    BP KHAZAN PROJECT - HVAC SYSTEM DESCRIPTION &

    OPERATING PROCEDURE

     The HVAC system for SER building consists of two numbers of 

    Fresh air handling units(FAHU!" # FAHU!$%& four numbers air

    cooled condensing units(C'U!"& C'U!$& C'U! # C'U!)%& *+e

    numbers Ceiling sus,ended ty,e '- s,lit units. /attery room

    +entilation ,ur,ose ha+e ,ro+ided two e0tract fans duty ,lus

    stand by basis.

    Control room and battery room ,ressurisation ,ur,ose fresh airhandling units are used. Control room is always maintained

    ,ositi+e ,ressure and battery room is maintained negati+e

    ,ressure.

    Each FAHU is connected with two condensing units('- ty,e%.

    FAHU with corres,onding condensing units are o,erating on duty

    ,lus stand by basis. Each FAHU is incor,erated with se,erate

    motori1ed +olume control dam,er to control the air +olume with

    its su,,ly air duct.

    FAHU!"('uty unit% selector switch is switched on& before the

    motor starts running& corres,onding motori1ed dam,er need to

    get $)!V su,,ly and the actuator need to energi1e and o,en the

    dam,er com,letely& minimum one minute time will ta2e for the

    full o,ening of dam,er. After the full o,ening of dam,er only the

    motor need to starts and corre,ondingly blower has to run. The

    motori1ed dam,er su,,ly need to retain during the FAHUo,eration.

    3hen the FAHU has get the start command then only the

    condensing unit need to get the start command. Each FAHU4s is

    tem,erature is controlled by indi+idual thermostat.

  • 8/17/2019 Bp Khazan - Hvac System Description

    2/3

    'uring the change o+er time& FAHU!"('uty unit% will come to o5 

    ,osition& and duty unit4s motor with blower will come to sto,

    ,osition.

    Automatically through /6S command the rele+ant motori1ed

    +olume control dam,er will go for closed ,osition.

    'am,er o,en 7 close ,osition of status (Feedbac2% is gi+en as+olt free contact (VFC% to monitor the E8' 8anel

    Ad9ustable $) hour timer is ,ro+ided to achie+e our run hour

    control logic and duty change o+er time control logic. Howe+er&

    normally it is recommended by maufactrer is : to "$ Hrs&

    inaddition that this ad9ustable time will hel,s to achie+e our own

    ,ro9ect re;uirements and it could be in line with our site

    re;uirements.

  • 8/17/2019 Bp Khazan - Hvac System Description

    3/3

    =n this system can monitor the blower rotation and other status

    such as *lter clogging& air >ow failure. System has ,ro+ided air

    >ow switch in the su,,ly air duct for the blower rotation.