catalogo general Media Tensión (abb)

132
Medium Voltage Products General catalogue Medium voltage apparatus

Transcript of catalogo general Media Tensión (abb)

Page 1: catalogo general Media Tensión (abb)

Medium Voltage Products

General catalogueMedium voltage apparatus

Page 2: catalogo general Media Tensión (abb)

2

Page 3: catalogo general Media Tensión (abb)

3

Contents

Introduction 4

Contactors 6

Circuit-breakers for indoor installation 8

Cartridge current limiters 20

Apparatus for railway traction 21

Enclosures and fixed parts 23

Switch-disconnectors 32

Fuses 41

Vacuum interrupters 43

Insulators 44

Apparatus for outdoor installation 48

Capacitors 53

Voltage indicators 55

Connectors 56

Primary distribution switchgear 58

Secondary distribution switchgear 70

Relays and multi-function units 76

Instrument transformers and sensors 92

Outdoor instrument transformers 108

Instrument transformer protection 109

Instrument transformers ANSI 110

Modular prefabricated solutions for photovoltaic fields

117

Substation automation systems 118

Medium Voltage Product Service 122

Page 4: catalogo general Media Tensión (abb)

4

IntroductionThis is ABB

ABB is a global leader inpower and automationtechnologies that enableutility and industrycustomers to improvetheir performance whilelowering environmentalimpact.

Our group comprises five maindivisions:

– Power products– Power systems– Discrete automation and motion– Low voltage products– Process automation

SustainabilitySustainability is integral to all aspects of ABB’s business so we aim to balanceeconomic success, environmental stewardship and social progress to benefit all ourstakeholders.

Sustainability considerations cover how we design and manufacture products,what we offer customers, how we engage suppliers, how we assess risksand opportunities, and how we behave in the communities where we operateand towards one another. We also strive for excellence in health and safetyperformance.

TechnologyTechnology plays a key role for ABB. We have nine research centres, 6,000scientists and 70 university collaborations across the world – all working to developunique technologies that make our customers more competitive and efficient whileminimizing impact on the environment.

Where to find usABB operates in more than 100 countries and we have offices in 87 of thosecountries to provide the support our global and local customers need to developand conduct their business successfully.

Page 5: catalogo general Media Tensión (abb)

5

The one-shop service for all your medium voltage needs

With ABB, you can meet all your requirements for medium voltage productsand systems from a single supplier. We have over 100 years of experiencein the design, development, manufacturing and through-life service supportof medium voltage switchgear, and the largest installed base of anymanufacturer worldwide.

Whatever your application – utility, industrial, transportation or commercial – wecan provide the perfect, coordinated solution that delivers maximum efficiency,reliability and safety. Our comprehensive medium voltage portfolio coversswitchgear, apparatus, modular systems and distribution automation. And, thanksto ABB’s global service network, we support our products and systems througha comprehensive range of services that ensure optimum performance throughouttheir life – from installation and commissioning to routine maintenance, retrofit andupgrades to eventual decommissioning.

Quality systemsABB operates the very highest global, national and industry-specific qualitystandards including ISO 9001. Our environmental management systems conformto ISO 14001 and our health and safety management system conforms to OHSAS18001.

A wide range of applicationsABB’s medium voltage equipmentserves a wide variety of applicationsthroughout the world including:

– Utility generation– Utility transmission– Utility distribution– Transportation– Heavy industrial process plant– Mining and mineral processing– Light industrial parks– Hospitals

Product portfolioABB offers a wide range of mediumvoltage products for primary andsecondary distribution applications,conforming to IEC standards as wellas those of the major industrializedcountries, including:

– Circuit breakers– Switch-disconnectors– Contactors– Fixed parts and enclosures– Distribution switchgear– Protection relays and control systems– Substation automation– Electrical distribution substations– A comprehensive range of accessories

Page 6: catalogo general Media Tensión (abb)

6

Contactor VSC 7 VSC 12

Rated voltage kV 7.2 12

Withstand voltage at 50 Hz kV 23 28 (2)

Impulse withstand voltage kVbil 60 75

Rated frequency Hz 50-60 50-60

Utilization Fixed/UniGear/PowerCube Fixed/UniGear/PowerCube

Rated service current A 400 400

Rated short-time withstand current for 1 s A 6,000 6,000

Rated peak current kA 15 15

Rated short-circuit time (tk) s 1 1

Nominal number of operations

SCO function Op./hr 900 900

DCO function Op./hr 900 900

Rated load and overload characteristics in category of utilisation:

(AC4 Category) 100 closing operations kA 4,000 4,000

(AC4 Category) 25 opening operations kA 4,000 4,000

Normal current A 400 400

Electrical life (AC1category) (operations) (3) No. 1,000,000 1,000,000

Mechanical life (operations) No. 1,000,000 1,000,000

Short-circuit breaking capacity (1) A 6,000 4,000

Short-circuit making capacity (1) A 15,000 8,000

Opening time ms 20 ... 30 20 ... 30

Closing time ms 35 ... 50 35 ... 50

Version mm Fixed Withdrawable Fixed Withdrawable

Overall dimensions (excluding accessories)

H mm 371 636 423 636

inch 14.6 25 16.6 25

Lmm 350 531 350 531

inch 13.8 21 13.8 21

Dmm 215 657 215 657

inch 8.5 25.9 8.5 25.9

Weight kg 44 108 44 108

lbs 20 49 20 49

Technical catalogue No. 1VCP000165 1VCP000165

V-Contact VSC

(1) O-3min-CO-3min-CO single operation sequence.(2) Version for 42 kV - 50 Hz x 1 min. between phases and between phase and earth available on request (only fixed contactors or for UniGear switchgear).(3) Electrical life obtainable by following the maintenance programme given in the installation manual.

Contactors IEC

D

H

L

Vacuum contactors• Tested and constructed in accordance with IEC Standards• Bistable permanent magnet actuator• SCO function: Single Command Operated – electrical latching function• DCO function: Double Command Operated – mechanical latching function• Limited power consumption• Very compact dimensions• Specific vacuum interrupters for motor switching• Up to 1,000,000 operations• Maintenance-free• Electronic multi-voltage feeder• Fixed and withdrawable versions

Page 7: catalogo general Media Tensión (abb)

7

Page 8: catalogo general Media Tensión (abb)

8

VD4/R - VD4/LVacuum circuit-breakers with mechanical operating mechanism for secondary distribution• Tested and manufactured in conformity with IEC Standards• Circuit-breaker with right- or left -hand lateral operating mechanism• On request, application of the PR521 self-supplied protection device or REF601

(not self-supplied) IEC version • Designed for installation in unmanned substations and without auxiliary power

supply (with PR521 only)• Sealed-for-life poles• Interchangeable with HD4/R circuit-breakers (up to 24 kV)

(1) Increase by 20 kg with PR521 and sensors.(2) Removable version for UniMix, UniSwitch and UniSec switchgear.(3) 230/300 mm pole centre distance.

Circuit-breaker VD4/R 12 VD4/R 17.5 VD4/R 24

Rated and insulation voltage kV 12 17.5 24

Withstand voltage (1 min) kV (50Hz) 28 38 50

Impulse withstand voltage kV 75 95 125

Rated frequency Hz 50-60 50-60 50-60

Rated normal current A (40 °C) 630 800 1250 630 800 1250 630 800 1250

Rated breaking capacity and short-timewithstand current (3 s)

kA

12.5 – – 12.5 – – 12.5 – –

16 16 16 16 16 16 16 16 16

20 20 20 20 20 20 20 20 20

25 25 25 – – – – – –

Making capacity kA

31.5 – – 31.5 – – 31.5 – –

40 40 40 40 40 40 40 40 40

50 50 50 50 50 50 50 50 50

63 63 63 – – – – – –

Operation sequence 0-3''-CO-15''-CO 0-3''-CO-15''-CO 0-3''-CO-15''-CO

Opening time ms 45 45 45

Arc time ms 10-15 10-15 10-15

Total interruption time ms 55-60 55-60 55-60

Closing time ms 80 80 80

Overall dimensions (fixed version)

H mm 785 785 785

L mm 317 317 317

D mm 1029/1170 (3) 1029/1170 (3) 1029/1170 (3)

Weight Fixed (1) kg 65 65 65

Withdrawable (1) (2) kg 70 70 70

Technical catalogue No. 1VCP000263 1VCP000263 1VCP000263

D

H

L

Circuit-breakers for indoor installation IEC

Page 9: catalogo general Media Tensión (abb)

9

HD4/RGas circuit-breakers with mechanical operating mechanism for secondary distribution• Tested and constructed in accordance with IEC Standards• Circuit-breaker with right-hand lateral operating mechanism• On request (up to 24 kV), application of PR521 self-supplied protection device or

REF601 (not self-supplied) IEC version • Designed for installation in unmanned substations without auxiliary power supply

(with PR521 only)• Sealed-for-life poles• Interchangeable with VD4/R circuit-breakers (up to 24 kV)• Available with or without pressure switch

(1) Increase by 20 kg with PR521 and sensors / REF601 and sensors.(2) HD4/UniAir removable version for UniAir switchgear, HD4/UniMix for UniMix switchgear or HD4/S for UniSwitch switchgear.(3) 230/300 mm pole centre distance.(4) 350 mm pole centre distance.(5) 20 kA for 1 s.

Circuit-breaker HD4/R 12 HD4/R 17 HD4/R 24 HD4/R 36

Rated and insulation voltage kV 12 17.5 24 36

Withstand voltage (1 min) kV (50Hz) 28 38 50 70

Impulse withstand voltage kV 75 95 125 170

Rated frequency Hz 50-60 50-60 50-60 50-60

Rated normal current A (40 °C) 630 800 1250 630 800 1250 630 800 1250 630 800 1250

Rated breaking capacity and short-timewithstand current (3 s)

kA

12.5 – – 12.5 – – 12.5 – – 12.5 12.5 12.5

16 16 16 16 16 16 16 16 16 16 16 16

20 (5) 20 20 20 (5) 20 20 20 20 20 – – –

25 25 25 – – – – – – – – –

Making capacity kA

31.5 – – 31.5 – – 31.5 – – 31.5 31.5 31.5

40 40 40 40 40 40 40 40 40 40 40 40

50 50 50 50 50 50 50 50 50 – – –

63 63 63 – – – – – – – – –

Operation sequence O-0.3s-CO-15s-CO

Opening time ms 45 45 45 45

Arc time ms 10-15 10-15 10-15 10-15

Total interruption time ms 55-60 55-60 55-60 55-60

Closing time ms 80 80 80 80

Overall dimensions(fixed version)

H mm 764.5 764.5 764.5 810

L mm 321 321 321 409

D mm 1049/1189 (3) 1049/1189 (3) 1049/1189 (3) 1348 (4)

Weight Fixed (1) kg 103 103 103 110

Withdrawable (1) (2) kg 108 108 108 –

Nominal gas pressure kPa 380 380 380 380

Technical catalogue No. 1VCP000028 1VCP000028 1VCP000028 1VCP000028

IEC

D

H

L

Page 10: catalogo general Media Tensión (abb)

10

Page 11: catalogo general Media Tensión (abb)

11

HD4Gas circuit-breakers with mechanical operating mechanism for primary distribution • Tested and constructed in accordance with IEC Standards• Compact dimensions• Long electrical and mechanical life• Maintenance-free poles• Sealed-for-life poles• Fixed and withdrawable versions• Gas monitoring device on request

(1) HD4 circuit-breakers are available in the withdrawable version with the following characteristics: – HD4/W 36: 36 kV; ... 2500 A; ... 31.5 kA for PowerCube 36 enclosures and UniGear ZS2 switchgear; – HD4/Z 36/40.5: 40.5 kV; ... 2500 A; ... 31.5 kA for UniGear ZS3.2 switchgear.(2) Rated current higher than 3150 A with forced ventilation.

Circuit-breaker HD4 12 HD4 17.5 HD4 24 HD4 36 (1)

Rated and insulation voltage kV 12 17.5 24 36

Withstand voltage (1 min) kV (50Hz) 28 38 50 70

Impulse withstand voltage kV 75 95 125 170

Rated frequency Hz 50-60 50-60 50-60 50-60

Utilization Fixed/UniGear/PowerCube Fixed/ZS3.2/PowerCube

Rated current (2) A (40 °C) 630-1250 1600-4000 630-1250 1600-4000 630-1250 1600-3600 630 1250 1600 2000 2500

Rated breaking capacity and rated short-timewithstand current (3 s)

kA

16 16 16 – 16 – 16 16 16 – –

– – – – 20 – 20 20 20 20 20

25 25 25 25 25 25 – 25 25 25 25

31.5 31.5 31.5 31.5 – 31.5 – 31.5 31.5 31.5 31.5

– 40 – 40 – 40 – – – – –

– 50 – 50 – – – – – – –

Making capacity kA

40 40 40 – 40 – 40 40 40 – –

– – – – 50 – 50 50 50 50 50

63 63 63 63 63 63 – 63 63 63 63

80 80 80 80 – 80 – 80 80 80 80

– 100 – 100 – 100 – – – – –

– 125 – 125 – – – – – – –

Operation sequence O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO

Opening time ms 45 45 45 45 45 45 45

Arc time ms 10-15 10-15 10-15 10-15 10-15 10-15 10-15

Total interruption time ms 55-60 55-60 55-60 55-60 55-60 55-60 55-60

Closing time ms 80 80 80 80 80 80 80

Overall dimensions (fixed version)

H mm 640 ... 655 649 ... 655 818 ... 855 712 ... 1123

L mm 493 ... 730 600 ... 730 600 ... 730 748 ... 955

D mm 495 ... 603 496 ... 603 516 ... 603 695 ... 833

Weight Fixed kg 114 ... 165 114 ... 165 119 ... 165 124 ... 190

Withdrawable kg 120 ... 230 120 ... 230 125 ... 220 280 ... 300

Nominal gas pressure kPa 380 380 380 380 ... 550

Technical catalogue No. 1VCP000004 1VCP000004 1VCP000004 1VCP000004

IEC

D

H

L

Circuit-breakers for indoor installation

Page 12: catalogo general Media Tensión (abb)

12

VD4

(1) ZS8.4 switchgear up to 1250 A and 25 kA.(2) In ABB switchgear with forced ventilation.(3) For high performances, please ask us.

Vacuum circuit-breakers with mechanical operating mechanism for primary distribution• Tested and constructed in accordance with IEC Standards• Compact dimensions• Long electrical and mechanical life• Resin poles with embedded interrupters • Sealed-for-life and maintenance-free poles• Fixed and withdrawable versions• Operating mechanisms with just a few highly reliable components• Accessories common to the whole range

Circuit-breaker VD4 12 VD4 17 VD4 24 VD4 36 VD4 40.5

Rated and insulation voltage kV 12 17.5 24 36 40.5

Withstand voltage (1 min) kV (50Hz) 28 38 50 70 85

Impulse withstand voltage kV 75 95 125 170 185

Rated frequency Hz 50-60 50-60 50-60 50-60 50-60

Utilization Fixed/UniGear/PowerCube/ZS8.4 (1) UniGear/PowerCube Fixed/UniGear/PowerCube/ZS8.4 (1) UniGear/PowerCube Fixed/UniGear/PowerCube/ZS8.4 (1) ZS3.2 ZS3.2

Rated current A (40 °C) 630 1250 1600 2000 2500 3150 4000 (2) 630 1250 1600 2000 2500 3150 4000 (2) 630 1250 1600 2000 2500 1250 1600 2000 2500 3150 (2) 1250 1600 2000 2500 3150 (2)

Rated breaking capacity and short-timewithstand current (3 s)

kA

16 16 – – – – – 16 16 – – – – – 16 16 – – – – – – – – – – – – –

20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 – – – – – – – – – – –

25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 – – – – – 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

– 40 40 40 40 40 40 – 40 40 40 40 40 40 – – – – – 40 40 40 40 40 – – – – –

– 50 50 50 50 50 50 – 50 50 50 50 50 50 – – – – – – – – – – – – – – –

Making capacity kA

40 40 – – – – – 40 40 – – – – – 40 40 – – – – – – – – – – – – –

50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 – – – – – – – – – – –

63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63

80 80 80 80 80 80 80 80 80 80 80 80 80 80 – – – – – 80 80 80 80 80 80 80 80 80 80

– 100 100 100 100 100 100 – 100 100 100 100 100 100 – – – – – 100 100 100 100 100 – – – – –

– 125 125 125 125 125 125 – 125 125 125 125 125 125 – – – – – – – – – – – – – – –

Operation sequence O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3)

Opening time ms 33 ... 60 33 ... 60 33 ... 60 40 … 60 40 … 60

Arc time ms 10 ... 15 10 ... 15 10 ... 15 10 … 15 10 … 15

Total interruption time ms 43 ... 75 43 ... 75 43 ... 75 50 … 75 50 … 75

Closing time ms 60 ... 80 60 ... 80 60 ... 80 60 … 80 60 … 80

Overall dimensions (fixed version)

Hmm 461 ... 616 599 ... 677 461 ... 616 599 ... 677 461 ... 616 1575 1575

inch 18.1 ... 24.1 23.6 ... 26.6 18.1 ... 24.1 23.6 ... 26.6 18.1 ... 24.1 62 62

Lmm 570 ... 700 23.6 ... 26.6 570 ... 700 600 ... 750 570 ... 700 895 … 1000 895

inch 22.4 ... 27.1 23.6 ... 29.5 22.4 ... 27.1 23.6 ... 29.5 22.4 ... 27 35.2 ... 39.4 32.5

Dmm 424 424 ... 459 424 424 ... 459 424 555 … 686 686

inch 16.7 16.7 ... 18 16.7 16.7 ... 18 16.7 21.8 ... 27 27

Weight

Fixedkg 80 ... 120 – 80 ... 120 – 80 ... 120 – –

lbs 178/264 – 178/264 – 176 ... 264 – –

Withdrawablekg 100 ... 150 159 ... 260 100 ... 150 159 ... 260 100 ... 150 290 … 350 290 … 350

lbs 220 ... 330 350 ... 572 220 ... 330 350 ... 572 220 ... 330 638 ... 770 638 ... 770

Technical catalogue No. 1VCP000001 DECMS231202 1VCP000001 DECMS231202 1VCP000001 DECMS 2312 03 DECMS 2312 03

Circuit-breakers for indoor installation IEC

D

H

L

Page 13: catalogo general Media Tensión (abb)

13

Circuit-breaker VD4 12 VD4 17 VD4 24 VD4 36 VD4 40.5

Rated and insulation voltage kV 12 17.5 24 36 40.5

Withstand voltage (1 min) kV (50Hz) 28 38 50 70 85

Impulse withstand voltage kV 75 95 125 170 185

Rated frequency Hz 50-60 50-60 50-60 50-60 50-60

Utilization Fixed/UniGear/PowerCube/ZS8.4 (1) UniGear/PowerCube Fixed/UniGear/PowerCube/ZS8.4 (1) UniGear/PowerCube Fixed/UniGear/PowerCube/ZS8.4 (1) ZS3.2 ZS3.2

Rated current A (40 °C) 630 1250 1600 2000 2500 3150 4000 (2) 630 1250 1600 2000 2500 3150 4000 (2) 630 1250 1600 2000 2500 1250 1600 2000 2500 3150 (2) 1250 1600 2000 2500 3150 (2)

Rated breaking capacity and short-timewithstand current (3 s)

kA

16 16 – – – – – 16 16 – – – – – 16 16 – – – – – – – – – – – – –

20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 – – – – – – – – – – –

25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 – – – – – 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

– 40 40 40 40 40 40 – 40 40 40 40 40 40 – – – – – 40 40 40 40 40 – – – – –

– 50 50 50 50 50 50 – 50 50 50 50 50 50 – – – – – – – – – – – – – – –

Making capacity kA

40 40 – – – – – 40 40 – – – – – 40 40 – – – – – – – – – – – – –

50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 – – – – – – – – – – –

63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63

80 80 80 80 80 80 80 80 80 80 80 80 80 80 – – – – – 80 80 80 80 80 80 80 80 80 80

– 100 100 100 100 100 100 – 100 100 100 100 100 100 – – – – – 100 100 100 100 100 – – – – –

– 125 125 125 125 125 125 – 125 125 125 125 125 125 – – – – – – – – – – – – – – –

Operation sequence O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3)

Opening time ms 33 ... 60 33 ... 60 33 ... 60 40 … 60 40 … 60

Arc time ms 10 ... 15 10 ... 15 10 ... 15 10 … 15 10 … 15

Total interruption time ms 43 ... 75 43 ... 75 43 ... 75 50 … 75 50 … 75

Closing time ms 60 ... 80 60 ... 80 60 ... 80 60 … 80 60 … 80

Overall dimensions (fixed version)

Hmm 461 ... 616 599 ... 677 461 ... 616 599 ... 677 461 ... 616 1575 1575

inch 18.1 ... 24.1 23.6 ... 26.6 18.1 ... 24.1 23.6 ... 26.6 18.1 ... 24.1 62 62

Lmm 570 ... 700 23.6 ... 26.6 570 ... 700 600 ... 750 570 ... 700 895 … 1000 895

inch 22.4 ... 27.1 23.6 ... 29.5 22.4 ... 27.1 23.6 ... 29.5 22.4 ... 27 35.2 ... 39.4 32.5

Dmm 424 424 ... 459 424 424 ... 459 424 555 … 686 686

inch 16.7 16.7 ... 18 16.7 16.7 ... 18 16.7 21.8 ... 27 27

Weight

Fixedkg 80 ... 120 – 80 ... 120 – 80 ... 120 – –

lbs 178/264 – 178/264 – 176 ... 264 – –

Withdrawablekg 100 ... 150 159 ... 260 100 ... 150 159 ... 260 100 ... 150 290 … 350 290 … 350

lbs 220 ... 330 350 ... 572 220 ... 330 350 ... 572 220 ... 330 638 ... 770 638 ... 770

Technical catalogue No. 1VCP000001 DECMS231202 1VCP000001 DECMS231202 1VCP000001 DECMS 2312 03 DECMS 2312 03

IEC

Page 14: catalogo general Media Tensión (abb)

14

IEC

Circuit-breaker eVD4 12 eVD4/P 12 eVD4 17 eVD4/P 17

Rated voltage kV 12 12 17.5 17.5

Rated insulation voltage kV 12 12 17.5 17.5

Withstand voltage at 50 Hz (1 min) kV 42 42 42 42

Impulse withstand voltage kV 75 75 95 95

Rated frequency Hz 50-60 50-60 50-60 50-60

Rated normal current (40 °C) A 630 - 2500 (*) 630 - 2500 (*) 630 - 2500 (*) 630 - 2500 (*)

Rated breaking capacity (rated symmetrical short-circuit current)

kA 16 - 40 16 - 40

Rated short-time withstand current (3s) kA 16 - 40 16 - 40

Making capacity kA 40 - 125 40 - 125

Sequence of operations O - 0.3 s - CO - 15 s - CO • •

Opening time ms 40 ... 60 40 ... 60

Arc time ms 10 ... 15 10 ... 15

Total breaking time ms 50 ... 75 50 ... 75

Closing time ms 50 ... 70 50 ... 70

Maximum overall dimensions

H mm 461 - 589 621 - 691 461 - 589 621 - 691

L mm 450 - 700 492 - 842 450 - 700 492 - 842

D mm 424 642 - 657 424 642 - 657

P mm (Pole centre distance) 150 - 275 150 - 275 150 - 275 150 - 275

Operating temperature °C - 25 ... + 40 - 25 ... + 40

Electromagnetic compatibility IEC: 61000; 60255 • •

Technical catalogue No. 1VCP000281 1VCP000281

D

H

L

P P

Vacuum circuit-breakers with sensors and integrated RBX 615 protection unit • Tested and constructed in accordance with IEC Standards• Mechanical actuator • Compatibility with the VD4 series, fixed and withdrawable versions• Compact dimensions, poles with embedded interrupters, sealed-for-life and

maintenance-free • Protection relay with five standard pre-configurations• Circuit-breaker and panel components fully factory-tested• Drastic reduction in cabling and risk of errors• Possibility of use in all types of plants• High environmental and electromagnetic compatibility

Circuit-breakers for indoor installation

eVD4

(*) For 2500 A please ask ABB.

Page 15: catalogo general Media Tensión (abb)

15

VmaxVacuum circuit-breakers with mechanical operating mechanism for primary distribution• Tested and constructed in accordance with IEC Standards• Compact dimensions• Long electrical and mechanical life• Sealed-for-life and maintenance-free interrupters• Fixed and withdrawable versions• Operating mechanism with just a few highly reliable components• Accessories common to the whole range

IEC

D

H

L

Circuit-breaker Vmax 12 Vmax 17

Rated and insulation voltage kV 12 17.5

Withstand voltage (1 min) kV (50Hz) 28 38

Impulse withstand voltage kV 75 95

Rated frequency Hz 50-60 50-60

Utilization Fixed/UniGear/PowerCube Fixed/UniGear/PowerCube

Rated current A (40 °C) 630 1250 630 1250

Rated breaking capacity and short-time withstand current (3 s)

kA

16 16 16 16

20 20 20 20

25 25 25 25

31.5 31.5 31.5 31.5

Making capacity kA

40 40 40 40

50 50 50 50

63 63 63 63

80 80 80 80

Operation sequence O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO

Opening time ms 33.5 ... 60 33.5 ... 60

Arc time ms 10 ... 15 10 ... 15

Total interruption time ms 43.5 ... 75 43.5 ... 75

Closing time ms 45 ... 80 45 ... 80

Overall dimensions(fixed version)

Hmm 496 531

inch 19.4 20.8

Lmm 416 416

inch 16.3 16.3

Dmm 433 433

inch 16.9 16.9

Weight

Fixedkg 77 77

lbs 171 171

Withdrawablekg 98 ... 100 98 ... 100

lbs 218...222 218...222

Technical catalogue No. 1VCP000169 1VCP000169

Page 16: catalogo general Media Tensión (abb)

16

VM1Vacuum circuit-breakers with magnetic actuator for primary distribution• Tested and constructed in accordance with IEC Standards• Operating mechanism with magnetic actuator• Compatible with the VD4 series• Compact dimensions• Control functions: circuit-breaker state, continuity of the actuator coils, capacitor

charging and watchdog• High environmental and electromagnetic compatibility• Limited power consumption• Poles with embedded interrupters, sealed-for-life and maintenance-free• Fixed and withdrawable versions

(1) Catalogue DEABB 2233 03

IEC

D

H

L

Circuit-breaker VM1 12 VM1 17 VM1 24

Rated and insulation voltage kV 12 17.5 24

Withstand voltage (1 min) kV (50Hz) 28 38 50

Impulse withstand voltage kV 75 95 125

Rated frequency Hz 50-60 50-60 50-60

Utilization Fixed/UniGear/PowerCube UniGear Fixed/UniGear/PowerCube UniGear Fixed/UniGear/PowerCube

Rated current A (40 °C) 630 1250 1600 2000 2500 3150 630 1250 1600 2000 2500 3150 630 1250 1600 2000 2500

Rated breaking capacity and short-time withstand current (3 s)

kA

16 16 – – – – 16 16 – – – – 16 16 16 16 –

20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 – – – – –

– 40 40 40 40 40 – 40 40 40 40 40 – – – – –

– – – 50 50 50 – – – – – – – – – – –

Making capacity kA

40 40 – – – – 40 40 – – – – 40 40 40 40 –

50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63

80 80 80 80 80 80 80 80 80 80 80 80 – – – – –

– 100 100 100 100 100 – 100 100 100 100 100 – – – – –

– – – 125 125 125 – – – – – – – – – – –

Operation sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3 min-CO

Opening time ms 40 ... 60 40 ... 60 40 ... 60

Arc time ms 10 ... 15 10 ... 15 10 ... 15

Total interruption time ms 50 ... 75 50 ... 75 50 ... 75

Closing time ms 60 ... 80 60 ... 80 60 ... 80

Actuator mechanical operations (cycles) No. ... 100,000 ... 100,000 ... 100,000

Interrupter mechanical operations (cycles) No. ... 30,000 ... 30,000 ... 30,000

Electrical operations at rated current (cycles) No. ... 30,000 ... 30,000 ... 30,000

Electrical operationsunder short-circuit (cycles) No. ... 100 ... 100 ... 100

Overall dimensions(fixed version)

Hmm 461 ... 616 620 461 ... 616 620 631 ... 661

inch 18.1 ... 24.1 24.4 18.1 ... 24.1 24.4 24.8 ... 26

Lmm 570 ... 700 750 570 ... 700 750 570 ... 700

inch 22.4 ... 27.1 29.5 22.4 ... 27.1 29.5 22.4 ... 27.5

Dmm 424 424 424 424 424

inch 16.7 16.7 16.7 16.7 16.7

Weight

Fixedkg 90 ... 130 – 90 ... 130 – 100 ... 140

lbs 198 ... 286 – 198 ... 286 – 220 ... 308

Withdrawablekg 110 ... 160 148 110 ... 160 148 120 ... 170

lbs 242 ... 352 325.6 242 ... 352 325.6 264 ... 374

Technical catalogue No. 1VCP000057 (1) 1VCP000057 (1) 1VCP000057

Circuit-breakers for indoor installation

Page 17: catalogo general Media Tensión (abb)

17

Circuit-breaker eVM1 12 eVM1 17

Rated and insulation voltage kV 12 17.5

Withstand voltage (1 min) kV (50Hz) 28 38

Impulse withstand voltage kV 75 95

Rated frequency Hz 50-60 50-60

Utilization Fixed / ZS1 / PowerCube Fixed / ZS1 / PowerCube

Rated current A (40 °C) 630 1250 630 1250

Rated breaking capacity and rated short-timewithstand current (3 s)

kA

16 16 16 16

20 20 20 20

25 25 25 25

31.5 31.5 31.5 31.5

Making capacity kA

40 40 40 40

50 50 50 50

63 63 63 63

80 80 80 80

Operation sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO

Opening time ms 33 33

Closing time ms 50 50

Actuator mechanical operations (cycles) No. ... 100,000 ... 100,000

Interrupter mechanical operations (cycles) No. ... 30,000 ... 30,000

Electrical operations at rated current (cycles) No. ... 30,000 ... 30,000

Consumption on stand-by W < 15 < 15

Consumption after a self-reclosing cycle W < 110 < 110

Overall dimensions (withdrawable version)

Hmm 461 461

inch 22.4 22.4

Lmm 570-700 570-700

inch 22.4-27.1 22.4-27.1

Dmm 464 464

inch 16.7 16.7

Withdrawable version weightkg 110 ... 160 110 ... 160

lbs 242...352 242...352

Technical catalogue No. 1VCP000168 1VCP000168

eVM1Vacuum circuit-breakers with magnetic actuator with integrated on-board sensors, protection and control, for primary distribution• Tested and constructed in accordance with IEC Standards• Compatibility with the VD4 series, fixed and withdrawable versions• Poles with embedded interrupters, sealed-for-life and maintenance-free• Simplification of preparation of specifications and ordering procedures• Drastic reduction of cabling and improved safety and reliability• Possibility of use in all types of plants• Control of the circuit-breaker state and watchdog function• High environmental and electromagnetic compatibility

Protections according to IEC 60255-3 and IEC 60255-8 Standards• The basic series includes: 51- overcurrent IDMT (NI, VI, EI, LI), 50 - overcurrent DT1, 50 - overcurrent DT2, 51N - earth fault IDMT, 50N - earth fault DT1, 50N -

earth fault DT2.• The complete series includes: 51MS - motor starting protection, 66 - number of start-ups, 51LR - blocked rotor, 49 - thermal overload, 46 - unbalanced load.

IEC

D

H

L

Page 18: catalogo general Media Tensión (abb)

18

ADVAC

D

H

L

Circuit-breakers for indoor installation ANSI

Vacuum circuit-breakers with mechanical actuator for primary distribution• Tested and constructed in accordance with ANSI Standards• Long electrical and mechanical life• Maintenance-free poles • Sealed-for-life poles • Fixed, withdrawable and retrofitting versions

Circuit-breaker ADVAC ADVAC ADVAC

Rated voltage kV 4.76 8.25 15

Withstand voltage at industrial frequency kV 19 36 36

Impulse withstand voltage (BIL) kV 60 95 95

Rated frequency Hz 50-60 50-60 50-60

Utilization kit, L-frame, modules, switchgear kit, L-frame, modules, switchgear kit, L-frame, modules, switchgear

Rated normal current A 1200 2000 3000 1200 2000 3000 1200 2000 3000

Rated breaking capacity kA

- - - - - - 20 20 20

25 25 25 - - - 25 25 25

31.5 31.5 31.5 - - - 31.5 31.5 31.5

40 40 40 40 40 40 40 40 40

50 50 50 - - - 50 50 50

Making capacity (crest current)

kA 1200 2000 3000 1200 2000 3000 1200 2000 3000

20 - - - - - - 52 52 52

25 65 65 65 - - - 65 65 65

31.5 82 82 82 - - - 82 82 82

40 104 104 104 104 104 104 104 104 104

50 130 130 130 - - - 130 130 130

Operation sequence C-O-15s-C-O C-O-15s-C-O C-O-15s-C-O

Opening time ms 35-40 35-40 35-40

Arc time ms <15 <15 <15

Total interruption time ms <55 <55 <55

Overall dimensions

Withdrawable Fixed Withdrawable Fixed Withdrawable Fixed

H mm 701 651 701 651 701 651

inch 27.62 25.65 27.62 25.65 27.62 25.65

Lmm 818 772 818 772 818 772

inch 32.20 30.39 32.20 30.39 32.20 30.39

Dmm 905 425 905 425 905 425

inch 35.65 16.75 35.65 16.75 35.65 16.75

Weight

Fixedkg 150-168 150-168 150-168

lbs 330-370 330-370 330-370

Withdrawablekg 168-250 168-250 168-250

lbs 370-550 370-550 370-550

Page 19: catalogo general Media Tensión (abb)

19

AMVACVacuum circuit-breakers with magnetic actuator for primary distribution• Tested and constructed in accordance with ANSI Standards• Long electrical and mechanical life• Maintenance-free poles • Sealed-for-life poles • Fixed and withdrawable versions (Advance/Safegear and floor-mounted) (1)

ANSI

D

H

L

Circuit-breaker AMVAC AMVAC AMVAC

Rated voltage kV 4.76 15 27

Withstand voltage at industrial frequency kV 19 36 60

Impulse withstand voltage (BIL) kV 60 95 125

Rated frequency Hz 50-60 50-60 50-60

Utilizationkit, L-frame, modules,

abbreviated swgrkit, L-frame, modules,

abbreviated swgrL-frame, modules

Rated normal current A 1200 2000 3000 1200 2000 3000 1200 2000 3000

Rated breaking capacity kA

- - - 20 20 20 16 16 -

25 25 25 25 25 25 25 25 -

31.5 31.5 31.5 31.5 31.5 31.5 - - -

40 40 40 40 40 40 - - -

50 50 50 50 50 50 - - -

Making capacity (crest current)

kA 1200 2000 3000 1200 2000 3000 1200 2000 3000

16 - - - - - - 42 42 -

20 - - - 52 52 52 - - -

25 65 65 65 65 65 65 65 65 -

31.5 82 82 82 82 82 82 - - -

40 104 104 104 104 104 104 - - -

50 130 130 130 130 130 130 - - -

Operation sequence C-O-15s-C-O C-O-15s-C-O C-O-15s-C-O

Closing time ms 60 60 60

Trip time ms 45 45 45

Overall dimensions

Withdrawable Fixed Withdrawable Fixed Withdrawable Fixed

H mm 701 651 701 651 701 651

inch 27.62 25.65 27.62 25.65 27.62 25.65

Lmm 818 772 818 772 818 772

inch 32.20 30.39 32.20 30.39 32.20 30.39

Dmm 905 425 905 425 905 425

inch 35.65 16.75 35.65 16.75 35.65 16.75

Weight

Fixedkg 141-152 141-152 141-152

lbs 310-335 310-335 310-335

Withdrawablekg 182-193 182-193 182-193

lbs 400-425 400-425 400-425

(1) Including the fixing frame (fixed part).

Page 20: catalogo general Media Tensión (abb)

20

IEC

Is-LimiterCartridge current limiters• Reduce the cost of distribution substations• Solve the short-circuit problems in new plants or in the case of enlargement• Are the optimal solution for interconnection of switchgear with electrical

distribution plants• In many cases are the only technical solution possible• Widely experimented and applied successfully in thousands of plants• Are found throughout the world• Never allow the peak short-circuit current to be reached• Limit the onset of the short-circuit current right from the first moments

Limiter Fixed Is - Limiter

Rated voltage kV 12 12 17.5 17.5 24 36

Rated current A 1250/2000 2500/3000/4000 (1) 1250/2000 2500/3000/4000 (1) 1250/1600/2000/3000 (1) 1250/2000/2500 (1)

Test voltage(50/60 Hz / 1 min)

kV 28 28 38 38 50 75

Impulse withstand voltage

kV 75 75 95 95 125 200

Rated short-circuit/opening current

kARMS 210 210 210 210 140 140

IS-Limiter Insert-holder kg 23/27.5 65 23/27.5 65 27/31.5/33 60

IS-Limiter Insert kg 12/12.5 15.5 14/14.5 17.5 19/19.5/24 42

Insert-holder complete with insert

H mm 180 180 180 180 180 240

L mm 637/651 951 637/651 951 740/754/837 1016

D mm 503/510 509 503/510 509 553/560/560 695

(1) With cooling fan.For higher currents, connection in parallel of several insert-holders with relative inserts is carried out.

Limiter Withdrawable Is - Limiter

Rated voltage kV 12 17.5 24

Rated current A 1250/2000/2500/3000 (1)/4000 (1) 1250/2000/3000 (1)/4000 (1) 1250/2000/3000 (1)/4000 (1)

Test voltage (50/60 Hz / 1 min)

kV 28 38 50

Impulse withstand voltage

kV 75 95 125

Dimensions

H mm 2200 2200 2325

L mm 1000 1000 1000

D mm 1300 1300 1500

Weight including truck kg 1200 1200 1300

D

H

L

Cartridge current limiters

D

H

L

Page 21: catalogo general Media Tensión (abb)

21

GSR II FSK II

GSR II FSK II

GSR II: Single-pole circuit-breakers for indoor installationFSK II: Two-pole circuit-breakers for outdoor installation• Vacuum interruption technology• Magnetic actuator• Sealed-for-life poles• Insulator made of silicone rubber (FSK II)• EC 694 - EN 51052 -1 Standards• Available in RFI (Italian Railway Network) approved version

Circuit-breaker GSRII - 5954 FSKII - 1020 FSKII - 1025

Rated and insulation voltage kV 27.5 27.5 27.5

Withstand voltage at industrial frequency (50 Hz/1 min)

- phase-earth kV 95 95 105

- between open contacts kV 110 95 110

Impulse withstand voltage (1,2/50 µs)

- phase-earth kV 200 200 250

- between open contacts kV 250 200 250

Rated frequency Hz 50 50 50

Rated current A 2500 1250-2000 2500

Rated breaking capacity kA 25 25 25

Rated short-time withstand current (3 s)

kA 25 25 25

Making capacity kA 63 63 63

Rated withstand peak current kA 63 63 63

Operation sequenceO - 0.3s - CO - 3min CO O - 0.3s - CO - 3min CO O - 0.3s - CO - 3min CO

– CO - 10s - CO CO - 10s - CO

Opening time ms ≤ 45 ≤ 40 ≤ 40

Closing time ms ≤ 60 ≤ 60 ≤ 60

Technical catalogue No. 1VSR0006B1851 1VSR0006B1851 1VSR0006B1851

Apparatus for railway traction IEC

Page 22: catalogo general Media Tensión (abb)

22

Page 23: catalogo general Media Tensión (abb)

23

PowerCube

(1) With forced ventilation.(2) For 36 kV, please contact us.(3) Except for PBE – PBM1 - PRE – PRM1 - PB6 and PR6.(4) Signal source to be provided by the customer.(5) Main circuits; for earthing circuits please see the technical catalogue.

Pre-assembled modules for medium voltage switchgear• Tested and constructed in accordance with IEC Standards• Modular structure studied to facilitate construction of switchgear• Fitted with mechanical and electromechanical locks• Metal shutters with optional fail safe device (prevention of manual opening)• Circuit-breaker/contactor racking-in/out with the door closed• Use with gas circuit-breakers, vacuum circuit-breakers and contactors• Version with earthing switch with making capacity• Earthing switch with making capacity fitted with interlocks • Bottom compartment can be fitted with measurement truck with VTs protected

by fuses (3)

• Voltage signalling lamps (4)

Module Incoming, outgoing and bus-tie units Riser, measurement and direct busbar incoming units

PB1M PB1E

PB2M PB2E

PB3M PB3E

PB4M PB4E

PB5M PB5E

PB 6PR1M PR1E

PR2MPR2E

PR3MPR3E

PR4MPR4E

PR5MPR5E

PR 6

Module widthmm 600 750 1000 750 1000 1000 600 750 1000 750 1000 1000

inch 23.6 29.5 39.4 29.5 39.4 39.4 23.6 29.5 39.4 29.5 39.4 39.4

Rated voltage kV

12 12 12 – – – 12 12 12 – – –

17.5 17.5 17.5 – – – 17.5 17.5 17.5 – – –

– – – 24 24 – – – – 24 24 –

– – – – – 36 (2) – – – – – 36 (2)

Test voltage at industrial frequency

kV

28 28 28 – – – 28 28 28 – – –

38 38 38 – – – 38 38 38 – – –

– – – 50 50 – – – – 50 50 –

– – – – – 70 – – – – – 70

Impulse withstand voltage

kV

75 75 75 – – – 75 75 75 – – –

95 95 95 – – – 95 95 95 – – –

– – – 125 125 – – – – 125 125 –

– – – – – 170 – – – – – 170

Rated short-time withstand current (5)

kA (3s)

25 25 25 25 25 25 25 25 25 25 25 25

31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5 – – 31.5

– 40 40 – – – – 40 40 – – –

kA (1s) – 50 50 – – – – 50 50 – – –

Peak current kA

63 63 63 63 63 63 63 63 63 63 63 63

79 79 79 – – 79 79 79 79 – – 79

– 100 100 – – – – 100 100 – – –

– 125 125 – – – – 125 125 – – –

Rated current A

630 630 – 630 – 630

N. A.

1250 1250 – 1250 – 1250

– 1600 – – 1600 1600

2000 – – 2000 2000

– – 2500 – 2500 (1) 2500 (1)

– – 3150 – – –

– – 3600 (1) – – –

– – 4000 (1) – – –

Technical catalogue No. 1VCP000091 (2) 1VCP000091 (2)

Enclosures and fixed parts IEC

Page 24: catalogo general Media Tensión (abb)

24

Enclosures and fixed parts

PowerCubeFixed parts• Tested and constructed in accordance with IEC Standards• Studied for replacement of fixed with withdrawable circuit-breakers and for

retrofitting and upgrading obsolete switchgear to the new standards• Compact dimensions and limited weights• Standardised construction• Possibility of installation both in the raised position and on the floor• Competitive solutions for economical switchgear

(1) The following fixed parts are provided for VD4 circuit-breakers: for 12 and 17.5 kV: CBF1 up to 1250 A, CBF2 up to 2000 A; for 24 kV: CBF4 up to 1250 A.(2) Up to 12 kV - 400 A.

Fixed part PB1/F PB2/F PB4/F

Panel width mm 600 750 750

Contact diameter mm 35 35 79 35

Rated voltage kV 12 17.5 12 17.5 24

Rated insulation voltage kV 12 17.5 12 17.5 24

Withstand voltage (1 min) kV (50Hz) 28 38 28 38 50

Impulse withstand voltage kV 75 95 75 95 125

Rated frequency Hz 50-60 50-60 50-60

Rated current A (40 °C) 630-1250 630-1250 1600-2000 630-1250

Rated short-time withstand current 3 s. kA 31.5 31.5 25

Overall dimensions (excluding the monoblocs)

H mm 1106 1106 1236

L mm 596 746 746

D mm 1061 1061 1338

Weight kg 64 87 88

Compatible circuit-breakers and contactors

HD4 • • •

VD4 (1) • • •

V-Contact (2) • – –

Technical catalogue No. 1VCP00253 1VCP00253 1VCP00253

H

DL

IEC

Page 25: catalogo general Media Tensión (abb)

25

Fixed part L-Frame

Ratings kV 5-15

Options Standard, Roll on the floor

Certification UL, CSA

Short circuit rating kA36

58

Continuous current A 1200, 2000, 3000

Bushings Polyester glass, Porcelain

Shutters types Ground Metal, Non-Metallic

Dimensions

A 1200 2000 3000

Hmm 914 1009 1009

inch 36 39.75 39.75

Lmm 876 876 876

inch 34.5 34.5 34.5

Dmm 1120 1120 1130

inch 44.12 44.12 44.5

ANSI

L-Frame• Advance Design OEM Frames & Enclosures • Manufactured to meet current medium voltage industry needs• Available for efficient assembly or individual part kits• Manufactured and assembled in ISO certified factories• Designed to provide efficient interface of ADVAC or AMVAC circuit-breakers• Intelligent design, rugged frame, and durable components provide high quality

finished assembly

H

DL

Page 26: catalogo general Media Tensión (abb)

26

Enclosures and fixed parts ANSI

Circuit-breaker modules• Advance Design OEM Frames & Enclosures • 38” High compartments• Modular construction allows for flexibility• 2000 and 3000 A include frontal ventilation system• 20, 25, 31.5 kA breakers compatible with 38 kA module• 40, 50 kA breakers compatible with 50 kA module

H

DL

Unit CB Module CB Module

Ratings kV 5-15 27

Options Standard, Roll on the floor Drawout

Certification A 1200, 2000, 3000 1200, 2000

Short circuit rating kA38 16

50 25

Continuous current 1200 2000 3000 1200

Bushings Polyester glass, Porcelain Porcelain

Shutter types Ground Metal, Non-Metallic Non-Metallic

Dimensions

A 1200 2000 3000 1200, 2000

H mm 878 965 965 965

inch 34.56 38 38 38

L mm 914 914 914 914

inch 36 36 36 36

D mm 987 987 987 987

inch 38.85 38.85 38.85 38.85

Page 27: catalogo general Media Tensión (abb)

27

ANSI

Potential transformer modules• Advance Design OEM Frames & Enclosures • 19” High compartments• Modular construction allows for flexibility• Four transformer arrangements• Include drawout trays and racking system

Unit Transformer module Transformer module

Ratings kV 5 15

Options Drawout Drawout

Transformer arrangements Delta, Wye, L-G, L-L Delta, Wye, L-G, L-L

Connections Cable, bus Cable, bus

Insulation Polyester glass, porcelain Porcelain

Continuous current A 1200, 2000, 3000 1200, 2000, 3000

Dimensions

Hmm 437 437

inch 17.21 17.21

Lmm 914 914

inch 36 36

Dmm 987 987

inch 38.85 38.85

CPTs, fuses, compartment doors are not included.

H

DL

Page 28: catalogo general Media Tensión (abb)

28

Enclosures and fixed parts ANSI

Drawout fuse modules• Advance Design OEM Frames & Enclosures • 38” High compartments• Modular construction allow for flexibility• Include basic stackable module w/ guide rails and primary connections Installed• Include drawout trays with primary contacts, fuse clips, mounting provisions, and

hardware for fuses

Unit Fuse module

Ratings kV 5-15

Connections 3-Phase L-L L-G

Number of fuses 3 2 1

Insulation Polyester glass, porcelain Polyester glass, porcelain Polyester glass, porcelain

Clip centers 9,12,15 9,12,15 9,12,15

Ferrule diameter 2.3 2.3 2.3

Dimensions

Hmm 965 965 965

inch 38 38 38

Lmm 914 914 914

inch 36 36 36

Dmm 987 987 987

inch 38.85 38.85 38.85

Fuses, secondary breakers and compartment door are not included.

H

DL

Page 29: catalogo general Media Tensión (abb)

29

ANSI

Low voltage compartment• Advance Design OEM Frames & Enclosures • 19”, 38”, 57” High compartments• Modular construction allows for flexibility• Includes side mounted grommets for control wiring.• Open bottom for access to low voltage mounting locations

Unit Low voltage compartment

Ratings kV 5-15

Sizemm 433 965 1448

inch 19 38 57

Applications (mounted over) Circuit-breaker, CPT, fuse, aux. Circuit-breaker, CPT, fuse, aux. Circuit-breaker, CPT, fuse, aux.

Dimensions

Hmm 433 965 1448

inch 19 38 57

Lmm 914 914 914

inch 36 36 36

Dmm 559 559 559

inch 22 22 22

Compartment doors are not included.

H

DL

Page 30: catalogo general Media Tensión (abb)

30

Enclosures and fixed parts ANSI

Modules for power transformer control• Advance Design OEM Frames & Enclosures • 38” High compartments• Available for 5, 10, 15 kVA transformers• Includes basic stackable module w/ guide rails and primary connections installed• Includes drawout trays with primary contacts, fuse clips, mounting provisions,

and hardware. Trays include primary and secondary contacts, fuse clips, fuse boots, and mounting hardware

H

DL

Unit Transformer module

CPT kVA 5, 10, 15

Connections Cable, bus

Insulation Polyester glass

Dimensions

H mm 965

inch 38

L mm 914

inch 36

D mm 481

inch 18.92

CPTs, fuses, secondary breakers and compartment doors are not included.

Page 31: catalogo general Media Tensión (abb)

31

Page 32: catalogo general Media Tensión (abb)

32

Gas insulated switch-disconnectors• Designed and constructed in conformity with IEC Standards• Suitable for installation in secondary distribution switchgear• Use of SF6 gas as quenching and insulation medium• Housing made of stainless steel• Sealed type apparatus, conforming with CEI EN 60694 Standards• Metal segregation between busbar and feeder compartments

(1) For other values, contact ABB. (2) 25 kA contact ABB.

SHS2

Type

Switch- disconnector IEC 60265-1

Isolator

IEC 62271-102

Earthing switch

IEC 62271-102

Line

Earthing switch

Line

Earthing switch

(SHS2 ES) Unit without fuses

Unit withfuses

Unit without fuses

Unit with fuses

Rated voltage kV 24 – – 24 – – –

Rated uninterrupted current (40 °C) A 400-630 – – 400-630 – – –

Frequency Hz 50/60 – – 50/60 – – –

Rated short-circuit making capacity

- Without spaced earthing switch kAp 31.5-40-50 31.5-40-50 N.O. – – N.O. N.O.

- With spaced earthing switch (1) kAp 31.5-40-50 – 2,5 31.5-40-50 – – –

Rated short-time withstand current - 1s (1) kA

12.5-16-20-25 (2)

12.5-16-20-25 (2) 1

12.5-16-20-25 (2) – 1

12.5-16-20-25 (2)

Rated breaking capacity

- Mainly active load service A 400-630 – – – – – –

- No-load transformer service A 4...16 – – – – – –

- No-load line service A 25 – – – – – –

- No-load cable service A 50 – – – – – –

- Ring circuit service A 400 – – – – – –

Operating mechanism T1-T1M-T2 T1-T1M-T2 T2 T3 T3 T3 T4

Test parameters for making and breaking capacity and for short-circuit making capacity (rms) (IEC 60265-1)

Test duties 1-2-3-4-

5-6-7– – – – – –

Electrical life E3 E1 E1 – E0-E1 E0 E0-E1

Test of maximum overtemperature under rated load (to Standards)

°C IEC 60694 – – IEC 60694 – – –

Mechanical life M1 M1 M1

Lightning withstand voltage (BIL 1.2/50 µs) (BIL 1.2/50 µs) (BIL 1.2/50 µs)

- Phase-Phase towards earth kVp 125 125 125

- Between open contacts kVp 145 145 145

Withstand voltage at industrial frequency

- Phase-Phase towards earth (rms) kV 1min 50 50 50

- Between open contacts (rms) kV 1min 60 60 60

Overall dimensions (basic version)

H mm 652 652 652

L mm 495 495 495

D mm 938 938 938

Technical catalogue No. 1VCP000046 1VCP000046 1VCP000046

H

DL

Switch-disconnectors IEC

Page 33: catalogo general Media Tensión (abb)

33

AirswitchAir insulated switch-disconnectors• Tested and constructed in accordance with IEC Standards • AM – AR – AS Series for installation in secondary distribution switchgear• GS – IMC Series for installation directly on the wall without supports or counter

frames • Sturdy structure, isolators with finning with large exhaust lines • Conforming to the DY 513 -518 – 519 (Enel) prescriptions• Suitable for building units conforming to the DY 402 – 403 – 404 – 405 – 408

(Enel) prescriptions

(1) May vary according to the version.

Switch-disconnector AM AR-AS

Switch-disconnector • –

Insulation disconnector – •

Switchgear version • •

Wall version – –

Rated voltage kV 24 24

Withstand voltage to earth and between phases kV 50 (50-60 Hz/1min) 50 (50-60 Hz/1min)

Withstand voltage between open contacts kV 60 (50-60 Hz/1min) 60 (50-60 Hz/1min)

Impulse withstand voltage to earth and between phases kV 125 125

Impulse withstand voltage between open contacts kV 145 145

Rated frequency Hz 50-60 50-60

Rated normal current A (40 °C) 400-630 400/630/800/1250

Rated short-time withstand current (1 s) kA 12.5-16 12.5-16-20-25

Rated short-circuit making capacity kAp 31.5-40 –

Rated breaking capacity

- Mainly active load service A 400/630 –

- No-load transformer service A 4 ... 16 –

- No-load line service A 25 –

- No-load cable service A 25 –

- Ring circuit service A 400/630 –

Overall dimensions (1)

(basic version)

H mm 710 745

L mm 692 692

D mm 1356 1346

Technical catalogue No. 1VCP000043 1VCP000043

H

DL

IEC

Page 34: catalogo general Media Tensión (abb)

34

NAL

NALF

Switch-disconnectors

NAL - NALFAir insulated switch-disconnectors• Tested and constructed in accordance with IEC Standards • Suitable for installation in switchgear and in distribution substations • Sturdy and simple structure which only requires minimum maintenance • Spring operating mechanism • Can be combined with protection fuses and with trip device

Switch-disconnector NAL/NALF 12 NAL/NALF 17 NAL/NALF 24 NAL/NALF 36

Switch-disconnector • • • •

Insulation disconnector • • • •

Rated voltage 12 17.5 24 36

Withstand voltage to earth and between phases kV 50 Hz 1 min 42 45 55 80

Withstand voltage between open contacts kV 48 60 70 88

Impulse withstand voltage to earth and between phases kV 75 95 125 170

Impulse withstand voltage between open contacts kV 85 110 145 195

Rated frequency Hz 50-60 50-60 50-60 50-60

Rated normal current A (40 °C) 400-630-1250 400-630-1250 400-630-1250 400-630-1000

Rated short-time withstand current kA 31.5 (1s) - 20 (3 s) 31.5 (1s) 31.5 (1s) - 16 (3 s) 25 (2s)

Rated short-circuit making capacity kA 67 50 50 50

Rated breaking capacity

- Mainly active load service A 400-630-1250 400-630-1250 400-630-1250 630-800

- Mainly capacitive load service A 16 16 16 16

- Mainly inductive load service A 150 45 80 50

Overall dimensions (basic version)

H mm 428 577 577 745

L mm 412 452 528 928

D mm 362 418 418 675

Technical catalogue No. 1YMR602160 1YMR602160 1YMR602160 1YMR602160

H

DL

IEC

Page 35: catalogo general Media Tensión (abb)

35

VersaRupter MV Indoor Switch• Tested and constructed in accordance with ANSI Standards• Long Electrical and mechanical life• 500,000 switches installed in over 50 countries worldwide• Offered in both Snap Action (K-mech) and Stored energy (A-mech)• 100% Production Testing• ISO-9001

Switch-disconnector VersaRupter

Rated max voltages kV 8.25 15.00 15.00 (*) 15.50 (*) 17.00 27.00 38.00

Continuous and loadbreak current A

200 (*) 200 (*) - - 200 200 -

600 (*) 600 (*) 600 (*) 600 (*) 600 600 600

- - - - - - 800

1200 1200 1200 (*) 1200 (*) 1200 1200 -

Rated BIL kV 75 95 95 110 110 125 150

Momentary rating K-mech (RMS kA) A-Mech (Asym kA) 40 40 61 61 40 40 40

Fault closing rating K-mech (RMS kA) or A-Mech (Asym kA) 40 40 61 61 40 40 30

Electrical control options

Remote shunt trip

Auxiliary switch available

Fuse auxiliary switch

Operating Handles

Side direct drive

Front shaft drive - Type HE

Front chain drive

Interlocks

- Mechanical

- Key

Grounding switch - Type E

Ground switch interlock with VersaRupter

Fuse options

Fuse base available

Mechanical fuse tripping

Overall dimensions

Hmm 576 600 614 614 600 600 870

inch 22.68 23.62 24.17 24.17 23.62 23.62 34.25

Lmm 576 616 746 746 746 826 1184

inch 22.68 24.25 29.37 29.37 29.37 32.52 46.61

Dmm 394 511 547 547 511 511 850

inch 15.51 20.12 21.55 21.55 20.12 20.12 33.46

Weight kg 32 34 50 50 42 43 100

lbs 71 75 110 110 93 95 220

VERSARUPTER

ANSI

DL

H

(*) The bolded values in bold are UL recognized when used with chain drive handles and no motor operator. Smart style codes for UL recognized designs end with "U". Smart style codes for non-UL designs end with "N".

Snap action actuator - K-Mechanism Stored energy actuator - A-Mechanism

Page 36: catalogo general Media Tensión (abb)

36

Switch-disconnectors

OJONAir insulated switch-disconnectors for indoor installation• Tested and constructed according to IEC Standards• High short-circuit capacity • Versatile operating mechanisms for various applications• Availability of safety interlocks• Possibility of connections with aluminium busbars• Compact dimensions• Silver-plated contacts• Die-cast resin insulators • Double blade contacts

Switch-disconnector OJON 1 OJON 3 OJON 12 OJON 24

Rated voltage kV 1 3,6 12 24

Impulse withstand voltage between open contacts kV 23 46 85 145

Impulse withstand voltage to earth and between phases kV 20 40 75 125

Withstand voltage between open contacts kV 12 12 32 60

Withstand voltage to earth and between phases kV 10 10 28 50

Rated frequency Hz 50-60 50-60 50-60 50-60

Rated normal current A 1000-1600 2500-4000 630…4000 630…4000

Rated short-time withstand current (1s) kA 50-80 90 31.5…60 20…60

Rated short-circuit making capacity kA 100-120 150 80…150 50…150

Technical catalogue No. OJON 4GB

IEC

Page 37: catalogo general Media Tensión (abb)

37

OWIIAir insulated switch-disconnectors for indoor installation• Tested and constructed in accordance with IEC Standards• Long life and great reliability • Compact dimensions• Easy-to-use and low maintenance

Switch-disconnector OWII

Rated voltage kV 7.2...36

Rated current A 630...1600

Rated short-time withstand current kA 80/31.5

Operating mechanisms

• manual type NRWO4/..-3 or NR3 or NRK

• pneumatic type NP9

• electrical type UEMC40A

IEC

ADNNAir insulated switch-disconnectors for indoor installation• Tested and constructed in accordance with ANSI Standards • Can be equipped with ADJ type earthing switch• Very simple and reliable construction• Limited dimensions

Switch-disconnector ADNN

Rated voltage kV 12 - 24 - 36 - 72.5

Rated current A 1250 - 2500

Rated short-time withstand current kA 160/65

Operating mechanisms

• manual •

• with motor type UEMC40A

Page 38: catalogo general Media Tensión (abb)

38

SECTOSGas insulated switch-disconnectors for outdoor installation- NXB with two positions (ON-OFF)- NXBD with three positions (ON-OFF-EARTH)• Tested and constructed according to IEC / ANSI / GB Standards• Adaptable to a wide range of installation systems • Simple adaptation from manual system to fully automated system• Versatile connection terminals and wide range of accessories• Limited weights• High quality insulating materials • All-steel enclosure of moving parts • High level of operating safety

Switch-disconnector SECTOS 12 SECTOS 24

Rated voltage kV 12 24

Impulse withstand voltage between open contacts kV 85 145

Impulse withstand voltage to earth and between phases kV 75 125

Withstand voltage between open contacts kV 32 60

Withstand voltage to earth and between phases kV 28 50

Rated frequency Hz 50-60 50-60

Rated normal current A 630 630

Rated current with mainly active load A 630 630

Breaking capacity for overhead lines A 50 50

Breaking capacity for cables A 50 50

Breaking capacity to earth A 50 50

Breaking capacity for cables two to earth fault A 28 28

Breaking capacity for no-load transformers A 6,3 6,3

Breaking capacity for capacitors (single bank) A 160 160

Rated short-time withstand current (3s) kA 20 20

Rated peak withstand current kA 50 50

Rated short-circuit making capacity kA 50 50

Operations at the rated current (CO) No. 100 100

Closing operations

- main contacts 50 kA (CL E2) No. 3 3

- main contacts 31.5 kA (CL E3) No. 10 10

- earthing contacts 50 kA (CL E2) No. 3 3

- earthing contacts 31.5 kA (CL E3) No. 5 5

Technical catalogue No. CNXEC – NXB EN/01/200/T-2004/01

Switch-disconnectors IEC/ANSI/GB

Page 39: catalogo general Media Tensión (abb)

39

NPSAir insulated pole switch-disconnectors for outdoor installation • Tested and constructed according to IEC Standards• Modular and adaptable to all installation systems • Simple adaptation from manual system with remote control • Wide range of accessories• High quality insulating materials • Limited weights and simple construction• Limited number of components• High level of operating safety

Switch-disconnectorNPS

24 A2NPS

24 A2_J2NPS

24 B1_J2NPS

36 A2

Rated voltage kV 24 24 24 36

Impulse withstand voltage between open contacts kV 145 165 145 220

Impulse withstand voltage to earth and between phases kV 125 150 125 200

Withstand voltage under very humid conditions

- between open contacts kV 75 75 75 88

- to earth and between phases kV 55 55 55 80

Minimum distance between phases mm 310 350 260 350

Minimum insulation distance mm 200 230 200 -

Rated frequency Hz 50-60 50-60 50-60 50-60

Rated normal current A 630 630 630 630

Breaking capacity with mainly active load (100 opening-closing operations)

- 12 kV A 40 40 40 -

- 15 kV A 32 32 32 -

- 24 kV A 25 25 25 16

- 36 kV A - - - 16

Breaking capacity for cables and lines (20 opening-closing operations)

A 15 15 15 10

Rated short-time withstand current kA (1s) 20 20 16 21

Rated short-time withstand current kA (3s) 16 16 10 16

Rated peak withstand current kA 50 50 40 52

Rated short-circuit making capacity (7 closing operations)

kA 5 5 5 -

Mechanical life (operations) No. 2000 2000 2000 2000

Maximum admissible ice thickness mm 5 - - -

Ambient temperature °C -40 … +40 -40 … +40 -40 … +40 -40 … +40

Technical catalogue No. NPS 5GB

IEC

Page 40: catalogo general Media Tensión (abb)

40

Switch-disconnectors

ICX-LBU NCX-EUSwitch-disconnectors for overhead lines• Tested and constructed in accordance with ANSI Standards • Use for outdoor installation • Suitable for overhead line isolation and protection • Visible isolation of the lines• Use in circuits with rated voltage from 15 to 38 kV

Model Description Application Options

ICX

Switch-disconnector for outdoor installation for overhead lines with overcurrent protection

Visible isolation Insulators made of silicone rubber (110-180 kV BIL) or of polymer resin (110-125 kV BIL)

Replaceable fuse cartridge Operation and maintenance Steel seats

15-38 kV; up to 16 kA –Can be combined with overvoltage surge arrestors

LBU

Switch-disconnector for outdoor installation

Visible isolation Insulators made of silicone rubber (110-180 kV BIL) or of polymer resin (110-125 kV BIL)

Complete with arcing chamber Overcurrent protection of capacitor banksCan be combined with overvoltage surge arrestors

15-27 kV; up to 16 kA Operation of no-load transformers Insulators made of polymer resin (110-125 kV BIL)

NCX

Disconnector for outdoor installation for overhead lines with overcurrent protection

Visible isolation Operation and maintenance

Disconnector for outdoor installation for overhead lines with overcurrent protection

15-38 kV; up to 20 kA Fuse intervention indicatorCan be combined with overvoltage surge arrestors

EUDisconnector for outdoor installation with porcelain chamber

Suitable for retrofitting and where higher guarantees of safety are required

ANSI

Page 41: catalogo general Media Tensión (abb)

41

IEC

CEF - CMFCEF fuses for indoor and outdoor installation for transformer protection• Low value of the minimum trip current • Low dissipated power • Low arc voltage • High breaking capacity • High current limitation • Available according to IEC and BS Standards

CMF fuses for indoor installation for motor protection• High rated currents in a single element • Tests in conformity with the IEC 644 Standard, which guarantees high resistance

to overcurrents due to motor start-ups • Low value of the minimum trip current • Low power losses • Low arc voltage • High breaking capacity and high current limiting capacity

CEF and CMF fuses are available with Temperature Control Unit (TCU) as an option.

Technical characteristics and dimensions of CEF type fuses

UN IN e D I1 I3 PN Ro

kV A mm mm kA A W mΩ

3.6/7.2

6 192/292 65 50 35 26 489

10 192/292 65 50 55 16 120

16 192/292 65 50 55 26 60.2

25 192/292 65 50 72 24 30.1

40 192/292 65 50 100 30 15.3

50 192/292 65 50 190 35 10.4

63 192/292 65 50 190 40 7.8

80 192/292 87 50 250 52 6.2

100 192/292 87 50 275 57 4.4

125 292/367 87 50 375 76 3.5

160 292/367 87 50 480 101 2.6200 292/367 87 50 650 107 1.7

12

6 292/442 65 63 35 41 735

10 292/442 65 63 55 33 180

16 292/442 65 63 55 32 105

25 292/442 65 63 77 47 52.6

40 292/442 65 63 105 52 23.0

50 292/442 65 63 190 70 17.9

63 292/442 65 63 190 78 13.4

80 292/442 87 63 250 82 9.2

100 292/442 87 63 275 84 6.6

125 442/537 87 50/63 375 125 5.3

160 442/537 87 50/63 480 170 3.9200 442/537 87 50 650 174 2.7

17.5

6 292/367/442 65 20 35 54 880

10 292/367/442 65 20 55 41 271

16 292/367/442 65 20 55 67 135

25 292/367/442 65 25 72 64 67.7

40 292/367/442 87 25 100 80 34.5

50 292/367/442 87 25 210 90 23.1

63 292/367/442 87 25 210 100 17.3

80 442/537 87 25 250 124 13.8

100 442/537 87 25 275 136 9.9125 442/537 87 25 375 175 7.9

Fuses IEC

Page 42: catalogo general Media Tensión (abb)

42

e

CEF-CMFABB

Technical characteristics and dimensions of CMF type fuses

Caption(1) K Coefficient corresponds to the average current value, conforming to the IEC 644 Standard.I1 = maximum short-circuit current for which the cartridge has been tested I3 = minimum trip currentPN = dissipated power at the rated currentRo = resistance at ambient temperature

UN IN e D I1 I3 PN Ro

kV A mm mm kA A W mΩ

24

6 442 65 63 35 91 1370

10 442 65 63 55 62 361

16 442 65 63 55 72 181

20 442 65 63 82 61 120.3

25 442 65 63 72 79 90.2

31.5 442 65 63 82 98 72.2

40 442 65 63 110 106 46.0

50 442 87 63 210 130 30.7

63 442 87 63 210 147 23.0

80 442/537 87 63 250 165 18.4

100 442/537 87 63 300 186 13.2

125 442/537 87 63 375 234 10.5

27

6 442 65 20 35 91 1340

10 442 65 20 55 80 451.2

16 442 65 20 55 90 225.6

25 442 87 20 72 100 112.8

40 442 87 20 110 130 55.6

50 442 87 20 210 130 30.7

63 442 87 20 210 147 23.0

80 537 87 20 250 210 23.0

100 537 87 20 300 235 15.8

36

6 537 65 20 35 137 2055

10 537 65 20 55 93 572

16 537 65 20 55 109 286

25 537 87 20 72 144 143

40 537 87 20 100 176 69.1

IEC

UN IN e D K (1) I1 I3 RO PN

MinimumI2 x t

Maximum I2 x t

kV A mm mm – kA A mΩ Watt Pre-arc

A2sInterrupted

A2s

3.6

100 292 65 0.75 50 275 3.25 49 1.4 x 104 17 x 104

160 292 65 0.7 50 400 1.94 75 3.8 x 104 50 x 104

200 292 87 0.7 50 500 1.42 75 7.6 x 104 71 x 104

250 292 87 0.6 50 760 1.03 90 14 x 104 115 x 104

315 292 87 0.6 50 900 0.85 122 21 x 104 180 x 104

7.2

63 442 65 0.75 50 175 8.63 45 0.48 x 104 6.5 x 104

100 442 65 0.75 50 275 4.93 67 1.40 x 104 18 x 104

160 442 65 0.7 50 400 2.96 119 3.8 x 104 54 x 104

200 442 87 0.7 50 500 2.15 118 7.6 x 104 75 x 104

250 442 87 0.6 50 800 1.5 6142 14 x 104 120 x 104

315 442 87 0.6 50 950 1.30 193 21 x 104 220 x 104

12

63 442 65 0.75 50 190 13.3 77 0.48 x 104 11 x 104

100 442 87 0.75 50 275 6.72 103 1.4 x 104 20 x 104

160 442 87 0.7 50 480 4.04 155 3.8 x 104 70 x 104

200 442 87 0.7 50 560 2.89 173 9.3 x104 91 x104

Fuses

D

Page 43: catalogo general Media Tensión (abb)

43

Vacuum Interrupters for circuit-breaker applications

Rated voltage kV ...40.5

Rated current A ...3150

Rated short-circuit breaking current kA ...63

Mechanical operation No. ...30,000

Vacuum Interrupters for contactor applications

Rated voltage kV ...12

Rated current A ...400

Rated short-circuit breaking current kA ...4

Mechanical operation No. ...1,000,000

Vacuum Interrupters for switch-disconnector applications

Rated voltage kV ...24

Rated current A ...630

Rated short-circuit breaking current kA ...4

Mechanical operation No. ...10,000

ABB offers vacuum interrupters universal in application with more than 20 years of experience in vacuum technology. • Compact and robust design to meet the highest demands • Reliability and long life from state-of-the-art manufacturing processes • Silicone moulding for maximum external dielectric strength • Quality management to DIN EN ISO 9001 • Most frequently used switching technology worldwide for medium

voltage • Environmentally friendly and maintenance-free for life • Experience from over 2 million vacuum interrupters in service

Vacuum interrupters

Page 44: catalogo general Media Tensión (abb)

44

Insulators

Indoor insulator for air insulated device• Epoxy resin • Tested and manufactured in accordance with major

electric standards • Suitable for high number of indoor applications

Model Description Rated Voltage Characteristics

IPA Post insulator with recessed metal fitting 7.2 - 40.5 kV Ultimate bending stress: 4000 - 10000 N

DC DCP DCL

Post insulator with capacitor divider for voltage indication

12 - 40.5 kV Rated current: 250 - 1000 A PSL: long type for concrete substation

SCD SF SC SCB SDY

Voltage presence indicator 1 - 40.5 kV Rated current: 630 A Coupling interface EN 50180 DIN 47636 or cable and bus-bar not insulated

IPAN PRC

Bushing air/air insulator 12 - 36 kV Rated current: 400 - 630 A

IPAR ISOF

Insulator for rotative switch-disconnector and Connection isulator with arc air suppresion

12 - 36 kV Rated current: 400 - 630 A Connection with cable or bus-bar not insulated

PRB Bushinhg air/interface with external cone plug connector

24 - 36 kV Theoretical tensile strenght: 10000 N Theoretical compressive strenght: 12000 N

PPA Bushinhg air/interface with internal cone plug connector

24 - 36 kV Rated current: 1250 A Coupling interface: EN 50180 DIN 47637

Page 45: catalogo general Media Tensión (abb)

45

Indoor insulator for SF6 gas insulated device • Epoxy resin • Tested and manufactured in accordance

with major electric standards• Suitable for high number of indoor

applications

Model Description Rated Voltage Characteristics

PPC PPT PPE

Bushing with internal cone plug connection 24 - 36 kV Rated current: 250 - 1250 A Coupling interface EN 50180 DIN 47637

PTC PTS

Bushing with external cone plug connection

24 - 36 kV Rated current: 250 - 1250 A Coupling interface EN 50180 DIN 47636

PRI Bushing air/SF6 indoor use 24 kV Rated current: 630 A Connection with cable or bus-bar not insulated

INV IPF IPC

Fuse holder, bushing and accessories for RMU

24 - 36 kV Rated current: 250 A

Page 46: catalogo general Media Tensión (abb)

46

Insulators

Outdoor insulator for air and SF6 gas insulated device • Cicloaliphatic resin or Silicon rubber protection• Tested and manufactured in accordance with major electric standards• Suitable for high number of outdoor applications

Model Description Rated Voltage Characteristics

IPAE Post insulator with embedded metal frame for fitting

12 - 40.5 kV Ultimate bending stress: 4000 - 10000 N

PSE PSL

Bushing air/air with higher creepage distance 12 - 36 kV Rated current: 250 - 1000 A PSL: long type for concrete substation

PGS Bushing with external cone plug connection and external rubber protection

24 - 36 kV Rated current: 630 A Coupling interface EN 50180 DIN 47636 or cable and bus-bar not insulated

PRG SF6/ Air composite bushing in epoxy resin and silicon rubber

24-36 kV Rated current: 400 - 630 A

PRE SF6/ Air bushing in epoxy resin 24 kV Rated current: 400 - 630 A Connection with cable or bus-bar not insulated

BSL Composite insulator for switch disconnector BIL 75 - 325 kV Theoretical tensile strenght: 10000 N Theoretical compressive strenght: 12000 N

PPA Bushing air/internal cone interface plug connection

24 kV Rated current: 1250 A Coupling interface: EN 50180 DIN 47637"

Page 47: catalogo general Media Tensión (abb)

47

Page 48: catalogo general Media Tensión (abb)

48

Apparatus for outdoor installation

OHBGas circuit-breakers for outdoor installation• Tested and constructed in accordance with IEC Standards • Operation at temperatures from – 25 °C to + 40 °C • Maintenance-free poles • Top and bottom terminals with NEMA 4 drilling• Gas pressure monitoring device as standard • Poles made with ceramic insulators, assembly using flanges with terminals • Pole covers and cups made of anodised aluminium • Pole covers with safety valves• Inspection window placed in the pole support box opposite the control signals

(1) Rated service value.

Circuit-breaker OHB 24 OHB 36 OHB 40

Rated and insulation voltage kV 24 36 40.5

Withstand voltage (1 min) kV (50Hz) 70 (dry) / 60 (wet) 95 (dry) / 80 (wet) 95 (dry) / 80 (wet)

Impulse withstand voltage kV 150 200 200

Rated frequency Hz 50-60 50-60 50-60

Rated current A (40 °C) 1250 2500 1250 2500 1250 2500

Rated breaking capacity and ratedshort-time withstand current (3 s)

kA25 25 25 25 25 25

31.5 31.5 31.5 31.5 31.5 31.5

Making capacity kA63 63 63 63 63 63

80 80 80 80 80 80

Operation sequence O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO

Opening time ms 45 ± 10 45 ± 10 45 ± 10

Arc time ms 10-15 10-15 10-15

Total interruption time ms 50-65 50-65 50-65

Closing time ms 75 ± 10 75 ± 10 75 ± 10

Overall dimensions

H mm 3090 ... 3840 3090 ... 3840 3090 ... 3840

L mm 900 900 900

D mm 686 686 686

Weight kg 900 900 900

Absolute pressure of SF6 gas (1) kPa 500 500 500

Operating temperature °C – 25 ... + 40 – 25 ... + 40 – 25 ... + 40

Tropicalization IEC: 60068-2-30, 721-2-1 • • •Electromagnetic compatibility IEC:60694, 61000-6-2, 61000-6-4 • • •

Solar radiation W/m2 1000 1000 1000

Presence of pollution IEC 815 - table 1 Level III Level III Level III

Creepage line cm/kV 3.75 2.5 2.23

Presence of surface ice mm 10 10 10

Wind speed m/s 34 34 34

Impact resistance g 0.3 0.3 0.3

Static force on the terminals

Longitudinal N 750 750 750

Transversal N 500 500 500

Vertical N 750 750 750

Technical catalogue No. 1VDS28003 1VDS28003 1VDS28003

IEC

H

L D

Page 49: catalogo general Media Tensión (abb)

49

IEC

VBFVacuum circuit-breakers for outdoor installation• Tested and constructed in accordance with IEC Standards • Operation at temperatures between – 25 °C and + 40 °C • Maintenance-free poles • Top and bottom terminals with NEMA 4 drilling• Suitable for self-reclosing cycles • Poles made with ceramic insulators, assembly using flanges with terminals • Pole covers and cups made of anodised aluminium • Inspection window placed in the pole support tank opposite the operating

mechanism signals

Circuit-breaker VBF

Rated and insulation voltage kV 36

Impulse withstand voltage kV 170

Rated frequency Hz 50

Rated current A (40 °C) 1600

Rated breaking capacity and rated short-time withstand current (3 s)

kA 26.3

Making capacity kA 65.75

Operation sequence O-0.3s-CO-15s-CO

Opening time ms 40 ± 10

Arc time ms 10-15

Total interruption time ms 55 ± 10

Closing time ms 60 ± 15

Overall dimensions

H mm 3168 ... 3968

L mm 900/1900

D mm 780/1538

Weight kg 850

Operating temperature °C – 25 ... + 40

Technical catalogue No. 1VDS28003

H

L D

Page 50: catalogo general Media Tensión (abb)

50

Apparatus for outdoor installation

OVRReclosers for outdoor installation for overhead lines• Tested and constructed in accordance with ANSI - IEC - Nema - IEEE Standards• Compact and sturdy design • Up to 10,000 operations • Maintenance-free poles • Embedded vacuum interrupters • Magnetic actuator• Microprocessor-based control unit

Recloser OVR 15 OVR 27 OVR 38

Service voltage kV 2.4 - 14.4 29.4 34.5

Rated voltage kV 15.5 27 38

Impulse withstand voltage kV 110/125 125 170

Withstand voltage at dry industrialfrequency at 60 Hz x 10 s

kV 50 60 70

Withstand voltage at industrial frequency in humid air 60 Hz x 10 s

kV 45 50 60

Rated uninterrupted current A 630/800/1000 630/800/1000 630/800

Breaking capacity kA 12.5 12.5 16

Pole centre distance mm 394 394 394

Phase-phase surface discharge distance mm 960 960 1288

Minimum phase-phase surface discharge distance mm 1160 1160 1260

Minimum insulation distance in free air mm 240 240 367

Maximum interruption time s 0.040 0.040 0.040

Maximum closing time s 0.060 0.060 0.060

Operating temperature °C - 40 ... + 70 - 40 ... + 70 - 40 ... + 70

Auxiliary voltage 90-264 V ac; 250 V dc and 50-150 V ac / 125 V dc with UPS

Current sensors One per phase integrated in the pole

Technical catalogue No. 1VAL2601

IEC/ANSI

Page 51: catalogo general Media Tensión (abb)

51

ANSI

PadmountElectric apparatus in enclosure for outdoor installation• The range of Padmount products includes: switch-disconnectors with direct

access with fuses, switch-disconnectors with access interlocked with fuses, switch-disconnectors with current-limiting fuses, capacitor banks and metering compartments

• Several types of configurations are available with rated voltages up to 25 kV • They are suitable for outdoor installation or in environments with aggressive

atmosphere, in the presence of damp, dust, etc. in plants for industries and utilities

• The characteristics of the enclosures are such as to ensure and exceed the prescriptions of the ANSI Standards

• Technical catalogue: 1VAM2201-DB

Switch-disconnectors with direct access15-25 kV – 600 A – 40 kA

Switch-disconnectors with interlocked access 15-25 kV – 600 A – 40 kA

Switch-disconnectors with current-limiting fuses 15-25 kV – 200 A

Enclosures with capacitor banks15-25 kV – 2400 kVAR

Measurement compartments15-25-35 kV – 200-600 A

Page 52: catalogo general Media Tensión (abb)

52

Apparatus for outdoor installation

AutoLinkResettable Electronic Auto Sectionalizer• Fits on a standard cutout body• Works in conjunction with an upstream recloser or circuit breaker• Field configurable and resettable as many times as needed between 6 and 215A,

and from 1 to 4 counts • Trip arm reset with no tools required• Does not require an auxiliary power source• Isolates temporary faults at the AutoLink preventing extensive outages• Detects and discriminates inrush current• Reduces operating costs and replacement of fuses• “One kV rating fits-all” design minimizes inventory

ANSI

Model AutoLink-15 AutoLink-27 AutoLink-27/33 AutoLink-33

Rated voltage kV 15 27 27/38 38

Insulation level kV BIL 110 125 150 170

Rated current A 200 200 200 200

Actuating current A 6 - 215 6 - 215 6 - 215 6 - 215

Number of counts before operation No 1 - 4 1 - 4 1 - 4 1 - 4

Short time current (1s effective) kA 4 4 4 4

Dead line detection ma < 200 < 200 < 200 < 200

Memory reset s 30 30 30 30

Asymmetrical initial (peak) kA 10 10 10 10

Page 53: catalogo general Media Tensión (abb)

53

CHDCapacitors allow the reactive power to be modulated according to the load present in the network with the following advantages:• improvement of energy quality and efficiency of the electrical systems • great reduction in leaks and limited consumption • improvement of the power factor of the electrical systems• greater network stability• limitation/elimination of the penalties for inadequacy of the power factor

Capacitors IEC/ANSI

Medium voltage capacitors

Capacitor Single phase Split phase Three phase

Rated power kVar up to 900 up to 800 (400 + 400) up to 500

Rated voltage kV up to 20 up to 17.5 (phase-phase) up to 20

Rated frequency Hz 50/60 50/60 50/60

Rated current A max. 180 max. 180 max. 180

Dielectric Polypropylene film Polypropylene film Polypropylene film

Impregnant Faradol 810 (non-PCB) Faradol 810 (non-PCB) Faradol 810 (non-PCB)

Diuscharge resistor Internal Internal Internal

Lones (including resistors) W/kVar ≤ 0.15 ≤ 0.15 ≤ 0.15

Page 54: catalogo general Media Tensión (abb)

54

PS_ Capitor Vacuum Switches • Maintenance free• Visual indication• Light weights and dimensions• Low power solenoid mechanism• Wide control voltage range• Few mowing parts • Trip lever for emergency operation

Capacitors

NotesClass 2 restrike in accordance to IEEE 37.66Type test certificates from independent testing facilities are available upon request.

Capacitor vacuum switch PS15 PS17 PS25 PS36

Rated maximum voltage, 50/60Hz

Ungrounded capacitor banks, line-to-line kV rms 15.5 17.5 25 38

Grounded capacitors banks, line-to-line kV rms 27 30 43 66

Impulse withstand voltage

Line to ground kV BIL 125 / 125 150 125 / 150 200

Open contact kV BIL 95 / 125 125 125 / 125 200

Withstand voltage, 60Hz

Dry, 1.0 minutes kV 50 60 60 70

Wet, 10 seconds kV 40 50 60 60

Continuous current 50/60 Hz A 200 / 400 400 200 300

Capacitive switching current (50/60Hz) A 200 / 400 400 200 300

Loading interrupting current A 5000 5000 5000 5000

Short time symmetrical withstand current (1 s) A 4500 / 5000 5000 4500 / 5000 5000

High frequency peak

Transient making current A 12000 15000 12000 15000

Transient in-rush frequency Hz 3000 / 6000 6000 6000 6000

Operating voltage range

110/120 Vac (50/60 Hz) or Vdc V 90…130 90…130 90…130 90…130

240 Vac (50/60 Hz) V 205…265 205…265 205…265 205…265

110/120 Vac (50/60 Hz) or Vdc (Electronically held) V 90…130 90…130 90…130 N/A

Nominal current A 10 10 10 30

Nominal open/close time ms 100 100 100 100

Continuous current (electronically held) mA 100 100 100 N/A

Creepage distance

Terminal to terminal mm 518 805 518 / 805 1600

inch 20.4 31.7 20.4 / 31.7 62.99

Terminal to ground mm 498 757 498 / 757 1350

inch 19.2 29.8 19.2 / 29.8 53.15

General

Weightkg 13 16 16 ≈ 110

lbs 28 35 35 ≈ 243

Operating temperature range °C - 40 … + 65 - 40 … + 65 - 40 … + 65 - 40 … + 65

°F - 40 … + 149 - 40 … + 149 - 40 … + 149 - 40 … + 149

Mechanical endurance, paired operations 50,000 50,000 50,000 50,000

ANSIANSI

Page 55: catalogo general Media Tensión (abb)

55

VisiVoltPassive voltage indicator for indoor and outdoor installation• Tested and constructed according to IEC and ANSI Standards• Can be applied to all types of busbars or insulated unshielded or bare cables, of

any section and diameter • For plants with rated voltage from 3 to 36 kV• Continuous status indication • Good visibility in any light conditions • Economical solution• Maintenance-free • No auxiliary power supply• Simple installation• Can be combined with current-limiting fuses

Voltage indicator VisiVolt VV-A VisiVolt VV-B

Rated voltage of three-phase systems kV 3 - 15 13.8 - 36

Threshold voltage of three-phase systems – phase-earth and phase-phase

kV > 0.6 kV > 1.5 kV

Rated voltage single-phase systems kV 4.8 – 8 8 - 20

Threshold voltage of single-phase – phase-earth systems kV> 1 kV > 1.5 kV

< 78 % Un < 78 % Un

Rated frequency Hz 50 - 60 50 - 60

Response time

s < 1 at - 20 °C < 1 at - 20 °C

s < 3 at - 30 °C < 3 at - 30 °C

s < 10 at - 40 °C < 10 at - 40 °C

Rated short-time withstand current (1s) kA 63 63

Peak current kA 164 164

Operating temperature °C - 40 … + 85 - 40 … + 85

Breaking capacity with capacitive load at 15 kV kVar - 2500

Dimensions (height x width x depth) mm 92 x 63 x 38 92 x 63 x 38

Weight kg 0.109 0.109

Voltage indicators IEC/ANSI

Page 56: catalogo general Media Tensión (abb)

56

SOC - KAPMedium voltage insulating connectors • Can be applied cold without special tools• Rapid and safe installation• Minimum removal of the cable insulation • Uniform pressure on the cable• Complete application kit for each connector • Minimum number of components• Long life • Limited number of types for cable sections from 50 to 300 mm2

SOC: shielded separable insulating connector for indoor and outdoor installation – 250-630 A – 12-24 kV• Tested and constructed according to the EN 50181, SS 244 14 45, HD 628.1 S1

and HD 629.1 S1 Standards• Connectors for XLPE type cables, insulated with single or three-pole conductor,

made of aluminium or copper• The SOC Slipover connectors are made with three layers of rubber: the central

insulating layer and the two internal and external layers • conductive to guarantee contact-proof earthing• The connectors are supplied in kits for three cables

KAP: insulating connector for indoor installation – 630 A – 12-24 kV• Tested and constructed according to the SEN 24 14 34, SS 424 14 17

Standards• Connectors for XLPE type cables, insulated with single or three-pole conductor,

made of aluminium or copper• The KAP connectors are suitable for connection of cables with gas insulated

electrical apparatus, for connection of transformers in compact substations• The connectors are supplied in kits for three cables

IEC/ANSIConnectors

Page 57: catalogo general Media Tensión (abb)

57

Page 58: catalogo general Media Tensión (abb)

58

Switchgear UniGear 12 UniGear 17 UniGear 24

Type of construction ( IEC 62271-200) LSC2B-PM LSC2B-PM LSC2B-PM

Rated voltage kV 12 17.5 24

Insulation levels kV 12/28/75 17.5/38/95 24/50/125

Rated current of the main busbars A (40 °C) ... 4000 ... 4000 ... 3150

Rated current of the branch connections A (40 °C) ... 4000 ... 4000 ... 2500

Rated short-time withstand current kA ... 50 ... 50 ... 31.5

Arc withstand current kA ... 50 ... 50 ... 31.5

Overall dimensions of the basic unit (with single level)

H mm 2200/2675 2200/2675 2325/2775

L mm 325(1)/550/650/800/1000 550/650/800/1000 800/1000

D mm 1340/1390 1340/1390 1560

Use of the following is foreseen:

- Vacuum circuit-breakers • • •

- Gas circuit-breakers • • •

- Vacuum contactors • – –

- Earthing switch • • •

- Microprocessor-based control unit • • •

- Instrument transformers • • •

- Measurement sensors • • •

Technical catalogue No. 1VCP000138 1VCP000138 1VCP000138

UniGear ZS1Air insulated switchgear • Tested and constructed in accordance with IEC Standards• Guaranteed arc-proof units (IAC)• Compartments segregated by means of metal partitions• Apparatus racking-in/out with the door closed• Units can be mounted against the wall• Complete with mechanical safety interlocks• Earthing switch with full making capacity• Available versions: Single level – double level – double busbar systems – 500R

with fixed Vmax circuit-breaker – 550 with withdrawable Vmax circuit-breaker – single and double level with marine approval

• Optional: Set up and/or integrated in the factory, for automation and supervision.

H

DL

Primary distribution switchgear IEC

Page 59: catalogo general Media Tensión (abb)

59

UniGear ZVCAir insulated switchgear for motor control• Tested and constructed in accordance with IEC Standards • Can be coupled with UniGear ZVC type switchgear• Guaranteed internal arc proof units (IAC) • Compartments segregated by means of metal partitions • Contactor racking-in/out with the door closed • Units can be mounted against the wall • Complete with mechanical safety interlocks • Approved versions for naval applications • Complete range of motor control units for contactors with fuses• Optional: Set up and/or integrated in the factory, for automation and supervision.

Switchgear UniGear ZVC 7.2

Type of construction (IEC62271-200) LSC2B-PM

Rated voltage kV 3.6 - 7.2

Insulation levels kV 40 -60

Rated current of the main busbars A (40 °C) ... 4000

Rated current of the branch connections A (40 °C) ... 400

Rated short-time withstand current kA ... 50

Arc withstand current kA ... 50

Overall dimensions of the basic unit (with single level)

H mm 2200/2595

L mm 325

D mm 1125

Use of the following is foreseen:

- Vacuum contactors •

- Earthing switch •

- Microprocessor-based control unit •

- Instrument transformers •

- Measurement sensors •

Technical catalogue No. 1VCP000138

IEC

H

DL

Page 60: catalogo general Media Tensión (abb)

60

UniGear ZS2Air insulated switchgear• Tested and constructed in accordance with IEC Standards• Guaranteed arc-proof units (IAC)• Compartments segregated by means of metal partitions• Apparatus racking-in/out with the door closed• Limited and simple maintenance activities• Complete with mechanical safety interlocks• Earthing switch with full making capacity• Studied to guarantee maximum service continuity• Optional Set up and/or integrated in the factory for automation and supervision.

Switchgear UniGear 36

Type of construction (IEC62271-200) LSC2B-PM

Rated voltage kV 36

Insulation levels kV 36/70/170

Rated current of the main busbars A (40 °C) ... 2500

Rated current of the branch connections A (40 °C) ... 2500

Rated short-time withstand current kA ... 25

Arc withstand current kA ... 25

Overall dimensions of the basic unit (with single level)

H mm 2161/2662

L mm 1000/1200

D mm 2400/2600

Use of the following is foreseen:

- Gas circuit-breakers •

- Earthing switch •

- Microprocessor-based control units •

- Instrument transformers •

Technical catalogue No. 1YTS030001

Primary distribution switchgear IEC

H

DL

Page 61: catalogo general Media Tensión (abb)

61

UniGear ZS3.2Air insulated switchgear• Tested and constructed in accordance with IEC and CNS Standards• Guaranteed arc-proof units (IAC)• Compartments segregated by means of metal partitions• Apparatus racking-in/out with the door closed• Limited and simple maintenance activities• Complete with mechanical safety interlocks• Earthing switch with full making capacity• Studied to guarantee maximum service continuity• Optional Set up and/or integrated in the factory for automation and supervision.

Switchgear UniGear 36 UniGear 40.5

Type of construction (IEC62271-200) LSC2B-PM CNS

Rated voltage kV 36 40.5

Insulation levels kV 36/70/170 40.5/95/185

Rated current of the main busbars A (40 °C) ... 3150 ... 3150

Rated current of the branch connections A (40 °C) ... 3150 ... 3150

Rated short-time withstand current kA ... 31.5 ... 31.5

Arc withstand current kA Ask ABB Ask ABB

Overall dimensions of the basic unit (with single level)

H mm 2400 2400

L mm 11200 1200

D mm 2565 2565

Use of the following is foreseen:

- Vacuum circuit-breakers • •

- Gas circuit-breakers • •

- Earthing switch • •

- Microprocessor-based control unit • •

- Instrument transformers • •

Technical catalogue No. 1YHA000023 1YHA000023

IEC

H

DL

Page 62: catalogo general Media Tensión (abb)

62

SafeGearAir insulated switchgear • Tested and constructed in accordance with ANSI Standards• Arc-proof units • Apparatus racking-in/out with the door closed• Solution with single or double level• Limited and simple maintenance activities• Studied to guarantee maximum service continuity

Switchgear SafeGear

Rated voltage kV 5 ... 27

Insulation levels kV 60 ... 125

Rated current of the main busbars A 1200 ... 3000

Rated short-time withstand current kA 50

Overall dimensions of the basic unit (with single level)

H mm 2413 (2603 with forced ventilation)

L mm 914

D mm 2159 ... 2591

Use of the following is foreseen:

- Vacuum circuit-breakers •

- Control units •

- Instrument transformers •

Technical catalogue No. 1VAL1001

Primary distribution switchgear

H

DL

ANSI

Page 63: catalogo general Media Tensión (abb)

63

UniGear R40Air insulated switchgear with single-pole circuit-breakers, for railway traction networks • Tested and constructed in accordance with IEC Standards • Arc proof units • Reduced and simple maintenance activities• Complete range of safety locks

Switchgear UniGear R40

Rated voltage kV 40.5

Service voltage kV 27.5

Insulation levels kV 95/200

Rated current of the main busbars A 2000

Rated short-time withstand current (1s) kA 25

Arc withstand current (1s) kA 25

Number of phases No. 1

Overall dimensions of basic unit (with single level)

H mm 2600

L mm 1000

D mm 2565

Use of the following is foreseen:

- Vacuum circuit-breakers •

- Control units •

- Instrument transformers •

Technical catalogue No. 1VSR000017

IEC

H

DL

Page 64: catalogo general Media Tensión (abb)

64

ZX0.2

ZX0Gas insulated switchgear with single-level busbar system • Tested and constructed in accordance with IEC Standards • Guaranteed arc proof units • Units can be installed against the wall • Complete with mechanical safety interlocks • Motor activated switch-disconnector with three positions • Medium voltage cable coupling system with connectors with external cone • Connection between the functional units by means of busbar coupling

connections • Studied to ensure maximum service continuity • Completely unaffected by environmental conditions • Optional: Set up and/or integrated in the factory, for automation and supervision.

Switchgear ZX0 12 ZX0 17 ZX0 24 ZX0.2

Type of construction GIS GIS GIS GIS

Rated voltage kV 12 17.5 24 12 - 24

Insulation levels kV 12/28/75 17.5/38/75 24/50/75 12/28/75 - 24/50/125

Rated current of the main busbars A (40 °C) ... 1250 ... 1250 ... 1250 1250 - 2500

Rated current of the branch connections A (40 °C) ... 1250 ... 1250 ... 1250 1250 - 2500

Rated short-time withstand current kA ... 25 ... 25 ... 25 31.5

Arc withstand current kA ... 25 ... 25 ... 25 31.5

Overall dimensions of the basic unit (with single level)

H mm 2100 (1)/1650 (2) 2100 (1)/1650 (2) 2100 (1)/1650 (2) 2400

L mm 400/600 (3) 400/600 (3) 400/600 (3) 600/900/1200

D mm 850 (4)/1000 (4) 850 (4)/1000 (4) 850 (4)/1000 (4) 1330

Nominal absolute SF6 gas filling pressure kPa 160 160 160 140

The use of the following is foreseen:

- Vacuum circuit-breakers • • • •

- Switch-disconnector with three positions • • • •

- Microprocessor-based control unit • • • •

- Instrument transformers • • • •

- Measurement sensors • • • •

Technical catalogue No. DECMS2313 03 DECMS2313 03 DECMS2313 03 1VBA680603

Primary distribution switchgear IEC

H

DL

(1) For all the panels in a system with circuit-breaker panels.(2) For panels without circuit-breaker.(3) For outgoing feeders with rated currents > 800 A and for panels divided individually into compartments. (4) Distance from wall > 100 mm.

Page 65: catalogo general Media Tensión (abb)

65

ZX1.2Gas insulated switchgear with single level busbar system• Tested and constructed in accordance with IEC Standards • Guaranteed arc proof units • Motor activated switch-disconnector with three positions • Medium voltage cable coupling system with connectors with internal cone • Connection between the functional units by means of coupling busbar connections • Cable fastening at a height of 1250 mm • Metal partitions between the various compartments of the individual panels • Completely unaffected by environmental conditions • Special version up to 40.5 kV• Optional: Set up and/or integrated in the factory, for automation and supervision.

(1) 800 mm for branch connections with rated current > 1250 A.(2) According to the number of cables per phase.

Switchgear ZX1.2 12 ZX1.2 24 ZX1.2 36

Type of construction GIS GIS GIS

Rated voltage kV 12 24 36

Insulation levels kV 12/28/75 24/50/125 36/70/170

Rated current of the main busbars A (40 °C) ... 2500 ... 2500 ... 2500

Rated current of the branch connections A (40 °C) ... 2500 ... 2500 ... 2500

Rated short-time withstand current kA ... 31.5 ... 31.5 ... 31.5

Arc withstand current kA ... 31.5 ... 31.5 ... 31.5

Overall dimensions of the basic unit (with single level)

H mm 2100 + 200 (gas exhaust) 2100 + 200 (gas exhaust) 2100 + 200 (gas exhaust)

L mm 600/800 (1) 600/800 (1) 600/800 (1)

D mm 1300/1800 (2) 1300/1800 (2) 1300/1800 (2)

Nominal absolute SF6 gas filling pressure kPa 1.47 1.47 1.47

The use of the following is foreseen:

- Vacuum circuit-breakers • • •

- Switch-disconnector with three positions • • •

- Microprocessor-based control unit • • •

- Instrument transformers • • •

- Measurement sensors • • •

Technical catalogue No. DECMS2305 02 DECMS2305 02 DECMS2305 02

IEC

H

DL

Page 66: catalogo general Media Tensión (abb)

66

Switchgear ZX1.5

Rated Voltage kV 27.5/2 x 27.5

Rated Frequency Hz 50

Rated power frequency withstand voltage

Line to earth kV 95

Line to line kV 140

Rated lighting impulse withstand voltage

Line to earth kV 200

Line to line V 325

Electrical endurance at rated short circuit current 30

Rated short-circuit breaking current for CB kA 31.5

Rated short-circuit making current kA 80

Rated peak withstand current kA 80

Rated short-time withstand current, 4s kA 31.5

Rated operating sequence O-0.3s-CO-180s-CO

Rated total opening time ms Ca. 60

Rated total closing time ms Ca. 80

Rated filling level for insulation (Pre) kPa 130

Alarm level for insulation (Pae) kPa 120

Minimum functional level for insulation (Pme) kPa 120

Degree of protection

Gas tank IP65

Low voltage compartment IP4X (1)

Ambient air temperature

Maximum °C +40

24 hour average, Maximum °C +35

Minimum °C -5

Operating altitude (2) m ...1000

Dimensions

Overall dimensions of the basic unit (with single level)

H mm 2100 (3)

L mm 1300-1800 (4)

D mm 800

Height of cable fixing mm 1250

Catalogue ZX1.5R09000202-V1EL

ZX1.5Single and two-phase gas insulated switchgear for railway applications• Tested and constructed in accordance with IEC Standards • Guaranteed arc proof units • Function separated and independent• High voltage compartment sealed• Operate easily and reliably• Longer service time, less maintenance• No gas work for assembly at site• Panel size minimum• Optional Set up and/or integrated in the factory, for automation and supervision.

Primary distribution switchgear IEC

1) Higher degree on request2) Higher altitude on request3) Additional 200mm depth for pressure release system4) Based on number of cables for each phase

H

PL

Page 67: catalogo general Media Tensión (abb)

67

IEC

ZX2Gas insulated switchgear with single and double level busbar system• Tested and constructed in accordance with IEC Standards • Guaranteed arc proof units • Motor activated switch-disconnector with three positions • Medium voltage cable coupling system with connectors with internal cone • Connection between the functional units by means of coupling busbar

connections without interventions in the compartments containing gas • Studied to ensure maximum service continuity • Completely unaffected by environmental conditions • Optional Set up and/or integrated in the factory, for automation and supervision.

Switchgear ZX2 12 ZX2 24 ZX2 36 (2)

Type of construction GIS GIS GIS

Rated voltage kV 12 24 36

Insulation levels kV 12/28/75 24/50/125 36/70/170

Rated current of the main busbars A (40 °C) ... 2500 ... 2500 ... 2500

Rated current of the branch connections A (40 °C) ... 2500 ... 2500 ... 2500

Rated short-time withstand current kA ... 40 ... 40 ... 40

Arc withstand current kA ...40 ...40 ...40

Overall dimensions of the basic unit (with single level)

H mm 2300 2300 2300

L mm 600/800 (1) 600/800 (1) 600/800 (1)

D mm 1710 1710 1710

Nominal absolute SF6 gas filling pressure kPa 1.47 1.47 1.47

The use of the following is foreseen:

- Vacuum circuit-breakers • • •

- Earthing switch • • •

- Microprocessor-based control unit • • •

- Instrument transformers • • •

- Measurement sensors • • •

Technical catalogue No. DECMS2301 02 DECMS2301 02 DECMS2301 02

H

DL

(1) 800 mm for branch connections with rated current > 1250 A. (2) Special version up to 40.5 kV.

Page 68: catalogo general Media Tensión (abb)

68

ZX2.2Gas insulated switchgear with single and double level busbar system• Tested and constructed in accordance with ANSI Standards • Guaranteed arc proof units • Vacuum circuit breaker characteristics: 42 kV, 200 kV BIL, 2500 A, 40 kA• Three-position disconnect/ground switches• Plug-type busbar and cable connections• Safety interlocking and view ports• Closed-door operation, grounding and testing• Compact dimensions • Optional Set up and/or integrated in the factory, for automation and supervision.

1) Higher values as per international standards on request2) Single busbar arrangements up to 4000 A on request3) Other sequences on request4) Insulating gas: sulphur hexafluoride5) All pressures stated are absolute pressures at 20°C; 100kPa = 1 bar6) Other auxiliary voltages on request7) Higher altitudes above sea level on request

Primary distribution switchgear

H

DL

ANSI

Switchgear ZX2.2

Maximum operating voltage kV 42

Rated power frequency withstand voltage kV 80 (1)

Rated lightning impulse withstand voltage kV 200

Rated frequency Hz 50/60

Rated busbars current A ...2500 (2)

Rated feeder current A ...2500

Rated peak withstand current kA ...104

Rated short-time current, 3s kA ...40

Rated short-circuit breaking current of circuit-breaker kA ...40

Rated short-circuit making current of circuit-breaker kA ...104

Rated operating sequence O - 0.3 s - CO - 3 min – CO (3)

Total break-time ms approx. 60

Make-time ms approx. 80

Insulating gas SF6 (4)

Rated filling level for insulation (5) Pre kPa/PSI 130/18.85

Alarm level for insulation (5) Pae kPa/PSI 120/17.40

Minimum functional level for insulation (5) Pme kPa/PSI 120/17.40

Rated data

Charging motor VA (W) 240

Closing coil VA (W) 250

Opening coil VA (W) 250

Auxiliary voltage V 60, 110, 125, 220 DC (6)

Degree of protection - HV live parts IP65

Ambient temperature

Maximum value °C/°F 40/104

Maximum value of 24 hour mean °C/°F 35/95

Minimum value °C/°F - 5/23

Altitude for erection above sea level (7) m/ft ...1000/3300

Basic dimensions

Overall dimensions of the basic unit (with single level)

H mm/inch 2311/91

L mm/inch 2057/81

D mm/inch 787/31.5

Page 69: catalogo general Media Tensión (abb)

69

Page 70: catalogo general Media Tensión (abb)

70

UniSecAir insulated switchgear• Tested and constructed in accordance with IEC Standards• Air insulation of all live parts• SF6 switch-disconnector• Removable circuit-breakers• LSC2A service continuity classification• Withdrawable circuit-breaker • Complete portfolio of functional units and accessories• Wide range of protection relays, integrated on circuit-breakers or separately

mounted • Optional Set up and/or integrated in the factory for automation and supervision.

(1) 25 kA - 2s

Switchgear UniSec 12 UniSec 17 UniSec 24

Rated voltage kV 12 17.5 24

Test voltage (50-60 Hz x 1 min) kV 28 38 50

Impulse withstand voltage kV 75 95 125

Rated frequency Hz 50-60 50-60 50-60

Rated main busbar current A 630/1250 630/1250 630/1250

Rated normal current of apparatus:

- VD4-HD4 removable circuit-breaker 630/800 630/800 630/800

- GSec gas switch-disconnector 630/800 630/800 630/800

Rated short time withstand current kA (3s) 16/21/25 (1) 16/21 16/21

Peak current kA 40/50/63 40/52.5 40/52.5

Internal arc withstand current (IAC AFLR) kA (1s) 12.5-16-21 12.5-16-21 12.5-16-21

Overall dimensionsdof the basic unit

H mm 1200 1700 1700

L mm 375/500/750 375/500/750 375/500/750

D mm 1070 1070 1070

Technical catalogue No. 1VFM200003 1VFM200003 1VFM200003

Secondary distribution switchgear IEC

H

DL

Page 71: catalogo general Media Tensión (abb)

71

UniMixAir insulated switchgear• Tested and constructed in accordance with IEC Standards• Standard and arc-proof versions (IAC)• Circuit-breaker with self-supplied protection release• Can be mounted against the wall• Accessories for carrying out operating sequences using safe procedures• Vast range of functional units • Optional Set up and/or integrated in the factory for automation and supervision.

(1) P1/F Unit = 750 mm. M Unit = 500 mm.

Switchgear UniMix 12 UniMix 17 UniMix 24

Type of construction (IEC62271-200) LSC2A-PM LSC2A-PM LSC2A-PM

Rated voltage kV 12 17.5 24

Insulation levels kV 12/28/75 17.5/38/95 24/50/125

Rated current (40 °C)

- Main busbars A 400-630-800-1250 400-630-800-1250 400-630-800-1250

- Circuit-breakers A 1250 1250 1250

- Switch-disconnectors A 400-630 400-630 400-630

- Insulating switch-disconnectors A 400-630 400-630 400-630

Rated short-time withstand current (1s)P1/F, P1/E, P1/A, ASR, A, R, Rac, M, P2, P3

kA 12.5-16-20-25 12.5-16-20-25 12.5-16-20-25

Overall dimensions of the basic unit

H mm 1950 1950 1950

L mm 375-500 (1) 375-500 (1) 375-500 (1)

D mm 1210 1210 1210

Use of the following is foreseen:

- Vacuum circuit-breakers • • •

- Gas circuit-breakers • • •

- Gas switch-disconnectors • • •

- Gas insulation switch-disconnectors • • •

- Earthing switch • • •

- Instrument transformers • • •

Technical catalogue No. 1VCP000008 1VCP000008 1VCP000008

IEC

H

DL

Page 72: catalogo general Media Tensión (abb)

72

UniAirAir insulated switchgear• Tested and constructed in accordance with IEC Standards• Standard and arc-proof versions (IAC)• Circuit-breaker with self-supplied protection relay• Can be mounted against the wall• Construction with pre-galvanised sheets without welding points• Vast range of functional units• Optional Set up and/or integrated in the factory for automation and supervision.

Switchgear UniAir 12 UniAir 24

Type of construction (IEC62271-200) LSC2A-PM LSC2A-PM

Rated voltage kV 12 24

Insulation levels kV 12/28/75 24/50/125

Rated current (40 °C)

- Main busbars A 400-630-800-1250 400-630-800-1250

- Circuit-breakers A 630-800-1250 630-800-1250

- Switch-disconnectors A 400-630 400-630

- Insulating switch-disconnectors A 400-630-800-1250 400-630-800-1250

Rated short-time withstand current

- Circuit-breakers kA 12.5-16-20-25 12.5-16-20

- Switch-disconnectors kA 12.5-16 12.5-16

- Insulating switch-disconnectors kA 12.5-16-20-25 12.5-16-20

Arc withstand current kA 12.5-16 12.5-16

Overall dimensions of the basic unit

H mm 1950 1950

L mm 700/750 700/750

D mm 1190/1290/1385 1190/1290/1385

Use of the following is foreseen:

- VD4 series vacuum circuit-breakers • •

- HD4 series gas circuit-breakers • •

- Switch-disconnectors • •

- Rotary insulation switch-disconnectors • •

- Earthing switch • •

- Instrument transformers • •

Technical catalogue No. 1VCP000065 1VCP000065

H

DL

IECSecondary distribution switchgear

Page 73: catalogo general Media Tensión (abb)

73

IEC

SafePlus SafeRing

Switchgear SafePlus 24 SafeRing 24

Type of construction (IEC62271-200) GIS GIS

Rated voltage kV 12 17.5 24 12 17.5 24

Insulation levels kV 12/28/75 17.5/38/95 24/50/125 12/28/75 17.5/38/95 24/50/125

Rated current of the main busbars A (40 °C) ... 1250 ... 1250 ... 1250 ... 630 ... 630 ... 630

Rated current of the branch connections A (40 °C) ... 630 ... 630 ... 630 ... 630 ... 630 ... 630

Rated short-time withstand current kA ... 25 ... 25 ... 20 ... 21 (*) ... 16 ... 16

Overall dimensions of the basic unit

Module 1 2 3 4 5 1 2 3 4 5

H mm 1365 1365 1365 1365 1365 1365 1365 1365 1365 1365

L mm 371 696 1021 1346 1671 371 696 1021 1346 1671

D mm 765 765 765 765 765 765 765 765 765 765

The use of the following is foreseen:

- Vacuum circuit-breakers • •

- Switch-disconnector • •

- Earthing switch • •

- Microprocessor-based control unit • •

- Instrument transformers • •

Technical catalogue No. 1VDD006104 1VDD006104

(*) V module = 16 kA; C module = 21 kA.

Gas insulated switchgear for ring or radial networks up to 24 kV • Tested and constructed in accordance with IEC Standards • Arc proof construction • Gas containing compartments made of stainless steel • Designed for public and industrial distribution • Units can be installed against the wall • Unaffected by environmental conditions• Extremely compact and reliable • Cable connection bushings on the front • Optional Set up and/or integrated in the factory, for automation and supervision.

H

DL

Page 74: catalogo general Media Tensión (abb)

74

IEC

(1) Width of basic module.

SafePlus SafeRingGas insulated switchgear for ring or radial networks up to 36 kV • Tested and constructed in accordance with IEC Standards • Arc proof construction • Gas containing compartments made of stainless steel • Designed for public and industrial distribution • Units can be installed against the wall • Unaffected by environmental conditions• Extremely compact and reliable • Cable connection bushings on the front • Optional Set up and/or integrated in the factory, for automation and supervision.

Switchgear SafePlus 36 SafeRing 36

Type of construction (IEC62271-200) GIS GIS

Rated voltage kV 36/40.5 36/40.5

Insulation levels kV 36-70-170/40.5-95-185 36-70-170/40.5-95-185

Rated current of the main busbars A (40 °C) 630 630

Rated current of the branch connections A (40 °C) ... 630 ... 630

Rated short-time withstand current kA 20/21 20/21

Overall dimensions of the basic unit

H mm 1930 1930

L mm 420 (1) 1330-1750

D mm 900 900

The use of the following is foreseen:

- Vacuum circuit-breakers • •

- Switch-disconnector • •

- Earthing switch • •

- Microprocessor-based control unit • •

- Instrument transformers • •

Technical catalogue No. 1VDD006114 1VDD006114

H

DL

Secondary distribution switchgear

Page 75: catalogo general Media Tensión (abb)

75

Page 76: catalogo general Media Tensión (abb)

76

REF 601

Protections- Three-phase overcurrent, first threshold (low setting) – characteristic with mini-

mum definite time or minimum inverse time – IDMT – I>- Three-phase overcurrent, second threshold (high setting) – characteristic with

minimum definite time – I>>- Three-phase short-circuit, third threshold (very high setting) – instantaneous –

I>>>- Earth fault, first threshold (low setting) – characteristic with minimum definite time

or minimum inverse time – IDMT – Io>- Earth fault, second threshold (high setting) – characteristic with minimum definite

time – Io>>

Multi-function current protection unit• Simple configuration via software• Fixed panel unit• Measurement of the phase current by means of Rogowski coil• Configurable operator interface • Non-volatile memory• Digital inputs and output contacts• CEI 0-16 certification

The REF601 multi-function unit mana-ges the current protection functions.The unit is microprocessor-based and is fitted with a continuous watchdog system.The LCD display allows local use of the unit.The REF601 relay is available for appli-cations (IDMT and DMT) according to CEI and IEC Standards.It can be combined with KEKA 250B1 type current sensors.

Relays and multi-function units

Page 77: catalogo general Media Tensión (abb)

77

REF542plusMulti-purpose protection and control unit• Simple modification and upgrading of the functions via software• Graphic type operator interface with LCD display• Man-machine interface separate from the central unit• Modular hardware and software• Field units for supervision and process systems• Single type of spare parts and accessories: just one hardware type• Drastic reduction in preventive maintenance, great limitation of faults caused by

tampering and errors• Available with ATEX (94/9/EC) certification for explosive environments• Version with sensors conforming to CEI 0-16 specification

REF542plus/DKThe REF542plus/DK protection and control device according to ENEL DK5600 specification is available for distribution networks with compensated neutral.

Protections- Overcurrent- Earth fault- Voltmetric- Electric machines- Distance measurement- Residual current

Communication protocols- SPABUS- LON (ABB LAG 1.4)- Modbus RTU (in simple and dual

configuration)- IEC 60870-5-103 with VDEW

extension (German utilities association)

Functions- Internal watchdog- Shunt opening relay supervision- Circuit-breaker supervision- Power factor control- Anti-resonance protection- Rapid changeover system- Event recording and

oscilloperturbography with absolute time

The REF542plus unit integrates all the secondary functions relative to the switchgear in a single module fitted with watchdog.Thanks to the flexibility of its software, the unit can satisfy a vast range of plant requirements: protection, measurement, switching, signalling, interlocking, automation and communication.The high level of flexibility of this unit is supported by a simple and user-friendly interface.Thanks to using the REF542plus unit, each medium voltage panel becomes an integrated and autonomous unit able to carry out all the required functions.The possibility of direct connection between the switchgear and the plant management system fully achieves the integrated plant concept at the highest levels.

Technical catalogue: 1VTA000001.

Measurements- Current / Voltages- Power / Energy- Power factor- Frequency

Hardware- Man-machine interface separate from

the central unit (IP44)- Separate access to the protection and

control functions by means of distinct electronic keys

- 8 analog inputs for transformers and non-inductive sensors

- Up to 3 input/output cards:- 14 digital inputs (max. 42)- 6 power relay outputs (max. 18)- 2 signalling relay outputs (max. 6)- 1 static signalling output (max. 3)

- 4 analog outputs (0…20 or 4…20 mA)- 6 analog inputs (4…20 mA)- 3 energy meters with impulse emitters- Interface for CAN OPEN digital bus- Integrated Web Server for supervision

and monitoring- Serial service interface- Communication with supervision

systems (optic fibres or RS485)- IRIG-B interface for synchronisation

(1 ms response)

Page 78: catalogo general Media Tensión (abb)

78

REF 54_ /REF 630

Protections- Self-closing for up to 5 cycles- Phase discontinuity- Earth fault with 3 thresholds- Directional earth fault with 3

thresholds- Phase overcurrent with 3 thresholds- Directional phase overcurrent with 3

thresholds- Overfrequency and underfrequency

1...5- Inrush function- Overvoltage with 3 thresholds- Undervoltage with 3 thresholds- Residual overvoltage with 3 thresholds- Synchrocheck- Thermal overload- Power factor correction bank

protection- Power factor correction bank control- Thermal overload with PT100 probes- Unbalanced load- Power factor control

Measurements- Phase currents- Residual earth current - Phase voltage- Residual voltage- Power, energy and power factor- Recording of transients and

interferences - Localisation of faults due to short-

circuit and earth fault

Power Quality Monitoring- Measurement of the current waveform

distortion- Measurement of the voltage waveform

distortion- Voltage fluctuation

Multi-function unit for substation protection, control and automation• Simple modification and upgrading of the functions by means of the configuration

software • Graphic type operator interface with LCD display• Modular hardware and software • Field units for substation automation systems • Precise localisation of faults• Monitoring of the operating conditions• Single type of spare parts and accessories: just one type of hardware• Drastic reduction of preventive maintenance, great limitation of faults caused by

tampering and errors

The REF54_/REF 630 units are desi-gned for switchgear protection and control, and to be inserted in substation automation systems.Thanks to the use of integrated digital technology, the REF units offer comple-te measurement, protection, control and monitoring functions.All the functions required are present in a single device. Therefore the use of accessory apparatus and switchgear cabling operations are reduced.The simple and user-friendly configura-tion software means specific configura-tions can be made. The graphic interface allows the events, state of the devices, measurements, alarms, etc. to be displayed, adapting to the various plant requirements.The REF54_/REF 630 units have just one configuration system common to the whole series, considerably facilita-ting its use by operators.The wide range of communication pro-tocols allows connection and integration in the plant management system.

Technical catalogue: 1MRS751818

Inputs and outputs- Up to 34 digital inputs- Up to 26 digital outputs including 2

outputs for relay trip supervision- 8 inputs RTD/DT100- Synchronisation by means of binary

input- 4 outputs 4...20 mA

Analog inputs- Connections for 4 current

transformers 1 A and 5 A- Connections for 1 current transformer

0.2 A and 1 A- Connections for 4 voltage

transformers 100 V and 120 V- 9 inputs for current/voltage sensors

CommunicationLON / SPA / Modbus / DNP 3.0 /PROFI-BUS / IEC 61850 / IEC 60870-5-103

Monitoring operating conditions- Trip supervision- Fuse fault- Circuit-breaker wear - Circuit-breaker stroke time- No. circuit-breaker operations- Circuit-breaker inactive time- Programmed maintenance alarm- Closing springs charging time- Measurement supervision- Gas pressure alarm- Timers

Relays and multi-function units

Page 79: catalogo general Media Tensión (abb)

79

REM 54_/REM 630Multi-function protection and control unit for motors and generators• Simple modification and upgrading of the functions via software • A single piece of apparatus for protection and control of electric rotating machines • Minimum use of auxiliary apparatus and systems, such as relays, signalling

devices, etc. • Drastic reduction of cabling, limitation of connection errors • Predefined operating sequences which respond to plant requirements • Graphic type operator interface with LCD display • Easily expandable hardware and software • Field device for supervision and process systems • Drastic reduction of preventive maintenance, great limitation of the faults cau sed

by tampering and errors

The REM 54_/REM 630 units are designed for protection and control of rotating electric machines. They are parti cularly suitable for generators of any power, for synchronous motors and high power asynchronous motors. The REM units are also suitable for use in marine and naval plants.Thanks to the use of integrated digital technology, the REM units offer economical functions complete with measurement, protection, control and monitoring.All the necessary functions are present in a single device. The use of accessory apparatus and control switchgear cabling operations is therefore reduced.The RTD (Resistance Temperature Device) analog input allows control of the machine temperature and ventilation of the machine and ambient conditions. This allows the protection against overload to be defined precisely and the motors and generators to be managed in the best way.The simple and user-friendly configuration software allows specific applications to be made.

The graphic interface allows events, state of the devices, measurements, alarms, etc. to be displayed, adapting itself to the various plant requirements. The wide range of communication protocols allows connection and integration in the plant management system.

Technical catalogue: 1MRS750915-MUM.

Protections- Non-directional overcurrent - Directional overcurrent - Voltage-dependent overcurrent- Minimum impedance- Non-directional earth fault- Directional earth fault- Residual voltage- Directional power overload- Minimum/low power - inverse power- Minimum excitation- Overload for motors, generators and

transformers- Negative phase sequence- Overvoltage - Undervoltage- Voltage sequence- Under/over frequency - Stabilised differential: high impedance

or differential based on balanced flow- High impedance based on confined

earth fault- Inrush current of transformers and

motor start-up- Motor start-up supervision

- Minimum non-directional current - Phase inversion- Over-excitation- Synchronisation of voltage- Supervision of fuse faults- Circuit-breaker fault

Measurements- Phase and neutral current- Phase voltage- Power / Energy / Power factor / Frequency- Oscilloperturbography

Inputs/Outputs- 15 or 20 free digital inputs- 5 or 11 power outputs for closing /

opening comman d of which two with continuity control

- 7 output signals- 8 inputs for RTD

Analog inputs - Several variants available, max 9 CTs

and VTs- Up to 8 1A and 5A current

transformers - 1 for 0.2 A and 1 A current

transformers - Up to 9 100 V-120 V voltage

transformers- Up to 9 non-inductive voltage/current

sensors

Communications protocols SPA, LON, Modbus RTU/ASCII

Configuration tools - CAP 505- CAP 501

Page 80: catalogo general Media Tensión (abb)

80

Relays and multi-function units

REF610Multi-function protection unit • Simple unit configuration via software • Complete protection against short-circuits, overload and earth fault • Suitable for medium voltage outgoing/incoming feeders • Four current inputs • Optional protection against internal arcs • Non-volatile memory and oscilloperturbography • Self-closing • Withdrawable unit with self-circuiting current connections

The REF 610 unit is a modern multi-function unit particularly suitable for protection of medium voltage lines (outgoing/incoming feeders). The high number of protection functions available, among which three overcurrent thresholds, two earth fault thresholds, thermal protection and three-stroke self-closing, make it a complete unit for protection of against short-circuits, overload and earth fault.The optional protection against internal arcs and numerous binary inputs and outputs considerably further increase its field of application.The simple and user-friendly man machine interface is fitted with an LCD display, with control pushbuttons control pushbuttons and with eight LEDs for signalling.The unit is withdrawable and characterised by “plug & play” connectivity. The user-friendly configuration software allows the units to be configured for each specific plant. The wide range of communication protocols available allows its integration in supervision and control systems.

Technical catalogue: 1MRS755431-MUM.

Protections- Overcurrent protection with definite

and inverse time (IDMT)- Protection against earth fault with

definite and inverse time (IDMT)- Optional protection against internal

arcs- Thermal protection for cables- Self-closing- Protection against circuit-breaker fault

Communications protocolsSPA, Modbus RTU/ASCII, IEC 60870-5-103

Configuration tools - CAP 505- CAP 501 to IEC 61131-3 Standards

Page 81: catalogo general Media Tensión (abb)

81

REM610Multi-function motor protection unit • Simple unit configuration via software • Specific unit for protection of medium voltage asynchronous motors • Suitable for medium and high powered motors • Withdrawable units with self-circuiting current connections • Configurable operator interface with LEDs and with multi-lingual display • Non-volatile memory • Suitable for control of circuit-breakers and contactors • Field units for supervision and process systems

The REM610 unit is specifically designed for protection of medium voltage asynchronous motors.The unit manages the fault situations both during the motor start-up and during service with particular reference to heavy-duty applications, such as: pumps, fans, mills, presses, etc.The REM610 unit can, furthermore, be used for protection of cable and transformer lines which require protection against thermal overload or single and three-phase protection against overcurrent or non-directional earth fault.The unit is withdrawable and is characterised by “plug&play” connectivity for rapid automatic installation and is provided with simple configuration software for the best adaptation to the conditions required by the plant.The wide range of communication protocols allows connection and integration in the plant management system.

Technical catalogue: 1MRS752263-MUM.

Protections- Thermal overload for motors - Motor starting supervision- Overcurrent protection with definite

time- Cumulative outgoing feeder meter- Short-circuit- Undercurrent- Unbalance- Phase inversion- Non-directional earth fault- Thermal protection with RTD- Circuit-breaker fault- Emergency starting

Communications protocolsSPA, Modbus RTU/ASCII, IEC 60870-5-103

Configuration tools- CAP 505- CAP 501 to IEC 61131-3 Standards

Page 82: catalogo general Media Tensión (abb)

82

Relays and multi-function units

REU 610

The REU610 multi-function unit manages a complete range of voltage protection functions and is the ideal completion for the REF610 line protection and REM 610 motor protection units.The unit is microprocessor-based and is fitted with a continual watchdog system.The LCD display allows local use of the unit.By means of the front communication port, local control is possible by means of a normal personal computer.On the other hand, a communication port located in the rear allows remote control.

Technical catalogue: 1MRS 756025.

Protections- Overvoltage, low threshold- Overvoltage, high threshold- Overvoltage with negative phase

sequence- Undervoltage, low threshold- Undervoltage, high threshold- Undervoltage with positive phase

sequence- Residual voltage, low threshold- Residual voltage, high threshold- Circuit-breaker fault- Relay lock

Multi-function voltage protection unit • Simple configuration via software• Wide range of integrated protection functions • Withdrawable unit• Operator interface configurable with LEDs and with multi-lingual display • Non-volatile memory• Large number of digital inputs and output contacts

Communications protocols and modules - SPA-bus, IEC 60870-5-103, Modbus

(RTU and ASCII) 1. Plastic optic fibre 2. Plastic and glass optic fibre 3. RS485- DNO 3.0 4. RS485 including protocol DNP 3.0

Configuration tools- CAP 501- CAP 505- SMS 510- LIB 510

Page 83: catalogo general Media Tensión (abb)

83

REF615

Protections- Three-phase overcurrent- Directional and non-directional earth

fault- Double earth fault- Transient double earth fault- Non-directional earth fault- Non-directional sensitive earth fault- Overcurrent with inverse phase

sequence- Phase discontinuity- Thermal overload- Circuit-breaker fault- Inrush current control- Lock function - Arc protection with three sensors

REF615 is a dedicated line protection relay for protection, measurement and monitoring of substations, utilities and industrial electrical systems. It is in full accordance with the IEC 61850 Standards on the subject of communication and interoperability of automation devices for substations.The REF615 relay guarantees general protection of distribution substation overhead lines, cable lines and busbar systems. It can adapt to any radial distribution network radial regardless of its earthing principle.

Technical catalogue: 1MRS 756381.

Communications protocols and module- IEC 61850-8-1 with GOOSE

communication system- MODBUS TCP and RTU (optional)- Timing synchronisation by means of

Ethernet bus with SNTP

Configuration tools - PCM600 ver. 2.0 SP1 for setting,

configuration of the signals and management of oscilloperturbography.

- User interface based on web browser (IE 7.0 or later).

- Standard products for automation of COM600 ver. 3.2. substations

Multi-function line protection unit • Simple configuration via software• Wide range of integrated protection functions • Withdrawable unit• Configurable operator interface with LED and with multi-lingual display• Non-volatile memory• Large number of digital inputs and output contacts• Monitoring of operative conditions• Display with mimic diagram (option)• Inputs for sensors (Rogowski) - version G

Page 84: catalogo general Media Tensión (abb)

84

Relays and multi-function units

REM615

ApplicationREM615 is the main protection for asynchronous motors and relative transmissions in process manufacturing. This protection is generally used on high voltage motors controlled by a circuit-breaker or contactor and on medium and large sized low voltage motors controlled by a contactor and used in various applications, such as pumps and conveyor belts, oil presses and shredders, mixers , fans and aerators.

Protection and controlREM615 offers all the functions needed to manage motor starting and normal operation of transmissions, including protection against faults and elimination of these in the case of an anomaly. The main protection functions include:• 27 three-phase undervoltage• 47 overvoltage for negative phase

sequence• 47 undervoltage for positive phase

sequence• 37 undercurrent or minimum power• 46 current negative sequence or

balance• prolonged start-ups• thermal overload• instantaneous overcurrent• overcurrent with inverse time • 51N ground fault (residual)• 51G ground fault (measured)• 51LR blocked rotor• 66 supervision of number of start-ups• 67N directional ground fault• 50BF circuit-breaker failure to open• 50L internal arc fault (optional).

Multi-function motor protection and control unit • Simple configuration via software• Protection and control for asynchronous motors• Wide range of incorporated protection functions• Compact design • Withdrawable unit• Compliance with IEC 61850 Standards• Monitoring of operative conditions• Display with mimic diagram (option)• Inputs from RTD (option)

With REM615 it is also possible to di-rectly control the circuit-breaker locally, by means of open / closed pushbuttons located on the display, or remotely if it is connected to a supervision system.To prevent unauthorized access and keep integrity of the data, the relay is provided with a user authentication systembased on a four-level role, with indivi-dual passwords for the level of inspec-tor, operator, technician and admini-strator. Access control is carried out by means of the HMI on the front panel.

Standardized communication REF615 intrinsically supports the new IEC 61850 Standard, with regard to communication between devices in sub-stations. It also supports the standard industrial Modbus® protocol, DNP3 and IEC 60870-5-103.The IEC61850 protocol is native in the 615 series and therefore, thanks to the GOOSE messaging services, defined by the protocol itself, point-to-point communication is also possible over an Ethernet network which covers the entire substation.The configuration language of the sub-station enables use of processing tools for efficient configuration and activation of the substation devices.For applications where time is a critical factor, REF615 supports the synchroni-zation function over Ethernet by means of the SNTP protocol or on a separate bus using IRIG-B.

Pre-emptive condition monitoringFor continuous monitoring of operatio-nal availability, REM615 incorporates a complete range of monitoring functions for the circuit-breaker trip circuit. Accor-ding to the configuration of the device selected, the relay monitors the status of circuit-breaker stress and wear, the spring charging time of the circuit-breaker operating mechanism and the gas pressure of the arcing chambers. The relay also measures the circuit-breaker travel time and the number of circuit-breaker operations to collect basic information for scheduling suitable circuit-breaker maintenance.

For further information, see the Guide to the REM615 product.

Page 85: catalogo general Media Tensión (abb)

85

ApplicationRET615 is a protection and control relay for power transformers with two win-dings and generator transformer units.The RET615 protection is available in four standard configurations (A-B-C-D) to satisfy the most common star-centre grounding applications of power tran-sformers and the relative ground protec-tion diagrams.

Protection and controlAccording to the model, the RET615 series has the following protection functions:• 49 thermal overload• 50 instantaneous overcurrent• 51 overcurrent with inverse time • 51N ground fault (calculated)• 51G ground fault (measured)• 87T transformer differential• 87N ground fault interrupter restricted

to high or low impedance • 50BF circuit-breaker failure to open

RET615 also includes basic control functions which facilitate management of a circuit-breaker by means of the HMI (human-machine interface) front panel of the relay or by means of remote con-trols. To prevent unauthorized access and to protect integrity of the informa-tion, the IED is provided with a four-level authentication system based on the role of the user. Access control is carried out by means of the HMI front panel, the WEB HMI WEB Browser and the IED PCM600 management and control too

Multi-function transformer protection and control unit• Simple configuration via software• Protection, control, measuring and monitoring of power transformers, step-up

transformers and power transformer-generator units • Use in utility and industrial networks• Wide range of incorporated protection functions• Compact design• Withdrawable unit• Compliance with IEC 61850 Standards• Monitoring of operative conditions• Display with mimic diagram (option)• Inputs from RTD (option)

Standard Communication RET615 has native support for the new IEC 61850 Standard regarding communication between devices in the substations. The industrial Modbus® protocol is also available, as well as the consolidated DNP3 and IEC 60870-5-103 protocols.Implementation of the IEC61850 com-munication protocol for substations in RET615 foresees both vertical com-munication towards a higher system, and horizontal communication between the various IEDs. It includes the GO-OSE messaging services and remote parameter setting in accordance with 61850-8-1.The substation configuration language enables use of processing tools for ef-ficient configuration and for putting the substation devices into operation.In applications where precise event time marking is required, RET615 supports the synchronization function over Ether-net by means of the SNTP protocol or over a separate bus using IRIG-B.

Preventive monitoring A complete range of functions is availa-ble in RET615 for monitoring:• the unit itself (IRF Internal Relay

Failure).• opening circuit• state of circuit-breaker wear and

stress• operating mechanism spring charging

time• gas pressure of the poles• measurement of the circuit-breaker

run time • operation count thereby collecting the fundamental infor-mation for programming suitable circuit-breaker maintenance and optimizing management of the network.

For further information, see the Guide to the REM615 product.

RET 615

Page 86: catalogo general Media Tensión (abb)

86

Relays and multi-function units

RED 615

ApplicationRED615 provides high speed, longitu-dinal differential protection, with phase selection for overhead line and cable feeders in utility and industrial distribu-tion networks. RED615 is available in three standard configurations: a pure and simple line differential protection and two extended configurations with additional protection functions. Two RED615s interconnected over a com-munication link make up a completely selective protection diagram. The pro-tection for ring and meshed distribution networks generally requires unit pro-tection solutions, also applied in radial networks containing distributed power generation.

Line differential protection and control • Simple configuration via software• Line differential protection and control p with phase selection, at two ends• Perfectly harmonized for industrial and utility power plants, including meshed and

not fully connected distribution networks, with or without decentralized power generation

• Wide range of incorporated protection functions• Compact design• Withdrawable unit• Compliance with Standards IEC 61850• Monitoring of operative conditions• Display with mimic diagram (option)

Protection and controlAccording to the model, the RED615 series has the following protection functions:• 46 negative sequence or current

balance• 49 thermal overload• 50 instantaneous overcurrent• 51 overcurrent with inverse time • 51N ground fault (residual)• 51G ground fault (measured)• 67N directional ground overcurrent • 68 transformer inrush• 87L cable residual current• 50BF circuit-breaker not opening• 79 auto-reclosing (optional)

By means of the RED615 it is also pos-sible to control the circuit-breaker di-rectly locally by means of open / closed pushbuttons located on the display, or remotely it is connected to a supervision system.To prevent unauthorized access and keep integrity of the data, the relay is provided with a user authentication system based on a four-level role, with individual passwords for the level of inspector, operator, technician and ad-ministrator. Access control is carried out by means of the HMI on the front panel.

Binary signal transferBinary signal transfer (BST) can be used for transferring blocking and inter-trip signals as well as status and position information between the local and remote line ends. The BST function includes eight binary signals, transfers among the substations by means of protection signals via wire transferred onto the communication link. The BST signals go in both directions and the signal transfer time is extremely short, in the order of a few milliseconds. The BST signal and the RED615 logic allow customizable protection and control dia-grams to be set up, to make electrical plants which will be even more highly performing in future.

RED 615

Page 87: catalogo general Media Tensión (abb)

87

Standard Communication RED615 has native support for the new IEC 61850 Standard on communication in substations. The relay also supports the standard industrial Modbus® protocol, as well as the consolidated DNP3 protocols and IEC 60870-5-103.The IEC61850 protocol is native in the 615 series and therefore, thanks to the GOOSE messaging services, defined by the protocol itself, point-to-point communication over an Ethernet net-work which covers the entire substation is also possible.

Supervision of communication protection The protection communication channel between the line ends is continually supervised. Should the communication channel be interrupted or subject to interferences, the fast-acting line diffe-rential protection and all other functions are immediately blocked. This automa-tic limitation involves all the functions which rely on continuous availability of the protection communication channel. Supervision of the channel includes re-cognition of missing or delayed signals which carry analogue measurements or binary data. The resetting delay can be selected by the user.

Pre-emptive condition monitoring To guarantee operational availability of the protection, RED615 incorporates a range of monitoring and watchdog functions to supervise the hardware and software, the communication system, the circuit-breaker trip circuit and the CTs. Faults at CT level can cause un-warranted activation of the differential phase protection and the phase unba-lance protection.Therefore a CT monitoring system with rapid action immediately blocks opera-tion of the line differential protection and phase unbalance protection function on detection of an erratic CT signal. According to the configuration of the device selected, the relay monitors the state of circuit-breaker stress and wear, the spring charging time of the circuit-breaker operating mechanism and the gas pressure in the arcing chambers. The relay also measures the circuit-breaker run time and counts the number of circuit-breaker operations, therefore collecting the fundamental information for programming suitable maintenance of the circuit-breaker.

For further information, see the Guide to the RED615 product.

Page 88: catalogo general Media Tensión (abb)

88

Relays and multi-function units

Line protection and control multi-function unit• Simple configuration via software• Wide range of integrated protection functions• Withdrawable unit• Configurable operator interface with multi-lingual display • Non-volatile memory• Ample number of digital inputs and output contacts• Monitoring of operating conditions• Display with mimic diagram (optional)• Integrated synchronism, load shedding and AVR functions

The REU615 device is a relay for pro-tection, measurement and monitoring of utility substations and industrial electri-cal plants.It fully complies with the IEC61850 Standard on communication and inter-operability of automation devices for substations.

UseREU615 guarantees protections for che-cking voltage, frequency, load shedding, and synchronism (25): the B version also allows the AVR (automatic voltage regulator) function.REU615 is currently available in 2 stan-dard configurations (A-B) to respond to the various line protection and control requirements.

Protection and controlAccording to the version, the REU615 series has the following protection func-tions:• 27 Phase undervoltage• 59 Three-phase overvoltage• 59N Homopolar overvoltage• 47 Reverse sequence or voltage ba-

lance• 81 Frequency• 25 Synchronism check• 90 (AVR)

By means of the REU615 it is also possible to directly control the circuit-breaker, either locally by means of open /closed pushbuttons on the display, or remotely if it is connected to a supervi-sion system.To prevent unauthorized access and keep integrity of the data, the relay is provided with a user authentication system based on a four-level role, with individual passwords for the level of inspector, operator, technician and ad-ministrator. Access control is carried out by means of the HMI on the front panel.

Standardized communicationREU615 intrinsically supports the new IEC 61850 Standard, with regard to communication between the devices in substations. It also supports the standard industrial Modbus® protocol, DNP3 and IEC 60870-5-103.

The IEC61850 protocol is native in the 615 series and therefore, thanks to the GOOSE messaging services, defined by the protocol itself, point-to-point communication is also possible over an Ethernet network which covers the entire substation.

The configuration language of the sub-station enables use of processing tools for efficient configuration and activation of the substation devices.For applications where time is a critical factor, REU615 supports the synchroni-zation function over Ethernet by means of the SNTP protocol or on a separate bus using IRIG-B.

Busbar protection by means of the GOOSE messaging functionImplementation of the IEC 61850 Standard in REU615 also includes rapid point-to-point communication over the substation bus. By using GOOSE communication, the REU615 incoming and outgoing line relays of a substation operate in synergy so as to make up a stable, reliable and high speed protec-tion system for busbars. Good quality/price protection for busbars based on GOOSE communication is obtained simply by configuring the relays, and the operative availability of the protection is guaranteed by constant monitoring of the protection relays and by the GOOSE messaging function on the substation bus. Separate physical wiring between the switchgear units is not required for horizontal communication.

REU 615

Page 89: catalogo general Media Tensión (abb)

89

REAProtection system against electric arcs for distribution switchgear • Optical fibre technology • Extendable system• Universal application• Rapid trip (< 2.5 ms)• Selective protection• Automatic compensation of environmental luminosity• Self-monitoring of the components• Maintenance-free

Functions and characteristics- Total trip time less than 2.5 ms- Optic fibre sensors- Current measurement by means of

current transformers- Protection against circuit-breaker fault - Continuous self-monitoring of the

system- Compensation of environmental light

REA 101 central unit- Double electronic circuit-breaker ope-

ning control circuit- Selective trip with an additional unit- Optic fibre connection for rapid tran-

sfer of the signals- Alarm relay for circuit-breaker fault- Two RJ 45 ports for extension of the

five units per port

The REA unit makes a protection system against electric arcs inside the switchgear.It can be used in all types of switchgear and does not require structural interven-tions.In switchgear and electric plants, the REA system is an effective tool for incre-asing overall plant reliability. In plants which have been in service for a long time, the REA system also allows the switchgear residual life to be increased.The REA system is sensitive to the light developed by the arc. It is therefore able to identify faults extremely rapidly and to intervene equally rapidly. This allows the energy developed by the electric arc to be drastically limited and the amount of damage to be reduced.The REA system can be used in low and medium voltage switchgear.

Technical catalogue: 1MRS75029-MVM.

Units for finding faults REA 103 - Two fibre sensors for ring or radial con-

nection - Two signalling relays which can be acti-

vated by light

REA 105- Fibre sensor for ring or radial connection - Two outputs with high speed semicon-

ductor for circuit-breaker trip- CAN Communication bus between

two REA 101 units

REA 107- Eight optic sensors for radial connection - Two signalling relays which can be acti-

vated by light

Page 90: catalogo general Media Tensión (abb)

90

Relays and multi-function units

SUE 3000

N.C. N.C.

N.O.

Unit 1 Unit 2

N.O. N.C.

Multi-function unit for rapid changeover of the power supply systems • Changeover in 30 ms • Simple modification and upgrading of functions by means of the configuration

software • Graphic type operator interface with LCD display • Man-machine interface separate from the central unit • Field device for substation automation systems • Configuration with two or three circuit-breakers • Integrated fault recorder• Inputs/outputs of analog type and static digital type and with relay

HSTS system in the configuration with two circuit-breakers without bus-tie: when no voltage is detected on the main power supply unit of the switchgear, the reserve unit closing command and the main unit opening command is launched simultaneously.

HSTS system in the configuration with three circuit-breakers with bus-tie: when no voltage is detected on one of the two power supply, the bus-tie closing command and the opening command of the unit without voltage is launched simultaneously.

The multi-function SUE 3000 unit allows rapid changeover between two alternative power supply systems.The HSTS (High Speed Transfer System) carried out by SUE 3000, is the ideal solution for critical industrial processes, where a power cut - even for just one or two cycles - can cause production process stoppage and considerable damage.This system can be fully integrated in the switchgear and is able to changeover the power supply of the main switchgear unit to an emergency alternative within a few milliseconds. Long and costly machine stoppages, damage to production equipment and production restarting downtimes are thereby avoided.The SUE 3000 HSTS allows changeover times of 100 ms to be obtained with traditional type circuit-breakers and of 30 ms with VM1 circuit-breakers in the version with rapid magnetic actuator.

Technical catalogue: 1HDK400075.

Unit 1 Unit 2

Communication- SPABUS- LON (ABB LAG 1.4)- Modbus RTU - IEC 60870-5-103 with VDEW

extension

Digital inputs and outputs with relay- 14 inputs per card- 8 outputs per card

Static digital inputs and outputs - 14 inputs per card- 9 outputs per card

Analog inputs and outputs - 6 inputs 0...20 mA or 4...20 mA - 4 outputs 0...20 mA or 4...20 mA

Page 91: catalogo general Media Tensión (abb)

91

Page 92: catalogo general Media Tensión (abb)

92

We offer wide range of Conventional Instrument Transformers as well as Electronic Instrument transformers, shortly called Sensors.

Our conventional Instrument Transformer portfolio includes various types of products for indoor and outdoor applications in medium voltage systems.Our main line indoor Current and Voltage transformers are designed in accordance to DIN 42600 standard thus very well fit to ABB switchgear portfolio as well as to OEM switchgear manufacturers. The indoor portfolio includes also other products used for different applications (GCBs, Generator outlets, summation CTs, etc.).The variety of our conventional ITs is used also in the outdoor environment, where hydrophobic cycloaliphatic epoxy insulation ensures the proper function of product in the heavy polluted conditions.

Reference standardsAll products comply with IEC and all IEC based standards (BS, GOST, AS) as well as IEEE (ANSI) standard. The main indoor IT portfolio is designed according to DIN dimensional standard. We are also able to deliver our products based on customer requirements.

Instrument transformers and sensors IEC

Our offering includes electronic Instrument transformers as an alternative to conventional technology. The range of Sensors is covering main ABB switchgear applications and together with IED brings wider possibilities in system solutions.

Main product typesThe conventional and electronic Instrument transformers are offered and delivered in a number of type series, which are used for measurement and protection purposes at an insulation level from 3,6 kV to 40,5 kV for both indoor and outdoor conditions.

Page 93: catalogo general Media Tensión (abb)

93

Current Transformer Support (Post) Type TPUA current transformer so arranged that it acts as a support for the conductor in the primary circuit.TPU current transformers are suitable for the current ABB air insulated switchgear portfolio, OEM partners

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 6 secondary windings (12 secondary

terminals)• Secondary or primary reconnectable versions• Most standards available including DIN 42600 dimension standard • Capacitive voltage divider in CT body for voltage indicator available

Ratings

Highest voltage for equipment kV 3.6 – 36 (40.5)

Primary current A 10 - 3 200

Secondary current A 1 or 5

Frequency Hz 50 or 60

Current Transformer Support (Post) Type TPEA current transformer so arranged that it acts as a support for the conductor in the primary circuit.TPE current transformers have lower ratings suitable for secondary distribution system, OEM Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with one or two secondaries only• Secondary reconnectable versions• Most standards available • Capacitive voltage divider in CT body for voltage indicator available

Ratings

Highest voltage for equipment kV 3,6 – 24(25)

Primary current A 30 - 1 250

Rated short time thermal current kA 25/1 sec

Secondary current A 1 or 5

Frequency Hz 50 or 60

Page 94: catalogo general Media Tensión (abb)

94

Instrument transformers and sensors IEC

Current Transformer Support (Post) Type KOFAA current transformer so arranged that it acts as a support for the conductor in the primary circuit.KOFA current transformers are suitable for the former ABB air insulated switchgear like MH, etc., OEM

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Primary reconnectable versions available• Most standards available Ratings

Highest voltage for equipment kV 3.6 – 24

Primary current A 10 - 2 500

Secondary current A 1 or 5

Frequency Hz 50 or 60

Current Transformer Support (Post) Type IHBFA current transformer so arranged that it acts as a support for the conductor in the primary circuit.IHBF current transformers are suitable for the former ABB air insulated switchgear like Safesix, etc., OEM

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Secondary or primary reconnectable versions• Most standards available

Ratings

Highest voltage for equipment kV 3.6 – 24

Primary current A 10 - 2 000

Secondary current A 1 or 5

Frequency Hz 50 or 60

Page 95: catalogo general Media Tensión (abb)

95

IEC

Current Transformer (Bar Primary) Bushing Type TTRA current transformer with bar primary conductor so constructed that it can be used as a bushing.TTR current transformers are suitable as a bushing between two AIS compartments, different switchboards, OEM

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Secondary reconnectable versions available

Ratings

Highest voltage for equipment kV 3.6 – 24 (25)

Primary current A 100 - 2 500

Secondary current A 1 or 5

Frequency Hz 50 or 60

Current Transformer Bushing Type BB(O)A current transformer without primary conductor but with primary insulation of its own which can be used as a bushing.

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Secondary or primary reconnectable versions

Ratings

Highest voltage for equipment kV 3.6 – 24 (25)

Primary current A 600 - 5 000

Secondary current A 1 or 5

Frequency Hz 50 or 60

Page 96: catalogo general Media Tensión (abb)

96

IEC

Current Transformer Bus Type KOKSA current transformer without primary conductor, but with primary insulation which can be fitted directly over a conductor or busbar.

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 4 secondary windings• KOKS 12, KOKS 17.5 current transformers are suitable for the current ABB air

insulated switchgear portfolio, OEM partners• KOKS 24 current transformers are suitable for outlets of generators, etc.

Ratings

Highest voltage for equipment kV 3.6 – 17.5 ... KOKS 12, KOKS 17.5

Primary current A 1 000 - 4 000

Highest voltage for equipment kA 17.5 - 24 ... KOKS 24

Primary current A 4 000 - 8 000

Secondary current A 1 or 5

Frequency Hz 50 or 60

Current transformer Special Application Type BDA current transformer for assembling on the cable, busbar, bushing ,...BD current transformers are suitable for the current ABB air insulated switchgear portfolio, OEM partners

Characteristics• Indoor dry type, • For measuring and protection • Secondary reconnectable versions• Most electrical standards available

Ratings

Highest voltage for equipment kV 0.72

Primary current A 100 – 1250 ... BD version A, B, C,

Primary current A 100 – 2 500 ...BD-00

Secondary current A 1 or 5

Frequency Hz 50 or 60

Instrument transformers and sensors

Page 97: catalogo general Media Tensión (abb)

97

IEC

Current transformer Special Application Type BP

A current transformer for outlets of generator, etc.

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Secondary reconnectable versions• Most electrical standards available

Ratings

Highest voltage for equipment kV 3.6 – 17.5

Primary current A 2 000 - 10 000

Secondary current A 1 or 5

Frequency Hz 50 or 60

Cable Current transformer Type KOLMA and KOLASuitable for the measurement of the sum of threephase currents in a 3-phase cable. Under normal operating conditions this sum is zero. In the event of an earth-fault the sum of the currents is equal to the earth-faul current and a corresponding current flows in the secondary.These transformers are used together with static earth-fault relays. The cable current transformers can generally be used when measuring the residual current e.g. to prewarn of, or locate an earth-fault. An busbar or cable serves as the primary conductor.

Ratings

Rated voltage kV 0.72 kV

Insulating test voltage 50 Hz 1 min kV 3 kV (IEC 60044-1)

Frequency Hz 50 Hz (60 Hz)

Rated thermal current 1.2 x I pn

Short-time withstand current Ith 1 s 60 x I pn

Peak withstand current Idyn 2.5 x Ith

Secondary terminals For 6 mm2 conductor

Operating temperature range °C –5...+40

Page 98: catalogo general Media Tensión (abb)

98

IEC

Cable Current transformer Type KOKM and KOKUCurrent transformers are suitable for measuring of phase currents. A busbar or cable serves as the primary conductor. Series KOKM current transformers can also be used for measuring the phase current at voltages even higher than 0.72 kV (for KOKM 06) or 1.2 kV (for KOKM 1), if the insulation of the primary conductor fulfils the respective Standards for the operating voltage. The secondary winding and ring shaped iron core is cast in resin which has good electrical and mechanical properties.

Transformer type KOKM KOKU

Rated voltage Um kV 0.72 or 1.2 0.72 or 1.2

Power frequency test voltage Up (1 min) kV 3 or 6 3 or 6

Lighting test voltage Upp kV - -

Frequency fn Hz 50 lub 60 50 lub 60

Max. primary current Ipn A 50 ÷ 10 000 50 ÷ 10 000

Rated secondary current Isn A 1 lub 5 1 lub 5

Rated thermal current Icont A 1.2 x Ipn 1.2 x Ipn

Short-time withstand current Ith (1 sec) kA 60 x Ipn 60 x Ipn

Peak withstand current Idyn kA 2.5 x Ith 2.5 x Ith

Secondary terminals For 6 mm2 conductor For 6 mm2 conductor

Operating temperature range °C - 25 … + 40 - 35 … + 40

Transport and storage °C - 40 … + 55 - 65 … + 55

Electrical standards IEC, VDE, ANSI, BS, AS, CAN IEC, VDE, ANSI, BS, AS, CAN

Instrument transformers and sensors

Page 99: catalogo general Media Tensión (abb)

99

IEC

Power transformer solution Type KOLTCurrent transformers type KOLT have neither housing nor primary winding. Under operating conditions the primary winding is the power transformer’s bushing insulator, which is at the same time the main insulation of the current transformer.They are suitable for mounting inside power transformers and are suitable for operating immersed in oil, under conditions of moderate and tropical climate. These current transformers are designed for supplying measurementand protection circuits of power systems operating under rated frequency of 50 Hz.

Type KOLT

Primary current Ipn A 100 - 15 000

Rated secondary current Isn A 1 ÷ 5

Insulation level 0.72 / 3 / -

Range of rated output Sn VA 1 - 90

Number of windings 1 - 4

Conformity with Standards IEC, PN-EN, SEV, VDE, ANSI, BS, CAN, CSA, GOST

Accuracy class acc. to IEC 0.2s; 0.5s; 0.2; 0.5; 1; 3; 5; 5P; 10P; PX

FS 5; 10

ALF 5; 10; 15; 20; 25; 30

Rated frequency f Hz 50, 60

Short-time withstand thermal current Ith (1 sec) A 100xIpn max. 100 kA

Insulation class acc. to Idyn A 2.5xIth max. 250 kA

Insulation level acc. to IEC B

Page 100: catalogo general Media Tensión (abb)

100

IEC

Single pole insulated voltage transformer TJCSingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJC voltage transformers are suitable for the current ABB air insulated switchgear portfolio and OEM partners.

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Most standards available, including DIN 42600 dimension standard • Reconnectable versions available

Ratings

Highest voltage for equipment kV 3.6 – 40.5

Primary current V 3 000/V3 – 35 000/V3

Secondary current V 100/V3 - 120/V3, 100/3-120/3

Frequency Hz 50 or 60

Single pole insulated voltage transformer TJESingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJE 3, TJE 4 voltage transformers have lower ratings and are suitable for mine switchboards, OEM

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Most electrical standards available• Reconnectable versions available

Ratings

Highest voltage for equipment kV 3.6 – 12

Primary current V 3 000/V3 – 10 000/V3

Secondary current V 100/V3 - 120/V3, 100/3-120/3

Frequency Hz 50 or 60

Instrument transformers and sensors

Page 101: catalogo general Media Tensión (abb)

101

IEC

Single pole insulated voltage transformer with fuse TJPSingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJP transformer is equipped with fuse connected to primary winding

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Various fuses from 300 mA to 6.3 A• Most electrical standards available• Reconnectable versions available

Ratings

Highest voltage for equipment kV 3.6 – 36

Primary current V 3 000/V3 – 30 000/V3

Secondary current V 100/V3 - 120/V3, 100/3-120/3

Frequency Hz 50 or 60

Double pole insulated voltage transformer TDCA voltage transformer which has all parts of its primary winding, including terminals, insulated from the earth at a level corresponding to its rated insulation level.

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Most standards available, including DIN 42600 dimension standard

Ratings

Highest voltage for equipment kV 3.6 – 36 (38.5)

Primary current V 3 000/V3 – 35 000/V3

Secondary current V 100 - 200

Frequency Hz 50 or 60

Page 102: catalogo general Media Tensión (abb)

102

IEC

Single pole voltage transformer for special application KGUGI

Single pole insulated voltage transformer with high power output,

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Most electrical standards available

Ratings

Highest voltage for equipment kV 24 – 36

Primary voltage V 15 000/V3 – 30 000/V3

Secondary voltage V 100/V3 - 120/V3, 100/3-120/3

Thermal burden VA 2000

Frequency Hz 50 or 60

Double pole voltage transformer for special application KGUG Single pole insulated voltage transformer with high power output

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with one secondary winding• Most electrical standards available

Ratings

Highest voltage for equipment kV 24 – 36

Primary voltage V 15 000 – 30 000

Secondary voltage V 100 - 120

Thermal burden VA 2 000

Frequency Hz 50 or 60

Instrument transformers and sensors

Page 103: catalogo general Media Tensión (abb)

103

IEC

Special application single pole insulated voltage transformer TJC_GSingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJC _G voltage transformers are suitable for installation in generators and CBs

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to

2 secondary windings• Special dimension

Ratings

Highest voltage for equipment kV 3.6 – 36

Primary current V 3 000/V3 – 30 000/V3

Secondary current V 100/V3 - 120/V3, 100/3-120/3

Frequency Hz 50 or 60

Special application single pole insulated voltage transformer TJP_FSingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJP_F voltage transformers are suitable for installation in ABB AIS and OEM

Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Special dimension • Various fuses from 2A to 6.3 A

Ratings

Highest voltage for equipment kV 3.6 – 17.5

Primary current V 3 000/V3 – 15 000/V3

Secondary current V 100/V3 - 120/V3, 100/3-120/3

Frequency Hz 50 or 60

Page 104: catalogo general Media Tensión (abb)

104

Combi Sensor Support Type KEVCDAn electronic combined transformer so arranged that it acts as a support for the conductor in the primary circuit.

CharacteristicsThe combination of Rogowski coil principle with Resistive divider. • Indoor dry type, cast resin insulated• For measuring and protection • DIN 42600 dimension standard • Capacitive voltage divider for voltage indicator available

Ratings

Highest voltage of equipment kV 12 – 24

Rated continuous primary current A 10-3 200

Current rated transformation ratios at 50 Hz 80A/150mV; 1600A/150mV

Voltage rated transformation ratio: Hz 10000 : 1

ApplicationInside the switchgear as support type

IECInstrument transformers and sensors

Sensors – Electronic Instrument TransformersCurrent Sensors The current sensing is based on Ro-gowski coil principle, which is uniformly wound coil over the air core immune to any risk of saturation and linear over the wide range of measured currents. The output from the coil proportional to change of current is voltage, which needs to be integrated to produce the output as current.

Voltage SensorsThe voltage sensing is based on resistive or capacitive dividers with the constant division ration of 10000:1. Due to absence of ferro-magnetic material the voltage sensor is immune to ferro-resonance problems.

Combi SensorsThe sensor combines Current and Voltage sensing principles in one unit. The Rogowski coil for current sensing is combined with resistive or capacitive dividers in order to optimize the functionality of product based on the customer specification.

Product types

Support (Post)• KEVCD

Bushing• KEVCY_RE• KEVCY_SA2; KEVCY_SB3

Special Application• KEVCR• KECR• KEVA

Cable• KECA

Page 105: catalogo general Media Tensión (abb)

105

Bushing Sensor Type KEVCY_REAn electronic combined instrument transformer with primary conductor so constructed that it can be used as a bushing.

CharacteristicsThe combination of Rogowski coil and Capacitive divider principles. This is very small and compact bushing type sensors for SF6 insulated switchgears.• Indoor dry type, cast resin insulated• For measuring and protection • With plug according to EN 50180 & 501• Capacitive voltage divider for voltage indicator available

Ratings

Highest voltage of equipment kV 24

Rated continuous primary current A 630

Current rated transformation ratios at 50 Hz 80A/150mV

Voltage rated transformation ratio: Hz 10000 : 1

ApplicationSF6 insulated switchgear use (Safe plus)

Bushing Sensor Type KEVCY_SA and KEVCY_SBAn electronic combined instrument transformer with primary conductor so constructed that it can be used as a bushing.

CharacteristicsThe combination of Rogowski coil and Capacitive divider principles. These are very small and compact bushing type sensors for outdoor SF6 insulated switch disconnectors.• Indoor dry type, cast resin insulated• With plug according to EN 50180 & 50181 connected to insulator for outdoor use• For measuring and protection • Capacitive voltage divider for voltage indicator available

Ratings

Highest voltage of equipment kV 24

Rated continuous primary current A 630

Current rated transformation ratios at 50 Hz 80A/150mV

Voltage rated transformation ratio: Hz 10000 : 1

ApplicationSF6 insulated outdoor switch

IEC

Page 106: catalogo general Media Tensión (abb)

106

Special application Sensor Type KECR An electronic current transformer without primary conductor but with primary insulation so constructed that it can be fitted directly over a conductor of the circuit-breaker.

CharacteristicsThe product is based on Rogowski coil principle. This unique design of sensor integrated with ABB circuit breaker type eVM1 and ABB IED in low voltage compartment creates opportunity for new possibilities in Switchgear designs. • Indoor dry type, cast resin insulated• For measuring and protection

Ratings

Highest voltage for equipment kV 17,5

Rated continuous thermal current A 1250

Current rated transformation ratios at 50 Hz 180A/150mV

Application• Integrated solution with ABB circuit breakers and IEDs• Any switchgear application where Sensor ratings are suitable

IECInstrument transformers and sensors

Special application Sensor Type KEVCR 24 AC2, 24 OC2An electronic current transformer with primary conductor so constructed that it can be used on a board of circuit breaker.

CharacteristicsThe product is based on Rogowski coil principle. This unique design of sensor integrated with ABB circuit breakers type VD4/R and HD4/R and ABB IED on board the breaker creates new possibilities in Switchgear designs. • Indoor dry type, cast resin insulated• For measuring and protection

Ratings

Highest voltage of equipment kV 24

Rated continuous thermal current A630 (KEVCR 24OC2);

1250 (KEVCR 24AC2)

Current rated transformation ratios at 50 Hz 250A/150mV

Application• Integrated solution with ABB circuit breakers and IEDs• Any switchgear application where Sensor ratings are suitable

Page 107: catalogo general Media Tensión (abb)

107

Special application Sensor Type KEVA (for AIS)A single phase electronic voltage transformer.

CharacteristicsThe voltage sensor is based on a resistive divider principle. This sensors is an ideal solution for Air Insulated switchgears with very dynamic voltage ratings and constant transformation ratio. The size and weight of this design are optimized to the maximum.• Indoor dry type, cast resin insulated• For measuring and protection

Ratings

Highest voltage for equipment kV 24

Voltage rated transformation ratio: 10 000 : 1

ApplicationAny air insulated switchgear application

Cable Current Sensor Type KECA, KECA 250An electronic current transformer for assembly on the insulated cable, insulated bus-bar or conductor, bushing, etc.

CharacteristicsThe Current sensor is based on Rogowski coil principle can be used in low voltage cable applications. Two designs of sensor capsulation provide different possibilities of use. • Indoor dry type, cast resin insulated• For measuring and protection

Ratings

Highest voltage for equipment kV 0.72

Rated continuous thermal current A 2000

Current rated transformation ratios at 50 Hz 80A/300A/800A/150mV – Al case sensor

Current rated transformation ratios at 50 Hz250A/150mV – plastic case sensor

ApplicationAny kind of low voltage cable application

IEC

Page 108: catalogo general Media Tensión (abb)

108

Types available for outdoor installation

Current transformers – TPO 6x.xx (... 24 kV)– TPO 7x.xx (... 40.5 kV)

Single-pole voltage transformers– TJC 6 (... 24 kV)– TJC 7 (... 40.5 kV)

Two-pole voltage transformers – TJP 6.x (... 24 kV)

• Rated primary current from 10 A to 8000 A according to types

• Rated secondary current 1 A, 2 A, 5 A

• Frequency 50 - 60 Hz

• Class Windings: 0.1 - 0.2 - 0.25 - 0.5 - 0.55 - 1 - 3 Safety factor: 5 - 10 Protection: 5 P - 10 P Overcurrent factor: 5 - 10 - 15 - 20

• Special class PX (IEC 60044-1) - Uk, Rct, Ik

• Primary rated voltage from 3 kV to 35 kV (phase-earth Un / √ 3)

• Rated secondary voltage 100 V - 110 V - 100/√ 3 V - 110/√ 3 V - 100/3 V - 110/3 V

• Frequency 50 - 60 Hz

• Class Measurement winding: 0.1 - 0.2 - 0.5 - 1 Primary winding: 3 P - 6 P Auxiliary winding: 6 P

Current transformers Voltage transformers

IECOutdoor instrument transformers

Page 109: catalogo general Media Tensión (abb)

109

VT GuardAnti-ferroresonance device for voltage measurement circuits• Low operating resistance • High resistance in the case of earth fault• Installation on DIN rail in low voltage compartment• Very limited dimensions• Applicable to all types of voltage transformer • Protection of a set of three transformers in open delta configuration • Highly reliable

Characteristics

Rated voltage 100 … 200 V

Area of imperceptibility 0 … 20 V

Damping time at 100 V 1 s

Ambient operating temperature - 10 °C … + 55 °C

Humidity up to 90%

Minimum storage and transport temperature down to – 30 °C

Red LED operation for earth fault

Technical catalogue No. 1VCL000031

VT Guard is a device studied to eliminate the phenomenon of ferroresonance in measurement circuits with voltage transformers. The device is particularly recommended in networks with an earthing connection. The phenomenon of ferroresonance can take place in this type of network for various reasons and can cause damage, due to overload, of the voltage transformers with the secondary winding connected to the earthing circuit.The VT Guard device has the peculiarity of coming into operation when the phenomenon appears and of remaining inactive in the case of natural unbalance between the system phases.

Instrument transformer protection IEC

Page 110: catalogo general Media Tensión (abb)

110

Instrument transformers ANSI

Toroidal current transformers for indoor installation• Application in isolated circuits for low voltage• High-resistance polycarbonate insulation • Passage hole available with double diameter• Characteristic curves and test reports available on request• Component recognised as conforming to UL Standards

Characteristics

Insulation voltage V 600

Impulse withstand voltage kV 10

Rated frequency Hz 25 … 400

Rated primary voltage A 50 … 5000

Dynamic resistance 180 x rated current

Thermal resistance 80 x rated current x 1s

Continuity factor

- primary current 50-4000: 1.33 at 30 °C (ambient temperature)

1.00 at 55 °C (ambient temperature)

- primary current 5000: 1.00 at 30 °C (ambient temperature)

0.5 at 55 °C (ambient temperature)

Technical catalogue 1VAP428781

Voltage transformers for indoor installation• Application for metal-clad medium voltage switchgear• Polycarbonate and polyurethane insulation formed under vacuum• Prepared with three protection fuses• Aluminium metallic anticorrosion base• Can be installed in different positions• Characteristic curves and test reports available on request• Component recognised as conforming to UL Standards

Characteristics

Insulation voltage kV 8.7 15

Impulse withstand voltage kV 75 110

Rated frequency Hz 60 60

Rated primary voltage V 2 400 14 400

Thermal resistanceVA 1500 at 30 °C (ambient temperature)

VA 1000 at 55 °C (ambient temperature)

Precision class at 6 Hz according to IEEE Standards

- 0.3 W, X, Y, Z, and 0.6 ZZ at 120 V

- 0.3 W, X, M, Y, and 1.2 Z at 69.3 V

Technical catalogue No. 1VAP4295

Page 111: catalogo general Media Tensión (abb)

111

Complete Product Portfolio for switchgear applications• Window type current transformers suitable for MV and LV switchgear

applications.• Dry-type voltage transformers encapsulated in polyurethane material.• Control Power Transformers (CPTs) encapsulated in epoxy resin.• Generator and Isolated-phase Bus Current Transformers

0.6 kV current transformers in plastic case• Current transformers enclosed in a case made of impact resistant polycarbonate.• Ratios range from 50:5 through 6000:5• Metering accuracies available from 0.3B-0.1 through 0.3B-1.8• Relaying accuracies available from C5 through C800.• Both 50 and 60 Hz designs are available.• These transformers meet applicable IEEE and NEMA standards and are UL

Recognized Components.• Applications

- Medium and low voltage switchgear- Distribution circuit-breakers.

5 kV and 15 kV indoor control power transformers (CPTs) for switchgear applications• Self-cooled, single-phase, dry-type design.• Nominal primary voltages range from 2.4 kV to 14.4 kV (60 Hz).• Secondary voltages are configured for series/parallel operation at 120 V or 240 V.• Standard basic insulation level of 60 kV for 5 kV applications and 95 kV

for 15 kV applications.• Available with 1 ± 7.5 % or 2 ± 2.5% primary taps.• The high-voltage coil is vacuum encapsulated in epoxy to seal out moisture and

contaminants, and to provide a higher ability to withstand short-circuit forces than conventional dry type transformers.

• Meets all applicable IEEE C57.13 requirements, including full-wave and chopped-wave impulse tests.

• CPTs are UL recognized components.

ANSI

Page 112: catalogo general Media Tensión (abb)

112

ANSI

5 kV – 36 kV indoor voltage transformers• Designed for service in metalclad MV switchgear.• Encapsulated in polyurethane resin.• 60 kV through 200 kV basic insulation level (BIL).• Primary voltage range from 0.8 kV through 34.5 kV.• Secondary voltage ranges from 33.3 V through 500 V.• Phase to earth, phase to neutral, and phase to phase designs are available.• Metering accuracies: 0.15, 0.3, and 0.6.• Burdens: W (12.5 VA) through ZZ (400 VA).• These transformers meet all applicable ANSI and CSA standards. IEC designs are

also available.• Frequency: 50 and 60 Hz.• Metering accuracies available from 0.3B-0.1 through 0.3 B-1.8.• Relaying accuracies available from C5 through C800.• These transformers meet applicable IEEE and NEMA standards and are UL

recognized components.• Applications

- Revenue metering- Protection- Control power (thermal VA)

Generator and isolated-phase bus current transformers (GCTs and ISO-CTs)• Full range of indoor/outdoor class, shielded and un-shielded, board and resin

cast current transformers specially designed for generation metering and protection.

• In isolated phase bus compartments a ISO-Phase bus current transformer centrally positioned around non-insulated bus with adequate air space can satisfy the dielectric requirements of the bus rating.

• 0.6 kV class / 10 kV BIL rated.• Standard insulation ratings of 130°C and 155°C for high temperature

applications.• All units provided with certified test reports documenting all results in accordance

with IEEE C57.13 and/or IEC 60044-1 (and 60044-6 when applicable).• Windows sizes range from 2.5” (63.5mm) to 41” (1040mm).• Metering accuracy up to 0.15 (IEEE) with burdens of B-0.1 up to B-1.8.• Protection class ratings up to C800.

Instrument transformers

Page 113: catalogo general Media Tensión (abb)

113

5 kV - 48 kV instrument transformers for outdoors • Revenue metering and protection applications.• Encapsulated in hydrophobic cycloaliphatic epoxy or polyurethane resin.• 60 kV through 250 kV basic insulation level (BIL).• Primary voltage ranges from 0.8 kV through 48 kV• Phase to earth, phase to neutral, and phase to phase designs are available.• Metering accuracies: ANSI 0.15, 0.3, 0.6, and 1.2.• Voltage transformer burdens: W (12.5 VA) through ZZ (400 VA)• Current transformer burdens: 0.1 (2.5VA) through 1.8 (45 VA).• Current transformer protection accuracies available from C5 through C800.• These transformers meet all applicable ANSI and CSA standards. IEC designs are

also available.• Frequency: 50 and 60 Hz.

Instrument transformers for outdoors • Medium voltage instrument transformers for outdoor revenue metering and

protection applications.• Low voltage outdoor/indoor current and voltage transformers for revenue

metering and protection applications.

5 kV - 36 kV indoor voltage transformers• Designed for service in metalclad MV switchgear.• Encapsulated in polyurethane resin.• 60 kV through 200 kV basic insulation level (BIL).• Primary voltage range from 0.8 kV through 34.5 kV.• Secondary voltage ranges from 33.3 V through 500 V.• Phase to earth, phase to neutral, and phase to phase designs are available.• Metering accuracies: 0.15, 0.3, and 0.6.• Burdens: W (12.5 VA) through ZZ (400 VA).• These transformers meet all applicable ANSI and CSA standards. IEC designs are

also available.• Frequency: 50 and 60 Hz.• Metering accuracies available from 0.3B-0.1 through 0.3 B-1.8.• Relaying accuracies available from C5 through C800.• These transformers meet applicable IEEE and NEMA standards and are UL

recognized components.• Applications

- Revenue metering- Protection- Control power (thermal VA)

ANSI

Page 114: catalogo general Media Tensión (abb)

114

ANSI

Low voltage outdoor/indoor current and voltage transformers• 0.6 kV class / 10 kV BIL rated.• Molded in thermoplastic rubber (TPR) material.• Window and bar type current transformer designs available.• Metering accuracies: ANSI 0.3, 0.6 and 1.2.• Voltage transformer burdens: W (12.5 VA) through Y (75 VA)• Current transformer burdens: 0.1 (2.5VA) through 1.8 (45 VA).• Current transformer protection accuracies available from C5 through C400.

Special products• Bushing current transformers for power transformers and power circuit-breakers

insulated with cotton or polyester tape.• Generator and isolated-phase bus current transformers.• Split-core current transformers.• Auxiliary voltage and current transformers.

5 kV - 36 kV indoor voltage transformers• Designed for service in metalclad MV switchgear.• Encapsulated in polyurethane resin.• 60 kV through 200 kV basic insulation level (BIL).• Primary voltage range from 0.8 kV through 34.5 kV.• Secondary voltage ranges from 33.3 V through 500 V.• Phase to earth, phase to neutral, and phase to phase designs are available.• Metering accuracies: 0.15, 0.3, and 0.6.• Burdens: W (12.5 VA) through ZZ (400 VA).• These transformers meet all applicable ANSI and CSA standards. IEC designs are

also available.• Frequency: 50 and 60 Hz.• Metering accuracies available from 0.3B-0.1 through 0.3 B-1.8.• Relaying accuracies available from C5 through C800.• These transformers meet applicable IEEE and NEMA standards and are UL

recognized components.• Applications

- Revenue metering- Protection - Control power (thermal VA)

Instrument transformers

Page 115: catalogo general Media Tensión (abb)

115

Bushing current transformers (BCT)• Specially made designs to fit a wide range of applications• Tape wound insulation made of cotton or polyester tape• Window sizes from 2.5” (63.5mm) to 41” (1040mm).• BCTs can provide up to 0.15 (IEEE) metering accuracy with burdens of B-0.1

up to B-1.8.• Protection class up to C800.• Continuous rated current factors of up to 4.0 times rated current.• Outdoor slip-over bushing current transformers are also available.

Split-core current transformers• 0.6 kV class / 10 kV BIL rated.• Convenient mounting around primaries which cannot be opened.• Primary current ratios are available from 100:5 to 5000:5.• Metering and protection classes available.• Two product families available for a variety of applications.• These transformers can provide a 0.3 ANSI/IEEE accuracy class with burdens

B-0.1 up to B-1.8.

Auxiliary current and voltage transformers• 0.6 kV class / 10 kV BIL rated.• Both current and voltage units available.• Used to change the effective voltage/current ratio for operating meters,

protection relays and other control devices.• Available in virtually any combination of ratio and accuracy.• Due to superior saturation characteristics, these transformers generally do not

saturate under extreme high fault currents.

ANSI

Page 116: catalogo general Media Tensión (abb)

116

Page 117: catalogo general Media Tensión (abb)

117

Modular prefabricated solutions for photovoltaic fields

The substation is a fundamental component of the plant for the electrical apparatus protection function and safety of operating personnel.

ABB uses prefabricated substations made of concrete whose metal reinforcement makes an equipotential homogeneous grounding mesh over the entire structure which, when then connected to the grounding system, protects the internal appa-ratus against atmospheric overvoltages and limits the effects of step and contact voltages to negligible values.

The whole structure is fully factory-assembled and tested in conformity with the CEI EN 61330 Standard. After this, it is ready to be placed on the worksite to then be put into service. Installation activities are therefore limited to cable connections among the various different substations and the field switchgear.

Transport of the substation does not require use of any exceptional means of transport. Should it be necessary to move the substation to another location, the operation is simple and rapid.

The substations are fitted with a base with the same characteristics as the housing, whose plan has the same dimensions as the substation. The base is supplied to bu-ild a sturdy platform to rest the substation on and to allow convenient cable entry. For this purpose, a series of pre-established knockout holes are provided in the walls.

The ground where the substation is to be positioned must be suitably prepared by digging and laying a layer of draining gravel to rest the base on.

The substations offered by ABB consist of a coordinated assembly of components subjected to type tests, including:– Medium voltage switchgear– Low voltage switchboards– MV/LV transformers– Inverters– Panels and auxiliary devices– Lighting plant– Connections.

The substations only have the name of the ABB manufacturer on the nameplate, which is the guarantee for the whole unit.

ABB has developed a full range of modular solutions for standard power photo-voltaic plants, incorporating its components optimally inside complete, turnkey systems, for each type of network configuration: radial, ring and distributed.

Page 118: catalogo general Media Tensión (abb)

118

Substation automation systems

SD-VIEW Concept Modular automation systems for power control and management

The SD-View Concept systems use advanced and consolidated technological solutions to manage the supervision, command, control, protection and automation functions. They are normally used in management of electrical plants in industries, infrastructures, the service sector and utilities.Using the SD-View Concept systems offers important advantages, such as: improvement of the energy quality, service continuity, reduction of consumption, advanced diagnosis, increased safety, simplicity of management, etc. By exploiting the modularity of SD-View Concept, it is possible to construct flexible architectures, aimed at the specific requirements of the plant and of the administrator, ensuring perfect integration with field instruments (high voltage, medium voltage and low voltage protection apparatus, motor control switchgear, air conditioning stations, fire-fighting stations, etc.).

Characteristics• User-friendly standard symbols; when required, the

graphics can be adapted to particular customer needs • Fully scalable: information, peripherals and computers can

be added at later stages• Completely flexible (there are no limits to the type of

applications)• Architectures can be made to measure and in respect of

the plant limits• Client-Server modes easily implemented (by placing

additional operator panels elsewhere other than in the plant does not require software development)

• Redundant architectures (immunity to apparatus faults)• Multi-language function (changeover of the operator

language without having to restart the machine)• Open towards other data importation/exportation systems,

in the standard ODBC data base formats.

Example of HSI application

Example of SD-View Panel Control application

Page 119: catalogo general Media Tensión (abb)

119

Example of SD-View Extend architecture

The SD-View Concept systems are available in three architectures:

SD-View BasicAllows supervision of a small power substation (a few concentrated switchgear) consisting of medium voltage and low voltage apparatus, and emergency power supply systems to be carried out.

SD-View Medium This is the solution suitable for supervising several distributed electrical substations (many pieces of distributed switchgear), consisting of medium voltage, low voltage apparatus, emergency UPS and zone switchgear. SD-View Extend Allows management of several large and distributed electrical substations, each of which consists of various pieces of high voltage, medium voltage and low voltage apparatus, emergency UPS, zone switchgear and other apparatus. The architecture also allows introduction of basic automation logics.Apart from the architectures described above, depending on the size of the installation and orientated towards management of power distribution, SD-View Concept can take on other functional roles (technological, building, Motor Control Center, etc.). Among these, we mention the two most widely used configurations.- SD-View Energy Profile which consists of software

characterisation, aimed at supervision and management of power consumption (of a factory, shopping mall, hotel, etc.). The module allows acquisition and supervision of water, gas, steam and electricity consumption, as well as calculation of the values and their attribution to the relative cost centres.

- SD-View Panel Control. This is the most suitable solution and, in view of its level of integration, the most economical one for supervision and control of a single switchgear.

The display and control unit is mounted directly in the medium and/or low voltage power distribution switchgear or, on request, in an additional dedicated panel.

SD-View Panel Control is based on Basic architecture and carries out the dual purpose of concentrating and displaying the information coming from the microprocessor-based and multi-function protection units of the power distribution switchgear.The investment in SD-View Panel Control is already amortised in the commissioning/start-up stage, allowing a simple check and set-up of the switchgear in the plant, and allows an archive of significant tracings and alarms to be set up right from the initial stages.

Local and Remote Monitoring and Technical AssistancePossible by means of usual methods (Intranet, Internet/WEB- Radio LAN, WAN, ADSL, GSM, GPRS, etc.)Sending groups of alarms by means of SMS.

ConnectionsConnections available by means of the most widespread communication standards (RS232, RS485, Ethernet, Fieldbus, etc.) using all means (copper, coax, optic fibres, wireless, etc.).

ProtocolsIt is able to interface with other systems using almost all public protocols as well as many propriety market protocols.

Page 120: catalogo general Media Tensión (abb)

120

COM615Network gateway for electric substation automation systems

Characteristics• Display of all the single-line diagram primary devices • Identification of alarms and events with date, time, stall,

apparatus, description and state of the object• Control of the operating apparatus by means of separate

dialog windows • Freely defined Web links • Display of measurements• Availability of control and protection oscilloperturbography • Parameter setting tool • Diagnosis of component communication, including the

process apparatus• Four password levels • Multi-lingual support• Protocol conversion gateway for substation automation• Efficient and user-friendly configuration tool • Communication redundancy with optional LAN card• Extended support for putting into service and diagnosis• Complete management safety

ApplicationCOM615 combines the characteristics and functions of the COM605 Control and Monitoring unit and the COM610 Communication Gateway. It offers gateway functions for mapping the signals between the protection and control IED (Intelligent Electronic Device) in industrial or utility substations and higher level systems, and an HMI (Human Machine Interface) which displays the substation data and information at users’ disposal.COM615 collects the protection and control apparatus data, as well as that of the process apparatus, using different protocols. It uses web technology to show the data to the various users and to transfer that data to the NCC (Network Control Centre) or to the DCS (Distributed Control System).The protocols supported can be freely combined in a computer for substations, with the only limitation being the number of hardware interfaces present in COM615.

Connectivity packagesPackages for ABB’s protection and control IEDs are available to make the COM615 configuration more efficient. A connectivity package includes descriptions of the signal data available in the IED and the descriptions are used to automatically configure the communication master in the 3.2 COM615 gateway.The following connectivity packages are available:– REF 541/3/5, REM 543/5 and RET 541/3/5– REF 542plus– REX 521– RE_610– SPACOM (Conn Pack v. 2.0 supported by SPAJ 140, SPAJ

141, SPAJ 142, SPAJ 144, SPAD 346, SACO 16D1, SACO 16D2 and SACO 64D4)

The computer configurability and functionality for COM615 stations depends on the type of communication protocol used for communication between COM615 and the IEDs.

Design COM615 is made up of the OPC (Ole for Process Control) Data Access server and of the customer components. The OPC server guarantees access of the master/client protocol stacks to the data in the apparatus connected to the protocol.The OPC clients serve the slave/server protocol stacks to allow external systems to access the data available in the OPC server. They also serve to show the data to the embedded web server to allow external clients, connected to the COM615 by means of LAN/WAN networks, to access the data available in the web server.

Protocols available

Master Slave

LON - LAG IEC 60870-5-101

SPA IEC 60870-5-104

IEC 60870-5-103 Serial DNP 3.0

IEC 61850-8-1 DNP 3.0 LAN/WAN

Serial Modbus SPA Router

Modbus TCP External Client OPC

Serial DNP3

DNP3 TCP

Substation automation systems

Page 121: catalogo general Media Tensión (abb)

121

Distributed ControlSystem

OPC Client/Server (DA,AE)

LV devicesenergy meters

Modbus RTU

COM615

Process communication

Local access

LAN / WAN

LAN / WAN

Standardweb browser

Web Server

OPC Client

IEC-104 Slave

OPC Client OPC Client

IEC 61850Client

SPA Bus Master

IEC 61850-8-1 SPA Bus

OPC Client

Overview of an industrial system

Example of COM615 configuration for substations

Page 122: catalogo general Media Tensión (abb)

122

Responsive worldwide networkCapability makes all the difference

A team for every missionABB’s medium voltage product service teams are experts in their own fields. They have the knowledge and experi-ence to meet all your needs in both on and off-site activity. We are located across all five continents with service centres close to you.

Our philosophy: Responsiveness.

Solutions for every situationWith over 100 years of experience in the design, development, manufactu-ring and through-life service support of medium voltage switchgear, we have established a wealth of technical solutions to meet your specific electrical network reliability needs. ABB has the largest installed base of any switchgear manufacturer worldwide. We support our products through a comprehensive range of services that ensure optimum performance throughout their life.

Our service portfolio starts with installation and commissioning and continues right through the product’s life until eventual decommissioning.

Products we supportABB offers a comprehensive range of products for electrical distribution networks.

We supply:• primary air and gas insulated

switchgear• circuit breakers, switches, contactors• outdoor switchgear• secondary switchgear, ring main units• compact substations• distribution protection and control.

In addition, we maintain archives con-taining complete technical information on a wide range of our legacy products: ABB, ASEA, BBC, Calor Emag, SACE, Strömberg, Gardy, EJF, ITE, ZWAR, LK NES, Westinghouse. These products remain fully supported, including options to extend their life through retrofit and upgrade services to include the latest technology standards.

Peace of mindOur service offerings are designed to maintain the highest levels of reliability throughout the product’s life cycle.

• Born healthy: through ABB’s expert installation and commissioning

• Stay healthy: through ABB’s certified maintenance and repair services

• Enjoy better life: through ABB’s engineering and consulting service

• Gain a new lease of life: through applying the latest ABB technology to upgrade or retrofit.

Medium Voltage Product Service

Page 123: catalogo general Media Tensión (abb)

123

Product life cycle servicesPerfect care for Medium Voltage switchgear

Installation and commissioningABB certified service engineers provide expert on-site installation and commis-sioning of our equipment. Our start-up and commissioning servi-ces range from installation support, to full on-site project management.

Benefits:• lower risk• faster start-up• optimum life cycle performance.

Spare partsSpare parts availability is critical to ongoing operations.

We maintain a comprehensive stock of certified ABB parts, guaranteeing their availability throughout the product life cycle. For urgent parts requests, our logistics personnel and partners are available 24-hours a day to provide immediate emergency response.

Spares are stocked throughout our global network of service units, inclu-ding everything from individual compo-nents to complete assemblies.

Benefits:• enhanced product reliability by using

high quality certified parts• improved uptime due to guaranteed

delivery• global logistics network ensures fast

delivery.

TrainingA skilled and efficient workforce is a plant’s most valuable asset. ABB can help by providing a range of product training courses, which typically cover:• safety procedures and correct

product operation• routine maintenance• basic fault finding.

Training courses are normally provided by our local ABB service office and if required, training can be provided on site.

Benefits:• long term product performance

through correct operation• improved safety• reduced downtime.

Maintenance and field servicesOur experienced service professionals provide a range of on-site services to ensure the reliability of your installed switchgear.

Services include:• planned maintenance• on-site or workshop repairs• emergency call-out to reduce

downtime• long term service agreements to

maintain peak performance.

Benefits• field service by certified service

technicians• faster response• improved equipment utilization.

Page 124: catalogo general Media Tensión (abb)

124

Life extension and upgradesFrom installation to end of life

Retrofit and refurbishmentMany ABB products will provide use-ful service for 30-40 years or more. Throughout the product life cycle, we can provide solutions that expand the functionality and extend the life of your switchgear, while maintaining the value of your core investment.

Options include:• complete overhaul and refurbishment

of switchgear to original specification with warranty

• switchgear upgrades through retrofitting of switching devices

• protection and control upgrades for increased functionality

• upgrades to improve safety, such as the installation of arc detection and fast switching systems.

Benefits:• cost-effective alternative to

replacement• maximize asset investment

performance• incorporate latest technology to

increase safety, performance and functionality.

ExtensionShould you need to expand your electrical network, ABB has the full capability to provide additional circuits for existing switchboard configurations.

We can supply equipment that matches the original specification for the exten-sion of both current and phased out switchgear.

Benefits:• maintain equipment and operating

procedures and safety standards• ensure consistent technical standards• optimization of spares and

maintenance.

Medium Voltage Product Service

Page 125: catalogo general Media Tensión (abb)

125

Performance improvementGetting the best from your switchgear

Monitoring and diagnosisABB can call on a number of condition monitoring solutions to measure the key parameters of installed equipment. We can retrofit monitoring systems into existing switchgear to provide information on equipment performance for increased flexibility in planning maintenance shutdowns. In addition, diagnostic information helps identify negative product performance trends and supports proactive correction.

Benefits:• proactive intelligent action to reduce

risk of failure• access to expert analysis• 24-hour, continuous asset monitoring.

Engineering and consultingABB provides a range of engineering and consulting services for medium voltage switchgear including:• recommendations on product

application, upgrades or replacement• fault finding and diagnostics• customized engineered switchgear

solutions• switchgear decommissioning and

disposal• safety, health and environmental

practices to meet regulatory compliance and safeguard your licences to operate.

Benefits:• access to expert product specialists• sharing of global best practices• combined analysis and

implementation capability.

Site auditsABB is a world leader in the field of medium voltage switchgear and has vast experience in a wide variety of applications. Our service experts can conduct audits on existing installations to assess the condition of the equipment. These audits can be structured to minimize outages within your network. A typical audit includes:• documenting substation equipment• assessment of the condition of the

equipment• recommendations for maintenance,

replacement or refurbishment.

Benefits:• quantified analysis of installed

switchgear• evaluation of risk profile• proactive customized

recommendations to maintain equipment performance.

Page 126: catalogo general Media Tensión (abb)

126

Global experience applied to local solutionsABB is one of the world’s largest power transmission and distribution manufacturers offering a wide range of services which cover an extensive global installed base of switchgear.The best practices worldwide and more than 100 years of experience and innovation are incorporated in every delivery we make. We work in partnership with you to ensure that you get the very best service in the fastest possible time.

Expert global networkThrough ABB you can access more than 1000 technical experts located around the world. Thanks to our global certifica-tion program, our extensive network of specialists provides consistent delivery to the highest service and safety standards.

Our service teams are available 24/7 no matter where you are based – in any of the five continents – with ABB at your service you’ll always have peace of mind.

Full service portfolioWhatever your needs, we support our switchgear installations with a full ser-vice portfolio that covers every network application, from large to small.Each and every job, on or off-site, is accurately assessed, utilizing highly developed skills and technical tools to ensure the best outcome. Our solutions take all factors into considera-tion, including technical, financial, environmental and safety aspects. The result is a reliable and long lasting solution.

Life cycle supportABB has several long established global switchgear factories and a robust R&D infrastructure. Combined with our extensive network of local service centres this enables us to provide the very highest standards of product support from installation to end of life. It doesn’t matter how old your switchgear is, with ABB there is always a solution.

Always one step aheadStaying ahead means taking the right decisions, at the right time, based on the right information.ABB Medium Voltage product service aims to work as an active partner in your business. At all times we support our installed base through proactive service offerings that ensure high reliability and optimal performance of your switchgear.

Your global service partnerResponsive service and expert support

Product life cycle services

Cus

tom

er n

eed

s

• Installation and commissioning• Spare parts• Maintenance and field service• Training

• Life cycle product support• Highest product reliability and fast

service response• Optimized maintenance investment

AB

B S

olu

tions • Retrofit and refurbishment

• Extension

• Exploit the latest technology for highest safety standards

• Cost-effective life extension• Increase functionality

Life extension and upgrade

• Monitoring and diagnostics• Engineering and consulting• Site audits

• Reduce risk through pro-active service approach

• Utilize real-time data for fast recovery• Optimize asset performance through

condition analysis

Performance improvement

Medium Voltage Product Service

Page 127: catalogo general Media Tensión (abb)

127

Product life cycle services

Installation and commissioning:• lower risk• faster start-up• ensure product life cycle

performance.

Spare parts:• product reliability through high quality

certified parts• improved uptime due to guaranteed

delivery• global logistics network ensures fast

delivery.

Training:• long term product performance

through correct operation• improve safety• lower downtime.

Maintenance and field services:• field service by certified service

technicians• faster response• improved equipment utilization.

Life extension and upgrades

Retrofit and refurbishment:• cost-effective alternative

to replacement• maximize investment performance of

assets• incorporate latest technology to

increase safety, performance and functionality.

Extension:• maintain equipment and operating

procedures and safety standards• ensure consistent equipment

technical standards• optimization of spares and

maintenance.

Performance improvement

Monitoring and Diagnostics:• proactive intelligent action to reduce

risk of failure• access to expert analysis• 24-hour continuous asset monitoring.

Engineering and consulting:• access to expert product specialists• sharing of global best practices• combined analysis and

implementation capability.

Site audits:• quantified analysis of installed

switchgear• evaluation of risk profile• pro-active customized

recommendations to maintain equipment performance.

Page 128: catalogo general Media Tensión (abb)

128

Notes

Page 129: catalogo general Media Tensión (abb)

129

Notes

Page 130: catalogo general Media Tensión (abb)

130

Notes

Page 131: catalogo general Media Tensión (abb)

131

Page 132: catalogo general Media Tensión (abb)

1VC

P00

0112

- R

ev.

H,

en -

MV

Gen

eral

Cat

alog

ue -

201

0.08

(gs)

(b)

Contact us

Your sales contact: www.abb.com/contactsMore product information: www.abb.com/productguide

The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product.

Copyright 2010 ABB.All rights reserved.