GREE ELECTRIC APPLIANCES INC.OF ZHUHAI
CENTRIFUGAL CHILLER
TECHNICAL SALES GUIDE-50Hz
CAPACITY RANGE:1400~7200kW
SUPER HIGH AMBIENT OPERATION TO 52
(GC201210)
2
CONTENTS
MODELS LIST ..........................................................................................................................3
NOMENCLATURE ....................................................................................................................4
CHILLER COMPONENTS ..........................................................................................................5
ACCESSORIES .........................................................................................................................6
FEATURES ...............................................................................................................................7
PRODUCT DATA ......................................................................................................................9
DIMENSION ..........................................................................................................................16
INSTALLATION ......................................................................................................................18
WIRING DIAGRAMS .............................................................................................................20
MICROPROCESSOR CONTROL SYSTEM ...............................................................................25
BMS .....................................................................................................................................34
LONG-DISTANCE MONITORING SYSTEM ..............................................................................37
3
Digital Multi VRF Technical Sales Guide
1 MODELS LIST
Nominal Capacity Model Power Supply
Ton Refrigerant Model Name Ph, V, Hz398
R134a
LSBLX1400-M 3,380,50398 LSBLX1400V-M 3,380,50398 LSBLX1400-G 3,10000,50456 LSBLX1600-M 3,380,50456 LSBLX1600V-M 3,380,50456 LSBLX1600-G 3,10000,50511 LSBLX1800-M 3,380,50511 LSBLX1800V-M 3,380,50511 LSBLX1800-G 3,10000,50568 LSBLX2000-M 3,380,50568 LSBLX2000V-M 3,380,50568 LSBLX2000-G 3,10000,50625 LSBLX2200-M 3,380,50625 LSBLX2200V-M 3,380V,50625 LSBLX2200-G 3,10000,50682 LSBLX2400-M 3,380,50682 LSBLX2400V-M 3,380,50682 LSBLX2400-G 3,10000,50740 LSBLX2600-M 3,380V,50740 LSBLX2600V-M 3,380,50740 LSBLX2600-G 3,10000,50796 LSBLX2800-M 3,380,50796 LSBLX2800V-M 3,380,50796 LSBLX2800-G 3,10000,50854 LSBLX3000-M 3,380,50854 LSBLX3000V-M 3,380,50854 LSBLX3000-G 3,10000,50909 LSBLX3200-M 3,380,50909 LSBLX3200V-M 3,380,50909 LSBLX3200-G 3,10000,50967 LSBLX3400-M 3,380,50967 LSBLX3400V-M 3,380,50967 LSBLX3400-G 3,10000,50
1023 LSBLX3600-M 3,380,501023 LSBLX3600V-M 3,380,501023 LSBLX3600-G 3,10000,501081 LSBLX3800-M 3,380,501081 LSBLX3800V-M 3,380,501081 LSBLX3800-G 3,10000,501136 LSBLX4000-M 3,380,501136 LSBLX4000V-M 3,380,501136 LSBLX4000-G 3,10000,501251 LSBLX4400-M 3,380,501251 LSBLX4400V-M 3,380,501251 LSBLX4400-G 3,10000,501364 LSBLX4800-G 3,10000,50 1479 LSBLX5200-G 3,10000,50 1591 LSBLX5600S-G 3,10000,501706 LSBLX6000S-G 3,10000,501818 LSBLX6400S-G 3,10000,501934 LSBLX6800S-G 3,10000,502044 LSBLX7200S-G 3,10000,50
Note:1Ton =12000Btu/h = 3.517kW
4
LS B LX S V W
Motor Voltage and Frequency: G-10000V,50Hz;C-6000V,50Hz;M-380V,50Hz.
Variable Frequency: Invariable Frequency-Defaut;V-Variable Frequency.
Compressor Class:Single-Detault;S-Two-stage.
Nominal Capacity:Number(kW).
Compressor Type: LX-Centrifugal Compressor.
Compressor Form: B-Semi-hermetic Compressor.
Water Chiller Symbol.
Example:LSBLX4000-G —— Centrifugal chiller with the nominal capacity of 4000kW and the motor voltage of 10000V;LSBLX3600V-M —— Centrifugal chiller with the nominal capacity of 3600kW,the motor voltage of 380V and variable frequency;LSBLX5600S-G —— Centrifugal chiller with the nominal capacity of 5600kW,the compressor class of Two-stage and the motor voltage of 10000V.
2 NOMENCLATURE
5
Digital Multi VRF Technical Sales Guide
FRONT VIEW
18
17
11
10
9
8
1213
77
14
15
16
654321
REAR VIEW
27
29
2020
21
22
12
14
20303132
28
28
25 26
25
2423
19
3 CHILLER COMPONENTS
6
No. Legend
1 Chiller Electric Control Cabinet Assembly
2 Governing Mechanism Assembly
3 Balance Pipe
4 Centrifugal Compressor Assembly
5 Oil Filter
6 Motor
7 Right Water Assembly
8 Cooling Water Outlet
9 Cooling Water Inlet
10 Chilled Water Outlet
11 Chilled Water Inlet
12 Chiller Support Assembly
13 Motor Support Assembly
14 Liquid Reservoir Pipe
15 Evaporator
16 Oil Pump Control Cabinet
17 Oil Heater
18 Oil Level Sight Glasses
19 Condenser
20 Electronic Expansion Valve
21 Oil Pump
22 Oil Cooler
23 Exhaust Pipe Assembly
24 Suction Pipe Assembly
25 Auto Reset Relief Valve
26 Manometer
27 Chiller Identification Nameplate
28 Left Waterbox Assembly
29 Bypass Pipe Assembly
30 Orifice Plate
31 Refrigerant Filter/Drier
32 Refrigerant Purifier
Name Standard Option REMARK
Refrigerant √ R134a
Lube Oil √ No.68 synthetic fatty oil
Oil Filter √
Low-voltage Startup Cabinet √Match for the Chiller with the motor voltage of
380V
High- voltage Wiring Cabinet √Match for the Chiller with the motor voltage of
6000V and 10000V
4 ACCESSORIES
7
Digital Multi VRF Technical Sales Guide
● High efficiency and energy efficiency:Today’s owners of chilled water plants demand high efficiency and energy efficiency from their chillers. The GREE C centrifugal chillers, equipped with variable frequency drive, maximize chiller efficiency by optimizing compressor operation. Electric power consumption drops dramatically when the motor frequency low. The C chillers deliver industry-leading integrated part-load values (IPLV).The governing mechanism of the chiller use high efficiency ternary impeller and movable diffuser. The new impeller equipped with back sweep long-and-short vane, which ensure the high efficiency at full-load and part-load. The movable diffuser adjusts the area of gas flow passage and maximizes chiller efficiency at part load.New heat-exchanger reduces dramatically heat-exchange resistance when using ultra-high efficiency heat-exchange pipe and increase dramatically the chiller’s capacity and the coefficient of performance.
● Environmental leadership: GREE has long been committed to the environment and its sustainability. The GREE C centrifugal chillers provide our customers with a high-efficiency, chlorine-free long-term solution unaffected by refrigerant phaseouts. The GREE C centrifugal chillers utilize non-ozone depleting HFC-134A refrigerant provides our customers with a safe and environmentally friendly choice without compromising efficiency. Therefore, the effects of potential direct or indirect global warming are greatly diminished.
● Reliability: The chiller’s simple, positive pressure compressor, coupled with new high efficiency heat exchangers, ensures superior reliability and sustainability. The compressor designed by America Concepts NREC-constructed pro-fessional software and checked the oscillation and critical speed by Ansys and DyRoBeS software. GREE’s semi-hermetic motors operate in a clean-liquid, refrigerant-cooled environment. The semi-hermetic design eliminates the potential for shaft seal leaks and refrigerant/oil loss. These are just some of the reasons why the chillers have the industry’s lowest leak rate.High-strength aluminium alloy-constructed impeller has high strength and preferable corrosion resistance. The impeller is tested to ensure proper operation, including profile test, dynamic balance running and over-speed test and so on.
● Positive Pressure design: The chiller’s positive pressure design reduces dramatically the chiller size compared to low-pressure designs. The smaller size minimizes the need for valuable mechanical room floor space. In addition, positive pressure designs eliminate the need for costly low-pressure containment devices, reducing the initial cost of the system.
● Optional unit-mounted starter: Available in low-voltage wye-delta and solid state, the chiller’s unit-mounted starter provides a single point power connection, reducing chiller installation time and expense.
● Compressor features: The chillers with the capacity less than 5200kW are designed for single-stage compressor and
5 FEATURES
8
the chillers with the capacity more than 5200kW are designed for two-stage compressor. This design increases product reliability by eliminating the additional moving parts associated with multiple stage chillers, such as additional guide vanes and complex economizers.Capacity regulating device is composed of Inlet Guide Vane (IGV), high efficiency ternary impeller and movable diffuser, and orifice plate and electronic expansion valve, that can achieve capacity step-less regulation at 0~100% load and matches for actual load.The motors are hermetically sealed from the machine room, cooling is accomplished by spraying liquid refrigerant on the motor windings. This highly efficient motor cooling method results in the use of smaller, cooler-running motors than could be realized with air-cooled designs of the same type. Thus, hermetic motors require less inrush current and are smaller and lighter than comparable air-cooled motors.
● Heat exchangers feature: New heat-exchanger specially design for centrifugal chiller uniform the distribution of refrigerant and rationaliz-ation the temperature field, thus increase heat-exchange efficiency. The new heat-exchanger reduces dramatically heat-exchange resistance when using ultra-high efficiency heat-exchanger pipe and increase dramatically the chiller’s capacity and the coefficient of performance.The condenser baffle prevents direct impingement of high velocity compressor gas onto the condenser tubes. The baffle eliminates the related vibration and wears of the tubes and distributes the refrigerant flow evenly over the length of the vessel for improved efficiency.
● Advanced control system:The advanced control system provides unparalleled ease of operation and full automatic running of the chiller.The LCD(liquid crystal display) display chiller’s operating, status and diagnostic messages for improved user interface. Modular pull-out/plug-in design, reducing wiring requirements and providing easy installation, and low-voltage design, providing the ultimate assurance of personal safety and control integrity.
9
Digital Multi VRF Technical Sales Guide
6 PRODUCT DATA
6.1 Performance Parameter
Singler-stage
ModelLSBLX1400-M LSBLX1600-M LSBLX1800-M LSBLX2000-M
LSBLX1400-G LSBLX1600-G LSBLX1800-G LSBLX2000-G
Cooling capacitykW 1400 1600 1800 2000
RT 398 456 511 562
Capacity adjustment range % 10-100 10-100 10-100 10-100
EER W/W 5.53 5.46 5.61 5.65
IPLV W/W 6.10 6.21 6.38 6.43
Power supply-M Ph,V,Hz 3Ph,380V,50Hz
-G Ph,V,Hz 3Ph,10000V,50Hz
Power input kW 261 293 321 354
RLA-M A 450.6 505.9 554.2 611.2
-G A 17.1 19.2 21.1 23.2
Comperssor
Type - Semi-hermetic Centrifugal Compressor
Starting mode - star-delta
Quantity - 1
Refrigerant charge volume kg 330 360 600 625
Refrigeration oil
Type - No.68 synthetic fatty oil
Charge volume L 50 50 60 60
Evaporator
Type - Flooded Shell and Tube
Fouling factor ㎡ ·℃ /W 0.018 0.018 0.018 0.018
Water flow volumeL/s 66.9 76.4 86.1 95.6
GPM 1061 1211 1365 1514
Pressure dropkPa 75 75 75 75
ft.WG 25.1 25.1 25.1 25.1
Connection pipe mm 200 200 250 250
Condenser
Type - Shell and Tube
Fouling factor ㎡ ·℃ /W 0.044 0.044 0.044 0.044
Water flow volumeL/s 83.6 95.6 107.5 119.4
GPM 1325 1514 1704 1893
Pressure dropkPa 70 70 70 70
ft.WG 23.4 23.4 23.4 23.4
Connection pipe mm 200 200 250 250
Sound pressure level dB(A) ≤88 ≤88 ≤88 ≤90
DimensionOutline(WxDxH) mm 3630×1680×2060 3630×1680×2060 4150×1900×2250 4150×1900×2250
Package(WxDxH) mm 3700×1750×2130 3700×1750×2130 4200×1970×2410 4200×1970×2410
Net/Gross/Operting Weight kg 6300/6500/6800 6600/6800/7100 8800/9000/9800 9200/9400/10200
Loading quantity
40'GP/40'HQ set 0/2 0/2 0/2 0/2
10
ModelLSBLX2200-M LSBLX2400-M LSBLX2600-M LSBLX2800-M
LSBLX2200-G LSBLX2400-G LSBLX2600-G LSBLX2800-G
Cooling capacitykW 2200 2400 2600 2800
RT 625 682 740 796
Capacity adjustment range % 10-100 10-100 10-100 10-100
EER W/W 5.74 5.74 5.80 5.83
IPLV W/W 6.54 6.53 6.6 6.64
Power supply-M Ph,V,Hz 3Ph,380V,50Hz
-G Ph,V,Hz 3Ph,10000V,50Hz
Power input kW 383 418 448 480
RLA-M A 661.3 721.7 773.5 828.8
-G A 25.1 27.4 29.4 31.5
Comperssor
Type - Semi-hermetic Centrifugal Compressor
Starting mode - star-delta
Quantity - 1
Refrigerant charge volume kg 650 700 725 750
Refrigeration oil
Type - No.68 synthetic fatty oil
Charge volume L 60 80 80 80
Evaporator
Type - Flooded Shell and Tube
Fouling factor ㎡ ·℃ /W 0.018 0.018 0.018 0.018
Water flow volume
L/s 105.0 114.7 124.2 133.9
GPM 1664 1818 1968 2122
Pressure dropkPa 75 90 90 90
ft.WG 25.1 30.1 30.1 30.1
Connection pipe mm 250 250 250 250
Condenser
Type - Shell and Tube
Fouling factor ㎡ ·℃ /W 0.044 0.044 0.044 0.044
Water flow volume
L/s 131.4 143.3 155.3 167.2
GPM 2082 2272 2461 2650
Pressure dropkPa 70 85 85 85
ft.WG 23.4 28.5 28.5 28.5
Connection pipe mm 250 250 250 250
Sound pressure level dB(A) ≤90 ≤90 ≤90 ≤90
DimensionOutline(WxDxH) mm 4150×1900×2250 4350×2070×2500 4350×2070×2500 4350×2070×2500
Package(WxDxH) mm 4200×1970×2410 4650×2110×2660 4650×2110×2660 4650×2110×2660
Net/Gross/Operting Weight kg 9400/9600/10600 10800/11000/12800 11200/11400/13000 11600/11800/13200
Loading quantity
40'GP/40'HQ set 0/2 0/0 0/0 0/0
11
Digital Multi VRF Technical Sales Guide
ModelLSBLX3000-M LSBLX3200-M LSBLX3400-M LSBLX3600-M
LSBLX3000-G LSBLX3200-G LSBLX3400-G LSBLX3600-G
Cooling capacitykW 3000 3200 3400 3600
RT 854 909 967 1023
Capacity adjustment range % 10-100 10-100 10-100 10-100
EER W/W 5.74 5.78 5.84 5.70
IPLV W/W 6.53 6.57 6.65 6.48
Power supply-M Ph,V,Hz 3Ph,380V,50Hz
-G Ph,V,Hz 3Ph,10000V,50Hz
Power input kW 523 554 582 632
RLA-M A 903.0 956.5 1004.9 1091.2
-G A 34.3 36.3 38.2 41.5
Comperssor
Type - Semi-hermetic Centrifugal Compressor
Starting mode - star-delta
Quantity - 1
Refrigerant charge volume kg 775 800 825 900
Refrigeration oil
Type - No.68 synthetic fatty oil
Charge volume L 80 80 80 100
Evaporator
Type - Flooded Shell and Tube
Fouling factor ㎡ ·℃ /W 0.018 0.018 0.018 0.018
Water flow volume
L/s 143.3 152.8 162.5 171.9
GPM 2272 2421 2575 2725
Pressure dropkPa 90 90 90 115
ft.WG 30.1 30.1 30.1 38.5
Connection pipe mm 300 300 300 300
Condenser
Type - Shell and Tube Shell and Tube Shell and Tube Shell and Tube
Fouling factor ㎡ ·℃ /W 0.044 0.044 0.044 0.044
Water flow volume
L/s 179.2 191.1 203.1 215.0
GPM 2839 3029 3218 3407
Pressure dropkPa 85 85 85 100
ft.WG 28.5 28.5 28.5 33.5
Connection pipe mm 300 300 300 350
Sound pressure level dB(A) ≤90 ≤92 ≤92 ≤92
DimensionOutline(WxDxH) mm 4530×2070×2500 4530×2120×2500 4530×2120×2500 4750×2330×2750
Package(WxDxH) mm 4650×2160×2660 4650×2160×2660 4650×2160×2660 5000×2340×2910
Net/Gross/Operting Weight kg 11800/12000/13500 12000/12200/14000 12200/12400/14500 14600/14800/16500
Loading quantity
40'GP/40'HQ set 0/0 0/0 0/0 0/0
12
ModelLSBLX3800-M LSBLX4000-M LSBLX4400-M —— ——
LSBLX3800-G LSBLX4000-G LSBLX4400-G LSBLX4800-G LSBLX5200-G
Cooling capacity kW 3800 4000 4200 4800 5200
RT 1081 1136 1251 1364 1479
Capacity adjustment range % 10-100 10-100 10-100 10-100 10-100
EER W/W 5.74 5.81 5.50 5.82 5.91
IPLV W/W 6.53 6.62 6.55 6.62 6.72
Power supply-M Ph,V,Hz 3Ph,380V,50Hz —— ——
-G Ph,V,Hz 3Ph,10000V,50Hz
Power input kW 662 688 764 825 880
RLA-M A 1143.0 1187.9 1319.1 —— ——
-G A 43.4 45.1 50.1 54.1 57.7
Comperssor
Type - Semi-hermetic Centrifugal Compressor
Starting mode - star-delta
Quantity - 1
Refrigerant charge volume kg 925 950 1000 1050 1100
Refrigeration
oil
Type - No.68 synthetic fatty oil
Charge volume L 100 100 100 100 100
Evaporator
Type -Flooded Shell and
Tube
Flooded Shell and
Tube
Flooded Shell and
Tube
Flooded Shell and
Tube
Flooded Shell and
Tube
Fouling factor ㎡ ·℃ /W 0.018 0.018 0.018 0.018 0.018
Water flow
volume
L/s 181.7 191.1 210.3 229 248.3
GPM 2879 3029 3332 3636.203557 3936
Pressure dropkPa 115 115 115 115 115
ft.WG 38.5 38.5 38.5 38.5 38.5
Connection pipe mm 300 300 350 350 350
Condenser
Type - Shell and Tube
Fouling factor ㎡ ·℃ /W 0.044 0.044 0.044 0.044 0.044
Water flow
volume
L/s 226.9 238.9 262.8 287 310.6
GPM 3597 3786 4164 4543.053354 4922
Pressure dropkPa 100 100 105 105 105
ft.WG 33.5 33.5 35.2 35.2 35.2
Connection pipe mm 350 350 350 350 350
Sound pressure level dB(A) ≤92 ≤92 ≤92 ≤95 ≤95
DimensionOutline(WxDxH) mm 4750×2330×2750 4750×2330×2750 4750×2480×2750 4750×2480×2750 4750×2480×2750
Package(WxDxH) mm 5000×2340×2910 5000×2340×2910 5000×2490×2910 5000×2490×2910 5000×2490×2910
Net/Gross/Operting Weight kg 14800/15000/17000 15200/15400/17500 15800/16000/18000 16200/16400/18500 16600/16800/19000
Loading
quantity40'GP/40'HQ set 0/0 0/0 0/0 0/0 0/0
13
Digital Multi VRF Technical Sales Guide
Tow-stageModel LSBLX5600S-G LSBLX6000S-G LSBLX6400S-G LSBLX6800S-G LSBLX7200S-G
Cooling capacity kW 5600 6000 6400 6800 7200RT 1591 1706 1818 1934 2044
Capacity adjustment range % 10-100EER W/W 5.89 5.94 5.97 5.98 6.03 IPLV W/W 6.71 6.76 6.79 6.80 6.86
Power supply Ph,V,Hz 3Ph,10000V,50HzPower input kW 950 1010 1072 1138 1195
RLA/LRA A 62.3 66.3 70.3 74.7 78.4
Comperssor
Type - Semi-hermetic Centrifugal CompressorStarting mode
- direct start
Quantity - 1 1 1 1 1Refrigerant charge volume kg 1500 1600 1700 1800 1900
Refrigeration oil
Type No.68 synthetic fatty oilCharge volume
L 125 125 125 125 125
Evaporator
Type - Flooded Shell and TubeFouling factor ㎡ ·℃ /W 0.018 0.018 0.018 0.018 0.018
Water flow volume
L/s 267.5 286.7 305.8 325.0 343.9GPM 4239.3 4543.6 4846.3 5150.6 5450.1
Pressure dropkPa 125 125 125 125 125
ft.WG 41.0 41.0 41.0 41.0 41.0 Connection
pipemm 350 350 400 400 400
Condenser
Type - Shell and Tube Fouling factor ㎡ ·℃ /W 0.044 0.044 0.044 0.044 0.044
Water flow volume
L/s 334.4 358.3 382.2 406.1 430.0 GPM 5299.5 5678.3 6057.1 6435.8 6814.6
Pressure dropkPa 125 125 125 125 125
ft.WG 41.0 41.0 41.0 41.0 41.0 Connection
pipemm 400 400 450 450 450
Sound pressure level dB(A) ≤95 ≤95 ≤95 ≤95 ≤95
DimensionOutline(WxDxH) mm 5350×2620×3100 5350×2620×3100 5350×2820×3100 5350×2820×3100 5350×2820×3100
Package(WxDxH) mm 5800×2630×3260 5800×2630×3260 5800×2830×3260 5800×2830×3260 5800×2830×3260
Net/Gross/Operting Weight
kg 22500/22700/25950 23800/24000/27500 25500/25700/29450 26100/26300/30200 26500/26700/31000
Loading quantity
40'GP/40'HQ set 0/0 0/0 0/0 0/0 0/0
Note: 1.The performance stated above is measured under following conditions: Inlet/Outlet chilled water temperature: 12/7℃ (53.6/44.6 ℉ ); Inlet/Outlet cooling water temperature: 30/35℃ (86.4/95.4 ℉ ). 2.The product data is standard by the data in identification nameplate. If has other special request, please don’t hesitate to contact with us.
14
6.2 Performance Correction
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05
1.00
0.95
0.90
0.85
0.805678 91 01 11 21 3
(41) (43) (45) (46) (48) (50) (52) (54) (55)℃
(℉)
℃(℉)
Outlet Chilled Water Temperature
Cor
reot
ion
Valu
e of
Coo
ling
Cap
acity
Inle
t Coo
ling
Wat
er T
empe
ratu
re
20(68)
25(77)
30(86)
35(95)
Note:1. Actual Cooling Capacity=Nominal Cooling Capacity × Correction Value (Here: Nominal Cooling Capacity is looked up in the table of performance parameter and Correction Value is looked up in curve diagram above).2. The cooling capacity increases with the increase of outlet chilled water temperature and decreases with the decrease of outlet cooling water temperature.
15
Digital Multi VRF Technical Sales Guide
6.3 Electrical Data
Motor Model Motor CharacteristicElectrical Data (380V)
Max. Power Input(kW) Current(A)
YSR308-2-R134a(380V)RLALRYALRDA
36061513983916
YSR352-2-R134a(380V)RLALRYALRDA
41270315984475
YSR383-2-R134a(380V)RLALRYALRDA
44876517394869
YSR452-2-R134a(380V)RLALRYALRDA
52990320525746
YSR520-2-R134a(380V)RLALRYALRDA
609103923616611
YSR590-2-R134a(380V)RLALRYALRDA
690117926797501
YSR665-2-R134a(380V)RLALRYALRDA
778132930198454
YSR750-2-R134a(380V)RLALRYALRDA
878149834059535
YSR905-2-R134a(380V)RLALRYALRDA
10591808410911505
Motor Model Motor CharacteristicElectrical Data (380V)
Max. Power Input(kW) Current(A)
YSR308-2-R134a(10kV)RLA
LRDA360 23.4
148.8
YSR352-2-R134a(10kV)RLA
LRDA412 26.7
170
YSR383-2-R134a(10kV)RLA
LRDA448 29.1
185
YSR452-2-R134a(10kV)RLA
LRDA529 34.3
218.4
YSR520-2-R134a(10kV)RLA
LRDA609 39.5
251.2
YSR590-2-R134a(10kV)RLA
LRDA690 44.8
285
YSR665-2-R134a(10kV)RLA
LRDA778 50.5
321.3
YSR750-2-R134a(10kV)RLA
LRDA878 56.9
362.3
YSR905-2-R134a(10kV)RLA
LRDA1059 68.7
437.2
YSR995-2-R134a(10kV)RLA
LRDA1164 75.5
480.7
YSR1110-2-R134a(10kV)RLA
LRDA1299 84.3
536.2
YSR1250-2-R134a(10kV)RLA
LRDA1463 94.9
603.9
Legend:RLA: RATED LOAD AMPSLRYA: LOCKED ROTOR AMPS for Y startLRDA: LOCKED ROTOR AMPS for Δ start
16
7 DIMENSION
7.1 Dimension-Units
C
BA
RECOMMENDED OVERHEAD SE RVICE CLEARANCE: 1500 mm
E
F
D
Model Length A(mm) Width B(mm) Height C(mm) Length for Tube DrawingD(mm)
Length for Motor Service
Clearance E(mm)
Length for Chiller
Side Service Clearance
F(mm)LSBLX1400(V)-M(G) 4150 1730 2150 3500 1500 1220LSBLX1600(V)-M(G) 4150 1730 2150 3500 1500 1220LSBLX1800(V)-M(G) 4150 1900 2250 3500 1500 1220LSBLX2000(V)-M(G) 4150 1900 2250 3500 1500 1220LSBLX2200(V)-M(G) 4150 1900 2250 3500 1500 1220LSBLX2400(V)-M(G) 4530 2070 2500 3800 1650 1320LSBLX2600(V)-M(G) 4530 2070 2500 3800 1650 1320LSBLX2800(V)-M(G) 4530 2070 2500 3800 1650 1320LSBLX3000(V)-M(G) 4530 2120 2500 3800 1650 1320LSBLX3200(V)-M(G) 4530 2120 2500 3800 1650 1320LSBLX3400(V)-M(G) 4530 2120 2500 3800 1650 1320LSBLX3600(V)-M(G) 4750 2330 2750 4000 1800 1320LSBLX3800(V)-M(G) 4750 2330 2750 4000 1800 1320LSBLX4000(V)-M(G) 4750 2330 2750 4000 1800 1320LSBLX4400(V)-M(G) 4750 2380 2750 4000 1800 1320
LSBLX4800-G 4750 2380 2750 4000 1800 1320LSBLX5200-G 4750 2380 2750 4000 1800 1320LSBLX5600S-G 5350 2620 3100 4400 1800 1520LSBLX6000S-G 5350 2620 3100 4400 1800 1520LSBLX6400S-G 5350 2820 3100 4400 1800 1520LSBLX6800S-G 5350 2820 3100 4400 1800 1520LSBLX7200S-G 5350 2820 3100 4400 1800 1520LSBLX7800S-G
17
Digital Multi VRF Technical Sales Guide
7.1 Dimension-Units
D
A BCE
EVAPORATOR
CONDENSER
F
DRIVE END: Cooler Waterboxes: Inlet; Outlet Condenser Waterboxes: Inlet; Outlet
Model Length A(mm) Width B(mm) Height C(mm) Length for Tube DrawingD(mm)
Length for Motor Service
Clearance E(mm)
Length for Chiller
Side Service Clearance
F(mm)LSBLX1400(V)-M(G) 4150 1730 2150 3500 1500 1220LSBLX1600(V)-M(G) 4150 1730 2150 3500 1500 1220LSBLX1800(V)-M(G) 4150 1900 2250 3500 1500 1220LSBLX2000(V)-M(G) 4150 1900 2250 3500 1500 1220LSBLX2200(V)-M(G) 4150 1900 2250 3500 1500 1220LSBLX2400(V)-M(G) 4530 2070 2500 3800 1650 1320LSBLX2600(V)-M(G) 4530 2070 2500 3800 1650 1320LSBLX2800(V)-M(G) 4530 2070 2500 3800 1650 1320LSBLX3000(V)-M(G) 4530 2120 2500 3800 1650 1320LSBLX3200(V)-M(G) 4530 2120 2500 3800 1650 1320LSBLX3400(V)-M(G) 4530 2120 2500 3800 1650 1320LSBLX3600(V)-M(G) 4750 2330 2750 4000 1800 1320LSBLX3800(V)-M(G) 4750 2330 2750 4000 1800 1320LSBLX4000(V)-M(G) 4750 2330 2750 4000 1800 1320LSBLX4400(V)-M(G) 4750 2380 2750 4000 1800 1320
LSBLX4800-G 4750 2380 2750 4000 1800 1320LSBLX5200-G 4750 2380 2750 4000 1800 1320LSBLX5600S-G 5350 2620 3100 4400 1800 1520LSBLX6000S-G 5350 2620 3100 4400 1800 1520LSBLX6400S-G 5350 2820 3100 4400 1800 1520LSBLX6800S-G 5350 2820 3100 4400 1800 1520LSBLX7200S-G 5350 2820 3100 4400 1800 1520LSBLX7800S-G
Note: 1. The product data is standard by the data in identification nameplate. If has other special request, please don't hesitate to contact with us.2. The dimensional data-nozzle above is base on the inlet/outlet on drive end and we also provide the products with the inlet/outlet on compressor end. If need, please don't hesitate to contact with us.
18
8 INSTALLATION
8.1 Request for Wiring and Tube Layout
8.2 Machine Footprint
The general requests for wiring and tube layout as follow:1. Certified field wiring and dimensional diagrams are available on request.2. All wiring and tube layout must be installed perfectly and comply with applicable codes.3. Electric cable must according to national electric standard, and the electric cable must be insulated.4. All wiring connect should be reliable and shouldn' t loose and pull-off connect. 5. Nozzle connect should be burnished flat and smooth, and pipeline should clear and have no fouling products.6. Filter screen must be installed in pipeline of chilled water and cooling water.7. To prevent the water washing and eroding the heat-exchange tube, flow governor valve must be installed in outlet.8. It should install temperature and pressure transducer in inlet/outlet chilled and cooling water. 9. The tubing of chilled and cooling water should support by support to prevent adding the load to evaporator and condenser.
Soleplate
300
Steel Base Plate (User Supplied)
Center Line (Condenser)
Center Line (Evaporator)
125
250
70
300
500
F
E
A
A
Model E F Model E F
LSBLX1000(H)(V)G 2790 1430 LSBLX3600(H)(V)G 3790 2080
LSBLX1200(H)(V)G 2790 1430 LSBLX3800(H)(V)G 3790 2080
LSBLX1400(H)(V)G 2790 1430 LSBLX4000(H)(V)G 3790 2080
LSBLX1600(H)(V)G 2790 1430 LSBLX4400(H)(V)G 3790 2230
LSBLX1800(H)(V)G 3290 1650 LSBLX4800HG 3790 2230
LSBLX2000(H)(V)G 3290 1650 LSBLX5200HG 3790 2230
LSBLX2200(H)(V)G 3290 1650 LSBLX5600SHG 4190 2370
LSBLX2400(H)(V)G 3590 1820 LSBLX6000SHG 4190 2370
LSBLX2600(H)(V)G 3590 1820 LSBLX6400SHG 4190 2570
LSBLX2800(H)(V)G 3590 1820 LSBLX6800SHG 4190 2570
LSBLX3000(H)(V)G 3590 1870 LSBLX7200SHG 4190 2570
LSBLX3200(H)(V)G 3590 1870 LSBLX7800SHG 4590 2570
LSBLX3400(H)(V)G 3590 1870
19
Digital Multi VRF Technical Sales Guide
To prevent eroding of chiller footing, request good drainage around the chiller and flat and smooth footprint,the specific requests as follow:1.The maximal difference in height (degree of level) among the footprints should less than 3mm;2.To service and clear easily, the height of footprint should higher 100mm than ground;3.Should set discharge ditch around the chiller;4.It must have no gaps between accessory soleplate and chiller’s soleplate.5.It must do second grout filling fix around accessory soleplate and adjusting shim.
45°
250
Gro
utin
g H
eigh
t500
>10
0
Washer (User Supplied)Screw M30 (User Supplied)Anchor Bolt (User Supplied)
350
Grouting
SoleplateRubber Plate 15mm Thick
200X200
A-A
ground
Steel Base Plate20mm Thick (User Supplied)
Note: 1. Dimensions in figure are in millimeters.2. It should stuff adjusting shim between accessory soleplate and footprint.3. Sling the chiller and lay the isolation rubber seat retainer on the soleplate, then lay the chiller on the rubberseat retainer rightly.4. Do grout filling fix after perching the chiller on footprint rightly and the grouting height is 500mm.
8.3 Isolation Style of Machine Footprint
20
9 WIRING DIAGRAMS
19 20
21
22
33
65
66
8 7XT3
XT3
6566
W37
IN
OUT
1 2
XT3
XT3
3XT3
4XT3
FS 5 6
XT3
XT3
Ormon mid.relay
KA2
27
26
34
28
W38
W39
W64
W65
W61
YEGN
W110
W111
W112
W113
W114
W115
W116
W117
W119
39
40
X40
W134
W135
W136
W137
N8 g
63 SP1
X2
SP2
X3
SP3
W102
X4
SP4
W138
W139
W144
W132
W145
W146
W147
W148
W149
W150
W152
W154
W156
W158
W151
W153
W155
W157
W159
TCi
DC
TCv
AP2
YV3
YV2
YV1
XT5
PE
BU
BN
BU
BN
BU
BU
BU
BU
BU
YEGN
Control box
Star
tup
Cab
inet
Current in the startup
cabinet sampling
startup
cabinet
malfunction
XT
XT
XT
XT4 AP1
W140
W142
TC
TCt
QF1
POWER
X55
4344
PTC
X67
44
123
4567891011121314
123
4567
8910 11121314
12
XT
64
W101
X66
13
W133
W131
W141
14
N L1
W161
W160
XT 1
PE
PE
W166
PE
installation
board
Door of
the cabinet
K4
W127
YEGN
XT4-f
XT4-N7
YV4
W162
W163
W164
W165
W167
W168
W169
W170
PE
PE
PE
W172
W171
2 1
W173
W174
XT5
PE
df
1XT
XT
XT4-d
XT4-N5
XT4-N4
N1
L1
M4
XT4-L1XT4-N1
Cooling fan
Controlling circuit to
the startup cabinet
21
65
thermal switch in COMP
SB
FUSE:50T 3.15A 250V~
TCv
X16
CN1
TC
M3
X18X6
IN
OUT
XT4-e
XT4-N6
4142
4748
TCt
ST2
QF1
15
17 18
16
SB
XT4-c
PTC
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
W11
W12
W14
W15
W16
W17
W18
W19
W20
W21
W22
W23
W106
W108
W13
W107
W109
W24
W25
W26
W27
W28
W29
W30
W31
W32
W33
W34
W35
W36
W40
W118
W46
W41
W45
W44
W43
W48
W49
W42
W47
W50
W51
W52
YEGN
W120
YEGN
W121
W122
W123
W124
W55
W56
W125
W57
W126
W58
W53
W54
W59
W60
W66
W67
W68
W75
W76
W69
W70
W80
W77
W78
W79
W128 W129
W90
W91
W92
W93
W94
W95
W96
W97
W98
W81
W82
W83
W84
W85
W86
W87
W88
W89
W103
W104
W105
W99
W143
W100
W130
XT4
8PM1
FR2
10
AP2
V+
V-
DC POWER2
XT4-a
XT4-N2
LN
W62
W63
W73
W74
W71
W72
4546
49505152535455565758
V+
V-
ST1
ST4ST5ST6
ST7ST8
5960
ST9
X23
X27
X26
X28
X39
X38
KM4
KM3
X43
TCi
PM2
N2
23
25
11
29
31
35
37
38
36
32
30
12
924
X20 AC-L
X21 AC-N
3 4
Tangibly
screen
+-
Display Dirgram
DC POWER1
XT4-b
XT4-N3
Breaker of 2 poles
FUSE
LN
YEGN
4
X35
65
7
FR
6162
INGND
X31
X34
X32
X33
X1
SA
SU1
SU2
X37
DC12V
32
N4
N6
N3
N5
N7
ac
eb
NAME
SYMBOL
X13
X14
X12
X11
X8
Controlling mainboard
AP1
X42
X50
X22
X24
X19
KM2
KM1
POWER
Co
ntro
l ca
bin
et w
iring
(38
0V)
21
Digital Multi VRF Technical Sales Guide
Co
ntro
l ca
bin
et w
iring
(10
000V
)
4546
49505152535455565758
V+
V-
ST1
ST4ST5ST6
ST7ST8
5960
ST9
X23
X27
X26
X28
X39
X38
KM4
KM3
X43
TCi
PM2
N2
23
25
29
31
35
37
38
36
32
30
24
X20
X21
3 4
-
DC POWER1
XT4-b
XT4-N3
FUSE
LN
4
X35
65
7
FR
6162
INGND
X31
X34
X32
X33
X1
K4
SA
SU1
SU2
X37
DC12V
3
2
N4
N6
8 7XT3
XT3
1413
IN
OUT
1 2
XT3
XT3
3XT3
4XT3
FS-61
5 6XT3
XT3
27
26
34
28
W39
W64
W65
W61
W110
W111
W112
W113
W114
W115
W116
W117
W119
39
40
X40
W134
W135
W136
W137
N8 g
63 SP1
X2
SP2
X3
SP3
W102
X4
SP4
W138
W139
W144
W142
W145
W146
W147
W148
W149
W150
W152
W154
W156
W158
W151
W153
W155
W157
W159
TCi
DC
TCv
6 5 4 3
7 8 1 2
1 2 3 4
5 6 7 8 AP2
42
N3
N5
N7
ac
eb
df
1XT
XT
XT4-d
XT4-N5
XT4-N4
N1
L1
M4
XT4-L1
XT4-N1
21
65
SB
FUSE:50T 3.15A 250V~
TCv
X16
CN1
TC
M3
X18X6
IN
OUT
XT4-e
XT4-N6
4142
4748
TCt
ST2
QF1
15
17 18
16
SB
XT4-c
PTC1
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
W11
W12
W14
W15
W16
W17
W18
W19
W20
W21
W22
W23
W106
W108
W13
W107
W109
W24
W25
W26
W27
W28
W29
W30
W31
W32
W33
W34
W35
W36
W40
W118
W46
W41
W45
W44
W48
W49
W42
W47
W50
W51
W52
W120
W121
W122
W123
W124
W55
W56
W125
W57
W126
W58
W53
W54
W59
W60
W66
W67
W68
W75
W76
W69
W70
W80
W77
W78
W79
W128 W129
W90
W91
W92
W93
W94
W95
W96
W97
W98
W81
W82
W83
W84
W85
W86
W87
W88
W89
W103
W104
W105
W99
W178
W100
W140
XT4
8PM1
V-
V+
DC POWER2
XT4-a
XT4-N2
LN
W62
W63
W73
W74
W71
W72
19 20
21
22
33
14
13
X13
X14
X12
X11
X8
Mainboard
AP1
X42
X50
X22
X24
X19
KM2
KM1
POWER
XT
XT
XT
XT4 AP1
W175
W177
TC
TCt
QF1
POWER
X55
4344
PTC2
X67
44
5678910 1112
5678910 1112
12
XT
65
W143
W141
W176
N L1
W161
W160
KM
N7
910
11
12
64
66
W101
FS-62
W37
W38
W130
W132
W131
W133
KM
W166
PE
PE
PE
PE
PE
PE
PE
PE
W43
+
W127
XT2
AP2XT4-f
XT4-N7
YV4
W162
W163
W164
W165
W167
W168
W169
W170
2 1
W174
XT5 YV3
YV2
YV1
W173
W172
YV5
W171
FUSE
Tangibly
screen
installation
board
Door of
the cabinet
Control box
Star
tup
Cab
inet
Controlling circuit to
the startup cabinet
Current in the startup
cabinet sampling
startup
cabinet
malfunction
NAME
SYMBOL
Breaker of 2 poles
Cooling fan
Ormon mid.relay
BU
BN
BU
BN
22
Power cabinet wiring:PO
WER W
1
W2
W3
L1 L3L2 N XT1
PEFS
EW
4W
5W
6
KM1
HL1
226
W27
W24
W13
W18
13
W11
W10
W12W
T3W
221
1 L1 L2 L3 L4
PM2
FSQ
F2K
M1
KM2
PM2
XT3
XT2
XT1 KM
2FS W
35W
34W
33W
32W
31W
30W
15W
14
W23
65
43
21
XT3
KM2
QF2
24
51
XT2
W7
W8
W9
135 5
13 246
L1L2
L3
W36
W37
W38
W28
Oil
pum
pU
VW
M2
W19
EW
25HL2
W26
W16
W29
HL3
XT2 W20
W21
W39
AB W
U
Oil
heat
erE
E
Doo
r of
the
cabi
net
Cont
rol c
abin
etXTXT
3
W17
87
Oil
pum
pO
il he
ater
Oil
pum
p
cont
rollin
gco
ntro
lling
over
load
E
E
1315
1617
1825
2634
33Q
F1NL1
87
65
43
21
26
Note:
the
wire
conn
ectio
n be
twee
n po
wer a
nd co
ntro
l cab
inet
show
s belo
w.
s
tand
for t
he se
quen
ces i
n th
e ter
mina
l boa
rd,
pow
er ca
bine
t.
23
Digital Multi VRF Technical Sales Guide
Typical wiring (10kV)
Centrifugal Chiller
Startup Cabinet
Main Power Cable from the Local Distribution Box
Note:Wire ① :Main power cable.Wire :Power Cable between Freestanding Compressor Motor Starter and Compressor Motor.Wire ③ :Power Cable between Low Voltage Power (380V 3N~) and Power Box.Wire ④ :Signal Cable between Freestanding Compressor Motor Starter and Control Box.Wire ⑤ :Signal Cable between Control Box and other equipment (Pump. Fan……)
Chi
lled
Pum
p C
onta
ctor
(220
V~)
Coo
ling
Pum
p/Fa
n C
onta
ctor
(220
V~)
Rem
ote
Sw
itch
Main Power
FreestandingCompressor MotorStarter Low Voltage Power
380V 3N~
Compressor Motor
PE
PE
PE
PE
PE
Control BoxPower Box
24
Typical wiring(380V)
Centrifugal Chiller
Startup Cabinet
Main Power Cable from the Local Distribution Box
Note:Wire ① :Main power cable.Wire :Power Cable between Freestanding Compressor Motor Starter and Compressor Motor.Wire ③ :Power Cable between Low Voltage Power (380V 3N~) and Power Box.Wire ④ :Signal Cable between Freestanding Compressor Motor Starter and Control Box.Wire ⑤ :Signal Cable between Control Box and other equipment (Pump. Fan……)
M
Chi
lled
Pum
p C
onta
ctor
(220
V~)
Coo
ling
Pum
p/Fa
n C
onta
ctor
(220
V~)
Rem
ote
Sw
itch
Main Power
Startup Cabinet
Compressor Motor
Oil PumpCabinet Control Cabinet
PE
PE
PE PE
PE
25
Digital Multi VRF Technical Sales Guide
10MICROPROCESSOR CONTROL SYSTEM
The chiller is allowed to be turned on only after the controller detects that all input signals goes normal: the start/stop of the compressor and the position of the preroation vane are dependent on the leaving chilled temperature and amperage of the motor; if anti-freezing measures should be taken for the evaporator is dependent on the leaving water temperature and the evaporating pressure; if the cooling water in the condenser is overheated is controlled by the condensing pressure; the opening angle of the electronic expansion valve automatically varies as the change of the temperature of the motor winding; the oil temperature is controlled and adjusted also by the electronic expansion valve; the compressor can be restarted only after it has turned off for at least 20 minutes; the oil heater acts depending on the oil sump temperature.
10.2.1 Outline Drawing of the Touch Screen
① ② ③ ④
Fig.1 Outline① .Power LED (PWR): Yellow; when the touch screen is powered on, the LED lights up.② .CPU LED (CPU): Green; when the touch screen is working normally, the LED lights up.③ .Communication LED (COM): Red; when the touch screen is communicating with other devices, the LED blinks.④ .LCD: Touch Screen and Color Liquid Crystal Display
10.1 General Control Design
10.2 Controller
26
10.3.1 Menu Bar
Fig.2 Menu BarMenu bar is on the bottom of the screen and the function of each touch button is described below:1). “CURVE”: Touch it to enter the CURVE screen to review the current and history curves of pressure, temp, etc.2). “EVENT”: Touch it to enter the EVENT screen to review the event record, such as error record and compressor record.3). “SET”: Touch it to enter the SET screen to set user parameters or factory parameters.4). “VIEW”: Touch it to enter the VIEW screen to check the current running status of the unit, version information. etc.5). “HOME”: Touch it to return to HOME screen.
10.3.2 Popped-up Window
Smaller than the full screen, the popped-up window is attached to the current screen and is used for information prompt, data input, password input and modification, function setting, etc. The popped-up window can be moved correspondingly by touching and moving the control strip on the trop of the popped-up window.
Fig.3 Popped-up Window
10.3.3 Numerical Value Input
There are generally two ways to input the numerals. One is touching the key “INC”/ “DEC to increase/decrease the original value; the other is to directly input the numerals through the small keyboard, as shown below.
Input by “INC” and “DEC” Input by small keyboardFig. 4 Input by “INC”/ “DEC” Input Fig.5 Input by Small Keyboard
10.3 Basic Screens and Operations
27
Digital Multi VRF Technical Sales Guide
By slightly touching the number input part, the small keyboard will appear along with the blinking cursor, which indicates values can be input herein. Then, touch the number on small keyboard to input the expected value. Finally, touch ENT to confirm the input and meanwhile the small keyboard disappear to end this input.Introduction to Buttons on the Small Keyboard1 ). Number Button: they are used to input numbers 0~9.2). “.”: it is used to input the decimal point.3). “ES”: it is used to close the small keyboard and cancel the input.4). “CR”: It is used to clear the currently input values and then input again.5). “ENT”: it is used to confirm the input. After that, the small keypad will disappear and the input is ended.
10.3.4 Welcome Screen
When the touch screen is powered on, what firstly emerges is the welcome screen as shown below and five seconds later it will switch to the HOME screen.
Fig.6 Welcome Screen
10.3.5 HOME Screen
HOME Screen
28
HOME screen is the main control screen and any other screen will be returned to the HOME screen if there is no any operation on the touch screen for 10min. HOME screen displays basic system information and control information such as system time, running status (OFF/ON), chilled water-in/out temperature, cooling water-in/out temperature and compressor status. Additionally, it can also show if the unit is networked properly and if any error occurs.
① .This black part represents ON/OFF status of the compressor 1. When the compressor 1 starts up, black is changed to green; when the unit is turned off, it turns back to black.
② .Entering Chilled Water Temperature③ .Leaving Chilled Water Temperature④ .Entering Cooling Water Temperature⑤ .Leaving Water Temperature
10.3.6 SET Screen
Touch SET on the menu bar and then a password input dialog box will pop up as shown below:
Only after the correct password has been input (default:101010) is it available to go to the parameter setting screen though which the user can configure various parameters, including “LCHW Temp Setting” (Leaving Chilled Water Temperature), “Oil Pump Control”, “Manual Oil-return”, “Water Storage”, “Timing Setting”, “Clocking Setting”, “Modbus Address”, “Control Mode”, “Remote Switch”, “Touch Sound”, “User Password”, and “Save to U Disk” etc. as shown below.
Fig.9 User Setting Screen The function of each touch button is described below:1).“INC”: Slightly touch it to increase the set temperature.2).“DEC”: Slightly touch it to decrease the set temperature.3).“Oil Pump Control”: slightly touch it to select the desired option, “Manual” or “Auto”. Under
29
Digital Multi VRF Technical Sales Guide
the “Manual” mode, it has two sub-options, “On” and “Off”.4).“Manual Oil-return”: slightly touch it to select the desired option, “Forbid”, or “Allow”.5).“Control Mode”: touch the option “Manual” or “Timing” of the Control Mode to select the desired one. Note: Under the Timing mode, the unit can also be turned on/off manually. Only when the timing setting is done and activated can Timing functions. However, when “Remote Switch” is set to “Allow”, “Control Mode” will be deactivated just with “R. M.” displayed where “Manual” or “Timing” once was.6).“Water Storage”: Slightly touch it and then a dialogue box will pop up where parameters related to this function can be set.7).Note: under this mode, the “LCHW Temp Setting” will be replaced by the “Water Storage” temperature setting which is un-adjustable.8).“Timing Setting”: Touch it to go the Timer Set screen as shown below:
Fig. 10 Time Setting ScreenThere are three timing modes: Mode 1, Mode 2, and Mode 3, each has 6 setting period. Each period include when to start the unit, when to stop the unit as well as if the timer setting is activated. Once the timer setting is done, by touching Mon./Tue./Wed/Thu./Fri./Sat./Sun., four mode options “--“/”1”(Mode 1)/”2”(Mode 2)/”3”(Mode 3) will be available to be selected circularly. Notes:
a.After the timing setting is done, only Control Mode is set to “Timing” can this setting work.
b.If the timing ON and/or timing OFF in the same day is set to be the same, the latter period setting will always be given the priority to be executed.8).“Clock Setting”: Touch Enter on the menu bar and then a dialog box will pop up where the year, month, day, hour, minute and second can be set. When setting, touch the part for inputting numeric value and then the small keyboard will pop up. After the desired values are input, touch Enter on the small keyboard to confirm and finish this operation.9).“Modbus Address”: It is used to set the address of the touch screen for Modbus communication which will realize the long-distance monitoring to the air conditioning unit. However, this setting does work for the unit without this function.10).“Remote Switch”: Touch the option “Allow” or “Forbid” of Remote ON/OFF to select the desired option. When “Allow” is selected, ON/OFF operation on the HOME screen and Timing do not work.11).“Touch Sound”: By touching it two options “ON”/“OFF” of the Touch Sound are available to be selected alternately12).“User Password”: It is intended for modifying user passwords, which is used to enter the User Setting screen as well as execute the ON/OFF operation on the HOME screen.13).“Save to U Disc”: It is for the EVENT and CURVE download as for backup. Thus, data can be opened and viewed in the file format of “txt” through a computer.14).Factory “Parameter”: slight touch “Parameter” and then a dialogue box will pop up which prompts to input the correct password. Factory parameters are mainly intended for
30
commissioning but not for the user. Modification to any parameter is password protected.Note: Haphazard modification to the factory parameters would cause serious impacts on the unit, so only professional personnel are allowed to take this operation.15).“English”/“ 中文 ”: slightly touch “English” to go to the screen in English and “ 中文 ”to go to the screens in Chinese.
10.3.7 VIEW Screen
Touch VIEW on the menu bar to enter the VIEW screen which provides detailed information for the running of the unit. There are totally 3 pages, first page: basic temperature and pressure data; second page: unit parameters, switching values of the water system, running information of the unit, etc; third page: switching value of the compressor.
Fig.11 Page One
Fig.11 Page Two
Fig. 12 Page Three
31
Digital Multi VRF Technical Sales Guide
10.3.8 EVENT Screen
1). Touch EVENT on the menu bar to enter EVENT screen which provides users with specific running errors of the unit and information of other events, such as startup of the compressor.2). Event records are classified into Current Event and History Event. Current Event displays the events after energization of the touch screen and they can only be found in the History Event after the touch screen is restarted.3). Touch HISOTRY on the Current Event screen to enter the History Event screen. History Event is intended to record the events which have happened and would also be saved even if power failure occurs. In the History Event screen, touch PREV or NEXT to switch to the previous or next page which is listed in the date order.4). CLEAR: touch it to clear the current error and take the error check again. Note: this function only enables the system to detect the error again after the error is manually cleared. However, the error has not been eliminated actually.
Fig. 16 Current Event
Fig. 17 History Event
10.3.9 CURVE Screen
1). Curve records are intended to display visually the status of key parameters of the unit (including both the temperature and pressure curves).2). Curve records are classified into Current Curve and History Curve. Current Curve is used to record the curve data after the touch screen is energized and they can only be found in the History Curve after the touch screen is restarted. History Curve is used to record the events which have happened and would also be saved even if power failure occurs.
32
Fig. 16 Current Curve
Fig. 17 History Curve
10.3.10 Others
For saving energy, if there is no operation to the touch screen for 30min, backlight will be turned off automatically and the screen becomes black until next touch operation occurs.This touch screen is universally designed based on the maximum capacity of the system, applicable to both the unit with a single compressor and the one with two compressors. Therefore, some contents and functions of the touch screen may only be intended for some specific units but invalid or meaningless for others. For instance, if the unit is only with a single compressor, the display and control for the compressor 2 are inapplicable.Note: the touch screen saves data every 3 min. That is, as soon as some parameter is set, it would fail to save the parameters successfully if power failure occurs in 3min.Please consult the manufacturer for specific configurations of the unit.
10.3.11 Quick Search for Common Operations
ON/OFFOn the HOME screen, touch ON or OFF to send the unit-on or unit-off command, which will also be reflected on the HOME screen. Startup of the unit is passwords protected and only correct password enables the unit to be started up (default passwords: 101010).
Control Mode SettingOn the User Setting screen, touch the option Manual or Timing of the Control Mode to select the desired mode. Manual: The unit can be turned on or off manually and Timing doesn’t work. Timing: Timing works but the unit also can be turned on or off manually. Note: if Remote
33
Digital Multi VRF Technical Sales Guide
ON/OFF is set to “Allow”, the setting of “Control Mode” won’t work but with “Remote ON/OFF” displayed instead of “Manual” or “Timing”.Note: Only after the Control Mode is set to “Timing” as well as Timing is set and activated on the Timing Set Screen can Timing works.
Leaving Chilled Water SettingOn the User Setting screen it is allowed to set the leaving chilled water temperature, which can be increased or decreased by 0.1℃ through each touch on “INC”/ “DEC”.
Temperature RangeNormal-Temperature Centrifugal Chiller : 3℃~ 30℃ ; Default: 7℃ ; Hi-Temperature Centrifugal Chiller :12℃~20℃ ; Default: 16℃ System Temperature View There are leaving chilled water temperatures, entering/leaving cooling water temperatures on the HOME screen. Also more details are available on the VIEW screen by touching VIEW.
Error ClearingOn the menu bar, touch EVENT to enter the EVENT screen and then touch CLEAR to clear the current error and take the error check again. Note: this function only enables the system to detect the error again after the error is manually cleared. However, the error has not been eliminated actually.
Curve ViewTouch CURVE on the menu bar to the CURVE screen, in which temperature, pressure, master motor amperage, and position of the prerotation vane curves can be viewed.
Event ViewTouch “EVENT” to enter the EVENT screen which contains latest errors of the unit and the status of compressor. An event record includes the occurrence time, recovery time and type of the error.
Remote SwitchOn the User Setting screen, touch Remote Switch and two options “Allow” and “Forbid” will be available to be selected alternately. When Remote ON/OFF is set to “Allow”, ON/OFF operation on the HOME screen and also Timing do not work.Note: this setting can be done only when the unit is turned off.
34
11BMS
BMS interface of Gree Central AC is only for Gree central AC devices. There is BMS interface or multifunctional gateway in the hardware and standard communication protocol and BMS software plug-in in the software. Gree central AC can be centrally monitored and managed through BMS interface together with other devices in the building.
Long-distance monitoring BMS interface kit is mainly composed of a communication module and a power adapter. They are sold together. Pictures of the power adaptor and communication module
11.1 Description to BMS
11.2 Picture of Fittings
35
Digital Multi VRF Technical Sales Guide
11.3.1Scope of Supply S=Standard parts; O= User Optional; P= User Provided Parts
Scope of Supply Type Selection Remarks
File of protocol SModbus protocol is used for user to integrate with BMS
system.
Communication module ME30-27/E(M)
SIncluding communication module ZJ9012, power
transformer and connecting wire
Long distance monitoring set FC30-23/A(M)
OIncluding CD and optoelectronic isolated converter
RS232- RS485
optoelectronic isolated converter RS232- RS485
OIt is needed when the interface protocol of BMS system
is RS232
Optoelectronic isolated repeater RS485
OOne every 800m of communication distance equipped with one and One every 30 communication modules
equipped with one.
4-core twisted pair wire P
3-way phone connector P
11.3.2 Confirmation of Quantity of Parts
Types Qty of Communication Modules Optoelectronic isolated
converterOptoelectronic Isolated Repeater
All typesOne unit equipped with a
communication module ZJ9012One if BMS COM is RS232
One every 800m of communication distance equipped with one.
One every 30 communication modules equipped with one
11.3.3 Selection ExampleBMS COM is RS232 ,one converter is needed.3 sets of units LSBLX2000-M, 3 communication modules are needed, the communication distance is above 800m and one repeater is necessary and the quantity of communication modules is below 30 repeater is unnecessary, as follow:
Project Requirements Quantity
Qty(set) 3(LSBLX2000-M)
Communication module 3(ZJ9012)
Repeater 1
Optoelectronic Isolated Converter 1
11.3 Installation and Selection of Water cooled centrifugal chiller
36
11.3.4 Wiring Diagram1) The connection way of the whole system
2) The connection way in the electrical cabinet
Description of above communication cables
Cable Description
D2 both crystal head
D3 crystal head and the other end connects of it connects with wiring terminal of converter.
H2 both 9-core head (Standard parts)
37
Digital Multi VRF Technical Sales Guide
12 LONG-DISTANCE MONITORING SYSTEM
As the development and improvement of manufacturing technology and in order to solve the problems of complex distribution of the central AC in the buildings and difficult control and maintenance of them, an platform easy and reliable to operate must be provided to the users for daily management and maintenance. So this long-distance monitoring system combining electronic communication and computer technologies is developed to collect the running state of the units and to monitor and control the units from a long distance. Its structure is as follow:
12.2.1Scope of Supply S=Standard parts; O= User Optional; P= User Provided Parts
Scope of Supply Type Selection Remarks
PC P
Communication module setME30-27/E(M)
SIncluding communication module ZJ9012, power
transformer and connecting wireWater cooled centrifugal chiller Long-distance
Monitoring System set FC30-23/A(M)S
Including CD and optoelectronic isolated converter RS232- RS485
Optoelectronic isolated repeater RS485
OOne every 800m of communication distance
equipped with one and One every 30 communi cation modules equipped with one.
4-core twisted pair wire P
3-way phone connector P
12.2.2 Scope of Supply
Types Qty of Communication Modules Long-distance Monitoring
System Optoelectronic Isolated Repeater
All typesOne unit equippedwith a communica
tion module ZJ9012
Water cooled centrifugal chiller Long-distanceMonitoring System set
FC30-23/A(M)
One every 800m of communication distance
equipped with one.One every 30 communication modules equipped with one
12.2.3 Selection Example3 sets of units LSBLX2000-M, 3 communication modules are needed, the communication distance is above 800m and one repeater is necessary and the quantity of communication modules is below 30 repeater is unnecessary, as follow:
Project Requirements Quantity
Qty(set) 3(LSBLX2000-M)
Water cooled centrifugal chiller Long-distance Monitoring System FC30-23/A(M)
1
Communication module 3(ZJ9012)
Repeater 1
Optoelectronic Isolated Converter 1
12.1 Introduction to Long-distance Monitoring System
12.2 nstallation and Selection of Water cooled centrifugal chiller
38
12.2.4 Wiring Diagram1) The connection way of the whole system
2) The connection way of the whole system
Description of above communication cables
Cable Description
D2 both crystal head
D3 crystal head and the other end connects of it connects with wiring terminal of converter.
H2 both 9-core head (Standard parts)
Add: West Jinji Rd,Qianshan Zhuhai,Guangdong,China519070Tel: (+86-756)8614883 Fax: (+86-756)8614998Http://www.gree.com Email: [email protected] continous improvement in the products, Gree reserves the right to modify the product specification and appearence in this manual withotu notice and without incurring and obligations.
GREE MAKING BETTER CONDITINERS GREE MAKING BETTER CONDITINERS GREE MAKING BETTER CONDITINERS GREE MAKING BE
SN00300032
Gree Electric Appliance, Inc. of Zhuhai, founded in 1991, is the world's largest air
conditioner enterprise integrating R&D, manufacturing, marketing and services.
Technology Innovation and quality are always our priority. With efforts of
thousands of Gree's engineers, we own more than 3500 patents for our products.
Nowadays, we have 7 production bases in Zhuhai, Chongqing, Hefei and
Zhengzhou(China), as well as Brazil, Pakistan and Vietnam, with annual
production capacity of 30 million sets of residential air conditioners and 4 million
sets of commercial air conditioners.
With the installation of Gree commercial air conditioners in important projects at
home and abroad like Media Village for 2008 Beijing Olympic Games, Stadiums
for 2010 World Cup in South Africa, as well as India Telecom base station, Gree
commercial air conditioners are ready to develop steadily to every corner in the
world, to present a more comfortable and harmonious working environment and
family atmosphere.