Case Study of a PROBE Building
Barclaycard Headquarters BuildingEngland
David Arnold
Troup Bywaters + Anders, London, England
![Page 2: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/2.jpg)
Client’s Brief
Environmentally Friendly Building37,000 m2
2200 Employees1500 Automobiles Opening Windows Peak Temperature < 25 oC Naturally Ventilated and (Cooled)
![Page 3: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/3.jpg)
Planning Options
![Page 4: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/4.jpg)
![Page 5: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/5.jpg)
Building Plan
![Page 6: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/6.jpg)
Solution - Mixed Mode HVAC
![Page 7: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/7.jpg)
Passive Features
Solar ShadingOpening WindowsControlled Natural VentsTrickle VentsExposed Building MassCooling/Balancing Pond
![Page 8: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/8.jpg)
Building System Concept
![Page 9: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/9.jpg)
Cooling - Passive Overnight
![Page 10: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/10.jpg)
Cooling - Chilled Beams
![Page 11: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/11.jpg)
Control
Pre-condition BuildingAllow temperature rise during dayThermal mass limits swingOnly use mechanical when needed Avoid conflict with occupant controlChange to A/C in extremes
![Page 12: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/12.jpg)
ControlOvernight cooling – powered roof
vents
Trickle vents - none
Displacement vent - CO2 Sensors
Perimeter radiation - compensator
Chilled beams- Local sensor
![Page 13: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/13.jpg)
![Page 14: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/14.jpg)
![Page 15: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/15.jpg)
Euphoria to Despondency
Control and Equipment FailuresExtreme ConditionsUnplanned Building OperationsLearning curveBuilding Manager
![Page 16: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/16.jpg)
PROBE Survey Results
Chiller only Used few days per yearGas Heating 96 kWh/m2Electricity Use 234 kWh/m257% energy of Typical Heated Bldg17% less than Good Practice
![Page 17: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/17.jpg)
PROBE End use Electricity
![Page 18: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/18.jpg)
PROBE Carbon Emissions
![Page 19: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/19.jpg)
Energy Use Comparison
![Page 20: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/20.jpg)
PROBE Lessons
A low energy, prestige office.
Significant factors in the exceptional performance of the building in terms of energy use were the integration of thermal storage in the building and cooling pond, solar shading and low transport energy use for the air and water systems. 75% of the ceiling slab is exposed and closely coupled to the occupied space, this seems to provide about the right balance for overnight cooling.
![Page 21: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/21.jpg)
PROBE Lessons
Life cycle costing avoids false economies.
CO2 sensors were specified originally but replaced by inferior detectors as part of a cost saving exercise to maintain the budget. With hindsight it was a mistake.
![Page 22: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/22.jpg)
PROBE Lessons
Manual versus automatic windows.
If the budget had been greater we would have used automatic windows with local controls. They were considered but omitted on cost grounds. Automatic window control would have increased control of overnight cooling but I am not certain whether it could have been justified on life cycle costs alone.
![Page 23: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/23.jpg)
PROBE Lessons
Vertical versus horizontal zoning.
This is a lesson well learnt. All buildings of this type have a problem with overheating on the upper floors. We were aware of the problem and were of the opinion that the temperature difference would be within the design limits. Generally this was the case but it led to complaints and we would use floor by floor control in future.
![Page 24: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/24.jpg)
PROBE Lessons
A success for mixed mode operation.
Mixed mode has proved successful but it has been complemented by the pro-active involvement and control of the facilities team. We need to develop more robust controls. The design strategy for chillers was that they would only be used for a few days per year in a typical summer however they also provide the client with an insurance against the effects of further climate change.
![Page 25: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/25.jpg)
Conclusions
Thermal Storage reduces energy usePrestige Building without full A/CInnovative designs need more timeAnticipatory control will improve useBuilding Operator essential to success
Acknowledgement: Toni Panebianco Building Manager Barclaycard
![Page 26: Case Study of a PROBE Building Barclaycard Headquarters Building England David Arnold Troup Bywaters + Anders, London, England.](https://reader035.fdocuments.in/reader035/viewer/2022062300/56649d895503460f94a6eb40/html5/thumbnails/26.jpg)
Update
Projected staff numbers up to 3350PCs greater than one to oneFour Call CentersChillers failedJoined emissions trading schemeMeasuring energy per person-hour