CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

37
CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations

Transcript of CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Page 1: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

CE 3372 Water Systems Design

EPA SWMM– Pumps and Lift Stations

Page 2: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Purposes

• To lift stormwater to higher elevation when discharge of local collection system lies below regional conveyance.

• To lift stormwater to higher elevation when terrain or man-made obstacles do not permit gravity flow to discharge point.

Page 3: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Pond and pump station

Page 4: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Types• Submersible

– Lower initial cost– Lower capacity– Smaller footprint

• Wet-well / dry-well – Higher initial cost– Easier inspection/

maintenance

Page 5: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Submersible lift station

Module 14

Page 6: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Wet-well / dry-well lift station

Page 7: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Design criteria

• Size the pumps and the wet-well (sump) storage capacity to accommodate inflow variability and detention time limits.

• Match the pumps to the flow and head requirements.

• Provide ‘near-absolute’ reliability– Automated controls – Redundant systems – Alarms– Regularly scheduled, preventive maintenance

• Assess and mitigate environmental factors– Flood risk, noise pollution, visibility

Page 8: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Site plan and facilities• Protected and

accessible during a major flood

• Redundant power supplies

• Intruder-resistant with controlled access

Page 9: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

• Height• Inflow pipe elevation• Ground elevation• Excavation costs

• Cross section• Constant• Variable

Wet-well (sump) dimension design

Module 14

Page 10: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Pump capacity

• Greater than average flow

• Less than the maximum flow

• Depends mainly upon– Inflow

variability– Marginal

costs of increasing sump volume

Page 11: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

FHWA-HDS-01-007

• Detailed “how-to”

• Reviews hydrology• Reviews hydraulics

Page 12: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Pump System Hydraulic Operation

1) Runoff enters the collection system and is conveyed to the storage unit and wet well of the pump station. For a period of time there is no outflow as the runoff is stored within the storage unit and wet well.

2) The water level in the wet well rises and a hydraulic gradient develops based on the rate of inflow, the water level in the wet well, and the conveyance capacity of the storage unit and collection system.

3) The first pump starts when the water level in the wet well reaches a specific elevation. The pump evacuates the flow at a rate that varies with the pump characteristics and total dynamic head.

Page 13: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Pump System Hydraulic Operation

4) The inflow rate will vary as defined by the inflow hydrograph. If the pumping rate is lower than the inflow rate, the water level in the storage unit and wet well continues to rise and the volume stored in the system increases.

5) Additional pumps start at predetermined elevations as the water level rises.

6) At some point, the inflow rate will be lower than the total pumping rate. The water level in the wet well drops as water is evacuated from storage.

Page 14: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Pump System Hydraulic Operation

7) At preset elevations, as the water level drops, individual pumps are stopped and the discharge rate drops accordingly.

8) When the water level drops to the minimum level required for submergence, the last pump is stopped. The last pump off is usually the first to have been switched on, although different switching schemes are feasible.

Page 15: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Station Design Process

• Design criteria include:– Design frequency– Peak outflow– Station type– Design philosophy– Minimum storage volume– Maximum allowable highwater– Discharge velocity

• Criteria must be established before design of storage and pump system (FHWA-HDS-01-007 pg 4-9)

Page 16: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Station Design Process• Hydrologic Analysis:

– Drainage boundary and area– Runoff characteristics– Design runoff hydrographs– Cumulative inflow

Page 17: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Station Design Process• Trial Pumping Configuration:

– The design is typically iterative– Minimum of two pumps recommended

Page 18: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Station Design Process

• Hydrologic/Hydraulic Analysis/Estimates– Inflow hydrograph– Inflow mass curve– Stage-storage relationship– Trial pump/switching scheme– Mass curve routing– System head curves

• Pump selection/operation

Page 19: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Hydrographs – review

• A hydrograph is a graphical representation of discharge (volume/time) with time

• The area under the hydrograph curve represents the total volume of runoff during the time represented

• The highest point on the graph is the peak discharge

Page 20: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Hydrographs – review

Page 21: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Storage• Storage is collection system, plus any sump

(wet well) on suction side of lift station.

Page 22: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Time distributed discharge• Route inflow hydrograph through lift station

(and collection system) to generate the time distributed discharge.

Page 23: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Basic assumptions • Pump station hydrologic design is conceptually

identical to reservoir routing design Inflow-outflow=change in storage

• Inflow is the hydrograph produced by the storm sewer system

• Outflow is derived from the sump geometry (stage/storage) and Pump Performance Curves for the pump or pumps in the station

Module 14

Page 24: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Stations in SWMM

• Used to “lift” water from a low elevation to a higher elevation.

• Lift provided by pumps, usually centrifugal.

• Pumps modeled similar to EPA-NET

Page 25: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Stations in SWMM

Page 26: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Stations in SWMM

• Lift stations are modeled as special links (like in EPA NET).

• Page 40 of the SWMM manual described the conceptual model used – there are 4 “kinds” of pumps in SWMM

Page 27: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Stations in SWMM

• Type 1 Pump Rule

• Semi-realistic (see next slide); actual operation would likely be by stage (depth)

Page 28: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Stations in SWMM

• Type 2 Pump Rule

Realistic rule: can use a PLC and transducer to control the pump; assumes discharge into free (open) pipe

Page 29: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Stations in SWMM

• Type 3 Pump Rule

Realistic rule: Like in EPA-NET. Assumes suction and discharge submerged – discharging into a force-main. This is the “kind” of pump you had in fluids and earlier in this course.

Page 30: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Stations in SWMM

• Type 4 Pump Rule

Realistic rule: Archimedes (screw) pumps work exactly like this rule. Reasonably common in wastewater treatment plants for initial lift into the reactors (then gravity flow rest of plant).

Page 31: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

• Woodlands Ditch C Subdivision.– As-is drainage

model, using 2-yr design storm.

– Suppose the goal is to keep ponding less than 2 feet.

Lift Stations in SWMM

Page 32: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Lift Stations in SWMM3:15 into the storm

Greater than 2 feet deep

Ok to be deep in the ditch

Page 33: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Add relief sewers3:15 into the storm

Ok to be deep in the ditch

Used a 8X16 box culvertTo “store” water in the sewer

Lift station hereFor the example

Page 34: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Run once to find lift station need3:15 into the storm

Probably need 100 cfs(5 low-head pumps)

Lift station hereFor the example

Page 35: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Run again with the lift station3:15 into the storm

Probably need 100 cfs(4 low-head pumps)

Lift station hereFor the example

Page 36: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Then Check

• Is such a lift station feasible?– How many pumps?– Force main diameter (4-foot this simulation), kind

of big– How much power?– Other alternatives (in this case a gravity relief

sewer probably makes more sense)

Page 37: CE 3372 Water Systems Design EPA SWMM– Pumps and Lift Stations.

Exercise

• Download the No-Relief-Sewer file and run the program.

• Then design a relief sewer(s) to keep all the storage nodes at 2 foot ponding depth or less.

• Require at least 5-foot cover (storage nodes are at grade, other nodes below grade).