Catalog Ktc 200pag(en) Debu024en

200
Prefabricated busbar trunking from 1000 to 5000 A Canalis ® Catalogue Canalis KTC

Transcript of Catalog Ktc 200pag(en) Debu024en

  • Prefabricated busbar trunking from 1000 to 5000 A

    Canalis

    CatalogueCanalis KTC

  • K9CE01010

    PD

    2023

    81

    PD

    2023

    82

    PD

    2023

    43

    1Schneider Electric

    Intr

    oduc

    tion

    In decentralised distribution,Canalis hits the high note!

    Canalis on its second world tourTo better meet your needs, Canalis extends its system solutions.New low and medium power busbar trunking products.Pre-equipped luminaires.Strip lighting.Specially designed cable trays.

    A total coordination with theSchneider Electric systemCanalis is now part of a comprehensive offering of Schneider Electric products designed to operate together. This concept covers all low and medium voltage electrical distribution components. The result is an optimised electrical installation with even higher performance through full electrical, mechanical and communication compatibility.With the new Canalis range, you get a complete, tested distribution solution that complies with standards. It is perfectly suited to traditional applications (factories, warehouses, etc.) and to the distribution of electrical power from the incoming transformer on through to all types of loads in offi ces, commercial premises, laboratories, etc.

    Canalis KT is changing to provide you with

    more fl exibility. The adjustable section adapts to the worksite thus making sure you meet deadlines.

    bbbbb

    b

    ease of connection with the plug and play transformer and switchboard connections.

    more assistance. Our teams will assist you throughout your project.

    b

    b

    Canalis moves forward without changing the way you workThe new Canalis range is fully compatible with the existing range.An existing installation can be upgraded without any problem.

    More than 50,000 km of Canalis busbar trunking has been sold around the world.

  • K9CE01020

    PD

    2020

    43P

    D20

    2044

    PD

    2021

    55

    2 Schneider Electric

    Intr

    oduc

    tion

    With Canalis, you play all the right notes!

    Distribution systems Schneider Electric offers different distribution systems to fi t your operating needs.

    Centralised distributionFor all continuous processes:cement plantsoil and gaspetrochemicalssteelpaper, etc.Centralised distribution offers:continuity of servicecombined distribution of power, control and monitoring circuitssupervision, etc.

    Our solutions:Prisma Plus and Okken switchboards.

    bvvvvvbvvv

    b

    Decentralised distributionFor manufacturing industries:mechanicaltextileslumberinjection mouldingelectronicspharmaceuticalslivestock, etc.Decentralised distribution lets you:design installations without layout detailsupgrade without shutting down productionget systems up and running sooner thanks to faster installationgenerate savings depending on the number of loads.

    Our solutions:Prisma Plus switchboardsCanalis busbar trunking.

    bvvvvvvvbvvvv

    bb

    Combined distributionWhere the advantages of both centralised and decentralised distribution are required.

    Commercial and service buildings:offi cesstoreshospitalsexhibition halls, etc.Infrastructures:airportstelecommunicationsinternet data centrestunnels, etc.Industrial facilities:pharmaceuticalsfood processing, etc.

    Our solutions:Prisma Plus and Okken switchboardsCanalis busbar trunking.

    bvvvvbvvvvbvv

    bb

  • K9CE01020

    PD

    2023

    83P

    D20

    2427

    3Schneider Electric

    Intr

    oduc

    tion

    With Canalis, you play all the right notes!

    The Canalis decentralised distribution concept

    Electrical power available at all points,throughout the installation.

    Exclusive features of the Schneider Electric systemTotal coordination of the Schneider Electric system provides maximum safety of life and property, continuity of service, upgradeability and ease of installation.Total coordination is made easy by the tables in the Selection Guide. They help you chose the right combination of circuit breakers and busbar trunking.Product characteristics are checked by calculations and tests carried out in our laboratories.

    A competitive installation.Simplicity, upgradeability, safety and continuity of service and operation.

    Savings start with installationWith tap-off points every 3 metres, Canalis busbar trunking reduces installation costs.Given the low cost of adding new circuits, savings increase as the number of loads increases, a natural consequence of the growth of your business.

    Upgradeable during operationIn decentralised distribution, evolving operating requirements and costs are integrated right from the start.

    The addition, relocation or replacement of load equipment can be carried out quickly, without de-energising the supply trunking or shutting down operation.

    The cost of making such changes is greatly reduced:loads are located close to supply pointstap-off points are always availabletap-units can be reused or new ones added quickly for load relocation or

    replacement needs.

    b

    bvvv

    Reusable in the event of major changesWhen making major modifi cations to your installation, the existing trunking can be easily dismantled and reused.

    DD

    2056

    58

  • K9CE01030

    DD

    2056

    75D

    D20

    5674

    2 Schneider Electric

    Intr

    oduc

    tion

    Canalis, in total harmony with the environment!

    Safety of life and property With Canalis, no risk in case of fi reThe busbar trunking has a low combustible load. Its construction uses very little consumable material and is halogen free.In the event of a fi re, the busbar trunking does not emit any gas or toxic smoke.

    An inherent fi re barrier, the busbar trunking helps prevent the propagation of a fi re through partition walls and fl oors for a duration of 2 hours.

    Halogen-sensitive applicationsPublic buildings (infrastructures, hospitals, schools, etc.).Buildings with evacuation diffi culties (high-rises, ships, etc.) and service-activity

    buildings.Sensitive processes (production of electronic components, etc.).

    Canalis contains no PVCsWhen PVCs burn, they produce large amounts of smoke that can be a serious safety hazard.

    Reduced visibility:risk of paniccomplicates rescue workSmoke toxicity:hydrogen chloride gas (highly toxic)carbon monoxide (danger of asphyxiation).

    bb

    b

    bvvbvv

    Canalis reduces the risk of exposure to electromagnetic fi eldsAccording to the WHO (World Health Organisation), exposure to electromagnetic fi elds can be a health hazard starting at levels as low as 0.2 micro-Teslas and could represent a long-term risk of cancer. Some countries have created standards that stipulate limits (e.g. 0.2 T at 1 metre in Sweden).

    All electrical conductors generate magnetic fi elds proportional to the distance between them. The design of Canalis busbar trunking with tightly spaced conductors in a metal enclosure helps to considerably reduce radiated electromagnetic fi elds.

    The electromagnetic fi eld characteristics of Canalis busbar trunking are well-defi ned and measurements show that they are far below potentially dangerous levels.You will fi nd the magnetic induction values of our products on the Characteristics pages.

    Example:Consequences of a fi re in a 100 m2 offi ce with electrical distribution by cables.200 kg of cables (i.e. 20 kg of PVC) produces:

    4400 m3 of smoke7.5 m3 of hydrochloric acid3.7 kg of corroded steel.

    bbb

    Health

  • K9CE01030

    DD

    2056

    73

    3Schneider Electric

    Intr

    oduc

    tion

    Canalis, in total harmony with theenvironment!

    Environment Canalis is fully recyclableCanalis busbar trunking can be reused.

    Canalis busbar trunking is designed for a long service life and can easily be dismantled, cleaned and reused.

    All packaging materials can be recycled (cardboard or recyclable polyethylene fi lm).

    All Canalis products are designed for safe end-of-life recycling. PVC, on the other hand, requires neutralisation of the hydrochloric acid produced using lime and generates dioxins that are extremely toxic.

    Canalis helps conserve natural resourcesThe depletion of raw materials (copper, plastics, etc.) is one of our ongoing concerns.For this reason, we have optimised the used of all materials used to make our busbar trunking.

    Reduction of dangerous or polluting materials. We design our products to meet future European directives.

    Reduction in the weight of insulating materials.Reduction in the use of plastics for improved fi re performance: less energy

    released during combustion, thereby limiting propagation and facilitating extinction (lower calorifi c value).

    b

    b

    b

    b

    bb

    Example:1 kg of PVC generates 1 kg of waste.

    Energy savings Canalis reduces your line losses by 40 %Canalis divides your consumption of copper and insulation by a factor of threeThe cost of an electrical installation includes the initial investment for the equipment and its installation, the cost of maintenance and the cost of energy losses during operation.The cross-sections of our products are dimensioned to minimise the total cost of your installation over a 3-year period for medium intensity use (30 % load level,5 days a week and 10 hours a day).

    Example:30 m of Canalis KS 250 A trunking equipped with ten 4-pole 25 A feeders.

    DD

    2056

    56

  • K9CE01040

    PD

    2023

    84

    2 Schneider Electric

    Intr

    oduc

    tion

    Canalis, fortissimo throughoutthe range!

  • K9CE01040 3Schneider Electric

    Intr

    oduc

    tion

    Canalis, fortissimo throughoutthe range!

  • K9CE02010

    PD

    2023

    85D

    D20

    2860

    2 Schneider Electric

    Intr

    oduc

    tion

    Canalis KT, a display of advantages!

    The compact size of Canalis KT means it takes up very little space in the building:

    used as a rising main, it takes up only a minimum of space,used for horizontal distribution, it fi ts easily into the buildings structure (false

    fl oors, false ceilings, service shafts, etc).

    Changes in direction have been designed to optimise the space taken up, contrary to an equivalent installation using cables which requires large bending radii.

    Tap-off units, complete with protective devices, are fi tted along the entire length of the busbar trunking thus reducing the fl oor area taken up by the electrical distribution switchboards.

    b

    vv

    b

    b

    A compact solution

    A simple and economical system

    The design study is easy to perform as it does not require a detailed layout of each load. Equipment choice is pre-determined and optimised.

    Installing the busbar trunking requires 2 or 3 people only, for a time equivalent to that for installing cableways. The time normally needed for laying cables is therefore saved.

    Connection to the MV/LV substation is made using a quick fi tting joint block. The tap-off units can be prepared in the workshop thus reducing on-site time. Their connection to the busbar trunking is done in a single plugging-on operation.

    Installing busbar trunking lengths can be done as and when building work progresses, thus optimising on-site work and allowing possible unexpected events to be anticipated in advance.

    It is also important to note that busbar trunking is a factory tested solution, meaning the time needed for inspecting connections is reduced (visual inspection of tightening torque).

    b

    b

    b

    b

    b

  • K9CE02010

    PD

    2022

    29-6

    8P

    D20

    2386

    3Schneider Electric

    Intr

    oduc

    tionComplete safety Busbar trunking temperature rise and short-circuit withstand are known and independent of the installation. Coordination of the Schneider Electric system

    results in complete control of the electrical network.

    Installation standards UTE C 15-105 chapter B.6.2 and IEC 60 364 chapter 5.523.6 stipulate that above 4 parallel cables, it is preferable to use busbar trunking. Paralleling many cables leads to uneven distribution of currents and the risk of abnormal temperature rise.

    The busbar trunking and tap-off units are designed to guarantee the safety of personnel and equipment:

    plug-on connections to silver-plated copper bars,bolted connections with tightening torque guaranteed by torque nuts,foolproof system to avoid the risk of assembly errors,IP55 certifi ed splash and dust protection,sprinkler resistance test in compliance with Volkswagen specifi cations,access to live parts have IPxxD protection (1 mm wire diameter).

    Its metal enclosure and high protection degree protect the busbar trunking from all external aggressions (corrosion, rodents, etc).

    b

    b

    b

    vvvvvv

    Operating continuity When working on the electrical installation, the busbar trunking provides immediate readability of the electrical circuit thus allowing the appropriate zone to be quickly identifi ed.Tap-off units can be plugged-on and off without the need for a shutdown; service continuity is thus irreproachable.

    The quality of the electrical contacts guarantees maintenance free operating continuity.

    A large range of tap-off units Canalis KS tap-off units are fully compatible with Canalis KT:they cover all your requirements:Canalis KS tap-off units: 63 to 400 A,Canalis KT tap-off units: 400 to 1000 A,they offer circuit-breaker or fuse protection.

    This offer includes tap-off units that can be fi tted with the Transparent Ready system:

    they monitor your installation to avoid overloads, thus ensuring service continuity,they provide metering to allow accurate management of your electrical

    distribution network (allocation of costs to each consumer).

    bvvb

    vv

    Canalis KT, a display of advantages!

  • K9CE02020

    PD

    2023

    91

    PD

    2023

    88

    PD

    2023

    87

    PD

    2023

    89

    PD

    2023

    90

    2 Schneider Electric

    Intr

    oduc

    tion

    Canalis KT, everyone to their music!

    Key points

    Fire barrier.

    Halogen free.

    Small size.

    Operating continuity.

    b

    b

    b

    b

    Offi ce and hospital buildings

    Key points

    Halogen free.

    Distribution and metering.

    Able to be evolved.

    Sprinklers.

    b

    b

    b

    b

    Shopping centres, airports and exhibition centres

  • K9CE02020

    PD

    3950

    77-6

    8

    PD

    2023

    92

    PD

    2023

    93

    1094

    05

    PD

    2023

    94

    PD

    2023

    95

    3Schneider Electric

    Intr

    oduc

    tion

    Canalis KT, everyone to their music!

    Key points

    Operating continuity.

    Able to be evolved.

    Low voltage drops.

    Network readability.

    b

    b

    b

    b

    Car industry andindustrial buildings

    Key points

    Operating continuity.

    High tap-off density.

    Able to be evolved.

    Network compactness and readability.

    b

    b

    b

    b

    Internet Data Centers

  • K9CE020302 Schneider Electric

    Intr

    oduc

    tion

    Play all the worlds musicwith Canalis!

    TertiaryName Lighting and low current Medium current High

    currentCountry

    KDP KBA KBB KN KS KT

    Offi ces

    PD

    2022

    44 Air France (headquarters) b b FranceAllianz b b GermanyAxa b b FranceChamber of Commerce b b LuxembourgCommerz Bank b b GermanyLexel b b b SwedenTelefnica b b SpainTrade Center b b SpainTour du RDC b b TunisiaTurning Torso b SwedenVodafone b b New Zealand

    Internet Data Center

    PD

    2022

    45 Banco Commercial Portugus b b PortugalColt b b FranceDigiplex b b SwedenIBM b b b b Spain, ItalyMCI-Worldcom b b b b Italy, United Kingdom

    Hotels and restaurantsHyatt b TunisiaMc Donalds b FranceSoldeo Andorra Hotel b b Spain

    Hospitals

    PD

    2022

    47 Children Clinic b b SwedenBrussels University Hospital b BelgiumDerby Hospital b United KingdomOran Hospital b b AlgeriaSt Joseph Hospital b FranceStockholm Hospital b SwedenVal de Grce Hospital b FranceMichalon Hospital b b FranceManussia Hospital b Egypt

    Supermarkets and hypermarkets

    PD

    2022

    48 Alcampo b b b SpainAuchan b b b b b b WorldB&Q b b b United KingdomCarrefour b b b b b b WorldCoop b b b ItalyFnac b b Spain, FranceIkea b b b b b China, Spain, France,

    SwedenMark & Spencer b Belgium, Spain,

    United KingdomToysR Us b Spain

    Play all the worlds music

  • K9CE02030 3Schneider Electric

    Intr

    oduc

    tion

    with Canalis!

    IndustryName Lighting and low current Medium current High

    currentCountry

    KDP KBA KBB KN KS KT

    Car industry

    PD

    2022

    49 BMW b b b b ItalyCitron b b b b b b China, Spain, FranceDaewo b South KoreaDacia b b b b b RomaniaIveco b b b b Spain, ItalyPeugeot b b b b China, Spain, FranceNissan b b b b b SpainRenault b b b b b Spain, France, Czech

    RepublicSeat SpainValo b b b China, France, Italy,

    PolandVolkswagen b b b Spain, Germany

    Other industriesAerospace industry

    Airbus b b b Italy

    Food-processing industryCoca-Cola b b Spain, Italy, BelgiumDanone b b b WorldPasquier b b France

    Livestock production farms and greenhousesFavier henhouse b b FranceGreenhouse b Netherlands

    Ceramic industryEsmalglas ceramic b b b b b Spain

    ElectricityLegrand b France, Turkey

    Watch-makingRolex b b b Switzerland

    MicroelectronicsIntel b b b b IrelandeST Micro-lectronique b b b b France

    Lead industry and water treatmentGrundfos b China

    Industrial technologyBosch b b China

    TelephonyPhillips b NetherlandsNokia b b Sweden

    Textile industryLouis Vuitton b b b SpainDelta b b Israel

  • K9CE020304 Schneider Electric

    Intr

    oduc

    tion Infrastructure

    Name Lighting and low current Medium current High current

    Country

    KDP KBA KBB KN KS KT

    Airports

    PD

    2022

    50 Paris Airport b b b b b France

    Cairo Airport b Egypt

    Heathrow Airport b b b United Kingdom

    Hong-Kong Airport b China

    Landvetter Airport b Sweden

    Arlanda b b b Sweden

    Satelite Barajas b Spain

    Marine

    PD

    2022

    51 Chantier de lAtlantique b b France

    Meyerwerft b b Germany

    Undergrounds

    PD

    2022

    52 Guanghzou Underground b China

    London Underground b United Kingdom

    Madrid Underground b b Spain

    Singapore Underground b Singapore

    Other infrastructuresAlexandria Library b b Egypt

    Centre international dexposition de Suzhou

    b b China

    CERN b b Switzerland

    Stade de France b b France

    Play all the worlds musicwith Canalis!

  • K9CE02030 5Schneider Electric

    Intr

    oduc

    tion

    Play all the worlds musicwith Canalis!

  • K9CE020402 Schneider Electric

    Intr

    oduc

    tion

    With the Canalis tools and services, let us compose your project!

    Technical fi les The technical fi les have been compiled from completed contracts and provide answers to questions concerning the installation of Canalis busbar trunking in specifi c business sectors.

    In data centersReference:ART 3722DESBS001FR

    In exhibition centresReference:ART 65946KD0C00CTAFEEN / 65946

    In shopping centresReference:Available in your sales offi ce.

    In electronics factoriesReference:ART 65944KD0C00CTAFEEN / 65944

    In tiles factoriesReference:DEBU005EN

    In car plantsReference:Available in your sales offi ce.

    In livestock buildingsReference:DESWED105010EN

    In greenhousesReference:ART 808260DESWED105013EN

    In logistic centresReference:ART 807993DESWED105011EN

    In cruise shipsReference:DESWED105014EN

    In garagesReference:DESWED103004EN

    Find a large range of Cahier Technique publications on the Schneider Electric web site: www.schneider-electric.com.

  • K9CE02040

    PD

    2023

    96D

    D21

    0861

    3Schneider Electric

    Intr

    oduc

    tion

    With the Canalis tools and services, let us compose your project!

    Work-out yoursolution together

    Our teams are available to provide customers with technical assistance throughout the installation of their projects.

    Design of electrical distribution architectures:design of decentralised transport and distribution systems,technical and fi nancial optimisation of busbar trunking design projects,transformer / switchboard link,installation coordination and discrimination.

    Full installation drawings:3D Autocad drawings with corresponding parts lists,2D drawing with dimensions,detailed connection drawings.

    Site supervision and commissioning assistance.

    Training for designers and contractors.

    bvvvv

    bvvv

    b

    b

    Project launch

    Technical support

    CanBrass drawing

    Autocad drawing

    Production

    Project management

    On-site instruction and installation

    After-sales service

  • K9CE020404 Schneider Electric

    Intr

    oduc

    tion

    Enter Canalis run characteristics.

    With the Canalis tools and services, let us compose your project!

    Switchboard access estimation of material and labour costs.

    Schneider Electric offers a comprehensive design and costing software.The CanBrass software, edited by Schneider Electric, was developed to help you design and cost Canalis busbar trunking runs.

    CanBrass, a comprehensive toolThe CanBrass software allows you to quickly design the best layout for your project.It allows:

    the material needed to be easily chosen,a list of catalogue numbers and their exact quantities to be defi ned,a comprehensive quote that includes material and labour.

    There are 2 options:linear metre costing,graphical costing.

    bbb

    bbb

    CanBrass gives you all the help you need

    Design guide

    Linear metre costingThe user enters the following parameters:

    for the power run: rating, polarity, protection degree,for each feeder: number of machines, rating and protection,overall run length, number of change-of-direction sections and the connection

    type.

    bbb

    PD

    2023

    74

    PD

    2023

    75P

    D20

    2376

  • K9CE02040 5Schneider Electric

    Intr

    oduc

    tion

    With the Canalis tools and services, let us compose your project!

    Defi nition of catalogue numbersThe software gives an optimum breakdown of the project and provides a bill of materials: catalogue number, quantity, price.The software can also generate 2D or 3D drawings with dimensions.

    Breakdown of the run by product function.

    QuoteThe CanBrass software can generate a comprehensive customised quote (quantity, catalogue number, unit price, total net price and installation time).

    Graphical costingSimply create a 3D drawing of the busbar trunking using appropriate dialogue boxes.Enter the following:

    rating,polarity,connection types.

    bbb

    PD

    2023

    77P

    D20

    2378

    PD

    2023

    79

  • K9CE110002 Schneider Electric

    Pres

    enta

    tion

    Presentation

    Range Canalis KDP Canalis KBA

    PD

    2022

    16

    PD

    2022

    17

    Run componentsDegree of protection IP55 IP55Number of circuits 1 1Rating 20 A 25 and 40 ATap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm 500 - 1000 and 1500 mmStandard lengths 24 and 192 meters 2 and 3 metersFinish - Galvanised steelMaximum distance between xing points 0,33 meter 3 meters

    KDP-KBA-KBB tap-off units

    PD

    2022

    25

    PD

    2022

    25

    Rating 10 and 16 A 10 and 16 A

    Option- White RAL 9010- Bus conductor- -

    Panorama of Canalis rangeLighting distribution

    Canalis KTC

  • K9CE11000 3Schneider Electric

    Pres

    enta

    tion

    Canalis KBB Canalis KBX

    PD

    2022

    19

    PD

    2022

    20

    IP55 IP201 or 2 125 and 40 A 25 A500 and 1000 mm -2 and 3 meters 1,53 and 3,06 metersGalvanised steel White5 meters 3 meters

    PD

    2022

    25

    10 and 16 A

    White RAL 9010 -Bus conductor -Clean earth -

    Presentation

    Canalis KTC

    Panorama of Canalis rangeLighting distribution

  • K9CE110004 Schneider Electric

    Pres

    enta

    tion

    Range Canalis KN Canalis KS

    PD

    2022

    21

    PD

    2022

    22

    Run componentsDegree of protection IP55 IP55Polarity 3L + N + PE 3L + N + PERating 40, 63, 100 and 160 A 100, 160, 250, 400, 500, 630, Tap-off intervals 500 - 1000 or 3000 mm 1000 mm on each faceStandard lengths 3 meters 3 and 5 metersFinish White RAL 9001 White RAL 9001Maximum distance between xing points 3 meters 3 meters

    Tap-off units

    PD

    2022

    27

    PD

    2022

    28

    Rating Plug-in 16 to 63 A 25 to 400 ABolt-on

    OptionRemote control conductor -

    Presentation

    Canalis KTC

    Panorama of Canalis rangePower distribution

  • K9CE11000 5Schneider Electric

    Pres

    enta

    tion

    Canalis KS colonne montante Canalis KT

    PD

    2022

    23

    PD

    2022

    24

    IP55 IP553L + N + PE 3L + PE ; 3L + N +PE ; 3L + N + oversized PE

    800 and 1000 A 100, 160, 250, 400, 500, 630, 800 and 1000 A 1000, 1350, 1600, 2000, 2500, 3200, 4000 and 5000 A500 mm 500 - 1000 mmDe ned by the oor pitch 2 and 4 metersWhite RAL 9001 White RAL 9001Li au pas dtage 3 meters

    PD

    2022

    28

    PD

    2022

    29

    25 to 400 A 25 to 400 A400 to 1000 A

    - -

    Presentation

    Canalis KTC

    Panorama of Canalis rangePower distribution

  • 24 Schneider Electric

    Pres

    enta

    tion

    Canalis KTC from 1000 to 5000 AFor horizontal transport and distribution

    Presentation

    Run sections Tap-off units Change-of-direction sections

    Rating: 1000 to 5000 A.Transport sections:fi xed lengths: 2 and 4 metres,non-standard lengths: 0.5 and 3 metres,Distribution sections:fi xed lengths: 2 and 4 metres,Adjustable lengths 1.10 to 1.50 metres.

    bbvvbvb

    Canalis KS plug-on tap-off units are compatible with the Canalis KT busbar trunking:

    protection by 25 to 400 A fuses,protection by 100 to 400 A Compact NS

    circuit breakers.Canalis KT fi xed tap-off units:protection by 400 to 1000 A Compact NS

    circuit breakers

    b

    vv

    bv

    Change-of-direction sections adapt to all busbar trunking requirements.

    There are both fi xed and made-to-measure lengths.

    b

    b

    Canalis KTC

    PD

    2023

    45P

    D20

    2328

    PD

    2023

    46

    PD

    2023

    47

    PD

    2023

    14

  • 25Schneider Electric

    Pres

    enta

    tion

    Presentation Canalis KTC from 1000 to 5000 AFor horizontal transport and distribution

    Interface connections Universal supply connections Horizontal fi xing supports

    Pre-fabricated interfaces connections can be incorporated into:

    Prisma Plus and Okken switchboards,France Transfo dry-type transformers.

    b

    vv

    Supply connections allow the busbar trunking to be connected to the switchboards busbar or to the transformer.

    b There are two types of support for installing the busbar trunking horizontally.

    One type of fi xing: to fi x the busbar trunking to its support.

    b

    b

    Canalis KTC

    PD

    2023

    44

    PD

    2024

    31

    PD

    2023

    48

    PD

    2023

    18

    PD

    2023

    58

  • 26 Schneider Electric

    Pres

    enta

    tion

    Run sectionsRating: 800 to 4000 A.Distribution sections, fi xed 2 metre lengths.Transport sections for going through fl oor slabs,

    fi xed 0.5 to 3 metre lengths.

    bbb

    Vertical fi xing supportFor installing the busbar trunking vertically, they

    ensure:height and depth adjustment,load sharing,absorption of expansions, vibrations, etc.They can be fi xed either to the fl oor, the wall or to

    a bracket.

    b

    vvvb

    Tap-off unitsCanalis KS tap-off units are compatible with the

    Canalis KT busbar trunking:protection by 25 to 400 A fuses,protection by 100 to 400 A Compact NS circuit

    breakers.Canalis KT fi xed tap-off units:protection by 400 to 1000 A Compact NS circuit

    breakers.

    b

    vv

    bv

    Presentation Canalis KTA from 800 to 4000 AFor distribution to different levelsRising mains

    Canalis KTA

    PD

    2023

    49

    PD

    2023

    319

    PD

    2023

    21P

    D20

    2322

  • 27Schneider Electric

    Pres

    enta

    tion

    Rating (A) Type of protectionModular switchgear Compact NS Fuses Compact NS with

    measurement and meteringPlug-on tap-off units25 to 125

    PD20

    2149

    PD20

    2150

    PD20

    2138

    25 / 50 A for NF / DIN fuses32 A for BS fuses63 A, 8 x 18 mm modules

    PD20

    2148

    PD20

    2147

    For Compact NS100 circuit breaker

    100 A, 12 x 18 mm modules63 A for DIN fuses100 A for NF / DIN fuses80 A for BS fuses

    160

    PD20

    2150

    PD20

    2150

    PD20

    2323

    For NG125 / 160 circuit breaker For Compact NS160 circuit breaker 160 A for NF / DIN / BS fuses250 to 400

    PD20

    2324

    PD20

    2184 Fitted with DIN rail for Powerlogic

    PM810

    PD20

    2324

    For Compact NS250 circuit breaker

    PD20

    2325

    For Compact NS250 circuit breaker

    PD20

    2325

    250 / 400 A for NF / DIN fuses

    For Compact NS400 circuit breaker

    For Compact NS400 circuit breakerFixed tap-off units400 and 630

    PD20

    2326

    For Compact NS400 and NS630 circuit breaker

    800 and 1000

    PD20

    2327

    Tap-off units from 25 to 1000 APresentation

    Canalis KTC

  • K9CE12000

    DD

    2023

    87D

    D20

    2388

    DD

    2023

    89

    DD

    2024

    34-m

    DD

    2024

    35-m

    DD

    2024

    36-m

    DD

    2024

    45

    2 Schneider Electric

    Des

    crip

    tion

    8 ratings are available, from 1000 to 5000 A.4 copper live conductors with identical cross-sections (3L + N + PE version).Conductors insulated using polyester fi lm, class B 130 C, halogen free.Standard busbar trunking is IP55.Insulation voltage: 1000 Volts.Available polarities: 3L + PE, 3L + N +PE, 3L + N + PER (reinforced PE)

    The KT busbar trunking is of compact design and can be installed edgewise, fl at or vertically.This design, without the addition of a fi re barrier joint, allows the busbar trunking to be installed through a fl oor slab or fi re barrier wall.As standard, the Canalis KT busbar trunking acts as a 2-hour fi re barrier in accordance with ISO 834.The RAL 9001 pre-lacquered galvanized steel casing provides protection and mechanical fi xing of the conductors. Further, it is used as the PE protective conductor (in accordance with NFC 15100 and IEC 60367).In its reinforced version 3L + N + PER, the busbar trunking is fi tted with an additional internal conductor with a cross-section equal to half that of the phase conductor.This version also has lateral reinforcements to allow high short-circuit currents (Isc) to be supported.

    The Canalis KT busbar trunking is suitable for applications containing harmonics by taking into account the appropriate derating factor. See Harmonic currents in the Design guide.

    bbbbbb

    The conductors are sandwiched together inside the metal casing.

    The junction between sections is made using a joint block.The joint block provides the following:

    electrical junction between live conductors and between PE protective conductors, mechanical link between the two sections.

    Contact zone coating:silver-plated copper

    It provides simultaneous continuity between all conductors.It is tightened using torque bolt(s) (1 to 4 depending on the rating) with snap-off heads.The nut head snaps-off, freeing a red washer, when the correct tightening torque is reached.

    This operation is checked visually:if the red washer is absent: it has been tightened,if the red washer is visible: it has not been tightened.

    This device guarantees the necessary contact pressure between live conductors and is operator independent.

    For dismantling or maintenance operations, the nut has a second head.The tightening torque is 6 daN.m.

    All sections (apart from ER and EL feed units) are supplied with their joint block, delivered in a separate parcel.If the run has a feed unit (ER or EL) at each end, an additional joint block must be ordered.

    bb

    b

    bb

    The KS plug-on tap-off units are connected to the busbar trunking whilst live (off-load) via spring jaw connections.Contact zone coating:

    silver-plated copper at jaw contact points.b

    3L + N + PER

    Description

    The Canalis KT busbar trunking is intended for high power distribution and transport in industrial, commercial and tertiary buildings. Assembly of prefabricated sections that adapt to all run confi gurations.

    General

    3L + PE

    3L + N + PE

    Run sections

    Tap-off contact

    Joint block

    Canalis KTC

  • K9CE12000

    DD

    2023

    90D

    D20

    2438

    DD

    2024

    37D

    D20

    2483

    3Schneider Electric

    Des

    crip

    tion

    Run sections

    Transport sections - Type ETTransport the current without tap-off points.Available in 2 and 4 metre fi xed lengths or made to measure from 0.50 to 3 metres.

    Adjustable section -Type AJCompensates for dimensional differences in the installation.Adjustable length from 1.10 to 1.50 metres.

    Sections with tap-off points for plug-on tap-off unitsType EDED run sections are for current distribution. They use 25 to 400 A KS tap-off units.These tap-off units can be plugged-on whilst live, but off-load.Available in fi xed 2 or 4 metre lengths with 3 tap-off points on one side.

    Sections with tap-off points for fi xed tap-off units - Type EBEB run sections are for current distribution. They use specifi c KT 400 to 1000 A tap-off units.These tap-off units can only be fi tted / removed when the run is not energised.Available in a 2 metre fi xed length with one tap-off point or a 4 metre fi xed length with 2 tap-off points.

    Description

    Canalis KTC

    Straight sections

  • K9CE12000

    DD

    2023

    91D

    D20

    2392

    DD

    2024

    39D

    D20

    2441

    DD

    2024

    40D

    D20

    2446

    DD

    2108

    11A

    DD

    2108

    13

    4 Schneider Electric

    Des

    crip

    tion

    The TP type transposes the phases.b

    Expansion section - Type DBIt controls and absorbs the expansion of Canalis runs and must be used on runs over 30 metres and each time the busbar trunking passes through a building expansion joint.Refer to the installation guide.

    Available in a 1 metre length, it can be fi tted vertically or horizontally.At its centre it has fl exible conductor joints and a sliding case able to absorb the relative movements of each part of the section.

    Transposition sections - Types TN, TPUsed when the phase order of the switchboard is different to that of the transformer.Available in a 1 metre length and is the same physical size as a transport section.

    The TN version transposes the neutral.b

    Additional joint block - Type YAIf the run has a feed unit (supplied without a joint block) at each end, an additional joint block must be ordered.Each joint block is supplied with the necessary covers, nuts and boltsRun end cover - Type FAThe end cover protects and insulates the conductor ends and is fi tted to the last section.

    Other run sectionsDisconnectors and run protective devices

    Fitted between 2 fl at or edgewise sections, they isolate or protect a busbar trunking part run.Each assembly is supplied fi tted with a 3 or 4-pole device complete with rotary handle.Supplied with:

    an auxiliary connection terminal,lifting rings,upstream and downstream terminal shields.

    Colour: white RAL 9001, 100 % polyester paint on galvanized sheet steel.Refer to manufacturers data for switchgear characteristics.Fitted with a rotary handle, the tap-off unit can only be opened once the device has been switched off.

    Run disconnector tap-off units - Type SLType SL for:

    Compact NS 1000 to 1600 A type NA fi xed isolators:unhingeable door,3-point closing (possibility of locking with key lock, not supplied),Interpact INV isolator, 2000 to 2500 A:unhingeable door,3-point closing (possibility of locking with key lock, not supplied),Masterpact NW 3200 A type HF fi xed isolator supplied with:transparent protection cover,adaptation kit for Ronis lock + 1 Ronis lock,complete Harting plug, not cabled.

    Run protection tap-off units - Type PLType PL for:

    Compact NS 1000 to 1600 A type N fi xed circuit-breakers:unhingeable door,3-point closing (possibility of locking with key lock, not supplied).

    For circuit-breakers greater than 1600 A, consult the sales offi ce.

    bbb

    bvvbvvbvvv

    bvv

    Description

    Canalis KTC

    Other run sections

    Disconnectors and run protective devices

  • K9CE12000

    DD

    2023

    93D

    D20

    2394

    DD

    2023

    95D

    D20

    2396

    DD

    2023

    97D

    D20

    2398

    DD

    2024

    33D

    D20

    2432

    5Schneider Electric

    Des

    crip

    tion

    Elbows - Types LP and LCTo go up or down, to turn right or left:

    type LP, fl at elbow available in fi xed or made-to-measure lengths,b

    Zeds - Types ZP, ZC, CP3-branch made-to-measure:fl at or edgewise, to move the run axis upwards, downwards, to the right or to the

    left without having to bend the busbar trunking:type ZP, fl at Zed,

    b

    v

    Edgewise T junctions - Type TCTo feed runs perpendicular to the main run.

    Change of direction sectionsDescription

    type LPpC, fl at made-to-measure angled elbow,b

    type LC, edgewise elbow available in fi xed or made-to-measure lengths,b

    type LCpC, edgewise made-to-measure angled elbow.b

    type ZC, edgewise Zed,v

    edgewise / fl at, to provide the busbar trunking with a bend.Type CP, edgewise and/or fl at Zed.

    bv

    Canalis KTC

    Simple changes of direction

    Changes of direction

  • K9CE12000

    DD

    2023

    06D

    D20

    2310

    DD

    2023

    14

    6 Schneider Electric

    Des

    crip

    tion

    To connect the KTC busbar trunking to different terminals or to transformer, switchboard, generator set, etc. busbars. Canalis offers high performance connection sections which meet all requirements.

    These sections provide installation fl exibility combined with quick and simple assembly.

    Further, the connections are made using torque bolts which provide both ease of installation (use of a standard spanner for tightening to 6 daN.m) and a visual check before energising.

    Direct connection to Trihal transformers and Prisma Plus & Okken switchboards.Supplied factory or panelbuilder assembled and tested to IEC 60439-1 and 2.Quick and simple connection of the busbar trunking to the interface.Reduced size.Joint block integrated into the interface.A sealing kit (rating dependent) must be ordered.

    Connection sectionsDescription

    Sealing kit

    Prisma Plus and Okken switchboardsFor fi xed or draw-out incoming device, front or rear connection:

    Masterpact NW08 to NW40 or NT06 to NT16 circuit-breaker,Compact NS630b to NS1600 circuit-breaker.

    Possibility of switching the phases around.

    bb

    Prisma Plus switchboard

    Okken switchboard

    Canalis KTC

    Connections via interface to Prisma Plus, Okken and Trihal

  • K9CE12000

    DD

    2025

    03

    7Schneider Electric

    Des

    crip

    tion

    Connection sectionsDescription

    France Transfo Trihal dry type transformersFor naturally ventilated or force ventilated transformers.Protection degree:

    IP00,IP31.

    Secondary voltage: 410 V

    15 mm adjustment in the 3 axes.

    bb

    Canalis KTC

  • K9CE12000

    DD

    2023

    99

    DD

    2107

    77D

    D20

    2502

    8 Schneider Electric

    Des

    crip

    tion

    Feed units - Type ERThey allow the busbar trunking to be connected to a switchboards busbar, or to the terminals of an oil immersed transformer, generator set, etc.

    They come complete with a mounting plate fi tted:either directly to the roof of the switchboard,or via the intermediary of a protective cover.

    Vertical or horizontal incoming busbar trunking.

    bb

    Connection:either directly to the busbar,or by fl exible bars and connection plates,or by braids,or by cables.

    ER feed units are supplied without a joint block.If the run has a feed unit at each end, an additional joint block must be ordered.

    bbbb

    bb

    Types ER N1/N2

    Connection sectionsDescription

    Canalis KTC

    Universal connections to switchboards and oil immersed transformers

    Types ER N3/N4 Types ER N5/N6 Type ER N7

  • K9CE12000

    DD

    2023

    21D

    D20

    2325

    1027

    6 -0

    3-d1

    1027

    6-3

    03-d

    4D

    D20

    5623

    DD

    2056

    24

    9Schneider Electric

    Des

    crip

    tion

    Protective covers - Types CS, CR, BCProtects the external part of the connection.

    Type CSHeight adaptable fl exible protective cover adaptable for ER N1 to N6 feed units with a between centres distance of 115 mm.

    b

    Connection sectionsDescription

    For a vertical incomer - Types CR1 to CR3Made-to-measure rigid protective cover for ER N1 to N7 feed units.They are height adjustable by 50 mm.

    Type CR 1 for a horizontal incomer.b

    Types CR7 and CR8Protective covers for oil immersed transformers.Only for ER N1 to N6 feed units with a between centres distance of 150 or 170 mm depending on the rating.

    Fit directly onto the BT series transformer tanks.

    Type CR7 for a vertical incomer.

    b

    v

    Type BCProtective cover for direct cable connection to ER N1 to N6 feed units with a between centres distance of 115 mm.

    v

    Type CR8 for a horizontal incomer.v

    Canalis KTC

    Types CR2 and CR3 for a vertical incomer.b

  • K9CE12000

    DD

    2024

    44

    DD

    2024

    43D

    D20

    2442

    DD

    2024

    48D

    D20

    2447

    10 Schneider Electric

    Des

    crip

    tion

    Feed units - Type ELFor dry type transformers with the neutral between the phases.They allow optimum connection to the busbar trunking.

    The junction with the busbar trunking is achieved:either from the side,b

    Connection sectionsDescription

    They are of similar design to straight transport sections and can be installed edgewise or fl at.If installed fl at, a set of angle brackets can be ordered.

    The following must be specifi ed at the time of order:phase order,distance between phases (a 20 mm lateral adjustment can be made use of on site).

    The link between the transformer terminals and the connection section is either by fl exible bar connection plates or by braids.

    Type EL N1/N2

    or from the centre.b

    Type EL N3/N4 Type EL N5

    Canalis KTC

    Universal connections to dry type transformers

  • K9CE12000

    DD

    2023

    43D

    D20

    2346

    DD

    2023

    42

    11Schneider Electric

    Des

    crip

    tion

    Protective covers - Type CR4 to CR6These protect the connections with an IP31 casing when connecting to a transformer.They are height adjustable by 50 mm.

    Type CR4Protective cover for EL N1 to N4 feed units.Edgewise assembly.

    b

    Connection sectionsDescription

    Type CR5Protective cover for EL N1 to N4 feed units.Flat assembly.

    b

    Type CR6Protective cover for EL N5 feed unit.Edgewise assembly.

    b

    Canalis KTC

  • K9CE12000

    DD

    2024

    00

    DD

    2024

    11

    DD

    2024

    10

    DD

    2024

    03D

    D20

    2402

    DD202401

    DD

    2023

    63D

    D20

    2478

    DD

    2107

    84

    12 Schneider Electric

    Des

    crip

    tion

    The conductors of ER N1 to N6 feed units are connected directly to the switchboard busbars.YB2 copper spacers are available to compensate differences in thickness between the switchboard bars (10 mm) and the connection part (6 mm).

    Make-up of kit:8 x 2 mm thick copper spacers,16 off M12 x 60 mm bolts, class 8.8,16 contact washers,16 torque nuts,8 steel spacer plates.

    Order a set per feed unit whatever the rating.

    bbbbb

    The conductors of ER N1 to N6 feed units are connected via connection plates to the switchboard busbars.

    The YC types are fl exible bars made up of 5 copper sheets of 1 x 100 mm (500 mm cross-section).The number of connection plates needed is proportional to the busbar trunking rating.There are 3 types:

    YC1, uninsulated 600 mm long bar with 4 oblong holes at one end.The length of the holes at the switchboard side are to be adapted on-site.b

    Connection accessoriesDescription

    YC2, uninsulated bar, made-to-measure length of 250 to 600 mm with 4 oblong holes at each end, ready to use.b

    YC5, insulated 1000 mm long fl exible bar, stripped at one end and with 4 oblong holes.The length of the holes at the switchboard side are to be adapted on-site.

    b

    Nuts and boltsThe connection plates are fi xed to the feed unit using the YB3 nut and bolt kit, made up of:

    16 off M12 x 60 mm bolts, class 8.8,16 contact washers16 torque nuts,8 steel spacer plates.

    ClampsYS1 clamps enable high short-circuit current levels to be withstood; only for bars with a 115 mm spacing.

    bbbb

    Canalis KTC

    Switchboard connection accessories using connection plates

    Accessories for direct connection to the switchboard

    InsulationA YF sheath is available to insulate the phases from one another.It can be fi tted to the YC1 and YC2 connection plates once they have been connected.

  • K9CE12000

    DD

    2024

    12D

    D20

    2414

    DD

    2024

    13D

    D20

    2415

    DD

    2024

    50

    13Schneider Electric

    Des

    crip

    tion

    The feed unit conductors are connected to the transformer bars via connection plates or braids:

    connection plates, YC types, are fl exible bars made up of 5 copper sheets of 1 x 100 mm (500 mm cross-section).

    braids, YT type, are copper braids with a 600 mm cross-section.

    The number of connection plates needed is proportional to the busbar trunking rating.

    Connection platesThe YC3 is an uninsulated bar with an expansion kink; it is 400 mm long and has 4 holes at one end.They can be fi tted to the transformer side:

    either using bar clamps (no drilling),or drilled and bolted (to be carried out on site).

    b

    b

    bb

    Connection accessoriesDescription

    YS2 and YS3 bar clamps enable connection without the need to drill the connection plates.They allow height adjustment.

    Type YS2, bar clamps for 100 mm transformer connection terminals.Type YS3, bar clamps for 120 mm transformer connection terminals.

    Make-up of kit: 1 set of 8 parts.

    bb

    The YC4 is an uninsulated bar with an expansion kink; it is 400 mm long and has 4 oblong holes at each end (ready to use).b

    BraidsType YT, 400 mm long insulated braid with 4 holes at each end.

    The connection plates and braids are fi xed to the feed unit using the YB4 nut and bolt kit, made up of:

    16 off M12 x 80 mm bolts, class 8.8,16 contact washers,16 torque nuts,8 steel spacer plates.

    bbbb

    Canalis KTC

    Transformer connections - Types YC, YT

  • K9CE12000

    DD202372

    DD

    2024

    84D

    D20

    2486

    DD

    2024

    85

    DD

    2023

    69D

    D20

    2368

    DD

    2024

    96

    DD

    2023

    74

    14 Schneider Electric

    Des

    crip

    tion

    Supports and fixings

    The ZA types allow the busbar trunking to be fi xed and adjusted along its length, as well as absorbing its movements.

    Supports for horizontal sectionsType ZA1, to support edgewise busbar trunking only, consists of a steel angle

    bracket and 2 x 1.2 metre threaded M10 rods. The maximum distance between supports is:

    3 metres for edgewise busbar trunking,2 metres for fl at busbar trunking.

    See installation precautions.

    b

    vv

    Fixing bracketThe ZA3 keeps the busbar trunking in place on its support, without blocking it, in order to allow expansion movements.

    The ZA5 is for supporting vertical sections.They fi x sections of a vertical run to the buildings structure.This type of fi xing support has the following advantages:

    assembly:to a wall,to a wall bracket,to the fl oor,height and depth adjustment,spring adjustment to ensure distribution of the load at each fl oor,avoids the transmission of building forces to the busbar trunking (expansion and

    vibration).

    bvvvbbb

    Description

    Type ZA4, to support the busbar trunking from the top.These supports are needed to fi x edgewise EL N1 to N4 feed units for dry type

    transformers.

    bb

    For KTC1000 to KTC2000. For KTC2500 to KTC5000.

    To a wall. To a wall bracket. To the fl oor.

    Canalis KTC

    Horizontal supports

    Vertical supports

  • K9CE12000 15Schneider Electric

    Des

    crip

    tion

    Description

    Canalis KTC

  • K9CE13000

    DD

    2104

    66D

    D20

    2012

    DD

    2102

    75D

    D21

    0276

    2 Schneider Electric

    Tap-off units

    The tap-off units are used to instantly connect loads or secondary runs, and comply with installation standards and regulations, whatever the earthing system (TT, TNS, TNC or IT).When off-load, they can be plugged-on and off and be operated whilst live.Plugging-on and plugging-off automatically opens and closes the tap-off point.

    Description

    No live part is accessible with the door open. The protection degree is IPXXB (fi nger protection).They are IP55 by construction (no accessory is required).

    Safety and operationFuse and modular switchgear tap-off units (AC22 to AC20) are isolated as soon as the tap-off unit door is opened.This isolating operation must only be carried out off-load.For circuit breaker tap-off units, there are safety mechanisms to prevent:

    the tap-off unit being plugged-on and plugged-off with the tap-off unit door closed,

    the door being closed if the tap-off unit has not been locked onto the busbar trunking,

    access to the electrical equipment and connection terminals when live,the door being opened in the ON position for tap-off units fi tted with a Compact

    NS or NG circuit breaker.

    These tap-off units can be fi tted with accessories such as:door early break contacts,adapter for lead sealing,etc.

    The sheet steel tap-off units are fi tted with a carrying handle.

    Characteristics of tap-off units up to 125 AColour: white (RAL 9001) body and carrying handles,transparent green door (similar design to the Kaedra enclosures).Material: self-extinguishing, halogen-free insulating plastic (fi re resistant and very

    high temperature withstand).Other characteristics: cable gland drilling zone, stainless steel screws and the door can be lead sealed.

    Characteristics of tap-off units from 160 to 400 AColour:white (RAL 9001) body,black carrying handles (RAL 9005),100 % polyester paint.Material: galvanized sheet steel.

    Other characteristics:unhingeable door (120 opening hinges),vertically bevelled polyurethane seals with a double fold for increased rigidity

    (similar design to the Sarel Spatial 3D enclosures),25 mm grill type gland plates for a maximum access area.

    b

    b

    bb

    bbb

    bvvb

    bvvvb

    bb

    b

    Canalis KTA

  • K9CE13000

    DD

    2104

    65D

    D21

    0461

    DD

    2021

    54D

    D21

    0454

    3Schneider Electric

    Plug-on tap-off units for circuit breakers

    Isolator tap-off units for modular switchgearMost 18 mm Multi 9 modular devices can be fi tted into these tap-off units.They have a window on the front face for switchgear control and visualisation.

    A transparent shutter ensures the window can be sealed.Two tap-off ratings are available:

    63 A nominal current for 8 modules,125 A nominal current for 12 modules (accepts C120 and NG125 circuit

    breakers).bb

    Tap-off units for NG type modular switchgearThese tap-off units are fi tted with a DIN rail and upstream connections for 18 mm wide modular devices.The switchgear is operated via a rotary handle which prevents door opening when the circuit breaker is in the ON position.Nominal current: 160 A for a 13-module capacity (accepts NG125 or NG160 fi tted

    with a Vigi unit).Isolator tap-off units for Compact NS circuit breakersThese tap-off units are fi tted with mounting plates and upstream connections for fi xed, front-connected 160 to 400 A Compact NS circuit breakers (N, H or L version) with a rotary handle.The 400 A tap-off units can only be fi tted onto straight lengths with a rating greater than 400 A.

    For plug-on circuit breakers, Vigi units, etc, please consult your Schneider Electric

    contact.Measurement and metering isolator tap-off unitsThese tap-off units allow sub-metering to re-allocate power consumption costs by consumer and to monitor installations by, for example, following run load levels.The values measured using the Compact NS TI unit are sent to the measurement unit which then sends the information to a central unit via a bus. (See Measurement and metering).They are fi tted with:

    a mounting plate for a Compact NS 250 or 400 A circuit breaker with an extended rotary handle and a Compact NS current transformer module (TI unit),

    a DIN rail for installing a Powerlogic PM810 measurement unit, a set of terminals, etc.

    In severe operating conditions (> 40C ambient temperature), we recommend the use of a PM810 without display.

    b

    b

    Description

    Canalis KTA

  • K9CE13000

    DD

    2104

    72D

    D20

    2012

    DD

    2104

    66

    4 Schneider Electric

    These tap-off units provide the tap-offs with fuse protection (fuses not supplied).They can only be fi tted to a horizontally mounted busbar trunking.

    Plastic tap-off unitsFitted with carriers for:

    50 to 100 A cylindrical NF fuses,25 to 63 A DIN screwed fuses,100 A DIN blade fuses,32 to 80 A BS screwed fuses.

    bbbb

    Plug-on tap-off units for fusesDescription

    Steel tap-off unitsFitted with carriers for:

    160 to 400 A NF / DIN blade fuses,160 A BS screwed fuses.

    bb

    Canalis KTA

  • K9CE13000

    DD

    2024

    51D

    D20

    2497

    5Schneider Electric

    Fixed tap-off units for circuit breakers

    Steel tap-off unitsThese tap-off units are used to supply loads or secondary runs (e.g. medium power distribution using Canalis KS). They are fi tted to specifi c EB type straight lengths.They comply with installation standards and regulations, whatever the earthing system (TT, IT, TNS or TNC):

    tap-off units fi tted with a mounting plate for Compact NS400/1000 A, 3 or 4 P:fi xed device,front connections,extended rotary handle.

    2 models:Compact NS400/630 A, connection capacity: 3 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm),150 mm for the PE,Compact NS800/1000 A, connection capacity:4 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm),200 mm2 for the PE (cable clamp).

    The standard tap-off unit is IP54.

    bvvv

    bvvbvv

    Characteristics of tap-off units from 400 to 1000 AColour:white (RAL 9001) body,Material: galvanized sheet steel.Other characteristics: the cables exit laterally through 2 aluminium plates (to be drilled by the

    installation contractor),cabling space can be increased by using the cable box supplied with the tap-off

    unit,the door is fi xed using 6 captive M6 screws and can be completely removed to

    facilitate cabling.

    bvbbv

    v

    v

    Description

    Safety and operationThe electrical connection is made by plugging-on the tap-off unit into dedicated tap-off point whilst the busbar trunking is de-energised (plugging-off the unit must also be done with the busbar trunking de-energised).The connection is mechanically tightened using a one-use torque bolt (10 daN.m).A mechanical foolproof system avoids the risk of incorrect assembly.The door can only be opened once the load has been isolated (rotary handle).The bolt can only be tightened or untightened with the door open.No live part is accessible with the door open, protection degree IP2X.

    Canalis KTA

  • K9CE20000 Schneider Electric 3

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Catalogue-number coding

    K T p p p p p p p p ppFour digits indicationg

    the rating of the trunking.b

    Two letters identifying the type of component.Type CodeAdjustable straight length AJCable box BCBolt-on tap-off unit CBEdgewise and fl at zed CPRigid protective cover CRFlexible protective cover CSExpansion unit DBDistribution length for bolt-on tap-off units EBDistribution length for plug-in tap-off unts EDFeed unit for dry-type transformers ELFeed unit ERFeeder length ETEnd cover FAEdgewise elbow LCFlat elbow LPTap-off unit with protective device PLTap-off unit with isolator SLEdgewise tee TCNeutral crossover TNPhase crossover TPSealing kit TTConnection device YAConnection torque nut kit YBFlexible bar YCBracket YEInsulating sheath YFBar supports YSBraids YTSupports and fi xing devices ZAEdgewise zed ZCFlat zed ZP

    b

    One digit indicating the trunking polarityPolarity Code3L + PE 33L + N + PE 43L + N + PER(1) 7(1) PER = oversized PE.

    b

    Variable number of alphanumeric characters indicating characteristics specifi c to the component.See the section dealing with the given component.

    b

    Trunking cross sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Number of bar jointing bolts 1 1 1 2 2 2 4 4Bar cross-section (mm) 70 x 6 100 x 6 120 x 6 160 x 6 200 x 6 2 x (120 x 6) 2 x (160 x 6) 2 x (200 x 6)Trunking height H (mm)

    DD

    2021

    80

    DD

    2021

    81

    Holes for connections (mm)

    DD

    2021

    82

    Y 230 230 230 350 350 350 510 510

    Catalogue-number composition

    One letter designating the material.Type CodeCopper CNon conducting B

    b

    Catalogue numbers anddimensions

    Canalis KTC

  • K9CE21010

    DD

    2107

    94

    DD

    2107

    95

    DD

    2107

    96

    DD

    2107

    97

    2 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    sCatalogue numbers and dimensions

    Straight feeder lengths

    Run componentsIP55

    Type Length L(mm)

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Fixed 4000 KTCppppET340 KTCppppET440 KTCppppET7402000 KTCppppET320 KTCppppET420 KTCppppET720

    Made to measure

    500 to 1500 KTCppppET31A KTCppppET41A KTCppppET71A1501 to 1999 KTCppppET32B KTCppppET42B KTCppppET72B2001 to 2500 KTCppppET32C KTCppppET42C KTCppppET72C2501 to 3000 KTCppppET33D KTCppppET43D KTCppppET73D

    KTCppppETppp

    Ordering

    Complete the catalogue number by replacing pppp by the rating.Important:

    add the dimensions of the selected component as a technical comment

    Example: the catalogue number of an 1000 A feeder length, 3L + N + PE,2450 mm long, is:KTC1000ET42C, L = 2450

    b

    Rating

    (1) See the Trunking cross-section table opposite.

    Canalis KTC

    Adjustable straight lenghts

    Type Length L(mm)

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Adjustable 1300 (basic)Adjustable: 200

    KTCppppAJ310 KTCppppAJ410 KTCppppAJ710

    KTCppppAJp10

    (1) See the Trunking cross-section table opposite.

    Table of dimensionsRating (A) Dimension A (mm) Weight (kg)1000 186 52.001350 219 68.001600 241 78.002000 307 102.002500 351 121.003200 395 141.004000 527 179.005000 615 218.00

    KTCppppETppp

    KTCppppAJp10

  • K9CE21010

    DD

    2107

    98

    DD

    2107

    99D

    D21

    0800

    3Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Catalogue numbers and dimensions

    Run componentsIP55

    Straight lengths with plug-in tap-off units

    Type Length L (mm)

    Number of tap-offs

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Fixed 4000 3 KTCppppED340 KTCppppED440 KTCppppED7402000 3 KTCppppED320 KTCppppED420 KTCppppED720

    KTCppppEDp40

    Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82

    3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114

    Height H (mm)Width W (mm)

    DD

    2021

    80

    DD

    2108

    67

    (1) See the Trunking cross-section table below.

    Canalis KTC

    KTCppppEDp20

    KTCppppEDp20

    KTCppppEDp40

  • K9CE21010

    DD

    2108

    01

    DD

    2108

    02D

    D21

    0803

    DD

    2107

    66

    4 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Straight lengths with bolt-on tap-off units

    Type Length L (mm)

    Number of tap-offs

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Fixed 4000 2 KTCppppEB340 KTCppppEB440 KTCppppEB7402000 1 KTCppppEB320 KTCppppEB420 KTCppppEB720

    KTCppppEBp40

    (1) See the Trunking cross-section table below.

    KTCppppEBp20

    KTCppppEBp20

    KTCppppEBp40

    Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82

    3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114

    Height H (mm)Width W (mm)

    DD

    2021

    80

    DD

    2108

    67Catalogue numbers and dimensions

    Canalis KTC

    Run componentsIP55

  • K9CE21010 5Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

  • DD

    2108

    05

    DD

    2108

    06

    DD

    2108

    07

    DD

    2108

    08

    DD

    2108

    09

    DD

    2108

    10

    2 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    sCatalogue numbers and dimensions

    Straight expansion unit

    Additional run componentsIP55

    Type Length L(mm)

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Fixed 1000 KTCppppDB310 KTCppppDB410 KTCppppDB710

    KTCppppDBp10

    Ordering

    Complete the catalogue number by replacing pppp by the rating.Important:

    add the dimensions of the selected component as a technical comment

    Example: the catalogue number of a 1350 A straght expansion unit, 3L + PE, 1000 mm long, is:KTC1350DB310

    b

    Rating

    (1) See the Trunking cross-section table opposite.

    Canalis KTC

    Neutral crossover length

    Type Length L(mm)

    Cat. no.3L + N + PE

    Fixed 1000 KTCppppTN410

    KTCppppTNp10

    (1) See the Trunking cross-section table opposite.

    Phase crossover length

    Type Length L(mm)

    Cat. no.3L + N + PE

    Fixed 1000 KTCppppTP410

    KTCppppTPp10

    (1) See the Trunking cross-section table opposite.

    KTCppppDBp10

    KTCppppTNp10

    KTCppppTPp10

  • DD

    2108

    11

    DD

    2108

    12

    DD

    2108

    13

    DD

    2108

    14n

    DD

    2108

    68

    3Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Catalogue numbers and dimensions

    Additional run componentsIP55

    Additional jointing unitsType Cat. no.

    3L + PE 3L + N + PE 3L + N + PERJointing unit KTCppppYA3 KTCppppYA4 KTCppppYA4

    KTCppppYAp

    (1) See the Trunking cross-section table below.

    Canalis KTC

    End coversType Rating of the

    trunking (A)Height H of the trunking (mm)

    Cat. no.

    End cover 1000 74 KTB0074FA1350 104 KTB0104FA1600 124 KTB0124FA2000 164 KTB0164FA2500 204 KTB0204FA3200 244 KTB0244FA4000 324 KTB0324FA5000 404 KTB0404FA

    KTB0pppFA

    KTCppppYAp

    KTB0pppFA

    Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82

    3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114

    Height H (mm)Width W (mm)

    DD

    2021

    80

    DD

    2108

    67

    (1) See the Trunking cross-section table below.

  • K9CE22010

    DD

    2108

    22D

    D21

    0824

    DD

    2108

    15D

    D21

    0816

    DD

    2108

    21D

    D21

    0823

    2 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    sCatalogue numbers and dimensions

    Elbow components for changing directionIP55

    Flat elbows

    Type Position of neutral

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Fixed N1 KTCppppLP3A1 KTCppppLP4A1 KTCppppLP7A1N2 KTCppppLP3A2 KTCppppLP4A2 KTCppppLP7A2

    Made to measure

    N1 KTCppppLP3B1 KTCppppLP4B1 KTCppppLP7B1N2 KTCppppLP3B2 KTCppppLP4B2 KTCppppLP7B2

    KTCppppLPppp

    Ordering

    Complete the catalogue number by replacing pppp by the rating.Important:

    add the dimensions of the selected component as a technical comment

    Example: the catalogue number of a 2000 A fl at elbow, N1, 3L + N + PE with dimensions A = 300 mm and B = 650 mm is:KTC2000LP4B1, A = 300, B = 650.

    b

    Rating

    (1) See the Trunking cross-section table opposite.

    DimensionsType Rating (A) Dimensions (mm)

    A BFixed All 300 300Made to measure(2)

    All 300 301 to 799301 to 799 300

    (2) Only one llmb may be made to measure.

    Canalis KTC

    Flat elbows with made to measure angles

    Type Position of neutral

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Made to measure angle

    N1 KTCppppLP3C1 KTCppppLP4C1 KTCppppLP7C1N2 KTCppppLP3C2 KTCppppLP4C2 KTCppppLP7C2

    KTCppppLPpCp

    (1) See the Trunking cross-section table opposite.

    DimensionsType Rating (A) Dimensions (mm)

    A B WMade to measure All 300 300 91 to 179

    KTCppppLPpp1

    KTCppppLPpp2

    KTCppppLPpC1

    KTCppppLPpC2

  • K9CE22010

    DD

    2108

    25

    DD

    2108

    26

    3Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Catalogue numbers and dimensions

    Elbow components for changing directionIP55

    Edgewise elbows

    Type Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Fixed KTCppppLC3A KTCppppLC4A KTCppppLC7AMade to measure KTCppppLC3B KTCppppLC4B KTCppppLC7B

    KTCppppLCpp

    (1) See the Trunking cross-section table below.

    DimensionsType Rating (A) Dimensions (mm)

    A BFixed 1000 275 275

    1350 290 2901600 300 3002000 320 3202500 340 3403200 360 3604000 400 4005000 440 440

    Made to measure(2)

    1000 276 to 774 275275 276 to 774

    1350 291 to 789 290290 291 to 789

    1600 301 to 799 300300 301 to 799

    2000 321 to 819 320320 321 to 819

    2500 341 to 839 340340 341 to 839

    3200 361 to 859 360360 361 to 859

    4000 401 to 899 400400 401 to 899

    5000 441 to 939 440440 441 to 939

    (2) Only one llmb may be made to measure.

    Canalis KTC

    KTCppppLCpp

    Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82

    3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114

    Height H (mm)Width W (mm)

    DD

    2021

    80

    DD

    2108

    67

  • K9CE22010

    DD

    2108

    19

    DD

    2108

    20

    4 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    sCatalogue numbers and dimensions

    Canalis KTC

    Elbow components for changing directionIP55

    Edgewise tee

    Type Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Fixed KTCppppTC3 KTCppppTC4 KTCppppTC7

    KTCppppTCp

    KTCppppTCp

    (1) See the Trunking cross-section table below.

    DimensionsType Rating (A) Dimensions (mm)

    A B CFixed 1000 275 275 275

    1350 290 290 2901600 300 300 3002000 320 320 3202500 340 340 3403200 360 360 3604000 400 400 4005000 440 440 440

    Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82

    3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114

    Height H (mm)Width W (mm)

    DD

    2021

    80

    DD

    2108

    67

  • K9CE22010 5Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

  • K9CE22020

    DD

    2021

    83

    DD

    2021

    84D

    D20

    2186

    DD

    2021

    85D

    D21

    0827

    2 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    sCatalogue numbers and dimensions

    Zed components for changing directionIP55

    Edgewise zed units

    Type Position of neutral

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Made to measure

    N1 KTCppppZC31 KTCppppZC41 KTCppppZC71N2 KTCppppZC32 KTCppppZC42 KTCppppZC72

    KTCppppZCpp

    Flat zed unitsType Cat. no.

    3L + PE 3L + N + PE 3L + N + PERMade to measure KTCppppZP3 KTCppppZP4 KTCppppZP7

    KTCppppZPp

    Ordering

    Complete the catalogue number by replacing pppp by the rating.Important:

    add the dimensions of the selected component as a technical comment

    Example: the catalogue number of a 1600 A edgewise zed unit, N2, 3L + N + PE with dimensions A = 300 mm, B = 450 mm, C = 300 mm is:KTC1600ZC42, A = 300, B = 450, C = 300.

    b

    Rating

    (1) See the Trunking cross-section table opposite.

    DimensionsRating (A) Dimensions (mm)

    A B CAll 300 130 to 599 300

    (1) See the Trunking cross-section table opposite.

    DimensionsRating (A) Dimensions (mm)

    A B C1000 275 90 to 549 2751350 290 90 to 579 2901600 300 90 to 599 3002000 320 90 to 639 3202500 340 90 to 679 3403200 360 90 to 719 3604000 400 90 to 799 4005000 440 90 to 879 440

    KTCppppZPp

    KTCppppZCp1

    KTCppppZCp2

    Canalis KTC

  • K9CE22020

    DD

    2021

    87

    DD

    2021

    88

    DD

    2108

    28D

    D21

    0829

    DD

    2108

    30

    DD

    2023

    67

    3Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Catalogue numbers and dimensions

    Zed components for changing directionIP55

    Edgewise and fl at zed units

    Type Position of neutral

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Made to measure

    N1 KTCppppCP31 KTCppppCP41 KTCppppCP71N2 KTCppppCP32 KTCppppCP42 KTCppppCP72N3 KTCppppCP33 KTCppppCP43 KTCppppCP73N4 KTCppppCP34 KTCppppCP44 KTCppppCP74

    (1) See the Trunking cross-section table below.

    Canalis KTC

    KTCppppCPp1

    KTCppppCPp2

    KTCppppCPp3

    KTCppppCPp4

    Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82

    3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114

    Height H (mm)Width W (mm)

    DD

    2021

    80

    DD

    2108

    67

    KTCppppCPp3and KTCppppCPp4

    KTCppppCPp1and KTCppppCPp2

    DimensionsRating (A) Dimensions (mm)

    A B C1000 300 195 to 574 2751350 300 210 to 589 2901600 300 220 to 599 3002000 300 240 to 619 3202500 300 260 to 639 3403200 300 280 to 659 3604000 300 320 to 699 4005000 300 360 to 739 440

  • K9CE23000

    DD

    2023

    04D

    D20

    2306

    DD

    2023

    05D

    D20

    2307

    2 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsCatalogue numbers Canalis interfaces for Prisma Plus

    LV switchboard

    Interfaces for Masterpact NW circuit breakers

    Circuit breaker

    Type of circuit breaker

    Number of poles

    Connection Cat. no.Top direct Rear

    NW08 / 16 Fixed or drawout 3 b b 047154 b b 04716

    NW20 / 25 Fixed or drawout 3 b b 047254 b b 04726

    NW32 Fixed or drawout 3 b b 047354 b b 04736

    NW40 Fixed or drawout 3 b 047374 b 04738

    For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.

    Number of modules required in the switchboardCircuit breaker Connection Type of circuit

    breakerNumber of vertical modules(1)

    NW08 / 16 Top direct Fixed or drawout 27Rear Fixed 16

    Drawout 17NW20 / 25 Top direct Fixed or drawout 28

    Rear Fixed 16Drawout 17

    NW32 Top direct or rear Fixed or drawout 28NW40 Rear Fixed or drawout 36(1) 1 module = 50 mm.

    Canalis KTC

    Interfaces for Masterpact NT and Compact NS circuit breakers

    Masterpact NTCircuit breaker

    Type of circuit breaker

    Number of poles

    Connection Cat. no.Top direct Rear

    NT06 / 12 Fixed or drawout 3 b b 047034 b b 04704

    NT16 Fixed or drawout 3 b 047034 b 04704

    For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.

    Compact NSCircuit breaker

    Type of circuit breaker

    Number of poles

    Connection Cat. no.Top direct Rear

    NS630b / 1250 Fixed or drawout 3 b b 047034 b b 04704

    NS1600 Fixed or drawout 3 b 047034 b 04704

    For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.

    Number of modules required in the switchboardCircuit breaker Connection Type of circuit

    breakerNumber of vertical modules(1)

    NT06 / 12NS630b / 1250

    Top direct Fixed 17Drawout 18

    Rear Fixed or drawout 16NT16NS1600

    Rear Fixed or drawout 16

    (1) 1 module = 50 mm.

    Top direct connection

    Rear connection

    Top direct connection

    Rear connection

  • K9CE23000

    DD

    2023

    08D

    D20

    2309

    3Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Catalogue numbers

    Canalis KTC

    Canalis interfaces for Prisma Plus LV switchboard

    Interface supports and protection covers

    Masterpact NWCircuit breaker

    Type of circuit breaker

    Connection Supports Terminal extension bar supports

    Cover

    NW08 / 32 Fixed or drawout

    Top direct 03561 3 x 04694 04871 + 04861Rear 03561 2 x 04694 04871 + 04863

    NW40 Fixed or drawout

    Top direct 03561 - 04871 + 04861Rear 03561 - 04871 + 04863

    Masterpact NTCircuit breaker

    Type of circuit breaker

    Number of poles

    Connection Supports Canalis /circuit breaker connection

    Cover

    NT06 / 12 Fixed or drawout

    3P Top direct 03561 04712 04871 + 04852Rear 03561 04713 04871 + 04853

    4P Top direct 03561 04712 04871 + 04852Rear 03561 04714 04871 + 04853

    NT16 Fixed or drawout

    3P Rear 03561 04713 04871 + 048544P Rear 03561 04714 04871 + 04854

    Compact NSCircuit breaker

    Type of circuit breaker

    Number of poles

    Connection Supports Canalis /circuit breaker connection

    Cover

    NS630b /1250

    Fixed 3P Top direct 03561 04712 04871 + 04851Rear 03561 04713 04871 + 04853

    4P Top direct 03561 04712 04871 + 04851Rear 03561 04714 04871 + 04853

    Drawout 3P Top direct 03561 04711 04871 + 04852Rear 03561 04713 04871 + 04854

    4P Top direct 03561 04712 04871 + 04852Rear 03561 04714 04871 + 04854

    NS1600 Fixed 3P Rear 03561 04713 04871 + 048534P Rear 03561 04714 04871 + 04853

    Drawout 3P Rear 03561 04713 04871 + 048544P Rear 03561 04714 04871 + 04854

    03561

    04711047120471304714

    Arc-chute covers

    Circuit breaker Type of circuit breaker Number of poles Cat. no.Masterpact NT Fixed 3P 47335

    4P 47336Compact NS Fixed 3P 33596

    4P 33597

  • K9CE23000

    DD

    2023

    10D

    D20

    2312

    DD

    2023

    11D

    D20

    2313

    4 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsCatalogue numbers Canalis interfaces for Okken

    LV switchboard

    Interfaces for Masterpact NW circuit breakersFitting the interface does not change switchboard modularity as fi xed by the devices.

    Circuit breaker

    Type of circuit breaker

    Number of poles

    Connection Cat. no.Top direct Rear

    NW08 / 16 Drawout 3 b 87811b 87821

    4 b 87812b 87822

    NW20 / 25 Drawout 3 b 87813b 87823

    4 b 87814b 87824

    NW32 Drawout 3 b 87815b 87825

    4 b 87816b 87826

    NW40 Drawout 3 b 87817b 87827

    4 b 87818b 87828

    For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.

    Canalis KTC

    Interfaces forMasterpact NT circuit breakersFitting the interface does not change switchboard modularity as fi xed by the devices.

    Circuit breaker

    Type of circuit breaker

    Number of poles

    Connection Cat. no.Top direct Rear

    NT08 / 16 Drawout 3 b 87811b 87821

    4 b 87812b 87822

    For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.

    Interface supports

    Circuit breaker Type of circuit breaker Connection Cat. no.NW08 / 40NT08 / 16

    Drawout Top direct 87800

    NW08 / 32(1)NT08 / 16

    Drawout Rear 87801

    (1) For rear connection of the interface to a Masterpact NW40 circuit breaker, the supports are supplied with the interface.

    Top direct connection (RDH)

    Rear connection (RAR)

    Top direct connection (RDH)

    Rear connection (RAR)

  • K9CE23000

    DD

    2023

    14

    5Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Catalogue numbers

    Canalis KTC

    Sealing kitsIP55

    Sealing kits for switchboard and Trihal transformer roofs with interfaceType Rating of the

    trunking (A)Height H of the trunking (mm)

    Cat. no.

    Sealing kit 1000 74 KTB0074TT011350 104 KTB0104TT011600 124 KTB0124TT012000 164 KTB0164TT012500 204 KTB0204TT013200 244 KTB0244TT014000 324 KTB0324TT015000 404 KTB0404TT01

    KTB0pppTT01

  • K9CE24010

    DD

    2108

    31

    DD

    2108

    32

    2 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    sCatalogue numbers and dimensions

    Feed units for switchboards and oil immersed transformersIP55

    Straight feed units

    Type Position of neutral

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Fixed N1 KTCppppER31 KTCppppER41 KTCppER71Made to measure N2 KTCppppER32 KTCppppER42 KTCppER72

    KTCppppERp1, KTCppppERp2

    To order

    Complete the catalogue number by replacing pppp by the rating.Important:

    add the dimensions of the selected unit as a technical comment.

    Example: the catalogue number of a 1350 A made to measure end feed unit, N2, 3L + N + PE, 235 mm long and with between centres J, K and M = 170 mm, is: KTC1350ER42, A = 235, J = 170, K = 170 and M = 170.

    b

    Rating

    (1) See the Trunking cross-section table opposite.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.

    Table of dimensionsRating (A) Neutral Dimensions (mm)

    A J, K, M Y1000 to 1600 N1 235 115 230

    N2 235 to 534 80 to 250 2302000 to 3200 N1 235 115 350

    N2 235 to 534 80 to 250 3504000 and 5000 N1 235 115 510

    N2 235 to 534 80 to 250 510

    KTCppppERp1KTCppppERp2

    Canalis KTC

    Dimensions of connection padsRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Drilling for connection (mm)

    DD

    2021

    82

  • K9CE24010

    DD

    2108

    33

    DD

    2108

    35

    DD

    2108

    34

    DD

    2108

    36

    3Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Flat elbow feed units

    Type Position of neutral

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Made to measure N3 KTCppppER33 KTCppppER43 KTCppER73N4 KTCppppER34 KTCppppER44 KTCppER74

    KTCppppERp3

    (1) See the Trunking cross-section table below.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.

    Tableau of dimensionsRating (A) Neutral Dimensions (mm)

    A B J, K, M Y1000 to 1600 N3, N4 200 to 534 300 80 to 250 2302000 to 3200 N3, N4 200 to 534 300 80 to 250 3504000 and 5000 N3, N4 200 to 534 300 80 to 250 510

    KTCppppERp3

    KTCppppERp4

    Catalogue numbers and dimensions

    Canalis KTC

    Feed units for switchboards and oil immersed transformersIP55

    Cut-out drawing for feed units placed directly on the device roof

    Table of dimensionsRating (A) Dimensions (mm)

    Y U V1000 to 1600 230 K / 2 + J + 80 K / 2 + M + 802000 to 3200 350 K / 2 + J + 80 K / 2 + M + 804000 and 5000 510 K / 2 + J + 80 K / 2 + M + 80

    KTCppppERp4

    Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82

    3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114

    Height H (mm)Width W (mm)

    DD

    2021

    80

    DD

    2108

    67

  • K9CE24010

    DD

    2108

    39

    DD

    2108

    37D

    D21

    0838

    DD

    2108

    36

    4 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Edgewise elbow feed units

    Type Position of neutral

    Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Made to measure N5 KTCppppER35 KTCppppER45 KTCppER75N6 KTCppppER36 KTCppppER46 KTCppER76

    KTCppppERp5

    KTCppppERp5

    KTCppppERp6

    (1) See the Trunking cross-section table opposite.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.

    Table of dimensionsRating (A) Neutral Dimensions (mm)

    A B J, K, M Y1000 N5, N6 175 to 509 275 80 to 250 2301350 N5, N6 190 to 524 290 80 to 250 2301600 N5, N6 200 to 534 300 80 to 250 2302000 N5, N6 220 to 554 320 80 to 250 3502500 N5, N6 240 to 574 340 80 to 250 3503200 N5, N6 260 to 594 360 80 to 250 3504000 N5, N6 300 to 634 400 80 to 250 5105000 N5, N6 340 to 674 440 80 to 250 510

    Cut-out drawing for feed units placed directly on the device

    Table of dimensionsRating (A) Dimensions (mm)

    Y U V1000 to 1600 230 K / 2 + J + 80 K / 2 + M + 802000 to 3200 350 K / 2 + J + 80 K / 2 + M + 804000 and 5000 510 K / 2 + J + 80 K / 2 + M + 80

    Catalogue numbers and dimensions

    Canalis KTC

    Feed units for switchboards and oil immersed transformersIP55

    KTCppppERp6

    Dimensions of connection padsRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Drilling for connection (mm)

    DD

    2021

    82

  • K9CE24010

    DD

    2023

    16

    DD

    2023

    15

    DD

    2023

    17

    5Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Catalogue numbers and dimensions

    Canalis KTC

    Feed units for switchboards and oil immersed transformersIP55

    Bar feed units, fl at outlets

    Type Cat. no.3L + PE 3L + N + PE 3L + N + PER

    Made to measure KTCppppER37 KTCppppER47 KTCppppER77Connection pad dimensions are identical to those of the feed units.

    KTCppppERp7

    KTCppppERp7

    (1) See the Trunking cross-section table below.

    Table of dimensionsRating (A) Dimensions (mm)

    A P - Q S - R ou R - S Q, R, S minimum Y1000 to 1600 235 to 734 160 to 600 160 to 600 80 2302000 to 3200 235 to 734 160 to 600 160 to 600 80 3504000 and 5000 235 to 734 160 to 600 160 to 600 80 510

    Cut-out drawing for straight feed units connected directly to the device

    Table of dimensionsRating (A) Dimensions (mm)

    Y U V1000 to 1600 230

    U = P + 80 if S > R, V = S + 80if R > S, V = R + 802000 to 3200 3504000 and 5000 510

    Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82

    3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114

    Height H (mm)Width W (mm)

    DD

    2021

    80

    DD

    2108

    67

  • K9CE24010

    DD

    2023

    26

    DD

    2023

    25

    6 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Rigid horizontal protective covers for feed units ER N1 to N7Important : when ordering a horizontal cover, make sure you indicate dimensions D, G and Z with the catalogue number.

    Rating (A) Dimensions Y (mm) Cat. no. Weight (kg)1000 to 1600 230 KTB0230CR1 12.002000 to 3200 350 KTB0350CR1 12.004000 and 5000 510 KTB0510CR1 12.00

    KTBppppCR1

    KTBppppCR1

    Protective cover for ER N1 to N6 straight end feed connectorsDimensions D and G are determined by the between centres dimensions (J, K and M) of the end feed connector bars to be protected.The position of the neutral on the feed connector also determines the rule to be used for calculating parameters D and G.

    If the feed connector comes into the cover with the neutral on the right:D = K / 2 + M + 100G = K / 2 + J + 100

    If the feed connector comes into the cover with the neutral on the left:D = K / 2 + J + 100G = K / 2 + M + 100

    Table of dimensionsRating (A) Dimensions (mm)

    Y D G Z1000 to 1600 230 220 to 475 220 to 475 310 to 8002000 to 3200 350 220 to 475 220 to 475 430 to 8004000 and 5000 510 220 to 475 220 to 475 590 to 800

    Protective cover for ER N7 straight end feed connectorsDimensions D and G are determined by the between centres dimensions (P, Q, R and S) of the end feed connector bars to be protected.Position of the neutral on the feed connector also determines the rule to be used for calculating parameters D and G.

    If the feed connector comes into the cover with the neutral on the right:D = max(R ; S) + 100G = max(P ; Q) + 100

    If the feed connector comes into the cover with the neutral on the left:D = max(P ; Q) + 100G = max(R ; S)+ 100

    Table of dimensionsRating (A) Dimensions (mm)

    Y D G Z1000 to 1600 230 340 to 1000 340 to 1000 310 to 8002000 to 3200 350 340 to 1000 340 to 1000 430 to 8004000 and 5000 510 340 to 1000 340 to 1000 590 to 800

    Catalogue numbers and dimensions

    Canalis KTC

    Rigid protective coversIP55

    To order

    To order a protective cover onto which a feed connector is fi tted, the parameters D, G and Z, which depend on the feed connector, must be given.

    Example: the catalogue number of a rigid vertical protective cover with dimension Y = 350 intended for a feed unit with different between centre dimensions D, G and Z (in mm) is:KTB0350CR2, D = 330, G = 450 and Z = 500.

  • K9CE24010

    DD

    2023

    22

    DD

    2023

    21

    DD

    2023

    24

    DD

    2023

    23

    7Schneider Electric

    Cat

    alog

    ue n

    umbe

    rsD

    imen

    sion

    s

    Rigid vertical protective covers for feed units ER N1 to N7Important: when ordering a vertical cover, make sure you indicate dimensions D, G and Z with the catalogue number.

    400 to 800 mm high coversRating (A) Dimensions Y (mm) Cat