Surge protective devices UL range OVR NE12 and OVR T2 Catalogue

Transcript of Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places...

Page 1: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

Surge protective devices UL rangeOVR NE12 and OVR T2

Catalogue

Page 2: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an
Page 3: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 1

Surge protective devices UL rangeOVR NE12 and OVR T2

Introduction 2

General points on lightning and its risks 3

UL 1449 update to 3rd edition 4-5

Terminology of SPD electrical characteristics 6

General wiring diagrams 7

OVR NE12 surge protective devices UL range

Product introduction 8

Product selection

Choosing the correct model 9

Part number diagram 9

Product selection tables 10

Technical data 11

Approximate dimensions 12

OVR T2 surge protective devices UL range

Product introduction 14

Product selection

Choosing the correct model 15

Part number diagram 15

Service voltage and location 16

Wiring diagrams 16

Product selection tables 17-20

Technical data 21

Approximate dimensions 22-24

2nd to 3rd edition cross reference 25

OVR PV surge protective devices 26

OVR TC surge protective devices UL range 27

Other documentation 28

Index 29

Page 4: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

2 | ABB Surge protective devices UL range

Introduction

What is a transient surge ?A transient surge is a sudden (shorter than a millisecond) rise in the flow of power. Voltage can peak at 12x the nomi-nal system voltage. Transient surges result from a number of sources, the most common of which are internal, such as load switching and even normal equipment operations. In fact, approximately 80 % of transients are generated internally. Ex-ternal transients are the result of lightning and load switching by utilities and upstream facilities.

Internal load switchingSwitching on/off any elements that create a sudden variation of load will also cause a sudden change in current flow and generate transient surges.

Lightning strikesA lightning strike (direct or indirect) can have a destructive or disturbing effect on installations located up to several miles from the actual point of the strike. During a storm, under-ground cables can transmit energy from a lightning strike to equipment installed inside buildings. A lightning protection device (such as a lightning rod or Fara-day cage) installed on a building to protect against the risk of a direct strike can increase the risk of damage to electrical equipment connected to the main power supply near or inside the building. The lightning protection device diverts the high strike current to ground, considerably raising the potential of the ground close to the building on which it is installed. This causes over-voltages on the electrical equipment directly via the ground terminals and induced via the underground supply cables.

Switching effects on power distributionThe switching of transformers, motors or inductances in gen-eral, variation of load, disconnection of circuit breakers or cut outs lead to overvoltages that penetrate a building. The closer the building is to a generating station, substation or upstream switching point, the higher the overvoltages may be.

Facilities and operations left unprotected are highly susceptible to the damaging effects of transients. such as: – Catastrophic equipment failure – Immediate operation shutdown – Long term disruption of business – Expensive equipment repair and replacement – Data losses, system resets and network down time

In order to ensure protection from transient surges, installa-tion of surge protective devices (SPD) is a must. ABB has a long history of engineering and manufacturing quality surge protective devices. This brochure will provide all the informa-tion needed to select the proper products to begin protecting any facility or operation. ABB’s family of surge protective devices include the following: – OVR NE12 enclosed SPD for service entrance locations – OVR DIN rail AC SPD for equipment protection – OVR PV DIN rail DC SPD for photovoltaic installations – OVR DIN rail data line SPD for sensitive communications

networks

Page 5: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 3

General points on lightning and its risks

Overvoltages due to direct lightning strikesThese can take two forms: – When lightning strikes a lightning conductor or the roof

of a building which is grounded, the lightning current is dissipated into the ground. The impedance of the ground and the current flowing through it create large difference of potential: this is the overvoltage. This overvoltage then propagates throughout the building via the cables, damag-ing equipment along the way.

– When lightning strikes an overhead low voltage line, the strike produces high currents which penetrate into the building creating large overvoltages. The damage caused by this type of overvoltage is usually catastrophic (e.g. fire in the electrical switchboard causing the destruction of buildings and industrial equipment) and results in explo-sions.

Direct lightning strike on an overhead lineDirect lightning strike on a lightning conductor or the roof of a building

Magnetic fieldIncrease in ground potential Electrostatic field

Overvoltages due to the indirect effects of lightning strikesOvervoltages are also produced when lightning strikes in the vicinity of a building, due to the increase in potential of the ground at the point of impact. The electromagnetic fields cre-ated by the lightning current generate inductive and capacitive coupling, leading to other overvoltages. Within a radius up to several kilometers, the electromagnetic field caused by light-ning in clouds can also create sudden increases in voltage.Although less spectacular than in the previous case, irrepara-ble damage is also caused to sensitive equipment such as fax machines, computer power supplies and safety and commu-nication systems.

Page 6: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

4 | ABB Surge protective devices UL range

UL 1449 update to 3rd edition

The underwriters laboratories (UL) standard for surge protective devices (SPDs) has been the primary safety standard for surge protection since the first edition was published in 1985, and updated to the second edition in 1996.

The objective of UL 1449 has always been to increase safety in terms of surge protection. Thus, major changes have re-cently been made to the surge protection standard.The latest edition, known as UL 1449 3rd edition, was pub-lished on September 29, 2006 and took effect September 2009, and is now also an ANSI standard. A revision was made on February 8, 2011.To avoid confusion, the objective of this paper is to explain and summarize the major changes made to the standard.The key updates are: – Change in the standard’s name – The different type designations of surge protective devices – The measured voltage protection level – The Nominal discharge current

Change in the standard’s name: from TVSS to SPDsPrior to UL 1449 3rd edition taking effect, the devices this standard covers were known as transient voltage surge sup-pressors (TVSS), operating on power circuits not exceeding 600 V. With the inception of the 3rd edition, these devices are now known as surge protective devices (SPDs), and may operate on power circuits not exceeding 1000 V.This new designation moves the UL standard closer to the In-ternational designation and to IEC standards. The new edition is now renamed UL standard for safety for surge protective devices, UL 1449.

The different type designations of surge protective devicesThe new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an electri-cal system. While type 1, type 2 and type 3 categories refer to different types of SPDs that can be installed at specific loca-tions, type 4 and type 5 categories refer to components used in an SPDs configuration.Type 1 – “Permanently connected SPDs intended for installa-tion between the secondary of the service transformer and the line side of the service equipment overcurrent device.”

Type 2 – “Permanently connected SPDs intended for instal-lation on the load side of the service equipment overcurrent device.”

Type 3 – “Point of utilization SPDs, installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel.”

Type 4 – Component assemblies – “Component assembly consisting of one or more Type 5 components together with a disconnect (integral or external) or a means of complying with the limited current tests.”

Type 1, 2, 3 – Component assemblies – “Consists of a type 4 component assembly with internal or external short circuit protection.”

Type 5 – “Discrete component surge suppressors, such is in-stalled to the equipment, the better the protection is. This is a push in the direction of providing stepped protection including external and internal surge protection.

Page 7: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 5

The measured voltage protection levelOne of the last changes found in the new UL 1449 3rd edi-tion, is the modification in the measured voltage protection level. The measured limiting voltage (MLV) is the maximum magnitude of voltage measured at the application of a specific impulse wave shape. When applying a certain surge current on the SPD the measured voltage at the device terminals is the so called “let-through voltage.” In UL 1449 2nd edition, the let-through voltage was referred to as suppressed voltage rating (SVR) and was calculated with a 0.5 kA surge wave form at 6 kV. The new designation is voltage protection rating (VPR) and is calculated with a 3 kA surge wave form at 6 kV.The MLV will allow comparison of different types of SPDs with regards to the let-through voltage. However, it is important to note that the surge current used to measure the let-through voltage is six times higher in the 3rd edition than in the 2nd edition. This means that, comparing the obsolete SVR des-ignation with the new VPR ratings will not be valid, as VPR ratings will of course be higher than SVR ratings.The nominal discharge current: InThe nominal discharge current, known as In test, is new to UL 1449, coming from the IEC standard.During the test, the SPD is subjected to 15 impulses at the selected nominal discharge current. In order to pass, the SPD cannot create a shock or fire hazard during the test, and nothing in the surge path can open during or after the test. The nominal discharge current values, with a 8/20 µs wave shape, are selected by the manufacturer as follows:Type 1: 10 or 20 kAType 2: 3, 5, 10 or 20 kAType 1, Type 2 and Type 4 SPDs (intended for type 1 or Type 2 applications) are subjected to this test.Sources: Underwriters laboratories Inc., standard for safety, surge protective devices (UL 1449 Third Edition, 2011)

UL 1449 update to 3rd edition

Page 8: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

6 | ABB Surge protective devices UL range

Terminology of SPD electrical characteristics

Imc

Note:Common mode overvoltages affect all grounding systems.

SPD terminology 8/20 wave:Current waveform which passes through equipment when subjected to an overvoltage (low energy).

Type 2 surge protective device (SPD)Permanently connected SPDs intended for installation on the load side of the service equipment overcurrent device, including SPDs located at a branch panel. It has successfully passed testing to the standard with the 8/20 wave (class II test).

Metal oxide varistor (MOV) A varistor is an electronic component with a “diode like” non-linear current-voltage characteristic, used to protect circuits against excessive transient voltages. Most commonly com-posed of metal oxides.

Maximum continuous operating voltage (MCOV, Uc)The maximum designated root mean square (rms) value of power frequency voltage that may be applied continuously between the terminals of the SPD.

Nominal discharge current (In)Peak current value of an 8/20 waveform which the SPD is rated for based on the test program.

Maximum discharge current (Imax)Peak current value of an 8/20 waveform which can be safely discharged by the SPD, with an amplitude complying with the class II operating test sequence. Imax > In

Short circuit current rating (SCCR)Maximum symmetrical fault current, at rated voltage, that the SPD can withstand without sustaining damage that exceeds acceptable criteria or creates a hazardous operating condition.

Voltage protection rating (VPR)The value of the VPR is determined as the nearest highest value, taken from table 63.1 of ANSI/UL 1449 3rd edition, to the measured limiting voltage determined during the transient voltage surge suppression test using the combination wave generator at a setting of 6 kV, 3 kA.

Voltage protection level (Up or Ures)The voltage let through by the SPD while diverting surge cur-rent to ground must not exceed the voltage withstand value of the equipment connected downstream.

Imd

Ph

N

V

A

Time (µs)

Time (µs)

Residual Voltage

Shaved Peak

* Graph depicts an 8/20 µs wave

Notes:Test wave 8/20 µs according to IEEE # C62.62-200/UL 1449The first number corresponds to the time from 10 % to 90 % of its peak value (8 µs).The second number corresponds to the time taken for the wave to descend to 50 % of its peak value (20 µs).

Common mode and / or differential mode protectionCommon modeCommon mode overvoltages appear between the live con-ductors and ground, e.g. phase/ground or neutral/ground. A live conductor not only refers to the phase conductors but also to the neutral conductor.This overvoltage mode destroys equipment connected to ground (class I equipment) and also equipment not connected to ground (class II equipment) which is located near a ground-ed mass and which does not have sufficient electrical isolation (a few kilovolts).Class II equipment not located near a grounded mass is theo-retically protected from this type of attack.

Differential modeDifferential mode overvoltages circulate between live conduc-tors: phase/phase or phase/neutral.These overvoltages have a potentially high damaging effect for all equipment connected to the electrical network, especially ‘sensitive’ equipment.

Page 9: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 7

General wiring diagrams

Wiring diagrams according to IEC 60364-1

Other wiring diagrams

L1L2L3PEN

TNC system230/400 V

Single phase120/240/277 V

TNS system230/400 V

Delta240/480/600 V

High-Leg Delta240/1200 V HLD

TNC-S system230/400 V

Split phase240/120 V, 480/240 V

TT system230/400 V

Grounded Wye208 Y/120 V, 480 Y/277 V, 600 Y/347 V

IT system230/400/600 V

Equipment

L1L2L3NPE

Equipment

L1L2L3NPE

Equipment

L1L2L3N

L1

N

L2G

L1

NG

L1

L2

L3

G

L1L2

N

L3

G

Equipment

L1L2L3

Equipment

L1L2

N

L3

G

Page 10: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

8 | ABB Surge protective devices UL range

OVR NE12 surge protective devices UL rangeProduct introduction

IntroductionThe OVR NE12 enclosed surge protective device (SPD) is the latest addition to ABB’s extensive range of surge protection products. It is designed to be installed at the service en-trance, thereby protecting the entire facility from the harmful effects of transient surges. These surges are the result of: – Direct and indirect lightning strikes – Power company load switching – Upstream load switching at other facilities

Extensive damage and expensive repairs can result from these types of disturbances if surge protection is not present.

Features & benefitsThe OVR NE12 is a multistage protector with fast acting varistor (MOV) and EMI/RFI noise attenuation filter to limit overvoltage to values compatible with the sensitive equipment connected to the network. In addition to the OVR NE12, ABB recommends adding OVR DIN rail SPDs at branch panels and equipment, creating a multi-level approach to protection.

General – NEMA 12 enclosure – All mode protection (L-L/L-N/L-G/N-G) – Auxiliary contacts for remote monitoring – Safety disconnect, fused – LED power on/fault indicator – Audible alarm.

MOV technology – 160 kA or 320 kA per phase – Replaceable MOV blocks – Visual and audible MOV replacement indication.

Surge counter/diagnostic LCD display (optional) – Count of surges 2 kA and higher with time and date – Visual diagnostic information.

ApplicationsThe OVR NE12 is suitable for protection for all manner of facilities and operations. It is designed with a NEMA type 12 enclosure, and rated as a type 2 SPD, requiring indoor instal-lation on the load side of the main breaker or fuse. Here are some examples of operations that would benefit from an OVR NE12 enclosed SPD: – Critical power (hospitals, data centers, etc.) – Communications – Renewable energy – Manufacturing – Water/wastewater – Commercial.

Specifications – Type 2 surge protective device – UL 1449, 3rd edition listed – NEMA 12 enclosure – Three service voltages (AC): 240/120V split phase, 480 V

delta and 480/277 V wye – 160 kA or 320 kA per phase protection – Short circuit current rating (SCCR): 200 kA.

ABB recommends the installation of the OVR NE12 enclosed SPD wherever uptime is a critical element of a facility or operation.

Page 11: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 9

OVR NE12 surge protective devices UL rangeProduct selection

Type Service voltage FeaturesDefault visualization Green/Red LED

Audible alarm Surge counter

OVR NE12 320 480DX 480V delta Yes Yes YesOVR NE12 160 480DX 480V delta Yes Yes YesOVR NE12 320 277YX 480Y/277V Yes Yes YesOVR NE12 160 277YX 480Y/277V Yes Yes YesOVR NE12 320 120SPX 240/120V split phase Yes Yes YesOVR NE12 160 120SPX 240/120V split phase Yes Yes YesOVR NE12 320 480D 480V delta Yes Yes NoOVR NE12 160 480D 480V delta Yes Yes NoOVR NE12 320 277Y 480Y/277V Yes Yes NoOVR NE12 160 277Y 480Y/277V Yes Yes NoOVR NE12 320 120SP 240/120V split phase Yes Yes NoOVR NE12 160 120SP 240/120V split phase Yes Yes No

Choosing the correct modelThere are three steps to choosing the correct OVR NE12 model:

1) Select service voltageConsult qualified personnel if the facility or operation service voltage is unknown. The OVR NE12 is available in three service voltages: – 480 V delta – 480 Y/277 V – 240/120 V Split Phase

2) Select the surge capacity (Imax)The surge capacity is the maximum discharge current (Imax) per phase. Each MOV is capable of withstanding multiple surges below the maximum surge level. Two protection levels are available: – 160 kA per phase – 320 kA per phase

3) Choose a basic display or the surge counter/diagnostic LCD display – Basic display: LED lights and alarm – Surge counter/diagnostic LCD display: LED lights, alarm

and LCD screen displaying percentage protection level, surge count and last surge date

Once these three steps are complete, consult the tables be-low and on Page 10 to select the unit. If technical assistance is required, please call ABB technical support at (888) 385-1221 option #4.

OVR NE12 enclosed SPD part number diagram

OVR NE12 320 480 D X

Surge capacity320 kA/phaseor 160 kA/phase

ServiceD=DeltaY=WyeSP=Split phase

OptionX = Surge counter/Diagnostic LCD displayBlank = Basic display

Service voltage480 V277 V120 V

Enclosure ratingNEMA 12

ABB SPD

Page 12: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

10 | ABB Surge protective devices UL range

OVR NE12 surge protective devices UL rangeProduct selection

OVR NE12 enclosed SPDSurge Service voltage Description Type Order code EAN codecapacity perphasekA320 480 V delta OVR NE12 enclosed SPD, 480 V delta, 320 kA, w/ surge counter OVR NE12 320 480DX 2CTB812001R1600 3660308516725

OVR NE12 enclosed SPD, 480 V delta, 320 kA OVR NE12 320 480D 2CTB812001R1000 3660308516718480 Y/277 V OVR NE12 enclosed SPD, 480 Y/277 V, 320 kA, w/ surge counter OVR NE12 320 277YX 2CTB812001R1200 3660308516640

OVR NE12 enclosed SPD, 480 Y/277 V, 320 kA OVR NE12 320 277Y 2CTB812001R0300 3660308516633240/120 V SP OVR NE12 enclosed SPD, 240/120 V split phase, 320 kA, w/ surge counter OVR NE12 320 120SPX 2CTB812001R1400 3660308516688

OVR NE12 enclosed SPD, 240/120 V split phase, 320 kA OVR NE12 320 120SP 2CTB812001R0400 3660308516671160 480 V delta OVR NE12 enclosed SPD, 480 V delta, 160 kA, w/ surge counter OVR NE12 160 480DX 2CTB812001R1500 3660308516701

OVR NE12 enclosed SPD, 480 V delta, 160 kA OVR NE12 160 480D 2CTB812001R0600 3660308516695480 Y/277 V OVR NE12 enclosed SPD, 480 Y/277 V, 160 kA, w/ surge counter OVR NE12 160 277YX 2CTB812001R1100 3660308516626

OVR NE12 enclosed SPD, 480 Y/277 V, 160 kA OVR NE12 160 277Y 2CTB812001R0500 3660308516619240/120 V SP OVR NE12 enclosed SPD, 240/120 V split phase, 160 kA, w/ surge counter OVR NE12 160 120SPX 2CTB812001R1300 3660308516664

OVR NE12 enclosed SPD, 240/120 V split phase, 160 kA OVR NE12 160 120SP 2CTB812001R0800 3660308516657

Replacement power supply and MOV block (1)Surge Service voltage Description Type Order code EAN codecapacity perphasekA160 480 V delta OVR NE12 power supply, 480 V delta, 160 kA OVR 1N 160 480PS 2CTB812001R2700 3660308516985

OVR NE12 MOV, 480 V delta, 160 kA OVR 1N 160 480 2CTB812001R1700 3660308516596480 Y/277 V OVR NE12 power supply, 480 Y/277 V, 160 kA OVR 1N 160 277PS 2CTB812001R2100 3660308516978

OVR NE12 MOV, 480 Y/277 V, 160 kA OVR 1N 160 277 2CTB812001R0100 3660308516572240/120 V SP OVR NE12 power supply, 240/120 V split phase, 160 kA OVR 1N 160 120PS 2CTB812001R2800 3660308516992

OVR NE12 MOV, 240/120 V split phase, 160 kA OVR 1N 160 120 2CTB812001R1800 3660308516602(1) Consult the OVR NE12 installation and operation manual (document number 1SXU430222M0201) for power supply and MOV block replacement instructions.

Page 13: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 11

OVR NE12 surge protective devices UL rangeTechnical data

OVR NE12 320 480DX OVR NE12 320 277YX OVR NE12 320 120SPXOVR NE12 320 480D OVR NE12 320 277Y OVR NE12 320 120SPOVR NE12 160 480DX OVR NE12 160 277YX OVR NE12 160 120SPXOVR NE12 160 480D OVR NE12 160 277Y OVR NE12 160 120SP

Technical characteristicsService voltage 480V delta 480/277V wye 240/120V split phaseApplication Service entrance Service entrance Service entrancePhases 3 3 2Mode of protection L-L / L-N / L-G / N-G L-L / L-N / L-G / N-G L-L / L-N / L-G / N-GSurge capacity/phase (Imax) 160 kA or 320 kA 160 kA or 320 kA 160 kA or 320 kAMaximum Continuous Operating Voltage (MCOV) 550 V 320 V 150 VVoltage Protection Rating (VPR - UL 3rd Ed.)

L-N – 1200 V 900 VL-L 1800 V 2000 V 1200 VL-G 1800 V 1200 V 800 VN-G – 1200 V 800 V

Nominal discharge current (In) 10 kA 10 kA 10 kAShort circuit current rating (SCCR) 200 kA 200 kA 200 kAAC power frequency 50 Hz-60 Hz 50 Hz-60 Hz 50 Hz-60 HzThermal fuse Type J 100A Type J 100A Type J 100AEMI/RFI filtering -30 dB -30 dB -30 dB

Mechanical characteristicsConnection terminals 1/4 - 5/16 - 3/8 - 1/2 inches 1/4 - 5/16 - 3/8 - 1/2 inches 1/4 - 5/16 - 3/8 - 1/2 inchesTerminal torque 6 Nm-75 Nm 6 Nm-75 Nm 6 Nm-75 NmAuxiliary contact connection terminals AWG 22-AWG 12 AWG 22-AWG 12 AWG 22-AWG 12Auxiliary contact terminal torque 1 Nm 1 Nm 1 NmFront display Yes Yes YesLED indicators Yes Yes YesAudible alarm Yes Yes YesAuxiliary contact Yes Yes YesSurge counter Yes - Option “X” Yes - Option “X” Yes - Option “X”Enclosure material Painted steel Painted steel Painted steelEnclosure rating NEMA 12 NEMA 12 NEMA 12Dimensions H x W x D (approx.) 24'' x 16'' x 8'' inches 24'' x 16'' x 8'' inches 24'' x 16'' x 8'' inchesWeight (approx.) 40 lbs 40 lbs 40 lbs

Miscellaneous characteristicsStocking temperature 32 °F (0 °C) to 104 °F (40 °C) 32 °F (0 °C) to 104 °F (40 °C) 32 °F (0 °C) to 104 °F (40 °C)Operating temperature 32 °F (0 °C) to 104 °F (40 °C) 32 °F (0 °C) to 104 °F (40 °C) 32 °F (0 °C) to 104 °F (40 °C)Maximum altitude 6600 feet (2000 m) 6600 feet (2000 m) 6600 feet (2000 m)Fire resistance according to UL 94 V0 V0 V0Approvals ANSI/UL 1449 3rd ed. ANSI/UL 1449 3rd ed. ANSI/UL 1449 3rd ed.

Meets IEEE requirements Meets IEEE requirements Meets IEEE requirements

Replacement MOV blockOVR 1N 160 480PS (power supply)OVR 1N 160 480

OVR 1N 160 277PS (power supply)OVR 1N 160 277

OVR 1N 160 120PS (power supply)OVR 1N 160 120

Page 14: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

12 | ABB Surge protective devices UL range

OVR NE12 surge protective devices UL range

Dimensions mm, inches

Front view, door removed Front view, of doorSection "A-A"

400 15.75"

A

A400 15.75"190 7.48"

600

23.

62"

600

23.

62"

201 7.91"

Page 15: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 13

Page 16: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

14 | ABB Surge protective devices UL range

OVR T2 surge protective devices UL rangeProduct introduction

IntroductionOver 80 % of transient surges are caused by internal sources such as load switching and normal equipment operations. The installation of ABB OVR UL 1449 3rd edition plugga-ble AC DIN rail SPDs will combat these surges and provide protection to valuable equipment and help keep an operation up and running. This new product range is approved as Type 4 recognized components and is usable in Type 2 applica-tions. These products are of the same high quality as ABB UL 1449 2nd edition devices, with improved safety as a result of additional testing required by the UL 1449 3rd edition stand-ard. Installation at branch panels, control panels and terminal equipment is recommended to provide the most complete protection.

Features & benefitsThe OVR DIN rail SPDs utilize fast acting metal oxide varistor (MOV) technology to limit overvoltage to values compatible with the sensitive equipment connected to the network.

End of life indicatorThis feature is standard on all ABB pluggable OVR DIN rail surge protectors. Each cartridge is equipped with a mechanical indicator which is green when the SPD is operational and protecting the sys-tem, and turns red when it has reached end of life. When this occurs, the cartridge must be replaced to guarantee protection.

PluggableThe ability to efficiently maintain equipment is a key focus topic for industrial facilities. For this reason, ABB OVR DIN rail SPDs (excluding data line products) now utilize pluggable cartridges. Should one or more cartridges reach end of life, the electrical circuit does not have to be isolated, nor does the whole device have to be removed.

Simply pull the dead cartridge from its housing and plug in a new one.

Remote indication (optional - “TS” designation)This function, achieved by wiring an integrated 3-point 1 A volt-free contact, enables the operational state of the SPD to be monitored remotely.

Technical features of the remote indicator – 1 NO (normally open) contact and 1 NC (normally closed)

contact – Min. load: 12 V DC - 10 mA – Max. load: 250 V AC - 1 A – Connection cross section: 1.5 mm² (16 AWG)

Specifications – UL 1449 3rd edition - Type 4 recognized component – Imax - 15 kA and 40 kA – Maximum Continuous Operating Voltage (Uc) - 175, 320, 440,

550 and 660 V AC – Configuration - 1L, 2L, 3L, N, 1N, 2N, 3N

ABB recommends a multi-level approach to surge protection. Combining OVR DIN rail SPDs with the OVR NE12 enclosed SPD will ensure the facility or operation is fully protected.

NOTE: A surge protector that has reached end of life does not interrupt service, it simply disconnects itself, and the system is no longer protected.

NOTE: Pluggable surge protector cartridges are equipped with a “key” matched to each part number base, preventing incorrect replacements.

Page 17: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 15

OVR T2 surge protective devices UL rangeProduct selection

Choosing the correct model1) Determine the service voltageConsult qualified personnel if the facility or operation service voltage is unknown.2) Select the SPD maximum continuous operating voltage (MCOV, Uc)The MCOV should correspond to the service voltage.Example: If the service voltage is 480 V delta, an SPD with 550 V or 660 V MCOV will be required.Surge protection devices must also provide a level of protection compatible with the withstand voltage of the equipment. This withstand voltage depends on the type of equipment and its sensitivity. The incoming surge protector may not provide adequate protection by itself, as certain electrical phenomena may greatly increase its residual voltage if cable lengths exceed 10 m. A sec-ond SPD may be necessary. See coordination below.3) Select the SPD surge capacity (Imax)Surge capacity is the amount of energy the SPD can withstand from a single surge event. The higher the surge capacity, the longer the device will protect the system. A second surge protector may be required if the surge capacity of the first is not capable of diverting all surge current to ground. See coordination below.4) Remote monitoring (optional)Integrated auxiliary contact for remote monitoring available on models with “TS” designation.Consult the service voltage and location table on page 16 for help in the selection of SPDs.

Complete facility protectionInstalling surge protection at the main distribution panel is only the beginning of protecting the entire operation. As most transient surges are created internally, it is necessary to install surge protection at sub-distribution panels (equipment protection) to be fully protected. Stepping down the Imax level from the service entrance panel toward equipment to be protected is recommended.For example, if a 40 kA Imax SPD is installed in the main distribution panel, then 15 kA Imax SPDs should be installed in sub-distri-bution panels for equipment protection.

CoordinationIt may be necessary to add a second surge protector, wired to the incoming unit, to achieve the required voltage protection and/or surge capacity. For Type 2 or 4 SPDs, installing this second unit a minimum of 1 m from the first unit will allow the two to work together, achieving the required protection.

Wiring rulesThe impedance of the cables increases the voltage across the connected equipment. Therefore, the length of the cable between the surge protector and the equipment should be minimized. The surge protective device should be installed as close to the equipment to be protected as possible. If this is not possible (the equipment is over 30 m from the panel), then a second surge protector must be installed.

OVR DIN rail SPD - Part number diagram

OVR T2 3N 40 320 P TS U

Surge capacity (Imax)15 kA 40 kA

ABB SPD

PluggableAuxiliary contact(Optional)

UL 14493rd edition

Max voltage (Uc) 150 V (175 V)320 V 440 V 550 V 660 V

Phases1P = No notation2P = 2L3P = 3L1P+N = 1N2P+N = 2N3P+N = 3N

DesignationT2 : Type 2 AppsPV : PhotovoltaicTC : Data line

Page 18: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

16 | ABB Surge protective devices UL range

OVR T2 surge protective devices UL rangeProduct selection

Service voltage and locationService entrance Main distribution panel Sub-distribution panel

Network Service voltage Number of wires OVR NE12 enclosed SPD OVR DIN rail SPD OVR DIN rail SPDDelta 240/120 V HLD 4W+G – OVR T2 3N 40 320PTSU OVR T2 3N 15 320PU

240 V 3W+G – OVR T2 3L 40 320PTSU OVR T2 3L 15 320PU480 V 3W+G OVR NE12 320 480D(X)

OVR NE12 160 480D(X)OVR T2 3L 40 550PTSU OVR T2 3L 40 550PTSU

600 V 3W+G – OVR T2 3L 40 660PTSU OVR T2 3L 40 660PTSUSingle phase 120 V 2W+G – OVR T2 1N 40 150PTSU OVR T2 1N 15 150PU

240 V 2W+G – OVR T2 1N 40 320PTSU OVR T2 1N 15 320PU277 V 2W+G – OVR T2 1N 40 320PTSU OVR T2 1N 15 320PU

Split phase 240/120 V 3W+G OVR NE12 320 120SP(X) OVR NE12 160 120SP(X)

OVR T2 2N 40 150PTSU OVR T2 2N 15 150PU

480/240 V 3W+G – OVR T2 2N 40 320PTSU OVR T2 2N 15 320PUWye 208/120 V 4W+G – OVR T2 3N 40 150PTSU OVR T2 3N 15 150PU

480/277 V 4W+G OVR NE12 320 277Y(X) OVR NE12 160 277Y(X)

OVR T2 3N 40 320PTSU OVR T2 3N 15 320PU

600/347 V 4W+G – OVR T2 3N 40 440PTSU OVR T2 3N 40 440PTSU

Page 19: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 17

OVR T2 surge protective devices UL rangeProduct selection

One poleService voltage (1) Max. discharge Aux. contact - Type Order code EAN code Replacement

current remote monitoring cartridgeImax, 8/20 µs, kA

120 V single phase, 240/120 V split phase, 208/120 V wye 15 No OVR T2 15 150PU 2CTB802341R0000 3660308518514 OVR T2 15 150CU240/120 V HLD, 240 V delta, 240 V single phase, 277 V single phase, 480/240 V split phase, 480/277 V wye

15 No OVR T2 15 320PU 2CTB802341R0400 3660308518521 OVR T2 15 320CU

120 V single phase, 240/120 V split phase, 208/120 V wye 40 No OVR T2 40 150PU 2CTB802341R2000 3660308518958 OVR T2 40 150CU120 V single phase, 240/120 V split phase, 208/120 V wye 40 Yes OVR T2 40 150PTSU 2CTB802341R2100 3660308518538 OVR T2 40 150CU240/120 V HLD, 240 V delta, 240 V single phase, 277 V single phase, 480/240 V split phase, 480/277 V wye

40 No OVR T2 40 320PU 2CTB802341R2400 3660308518965 OVR T2 40 320CU

240/120 V HLD, 240 V delta, 240 V single phase, 277 V single phase, 480/240 V split phase, 480/277 V wye

40 Yes OVR T2 40 320PTSU 2CTB802341R2500 3660308518545 OVR T2 40 320CU

600/347 V wye 40 Yes OVR T2 40 440PTSU 2CTB802341R2900 3660308518552 OVR T2 40 440CU480 V delta 40 Yes OVR T2 40 550PTSU 2CTB802341R3300 3660308518569 OVR T2 40 550CU600 V delta 40 Yes OVR T2 40 660PTSU 2CTB802341R3700 3660308518576 OVR T2 40 660CU

(1) May require multiple SPDs.

Two poleService voltage (1) Max. discharge Aux. contact - Type Order code EAN code Replacement

current remote monitoring cartridge (2)Imax, 8/20 µs, kA

120V single phase, 240/120V split phase, 208/120V wye 15 No OVR T2 2L 15 150PU 2CTB802343R0000 3660308518590 OVR T2 15 150CU240/120V HLD, 240V delta, 240V single phase, 277V single phase, 480/240V split phase, 480/277V wye

15 No OVR T2 2L 15 320PU 2CTB802343R0400 3660308518606 OVR T2 15 320CU

120V single phase, 240/120V split phase, 208/120V wye 40 Yes OVR T2 2L 40 150PTSU 2CTB802343R2100 3660308518613 OVR T2 40 150CU240/120V HLD, 240V delta, 240V single phase, 277V single phase, 480/240V split phase, 480/277V wye

40 Yes OVR T2 2L 40 320PTSU 2CTB802343R2500 3660308518620 OVR T2 40 320CU

(1) May require multiple SPDs.(2) May require up to two replacement cartridges.

Three poleService voltage (1) Max. discharge Aux. contact - Type Order code EAN code Replacement

current remote monitoring cartridge (2)Imax, 8/20 µs, kA

240/120 V split phase, 208/120 V wye 15 No OVR T2 3L 15 150PU 2CTB802345R0000 3660308518637 OVR T2 15 150CU240/120 V HLD, 240 V delta, 480/240 V split phase, 480/277 V wye

15 No OVR T2 3L 15 320PU 2CTB802345R0400 3660308518644 OVR T2 15 320CU

240/120 V split phase, 208/120 V wye 40 Yes OVR T2 3L 40 150PTSU 2CTB802345R2100 3660308518651 OVR T2 40 150CU240/120 V HLD, 240 V delta, 480/240 V split phase, 480/277 V wye

40 Yes OVR T2 3L 40 320PTSU 2CTB802345R2500 3660308518668 OVR T2 40 320CU

240 V delta, 480/240 V split phase, 600/347 V wye 40 Yes OVR T2 3L 40 440PTSU 2CTB802345R2900 3660308518675 OVR T2 40 440CU480 V delta 40 Yes OVR T2 3L 40 550PTSU 2CTB802345R3300 3660308518682 OVR T2 40 550CU(1) May require multiple SPDs.(2) May require up to three replacement cartridges.

Consult the service voltage and location table on page 16 for proper SPD selection. The following tables also present information on service voltage compatibility. Please note that multiple SPDs may be required depending on service voltage. Contact ABB technical support with any questions.

Page 20: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

18 | ABB Surge protective devices UL range

One pole + neutralService voltage (1) Max. discharge Aux. contact - remote Type Order code EAN code Replacement

current monitoring cartridge (2)Imax, 8/20 µs, kA

120 V single phase, 240/120 V split phase, 208/120 V wye 15 No OVR T2 1N 15 150PU 2CTB802342R0000 3660308519238 OVR T2 15 150CU, OVR T2 70NCU

240/120 V HLD, 240 V single phase, 277 V single phase, 480/240 V split phase, 480/277 V wye

15 No OVR T2 1N 15 320PU 2CTB802342R0400 3660308519245 OVR T2 15 320CU, OVR T2 70NCU

120 V single phase, 240/120 V split phase, 208/120 V wye 40 Yes OVR T2 1N 40 150PTSU 2CTB802342R2100 3660308519252 OVR T2 40 150CU, OVR T2 70NCU

240/120 V HLD, 240 V single phase, 277 V single phase, 480/240 V split phase, 480/277 V wye

40 Yes OVR T2 1N 40 320PTSU 2CTB802342R2500 3660308519269 OVR T2 40 320CU, OVR T2 70NCU

600/347 V wye 40 Yes OVR T2 1N 40 440PTSU 2CTB802342R2900 3660308519276 OVR T2 40 440CU, OVR T2 70NCU

600/347 V wye 40 Yes OVR T2 1N 40 550PTSU 2CTB802342R3300 3660308519283 OVR T2 40 550CU, OVR T2 70NCU

600/347 V wye 40 Yes OVR T2 1N 40 660PTSU 2CTB802342R3700 3660308519290 OVR T2 40 660CU, OVR T2 70NCU

(1) May require multiple SPDs.(2) May require up to one phase and one neutral replacement cartridges.

Two pole + neutralService voltage (1) Max. discharge Aux. contact - remote Type Order code EAN code Replacement

current monitoring cartridge (2)Imax, 8/20 µs, kA

240/120 V split phase, 208/120 V wye 15 No OVR T2 2N 15 150PU 2CTB802344R0000 3660308519306 OVR T2 15 150CU, OVR T2 70NCU

240/120 V HLD, 480/240 V split phase, 480/277 V wye 15 No OVR T2 2N 15 320PU 2CTB802344R0400 3660308519313 OVR T2 15 320CU, OVR T2 70NCU

240/120 V split phase, 208/120 V wye 40 Yes OVR T2 2N 40 150PTSU 2CTB802344R2100 3660308519320 OVR T2 40 150CU, OVR T2 70NCU

240/120 V HLD, 480/240 V split phase, 480/277 V wye 40 Yes OVR T2 2N 40 320PTSU 2CTB802344R2500 3660308519337 OVR T2 40 320CU, OVR T2 70NCU

600/347 V wye 40 Yes OVR T2 2N 40 440PTSU 2CTB802344R2900 3660308519344 OVR T2 40 440CU, OVR T2 70NCU

600/347 V wye 40 Yes OVR T2 2N 40 550PTSU 2CTB802344R3300 3660308519351 OVR T2 40 550CU, OVR T2 70NCU

600/347 V wye 40 Yes OVR T2 2N 40 660PTSU 2CTB802344R3700 3660308519368 OVR T2 40 660CU, OVR T2 70NCU

(1) May require multiple SPDs.(2) May require up to two phase and one neutral replacement cartridges.

OVR T2 surge protective devices UL rangeProduct selection

Page 21: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 19

Three pole + neutralService voltage Max. discharge Aux. contact - remote Type Order code EAN code Replacement

current monitoring cartridge (1) Imax, 8/20 µs, kA

208/120 V wye 15 No OVR T2 3N 15 150PU 2CTB802346R0000 3660308518699 OVR T2 15 150CU, OVR T2 70NCU

480/277 V wye, 240/120 V HLD 15 No OVR T2 3N 15 320PU 2CTB802346R0400 3660308518705 OVR T2 15 320CU, OVR T2 70NCU

208/120 V wye 40 Yes OVR T2 3N 40 150PTSU 2CTB802346R2100 3660308518712 OVR T2 40 150CU, OVR T2 70NCU

480/277 V wye, 240/120 V HLD 40 Yes OVR T2 3N 40 320PTSU 2CTB802346R2500 3660308518729 OVR T2 40 320CU, OVR T2 70NCU

600/347 V wye 40 Yes OVR T2 3N 40 440PTSU 2CTB802346R2900 3660308518736 OVR T2 40 440CU, OVR T2 70NCU

600/347 V wye 40 Yes OVR T2 3N 40 550PTSU 2CTB802346R3300 3660308518743 OVR T2 40 550CU, OVR T2 70NCU

600/347 V wye 40 Yes OVR T2 3N 40 660PTSU 2CTB802346R3700 3660308518750 OVR T2 40 660CU, OVR T2 70NCU

(1) May require up to three phase and one neutral replacement cartridges.

NeutralService voltage Max. discharge Aux. contact - remote Type Order code EAN code Replacement

current monitoring cartridgeImax, 8/20 µs, kA

HLD, single phase, split phase and wye 70 No OVR T2 70NPU 2CTB802341R8000 3660308518583 OVR T2 70NCU

Replacement cartridgesType Order code EAN code

OVR T2 15 150CU 2CTB802348R2500 3660308518767OVR T2 15 320CU 2CTB802348R2700 3660308518774OVR T2 40 150CU 2CTB802348R3500 3660308518781OVR T2 40 320CU 2CTB802348R3700 3660308518798OVR T2 40 440CU 2CTB802348R3900 3660308518804OVR T2 40 550CU 2CTB802348R4100 3660308518811OVR T2 40 660CU 2CTB802348R4300 3660308518828OVR T2 70NCU 2CTB802348R6500 3660308518835NOTE: These replacement cartridges are usable only with the new OVR DIN rail product range shown in this brochure.

OVR T2 surge protective devices UL rangeProduct selection

Page 22: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

20 | ABB Surge protective devices UL range

OVR T2 surge protective devices UL rangeProduct selection

Max. discharge Maximum continuous Voltage protection rating Type Order code EAN codecurrent operating voltageImax, 8/20 µs, kA Uc kV15 175 0.6 OVR T2 15 150PU 2CTB802341R0000 366030851851415 320 1.0 OVR T2 15 320PU 2CTB802341R0400 366030851852140 175 0.6 OVR T2 40 150PU 2CTB802341R2000 366030851895840 175 0.6 OVR T2 40 150PTSU 2CTB802341R2100 366030851853840 320 1.0 OVR T2 40 320PU 2CTB802341R2400 366030851896540 320 1.0 OVR T2 40 320PTSU 2CTB802341R2500 366030851854540 440 1.3 OVR T2 40 440PTSU 2CTB802341R2900 366030851855240 550 1.7 OVR T2 40 550PTSU 2CTB802341R3300 366030851856940 660 1.9 OVR T2 40 660PTSU 2CTB802341R3700 366030851857670 255 1.2 OVR T2 70NPU 2CTB802341R8000 366030851858315 175 0.6 OVR T2 2L 15 150PU 2CTB802343R0000 366030851859015 320 1.0 OVR T2 2L 15 320PU 2CTB802343R0400 366030851860640 175 0.6 OVR T2 2L 40 150PTSU 2CTB802343R2100 366030851861340 320 1.0 OVR T2 2L 40 320PTSU 2CTB802343R2500 366030851862015 175 0.6 OVR T2 3L 15 150PU 2CTB802345R0000 366030851863715 320 1.0 OVR T2 3L 15 320PU 2CTB802345R0400 366030851864440 175 0.6 OVR T2 3L 40 150PTSU 2CTB802345R2100 366030851865140 320 1.0 OVR T2 3L 40 320PTSU 2CTB802345R2500 366030851866840 440 1.3 OVR T2 3L 40 440PTSU 2CTB802345R2900 366030851867540 550 1.7 OVR T2 3L 40 550PTSU 2CTB802345R3300 366030851868215 175 0.6 / 0.7 (L-N / L-G) OVR T2 1N 15 150PU 2CTB802342R0000 366030851923815 320 1.0 / 1.1 (L-N / L-G) OVR T2 1N 15 320PU 2CTB802342R0400 366030851924540 175 0.6 / 0.7 (L-N / L-G) OVR T2 1N 40 150PTSU 2CTB802342R2100 366030851925240 320 1.0 / 1.1 (L-N / L-G) OVR T2 1N 40 320PTSU 2CTB802342R2500 366030851926940 440 1.3 / 1.4 (L-N / L-G) OVR T2 1N 40 440PTSU 2CTB802342R2900 366030851927640 550 1.7 / 1.8 (L-N / L-G) OVR T2 1N 40 550PTSU 2CTB802342R3300 366030851928340 660 1.9 / 2.0 (L-N / L-G) OVR T2 1N 40 660PTSU 2CTB802342R3700 366030851929015 175 0.6 / 1.2 / 0.7 (L-N / N-G / L-G) OVR T2 2N 15 150PU 2CTB802344R0000 366030851930615 320 1.0 / 1.2 / 1.1 (L-N / N-G / L-G) OVR T2 2N 15 320PU 2CTB802344R0400 366030851931340 175 0.6 / 1.2 / 0.7 (L-N / N-G / L-G) OVR T2 2N 40 150PTSU 2CTB802344R2100 366030851932040 320 1.0 / 1.2 / 1.1 (L-N / N-G / L-G) OVR T2 2N 40 320PTSU 2CTB802344R2500 366030851933740 440 1.3 / 1.2 / 1.4 (L-N / N-G / L-G) OVR T2 2N 40 440PTSU 2CTB802344R2900 366030851934440 550 1.7 / 1.2 / 1.8 (L-N / N-G / L-G) OVR T2 2N 40 550PTSU 2CTB802344R3300 366030851935140 660 1.9 / 1.2 / 2.0 (L-N / N-G / L-G) OVR T2 2N 40 660PTSU 2CTB802344R3700 366030851936815 175 0.6 / 1.2 / 0.7 (L-N / N-G / L-G) OVR T2 3N 15 150PU 2CTB802346R0000 366030851869915 320 1.0 / 1.2 / 1.1 (L-N / N-G / L-G) OVR T2 3N 15 320PU 2CTB802346R0400 366030851870540 175 0.6 / 1.2 / 0.7 (L-N / N-G / L-G) OVR T2 3N 40 150PTSU 2CTB802346R2100 366030851871240 320 1.0 / 1.2 / 1.1 (L-N / N-G / L-G) OVR T2 3N 40 320PTSU 2CTB802346R2500 366030851872940 440 1.3 / 1.2 / 1.4 (L-N / N-G / L-G) OVR T2 3N 40 440PTSU 2CTB802346R2900 366030851873640 550 1.7 / 1.2 / 1.8 (L-N / N-G / L-G) OVR T2 3N 40 550PTSU 2CTB802346R3300 366030851874340 660 1.9 / 1.2 / 2.0 (L-N / N-G / L-G) OVR T2 3N 40 660PTSU 2CTB802346R3700 3660308518750

Page 23: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 21

OVR T2 surge protective devices UL rangeTechnical data

Electrical characteristicsType / Test class UL 1449 3rd edition - Type 4 for type 2 apps

IEC 61 643-1 - T2 / IIFrequency 50-60 HzResponse time <25 nsOperating current (Ic) <0.1 mAShort circuit withstand current (Isccr) 200 kAIntegrated thermal disconnector YesState indicator YesSafety reserve NoRemote indicator OptionalDisconnector Circuit breaker - B or C curve ≤125 AClass J fuse ≤100 A

Mechanical characteristicsWire range - solid wire AWG 4-AWG 14Wire range - stranded wire AWG 6-AWG 14Stripping length 0.5 inTightening torque 24.5 in-lbsDegree of protection NEMA 1

Remote indicator (optional)Type of contact 1 NO / 1 NCMinimum load 12 VDC / 10 mAMaximum load 250 VAC / 1 AConnection cross section AWG 16

Miscellaneous characteristicsOperating temperature -40 ˚F to 176 ˚FMaximum altitude 6562 ftColor of housing / Fire resistance according to UL 94 Gray RAL 7035 / V-0Reference standards UL 1449 3rd edition, IEC 61 643-1

Page 24: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

22 | ABB Surge protective devices UL range

OVR T2 surge protective devices UL range

Dimensions mm, inches

One pole

Two pole

64.8 2.55"

58 2.28"

43.5 1.71"

85 3

.35"

45 1

.77"

17.8 0.7"

OVR T2 15 150PUOVR T2 15 320PUOVR T2 40 150PUOVR T2 40 320PUOVR T2 70NPU

35.6 1.4"

64.8 2.55"

58 2.28"

43.5 1.71"

90.5

3.5

6"

85 3

.35"

45 1

.77"

OVR T2 2L 15 150PUOVR T2 2L 15 320PU

64.8 2.55"

58 2.28"

43.5 1.71"

96 3

.78"

85 3

.35"

45 1

.77"

17.8 0.7"

OVR T2 40 150PTSUOVR T2 40 320PTSUOVR T2 40 440PTSUOVR T2 40 550PTSUOVR T2 40 660PTSU

64.8 2.55"

58 2.28"

98.5

3.8

8"

85 3

.35"

45 1

.77"

43.5 1.71"

35.6 1.4"

OVR T2 2L 40 150PTSUOVR T2 2L 40 320PTSU

Page 25: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 23

OVR T2 surge protective devices UL range

Dimensions mm, inches

Three pole

One pole + neutral

64.8 2.55"

58 2.28"

90.5

3.5

6"85

3.3

5"45

1.7

7"

43.5 1.71"

53.4 2.1"

OVR T2 3L 15 150PUOVR T2 3L 15 320PU

64.8 2.55"

43.5 1.71"

90.5

3.5

6"

85 3

.35"

45 1

.77"

58 2.28"35.6 1.4"

OVR T2 1N 15 150PUOVR T2 1N 15 320PU

64.8 2.55"

58 2.28"

43.5 1.71"

98.5

3.8

8"

85 3

.35"

45 1

.77"

53.4 2.1"

OVR T2 3L 40 150PTSUOVR T2 3L 40 320PTSUOVR T2 3L 40 440PTSUOVR T2 3L 40 550PTSU

64.8 2.55"

58 2.28"

98.5

3.8

8"

85 3

.35"

45 1

.77"

43.5 1.71"

35.6 1.4"

OVR T2 1N 40 150PTSUOVR T2 1N 40 320PTSUOVR T2 1N 40 440PTSUOVR T2 1N 40 550PTSUOVR T2 1N 40 660PTSU

Page 26: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

24 | ABB Surge protective devices UL range

OVR T2 surge protective devices UL range

Dimensions mm, inches

Two pole + neutral

Three pole + neutral

64.8 2.55"58 2.28"

43.5 1.71"

45 1

.77"

85 3

.35"

90.5

3.5

6"

53.4 2.1"

OVR T2 2N 15 150PUOVR T2 2N 15 320PU

64.8 2.55"

58 2.28"

90.5

3.5

6"

85 3

.35"

45 1

.77"

43.5 1.71"

71.2 2.8"

OVR T2 3N 15 150PUOVR T2 3N 15 320PU

64.8 2.55"

58 2.28"

98.5

3.8

8"

85 3

.35"

45 1

.77"

43.5 1.71"

53.4 2.1"

OVR T2 2N 40 150PTSUOVR T2 2N 40 320PTSUOVR T2 2N 40 440PTSUOVR T2 2N 40 550PTSUOVR T2 2N 40 660PTSU

64.8 2.55"

58 2.28"

98.5

3.8

8"

85 3

.35"

45 1

.77"

43.5 1.71"

71.2 2.8"

OVR T2 3N 40 150PTSUOVR T2 3N 40 320PTSUOVR T2 3N 40 440PTSUOVR T2 3N 40 550PTSUOVR T2 3N 40 660PTSU

Page 27: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 25

Previous ABB catalog number - New ABB catalog number - UL 1449 2nd edition parts UL 1449 3rd edition partsOVR 15 150 OVR T2 15 150PUOVR 15 150SPOVR 15 275 OVR T2 15 320PUOVR 40 150P OVR T2 40 150PUOVR 40 150OVR 40 150SPOVR 65 150SPOVR 40 150SPTS OVR T2 40 150PTSUOVR 40 275P OVR T2 40 320PUOVR 40 275SPOVR 40 320POVR 65 275SPOVR 10 0275SPOVR 40 320SPOVR 65 320SPOVR 100 320SPOVR 40 275SPTS OVR T2 40 320PTSUOVR 40 320SPTSOVR 65 275SPTSOVR 100 320SPTSOVR 15 275PTSOVR 40 440 OVR T2 40 440PTSUOVR 40 440SPOVR 40 320D440POVR 40 440SPTSOVR 65 440SPTSOVR 15 440OVR 65 440SPOVR 100 440SOVR 100 440SPOVR 15 550 OVR T2 40 550PTSUOVR 65 550SOVR 40 550OVR 40 550SOVR 40 660PTS OVR T2 40 660PTSUOVR 40 660POVR 40 660SPOVR 40 660SPTSOVR 15 660OVR 40 660SOVR 65 660SOVR 65NP OVR T2 70NPUOVR 100NP

Previous ABB catalog number - New ABB catalog number - UL 1449 2nd edition parts UL 1449 3rd edition partsOVR 3L 15 275P OVR T2 3L 15 320PUOVR 3L 40 275SP OVR T2 3L 40 320PTSUOVR 3L 65 275SPOVR 3N 15 150 OVR T2 3N 15 150PUOVR 3N 15 320 OVR T2 3N 15 320PUOVR 3N 40 150SP OVR T2 3N 40 150PTSUOVR 3N 40 320PTS OVR T2 3N 40 320PTSUOVR 3N 15 275OVR 3N 40 320POVR 3N 40 320SPTSOVR 3N 100 320SPTSOVR 3N 40 275SPOVR 3N 65 275SPOVR 3N 40 320SPOVR 3N 65 320SPOVR 3N 65 320SPTSOVR 3N 100 320SPOVR N3 40 320SPTSOVR 3N 40 440SP OVR T2 3N 40 440PTSUOVR N3 65 440SOVR 3N 65 440SPOVR 1N 15 150 OVR T2 1N 15 150PUOVR 1N 15 150SPTSOVR 1N 40 150SP OVR T2 1N 40 150PTSUOVR 1N 40 150SPTSOVR 1N 65 150SPOVR N1 40 275P OVR T2 1N 40 320PTSUOVR N1 40 275PTSOVR 4L 65 440S OVR T2 3L 40 440PTSU +

OVR T2 40 440PTSU

Cross referenceUL 1449 2nd edition to 3rd edition

Page 28: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

26 | ABB Surge protective devices UL range

OVR PV surge protective devicesPhotovoltaic surge protection

IntroductionProviding power with photovoltaic (PV) solar panels is an ever increasing part of public utilities’ renewable energy portfo-lios, designed to provide electricity in an economical manner, within the context of regulations and scarce resources. Instal-lations are frequently in isolated areas, and combined with the large surface area of a group of panels, the risk of damage from direct and indirect lightning strikes is high. To mitigate this risk, ABB recommends the installation of OVR PV surge protective devices on the DC portion of the system. ABB provides a wide range of surge protection devices that have been specifically designed for photovoltaic systems.The main features of the OVR PV surge protectors are: – Built-in thermal protection with 25 A DC breaking capacity – Removable cartridges for easy maintenance with no need

to isolate the line – Remote signalling contact for monitoring the operating

status (TS versions) – No subsequent short-circuit current – No risk if the polarity is reversed – Approvals: IEC only.

OVR PV surge protective devicesConverter Umax - Max. discharge Aux. contact - Type Order code EAN code ReplacementDC portion current remote monitoring cartridgeV Imax, 8/20 µs, kA500 and 600 40 No OVR PV 40 600P 2CTB803953R5300 3660308516510 OVR PV 40 600C, OVR PV MC500 and 600 40 Yes OVR PV 40 600PTS 2CTB803953R5400 3660308516527 OVR PV 40 600C, OVR PV MC1000 40 No OVR PV 40 1000P 2CTB803953R6400 3660308516534 OVR PV 40 1000C1000 40 Yes OVR PV 40 1000PTS 2CTB803953R6500 3660308516541 OVR PV 40 1000C

Replacement cartridgesType Order code EAN code

OVR PV 40 600C 2CTB803950R0000 3660308516558OVR PV 40 1000C 2CTB803950R0100 3660308516565OVR PV MC 2CTB803950R0300 3660308516756

Installation of OVR SPD on photovoltaic networks

Page 29: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 27

OVR TC surge protective devices UL rangeData line surge protection

OVR TC surge protective devices UL rangeMaximum continuous operating voltage Max. discharge current Type Order code EAN codeUc Imax, 8/20 µs, kA7 10 OVR TC 06V 2CTB811814R0100 366030851224614 10 OVR TC 12V 2CTB811814R0200 366030851225327 10 OVR TC 24V 2CTB811814R0300 366030851226053 10 OVR TC 48V 2CTB811814R0400 3660308512277220 10 OVR TC 200V (1) 2CTB811814R0500 3660308512284220 10 OVR TC 200FR 2CTB811814R0000 3660308512291(1) Connection type is parallel. All other parts, series.

IntroductionIn order to ensure complete protection for equipment in a facility, telecommunication lines entering the installation must have surge protection. Doing so will keep computers, fax machines and other data and communications equipment safe.The main features of OVR data line surge protectors are: – 10 kA maximum discharge current – Nominal voltage: 6, 12, 24, 48 and 200 V DC – Visual life indicator – UL 497B approved

OVR T2 3N 15 320PU

Sub- distribution panels

OVR T2 3N 40 320PTSU

Main distribution panel

OVR TC 48V

Telecom switching system protection

Telecom protection

OVR TC 48V

Intercom protection

Page 30: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

28 | ABB Surge protective devices UL range

ABB solutions for photovoltaicsProtection and other modular devices

BrochureABB solutions for photovoltaicsProtection and other modular devices

Technical catalogueSystem pro M compact® DIN Rail components for low voltage installation

Global ABB solutions

System pro M compact®

DIN Rail components for low voltage installation

Technical catalogue - Edition 2012

Contact us

2CS

C40

0002

D02

10 -

04/

2012

- 1

2.00

0 P

z. -

CA

LABB SACE a division of ABB S.p.A.ABB STOTZ-KONTAKT GmbH

In consideration of modifications to Standards and materials, the characteristics and overall dimensions indicated in this catalogue may be considered binding only following confirmation by ABB

Copyright 2012 ABB. All rights reserved.

System

pro

M co

mp

act® D

IN R

ail components for low

voltage installation

Main catalogueSystem pro M compact®

Surge and lightning protection solutions

Main catalogue

System pro M compact®

Surge and lightning protection solutions

Brochure

Contact us

1TX

H 0

00 0

45 B

0202

- P

rinte

d in

Fra

nce

(V 1

2.20

10 L

amaz

ière

)

Autoprotected surge arrestersNew OVR PLUS range

1TXH 000 045 B0202 - Autoprotected Surge Arresters.indd 7 10/12/2010 12:18:30

BrochureAutoprotected surge arresters New OVR PLUS range

Solar energyLightning and surge protective devices

Brochure

1TXH 000 118 B0_01.indd 1 31/05/2011 17:30:06

BrochureSolar energy Lightning and surge protective devices

Lightning protection systemEarly streamer emission air terminal

1TXH 000 134 B0201_OPR-Direct-Lightning-Protection.indd 1 17/08/2011 13:42:22

BrochureLightning protection system Early streamer emission air terminal

DatasheetSurge protective devices OVR PV range

Surge protective devicesOVR PV range

Datasheet

New UTE C 61-740-51 on photovoltaic installation

Part-51: surge protective devices connected to photovoltaic generators – Performance requirements and testing methods.

A new guide on a developing marketA new document taking account of varied aspects of photovoltaic generators and technologies is available, designed UTE C 61-740-51, to define specific surge protection to photovoltaic installations. This document is for now the only one available worldwide to define surge protective devices for photovoltaic installations.

The New UTE C 61-740-51 defi nes testing performances and safety for specifi c surge protection to the photovoltaic structure.

According to the very specific characteristics of PV generators and PV installations with high voltages and low DC current, the UTE C 61-740-51 introduces the idea of testing the be-haviour of photovoltaic surge protective devices on end of life for the safety of the equipments.

PV characteristicsThe following information shall be given by the manufacturer: – PV symbol on the product – Ucpv maximum continuous operating voltage – In nominal discharge current – Iimp or Imax depending on if it is a Type 1 or Type 2 surge

protection – Up protection level – Iscwpv short circuit DC current withstand.

Only SPDs with the above declared characteristics and with their conformity declaration are suitable for photovoltaic installations.

Using a surge protection not conforms to such specific ap-plication or using AC dedicated SPDs on DC photovoltaic installations shall result in fire and equipment damages.

New ABB photovoltaic OVR surge protection ratingsComplying with the new UTE C 61-740-51, the new ratings of our OVR PV range have been defined for an easier selection and to fulfil requirements of photovoltaic specific networks.

Surge arrester OVR PV 40 600 OVR PV 40 1000

Maximum operating voltage Ucpv : 670 V Ucpv : 1000 V

Short circuit current Iscwpv : 100 A Iscwpv : 100 A

Back-up protection if Iscwpv >100 A: – E90Fuse / 10AgPV / 10AgPV – MCB / S802PV-S10 / S804PV-S10

1TXH 000 043 L0_01 - OVR PV photovoltaic.indd 1 12/08/2011 14:04:44

Surge Protective DevicesUL 1449 from 2nd to 3rd Edition

Technical paper, March 2011

The Underwriters Laboratories (UL) standard for Surge Protective Devices (SPDs) has been the primary safety standard for surge protection since the first edition was published in 1985, and updated to the second edition in 1996.

The objective of UL 1449 has always been to increase safety in terms of surge protection. Thus, major changes have re-cently been made to the surge protection standard.

The latest edition, known as UL 1449 3rd Edition, was pub-lished on September 29, 2006 and took effect September 2009, and is now also an ANSI standard. A revision was made on February 8, 2011.

To avoid confusion, the objective of this paper is to explain and summarize the major changes made to the standard.

The key updates are: – Change in the standard’s name – The different Type designations of Surge Protective Devices – The measured voltage protection level – The Nominal discharge current

Change in the standard’s name: From TVSS to SPDsPrior to UL 1449 3rd Edition taking effect, the devices this standard covers were known as Transient Voltage Surge Suppres-sors (TVSS), operating on power circuits not exceeding 600 V. With the inception of the 3rd Edition, these devices are now known as Surge Protective Devices (SPDs), and may operate on power circuits not exceeding 1000 V.

This new designation moves the UL standard closer to the Inter-national designation and to IEC standards. The new edition is now renamed UL Standard for Safety for Surge Protective Devices, UL 1449.

The different Type designations of Surge Protective DevicesThe new UL 1449 3rd Edition places SPDs into five different Type categories based on installation location within an electrical system. While Type 1, Type 2 and Type 3 categories refer to different types of SPDs that can be installed at specific locations, Type 4 and Type 5 categories refer to components used in an SPDs configuration.

Type 1 – "Permanently connected SPDs intended for installa-tion between the secondary of the service transformer and the line side of the service equipment overcurrent device."

Type 2 – "Permanently connected SPDs intended for installation on the load side of the service equipment overcurrent device."

Type 3 – "Point of utilization SPDs, installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel."

Type 4 – Component Assemblies – "Component assembly consisting of one or more Type 5 components together with a disconnect (integral or external) or a means of complying with the limited current tests."

Type 1, 2, 3 – Component Assemblies – "Consists of a Type 4 component assembly with internal or external short circuit protection."

Type 5 – "Discrete component surge suppressors, such as MOVs that may be mounted on a PWB, connected by its leads or provided within an enclosure with mounting means and wiring terminations."

These new categories are by far the major changes applied to UL 1449 3rd Edition. SPDs installation location is now taken into account. The closer an SPD is installed to the equipment, the better the protection is. This is a push in the direction of providing stepped protection including external and internal surge protection.

The measured voltage protection levelOne of the last changes found in the new UL 1449 3rd Edition, is the modification in the measured voltage protection level. The Measured Limiting Voltage (MLV) is the maximum magnitude of voltage measured at the application of a specific impulse wave shape. When applying a certain surge current on the SPD the measured voltage at the device terminals is the so called “let-through voltage.” In UL 1449 2nd Edition, the let-through voltage was referred to as Suppressed Voltage Rating (SVR) and was calcu-lated with a 0.5 kA surge wave form at 6 kV. The new designation is Voltage Protection Rating (VPR) and is calculated with a 3 kA surge wave form at 6 kV.

The MLV will allow comparison of different types of SPDs with regards to the let-through voltage. However, it is important to

1TXH 000 106 L0201_Leaflet Surge Protection Devices.indd 1 12/08/2011 14:11:52

Technical paper, March 2011Surge protective devices UL 1449 from 2nd to 3rd Edition

Page 31: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

ABB Surge protective devices UL range | 29

Index

Order code Type Page Type Order code Page

2CTB802341R0000 OVR T2 15 150PU 172CTB802341R0400 OVR T2 15 320PU 172CTB802341R2000 OVR T2 40 150PU 172CTB802341R2100 OVR T2 40 150PTSU 172CTB802341R2400 OVR T2 40 320PU 172CTB802341R2500 OVR T2 40 320PTSU 172CTB802341R2900 OVR T2 40 440PTSU 172CTB802341R3300 OVR T2 40 550PTSU 172CTB802341R3700 OVR T2 40 660PTSU 172CTB802341R8000 OVR T2 70NPU 192CTB802342R0000 OVR T2 1N 15 150PU 182CTB802342R0400 OVR T2 1N 15 320PU 182CTB802342R2100 OVR T2 1N 40 150PTSU 182CTB802342R2500 OVR T2 1N 40 320PTSU 182CTB802342R2900 OVR T2 1N 40 440PTSU 182CTB802342R3300 OVR T2 1N 40 550PTSU 182CTB802342R3700 OVR T2 1N 40 660PTSU 182CTB802343R0000 OVR T2 2L 15 150PU 172CTB802343R0400 OVR T2 2L 15 320PU 172CTB802343R2100 OVR T2 2L 40 150PTSU 172CTB802343R2500 OVR T2 2L 40 320PTSU 172CTB802344R0000 OVR T2 2N 15 150PU 182CTB802344R0400 OVR T2 2N 15 320PU 182CTB802344R2100 OVR T2 2N 40 150PTSU 182CTB802344R2500 OVR T2 2N 40 320PTSU 182CTB802344R2900 OVR T2 2N 40 440PTSU 182CTB802344R3300 OVR T2 2N 40 550PTSU 182CTB802344R3700 OVR T2 2N 40 660PTSU 182CTB802345R0000 OVR T2 3L 15 150PU 172CTB802345R0400 OVR T2 3L 15 320PU 172CTB802345R2100 OVR T2 3L 40 150PTSU 172CTB802345R2500 OVR T2 3L 40 320PTSU 172CTB802345R2900 OVR T2 3L 40 440PTSU 172CTB802345R3300 OVR T2 3L 40 550PTSU 172CTB802346R0000 OVR T2 3N 15 150PU 192CTB802346R0400 OVR T2 3N 15 320PU 192CTB802346R2100 OVR T2 3N 40 150PTSU 192CTB802346R2500 OVR T2 3N 40 320PTSU 192CTB802346R2900 OVR T2 3N 40 440PTSU 192CTB802346R3300 OVR T2 3N 40 550PTSU 192CTB802346R3700 OVR T2 3N 40 660PTSU 192CTB802348R2500 OVR T2 15 150CU 192CTB802348R2700 OVR T2 15 320CU 192CTB802348R3500 OVR T2 40 150CU 192CTB802348R3700 OVR T2 40 320CU 192CTB802348R3900 OVR T2 40 440CU 192CTB802348R4100 OVR T2 40 550CU 192CTB802348R4300 OVR T2 40 660CU 192CTB802348R6500 OVR T2 70NCU 192CTB803950R0000 OVR PV 40 600C 262CTB803950R0100 OVR PV 40 1000C 262CTB803950R0300 OVR PV MC 262CTB803953R5300 OVR PV 40 600P 262CTB803953R5400 OVR PV 40 600PTS 262CTB803953R6400 OVR PV 40 1000P 262CTB803953R6500 OVR PV 40 1000PTS 262CTB811814R0000 OVR TC 200FR 272CTB811814R0100 OVR TC 06V 272CTB811814R0200 OVR TC 12V 272CTB811814R0300 OVR TC 24V 272CTB811814R0400 OVR TC 48V 272CTB811814R0500 OVR TC 200V 272CTB812001R0100 OVR 1N 160 277 102CTB812001R0300 OVR NE12 320 277Y 102CTB812001R0400 OVR NE12 320 120SP 102CTB812001R0500 OVR NE12 160 277Y 102CTB812001R0600 OVR NE12 160 480D 102CTB812001R0800 OVR NE12 160 120SP 102CTB812001R1000 OVR NE12 320 480D 102CTB812001R1100 OVR NE12 160 277YX 102CTB812001R1200 OVR NE12 320 277YX 102CTB812001R1300 OVR NE12 160 120SPX 102CTB812001R1400 OVR NE12 320 120SPX 102CTB812001R1500 OVR NE12 160 480DX 102CTB812001R1600 OVR NE12 320 480DX 102CTB812001R1700 OVR 1N 160 480 102CTB812001R1800 OVR 1N 160 120 102CTB812001R2100 OVR 1N 160 277PS 102CTB812001R2700 OVR 1N 160 480PS 102CTB812001R2800 OVR 1N 160 120PS 10

OVR 1N 160 120 2CTB812001R1800 10OVR 1N 160 120PS 2CTB812001R2800 10OVR 1N 160 277 2CTB812001R0100 10OVR 1N 160 277PS 2CTB812001R2100 10OVR 1N 160 480 2CTB812001R1700 10OVR 1N 160 480PS 2CTB812001R2700 10OVR NE12 160 120SP 2CTB812001R0800 10OVR NE12 160 120SPX 2CTB812001R1300 10OVR NE12 160 277Y 2CTB812001R0500 10OVR NE12 160 277YX 2CTB812001R1100 10OVR NE12 160 480D 2CTB812001R0600 10OVR NE12 160 480DX 2CTB812001R1500 10OVR NE12 320 120SP 2CTB812001R0400 10OVR NE12 320 120SPX 2CTB812001R1400 10OVR NE12 320 277Y 2CTB812001R0300 10OVR NE12 320 277YX 2CTB812001R1200 10OVR NE12 320 480D 2CTB812001R1000 10OVR NE12 320 480DX 2CTB812001R1600 10OVR PV 40 600C 2CTB803950R0000 26OVR PV 40 600P 2CTB803953R5300 26OVR PV 40 600PTS 2CTB803953R5400 26OVR PV 40 1000C 2CTB803950R0100 26OVR PV 40 1000P 2CTB803953R6400 26OVR PV 40 1000PTS 2CTB803953R6500 26OVR PV MC 2CTB803950R0300 26OVR T2 1N 15 150PU 2CTB802342R0000 18OVR T2 1N 15 320PU 2CTB802342R0400 18OVR T2 1N 40 150PTSU 2CTB802342R2100 18OVR T2 1N 40 320PTSU 2CTB802342R2500 18OVR T2 1N 40 440PTSU 2CTB802342R2900 18OVR T2 1N 40 550PTSU 2CTB802342R3300 18OVR T2 1N 40 660PTSU 2CTB802342R3700 18OVR T2 2L 15 150PU 2CTB802343R0000 17OVR T2 2L 15 320PU 2CTB802343R0400 17OVR T2 2L 40 150PTSU 2CTB802343R2100 17OVR T2 2L 40 320PTSU 2CTB802343R2500 17OVR T2 2N 15 150PU 2CTB802344R0000 18OVR T2 2N 15 320PU 2CTB802344R0400 18OVR T2 2N 40 150PTSU 2CTB802344R2100 18OVR T2 2N 40 320PTSU 2CTB802344R2500 18OVR T2 2N 40 440PTSU 2CTB802344R2900 18OVR T2 2N 40 550PTSU 2CTB802344R3300 18OVR T2 2N 40 660PTSU 2CTB802344R3700 18OVR T2 3L 15 150PU 2CTB802345R0000 17OVR T2 3L 15 320PU 2CTB802345R0400 17OVR T2 3L 40 150PTSU 2CTB802345R2100 17OVR T2 3L 40 320PTSU 2CTB802345R2500 17OVR T2 3L 40 440PTSU 2CTB802345R2900 17OVR T2 3L 40 550PTSU 2CTB802345R3300 17OVR T2 3N 15 150PU 2CTB802346R0000 19OVR T2 3N 15 320PU 2CTB802346R0400 19OVR T2 3N 40 150PTSU 2CTB802346R2100 19OVR T2 3N 40 320PTSU 2CTB802346R2500 19OVR T2 3N 40 440PTSU 2CTB802346R2900 19OVR T2 3N 40 550PTSU 2CTB802346R3300 19OVR T2 3N 40 660PTSU 2CTB802346R3700 19OVR T2 15 150CU 2CTB802348R2500 19OVR T2 15 150PU 2CTB802341R0000 17OVR T2 15 320CU 2CTB802348R2700 19OVR T2 15 320PU 2CTB802341R0400 17OVR T2 40 150CU 2CTB802348R3500 19OVR T2 40 150PTSU 2CTB802341R2100 17OVR T2 40 150PU 2CTB802341R2000 17OVR T2 40 320CU 2CTB802348R3700 19OVR T2 40 320PTSU 2CTB802341R2500 17OVR T2 40 320PU 2CTB802341R2400 17OVR T2 40 440CU 2CTB802348R3900 19OVR T2 40 440PTSU 2CTB802341R2900 17OVR T2 40 550CU 2CTB802348R4100 19OVR T2 40 550PTSU 2CTB802341R3300 17OVR T2 40 660CU 2CTB802348R4300 19OVR T2 40 660PTSU 2CTB802341R3700 17OVR T2 70NCU 2CTB802348R6500 19OVR T2 70NPU 2CTB802341R8000 19OVR TC 06V 2CTB811814R0100 27OVR TC 12V 2CTB811814R0200 27OVR TC 24V 2CTB811814R0300 27OVR TC 48V 2CTB811814R0400 27OVR TC 200FR 2CTB811814R0000 27OVR TC 200V 2CTB811814R0500 27

Page 32: Catalogue Surge protective devices UL range OVR NE12 and ... · The new UL 1449 3rd edition places SPDs into five different type categories based on installation location within an

1TX

H 0

00 1

68 C

0201

- Im

prim

é en

Fra

nce

(PD

F 06

.201

2)

Contact us

ABB FranceLow Voltage Products DivisionPôle Foudre Soulé & Hélita465, avenue des Pré Seigneurs - La BoisseF-01124 Montluel cedex / France

www.abb.com

NoteWe reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.

We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB.

Copyright© 2012 ABBAll rights reserved