CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E...

20
National Building Code (NBC) – Part 2 CANADIAN FARM BUILDERS ASSOCIATION PROPOSED CHANGES TO THE NATIONAL FARM BUILDING CODE OF CANADA

Transcript of CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E...

Page 1: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

National Building Code (NBC) – Part 2

CANADIAN FARM BUILDERS ASSOCIATION

PROPOSED CHANGES TO THE NATIONAL FARM BUILDING CODE OF CANADA

Page 2: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

TASK GROUP MEMBERS

The CFBA sincerely thanks our Task Group Members

• Bram Van den Heuvel (Co-Chair)

• Tyler Griffith (Co-Chair)

• Terry Rothwell

• Dan Reymer

• Trish Douel

• Chet Liu

• Ed Podniewicz

• Sam Bradshaw

• Ken Worsley

• Matt Farrell

• Herman Post

• Gary van Bolderen

Page 3: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

TASK GROUP OBJECTIVES

• Review of the proposed changes to the National Building Code (NBC) – Part 2

• Identifying areas of concern for the farming industry

• Collaboration between task group and CFBA members

• Preparation and submission of responses back to the NRC on behalf of the CFBA.

Page 4: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

BUILDING CLASSIFICATIONOCCUPANCY

• All large farm buildings will be classified as (Group G) Occupancy

• Divisions of Group G:

– (Division 1) High Hazard

– (Division 2) Agricultural Occupancies not elsewhere in Group G

BELOW FLOOR MANURE STORAGE (DIVISION 1) HIGH HAZARD IMPLEMENT SHED (DIVISION 2) – ALL OTHER

Page 5: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

(DIVISION 3) - GREENHOUSES FEED BUNKERS (DIVISION 4) – NO HUMAN OCCUPANTS

• Divisions of Group G:- (Division 3) Greenhouses- (Division 4) No Human Occupancy

• Allowance for other occupancies other than farm within same building.

BUILDING CLASSIFICATIONOCCUPANCY

Page 6: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

SPATIAL SEPARATION

• Currently not included in legislation

• Focus of National Code is human life safety

• No protection for primary or secondary residences, or other non-farm occupancies, could affect human life safety

• No spatial separation requirements could raise human life safety concerns on adjacent properties

Page 7: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

SPATIAL SEPARATION

https://www.simcoe.com/news-story/8646480-fire-destroys-barn-in-springwater-township/

Page 8: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

SEISMIC DESIGN REQUIREMENTS

• Low Seismic Zones IEF(0.2)Sa(0.2) < 0.35, and

• Seismic factors for Ductility Rd & Overstrength Ro– RdRo > 5.0

• OSB or plywood panel based, nailed shear walls allow for no seismic analysis

• Wood diagonal bracing would require seismic analysis.

• Significant use of wood diagonal bracing in farm buildings today. CFBA will respond to allow for diagonal braces to be used without the need for seismic analysis.

Page 9: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

SEISMIC DESIGN REQUIREMENTS

DIAGONAL BRACES SHEARWALLS

Page 10: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

EXITING REQUIREMENTS

• Exit door swing currently required in the direction of travel (outward)

• Sliding or roll-up type doors are no longer permitted as an exit type

• CFBA is proposing to change door swing to inward due to low human occupancy and potential ice / snow blockage preventing exiting

• Proposing increases to travel distances for egress

Page 11: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

EXITING REQUIREMENTS

https://business.financialpost.com/commodities/agriculture/winter-brings-out-the-best-and-worst-of-life-on-the-farm

https://www.freshdaily.ca/culture/2020/01/canadians-snow-doors/

Page 12: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

ATTIC FIRE BLOCKING

• Identifying need to used area based calculation in determining locations of firestops (900m2). Buildings wider than 98’-5”.

• Materials to be used as the fire block remain the same.

• (1/2”) 12.5mm OSB is a special order item (expensive)

• (1/2”) 12.5mm Plywood (4’x8’ sheet $25)

• (7/16”) 11.1mm OSB (4’x8’ sheet $12)

• (5/8”) 15.8mm OSB (4’x8’ sheet $19)

• CFBA will propose allowance for use of standard (7/16”) 11.1mm OSB to used as fire block material

Page 13: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

ATTIC FIRE BLOCKING

http://www.omafra.gov.on.ca/english/engineer/barnfire/section3.htm#3

Page 14: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

FIRE SUPPRESSION / DETECTION

• Option to sprinkler farm buildings

• On site water requirements for sprinkler systems and other applicable requirements

• Fire alarm requirements for farm structures of two storeys or greater

• CFBA is proposing to increase to greater than two storeys for fire alarm requirements

• Longevity of suppression and detection systems in farm buildings

Page 15: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

FIRE SUPPRESSION / DETECTION

https://durangoherald.com/articles/90084

https://www.grainger.com/product/NAPCO-Fire-Pull-Station-54TT19

Page 16: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

FIRE DEPARTMENT ACCESS

• Access for the fire department equipment shall be provided to each farm building by means of a street, private roadway or yard.

• Where access is provided by means of a roadway or yard, the design shall take into account

- connection with public thoroughfares

- weight of firefighting equipment

- width of the roadway, radius of curves

- overhead clearances

- location of fire hydrants and fire department connections

- vehicular parking

• CFBA response to proposed more detailed description of the requirements. 6m road width, 12m radius of curve, 5m OH clearances. Elaboration on “shall take into account”.

Page 17: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

https://www.barricadetrafficservices.com/products/fire-access-route-sign

http://free.bcpublications.ca/civix/document/id/public/vbbl2007/building_b_appa_p3

Page 18: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

ONGOING INSPECTIONS / FIRE CODE

• Mandatory electrical and mechanical inspections including thermal imaging are required

• Required upgrades to mitigate fire risks

• New fire code implementation with potential fire orders on farm properties for non-compliance

Page 19: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

ONGOING INSPECTIONS / FIRE CODE

https://farmtario.com/news/finding-hot-spots-in-the-barn/

https://www.thermalimaging.co.uk/wp-content/uploads/2013/08/Circuit-Breakers1.jpg

Page 20: CANADIAN FARM BUILDERS ASSOCIATION€¦ · SEISMIC DESIGN REQUIREMENTS •Low Seismic Zones I E F(0.2)S a (0.2) < 0.35, and •Seismic factors for Ductility R d & Overstrength

TASK GROUP - NEXT STEPS

• Finalize proposed changes and reasoning to identified articles by the CFBA task group

• Final review by task group on all proposed changes

• All proposed changes to be formatted for submission to NRC

• All proposed changes to be submitted before March 13, 2020 deadline