catalogo general Media Tensión (abb)
-
Upload
perrin3141592 -
Category
Documents
-
view
734 -
download
3
Transcript of catalogo general Media Tensión (abb)
Medium Voltage Products
General catalogueMedium voltage apparatus
2
3
Contents
Introduction 4
Contactors 6
Circuit-breakers for indoor installation 8
Cartridge current limiters 20
Apparatus for railway traction 21
Enclosures and fixed parts 23
Switch-disconnectors 32
Fuses 41
Vacuum interrupters 43
Insulators 44
Apparatus for outdoor installation 48
Capacitors 53
Voltage indicators 55
Connectors 56
Primary distribution switchgear 58
Secondary distribution switchgear 70
Relays and multi-function units 76
Instrument transformers and sensors 92
Outdoor instrument transformers 108
Instrument transformer protection 109
Instrument transformers ANSI 110
Modular prefabricated solutions for photovoltaic fields
117
Substation automation systems 118
Medium Voltage Product Service 122
4
IntroductionThis is ABB
ABB is a global leader inpower and automationtechnologies that enableutility and industrycustomers to improvetheir performance whilelowering environmentalimpact.
Our group comprises five maindivisions:
– Power products– Power systems– Discrete automation and motion– Low voltage products– Process automation
SustainabilitySustainability is integral to all aspects of ABB’s business so we aim to balanceeconomic success, environmental stewardship and social progress to benefit all ourstakeholders.
Sustainability considerations cover how we design and manufacture products,what we offer customers, how we engage suppliers, how we assess risksand opportunities, and how we behave in the communities where we operateand towards one another. We also strive for excellence in health and safetyperformance.
TechnologyTechnology plays a key role for ABB. We have nine research centres, 6,000scientists and 70 university collaborations across the world – all working to developunique technologies that make our customers more competitive and efficient whileminimizing impact on the environment.
Where to find usABB operates in more than 100 countries and we have offices in 87 of thosecountries to provide the support our global and local customers need to developand conduct their business successfully.
5
The one-shop service for all your medium voltage needs
With ABB, you can meet all your requirements for medium voltage productsand systems from a single supplier. We have over 100 years of experiencein the design, development, manufacturing and through-life service supportof medium voltage switchgear, and the largest installed base of anymanufacturer worldwide.
Whatever your application – utility, industrial, transportation or commercial – wecan provide the perfect, coordinated solution that delivers maximum efficiency,reliability and safety. Our comprehensive medium voltage portfolio coversswitchgear, apparatus, modular systems and distribution automation. And, thanksto ABB’s global service network, we support our products and systems througha comprehensive range of services that ensure optimum performance throughouttheir life – from installation and commissioning to routine maintenance, retrofit andupgrades to eventual decommissioning.
Quality systemsABB operates the very highest global, national and industry-specific qualitystandards including ISO 9001. Our environmental management systems conformto ISO 14001 and our health and safety management system conforms to OHSAS18001.
A wide range of applicationsABB’s medium voltage equipmentserves a wide variety of applicationsthroughout the world including:
– Utility generation– Utility transmission– Utility distribution– Transportation– Heavy industrial process plant– Mining and mineral processing– Light industrial parks– Hospitals
Product portfolioABB offers a wide range of mediumvoltage products for primary andsecondary distribution applications,conforming to IEC standards as wellas those of the major industrializedcountries, including:
– Circuit breakers– Switch-disconnectors– Contactors– Fixed parts and enclosures– Distribution switchgear– Protection relays and control systems– Substation automation– Electrical distribution substations– A comprehensive range of accessories
6
Contactor VSC 7 VSC 12
Rated voltage kV 7.2 12
Withstand voltage at 50 Hz kV 23 28 (2)
Impulse withstand voltage kVbil 60 75
Rated frequency Hz 50-60 50-60
Utilization Fixed/UniGear/PowerCube Fixed/UniGear/PowerCube
Rated service current A 400 400
Rated short-time withstand current for 1 s A 6,000 6,000
Rated peak current kA 15 15
Rated short-circuit time (tk) s 1 1
Nominal number of operations
SCO function Op./hr 900 900
DCO function Op./hr 900 900
Rated load and overload characteristics in category of utilisation:
(AC4 Category) 100 closing operations kA 4,000 4,000
(AC4 Category) 25 opening operations kA 4,000 4,000
Normal current A 400 400
Electrical life (AC1category) (operations) (3) No. 1,000,000 1,000,000
Mechanical life (operations) No. 1,000,000 1,000,000
Short-circuit breaking capacity (1) A 6,000 4,000
Short-circuit making capacity (1) A 15,000 8,000
Opening time ms 20 ... 30 20 ... 30
Closing time ms 35 ... 50 35 ... 50
Version mm Fixed Withdrawable Fixed Withdrawable
Overall dimensions (excluding accessories)
H mm 371 636 423 636
inch 14.6 25 16.6 25
Lmm 350 531 350 531
inch 13.8 21 13.8 21
Dmm 215 657 215 657
inch 8.5 25.9 8.5 25.9
Weight kg 44 108 44 108
lbs 20 49 20 49
Technical catalogue No. 1VCP000165 1VCP000165
V-Contact VSC
(1) O-3min-CO-3min-CO single operation sequence.(2) Version for 42 kV - 50 Hz x 1 min. between phases and between phase and earth available on request (only fixed contactors or for UniGear switchgear).(3) Electrical life obtainable by following the maintenance programme given in the installation manual.
Contactors IEC
D
H
L
Vacuum contactors• Tested and constructed in accordance with IEC Standards• Bistable permanent magnet actuator• SCO function: Single Command Operated – electrical latching function• DCO function: Double Command Operated – mechanical latching function• Limited power consumption• Very compact dimensions• Specific vacuum interrupters for motor switching• Up to 1,000,000 operations• Maintenance-free• Electronic multi-voltage feeder• Fixed and withdrawable versions
7
8
VD4/R - VD4/LVacuum circuit-breakers with mechanical operating mechanism for secondary distribution• Tested and manufactured in conformity with IEC Standards• Circuit-breaker with right- or left -hand lateral operating mechanism• On request, application of the PR521 self-supplied protection device or REF601
(not self-supplied) IEC version • Designed for installation in unmanned substations and without auxiliary power
supply (with PR521 only)• Sealed-for-life poles• Interchangeable with HD4/R circuit-breakers (up to 24 kV)
(1) Increase by 20 kg with PR521 and sensors.(2) Removable version for UniMix, UniSwitch and UniSec switchgear.(3) 230/300 mm pole centre distance.
Circuit-breaker VD4/R 12 VD4/R 17.5 VD4/R 24
Rated and insulation voltage kV 12 17.5 24
Withstand voltage (1 min) kV (50Hz) 28 38 50
Impulse withstand voltage kV 75 95 125
Rated frequency Hz 50-60 50-60 50-60
Rated normal current A (40 °C) 630 800 1250 630 800 1250 630 800 1250
Rated breaking capacity and short-timewithstand current (3 s)
kA
12.5 – – 12.5 – – 12.5 – –
16 16 16 16 16 16 16 16 16
20 20 20 20 20 20 20 20 20
25 25 25 – – – – – –
Making capacity kA
31.5 – – 31.5 – – 31.5 – –
40 40 40 40 40 40 40 40 40
50 50 50 50 50 50 50 50 50
63 63 63 – – – – – –
Operation sequence 0-3''-CO-15''-CO 0-3''-CO-15''-CO 0-3''-CO-15''-CO
Opening time ms 45 45 45
Arc time ms 10-15 10-15 10-15
Total interruption time ms 55-60 55-60 55-60
Closing time ms 80 80 80
Overall dimensions (fixed version)
H mm 785 785 785
L mm 317 317 317
D mm 1029/1170 (3) 1029/1170 (3) 1029/1170 (3)
Weight Fixed (1) kg 65 65 65
Withdrawable (1) (2) kg 70 70 70
Technical catalogue No. 1VCP000263 1VCP000263 1VCP000263
D
H
L
Circuit-breakers for indoor installation IEC
9
HD4/RGas circuit-breakers with mechanical operating mechanism for secondary distribution• Tested and constructed in accordance with IEC Standards• Circuit-breaker with right-hand lateral operating mechanism• On request (up to 24 kV), application of PR521 self-supplied protection device or
REF601 (not self-supplied) IEC version • Designed for installation in unmanned substations without auxiliary power supply
(with PR521 only)• Sealed-for-life poles• Interchangeable with VD4/R circuit-breakers (up to 24 kV)• Available with or without pressure switch
(1) Increase by 20 kg with PR521 and sensors / REF601 and sensors.(2) HD4/UniAir removable version for UniAir switchgear, HD4/UniMix for UniMix switchgear or HD4/S for UniSwitch switchgear.(3) 230/300 mm pole centre distance.(4) 350 mm pole centre distance.(5) 20 kA for 1 s.
Circuit-breaker HD4/R 12 HD4/R 17 HD4/R 24 HD4/R 36
Rated and insulation voltage kV 12 17.5 24 36
Withstand voltage (1 min) kV (50Hz) 28 38 50 70
Impulse withstand voltage kV 75 95 125 170
Rated frequency Hz 50-60 50-60 50-60 50-60
Rated normal current A (40 °C) 630 800 1250 630 800 1250 630 800 1250 630 800 1250
Rated breaking capacity and short-timewithstand current (3 s)
kA
12.5 – – 12.5 – – 12.5 – – 12.5 12.5 12.5
16 16 16 16 16 16 16 16 16 16 16 16
20 (5) 20 20 20 (5) 20 20 20 20 20 – – –
25 25 25 – – – – – – – – –
Making capacity kA
31.5 – – 31.5 – – 31.5 – – 31.5 31.5 31.5
40 40 40 40 40 40 40 40 40 40 40 40
50 50 50 50 50 50 50 50 50 – – –
63 63 63 – – – – – – – – –
Operation sequence O-0.3s-CO-15s-CO
Opening time ms 45 45 45 45
Arc time ms 10-15 10-15 10-15 10-15
Total interruption time ms 55-60 55-60 55-60 55-60
Closing time ms 80 80 80 80
Overall dimensions(fixed version)
H mm 764.5 764.5 764.5 810
L mm 321 321 321 409
D mm 1049/1189 (3) 1049/1189 (3) 1049/1189 (3) 1348 (4)
Weight Fixed (1) kg 103 103 103 110
Withdrawable (1) (2) kg 108 108 108 –
Nominal gas pressure kPa 380 380 380 380
Technical catalogue No. 1VCP000028 1VCP000028 1VCP000028 1VCP000028
IEC
D
H
L
10
11
HD4Gas circuit-breakers with mechanical operating mechanism for primary distribution • Tested and constructed in accordance with IEC Standards• Compact dimensions• Long electrical and mechanical life• Maintenance-free poles• Sealed-for-life poles• Fixed and withdrawable versions• Gas monitoring device on request
(1) HD4 circuit-breakers are available in the withdrawable version with the following characteristics: – HD4/W 36: 36 kV; ... 2500 A; ... 31.5 kA for PowerCube 36 enclosures and UniGear ZS2 switchgear; – HD4/Z 36/40.5: 40.5 kV; ... 2500 A; ... 31.5 kA for UniGear ZS3.2 switchgear.(2) Rated current higher than 3150 A with forced ventilation.
Circuit-breaker HD4 12 HD4 17.5 HD4 24 HD4 36 (1)
Rated and insulation voltage kV 12 17.5 24 36
Withstand voltage (1 min) kV (50Hz) 28 38 50 70
Impulse withstand voltage kV 75 95 125 170
Rated frequency Hz 50-60 50-60 50-60 50-60
Utilization Fixed/UniGear/PowerCube Fixed/ZS3.2/PowerCube
Rated current (2) A (40 °C) 630-1250 1600-4000 630-1250 1600-4000 630-1250 1600-3600 630 1250 1600 2000 2500
Rated breaking capacity and rated short-timewithstand current (3 s)
kA
16 16 16 – 16 – 16 16 16 – –
– – – – 20 – 20 20 20 20 20
25 25 25 25 25 25 – 25 25 25 25
31.5 31.5 31.5 31.5 – 31.5 – 31.5 31.5 31.5 31.5
– 40 – 40 – 40 – – – – –
– 50 – 50 – – – – – – –
Making capacity kA
40 40 40 – 40 – 40 40 40 – –
– – – – 50 – 50 50 50 50 50
63 63 63 63 63 63 – 63 63 63 63
80 80 80 80 – 80 – 80 80 80 80
– 100 – 100 – 100 – – – – –
– 125 – 125 – – – – – – –
Operation sequence O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO
Opening time ms 45 45 45 45 45 45 45
Arc time ms 10-15 10-15 10-15 10-15 10-15 10-15 10-15
Total interruption time ms 55-60 55-60 55-60 55-60 55-60 55-60 55-60
Closing time ms 80 80 80 80 80 80 80
Overall dimensions (fixed version)
H mm 640 ... 655 649 ... 655 818 ... 855 712 ... 1123
L mm 493 ... 730 600 ... 730 600 ... 730 748 ... 955
D mm 495 ... 603 496 ... 603 516 ... 603 695 ... 833
Weight Fixed kg 114 ... 165 114 ... 165 119 ... 165 124 ... 190
Withdrawable kg 120 ... 230 120 ... 230 125 ... 220 280 ... 300
Nominal gas pressure kPa 380 380 380 380 ... 550
Technical catalogue No. 1VCP000004 1VCP000004 1VCP000004 1VCP000004
IEC
D
H
L
Circuit-breakers for indoor installation
12
VD4
(1) ZS8.4 switchgear up to 1250 A and 25 kA.(2) In ABB switchgear with forced ventilation.(3) For high performances, please ask us.
Vacuum circuit-breakers with mechanical operating mechanism for primary distribution• Tested and constructed in accordance with IEC Standards• Compact dimensions• Long electrical and mechanical life• Resin poles with embedded interrupters • Sealed-for-life and maintenance-free poles• Fixed and withdrawable versions• Operating mechanisms with just a few highly reliable components• Accessories common to the whole range
Circuit-breaker VD4 12 VD4 17 VD4 24 VD4 36 VD4 40.5
Rated and insulation voltage kV 12 17.5 24 36 40.5
Withstand voltage (1 min) kV (50Hz) 28 38 50 70 85
Impulse withstand voltage kV 75 95 125 170 185
Rated frequency Hz 50-60 50-60 50-60 50-60 50-60
Utilization Fixed/UniGear/PowerCube/ZS8.4 (1) UniGear/PowerCube Fixed/UniGear/PowerCube/ZS8.4 (1) UniGear/PowerCube Fixed/UniGear/PowerCube/ZS8.4 (1) ZS3.2 ZS3.2
Rated current A (40 °C) 630 1250 1600 2000 2500 3150 4000 (2) 630 1250 1600 2000 2500 3150 4000 (2) 630 1250 1600 2000 2500 1250 1600 2000 2500 3150 (2) 1250 1600 2000 2500 3150 (2)
Rated breaking capacity and short-timewithstand current (3 s)
kA
16 16 – – – – – 16 16 – – – – – 16 16 – – – – – – – – – – – – –
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 – – – – – – – – – – –
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 – – – – – 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
– 40 40 40 40 40 40 – 40 40 40 40 40 40 – – – – – 40 40 40 40 40 – – – – –
– 50 50 50 50 50 50 – 50 50 50 50 50 50 – – – – – – – – – – – – – – –
Making capacity kA
40 40 – – – – – 40 40 – – – – – 40 40 – – – – – – – – – – – – –
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 – – – – – – – – – – –
63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80 80 80 80 80 80 – – – – – 80 80 80 80 80 80 80 80 80 80
– 100 100 100 100 100 100 – 100 100 100 100 100 100 – – – – – 100 100 100 100 100 – – – – –
– 125 125 125 125 125 125 – 125 125 125 125 125 125 – – – – – – – – – – – – – – –
Operation sequence O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3)
Opening time ms 33 ... 60 33 ... 60 33 ... 60 40 … 60 40 … 60
Arc time ms 10 ... 15 10 ... 15 10 ... 15 10 … 15 10 … 15
Total interruption time ms 43 ... 75 43 ... 75 43 ... 75 50 … 75 50 … 75
Closing time ms 60 ... 80 60 ... 80 60 ... 80 60 … 80 60 … 80
Overall dimensions (fixed version)
Hmm 461 ... 616 599 ... 677 461 ... 616 599 ... 677 461 ... 616 1575 1575
inch 18.1 ... 24.1 23.6 ... 26.6 18.1 ... 24.1 23.6 ... 26.6 18.1 ... 24.1 62 62
Lmm 570 ... 700 23.6 ... 26.6 570 ... 700 600 ... 750 570 ... 700 895 … 1000 895
inch 22.4 ... 27.1 23.6 ... 29.5 22.4 ... 27.1 23.6 ... 29.5 22.4 ... 27 35.2 ... 39.4 32.5
Dmm 424 424 ... 459 424 424 ... 459 424 555 … 686 686
inch 16.7 16.7 ... 18 16.7 16.7 ... 18 16.7 21.8 ... 27 27
Weight
Fixedkg 80 ... 120 – 80 ... 120 – 80 ... 120 – –
lbs 178/264 – 178/264 – 176 ... 264 – –
Withdrawablekg 100 ... 150 159 ... 260 100 ... 150 159 ... 260 100 ... 150 290 … 350 290 … 350
lbs 220 ... 330 350 ... 572 220 ... 330 350 ... 572 220 ... 330 638 ... 770 638 ... 770
Technical catalogue No. 1VCP000001 DECMS231202 1VCP000001 DECMS231202 1VCP000001 DECMS 2312 03 DECMS 2312 03
Circuit-breakers for indoor installation IEC
D
H
L
13
Circuit-breaker VD4 12 VD4 17 VD4 24 VD4 36 VD4 40.5
Rated and insulation voltage kV 12 17.5 24 36 40.5
Withstand voltage (1 min) kV (50Hz) 28 38 50 70 85
Impulse withstand voltage kV 75 95 125 170 185
Rated frequency Hz 50-60 50-60 50-60 50-60 50-60
Utilization Fixed/UniGear/PowerCube/ZS8.4 (1) UniGear/PowerCube Fixed/UniGear/PowerCube/ZS8.4 (1) UniGear/PowerCube Fixed/UniGear/PowerCube/ZS8.4 (1) ZS3.2 ZS3.2
Rated current A (40 °C) 630 1250 1600 2000 2500 3150 4000 (2) 630 1250 1600 2000 2500 3150 4000 (2) 630 1250 1600 2000 2500 1250 1600 2000 2500 3150 (2) 1250 1600 2000 2500 3150 (2)
Rated breaking capacity and short-timewithstand current (3 s)
kA
16 16 – – – – – 16 16 – – – – – 16 16 – – – – – – – – – – – – –
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 – – – – – – – – – – –
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 – – – – – 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
– 40 40 40 40 40 40 – 40 40 40 40 40 40 – – – – – 40 40 40 40 40 – – – – –
– 50 50 50 50 50 50 – 50 50 50 50 50 50 – – – – – – – – – – – – – – –
Making capacity kA
40 40 – – – – – 40 40 – – – – – 40 40 – – – – – – – – – – – – –
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 – – – – – – – – – – –
63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80 80 80 80 80 80 – – – – – 80 80 80 80 80 80 80 80 80 80
– 100 100 100 100 100 100 – 100 100 100 100 100 100 – – – – – 100 100 100 100 100 – – – – –
– 125 125 125 125 125 125 – 125 125 125 125 125 125 – – – – – – – – – – – – – – –
Operation sequence O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3) O-0.3s-CO-15s-CO (3)
Opening time ms 33 ... 60 33 ... 60 33 ... 60 40 … 60 40 … 60
Arc time ms 10 ... 15 10 ... 15 10 ... 15 10 … 15 10 … 15
Total interruption time ms 43 ... 75 43 ... 75 43 ... 75 50 … 75 50 … 75
Closing time ms 60 ... 80 60 ... 80 60 ... 80 60 … 80 60 … 80
Overall dimensions (fixed version)
Hmm 461 ... 616 599 ... 677 461 ... 616 599 ... 677 461 ... 616 1575 1575
inch 18.1 ... 24.1 23.6 ... 26.6 18.1 ... 24.1 23.6 ... 26.6 18.1 ... 24.1 62 62
Lmm 570 ... 700 23.6 ... 26.6 570 ... 700 600 ... 750 570 ... 700 895 … 1000 895
inch 22.4 ... 27.1 23.6 ... 29.5 22.4 ... 27.1 23.6 ... 29.5 22.4 ... 27 35.2 ... 39.4 32.5
Dmm 424 424 ... 459 424 424 ... 459 424 555 … 686 686
inch 16.7 16.7 ... 18 16.7 16.7 ... 18 16.7 21.8 ... 27 27
Weight
Fixedkg 80 ... 120 – 80 ... 120 – 80 ... 120 – –
lbs 178/264 – 178/264 – 176 ... 264 – –
Withdrawablekg 100 ... 150 159 ... 260 100 ... 150 159 ... 260 100 ... 150 290 … 350 290 … 350
lbs 220 ... 330 350 ... 572 220 ... 330 350 ... 572 220 ... 330 638 ... 770 638 ... 770
Technical catalogue No. 1VCP000001 DECMS231202 1VCP000001 DECMS231202 1VCP000001 DECMS 2312 03 DECMS 2312 03
IEC
14
IEC
Circuit-breaker eVD4 12 eVD4/P 12 eVD4 17 eVD4/P 17
Rated voltage kV 12 12 17.5 17.5
Rated insulation voltage kV 12 12 17.5 17.5
Withstand voltage at 50 Hz (1 min) kV 42 42 42 42
Impulse withstand voltage kV 75 75 95 95
Rated frequency Hz 50-60 50-60 50-60 50-60
Rated normal current (40 °C) A 630 - 2500 (*) 630 - 2500 (*) 630 - 2500 (*) 630 - 2500 (*)
Rated breaking capacity (rated symmetrical short-circuit current)
kA 16 - 40 16 - 40
Rated short-time withstand current (3s) kA 16 - 40 16 - 40
Making capacity kA 40 - 125 40 - 125
Sequence of operations O - 0.3 s - CO - 15 s - CO • •
Opening time ms 40 ... 60 40 ... 60
Arc time ms 10 ... 15 10 ... 15
Total breaking time ms 50 ... 75 50 ... 75
Closing time ms 50 ... 70 50 ... 70
Maximum overall dimensions
H mm 461 - 589 621 - 691 461 - 589 621 - 691
L mm 450 - 700 492 - 842 450 - 700 492 - 842
D mm 424 642 - 657 424 642 - 657
P mm (Pole centre distance) 150 - 275 150 - 275 150 - 275 150 - 275
Operating temperature °C - 25 ... + 40 - 25 ... + 40
Electromagnetic compatibility IEC: 61000; 60255 • •
Technical catalogue No. 1VCP000281 1VCP000281
D
H
L
P P
Vacuum circuit-breakers with sensors and integrated RBX 615 protection unit • Tested and constructed in accordance with IEC Standards• Mechanical actuator • Compatibility with the VD4 series, fixed and withdrawable versions• Compact dimensions, poles with embedded interrupters, sealed-for-life and
maintenance-free • Protection relay with five standard pre-configurations• Circuit-breaker and panel components fully factory-tested• Drastic reduction in cabling and risk of errors• Possibility of use in all types of plants• High environmental and electromagnetic compatibility
Circuit-breakers for indoor installation
eVD4
(*) For 2500 A please ask ABB.
15
VmaxVacuum circuit-breakers with mechanical operating mechanism for primary distribution• Tested and constructed in accordance with IEC Standards• Compact dimensions• Long electrical and mechanical life• Sealed-for-life and maintenance-free interrupters• Fixed and withdrawable versions• Operating mechanism with just a few highly reliable components• Accessories common to the whole range
IEC
D
H
L
Circuit-breaker Vmax 12 Vmax 17
Rated and insulation voltage kV 12 17.5
Withstand voltage (1 min) kV (50Hz) 28 38
Impulse withstand voltage kV 75 95
Rated frequency Hz 50-60 50-60
Utilization Fixed/UniGear/PowerCube Fixed/UniGear/PowerCube
Rated current A (40 °C) 630 1250 630 1250
Rated breaking capacity and short-time withstand current (3 s)
kA
16 16 16 16
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
Making capacity kA
40 40 40 40
50 50 50 50
63 63 63 63
80 80 80 80
Operation sequence O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO
Opening time ms 33.5 ... 60 33.5 ... 60
Arc time ms 10 ... 15 10 ... 15
Total interruption time ms 43.5 ... 75 43.5 ... 75
Closing time ms 45 ... 80 45 ... 80
Overall dimensions(fixed version)
Hmm 496 531
inch 19.4 20.8
Lmm 416 416
inch 16.3 16.3
Dmm 433 433
inch 16.9 16.9
Weight
Fixedkg 77 77
lbs 171 171
Withdrawablekg 98 ... 100 98 ... 100
lbs 218...222 218...222
Technical catalogue No. 1VCP000169 1VCP000169
16
VM1Vacuum circuit-breakers with magnetic actuator for primary distribution• Tested and constructed in accordance with IEC Standards• Operating mechanism with magnetic actuator• Compatible with the VD4 series• Compact dimensions• Control functions: circuit-breaker state, continuity of the actuator coils, capacitor
charging and watchdog• High environmental and electromagnetic compatibility• Limited power consumption• Poles with embedded interrupters, sealed-for-life and maintenance-free• Fixed and withdrawable versions
(1) Catalogue DEABB 2233 03
IEC
D
H
L
Circuit-breaker VM1 12 VM1 17 VM1 24
Rated and insulation voltage kV 12 17.5 24
Withstand voltage (1 min) kV (50Hz) 28 38 50
Impulse withstand voltage kV 75 95 125
Rated frequency Hz 50-60 50-60 50-60
Utilization Fixed/UniGear/PowerCube UniGear Fixed/UniGear/PowerCube UniGear Fixed/UniGear/PowerCube
Rated current A (40 °C) 630 1250 1600 2000 2500 3150 630 1250 1600 2000 2500 3150 630 1250 1600 2000 2500
Rated breaking capacity and short-time withstand current (3 s)
kA
16 16 – – – – 16 16 – – – – 16 16 16 16 –
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 – – – – –
– 40 40 40 40 40 – 40 40 40 40 40 – – – – –
– – – 50 50 50 – – – – – – – – – – –
Making capacity kA
40 40 – – – – 40 40 – – – – 40 40 40 40 –
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80 80 80 80 – – – – –
– 100 100 100 100 100 – 100 100 100 100 100 – – – – –
– – – 125 125 125 – – – – – – – – – – –
Operation sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3 min-CO
Opening time ms 40 ... 60 40 ... 60 40 ... 60
Arc time ms 10 ... 15 10 ... 15 10 ... 15
Total interruption time ms 50 ... 75 50 ... 75 50 ... 75
Closing time ms 60 ... 80 60 ... 80 60 ... 80
Actuator mechanical operations (cycles) No. ... 100,000 ... 100,000 ... 100,000
Interrupter mechanical operations (cycles) No. ... 30,000 ... 30,000 ... 30,000
Electrical operations at rated current (cycles) No. ... 30,000 ... 30,000 ... 30,000
Electrical operationsunder short-circuit (cycles) No. ... 100 ... 100 ... 100
Overall dimensions(fixed version)
Hmm 461 ... 616 620 461 ... 616 620 631 ... 661
inch 18.1 ... 24.1 24.4 18.1 ... 24.1 24.4 24.8 ... 26
Lmm 570 ... 700 750 570 ... 700 750 570 ... 700
inch 22.4 ... 27.1 29.5 22.4 ... 27.1 29.5 22.4 ... 27.5
Dmm 424 424 424 424 424
inch 16.7 16.7 16.7 16.7 16.7
Weight
Fixedkg 90 ... 130 – 90 ... 130 – 100 ... 140
lbs 198 ... 286 – 198 ... 286 – 220 ... 308
Withdrawablekg 110 ... 160 148 110 ... 160 148 120 ... 170
lbs 242 ... 352 325.6 242 ... 352 325.6 264 ... 374
Technical catalogue No. 1VCP000057 (1) 1VCP000057 (1) 1VCP000057
Circuit-breakers for indoor installation
17
Circuit-breaker eVM1 12 eVM1 17
Rated and insulation voltage kV 12 17.5
Withstand voltage (1 min) kV (50Hz) 28 38
Impulse withstand voltage kV 75 95
Rated frequency Hz 50-60 50-60
Utilization Fixed / ZS1 / PowerCube Fixed / ZS1 / PowerCube
Rated current A (40 °C) 630 1250 630 1250
Rated breaking capacity and rated short-timewithstand current (3 s)
kA
16 16 16 16
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
Making capacity kA
40 40 40 40
50 50 50 50
63 63 63 63
80 80 80 80
Operation sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
Opening time ms 33 33
Closing time ms 50 50
Actuator mechanical operations (cycles) No. ... 100,000 ... 100,000
Interrupter mechanical operations (cycles) No. ... 30,000 ... 30,000
Electrical operations at rated current (cycles) No. ... 30,000 ... 30,000
Consumption on stand-by W < 15 < 15
Consumption after a self-reclosing cycle W < 110 < 110
Overall dimensions (withdrawable version)
Hmm 461 461
inch 22.4 22.4
Lmm 570-700 570-700
inch 22.4-27.1 22.4-27.1
Dmm 464 464
inch 16.7 16.7
Withdrawable version weightkg 110 ... 160 110 ... 160
lbs 242...352 242...352
Technical catalogue No. 1VCP000168 1VCP000168
eVM1Vacuum circuit-breakers with magnetic actuator with integrated on-board sensors, protection and control, for primary distribution• Tested and constructed in accordance with IEC Standards• Compatibility with the VD4 series, fixed and withdrawable versions• Poles with embedded interrupters, sealed-for-life and maintenance-free• Simplification of preparation of specifications and ordering procedures• Drastic reduction of cabling and improved safety and reliability• Possibility of use in all types of plants• Control of the circuit-breaker state and watchdog function• High environmental and electromagnetic compatibility
Protections according to IEC 60255-3 and IEC 60255-8 Standards• The basic series includes: 51- overcurrent IDMT (NI, VI, EI, LI), 50 - overcurrent DT1, 50 - overcurrent DT2, 51N - earth fault IDMT, 50N - earth fault DT1, 50N -
earth fault DT2.• The complete series includes: 51MS - motor starting protection, 66 - number of start-ups, 51LR - blocked rotor, 49 - thermal overload, 46 - unbalanced load.
IEC
D
H
L
18
ADVAC
D
H
L
Circuit-breakers for indoor installation ANSI
Vacuum circuit-breakers with mechanical actuator for primary distribution• Tested and constructed in accordance with ANSI Standards• Long electrical and mechanical life• Maintenance-free poles • Sealed-for-life poles • Fixed, withdrawable and retrofitting versions
Circuit-breaker ADVAC ADVAC ADVAC
Rated voltage kV 4.76 8.25 15
Withstand voltage at industrial frequency kV 19 36 36
Impulse withstand voltage (BIL) kV 60 95 95
Rated frequency Hz 50-60 50-60 50-60
Utilization kit, L-frame, modules, switchgear kit, L-frame, modules, switchgear kit, L-frame, modules, switchgear
Rated normal current A 1200 2000 3000 1200 2000 3000 1200 2000 3000
Rated breaking capacity kA
- - - - - - 20 20 20
25 25 25 - - - 25 25 25
31.5 31.5 31.5 - - - 31.5 31.5 31.5
40 40 40 40 40 40 40 40 40
50 50 50 - - - 50 50 50
Making capacity (crest current)
kA 1200 2000 3000 1200 2000 3000 1200 2000 3000
20 - - - - - - 52 52 52
25 65 65 65 - - - 65 65 65
31.5 82 82 82 - - - 82 82 82
40 104 104 104 104 104 104 104 104 104
50 130 130 130 - - - 130 130 130
Operation sequence C-O-15s-C-O C-O-15s-C-O C-O-15s-C-O
Opening time ms 35-40 35-40 35-40
Arc time ms <15 <15 <15
Total interruption time ms <55 <55 <55
Overall dimensions
Withdrawable Fixed Withdrawable Fixed Withdrawable Fixed
H mm 701 651 701 651 701 651
inch 27.62 25.65 27.62 25.65 27.62 25.65
Lmm 818 772 818 772 818 772
inch 32.20 30.39 32.20 30.39 32.20 30.39
Dmm 905 425 905 425 905 425
inch 35.65 16.75 35.65 16.75 35.65 16.75
Weight
Fixedkg 150-168 150-168 150-168
lbs 330-370 330-370 330-370
Withdrawablekg 168-250 168-250 168-250
lbs 370-550 370-550 370-550
19
AMVACVacuum circuit-breakers with magnetic actuator for primary distribution• Tested and constructed in accordance with ANSI Standards• Long electrical and mechanical life• Maintenance-free poles • Sealed-for-life poles • Fixed and withdrawable versions (Advance/Safegear and floor-mounted) (1)
ANSI
D
H
L
Circuit-breaker AMVAC AMVAC AMVAC
Rated voltage kV 4.76 15 27
Withstand voltage at industrial frequency kV 19 36 60
Impulse withstand voltage (BIL) kV 60 95 125
Rated frequency Hz 50-60 50-60 50-60
Utilizationkit, L-frame, modules,
abbreviated swgrkit, L-frame, modules,
abbreviated swgrL-frame, modules
Rated normal current A 1200 2000 3000 1200 2000 3000 1200 2000 3000
Rated breaking capacity kA
- - - 20 20 20 16 16 -
25 25 25 25 25 25 25 25 -
31.5 31.5 31.5 31.5 31.5 31.5 - - -
40 40 40 40 40 40 - - -
50 50 50 50 50 50 - - -
Making capacity (crest current)
kA 1200 2000 3000 1200 2000 3000 1200 2000 3000
16 - - - - - - 42 42 -
20 - - - 52 52 52 - - -
25 65 65 65 65 65 65 65 65 -
31.5 82 82 82 82 82 82 - - -
40 104 104 104 104 104 104 - - -
50 130 130 130 130 130 130 - - -
Operation sequence C-O-15s-C-O C-O-15s-C-O C-O-15s-C-O
Closing time ms 60 60 60
Trip time ms 45 45 45
Overall dimensions
Withdrawable Fixed Withdrawable Fixed Withdrawable Fixed
H mm 701 651 701 651 701 651
inch 27.62 25.65 27.62 25.65 27.62 25.65
Lmm 818 772 818 772 818 772
inch 32.20 30.39 32.20 30.39 32.20 30.39
Dmm 905 425 905 425 905 425
inch 35.65 16.75 35.65 16.75 35.65 16.75
Weight
Fixedkg 141-152 141-152 141-152
lbs 310-335 310-335 310-335
Withdrawablekg 182-193 182-193 182-193
lbs 400-425 400-425 400-425
(1) Including the fixing frame (fixed part).
20
IEC
Is-LimiterCartridge current limiters• Reduce the cost of distribution substations• Solve the short-circuit problems in new plants or in the case of enlargement• Are the optimal solution for interconnection of switchgear with electrical
distribution plants• In many cases are the only technical solution possible• Widely experimented and applied successfully in thousands of plants• Are found throughout the world• Never allow the peak short-circuit current to be reached• Limit the onset of the short-circuit current right from the first moments
Limiter Fixed Is - Limiter
Rated voltage kV 12 12 17.5 17.5 24 36
Rated current A 1250/2000 2500/3000/4000 (1) 1250/2000 2500/3000/4000 (1) 1250/1600/2000/3000 (1) 1250/2000/2500 (1)
Test voltage(50/60 Hz / 1 min)
kV 28 28 38 38 50 75
Impulse withstand voltage
kV 75 75 95 95 125 200
Rated short-circuit/opening current
kARMS 210 210 210 210 140 140
IS-Limiter Insert-holder kg 23/27.5 65 23/27.5 65 27/31.5/33 60
IS-Limiter Insert kg 12/12.5 15.5 14/14.5 17.5 19/19.5/24 42
Insert-holder complete with insert
H mm 180 180 180 180 180 240
L mm 637/651 951 637/651 951 740/754/837 1016
D mm 503/510 509 503/510 509 553/560/560 695
(1) With cooling fan.For higher currents, connection in parallel of several insert-holders with relative inserts is carried out.
Limiter Withdrawable Is - Limiter
Rated voltage kV 12 17.5 24
Rated current A 1250/2000/2500/3000 (1)/4000 (1) 1250/2000/3000 (1)/4000 (1) 1250/2000/3000 (1)/4000 (1)
Test voltage (50/60 Hz / 1 min)
kV 28 38 50
Impulse withstand voltage
kV 75 95 125
Dimensions
H mm 2200 2200 2325
L mm 1000 1000 1000
D mm 1300 1300 1500
Weight including truck kg 1200 1200 1300
D
H
L
Cartridge current limiters
D
H
L
21
GSR II FSK II
GSR II FSK II
GSR II: Single-pole circuit-breakers for indoor installationFSK II: Two-pole circuit-breakers for outdoor installation• Vacuum interruption technology• Magnetic actuator• Sealed-for-life poles• Insulator made of silicone rubber (FSK II)• EC 694 - EN 51052 -1 Standards• Available in RFI (Italian Railway Network) approved version
Circuit-breaker GSRII - 5954 FSKII - 1020 FSKII - 1025
Rated and insulation voltage kV 27.5 27.5 27.5
Withstand voltage at industrial frequency (50 Hz/1 min)
- phase-earth kV 95 95 105
- between open contacts kV 110 95 110
Impulse withstand voltage (1,2/50 µs)
- phase-earth kV 200 200 250
- between open contacts kV 250 200 250
Rated frequency Hz 50 50 50
Rated current A 2500 1250-2000 2500
Rated breaking capacity kA 25 25 25
Rated short-time withstand current (3 s)
kA 25 25 25
Making capacity kA 63 63 63
Rated withstand peak current kA 63 63 63
Operation sequenceO - 0.3s - CO - 3min CO O - 0.3s - CO - 3min CO O - 0.3s - CO - 3min CO
– CO - 10s - CO CO - 10s - CO
Opening time ms ≤ 45 ≤ 40 ≤ 40
Closing time ms ≤ 60 ≤ 60 ≤ 60
Technical catalogue No. 1VSR0006B1851 1VSR0006B1851 1VSR0006B1851
Apparatus for railway traction IEC
22
23
PowerCube
(1) With forced ventilation.(2) For 36 kV, please contact us.(3) Except for PBE – PBM1 - PRE – PRM1 - PB6 and PR6.(4) Signal source to be provided by the customer.(5) Main circuits; for earthing circuits please see the technical catalogue.
Pre-assembled modules for medium voltage switchgear• Tested and constructed in accordance with IEC Standards• Modular structure studied to facilitate construction of switchgear• Fitted with mechanical and electromechanical locks• Metal shutters with optional fail safe device (prevention of manual opening)• Circuit-breaker/contactor racking-in/out with the door closed• Use with gas circuit-breakers, vacuum circuit-breakers and contactors• Version with earthing switch with making capacity• Earthing switch with making capacity fitted with interlocks • Bottom compartment can be fitted with measurement truck with VTs protected
by fuses (3)
• Voltage signalling lamps (4)
Module Incoming, outgoing and bus-tie units Riser, measurement and direct busbar incoming units
PB1M PB1E
PB2M PB2E
PB3M PB3E
PB4M PB4E
PB5M PB5E
PB 6PR1M PR1E
PR2MPR2E
PR3MPR3E
PR4MPR4E
PR5MPR5E
PR 6
Module widthmm 600 750 1000 750 1000 1000 600 750 1000 750 1000 1000
inch 23.6 29.5 39.4 29.5 39.4 39.4 23.6 29.5 39.4 29.5 39.4 39.4
Rated voltage kV
12 12 12 – – – 12 12 12 – – –
17.5 17.5 17.5 – – – 17.5 17.5 17.5 – – –
– – – 24 24 – – – – 24 24 –
– – – – – 36 (2) – – – – – 36 (2)
Test voltage at industrial frequency
kV
28 28 28 – – – 28 28 28 – – –
38 38 38 – – – 38 38 38 – – –
– – – 50 50 – – – – 50 50 –
– – – – – 70 – – – – – 70
Impulse withstand voltage
kV
75 75 75 – – – 75 75 75 – – –
95 95 95 – – – 95 95 95 – – –
– – – 125 125 – – – – 125 125 –
– – – – – 170 – – – – – 170
Rated short-time withstand current (5)
kA (3s)
25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5 – – 31.5
– 40 40 – – – – 40 40 – – –
kA (1s) – 50 50 – – – – 50 50 – – –
Peak current kA
63 63 63 63 63 63 63 63 63 63 63 63
79 79 79 – – 79 79 79 79 – – 79
– 100 100 – – – – 100 100 – – –
– 125 125 – – – – 125 125 – – –
Rated current A
630 630 – 630 – 630
N. A.
1250 1250 – 1250 – 1250
– 1600 – – 1600 1600
2000 – – 2000 2000
– – 2500 – 2500 (1) 2500 (1)
– – 3150 – – –
– – 3600 (1) – – –
– – 4000 (1) – – –
Technical catalogue No. 1VCP000091 (2) 1VCP000091 (2)
Enclosures and fixed parts IEC
24
Enclosures and fixed parts
PowerCubeFixed parts• Tested and constructed in accordance with IEC Standards• Studied for replacement of fixed with withdrawable circuit-breakers and for
retrofitting and upgrading obsolete switchgear to the new standards• Compact dimensions and limited weights• Standardised construction• Possibility of installation both in the raised position and on the floor• Competitive solutions for economical switchgear
(1) The following fixed parts are provided for VD4 circuit-breakers: for 12 and 17.5 kV: CBF1 up to 1250 A, CBF2 up to 2000 A; for 24 kV: CBF4 up to 1250 A.(2) Up to 12 kV - 400 A.
Fixed part PB1/F PB2/F PB4/F
Panel width mm 600 750 750
Contact diameter mm 35 35 79 35
Rated voltage kV 12 17.5 12 17.5 24
Rated insulation voltage kV 12 17.5 12 17.5 24
Withstand voltage (1 min) kV (50Hz) 28 38 28 38 50
Impulse withstand voltage kV 75 95 75 95 125
Rated frequency Hz 50-60 50-60 50-60
Rated current A (40 °C) 630-1250 630-1250 1600-2000 630-1250
Rated short-time withstand current 3 s. kA 31.5 31.5 25
Overall dimensions (excluding the monoblocs)
H mm 1106 1106 1236
L mm 596 746 746
D mm 1061 1061 1338
Weight kg 64 87 88
Compatible circuit-breakers and contactors
HD4 • • •
VD4 (1) • • •
V-Contact (2) • – –
Technical catalogue No. 1VCP00253 1VCP00253 1VCP00253
H
DL
IEC
25
Fixed part L-Frame
Ratings kV 5-15
Options Standard, Roll on the floor
Certification UL, CSA
Short circuit rating kA36
58
Continuous current A 1200, 2000, 3000
Bushings Polyester glass, Porcelain
Shutters types Ground Metal, Non-Metallic
Dimensions
A 1200 2000 3000
Hmm 914 1009 1009
inch 36 39.75 39.75
Lmm 876 876 876
inch 34.5 34.5 34.5
Dmm 1120 1120 1130
inch 44.12 44.12 44.5
ANSI
L-Frame• Advance Design OEM Frames & Enclosures • Manufactured to meet current medium voltage industry needs• Available for efficient assembly or individual part kits• Manufactured and assembled in ISO certified factories• Designed to provide efficient interface of ADVAC or AMVAC circuit-breakers• Intelligent design, rugged frame, and durable components provide high quality
finished assembly
H
DL
26
Enclosures and fixed parts ANSI
Circuit-breaker modules• Advance Design OEM Frames & Enclosures • 38” High compartments• Modular construction allows for flexibility• 2000 and 3000 A include frontal ventilation system• 20, 25, 31.5 kA breakers compatible with 38 kA module• 40, 50 kA breakers compatible with 50 kA module
H
DL
Unit CB Module CB Module
Ratings kV 5-15 27
Options Standard, Roll on the floor Drawout
Certification A 1200, 2000, 3000 1200, 2000
Short circuit rating kA38 16
50 25
Continuous current 1200 2000 3000 1200
Bushings Polyester glass, Porcelain Porcelain
Shutter types Ground Metal, Non-Metallic Non-Metallic
Dimensions
A 1200 2000 3000 1200, 2000
H mm 878 965 965 965
inch 34.56 38 38 38
L mm 914 914 914 914
inch 36 36 36 36
D mm 987 987 987 987
inch 38.85 38.85 38.85 38.85
27
ANSI
Potential transformer modules• Advance Design OEM Frames & Enclosures • 19” High compartments• Modular construction allows for flexibility• Four transformer arrangements• Include drawout trays and racking system
Unit Transformer module Transformer module
Ratings kV 5 15
Options Drawout Drawout
Transformer arrangements Delta, Wye, L-G, L-L Delta, Wye, L-G, L-L
Connections Cable, bus Cable, bus
Insulation Polyester glass, porcelain Porcelain
Continuous current A 1200, 2000, 3000 1200, 2000, 3000
Dimensions
Hmm 437 437
inch 17.21 17.21
Lmm 914 914
inch 36 36
Dmm 987 987
inch 38.85 38.85
CPTs, fuses, compartment doors are not included.
H
DL
28
Enclosures and fixed parts ANSI
Drawout fuse modules• Advance Design OEM Frames & Enclosures • 38” High compartments• Modular construction allow for flexibility• Include basic stackable module w/ guide rails and primary connections Installed• Include drawout trays with primary contacts, fuse clips, mounting provisions, and
hardware for fuses
Unit Fuse module
Ratings kV 5-15
Connections 3-Phase L-L L-G
Number of fuses 3 2 1
Insulation Polyester glass, porcelain Polyester glass, porcelain Polyester glass, porcelain
Clip centers 9,12,15 9,12,15 9,12,15
Ferrule diameter 2.3 2.3 2.3
Dimensions
Hmm 965 965 965
inch 38 38 38
Lmm 914 914 914
inch 36 36 36
Dmm 987 987 987
inch 38.85 38.85 38.85
Fuses, secondary breakers and compartment door are not included.
H
DL
29
ANSI
Low voltage compartment• Advance Design OEM Frames & Enclosures • 19”, 38”, 57” High compartments• Modular construction allows for flexibility• Includes side mounted grommets for control wiring.• Open bottom for access to low voltage mounting locations
Unit Low voltage compartment
Ratings kV 5-15
Sizemm 433 965 1448
inch 19 38 57
Applications (mounted over) Circuit-breaker, CPT, fuse, aux. Circuit-breaker, CPT, fuse, aux. Circuit-breaker, CPT, fuse, aux.
Dimensions
Hmm 433 965 1448
inch 19 38 57
Lmm 914 914 914
inch 36 36 36
Dmm 559 559 559
inch 22 22 22
Compartment doors are not included.
H
DL
30
Enclosures and fixed parts ANSI
Modules for power transformer control• Advance Design OEM Frames & Enclosures • 38” High compartments• Available for 5, 10, 15 kVA transformers• Includes basic stackable module w/ guide rails and primary connections installed• Includes drawout trays with primary contacts, fuse clips, mounting provisions,
and hardware. Trays include primary and secondary contacts, fuse clips, fuse boots, and mounting hardware
H
DL
Unit Transformer module
CPT kVA 5, 10, 15
Connections Cable, bus
Insulation Polyester glass
Dimensions
H mm 965
inch 38
L mm 914
inch 36
D mm 481
inch 18.92
CPTs, fuses, secondary breakers and compartment doors are not included.
31
32
Gas insulated switch-disconnectors• Designed and constructed in conformity with IEC Standards• Suitable for installation in secondary distribution switchgear• Use of SF6 gas as quenching and insulation medium• Housing made of stainless steel• Sealed type apparatus, conforming with CEI EN 60694 Standards• Metal segregation between busbar and feeder compartments
(1) For other values, contact ABB. (2) 25 kA contact ABB.
SHS2
Type
Switch- disconnector IEC 60265-1
Isolator
IEC 62271-102
Earthing switch
IEC 62271-102
Line
Earthing switch
Line
Earthing switch
(SHS2 ES) Unit without fuses
Unit withfuses
Unit without fuses
Unit with fuses
Rated voltage kV 24 – – 24 – – –
Rated uninterrupted current (40 °C) A 400-630 – – 400-630 – – –
Frequency Hz 50/60 – – 50/60 – – –
Rated short-circuit making capacity
- Without spaced earthing switch kAp 31.5-40-50 31.5-40-50 N.O. – – N.O. N.O.
- With spaced earthing switch (1) kAp 31.5-40-50 – 2,5 31.5-40-50 – – –
Rated short-time withstand current - 1s (1) kA
12.5-16-20-25 (2)
12.5-16-20-25 (2) 1
12.5-16-20-25 (2) – 1
12.5-16-20-25 (2)
Rated breaking capacity
- Mainly active load service A 400-630 – – – – – –
- No-load transformer service A 4...16 – – – – – –
- No-load line service A 25 – – – – – –
- No-load cable service A 50 – – – – – –
- Ring circuit service A 400 – – – – – –
Operating mechanism T1-T1M-T2 T1-T1M-T2 T2 T3 T3 T3 T4
Test parameters for making and breaking capacity and for short-circuit making capacity (rms) (IEC 60265-1)
Test duties 1-2-3-4-
5-6-7– – – – – –
Electrical life E3 E1 E1 – E0-E1 E0 E0-E1
Test of maximum overtemperature under rated load (to Standards)
°C IEC 60694 – – IEC 60694 – – –
Mechanical life M1 M1 M1
Lightning withstand voltage (BIL 1.2/50 µs) (BIL 1.2/50 µs) (BIL 1.2/50 µs)
- Phase-Phase towards earth kVp 125 125 125
- Between open contacts kVp 145 145 145
Withstand voltage at industrial frequency
- Phase-Phase towards earth (rms) kV 1min 50 50 50
- Between open contacts (rms) kV 1min 60 60 60
Overall dimensions (basic version)
H mm 652 652 652
L mm 495 495 495
D mm 938 938 938
Technical catalogue No. 1VCP000046 1VCP000046 1VCP000046
H
DL
Switch-disconnectors IEC
33
AirswitchAir insulated switch-disconnectors• Tested and constructed in accordance with IEC Standards • AM – AR – AS Series for installation in secondary distribution switchgear• GS – IMC Series for installation directly on the wall without supports or counter
frames • Sturdy structure, isolators with finning with large exhaust lines • Conforming to the DY 513 -518 – 519 (Enel) prescriptions• Suitable for building units conforming to the DY 402 – 403 – 404 – 405 – 408
(Enel) prescriptions
(1) May vary according to the version.
Switch-disconnector AM AR-AS
Switch-disconnector • –
Insulation disconnector – •
Switchgear version • •
Wall version – –
Rated voltage kV 24 24
Withstand voltage to earth and between phases kV 50 (50-60 Hz/1min) 50 (50-60 Hz/1min)
Withstand voltage between open contacts kV 60 (50-60 Hz/1min) 60 (50-60 Hz/1min)
Impulse withstand voltage to earth and between phases kV 125 125
Impulse withstand voltage between open contacts kV 145 145
Rated frequency Hz 50-60 50-60
Rated normal current A (40 °C) 400-630 400/630/800/1250
Rated short-time withstand current (1 s) kA 12.5-16 12.5-16-20-25
Rated short-circuit making capacity kAp 31.5-40 –
Rated breaking capacity
- Mainly active load service A 400/630 –
- No-load transformer service A 4 ... 16 –
- No-load line service A 25 –
- No-load cable service A 25 –
- Ring circuit service A 400/630 –
Overall dimensions (1)
(basic version)
H mm 710 745
L mm 692 692
D mm 1356 1346
Technical catalogue No. 1VCP000043 1VCP000043
H
DL
IEC
34
NAL
NALF
Switch-disconnectors
NAL - NALFAir insulated switch-disconnectors• Tested and constructed in accordance with IEC Standards • Suitable for installation in switchgear and in distribution substations • Sturdy and simple structure which only requires minimum maintenance • Spring operating mechanism • Can be combined with protection fuses and with trip device
Switch-disconnector NAL/NALF 12 NAL/NALF 17 NAL/NALF 24 NAL/NALF 36
Switch-disconnector • • • •
Insulation disconnector • • • •
Rated voltage 12 17.5 24 36
Withstand voltage to earth and between phases kV 50 Hz 1 min 42 45 55 80
Withstand voltage between open contacts kV 48 60 70 88
Impulse withstand voltage to earth and between phases kV 75 95 125 170
Impulse withstand voltage between open contacts kV 85 110 145 195
Rated frequency Hz 50-60 50-60 50-60 50-60
Rated normal current A (40 °C) 400-630-1250 400-630-1250 400-630-1250 400-630-1000
Rated short-time withstand current kA 31.5 (1s) - 20 (3 s) 31.5 (1s) 31.5 (1s) - 16 (3 s) 25 (2s)
Rated short-circuit making capacity kA 67 50 50 50
Rated breaking capacity
- Mainly active load service A 400-630-1250 400-630-1250 400-630-1250 630-800
- Mainly capacitive load service A 16 16 16 16
- Mainly inductive load service A 150 45 80 50
Overall dimensions (basic version)
H mm 428 577 577 745
L mm 412 452 528 928
D mm 362 418 418 675
Technical catalogue No. 1YMR602160 1YMR602160 1YMR602160 1YMR602160
H
DL
IEC
35
VersaRupter MV Indoor Switch• Tested and constructed in accordance with ANSI Standards• Long Electrical and mechanical life• 500,000 switches installed in over 50 countries worldwide• Offered in both Snap Action (K-mech) and Stored energy (A-mech)• 100% Production Testing• ISO-9001
Switch-disconnector VersaRupter
Rated max voltages kV 8.25 15.00 15.00 (*) 15.50 (*) 17.00 27.00 38.00
Continuous and loadbreak current A
200 (*) 200 (*) - - 200 200 -
600 (*) 600 (*) 600 (*) 600 (*) 600 600 600
- - - - - - 800
1200 1200 1200 (*) 1200 (*) 1200 1200 -
Rated BIL kV 75 95 95 110 110 125 150
Momentary rating K-mech (RMS kA) A-Mech (Asym kA) 40 40 61 61 40 40 40
Fault closing rating K-mech (RMS kA) or A-Mech (Asym kA) 40 40 61 61 40 40 30
Electrical control options
Remote shunt trip
Auxiliary switch available
Fuse auxiliary switch
Operating Handles
Side direct drive
Front shaft drive - Type HE
Front chain drive
Interlocks
- Mechanical
- Key
Grounding switch - Type E
Ground switch interlock with VersaRupter
Fuse options
Fuse base available
Mechanical fuse tripping
Overall dimensions
Hmm 576 600 614 614 600 600 870
inch 22.68 23.62 24.17 24.17 23.62 23.62 34.25
Lmm 576 616 746 746 746 826 1184
inch 22.68 24.25 29.37 29.37 29.37 32.52 46.61
Dmm 394 511 547 547 511 511 850
inch 15.51 20.12 21.55 21.55 20.12 20.12 33.46
Weight kg 32 34 50 50 42 43 100
lbs 71 75 110 110 93 95 220
VERSARUPTER
ANSI
DL
H
(*) The bolded values in bold are UL recognized when used with chain drive handles and no motor operator. Smart style codes for UL recognized designs end with "U". Smart style codes for non-UL designs end with "N".
Snap action actuator - K-Mechanism Stored energy actuator - A-Mechanism
36
Switch-disconnectors
OJONAir insulated switch-disconnectors for indoor installation• Tested and constructed according to IEC Standards• High short-circuit capacity • Versatile operating mechanisms for various applications• Availability of safety interlocks• Possibility of connections with aluminium busbars• Compact dimensions• Silver-plated contacts• Die-cast resin insulators • Double blade contacts
Switch-disconnector OJON 1 OJON 3 OJON 12 OJON 24
Rated voltage kV 1 3,6 12 24
Impulse withstand voltage between open contacts kV 23 46 85 145
Impulse withstand voltage to earth and between phases kV 20 40 75 125
Withstand voltage between open contacts kV 12 12 32 60
Withstand voltage to earth and between phases kV 10 10 28 50
Rated frequency Hz 50-60 50-60 50-60 50-60
Rated normal current A 1000-1600 2500-4000 630…4000 630…4000
Rated short-time withstand current (1s) kA 50-80 90 31.5…60 20…60
Rated short-circuit making capacity kA 100-120 150 80…150 50…150
Technical catalogue No. OJON 4GB
IEC
37
OWIIAir insulated switch-disconnectors for indoor installation• Tested and constructed in accordance with IEC Standards• Long life and great reliability • Compact dimensions• Easy-to-use and low maintenance
Switch-disconnector OWII
Rated voltage kV 7.2...36
Rated current A 630...1600
Rated short-time withstand current kA 80/31.5
Operating mechanisms
• manual type NRWO4/..-3 or NR3 or NRK
• pneumatic type NP9
• electrical type UEMC40A
IEC
ADNNAir insulated switch-disconnectors for indoor installation• Tested and constructed in accordance with ANSI Standards • Can be equipped with ADJ type earthing switch• Very simple and reliable construction• Limited dimensions
Switch-disconnector ADNN
Rated voltage kV 12 - 24 - 36 - 72.5
Rated current A 1250 - 2500
Rated short-time withstand current kA 160/65
Operating mechanisms
• manual •
• with motor type UEMC40A
38
SECTOSGas insulated switch-disconnectors for outdoor installation- NXB with two positions (ON-OFF)- NXBD with three positions (ON-OFF-EARTH)• Tested and constructed according to IEC / ANSI / GB Standards• Adaptable to a wide range of installation systems • Simple adaptation from manual system to fully automated system• Versatile connection terminals and wide range of accessories• Limited weights• High quality insulating materials • All-steel enclosure of moving parts • High level of operating safety
Switch-disconnector SECTOS 12 SECTOS 24
Rated voltage kV 12 24
Impulse withstand voltage between open contacts kV 85 145
Impulse withstand voltage to earth and between phases kV 75 125
Withstand voltage between open contacts kV 32 60
Withstand voltage to earth and between phases kV 28 50
Rated frequency Hz 50-60 50-60
Rated normal current A 630 630
Rated current with mainly active load A 630 630
Breaking capacity for overhead lines A 50 50
Breaking capacity for cables A 50 50
Breaking capacity to earth A 50 50
Breaking capacity for cables two to earth fault A 28 28
Breaking capacity for no-load transformers A 6,3 6,3
Breaking capacity for capacitors (single bank) A 160 160
Rated short-time withstand current (3s) kA 20 20
Rated peak withstand current kA 50 50
Rated short-circuit making capacity kA 50 50
Operations at the rated current (CO) No. 100 100
Closing operations
- main contacts 50 kA (CL E2) No. 3 3
- main contacts 31.5 kA (CL E3) No. 10 10
- earthing contacts 50 kA (CL E2) No. 3 3
- earthing contacts 31.5 kA (CL E3) No. 5 5
Technical catalogue No. CNXEC – NXB EN/01/200/T-2004/01
Switch-disconnectors IEC/ANSI/GB
39
NPSAir insulated pole switch-disconnectors for outdoor installation • Tested and constructed according to IEC Standards• Modular and adaptable to all installation systems • Simple adaptation from manual system with remote control • Wide range of accessories• High quality insulating materials • Limited weights and simple construction• Limited number of components• High level of operating safety
Switch-disconnectorNPS
24 A2NPS
24 A2_J2NPS
24 B1_J2NPS
36 A2
Rated voltage kV 24 24 24 36
Impulse withstand voltage between open contacts kV 145 165 145 220
Impulse withstand voltage to earth and between phases kV 125 150 125 200
Withstand voltage under very humid conditions
- between open contacts kV 75 75 75 88
- to earth and between phases kV 55 55 55 80
Minimum distance between phases mm 310 350 260 350
Minimum insulation distance mm 200 230 200 -
Rated frequency Hz 50-60 50-60 50-60 50-60
Rated normal current A 630 630 630 630
Breaking capacity with mainly active load (100 opening-closing operations)
- 12 kV A 40 40 40 -
- 15 kV A 32 32 32 -
- 24 kV A 25 25 25 16
- 36 kV A - - - 16
Breaking capacity for cables and lines (20 opening-closing operations)
A 15 15 15 10
Rated short-time withstand current kA (1s) 20 20 16 21
Rated short-time withstand current kA (3s) 16 16 10 16
Rated peak withstand current kA 50 50 40 52
Rated short-circuit making capacity (7 closing operations)
kA 5 5 5 -
Mechanical life (operations) No. 2000 2000 2000 2000
Maximum admissible ice thickness mm 5 - - -
Ambient temperature °C -40 … +40 -40 … +40 -40 … +40 -40 … +40
Technical catalogue No. NPS 5GB
IEC
40
Switch-disconnectors
ICX-LBU NCX-EUSwitch-disconnectors for overhead lines• Tested and constructed in accordance with ANSI Standards • Use for outdoor installation • Suitable for overhead line isolation and protection • Visible isolation of the lines• Use in circuits with rated voltage from 15 to 38 kV
Model Description Application Options
ICX
Switch-disconnector for outdoor installation for overhead lines with overcurrent protection
Visible isolation Insulators made of silicone rubber (110-180 kV BIL) or of polymer resin (110-125 kV BIL)
Replaceable fuse cartridge Operation and maintenance Steel seats
15-38 kV; up to 16 kA –Can be combined with overvoltage surge arrestors
LBU
Switch-disconnector for outdoor installation
Visible isolation Insulators made of silicone rubber (110-180 kV BIL) or of polymer resin (110-125 kV BIL)
Complete with arcing chamber Overcurrent protection of capacitor banksCan be combined with overvoltage surge arrestors
15-27 kV; up to 16 kA Operation of no-load transformers Insulators made of polymer resin (110-125 kV BIL)
NCX
Disconnector for outdoor installation for overhead lines with overcurrent protection
Visible isolation Operation and maintenance
Disconnector for outdoor installation for overhead lines with overcurrent protection
15-38 kV; up to 20 kA Fuse intervention indicatorCan be combined with overvoltage surge arrestors
EUDisconnector for outdoor installation with porcelain chamber
Suitable for retrofitting and where higher guarantees of safety are required
–
ANSI
41
IEC
CEF - CMFCEF fuses for indoor and outdoor installation for transformer protection• Low value of the minimum trip current • Low dissipated power • Low arc voltage • High breaking capacity • High current limitation • Available according to IEC and BS Standards
CMF fuses for indoor installation for motor protection• High rated currents in a single element • Tests in conformity with the IEC 644 Standard, which guarantees high resistance
to overcurrents due to motor start-ups • Low value of the minimum trip current • Low power losses • Low arc voltage • High breaking capacity and high current limiting capacity
CEF and CMF fuses are available with Temperature Control Unit (TCU) as an option.
Technical characteristics and dimensions of CEF type fuses
UN IN e D I1 I3 PN Ro
kV A mm mm kA A W mΩ
3.6/7.2
6 192/292 65 50 35 26 489
10 192/292 65 50 55 16 120
16 192/292 65 50 55 26 60.2
25 192/292 65 50 72 24 30.1
40 192/292 65 50 100 30 15.3
50 192/292 65 50 190 35 10.4
63 192/292 65 50 190 40 7.8
80 192/292 87 50 250 52 6.2
100 192/292 87 50 275 57 4.4
125 292/367 87 50 375 76 3.5
160 292/367 87 50 480 101 2.6200 292/367 87 50 650 107 1.7
12
6 292/442 65 63 35 41 735
10 292/442 65 63 55 33 180
16 292/442 65 63 55 32 105
25 292/442 65 63 77 47 52.6
40 292/442 65 63 105 52 23.0
50 292/442 65 63 190 70 17.9
63 292/442 65 63 190 78 13.4
80 292/442 87 63 250 82 9.2
100 292/442 87 63 275 84 6.6
125 442/537 87 50/63 375 125 5.3
160 442/537 87 50/63 480 170 3.9200 442/537 87 50 650 174 2.7
17.5
6 292/367/442 65 20 35 54 880
10 292/367/442 65 20 55 41 271
16 292/367/442 65 20 55 67 135
25 292/367/442 65 25 72 64 67.7
40 292/367/442 87 25 100 80 34.5
50 292/367/442 87 25 210 90 23.1
63 292/367/442 87 25 210 100 17.3
80 442/537 87 25 250 124 13.8
100 442/537 87 25 275 136 9.9125 442/537 87 25 375 175 7.9
Fuses IEC
42
e
CEF-CMFABB
Technical characteristics and dimensions of CMF type fuses
Caption(1) K Coefficient corresponds to the average current value, conforming to the IEC 644 Standard.I1 = maximum short-circuit current for which the cartridge has been tested I3 = minimum trip currentPN = dissipated power at the rated currentRo = resistance at ambient temperature
UN IN e D I1 I3 PN Ro
kV A mm mm kA A W mΩ
24
6 442 65 63 35 91 1370
10 442 65 63 55 62 361
16 442 65 63 55 72 181
20 442 65 63 82 61 120.3
25 442 65 63 72 79 90.2
31.5 442 65 63 82 98 72.2
40 442 65 63 110 106 46.0
50 442 87 63 210 130 30.7
63 442 87 63 210 147 23.0
80 442/537 87 63 250 165 18.4
100 442/537 87 63 300 186 13.2
125 442/537 87 63 375 234 10.5
27
6 442 65 20 35 91 1340
10 442 65 20 55 80 451.2
16 442 65 20 55 90 225.6
25 442 87 20 72 100 112.8
40 442 87 20 110 130 55.6
50 442 87 20 210 130 30.7
63 442 87 20 210 147 23.0
80 537 87 20 250 210 23.0
100 537 87 20 300 235 15.8
36
6 537 65 20 35 137 2055
10 537 65 20 55 93 572
16 537 65 20 55 109 286
25 537 87 20 72 144 143
40 537 87 20 100 176 69.1
IEC
UN IN e D K (1) I1 I3 RO PN
MinimumI2 x t
Maximum I2 x t
kV A mm mm – kA A mΩ Watt Pre-arc
A2sInterrupted
A2s
3.6
100 292 65 0.75 50 275 3.25 49 1.4 x 104 17 x 104
160 292 65 0.7 50 400 1.94 75 3.8 x 104 50 x 104
200 292 87 0.7 50 500 1.42 75 7.6 x 104 71 x 104
250 292 87 0.6 50 760 1.03 90 14 x 104 115 x 104
315 292 87 0.6 50 900 0.85 122 21 x 104 180 x 104
7.2
63 442 65 0.75 50 175 8.63 45 0.48 x 104 6.5 x 104
100 442 65 0.75 50 275 4.93 67 1.40 x 104 18 x 104
160 442 65 0.7 50 400 2.96 119 3.8 x 104 54 x 104
200 442 87 0.7 50 500 2.15 118 7.6 x 104 75 x 104
250 442 87 0.6 50 800 1.5 6142 14 x 104 120 x 104
315 442 87 0.6 50 950 1.30 193 21 x 104 220 x 104
12
63 442 65 0.75 50 190 13.3 77 0.48 x 104 11 x 104
100 442 87 0.75 50 275 6.72 103 1.4 x 104 20 x 104
160 442 87 0.7 50 480 4.04 155 3.8 x 104 70 x 104
200 442 87 0.7 50 560 2.89 173 9.3 x104 91 x104
Fuses
D
43
Vacuum Interrupters for circuit-breaker applications
Rated voltage kV ...40.5
Rated current A ...3150
Rated short-circuit breaking current kA ...63
Mechanical operation No. ...30,000
Vacuum Interrupters for contactor applications
Rated voltage kV ...12
Rated current A ...400
Rated short-circuit breaking current kA ...4
Mechanical operation No. ...1,000,000
Vacuum Interrupters for switch-disconnector applications
Rated voltage kV ...24
Rated current A ...630
Rated short-circuit breaking current kA ...4
Mechanical operation No. ...10,000
ABB offers vacuum interrupters universal in application with more than 20 years of experience in vacuum technology. • Compact and robust design to meet the highest demands • Reliability and long life from state-of-the-art manufacturing processes • Silicone moulding for maximum external dielectric strength • Quality management to DIN EN ISO 9001 • Most frequently used switching technology worldwide for medium
voltage • Environmentally friendly and maintenance-free for life • Experience from over 2 million vacuum interrupters in service
Vacuum interrupters
44
Insulators
Indoor insulator for air insulated device• Epoxy resin • Tested and manufactured in accordance with major
electric standards • Suitable for high number of indoor applications
Model Description Rated Voltage Characteristics
IPA Post insulator with recessed metal fitting 7.2 - 40.5 kV Ultimate bending stress: 4000 - 10000 N
DC DCP DCL
Post insulator with capacitor divider for voltage indication
12 - 40.5 kV Rated current: 250 - 1000 A PSL: long type for concrete substation
SCD SF SC SCB SDY
Voltage presence indicator 1 - 40.5 kV Rated current: 630 A Coupling interface EN 50180 DIN 47636 or cable and bus-bar not insulated
IPAN PRC
Bushing air/air insulator 12 - 36 kV Rated current: 400 - 630 A
IPAR ISOF
Insulator for rotative switch-disconnector and Connection isulator with arc air suppresion
12 - 36 kV Rated current: 400 - 630 A Connection with cable or bus-bar not insulated
PRB Bushinhg air/interface with external cone plug connector
24 - 36 kV Theoretical tensile strenght: 10000 N Theoretical compressive strenght: 12000 N
PPA Bushinhg air/interface with internal cone plug connector
24 - 36 kV Rated current: 1250 A Coupling interface: EN 50180 DIN 47637
45
Indoor insulator for SF6 gas insulated device • Epoxy resin • Tested and manufactured in accordance
with major electric standards• Suitable for high number of indoor
applications
Model Description Rated Voltage Characteristics
PPC PPT PPE
Bushing with internal cone plug connection 24 - 36 kV Rated current: 250 - 1250 A Coupling interface EN 50180 DIN 47637
PTC PTS
Bushing with external cone plug connection
24 - 36 kV Rated current: 250 - 1250 A Coupling interface EN 50180 DIN 47636
PRI Bushing air/SF6 indoor use 24 kV Rated current: 630 A Connection with cable or bus-bar not insulated
INV IPF IPC
Fuse holder, bushing and accessories for RMU
24 - 36 kV Rated current: 250 A
46
Insulators
Outdoor insulator for air and SF6 gas insulated device • Cicloaliphatic resin or Silicon rubber protection• Tested and manufactured in accordance with major electric standards• Suitable for high number of outdoor applications
Model Description Rated Voltage Characteristics
IPAE Post insulator with embedded metal frame for fitting
12 - 40.5 kV Ultimate bending stress: 4000 - 10000 N
PSE PSL
Bushing air/air with higher creepage distance 12 - 36 kV Rated current: 250 - 1000 A PSL: long type for concrete substation
PGS Bushing with external cone plug connection and external rubber protection
24 - 36 kV Rated current: 630 A Coupling interface EN 50180 DIN 47636 or cable and bus-bar not insulated
PRG SF6/ Air composite bushing in epoxy resin and silicon rubber
24-36 kV Rated current: 400 - 630 A
PRE SF6/ Air bushing in epoxy resin 24 kV Rated current: 400 - 630 A Connection with cable or bus-bar not insulated
BSL Composite insulator for switch disconnector BIL 75 - 325 kV Theoretical tensile strenght: 10000 N Theoretical compressive strenght: 12000 N
PPA Bushing air/internal cone interface plug connection
24 kV Rated current: 1250 A Coupling interface: EN 50180 DIN 47637"
47
48
Apparatus for outdoor installation
OHBGas circuit-breakers for outdoor installation• Tested and constructed in accordance with IEC Standards • Operation at temperatures from – 25 °C to + 40 °C • Maintenance-free poles • Top and bottom terminals with NEMA 4 drilling• Gas pressure monitoring device as standard • Poles made with ceramic insulators, assembly using flanges with terminals • Pole covers and cups made of anodised aluminium • Pole covers with safety valves• Inspection window placed in the pole support box opposite the control signals
(1) Rated service value.
Circuit-breaker OHB 24 OHB 36 OHB 40
Rated and insulation voltage kV 24 36 40.5
Withstand voltage (1 min) kV (50Hz) 70 (dry) / 60 (wet) 95 (dry) / 80 (wet) 95 (dry) / 80 (wet)
Impulse withstand voltage kV 150 200 200
Rated frequency Hz 50-60 50-60 50-60
Rated current A (40 °C) 1250 2500 1250 2500 1250 2500
Rated breaking capacity and ratedshort-time withstand current (3 s)
kA25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5
Making capacity kA63 63 63 63 63 63
80 80 80 80 80 80
Operation sequence O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO
Opening time ms 45 ± 10 45 ± 10 45 ± 10
Arc time ms 10-15 10-15 10-15
Total interruption time ms 50-65 50-65 50-65
Closing time ms 75 ± 10 75 ± 10 75 ± 10
Overall dimensions
H mm 3090 ... 3840 3090 ... 3840 3090 ... 3840
L mm 900 900 900
D mm 686 686 686
Weight kg 900 900 900
Absolute pressure of SF6 gas (1) kPa 500 500 500
Operating temperature °C – 25 ... + 40 – 25 ... + 40 – 25 ... + 40
Tropicalization IEC: 60068-2-30, 721-2-1 • • •Electromagnetic compatibility IEC:60694, 61000-6-2, 61000-6-4 • • •
Solar radiation W/m2 1000 1000 1000
Presence of pollution IEC 815 - table 1 Level III Level III Level III
Creepage line cm/kV 3.75 2.5 2.23
Presence of surface ice mm 10 10 10
Wind speed m/s 34 34 34
Impact resistance g 0.3 0.3 0.3
Static force on the terminals
Longitudinal N 750 750 750
Transversal N 500 500 500
Vertical N 750 750 750
Technical catalogue No. 1VDS28003 1VDS28003 1VDS28003
IEC
H
L D
49
IEC
VBFVacuum circuit-breakers for outdoor installation• Tested and constructed in accordance with IEC Standards • Operation at temperatures between – 25 °C and + 40 °C • Maintenance-free poles • Top and bottom terminals with NEMA 4 drilling• Suitable for self-reclosing cycles • Poles made with ceramic insulators, assembly using flanges with terminals • Pole covers and cups made of anodised aluminium • Inspection window placed in the pole support tank opposite the operating
mechanism signals
Circuit-breaker VBF
Rated and insulation voltage kV 36
Impulse withstand voltage kV 170
Rated frequency Hz 50
Rated current A (40 °C) 1600
Rated breaking capacity and rated short-time withstand current (3 s)
kA 26.3
Making capacity kA 65.75
Operation sequence O-0.3s-CO-15s-CO
Opening time ms 40 ± 10
Arc time ms 10-15
Total interruption time ms 55 ± 10
Closing time ms 60 ± 15
Overall dimensions
H mm 3168 ... 3968
L mm 900/1900
D mm 780/1538
Weight kg 850
Operating temperature °C – 25 ... + 40
Technical catalogue No. 1VDS28003
H
L D
50
Apparatus for outdoor installation
OVRReclosers for outdoor installation for overhead lines• Tested and constructed in accordance with ANSI - IEC - Nema - IEEE Standards• Compact and sturdy design • Up to 10,000 operations • Maintenance-free poles • Embedded vacuum interrupters • Magnetic actuator• Microprocessor-based control unit
Recloser OVR 15 OVR 27 OVR 38
Service voltage kV 2.4 - 14.4 29.4 34.5
Rated voltage kV 15.5 27 38
Impulse withstand voltage kV 110/125 125 170
Withstand voltage at dry industrialfrequency at 60 Hz x 10 s
kV 50 60 70
Withstand voltage at industrial frequency in humid air 60 Hz x 10 s
kV 45 50 60
Rated uninterrupted current A 630/800/1000 630/800/1000 630/800
Breaking capacity kA 12.5 12.5 16
Pole centre distance mm 394 394 394
Phase-phase surface discharge distance mm 960 960 1288
Minimum phase-phase surface discharge distance mm 1160 1160 1260
Minimum insulation distance in free air mm 240 240 367
Maximum interruption time s 0.040 0.040 0.040
Maximum closing time s 0.060 0.060 0.060
Operating temperature °C - 40 ... + 70 - 40 ... + 70 - 40 ... + 70
Auxiliary voltage 90-264 V ac; 250 V dc and 50-150 V ac / 125 V dc with UPS
Current sensors One per phase integrated in the pole
Technical catalogue No. 1VAL2601
IEC/ANSI
51
ANSI
PadmountElectric apparatus in enclosure for outdoor installation• The range of Padmount products includes: switch-disconnectors with direct
access with fuses, switch-disconnectors with access interlocked with fuses, switch-disconnectors with current-limiting fuses, capacitor banks and metering compartments
• Several types of configurations are available with rated voltages up to 25 kV • They are suitable for outdoor installation or in environments with aggressive
atmosphere, in the presence of damp, dust, etc. in plants for industries and utilities
• The characteristics of the enclosures are such as to ensure and exceed the prescriptions of the ANSI Standards
• Technical catalogue: 1VAM2201-DB
Switch-disconnectors with direct access15-25 kV – 600 A – 40 kA
Switch-disconnectors with interlocked access 15-25 kV – 600 A – 40 kA
Switch-disconnectors with current-limiting fuses 15-25 kV – 200 A
Enclosures with capacitor banks15-25 kV – 2400 kVAR
Measurement compartments15-25-35 kV – 200-600 A
52
Apparatus for outdoor installation
AutoLinkResettable Electronic Auto Sectionalizer• Fits on a standard cutout body• Works in conjunction with an upstream recloser or circuit breaker• Field configurable and resettable as many times as needed between 6 and 215A,
and from 1 to 4 counts • Trip arm reset with no tools required• Does not require an auxiliary power source• Isolates temporary faults at the AutoLink preventing extensive outages• Detects and discriminates inrush current• Reduces operating costs and replacement of fuses• “One kV rating fits-all” design minimizes inventory
ANSI
Model AutoLink-15 AutoLink-27 AutoLink-27/33 AutoLink-33
Rated voltage kV 15 27 27/38 38
Insulation level kV BIL 110 125 150 170
Rated current A 200 200 200 200
Actuating current A 6 - 215 6 - 215 6 - 215 6 - 215
Number of counts before operation No 1 - 4 1 - 4 1 - 4 1 - 4
Short time current (1s effective) kA 4 4 4 4
Dead line detection ma < 200 < 200 < 200 < 200
Memory reset s 30 30 30 30
Asymmetrical initial (peak) kA 10 10 10 10
53
CHDCapacitors allow the reactive power to be modulated according to the load present in the network with the following advantages:• improvement of energy quality and efficiency of the electrical systems • great reduction in leaks and limited consumption • improvement of the power factor of the electrical systems• greater network stability• limitation/elimination of the penalties for inadequacy of the power factor
Capacitors IEC/ANSI
Medium voltage capacitors
Capacitor Single phase Split phase Three phase
Rated power kVar up to 900 up to 800 (400 + 400) up to 500
Rated voltage kV up to 20 up to 17.5 (phase-phase) up to 20
Rated frequency Hz 50/60 50/60 50/60
Rated current A max. 180 max. 180 max. 180
Dielectric Polypropylene film Polypropylene film Polypropylene film
Impregnant Faradol 810 (non-PCB) Faradol 810 (non-PCB) Faradol 810 (non-PCB)
Diuscharge resistor Internal Internal Internal
Lones (including resistors) W/kVar ≤ 0.15 ≤ 0.15 ≤ 0.15
54
PS_ Capitor Vacuum Switches • Maintenance free• Visual indication• Light weights and dimensions• Low power solenoid mechanism• Wide control voltage range• Few mowing parts • Trip lever for emergency operation
Capacitors
NotesClass 2 restrike in accordance to IEEE 37.66Type test certificates from independent testing facilities are available upon request.
Capacitor vacuum switch PS15 PS17 PS25 PS36
Rated maximum voltage, 50/60Hz
Ungrounded capacitor banks, line-to-line kV rms 15.5 17.5 25 38
Grounded capacitors banks, line-to-line kV rms 27 30 43 66
Impulse withstand voltage
Line to ground kV BIL 125 / 125 150 125 / 150 200
Open contact kV BIL 95 / 125 125 125 / 125 200
Withstand voltage, 60Hz
Dry, 1.0 minutes kV 50 60 60 70
Wet, 10 seconds kV 40 50 60 60
Continuous current 50/60 Hz A 200 / 400 400 200 300
Capacitive switching current (50/60Hz) A 200 / 400 400 200 300
Loading interrupting current A 5000 5000 5000 5000
Short time symmetrical withstand current (1 s) A 4500 / 5000 5000 4500 / 5000 5000
High frequency peak
Transient making current A 12000 15000 12000 15000
Transient in-rush frequency Hz 3000 / 6000 6000 6000 6000
Operating voltage range
110/120 Vac (50/60 Hz) or Vdc V 90…130 90…130 90…130 90…130
240 Vac (50/60 Hz) V 205…265 205…265 205…265 205…265
110/120 Vac (50/60 Hz) or Vdc (Electronically held) V 90…130 90…130 90…130 N/A
Nominal current A 10 10 10 30
Nominal open/close time ms 100 100 100 100
Continuous current (electronically held) mA 100 100 100 N/A
Creepage distance
Terminal to terminal mm 518 805 518 / 805 1600
inch 20.4 31.7 20.4 / 31.7 62.99
Terminal to ground mm 498 757 498 / 757 1350
inch 19.2 29.8 19.2 / 29.8 53.15
General
Weightkg 13 16 16 ≈ 110
lbs 28 35 35 ≈ 243
Operating temperature range °C - 40 … + 65 - 40 … + 65 - 40 … + 65 - 40 … + 65
°F - 40 … + 149 - 40 … + 149 - 40 … + 149 - 40 … + 149
Mechanical endurance, paired operations 50,000 50,000 50,000 50,000
ANSIANSI
55
VisiVoltPassive voltage indicator for indoor and outdoor installation• Tested and constructed according to IEC and ANSI Standards• Can be applied to all types of busbars or insulated unshielded or bare cables, of
any section and diameter • For plants with rated voltage from 3 to 36 kV• Continuous status indication • Good visibility in any light conditions • Economical solution• Maintenance-free • No auxiliary power supply• Simple installation• Can be combined with current-limiting fuses
Voltage indicator VisiVolt VV-A VisiVolt VV-B
Rated voltage of three-phase systems kV 3 - 15 13.8 - 36
Threshold voltage of three-phase systems – phase-earth and phase-phase
kV > 0.6 kV > 1.5 kV
Rated voltage single-phase systems kV 4.8 – 8 8 - 20
Threshold voltage of single-phase – phase-earth systems kV> 1 kV > 1.5 kV
< 78 % Un < 78 % Un
Rated frequency Hz 50 - 60 50 - 60
Response time
s < 1 at - 20 °C < 1 at - 20 °C
s < 3 at - 30 °C < 3 at - 30 °C
s < 10 at - 40 °C < 10 at - 40 °C
Rated short-time withstand current (1s) kA 63 63
Peak current kA 164 164
Operating temperature °C - 40 … + 85 - 40 … + 85
Breaking capacity with capacitive load at 15 kV kVar - 2500
Dimensions (height x width x depth) mm 92 x 63 x 38 92 x 63 x 38
Weight kg 0.109 0.109
Voltage indicators IEC/ANSI
56
SOC - KAPMedium voltage insulating connectors • Can be applied cold without special tools• Rapid and safe installation• Minimum removal of the cable insulation • Uniform pressure on the cable• Complete application kit for each connector • Minimum number of components• Long life • Limited number of types for cable sections from 50 to 300 mm2
SOC: shielded separable insulating connector for indoor and outdoor installation – 250-630 A – 12-24 kV• Tested and constructed according to the EN 50181, SS 244 14 45, HD 628.1 S1
and HD 629.1 S1 Standards• Connectors for XLPE type cables, insulated with single or three-pole conductor,
made of aluminium or copper• The SOC Slipover connectors are made with three layers of rubber: the central
insulating layer and the two internal and external layers • conductive to guarantee contact-proof earthing• The connectors are supplied in kits for three cables
KAP: insulating connector for indoor installation – 630 A – 12-24 kV• Tested and constructed according to the SEN 24 14 34, SS 424 14 17
Standards• Connectors for XLPE type cables, insulated with single or three-pole conductor,
made of aluminium or copper• The KAP connectors are suitable for connection of cables with gas insulated
electrical apparatus, for connection of transformers in compact substations• The connectors are supplied in kits for three cables
IEC/ANSIConnectors
57
58
Switchgear UniGear 12 UniGear 17 UniGear 24
Type of construction ( IEC 62271-200) LSC2B-PM LSC2B-PM LSC2B-PM
Rated voltage kV 12 17.5 24
Insulation levels kV 12/28/75 17.5/38/95 24/50/125
Rated current of the main busbars A (40 °C) ... 4000 ... 4000 ... 3150
Rated current of the branch connections A (40 °C) ... 4000 ... 4000 ... 2500
Rated short-time withstand current kA ... 50 ... 50 ... 31.5
Arc withstand current kA ... 50 ... 50 ... 31.5
Overall dimensions of the basic unit (with single level)
H mm 2200/2675 2200/2675 2325/2775
L mm 325(1)/550/650/800/1000 550/650/800/1000 800/1000
D mm 1340/1390 1340/1390 1560
Use of the following is foreseen:
- Vacuum circuit-breakers • • •
- Gas circuit-breakers • • •
- Vacuum contactors • – –
- Earthing switch • • •
- Microprocessor-based control unit • • •
- Instrument transformers • • •
- Measurement sensors • • •
Technical catalogue No. 1VCP000138 1VCP000138 1VCP000138
UniGear ZS1Air insulated switchgear • Tested and constructed in accordance with IEC Standards• Guaranteed arc-proof units (IAC)• Compartments segregated by means of metal partitions• Apparatus racking-in/out with the door closed• Units can be mounted against the wall• Complete with mechanical safety interlocks• Earthing switch with full making capacity• Available versions: Single level – double level – double busbar systems – 500R
with fixed Vmax circuit-breaker – 550 with withdrawable Vmax circuit-breaker – single and double level with marine approval
• Optional: Set up and/or integrated in the factory, for automation and supervision.
H
DL
Primary distribution switchgear IEC
59
UniGear ZVCAir insulated switchgear for motor control• Tested and constructed in accordance with IEC Standards • Can be coupled with UniGear ZVC type switchgear• Guaranteed internal arc proof units (IAC) • Compartments segregated by means of metal partitions • Contactor racking-in/out with the door closed • Units can be mounted against the wall • Complete with mechanical safety interlocks • Approved versions for naval applications • Complete range of motor control units for contactors with fuses• Optional: Set up and/or integrated in the factory, for automation and supervision.
Switchgear UniGear ZVC 7.2
Type of construction (IEC62271-200) LSC2B-PM
Rated voltage kV 3.6 - 7.2
Insulation levels kV 40 -60
Rated current of the main busbars A (40 °C) ... 4000
Rated current of the branch connections A (40 °C) ... 400
Rated short-time withstand current kA ... 50
Arc withstand current kA ... 50
Overall dimensions of the basic unit (with single level)
H mm 2200/2595
L mm 325
D mm 1125
Use of the following is foreseen:
- Vacuum contactors •
- Earthing switch •
- Microprocessor-based control unit •
- Instrument transformers •
- Measurement sensors •
Technical catalogue No. 1VCP000138
IEC
H
DL
60
UniGear ZS2Air insulated switchgear• Tested and constructed in accordance with IEC Standards• Guaranteed arc-proof units (IAC)• Compartments segregated by means of metal partitions• Apparatus racking-in/out with the door closed• Limited and simple maintenance activities• Complete with mechanical safety interlocks• Earthing switch with full making capacity• Studied to guarantee maximum service continuity• Optional Set up and/or integrated in the factory for automation and supervision.
Switchgear UniGear 36
Type of construction (IEC62271-200) LSC2B-PM
Rated voltage kV 36
Insulation levels kV 36/70/170
Rated current of the main busbars A (40 °C) ... 2500
Rated current of the branch connections A (40 °C) ... 2500
Rated short-time withstand current kA ... 25
Arc withstand current kA ... 25
Overall dimensions of the basic unit (with single level)
H mm 2161/2662
L mm 1000/1200
D mm 2400/2600
Use of the following is foreseen:
- Gas circuit-breakers •
- Earthing switch •
- Microprocessor-based control units •
- Instrument transformers •
Technical catalogue No. 1YTS030001
Primary distribution switchgear IEC
H
DL
61
UniGear ZS3.2Air insulated switchgear• Tested and constructed in accordance with IEC and CNS Standards• Guaranteed arc-proof units (IAC)• Compartments segregated by means of metal partitions• Apparatus racking-in/out with the door closed• Limited and simple maintenance activities• Complete with mechanical safety interlocks• Earthing switch with full making capacity• Studied to guarantee maximum service continuity• Optional Set up and/or integrated in the factory for automation and supervision.
Switchgear UniGear 36 UniGear 40.5
Type of construction (IEC62271-200) LSC2B-PM CNS
Rated voltage kV 36 40.5
Insulation levels kV 36/70/170 40.5/95/185
Rated current of the main busbars A (40 °C) ... 3150 ... 3150
Rated current of the branch connections A (40 °C) ... 3150 ... 3150
Rated short-time withstand current kA ... 31.5 ... 31.5
Arc withstand current kA Ask ABB Ask ABB
Overall dimensions of the basic unit (with single level)
H mm 2400 2400
L mm 11200 1200
D mm 2565 2565
Use of the following is foreseen:
- Vacuum circuit-breakers • •
- Gas circuit-breakers • •
- Earthing switch • •
- Microprocessor-based control unit • •
- Instrument transformers • •
Technical catalogue No. 1YHA000023 1YHA000023
IEC
H
DL
62
SafeGearAir insulated switchgear • Tested and constructed in accordance with ANSI Standards• Arc-proof units • Apparatus racking-in/out with the door closed• Solution with single or double level• Limited and simple maintenance activities• Studied to guarantee maximum service continuity
Switchgear SafeGear
Rated voltage kV 5 ... 27
Insulation levels kV 60 ... 125
Rated current of the main busbars A 1200 ... 3000
Rated short-time withstand current kA 50
Overall dimensions of the basic unit (with single level)
H mm 2413 (2603 with forced ventilation)
L mm 914
D mm 2159 ... 2591
Use of the following is foreseen:
- Vacuum circuit-breakers •
- Control units •
- Instrument transformers •
Technical catalogue No. 1VAL1001
Primary distribution switchgear
H
DL
ANSI
63
UniGear R40Air insulated switchgear with single-pole circuit-breakers, for railway traction networks • Tested and constructed in accordance with IEC Standards • Arc proof units • Reduced and simple maintenance activities• Complete range of safety locks
Switchgear UniGear R40
Rated voltage kV 40.5
Service voltage kV 27.5
Insulation levels kV 95/200
Rated current of the main busbars A 2000
Rated short-time withstand current (1s) kA 25
Arc withstand current (1s) kA 25
Number of phases No. 1
Overall dimensions of basic unit (with single level)
H mm 2600
L mm 1000
D mm 2565
Use of the following is foreseen:
- Vacuum circuit-breakers •
- Control units •
- Instrument transformers •
Technical catalogue No. 1VSR000017
IEC
H
DL
64
ZX0.2
ZX0Gas insulated switchgear with single-level busbar system • Tested and constructed in accordance with IEC Standards • Guaranteed arc proof units • Units can be installed against the wall • Complete with mechanical safety interlocks • Motor activated switch-disconnector with three positions • Medium voltage cable coupling system with connectors with external cone • Connection between the functional units by means of busbar coupling
connections • Studied to ensure maximum service continuity • Completely unaffected by environmental conditions • Optional: Set up and/or integrated in the factory, for automation and supervision.
Switchgear ZX0 12 ZX0 17 ZX0 24 ZX0.2
Type of construction GIS GIS GIS GIS
Rated voltage kV 12 17.5 24 12 - 24
Insulation levels kV 12/28/75 17.5/38/75 24/50/75 12/28/75 - 24/50/125
Rated current of the main busbars A (40 °C) ... 1250 ... 1250 ... 1250 1250 - 2500
Rated current of the branch connections A (40 °C) ... 1250 ... 1250 ... 1250 1250 - 2500
Rated short-time withstand current kA ... 25 ... 25 ... 25 31.5
Arc withstand current kA ... 25 ... 25 ... 25 31.5
Overall dimensions of the basic unit (with single level)
H mm 2100 (1)/1650 (2) 2100 (1)/1650 (2) 2100 (1)/1650 (2) 2400
L mm 400/600 (3) 400/600 (3) 400/600 (3) 600/900/1200
D mm 850 (4)/1000 (4) 850 (4)/1000 (4) 850 (4)/1000 (4) 1330
Nominal absolute SF6 gas filling pressure kPa 160 160 160 140
The use of the following is foreseen:
- Vacuum circuit-breakers • • • •
- Switch-disconnector with three positions • • • •
- Microprocessor-based control unit • • • •
- Instrument transformers • • • •
- Measurement sensors • • • •
Technical catalogue No. DECMS2313 03 DECMS2313 03 DECMS2313 03 1VBA680603
Primary distribution switchgear IEC
H
DL
(1) For all the panels in a system with circuit-breaker panels.(2) For panels without circuit-breaker.(3) For outgoing feeders with rated currents > 800 A and for panels divided individually into compartments. (4) Distance from wall > 100 mm.
65
ZX1.2Gas insulated switchgear with single level busbar system• Tested and constructed in accordance with IEC Standards • Guaranteed arc proof units • Motor activated switch-disconnector with three positions • Medium voltage cable coupling system with connectors with internal cone • Connection between the functional units by means of coupling busbar connections • Cable fastening at a height of 1250 mm • Metal partitions between the various compartments of the individual panels • Completely unaffected by environmental conditions • Special version up to 40.5 kV• Optional: Set up and/or integrated in the factory, for automation and supervision.
(1) 800 mm for branch connections with rated current > 1250 A.(2) According to the number of cables per phase.
Switchgear ZX1.2 12 ZX1.2 24 ZX1.2 36
Type of construction GIS GIS GIS
Rated voltage kV 12 24 36
Insulation levels kV 12/28/75 24/50/125 36/70/170
Rated current of the main busbars A (40 °C) ... 2500 ... 2500 ... 2500
Rated current of the branch connections A (40 °C) ... 2500 ... 2500 ... 2500
Rated short-time withstand current kA ... 31.5 ... 31.5 ... 31.5
Arc withstand current kA ... 31.5 ... 31.5 ... 31.5
Overall dimensions of the basic unit (with single level)
H mm 2100 + 200 (gas exhaust) 2100 + 200 (gas exhaust) 2100 + 200 (gas exhaust)
L mm 600/800 (1) 600/800 (1) 600/800 (1)
D mm 1300/1800 (2) 1300/1800 (2) 1300/1800 (2)
Nominal absolute SF6 gas filling pressure kPa 1.47 1.47 1.47
The use of the following is foreseen:
- Vacuum circuit-breakers • • •
- Switch-disconnector with three positions • • •
- Microprocessor-based control unit • • •
- Instrument transformers • • •
- Measurement sensors • • •
Technical catalogue No. DECMS2305 02 DECMS2305 02 DECMS2305 02
IEC
H
DL
66
Switchgear ZX1.5
Rated Voltage kV 27.5/2 x 27.5
Rated Frequency Hz 50
Rated power frequency withstand voltage
Line to earth kV 95
Line to line kV 140
Rated lighting impulse withstand voltage
Line to earth kV 200
Line to line V 325
Electrical endurance at rated short circuit current 30
Rated short-circuit breaking current for CB kA 31.5
Rated short-circuit making current kA 80
Rated peak withstand current kA 80
Rated short-time withstand current, 4s kA 31.5
Rated operating sequence O-0.3s-CO-180s-CO
Rated total opening time ms Ca. 60
Rated total closing time ms Ca. 80
Rated filling level for insulation (Pre) kPa 130
Alarm level for insulation (Pae) kPa 120
Minimum functional level for insulation (Pme) kPa 120
Degree of protection
Gas tank IP65
Low voltage compartment IP4X (1)
Ambient air temperature
Maximum °C +40
24 hour average, Maximum °C +35
Minimum °C -5
Operating altitude (2) m ...1000
Dimensions
Overall dimensions of the basic unit (with single level)
H mm 2100 (3)
L mm 1300-1800 (4)
D mm 800
Height of cable fixing mm 1250
Catalogue ZX1.5R09000202-V1EL
ZX1.5Single and two-phase gas insulated switchgear for railway applications• Tested and constructed in accordance with IEC Standards • Guaranteed arc proof units • Function separated and independent• High voltage compartment sealed• Operate easily and reliably• Longer service time, less maintenance• No gas work for assembly at site• Panel size minimum• Optional Set up and/or integrated in the factory, for automation and supervision.
Primary distribution switchgear IEC
1) Higher degree on request2) Higher altitude on request3) Additional 200mm depth for pressure release system4) Based on number of cables for each phase
H
PL
67
IEC
ZX2Gas insulated switchgear with single and double level busbar system• Tested and constructed in accordance with IEC Standards • Guaranteed arc proof units • Motor activated switch-disconnector with three positions • Medium voltage cable coupling system with connectors with internal cone • Connection between the functional units by means of coupling busbar
connections without interventions in the compartments containing gas • Studied to ensure maximum service continuity • Completely unaffected by environmental conditions • Optional Set up and/or integrated in the factory, for automation and supervision.
Switchgear ZX2 12 ZX2 24 ZX2 36 (2)
Type of construction GIS GIS GIS
Rated voltage kV 12 24 36
Insulation levels kV 12/28/75 24/50/125 36/70/170
Rated current of the main busbars A (40 °C) ... 2500 ... 2500 ... 2500
Rated current of the branch connections A (40 °C) ... 2500 ... 2500 ... 2500
Rated short-time withstand current kA ... 40 ... 40 ... 40
Arc withstand current kA ...40 ...40 ...40
Overall dimensions of the basic unit (with single level)
H mm 2300 2300 2300
L mm 600/800 (1) 600/800 (1) 600/800 (1)
D mm 1710 1710 1710
Nominal absolute SF6 gas filling pressure kPa 1.47 1.47 1.47
The use of the following is foreseen:
- Vacuum circuit-breakers • • •
- Earthing switch • • •
- Microprocessor-based control unit • • •
- Instrument transformers • • •
- Measurement sensors • • •
Technical catalogue No. DECMS2301 02 DECMS2301 02 DECMS2301 02
H
DL
(1) 800 mm for branch connections with rated current > 1250 A. (2) Special version up to 40.5 kV.
68
ZX2.2Gas insulated switchgear with single and double level busbar system• Tested and constructed in accordance with ANSI Standards • Guaranteed arc proof units • Vacuum circuit breaker characteristics: 42 kV, 200 kV BIL, 2500 A, 40 kA• Three-position disconnect/ground switches• Plug-type busbar and cable connections• Safety interlocking and view ports• Closed-door operation, grounding and testing• Compact dimensions • Optional Set up and/or integrated in the factory, for automation and supervision.
1) Higher values as per international standards on request2) Single busbar arrangements up to 4000 A on request3) Other sequences on request4) Insulating gas: sulphur hexafluoride5) All pressures stated are absolute pressures at 20°C; 100kPa = 1 bar6) Other auxiliary voltages on request7) Higher altitudes above sea level on request
Primary distribution switchgear
H
DL
ANSI
Switchgear ZX2.2
Maximum operating voltage kV 42
Rated power frequency withstand voltage kV 80 (1)
Rated lightning impulse withstand voltage kV 200
Rated frequency Hz 50/60
Rated busbars current A ...2500 (2)
Rated feeder current A ...2500
Rated peak withstand current kA ...104
Rated short-time current, 3s kA ...40
Rated short-circuit breaking current of circuit-breaker kA ...40
Rated short-circuit making current of circuit-breaker kA ...104
Rated operating sequence O - 0.3 s - CO - 3 min – CO (3)
Total break-time ms approx. 60
Make-time ms approx. 80
Insulating gas SF6 (4)
Rated filling level for insulation (5) Pre kPa/PSI 130/18.85
Alarm level for insulation (5) Pae kPa/PSI 120/17.40
Minimum functional level for insulation (5) Pme kPa/PSI 120/17.40
Rated data
Charging motor VA (W) 240
Closing coil VA (W) 250
Opening coil VA (W) 250
Auxiliary voltage V 60, 110, 125, 220 DC (6)
Degree of protection - HV live parts IP65
Ambient temperature
Maximum value °C/°F 40/104
Maximum value of 24 hour mean °C/°F 35/95
Minimum value °C/°F - 5/23
Altitude for erection above sea level (7) m/ft ...1000/3300
Basic dimensions
Overall dimensions of the basic unit (with single level)
H mm/inch 2311/91
L mm/inch 2057/81
D mm/inch 787/31.5
69
70
UniSecAir insulated switchgear• Tested and constructed in accordance with IEC Standards• Air insulation of all live parts• SF6 switch-disconnector• Removable circuit-breakers• LSC2A service continuity classification• Withdrawable circuit-breaker • Complete portfolio of functional units and accessories• Wide range of protection relays, integrated on circuit-breakers or separately
mounted • Optional Set up and/or integrated in the factory for automation and supervision.
(1) 25 kA - 2s
Switchgear UniSec 12 UniSec 17 UniSec 24
Rated voltage kV 12 17.5 24
Test voltage (50-60 Hz x 1 min) kV 28 38 50
Impulse withstand voltage kV 75 95 125
Rated frequency Hz 50-60 50-60 50-60
Rated main busbar current A 630/1250 630/1250 630/1250
Rated normal current of apparatus:
- VD4-HD4 removable circuit-breaker 630/800 630/800 630/800
- GSec gas switch-disconnector 630/800 630/800 630/800
Rated short time withstand current kA (3s) 16/21/25 (1) 16/21 16/21
Peak current kA 40/50/63 40/52.5 40/52.5
Internal arc withstand current (IAC AFLR) kA (1s) 12.5-16-21 12.5-16-21 12.5-16-21
Overall dimensionsdof the basic unit
H mm 1200 1700 1700
L mm 375/500/750 375/500/750 375/500/750
D mm 1070 1070 1070
Technical catalogue No. 1VFM200003 1VFM200003 1VFM200003
Secondary distribution switchgear IEC
H
DL
71
UniMixAir insulated switchgear• Tested and constructed in accordance with IEC Standards• Standard and arc-proof versions (IAC)• Circuit-breaker with self-supplied protection release• Can be mounted against the wall• Accessories for carrying out operating sequences using safe procedures• Vast range of functional units • Optional Set up and/or integrated in the factory for automation and supervision.
(1) P1/F Unit = 750 mm. M Unit = 500 mm.
Switchgear UniMix 12 UniMix 17 UniMix 24
Type of construction (IEC62271-200) LSC2A-PM LSC2A-PM LSC2A-PM
Rated voltage kV 12 17.5 24
Insulation levels kV 12/28/75 17.5/38/95 24/50/125
Rated current (40 °C)
- Main busbars A 400-630-800-1250 400-630-800-1250 400-630-800-1250
- Circuit-breakers A 1250 1250 1250
- Switch-disconnectors A 400-630 400-630 400-630
- Insulating switch-disconnectors A 400-630 400-630 400-630
Rated short-time withstand current (1s)P1/F, P1/E, P1/A, ASR, A, R, Rac, M, P2, P3
kA 12.5-16-20-25 12.5-16-20-25 12.5-16-20-25
Overall dimensions of the basic unit
H mm 1950 1950 1950
L mm 375-500 (1) 375-500 (1) 375-500 (1)
D mm 1210 1210 1210
Use of the following is foreseen:
- Vacuum circuit-breakers • • •
- Gas circuit-breakers • • •
- Gas switch-disconnectors • • •
- Gas insulation switch-disconnectors • • •
- Earthing switch • • •
- Instrument transformers • • •
Technical catalogue No. 1VCP000008 1VCP000008 1VCP000008
IEC
H
DL
72
UniAirAir insulated switchgear• Tested and constructed in accordance with IEC Standards• Standard and arc-proof versions (IAC)• Circuit-breaker with self-supplied protection relay• Can be mounted against the wall• Construction with pre-galvanised sheets without welding points• Vast range of functional units• Optional Set up and/or integrated in the factory for automation and supervision.
Switchgear UniAir 12 UniAir 24
Type of construction (IEC62271-200) LSC2A-PM LSC2A-PM
Rated voltage kV 12 24
Insulation levels kV 12/28/75 24/50/125
Rated current (40 °C)
- Main busbars A 400-630-800-1250 400-630-800-1250
- Circuit-breakers A 630-800-1250 630-800-1250
- Switch-disconnectors A 400-630 400-630
- Insulating switch-disconnectors A 400-630-800-1250 400-630-800-1250
Rated short-time withstand current
- Circuit-breakers kA 12.5-16-20-25 12.5-16-20
- Switch-disconnectors kA 12.5-16 12.5-16
- Insulating switch-disconnectors kA 12.5-16-20-25 12.5-16-20
Arc withstand current kA 12.5-16 12.5-16
Overall dimensions of the basic unit
H mm 1950 1950
L mm 700/750 700/750
D mm 1190/1290/1385 1190/1290/1385
Use of the following is foreseen:
- VD4 series vacuum circuit-breakers • •
- HD4 series gas circuit-breakers • •
- Switch-disconnectors • •
- Rotary insulation switch-disconnectors • •
- Earthing switch • •
- Instrument transformers • •
Technical catalogue No. 1VCP000065 1VCP000065
H
DL
IECSecondary distribution switchgear
73
IEC
SafePlus SafeRing
Switchgear SafePlus 24 SafeRing 24
Type of construction (IEC62271-200) GIS GIS
Rated voltage kV 12 17.5 24 12 17.5 24
Insulation levels kV 12/28/75 17.5/38/95 24/50/125 12/28/75 17.5/38/95 24/50/125
Rated current of the main busbars A (40 °C) ... 1250 ... 1250 ... 1250 ... 630 ... 630 ... 630
Rated current of the branch connections A (40 °C) ... 630 ... 630 ... 630 ... 630 ... 630 ... 630
Rated short-time withstand current kA ... 25 ... 25 ... 20 ... 21 (*) ... 16 ... 16
Overall dimensions of the basic unit
Module 1 2 3 4 5 1 2 3 4 5
H mm 1365 1365 1365 1365 1365 1365 1365 1365 1365 1365
L mm 371 696 1021 1346 1671 371 696 1021 1346 1671
D mm 765 765 765 765 765 765 765 765 765 765
The use of the following is foreseen:
- Vacuum circuit-breakers • •
- Switch-disconnector • •
- Earthing switch • •
- Microprocessor-based control unit • •
- Instrument transformers • •
Technical catalogue No. 1VDD006104 1VDD006104
(*) V module = 16 kA; C module = 21 kA.
Gas insulated switchgear for ring or radial networks up to 24 kV • Tested and constructed in accordance with IEC Standards • Arc proof construction • Gas containing compartments made of stainless steel • Designed for public and industrial distribution • Units can be installed against the wall • Unaffected by environmental conditions• Extremely compact and reliable • Cable connection bushings on the front • Optional Set up and/or integrated in the factory, for automation and supervision.
H
DL
74
IEC
(1) Width of basic module.
SafePlus SafeRingGas insulated switchgear for ring or radial networks up to 36 kV • Tested and constructed in accordance with IEC Standards • Arc proof construction • Gas containing compartments made of stainless steel • Designed for public and industrial distribution • Units can be installed against the wall • Unaffected by environmental conditions• Extremely compact and reliable • Cable connection bushings on the front • Optional Set up and/or integrated in the factory, for automation and supervision.
Switchgear SafePlus 36 SafeRing 36
Type of construction (IEC62271-200) GIS GIS
Rated voltage kV 36/40.5 36/40.5
Insulation levels kV 36-70-170/40.5-95-185 36-70-170/40.5-95-185
Rated current of the main busbars A (40 °C) 630 630
Rated current of the branch connections A (40 °C) ... 630 ... 630
Rated short-time withstand current kA 20/21 20/21
Overall dimensions of the basic unit
H mm 1930 1930
L mm 420 (1) 1330-1750
D mm 900 900
The use of the following is foreseen:
- Vacuum circuit-breakers • •
- Switch-disconnector • •
- Earthing switch • •
- Microprocessor-based control unit • •
- Instrument transformers • •
Technical catalogue No. 1VDD006114 1VDD006114
H
DL
Secondary distribution switchgear
75
76
REF 601
Protections- Three-phase overcurrent, first threshold (low setting) – characteristic with mini-
mum definite time or minimum inverse time – IDMT – I>- Three-phase overcurrent, second threshold (high setting) – characteristic with
minimum definite time – I>>- Three-phase short-circuit, third threshold (very high setting) – instantaneous –
I>>>- Earth fault, first threshold (low setting) – characteristic with minimum definite time
or minimum inverse time – IDMT – Io>- Earth fault, second threshold (high setting) – characteristic with minimum definite
time – Io>>
Multi-function current protection unit• Simple configuration via software• Fixed panel unit• Measurement of the phase current by means of Rogowski coil• Configurable operator interface • Non-volatile memory• Digital inputs and output contacts• CEI 0-16 certification
The REF601 multi-function unit mana-ges the current protection functions.The unit is microprocessor-based and is fitted with a continuous watchdog system.The LCD display allows local use of the unit.The REF601 relay is available for appli-cations (IDMT and DMT) according to CEI and IEC Standards.It can be combined with KEKA 250B1 type current sensors.
Relays and multi-function units
77
REF542plusMulti-purpose protection and control unit• Simple modification and upgrading of the functions via software• Graphic type operator interface with LCD display• Man-machine interface separate from the central unit• Modular hardware and software• Field units for supervision and process systems• Single type of spare parts and accessories: just one hardware type• Drastic reduction in preventive maintenance, great limitation of faults caused by
tampering and errors• Available with ATEX (94/9/EC) certification for explosive environments• Version with sensors conforming to CEI 0-16 specification
REF542plus/DKThe REF542plus/DK protection and control device according to ENEL DK5600 specification is available for distribution networks with compensated neutral.
Protections- Overcurrent- Earth fault- Voltmetric- Electric machines- Distance measurement- Residual current
Communication protocols- SPABUS- LON (ABB LAG 1.4)- Modbus RTU (in simple and dual
configuration)- IEC 60870-5-103 with VDEW
extension (German utilities association)
Functions- Internal watchdog- Shunt opening relay supervision- Circuit-breaker supervision- Power factor control- Anti-resonance protection- Rapid changeover system- Event recording and
oscilloperturbography with absolute time
The REF542plus unit integrates all the secondary functions relative to the switchgear in a single module fitted with watchdog.Thanks to the flexibility of its software, the unit can satisfy a vast range of plant requirements: protection, measurement, switching, signalling, interlocking, automation and communication.The high level of flexibility of this unit is supported by a simple and user-friendly interface.Thanks to using the REF542plus unit, each medium voltage panel becomes an integrated and autonomous unit able to carry out all the required functions.The possibility of direct connection between the switchgear and the plant management system fully achieves the integrated plant concept at the highest levels.
Technical catalogue: 1VTA000001.
Measurements- Current / Voltages- Power / Energy- Power factor- Frequency
Hardware- Man-machine interface separate from
the central unit (IP44)- Separate access to the protection and
control functions by means of distinct electronic keys
- 8 analog inputs for transformers and non-inductive sensors
- Up to 3 input/output cards:- 14 digital inputs (max. 42)- 6 power relay outputs (max. 18)- 2 signalling relay outputs (max. 6)- 1 static signalling output (max. 3)
- 4 analog outputs (0…20 or 4…20 mA)- 6 analog inputs (4…20 mA)- 3 energy meters with impulse emitters- Interface for CAN OPEN digital bus- Integrated Web Server for supervision
and monitoring- Serial service interface- Communication with supervision
systems (optic fibres or RS485)- IRIG-B interface for synchronisation
(1 ms response)
78
REF 54_ /REF 630
Protections- Self-closing for up to 5 cycles- Phase discontinuity- Earth fault with 3 thresholds- Directional earth fault with 3
thresholds- Phase overcurrent with 3 thresholds- Directional phase overcurrent with 3
thresholds- Overfrequency and underfrequency
1...5- Inrush function- Overvoltage with 3 thresholds- Undervoltage with 3 thresholds- Residual overvoltage with 3 thresholds- Synchrocheck- Thermal overload- Power factor correction bank
protection- Power factor correction bank control- Thermal overload with PT100 probes- Unbalanced load- Power factor control
Measurements- Phase currents- Residual earth current - Phase voltage- Residual voltage- Power, energy and power factor- Recording of transients and
interferences - Localisation of faults due to short-
circuit and earth fault
Power Quality Monitoring- Measurement of the current waveform
distortion- Measurement of the voltage waveform
distortion- Voltage fluctuation
Multi-function unit for substation protection, control and automation• Simple modification and upgrading of the functions by means of the configuration
software • Graphic type operator interface with LCD display• Modular hardware and software • Field units for substation automation systems • Precise localisation of faults• Monitoring of the operating conditions• Single type of spare parts and accessories: just one type of hardware• Drastic reduction of preventive maintenance, great limitation of faults caused by
tampering and errors
The REF54_/REF 630 units are desi-gned for switchgear protection and control, and to be inserted in substation automation systems.Thanks to the use of integrated digital technology, the REF units offer comple-te measurement, protection, control and monitoring functions.All the functions required are present in a single device. Therefore the use of accessory apparatus and switchgear cabling operations are reduced.The simple and user-friendly configura-tion software means specific configura-tions can be made. The graphic interface allows the events, state of the devices, measurements, alarms, etc. to be displayed, adapting to the various plant requirements.The REF54_/REF 630 units have just one configuration system common to the whole series, considerably facilita-ting its use by operators.The wide range of communication pro-tocols allows connection and integration in the plant management system.
Technical catalogue: 1MRS751818
Inputs and outputs- Up to 34 digital inputs- Up to 26 digital outputs including 2
outputs for relay trip supervision- 8 inputs RTD/DT100- Synchronisation by means of binary
input- 4 outputs 4...20 mA
Analog inputs- Connections for 4 current
transformers 1 A and 5 A- Connections for 1 current transformer
0.2 A and 1 A- Connections for 4 voltage
transformers 100 V and 120 V- 9 inputs for current/voltage sensors
CommunicationLON / SPA / Modbus / DNP 3.0 /PROFI-BUS / IEC 61850 / IEC 60870-5-103
Monitoring operating conditions- Trip supervision- Fuse fault- Circuit-breaker wear - Circuit-breaker stroke time- No. circuit-breaker operations- Circuit-breaker inactive time- Programmed maintenance alarm- Closing springs charging time- Measurement supervision- Gas pressure alarm- Timers
Relays and multi-function units
79
REM 54_/REM 630Multi-function protection and control unit for motors and generators• Simple modification and upgrading of the functions via software • A single piece of apparatus for protection and control of electric rotating machines • Minimum use of auxiliary apparatus and systems, such as relays, signalling
devices, etc. • Drastic reduction of cabling, limitation of connection errors • Predefined operating sequences which respond to plant requirements • Graphic type operator interface with LCD display • Easily expandable hardware and software • Field device for supervision and process systems • Drastic reduction of preventive maintenance, great limitation of the faults cau sed
by tampering and errors
The REM 54_/REM 630 units are designed for protection and control of rotating electric machines. They are parti cularly suitable for generators of any power, for synchronous motors and high power asynchronous motors. The REM units are also suitable for use in marine and naval plants.Thanks to the use of integrated digital technology, the REM units offer economical functions complete with measurement, protection, control and monitoring.All the necessary functions are present in a single device. The use of accessory apparatus and control switchgear cabling operations is therefore reduced.The RTD (Resistance Temperature Device) analog input allows control of the machine temperature and ventilation of the machine and ambient conditions. This allows the protection against overload to be defined precisely and the motors and generators to be managed in the best way.The simple and user-friendly configuration software allows specific applications to be made.
The graphic interface allows events, state of the devices, measurements, alarms, etc. to be displayed, adapting itself to the various plant requirements. The wide range of communication protocols allows connection and integration in the plant management system.
Technical catalogue: 1MRS750915-MUM.
Protections- Non-directional overcurrent - Directional overcurrent - Voltage-dependent overcurrent- Minimum impedance- Non-directional earth fault- Directional earth fault- Residual voltage- Directional power overload- Minimum/low power - inverse power- Minimum excitation- Overload for motors, generators and
transformers- Negative phase sequence- Overvoltage - Undervoltage- Voltage sequence- Under/over frequency - Stabilised differential: high impedance
or differential based on balanced flow- High impedance based on confined
earth fault- Inrush current of transformers and
motor start-up- Motor start-up supervision
- Minimum non-directional current - Phase inversion- Over-excitation- Synchronisation of voltage- Supervision of fuse faults- Circuit-breaker fault
Measurements- Phase and neutral current- Phase voltage- Power / Energy / Power factor / Frequency- Oscilloperturbography
Inputs/Outputs- 15 or 20 free digital inputs- 5 or 11 power outputs for closing /
opening comman d of which two with continuity control
- 7 output signals- 8 inputs for RTD
Analog inputs - Several variants available, max 9 CTs
and VTs- Up to 8 1A and 5A current
transformers - 1 for 0.2 A and 1 A current
transformers - Up to 9 100 V-120 V voltage
transformers- Up to 9 non-inductive voltage/current
sensors
Communications protocols SPA, LON, Modbus RTU/ASCII
Configuration tools - CAP 505- CAP 501
80
Relays and multi-function units
REF610Multi-function protection unit • Simple unit configuration via software • Complete protection against short-circuits, overload and earth fault • Suitable for medium voltage outgoing/incoming feeders • Four current inputs • Optional protection against internal arcs • Non-volatile memory and oscilloperturbography • Self-closing • Withdrawable unit with self-circuiting current connections
The REF 610 unit is a modern multi-function unit particularly suitable for protection of medium voltage lines (outgoing/incoming feeders). The high number of protection functions available, among which three overcurrent thresholds, two earth fault thresholds, thermal protection and three-stroke self-closing, make it a complete unit for protection of against short-circuits, overload and earth fault.The optional protection against internal arcs and numerous binary inputs and outputs considerably further increase its field of application.The simple and user-friendly man machine interface is fitted with an LCD display, with control pushbuttons control pushbuttons and with eight LEDs for signalling.The unit is withdrawable and characterised by “plug & play” connectivity. The user-friendly configuration software allows the units to be configured for each specific plant. The wide range of communication protocols available allows its integration in supervision and control systems.
Technical catalogue: 1MRS755431-MUM.
Protections- Overcurrent protection with definite
and inverse time (IDMT)- Protection against earth fault with
definite and inverse time (IDMT)- Optional protection against internal
arcs- Thermal protection for cables- Self-closing- Protection against circuit-breaker fault
Communications protocolsSPA, Modbus RTU/ASCII, IEC 60870-5-103
Configuration tools - CAP 505- CAP 501 to IEC 61131-3 Standards
81
REM610Multi-function motor protection unit • Simple unit configuration via software • Specific unit for protection of medium voltage asynchronous motors • Suitable for medium and high powered motors • Withdrawable units with self-circuiting current connections • Configurable operator interface with LEDs and with multi-lingual display • Non-volatile memory • Suitable for control of circuit-breakers and contactors • Field units for supervision and process systems
The REM610 unit is specifically designed for protection of medium voltage asynchronous motors.The unit manages the fault situations both during the motor start-up and during service with particular reference to heavy-duty applications, such as: pumps, fans, mills, presses, etc.The REM610 unit can, furthermore, be used for protection of cable and transformer lines which require protection against thermal overload or single and three-phase protection against overcurrent or non-directional earth fault.The unit is withdrawable and is characterised by “plug&play” connectivity for rapid automatic installation and is provided with simple configuration software for the best adaptation to the conditions required by the plant.The wide range of communication protocols allows connection and integration in the plant management system.
Technical catalogue: 1MRS752263-MUM.
Protections- Thermal overload for motors - Motor starting supervision- Overcurrent protection with definite
time- Cumulative outgoing feeder meter- Short-circuit- Undercurrent- Unbalance- Phase inversion- Non-directional earth fault- Thermal protection with RTD- Circuit-breaker fault- Emergency starting
Communications protocolsSPA, Modbus RTU/ASCII, IEC 60870-5-103
Configuration tools- CAP 505- CAP 501 to IEC 61131-3 Standards
82
Relays and multi-function units
REU 610
The REU610 multi-function unit manages a complete range of voltage protection functions and is the ideal completion for the REF610 line protection and REM 610 motor protection units.The unit is microprocessor-based and is fitted with a continual watchdog system.The LCD display allows local use of the unit.By means of the front communication port, local control is possible by means of a normal personal computer.On the other hand, a communication port located in the rear allows remote control.
Technical catalogue: 1MRS 756025.
Protections- Overvoltage, low threshold- Overvoltage, high threshold- Overvoltage with negative phase
sequence- Undervoltage, low threshold- Undervoltage, high threshold- Undervoltage with positive phase
sequence- Residual voltage, low threshold- Residual voltage, high threshold- Circuit-breaker fault- Relay lock
Multi-function voltage protection unit • Simple configuration via software• Wide range of integrated protection functions • Withdrawable unit• Operator interface configurable with LEDs and with multi-lingual display • Non-volatile memory• Large number of digital inputs and output contacts
Communications protocols and modules - SPA-bus, IEC 60870-5-103, Modbus
(RTU and ASCII) 1. Plastic optic fibre 2. Plastic and glass optic fibre 3. RS485- DNO 3.0 4. RS485 including protocol DNP 3.0
Configuration tools- CAP 501- CAP 505- SMS 510- LIB 510
83
REF615
Protections- Three-phase overcurrent- Directional and non-directional earth
fault- Double earth fault- Transient double earth fault- Non-directional earth fault- Non-directional sensitive earth fault- Overcurrent with inverse phase
sequence- Phase discontinuity- Thermal overload- Circuit-breaker fault- Inrush current control- Lock function - Arc protection with three sensors
REF615 is a dedicated line protection relay for protection, measurement and monitoring of substations, utilities and industrial electrical systems. It is in full accordance with the IEC 61850 Standards on the subject of communication and interoperability of automation devices for substations.The REF615 relay guarantees general protection of distribution substation overhead lines, cable lines and busbar systems. It can adapt to any radial distribution network radial regardless of its earthing principle.
Technical catalogue: 1MRS 756381.
Communications protocols and module- IEC 61850-8-1 with GOOSE
communication system- MODBUS TCP and RTU (optional)- Timing synchronisation by means of
Ethernet bus with SNTP
Configuration tools - PCM600 ver. 2.0 SP1 for setting,
configuration of the signals and management of oscilloperturbography.
- User interface based on web browser (IE 7.0 or later).
- Standard products for automation of COM600 ver. 3.2. substations
Multi-function line protection unit • Simple configuration via software• Wide range of integrated protection functions • Withdrawable unit• Configurable operator interface with LED and with multi-lingual display• Non-volatile memory• Large number of digital inputs and output contacts• Monitoring of operative conditions• Display with mimic diagram (option)• Inputs for sensors (Rogowski) - version G
84
Relays and multi-function units
REM615
ApplicationREM615 is the main protection for asynchronous motors and relative transmissions in process manufacturing. This protection is generally used on high voltage motors controlled by a circuit-breaker or contactor and on medium and large sized low voltage motors controlled by a contactor and used in various applications, such as pumps and conveyor belts, oil presses and shredders, mixers , fans and aerators.
Protection and controlREM615 offers all the functions needed to manage motor starting and normal operation of transmissions, including protection against faults and elimination of these in the case of an anomaly. The main protection functions include:• 27 three-phase undervoltage• 47 overvoltage for negative phase
sequence• 47 undervoltage for positive phase
sequence• 37 undercurrent or minimum power• 46 current negative sequence or
balance• prolonged start-ups• thermal overload• instantaneous overcurrent• overcurrent with inverse time • 51N ground fault (residual)• 51G ground fault (measured)• 51LR blocked rotor• 66 supervision of number of start-ups• 67N directional ground fault• 50BF circuit-breaker failure to open• 50L internal arc fault (optional).
Multi-function motor protection and control unit • Simple configuration via software• Protection and control for asynchronous motors• Wide range of incorporated protection functions• Compact design • Withdrawable unit• Compliance with IEC 61850 Standards• Monitoring of operative conditions• Display with mimic diagram (option)• Inputs from RTD (option)
With REM615 it is also possible to di-rectly control the circuit-breaker locally, by means of open / closed pushbuttons located on the display, or remotely if it is connected to a supervision system.To prevent unauthorized access and keep integrity of the data, the relay is provided with a user authentication systembased on a four-level role, with indivi-dual passwords for the level of inspec-tor, operator, technician and admini-strator. Access control is carried out by means of the HMI on the front panel.
Standardized communication REF615 intrinsically supports the new IEC 61850 Standard, with regard to communication between devices in sub-stations. It also supports the standard industrial Modbus® protocol, DNP3 and IEC 60870-5-103.The IEC61850 protocol is native in the 615 series and therefore, thanks to the GOOSE messaging services, defined by the protocol itself, point-to-point communication is also possible over an Ethernet network which covers the entire substation.The configuration language of the sub-station enables use of processing tools for efficient configuration and activation of the substation devices.For applications where time is a critical factor, REF615 supports the synchroni-zation function over Ethernet by means of the SNTP protocol or on a separate bus using IRIG-B.
Pre-emptive condition monitoringFor continuous monitoring of operatio-nal availability, REM615 incorporates a complete range of monitoring functions for the circuit-breaker trip circuit. Accor-ding to the configuration of the device selected, the relay monitors the status of circuit-breaker stress and wear, the spring charging time of the circuit-breaker operating mechanism and the gas pressure of the arcing chambers. The relay also measures the circuit-breaker travel time and the number of circuit-breaker operations to collect basic information for scheduling suitable circuit-breaker maintenance.
For further information, see the Guide to the REM615 product.
85
ApplicationRET615 is a protection and control relay for power transformers with two win-dings and generator transformer units.The RET615 protection is available in four standard configurations (A-B-C-D) to satisfy the most common star-centre grounding applications of power tran-sformers and the relative ground protec-tion diagrams.
Protection and controlAccording to the model, the RET615 series has the following protection functions:• 49 thermal overload• 50 instantaneous overcurrent• 51 overcurrent with inverse time • 51N ground fault (calculated)• 51G ground fault (measured)• 87T transformer differential• 87N ground fault interrupter restricted
to high or low impedance • 50BF circuit-breaker failure to open
RET615 also includes basic control functions which facilitate management of a circuit-breaker by means of the HMI (human-machine interface) front panel of the relay or by means of remote con-trols. To prevent unauthorized access and to protect integrity of the informa-tion, the IED is provided with a four-level authentication system based on the role of the user. Access control is carried out by means of the HMI front panel, the WEB HMI WEB Browser and the IED PCM600 management and control too
Multi-function transformer protection and control unit• Simple configuration via software• Protection, control, measuring and monitoring of power transformers, step-up
transformers and power transformer-generator units • Use in utility and industrial networks• Wide range of incorporated protection functions• Compact design• Withdrawable unit• Compliance with IEC 61850 Standards• Monitoring of operative conditions• Display with mimic diagram (option)• Inputs from RTD (option)
Standard Communication RET615 has native support for the new IEC 61850 Standard regarding communication between devices in the substations. The industrial Modbus® protocol is also available, as well as the consolidated DNP3 and IEC 60870-5-103 protocols.Implementation of the IEC61850 com-munication protocol for substations in RET615 foresees both vertical com-munication towards a higher system, and horizontal communication between the various IEDs. It includes the GO-OSE messaging services and remote parameter setting in accordance with 61850-8-1.The substation configuration language enables use of processing tools for ef-ficient configuration and for putting the substation devices into operation.In applications where precise event time marking is required, RET615 supports the synchronization function over Ether-net by means of the SNTP protocol or over a separate bus using IRIG-B.
Preventive monitoring A complete range of functions is availa-ble in RET615 for monitoring:• the unit itself (IRF Internal Relay
Failure).• opening circuit• state of circuit-breaker wear and
stress• operating mechanism spring charging
time• gas pressure of the poles• measurement of the circuit-breaker
run time • operation count thereby collecting the fundamental infor-mation for programming suitable circuit-breaker maintenance and optimizing management of the network.
For further information, see the Guide to the REM615 product.
RET 615
86
Relays and multi-function units
RED 615
ApplicationRED615 provides high speed, longitu-dinal differential protection, with phase selection for overhead line and cable feeders in utility and industrial distribu-tion networks. RED615 is available in three standard configurations: a pure and simple line differential protection and two extended configurations with additional protection functions. Two RED615s interconnected over a com-munication link make up a completely selective protection diagram. The pro-tection for ring and meshed distribution networks generally requires unit pro-tection solutions, also applied in radial networks containing distributed power generation.
Line differential protection and control • Simple configuration via software• Line differential protection and control p with phase selection, at two ends• Perfectly harmonized for industrial and utility power plants, including meshed and
not fully connected distribution networks, with or without decentralized power generation
• Wide range of incorporated protection functions• Compact design• Withdrawable unit• Compliance with Standards IEC 61850• Monitoring of operative conditions• Display with mimic diagram (option)
Protection and controlAccording to the model, the RED615 series has the following protection functions:• 46 negative sequence or current
balance• 49 thermal overload• 50 instantaneous overcurrent• 51 overcurrent with inverse time • 51N ground fault (residual)• 51G ground fault (measured)• 67N directional ground overcurrent • 68 transformer inrush• 87L cable residual current• 50BF circuit-breaker not opening• 79 auto-reclosing (optional)
By means of the RED615 it is also pos-sible to control the circuit-breaker di-rectly locally by means of open / closed pushbuttons located on the display, or remotely it is connected to a supervision system.To prevent unauthorized access and keep integrity of the data, the relay is provided with a user authentication system based on a four-level role, with individual passwords for the level of inspector, operator, technician and ad-ministrator. Access control is carried out by means of the HMI on the front panel.
Binary signal transferBinary signal transfer (BST) can be used for transferring blocking and inter-trip signals as well as status and position information between the local and remote line ends. The BST function includes eight binary signals, transfers among the substations by means of protection signals via wire transferred onto the communication link. The BST signals go in both directions and the signal transfer time is extremely short, in the order of a few milliseconds. The BST signal and the RED615 logic allow customizable protection and control dia-grams to be set up, to make electrical plants which will be even more highly performing in future.
RED 615
87
Standard Communication RED615 has native support for the new IEC 61850 Standard on communication in substations. The relay also supports the standard industrial Modbus® protocol, as well as the consolidated DNP3 protocols and IEC 60870-5-103.The IEC61850 protocol is native in the 615 series and therefore, thanks to the GOOSE messaging services, defined by the protocol itself, point-to-point communication over an Ethernet net-work which covers the entire substation is also possible.
Supervision of communication protection The protection communication channel between the line ends is continually supervised. Should the communication channel be interrupted or subject to interferences, the fast-acting line diffe-rential protection and all other functions are immediately blocked. This automa-tic limitation involves all the functions which rely on continuous availability of the protection communication channel. Supervision of the channel includes re-cognition of missing or delayed signals which carry analogue measurements or binary data. The resetting delay can be selected by the user.
Pre-emptive condition monitoring To guarantee operational availability of the protection, RED615 incorporates a range of monitoring and watchdog functions to supervise the hardware and software, the communication system, the circuit-breaker trip circuit and the CTs. Faults at CT level can cause un-warranted activation of the differential phase protection and the phase unba-lance protection.Therefore a CT monitoring system with rapid action immediately blocks opera-tion of the line differential protection and phase unbalance protection function on detection of an erratic CT signal. According to the configuration of the device selected, the relay monitors the state of circuit-breaker stress and wear, the spring charging time of the circuit-breaker operating mechanism and the gas pressure in the arcing chambers. The relay also measures the circuit-breaker run time and counts the number of circuit-breaker operations, therefore collecting the fundamental information for programming suitable maintenance of the circuit-breaker.
For further information, see the Guide to the RED615 product.
88
Relays and multi-function units
Line protection and control multi-function unit• Simple configuration via software• Wide range of integrated protection functions• Withdrawable unit• Configurable operator interface with multi-lingual display • Non-volatile memory• Ample number of digital inputs and output contacts• Monitoring of operating conditions• Display with mimic diagram (optional)• Integrated synchronism, load shedding and AVR functions
The REU615 device is a relay for pro-tection, measurement and monitoring of utility substations and industrial electri-cal plants.It fully complies with the IEC61850 Standard on communication and inter-operability of automation devices for substations.
UseREU615 guarantees protections for che-cking voltage, frequency, load shedding, and synchronism (25): the B version also allows the AVR (automatic voltage regulator) function.REU615 is currently available in 2 stan-dard configurations (A-B) to respond to the various line protection and control requirements.
Protection and controlAccording to the version, the REU615 series has the following protection func-tions:• 27 Phase undervoltage• 59 Three-phase overvoltage• 59N Homopolar overvoltage• 47 Reverse sequence or voltage ba-
lance• 81 Frequency• 25 Synchronism check• 90 (AVR)
By means of the REU615 it is also possible to directly control the circuit-breaker, either locally by means of open /closed pushbuttons on the display, or remotely if it is connected to a supervi-sion system.To prevent unauthorized access and keep integrity of the data, the relay is provided with a user authentication system based on a four-level role, with individual passwords for the level of inspector, operator, technician and ad-ministrator. Access control is carried out by means of the HMI on the front panel.
Standardized communicationREU615 intrinsically supports the new IEC 61850 Standard, with regard to communication between the devices in substations. It also supports the standard industrial Modbus® protocol, DNP3 and IEC 60870-5-103.
The IEC61850 protocol is native in the 615 series and therefore, thanks to the GOOSE messaging services, defined by the protocol itself, point-to-point communication is also possible over an Ethernet network which covers the entire substation.
The configuration language of the sub-station enables use of processing tools for efficient configuration and activation of the substation devices.For applications where time is a critical factor, REU615 supports the synchroni-zation function over Ethernet by means of the SNTP protocol or on a separate bus using IRIG-B.
Busbar protection by means of the GOOSE messaging functionImplementation of the IEC 61850 Standard in REU615 also includes rapid point-to-point communication over the substation bus. By using GOOSE communication, the REU615 incoming and outgoing line relays of a substation operate in synergy so as to make up a stable, reliable and high speed protec-tion system for busbars. Good quality/price protection for busbars based on GOOSE communication is obtained simply by configuring the relays, and the operative availability of the protection is guaranteed by constant monitoring of the protection relays and by the GOOSE messaging function on the substation bus. Separate physical wiring between the switchgear units is not required for horizontal communication.
REU 615
89
REAProtection system against electric arcs for distribution switchgear • Optical fibre technology • Extendable system• Universal application• Rapid trip (< 2.5 ms)• Selective protection• Automatic compensation of environmental luminosity• Self-monitoring of the components• Maintenance-free
Functions and characteristics- Total trip time less than 2.5 ms- Optic fibre sensors- Current measurement by means of
current transformers- Protection against circuit-breaker fault - Continuous self-monitoring of the
system- Compensation of environmental light
REA 101 central unit- Double electronic circuit-breaker ope-
ning control circuit- Selective trip with an additional unit- Optic fibre connection for rapid tran-
sfer of the signals- Alarm relay for circuit-breaker fault- Two RJ 45 ports for extension of the
five units per port
The REA unit makes a protection system against electric arcs inside the switchgear.It can be used in all types of switchgear and does not require structural interven-tions.In switchgear and electric plants, the REA system is an effective tool for incre-asing overall plant reliability. In plants which have been in service for a long time, the REA system also allows the switchgear residual life to be increased.The REA system is sensitive to the light developed by the arc. It is therefore able to identify faults extremely rapidly and to intervene equally rapidly. This allows the energy developed by the electric arc to be drastically limited and the amount of damage to be reduced.The REA system can be used in low and medium voltage switchgear.
Technical catalogue: 1MRS75029-MVM.
Units for finding faults REA 103 - Two fibre sensors for ring or radial con-
nection - Two signalling relays which can be acti-
vated by light
REA 105- Fibre sensor for ring or radial connection - Two outputs with high speed semicon-
ductor for circuit-breaker trip- CAN Communication bus between
two REA 101 units
REA 107- Eight optic sensors for radial connection - Two signalling relays which can be acti-
vated by light
90
Relays and multi-function units
SUE 3000
N.C. N.C.
N.O.
Unit 1 Unit 2
N.O. N.C.
Multi-function unit for rapid changeover of the power supply systems • Changeover in 30 ms • Simple modification and upgrading of functions by means of the configuration
software • Graphic type operator interface with LCD display • Man-machine interface separate from the central unit • Field device for substation automation systems • Configuration with two or three circuit-breakers • Integrated fault recorder• Inputs/outputs of analog type and static digital type and with relay
HSTS system in the configuration with two circuit-breakers without bus-tie: when no voltage is detected on the main power supply unit of the switchgear, the reserve unit closing command and the main unit opening command is launched simultaneously.
HSTS system in the configuration with three circuit-breakers with bus-tie: when no voltage is detected on one of the two power supply, the bus-tie closing command and the opening command of the unit without voltage is launched simultaneously.
The multi-function SUE 3000 unit allows rapid changeover between two alternative power supply systems.The HSTS (High Speed Transfer System) carried out by SUE 3000, is the ideal solution for critical industrial processes, where a power cut - even for just one or two cycles - can cause production process stoppage and considerable damage.This system can be fully integrated in the switchgear and is able to changeover the power supply of the main switchgear unit to an emergency alternative within a few milliseconds. Long and costly machine stoppages, damage to production equipment and production restarting downtimes are thereby avoided.The SUE 3000 HSTS allows changeover times of 100 ms to be obtained with traditional type circuit-breakers and of 30 ms with VM1 circuit-breakers in the version with rapid magnetic actuator.
Technical catalogue: 1HDK400075.
Unit 1 Unit 2
Communication- SPABUS- LON (ABB LAG 1.4)- Modbus RTU - IEC 60870-5-103 with VDEW
extension
Digital inputs and outputs with relay- 14 inputs per card- 8 outputs per card
Static digital inputs and outputs - 14 inputs per card- 9 outputs per card
Analog inputs and outputs - 6 inputs 0...20 mA or 4...20 mA - 4 outputs 0...20 mA or 4...20 mA
91
92
We offer wide range of Conventional Instrument Transformers as well as Electronic Instrument transformers, shortly called Sensors.
Our conventional Instrument Transformer portfolio includes various types of products for indoor and outdoor applications in medium voltage systems.Our main line indoor Current and Voltage transformers are designed in accordance to DIN 42600 standard thus very well fit to ABB switchgear portfolio as well as to OEM switchgear manufacturers. The indoor portfolio includes also other products used for different applications (GCBs, Generator outlets, summation CTs, etc.).The variety of our conventional ITs is used also in the outdoor environment, where hydrophobic cycloaliphatic epoxy insulation ensures the proper function of product in the heavy polluted conditions.
Reference standardsAll products comply with IEC and all IEC based standards (BS, GOST, AS) as well as IEEE (ANSI) standard. The main indoor IT portfolio is designed according to DIN dimensional standard. We are also able to deliver our products based on customer requirements.
Instrument transformers and sensors IEC
Our offering includes electronic Instrument transformers as an alternative to conventional technology. The range of Sensors is covering main ABB switchgear applications and together with IED brings wider possibilities in system solutions.
Main product typesThe conventional and electronic Instrument transformers are offered and delivered in a number of type series, which are used for measurement and protection purposes at an insulation level from 3,6 kV to 40,5 kV for both indoor and outdoor conditions.
93
Current Transformer Support (Post) Type TPUA current transformer so arranged that it acts as a support for the conductor in the primary circuit.TPU current transformers are suitable for the current ABB air insulated switchgear portfolio, OEM partners
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 6 secondary windings (12 secondary
terminals)• Secondary or primary reconnectable versions• Most standards available including DIN 42600 dimension standard • Capacitive voltage divider in CT body for voltage indicator available
Ratings
Highest voltage for equipment kV 3.6 – 36 (40.5)
Primary current A 10 - 3 200
Secondary current A 1 or 5
Frequency Hz 50 or 60
Current Transformer Support (Post) Type TPEA current transformer so arranged that it acts as a support for the conductor in the primary circuit.TPE current transformers have lower ratings suitable for secondary distribution system, OEM Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with one or two secondaries only• Secondary reconnectable versions• Most standards available • Capacitive voltage divider in CT body for voltage indicator available
Ratings
Highest voltage for equipment kV 3,6 – 24(25)
Primary current A 30 - 1 250
Rated short time thermal current kA 25/1 sec
Secondary current A 1 or 5
Frequency Hz 50 or 60
94
Instrument transformers and sensors IEC
Current Transformer Support (Post) Type KOFAA current transformer so arranged that it acts as a support for the conductor in the primary circuit.KOFA current transformers are suitable for the former ABB air insulated switchgear like MH, etc., OEM
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Primary reconnectable versions available• Most standards available Ratings
Highest voltage for equipment kV 3.6 – 24
Primary current A 10 - 2 500
Secondary current A 1 or 5
Frequency Hz 50 or 60
Current Transformer Support (Post) Type IHBFA current transformer so arranged that it acts as a support for the conductor in the primary circuit.IHBF current transformers are suitable for the former ABB air insulated switchgear like Safesix, etc., OEM
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Secondary or primary reconnectable versions• Most standards available
Ratings
Highest voltage for equipment kV 3.6 – 24
Primary current A 10 - 2 000
Secondary current A 1 or 5
Frequency Hz 50 or 60
95
IEC
Current Transformer (Bar Primary) Bushing Type TTRA current transformer with bar primary conductor so constructed that it can be used as a bushing.TTR current transformers are suitable as a bushing between two AIS compartments, different switchboards, OEM
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Secondary reconnectable versions available
Ratings
Highest voltage for equipment kV 3.6 – 24 (25)
Primary current A 100 - 2 500
Secondary current A 1 or 5
Frequency Hz 50 or 60
Current Transformer Bushing Type BB(O)A current transformer without primary conductor but with primary insulation of its own which can be used as a bushing.
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Secondary or primary reconnectable versions
Ratings
Highest voltage for equipment kV 3.6 – 24 (25)
Primary current A 600 - 5 000
Secondary current A 1 or 5
Frequency Hz 50 or 60
96
IEC
Current Transformer Bus Type KOKSA current transformer without primary conductor, but with primary insulation which can be fitted directly over a conductor or busbar.
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 4 secondary windings• KOKS 12, KOKS 17.5 current transformers are suitable for the current ABB air
insulated switchgear portfolio, OEM partners• KOKS 24 current transformers are suitable for outlets of generators, etc.
Ratings
Highest voltage for equipment kV 3.6 – 17.5 ... KOKS 12, KOKS 17.5
Primary current A 1 000 - 4 000
Highest voltage for equipment kA 17.5 - 24 ... KOKS 24
Primary current A 4 000 - 8 000
Secondary current A 1 or 5
Frequency Hz 50 or 60
Current transformer Special Application Type BDA current transformer for assembling on the cable, busbar, bushing ,...BD current transformers are suitable for the current ABB air insulated switchgear portfolio, OEM partners
Characteristics• Indoor dry type, • For measuring and protection • Secondary reconnectable versions• Most electrical standards available
Ratings
Highest voltage for equipment kV 0.72
Primary current A 100 – 1250 ... BD version A, B, C,
Primary current A 100 – 2 500 ...BD-00
Secondary current A 1 or 5
Frequency Hz 50 or 60
Instrument transformers and sensors
97
IEC
Current transformer Special Application Type BP
A current transformer for outlets of generator, etc.
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Secondary reconnectable versions• Most electrical standards available
Ratings
Highest voltage for equipment kV 3.6 – 17.5
Primary current A 2 000 - 10 000
Secondary current A 1 or 5
Frequency Hz 50 or 60
Cable Current transformer Type KOLMA and KOLASuitable for the measurement of the sum of threephase currents in a 3-phase cable. Under normal operating conditions this sum is zero. In the event of an earth-fault the sum of the currents is equal to the earth-faul current and a corresponding current flows in the secondary.These transformers are used together with static earth-fault relays. The cable current transformers can generally be used when measuring the residual current e.g. to prewarn of, or locate an earth-fault. An busbar or cable serves as the primary conductor.
Ratings
Rated voltage kV 0.72 kV
Insulating test voltage 50 Hz 1 min kV 3 kV (IEC 60044-1)
Frequency Hz 50 Hz (60 Hz)
Rated thermal current 1.2 x I pn
Short-time withstand current Ith 1 s 60 x I pn
Peak withstand current Idyn 2.5 x Ith
Secondary terminals For 6 mm2 conductor
Operating temperature range °C –5...+40
98
IEC
Cable Current transformer Type KOKM and KOKUCurrent transformers are suitable for measuring of phase currents. A busbar or cable serves as the primary conductor. Series KOKM current transformers can also be used for measuring the phase current at voltages even higher than 0.72 kV (for KOKM 06) or 1.2 kV (for KOKM 1), if the insulation of the primary conductor fulfils the respective Standards for the operating voltage. The secondary winding and ring shaped iron core is cast in resin which has good electrical and mechanical properties.
Transformer type KOKM KOKU
Rated voltage Um kV 0.72 or 1.2 0.72 or 1.2
Power frequency test voltage Up (1 min) kV 3 or 6 3 or 6
Lighting test voltage Upp kV - -
Frequency fn Hz 50 lub 60 50 lub 60
Max. primary current Ipn A 50 ÷ 10 000 50 ÷ 10 000
Rated secondary current Isn A 1 lub 5 1 lub 5
Rated thermal current Icont A 1.2 x Ipn 1.2 x Ipn
Short-time withstand current Ith (1 sec) kA 60 x Ipn 60 x Ipn
Peak withstand current Idyn kA 2.5 x Ith 2.5 x Ith
Secondary terminals For 6 mm2 conductor For 6 mm2 conductor
Operating temperature range °C - 25 … + 40 - 35 … + 40
Transport and storage °C - 40 … + 55 - 65 … + 55
Electrical standards IEC, VDE, ANSI, BS, AS, CAN IEC, VDE, ANSI, BS, AS, CAN
Instrument transformers and sensors
99
IEC
Power transformer solution Type KOLTCurrent transformers type KOLT have neither housing nor primary winding. Under operating conditions the primary winding is the power transformer’s bushing insulator, which is at the same time the main insulation of the current transformer.They are suitable for mounting inside power transformers and are suitable for operating immersed in oil, under conditions of moderate and tropical climate. These current transformers are designed for supplying measurementand protection circuits of power systems operating under rated frequency of 50 Hz.
Type KOLT
Primary current Ipn A 100 - 15 000
Rated secondary current Isn A 1 ÷ 5
Insulation level 0.72 / 3 / -
Range of rated output Sn VA 1 - 90
Number of windings 1 - 4
Conformity with Standards IEC, PN-EN, SEV, VDE, ANSI, BS, CAN, CSA, GOST
Accuracy class acc. to IEC 0.2s; 0.5s; 0.2; 0.5; 1; 3; 5; 5P; 10P; PX
FS 5; 10
ALF 5; 10; 15; 20; 25; 30
Rated frequency f Hz 50, 60
Short-time withstand thermal current Ith (1 sec) A 100xIpn max. 100 kA
Insulation class acc. to Idyn A 2.5xIth max. 250 kA
Insulation level acc. to IEC B
100
IEC
Single pole insulated voltage transformer TJCSingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJC voltage transformers are suitable for the current ABB air insulated switchgear portfolio and OEM partners.
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 3 secondary windings• Most standards available, including DIN 42600 dimension standard • Reconnectable versions available
Ratings
Highest voltage for equipment kV 3.6 – 40.5
Primary current V 3 000/V3 – 35 000/V3
Secondary current V 100/V3 - 120/V3, 100/3-120/3
Frequency Hz 50 or 60
Single pole insulated voltage transformer TJESingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJE 3, TJE 4 voltage transformers have lower ratings and are suitable for mine switchboards, OEM
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Most electrical standards available• Reconnectable versions available
Ratings
Highest voltage for equipment kV 3.6 – 12
Primary current V 3 000/V3 – 10 000/V3
Secondary current V 100/V3 - 120/V3, 100/3-120/3
Frequency Hz 50 or 60
Instrument transformers and sensors
101
IEC
Single pole insulated voltage transformer with fuse TJPSingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJP transformer is equipped with fuse connected to primary winding
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Various fuses from 300 mA to 6.3 A• Most electrical standards available• Reconnectable versions available
Ratings
Highest voltage for equipment kV 3.6 – 36
Primary current V 3 000/V3 – 30 000/V3
Secondary current V 100/V3 - 120/V3, 100/3-120/3
Frequency Hz 50 or 60
Double pole insulated voltage transformer TDCA voltage transformer which has all parts of its primary winding, including terminals, insulated from the earth at a level corresponding to its rated insulation level.
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Most standards available, including DIN 42600 dimension standard
Ratings
Highest voltage for equipment kV 3.6 – 36 (38.5)
Primary current V 3 000/V3 – 35 000/V3
Secondary current V 100 - 200
Frequency Hz 50 or 60
102
IEC
Single pole voltage transformer for special application KGUGI
Single pole insulated voltage transformer with high power output,
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Most electrical standards available
Ratings
Highest voltage for equipment kV 24 – 36
Primary voltage V 15 000/V3 – 30 000/V3
Secondary voltage V 100/V3 - 120/V3, 100/3-120/3
Thermal burden VA 2000
Frequency Hz 50 or 60
Double pole voltage transformer for special application KGUG Single pole insulated voltage transformer with high power output
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with one secondary winding• Most electrical standards available
Ratings
Highest voltage for equipment kV 24 – 36
Primary voltage V 15 000 – 30 000
Secondary voltage V 100 - 120
Thermal burden VA 2 000
Frequency Hz 50 or 60
Instrument transformers and sensors
103
IEC
Special application single pole insulated voltage transformer TJC_GSingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJC _G voltage transformers are suitable for installation in generators and CBs
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to
2 secondary windings• Special dimension
Ratings
Highest voltage for equipment kV 3.6 – 36
Primary current V 3 000/V3 – 30 000/V3
Secondary current V 100/V3 - 120/V3, 100/3-120/3
Frequency Hz 50 or 60
Special application single pole insulated voltage transformer TJP_FSingle phase voltage transformer which is intended to have one end of its primary winding directly earthed.TJP_F voltage transformers are suitable for installation in ABB AIS and OEM
Characteristics• Indoor dry type, cast resin insulated• For measuring and protection with up to 2 secondary windings• Special dimension • Various fuses from 2A to 6.3 A
Ratings
Highest voltage for equipment kV 3.6 – 17.5
Primary current V 3 000/V3 – 15 000/V3
Secondary current V 100/V3 - 120/V3, 100/3-120/3
Frequency Hz 50 or 60
104
Combi Sensor Support Type KEVCDAn electronic combined transformer so arranged that it acts as a support for the conductor in the primary circuit.
CharacteristicsThe combination of Rogowski coil principle with Resistive divider. • Indoor dry type, cast resin insulated• For measuring and protection • DIN 42600 dimension standard • Capacitive voltage divider for voltage indicator available
Ratings
Highest voltage of equipment kV 12 – 24
Rated continuous primary current A 10-3 200
Current rated transformation ratios at 50 Hz 80A/150mV; 1600A/150mV
Voltage rated transformation ratio: Hz 10000 : 1
ApplicationInside the switchgear as support type
IECInstrument transformers and sensors
Sensors – Electronic Instrument TransformersCurrent Sensors The current sensing is based on Ro-gowski coil principle, which is uniformly wound coil over the air core immune to any risk of saturation and linear over the wide range of measured currents. The output from the coil proportional to change of current is voltage, which needs to be integrated to produce the output as current.
Voltage SensorsThe voltage sensing is based on resistive or capacitive dividers with the constant division ration of 10000:1. Due to absence of ferro-magnetic material the voltage sensor is immune to ferro-resonance problems.
Combi SensorsThe sensor combines Current and Voltage sensing principles in one unit. The Rogowski coil for current sensing is combined with resistive or capacitive dividers in order to optimize the functionality of product based on the customer specification.
Product types
Support (Post)• KEVCD
Bushing• KEVCY_RE• KEVCY_SA2; KEVCY_SB3
Special Application• KEVCR• KECR• KEVA
Cable• KECA
105
Bushing Sensor Type KEVCY_REAn electronic combined instrument transformer with primary conductor so constructed that it can be used as a bushing.
CharacteristicsThe combination of Rogowski coil and Capacitive divider principles. This is very small and compact bushing type sensors for SF6 insulated switchgears.• Indoor dry type, cast resin insulated• For measuring and protection • With plug according to EN 50180 & 501• Capacitive voltage divider for voltage indicator available
Ratings
Highest voltage of equipment kV 24
Rated continuous primary current A 630
Current rated transformation ratios at 50 Hz 80A/150mV
Voltage rated transformation ratio: Hz 10000 : 1
ApplicationSF6 insulated switchgear use (Safe plus)
Bushing Sensor Type KEVCY_SA and KEVCY_SBAn electronic combined instrument transformer with primary conductor so constructed that it can be used as a bushing.
CharacteristicsThe combination of Rogowski coil and Capacitive divider principles. These are very small and compact bushing type sensors for outdoor SF6 insulated switch disconnectors.• Indoor dry type, cast resin insulated• With plug according to EN 50180 & 50181 connected to insulator for outdoor use• For measuring and protection • Capacitive voltage divider for voltage indicator available
Ratings
Highest voltage of equipment kV 24
Rated continuous primary current A 630
Current rated transformation ratios at 50 Hz 80A/150mV
Voltage rated transformation ratio: Hz 10000 : 1
ApplicationSF6 insulated outdoor switch
IEC
106
Special application Sensor Type KECR An electronic current transformer without primary conductor but with primary insulation so constructed that it can be fitted directly over a conductor of the circuit-breaker.
CharacteristicsThe product is based on Rogowski coil principle. This unique design of sensor integrated with ABB circuit breaker type eVM1 and ABB IED in low voltage compartment creates opportunity for new possibilities in Switchgear designs. • Indoor dry type, cast resin insulated• For measuring and protection
Ratings
Highest voltage for equipment kV 17,5
Rated continuous thermal current A 1250
Current rated transformation ratios at 50 Hz 180A/150mV
Application• Integrated solution with ABB circuit breakers and IEDs• Any switchgear application where Sensor ratings are suitable
IECInstrument transformers and sensors
Special application Sensor Type KEVCR 24 AC2, 24 OC2An electronic current transformer with primary conductor so constructed that it can be used on a board of circuit breaker.
CharacteristicsThe product is based on Rogowski coil principle. This unique design of sensor integrated with ABB circuit breakers type VD4/R and HD4/R and ABB IED on board the breaker creates new possibilities in Switchgear designs. • Indoor dry type, cast resin insulated• For measuring and protection
Ratings
Highest voltage of equipment kV 24
Rated continuous thermal current A630 (KEVCR 24OC2);
1250 (KEVCR 24AC2)
Current rated transformation ratios at 50 Hz 250A/150mV
Application• Integrated solution with ABB circuit breakers and IEDs• Any switchgear application where Sensor ratings are suitable
107
Special application Sensor Type KEVA (for AIS)A single phase electronic voltage transformer.
CharacteristicsThe voltage sensor is based on a resistive divider principle. This sensors is an ideal solution for Air Insulated switchgears with very dynamic voltage ratings and constant transformation ratio. The size and weight of this design are optimized to the maximum.• Indoor dry type, cast resin insulated• For measuring and protection
Ratings
Highest voltage for equipment kV 24
Voltage rated transformation ratio: 10 000 : 1
ApplicationAny air insulated switchgear application
Cable Current Sensor Type KECA, KECA 250An electronic current transformer for assembly on the insulated cable, insulated bus-bar or conductor, bushing, etc.
CharacteristicsThe Current sensor is based on Rogowski coil principle can be used in low voltage cable applications. Two designs of sensor capsulation provide different possibilities of use. • Indoor dry type, cast resin insulated• For measuring and protection
Ratings
Highest voltage for equipment kV 0.72
Rated continuous thermal current A 2000
Current rated transformation ratios at 50 Hz 80A/300A/800A/150mV – Al case sensor
Current rated transformation ratios at 50 Hz250A/150mV – plastic case sensor
ApplicationAny kind of low voltage cable application
IEC
108
Types available for outdoor installation
Current transformers – TPO 6x.xx (... 24 kV)– TPO 7x.xx (... 40.5 kV)
Single-pole voltage transformers– TJC 6 (... 24 kV)– TJC 7 (... 40.5 kV)
Two-pole voltage transformers – TJP 6.x (... 24 kV)
• Rated primary current from 10 A to 8000 A according to types
• Rated secondary current 1 A, 2 A, 5 A
• Frequency 50 - 60 Hz
• Class Windings: 0.1 - 0.2 - 0.25 - 0.5 - 0.55 - 1 - 3 Safety factor: 5 - 10 Protection: 5 P - 10 P Overcurrent factor: 5 - 10 - 15 - 20
• Special class PX (IEC 60044-1) - Uk, Rct, Ik
• Primary rated voltage from 3 kV to 35 kV (phase-earth Un / √ 3)
• Rated secondary voltage 100 V - 110 V - 100/√ 3 V - 110/√ 3 V - 100/3 V - 110/3 V
• Frequency 50 - 60 Hz
• Class Measurement winding: 0.1 - 0.2 - 0.5 - 1 Primary winding: 3 P - 6 P Auxiliary winding: 6 P
Current transformers Voltage transformers
IECOutdoor instrument transformers
109
VT GuardAnti-ferroresonance device for voltage measurement circuits• Low operating resistance • High resistance in the case of earth fault• Installation on DIN rail in low voltage compartment• Very limited dimensions• Applicable to all types of voltage transformer • Protection of a set of three transformers in open delta configuration • Highly reliable
Characteristics
Rated voltage 100 … 200 V
Area of imperceptibility 0 … 20 V
Damping time at 100 V 1 s
Ambient operating temperature - 10 °C … + 55 °C
Humidity up to 90%
Minimum storage and transport temperature down to – 30 °C
Red LED operation for earth fault
Technical catalogue No. 1VCL000031
VT Guard is a device studied to eliminate the phenomenon of ferroresonance in measurement circuits with voltage transformers. The device is particularly recommended in networks with an earthing connection. The phenomenon of ferroresonance can take place in this type of network for various reasons and can cause damage, due to overload, of the voltage transformers with the secondary winding connected to the earthing circuit.The VT Guard device has the peculiarity of coming into operation when the phenomenon appears and of remaining inactive in the case of natural unbalance between the system phases.
Instrument transformer protection IEC
110
Instrument transformers ANSI
Toroidal current transformers for indoor installation• Application in isolated circuits for low voltage• High-resistance polycarbonate insulation • Passage hole available with double diameter• Characteristic curves and test reports available on request• Component recognised as conforming to UL Standards
Characteristics
Insulation voltage V 600
Impulse withstand voltage kV 10
Rated frequency Hz 25 … 400
Rated primary voltage A 50 … 5000
Dynamic resistance 180 x rated current
Thermal resistance 80 x rated current x 1s
Continuity factor
- primary current 50-4000: 1.33 at 30 °C (ambient temperature)
1.00 at 55 °C (ambient temperature)
- primary current 5000: 1.00 at 30 °C (ambient temperature)
0.5 at 55 °C (ambient temperature)
Technical catalogue 1VAP428781
Voltage transformers for indoor installation• Application for metal-clad medium voltage switchgear• Polycarbonate and polyurethane insulation formed under vacuum• Prepared with three protection fuses• Aluminium metallic anticorrosion base• Can be installed in different positions• Characteristic curves and test reports available on request• Component recognised as conforming to UL Standards
Characteristics
Insulation voltage kV 8.7 15
Impulse withstand voltage kV 75 110
Rated frequency Hz 60 60
Rated primary voltage V 2 400 14 400
Thermal resistanceVA 1500 at 30 °C (ambient temperature)
VA 1000 at 55 °C (ambient temperature)
Precision class at 6 Hz according to IEEE Standards
- 0.3 W, X, Y, Z, and 0.6 ZZ at 120 V
- 0.3 W, X, M, Y, and 1.2 Z at 69.3 V
Technical catalogue No. 1VAP4295
111
Complete Product Portfolio for switchgear applications• Window type current transformers suitable for MV and LV switchgear
applications.• Dry-type voltage transformers encapsulated in polyurethane material.• Control Power Transformers (CPTs) encapsulated in epoxy resin.• Generator and Isolated-phase Bus Current Transformers
0.6 kV current transformers in plastic case• Current transformers enclosed in a case made of impact resistant polycarbonate.• Ratios range from 50:5 through 6000:5• Metering accuracies available from 0.3B-0.1 through 0.3B-1.8• Relaying accuracies available from C5 through C800.• Both 50 and 60 Hz designs are available.• These transformers meet applicable IEEE and NEMA standards and are UL
Recognized Components.• Applications
- Medium and low voltage switchgear- Distribution circuit-breakers.
5 kV and 15 kV indoor control power transformers (CPTs) for switchgear applications• Self-cooled, single-phase, dry-type design.• Nominal primary voltages range from 2.4 kV to 14.4 kV (60 Hz).• Secondary voltages are configured for series/parallel operation at 120 V or 240 V.• Standard basic insulation level of 60 kV for 5 kV applications and 95 kV
for 15 kV applications.• Available with 1 ± 7.5 % or 2 ± 2.5% primary taps.• The high-voltage coil is vacuum encapsulated in epoxy to seal out moisture and
contaminants, and to provide a higher ability to withstand short-circuit forces than conventional dry type transformers.
• Meets all applicable IEEE C57.13 requirements, including full-wave and chopped-wave impulse tests.
• CPTs are UL recognized components.
ANSI
112
ANSI
5 kV – 36 kV indoor voltage transformers• Designed for service in metalclad MV switchgear.• Encapsulated in polyurethane resin.• 60 kV through 200 kV basic insulation level (BIL).• Primary voltage range from 0.8 kV through 34.5 kV.• Secondary voltage ranges from 33.3 V through 500 V.• Phase to earth, phase to neutral, and phase to phase designs are available.• Metering accuracies: 0.15, 0.3, and 0.6.• Burdens: W (12.5 VA) through ZZ (400 VA).• These transformers meet all applicable ANSI and CSA standards. IEC designs are
also available.• Frequency: 50 and 60 Hz.• Metering accuracies available from 0.3B-0.1 through 0.3 B-1.8.• Relaying accuracies available from C5 through C800.• These transformers meet applicable IEEE and NEMA standards and are UL
recognized components.• Applications
- Revenue metering- Protection- Control power (thermal VA)
Generator and isolated-phase bus current transformers (GCTs and ISO-CTs)• Full range of indoor/outdoor class, shielded and un-shielded, board and resin
cast current transformers specially designed for generation metering and protection.
• In isolated phase bus compartments a ISO-Phase bus current transformer centrally positioned around non-insulated bus with adequate air space can satisfy the dielectric requirements of the bus rating.
• 0.6 kV class / 10 kV BIL rated.• Standard insulation ratings of 130°C and 155°C for high temperature
applications.• All units provided with certified test reports documenting all results in accordance
with IEEE C57.13 and/or IEC 60044-1 (and 60044-6 when applicable).• Windows sizes range from 2.5” (63.5mm) to 41” (1040mm).• Metering accuracy up to 0.15 (IEEE) with burdens of B-0.1 up to B-1.8.• Protection class ratings up to C800.
Instrument transformers
113
5 kV - 48 kV instrument transformers for outdoors • Revenue metering and protection applications.• Encapsulated in hydrophobic cycloaliphatic epoxy or polyurethane resin.• 60 kV through 250 kV basic insulation level (BIL).• Primary voltage ranges from 0.8 kV through 48 kV• Phase to earth, phase to neutral, and phase to phase designs are available.• Metering accuracies: ANSI 0.15, 0.3, 0.6, and 1.2.• Voltage transformer burdens: W (12.5 VA) through ZZ (400 VA)• Current transformer burdens: 0.1 (2.5VA) through 1.8 (45 VA).• Current transformer protection accuracies available from C5 through C800.• These transformers meet all applicable ANSI and CSA standards. IEC designs are
also available.• Frequency: 50 and 60 Hz.
Instrument transformers for outdoors • Medium voltage instrument transformers for outdoor revenue metering and
protection applications.• Low voltage outdoor/indoor current and voltage transformers for revenue
metering and protection applications.
5 kV - 36 kV indoor voltage transformers• Designed for service in metalclad MV switchgear.• Encapsulated in polyurethane resin.• 60 kV through 200 kV basic insulation level (BIL).• Primary voltage range from 0.8 kV through 34.5 kV.• Secondary voltage ranges from 33.3 V through 500 V.• Phase to earth, phase to neutral, and phase to phase designs are available.• Metering accuracies: 0.15, 0.3, and 0.6.• Burdens: W (12.5 VA) through ZZ (400 VA).• These transformers meet all applicable ANSI and CSA standards. IEC designs are
also available.• Frequency: 50 and 60 Hz.• Metering accuracies available from 0.3B-0.1 through 0.3 B-1.8.• Relaying accuracies available from C5 through C800.• These transformers meet applicable IEEE and NEMA standards and are UL
recognized components.• Applications
- Revenue metering- Protection- Control power (thermal VA)
ANSI
114
ANSI
Low voltage outdoor/indoor current and voltage transformers• 0.6 kV class / 10 kV BIL rated.• Molded in thermoplastic rubber (TPR) material.• Window and bar type current transformer designs available.• Metering accuracies: ANSI 0.3, 0.6 and 1.2.• Voltage transformer burdens: W (12.5 VA) through Y (75 VA)• Current transformer burdens: 0.1 (2.5VA) through 1.8 (45 VA).• Current transformer protection accuracies available from C5 through C400.
Special products• Bushing current transformers for power transformers and power circuit-breakers
insulated with cotton or polyester tape.• Generator and isolated-phase bus current transformers.• Split-core current transformers.• Auxiliary voltage and current transformers.
5 kV - 36 kV indoor voltage transformers• Designed for service in metalclad MV switchgear.• Encapsulated in polyurethane resin.• 60 kV through 200 kV basic insulation level (BIL).• Primary voltage range from 0.8 kV through 34.5 kV.• Secondary voltage ranges from 33.3 V through 500 V.• Phase to earth, phase to neutral, and phase to phase designs are available.• Metering accuracies: 0.15, 0.3, and 0.6.• Burdens: W (12.5 VA) through ZZ (400 VA).• These transformers meet all applicable ANSI and CSA standards. IEC designs are
also available.• Frequency: 50 and 60 Hz.• Metering accuracies available from 0.3B-0.1 through 0.3 B-1.8.• Relaying accuracies available from C5 through C800.• These transformers meet applicable IEEE and NEMA standards and are UL
recognized components.• Applications
- Revenue metering- Protection - Control power (thermal VA)
Instrument transformers
115
Bushing current transformers (BCT)• Specially made designs to fit a wide range of applications• Tape wound insulation made of cotton or polyester tape• Window sizes from 2.5” (63.5mm) to 41” (1040mm).• BCTs can provide up to 0.15 (IEEE) metering accuracy with burdens of B-0.1
up to B-1.8.• Protection class up to C800.• Continuous rated current factors of up to 4.0 times rated current.• Outdoor slip-over bushing current transformers are also available.
Split-core current transformers• 0.6 kV class / 10 kV BIL rated.• Convenient mounting around primaries which cannot be opened.• Primary current ratios are available from 100:5 to 5000:5.• Metering and protection classes available.• Two product families available for a variety of applications.• These transformers can provide a 0.3 ANSI/IEEE accuracy class with burdens
B-0.1 up to B-1.8.
Auxiliary current and voltage transformers• 0.6 kV class / 10 kV BIL rated.• Both current and voltage units available.• Used to change the effective voltage/current ratio for operating meters,
protection relays and other control devices.• Available in virtually any combination of ratio and accuracy.• Due to superior saturation characteristics, these transformers generally do not
saturate under extreme high fault currents.
ANSI
116
117
Modular prefabricated solutions for photovoltaic fields
The substation is a fundamental component of the plant for the electrical apparatus protection function and safety of operating personnel.
ABB uses prefabricated substations made of concrete whose metal reinforcement makes an equipotential homogeneous grounding mesh over the entire structure which, when then connected to the grounding system, protects the internal appa-ratus against atmospheric overvoltages and limits the effects of step and contact voltages to negligible values.
The whole structure is fully factory-assembled and tested in conformity with the CEI EN 61330 Standard. After this, it is ready to be placed on the worksite to then be put into service. Installation activities are therefore limited to cable connections among the various different substations and the field switchgear.
Transport of the substation does not require use of any exceptional means of transport. Should it be necessary to move the substation to another location, the operation is simple and rapid.
The substations are fitted with a base with the same characteristics as the housing, whose plan has the same dimensions as the substation. The base is supplied to bu-ild a sturdy platform to rest the substation on and to allow convenient cable entry. For this purpose, a series of pre-established knockout holes are provided in the walls.
The ground where the substation is to be positioned must be suitably prepared by digging and laying a layer of draining gravel to rest the base on.
The substations offered by ABB consist of a coordinated assembly of components subjected to type tests, including:– Medium voltage switchgear– Low voltage switchboards– MV/LV transformers– Inverters– Panels and auxiliary devices– Lighting plant– Connections.
The substations only have the name of the ABB manufacturer on the nameplate, which is the guarantee for the whole unit.
ABB has developed a full range of modular solutions for standard power photo-voltaic plants, incorporating its components optimally inside complete, turnkey systems, for each type of network configuration: radial, ring and distributed.
118
Substation automation systems
SD-VIEW Concept Modular automation systems for power control and management
The SD-View Concept systems use advanced and consolidated technological solutions to manage the supervision, command, control, protection and automation functions. They are normally used in management of electrical plants in industries, infrastructures, the service sector and utilities.Using the SD-View Concept systems offers important advantages, such as: improvement of the energy quality, service continuity, reduction of consumption, advanced diagnosis, increased safety, simplicity of management, etc. By exploiting the modularity of SD-View Concept, it is possible to construct flexible architectures, aimed at the specific requirements of the plant and of the administrator, ensuring perfect integration with field instruments (high voltage, medium voltage and low voltage protection apparatus, motor control switchgear, air conditioning stations, fire-fighting stations, etc.).
Characteristics• User-friendly standard symbols; when required, the
graphics can be adapted to particular customer needs • Fully scalable: information, peripherals and computers can
be added at later stages• Completely flexible (there are no limits to the type of
applications)• Architectures can be made to measure and in respect of
the plant limits• Client-Server modes easily implemented (by placing
additional operator panels elsewhere other than in the plant does not require software development)
• Redundant architectures (immunity to apparatus faults)• Multi-language function (changeover of the operator
language without having to restart the machine)• Open towards other data importation/exportation systems,
in the standard ODBC data base formats.
Example of HSI application
Example of SD-View Panel Control application
119
Example of SD-View Extend architecture
The SD-View Concept systems are available in three architectures:
SD-View BasicAllows supervision of a small power substation (a few concentrated switchgear) consisting of medium voltage and low voltage apparatus, and emergency power supply systems to be carried out.
SD-View Medium This is the solution suitable for supervising several distributed electrical substations (many pieces of distributed switchgear), consisting of medium voltage, low voltage apparatus, emergency UPS and zone switchgear. SD-View Extend Allows management of several large and distributed electrical substations, each of which consists of various pieces of high voltage, medium voltage and low voltage apparatus, emergency UPS, zone switchgear and other apparatus. The architecture also allows introduction of basic automation logics.Apart from the architectures described above, depending on the size of the installation and orientated towards management of power distribution, SD-View Concept can take on other functional roles (technological, building, Motor Control Center, etc.). Among these, we mention the two most widely used configurations.- SD-View Energy Profile which consists of software
characterisation, aimed at supervision and management of power consumption (of a factory, shopping mall, hotel, etc.). The module allows acquisition and supervision of water, gas, steam and electricity consumption, as well as calculation of the values and their attribution to the relative cost centres.
- SD-View Panel Control. This is the most suitable solution and, in view of its level of integration, the most economical one for supervision and control of a single switchgear.
The display and control unit is mounted directly in the medium and/or low voltage power distribution switchgear or, on request, in an additional dedicated panel.
SD-View Panel Control is based on Basic architecture and carries out the dual purpose of concentrating and displaying the information coming from the microprocessor-based and multi-function protection units of the power distribution switchgear.The investment in SD-View Panel Control is already amortised in the commissioning/start-up stage, allowing a simple check and set-up of the switchgear in the plant, and allows an archive of significant tracings and alarms to be set up right from the initial stages.
Local and Remote Monitoring and Technical AssistancePossible by means of usual methods (Intranet, Internet/WEB- Radio LAN, WAN, ADSL, GSM, GPRS, etc.)Sending groups of alarms by means of SMS.
ConnectionsConnections available by means of the most widespread communication standards (RS232, RS485, Ethernet, Fieldbus, etc.) using all means (copper, coax, optic fibres, wireless, etc.).
ProtocolsIt is able to interface with other systems using almost all public protocols as well as many propriety market protocols.
120
COM615Network gateway for electric substation automation systems
Characteristics• Display of all the single-line diagram primary devices • Identification of alarms and events with date, time, stall,
apparatus, description and state of the object• Control of the operating apparatus by means of separate
dialog windows • Freely defined Web links • Display of measurements• Availability of control and protection oscilloperturbography • Parameter setting tool • Diagnosis of component communication, including the
process apparatus• Four password levels • Multi-lingual support• Protocol conversion gateway for substation automation• Efficient and user-friendly configuration tool • Communication redundancy with optional LAN card• Extended support for putting into service and diagnosis• Complete management safety
ApplicationCOM615 combines the characteristics and functions of the COM605 Control and Monitoring unit and the COM610 Communication Gateway. It offers gateway functions for mapping the signals between the protection and control IED (Intelligent Electronic Device) in industrial or utility substations and higher level systems, and an HMI (Human Machine Interface) which displays the substation data and information at users’ disposal.COM615 collects the protection and control apparatus data, as well as that of the process apparatus, using different protocols. It uses web technology to show the data to the various users and to transfer that data to the NCC (Network Control Centre) or to the DCS (Distributed Control System).The protocols supported can be freely combined in a computer for substations, with the only limitation being the number of hardware interfaces present in COM615.
Connectivity packagesPackages for ABB’s protection and control IEDs are available to make the COM615 configuration more efficient. A connectivity package includes descriptions of the signal data available in the IED and the descriptions are used to automatically configure the communication master in the 3.2 COM615 gateway.The following connectivity packages are available:– REF 541/3/5, REM 543/5 and RET 541/3/5– REF 542plus– REX 521– RE_610– SPACOM (Conn Pack v. 2.0 supported by SPAJ 140, SPAJ
141, SPAJ 142, SPAJ 144, SPAD 346, SACO 16D1, SACO 16D2 and SACO 64D4)
The computer configurability and functionality for COM615 stations depends on the type of communication protocol used for communication between COM615 and the IEDs.
Design COM615 is made up of the OPC (Ole for Process Control) Data Access server and of the customer components. The OPC server guarantees access of the master/client protocol stacks to the data in the apparatus connected to the protocol.The OPC clients serve the slave/server protocol stacks to allow external systems to access the data available in the OPC server. They also serve to show the data to the embedded web server to allow external clients, connected to the COM615 by means of LAN/WAN networks, to access the data available in the web server.
Protocols available
Master Slave
LON - LAG IEC 60870-5-101
SPA IEC 60870-5-104
IEC 60870-5-103 Serial DNP 3.0
IEC 61850-8-1 DNP 3.0 LAN/WAN
Serial Modbus SPA Router
Modbus TCP External Client OPC
Serial DNP3
DNP3 TCP
Substation automation systems
121
Distributed ControlSystem
OPC Client/Server (DA,AE)
LV devicesenergy meters
Modbus RTU
COM615
Process communication
Local access
LAN / WAN
LAN / WAN
Standardweb browser
Web Server
OPC Client
IEC-104 Slave
OPC Client OPC Client
IEC 61850Client
SPA Bus Master
IEC 61850-8-1 SPA Bus
OPC Client
Overview of an industrial system
Example of COM615 configuration for substations
122
Responsive worldwide networkCapability makes all the difference
A team for every missionABB’s medium voltage product service teams are experts in their own fields. They have the knowledge and experi-ence to meet all your needs in both on and off-site activity. We are located across all five continents with service centres close to you.
Our philosophy: Responsiveness.
Solutions for every situationWith over 100 years of experience in the design, development, manufactu-ring and through-life service support of medium voltage switchgear, we have established a wealth of technical solutions to meet your specific electrical network reliability needs. ABB has the largest installed base of any switchgear manufacturer worldwide. We support our products through a comprehensive range of services that ensure optimum performance throughout their life.
Our service portfolio starts with installation and commissioning and continues right through the product’s life until eventual decommissioning.
Products we supportABB offers a comprehensive range of products for electrical distribution networks.
We supply:• primary air and gas insulated
switchgear• circuit breakers, switches, contactors• outdoor switchgear• secondary switchgear, ring main units• compact substations• distribution protection and control.
In addition, we maintain archives con-taining complete technical information on a wide range of our legacy products: ABB, ASEA, BBC, Calor Emag, SACE, Strömberg, Gardy, EJF, ITE, ZWAR, LK NES, Westinghouse. These products remain fully supported, including options to extend their life through retrofit and upgrade services to include the latest technology standards.
Peace of mindOur service offerings are designed to maintain the highest levels of reliability throughout the product’s life cycle.
• Born healthy: through ABB’s expert installation and commissioning
• Stay healthy: through ABB’s certified maintenance and repair services
• Enjoy better life: through ABB’s engineering and consulting service
• Gain a new lease of life: through applying the latest ABB technology to upgrade or retrofit.
Medium Voltage Product Service
123
Product life cycle servicesPerfect care for Medium Voltage switchgear
Installation and commissioningABB certified service engineers provide expert on-site installation and commis-sioning of our equipment. Our start-up and commissioning servi-ces range from installation support, to full on-site project management.
Benefits:• lower risk• faster start-up• optimum life cycle performance.
Spare partsSpare parts availability is critical to ongoing operations.
We maintain a comprehensive stock of certified ABB parts, guaranteeing their availability throughout the product life cycle. For urgent parts requests, our logistics personnel and partners are available 24-hours a day to provide immediate emergency response.
Spares are stocked throughout our global network of service units, inclu-ding everything from individual compo-nents to complete assemblies.
Benefits:• enhanced product reliability by using
high quality certified parts• improved uptime due to guaranteed
delivery• global logistics network ensures fast
delivery.
TrainingA skilled and efficient workforce is a plant’s most valuable asset. ABB can help by providing a range of product training courses, which typically cover:• safety procedures and correct
product operation• routine maintenance• basic fault finding.
Training courses are normally provided by our local ABB service office and if required, training can be provided on site.
Benefits:• long term product performance
through correct operation• improved safety• reduced downtime.
Maintenance and field servicesOur experienced service professionals provide a range of on-site services to ensure the reliability of your installed switchgear.
Services include:• planned maintenance• on-site or workshop repairs• emergency call-out to reduce
downtime• long term service agreements to
maintain peak performance.
Benefits• field service by certified service
technicians• faster response• improved equipment utilization.
124
Life extension and upgradesFrom installation to end of life
Retrofit and refurbishmentMany ABB products will provide use-ful service for 30-40 years or more. Throughout the product life cycle, we can provide solutions that expand the functionality and extend the life of your switchgear, while maintaining the value of your core investment.
Options include:• complete overhaul and refurbishment
of switchgear to original specification with warranty
• switchgear upgrades through retrofitting of switching devices
• protection and control upgrades for increased functionality
• upgrades to improve safety, such as the installation of arc detection and fast switching systems.
Benefits:• cost-effective alternative to
replacement• maximize asset investment
performance• incorporate latest technology to
increase safety, performance and functionality.
ExtensionShould you need to expand your electrical network, ABB has the full capability to provide additional circuits for existing switchboard configurations.
We can supply equipment that matches the original specification for the exten-sion of both current and phased out switchgear.
Benefits:• maintain equipment and operating
procedures and safety standards• ensure consistent technical standards• optimization of spares and
maintenance.
Medium Voltage Product Service
125
Performance improvementGetting the best from your switchgear
Monitoring and diagnosisABB can call on a number of condition monitoring solutions to measure the key parameters of installed equipment. We can retrofit monitoring systems into existing switchgear to provide information on equipment performance for increased flexibility in planning maintenance shutdowns. In addition, diagnostic information helps identify negative product performance trends and supports proactive correction.
Benefits:• proactive intelligent action to reduce
risk of failure• access to expert analysis• 24-hour, continuous asset monitoring.
Engineering and consultingABB provides a range of engineering and consulting services for medium voltage switchgear including:• recommendations on product
application, upgrades or replacement• fault finding and diagnostics• customized engineered switchgear
solutions• switchgear decommissioning and
disposal• safety, health and environmental
practices to meet regulatory compliance and safeguard your licences to operate.
Benefits:• access to expert product specialists• sharing of global best practices• combined analysis and
implementation capability.
Site auditsABB is a world leader in the field of medium voltage switchgear and has vast experience in a wide variety of applications. Our service experts can conduct audits on existing installations to assess the condition of the equipment. These audits can be structured to minimize outages within your network. A typical audit includes:• documenting substation equipment• assessment of the condition of the
equipment• recommendations for maintenance,
replacement or refurbishment.
Benefits:• quantified analysis of installed
switchgear• evaluation of risk profile• proactive customized
recommendations to maintain equipment performance.
126
Global experience applied to local solutionsABB is one of the world’s largest power transmission and distribution manufacturers offering a wide range of services which cover an extensive global installed base of switchgear.The best practices worldwide and more than 100 years of experience and innovation are incorporated in every delivery we make. We work in partnership with you to ensure that you get the very best service in the fastest possible time.
Expert global networkThrough ABB you can access more than 1000 technical experts located around the world. Thanks to our global certifica-tion program, our extensive network of specialists provides consistent delivery to the highest service and safety standards.
Our service teams are available 24/7 no matter where you are based – in any of the five continents – with ABB at your service you’ll always have peace of mind.
Full service portfolioWhatever your needs, we support our switchgear installations with a full ser-vice portfolio that covers every network application, from large to small.Each and every job, on or off-site, is accurately assessed, utilizing highly developed skills and technical tools to ensure the best outcome. Our solutions take all factors into considera-tion, including technical, financial, environmental and safety aspects. The result is a reliable and long lasting solution.
Life cycle supportABB has several long established global switchgear factories and a robust R&D infrastructure. Combined with our extensive network of local service centres this enables us to provide the very highest standards of product support from installation to end of life. It doesn’t matter how old your switchgear is, with ABB there is always a solution.
Always one step aheadStaying ahead means taking the right decisions, at the right time, based on the right information.ABB Medium Voltage product service aims to work as an active partner in your business. At all times we support our installed base through proactive service offerings that ensure high reliability and optimal performance of your switchgear.
Your global service partnerResponsive service and expert support
Product life cycle services
Cus
tom
er n
eed
s
• Installation and commissioning• Spare parts• Maintenance and field service• Training
• Life cycle product support• Highest product reliability and fast
service response• Optimized maintenance investment
AB
B S
olu
tions • Retrofit and refurbishment
• Extension
• Exploit the latest technology for highest safety standards
• Cost-effective life extension• Increase functionality
Life extension and upgrade
• Monitoring and diagnostics• Engineering and consulting• Site audits
• Reduce risk through pro-active service approach
• Utilize real-time data for fast recovery• Optimize asset performance through
condition analysis
Performance improvement
Medium Voltage Product Service
127
Product life cycle services
Installation and commissioning:• lower risk• faster start-up• ensure product life cycle
performance.
Spare parts:• product reliability through high quality
certified parts• improved uptime due to guaranteed
delivery• global logistics network ensures fast
delivery.
Training:• long term product performance
through correct operation• improve safety• lower downtime.
Maintenance and field services:• field service by certified service
technicians• faster response• improved equipment utilization.
Life extension and upgrades
Retrofit and refurbishment:• cost-effective alternative
to replacement• maximize investment performance of
assets• incorporate latest technology to
increase safety, performance and functionality.
Extension:• maintain equipment and operating
procedures and safety standards• ensure consistent equipment
technical standards• optimization of spares and
maintenance.
Performance improvement
Monitoring and Diagnostics:• proactive intelligent action to reduce
risk of failure• access to expert analysis• 24-hour continuous asset monitoring.
Engineering and consulting:• access to expert product specialists• sharing of global best practices• combined analysis and
implementation capability.
Site audits:• quantified analysis of installed
switchgear• evaluation of risk profile• pro-active customized
recommendations to maintain equipment performance.
128
Notes
129
Notes
130
Notes
131
1VC
P00
0112
- R
ev.
H,
en -
MV
Gen
eral
Cat
alog
ue -
201
0.08
(gs)
(b)
Contact us
Your sales contact: www.abb.com/contactsMore product information: www.abb.com/productguide
The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product.
Copyright 2010 ABB.All rights reserved.