By Revision/Date PINNACLE HEALTH TRISTAN …€¦ · · 2013-07-19list of drawings: architectural...
Transcript of By Revision/Date PINNACLE HEALTH TRISTAN …€¦ · · 2013-07-19list of drawings: architectural...
LIST OF DRAWINGS:
ARCHITECTURAL
CS - COVER SHEET
A1 - TITAN MRI NEW FLOOR PLAN
NEW CHILLER PAD PLAN
PARTIAL DEMOLITION PLAN
A2 - BSMT. EQUIPMENT ROOM PLAN
S1 - STRUCTURAL DETAILS
E1 - ELECTRICAL POWER PLAN
E2 - ELECTRICAL LIGHTING PLAN
M1 - BASIC MECHANICAL REQUIREMENTS - EQUIPMENT SCHEDULES
M2 - BASEMENT & FIRST FLOOR MECHANICAL DEMO PLANS
M3 - BASEMENT & FIRST FLOOR MECHANICAL PLANS
TOSHIBA SITE SPECIFIC DRAWINGS
C1 - COVER SHEET
GN - GENERAL NOTES
SECTION A
A1 - EQUIPMENT LAYOUT
A2 - MAGNETIC FIELD LAYOUT
A3 - DETAILS
A4 - EQUIPMENT ELEVATIONS
A5 - EQUIPMENT ELEVATIONS
SECTION S
S1 - STRUCTURAL LAYOUT / BASE DETAIL
SECTION P
P1 - PLUMBING LAYOUT
P2 - WATER COOLING FACILITIES CONFIGURATION
P3 - PLUMBING / MEDICAL GAS DETAILS
SECTION M
M1 - MECHANICAL LAYOUT
M2 - QUENCH PIPE DETAILS
M3 - QUENCH PIPE DETAILS
M4 - QUENCH PIPE DETAILS
SECTION E
E1 - ELECTRICAL LAYOUT
E2 - ELECTRICAL SCHEMATIC
E3 - ELECTRICAL DETAILS
E4 - LINE FILTER PANEL
E5 - POWER SYSTEM DIAGRAM / POWER QUALITY REQUIREMENTS
E6 - CABLE LENGTH DIAGRAM (FOR INTERNAL USE ONLY)
SUBMITTER INFORMATION
COMPANY SUBMITTING PLANS: PINNACLE HEALTH SYSTEMS
CONTACT PERSON: DANA KLINEPETER, CONSTRUCTION PROJECT MANAGER
TELEPHONE NUMBER: 717-782-3168 CELL: 717-810-7553
ADDRESS: HARRISBURG HOSPITAL CAMPUS, COLE BUILDING
218 SOUTH SECOND STREET
CITY: HARRISBURG STATE: PA ZIP: 17104-8700
FACILITY INFORMATION
FACILITY NAME: PINNACLE HEALTH IMAGING
ID NUMBER: COMPONENT NAME OR NUMBER:
ADDRESS: 4518 UNION DEPOSIT ROAD
CITY: HARRISBURG STATE: PA ZIP: 17101
COUNTY: DAUPHIN
SCOPE OF PROJECT:
CHANGEOUT EXISTING PHILIPS MRI TO A NEW TOSHIBA
VANTAGE TITAN IN EXISTING FIRST FLOOR MRI EXAM ROOM
Drawn
Start Date
Scale
Checked
Job No.
Sheet
Revision/Date
TR
AD
E E
AS
TE
RN
, IN
C.
By
PREPARED BY:
NFPA 101
LIFE SAFETY CODE
2012 EDITION
GUIDELINES FOR DESIGN AND CONSTRUCTION
OF HOSPITAL AND HEALTH CARE FACILITY
2010
NEW TOSHIBA VANTAGE TITAN MRI INSTALLATION
PINNACLE HEALTH TRISTAN
RADIOLOGY SPECIALISTS
UNION DEPOSIT
4518 UNION DEPOSIT ROAD, HARRISBURG, PA
NOT TO SCALE
1ST FLOOR KEY PLAN
1
NOT TO SCALE
BASEMENT KEY PLAN
2
EX
IS
T. W
IN
DO
W
CO
VE
RE
D B
Y W
ALL
TO
R
EM
AIN
SCAN
ROOM
CONTROL
9'-0"
7'-8" 7'-8"
3'-6"6'-0"
NEW FULL HT CABS.
EX
IS
T. W
IN
DO
W
CO
VE
RE
D B
Y W
ALL
TO
R
EM
AIN
5'-9"
1'-6"
CLR.
MRI
WOMEN'S
WTG.
3'-6"
5'-0"
5'-0"
NEW FULL
HT CAB'S
4'-0"
2'-5"
EXIST ELECT
PNL TO REMAIN
Drawn
Start Date
Scale
Checked
Job No.
Sheet
Revision/Date
TR
AD
E E
AS
TE
RN
, IN
C.
By
DEMOLITION LEGEND
1 REMOVE EXISTING DOOR AND FRAME.
2 REMOVE EXISTING PARTITION
3 REMOVE EXISTING CEILING TILE & GRID
4 REMOVE EXISTING FLOORING
5 PROVIDE NEW DOOR OPENING
6 REMOVE EXISTING WINDOW
7 REMOVE EXISTING MRI SHIELDED BOX
8 SHORE EXISTING FLOOR JOISTS FROM BASEMENT EQUIPMENT ROOM
BELOW. CUT & REMOVE EXISTING CONCRETE FLOOR SLAB AND METAL
DECK, SEE S-1 PLAN FOR NEW PAD METAL COLUMN SUPPORT AND
FLOOR PAD RECONSTRUCTION.
Scale:1/4" = 1'-0"
DEMOLITION PLAN
1
Scale:1/4" = 1'-0"
TITAN MRI NEW FLOOR PLAN
2
SCAN
ROOM
9'-0"
9'-0"
Scale:1/4" = 1'-0"
SCAN ROOM FLOOR CUT LOCATION
3
EXISTING MRI TO
BE REMOVED BY
OTHERS
4'-6"
4'-6"
VERIFY
ISOCENTER.
LOCATION
WITH TOSHIBA
PLANS
17'-5"
EQUIPMENT
ROOM
COMPUTER
ROOM
BASEMENT EQUIPMENT ROOM
PLAN A
1/4" = 1'-0"
LUNCH
ROOM
WOMEN
MEN
CORRIDOR
STAIR
FILE
STORAGE
LINE OF SLAB
ABOVE @ 9'-0"
A.F.F.
4'-0"
RELOCATE
PARTITION
AS SHOWN
COMP. EQUIP
TOP REMAIN
REMOVE
EXISTING
HVAC
CHASE
WALL
NEW TITAN MRI
ISOCENTER
10'-4"
10'-4"
8'-3"
7'-10 3/8"
9'-6 5/8"
Drawn
Start Date
Scale
Checked
Job No.
Sheet
Revision/Date
TR
AD
E E
AS
TE
RN
, IN
C.
By
8'-0"
9'-0"
14'-0"
9'-0"
2'-4"
6"
1'-10"
6" 6"9'-0" x 9'-0"
13'-0"
10'-8"
6" 6"
MRI PEDESTAL SECTION
SCALE: 1/2" = 1'-0"
MRI PEDESTAL PLAN @ 1ST FLR SCAN ROOM
SCALE: 1/2" = 1'-0"
℄ISOCENTER
SK-2
EX
IS
TIN
G 20K
5 B
AR
JO
IS
TS
, C
UT
JO
IS
T &
M
OD
IF
Y JO
IS
T B
EA
RIN
G
EX
IS
TIN
G 20K
5 B
AR
JO
IS
TS
, C
UT
JO
IS
T &
M
OD
IF
Y JO
IS
T B
EA
RIN
G
8'-0"
10'-0"
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
10'-0"
4"
1'-8"
10'-0" x 10'-0"
4"
3"
2"
1'-0"
BEAMS ASTM A992
TUBES ASTM A500 GRADE B
ALL STEEL PRIMER GREY
Drawn
Start Date
Scale
Checked
Job No.
Sheet
Revision/Date
TR
AD
E E
AS
TE
RN
, IN
C.
By
PARTIAL BASEMENT ELECTRICAL PLAN
1/4" = 1'-0"
MRI
EQUIPMENT
ROOM
LUNCH
ROOM
CORRIDOR
STAIR
S
S
4
13
11
MDP2
8
10
EXIST. LEIBERT
UNIT CU
MRI CHILLER
5
EXISTING
COMPUTER
RACK CU
EXISTING
COMPUTER
RACK CU
EXISTING
COMPUTER
ROOM CU
EXISTING PANEL LPB-1,
120 / 208 V, 3 , 4W
APC
LUXAIRE
APC
W.P.
W.P.
W.P.
W.P.
W.P.
7
6
6
TD
F
F
S
3
TD
2# 12 + 1# 12G IN 3/4"C
TO 20A-1P BREAKER.
2#12 + 1#12G - 3/4"C
TO 20A-1P BREAKER
3
S
3
12
W.P.
15
S
M
14
SEE NOTE2
1042
MECH.
1063
CHG
1062
CORRIDOR
1061
D.R.
1065
CORRIDOR
CONSULT
1060
HC.D.R.
1059
TOILET
1057
CONSULT
PAT.
CHG
PARTIAL FIRST FLOOR POWER PLAN
1/4" = 1'-0"
T.D. T.D.
NOTES:
EXTEND, 2# 12 + 1# 12 G
- 3/4"MC (H.G.) CABLE
TO PANEL LP-2.
PROVIDE BREAKER AS
REQUIRED.
EXHAUST FAN, EF-1, 1/4
HP, 120V, WITH BUILT-IN
DISCONNECT SWITCH.
PROVIDE WIRING PER
TOSHIBA DRAWINGS.
EMO
EMO
IN USE
1
RECONNECT TO
EXISTING BRANCH
CIRCUIT
EXISTING ELECTRICAL
PANEL, LP-2, 120/208V
RELOCATED RECEPTACLE,
CONNECT TO EXISTING
BRANCH WIRING
1
CONTROL
ROOM
MRI SCAN
ROOM
SEE NOTE 2
2
2
ELECTRICAL LEGEND
SYMBOL DESCRIPTION
RECESSED ROUND LIGHT FIXTURE, TYPE AS NOTED.
RECESSED FLUORESCENT LIGHT FIXTURE 2' x 2' OR 2'
x 4' AS INDICATED.
RECESSED FLUORESCENT LIGHT FIXTURE OR
EMERGENCY POWER.
DUPLEX CONVENIENCE RECEPTACLE 24" A.F.F.,
U.N.O.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE 24"
A.F.F., U.N.O.
SWITCH SINGLE POLE
SWITCH 3-WAY
DIMMER SWITCH
TELEPHONE, DATA OR TELEPHONE / DATA AS NOTED.
EMERGENCY OFF BUTTON
DISCONNECT SWITCH, TYPE AS NOTED.
MOTOR, TYPE AS NOTED.
MANUAL MOTOR STARTER SWITCH
FIRE ALARM PULL STATION
FIRE ALARM AUDIO / VISUAL
FIRE ALARM VISUAL ONLY
SMOKE DETECTOR
SPEAKER
HOMERUN TO PANEL AS NOTED
BRANCH WIRING
EXIT LIGHTING FIXTURE ARROWS AS INDICATED
EMERGENCY BATTERY UNIT WITH 2 UNIT MOUNTED
HEADS
REMOTE MOUTNED EMERGENCY HEADS
U.F. UNFUSED
W.P. WEATHER PROOF
S
S
3
D
T.D.
S
M
F
F
F
S
S
LIGHTING FIXTURE SCHEDULE
TYPE A
6 1/2" ROUND RECESSED 150W INCANDESCENT
DOWNLIGHT W/ CLEAR ALZAK REFLECTORS SUITABLE
FOR USE IN MRI SCAN ROOM. SIMILAR TO
PEACHTREE LIGHTING CAT. NO. PMRI-7150-C.
TYPE B
6" ROUND RECESSED FLUORESCENT W/ (2) 26W PL
LAMPS, LOW IRIDESCENT CLEAR SPECULAR
REFLECTOR, AND DIMMING BALLAST.
POWER RISER DIAGRAM
N.T.S.
TOSHIBA
VRDU,
FOR MRI II
MRI
EQUIPMENT
ROOM
DRAKE
CHILLER
30 MCA
45 MOP
480V, 3
REMOVE EXIST. DISC.
SWITCH. PROVIDE
60A-3P U.F. W.P.
DISCONNECT SWITCH
REMOVE EXISTING
FEEDER, PROVIDE
3#6
1#10G
1"C
REMOVE EXISTING
CONDUCTORS
PROVIDE
3# 2/0
1# 2/0 G
EXISTING
2"C
REMOVE EXISTING 80A-3P BREAKER,
PROVIDE A 150A-3P SHUNT TRIP
ENCLOSED CIRCUIT BREAKER IN
BASEMENT EQUIPMENT ROOM,
WHERE INDICATED ON PLAN.
EXISTING PANEL MDP-2, 277/480V,
3 , IN MECH. / ELECT. RM 0004.
REMOVE EXISTING 80A-3P
BREAKER, PROVIDE, 150A-3P
BREAKER, MATCH A.I.C. OF
EXISTING BREAKERS.
REMOVE 30A-3P, PROVIDE
45A-3P BREAKER, MATCH A.I.C.
OF EXISTING BREAKERS.
ENLARGED
MRI EQUIPMENT ROOM PLAN
1/2" = 1'-0"
S
3
F
3
3
T
T.D.
1
F
F
MDP2
MRI
EQUIPMENT
ROOM
9
NOTES:
RELOCATE F.A. AUDIO-VISUAL UNIT, TELEPHONE OUTLET AND
EMERGENCY LIGHTING BATTERY UNIT TO NEW WALL AS INDICATED.
EXISTING 2' x 2' RECESSED FLOOR FIXTURES (TYP. FOR 6), RELOCATE
FIXTURES AS REQUIRED TO CLEAR NEW SUPPORT COLUMNS.
EXISTING SWITCH AND FIRE SUPPRESSION SYSTEM P.B. AND PULL
STATIN TO REMAIN.
EXISTING LIGHTING FIXTURES (8), SMOKE DETECTORS (2) TO REMAIN.
EXISTING CHILLER TO BE REMOVED BY OTHERS, NEW DRAKE CHILLER
FURNISHED BY TOSHIBA AND INSTALLED BY HVAC CONTRACTOR 30A
MCA, 45A MOP, 480V, 3 , SEE POWER RISER THIS DRAWING.
RELOCATE RECEPTACLES AND TELEPHONE TO NEW WALL.
RELOCATE EXISTING 100A-208 V, 1 PANEL AN FOR AUX. HEAT TO NEW
PARTITION, WHERE INDICATED.
EXISTING SHUNT TRIP BREAKER FOR MRI, SEE POWER RISER, THIS DWG.
VERIFY LOCATION OF NEW BREAKER.
NEW SHUNT TRIP BREAKER FOR TOSHIBA MRI II, SEE POWER RISER
THIS DWG.
EXISTING LIEBERT OUTDOOR UNIT AND FEEDER TO REMAIN.
EXISTING LIEBERT INDOOR UNIT AND FEEDER TO BE RELOCATED BY
HVAC, RELOCATE BREAKER AND FEED T NEW WALL.
NEW LIEBERT OUTDOOR UNIT, 5 TON, 11.7 FCA, 20A MOP, 480V, 3 ,
PROVIDE A 30A-3P, UF, WATERPROOF DISCONNECT SWITCH EXTEND 3#12
+ 1#12G - 3/4"C TO 480V, MRI EQUIPMENT PANEL IN 1ST FLOOR STORAGE
CLOSET, PROVIDE 20A-3P BREAKER , MATCH A.I.C. RATING OF EXISTING
BREAKERS.
NEW LIEBERT 570H INDOOR UNIT, 30, 3FLA, 40A, MOP, 480V, 3 , WITH
BUILT-IN DISCONNECT SWITCH, EXTEND 3#8 + 1#10GIN 1"C TO 480V MRI
EQUIPMENT PANEL IN 1ST FLOOR STORAGE CLOSET. PROVIDE 40A-3P
BREAKER, TO MATCH EXISTING BREAKER A.I.C. RATINGS.
IN-LINE EXHAUST FAN, .36 HP, 120V, 1 , PROVIDE MANUAL STARTER.
EXTEND 2# 12 + 1# 12G - 3/4"C TO 15A-1P BREAKER IN LOCAL PANEL.
DISCONNECT POWER TO ELECTRIC REHEAT BOXES. REMOVE BRANCH
WIRING TO EXISTING PANEL AN.
NOTES:
1. ALL ELECTRICAL WORK SHALL CONFORM TO
THE APPLICABLE NATIONAL ELECTRIC CODE,
STATE AND LOCAL CODES.
2. SEE TOSHIBA TITAN MRI DRAWINGS FOR
REQUIRED WIREWAYS, J/B'S, CONDUIT RUNS,
CABLE TRAYS, REQUIRED POWER AND
CONTROL INTERCONNECT WIRING AND
GROUNDING.
3. NEW DEXA ROOM 1069, PROVIDE A DEDICATED
20A, 120V CIRCUIT AND RECEPTACLE FOR THE
RELOCATED DEXA MACHINE. VERIFY EXACT
LOCATION OF THE RECEPTACLE, SEE DRAWING
CS (COVER SHEET) FOR DEXA ROOM LOCATION.
1
2
3
4
Drawn
Start Date
Scale
Checked
Job No.
Sheet
Revision/Date
TR
AD
E E
AS
TE
RN
, IN
C.
By
5
6
7
8
9
10
11
13
12
REFER TO
ENLARGED
PLAN BELOW.
14
15
FIRST FLOOR
LIGHTING DEMOLITION PLAN
1/4" = 1'-0"
1042
MECH.
1063
CHG
1062
1041
CORRIDOR
1061
D.R.
1065
CORRIDOR
CONSULT
CO
RR
ID
OR
1060
HC.D.R.
1059
TOILET
1057
CONSULT
PAT.
CHG
NEW WOMEN'S
MAMMO WAITING
MAMMO #2
MRI
1056
SUB WAITING
MAMMOGRAM
MEDICAL LIBRARY
CONTROL
1
S
S
S
3
4
EXISTING 2x4
PARABOLIC
F
F
2
EM
D D D D
4x4 WIREWAY
2
FIRST FLOOR LIGHTING PLAN
1/4" = 1'-0"
1042
MECH.
1063
CHG
1062
1041
CORRIDOR
1061
D.R.
1065
CORRIDOR
CONSULT
CO
RR
ID
OR
1060
HC.D.R.
1059
TOILET
1057
CONSULT
PAT.
MRI
SCAN ROOM
CONTROL
CHG
NEW WOMEN'S
MAMMO WAITING
MAMMO #2
EX
IS
T. W
IN
DO
W
CO
VE
RE
D B
Y W
ALL
TO
R
EM
AIN
MRI
WOMEN'S
WTG.
A A
AA
A A
S
S
A
A
1
S
5
EM
D1
D2
B
B
3
TO
EXISTING
BRANCH
WIRING
12
TO DIMMER
SYSTEM IN MRI
EQUIPMENT
ROOM BELOW.
2
2
F
4
F
7
S
6
S
F
RELOCATE
EXISTING FIRE
ALARM VISUAL
TO NEW WALL
E
8
9
F
S S
2
11
12
10
F
Drawn
Start Date
Scale
Checked
Job No.
Sheet
Revision/Date
TR
AD
E E
AS
TE
RN
, IN
C.
By
DEMOLITION NOTES:
EXISTING MRI SCAN ROOM, REMOVE ALL RECESSED INCANDESCENT
LIGHTING AND RELATED BRANCH WIRING. RELOCATE RECEPTACLES,
SPEAKERS AND SMOKE DETECTORS TO NEW SCAN ROOM. PROVIDE
NEW RECEPTACLE DEVICES, REMOVE EXISTING E.M. PUSHBUTTON.
EXISTING MRI CONTROL ROOM AND HALLWAY, REMOVE ALL
RECEPTACLES, SWITCHES, DIMMERS, WIREWAYS, E.M. PUSHBUTTONS
AND RECESSED INCANDESCENT LIGHTING. RELOCATE (3) 2x2 RECESSED
FLUORESCENT LIGHTS AND FIRE ALARM AUDIO VISUAL.
EXISTING MEDICAL LIBRARY, REMOVE EXISTING LIGHTING FIXTURES,
SWITCHES AND DIMMER SWITCHES. FIRE ALARM AUDIO / VISUAL AND
RECEPTACLE TO REMAIN.
RELOCATE EXISTING LIGHT FIXTURE AND RECEPTACLE.
1
2
3
4
NOTES:
RELOCATED SPEAKER.
RELOCATED LIGHT FIXTURE.
CONNECT BATTERY UNIT TO UNSWITCHED NORMAL LIGHTING ALT.
EXISTING FIRE ALARM AUDIO / VISUAL UNIT TO REMAIN.
RELOCATED SMOKE DETECTOR.
EXISTING LIGHTING FIXTURES SWITCH AND SMOKE DETECTORS TO
REMAIN.
PROVIDE NEW FIRE ALARM VISUAL UNIT TIE INTO EXISTING SYSTEM.
PROVIDE (2) 2x2 RECESSED FLOOR FIXTURES TO MATCH EXISTING.
CONNECT TO EXISTING BRANCH WIRING. PROVIDE NEW SWITCH.
PROVIDE EXIT LIGHT TO MATCH EXISTING.
EXISTING LIGHT FIXTURES TO REMAIN.
EXISTING FIRE ALARM AUDIO / VISUAL TO REMAIN.
EXISTING SMOKE DETECTOR AND SPEAKER TO REMAIN.
1
2
3
4
5
6
7
8
9
10
11
12