C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 and section 7.3 Prepared by Claude Beauchemin GE Canada

Transcript of C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed...

Page 1: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

C57.104 Draft 11d

Evaluation of proposedgas-in-oil limits of Table 1and section 7.3

Prepared by Claude BeaucheminGE Canada

Page 2: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

2 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

In Table 1 of section 6.1, the revised C57.104 present a set of ppm limit value for each combustible gases used for the classification of Type 1 transformer status (Normal, Caution, Warning)

In this statistical study of DGA, data from one laboratory is compared to the proposed limits

Page 3: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

3 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

Source of Data: DGA performed at GE Canada laboratory (Montreal)

Number of samples: 35240

Period covered: May 1990 to October 2000

Source of samples: North-East of North America, mixed sources (Industrial and Utilities), mixed population of breather and sealed type transformers of all size

Page 4: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

4 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

Methodology of analysis:

All sample of the period included in the study

- No discrimination for:- Transformer size- Sampling point- Utility VS Industrial- “Fault” VS “No fault”

Population is typical of a transformer Type 1 DGA result

Page 5: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

5 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

Methodology of analysis:

For each gas, all samples were sorted by increasing value

A population curve was prepared ( % of total population <= x ppm Value)

% of population of DGA less than each proposed ppm limits was determined

Page 6: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

6 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

Methodology of analysis:

Limit value used for this study were as follow (from draft 10):Table 1 of section 6.1:

H2 CH4 C2H2 C2H4 C2H6 CO TDCG

Caution: 100 120 2 50 65 350 700

Warning: 700 400 5 100 100 570 1900

Section 7.3Ratio CO2/CO : 3 < normal > 10

Page 7: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

7 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Population curve for H2

H2 Population Curve

0

100

200

300

400

500

600

700

800

900

1000

0 10 20 30 40 50 60 70 80 90 100

% of Population

H2 P

PM

Caution Level

Warning Level

Page 8: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

8 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Population curve for CH4

CH4 Population Curve

0

100

200

300

400

500

600

700

800

900

1000

0 10 20 30 40 50 60 70 80 90 100

% of Population

CH4

PPM

Caution Level

Warning Level

Page 9: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

9 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Population curve for C2H6

C2H6 Population Curve

0

20

40

60

80

100

120

140

160

180

200

0 10 20 30 40 50 60 70 80 90 100

% of Population

C2H

6 PP

M

Caution Level

Warning Level

Page 10: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

10 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Population curve for C2H4

C2H4 Population Curve

0

20

40

60

80

100

120

140

160

180

200

0 10 20 30 40 50 60 70 80 90 100

% of Population

C2H

4 PP

M

Caution Level

Warning Level

Page 11: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

11 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Population curve for C2H2

C2H2 Population Curve

0

1

2

3

4

5

6

7

8

9

10

0 10 20 30 40 50 60 70 80 90 100

% of Population

C2H

2 PP

M

Caution Level

Warning Level

Page 12: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

12 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Population curve for COCO Population Curve

0

100

200

300

400

500

600

700

800

900

1000

0 10 20 30 40 50 60 70 80 90 100

% of Population

CO

PPM

Caution Level

Warning Level

Page 13: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

13 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Population curve for COCO Population Curve

0

500

1000

1500

2000

2500

3000

0 10 20 30 40 50 60 70 80 90 100

% of Population

CO

PPM

Caution Level

Warning Level

Page 14: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

14 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Population curve for TDCGTDCG Population Curve

0

500

1000

1500

2000

2500

3000

3500

0 10 20 30 40 50 60 70 80 90 100

% of Population

TDC

G P

PM

Caution Level

Warning Level

Page 15: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

15 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

Correlation between each level limit and the % of DGA populationbelow the limit:

H2 CH4 C2H2 C2H4 C2H6 CO TDCG Avrg

Caution ppm: 100 120 2 50 65 350 700% DGA 92.1 94.8 89.7 86.6 93.6 62.3 73.5 86.5

Warning ppm: 700 400 5 100 100 570 1900% DGA 98.4 98 93.1 92.5 95.6 80 95.9 92.9

Page 16: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

16 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

First question: What is the % of population that should be used for “Caution” and “Warning” ?

The average of all limits for “Caution” is 86.5% of population for (H2 + Hydrocarbon + CO) and 91.4% for (H2 + Hydrocarbon) only

The average of all limits for “Warning” is 92.9% of population for (H2 + Hydrocarbon + CO) and 95.5% for (H2 + Hydrocarbon) only

Page 17: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

17 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

On average, the “Caution” limits used seems to be in line with a value of 90% of the population, but there is several exceptions, as a small change of % population correlate with a large Change of ppm:

CH4: 90% = 44 ppm for a limit of 120 (94.8%)C2H6: 90% = 27 ppm for a limit of 65 (93.6%)CO: 90% = 932 ppm for a limit of 350 (62.3%)TDCG: 90% = 1246 ppm for a limit of 700 (73.5%)

Page 18: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

18 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

If instead we take 95% for the “Caution” limits, then we have the following exceptions:

C2H2: 95% = 9.1 ppm for a limit of 2 (89.7%)C2H4: 95% = 189 ppm for a limit of 50 (86.6%) CO: 95% = 1180 ppm for a limit of 350 (62.3%)TDCG: 95% = 1730 ppm for a limit of 700 (73.5%)

Page 19: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

19 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

We see the same situation for the “Warning” limits which seems to be in line with a value of 95% of the population. But in fact virtually all gases are “out of range”, to the exceptions of C2H6 and TDCG

H2: 95% = 166 ppm for a limit of 700 (98.4%)CH4: 95% = 126 ppm for a limit of 400 (98%)C2H4: 95% = 189 ppm for a limit of 100 (92.5%)C2H2: 95% = 9.1 ppm for a limit of 5 (93.1%)CO: 95% = 1180 ppm for a limit of 570 (80%)

Page 20: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

20 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

If instead we take 98% for the “Warning” limits, then we have the following exceptions:

C2H6: 98% = 258 ppm for a limit of 100 (95.6%)C2H4: 98% = 773 ppm for a limit of 100 (92.5%)C2H2: 98% = 58 ppm for a limit of 5 (93.1%)CO: 98% = 1564 ppm for a limit of 570 (80%)TDCG: 98% = 3106 ppm for a limit of 1900 (95.9%)

Page 21: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

21 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas levelActual PPM value for 90%, 95% and 98% population:

H2 CH4 C2H2 C2H4 C2H6 CO TDCGCaution ppm: 100 120 2 50 65 350 70090 % DGA 79 44* 2 67 27* 932* 1246*or95 % DGA 166 126 9.1* 189* 84 1180* 1730*

Warning ppm: 700 400 5 100 100 570 190095 % DGA 166* 126* 9.1* 189* 84 1180* 1730or98% DGA 509 391 58* 773* 258* 1564* 3106*

* Significant discrepancy

Page 22: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

22 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

It seems these limit are too low in general and give high number of “abnormal” DGA

This is compound by the fact that ANY limit being exceeded will lead to the classification of a sample as “Caution” or “Warning”, increasing the percentage of “abnormal” results

Page 23: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

With the set of DGA results used in this study:

49% of samples would be classified as “Caution” or “Warning”

33% of samples would be classified as “Warning”

(not counting the CO2/CO ratio limit)

Proposed gas level

23 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Page 24: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

ConclusionTherefore, based on this study alone (which is limited in its geographical distribution), some revision of limits value seems required.

More statistic studies in other location and from other laboratories are probably needed to confirm this data

We also need to determine which % threshold to use.

Any volunteers?

24 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Page 25: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

25 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Proposed gas level

Second question: Is there some discrimination we should use to determine these limits?

Age?Size?Sealed or not?OLTC or not?….

This question is particularly important for CO

Page 26: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

26 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

The CO question

The situation with CO and the proposed limits is as follow:

Close to 40% of samples are in “Caution”

20 % of samples are in “Warning”

Also, the CO2 / CO ratio give between 60% to 80% of samples as “abnormal” (less than 7 or more than 10) depending of the level of CO or CO2 selected.

Even if we limit analysis to CO > 500 ppm andCO2 > 5000 ppm, the proportion is still 66% of samples

Page 27: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

27 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

The CO question

If we use the limit of 3 to 10 for a “normal” CO2 / CO ratio, then we could reduce the level of “abnormal” DGA (less than 3 or more than 10) to “just” 33%

However, only 0.3% of the sample have a ratio below 3, which is suspiciously too low.

2% of DGA have ratio below 3.98

5% of DGA have ratio below 4.4

Page 28: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

28 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

The CO questionCO2 / CO Population Curve

0

5

10

15

20

25

30

35

40

45

50

0 10 20 30 40 50 60 70 80 90 100

% of Population

CO

2/C

O R

atio

Normal Zone

Page 29: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

29 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

The CO questionDiscriminating between samples from sealed type and breather type transformer

Large difference in CO and CO2 behavior between the two populations of samples

For purpose of data analysis, sample is presumed coming from sealed transformer if O2 < 5% of the total O2 + N2 and is presumed coming from open breather transformer if O2 > 15% of the total O2 + N2

Page 30: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

30 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

The CO questionCO Population Curve

0

100

200

300

400

500

600

700

800

900

1000

0 10 20 30 40 50 60 70 80 90 100

% of Population

CO

PPM

Caution Level

Warning Level

O2 / (O2 + N2) < 5%

O2 / (O2 + N2) > 15%

All Samples

Page 31: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

31 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

The CO questionCO Population Curve

0

500

1000

1500

2000

2500

3000

3500

0 10 20 30 40 50 60 70 80 90 100

% of Population

CO

PPM

Caution Level

Warning Level

O2 / (O2 + N2) < 5%

O2 / (O2 + N2) > 15%

All Samples

Page 32: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

32 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

CO2 / CO Population Curve for CO and CO2 > 25 ppm

0

5

10

15

20

25

30

35

40

45

50

0 10 20 30 40 50 60 70 80 90 100

% of Population

CO

2/C

O R

atio

ProposedNormal Zone

O2 > 15%

All

O2 < 5%

The CO question

Page 33: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

33 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

The CO question

If we discriminate between the two populations then:

For “sealed” transformer 90% of DGA are below 1454 ppm of CO and for “open breather”transformer 90% of DGA are below 478 ppm of CO:

3 to 1 ratio !!

If this is confirmed, we obviously need to take it into account for the determination of the “Caution” and “Warning” limit.

Page 34: C57.104 Draft 11d Evaluation of proposed gas-in-oil … · C57.104 Draft 11d Evaluation of proposed gas-in-oil limits of Table 1 ... Exclusively for consultation by member of the

34 / 33Copyright GE Canada 2006; DO NOT DISTRIBUTE;

Exclusively for consultation by member of the IEEE transformer committee /3/15/2006

Conclusion

The actual set of limits in section 6.1 and 7.3 probably need to be revised

More set of data will be required to refine the limit value

In the set of data presented here, too many transformer will be classified as “Caution”or “warning”