bscience integration A4 report
-
Upload
ken-wong -
Category
Art & Photos
-
view
79 -
download
2
Transcript of bscience integration A4 report
1
BUILDING SCIENCE 2 ARC3413
PROJECT 2 INTEGRATION PROJECT COMMUNITY LIBRARY
NAME: Ken Wong Chun Thim ID: 0315534
TUTOR: MR AZIM SULAIMAN
2
TABLE OF CONTENTS 1.0 LIGHTING CALCULATION (SPACE A)
1.1 DAYLIGHT ANALYSIS 3 1.2 ARTIFICIAL LIGHTING PROPOSAL 7 1.3 PSALI 11
2.0 LIGHTING CALCULATION (SPACE B)
2.1 DAYLIGHT ANALYSIS 12 2.2 ARTIFICIAL LIGHTING PROPOSAL 16 2.3 PSALI 20
3
SPACE A
DAYLIGHTING
According to MS1525, Daylight Factor distribution is as below.
Daylight Factor (%) Distribution
> 6 Very bright with thermal and glare problem
3 - 6 Bright
1 - 3 Average
0 - 1 Dark
The table shown below describe the nearest example to the idea of illuminance range.
Illuminance Example
120,000 lux Brightest sunlight
110,000 lux Bright sunlight
20,000 lux Shade illuminated by entire clear blue sky, midday
1,000 – 2,000 lux Typical overcast day, midday
400 lux Sunrise or sunset on a clear day (ambient illumination
<200 lux Extreme of darkest storm clouds, midday
40 lux Fully overcast, sunset/sunrise
<1 lux Extreme of darkest storm clouds, sunset/sunrise
4
Floor plans & section
Semi open air reading area with discussion tables on first floor level. Illuminance for this space is needed for reading and discussion activities to take place. The skylights provide reflected daylight into the space while the west façade is shaded by the brick façade system.
5
Floor Area (m2) 64.7
Area of façade exposed to sunlight (m2) 4(1.4x2) + 6(0.9x2) = 22
Required Illuminance, Lux from Daylight Factor (3% - 6%)
3.0% of daylight factor
𝟑𝟑% = 𝑬𝑬𝑬𝑬
𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐%
Ei = 600 Lux
6% of daylight factor
𝟔𝟔% = 𝑬𝑬𝑬𝑬
𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐%
Ei = 1200 Lux
Illuminance from the space , Lux 𝟐𝟐𝟐𝟐𝟔𝟔𝟔𝟔.𝟕𝟕 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐% = 𝟑𝟑𝟔𝟔%
34% x 0.1 = 3.4%
𝟑𝟑.𝟔𝟔% = 𝑬𝑬𝑬𝑬
𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐
Ei = 680 Lux
6
Based on the table for daylight factor in MS1525, the space has adequate uniform daylighting with the average value of 3.4 with illuminance of 680 lux.
Annual daylight factor analysis
Considering this is semi open air space for reading and discussion, the three tables located at the facade have slightly reduced light which provides a better environment for reading. The variety of light in this space allows both reading and discussions to take place in brightly lit areas.
1.5% of daylight factor
𝟏𝟏.𝟓𝟓% = 𝑬𝑬𝑬𝑬
𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐%
Ei = 300 Lux
The illuminance for the reading area is 300 Lux which corresponds to the standard of IES and MS1525 for reading activity.
7
SPACE A
ARTIFICIAL LIGHTING
Surface Reflectance Table
Function Material Colour Surface Type Reflectance Value
Ceiling Concrete finish Grey Absorptive 0.3
Wall Concrete with paint finishing
White Reflective 0.33
Window Glass Transparent Reflective 0.06
Type of luminaire used as showed below:
Type of fixture Mount fixing
Type of light bulb
LED
Wattage Range (W) 20 W
Colour rendering Index (CRI)
82
Colour Temperature (K) 2700 K
Colour Designation Warm White
Lumens 3000 lm
8
Location Space A
Dimension of room (m) Length (L) = 10.4m
Width (W) = 6.2m
Height (H) = 6.1m
Total Floor Area, A (m²) 64.7 m²
Type of Lighting Fixture Ceiling mounted
Height of luminaries (m) 3.5
Height of work level (m) 0.8
Mounting height (m) 2.7
Reflection factors Ceiling: 0.3
Wall: 0.3
Room Index, RI (K)
𝑅𝑅𝑅𝑅 = 𝐿𝐿 𝑥𝑥 𝑊𝑊
(𝐿𝐿 + 𝑊𝑊) 𝑥𝑥 𝐻𝐻
𝑅𝑅𝑅𝑅 = 10.4 𝑥𝑥 6.2
(10.4 + 6.2) 𝑥𝑥 6.1
= 0.64
Utilization factor, UF 0.3
Maintenance factor, MF 0.8
Number of light required
𝑁𝑁 = 𝐸𝐸 𝑥𝑥 𝐴𝐴
( 𝐹𝐹 𝑥𝑥 𝑈𝑈𝐹𝐹 𝑥𝑥 𝑀𝑀𝐹𝐹)
MS1525 recommended reading area to have illumination level – 400 Lux
𝑁𝑁 = 𝐸𝐸 𝑥𝑥 𝐴𝐴
( 𝐹𝐹 𝑥𝑥 𝑈𝑈𝐹𝐹 𝑥𝑥 𝑀𝑀𝐹𝐹)
= 400 𝑥𝑥 64.7(3000 𝑥𝑥 0.3 𝑥𝑥 0.8)
= 35.9
= 36 lamps
9
Spacing to Height ratio (SHR)
𝑆𝑆𝐻𝐻𝑅𝑅 = 1𝐻𝐻𝐻𝐻 𝑥𝑥 √
𝐴𝐴𝑁𝑁
𝑆𝑆𝐻𝐻𝑅𝑅 = 1
2.7 𝑥𝑥 √64.736
= 0.50
𝑆𝑆
2.7 = 0.50
S = 1.35
Fittings Layout Fittings Required = 10.41.35
= 7.7 = 8 Rows
Number of lamps in each row = 36 8
= 4.5 lamps = 5 lamps
Spacing along wall = 6.2 8
= 0.775 m
10
Mounted lights in green are of 5 lamps in 8 rows and extra lights in blue are added to cover the trapezoidal shape of the space. By using this fitting layout, the required illuminance of
400 lux can be achieved for optimal reading and discussion activities.
11
SPACE A
PSALI
By comparing the lighting contour analysis and fitting layout, the 40 (+8) luminaries can be controlled with three switches. The blue switches can be used when daylight is not available (early morning and night). The red switches will be switched on at around 3.00pm as there will be not enough daylight at that area. The green switches will only be switched on in the evening as daylight is available throughout the afternoon.
12
SPACE B
DAYLIGHTING
According to MS1525, Daylight Factor distribution is as below.
Daylight Factor (%) Distribution
> 6 Very bright with thermal and glare problem
3 - 6 Bright
1 - 3 Average
0 - 1 Dark
The table shown below describe the nearest example to the idea of illuminance range.
Illuminance Example
120,000 lux Brightest sunlight
110,000 lux Bright sunlight
20,000 lux Shade illuminated by entire clear blue sky, midday
1,000 – 2,000 lux Typical overcast day, midday
400 lux Sunrise or sunset on a clear day (ambient illumination
<200 lux Extreme of darkest storm clouds, midday
40 lux Fully overcast, sunset/sunrise
<1 lux Extreme of darkest storm clouds, sunset/sunrise
13
Floor plans & section
The space chosen is an outdoor reading and discussion area on the first floor and mezzanine level between first and second floor. There are two skylight openings from the sawtooth roof above. With a ceiling height of 6 metres.
14
Floor Area (m2) 56.0
Area of façade exposed to sunlight (m2) 9.2 x 2 = 18.4
Required Illuminance, Lux from Daylight Factor (3% - 6%)
3.0% of daylight factor
𝟑𝟑% = 𝑬𝑬𝑬𝑬
𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐%
Ei = 600 Lux
6% of daylight factor
𝟔𝟔% = 𝑬𝑬𝑬𝑬
𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐%
Ei = 1200 Lux
Illuminance from the space , Lux 𝟏𝟏𝟏𝟏.𝟔𝟔𝟓𝟓𝟔𝟔 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐% = 𝟑𝟑𝟐𝟐.𝟗𝟗%
32.9% x 0.1 = 3.29%
𝟑𝟑.𝟐𝟐𝟗𝟗% = 𝑬𝑬𝑬𝑬
𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐
Ei = 658 Lux
15
Based on the table for daylight factor in MS1525, the space has adequate uniform daylighting with the average value of 3.29 with illuminance of 658 lux.
Annual daylight factor analysis
This outdoor space is geared towards discussion areas, the two tables are located near the east facing façade of brick façade system. Although light is filtered from the façade, the skylight above provides ample sunlight for the discussion area to create a space with moderate temperature for the occupants while having ample light for activity. The inner reading area is located 500mm below the discussion area, therefore creates a space with comfortable lighting for reading. Based on the diagram above, the green area ranges from 2.5 – 4.0 daylight factor. The illuminance for the inner reading area is 600 Lux which very close to the standard of IES and MS1525 for reading activity of 500 Lux.
3.0% of daylight factor
𝟑𝟑.𝟐𝟐% = 𝑬𝑬𝑬𝑬
𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒙𝒙 𝟏𝟏𝟐𝟐𝟐𝟐%
Ei = 600 Lux
16
SPACE B
ARTIFICIAL LIGHTING
Surface Reflectance Table
Function Material Colour Surface Type Reflectance Value
Ceiling Concrete finish Grey Absorptive 0.3
Wall Concrete with paint finishing
White Reflective 0.33
Window Glass Transparent Reflective 0.06
Type of luminaire used as showed below:
Type of fixture Mount fixing
Type of light bulb
Fluorescent tube
Wattage Range (W) 36 W
Colour rendering Index (CRI)
82
Colour Temperature (K) 6500 K
Colour Designation Cool White
Lumens 2500 lm
17
Location Space B
Dimension of room (m) Length (L) = 14m
Width (W) = 4m
Height (H) = 6.1m
Total Floor Area, A (m²) 56.0 m²
Type of Lighting Fixture Ceiling mounted
Height of luminaries (m) 3.5
Height of work level (m) 0.8
Mounting height (m) 2.7
Reflection factors Ceiling: 0.3
Wall: 0.3
Room Index, RI (K)
𝑅𝑅𝑅𝑅 = 𝐿𝐿 𝑥𝑥 𝑊𝑊
(𝐿𝐿 + 𝑊𝑊) 𝑥𝑥 𝐻𝐻
𝑅𝑅𝑅𝑅 = 14 𝑥𝑥 4
(14 + 4) 𝑥𝑥 6.1
= 0.51
Utilization factor, UF 0.3
Maintenance factor, MF 0.8
Number of light required
𝑁𝑁 = 𝐸𝐸 𝑥𝑥 𝐴𝐴
( 𝐹𝐹 𝑥𝑥 𝑈𝑈𝐹𝐹 𝑥𝑥 𝑀𝑀𝐹𝐹)
MS1525 recommended reading area to have illumination level – 300 Lux
𝑁𝑁 = 𝐸𝐸 𝑥𝑥 𝐴𝐴
( 𝐹𝐹 𝑥𝑥 𝑈𝑈𝐹𝐹 𝑥𝑥 𝑀𝑀𝐹𝐹)
= 300 𝑥𝑥 56(2500 𝑥𝑥 0.3 𝑥𝑥 0.8)
= 28 lamps
18
Spacing to Height ratio (SHR)
𝑆𝑆𝐻𝐻𝑅𝑅 = 1𝐻𝐻𝐻𝐻 𝑥𝑥 √
𝐴𝐴𝑁𝑁
𝑆𝑆𝐻𝐻𝑅𝑅 = 1
2.7 𝑥𝑥 √5628
= 0.52
𝑆𝑆
2.7 = 0.52
S = 1.41
Fittings Layout Fittings Required = 14
1.41 = 9.9 = 10 Rows
Number of lamps in each row = 10 4
= 2.5 lamps = 3 lamps
Spacing along wall = 4
10 = 0.4 m
19
FITTING LAYOUT
Since the space is L shaped, the calculation is made from a rectangle (14m x 4m) then the bottom portion of that rectangle is rotated to form the L shape. Therefore, it is possible to achieve uniform distribution of light in this space.
20
SPACE B
PSALI
ILLUMINANCE ANALYSIS AT 5:30PM
By 5:30PM, the areas of the space drop below 150 Lux which is inadequate for reading and discussion activities.
By comparing the lighting contour analysis and fitting layout, the 30 luminaries can be controlled with two switches. One for the inner reading area and another for the discussion area. The blue switches can be used when daylight is not available (from 5:30 PM) and red switches at 4:30.