5 82,1 96,9 112,7 137,8
158 193 232 232 239 245 250 410 445 468 520
53 53 62 62 63 64 65 66 66 66 66
2 Scroll
802 802 802 802 802 802 802 580 580 580 580
602 602 602 602 602 602 602 1062 1062 1062 1062
790 790 915 915 915 915 915 1538 1538 1538 1538
102 142 162 182 202 222 242 292 322 362 422
Single screw compressor
222,8 266,2 296,7 316,8 361,9 380,3 407,7 459,7 542,2 618,7 682,9 747,2 785,3 823,4
1381 1543 1673 1719 1769 1997 1992 2083 2127 2252 2548 2874 2920 2966
74 74 75 76 77 77 77 78 78 79 79 79 80 80
2 Single Screw
3620 3620 3620 3620 3620 3780 3780 3780 3780 4150 4150 4150 4150 4150
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000
2 .9 0 2 .1 00 2 .1 10 2 .1 25 2 .14 0 2. 15 5 2 .1 70 2 .20 0 2 .2 30 2 .2 60 2. 28 0 2 .3 00 2 .33 0 2. 36 0
Hermetic compressor
Scroll type
Braze welded plate
exchanger
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 12/15
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
Dimensions
MSE 3.260-4.480
Potenzialità frigorifera [1]
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
Dimensions
Unit with semi-hermetic screw type compressor
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with semi-hermetic screw type compressor
226,6 265,0 295,7 324,5 358,1 414,2 476,9 501,4 540,9
1741 1889 1981 2099 2273 2753 3185 3194 3277
71 73 73 75 75 76 77 77 772 Single Screw
3200 3400 3700 3700 3700 4600 4600 4600 4600
895 1000 1000 1000 1000 1200 1200 1200 1200
1300 1500 1500 1500 1500 1800 1800 1800 1800
3.260 3.280 3.300 3.320 3.340 3.360 4.380 4.400 4.420 4.440 4.460 4.480
5 83 ,4 6 41, 1 7 10 ,5 7 36 ,1 7 68 ,0 7 94, 3 89 1, 1 9 53 ,9 9 78 ,3 1 00 2,8 1 04 2, 3 1 08 1, 9
3898 4108 4542 4569 4597 4624 6253 6449 6483 6503 6532 6557
77 77 77 78 78 78 79 79 80 80 80 80
3 Single Screw 4 Single Screw
4300 4300 4300 4300 4300 4300 4650 4650 4650 4650 4650 4650
1815 1815 1815 1815 1815 1815 2340 2340 2340 2340 2340 2340
2150 2150 2200 2200 2200 2200 1700 1700 1700 1700 1700 1700
Can be installed anywhere
• the special structure with base made
from thick galvanised steel plate section
bars ensures uniform weightdistribution.
Flexibility of use
• exclusive single-screw compressors
with avant-garde technology offering
excellent performance.
Reliability and build quality
• exclusive single-screw compressors
with avant-garde technology offering
excellent performance.
Condenserless water
chiller for indoor installation
with remote condenser
2 . 9 0 ÷ 2 . 2 4 0
3 . 2 6 0 ÷ 4 . 4 8 0
MSE
®
MSE 2.90-2.240
MSE 3.260-4.480
data refer to the following conditions:[1] evaporator water = 12/7°C; condensing temperature = 45°C;
[2] he sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
Accessibility
• all the components is easily accessible
for any maintenance or replacement
operations, with significant savings intime and money.
Energy saving
• part or all of the normally-lost
condensing energy can be recovered,
for the production of hot water for a
variety of uses.
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 15%
Standard
B
D
S
33
H Y D R O N I C
Sizes
DIVISION
R134a
CLIVET is an active member of the EUROVENT
certification program.
Mse R134a
Length
Depth
Height
Mse R134a
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
kW
Kg
dB(A)
mm
mm
mm
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
Dimensions
CLIVET is an active member of the
EUROVENT certification program.
Suitable for any kind of installation
• for renovations and all cases where
space is limited, the compact
dimensions of the unit simplifyinstallation.
Reliability and build quality
• guaranteed quality of all the
components installed.
MSECondenserless water chiller
for indoor installation with
remote condenser
®
data refer to the following conditions:[1] size 3.390÷3.540; evaporator water = 13/7 °C; condensing temperature = 45°C;
size 4.560÷4.720; evaporator water = 12/7 °C; condensing temperature = 45°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.32
Low noise Level
• wherever silent operation is required,
the units can be configured for reduced
noise emissions and transmission of vibrations to the support structures.
Control Logic
• the unit dynamically modulates the
temperature of the chilled fluid
according to the outside temperature,
thus optimising energy efficiency.
• a series of units installed to operate in
the same circuit communicate with
each other to optimise the management
of the various components.
DIVISION
3 . 3 9 0 ÷ 4 . 7 2 0
H Y D R O N I C
R407C
R22
HYDRONIC SPLIT SYSTEM PACKAGED
MSE
Mse R407C
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
Sizes
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 15%
Standard
B
D
S
830,9 900,0 958,41034,41084,01133,51183,01229,21283,11349,71398,61457,11506,01564,5
3708 4316 4656 5032 4990 5031 5071 6465 6732 7021 7052 7045 7076 7050
80 80 80 80 81 81 81 82 82 82 83 83 83 83
3 Single Screw 4 Single Screw
4300 4300 4300 4300 4300 4300 4300 4600 4600 4600 4600 4600 4600 4600
1815 1815 1815 1815 1815 1815 1815 2340 2340 2340 2340 2340 2340 2340
2150 2250 2250 2300 2300 2300 2300 1900 1900 1900 1900 1900 1900 1900
3.390 3.410 3.430 3.450 3.480 3.510 3.540 4.560 4.580 4.600 4.630 4.660 4.690 4.720 2.90 2.110 2.130 2.145 2.160 2.180 2.200 2.220 2.240
Single screw compressor
with satellites
Single screw compressorShell and tube heat
exchanger
Shell and tube heat
exchanger
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 13/15
Unit with semi-hermetic reciprocating type compressor
TERMINAL U NIT GEOTHERMIC CLOSECONTROL
Unit with semi-hermetic reciprocating type compressor
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
Dimensions
Low noise Level
• wherever silent operation is required,
the units can be configured for reduced
noise emissions and transmission of vibrations to the support structures.
Regulation
• a series of units installed to operate in
the same circuit communicate with
each other to optimise the management
of the various components.
Can be installed anywhere
• the special structure with base made
from thick galvanised steel plate section
bars ensures uniform weight
distribution.
Condenserless water
chiller for indoor installation
with remote condenser
2 . 7 0 ÷ 4 . 2 4 0
ME
®
ME
data refer to the following conditions:[1] evaporator water = 12/7°C; condensing temperature = 45°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.
Accessibility
• all the components is easily accessible
for any maintenance or replacement
operations, with significant savings intime and money.
Suitable for any kind of installation
• part or all of the normally-lost
condensing energy can be recovered,
for the production of hot water for a
variety of uses.
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 15%
Standard
B
D
S
35
H Y D R O N I C
Sizes
DIVISION
R22
CLIVET is an active member of the EUROVENT
certification program.
Me R22
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
Cooling capacity [1]
Shipping weight
Sound pressure level [2]
No. & Type of Compressors
Dimensions
CLIVET is an active member of the
EUROVENT certification program.
Reliability and build quality
• the use of plate exchangers, specifically
designed for use with ecological gas
and with perfectly opposing flows,optimises the heat exchange of the
water on the utility side.
Time is precious
• the careful design allows the unit to be
handled, positioned and connected on
site with extreme simplicity.
MECondenserless water chiller
for indoor installation with
remote condenser
®
data refer to the following conditions:[1] evaporator water = 12/7°C; condensing temperature = 45°C;
[2] the sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refersto a distance of 1m from the external surface of the units operating in an open field.34
Control Logic
• analyses the thermal requirements of
the system, optimising the compressor
starts and stops.• the unit dynamically modulates the
temperature of the chilled fluid
according to the outside temperature,
thus optimising energy efficiency.
Suitable for any kind of installation
• for renovations and all cases where
space is limited, the compact
dimensions of the unit simplify
installation.
• in systems with widely varying loads,
the reduced load phases are managed
intelligently so as to minimise energy
consumption.
DIVISION
2 . 7 0 ÷ 2 . 1 4 0
H Y D R O N I C
R407C
HYDRONIC SPLIT SYSTEM PACKAGED
ME
Me R407C
Length
Depth
Height
kW
Kg
dB(A)
mm
mm
mm
Sizes
Possible Configurations
Unit for production of chilled
water to -8°C
Partial recovery of condensing
heat, up to 25%
Standard
B
D
S
153,0 173,0 187,0 196,0 217,0 252,0 272,0 301,0 315,0
1040 1081 1117 1230 1329 1365 1436 1430 1437
80 80 80 81 81 81 81 84 86
2 Reciprocating
2750 2750 2750 2750 2750 2750 2750 2750 2750
770 770 770 770 770 770 770 770 770
1360 1360 1360 1360 1360 1360 1360 1360 1360
2.70 2.75 2.80 2.90 2.100 2.110 2.120 2.130 2.140
167,1 185,8 200,1 223,4 241,8 290,5 331,6 394,8 443,6 489,3 540,8 581,1
858 918 994 1123 1253 1630 1781 1978 2273 2453 2538 2642
82 82 82 82 82 85 85 85 85 85 87 88
2 Reciprocating 4 Reciprocating
2850 2850 2850 3049 3049 3080 3630 3630 3680 3680 3680 3680
700 700 700 700 700 700 950 950 950 950 950 950
1260 1290 1290 1290 1290 1365 1570 1570 1570 1570 1580 1580
2.70 2.75 2.80 2.90 2.100 2.120 4.140 4.160 4.180 4.200 4.220 4.240
Reciprocating
compressor
Reciprocating
compressor
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
ST
LNEN
Configuration:
Standard
Low noise
Extremely low noise
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 14/15
TERMINAL U NIT GEOTHERMIC CLOSECONTROLHYDRONIC SPLIT SYSTEM PACKAGED
0,300 0,450 0,300 0,450 0,550 0,750 0,450 0,550 0,750 0,900
0,80 1,20 0,80 1,20 1,50 2,00 1,20 1,50 2,00 2,40
72
87
8
800
150
65
150
600
400/3/50
600 x GPA 65 790 x GPA 150
470 x GPA 65 600 x GPA 150
790 x GPA 65 1186 x GPA 150
2 poles pump
Expansion tank
Storage tank capacity
Safety valve regulation
Power supply
Dimensions
The hydraulic circuit is installed quickly
• The hydraulic circuit is included in one
unit.
Control Logic• possibility of two pumps, one in reserve
to the other with automatic start.
Pumping station
0 0 ÷ 1 2
GP1Pumping station with
storage tank
GP2
®
GP1 - GP2
Ready to install: reliability and reduced
installation time
• choice of 12 pump sizes.
• storage tank available in 4 sizes.
Possible Configurations
Suitable kit available for connection
to chiller
Three-way valve
Auxiliary electric heating elements
Adjustable connection from and to the
installation (GP1)
37
H Y D R O N I C
Sizes
DIVISION
CLIVET is an active member of the
EUROVENT certification program.
Nominal power
Nominal abs. Current
Shipping weight
Capacity
Max pressure
Standard pressure
Length
Depth
Height
kW
A
Kg
L
kPa
kPa
L
kPa
V/Ph/Hz
mm
mm
mm
2 poles pump
Expansion tank
Storage tank capacity
Safety valve regulation
Power supply
Dimensions
CLIVET is an active member of the
EUROVENT certification program.
• wide range of available pump head
pressure.
• possibility to choose the right heating
inertia (2 sizes of storage tank).
GPA Pumping station with
storage tank
®
36
It does not leave empty space
• electrical panel.
• equipped with all hydraulic components
to optimize the installation.
Possible Configurations
Suitable kit available for connection
to chiller
Adaptation for operation as primary and
secondary circuit
DIVISION
M 0 ÷ M 9
H Y D R O N I C
GPA
Nominal power
Nominal abs. Current
Shipping weight
Capacity
Max pressure
Standard pressure
Length
Depth
Height
kW
A
Kg
L
kPa
kPa
L
kPa
V/Ph/Hz
mm
mm
mm
Sizes
GPA 65GPA150
GPA65
GPA150
M0 M1 M2 M3 M4 M5 M6 M7 M8 M9
GP1
0,5 0,6 0,9 1,1 0,8 1,2 1,1 1,5 2 2,3 1,5 2,1 2,6
0,8 1,1 1,8 2 1,6 2,2 2 2,8 3,6 4,4 2,8 3,6 4,5
70
130xGP2(300) 170xGP2(500) 205xGP2(600) 260xGP2(1000)
12 x GP1 16 x GP2 (300 e 500L) 24 x GP2 (600L) 32 x GP2 (1000L)
800
150
300 - 500 - 600 - 1000
600
400/3/50
616 (GP1.1 - GP1.2) 831 (GP2.1 - 300-500) 1356 (GP2.2 - 600-1000)
514 (GP1.1 - GP1.2) 831 (GP2.1 - 300-500) 865 (GP2.2 - 600-1000)
1299 (GP1.1 - GP1.2) 1502 (300) 2225 (500) 1502 (600) 2225 (1000)
GP1
GP2
GP2
00 1 2 3 4 5 6 7 8 9 10 11 12
GP2
Water pump close
coupled, body instainless steel, highefficiency single impeller
Water pump close
coupled, body instainless steel, high
efficiency single impeller
7/23/2019 Clivet Toplotne Pumpe
http://slidepdf.com/reader/full/clivet-toplotne-pumpe 15/15
2 poles pump
Expansion tank
Storage tank capacity
Safety valve regulation
Power supply
Dimensions
1,5 2,20 3,00 4,00
3,6 4,90 6,50 8,50
305 310 340 34524(600L) 32(1000L)
800
150
600 1000
600
400/3/50
1355
911
1505 x (600L) 2225 x (1000L)
Centrifugal pump
Expansion tank
Storage tank capacity
Safety valve regulation
Power supply
Dimensions
2 4
1,5 2,2 3,0 4,0 2,2 3,0 4,0 5,5 5,5 7,5 11,0 0,75 1,5 2,2 1,1 1,5 2,2 4,0 5,5 5,5 7,5
3 ,6 4 ,9 6 ,5 8 ,5 4 ,9 6 ,5 8 ,5 11, 511,515, 522,0 2 ,1 3 ,6 5 ,2 2 ,8 3 ,6 5 ,2 8 ,7 12, 412,415, 8552 556 565 574 570 572 582 610 625 628 674 579 595 614 601 602 633 698 710 710 720
74
800
150
1200 (2400 optional)
600
400/3/50
2040
1260 (1200L) 2520 (2400 L)
2113
TERMINAL U NIT GEOTHERMIC CLOSECONTROLHYDRONIC SPLIT SYSTEM PACKAGED
Low noise Level
• wherever silent operation is required,
the units can be configured for reduced
noise emissions and transmission of vibrations to the support structures.
Control Logic
• possibility of two pumps, one in reserve
to the other with automatic start.
Pumping station with
storage tank
6 0 ÷ 9 9
GPM
®
GPM
Certification
• guaranteed quality of all the
components installed.
• unit manufactured according to the ISO9001 quality standards and subject to
functional testing at the end of the
production line.
Possible Configurations
Standard
Primary circuit and fitted for the
secondary
1200 litre storage
2400 litre storage
S
P
A1
A2
39
H Y D R O N I C
Sizes
DIVISION
CLIVET is an active member of the
EUROVENT certification program.
Nominal power
Nominal abs. Current
Shipping weight (1200 L)
Capacity
Max pressure
Standard pressure
Length
Depth
Height
N° poles
kW
A
Kg
L
kPa
kPa
L
kPa
V/Ph/Hz
mm
mm
mm
CLIVET is an active member of the
EUROVENT certification program.
Control Logic
• possibility of two pumps, one in reserve
to the other with automatic start.
GP7Pumping station with
storage tank
®
38
“There is nothing else to be added”
• The hydraulic circuit is included in one
unit.
• equipped with all hydraulic componentsto optimize the installation.
Applicative versatility
• wide range of available pump head
pressure.
• 600 or 1000 l. storage tank.
Possible Configurations
Suitable kit available for connectionto chiller
Antifreeze heater with safety thermostat
Auxiliary electric heating elements
DIVISION
1 / 2 p o m p e
6 0 0 / 1 0 0 0 l
H Y D R O N I C
GP7
Nominal power
Nominal abs. Current
Shipping weight
Capacity
Max pressure
Standard pressure
Length
Depth
Height
kW
A
Kg
L
kPa
kPa
L
kPa
V/Ph/Hz
mm
mm
mm
Sizes
60 61 62 63 60 61 62 63 68 69 70 71 78 79 80 83 85 87 90 91 92 93 94 98 99
Centrifugal pump Centrifugal pump