Charlotte-Mecklenburg Schools Drinking Water Program …...Drinking Water Program Phase II –
Transcript of Charlotte-Mecklenburg Schools Drinking Water Program …...Drinking Water Program Phase II –
AECOM Technical Services of North Carolina, Inc.
5925 Carnegie Blvd
Suite 370
Charlotte, NC 28209
www.aecom.com
(704) 553-6150 tel
(704) 553-6151 fax
Charlotte-Mecklenburg Schools
Drinking Water Program Phase II – <1990 Administrative, Middle School
and High School Facilities
Laboratory Analytical Results Summary: Myers Park HS
2400 Colony Road
Charlotte, NC 28209
Sampling Date: 11/10/2018
Number of Consumption Points
Sampled: 95
Consumption Points with Values
Exceeding NCDEQ DWS: 2 (Pb) & 2 (Cu)
Low Value (µg/L): <0.40 (Pb - lead); <0.28 (Cu - copper)
High Value (µg/L): 140 (Pb - lead); 2,860 (Cu - copper)
Consumption Point(s) in Exceedance of NCDEQ DWS
Sample
Collection
Point ID
Sample
Collection
Date
Fixture
Type Location
Initial
Result
(µg/L)
Flush
Result
(µg/L)
CMS
Notification
Date
Corrective Action
466-KS-8 11/10/18 Kitchen
Sink
Football Field
Visitors
Concession Stand
22.6 (Pb) 1.89 (Pb) 12/5/18 Fixture taken out
of service 12/5/18
466-WC-1 11/10/18 Water
Cooler Cafeteria 2,860 (Cu) Pending 12/5/18
Fixture taken out
of service 12/5/18
466-WC-19 11/10/18 Water
Cooler
Auditorium –
Back Stage 140 (Pb) Pending 12/5/18
Fixture taken out
of service 12/5/18
466-WC-50 11/10/18 Water
Cooler
Hallway Outside
Room #SET-311 2,450 (Cu) Pending 12/5/18
Fixture taken out
of service 12/5/18
Notes:
Pb = Lead
Cu = Copper
NCDEQ = North Carolina Department of Environmental Quality
DWS = Drinking Water Standard (Pb = 15 µg/L, Cu = 1,300 µg/L)
µg/L = micrograms per liter or parts per billion (ppb)
Bolded, highlighted values indicate concentrations in excess of the respective NCDEQ DWS
* A detailed report summarizing all assessment and remediation activities will be provided upon completion of the Drinking Water Program Phase II
466-KS-8Myers Park HSKitchen SinkFootball Stadium Visitor's Side Concession Stand Sink
Sample Collection Point IDSchoolFixture TypeNotes
Sample Collection Date 11/10/2018
466-WC-1Myers Park HSWater CoolerCafeteria
Sample Collection Point IDSchoolFixture TypeNotes
Sample Collection Date 11/10/2018
466-WC-19Myers Park HSWater CoolerAuditorium - Back Stage
Sample Collection Point IDSchoolFixture TypeNotes
Sample Collection Date 11/10/2018
466-WC-50Myers Park HSWater CoolerHallway Outside of Room #SET-311 (left water cooler in pair)
Sample Collection Point IDSchoolFixture TypeNotes
Sample Collection Date 11/10/2018