CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
-
Upload
isaias-maqque-ramirez -
Category
Documents
-
view
214 -
download
0
Transcript of CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
1/19
Setting Out-Of-Step
Blocking or Tripping UsingDynamic Simulations
Yofre JacomeCOESPeru
Western Protective Relaying Conference
October, 2011
Charles HenvilleHenville Consulting
Inc.
Prepared by
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
2/19
2
Overview
Power Swing and Out-Of-Step
A Power Swing causes a Southern Peru
blackout An example setting study using Dynamic
Simulations and relay models in the same
software
Conclusions
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
3/19
3
Power Swing and Out-Of-Step
0
50
100
150
200
0 1 2 3 4 5
time (s)
Angle(Degrees)
Loss of synchronism
Oscillations leading to
stable equilibrium
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
4/19
Distance Relays
4
Power Swing and Out-Of-Step
P1
P2
P3
P1 : Steady state stability limit
P2: Transient stability limitP3 : Loss of synchronism
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
5/19
5
Power Swing and Out-Of-Step
Power Swing
Out-Of-Step
X
R
Power Swing
Out-Of-Step
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
6/19
6
Power Swing and Out-Of-Step
t/s-0.2 -0.1 -0.0 0.1 0.2 0.3 0.4 0.5 0.6
IR R
-10
0
10
t/s-0.2 -0.1 -0.0 0.1 0.2 0.3 0.4 0.5 0.6
IS R
-10
0
10
t/s-0.2 -0.1 -0.0 0.1 0.2 0.3 0.4 0.5 0.6
IT R
-10
0
10
t/s-0.2 -0.1 -0.0 0.1 0.2 0.3 0.4 0.5 0.6
VR R
-50
0
t/s-0.2 -0.1 -0.0 0.1 0.2 0.3 0.4 0.5 0.6
VS R
-50
0
t/s-0.2 -0.1 -0.0 0.1 0.2 0.3 0.4 0.5 0.6
VT R
-50
0
A power Swing is Usually Considered as an Three PhasePhenomena
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
7/19
7
A Trip During a Power Swing
SICN SISUR
Mantaro Cotaruse Socabaya
L-2054
L-2053
300 km 300 km
L-2052
L-2051
North-Center area (SICN) of the Peruvian power system
interconnection with the South area (SISUR),
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
8/19
8
A Trip During a Power Swing
L-2053 trips 3 phase simultaneously with single phase trip
on line L-2054
Trigger14/01/2010
02:41:57 p.m..593
t/s-0.4 -0.2 -0.0 0.2 0.4 0.6 0.8 1.0 1.2
SUM_CT_IL1/kA
-2
-1
0
1
t/s-0.4 -0.2 -0.0 0.2 0.4 0.6 0.8 1.0 1.2
SUM_CT_IL2/kA
-2
-1
0
1
t/s-0.4 -0.2 -0.0 0.2 0.4 0.6 0.8 1.0 1.2
SUM_CT_IL3/kA
-2
-1
0
1
t/s-0.4 -0.2 -0.0 0.2 0.4 0.6 0.8 1.0 1.2
LINE1_UL1/kV
-200
-100
0
100
t/s-0.4 -0.2 -0.0 0.2 0.4 0.6 0.8 1.0 1.2
LINE1_UL2/kV
-200
-100
0
100
t/s-0.4 -0.2 -0.0 0.2 0.4 0.6 0.8 1.0 1.2
LINE1_UL3/kV
-200
-100
0
100
Two phases carry the
power that was in sixOut of step
condition trips
remaining
two phases
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
9/19
9
A Trip During a Power Swing
Power Swing during the
dead time of the single
phasereclosing T
The rate of change of apparent impedance slows down
as the swing angle increases
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
10/19
System wide review of power
swing protection
Simulations carried out on power system
model with relay models included
Simulates system dynamic performance
And also simulates relay performance in
the same software
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
11/19
Load
Fault
Power Swing
11
3 Phase fault near Mantaro
2121
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
12/19
12
L-2052 3 phase fault near
Cotaruse
Load
Fault with series capacitor in service
Out-Of-Step
470 /sec
Fault with series capacitor by-passed
12
2121
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
13/19
Load
Fault with series
Capacitor in service
Out-Of-Step
650 /sec
Fault with series
Capacitor by-passed
131313
21 21
L-2054 3 phase fault near
Cotaruse
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
14/19
14
Load
Fault
Power Swing
L-2054 3 phase fault near
Socabaya
141414
21 21
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
15/19
Power swing blocking for external
fault
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
16/19
Power swing impedance may
remain in the first quadrant
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
17/19
17
Conclusions
Weakened transmission during single phase open
conditions may cause a power swing
Combined modeling of power system dynamics and relayperformance enhances the settings process
Knowing the rate of change of impedance allows trip and
block timers to be set easily
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
18/19
18
Conclusions
Out-Of-Step tripping must not be applied in all the lines.
Separation points should be carefully chosen in order to
save the system after out-of-step tripping.
As a result of the analysis of the event in the Peruvian
Power System, and the Coordination Study. Power swing
blocking and tripping functions were activated.
-
7/28/2019 CFH Markup Setting Out-Of-Step Protection Using Dynamic Simulations DR2
19/19
19
Questions?