By Revision/Date PINNACLE HEALTH TRISTAN …€¦ ·  · 2013-07-19list of drawings: architectural...

9
LIST OF DRAWINGS: ARCHITECTURAL CS - COVER SHEET A1 - TITAN MRI NEW FLOOR PLAN NEW CHILLER PAD PLAN PARTIAL DEMOLITION PLAN A2 - BSMT. EQUIPMENT ROOM PLAN S1 - STRUCTURAL DETAILS E1 - ELECTRICAL POWER PLAN E2 - ELECTRICAL LIGHTING PLAN M1 - BASIC MECHANICAL REQUIREMENTS - EQUIPMENT SCHEDULES M2 - BASEMENT & FIRST FLOOR MECHANICAL DEMO PLANS M3 - BASEMENT & FIRST FLOOR MECHANICAL PLANS TOSHIBA SITE SPECIFIC DRAWINGS C1 - COVER SHEET GN - GENERAL NOTES SECTION A A1 - EQUIPMENT LAYOUT A2 - MAGNETIC FIELD LAYOUT A3 - DETAILS A4 - EQUIPMENT ELEVATIONS A5 - EQUIPMENT ELEVATIONS SECTION S S1 - STRUCTURAL LAYOUT / BASE DETAIL SECTION P P1 - PLUMBING LAYOUT P2 - WATER COOLING FACILITIES CONFIGURATION P3 - PLUMBING / MEDICAL GAS DETAILS SECTION M M1 - MECHANICAL LAYOUT M2 - QUENCH PIPE DETAILS M3 - QUENCH PIPE DETAILS M4 - QUENCH PIPE DETAILS SECTION E E1 - ELECTRICAL LAYOUT E2 - ELECTRICAL SCHEMATIC E3 - ELECTRICAL DETAILS E4 - LINE FILTER PANEL E5 - POWER SYSTEM DIAGRAM / POWER QUALITY REQUIREMENTS E6 - CABLE LENGTH DIAGRAM (FOR INTERNAL USE ONLY) SUBMITTER INFORMATION COMPANY SUBMITTING PLANS: PINNACLE HEALTH SYSTEMS CONTACT PERSON: DANA KLINEPETER, CONSTRUCTION PROJECT MANAGER TELEPHONE NUMBER: 717-782-3168 CELL: 717-810-7553 ADDRESS: HARRISBURG HOSPITAL CAMPUS, COLE BUILDING 218 SOUTH SECOND STREET CITY: HARRISBURG STATE: PA ZIP: 17104-8700 FACILITY INFORMATION FACILITY NAME: PINNACLE HEALTH IMAGING ID NUMBER: COMPONENT NAME OR NUMBER: ADDRESS: 4518 UNION DEPOSIT ROAD CITY: HARRISBURG STATE: PA ZIP: 17101 COUNTY: DAUPHIN SCOPE OF PROJECT: CHANGEOUT EXISTING PHILIPS MRI TO A NEW TOSHIBA VANTAGE TITAN IN EXISTING FIRST FLOOR MRI EXAM ROOM Drawn Start Date Scale Checked Job No. Sheet Revision/Date TRADE EASTERN, INC. By PREPARED BY: NFPA 101 LIFE SAFETY CODE 2012 EDITION GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITAL AND HEALTH CARE FACILITY 2010 NEW TOSHIBA VANTAGE TITAN MRI INSTALLATION PINNACLE HEALTH TRISTAN RADIOLOGY SPECIALISTS UNION DEPOSIT 4518 UNION DEPOSIT ROAD, HARRISBURG, PA NOT TO SCALE 1ST FLOOR KEY PLAN 1 NOT TO SCALE BASEMENT KEY PLAN 2

Transcript of By Revision/Date PINNACLE HEALTH TRISTAN …€¦ ·  · 2013-07-19list of drawings: architectural...

LIST OF DRAWINGS:

ARCHITECTURAL

CS - COVER SHEET

A1 - TITAN MRI NEW FLOOR PLAN

NEW CHILLER PAD PLAN

PARTIAL DEMOLITION PLAN

A2 - BSMT. EQUIPMENT ROOM PLAN

S1 - STRUCTURAL DETAILS

E1 - ELECTRICAL POWER PLAN

E2 - ELECTRICAL LIGHTING PLAN

M1 - BASIC MECHANICAL REQUIREMENTS - EQUIPMENT SCHEDULES

M2 - BASEMENT & FIRST FLOOR MECHANICAL DEMO PLANS

M3 - BASEMENT & FIRST FLOOR MECHANICAL PLANS

TOSHIBA SITE SPECIFIC DRAWINGS

C1 - COVER SHEET

GN - GENERAL NOTES

SECTION A

A1 - EQUIPMENT LAYOUT

A2 - MAGNETIC FIELD LAYOUT

A3 - DETAILS

A4 - EQUIPMENT ELEVATIONS

A5 - EQUIPMENT ELEVATIONS

SECTION S

S1 - STRUCTURAL LAYOUT / BASE DETAIL

SECTION P

P1 - PLUMBING LAYOUT

P2 - WATER COOLING FACILITIES CONFIGURATION

P3 - PLUMBING / MEDICAL GAS DETAILS

SECTION M

M1 - MECHANICAL LAYOUT

M2 - QUENCH PIPE DETAILS

M3 - QUENCH PIPE DETAILS

M4 - QUENCH PIPE DETAILS

SECTION E

E1 - ELECTRICAL LAYOUT

E2 - ELECTRICAL SCHEMATIC

E3 - ELECTRICAL DETAILS

E4 - LINE FILTER PANEL

E5 - POWER SYSTEM DIAGRAM / POWER QUALITY REQUIREMENTS

E6 - CABLE LENGTH DIAGRAM (FOR INTERNAL USE ONLY)

SUBMITTER INFORMATION

COMPANY SUBMITTING PLANS: PINNACLE HEALTH SYSTEMS

CONTACT PERSON: DANA KLINEPETER, CONSTRUCTION PROJECT MANAGER

TELEPHONE NUMBER: 717-782-3168 CELL: 717-810-7553

ADDRESS: HARRISBURG HOSPITAL CAMPUS, COLE BUILDING

218 SOUTH SECOND STREET

CITY: HARRISBURG STATE: PA ZIP: 17104-8700

FACILITY INFORMATION

FACILITY NAME: PINNACLE HEALTH IMAGING

ID NUMBER: COMPONENT NAME OR NUMBER:

ADDRESS: 4518 UNION DEPOSIT ROAD

CITY: HARRISBURG STATE: PA ZIP: 17101

COUNTY: DAUPHIN

SCOPE OF PROJECT:

CHANGEOUT EXISTING PHILIPS MRI TO A NEW TOSHIBA

VANTAGE TITAN IN EXISTING FIRST FLOOR MRI EXAM ROOM

Drawn

Start Date

Scale

Checked

Job No.

Sheet

Revision/Date

TR

AD

E E

AS

TE

RN

, IN

C.

By

PREPARED BY:

NFPA 101

LIFE SAFETY CODE

2012 EDITION

GUIDELINES FOR DESIGN AND CONSTRUCTION

OF HOSPITAL AND HEALTH CARE FACILITY

2010

NEW TOSHIBA VANTAGE TITAN MRI INSTALLATION

PINNACLE HEALTH TRISTAN

RADIOLOGY SPECIALISTS

UNION DEPOSIT

4518 UNION DEPOSIT ROAD, HARRISBURG, PA

NOT TO SCALE

1ST FLOOR KEY PLAN

1

NOT TO SCALE

BASEMENT KEY PLAN

2

EX

IS

T. W

IN

DO

W

CO

VE

RE

D B

Y W

ALL

TO

R

EM

AIN

SCAN

ROOM

CONTROL

9'-0"

7'-8" 7'-8"

3'-6"6'-0"

NEW FULL HT CABS.

EX

IS

T. W

IN

DO

W

CO

VE

RE

D B

Y W

ALL

TO

R

EM

AIN

5'-9"

1'-6"

CLR.

MRI

WOMEN'S

WTG.

3'-6"

5'-0"

5'-0"

NEW FULL

HT CAB'S

4'-0"

2'-5"

EXIST ELECT

PNL TO REMAIN

Drawn

Start Date

Scale

Checked

Job No.

Sheet

Revision/Date

TR

AD

E E

AS

TE

RN

, IN

C.

By

DEMOLITION LEGEND

1 REMOVE EXISTING DOOR AND FRAME.

2 REMOVE EXISTING PARTITION

3 REMOVE EXISTING CEILING TILE & GRID

4 REMOVE EXISTING FLOORING

5 PROVIDE NEW DOOR OPENING

6 REMOVE EXISTING WINDOW

7 REMOVE EXISTING MRI SHIELDED BOX

8 SHORE EXISTING FLOOR JOISTS FROM BASEMENT EQUIPMENT ROOM

BELOW. CUT & REMOVE EXISTING CONCRETE FLOOR SLAB AND METAL

DECK, SEE S-1 PLAN FOR NEW PAD METAL COLUMN SUPPORT AND

FLOOR PAD RECONSTRUCTION.

Scale:1/4" = 1'-0"

DEMOLITION PLAN

1

Scale:1/4" = 1'-0"

TITAN MRI NEW FLOOR PLAN

2

SCAN

ROOM

9'-0"

9'-0"

Scale:1/4" = 1'-0"

SCAN ROOM FLOOR CUT LOCATION

3

EXISTING MRI TO

BE REMOVED BY

OTHERS

4'-6"

4'-6"

VERIFY

ISOCENTER.

LOCATION

WITH TOSHIBA

PLANS

17'-5"

EQUIPMENT

ROOM

COMPUTER

ROOM

BASEMENT EQUIPMENT ROOM

PLAN A

1/4" = 1'-0"

LUNCH

ROOM

WOMEN

MEN

CORRIDOR

STAIR

FILE

STORAGE

LINE OF SLAB

ABOVE @ 9'-0"

A.F.F.

4'-0"

RELOCATE

PARTITION

AS SHOWN

COMP. EQUIP

TOP REMAIN

REMOVE

EXISTING

HVAC

CHASE

WALL

NEW TITAN MRI

ISOCENTER

10'-4"

10'-4"

8'-3"

7'-10 3/8"

9'-6 5/8"

Drawn

Start Date

Scale

Checked

Job No.

Sheet

Revision/Date

TR

AD

E E

AS

TE

RN

, IN

C.

By

8'-0"

9'-0"

14'-0"

9'-0"

2'-4"

6"

1'-10"

6" 6"9'-0" x 9'-0"

13'-0"

10'-8"

6" 6"

MRI PEDESTAL SECTION

SCALE: 1/2" = 1'-0"

MRI PEDESTAL PLAN @ 1ST FLR SCAN ROOM

SCALE: 1/2" = 1'-0"

℄ISOCENTER

SK-2

EX

IS

TIN

G 20K

5 B

AR

JO

IS

TS

, C

UT

JO

IS

T &

M

OD

IF

Y JO

IS

T B

EA

RIN

G

EX

IS

TIN

G 20K

5 B

AR

JO

IS

TS

, C

UT

JO

IS

T &

M

OD

IF

Y JO

IS

T B

EA

RIN

G

8'-0"

10'-0"

2'-0"

2'-0"

2'-0"

2'-0"

2'-0"

2'-0"

10'-0"

4"

1'-8"

10'-0" x 10'-0"

4"

3"

2"

1'-0"

BEAMS ASTM A992

TUBES ASTM A500 GRADE B

ALL STEEL PRIMER GREY

Drawn

Start Date

Scale

Checked

Job No.

Sheet

Revision/Date

TR

AD

E E

AS

TE

RN

, IN

C.

By

PARTIAL BASEMENT ELECTRICAL PLAN

1/4" = 1'-0"

MRI

EQUIPMENT

ROOM

LUNCH

ROOM

CORRIDOR

STAIR

S

S

4

13

11

MDP2

8

10

EXIST. LEIBERT

UNIT CU

MRI CHILLER

5

EXISTING

COMPUTER

RACK CU

EXISTING

COMPUTER

RACK CU

EXISTING

COMPUTER

ROOM CU

EXISTING PANEL LPB-1,

120 / 208 V, 3 , 4W

APC

LUXAIRE

APC

W.P.

W.P.

W.P.

W.P.

W.P.

7

6

6

TD

F

F

S

3

TD

2# 12 + 1# 12G IN 3/4"C

TO 20A-1P BREAKER.

2#12 + 1#12G - 3/4"C

TO 20A-1P BREAKER

3

S

3

12

W.P.

15

S

M

14

SEE NOTE2

1042

MECH.

1063

CHG

1062

CORRIDOR

1061

D.R.

1065

CORRIDOR

CONSULT

1060

HC.D.R.

1059

TOILET

1057

CONSULT

PAT.

CHG

PARTIAL FIRST FLOOR POWER PLAN

1/4" = 1'-0"

T.D. T.D.

NOTES:

EXTEND, 2# 12 + 1# 12 G

- 3/4"MC (H.G.) CABLE

TO PANEL LP-2.

PROVIDE BREAKER AS

REQUIRED.

EXHAUST FAN, EF-1, 1/4

HP, 120V, WITH BUILT-IN

DISCONNECT SWITCH.

PROVIDE WIRING PER

TOSHIBA DRAWINGS.

EMO

EMO

IN USE

1

RECONNECT TO

EXISTING BRANCH

CIRCUIT

EXISTING ELECTRICAL

PANEL, LP-2, 120/208V

RELOCATED RECEPTACLE,

CONNECT TO EXISTING

BRANCH WIRING

1

CONTROL

ROOM

MRI SCAN

ROOM

SEE NOTE 2

2

2

ELECTRICAL LEGEND

SYMBOL DESCRIPTION

RECESSED ROUND LIGHT FIXTURE, TYPE AS NOTED.

RECESSED FLUORESCENT LIGHT FIXTURE 2' x 2' OR 2'

x 4' AS INDICATED.

RECESSED FLUORESCENT LIGHT FIXTURE OR

EMERGENCY POWER.

DUPLEX CONVENIENCE RECEPTACLE 24" A.F.F.,

U.N.O.

DOUBLE DUPLEX CONVENIENCE RECEPTACLE 24"

A.F.F., U.N.O.

SWITCH SINGLE POLE

SWITCH 3-WAY

DIMMER SWITCH

TELEPHONE, DATA OR TELEPHONE / DATA AS NOTED.

EMERGENCY OFF BUTTON

DISCONNECT SWITCH, TYPE AS NOTED.

MOTOR, TYPE AS NOTED.

MANUAL MOTOR STARTER SWITCH

FIRE ALARM PULL STATION

FIRE ALARM AUDIO / VISUAL

FIRE ALARM VISUAL ONLY

SMOKE DETECTOR

SPEAKER

HOMERUN TO PANEL AS NOTED

BRANCH WIRING

EXIT LIGHTING FIXTURE ARROWS AS INDICATED

EMERGENCY BATTERY UNIT WITH 2 UNIT MOUNTED

HEADS

REMOTE MOUTNED EMERGENCY HEADS

U.F. UNFUSED

W.P. WEATHER PROOF

S

S

3

D

T.D.

S

M

F

F

F

S

S

LIGHTING FIXTURE SCHEDULE

TYPE A

6 1/2" ROUND RECESSED 150W INCANDESCENT

DOWNLIGHT W/ CLEAR ALZAK REFLECTORS SUITABLE

FOR USE IN MRI SCAN ROOM. SIMILAR TO

PEACHTREE LIGHTING CAT. NO. PMRI-7150-C.

TYPE B

6" ROUND RECESSED FLUORESCENT W/ (2) 26W PL

LAMPS, LOW IRIDESCENT CLEAR SPECULAR

REFLECTOR, AND DIMMING BALLAST.

POWER RISER DIAGRAM

N.T.S.

TOSHIBA

VRDU,

FOR MRI II

MRI

EQUIPMENT

ROOM

DRAKE

CHILLER

30 MCA

45 MOP

480V, 3

REMOVE EXIST. DISC.

SWITCH. PROVIDE

60A-3P U.F. W.P.

DISCONNECT SWITCH

REMOVE EXISTING

FEEDER, PROVIDE

3#6

1#10G

1"C

REMOVE EXISTING

CONDUCTORS

PROVIDE

3# 2/0

1# 2/0 G

EXISTING

2"C

REMOVE EXISTING 80A-3P BREAKER,

PROVIDE A 150A-3P SHUNT TRIP

ENCLOSED CIRCUIT BREAKER IN

BASEMENT EQUIPMENT ROOM,

WHERE INDICATED ON PLAN.

EXISTING PANEL MDP-2, 277/480V,

3 , IN MECH. / ELECT. RM 0004.

REMOVE EXISTING 80A-3P

BREAKER, PROVIDE, 150A-3P

BREAKER, MATCH A.I.C. OF

EXISTING BREAKERS.

REMOVE 30A-3P, PROVIDE

45A-3P BREAKER, MATCH A.I.C.

OF EXISTING BREAKERS.

ENLARGED

MRI EQUIPMENT ROOM PLAN

1/2" = 1'-0"

S

3

F

3

3

T

T.D.

1

F

F

MDP2

MRI

EQUIPMENT

ROOM

9

NOTES:

RELOCATE F.A. AUDIO-VISUAL UNIT, TELEPHONE OUTLET AND

EMERGENCY LIGHTING BATTERY UNIT TO NEW WALL AS INDICATED.

EXISTING 2' x 2' RECESSED FLOOR FIXTURES (TYP. FOR 6), RELOCATE

FIXTURES AS REQUIRED TO CLEAR NEW SUPPORT COLUMNS.

EXISTING SWITCH AND FIRE SUPPRESSION SYSTEM P.B. AND PULL

STATIN TO REMAIN.

EXISTING LIGHTING FIXTURES (8), SMOKE DETECTORS (2) TO REMAIN.

EXISTING CHILLER TO BE REMOVED BY OTHERS, NEW DRAKE CHILLER

FURNISHED BY TOSHIBA AND INSTALLED BY HVAC CONTRACTOR 30A

MCA, 45A MOP, 480V, 3 , SEE POWER RISER THIS DRAWING.

RELOCATE RECEPTACLES AND TELEPHONE TO NEW WALL.

RELOCATE EXISTING 100A-208 V, 1 PANEL AN FOR AUX. HEAT TO NEW

PARTITION, WHERE INDICATED.

EXISTING SHUNT TRIP BREAKER FOR MRI, SEE POWER RISER, THIS DWG.

VERIFY LOCATION OF NEW BREAKER.

NEW SHUNT TRIP BREAKER FOR TOSHIBA MRI II, SEE POWER RISER

THIS DWG.

EXISTING LIEBERT OUTDOOR UNIT AND FEEDER TO REMAIN.

EXISTING LIEBERT INDOOR UNIT AND FEEDER TO BE RELOCATED BY

HVAC, RELOCATE BREAKER AND FEED T NEW WALL.

NEW LIEBERT OUTDOOR UNIT, 5 TON, 11.7 FCA, 20A MOP, 480V, 3 ,

PROVIDE A 30A-3P, UF, WATERPROOF DISCONNECT SWITCH EXTEND 3#12

+ 1#12G - 3/4"C TO 480V, MRI EQUIPMENT PANEL IN 1ST FLOOR STORAGE

CLOSET, PROVIDE 20A-3P BREAKER , MATCH A.I.C. RATING OF EXISTING

BREAKERS.

NEW LIEBERT 570H INDOOR UNIT, 30, 3FLA, 40A, MOP, 480V, 3 , WITH

BUILT-IN DISCONNECT SWITCH, EXTEND 3#8 + 1#10GIN 1"C TO 480V MRI

EQUIPMENT PANEL IN 1ST FLOOR STORAGE CLOSET. PROVIDE 40A-3P

BREAKER, TO MATCH EXISTING BREAKER A.I.C. RATINGS.

IN-LINE EXHAUST FAN, .36 HP, 120V, 1 , PROVIDE MANUAL STARTER.

EXTEND 2# 12 + 1# 12G - 3/4"C TO 15A-1P BREAKER IN LOCAL PANEL.

DISCONNECT POWER TO ELECTRIC REHEAT BOXES. REMOVE BRANCH

WIRING TO EXISTING PANEL AN.

NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO

THE APPLICABLE NATIONAL ELECTRIC CODE,

STATE AND LOCAL CODES.

2. SEE TOSHIBA TITAN MRI DRAWINGS FOR

REQUIRED WIREWAYS, J/B'S, CONDUIT RUNS,

CABLE TRAYS, REQUIRED POWER AND

CONTROL INTERCONNECT WIRING AND

GROUNDING.

3. NEW DEXA ROOM 1069, PROVIDE A DEDICATED

20A, 120V CIRCUIT AND RECEPTACLE FOR THE

RELOCATED DEXA MACHINE. VERIFY EXACT

LOCATION OF THE RECEPTACLE, SEE DRAWING

CS (COVER SHEET) FOR DEXA ROOM LOCATION.

1

2

3

4

Drawn

Start Date

Scale

Checked

Job No.

Sheet

Revision/Date

TR

AD

E E

AS

TE

RN

, IN

C.

By

5

6

7

8

9

10

11

13

12

REFER TO

ENLARGED

PLAN BELOW.

14

15

FIRST FLOOR

LIGHTING DEMOLITION PLAN

1/4" = 1'-0"

1042

MECH.

1063

CHG

1062

1041

CORRIDOR

1061

D.R.

1065

CORRIDOR

CONSULT

CO

RR

ID

OR

1060

HC.D.R.

1059

TOILET

1057

CONSULT

PAT.

CHG

NEW WOMEN'S

MAMMO WAITING

MAMMO #2

MRI

1056

SUB WAITING

MAMMOGRAM

MEDICAL LIBRARY

CONTROL

1

S

S

S

3

4

EXISTING 2x4

PARABOLIC

F

F

2

EM

D D D D

4x4 WIREWAY

2

FIRST FLOOR LIGHTING PLAN

1/4" = 1'-0"

1042

MECH.

1063

CHG

1062

1041

CORRIDOR

1061

D.R.

1065

CORRIDOR

CONSULT

CO

RR

ID

OR

1060

HC.D.R.

1059

TOILET

1057

CONSULT

PAT.

MRI

SCAN ROOM

CONTROL

CHG

NEW WOMEN'S

MAMMO WAITING

MAMMO #2

EX

IS

T. W

IN

DO

W

CO

VE

RE

D B

Y W

ALL

TO

R

EM

AIN

MRI

WOMEN'S

WTG.

A A

AA

A A

S

S

A

A

1

S

5

EM

D1

D2

B

B

3

TO

EXISTING

BRANCH

WIRING

12

TO DIMMER

SYSTEM IN MRI

EQUIPMENT

ROOM BELOW.

2

2

F

4

F

7

S

6

S

F

RELOCATE

EXISTING FIRE

ALARM VISUAL

TO NEW WALL

E

8

9

F

S S

2

11

12

10

F

Drawn

Start Date

Scale

Checked

Job No.

Sheet

Revision/Date

TR

AD

E E

AS

TE

RN

, IN

C.

By

DEMOLITION NOTES:

EXISTING MRI SCAN ROOM, REMOVE ALL RECESSED INCANDESCENT

LIGHTING AND RELATED BRANCH WIRING. RELOCATE RECEPTACLES,

SPEAKERS AND SMOKE DETECTORS TO NEW SCAN ROOM. PROVIDE

NEW RECEPTACLE DEVICES, REMOVE EXISTING E.M. PUSHBUTTON.

EXISTING MRI CONTROL ROOM AND HALLWAY, REMOVE ALL

RECEPTACLES, SWITCHES, DIMMERS, WIREWAYS, E.M. PUSHBUTTONS

AND RECESSED INCANDESCENT LIGHTING. RELOCATE (3) 2x2 RECESSED

FLUORESCENT LIGHTS AND FIRE ALARM AUDIO VISUAL.

EXISTING MEDICAL LIBRARY, REMOVE EXISTING LIGHTING FIXTURES,

SWITCHES AND DIMMER SWITCHES. FIRE ALARM AUDIO / VISUAL AND

RECEPTACLE TO REMAIN.

RELOCATE EXISTING LIGHT FIXTURE AND RECEPTACLE.

1

2

3

4

NOTES:

RELOCATED SPEAKER.

RELOCATED LIGHT FIXTURE.

CONNECT BATTERY UNIT TO UNSWITCHED NORMAL LIGHTING ALT.

EXISTING FIRE ALARM AUDIO / VISUAL UNIT TO REMAIN.

RELOCATED SMOKE DETECTOR.

EXISTING LIGHTING FIXTURES SWITCH AND SMOKE DETECTORS TO

REMAIN.

PROVIDE NEW FIRE ALARM VISUAL UNIT TIE INTO EXISTING SYSTEM.

PROVIDE (2) 2x2 RECESSED FLOOR FIXTURES TO MATCH EXISTING.

CONNECT TO EXISTING BRANCH WIRING. PROVIDE NEW SWITCH.

PROVIDE EXIT LIGHT TO MATCH EXISTING.

EXISTING LIGHT FIXTURES TO REMAIN.

EXISTING FIRE ALARM AUDIO / VISUAL TO REMAIN.

EXISTING SMOKE DETECTOR AND SPEAKER TO REMAIN.

1

2

3

4

5

6

7

8

9

10

11

12

Drawn

Start Date

Scale

Checked

Job No.

Sheet

Revision/Date

TR

AD

E E

AS

TE

RN

, IN

C.

By

Drawn

Start Date

Scale

Checked

Job No.

Sheet

Revision/Date

TR

AD

E E

AS

TE

RN

, IN

C.

By

Drawn

Start Date

Scale

Checked

Job No.

Sheet

Revision/Date

TR

AD

E E

AS

TE

RN

, IN

C.

By