Canalis KTA 800_4000A

download Canalis KTA 800_4000A

of 205

Transcript of Canalis KTA 800_4000A

  • 7/21/2019 Canalis KTA 800_4000A

    1/205

    Prefabricated busbar trunkingfrom 800 -4000 A

    Canalis

    Catalogue

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    2/205

  • 7/21/2019 Canalis KTA 800_4000A

    3/2053Schneider Electric

    Contents

    Presentation and description

    Panorama of Canalis range K9AE11000/2General K9AE12000/2Run sections K9AE12000/3Disconnectors and run protective devices K9AE12000/4

    Change of direction sections K9AE12000/5Connection sections K9AE12000/6Connection accessories K9AE12000/12Supports and fixings K9AE12000/14Tap-off units K9AE13000/2

    Catalogue numbers and dimensions

    Run components K9AE21010/2Elbow components for changing direction K9AE22010/2Zed components for changing direction K9AE22020/2Canalis interfaces K9AE23000/2Feed units for switchboards and oil immersed transformers K9AE24010/2Feed units for dry-type transformers K9AE24020/2Supports and fixings K9AE25000/2Tap-off units K9AE26010/2

    Coupling isolators and protection of the run K9AE26030/2Special products K9AE27000/2

    Design guide

    Characteristics K9AE39000/2Design guide K9AE31000/2Selection guide K9AE31000/14Degree of protection K9AE32000/2Harmonic currents K9AE33000/2Direct current K9AE34010/2Frequencies K9AE34020/2Measurements and metering K9AE34030/2Fire resistance K9AE35000/2Testing and commissioning procedure K9AE36010/2

    Installation guide

    Layout advice K9AE41000/2Horizontal distribution K9AE41000/12Rising mains K9AE45000/2Panorama of connection solutions K9AE42000/2Connection to LV switchboards K9AE42000/4Connection to cast resin transformers K9AE43000/2Connection to oil immersed transformers K9AE44000/2

    Recommendations

    Reception, handling and storage 2Maintenance 2Recycling 3

    Introduction

    In decentralised distribution, Canalis hits the high note! K9AE01010/3With Canalis, you play all the right notes! K9AE01020/2Canalis, in total harmony with the environment! K9AE01030/2Canalis, fortissimo throughout the range! K9AE01040/2Canalis KT, a display of advantages! K9AE02010/2Canalis KT, everyone to their music! K9AE02020/2Play all the worlds musicwith Canalis! K9AE02030/2With the Canalis tools and services, let us compose your project! K9AE02040/2

  • 7/21/2019 Canalis KTA 800_4000A

    4/205

  • 7/21/2019 Canalis KTA 800_4000A

    5/205

    PD2023

    82

    PD202380

    PD202088-104

    3Schneider Electric

    Introduction

    In decentralised distribution,Canalis hits the high note!

    Canalis on its second world tourTo better meet your needs, Canalis extends its system solutions.New low and medium power busbar trunking products.Pre-equipped luminaires.Strip lighting.Specially designed cable trays.

    A total coordination with theSchneider Electric systemCanalis is now part of a comprehensive offering of Schneider Electric productsdesigned to operate together. This concept covers all low and mediumvoltage electrical distribution components. The result is an optimised electrical

    installation with even higher performance through full electrical, mechanical andcommunication compatibility.With the new Canalis range, you get a complete, tested distribution solutionthat complies with standards. It is perfectly suited to traditional applications(factories, warehouses, etc.) and to the distribution of electrical power from theincoming transformer on through to all types of loads in offices, commercialpremises, laboratories, etc.

    Canalis KT is changing to provide youwith

    more flexibility. The adjustable section adapts to the worksite thus makingsure you meet deadlines.

    bbbbb

    b

    ease of connection with the plug and play transformer and switchboardconnections.

    more assistance. Our teams will assist you throughout your project.

    b

    b

    Canalis moves forward without changingthe way you workThe new Canalis range is fully compatible with the existing range.An existing installation can be upgraded without any problem.

    More than 50,000 km of Canalis busbar trunking has been

    sold around the world.

    K9AF01010

  • 7/21/2019 Canalis KTA 800_4000A

    6/205K9AE01020

    PD202043

    PD202044

    PD202155

    2 Schneider Electric

    Introduction

    With Canalis, you play all the rightnotes!

    Distribution systems Schneider Electric offers different distribution systems tofi

    t your operating needs.

    Centralised distribution

    For all continuous processes:cement plantsoil and gaspetrochemicalssteelpaper, etc.Centralised distribution offers:continuity of servicecombined distribution of power, control and monitoring circuitssupervision, etc.

    Our solutions:

    Prisma Plus and Okken switchboards.

    bvvvvvbvvv

    b

    Decentralised distribution

    For manufacturing industries:mechanicaltextileslumberinjection mouldingelectronicspharmaceuticals

    livestock, etc.Decentralised distribution lets you:design installations without layout detailsupgrade without shutting down productionget systems up and running sooner thanks to faster installationgenerate savings depending on the number of loads.

    Our solutions:Prisma Plus switchboardsCanalis busbar trunking.

    bvvvvvvvbvvvv

    bb

    Combined distribution

    Where the advantages of both centralised and decentralised distribution arerequired.

    Commercial and service buildings:

    officesstoreshospitalsexhibition halls, etc.Infrastructures:airportstelecommunicationsinternet data centrestunnels, etc.Industrial facilities:pharmaceuticalsfood processing, etc.

    Our solutions:Prisma Plus and Okken switchboardsCanalis busbar trunking.

    b

    vvvvbvvvvbvv

    bb

  • 7/21/2019 Canalis KTA 800_4000A

    7/205K9AE01020

    PD202383

    PD202427

    3Schneider Electric

    Introduction

    With Canalis, you play all the rightnotes!

    The Canalisdecentraliseddistribution concept

    Electrical power available at all points,throughout theinstallation.

    Exclusive features of the Schneider Electric systemTotal coordination of the Schneider Electric system provides maximum safety of lifeand property, continuity of service, upgradeability and ease of installation.Total coordination is made easy by the tables in the Selection Guide. They helpyou chose the right combination of circuit breakers and busbar trunking.Product characteristics are checked by calculations and tests carried out in ourlaboratories.

    A competitive installation.Simplicity, upgradeability, safety and continuity of service and operation.

    Savings start with installationWith tap-off points every 3 metres, Canalis busbar trunking reduces installationcosts.Given the low cost of adding new circuits, savings increase as the number of loadsincreases, a natural consequence of the growth of your business.

    Upgradeable during operationIn decentralised distribution, evolving operating requirements and costs areintegrated right from the start.

    The addition, relocation or replacement of load equipment can be carried outquickly, without de-energising the supply trunking or shutting down operation.

    The cost of making such changes is greatly reduced:loads are located close to supply pointstap-off points are always available

    tap-units can be reused or new ones added quickly for load relocation orreplacement needs.

    b

    bvv

    v

    Reusable in the event of major changesWhen making major modifications to your installation, the existing trunking can beeasily dismantled and reused.

    DD205658

  • 7/21/2019 Canalis KTA 800_4000A

    8/205K9AF01030

    DD205675

    D

    D205674

    2 Schneider Electric

    Introduction

    Canalis, in total harmony with theenvironment!

    Safety of life and property With Canalis, no risk in case of fireThe busbar trunking has a low combustible load. Its construction uses very littleconsumable material and is halogen free.In the event of a fire, the busbar trunking does not emit any gas or toxic smoke.

    An inherent fire barrier, the busbar trunking helps prevent the propagation of afire through partition walls and floors for a duration of 2 hours.

    Halogen-sensitive applicationsPublic buildings (infrastructures, hospitals, schools, etc.).Buildings with evacuation difficulties (high-rises, ships, etc.) and service-activity

    buildings.Sensitive processes (production of electronic components, etc.).

    Canalis contains no PVCs

    When PVCs burn, they produce large amounts of smoke that can be a serioussafety hazard.Reduced visibility:risk of paniccomplicates rescue workSmoke toxicity:hydrogen chloride gas (highly toxic)carbon monoxide (danger of asphyxiation).

    bb

    b

    bvvbvv

    Canalis reduces the risk of exposure to electromagnetic fieldsAccording to the WHO (World Health Organisation), exposure to electromagneticfields can be a health hazard starting at levels as low as 0.2 micro-Teslas andcould represent a long-term risk of cancer. Some countries have created standards

    that stipulate limits (e.g. 0.2 T at 1 metre in Sweden).

    All electrical conductors generate magnetic fields proportional to the distancebetween them. The design of Canalis busbar trunking with tightly spacedconductors in a metal enclosure helps to considerably reduce radiatedelectromagnetic fields.

    The electromagnetic field characteristics of Canalis busbar trunking are well-defined and measurements show that they are far below potentially dangerouslevels.You will find the magnetic induction values of our products on the Characteristicspages.

    Example:Consequences of a fire in a 100 m2 office withelectrical distribution by cables.200 kg of cables (i.e. 20 kg of PVC) produces:

    4400 m3 of smoke7.5 m3 of hydrochloric acid3.7 kg of corroded steel.

    bbb

    Health

  • 7/21/2019 Canalis KTA 800_4000A

    9/205K9AF01030

    DD205673

    3Schneider Electric

    Introduction

    Canalis, in total harmony with theenvironment!

    Environment Canalis is fully recyclableCanalis busbar trunking can be reused.Canalis busbar trunking is designed for a long service life and can easily bedismantled, cleaned and reused.

    All packaging materials can be recycled (cardboard or recyclable polyethylenefilm).

    All Canalis products are designed for safe end-of-life recycling. PVC, on theother hand, requires neutralisation of the hydrochloric acid produced using limeand generates dioxins that are extremely toxic.

    Canalis helps conserve natural resourcesThe depletion of raw materials (copper, plastics, etc.) is one of our ongoingconcerns.For this reason, we have optimised the used of all materials used to make ourbusbar trunking.

    Reduction of dangerous or polluting materials. We design our products to meet

    future European directives.Reduction in the weight of insulating materials.Reduction in the use of plastics for improved fire performance: less energy

    released during combustion, thereby limiting propagation and facilitating extinction(lower calorific value).

    b

    b

    b

    b

    bb

    Example:1 kg of PVC generates 1 kg of waste.

    Energy savings Canalis reduces your line losses by 40 %Canalis divides your consumption of copper and insulation

    by a factor of threeThe cost of an electrical installation includes the initial investment for theequipment and its installation, the cost of maintenance and the cost of energylosses during operation.The cross-sections of our products are dimensioned to minimise the total cost ofyour installation over a 3-year period for medium intensity use (30 % load level,5 days a week and 10 hours a day).

    Example:30 m of Canalis KS 250 A trunking equipped with ten 4-pole 25 A feeders.

    DD205656

  • 7/21/2019 Canalis KTA 800_4000A

    10/205K9AE01040

    PD202384

    2 Schneider Electric

    Introduction

    Canalis, fortissimo throughoutthe range!

  • 7/21/2019 Canalis KTA 800_4000A

    11/205K9AE01040 3Schneider Electric

    Introduction

    Canalis, fortissimo throughoutthe range!

  • 7/21/2019 Canalis KTA 800_4000A

    12/205

  • 7/21/2019 Canalis KTA 800_4000A

    13/205K9AE02010

    PD202229-68

    PD202386

    3Schneider Electric

    IntroductionComplete safety Busbar trunking temperature rise and short-circuit withstand are known andindependent of the installation. Coordination of the Schneider Electric system

    results in complete control of the electrical network.

    Installation standards UTE C 15-105 chapter B.6.2 and IEC 60 364 chapter5.523.6 stipulate that above 4 parallel cables, it is preferable to use busbartrunking. Paralleling many cables leads to uneven distribution of currents and therisk of abnormal temperature rise.

    The busbar trunking and tap-off units are designed to guarantee the safety ofpersonnel and equipment:

    plug-on connections to silver-plated copper bars,bolted connections with tightening torque guaranteed by torque nuts,foolproof system to avoid the risk of assembly errors,IP55 certified splash and dust protection,sprinklerresistance test in compliance with Volkswagen specifications,access to live parts have IPxxD protection (1 mm wire diameter).

    Its metal enclosure and high protection degree protect the busbar trunking from allexternal aggressions (corrosion, rodents, etc).

    b

    b

    b

    vvvvvv

    Operating continuity When working on the electrical installation, the busbar trunking provides immediatereadability of the electrical circuit thus allowing the appropriate zone to be quicklyidentified.Tap-off units can be plugged-on and off without the need for a shutdown; service

    continuity is thus irreproachable.The quality of the electrical contacts guarantees maintenance free operatingcontinuity.

    A large range of tap-off units Canalis KS tap-off units are fully compatible with Canalis KT:they cover all your requirements:Canalis KS tap-off units: 63 to 400 A,Canalis KT tap-off units: 400 to 1000 A,they offer circuit breaker or fuse protection.

    This offer includes tap-off units that can be fitted with the Transparent Readysystem:

    they monitor your installation to avoid overloads, thus ensuring service continuity,they provide metering to allow accurate management of your electrical

    distribution network (allocation of costs to each consumer).

    bvvb

    vv

    Canalis KT, a display ofadvantages!

  • 7/21/2019 Canalis KTA 800_4000A

    14/205K9AE02020

    PD202391

    PD202388

    PD202387

    PD202389

    PD202390

    2 Schneider Electric

    Introduction

    Canalis KT, everyone totheir music!

    Key pointsFire barrier.

    Halogen free.

    Small size.

    Operating continuity.

    b

    b

    b

    b

    Office and hospital buildings

    Key points

    Halogen free.

    Distribution and metering.

    Able to be evolved.

    Sprinklers.

    b

    b

    b

    b

    Shopping centres, airportsand exhibition centres

  • 7/21/2019 Canalis KTA 800_4000A

    15/205K9AE02020

    PD395077-68

    PD202392

    PD202393

    109405

    PD202394

    PD202395

    3Schneider Electric

    Introduction

    Canalis KT, everyone totheir music!

    Key pointsOperating continuity.

    Able to be evolved.

    Low voltage drops.

    Network readability.

    b

    b

    b

    b

    Car industry andindustrial buildings

    Key points

    Operating continuity.

    High tap-off density.

    Able to be evolved.

    Network compactness and readability.

    b

    b

    b

    b

    Internet Data Centers

  • 7/21/2019 Canalis KTA 800_4000A

    16/205K9AE020302 Schneider Electric

    Introduction

    Play all the worlds musicwith Canalis!

    Tertiary

    Name Lighting and low current Medium current Highcurrent

    Country

    KDP KBA KBB KN KS KT

    Offices

    PD202244 Air France (headquarters) b b France

    Allianz b b Germany

    Axa b b France

    Chamber of Commerce b b Luxembourg

    Commerz Bank b b Germany

    Lexel b b b Sweden

    Telefnica b b Spain

    Trade Center b b Spain

    Tour du RDC b b Tunisia

    Turning Torso b Sweden

    Vodafone b b New Zealand

    Internet Data Center

    PD202245 Banco Commercial Portugus b b Portugal

    Colt b b France

    Digiplex b b Sweden

    IBM b b b b Spain, Italy

    MCI-Worldcom b b b b Italy, United Kingdom

    Hotels and restaurants

    PD202246 Hyatt b Tunisia

    Mc Donalds b France

    Soldeo Andorra Hotel b b Spain

    Hospitals

    PD202247 Children Clinic b b Sweden

    Brussels University Hospital b Belgium

    Derby Hospital b United KingdomOran Hospital b b Algeria

    St Joseph Hospital b France

    Stockholm Hospital b Sweden

    Val de Grce Hospital b France

    Michalon Hospital b b France

    Manussia Hospital b Egypt

    Supermarkets and hypermarkets

    PD202248 Alcampo b b b Spain

    Auchan b b b b b b World

    B&Q b b b United Kingdom

    Carrefour b b b b b b World

    Coop b b b

    Italy

    Fnac b b Spain, France

    Ikea b b b b b China, Spain, France,Sweden

    Mark & Spencer b Belgium, Spain,United Kingdom

    ToysR Us b Spain

  • 7/21/2019 Canalis KTA 800_4000A

    17/205K9AE02030 3Schneider Electric

    Introduction

    Play all the worlds musicwith Canalis!

    Industry

    Name Lighting and low current Medium current Highcurrent

    Country

    KDP KBA KBB KN KS KT

    Car industry

    PD202249 BMW b b b b Italy

    Citron b b b b b b China, Spain, France

    Daewo b South Korea

    Dacia b b b b b Romania

    Iveco b b b b Spain, Italy

    Peugeot b b b b China, Spain, France

    Nissan b b b b b Spain

    Renault b b b b b Spain, France, CzechRepublic

    Seat SpainValo b b b China, France, Italy,

    Poland

    Volkswagen b b b Spain, Germany

    Other industriesAerospace industry

    Airbus b b b Italy

    Food-processing industry

    Coca-Cola b b Spain, Italy, Belgium

    Danone b b b World

    Pasquier b b France

    Livestock production farms and greenhouses

    Favier henhouse b b France

    Greenhouse b Netherlands

    Ceramic industry

    Esmalglas ceramic b b b b b Spain

    Electricity

    Legrand b France, Turkey

    Watch-making

    Rolex b b b Switzerland

    Microelectronics

    Intel b b b b Irelande

    ST Micro-lectronique b b b b France

    Lead industry and water treatment

    Grundfos b China

    Industrial technology

    Bosch b b China

    Telephony

    Phillips b Netherlands

    Nokia b b Sweden

    Textile industry

    Louis Vuitton b b b Spain

    Delta b b Israel

  • 7/21/2019 Canalis KTA 800_4000A

    18/205K9AE020304 Schneider Electric

    Introduction

    Infrastructure

    Name Lighting and low current Medium current Highcurrent

    Country

    KDP KBA KBB KN KS KT

    Airports

    PD202250 Paris Airport b b b b b France

    Cairo Airport b Egypt

    Heathrow Airport b b b United Kingdom

    Hong-Kong Airport b China

    Landvetter Airport b Sweden

    Arlanda b b b Sweden

    Satelite Barajas b Spain

    Marine

    PD202251 Chantier de lAtlantique b b France

    Meyerwerft b b Germany

    Undergrounds

    PD202252 Guanghzou Underground b China

    London Underground b United Kingdom

    Madrid Underground b b Spain

    Singapore Underground b Singapore

    Other infrastructuresAlexandria Library b b Egypt

    Centre international dexpositionde Suzhou

    b b China

    CERN b b Switzerland

    Stade de France b b France

    Play all the worlds musicwith Canalis!

  • 7/21/2019 Canalis KTA 800_4000A

    19/205K9AE02030 5Schneider Electric

    Introduction

  • 7/21/2019 Canalis KTA 800_4000A

    20/205K9AE020402 Schneider Electric

    Introductio

    n

    With the Canalis tools andservices, let us compose yourproject!

    Technical files The technicalfi

    les have been compiled from completed contracts and provideanswers to questions concerning the installation of Canalis busbar trunking inspecific business sectors.

    In data centersReference:ART 3722DESBS001FR

    In exhibition centresReference:ART 65946KD0C00CTAFEEN / 65946

    In shopping centresReference:Available in your sales office.

    In electronics factoriesReference:ART 65944KD0C00CTAFEEN / 65944

    In tiles factoriesReference:DEBU005EN

    In car plantsReference:

    Available in your sales office.

    In livestock buildingsReference:DESWED105010EN

    In greenhousesReference:ART 808260DESWED105013EN

    In logistic centresReference:ART 807993DESWED105011EN

    In cruise shipsReference:DESWED105014EN

    In garagesReference:DESWED103004EN

    Find a large range of Cahier Technique publications on the Schneider Electricweb site: www.schneider-electric.com.

  • 7/21/2019 Canalis KTA 800_4000A

    21/205K9AE02040

    PD202396

    DD210861

    3Schneider Electric

    Introductio

    n

    With the Canalis tools andservices, let us compose yourproject!

    Work-out yoursolution together

    Our teams are available to provide customers with technical assistance throughoutthe installation of their projects.

    Design of electrical distribution architectures:design of decentralised transport and distribution systems,technical and financial optimisation of busbar trunking design projects,transformer / switchboard link,installation coordination and discrimination.

    Full installation drawings:3D Autocad drawings with corresponding parts lists,2D drawing with dimensions,detailed connection drawings.

    Site supervision and commissioning assistance.

    Training for designers and contractors.

    bvvvv

    bvvv

    b

    b

    Project

    launch

    Technical

    support

    CanBrass

    drawing

    Autocad

    drawing

    Production

    Project

    management

    On-site

    instruction

    and

    installation

    After-sales

    service

  • 7/21/2019 Canalis KTA 800_4000A

    22/205K9AE020404 Schneider Electric

    Introductio

    n

    Enter Canalis run characteristics.

    With the Canalis tools andservices, let us compose yourproject!

    Switchboard access estimation of material and labour costs.

    Schneider Electric offers a comprehensive design and costing software.The CanBrasssoftware, edited by Schneider Electric, was developed to help youdesign and cost Canalis busbar trunking runs.

    CanBrass, a comprehensive toolThe CanBrass software allows you to quickly design the best layout for yourproject.It allows:

    the material needed to be easily chosen,a list of catalogue numbers and their exact quantities to be defined,a comprehensive quote that includes material and labour.

    There are 2 options:linear metre costing,graphical costing.

    bbb

    bbb

    CanBrass gives you all thehelp you need

    Design guide

    Linear metre costingThe user enters the following parameters:

    for the power run: rating, polarity, protection degree,for each feeder: number of machines, rating and protection,overall run length, number of change-of-direction sections and the connection

    type.

    bbb

    PD202374

    PD202375

    PD202376

  • 7/21/2019 Canalis KTA 800_4000A

    23/205K9AE02040 5Schneider Electric

    Introductio

    n

    With the Canalis tools andservices, let us compose yourproject!

    Definition of catalogue numbersThe software gives an optimum breakdown of the project and provides a bill ofmaterials: catalogue number, quantity, price.The software can also generate 2D or 3D drawings with dimensions.

    Breakdown of the run by product function.

    QuoteThe CanBrass software can generate a comprehensive customised quote (quantity,catalogue number, unit price, total net price and installation time).

    Graphical costingSimply create a 3D drawing of the busbar trunking using appropriate dialogueboxes.Enter the following:

    rating,polarity,connection types.

    bbb

    PD202377

    PD202378

    PD202379

  • 7/21/2019 Canalis KTA 800_4000A

    24/205K9AE110002 Schneider Electric

    Presentation

    Presentation

    Range Canalis KDP Canalis KBA

    PD202216

    PD202217

    Run componentsDegree of protection IP55 IP55

    Number of circuits 1 1

    Rating 20 A 25 and 40 A

    Tap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm 500 - 1000 and 1500 mm

    Standard lengths 24 and 192 meters 2 and 3 meters

    Finish - Galvanised steel

    Maximum distance between fixing points 0,33 meter 3 meters

    KDP-KBA-KBB tap-off units

    PD202225

    PD202225

    Rating 10 and 16 A 10 and 16 A

    Option- White RAL 9010

    - Bus conductor

    - -

    Panorama of Canalis rangeLighting distribution

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    25/205K9AE11000 3Schneider Electric

    Presentation

    Canalis KBB Canalis KBX

    PD202219

    PD202220

    IP55 IP20

    1 or 2 1

    25 and 40 A 25 A

    500 and 1000 mm -

    2 and 3 meters 1,53 and 3,06 meters

    Galvanised steel White

    5 meters 3 meters

    PD202225

    10 and 16 A

    White RAL 9010 -

    Bus conductor -

    Clean earth -

    Presentation

    Canalis KTA

    Panorama of Canalis rangeLighting distribution

  • 7/21/2019 Canalis KTA 800_4000A

    26/205K9AE110004 Schneider Electric

    Presentation

    Range Canalis KN Canalis KS

    PD202221

    PD202222

    Run componentsDegree of protection IP55 IP55

    Polarity 3L + N + PE 3L + N + PE

    Rating 40, 63, 100 and 160 A 100, 160, 250, 400, 500, 630,

    Tap-off intervals 500 - 1000 or 3000 mm 1000 mm on each face

    Standard lengths 3 meters 3 and 5 meters

    Finish White RAL 9001 White RAL 9001

    Maximum distance between fixing points 3 meters 3 meters

    Tap-off units

    PD

    202227

    PD

    202228

    Rating Plug-in 16 to 63 A 25 to 400 A

    Bolt-on

    OptionRemote control conductor -

    Presentation

    Canalis KTA

    Panorama of Canalis rangePower distribution

  • 7/21/2019 Canalis KTA 800_4000A

    27/205K9AE11000 5Schneider Electric

    Presentation

    Canalis KS colonne montante Canalis KT

    PD202223

    PD202088-74

    IP55 IP55

    3L + N + PE 3L + PE ; 3L + N +PE ; 3L + N + oversized PE

    and 1000 A 100, 160, 250, 400, 500, 630, 800 and 1000 A 800, 1000, 1250, 1600, 2000, 2500, 3200 and 4000

    500 mm 500 - 1000 mm

    Defined by the floor pitch 2 and 4 meters

    White RAL 9001 White RAL 9001

    Li au pas dtage 3 meters

    PD

    202228

    PD

    202229

    25 to 400 A 25 to 400 A

    400 to 1000 A

    - -

    Presentation

    Canalis KTA

    Panorama of Canalis rangePower distribution

  • 7/21/2019 Canalis KTA 800_4000A

    28/205K9AE11500

    PD202312

    PD202328

    2 Schneider Electric

    Presentation

    Canalis KTA from 800 to 4000 AFor horizontal transport anddistribution

    Presentation

    Run sections Tap-off units Change-of-direction sections

    Rating: 800 to 4000 A.Transport sections:fixed lengths: 2 and 4 metres,non-standard lengths: 0.5 and 3 metres,Distribution sections:fixed lengths: 2 and 4 metres,Adjustable lengths 1.10 to 1.50 metres.

    bbvvbvb

    Canalis KS plug-on tap-off units arecompatible with the Canalis KT busbartrunking:

    protection by 25 to 400 A fuses,protection by 100 to 400 A Compact NS

    circuit breakers.Canalis KT fixed tap-off units:protection by 400 to 1000 A Compact NS

    circuit breakers

    b

    vv

    bv

    Change-of-direction sections adapt to allbusbar trunking requirements.There are both fixed and made-to-

    measure lengths.

    b

    b

    PD202313

    PD202314

    PD202315

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    29/205K9AE11500

    PD202300

    3Schneider Electric

    Presentation

    Presentation Canalis KTA from 800 to 4000 AFor horizontal transport anddistribution

    Interface connections Universal supply connections Horizontal fixing supports

    Pre-fabricated interfaces connections canbe incorporated into:Prisma Plus and Okken switchboards,France Transfo dry-type transformers.

    b

    vv

    Supply connections allow thebusbar trunking to be connected to theswitchboards busbar or to the transformer.

    b There are two types of support forinstalling the busbar trunking horizontally.One type of fixing: to fix the busbar

    trunking to its support.

    b

    b

    PD202431

    PD202317

    PD202318

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    30/205K9AE115004 Schneider Electric

    Presentation

    Run sectionsRating: 800 to 4000 A.

    Distribution sections,fi

    xed 2 metre lengths.Transport sections for going through floor slabs,fixed 0.5 to 3 metre lengths.

    b

    bb

    PD202320

    PD202319

    Vertical fixing supportFor installing the busbar trunking vertically, they

    ensure:height and depth adjustment,load sharing,absorption of expansions, vibrations, etc.They can be fixed either to the floor, the wall or to

    a bracket.

    b

    vvvb

    PD202321

    Tap-off unitsCanalis KS tap-off units are compatible with the

    Canalis KT busbar trunking:protection by 25 to 400 A fuses,protection by 100 to 400 A Compact NS circuit

    breakers.Canalis KT fixed tap-off units:protection by 400 to 1000 A Compact NS circuit

    breakers.

    b

    vv

    bv

    PD202322

    Presentation Canalis KTA from 800 to 4000 AFor distribution to different levelsRising mains

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    31/205K9AE11500 5Schneider Electric

    Presentation

    Rating (A) Type of protectionModular switchgear Compact NS Fuses Compact NS with

    measurement and metering

    Plug-on tap-off units

    25 to 125

    PD202149

    PD202150

    PD202138

    25 / 50 A for NF / DIN fuses32 A for BS fuses63 A, 8 x 18 mm modules

    PD202148

    PD202147

    For Compact NS100 circuit breaker

    100 A, 12 x 18 mm modules

    63 A for DIN fuses100 A for NF / DIN fuses80 A for BS fuses

    160

    PD202150

    PD202150

    PD202323

    For NG125 / 160 circuit breaker For Compact NS160 circuit breaker 160 A for NF / DIN / BS fuses

    250 to 400

    PD202324

    PD202184 Fitted with DIN rail for Powerlogic

    PM810

    PD

    202324

    For Compact NS250 circuit breaker

    PD202325

    For Compact NS250 circuit breaker

    PD202325

    250 / 400 A for NF / DIN fuses

    For Compact NS400 circuit breaker

    For Compact NS400 circuit breaker

    Fixed tap-off units

    400 and 630

    PD202326

    For Compact NS400 and NS630circuit breaker

    800 and 1000

    PD202327

    For Compact NS800 and NS1000circuit breaker

    Tap-off units from 25 to 1000 APresentation

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    32/205

    DD202387

    DD202388

    DD202389

    DD202434-m

    DD202435-m

    DD202436-m

    DD202445

    DD202498

    2 Schneider Electric

    Description

    8 ratings are available, from 800 to 4000 A.4 aluminium live conductors with identical cross-sections (3L + N + PE version).Conductors insulated using polyester film, class B 130 C, halogen free.Standard busbar trunking is IP55.Insulation voltage: 1000 Volts.Available polarities: 3L + PE, 3L + N +PE, 3L + N + PER (reinforced PE)

    The KT busbar trunking is of compact design and can be installed edgewise, flat orvertically.This design, without the addition of a fire barrier joint, allows the busbar trunking tobe installed through a floor slab or fire barrier wall.As standard, the Canalis KT busbar trunking acts as a 2-hour fire barrier inaccordance with

    ISO 834.The RAL 9001 pre-lacquered galvanized steel casing provides protection andmechanical fixing of the conductors.Further, it is used as the PE protective conductor (in accordance with NFC 15100and IEC 60367).In its reinforced version 3L + N + PER, the busbar trunking is fitted with anadditional internal conductor with a cross-section equal to half that of the phaseconductor.This version also has lateral reinforcements to allow high short-circuit currents (Isc)to be supported.

    The Canalis KT busbar trunking is suitable for applications containing harmonics bytaking into account the appropriate derating factor. See Harmonic currents in theDesign guide.

    bbbbbb

    The conductors are sandwiched together inside the metal

    casing.

    The electrical contact pads of the sections are made from

    bonded bimetallic aluminium / copper.

    The junction between sections is made using a joint block.The joint block provides the following:

    electrical junction between live conductors and between PE protective

    conductors, mechanical link between the two sections.

    It provides simultaneous continuity between all conductors.It is tightened using torque bolt(s) (1 to 4 depending on the rating) with snap-offheads.The nut head snaps-off, freeing a red washer, when the correct tightening torque isreached.

    This operation is checked visually:if the red washer is absent: it has been tightened,if the red washer is visible: it has not been tightened.

    This device guarantees the necessary contact pressure between live conductorsand is operator independent.

    For dismantling or maintenance operations, the nut has a second head.The tightening torque is 6 daN.m.

    All sections (apart from ER and EL feed units) are supplied with their jointblock, delivered in a separate parcel.If the run has a feed unit (ER or EL) at each end, an additional joint blockmust be ordered.

    b

    bb

    The KS plug-on tap-off units are connected to the busbar trunking whilst live (off-load) via spring jaw connections.Contact zone coating:

    silver-plated copper at jaw contact points,aluminium / silver-plated copper bimetallic saddle welded to the live conductors.

    bb

    3L + N + PER

    Description

    The Canalis KT busbar trunking is intended for high power distribution andtransport in industrial, commercial and tertiary buildings.Assembly of prefabricated sections that adapt to all run configurations.

    General

    3L + PE

    3L + N + PE

    Run sections

    Tap-off contact

    Joint block

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    33/205

    DD202390

    DD202438

    DD202437

    DD202483

    3Schneider Electric

    Description

    Run sections

    Transport sections - Type ETTransport the current without tap-off points.Available in 2 and 4 metre fixed lengths or made to measure from 0.50 to 3 metres.

    Adjustable section -Type AJCompensates for dimensional differences in the installation.

    Adjustable length from 1.10 to 1.50 metres.

    Sections with tap-off points for plug-on tap-off units

    Type EDED run sections are for current distribution.They use 25 to 400 A KS tap-off units.These tap-off units can be plugged-on whilst live, but off-load.

    Available in fixed 2 or 4 metre lengths with 3 tap-off points on one side.

    Sections with tap-off points for fixed tap-off units - Type EBEB run sections are for current distribution.They use specific KT 400 to 1000 A tap-off units.These tap-off units can only be fitted / removed when the run is not energised.

    Available in a 2 metre fixed length with one tap-off point or a 4 metre fixed lengthwith 2 tap-off points.

    Description

    Canalis KTA

    Straight sections

  • 7/21/2019 Canalis KTA 800_4000A

    34/205

    DD202391

    DD202392

    DD202439

    DD202

    441

    DD202440

    DD2024

    46

    DD210811A

    DD210813

    4 Schneider Electric

    Description

    The TP type transposes the phases.b

    Expansion section - Type DBIt controls and absorbs the expansion of Canalis runs and must be used on runsover 30 metres and each time the busbar trunking passes through a buildingexpansion joint.Refer to the installation guide.

    Available in a 1 metre length, it can be fitted vertically or horizontally.At its centre it has flexible conductor joints and a sliding case able to absorb therelative movements of each part of the section.

    Transposition sections - Types TN, TPUsed when the phase order of the switchboard is different to that of thetransformer.Available in a 1 metre length and is the same physical size as a transport section.

    The TN version transposes the neutral.b

    Additional joint block - Type YAIf the run has a feed unit (supplied without a joint block) at each end, an additionaljoint block must be ordered.Each joint block is supplied with the necessary covers, nuts and bolts.

    Run end cover - Type FAThe end cover protects and insulates the conductor ends and is fitted to the lastsection.

    Other run sectionsDisconnectors and run protectivedevices

    Fitted between 2 flat or edgewise sections, they isolate or protect a busbartrunking part run.Each assembly is supplied fitted with a 3 or 4-pole device complete with rotaryhandle.Supplied with:

    an auxiliary connection terminal,lifting rings,upstream and downstream terminal shields.

    Colour: white RAL 9001, 100 % polyester paint on galvanized sheet steel.Refer to manufacturers data for switchgear characteristics.Fitted with a rotary handle, the tap-off unit can only be opened once the device

    has been switched off.

    Run disconnector tap-off units - Type SLType SL for:

    Compact NS 1000 to 1600 A type NA fixed isolators:unhingeable door,3-point closing (possibility of locking with key lock, not supplied),Interpact INV isolator, 2000 to 2500 A:unhingeable door,3-point closing (possibility of locking with key lock, not supplied),Masterpact NW 3200 A type HF fixed isolator supplied with:transparent protection cover,adaptation kit for Ronis lock + 1 Ronis lock,complete Harting plug, not cabled.

    Run protection tap-off units - Type PL

    Type PL for:Compact NS 1000 to 1600 A type N fixed circuit-breakers:unhingeable door,3-point closing (possibility of locking with key lock, not supplied).

    For circuit-breakers greater than 1600 A, consult the sales office.

    bbb

    bvvbvvbvvv

    bvv

    Description

    Canalis KTA

    Other run sections

    Disconnectors and run protective devices

  • 7/21/2019 Canalis KTA 800_4000A

    35/205

    DD202393

    DD

    202394

    DD202395

    DD2023

    96

    DD202397

    DD202398

    DD202433

    DD202432

    5Schneider Electric

    Description

    Elbows - Types LP and LCTo go up or down, to turn right or left:

    type LP, flat elbow available in fixed or made-to-measure lengths,b

    Zeds - Types ZP, ZC, CP3-branch made-to-measure:

    flat or edgewise, to move the run axis upwards, downwards, to the right or to theleft without having to bend the busbar trunking:

    type ZP, flat Zed,

    b

    v

    Edgewise T junctions - Type TCTo feed runs perpendicular to the main run.

    Change of direction sectionsDescription

    type LPpC, flat made-to-measure angled elbow,b

    type LC, edgewise elbow available in fixed or made-to-measure lengths,b

    type LCpC, edgewise made-to-measure angled elbow.b

    type ZC, edgewise Zed,v

    edgewise / flat, to provide the busbar trunking with a bend.Type CP, edgewise and/or flat Zed.

    bv

    Canalis KTA

    Simple changes of direction

    Changes of direction

  • 7/21/2019 Canalis KTA 800_4000A

    36/205

    DD202306

    DD202310

    DD202314

    6 Schneider Electric

    Description

    To connect the KTA busbar trunking to different terminals or to transformer,switchboard, generator set, etc. busbars. Canalis offers high performanceconnection sections which meet all requirements.

    These sections provide installation flexibility combined with quick and simpleassembly.

    Further, the connections are made using torque bolts which provide both easeof installation (use of a standard spanner for tightening to 6 daN.m) and a visualcheck before energising.

    Direct connection to Trihal transformers and Prisma Plus & Okken switchboards.Supplied factory or panelbuilder assembled and tested to IEC 60439-1 and 2.Quick and simple connection of the busbar trunking to the interface.Reduced size.Joint block integrated into the interface.A sealing kit (rating dependent) must be ordered.

    Connection sectionsDescription

    Sealing kit

    Prisma Plus and Okken switchboardsFor fixed or draw-out incoming device, front or rear connection:

    Masterpact NW08 to NW40 or NT06 to NT16 circuit-breaker,Compact NS630b to NS1600 circuit-breaker.

    Possibility of switching the phases around.

    bb

    Prisma Plus switchboard

    Okken switchboard

    Canalis KTA

    Connections via interface to Prisma Plus, Okken and Trihal

  • 7/21/2019 Canalis KTA 800_4000A

    37/205

    DD202503

    7Schneider Electric

    Description

    Connection sectionsDescription

    France Transfo Trihal dry type transformersFor naturally ventilated or force ventilated transformers.Protection degree:

    IP00,IP31.

    Secondary voltage: 410 V

    15 mm adjustment in the 3 axes.

    bb

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    38/205

    DD202399

    DD21

    0777

    DD202502

    8 Schneider Electric

    Description

    Feed units - Type ERThey allow the busbar trunking to be connected to a switchboards busbar, or to theterminals of an oil immersed transformer, generator set, etc.

    They come complete with a mounting plate fitted:either directly to the roof of the switchboard,or via the intermediary of a protective cover.

    Vertical or horizontal incoming busbar trunking.

    bb

    Connection:either directly to the busbar,or by flexible bars and connection plates,or by braids,or by cables.

    ER feed units are supplied without a joint block.If the run has a feed unit at each end, an additional joint block must be ordered.

    bbbb

    bb

    Types ER N1/N2

    Connection sectionsDescription

    Canalis KTA

    Universal connections to switchboards and oil immersed transformers

    Types ER N3/N4 Types ER N5/N6 Type ER N7

  • 7/21/2019 Canalis KTA 800_4000A

    39/205

    DD20232

    1

    DD202325

    10276-03-d1

    10276-303-d4

    DD205623

    DD205624

    9Schneider Electric

    Description

    Protective covers - Types CS, CR, BCProtects the external part of the connection.

    Type CSHeight adaptable flexible protective cover adaptable for ER N1 to N6 feed unitswith a between centres distance of 115 mm.

    b

    Connection sectionsDescription

    For a vertical incomer - Types CR1 to CR3Made-to-measure rigid protective cover for ER N1 to N7 feed units.They are height adjustable by 50 mm.

    Type CR 1 for a horizontal incomer.b

    Types CR7 and CR8Protective covers for oil immersed transformers.Only for ER N1 to N6 feed units with a between centres distance of 150 or 170 mmdepending on the rating.

    Fit directly onto the BT series transformer tanks.

    Type CR7 for a vertical incomer.

    b

    v

    Type BCProtective cover for direct cable connection to ER N1 to N6 feed units with abetween centres distance of 115 mm.

    v

    Type CR8 for a horizontal incomer.v

    Canalis KTA

    Types CR2 and CR3 for a vertical incomer.b

  • 7/21/2019 Canalis KTA 800_4000A

    40/205

    DD202444

    DD202443

    DD202442

    DD202448

    DD20

    2447

    10 Schneider Electric

    Description

    Feed units - Type ELFor dry type transformers with the neutral between the phases.They allow optimum connection to the busbar trunking.

    The junction with the busbar trunking is achieved:either from the side,b

    Connection sectionsDescription

    They are of similar design to straight transport sections and can be installededgewise or flat.If installed flat, a set of angle brackets can be ordered.

    The following must be specified at the time of order:phase order,distance between phases (a 20 mm lateral adjustment can be made use of onsite).

    The link between the transformer terminals and the connection section is either byflexible bar connection plates or by braids.

    Type EL N1/N2

    or from the centre.b

    Type EL N3/N4 Type EL N5

    Canalis KTA

    Universal connections to dry type transformers

  • 7/21/2019 Canalis KTA 800_4000A

    41/205

    DD202343

    DD202346

    DD202342

    11Schneider Electric

    Description

    Protective covers - Type CR4 to CR6These protect the connections with an IP31 casing when connecting to atransformer.

    They are height adjustable by 50 mm.

    Type CR4Protective cover for EL N1 to N4 feed units.Edgewise assembly.

    b

    Connection sectionsDescription

    Type CR5Protective cover for EL N1 to N4 feed units.Flat assembly.

    b

    Type CR6Protective cover for EL N5 feed unit.Edgewise assembly.

    b

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    42/205

    DD202400

    DD202411

    DD202410

    DD202403

    DD202402

    DD202401

    DD202363

    DD202478

    DD210784

    12 Schneider Electric

    Description

    The conductors of ER N1 to N6 feed units are connected directly to the

    switchboard busbars.YB2 copper spacers are available to compensate differences in thickness betweenthe switchboard bars (10 mm) and the connection part(6 mm).

    Make-up of kit:8 x 2 mm thick copper spacers,16 off M12 x 60 mm bolts, class 8.8,16 contact washers,16 torque nuts,8 steel spacer plates.

    Order a set per feed unit whatever the rating.

    bbbbb

    The conductors of ER N1 to N6 feed units are connected via connection plates tothe switchboard busbars.

    The YC types are flexible bars made up of 5 copper sheets of 1 x 100 mm (500mm cross-section).The number of connection plates needed is proportional to the busbar trunkingrating.There are 3 types:

    YC1, uninsulated 600 mm long bar with 4 oblong holes at one end.The length of the holes at the switchboard side are to be adapted on-site.b

    Connection accessoriesDescription

    YC2, uninsulated bar, made-to-measure length of 250 to 600 mm with 4 oblongholes at each end, ready to use.b

    YC5, insulated 1000 mm long flexible bar, stripped at one end and with 4 oblongholes.The length of the holes at the switchboard side are to be adapted on-site.

    b

    Nuts and bolts

    The connection plates are fixed to the feed unit using the YB3 nut and bolt kit,made up of:

    16 off M12 x 60 mm bolts, class 8.8,16 contact washers16 torque nuts,8 steel spacer plates.

    ClampsYS1 clamps enable high short-circuit current levels to be withstood; only for barswith a 115 mm spacing.

    bbbb

    Canalis KTA

    Switchboard connection accessories using connection plates

    Accessories for direct connection to the switchboard

    InsulationA YF sheath is available to insulate the phases from one another.It can be fitted to the YC1 and YC2 connection plates once they have beenconnected.

  • 7/21/2019 Canalis KTA 800_4000A

    43/205

    DD

    202412

    DD202414

    DD202413

    DD202415

    DD20

    2450

    13Schneider Electric

    Description

    The feed unit conductors are connected to the transformer bars via connection

    plates or braids:connection plates, YC types, are flexible bars made up of 5 copper sheets of 1 x

    100 mm (500 mm cross-section).braids, YT type, are copper braids with a 600 mm cross-section.

    The number of connection plates needed is proportional to the busbar trunkingrating.

    Connection platesThe YC3 is an uninsulated bar with an expansion kink; it is 400 mm long and has 4holes at one end.They can be fitted to the transformer side:

    either using bar clamps (no drilling),or drilled and bolted (to be carried out on site).

    b

    b

    bb

    Connection accessoriesDescription

    YS2 and YS3 bar clamps enable connection without the need to drill the connectionplates.They allow height adjustment.

    Type YS2, bar clamps for 100 mm transformer connection terminals.Type YS3, bar clamps for 120 mm transformer connection terminals.

    Make-up of kit: 1 set of 8 parts.

    bb

    The YC4 is an uninsulated bar with an expansion kink; it is 400 mm long and has4 oblong holes at each end (ready to use).b

    BraidsType YT, 400 mm long insulated braid with 4 holes at each end.

    The connection plates and braids are fixed to the feed unit using the YB4 nut andbolt kit, made up of:

    16 off M12 x 80 mm bolts, class 8.8,16 contact washers,16 torque nuts,8 steel spacer plates.

    bbbb

    Canalis KTA

    Transformer connections - Types YC, YT

  • 7/21/2019 Canalis KTA 800_4000A

    44/205

    DD202372

    DD202

    484

    DD202486

    DD202485

    DD202369

    DD202368

    DD202496

    DD202374

    14 Schneider Electric

    Description

    Supports and fixings

    The ZA types allow the busbar trunking to be fixed and adjusted along its length, as

    well as absorbing its movements.

    Supports for horizontal sectionsType ZA1, to support edgewise busbar trunking only, consists of a steel angle

    bracket and 2 x 1.2 metre threaded M10 rods.The maximum distance between supports is:

    3 metres for edgewise busbar trunking,2 metres for flat busbar trunking.

    See installation precautions.

    b

    vv

    Fixing bracketThe ZA3 keeps the busbar trunking in place on its support, without blocking it, inorder to allow expansion movements.

    The ZA5 is for supporting vertical sections.They fix sections of a vertical run to the buildings structure.This type of fixing support has the following advantages:

    assembly:to a wall,to a wall bracket,to the floor,height and depth adjustment,spring adjustment to ensure distribution of the load at each floor,avoids the transmission of building forces to the busbar trunking (expansion and

    vibration).

    bvvvbbb

    Description

    Type ZA4, to support the busbar trunking from the top.These supports are needed to fix edgewise EL N1 to N4 feed units for dry type

    transformers.

    bb

    For KTA08 to KTA16. For KTA20 to KTA40.

    To a wall. To a wall bracket. To the floor.

    Canalis KTA

    Horizontal supports

    Vertical supports

  • 7/21/2019 Canalis KTA 800_4000A

    45/205K9AE13000

    DD210466

    DD202012

    DD210275

    DD210276

    2 Schneider Electric

    Description

    Tap-off units

    The tap-off units are used to instantly connect loads or secondary runs, and complywith installation standards and regulations, whatever the earthing system (TT, TNS,TNC or IT).

    When off-load, they can be plugged-on and off and be operated whilst live.Plugging-on and plugging-off automatically opens and closes the tap-off point.

    Description

    No live part is accessible with the door open. The protection degree is IPXXB(finger protection).

    They are IP55 by construction (no accessory is required).

    Safety and operationFuse and modular switchgear tap-off units (AC22 to AC20) are isolated as soon asthe tap-off unit door is opened.This isolating operation must only be carried out off-load.For circuit breaker tap-off units, there are safety mechanisms to prevent:

    the tap-off unit being plugged-on and plugged-off with the tap-off unit doorclosed,

    the door being closed if the tap-off unit has not been locked onto the busbartrunking,

    access to the electrical equipment and connection terminals when live,the door being opened in the ON position for tap-off units fitted with a Compact

    NS or NG circuit breaker.

    These tap-off units can be fitted with accessories such as:door early break contacts,adapter for lead sealing,etc.

    The sheet steel tap-off units are fitted with a carrying handle.

    Characteristics of tap-off units up to 125 A

    Colour:white (RAL 9001) body and carrying handles,transparent green door (similar design to the Kaedra enclosures).Material: self-extinguishing, halogen-free insulating plastic (fire resistant and very

    high temperature withstand).Other characteristics: cable gland drilling zone, stainless steel screws and the doorcan be lead sealed.

    Characteristics of tap-off units from 160 to 400 AColour:white (RAL 9001) body,black carrying handles (RAL 9005),100 % polyester paint.Material: galvanized sheet steel.

    Other characteristics:unhingeable door (120 opening hinges),vertically bevelled polyurethane seals with a double fold for increased rigidity

    (similar design to the Sarel Spatial 3D enclosures),25 mm grill type gland plates for a maximum access area.

    b

    b

    bb

    bbb

    bvvb

    bvvvb

    bb

    b

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    46/205K9AE13000

    DD210465

    DD210461

    DD202154

    DD210454

    3Schneider Electric

    Description

    Plug-on tap-off units for circuitbreakers

    Isolator tap-off units for modular switchgearMost 18 mm Multi 9 modular devices can be fitted into these tap-off units.They have a window on the front face for switchgear control and visualisation.

    A transparent shutter ensures the window can be sealed.Two tap-off ratings are available:

    63 A nominal current for 8 modules,125 A nominal current for 12 modules (accepts C120 and NG125 circuit

    breakers).

    bb

    Tap-off units for NG type modular switchgearThese tap-off units are fitted with a DIN rail and upstream connections for 18 mmwide modular devices.The switchgear is operated via a rotary handle which prevents door opening when

    the circuit breaker is in the ON position.Nominal current: 160 A for a 13-module capacity (accepts NG125 or NG160 fittedwith a Vigi unit).

    Isolator tap-off units for Compact NS circuit breakersThese tap-off units are fitted with mounting plates and upstream connections forfixed, front-connected 160 to 400 A Compact NS circuit breakers (N, H or L version)with a rotary handle.

    The 400 A tap-off units can only be fitted onto straight lengths with a rating greaterthan 400 A.

    For plug-on circuit breakers, Vigi units, etc, please consult your Schneider Electriccontact.

    Measurement and metering isolator tap-off unitsThese tap-off units allow sub-metering to re-allocate power consumption costs byconsumer and to monitor installations by, for example, following run load levels.The values measured using the Compact NS TI unit are sent to the measurementunit which then sends the information to a central unit via a bus.(See Measurement and metering).

    They are fitted with:

    a mounting plate for a Compact NS 250 or 400 A circuit breaker with anextended rotary handle and a Compact NS current transformer module (TI unit),a DIN rail for installing a Powerlogic PM810 measurement unit, a set of

    terminals, etc.

    In severe operating conditions (> 40C ambient temperature), we recommend theuse of a PM810 without display.

    b

    b

    Description

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    47/205K9AE13000

    DD210472

    DD202012

    DD210466

    4 Schneider Electric

    Description

    These tap-off units provide the tap-offs with fuse protection (fuses not supplied).They can only be fitted to a horizontally mounted busbar trunking.

    Plastic tap-off unitsFitted with carriers for:

    50 to 100 A cylindrical NF fuses,25 to 63 A DIN screwed fuses,100 A DIN blade fuses,32 to 80 A BS screwed fuses.

    bbbb

    Plug-on tap-off units for fusesDescription

    Steel tap-off unitsFitted with carriers for:

    160 to 400 A NF / DIN blade fuses,160 A BS screwed fuses.

    bb

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    48/205K9AE13000

    DD202451

    DD202497

    5Schneider Electric

    Description

    Fixed tap-off units for circuitbreakers

    Steel tap-off unitsThese tap-off units are used to supply loads or secondary runs (e.g. medium powerdistribution using Canalis KS).They are fitted to specific EB type straight lengths.They comply with installation standards and regulations, whatever the earthingsystem (TT, IT, TNS or TNC):

    tap-off units fitted with a mounting plate for Compact NS400/1000 A, 3 or 4 P:fixed device,front connections,

    extended rotary handle.2 models:

    Compact NS400/630 A, connection capacity:3 x 300 mm2cables for the phases and neutral (hole diameter = 15 mm),150 mm for the PE,Compact NS800/1000 A, connection capacity:4 x 300 mm2cables for the phases and neutral (hole diameter = 15 mm),200 mm2for the PE (cable clamp).

    The standard tap-off unit is IP54.

    bvv

    v

    bvvbvv

    Characteristics of tap-off units from 400 to 1000 AColour:white (RAL 9001) body,Material: galvanized sheet steel.Other characteristics:the cables exit laterally through 2 aluminium plates (to be drilled by the

    installation contractor),cabling space can be increased by using the cable box supplied with the tap-offunit,

    the door is fixed using 6 captive M6 screws and can be completely removed tofacilitate cabling.

    bvbbv

    v

    v

    Description

    Safety and operationThe electrical connection is made by plugging-on the tap-off unit into dedicated tap-off point whilst the busbar trunking is de-energised (plugging-off the unit must also

    be done with the busbar trunking de-energised).The connection is mechanically tightened using a one-use torque bolt (10 daN.m).A mechanical foolproof system avoids the risk of incorrect assembly.The door can only be opened once the load has been isolated (rotary handle).The bolt can only be tightened or untightened with the door open.No live part is accessible with the door open, protection degree IP2X.

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    49/205

  • 7/21/2019 Canalis KTA 800_4000A

    50/205K9AE20000 Schneider Electric 3

    C

    ataloguenumbers

    D

    imensions

    Catalogue-number coding

    K T pp p p p p p p ppFour digits indicationg

    the rating of the trunking.Important : for an 800 A rating,indicate KTA0800.

    b

    Two letters identifying the type of component.

    Type Code

    Adjustable straight length AJCable box BCBolt-on tap-off unit CBEdgewise and flat zed CPRigid protective cover CRFlexible protective cover CSExpansion unit DB

    Distribution length for bolt-on tap-off units EBDistribution length for plug-in tap-off unts EDFeed unit for dry-type transformers ELFeed unit ERFeeder length ETEnd cover FAEdgewise elbow LCFlat elbow LPTap-off unit with protective device PLTap-off unit with isolator SLEdgewise tee TCNeutral crossover TNPhase crossover TPSealing kit TTConnection device YAConnection torque nut kit YB

    Flexible bar YCBracket YEInsulating sheath YFBar supports YSBraids YTSupports and fixing devices ZAEdgewise zed ZCFlat zed ZP

    b

    One digit indicating the trunkingpolarity

    Polarity Code

    3L + PE 3

    3L + N + PE 43L + N + PER(1) 7(1) PER = oversized PE.

    b

    Variable number of alphanumericcharacters indicating characteristicsspecific to the component.See the section dealing with the givencomponent.

    b

    Trunking cross section

    Rating (A) 800 1000 1250 1600 2000 2500 3200 4000

    Number of bar jointing bolts 1 1 1 2 2 2 4 4

    Bar cross-section (mm) 70 x 6 100 x 6 120 x 6 160 x 6 200 x 6 2 x (120 x 6) 2 x (160 x 6) 2 x (200 x 6)

    Trunking height H (mm)

    D

    D202180

    DD202181

    Holes for connections (mm)

    DD202182

    Y 230 230 230 350 350 350 510 510

    Catalogue-number composition

    One letter designating the material.

    Type Code

    Aluminium A

    Non conducting B

    b

    Catalogue numbers anddimensions

    Canalis KTA

  • 7/21/2019 Canalis KTA 800_4000A

    51/205K9AE21010

    DD210794

    DD210795

    DD210796

    DD210797

    2 Schneider Electric

    D

    imensions

    Catalogue numbers anddimensions

    Straight feeder lengths

    Run componentsIP55

    Type Length L(mm)

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Fixed 4000 KTAppppE T34 0 KTAppppE T44 0 KTAppppET740

    2000 KTAppppE T32 0 KTAppppE T42 0 KTAppppET720Made tomeasure

    500 to 1500 KTAppppET31A KTAppppET41A KTAppppET71A

    1501 to 1999 KTAppppET32B KTAppppET42B KTAppppET72B

    2001 to 2500 KTAppppET32C KTAppppET42C KTAppppET72C

    2501 to 3000 KTAppppET33D KTAppppET43D KTAppppET73D

    KTAppppETppp

    Ordering

    Complete the catalogue number by replacing pppp by the rating.

    Important: for the 800 A rating, add a 0 in the catalogue number : KTA0800,add the dimensions of the selected component as a technical comment

    Example:the catalogue number of an 800 A feeder length, 3L + N + PE,2450 mm long, is:KTA0800ET42C, L = 2450

    bb

    Rating

    (1) See the Trunking cross-sectiontable opposite.

    Canalis KTA

    Adjustable straight lenghts

    Type Length L(mm)

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Adjustable 1300 (basic)Adjustable: 200

    KTAppppAJ31 0 KTAppppAJ41 0 KTAppppAJ710

    KTAppppAJp10

    (1) See the Trunking cross-sectiontable opposite.

    Table of dimensions

    Rating (A) Dimension A (mm) Weight (kg)

    800(2) 180 52.001000 200 68.001250 240 78.001600 285 102.002000 325 121.002500 405 141.003200 495 179.004000 695 218.00(2) for the 800 A rating, indicate KTA0800 .

    KTAppppETppp

    KTAppppAJp10

  • 7/21/2019 Canalis KTA 800_4000A

    52/205K9AE21010

    DD2

    10798

    DD210799

    DD210800

    3Schneider Electric

    C

    ataloguenumbers

    D

    imensions

    Catalogue numbers anddimensions

    Run componentsIP55

    Straight lengths with plug-in tap-off units

    Type Length

    L (mm)

    Number of

    tap-offs

    Cat. no.

    Fixed 4000 3 KTAppppED340 KTAppppED440 KTAppppED740

    2000 3 KTAppppED320 KTAppppED420 KTAppppED720

    KTAppppEDp40

    Trunking cross-section

    Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000

    Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38

    3L + N + PE 13 16 18 22 26 30 37 45

    3L + N + PER 15 19 21 26 31 36 46 56

    Height H (mm)Width W (mm)

    DD

    202180

    DD210867

    (1) Important: for the 800 A rating, indicate KTA0800 .

    (1) See the Trunking cross-sectiontable below.

    Canalis KTA

    KTAppppEDp20

    KTAppppEDp20

    KTAppppEDp40

  • 7/21/2019 Canalis KTA 800_4000A

    53/205K9AE21010

    DD2

    10801

    DD210802

    DD210803

    DD210766

    4 Schneider Electric

    D

    imensions

    Straight lengths with bolt-on tap-off units

    Type Length

    L (mm)

    Number of

    tap-offs

    Cat. no.

    Fixed 4000 2 KTAppppE B3 40 KTAppppE B4 40 KTAppppEB740

    2000 1 KTAppppE B3 20 KTAppppE B4 20 KTAppppEB720

    KTAppppEBp40

    (1) See the Trunking cross-sectiontable below.

    KTAppppEBp20

    KTAppppEBp20

    KTAppppEBp40

    Trunking cross-section

    Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000

    Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38

    3L + N + PE 13 16 18 22 26 30 37 45

    3L + N + PER 15 19 21 26 31 36 46 56

    Height H (mm)Width W (mm)

    DD

    202180

    DD210867

    (1) Important: for the 800 A rating, indicate KTA0800 .

    Catalogue numbers anddimensions

    Canalis KTA

    Run componentsIP55

  • 7/21/2019 Canalis KTA 800_4000A

    54/205K9AE21010

    5Schneider Electric

    C

    ataloguenumbers

    D

    imensions

  • 7/21/2019 Canalis KTA 800_4000A

    55/205K9AE21020

    DD210805

    DD210806

    DD210807

    DD210808

    DD210809

    DD210810

    2 Schneider Electric

    D

    imensions

    Catalogue numbers anddimensions

    Straight expansion unit

    Additional run componentsIP55

    Type Length L(mm)

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Fixed 1000 KTAppppDB310 KTAppppDB410 KTAppppDB710

    KTAppppDBp10

    Ordering

    Complete the catalogue number by replacing pppp by the rating.

    Important: for the 800 A rating, add a 0 in the catalogue number : KTA0800,add the dimensions of the selected component as a technical comment

    Example:the catalogue number of a 1250 A neutral crossover length,3L + N + PE, 1000 mm long, is:KTA1250TN410

    bb

    Rating

    (1) See the Trunking cross-sectiontable opposite.

    Canalis KTA

    Neutral crossover length

    Type Length L(mm)

    Cat. no.

    3L + N + PE

    Fixed 1000 KTAppppTN410

    KTAppppTNp10

    (1) See the Trunking cross-sectiontable opposite.

    Phase crossover length

    Type Length L(mm)

    Cat. no.

    3L + N + PE

    Fixed 1000 KTAppppTP410

    KTAppppTPp10

    (1) See the Trunking cross-sectiontable opposite.

    KTAppppDBp10

    KTAppppTNp10

    KTAppppTPp10

  • 7/21/2019 Canalis KTA 800_4000A

    56/205K9AE21020

    DD2

    10811

    DD210812

    DD210

    813

    DD210814

    DD210868

    3Schneider Electric

    C

    ataloguenumbers

    D

    imensions

    Catalogue numbers anddimensions

    Additional run componentsIP55

    Additional jointing units

    Type Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Jointing unit KTAppppYA3 KTAppppYA4 KTAppppYA4

    KTAppppYAp

    (1) See the Trunking cross-sectiontable below.

    Canalis KTA

    End covers

    Type Rating of thetrunking (A)

    Height H of thetrunking (mm)

    Cat. no.

    End cover 800(1) 74 KTB0074FA1000 104 KTB0104FA1250 124 KTB0124FA1600 164 KTB0164FA2000 204 KTB0204FA2500 244 KTB0244FA3200 324 KTB0324FA4000 404 KTB0404FA

    KTB0pppFA

    KTAppppYAp

    KTB0pppFA

    Trunking cross-section

    Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000

    Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38

    3L + N + PE 13 16 18 22 26 30 37 45

    3L + N + PER 15 19 21 26 31 36 46 56

    Height H (mm)Width W (mm)

    DD

    202180

    DD210867

    (1) Important: for the 800 A rating, indicate KTA0800 .

    (1) For the 800 A rating, indicate KTA0800 .

    (2) See the Trunking cross-sectiontable below.

  • 7/21/2019 Canalis KTA 800_4000A

    57/205K9AE22010

    DD210822

    DD210824

    DD210815

    DD210816

    DD210821

    DD210823

    2 Schneider Electric

    D

    imensions

    Catalogue numbers anddimensions

    Elbow components for changingdirectionIP55

    Flat elbows

    Type Position ofneutral

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Fixed N1 KTAppppLP3A1 KTAppppLP4A1 KTAppppLP7A1

    N2 KTAppppLP3A2 KTAppppLP4A2 KTAppppLP7A2Made tomeasure

    N1 KTAppppLP3B1 KTAppppLP4B1 KTAppppLP7B1

    N2 KTAppppLP3B2 KTAppppLP4B2 KTAppppLP7B2

    KTAppppLPppp

    Ordering

    Complete the catalogue number by replacing pppp by the rating.

    Important: for the 800 A rating, add a 0 in the catalogue number : KTA0800,add the dimensions of the selected component as a technical comment

    Example:the catalogue number of a 2000 A flat elbow, N1, 3L + N + PE withdimensions A = 300 mm and B = 650 mm is:KTA2000LP4B1, A = 300, B = 650.

    bb

    Rating

    (1) See the Trunking cross-sectiontable opposite.

    Dimensions

    Type Rating (A) Dimensions (mm)

    A B

    Fixed All 300 300Made tomeasure(2)

    All 300 301 to 799301 to 799 300

    (2) Only one llmb may be made to measure.

    Canalis KTA

    Flat elbows with made to measure angles

    Type Position ofneutral

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Made tomeasure angle

    N1 KTAppppLP3C1 KTAppppLP4C1 KTAppppLP7C1

    N2 KTAppppLP3C2 KTAppppLP4C2 KTAppppLP7C2

    KTAppppLPpCp

    (1) See the Trunking cross-sectiontable opposite.

    Dimensions

    Type Rating (A) Dimensions (mm)

    A B W

    Made to measure All 300 300 91 to 179

    KTAppppLPpp1

    KTAppppLPpp2

    KTAppppLPpC1

    KTAppppLPpC2

  • 7/21/2019 Canalis KTA 800_4000A

    58/205K9AE22010

    DD2

    10825

    DD210826

    3Schneider Electric

    C

    ataloguenumbers

    D

    imensions

    Catalogue numbers anddimensions

    Elbow components for changingdirectionIP55

    Edgewise elbows

    Type Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Fixed KTAppppLC3A KTAppppLC4A KTAppppLC7A

    Made to measure KTAppppLC3B KTAppppLC4B KTAppppLC7B

    KTAppppLCpp

    (1) See the Trunking cross-sectiontable below.

    Dimensions

    Type Rating (A) Dimensions (mm)

    A BFixed 800(2) 275 275

    1000 290 2901250 300 3001600 320 3202000 340 3402500 360 360

    3200 400 4004000 440 440Made tomeasure(3)

    800(2) 276 to 774 275275 276 to 774

    1000 291 to 789 290290 291 to 789

    1250 301 to 799 300300 301 to 799

    1600 321 to 819 320320 321 to 819

    2000 341 to 839 340340 341 to 839

    2500 361 to 859 360360 361 to 859

    3200 401 to 899 400400 401 to 899

    4000 441 to 939 440440 441 to 939

    (2) For the 800 A rating, indicate KTA0800 .

    (3) Only one llmb may be made to measure.

    Canalis KTA

    KTAppppLCpp

    Trunking cross-section

    Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000

    Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38

    3L + N + PE 13 16 18 22 26 30 37 45

    3L + N + PER 15 19 21 26 31 36 46 56

    Height H (mm)Width W (mm)

    DD

    202180

    DD210867

    (1) Important: for the 800 A rating, indicate KTA0800 .

  • 7/21/2019 Canalis KTA 800_4000A

    59/205K9AE22010

    DD2

    10819

    DD210820

    4 Schneider Electric

    D

    imensions

    Catalogue numbers anddimensions

    Canalis KTA

    Elbow components for changingdirectionIP55

    Edgewise tee

    Type Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Fixed KTAppppTC3 KTAppppTC4 KTAppppTC7

    KTAppppTCp

    KTAppppTCp

    (1) See the Trunking cross-sectiontable below.

    Dimensions

    Type Rating (A) Dimensions (mm)

    A B CFixed 800(2) 275 275 275

    1000 290 290 2901250 300 300 3001600 320 320 3202000 340 340 3402500 360 360 3603200 400 400 4004000 440 440 440

    (2) For the 800 A rating, indicate KTA0800.

    Trunking cross-section

    Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000

    Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38

    3L + N + PE 13 16 18 22 26 30 37 45

    3L + N + PER 15 19 21 26 31 36 46 56

    Height H (mm)Width W (mm)

    DD

    202180

    DD210867

    (1) Important: for the 800 A rating, indicate KTA0800.

  • 7/21/2019 Canalis KTA 800_4000A

    60/205K9AE22010 5Schneider Electric

    C

    ataloguenumbers

    D

    imensions

  • 7/21/2019 Canalis KTA 800_4000A

    61/205K9AE22020

    DD202183

    DD202184

    DD202186

    DD202185

    DD210827

    2 Schneider Electric

    D

    imensions

    Catalogue numbers anddimensions

    Zed components for changingdirectionIP55

    Edgewise zed units

    Type Position ofneutral

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Made tomeasure

    N1 KTAppppZC31 KTAppppZC41 KTAppppZC71

    N2 KTAppppZC32 KTAppppZC42 KTAppppZC72

    KTAppppZCpp

    Flat zed units

    Type Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Made to measure KTAppppZP3 KTAppppZP4 KTAppppZP7

    KTAppppZPp

    Ordering

    Complete the catalogue number by replacing pppp by the rating.

    Important: for the 800 A rating, add a 0 in the catalogue number : KTA0800,add the dimensions of the selected component as a technical comment

    Example:the catalogue number of a 1600 A edgewise zed unit, N2, 3L + N + PEwith dimensions A = 300 mm, B = 450 mm, C = 300 mm is:KTA1600ZC42, A = 300, B = 450, C = 300.

    bb

    Rating

    (1) See the Trunking cross-sectiontable opposite.

    Dimensions

    Rating (A) Dimensions (mm)

    A B C

    All 300 130 to 599 300

    (1) See the Trunking cross-sectiontable opposite.

    Dimensions

    Rating (A) Dimensions (mm)

    A B C

    800(2) 275 90 to 549 2751000 290 90 to 579 2901250 300 90 to 599 3001600 320 90 to 639 3202000 340 90 to 679 3402500 360 90 to 719 3603200 400 90 to 799 4004000 440 90 to 879 440

    KTAppppZPp

    KTAppppZCp1

    KTAppppZCp2

    Canalis KTA

    (2) For the 800 A rating,

    indicate KTA0800 .

  • 7/21/2019 Canalis KTA 800_4000A

    62/205K9AE22020

    DD2

    02187

    DD202188

    DD210828

    DD210829

    DD210830

    DD202367

    3Schneider Electric

    C

    ataloguenumbers

    D

    imensions

    Catalogue numbers anddimensions

    Zed components for changingdirectionIP55

    Edgewise and flat zed units

    Type Position of

    neutral

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Made tomeasure

    N1 KTAppppCP31 KTAppppCP41 KTAppppCP71

    N2 KTAppppCP32 KTAppppCP42 KTAppppCP72

    N3 KTAppppCP33 KTAppppCP43 KTAppppCP73

    N4 KTAppppCP34 KTAppppCP44 KTAppppCP74

    (1) See the Trunking cross-sectiontable below.(2) For the 800 A rating,

    indicate KTA0800 .

    Canalis KTA

    KTAppppCPp1

    KTAppppCPp2

    KTAppppCPp3

    KTAppppCPp4

    Trunking cross-section

    Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000

    Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38

    3L + N + PE 13 16 18 22 26 30 37 45

    3L + N + PER 15 19 21 26 31 36 46 56

    Height H (mm)Width W (mm)

    DD

    202180

    DD210867

    (1) Important: for the 800 A rating, indicate KTA0800 .

    KTAppppCPp3and KTAppppCPp4

    KTAppppCPp1and KTAppppCPp2

    Dimensions

    Rating (A) Dimensions (mm)

    A B C

    800(2)

    300 195 to 574 2751000 300 210 to 589 2901250 300 220 to 599 3001600 300 240 to 619 3202000 300 260 to 639 3402500 300 280 to 659 3603200 300 320 to 699 4004000 300 360 to 739 440

  • 7/21/2019 Canalis KTA 800_4000A

    63/205K9AE23000

    DD2

    02304

    DD20230

    6

    DD202305

    DD202307

    2 Schneider Electric

    Ca

    taloguenumbers

    Catalogue numbers Canalis interfaces for Prisma PlusLV switchboard

    Interfaces for Masterpact NW circuit breakers

    Circuit

    breaker

    Type of circuit

    breaker

    Number of

    poles

    Connection Cat. no.

    Top direct Rear

    NW08 / 16 Fixed or drawout 3 b b 04715

    4 b b 04716

    NW20 / 25 Fixed or drawout 3 b b 04725

    4 b b 04726

    NW32 Fixed or drawout 3 b b 04735

    4 b b 04736

    NW40 Fixed or drawout 3 b 04737

    4 b 04738

    For the position in the switchboard, see the Installation guide.

    For connection to the PER, consult your sales agency.

    Number of modules required in the switchboard

    Circuit breaker Connection Type of circuit

    breaker

    Number of vertical

    modules

    (1)

    NW08 / 16 Top direct Fixed or drawout 27

    Rear Fixed 16

    Drawout 17

    NW20 / 25 Top direct Fixed or drawout 28

    Rear Fixed 16

    Drawout 17

    NW32 Top direct or rear Fixed or drawout 28

    NW40 Rear Fixed or drawout 36

    (1) 1 module = 50 mm.

    Canalis KTA

    Interfaces for Masterpact NT and Compact NS circuit breakers

    Masterpact NT

    Circuitbreaker

    Type of circuitbreaker

    Number ofpoles

    Connection Cat. no.

    Top direct Rear

    NT06 / 12 Fixed or drawout 3 b b 04703

    4 b b 04704

    NT16 Fixed or drawout 3 b 04703

    4 b 04704

    For the position in the switchboard, see the Installation guide.

    For connection to the PER, consult your sales agency.

    Compact NS

    Circuitbreaker

    Type of circuitbreaker

    Number ofpoles

    Connection Cat. no.

    Top direct Rear

    NS630b / 1250 Fixed or drawout 3 b b 04703

    4 b b 04704

    NS1600 Fixed or drawout 3 b 04703

    4 b 04704

    For the position in the switchboard, see the Installation guide.

    For connection to the PER, consult your sales agency.

    Number of modules required in the switchboard

    Circuit breaker Connection Type of circuitbreaker

    Number of verticalmodules(1)

    NT06 / 12NS630b / 1250

    Top direct Fixed 17

    Drawout 18

    Rear Fixed or drawout 16

    NT16NS1600

    Rear Fixed or drawout 16

    (1) 1 module = 50 mm.

    Top direct connection

    Rear connection

    Top direct connection

    Rear connection

  • 7/21/2019 Canalis KTA 800_4000A

    64/205K9AE23000

    DD2

    02308

    DD202309

    3Schneider Electric

    Ca

    taloguenumbers

    Catalogue numbers

    Canalis KTA

    Canalis interfaces for Prisma PlusLV switchboard

    Interface supports and protection covers

    Masterpact NW

    Circuitbreaker

    Type of circuitbreaker

    Connection Supports Terminalextensionbar supports

    Cover

    NW08 / 32 Fixed ordrawout

    Top direct 03561 3 x 04694 04871 + 04861

    Rear 03561 2 x 04694 04871 + 04863

    NW40 Fixed ordrawout

    Top direct 03561 - 04871 + 04861

    Rear 03561 - 04871 + 04863

    Masterpact NT

    Circuitbreaker

    Type ofcircuitbreaker

    Numberof poles

    Connection Supports Canalis /circuitbreakerconnection

    Cover

    NT06 / 12 Fixed ordrawout

    3P Top direct 03561 04712 04871 + 04852

    Rear 03561 04713 04871 + 04853

    4P Top direct 03561 04712 04871 + 04852Rear 03561 04714 04871 + 04853

    NT16 Fixed ordrawout

    3P Rear 03561 04713 04871 + 04854

    4P Rear 03561 04714 04871 + 04854

    Compact NS

    Circuitbreaker

    Type ofcircuitbreaker

    Numberof poles

    Connection Supports Canalis /circuitbreakerconnection

    Cover

    NS630b /1250

    Fixed 3P Top direct 03561 04712 04871 + 04851

    4P Top direct 03561 04712 04871 + 04851

    Rear 03561 04714 04871 + 04853

    Drawout 3P Top direct 03561 04711 04871 + 04852

    Rear 03561 04713 04871 + 04854

    4P Top direct 03561 04712 04871 + 04852

    Rear 03561 04714 04871 + 04854

    NS1600 Fixed 3P Rear 03561 04713 04871 + 04853

    4P Rear 03561 04714 04871 + 04853

    Drawout 3P Rear 03561 04713 04871 + 04854

    4P Rear 03561 04714 04871 + 0485403561

    04711

    047120471304714

    Arc-chute covers

    Circuit breaker Type of circuit breaker Number of poles Cat. no.

    Masterpact NT Fixed 3P 47335

    4P 47336

    Compact NS Fixed 3P 33596

    4P 33597

  • 7/21/2019 Canalis KTA 800_4000A

    65/205K9AE23000

    DD2

    02310

    DD20231

    2

    DD202311

    DD2

    02313

    4 Schneider Electric

    Ca

    taloguenumbers

    Catalogue numbers Canalis interfaces for OkkenLV switchboard

    Interfaces for Masterpact NW circuit breakers

    Fitting the interface does not change switchboard modularity as fixed by the devices.

    Circuitbreaker

    Type of circuitbreaker

    Number ofpoles

    Connection Cat. no.

    Top direct Rear

    NW08 / 16 Drawout 3 b 87811

    b 87821

    4 b 87812

    b 87822

    NW20 / 25 Drawout 3 b 87813

    b 87823

    4 b 87814

    b 87824

    NW32 Drawout 3 b 87815

    b 87825

    4 b 87816

    b 87826NW40 Drawout 3 b 87817

    b 87827

    4 b 87818

    b 87828

    For the position in the switchboard, see the Installation guide.

    For connection to the PER, consult your sales agency.

    Canalis KTA

    Interfaces forMasterpact NT circuit breakers

    Fitting the interface does not change switchboard modularity as fixed by the devices.

    Circuitbreaker

    Type of circuitbreaker

    Number ofpoles

    Connection Cat. no.

    Top direct Rear

    NT08 / 16 Drawout 3 b 87811

    b 87821

    4 b 87812

    b 87822

    For the position in the switchboard, see the Installation guide.

    For connection to the PER, consult your sales agency.

    Interface supports

    Circuit breaker Type of circuit breaker Connection Cat. no.

    NW08 / 40NT08 / 16

    Drawout Top direct 87800

    NW08 / 32(1)

    NT08 / 16Drawout Rear 87801

    (1) For rear connection of the interface to a Masterpact NW40 circuit breaker, the supports are

    supplied with the interface.

    Top direct connection (RDH)

    Rear connection (RAR)

    Top direct connection (RDH)

    Rear connection (RAR)

  • 7/21/2019 Canalis KTA 800_4000A

    66/205K9AE23000

    DD2

    02314

    5Schneider Electric

    Ca

    taloguenumbers

    Catalogue numbers

    Canalis KTA

    Sealing kitsIP55

    Sealing kits for switchboard and Trihal transformer roofs with interface

    Type Rating of the

    trunking (A)

    Height H of the

    trunking (mm)

    Cat. no.

    Sealing kit 800 74 KTB0074TT01

    1000 104 KTB0104TT01

    1250 124 KTB0124TT01

    1600 164 KTB0164TT01

    2000 204 KTB0204TT01

    2500 244 KTB0244TT01

    3200 324 KTB0324TT01

    4000 404 KTB0404TT01

    KTB0pppTT01

  • 7/21/2019 Canalis KTA 800_4000A

    67/205K9AE24010

    DD210831

    DD210832

    2 Schneider Electric

    Dimensions

    Catalogue numbers anddimensions

    Feed units for switchboards andoil immersed transformersIP55

    Straight feed units

    Type Position ofneutral

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Fixed N1 KTAppppER31 KTAppppER41 KTAppppER71

    Made to measure N2 KTAppppER32 KTAppppER42 KTAppppER72

    KTAppppERp1, KTAppppERp2

    To order

    Complete the catalogue number by replacing pppp by the rating.

    Important: in the catalogue number for the 800 A rating, add a 0: KTA0800,add the dimensions of the selected unit as a technical comment.

    Example:the catalogue number of a 1250 A made to measure end feed unit, N2,3L + N + PE, 235 mm long and with between centres J, K and M = 170 mm, is:KTA1250ER42, A = 235, J = 170, K = 170 and M = 170.

    bb

    Rating

    (1) See the Trunking cross-sectiontable opposite.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.

    Table of dimensions

    Rating (A) Neutral Dimensions (mm)

    A J, K, M Y800(3)to 1250 N1 235 115 230

    N2 235 to 534 80 to 250 2301600 to 2500 N1 235 115 350

    N2 235 to 534 80 to 250 3503200 to 4000 N1 235 115 510

    N2 235 to 534 80 to 250 510(3) For the 800 A rating, indicate KTA0800 .

    KTAppppERp1KTAppppERp2

    Canalis KTA

    Dimensions of connection pads

    Rating (A) 800 1000 1250 1600 2000 2500 3200 4000

    Drilling for connection (mm)

    DD202182

  • 7/21/2019 Canalis KTA 800_4000A

    68/205K9AE24010

    DD2

    10833

    DD210835

    DD210834

    DD210836

    3Schneider Electric

    C

    ataloguenumbers

    D

    imensions

    Flat elbow feed units

    Type Position of

    neutral

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Made to measure N3 KTAppppER33 KTAppppER43 KTAppppER73

    N4 KTAppppER34 KTAppppER44 KTAppppER74

    KTAppppERp3

    (1) See the Trunking cross-sectiontable below.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.

    Tableau of dimensions

    Rating (A) Neutral Dimensions (mm)

    A B J, K, M Y800(3)to 1250 N3, N4 200 to 534 300 80 to 250 2301600 to 2500 N3, N4 200 to 534 300 80 to 250 3503200 to 4000 N3, N4 200 to 534 300 80 to 250 510(3) For the 800 A rating, indicate KTA0800 .

    KTAppppERp3

    KTAppppERp4

    Catalogue numbers anddimensions

    Canalis KTA

    Feed units for switchboards andoil immersed transformersIP55

    Cut-out drawing for feed units placed directly on the device roof

    Table of dimensions

    Rating (A) Dimensions (mm)

    Y U V800(1)to 1250 230 K / 2 + J + 80 K / 2 + M + 801600 to 2500 350 K / 2 + J + 80 K / 2 + M + 803200 to 4000 510 K / 2 + J + 80 K / 2 + M + 80(1) For the 800 A rating, indicate KTA0800 .

    KTAppppERp4

    Trunking cross-section

    Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000

    Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38

    3L + N + PE 13 16 18 22 26 30 37 45

    3L + N + PER 15 19 21 26 31 36 46 56

    Height H (mm)Width W (mm)

    DD

    202180

    DD210867

    (1) Important: for the 800 A rating, indicate KTA0800 .

  • 7/21/2019 Canalis KTA 800_4000A

    69/205K9AE24010

    DD210839

    DD2

    10837

    DD210838

    DD210836

    4 Schneider Electric

    Dimensions

    Edgewise elbow feed units

    Type Position of

    neutral

    Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Made to measure N5 KTAppppER35 KTAppppER45 KTAppppER75

    N6 KTAppppER36 KTAppppER46 KTAppppER76

    KTAppppERp5

    KTAppppERp5

    KTAppppERp6

    (1) See the Trunking cross-sectiontable opposite.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.

    Table of dimensions

    Rating (A) Neutral Dimensions (mm)

    A B J, K, M Y800(3) N5, N6 175 to 509 275 80 to 250 2301000 N5, N6 190 to 524 290 80 to 250 2301250 N5, N6 200 to 534 300 80 to 250 2301600 N5, N6 220 to 554 320 80 to 250 3502000 N5, N6 240 to 574 340 80 to 250 3502500 N5, N6 260 to 594 360 80 to 250 3503200 N5, N6 300 to 634 400 80 to 250 5104000 N5, N6 340 to 674 440 80 to 250 510(3) For the 800 A rating, indicate KTA0800 .

    Cut-out drawing for feed units placed directly on the device

    Table of dimensions

    Rating (A) Dimensions (mm)

    Y U V

    800(1)to 1250 230 K / 2 + J + 80 K / 2 + M + 801600 to 2500 350 K / 2 + J + 80 K / 2 + M + 803200 to 4000 510 K / 2 + J + 80 K / 2 + M + 80(1) For the 800 A rating, indicate KTA0800 .

    Catalogue numbers anddimensions

    Canalis KTA

    Feed units for switchboards andoil immersed transformersIP55

    KTAppppERp6

    Dimensions of connection pads

    Rating (A) 800 1000 1250 1600 2000 2500 3200 4000

    Drilling for connection (mm)

    DD202182

  • 7/21/2019 Canalis KTA 800_4000A

    70/205K9AE24010

    DD202316

    DD2

    02315

    DD202317

    5Schneider Electric

    C

    ataloguenumbers

    D

    imensions

    Catalogue numbers anddimensions

    Canalis KTA

    Feed units for switchboards andoil immersed transformersIP55

    Bar feed units, flat outlets

    Type Cat. no.

    3L + PE 3L + N + PE 3L + N + PER

    Made to measure KTAppppER37 KTAppppER47 KTAppppER77

    Connection pad dimensions are identical to those of the feed units.

    KTAppppERp7

    KTAppppERp7

    (1) See the Trunking cross-sectiontable below.

    Table of dimensions

    Rating (A) Dimensions (mm)

    A P - Q S - R ou R - S Q, R, S minimum Y800(2)to 1250 235 to 734 160 to 600 160 to 600 80 2301600 to 2500 235 to 734 160 to 600 160 to 600 80 3503200 to 4000 235 to 734 160 to 600 160 to 600 80 510(2) For the 800 A rating, indicate KTA0800 .

    Cut-out drawing for straight feed units connected directly to the device

    Table of dimensions

    Rating (A) Dimensions (mm)

    Y U V800(1)to 1250 230

    U = P + 80if S > R, V = S + 80if R > S, V = R + 80

    1600 to 2500 35