BOLTED CONNECTIONS IN S - COnnecting … · This thesis aims to investigate the characteristics and...

93
Faculty of Engineering, Health, Science and the Environment School of Engineering and Information Technology BOLTED CONNECTIONS IN STRUCTURAL STEELWORK Author: Cielo Marie Alvaran s213623 A thesis submitted in partial fulfilment of the requirement for the degree of Bachelor of Engineering Co-Op Thesis Supervisor: Professor David Lilley Professor of Structural Engineering at Charles Darwin University June 2014

Transcript of BOLTED CONNECTIONS IN S - COnnecting … · This thesis aims to investigate the characteristics and...

Faculty of Engineering, Health, Science and the Environment

School of Engineering and Information Technology

BOLTED CONNECTIONS IN

STRUCTURAL STEELWORK

Author:

Cielo Marie Alvaran

s213623

A thesis submitted in partial fulfilment of the requirement for the degree of

Bachelor of Engineering Co-Op

Thesis Supervisor:

Professor David Lilley

Professor of Structural Engineering at Charles Darwin University

June 2014

Abstract:

This thesis aims to investigate the characteristics and structural properties of bolted

connections in steel structures with the main focus on the design adequacy and failure

mechanisms of high-strength friction-grip (HSFG) bolted connections.

As a case study, the bolted connections on the Mary River Bridge along Arnhem Highway in

the Northern Territory have been investigated. The composite highway bridge is composed of

reinforced concrete deck over five simply supported spans of structural steelwork. The

structural steelwork includes five main UB girders connected to diaphragms and horizontal

bracings by HSFG bolted connections. Initial inspection of the bridge found that a number of

bolts were loosened, missing or had already fractured and most were heavily corroded.

Remedial works in which the original bolted connections have been replaced and the new

ones ensured to be installed at the correct tension have been recently completed.

The structural and environmental factors that may have contributed to the eventual failure of

the bolts have been investigated. The design adequacy of the bolted connections compared to

the externally applied loads on the bridge superstructure was checked in accordance with

current standards: AS5100 and AS4100. The failure mechanisms of the fractured bolts were

investigated. The residual loads on the original bolts have been identified through slip testing

on both the original bolts and new HSFG bolts in double shear configuration. The fractured

bolts were analysed through optical and scanned electron microscopy. The design fatigue life

of the bolts were identified through fatigue testing of the M16 bolts in double shear

configuration and the M22 bolts subjected to cyclic tensile load. The difference of the rate of

corrosion of the bolts with and without the zinc plate corrosion protection was also identified.

It was found that the main factors the contributed to the failure of the bolted connections at

the Mary River Bridge include overstressing of the bolts, the fluctuating loads, the eventual

abrasion and wear of the corrosive protection and the corrosive environment it was subjected

to. The failure mechanisms of the fractured bolts were mainly due to corrosion and fretting

fatigue. Similarly, the bolts subjected to tension, have failed due to self-loosening over time.

Keywords:

highway bridge, HSFG bolts, modes of failure

ACKNOWLEDGEMENTS

I would like to express my gratitude for the constant guidance and unwavering patience of

my supervisor Prof. David Lilley.

I’m also grateful to Richard Underhill, Krishnan Kannoorpatti and Margarita Vargas for their

feedbacks and guidance.

Undertaking this thesis has been challenging and completing this report would not have been

possible without the guidance of these people, so again, thank you.

LIST OF TABLES

Table 1: UB members dimensions (Polsteel, 2012) ................................................................... 5

Table 2: Summary of Bolt types and categories (GAA) .......................................................... 11

Table 3: Corrosion rate of steel and zinc in C3 zones (GAA, 2012) ........................................ 14

Table 4: Permissible Loads on the Mary River Bridge according to the Report on Bridge

Load Capacities (1979) ............................................................................................................. 28

Table 5: Vertical and Horizontal Loads on the Bridge Superstructure over one span ............. 33

Table 6: Vickers Hardness Results ........................................................................................... 40

Table 7: Slip loads of Old and New bolts ................................................................................. 45

Table 8: Fatigue Testing Parameters ........................................................................................ 48

Table 9: Bolt Specimens Properties .......................................................................................... 50

Table 10: Total Surface Area exposed to corrosive media ....................................................... 50

Table 11: Weight loss after corrosion by immersion testing .................................................... 51

Table 12: Design Shear and Tension - Strength Limit State (Blacks Fasteners) ..................... 60

Table 13: Design Shear - Serviceability Limit State (Blacks Fasteners) ................................. 60

LIST OF FIGURES

Figure 1: Bridge Cross Section (DoW, 1968) ............................................................................ 5

Figure 2: Concrete Slab as top flange ......................................................................................... 8

Figure 3: Grillage System for a Two-Span Bridge (SCI, 2012) ................................................. 9

Figure 4: (a) Bearing and shear and (b) friction grip on a bolted lap joint (Gorenc, 2012) ..... 10

Figure 5: ASSHTO and Eurocode S-N curves (NHCRP, 2012) .............................................. 13

Figure 6: Life to First Maintenance of Hot Dipped Galvanized Steel (GAA, 2012) ............... 14

Figure 7: Percentage Error and Relative Cost in Bolt Installation (Fernando, 2001) .............. 15

Figure 8: Typical failure points of a bolt: (a) head fillet, (b) thread runout, ............................ 16

Figure 9: Joint Face Angularity (Bolt Science Limited, 2013) ................................................ 16

Figure 10: Major Steps in Conducting a Failure Analysis (Davidson, 1999) .......................... 18

Figure 11: Diamond Indenter for Hardness Test (ibid., p112) ................................................. 20

Figure 12: FHWA Transverse Wind Load Reactions at Pier bearings from Wind on

Superstructure ........................................................................................................................... 30

Figure 13: A160 Axle Load (SA, 2004) ................................................................................... 30

Figure 14: S1600 Stationary Traffic Load (SA, 2004) ............................................................. 31

Figure 15: M1600 Moving Traffic Load (SA, 2004) ............................................................... 31

Figure 16: M1600 loading position causing maximum bending moment over one span ......... 31

Figure 17: Horizontal Loads on a Bridge Span (in Plan View) ................................................ 32

Figure 18: Vertical Loads over a beam .................................................................................... 33

Figure 19: Resultant Shear Forces(maximum of 916kN at LHS support) ............................... 34

Figure 20: Bending Moment Diagram (maximum of 5127 kNm) ........................................... 34

Figure 21: Grillage Model of Bridge Span Superstructure ....................................................... 35

Figure 22: EDS Spectrum of Sample (prior to acid pickling) .................................................. 41

Figure 23: Macrographs of Fractured Surfaces for Sample A and Sample B .......................... 42

Figure 24: Shear Slip Testing Results ...................................................................................... 45

Figure 25: New M16 bolts loaded over slip critical load (Graph generated by software used

by the machine) ........................................................................................................................ 46

Figure 26: Old 5/8” bolts loaded over slip critical load (graph generated by use of raw data

from testing) ............................................................................................................................. 46

Figure 27: M16 and 5/8" bolts loaded over design slip capacity ............................................. 46

Figure 28: One Cycle of Load Applied .................................................................................... 48

LIST OF ILLUSTRATIONS

Illustration 1: Mary River Bridge (Bennett, 2013) ..................................................................... 5

Illustration 2: Mary River Bridge Telemetered Gauging Station (NRETA, 2007) .................... 5

Illustration 3: Mary River Bridge from the end abutment .......................................................... 6

Illustration 4: Inverted V brace at abutment ............................................................................... 6

Illustration 5: UB Diaphragm section ......................................................................................... 6

Illustration 6: EM Photomicrographs of Fracture Surfaces Exhibiting (a) Dimpled Fracture,

(b) Brittle Transgranular Fracture, (c) Intergranular Fracture, and (d) Fatigue Striations

(Shamsudin, 2011) .................................................................................................................... 19

Illustration 7: Test Fixtures for Slip and Cyclic loading (from left to right: M16 double shear

plates, M22 double shear plates, M16 2 bolts in tensile T-plates and M22 in tensile L-plates)24

Illustration 8: Set-up for Tensile Testing of M22 bolts ........................................................... 24

Illustration 9: Fractured 5/8" Bolt Samples A and B from bridge diaphragms ........................ 38

Illustration 10: Heavily Corroded 7/8" Nuts............................................................................. 38

Illustration 11: SEM micrograph at the outer surface .............................................................. 42

Illustration 12: SEM micrograph on fracture surface showing “indentations” .................... 42

Illustration 13: Surface Fractograph After Acid Pickling along a surface crack ...................... 43

Illustration 14: Surface Fractograph at Final Fracture .............................................................. 43

Illustration 15: Surface Fractograph at 500x Magnification .................................................... 43

Illustration 16: Surface Fractograph at 1000x Magnification .................................................. 43

Illustration 17: Surface Fractograph at 2000x Magnification .................................................. 44

Illustration 18: Bolt Fracture Surface ....................................................................................... 44

Illustration 19: Fatigue Cracks at the Bolt Fracture Surface .................................................... 44

Illustration 20: Slip Load Testing Setup ................................................................................... 45

Illustration 21: M22 tensile testing set-up ................................................................................ 47

Illustration 22: Corrosion by immersion set-up ........................................................................ 49

TABLE OF CONTENTS

1. Introduction .................................................................................................................................... 1

1.1. Background ............................................................................................................................ 1

1.2. Scope and Approach............................................................................................................... 2

2. Literature Review ........................................................................................................................... 4

2.1. The Mary River Bridge .......................................................................................................... 4

2.2. Bridge Loading ....................................................................................................................... 7

2.2.1. Bridge Design Loads ...................................................................................................... 7

2.2.2. Analysis of Composite Concrete and Steel Girder Bridges ........................................... 7

2.3. Bolted Connections ................................................................................................................ 9

2.3.1. Bolt Types and Properties .............................................................................................. 9

2.3.2. Design of High Strength Friction Grip (HSFG) Bolts.................................................. 11

2.4. Mechanical Modes of Bolt Failure ....................................................................................... 14

2.4.1. Overstressing ................................................................................................................ 14

2.4.2. Cyclic Loading ............................................................................................................. 15

2.4.3. Corrosion ...................................................................................................................... 16

2.5. Metal Failure Analysis ......................................................................................................... 17

3. Methodology of Analysis and Testing ......................................................................................... 22

3.1. Investigation of Design Adequacy of the Bridge Connections ............................................ 22

3.2. Failure Analysis of the Bolts Taken from the Bridge........................................................... 23

3.3. Methodology of Mechanical Testings Conducted ................................................................ 24

3.4. Corrosion by Immersion ....................................................................................................... 25

4. Investigation on Design Adequacy of Bolted Connections on Mary River Bridge ..................... 27

4.1. Mary River Bridge Loads ..................................................................................................... 27

4.1.1. Original Design Loads ................................................................................................. 27

4.1.2. Design Loads based on Current Standards ................................................................... 28

4.2. Bolted Connections at the Mary River Bridge ..................................................................... 34

5. Bolt Failure Analysis Results and Discussion .............................................................................. 37

5.1. Inspection of Conditions of Bolted Connections at the Mary River Bridge ........................ 37

5.2. Microstructure ...................................................................................................................... 39

5.3. Residual Loads ..................................................................................................................... 45

5.4. Fatigue Testing ..................................................................................................................... 48

5.5. Corrosion Testing ................................................................................................................. 49

6. Summary, Conclusion and Recommendations ............................................................................. 52

6.1. Summary of Findings ........................................................................................................... 52

6.1.1. Design Adequacy of the HSFG joints .......................................................................... 52

6.1.2. Bolt Analysis and Testing ............................................................................................ 52

6.1.3. Failure Mechanism of the HSFG bolts At Mary River Bridge .................................... 53

6.2. Conclusion ............................................................................................................................ 54

6.3. Recommendations ................................................................................................................ 55

6.3.1. Maintenance of Steel Structures ................................................................................... 55

6.3.2. Thesis Improvement ..................................................................................................... 55

6.3.3. Further Studies ............................................................................................................. 56

References ............................................................................................................................................ 57

Appendices ........................................................................................................................................... 60

Appendix A. Load Capacity of M16 and M22 bolts .................................................................. 60

Appendix B. Bridge Loading Analysis ...................................................................................... 62

1. Calculations of Loads on the Superstructure ........................................................................ 62

2. Microstran Analysis Reports ................................................................................................ 67

Appendix C. Specified Properties of 8.8/TF bolts ..................................................................... 76

Appendix D. Bolts, Nuts and Washers Inventory ...................................................................... 77

Appendix E. Equipment Used for Sample Preparation, Bolt Analysis and Bolt Testing .......... 79

Appendix F. Vickers Hardness Testing ..................................................................................... 80

Appendix G. Images from Optical and Scanned Electron Microscopy ..................................... 82

Appendix H. Mechanical Testings ............................................................................................. 83

1. One Set of Slip Load Graph from the Slip Testing Experiments ......................................... 83

2. Fatigue Testing Experimental Design .................................................................................. 83

1

CHAPTER 1

1. INTRODUCTION

1.1. BACKGROUND

Connections are essential members of a structure allowing the applied load to be transferred

effectively between the structural members and transmitted to the ground. For a steel

structure, these loads include the dead loads due to structural self-weight and all the external

loads to which the structure is subjected to. In bridges, these forces include the road traffic

loads, wind loads, forces due to water flow and many others as specified in relevant clauses

of the bridge design standards: AS5100 (SA, 2004). As the load applied on the system varies,

the structure must be capable of resisting the loading condition causing the most adverse

effect. Members of a structural steel framework are connected either by welding, riveting or

bolting. These connections must hence, be capable of transferring the design strength and

serviceability loads. As bridges experience cyclic loading conditions, the type of bolted

connections most commonly used for its superstructure are the high-strength friction-grip

(HSFG) bolts.

The design of bolted connections and the type of bolts used, vary depending on the loads the

structure itself is subjected to. Structural steel bolts are categorised according to grades and

methods of installation. Categories of bolts in steel construction include commercial bolts,

high-strength structural bolts and precision bolts (Gorenc et al, 2012, p206). Depending on

the modes of force transfer in which they are subjected to and allowance in slippage of

surfaces, the bolts are then further categorised as either bearing or friction type (ibid, p208).

The appropriate bolt type must be chosen in the design of the connection depending on the

nature and combination of loads. When the bolts are either in shear, in tension or loaded in

both shear and tension, the connections must be designed to conform to the strength and

serviceability limit states as specified in relevant clauses of AS4100 (Standards Australia,

1998).

As parts of the structure, connections are also subjected to the effects of environmental

conditions and repetitive loadings, if any. If exposed to oxygen and water, connections may

suffer from wet corrosion, in which, the rusting may occur rapidly (Ashby & Jones, 2005).

2

Due to fluctuating loads on a structure, its connections may hence also be subjected to fatigue

loading.

In AS4100, HSFG bolts of grade 8.8 are referred to as Grade8.8/TF bolts as As HSFG bolts,

specifically that of grade 8.8, otherwise referred to as Grade8.8/TF bolts in AS4100, is the

most commonly used bolt type connection in general structural steelwork (Barber, 1992), the

main focus of this thesis is investigating the properties both structural and environmental

affecting the life span of this type of bolted connection.

Mary River Bridge is a composite steel girders and concrete deck bridge of over 100m length

located along Arnhem Highway in the Northern Territory. The bridge has recently undergone

rehabilitation works in which the HSFG bolted connections throughout the superstructure

have been replaced. From inspection conducted by the Department of Infrastructure (DoI), it

was found that the majority of the bolts (from both diameters: 16mm and 22mm) in the

structure were either rusted or missing. This has then led to the question at hand of whether

or not these connections have failed prematurely, or before their design life span, and if so,

what may have caused said failures.

1.2. SCOPE AND APPROACH

The aim of this thesis is to investigate the characteristics and structural properties of bolted

connections in steel structures, specifically that of HSFG. This has been achieved through the

completion of the following tasks:

1. Intensive review of related literature of the following topics:

Types and designs of bolted connections on steel structures, including High Strength

Friction Grip (HSFG) bolts and other more conventional bolted connections, and

comparison of their material characteristics and structural properties,

Causes of failure on bolted connections on steel structures such as environmental

factors causing corrosion and crack propagation, and fatigue loading and thermal changes

on the structures causing yielding, loosening or unthreading of the bolts,

Metallurgical testing mechanisms and failure analysis,

Behaviour of bolted connections in response to application of dynamic loads on the

steel structure (such as fracture and loosening),

Standards for appropriate maintenance of bolted connections in structural steelwork.

3

2. Investigation of bolted connections on the Mary River Bridge along Arnhem Highway

through:

Determination and comparison of original design loads and loads causing most adverse

effects on the superstructure based on AS1170.0-2: Structural Design and AS5100.2:2004

Bridge Design Standard Design Loads and through finite element analysis,

Checking the adequacy of the design of the bolted connections in accordance with

AS4100.9: Design of Steel Structures: Bolted Connections.

3. Determination of causes of failure of the removed bolts from the existing connections on

the bridge and identification of material and structural properties of the existing bolted

connections, both from the removed original set of bolts and the new replacement bolts

through the following:

Metallographic examination of the original bolts through optical and scanned electron

microscopy,

Comparison of Vickers hardness of new and old bolts,

Slip testing as a measure of residual loads on the removed bolts compared to slip loads

of new HSFG bolts

Fatigue load testing to compare total service life of removed bolts to expected fatigue

life of bolts loaded to design loads

Corrosion by immersion testing of bolts with and without the zinc plating in different

corrosive media

4. From the research, analysis and testings as listed above, draw conclusions to answer the

following questions:

Have the bolts failed prematurely (or before expected end of service life)?

Are the bolted connections in Mary River Bridge adequate to resist the design loads

based on current standards?

What are the main causes of failure on the bolted connections of the bridge? And thus,

conclude on possible most common failure modes of HSFG bolts in structural steelwork.

4

CHAPTER 2

2. LITERATURE REVIEW

This chapter consists of the review of literature related to the main components of this thesis.

It includes the background research on the theories and similar past investigations related to

the thesis work found in various publications, as well as, a review of the design and history of

Mary River Bridge and its connections. This chapter includes a background on bridge loading

conditions and the design of its bolted connections, a study on various mechanical modes of

bolt failure and procedures for the analysis of metal failures and bolt testing. Brief summaries

and descriptions of some of the related publications are also included.

2.1. THE MARY RIVER BRIDGE

The Mary River Bridge is located at a section along Arnhem Highway with several

aggregates quarry sites nearby. Although, there is no nearby traffic counter in the area (the

closest of which is at the intersection of Arnhem Highway and Stuart Highway), a significant

percentage of the vehicles traversing over the bridge consists of loaded and unloaded trucks

from tipper trucks to multi-trailer transfer trucks.

The bridge is located within the Mary River Coastal Floodplain about 90km east of Darwin

(NRETAS, 2013). The floodplain is a large one but is poorly drained as instead of a direct

channel to the sea, the inflow diffuses over swamps and through tidal channels. The

floodplain thus experiences extended flooding over its wetland habitat areas. Over the years,

there have also been a major saltwater control program that have been implemented to

minimize saltwater intrusion in the floodplain (ibid.).

The three main sections of a bridge include the bridge deck, the superstructure (structural

steelwork or other) and the sub-structure (the headstocks and piers). The superstructure of

Mary River Bridge is made up of five equal spans of simply supported beams composed of a

concrete deck over five universal beam (UB) girders. The typical cross-section of the bridge

is illustrated in Figure 1 below The bridge was earlier constructed with three 762UB147

girders in 1968 and was then widened in 1972 with the addition of two 762UB197 girders of

the same web dimensions but higher flange width and hence, heavier sections (Department of

5

Works (DoW), 1968). Each beam was designed to span at 75ft centres (22.86m) and have a

total width of 24ft (7.315m).

Figure 1: Bridge Cross Section (DoW, 1968)

The section properties of the members are as tabulated below. As the UB members are bigger

than what is commercially available, the second moments of area about the X and the Y axes

were calculated.

Table 1: UB members dimensions (Polsteel, 2012)

Type Weight

[kg/m]

H: Web

height

[mm]

D:

Width

[mm]

d: Web

thickness

[mm]

h: Flange

thickness

[mm]

IX-area [mm4] IY-area [mm

4]

(H3d)/12 + 2* [(h3D)/12

+ h*D(H+h)2/4 ] (d3H/)12 + 2(D3h/12 )

762 x 267 UB

147

147 719 265.2 12.8 17.5 1.2897E+09 5.4401E+07

762 x 267 UB

197

197 719 268 15.6 25.4 1.9170E+09 8.1487E+07

The following figures are photographs of Mary River Bridge.

Illustration 1: Mary River Bridge (Bennett,

2013)

Illustration 2: Mary River Bridge Telemetered

Gauging Station (NRETA, 2007)

The second, third and fourth piers of the bridge can be seen in Illustration 1, where the pier in

which the river height gauge is adjacent to is the second pier along Arnhem Highway in the

outbound direction (also shown in Illustration 2).

6

Illustration 3: Mary River Bridge from the end abutment

The photograph in

Illustration 3 was taken from the end abutment of the bridge. It shows piers 3 and 4 and spans

4 and 5 of the bridge.

Illustration 4: Inverted V brace at abutment

Illustration 5: UB Diaphragm section

The figures below show the typical detail of the diaphragms and braces of the bridge. The

brace system (Illustration 4), positioned on each pier, is composed of sections similar to those

used in the girder. The diaphragms are located at the mid-span between each pier. In

Illustration 5, the bolt groups on the left are not aligned with those on the right as this view

shows the new beam at the left (from the 1972 widening) and the old beam (1968) at the

right. The horizontally oriented bolts at the diaphragms and the bracings are 5/8” in diameter

while the vertical bolts at the headstock and at the underside of the diaphragm-to-girder

connections are 7/8” diameter bolts. As these bolts are in imperial sizes, the replacement

bolts, as well as the bolts used for the experiments, were the M16 and M22 equivalent.

7

2.2. BRIDGE LOADING

2.2.1. BRIDGE DESIGN LOADS

The main bridge design loads covered in the book The Design of Modern Steel Bridges are

the dead loads, live loads, longitudinal forces on bridges, wind loading and thermal forces

(Chatterjee, 1991). Other possible sources of stresses on the superstructures were also

enlisted but have not been discussed in detail (ibid, p.74).

In AS5100.2: Design loads in bridge superstructures, the design loads include the following:

Dead Loads

Road Traffic Loads

Fatigue Load

Braking Forces

Collision Loads

Forces due to water flow and debris

Wind Load

Earthquake Load

(SA, 2004)

The bridge design live loadings from different guidelines, in different countries, vary not

only with the uniformly distributed loads and the axle loads, but also in terms of the number

of axles, axle width and the spacing between them. The American Association of State

Highway and Transportation Officials (AASHTO) specifications from the USA, BS5200-

1997 and Australia’s AS5100 stipulate different classes of vehicle loadings (Chatterjee, 1991;

SA, 2004).

According to Chatterjee (1991), the worst loading for 20m length bridge span is often caused

by more than three two-axled, medium-weight, compact vehicles rather than road-trains with

the heaviest loads and more axles (Chatterjee, 1991, p54). This implies that the heaviest loads

do not necessarily cause the most adverse effect and thus, in determining the design live

loads, analysis of the bridge response due to combination of various types of vehicles

traversing over the bridge must be conducted.

2.2.2. ANALYSIS OF COMPOSITE CONCRETE AND STEEL GIRDER BRIDGES

Composite construction of bridges has been practiced as an economical engineering

solution. In a composite steel and concrete bridge, the reinforced concrete slab is bonded to

the top of the steel girder and acts as part of its flange, as shown below (O’Connor, 1971).

8

In this configuration, the concrete, thus, effectively has two

main functions: (1) transmit the externally applied loads

(vehicle loads on deck) to the girder and (2) participate in

carrying the bending moments in the beam. By analysing the

concrete deck as effectively a section of the girder’s top

flange, the structural behaviour due to live loads can hence

be defined (ibid).

As the neutral axis of a composite section is at a higher depth on the UB, compared to when

UB is analysed alone, the stiffness and the section modulus of the composite section, are

hence also higher (Lawson & Wickens, 1992).

In concrete and steel-girder bridges, the structure is commonly made of a number of parallel

longitudinal members linked through a transverse system (ibid, p351).The load distribution in

this parallel girder system is complex and hence, special techniques are required in its

analysis. O’Connor (1971) states that for cases in which the main structure and the deck

beams are integral with a continuous deck slab, as is the case with the Mary River Bridge, the

load distribution can be analysed through two ways: (1) to subdivide the slab into areas

effectively acting as the upper flange on the steel girder beams or (2) subdivide the slabs such

that they are represented by additional transverse or longitudinal elements. The bridge is then

analysed as a grid system composed of longitudinal elements representing the parallel main

girders (topped with the concrete slab of the defined effective width) and transverse elements

representing the cross-girders, which in the case of the Mary River Bridge is the diaphragm at

mid-span and the braces on the piers.

The bridge analysis can be either a two-dimensional (2D) analysis or three-dimensional (3D).

The road traffic loads on the bridge can be analysed by simplifying the loading conditions

into two simple linear elastic models. The first beam being the cross-section in which the

steel girders act as pinned supports and the second beam is a simply supported beam

representing one span of the bridge between two piers. This method of analysis is both

simpler and quicker to carry out. However, it treats each beam as elastic and does not take

into account the transverse distribution of the loads over the concrete deck. The line beam

Figure 2: Concrete Slab as top

flange

9

also does not consider the effects of skew. This method is useful in preliminary design, but

may prove to be unrealistic in detail design (SCI, 2012).

In order to investigate the dynamic response of highway girder bridges, Huang and his

colleagues from the Department of Civil and Environmental Engineering in Florida (1995)

has modelled a girder bridge through the finite element method (FEM) as a grillage beam

system. In this system, the bridge is divided into grillage members, in both transverse and

longitudinal directions, with set node intervals. Shown in Figure 3 is an example of how a

two-span bridge is modelled as a grillage beam.

Figure 3: Grillage System for a Two-Span Bridge (SCI, 2012)

The grillage system can be applied through the use of Microstran Analysis and SAP2000

structural analysis software packages. In Microstran Analysis, the traffic loading condition

found to cause the most adverse effect can be found when analysed using simple linear

elastic models. This loading condition, together with the other design loads on the bridge

superstructure can then be applied in the grillage beam model of the bridge. A similar grillage

bridge can be modelled in SAP2000 wherein the traffic loads and the horizontal loads, such

as water flow and debris, can be modelled dynamically for a 3D analysis.

2.3. BOLTED CONNECTIONS

2.3.1. BOLT TYPES AND PROPERTIES

Bolts are categorised according to their property classes as either 4.6 commercial bolts, 8.8

high-strength structural bolts, or 8.8, 10.9 or 12.9 precision bolts (Gorenc, op cit). According

to Barber (1992) of The Steel Construction Institute (SCI), the most commonly used bolts in

10

structural connections are of grades 4.6 and 8.8. Each of these bolt connections must conform

to AS1111-1980 ISO Metric hexagon and commercial bolts and screws and AS/NZS1252-

1983: High-strength steel bolts with associated nuts and washers for structural engineering

respectively (Gorenc, op cit; SA, 1980; SA, 1983).

The three fundamental modes of force transfer in the design of individual bolts (in bolt

groups) are shear or bearing mode, friction mode and axial tension mode. The bolt axis for

the axial tension mode of force transfer is parallel to the applied external loads. This force

transfer is also applicable in combination with the other bolting categories as bolts are often

subjected to axial loads as well as the external forces being transferred (ibid). The bearing

and friction modes of force transfer are as illustrated in Figure 4.

Figure 4: (a) Bearing and shear and (b) friction grip on a bolted lap joint (Gorenc, 2012)

In shear or bearing mode, when the applied load acts perpendicular to the bolt axis, they are

transferred by shear and bearing on the connecting plies (GAA, 2011). In this mode, the

connection is allowed to slip until the bolts come in bearing contact (Gorenc, op cit). Similar

to the bearing mode, the loads in friction mode are transferred perpendicular to the bolt axis.

However, as the joints are designed to not allow for slippage under limit loads, the frictional

forces at the mating surfaces, as illustrated in Figure 1.b are able to resist external loads

(GAA & Gorenc, op cit). Both the 8.8/TB and 8.8/TF connections must be installed through

full tightening of the bolts (GAA, 2011). The following table, taken from a publication by the

Galvanizers Association of Australia, summarises the attributes of the different common bolt

types.

11

Table 2: Summary of Bolt types and categories (GAA)

Australian Steel Institute released publications by Hogan and Munter (2007) regarding the

bolting of steel structures containing tables summarising the attributes and design capacities

of different bolt types. The Steel Designer’s Handbook also includes such tables, as well as

discussion on the mechanisms of each joint type (Gorenc et al, 2012).

According to the Research Council on Structural Connections (RCSC), if the joint is

subjected to tensile fatigue loading, referring to the cyclic application of externally applied

service loads and prying force (if any), it must be designed to either be pre-tensioned or slip-

critical (2004).

Barber (1992) claimed that HSFG bolts of the general grade, as governed by the British

Standard (BS) 4395, amongst all the other bolt types, is the most commonly used type in

general structural steelwork. This thesis thus focuses on the design and properties of the

8.8/TF bolts.

2.3.2. DESIGN OF HIGH STRENGTH FRICTION GRIP (HSFG) BOLTS

AS4100-1998 defines friction-type connections as: “high-strength bolts tightened to induce a

specified minimum bolt tension so that the resultant clamping action transfers the design

shear forces at the serviceability limit state acting in the plane of the common contact

surfaces by the friction developed between the contact surfaces” (Standards Australia, 1998).

12

The design of high strength fully tensioned friction type joints differs from that of

conventional bolt connections as slip is required to be limited in the serviceability limit state

design (SA, 1998). Due to this, for 8.8/TF bolted connections, the strength and serviceability

limit states are assessed separately in accordance with AS4100 clauses 9.3.2 and 9.3.3

respectively. As shown in Appendix A, the calculations for the tensile load capacity of a

friction tightened bolt vary for both the strength limit state and the serviceability limit state or

strength limit state, the tensile capacity is determined similarly to bolts of different grade.

However, for the serviceability limit state, the slip factor is considered. The nominal

capacities of bolts in tension, shear and combined shear and tension must be calculated in

designing for both the strength and serviceability limit states, and the design loads

transmitted through the bolted connection must not exceed these values.

According to Barber (1992), general grade HSFG bolts, as covered by the British Standard

(BS) 4395, has the strength of 8.8 bolts given that the nominal diameter is less than 24mm,

which is the case in the bolts utilised in the Mary River Bridge.

Based on ASSHTO LRFD Bridge design, the bridge’s design life is the “period of time on

which the statistical derivation of transient loads is based is 75 years” whilst its service life is

the time it is expected to be in operation (Bartholomew, 2009, p12). The expected service life

of the bridge depends on the original designer while its actual service life actually varies

according to various factors such as the structure’s exposure conditions, quality of design,

materials used upon construction and maintenance periods (ibid, p13). The indicative value

for the design service life of bridges is 100 years (ibid, p14). NHCRP (12) has conducted a

research testing of steel components of bridges under fatigue loading conditions and

compared with the S-N curves according the ASSHTO and Eurocode standards as illustrated

in the figure below.

13

Figure 5: ASSHTO and Eurocode S-N curves (NHCRP, 2012)

In Australia, hot dipped galvanized (HDG) steel are commonly used commercially as its

performance in the Australian atmosphere is relatively predictable and that compared to other

cathodic protection such as electroplating, zinc-plating and paint, HDG provides the thickest

coating and longer life to first maintenance (LFM) (GAA, 2012 & AMA, 2009). Shown

below is a chart of approximated LFM of HDG steel. The bolted connections in Mary River

Bridge are classified into C3 (medium corrosivity) due to its atmospheric environmental

conditions and although the bridge itself is not directly adjacent to the coastal region, as

previously mentioned, the site has experienced salt water intrusion (GAA, 2012). From the

chart below, it could be seen, that the LFM of HDG steels in C3 classified zones within

Australia varies from 21 to 40 years depending on the thickness of the zinc corrosion

protection layer on the steel.

14

Figure 6: Life to First Maintenance of Hot Dipped Galvanized Steel (GAA, 2012)

GAA also developed a table based on ISO9223Corrosion of metals and alloys which

included the rate of corrosion of carbon steel and zinc in the different corrosivity category

(20112).The values for C3 classified zone are as tabulated below.

Table 3: Corrosion rate of steel and zinc in C3 zones (GAA, 2012)

Unit Carbon Steel Zinc

g/(m2a)

grams per square metre per year

200 to 400 5 to 15

µm/a

Recalculated in micrometres per year

25 to 50 0.7 to 2.1

2.4. MECHANICAL MODES OF BOLT FAILURE

Bolts generally fail due to one or a combination of overstress, fatigue and corrosion (Buda,

1994).

2.4.1. OVERSTRESSING

The bolts are said to be overstressed if they are subjected to loads which are higher than what

their capacities allow. This may be the case if the design of the bolted connections is

inadequate compared to the loads they are actually subjected to. Overstressing of the bolts

due to tensile loads may be caused by the following:

Preload or torque of the bolts during installation exceeds specified preload and hence,

reduces the bolt’s axial tensile strength.

Loads transmitted by the bolted connection exceed its ultimate tensile strength, which may

cause fracture on the bolt. (Buda, 1994, p85)

15

Another cause of failure is due to improper torque upon installation. In a Steel Construction

journal by Dr. Fernando (2001), he has stated that using torque as a measure of tension can

lead to high percentages of errors as shown in Figure 7.

Figure 7: Percentage Error and Relative Cost in Bolt Installation (Fernando, 2001)

2.4.2. CYCLIC LOADING

When a structure or any of its components is subjected to a cyclic tensile stress, fatigue

failure may occur (Taylor, 2003). This failure is characterised by an incremental propagation

of a fatigue crack on the material caused by each stress cycle (ibid, p25). Din and Ghazali

(2004) claims that currently, in designing steel structures subjected to fatigue loading, the

focus of the designer is normally on the main structural elements. This has been observed in a

number of publications, wherein the focus is in selecting structural members after

determining the design loads as the importance is on the internal stresses induced and the

displacements due to the externally applied loads and does not discuss connections

requirements in as much detail. They also claim that there is a presumption that fatigue

failure is not likely to happen and that bolt connections do not play a major role in resisting

such loads (ibid, p20). However, this has not been the case for structural collapses that have

occurred due to insufficient fatigue resistance on the bearings (ibid). The cyclic stresses, due

to alternating applied loads on the bolts, from the pre-load torque to the externally applied

service loads, may cause for failure below the bolt’s rated tensile strength (Buda, 1994).

16

Fatigue failure on bolts normally occurs on points where there is a change in the cross-

sectional area as shown in Figure 8. The joint face angularity, as indicated in Figure 9, caused

by uneven joint surfaces, also affects the fatigue life of a bolt.

Figure 8: Typical failure points of a bolt: (a)

head fillet, (b) thread runout,

(c) first thread to engage the nut (Hobson. 1997)

Figure 9: Joint Face Angularity (Bolt Science

Limited, 2013)

2.4.3. CORROSION

Corrosion is the process of material degradation due to exposure and hence, chemical or

electrochemical interaction with its environment. As metal reacts with its environment,

various types of metallic corrosion may occur (ACA, 2013). The metal may reach a point in

which it is no longer capable of functioning to its original design capacity due to corrosion in

which case, it is said that corrosion failure has occurred. Bolted connections are often coated

to prevent this; however, over time, the coating themselves corrode and hence, the outer layer

of the bolts themselves begin to corrode. Bolt failure due to corrosion is either in the form of

chemical decomposition, galvanic corrosion, corrosion fatigue or stress corrosion cracking

(Buda op cit).

Often, corrosion and fatigue both contribute to the eventual failure of a mechanical

component in failure modes including stress corrosion cracking (SCC), fretting corrosion and

corrosion fatigue. As previously mentioned, high strength bolts are used in high tensile load

applications. When these types of bolts are in the presence of corrosive agents, stress

corrosion cracking may occur (ibid). The two factors determining the rate in which the

corrosion assists crack propagation are the stress on the bolt and the fracture toughness of the

material (Buda, 1994). Fretting corrosion, on the other hand, occurs when the contact

surfaces between materials subjected to repetitive motion cause abrasion and wear of the

material’s surface. In terms of bolts, fretting corrosion would be observed on the bolt shank

17

as the motion of the plates cause abrasion and wear on the bolt due to the vibration as effect

of externally applied fluctuating loads. The abrasion on the bolt threads essentially remove

the corrosion protective layer on the bolt allowing for accelerated corrosion attack to occur.

The causes of bolt failure are not limited to the earlier discussed ones. Determining the

causes of bolt failure will thus enable the engineers, in charge of the design phase,

maintenance and quality assurance, to take proper actions in preventing the same type of

failures from occurring.

2.5. METAL FAILURE ANALYSIS

ASTM’s Standard Guide for Corrosion-Related Failure Analysis is a guideline intending to

assist in an analysis wherein corrosion is a possible causative factor for failure of the material

(2013). The standard discusses the steps that may help an investigator in identifying relevant

corrosion information contributing to eventual failure. These steps include organising the

analysis, examination of failure site conditions, observation of operating conditions at time of

failure, records of historical information when available, careful sampling, evaluation of

samples and failure assessment (ASTM International, 2013).

The online article entitled The Consequences of Bolt Failures have several examples of bolt

failures that have been involved in what the author called “serious losses” referring to both

the structural and economic damages (Roberts, 2013). Photographs of failed bolts,

examination of the failure surface and description of their primary cause of failure have been

included. Davidson published a paper on failure analysis from a series of case studies of bolt

connection failures (1999). The procedure generally followed while conducting a

metallurgical failure analysis has been summarised as shown in Figure 10.

18

Figure 10: Major Steps in Conducting a Failure Analysis (Davidson, 1999)

Through visual examination, the fracture surfaces can be analysed in detail from which

possible causes of failure may be determined (Davidson, 1999). As each type of failure

results in a different fracture surface, comparison of the broken parts to recorded and

catalogued fracture surfaces available in various publications may hence be done.

Non-destructive tests (NDTs) can be done without permanently damaging the bolts (ibid.).

These tests are normally conducted in the field (prior to removal of bolts) to detect failures.

Metallographic examinations require for the samples to be sectioned (both longitudinally and

through its cross-section) to study its microstructure and thus, may be done in conjunction

with the mechanical testings. As the bolts are steel, hence ferritic, appropriate metallographic

preparation procedures must be followed (Struers, 1992). An optical microscopy evaluation

of the bolt sectioned about its cross-sectional and longitudinal axes will enable analysis of its

microstructure (Davidson, 1999). The properties determined from the microstructure are then

compared with those available in various literature.

Chemical analysis is done to determine the chemical composition of the material (Davidson,

1999). The chemical composition of the metal can be identified through Scanned Electron

Microscope (SEM).

Macrographs and photomicrographs of failure surface could also be produced though use of

SEM from which the fracture surface exhibited could be identified (Shamsudin, 2011). The

following images are SEM micrographs of fracture surfaces from which the type of failure

have been determined. The SEM micrographs from the fracture surface of the bolts from the

bridge could hence be compared with these images. Also through SEM, an Energy-

19

Dispersive X-Ray Spectroscopy (EDS) spectrum of the chemical composition of the surface

can be produced (ibid).

Illustration 6: EM Photomicrographs of Fracture Surfaces Exhibiting (a) Dimpled Fracture, (b) Brittle

Transgranular Fracture, (c) Intergranular Fracture, and (d) Fatigue Striations (Shamsudin, 2011)

Mechanical testings are carried out to verify whether the mechanical properties of the bolts

conform to relevant standards, in this case AS4291.1-2000: Mechanical properties of

fasteners made of carbon and alloy steel (SA, 2000). For checking whether the mechanical

properties of the bolts are within the range of values as specified in the standards, a hardness

tests was conducted.

The Vickers hardness test, as specified in AS4291.1, is one of the many types of hardness

tests available (SA, 2000). Ashby and Jones (2006) define the hardness tests as a loading of

an indenter (a pointed diamond for Vickers test) onto the material surface. The material

hardness (H) is determined by dividing the load (F) by projected area (A) of the indent (ibid.)

as shown in Figure 11. However, in the case of Vickers Hardness test, the Vickers Hardness

(Hv) derived is F over the indent’s total surface area as opposed to projected area and thus, H

must be found from the Hv value determined (ibid.)

20

Figure 11: Diamond Indenter for Hardness Test (ibid., p112)

As the yield strength of a metal is proportional to its hardness, an approximate tensile

strength can be derived from the hardness value determined through the relationship H=3y

where H=hardness and y= yield strength (Ashby & Jones, 2006). Alternatively, separate

tensile testing of the bolts could also be carried out.

As the bolted connections in the bridge are in different orientations, the connections can be

grouped into those subjected to mostly tensile loads (due to vertical loads on the deck), to

those subjected to only shear loads and to the connections that may be subjected to

combination of both tensile and shear loads. Due to this, research has also been conducted for

testing methodology in determining the residual loads on the bolted connections subjected to

different types of loading conditions.

8.8/TF bolted connections are designed to be loaded to their slip critical loads. Hirashima and

Uesugi (2004) have conducted an experimental study on the shear strength of HSFG bolted

joints at elevated temperature in which they have conducted slip loading tests of bolts

hardened at different temperatures. In this thesis, although the focus is not on temperature

difference, their testing methodology can be adopted to compare the slip loads of the imperial

bolts (5/8” and7/8” bolts from the original design) and slip loads of the new bolts (M16 and

M22) as the original bolts have already been exposed to loads causing work-hardening and to

a corrosive environment which have caused different levels of corrosion on the connections.

As the bridge is subjected to fatigue loads, one of the mechanical testings earlier proposed to

be conducted is a fatigue loading test. Din and Ghazali (2004) have conducted fatigue

loading tests on two sizes of HSFG bolts: 12mm diameter and 25mm diameter. They have

21

conducted mechanical testings, including tensile tests, to define the parameters of their

fatigue loading test. Young’s Modulus (E) and the Yield Strength (y) can be determined

through the tensile testing. They then proceeded to subject the bolt under cyclic constant

tensile loads (of 50% y for the smaller bolt and 30% y for the larger bolt) through a cyclic

sine wave loading of 8 to 10 Hz (ibid, p21). To establish the Stress-Number of Cycles (S-N)

Curve of the bolts, it was hence proposed to subject M16 and M22 bolts under fatigue

loading tests.

Vaious studies conducted regarding the fatigue life of bolted connections have been

reviewed. A study regarding the fatigue performance of HSFG bols of overlapped joints

conducted by H.Wang and his colleagues (2013) have analysed the fatigue life and damage

of HSFG bolted connections when loaded in a double shear configuration where the load is

applied on the middle plate (as shown below) and at varying friction coefficients through

finite element analysis. From their analysis, friction coefficients ranging from 0.4 to 0.6 have

resulted to fatigue life within the range of 107

cycles (Wang et al, 2013). A research on

estimation of fatigue life of bolt clamped in double shear lap joints included finite element

analysis (FEA) and fatigue tests of aluminium specimen have resulted to number of cycles in

the 105 to 10

6 range. A study on the different aspects of fatigue resistance of HSFG bolts with

large diameters by Prof.P.Schaumann (2008) dealt with the reduction of fatigue strength of

bolts with diameters larger than 30mm. The article included Stress to Number of Cycles

(S/N) curves for fatigue loading of high-strength bolts, as well as a chart showing the

decrease in the fatigue limit for an increase in the bolt diameter (Schaumann, 2008). Fatigue

testing of high strength M48 bolts in axial, bending and combined loading have been

conducted for said study from which testing in this thesis could be based on (ibid.).

The deterioration of a metal as its reaction to its environment is called corrosion (Byers, n.d.).

As corrosion is observed on the surfaces of the bolted connections, corrosion testing was also

proposed to be conducted. The rate of corrosion varies due to different factors including

moisture, temperature, and water quality and concentration differences of the corrosion

agents. There are several available standards and types of corrosion testing aiming to measure

the corrosion rate of a material including corrosion by immersion and electrochemical

testing. For this thesis work, the corrosion by immersion has been chosen.

22

CHAPTER 3

3. METHODOLOGY OF ANALYSIS AND TESTING

This section contains the methodology followed in the investigation of the bolted connections

on the Mary River Bridge. In this section of the thesis, the methods for the metal failure

analysis, calculation of design loads and allowable loads on the connections, as well as, the

procedure of the experiments conducted are discussed. The equipment used for the

experiments outlined in this section are found in Appendix E.

3.1. INVESTIGATION OF DESIGN ADEQUACY OF THE BRIDGE CONNECTIONS

To investigate the design adequacy of the bolted connections in the Mary River Bridge, two

main tasks are to: (1) identify the loads acting on the superstructure based on current

standards Compare values acquired to original design values and (2) calculate design loads

on bolted connections and compare these values on the calculated allowable loads on the

connections.

These tasks are conducted based on the following standards: AS5100: Bridge Design AS1170

Structural Design and AS4100: Design of Steel Structures. Microstran Analysis and

SAP2000 software packages were proposed to be utilised for the first task. However, after the

elements, nodes, traffic loading conditions were inputted in SAP2000, the dynamic 3D

analysis could not be conducted and thus, 2D analyses of the vertical loads and horizontal

loads were instead conducted using Microstran Analysis. As the main task was to determine

the loads at the location of the bolted connections and the maximum bending moment

induced along the bridge span and not the displacements and internal stresses throughout the

bridge superstructure, the use of 2D analysis should be sufficient.

The detailed methodology for this section has been further discussed in Section 4 of this

paper.

23

3.2. FAILURE ANALYSIS OF THE BOLTS TAKEN FROM THE BRIDGE

To analyse the failure mechanisms of the bolts taken from the bridge, the following steps

were followed:

1. Take an inventory of the 5/8” and 7/8” bolts removed from the side and record

observations.

2. Take 5/8” and 7/8” bolts from sections installed in 1968 and 1972 and prepare them

for metallographic investigation.

a. Cut sections of bolts from the 1968, 1972 and 2013 batches through their cross-

section and longitudinally,

b. grind the sectioned samples on coarse paper (80 grit),

c. mount the specimens by embedding them in resin epoxy stands,

d. polish specimens on different polishing surfaces (to 6µm).

e. Examine specimens through an optical microscope:

i. etching of the polished specimen in a nital solution for 30 sec

ii. examining the surfaces under the optical microscope of different magnification

iii. measuring corroded area around the bolt cross-section

iv. comparing the microstructure of the specimen with those in literature

f. Conduct Vickers Hardness Tests on both the cross-sectional and longitudinal

sectioned test specimens, in accordance with AS4192 as summarised:

i. apply HV0,3 loading in a series on the cross-section

ii. apply HV0,3 loading on the longitudinally cut specimens on the positions as

specified

iii. record the diagonals for each and calculate the hardness number and tensile

strength

3. Take fractured bolt surfaces and cut to a shorter length (less than 10mm) for SEM.

a. View specimen through SEM and take macro and micrographs.

b. Generate EDS graph of the specimens’ microstructure.

c. Submerge specimens in acid pickling solution to remove rust on the surface.

d. View specimen through SEM and take micrographs at similar magnification settings

as those in literatures for direct comparison

e. Analyse failure mechanism of bolts from the micrographs taken.

24

3.3. METHODOLOGY OF MECHANICAL TESTINGS CONDUCTED

The mechanical experiments required for this thesis work have been conducted in the Instron

machine (Appendix E) which required test fixtures to be designed for the bolt testings. The

test fixtures are flat, L and tee plates made of grade 350 structural steel designed to

dimensions that will allow for load application to the bolts’ theoretical slip loads without the

risk of plate tearing and with holes of the design standard diameter (2mm larger than bolt

shank) at allowable spacing from the edges and from other holes as specified in AS41000.9:

Design of Steel Structures: Connections (1998). A set-up of metal plates welded and

connected through threaded fasteners were also designed. The test fixtures designed and

machined are as shown below:

Illustration 7: Test Fixtures for Slip and Cyclic loading (from left to right: M16 double shear plates, M22

double shear plates, M16 2 bolts in tensile T-plates and M22 in tensile L-plates)

Note: The bolts placed through the above fixtures are not the ones tested – they were only

placed to hold the plates together initially. The M16 and M22 bolts tested were ordered to

the available length closest to the original imperial bolts from the bridge.

The set-up adjacent is composed of 2 T-sections made of

plates joined by full-penetration bevelled welds designed

to not fail before the M22 central bolt and 2 flat plates in

the middle. 8 threaded rods were used to connect each T-

section with a central flat plate. However, as shown, the

welding in the T-section have caused the plates to not

stay level and thus when the test specimen was placed in

Intron, bending was induced at the extreme ends from

Illustration 8: Set-up for Tensile

Testing of M22 bolts

25

the centre, causing for the failure to occur in the threaded

rods instead.

The steps followed for the slip and fatigue testing are outlined below:

1. Choose 3 sets of each of the following bolt groups: (a) 2x 5/8”, 2x M16, 2x 7/8” and

2x M22 bolts for slip testing in double shear configuration, (b) 2x 5/8”, 2x M16, 1x 7/8” and

1x M22 bolts for slip testing in tensile

2. Tighten bolts to specified preload for HSFG bolted connections of their bolt size

using the appropriate torque wrench and a DTI washer (also known as load indicating

washers). As the new bolts, nuts and washers were galvanized, the bolts were tightened until

the gap between the DTI washer and the plate was reduced to 0.025mm which was measured

by a feeler gauge.

3. Position test specimens on the Instron machine as shown below. After calibrating the

gauge length and zeroing the load applied by the machine, initiate axial testing and record

load in which the bolts begin to slip.

4. Plot theoretical and experimental slip loads.

5. From the slip loads determined, conduct fatigue load testing of new sets of bolts (M16

and M22) by subjecting the specimen in constant cyclic loading of constant amplitude of

70% the determined average critical loads of the new sets of bolts at low frequencies (no

more than 10Hz) to cycles of 500 000 to 2 000 000 cycles.

3.4. CORROSION BY IMMERSION

As previously discussed in Section 2.5, the corrosion test chosen was by weight loss through

immersion. From similar experiments in literature, the standard for this test and the

availability of materials, the methodology for this testing has been summarised below.

The aim of this test was to show the difference in the corrosion rate of the medium carbon

bolts when coated with corrosion protection layer and as plain bolts. This would show that

once fretting fatigue causes abrasion and wear on the coating of the bolts, the corrosion attack

is accelerated.

26

The equipment used for this experiment are as listed below:

Corrosive Media: Consistent volume of Tap water, Seawater (with approximately 3%

by weight of NaCl solution) and HCl (Hydrochloric Acid) 0.1mol in all 6 setups

6 250ml glass beakers, Teflon tape, sticks and weighing scale (accurate to 1mg)

6 M16 bolts, HCl acid, Distilled water

The experiment was completed by following the steps listed below:

1. Select 6 of the same type hot-dipped galvanised bolts.

2. Submerge 3 of them in concentrated HCl acid until zinc layer is completely removed.

After removing, wash specimens in distilled water and dry.

3. Measure initial values listed below to enable calculation of the bolt’s total exposed

area to the corrosion medium each is to be submerged in.

a. Sample weight,

b. Total length,

c. Length of head,

d. Length of unthreaded shank

area,

e. Minor diameter of bolt pitch,

f. Major diameter of bolt pitch (i.e.

also diameter of unthreaded area),

g. Width of side of hexagon (head)

4. Submerge bolts (up to where threaded area only for consistency and ease in exposed

area calculation)

5. Ensure volume of liquid in each set up stays consistent i.e. fill up with distilled water

to the same level.

6. After a set number of immersion days, note corrosion deposits observed (if any) on

the specimen, wash, and dry then weight sample again.

7. Calculate rate of corrosion of each.

27

CHAPTER 4

4. INVESTIGATION ON DESIGN ADEQUACY OF BOLTED

CONNECTIONS ON MARY RIVER BRIDGE

This section contains the discussion of how the design stresses on the bolts have been

determined, as well as, the comparison between the design loads and the allowable loads on

the bolted connections.

4.1. MARY RIVER BRIDGE LOADS

4.1.1. ORIGINAL DESIGN LOADS

In 1968, the bridge was originally designed to the following design loads:

Design maximum stream velocity: 8.5fps = 2.591m/s

Average stream velocity over one span: 7.5fps = 2.286m/s

Debris plus stream force loading 0.6 kips per ft run = 8.756kN/m

Live Loading: AASHTO H20-S16-44

Braking Load: 70% of one 83 Ton ore truck = 569.96kN

The loads in imperial units were converted into metric for ease in comparison with current

standards.

In May 1979, a report on Bridge Road Capacities on the NT bridges was prepared by

Cameron McNamara & Partners Consulting Engineers. The report contained computations

for the overload capacities of the bridge superstructures including the Mary River Bridge.

The document states that for bridges composed of steel girders and reinforced concrete deck,

“the overstress limits are 40% above the working stress limits” (ibid, 1979). The report

assumes the spacing between the two wheels in each axle to be 1800mm, where the allowable

bending moment and shear force are decreased by 3% when the spacing is at 1500mm and

increased by 2% when the spacing is 2100mm. From the report, the design bridge span was

22650mm and the permissible lane loads are as tabulated below.

28

Table 4: Permissible Loads on the Mary River Bridge according to the Report on Bridge Load Capacities

(1979)

Load Type Allowable

Stress

Mid-Span Bending

Moment (kNm)

Support

Shear (kN)

1 Two Lanes Working 2200 300

2 One Lane Working 2760 380

3 One Lane in Centre Working 3810 530

4 One Lane 50% Overstress 4000 650

5 One Lane on Centre 50% Overstress 5510 940

The above table includes the allowable loads on the bridge. However, the maximum bending

moment and shear force induced by the vehicle loadings, including the percentage impact by

which the loading should be increased, on the position along a span of the bridge that may

cause the most adverse effects, have not been determined. Different vehicle loading types

must be identified and moved along various points on the span. Through this, the maximum

bending and its location, as well as shear forces on the supports, can be identified for each

relative position of the loads on the beam. This is done through a series of influence line

diagrams in which the loads acting on the specific position along the beam are combined with

relevant uniformly distributed load. Once identified, the maximum bending moment and

maximum support shear could then be compared to the permissible loads in the table above.

4.1.2. DESIGN LOADS BASED ON CURRENT STANDARDS

The steel structure of the Mary River Bridge is composed of five main UB girders spanning

across four main headstocks between two abutments with secondary UB girders as

diaphragms located mid-span between the supports. Due to this design, the cross-section of

the bridge, is hence classified as an open-section as opposed to a closed section bridge cross-

section typical of bridges with completely closed steel cross-section, and as such, the internal

forces and moments in each bridge span must be analysed the way bridges with open cross

sections are analysed.

As previously mentioned, the bridge superstructure has a concrete deck which spans over the

girders. Throughout the concrete deck, there are shear connectors which effectively allow for

externally applied loads to act as uniformly distributed loads onto the structure.

As the case with simply supported beams, the maximum shear forces are found on the

supports and as such, the vertical loads acting on the deck including the dead loads of the

29

superstructure and the traffic loading condition causing the most adverse effect on the

structure are distributed such that they are acting on the bridge supports on which the

inverted V-braces are located. This then implies that when checking for load capacities of the

bolted connections all vertical loads and all induced bending moments are transmitted to the

connections on the supports.

The maximum moment and deflection on a simply supported beam with a uniformly

distributed load are located at mid-span; which in this case is where the diaphragms are

positioned. The forces transmitted onto the diaphragms are those of the lateral forces applied

on the deck which may include braking loads, drag forces and the reaction of the bridge due

to traversing vehicles.

The loads due to traversing traffic, as well as the self-weight of the reinforced concrete slab

on top must be determined to enable determination of loads on the bolted connections at the

bridge diaphragms and those at the inverse v-bracings. Similarly, the loads transmitted by the

bolted connection finally connecting the structural steels to the concrete headstocks can only

be determined after the dead loads and the traffic loading condition causing the most adverse

effect on the structure is determined.

The bridge responds to (mechanical, physical or chemical) actions in terms of action effects

including moments, stresses, support reactions and displacements (Hirt & Lebet, 2013). Hirt

and Lebet categories the types of actions identified for the design of a bridge to be

permanent, variable or accidental. The permanent loads include the self-weights of all

components of the structure and any prestressing force, the variable actions refer to the traffic

and climatic loads and the accidental actions are the very rare but have very high intensity

loads (ibid., 2013).

In order to analyse if the bolt connections in this bridge is under-designed in accordance with

current standards, the design loads must first be identified through AS5100.2. The loads

acting on the superstructure have been divided into vertical and horizontal loads. The bridge

is made up of 5 simply supported spans and hence, one span is analysed.

30

Figure 12: FHWA Transverse Wind Load Reactions at Pier bearings from Wind on Superstructure

The figure above is from FHWA’s design example with the same configuration (different

dimensions) as the Mary River Bridge cross-sections. As the document included calculations

of the loads for the design of the bridge, together with the standards, the example has served

as a basis for the calculations conducted in this section. One of the differences between the

FHWA’s sample problem and Mary River Bridge’s design is that the parapets on the design

example is a closed one while those on Mary River bridge are open. Relevant clauses in

AS5100.2 have been used for these load calculations. The Commentary for AS5100.2 have

also been used as guidelines.

The vertical loads include the permanent dead loads due to structural self-weight and the

imposed road traffic loads. The calculations of the loads are as shown in Appendix B.1 where

it was found that the dead load due to the self-weight was approximately 1009kN/span – as

the bridge is composed of 5 spans of the same lengths and includes the same components,

then each support should be able to hold the total of 1009kN. Over each UB girder in a span,

the uniformly distributed load is 11.04kN/m.

Each beam was then statically analysed for SM1600 loads,

referring to the stationary and moving traffic loads, and a series

of A160 axle loads as shown in Figures 12, 13 and 14 where the

axle loads were analysed as concentrated point loads along the

beam. The support reactions required were then calculated and a

dynamic factor of 35% was added onto the moving loads (SA,

2004). The HS20 truck loads as specified in AASHTO have axle

width of 1.8m while AS5100.2 specifies for 2.0 axle width (SA,

2004).

Figure 13: A160 Axle Load

(SA, 2004)

31

Figure 14: S1600 Stationary Traffic Load (SA, 2004)

Figure 15: M1600 Moving Traffic Load (SA, 2004)

Each vehicle load type was positioned over the 22.860m (75ft) simply supported bridge span

and the maximum bending moments and support reactions were derived through Microstran,

from which it was found that the loading type producing the maximum bending moment was

the M1600 when the front axle wheels are in line with the left hand support and the varying

axle spacing between the sixth and seventh axle is at its minimum of 6.25m, as shown in

Figure 16.

Figure 16: M1600 loading position causing maximum bending moment over one span

32

This loading condition (M1600 traffic loads positioned on a span as shown above) was then

used to calculate the maximum road traffic loads at each support with the appropriate factors

for the dynamic load allowance and the fatigue load effects following Clause 6: Road Traffic

Loads of AS5100.2 (SA, 2004). The value of the maximum total road traffic loads at each

support was calculated to be 3161kN. The total vertical forces due to traffic loads and dead

loads at each support was hence calculated to be 4170kN.

The ultimate and serviceability vertical wind loads acting on the bridge deck were also

calculated based on Clause16.6 of AS5100 and relevant clauses in AS1170.2 Structural

Design Actions Part 2: Wind Loads. The values for the ultimate and serviceability vertical

wind loads were calculated as 454.33kN and 166.24kN respectively over the surface area of

the bridge deck over one span.

Horizontal loads on the bridge include the braking forces of vehicles stopping at any point

along the bridge span. The braking forces are to be applied horizontally on the deck in

opposite directions.

The horizontal loads acting on the bridge superstructure are summarised in Figure 17 below.

Figure 17: Horizontal Loads on a Bridge Span (in Plan View)

33

Table 5: Vertical and Horizontal Loads on the Bridge Superstructure over one span

Action Load

(kN) Direction

Bridge deck and superstructure self-weight 1009.00 Vertical (uniformly distributed onto span)

Traffic Load (S1600) 2427.55 Vertical (on wheel axle lines)

Traffic Load (M1600 + dynamic, fatigue and other

factors) 3161.00 Vertical (on wheel axle lines)

Vertical wind load (Ultimate) 454.33 Vertical (uniformly distributed onto span)

Vertical wind load (serviceability) 166.24 Vertical (uniformly distributed onto span)

Braking Load (single vehicle stopping) 1337.00 Horizontal (longitudinal on bridge plan centreline)

Braking Load (multiple vehicle stopping ) 601.72 Horizontal (longitudinal on centreline of each of the

2 lanes)

Drag force on superstructure due to water flow (dry

season) Ultimate 3.96

Horizontal (longitudinal on bridge superstructure

centreline)

Drag force on superstructure due to water flow

(superstructure height) ultimate 6.86 Horizontal (longitudinal on bridge superstructure)

Drag force on superstructure due to water flow (5

year flood level) ultimate 7.81 Horizontal (longitudinal on bridge superstructure)

Drag force on superstructure due to water flow (dry

season) serviceability 3.10 Horizontal (longitudinal on bridge superstructure)

Drag force on superstructure due to water flow

(superstructure height) Serviceability 5.37 Horizontal (longitudinal on bridge superstructure)

Drag force on superstructure due to water flow (5

year flood level) Serviceability 6.11 Horizontal (longitudinal on bridge superstructure)

Transverse wind load (Ultimate) 94.65 Horizontal (transverse on bridge superstructure)

Transverse wind load (serviceability) 34.63 Horizontal (transverse on bridge superstructure)

Longitudinal wind load (Ultimate) 187.31 Horizontal (longitudinal on bridge superstructure)

Longitudinal wind load (serviceability) 68.53 Horizontal (longitudinal on bridge superstructure)

The loads acting on the bridge superstructure have been summarised in the above table. The

calculations for the values presented are attached in Appendix B.1.

From the above table, the braking forces as specified by AS5100.2 Clause 6.8.2 to be applied

in either direction horizontally on the bridge span is 601.72kN. However, as mentioned in

Secion 4.1.1, the bridge was earlier designed for braking forces of 569.96kN which signifies

an increase of 5% on the design braking forces.

The maximum bending moments induced by the combination of the dead loads and the traffic

loads causing the most adverse effect on the structure have been determined again through

the use of Microstran Analysis and compared to the maximum value earlier in Table 4.

Figure 18: Vertical Loads over a beam

34

The above figure shows the maximum vertical loads on the beam at the line of action of the

wheels of M1600 road traffic vehicle on the bridge deck, These loads include the vertical

wind loads, structural self-weight, axle loads and vehicle line loads. The shear forces and

bending moment diagrams along the beam as the resultant of the combination of the

externally applied vertical loads on the deck is shown in the figure below.

Figure 19: Resultant Shear Forces(maximum of 916kN at LHS support)

Figure 20: Bending Moment Diagram (maximum of 5127 kNm)

As shown above, the maximum moment induced by this loading condition is 5127kNm

which is within the maximum 50% overstress permissible bending moment of 5510kNm.

This implies that the maximum design loads are still within the permissible limits of the

bridge.

4.2. BOLTED CONNECTIONS AT THE MARY RIVER BRIDGE

The results from the linear models representing a UB girder member in each span loaded

with the vertical loads, as well as the different loads determined from Section 4.1.2 have been

inputted in Microstran Analysis at the grillage model of the superstructure of one bridge span

as shown below. The line-elements of the model represent the UB girder members,

diaphragm sections and the inverted V bracings at the supports and the nodes represent the

locations of the bolted connections. Rotation about the X, Y and Z saxes at the supports have

not been fixed as each bridge span essentially acts as a simply supported beam. Linear

35

models representing a UB girder member in a span have also been modelled for the traffic

loads.

Figure 21: Grillage Model of Bridge Span Superstructure

Combinations of longitudinal and transverse horizontal ultimate and serviceability loads (or

those acting at the X and Z axes) together with the vertical loads from the vehicle type and

position causing the most adverse effect on the beam have been analysed through the

software with factors based on AS1170.0: Structural Design Loading Combinations applied.

The longitudinal wind load and the drag force on the superstructure due to water load were

applied coming from the same direction as this would cause the worst combination on the

longitudinal forces. These combinations, as well as the reports generated by the software, are

attached in Appendix B.2.

From equilibrium equations, the node reactions at the X, Y and Z axes are then used as the

total load applied at each group of bolted connections located about those points. These loads

are included in the second Microstran report attached in Appendix B.2.

As shown in the above table the diaphragm-to-girder connections are only subjected to shear

forces and as such must be compared to the total design slip load of a connection with 12

M16 bolts..

The resultant support reactions at the Microstran generated report are calculated based on the

current design standards and the maximum total shear force at a diaphragm bolt group

connection in shear was found to be 261.26kN. As the nodes have 12 bolts, the shear load

each must resist is approximately 21.77kN. This is not the exact value as the strength of the

bolt group connection is not directly a product of the strength of one bolt and the number of

bolts in the connection. This value is however taken as the design for this thesis work as it is

36

an overestimation of the actual load. This design load is then compared with the slip critical

load of one M16 bolt loaded in shear.

As shown in Appendix A, the allowable design load for M16 varies from 16.30kN to

23.30kN with a reduction factor of 0.7 and depending on the kh factor for the hole type. The

slip critical load (the actual load in which the bolt will start slipping without the safety

reduction factor) for M16 bolts varies from 23.29kN to 33.29kN, again depending on the hole

type. As the holes on the structural steelwork for the bolted connections are standard sized

(with diameter 2mm larger than the bolt shank) and are positioned in a vertical manner as to

not have any stagger of the holes, kh is hence 1.0 (SA, 1998). The design slip load allowed

for M16 bolts according to the standards is 23.30kN (and the slip load is 33.29kN).

The design shear force applied of 21.77kN is less than 23.30kN and hence, the M16 bolts in

the diaphragm connection are still adequate in accordance with current standards.

37

CHAPTER 5

5. BOLT FAILURE ANALYSIS RESULTS AND DISCUSSION

In this section, the results of the testing as described in sections 3.2 to 3.4 are summarised.

Discussion of results for each test is also included at the end of each sub-section.

5.1. INSPECTION OF CONDITIONS OF BOLTED CONNECTIONS AT THE MARY

RIVER BRIDGE

An inventory of the original bolts from the bridge removed that were sent to CDU, as

tabulated in Appendix D, showed that the connections from which the most number of bolts

that have failed are those located at the diaphragm-to-web-girder connections, both those

oriented horizontally in shear and vertically at the underside of the steel in tension.

From Illustration 5 (in Section 2), it can be seen that there are a total of 6x 5/8” (equivalent to

M16) HSFG bolts on either side of a UB girder web. From the inventory, the bolts from these

sets of connections have showed the most number of bolts that are heavily corroded and were

either missing, has fractured in shear and showed indentations along the bolts such as

necking and abrasion and wear along the bolt shanks due to fretting. These bolts are designed

to be slip-critical and as such the necking and fretting along the bolts imply that the bolts

have been overstressed.

The other bolt group located on the UB diaphragms are the 4x7/8” bolts (replaced with M22

bolts) at the underside of the girder where the connections to the diaphragms are located.

From the inventory, these bolts have shown relatively uniform rusting along the bolt shanks

compared to the 5/8” bolts and there have not been any fractured bolt recovered. However,

there are a number of missing 7/8” bolts from the diaphragm connection sets that may be

attributed to the bolts have loosened over time, lost the pre-tension applied unto them upon

installation and have simply fallen off the bridge.

Also observed upon inspection, the bolted connections that have suffered the most corrosion

are those located at the abutments followed by those on the headstocks, both of which are the

sets of bolts connecting the steel structure on the concrete. Localised corrosion and corrosion

38

pitting have been observed on the connections, especially the ones on the abutments, due to

exposure of those areas to atmosphere, marine water and soil.

Depicted in the following images are two sets of fractured bolts from the bridge diaphragms

and nuts from the bridge.

Illustration 9: Fractured 5/8" Bolt Samples A and B from bridge diaphragms

Illustration 10: Heavily Corroded 7/8" Nuts

Two bolts have been investigated to represent all bolts from diaphragms that have failed.

Abrasion and wear along the bolt shanks were noted. The bolts have also already failed

before the painting works conducted on the bridge superstructure back in 2008. The fractured

bolts all sheared in the first thread to engage the nut. The part of the bolt that was in the nut

was cut, examined through an optical microscope and was used to check for material

hardness while the other part (the piece with the head and the longer shank length) was then

examined through Energy-Dispersive X-ray Spectroscopy(EDS) and SEM before and after

acid pickling. By analysing the sample through the aforementioned methods, the general

mode of failure of the sheared bolts could be determined.

39

5.2. MICROSTRUCTURE

The microstructure of the bolts were analysed through optical microscopy and compared to

optical micrographs available in literature as tabulated:

Optical Microscope Image Magnification Observation

5x magnification of

outer surface of

threaded area of a

1968 5/8” bolt

surface fretting and

corrosion of the protective

layer at low magnification

20x magnification of

5/8” bolt

Decarburization of bolt

surface, minimal layer of

corrosion protection layer

left

5x magnification of

5/8” bolt thread

Fretting corrosion at the

bolt shank

100x Magnification

taken about the

middle of the bolt

Shows micro-structure

similar to Medium Carbon

steel

The following table summarises the results from the Vickers Hardness testing conducted. The

measurements of the diagonals are attached in Appendix F.

40

Table 6: Vickers Hardness Results

Bolt Average Vickers

Hardness

Average Tensile

Strength (Mpa)

1968 M16 Bolt 1 Cross-section 292.4 935.7

1968 M16 Bolt 2 Cross-section 288.6 923.5

1972 M16 Bolt 1 Cross-Section 306.8 981.8

1972 M16 Bolt 2 Cross-Section 309.0 988.8

1968 M16 Bolt Thread 1 321.7 1029.3

1968 M16 Bolt Thread 2 326.7 1045.3

1972 M16 Bolt Thread 1 309.0 988.8

1972 M16 Bolt Thread 2 311.3 996.3

1968 M22 Bolt Thread 2 (Hv 1) 296.2 947.8

1972 M22 Bolt Thread 1 (Hv 0,3) 278.6 891.5

1968 M22 Bolt Cross-section 1 (Hv 0,3) 297.0 950.4

1972 M22 Bolt Cross-section 2 (Hv 0,3) 297.0 950.4

1972 M22 Bolt Cross-section 2 (Hv 0,3) 296.2 947.8

From the Vickers Hardness tests conducted, it was observed that the Vickers hardness (and

by association the tensile strength) of bolts installed in 1968 and their 1972 counterparts were

in the similar range. The hardness and tensile strength of 5/8” bolts were higher than those of

the 78” bolts. All values are also higher than the minimum values as specified in AS1252

(attached in Appendix C) and some of the M16 hardness are higher than the maximum limit.

The figure below shows the EDS spectrum of the failed bolt taken about the centre of the

sample. As shown, high levels of oxide were scanned due to the heavy corrosion deposits

found on the failed surface. Within the spectrum, it can be seen that chlorine and sodium

peaks are relatively close together implying there have been salt and chloride compound

levels in the river that have contributed to the corrosive environment of the bridge and its

bolted connections. No discernible zinc peaks have been observed implying low levels of

zinc from the protective layer were found on the surface of the corrosion deposit. The other

element peaks are those included in the alloy of the base metal (as specified in the tables in

Appendix C).

41

Figure 22: EDS Spectrum of Sample (prior to acid pickling)

The following images depict the fracture surface of the bolt samples viewed through an

optical microscope. The image on the left of Figure 23 shows that sample A has been

inappropriately pickled and dried which led to embrittlement and fibre filaments on the

surface whilst Sample B was pickled and dried with the appropriate acid and dried with

compressed air. Some corrosion is seen on the image at the right as this optical microscopy

image (and the SEM after pickling) were taken not immediately after pickling and hence,

corrosion of the base metal has commenced. Despite the fibre filaments on Sample A, it can

be seen that the bolts did not fail at the same overstress crack growth rate. As the two bolts

were from different diaphragm sections on the bridge, the difference in the fatigue striations

and final fracture can be attributed to the number of bolts missing from their bolt groups prior

to fracture of these bolts. From both samples, hairline fatigue cracks from the outer surface of

the bolts were observed and cracks that have propagated across the surface have been

observed under the microscope.

42

Figure 23: Macrographs of Fractured Surfaces for Sample A and Sample B

Fractographs of higher magnification taken from different areas of sample A before acid

pickling are shown in the images below. As shown, the striations, and hence by association,

the mode of failure cannot be identified in 70x magnification due to the debris including

corrosion deposits that were still on the metal. This was also the case for Sample B. The

images (Illustration 11 and Illustration 12)are taken using Back-scattered Electron in the

SEM. Illustration 11 shows the outer edge where the failure has begun with the fretting

damaged zone at the top left corner, the thinning of the zinc layer and the location where

there is more debris in the surface. Illustration 12 shows different levels on the surface,

however it cannot be said for certain whether these are indentations of the fatigue striations

as there have been a thick layer of rust on the fractured surface and these lines may be

attributed to those of the debris and not actual cracks or depression on the metal surface.

Illustration 11: SEM micrograph at the outer

surface

Illustration 12: SEM micrograph on fracture

surface showing “indentations”

43

After acid pickling, Sample B has been observed through the SEM in which the following

images have been produced:

Illustration 13: Surface Fractograph After Acid

Pickling along a surface crack

Illustration 14: Surface Fractograph at Final

Fracture

The above images were taken through Secondary Electron in the SEM after the corrosion

deposits on Bolt Sample B have been cleaned through pickling in 50% hydrochloride acid.

Illustration 13 shows the fatigue cracks along the surface approaching the final fracture while

Illustration 14 is that of the final fracture itself wherein multiple cracks can be seen.

Fractographs of different magnification of the failure surface at different points after acid

pickling were taken and shown in the following images. Illustration 15 shows magnified

fatigue striations on the bolt surface. Both Illustration 15 and Illustration 16 indicate fatigue

as the failure mode.

Illustration 15: Surface Fractograph at 500x

Magnification

Illustration 16: Surface Fractograph at 1000x

Magnification

44

The fatigue striations shown are not only

depicting striations but also suggests stress

corrosion cracking. A more magnified image was

hence taken, as shown in Illustration 17 which

indicate that there has indeed been intergranular

stress corrosion cracking which could be

attributed to long-term exposure to hydrogen,

oxygen and chloride. This implies that the bolts

failed due to a combination of overstressing,

fatigue and corrosion.

The cross-section of the other section of the fractured bolt (the part that was in the nut) was

mounted, polished and observed under an optical microscope as shown in the images below.

Figure 14(a) shows indentations on the fracture surface and it can be seen that there is

discoloration due to corrosion and area in which the corrosion protective layer is not evident.

Figure 14(b) shows a part of the shear surface where fatigue cracks can be seen.

Illustration 18: Bolt Fracture Surface

Illustration 19: Fatigue Cracks at the Bolt

Fracture Surface

The other photomicrographs taken are attached in Appendix G.

Illustration 17: Surface Fractograph at 2000x

Magnification

45

5.3. RESIDUAL LOADS

The testing methodology outlined in Section 3.3 has

been followed and the results have been tabulated

below. Shown in the image is the setup of the

experiment conducted. The Instron machine was

operated through a computer software that generated

graphs for slip loads and provides the raw data

recorded for testing so that the user could better

analyse the values.

The results of the slip loading test are as tabulated below.

Table 7: Slip loads of Old and New bolts

Type Slip Load (kN) From literature 42.00

From Appendix

A 46.60

Experimental:

M16 Bolts 39.90

Average

41.90

43.00 41.60 Experimental:

5/8" 20.00

Average

7.00

0.00 9.00 From literature 72.40

Interpolated

from Appendix

A

83.00

Experimental:

M22 Bolts 70.03 Average

75.56

73.62 75.28

Experimental:

7/8" Bolts 73.28 Average

50.23

65.60 73.30

From the table and figure above, the average slip load for the new bolts tested was 41.6kN

(20.8kN each bolt) while that of the old ones was 9kN due to how the bolts could not be

tightened to required pre-tension and as such the slip loads were more varied.

Illustration 20: Slip Load Testing

Setup

0

10

20

30

40

50

60

70

80

90

Slip

Lo

ad (

kN)

M16 (5/8") Bolts M22 (7/8") bolts

Theoretical Experimental: New Experimental: Old

Figure 24: Shear Slip Testing Results

46

M22 bolts, new and old, have also been subjected to slip testing, however, both sets of bolts

were tightened to required pre-tension as indicated by the gap in between the plates and the

load indicating washers as the old M22 bolts are not as heavily corroded as the old M!6 ones.

The slip load for 2 old M22 bolt was 65.6kN and for the new, it was 73.62kN. This indicates

that there was 89% residual load in the M22 bolts. The difference between the slip loads of

the new bolts compared to the theoretical values can be attributed to the use of torque wrench

and DTI washers that, according to literature (Figure 7) may result to up to 15% inaccuracy

in reaching the required tension upon installation or initial tightening of bolt.

Figure 25: New M16 bolts loaded over slip

critical load (Graph generated by software used

by the machine)

Figure 26: Old 5/8” bolts loaded over slip

critical load (graph generated by use of raw

data from testing)

Old and new M16 bolts where loaded over the slip critical load as shown in the graphs above.

From the separate data files generated for each testing, Figure 27 was hence generated. A

similar graph was plotted for one set of results for the M22 bolt slip testing in double shear

attached in Appendix H.

The old M16 bolts are heavily corroded that the

nuts could no longer be tightened to required

pre-tension and as such, did not reach a slip load

and behaved elastically, as shown in Figure 27.

This implies that no clamp loads were induced

on the M16 bolts and that the corrosion on the

bolts indicates they have reached their end of

service life and if left on the bridge, they would

have eventually sheared. As shown, once the

0

10000

20000

30000

40000

50000

60000

70000

0 1 2 3 4 5

load

(N

)

extension (mm)

Figure 27: M16 and 5/8" bolts loaded over

design slip capacity

47

slip load of the bolts were reached and the bolts are still loaded, the bolts behave elastically

such that the elongation starts increasing proportionally to the load. When both the old and

the new bolts were loaded over the slip resistance load (theoretical value of 46.6kN), when

removed from the set-up, the new bolts did not have a discernible difference along its length

while the old bolts have elongated and begun to bend.

For slip testing of the bolts in tensile configuration, the T and L sections were designed and

prepared. However, only one trial for each have been conducted for these testings. This is

because, slip critical load is essential for HSFG bolted connections loaded in shear

configuration and the tensile testing were conducted to observe the behaviour of the friction

tightened tensile joint when subjected to loads higher than its design allowable loads.

The set-up adjacent is composed of 2 T-sections made

of plates joined by full-penetration bevelled welds

designed to not fail before the M22 central bolt and 2

flat plates in the middle. 8 threaded rods were used to

connect each T-section with a central flat plate. It was

designed to allow for slip load testing of M22 tensile

bolt as the L pieces were designed for the fatigue

testing in which lower load amplitude to be applied.

However, as shown, the welding in the T-section

caused the plates to not stay level and thus when the

test specimen was placed in Intron, the adjusting of the

machine grips caused for the rods compress at certain

areas inducing unequal stresses which led to pulling

out of the bottom rods. Although, this testing did not

allow for the M22 bolt to reach slip critical load, when

the set-up was taken out of the machine, the M22 bolt

that was earlier tightened with a DTI washer was noted

to have loosened to a great extent. This suggests that

unexpected loading on friction tightened bolts

designed for tensile loads, self-loosening could readily

occur.

Illustration 21: M22 tensile testing set-up

48

5.4. FATIGUE TESTING

The parameters for the fatigue testing, as derived in Appendix H, are tabulated below.

Table 8: Fatigue Testing Parameters

Loading Condition Double shear Tensile

Bolt Size M16 M22

Test fixture flat plates L-plates

Test set-up

Bolt tension at installation 95 kN 175kN

Test frequency 10Hz 1Hz

Number of cycles tested 2,500,000 100,000

Load amplitude 35-45kN 15-100kN

The following graph represents one cycle of the fatigue testing

Figure 28: One Cycle of Load Applied

The M16 double-shear set-up was similar to that used in the slip testing but with wider plates

and the thickness of the central plates were increased and the outer plates decreased. Both

-60

-40

-20

0

20

40

60

0 0.02 0.04 0.06 0.08 0.1 0.12Load

(kN

)

time (s)

Cyclic Loading for M16 Bolts

33kN amplitude

45N amplitude

49

testing have not reached rupture, however, cracks were observed on the double shear M16

bolts set-up. Fatigue cracks were observed on the outer side of the middle plates. This could

be attributed to the thickness of the middle plate (10mm) being not sufficient for fatigue

testing such that the stress was concentrated on the plates rather than the bolts. However,

after 2,500,000 cycles, the M16 HSFG bolts have not loosened.

As the design experiment on the M22 bolts in tensile required load application of over 100kN

at 5Hz, as shown in Appendix H, the set-up was subjected to that high load amplitude

initially, however, cyclic testing at higher amplitude was not ideal in the system and hence

lowered until the parameters of the test was at 15kN amplitude at frequency of less than 1Hz.

As higher load and frequency was earlier applied, the set-up appeared to have already

loosened and would have failed earlier than the expected 500,000 to 2,500,000 cycles range.

5.5. CORROSION TESTING

The outline in Section 3.4 was followed and the

bolts have been submerged as shown in the

adjacent image. The corrosive media had the

following pH level: tap-water: 6.8, seawater: 7.9

and diluted HCl solution: 3.0.

The equation used to calculate the total surface

area exposed was derived as shown:

;

Where:

√ ,

,

For isometric bolts, the thread angle was kept at 60º and pitch diameter at 2mm and thus, the

surface area of the threaded area can be estimated as twice the same equation as that of the

unthreaded but multiplied to the length of the threaded area and doubled due to equilateral

triangle approximation caused by the thread angle.

,

Illustration 22: Corrosion by immersion set-

up

50

The initial measurements and approximate total surface area are as tabulated below.

Table 9: Bolt Specimens Properties

Plain or

Galvanized

Corrosive

Medium

Initial Dimensions of the bolt (mm)

Initial

weight (g) Total

Length

Minor

Pitch

Diameter

Major

Pitch

Diameter

Head

Height

Side of

Hexagonal

Head

Unthreaded

height

plain tapwater 70.37 13.72 15.77 9.96 26.44 20.41 126.69

plain seawater 70.50 13.79 15.72 9.93 26.34 20.57 126.41

plain

Hcl

solution 70.00 13.75 15.73 10.30 26.44 19.70 126.51

galvanized tapwater 70.35 14.03 16.03 10.31 26.49 20.04 129.50

galvanized seawater 70.18 13.92 16.04 10.21 26.41 19.97 129.62

galvanized

Hcl

solution 70.04 14.00 16.00 10.08 26.49 19.96 128.90

Table 10: Total Surface Area exposed to corrosive media

Bolt Specimen A(head) A(unthreaded) A(threaded) Total Surface Area (mm2)

1 1816.25 1401.82 4744.73 7962.79

2 1802.53 1404.04 4727.21 7933.79

3 1816.25 1362.19 4730.71 7909.15

4 1823.12 1412.84 4836.04 8072.01

5 1812.13 1410.45 4839.57 8062.14

6 1823.12 1405.42 4825.49 8054.03

The results of the corrosion by immersion test is tabulated below. After the last weighing, the

bolts were placed back in the corrosive media and again weighed after 3 days.

51

Table 11: Weight loss after corrosion by immersion testing

Bolt

Specimen

Weight before

immersion(g)

Weight after 7

days of

immersion (g)

Weight

loss (mg)

Exposed

Surface Area

(cm2)

Weight

loss/surface area

(mg/cm2)

1 126.691 126.419 272.00 79.63 3.42

2 126.513 126.445 68.00 79.34 0.86

3 126.509 125.734 775.00 79.09 9.80

4 129.500 129.496 4.00 80.72 0.05

5 129.618 129.548 70.00 80.62 0.87

6 128.901 128.140 761.00 80.54 9.45

Bolt

Specimen

Weight before

immersion(g)

Weight after 10

days of

immersion

Weight

loss (mg)

Exposed

Surface Area

(cm2)

Weight

loss/surface area

(mg/cm2)

1 126.691 126.389 302 79.63 3.79

2 126.513 126.417 96 79.34 1.21

3 126.509 125.693 816 79.09 10.32

4 129.500 129.477 23 80.72 0.28

5 129.618 129.477 141 80.62 1.75

6 128.901 128.134 767 80.54 9.52

From the results above, the bolts have experienced the highest corrosion rate when exposed

to the HCl solution with or without the protective layer. Bolt specimen 3 with the removed

protective layer had a weight loss of 4% more than the one with the zinc layer (Bolt 6) after 7

days and over 8% difference after 10 days. This was also the case for the bolts submerged in

tap-water (bolts 1 and 4) shows the increase in the corrosion rate of bolts after its corrosive

layer have worn off or have fretted when exposed to acidic corrosive media. On the other

hand, , the bolts with the protective layer exposed in the natural seawater resulted to weight

losses of higher rate than the plain ones. This shows that when exposed to corrosive media

with high salinity and have chloride compounds present (about 2 to 3% NaCl present in

seawater) the corrosion is also accelerated.

52

CHAPTER 6

6. SUMMARY, CONCLUSION AND RECOMMENDATIONS

6.1. SUMMARY OF FINDINGS

As discussion of each component of the results were included earlier, this section serves as a

summary of the findings as discussed in Chapter 4 and each sub-section of Chapter 5.

6.1.1. DESIGN ADEQUACY OF THE HSFG JOINTS

From the investigation in Section 4, the maximum moment induced by the design loading

condition with the most adverse effect on the structure is 5127kNm which is still within the

maximum permissible bending moment of 5510kNm when the bridge is overstressed by

50%. Also found was that the design shear force on the HSFG bolts at the diaphragm-to-

girder connections was 21.77kN for each bolt which was less than the 23.30 allowable design

load as per AS4100 and thus, the design of the M16 shear joints at the diaphragms are still

adequate in accordance with current standards.

6.1.2. BOLT ANALYSIS AND TESTING

Based on the inspection of the bridge before and during the bolt connections replacement

work. as well as, the inventory taken of the components of the bolted connections removed

from the bridge, the following have been observed:

- The bolted connections that were most heavily corroded were those at the abutments

where the metal is exposed to the atmosphere and the water, debris and soil that may get

concentrated underneath the bridge deck and on the steel on the abutments.

- The connections on the concrete headstocks have apparent localised corrosion from

which cracks on the concrete have propagated

- The bolted connections on the diaphragm have the most number of missing and

fractured bolts. The 5/8” bolts loaded in shear were also noted to have fretted shank areas and

deformation about the bolt neck.

53

From the slip testings conducted, the general trend found was that the old bolts when

retightened and tested have slipped at loads lower than the new bolts. This would imply that

there is a limit to retightening the bolts until which they would require immediate

replacement.

Based on both the literature review and the corrosion by immersion test conducted, the bolts

that had their corrosion protective layer removed prior to immersion have an increased

corrosion rate except for those submerged in seawater in which the HDG bolt have resulted

in a higher corrosion rate than its plain counterpart. From the corrosion test, it can hence be

concluded that the general trend for bolts that have fretted surfaces would be to experience an

accelerated corrosion and that when exposed to corrosive media with high salinity (and by

association, chloride content), the corrosion rate is also increased.

6.1.3. FAILURE MECHANISM OF THE HSFG BOLTS AT MARY RIVER BRIDGE

The following have attributed to the eventual failure of the HSFG bolted connections on the

Mary River Bridge:

a. Incorrect pre-tension on bolts upon installation and decreasing clamp force on bolts

over time

As the capacity of the HSFG bolts are dependent on the friction forces induced upon

installation, if not tightened to the correct torque (less than or more than required pretension),

the bolt may slip at a lower load than designed and will behave as snug tight connection

would and may eventually shear. In case of bolted connections in a group, as the case with

the connections on the bridge diaphragm, if the bolts are not tightened such that the pre-

tension on each of the bolts in the group are not similar, over time, as the structure is

subjected to fluctuating loads, the bolts with the least pre-tension upon installation may

loosen or shear and fall off leaving the rest of the bolts in the group to carry the same

maximum load but with less number of bolts in the group. The stress induced on each of the

bolt is hence, higher than what was originally designed.

b. Overstressing of bolts

If the loads to which the bolts have been designed to carry are less than the externally applied

loads, the bolts are overstressed. In slip-critical bolted connections, the slip resistance load

54

may be surpassed by the externally applied load or the bolted connection designed to be

subjected only in shear and experiences increased loads due to the structure’s internal

moments or combined shear and tension loading. Similarly, when bolts in tensile are loaded

over their design allowable loads, decrease in the clamp force is quickened.

For this thesis, the analysis conducted were all elastic and thus, the plastic effects of the stress

concentration over each bolt group was not analysed. Although each bolt in a bolt group must

withstand the highest load, the concentration of stress over the entire group is not equal and

failure of one bolt may lead to overstressing of the rest of the bolts.

c. Fatigue and Fretting Corrosion

Due to fluctuating loads to which the bridge superstructure is subjected to, the coated bolt

shanks would experience would begin to exhibit abrasion and wear, also known as fretting.

Fretting may also cause for a decrease in the cross-sectional area. Due to the wear of the

corrosion protective zinc layer, corrosion attack is hence accelerated.

6.2. CONCLUSION

The modes of mechanical failure of the bolted connections on the Mary River Bridge are a

combination of overstressed, fatigue and corrosion. Even if the bridge is not structurally

under-designed, it is subjected to fluctuating loads, failure will occur on loads less than the

design yield of the friction tightened bolts. Corrosion also lowers the design life expectancy

of the connections. Combined, both fatigue and corrosion contribute to decreasing the life

span of the bridge’s bolted connections.

The failure of the bolts have initialised at the threaded section of the bolt shank that was in

contact with the web girder plates. As the fretted surface no longer had the protection of the

zinc plate, the corrosion attack is accelerated and together with the fluctuating loads, as well

as the decrease in the clamp force on the bolts, lead to propagation of fatigue cracks and

eventual fracture of the bolts.

The life expectancy of bolted connections on structural steelwork is not only governed by the

ultimate limit states of the structural design and its metallographic properties based on the

standards and the chemical components increasing the design strength of the steel alloy, but

is also greatly affected by the fluctuation of the serviceability loads, the effect of the

55

environmental condition to the corrosivity and the interval and quality of inspection and

maintenance works.

Although the design loads may be lower than the loads that would cause immediate failure in

a system, it is important to allow for factors such as the structure’s dynamic response and the

fatigue effect of the loads in designing the bolted connections on a steel superstructure.

Similarly, allowances for rate of corrosion of the metals at the location of the bridge must be

taken into account when choosing the appropriate corrosive protection layer of a steel

structure and its components.

6.3. RECOMMENDATIONS

6.3.1. MAINTENANCE OF STEEL STRUCTURES

Steel structures in the Northern Territory are subjected to medium to high corrosivity due to

its tropical climate and geographical conditions as a significant portion is at a coastal region

and there are wide catchment areas and floodplains). Due to this, the inspection and quality

assurance of steel structures must be regularly monitored. It may be more beneficial

economically for shorter intervals between maintenance work to be implemented rather than

higher risks and more costly operations required when the components that are beginning to

fail are not recognized earlier.

6.3.2. THESIS IMPROVEMENT

In analysing material failure as a component of a structural steel work, the following tasks are

recommended to be incorporated in the methodology:

- Through Finite Element Method, analyse the following:

o dynamic response of the bridge in 3D

o stresses induced on the bolt as fluctuating loads on the system

- Conduct the following experiments:

o accelerated corrosion testing over a longer duration, with more test specimens and

using other corrosion testing (such as an electrochemical corrosion testing)

o fatigue testing of connections to rupture

56

o corrosion fatigue test on the joints in which the fatigue testing is conducted whilst the

test specimen is immersed in a corrosive media

6.3.3. FURTHER STUDIES

Research work and investigation on the following topics:

- Economic analysis on different maintenance practices to increase the serviceability life-

span of a structural steelwork

- Loads induced in the components of a bridge super-structure due to vibration as a

response of the bridge to the changing speeds of the traversing traffic

- Effect of varying salinity (airborne or otherwise), on the corrosion rate of a material

57

REFERENCES

ACA – see The Australian Corrosion Association

Ashby, M, Jones, D, 2005, Engineering Materials 1, 3rd

Edition, ISBN-10: 0080966659, Elsevier,

USA

ASTM – see ASTM International

ASTM Internatonal, 2013, G161-00 Standard Guide for Corrosion-Related Failure Analysis

Barber, H, 1992, Steel Designers’ Manual, 5th Edition, Chapter 23: Bolts, The Steel Construction

Institute, ISBN: 9780470775097, Blackwell Scientific Publication, Cambridge

Bartholomew, 2009, Design for Service Life, Bridge Birth Certificate & Concrete Structures

Management Concepts, [online] available via www.bridge.transportation.org

Bennett, C, 2013, Mary River Wilderness Retreat and Caravan Park told of man taken by crocodile

while swimming in Mary River, NT

Blacks Fasteners, n.d., Blacks Structural Fasteners, [online] available:

<http://www.gaa.com.au/index.php?page=bolting>

Bolt Science Limited, 2013, Joint Face Angularity, [online] available:

<http://www.boltscience.com/pages/nutfaceangularity.htm>, accessed October 2013

Buda, J, 1994, Why Bolts Fail, Machine Design, pp85-90, [online] available:

<http://www.rexnord.com/sites/Process/ringgears/Documents/Design%20-

%20Bolt%20Design%20and%20Avoiding%20Failure.pdf>,accessed October 2013

Byers, J, n.d., Corrosion Issues and Test Methods, [online] available:

<http://mwfmag.com/mwf/docs/Corrosion_STLE2010_2.pdf>

Cameron McNamara & Partners Consulting Engineers, 1979, Report on Bridge Load Capacities, NT,

via DoI NTG

Carbide Depot, n.d., Hardness Conversion Chart, [online] available:

<www.carbidedepot.com/formulas-hardness.htm>

Chatterjee, S, 1991, The Design of Modern Steel Bridges, Oxford BSP Professional Books, ISBN:

978-0-632-05511-1, Great Britain

Davidson, T, 1991, An Introduction to Failure Analysis for Metallurgical Engineers, TMS, [online]

available: <http://www.tms.org/Students/Winners/Davidson/Davidson.html>

Department of Natural Resources, Environment, The Arts and Sports, 2013, Sites of Conservation

Significance: Mary River Coastal Floodplain, online, available:

<http://www.lrm.nt.gov.au/__data/assets/pdf_file/0004/13927/13_mary.pdf>

Department of Works, 1968, Mary River Bridge Drawings, via DoI NTG

58

Din, K & Ghazala, M, 2004, Fatigue Life of Bolt Subjected to Fatigue Loading Condition,

International Journal of Engineering and Technology, Vol.1, No.4, pp.20-27

EPI (EPI Engineering), 2012, Fretting Corrosion, [online] available: <http://www.epi-

eng.com/mechanical_engineering_basics/fretting_corrosion.htm>, accessed April 2014

Federal Highway Administration, 2013, LRFD (Load and Resistance Factor Design) Steel Girder

Superstructure Design Example, [online], available:

<http://www.fhwa.dot.gov/bridge/lrfd/us_ds3.cfm>, accessed: March 2014

Fernando, Dr. S, 2001, An Engineering Insight to the Fundamental Behaviour of Tensile Bolted

Joints,[online] via: www.researchnet.net

FHWA – see Federal Highway Administration

GAA – See Galvanizers Association of Australia

Galvanizers Association of Australia, 2011, Bolting Galvanized Steel, [online] available:

<http://www.gaa.com.au/index.php?page=bolting> accessed: September 2013

Galvanizers Association of Australia, 2012, Atmospheric Corrosion Resistance of Hot Dip

Galvanized Coatings,

Gorenc, B, Syam, A, Tinyou, R, 2012, Steel Designer’s Handbook, 8th edition, ISBN-13:

9781742233413, Chapter 8, New South Publishing, Sydney, NSW

Hobson, P, 1997, The Hobson Update, Volume 13, ‘Typical Failure Locations of a Bolt’, Australia

Lawson, M, Wickens, P, 1992, Steel Designers’ Manual, 5th Edition, Chapter 21: Composite Beams,

The Steel Construction Institute, Blackwell Scientific Publication, Cambridge

Munter, S, 2007, High Strength Bolt Assemblies Certification to AS/NZS 1252/1996…Reject or

Accept?, Australian Steel Institute

National Cooperative Highway Research Program, 2012, Fatigue Evaluation of Steel Bridges,

Natural Resources, Environment and the Arts, 2007, Description of Telemetered Gauging Station,

National Research Board, via national-academies.org

NHCRP – see National Cooperative Highway Research Program

NORCAT, n.d., Corrosion Testing of Friction Bolts, [online] available:

<http://www.partshq.com/bolts.skema.corrosion.fulltest1.htm>, accessed October 2013

NRETA- see Natural Resources, Environment and the Arts

NRETAS – see Department of Natural Resources, Environment, The Arts and Sports

O’Connor, C, 1971, Design of Bridge Superstructures, Chapter 7: Parallel Girder Systems, Wiley-

Interscience, USA

Polsteel, 2012, Universal Steel Beam, [online] available: <http://polsteel.co.uk/steel-guide/steel-

sections/ub/>, accessed October 2013

59

RCSC – see Research Council on Structural Connections

Research Council on Structural Connections, 2004, Specification for Structural Joints Using ASTM

A325 and A490 Bolts, [online] via www.boltcouncil.org

Roberts, C, 2013, The Consequences of Bolt Failure, [online] available:

<http://www.croberts.com/bolt.htm> accessed October 2013

SA- see Standards Australia

SCI – See Steelconstruction.info

Shamsudin, S, 20011, Role of Scanning Electron Microscope (SEM) in Metal Failure Analysis,

[online] available:< http://emicroscope.blogspot.com.au/2011/03/role-of-scanning-electron-

microscope.html> accessed April 2014

Standards Australia, 1980, AS1111-1980: ISO metric hexagon commercial bolts and screws, via

SAIGlobal

Standards Australia, 1983, AS 1252-1983 High strength steel bolts with associated nuts and washers

for structural engineering, via SAIGlobal

Standards Australia, 1998, AS4100.9 Steel Structures: Connections, via SAIGlobal

Standards Australia, 2000, AS4291.1 Mechanical Properties of Fasteners Made of Carbon Steel and

Alloy Steel, via SAIGlobal

Standards Australia, 2004, AS5100.2: Bridge Design Part 2: Design Loads, via SAIGlobal

Steelconstruction.info, 2012, Modelling and Analysis of Beam Bridges, [online] available:

<http://www.steelconstruction.info/Modelling_and_analysis_of_beam_bridges>, accessed September

2013

Struers, 1992, Metalog Guide, Denmark

Taylor, J, 2003, An Engineer’s Guide to Fabricating Steel Structures, Volume 2, Chapter 2: Fatigue of

Steel Structures, [online] via: Australian Steel Institute

The Australian Corrosion Association, 2013, Technical Publication Series, ACA 6: Corrosion in

Natural Environment, version1.0, The Australian Corrosion Association Inc, Victoria Australia

Wang, H, Qin, S, Yin, H, 2013, Fatigue performance analysis of frictional type high strength bolts of

overlapped joints, International Conference on Fracture, Beijing

60

APPENDICES

Appendix A. LOAD CAPACITY OF M16 AND M22 BOLTS

The following tables have been taken from a publication by Blacks Fasteners. The load capacities

have been calculated based on AS1252 and AS4100.

Table 12: Design Shear and Tension - Strength Limit State (Blacks Fasteners)

Table 13: Design Shear - Serviceability Limit State (Blacks Fasteners)

For Design of 8.8/TF bolts, AS4100 Clauses 3.5.5, 9.1.6 and 9.3.3 applies.

61

As M22 bolts are not standard sizes, dimensions like pitch threads and diameters must first be

measured and the stress area and cross-sectional areas at the threaded and unthreaded region can be

identified through AS1252. Steps in calculating load capacities are as summarised from AS4100:

Strength Limit States:

Nominal Tensile Capacity of Bolts: where

For M16 bolts:

For M22 bolts:

Nominal Shear Capacity of Bolts:

The shear capacity of the bolts varies depending on the number of shear planes in the threaded, as

well as, the unthreaded regions of the bolt.

For bolts where the shear planes are all in the unthreaded region:

For bolts where the shear planes are all in the threaded region:

For bolts where there is 1 shear plane in the threaded and 1 in the unthreaded:

It is hence assumed that there are no more than two shear planes on the bolts at any given time (i.e.

that each joint is not connecting more than 3 surfaces together).

Bolts in shear and tension must satisfy: (

)

(

)

The tables above only account for having only a single shear. This means that the bolt is effectively

connecting two plates upon shear failure.

62

Appendix B. BRIDGE LOADING ANALYSIS

1. CALCULATIONS OF LOADS ON THE SUPERSTRUCTURE

The clauses referred to in this section are those in AS5100.2: Bridge Design Loads. Clauses from

other standards (AS1170 and others) are also included.

Vertical Loads:

The load effects on the superstructure can be categorised into three: dead load effects, live load effects

and other load effects.

The dead loads have been calculated as shown:

Cl.5: Dead Loads over a bridge span

Take L=75ft=22.86m (span centres)

Girders:

Thus, including connections, take girder weight as approximately 200kN.

Diaphragm

1968:

1972:

2(6+7) = 26kN

Decking: 24ft wide = 7.3152m, 75ft long = 22.86m, 7.25in thick=184.15mm

Volume=

Decking is reinforced, thus, take unit weight =

Braces (Inverted V):

Total: 1009kN/span – as the bridge is composed of 5 spans of the same lengths and includes the same

components, then each support should be able to hold the total of 1009kN.

The live loads effects have been calculated as shown:

Cl.6: Road Traffic Loads

S1600: The load position found to have most adverse effect (through Microstran) is as shown below:

63

Cl.6.5:

, rounded down, n=2 lanes

Two lanes are loaded, thus accompanying lane factors: 1.0 for the first lane and 0.8 for the second

lane.

Each support must resist is the load on support due to S1600

loading at position causing most adverse effect over one span.

M1600: When bridge is loaded as shown:

Each support must resist is the load on support due to M1600

loading at position causing most adverse effect over one span. Also, unlike S1600 stationary traffic

loads, M1600 moving traffic loads allow for dynamic, braking and centrifugal effects to be applied.

Cl.6.7.2 Dynamic Load allowance for M1600 load =0.30

Load on each support =2406.89x1.3=3128.95kN= load on support due to M1600 loads.

Cl.6.9: Fatigue Load Effects

(vehicles/lane/day)

; =1092kN:107413.6, Factor=0.0102

(where 410 vehicles count taken from Arnhem/Stuart count and may be an overestimate on number of

cars passing over the bridge)

The factor is added onto the calculated load on each support: 3129kN x 1.0102 = 3161kN on each

support.

Moving traffic load is said to be a function of speed. Figure C6.2.3 of AS5100.2 Commentary is a

chart showing the load per unit length equivalent of M1600 and S1600 when the influence of the

speed on the land load is factored into the loads. From the chart, it can be seen that for loaded length

of less than about 40m, the load per unit length has no variation whether the speed is around 60kph or

120kph. Mary River Bridge is essentially 5 simply supported spans and as such the loaded length is

considered to be the full length of each span (22.86m) which imply that the total load on each support

due to the M1600 loads with the dynamic allowance and accompanying lane factors is 3161kN as

calculated above. Total vertical forces due to traffic loads and dead loads at each support =

3161+1009 kN = 4170kN

Cl.16.6 Vertical Wind Load (for wind with angles of inclination to the superstructure of less than 5º)

Ultimate design vertical wind load (W*vu):

=454.33kN

Serviceability design vertical wind load (W*vs):

Where:

As = area of bridge span in plan: 7.3152m*22.86m =167.23m2.

64

CL= lift coefficient: 0.75

Vu = 77.7m/s and Vs=47m/s (as explained in Horizontal loads)

Horizontal Loads:

The horizontal forces acting on the system include the centrifugal forces (transverse forces required

for vehicles to move around a curve) and braking forces (longitudinal forces induced by accelerating

or decelerating traffic stream). The bridge is along a straight road and thus no geometrical curve

considerations are considered in the design (i.e. Fc=mv2/r is 0). Thus, the only horizontal loads

considered to be acting on the bridge surface are those induced by the braking forces.

Cl.6.8.2: Braking Forces

Single vehicle stopping

M1600 in one lane without dynamic allowance = 1337.16kN

Multi-lane moving traffic stream stopping

Braking forces to be applied in either direction = 601.72 kN

When compared to Figure C6.8.2 Braking Forces FBS and FBM for different bridge lengths, the

calculated values of 1337kN for the ultimate load with a single vehicle stopping and 602kN for 2

lanes of vehicles are both within the expected range.

Note: FHWA specifications state that the braking force is applied at a distance of six feet above the

roadway surface. However, an assumption that the bearings are “incapable of transmitting

longitudinal moment, the bearing force will be applied at the bearing elevation”.

Cl15.4: Forces on superstructures due to water flow

The commentary for the Bridge Design standards state that further research is required to determine

how much of the drag forces acting on the piers due to the water flow acts on the superstructure itself,

however, as an interim a value of 30% of the drag force may be taken as the load along the

longitudinal centreline of the bridge superstructure. The drag force itself is not reduced and the

transverse load would be applied in the direction of the upstream abutment.

Cl.15.3.1: Drag forces on piers

Ultimate design drag force (F*du):

Serviceability design drag force (F*ds):

Where Cd= drag coefficient, depending upon pier shape: Due to absence of more exact estimates, the

value of Cd is hence assumed to be 0.7 due to the semi-circular pier nosing.

Vu = mean velocity of water flow for ultimate limit states at the level of the superstructure or debris as

appropriate (2.6m/s)

Vs = mean velocity of water flow for serviceability limit states at the level of the superstructure or

debris as appropriate (2.3m/s)

Ad = area, equal to the thickness of the pier normal to the direction of the water flow, multiplied by

the height of the water flow: d of pier x height of water flow (height from river bed to centre of

superstructure) =2’ x 52’=104ft2 x (0.3048m/ft)2 = 9.66m2

65

RL: Dry season water level = 30ft, 5 year predicted flood level = 59.19ft, crown = 54.5ft (take

headstock level as 52ft).

Therefore, along the longitudinal centreline of the bridge superstructure, the design drag force due to

water flow = 7.81kN/m.

Cl.16 Wind Loads

As Mary River Bridge is a conventional type bridge structure such that it is neither a suspension nor

long-span cable-stayed bridge (those that may be subjected to wind excited oscillations), this clause

should be adequate in determining the wind loads on the system.

Cl.16.3.1 Transverse wind loads act horizontally at the centroids of the area it is calculated for (i.e. in

this case over the one span)

Ultimate design transverse wind load (W*tu):

(

)

Serviceability design transverse wind load (W*ts):

Where:

Vu = design wind speed for ultimate limit states

Vs = design wind speed for serviceability limit states

Based on AS1170.0 and AS1170.2:

The bridge is categorised as a major structure (i.e. affects crowds) thus it falls under high

consequence of failure – which would give an importance level of 3. As a bridge, the design working

life is categorised as over 100 years and thus, annual probability of exceedance for ultimate state is

1/2500 and for serviceability state is 1/25. From AS1170.2, the location is within the Cyclonic Region

C. From which, and

Where Fc =1.05 for R>50 and 1.00 for R<50. Therefore, Vu=74*1.05=77.7m/s and Vs=47m/s.

At = area of structure for calculation of wind loads (according to Commentary, this would only

include the transverse area of the superstructure – not including effect of wind loads to traffic loads);

take area of superstructure as b x d = 7.3152 * 2.3813 = 17.42m2 (although the cross-section is open,

there are diaphragms and other horizontal bracings along the bridge hence, this area is taken to be the

overall area).

Cd = drag coefficient from the chart Figure 16.3.3 in the standards (as Mary River bridge can be

considered a typical superstructure with multiple beams/girders, the values in the chart would apply);

includes an open parapet hence the depth does not include barriers: b/d=7.3152m/2.3813m = 3.072;

from chart, Cd=1.5

Note: An example calculation for steel bridges from FHWA determined the wind actions on the

transverse and longitudinal area of the bridge at varying angles but showed that the maximum loads

are generated when the winds are acting from the direction normal to the bridge face analysed.

Design Level Design Drag Force Due to Water Flow

Level (ft) (m) Ultimate 30%Ult Serviceability 30%Serv

Dry season water level 30 9.14 13.19 3.96 10.32 3.10

5 Yr predicted flood level 59.19 18.04 26.02 7.81 20.36 6.11

Pier Headstock level 52 15.85 22.86 6.86 17.89 5.37

66

Cl.16.4 Longitudinal Wind Load

Longitudinal wind loads for ultimate and serviceability are calculated in the same manner as the

transverse one – except the area considered is the longitudinal side (75ft) therefore,

A=22.86*2.3813=54.43m2

Cd based on b/d (22.86/2.3813) of 9.6 is 0.95. And the longitudinal and transverse wind loads are as

tabulated below:

Wind Direction relative to the bridge Ultimate wind load Serviceability wind load

Longitudinal 187.3075kN 68.53kN

Transverse 94.65kN 34.63kN

67

2. MICROSTRAN ANALYSIS REPORTS (Basis for Section 4.1) == I N P U T / A N A L Y S I S R E P O R T ==

Title: Longitudinal Line Beam loads

Type: Plane frame

Nodes ............................. 12

Members ........................... 11

Spring supports ................... 0

Sections .......................... 1

Materials ......................... 1

Primary load cases ................ 4

Combination load cases ............ 1

Analysis: Linear elastic

== L O A D C A S E S ==

Case Type Analysis Title

2 P L M1600axle loads

3 P L M1600line loads

11 C L Vertical loads combination

Analysis Types:

S - Skipped (not analysed)

L - Linear

N - Non-linear

== N O D E C O O R D I N A T E S ==

Node X Y Z Restraint

m m m

1 0.000 0.000 0.000 111000

2 1.250 0.000 0.000 000000

3 2.500 0.000 0.000 000000

4 6.250 0.000 0.000 000000

5 7.500 0.000 0.000 000000

6 8.750 0.000 0.000 000000

7 11.430 0.000 0.000 000000

8 15.000 0.000 0.000 000000

9 16.250 0.000 0.000 000000

10 17.500 0.000 0.000 000000

11 22.500 0.000 0.000 000000

12 22.860 0.000 0.000 111000

== M E M B E R D E F I N I T I O N ==

Member A B C Prop Matl Rel-A Rel-B Length

m

1 1 2 Y 1 1 000000 000000 1.250

2 2 3 Y 1 1 000000 000000 1.250

3 3 4 Y 1 1 000000 000000 3.750

4 4 5 Y 1 1 000000 000000 1.250

5 5 6 Y 1 1 000000 000000 1.250

6 6 7 Y 1 1 000000 000000 2.680

7 7 8 Y 1 1 000000 000000 3.570

8 8 9 Y 1 1 000000 000000 1.250

9 9 10 Y 1 1 000000 000000 1.250

10 10 11 Y 1 1 000000 000000 5.000

11 11 12 Y 1 1 000000 000000 0.360

== S E C T I O N S I N P U T B Y P R O P E R T Y V A L U E S ==

Section Name Comment

1 UBgirder comment

== S E C T I O N P R O P E R T I E S ==

Section Ax Ay Az J Iy Iz fact

68

m2 m2 m2 m4 m4 m4

1 7.500E-01 1.300E-02 2.650E-01 1.800E-02 2.650E-01 1.800E-02

== M A T E R I A L P R O P E R T I E S ==

Material E u Density Alpha

kN/m2 t/m3 /deg C

1 2.000E+08 0.2500 7.850E+00 1.170E-05

== T A B L E O F Q U A N T I T I E S ==

MATERIAL 1

Section Name Length Mass Comment

m tonne

1 UBgirder 22.860 134.588 comment

---------- ----------

22.860 134.588

== C O N D I T I O N N U M B E R ==

Maximum condition number: 2.179E+01 at node: 12 DOFN: 6

== A P P L I E D L O A D I N G ==

CASE 2: M1600axle loads

-- Node Loads --

Node X Force Y Force Z Force X Moment Y Moment Z Moment

kN kN kN kNm kNm kNm

1 0.000 -120.000 0.000 0.000 0.000 0.000

2 0.000 -120.000 0.000 0.000 0.000 0.000

3 0.000 -120.000 0.000 0.000 0.000 0.000

4 0.000 -120.000 0.000 0.000 0.000 0.000

5 0.000 -120.000 0.000 0.000 0.000 0.000

6 0.000 -120.000 0.000 0.000 0.000 0.000

7 0.000 -120.000 0.000 0.000 0.000 0.000

8 0.000 -120.000 0.000 0.000 0.000 0.000

9 0.000 -120.000 0.000 0.000 0.000 0.000

10 0.000 -120.000 0.000 0.000 0.000 0.000

11 0.000 -120.000 0.000 0.000 0.000 0.000

-- Sum of Applied Loads (Global Axes): --

FX: 0.000 FY: -1320.000 FZ: 0.000

Moments about the global origin:

MX: 0.000 MY: 0.000 MZ: -13071.600

== M E M B E R F O R C E S ==

CASE 2: M1600axle loads

Member Node Axial Shear-y Shear-z Torque Moment-y Moment-z

kN kN kN kNm kNm kNm

1 1 0.00 -628.19 0.00 0.00 0.00 0.00

2 0.00 -628.19 0.00 0.00 0.00 785.24

2 2 0.00 -508.19 0.00 0.00 0.00 785.24

3 0.00 -508.19 0.00 0.00 0.00 1420.47

3 3 0.00 -388.19 0.00 0.00 0.00 1420.47

4 0.00 -388.19 0.00 0.00 0.00 2876.18

4 4 0.00 -268.19 0.00 0.00 0.00 2876.18

5 0.00 -268.19 0.00 0.00 0.00 3211.42

5 5 0.00 -148.19 0.00 0.00 0.00 3211.42

6 0.00 -148.19 0.00 0.00 0.00 3396.65

6 6 0.00 -28.19 0.00 0.00 0.00 3396.65

7 0.00 -28.19 0.00 0.00 0.00 3472.20

7 7 0.00 91.81 0.00 0.00 0.00 3472.20

8 0.00 91.81 0.00 0.00 0.00 3144.43

8 8 0.00 211.81 0.00 0.00 0.00 3144.43

9 0.00 211.81 0.00 0.00 0.00 2879.67

9 9 0.00 331.81 0.00 0.00 0.00 2879.67

69

10 0.00 331.81 0.00 0.00 0.00 2464.91

10 10 0.00 451.81 0.00 0.00 0.00 2464.91

11 0.00 451.81 0.00 0.00 0.00 205.85

11 11 0.00 571.81 0.00 0.00 0.00 205.85

12 0.00 571.81 0.00 0.00 0.00 0.00

Positive Forces (Member Axes):

Axial - Tension Shear - End A sagging

Torque - Right-hand twist Moment - Sagging

== S U P P O R T R E A C T I O N S ==

CASE 2: M1600axle loads

Node Force-X Force-Y Force-Z Moment-X Moment-Y Moment-Z

kN kN kN kNm kNm kNm

1 0.00 748.19 0.00 0.00 0.00 0.00

12 0.00 571.81 0.00 0.00 0.00 0.00

SUM: 0.00 1320.00 0.00 (all nodes)

Max. residual: -1.091E-11 at DOFN: 4

(Reactions act on structure in positive global axis directions.)

CASE 3: M1600line loads

-- Member Loads --

Member Form T A S F1 X1 F2 X2

1 UNIF FY LO -6.000

2 UNIF FY LO -6.000

3 UNIF FY LO -6.000

4 UNIF FY LO -6.000

5 UNIF FY LO -6.000

6 UNIF FY LO -6.000

7 UNIF FY LO -6.000

8 UNIF FY LO -6.000

9 UNIF FY LO -6.000

10 UNIF FY LO -6.000

11 UNIF FY LO -6.000

-- Sum of Applied Loads (Global Axes): --

FX: 0.000 FY: -137.160 FZ: 0.000

Moments about the global origin:

MX: 0.000 MY: 0.000 MZ: -1567.739

== M E M B E R F O R C E S ==

CASE 3: M1600line loads

Member Node Axial Shear-y Shear-z Torque Moment-y Moment-z

kN kN kN kNm kNm kNm

1 1 0.00 -68.58 0.00 0.00 0.00 0.00

2 0.00 -61.08 0.00 0.00 0.00 81.04

2 2 0.00 -61.08 0.00 0.00 0.00 81.04

3 0.00 -53.58 0.00 0.00 0.00 152.70

3 3 0.00 -53.58 0.00 0.00 0.00 152.70

4 0.00 -31.08 0.00 0.00 0.00 311.44

4 4 0.00 -31.08 0.00 0.00 0.00 311.44

5 0.00 -23.58 0.00 0.00 0.00 345.60

5 5 0.00 -23.58 0.00 0.00 0.00 345.60

6 0.00 -16.08 0.00 0.00 0.00 370.39

6 6 0.00 -16.08 0.00 0.00 0.00 370.39

7 0.00 0.00 0.00 0.00 0.00 391.93

7 7 0.00 0.00 0.00 0.00 0.00 391.93

8 0.00 21.42 0.00 0.00 0.00 353.70

8 8 0.00 21.42 0.00 0.00 0.00 353.70

9 0.00 28.92 0.00 0.00 0.00 322.24

9 9 0.00 28.92 0.00 0.00 0.00 322.24

10 0.00 36.42 0.00 0.00 0.00 281.40

10 10 0.00 36.42 0.00 0.00 0.00 281.40

11 0.00 66.42 0.00 0.00 0.00 24.30

11 11 0.00 66.42 0.00 0.00 0.00 24.30

12 0.00 68.58 0.00 0.00 0.00 0.00

Positive Forces (Member Axes):

70

Axial - Tension Shear - End A sagging

Torque - Right-hand twist Moment - Sagging

== S U P P O R T R E A C T I O N S ==

CASE 3: M1600line loads

Node Force-X Force-Y Force-Z Moment-X Moment-Y Moment-Z

kN kN kN kNm kNm kNm

1 0.00 68.58 0.00 0.00 0.00 0.00

12 0.00 68.58 0.00 0.00 0.00 0.00

SUM: 0.00 137.16 0.00 (all nodes)

Max. residual: -1.137E-12 at DOFN: 4

(Reactions act on structure in positive global axis directions.)

CASE 11: Vertical loads combination

-- Load Combinations --

Case Factor

1 1.300 Self weight

2 1.000 M1600axle loads

3 1.000 M1600line loads

4 1.000 Vertical Wind loads

-- Sum of Applied Loads (Global Axes): --

FX: 0.000 FY: -1899.158 FZ: 0.000

Moments about the global origin:

MX: 0.000 MY: 0.000 MZ: -19691.375

== M E M B E R F O R C E S ==

CASE 11: Vertical loads combination

Member Node Axial Shear-y Shear-z Torque Moment-y Moment-z

kN kN kN kNm kNm kNm

1 1 0.00 -917.77 0.00 0.00 0.00 0.00

2 0.00 -886.10 0.00 0.00 0.00 1127.42

2 2 0.00 -766.10 0.00 0.00 0.00 1127.42

3 0.00 -734.43 0.00 0.00 0.00 2065.25

3 3 0.00 -614.43 0.00 0.00 0.00 2065.25

4 0.00 -519.42 0.00 0.00 0.00 4191.23

4 4 0.00 -399.42 0.00 0.00 0.00 4191.23

5 0.00 -367.76 0.00 0.00 0.00 4670.71

5 5 0.00 -247.76 0.00 0.00 0.00 4670.71

6 0.00 -216.09 0.00 0.00 0.00 4960.61

6 6 0.00 -96.09 0.00 0.00 0.00 4960.61

7 0.00 -28.19 0.00 0.00 0.00 5127.14

7 7 0.00 91.81 0.00 0.00 0.00 5127.14

8 0.00 182.26 0.00 0.00 0.00 4637.93

8 8 0.00 302.26 0.00 0.00 0.00 4637.93

9 0.00 333.93 0.00 0.00 0.00 4240.32

9 9 0.00 453.93 0.00 0.00 0.00 4240.32

10 0.00 485.59 0.00 0.00 0.00 3653.12

10 10 0.00 605.59 0.00 0.00 0.00 3653.12

11 0.00 732.27 0.00 0.00 0.00 308.46

11 11 0.00 852.27 0.00 0.00 0.00 308.46

12 0.00 861.39 0.00 0.00 0.00 0.00

Positive Forces (Member Axes):

Axial - Tension Shear - End A sagging

Torque - Right-hand twist Moment - Sagging

== S U P P O R T R E A C T I O N S ==

CASE 11: Vertical loads combination

Node Force-X Force-Y Force-Z Moment-X Moment-Y Moment-Z

kN kN kN kNm kNm kNm

1 0.00 1037.77 0.00 0.00 0.00 0.00

12 0.00 861.39 0.00 0.00 0.00 0.00

SUM: 0.00 1899.16 0.00 (all nodes)

(Reactions act on structure in positive global axis directions.)

71

(Basis for Section 4.2)

a

Longitudinal And Transverse Horizontal Loads on a Bridge Span (At the Superstructure)

Combination of Ultimate Loads on a Bridge Span

(Note: The Vertical loads have been modelled as uniformly distriuted load from the deck

onto the girders)

== I N P U T / A N A L Y S I S R E P O R T ==

Job: Load Combinations

Title: Ultimate Loads

Type: Space frame

Nodes ............................. 15

Members ........................... 22

Spring supports ................... 0

Sections .......................... 2

Materials ......................... 1

Primary load cases ................ 7

Combination load cases ............ 1

Analysis: Linear elastic

== L O A D C A S E S ==

Case Type Analysis Title

1 P L Transverse Wind Loads- ultimate

2 P L Longitudinal Wind Loads - ultimate

3 P L Self-weight

72

4 P L Braking Loads - Multiple

5 P L Drag Force Due to Water Flow - flood level

7 P L Vertical Wind Loads - ultimate

8 P L Traffic Loads

11 C L Title of case 11

Analysis Types:

S - Skipped (not analysed)

L - Linear

N - Non-linear

== N O D E C O O R D I N A T E S ==

Node X Y Z Restraint

m m m

1 0.000 0.000 0.000 111000

2 0.000 0.000 1.638 111000

3 0.000 0.000 3.277 111000

4 0.000 0.000 5.144 111000

5 0.000 0.000 7.010 111000

6 11.430 0.000 0.000 100000

7 11.430 0.000 1.638 100000

8 11.430 0.000 3.277 100000

9 11.430 0.000 5.144 100000

10 11.430 0.000 7.010 100000

11 22.860 0.000 0.000 111000

12 22.860 0.000 1.638 111000

13 22.860 0.000 3.277 111000

14 22.860 0.000 5.144 111000

15 22.860 0.000 7.010 111000

== M E M B E R D E F I N I T I O N ==

Member A B C Prop Matl Rel-A Rel-B Length

m

1 1 2 -Y 1 1 000000 000000 1.638

2 2 3 -Y 1 1 000000 000000 1.639

3 3 4 -Y 1 1 000000 000000 1.867

4 4 5 -Y 1 1 000000 000000 1.866

5 1 6 -Y 1 1 000000 000000 11.430

6 2 7 -Y 1 1 000000 000000 11.430

7 3 8 Y 2 1 000000 000000 11.430

8 4 9 Y 2 1 000000 000000 11.430

9 5 10 Y 2 1 000000 000000 11.430

10 6 11 Y 1 1 000000 000000 11.430

11 7 12 Y 1 1 000000 000000 11.430

12 8 13 Y 2 1 000000 000000 11.430

13 9 14 Y 2 1 000000 000000 11.430

14 10 15 Y 2 1 000000 000000 11.430

15 6 7 -Y 1 1 000000 000000 1.638

16 7 8 -Y 1 1 000000 000000 1.639

17 8 9 -Y 2 1 000000 000000 1.867

18 9 10 -Y 2 1 000000 000000 1.866

19 11 12 -Y 1 1 000000 000000 1.638

20 12 13 -Y 1 1 000000 000000 1.639

21 13 14 -Y 1 1 000000 000000 1.867

22 14 15 -Y 1 1 000000 000000 1.866

== S T A N D A R D S H A P E S ==

Section Shape Name Comment D1/D4 D2/D5 D3/D6

1 I/H 762X267UB147 comment 0.750 0.013 0.265

0.018 0.265 0.018

2 I/H 762X267UB197 comment 0.770 0.016 0.268

0.025 0.268 0.025

Dimension codes:

I/H - D1=D D2=Tw D3=Btf D4=Ttf D5=Bbf D6=Tbf

== S E C T I O N P R O P E R T I E S ==

Section Ax Ay Az J Iy Iz fact

m2 m2 m2 m4 m4 m4

1 1.882E-02 0.000E+00 0.000E+00 1.503E-06 5.596E-05 1.673E-03 1.000

2 2.492E-02 0.000E+00 0.000E+00 3.597E-06 8.045E-05 2.358E-03 1.000

== M A T E R I A L P R O P E R T I E S ==

73

Material E u Density Alpha

kN/m2 t/m3 /deg C

1 2.000E+08 0.2500 7.850E+00 1.170E-05

== T A B L E O F Q U A N T I T I E S ==

MATERIAL 1

Section Name Length Mass Comment

m tonne

1 762X267UB147 63.017 9.311 comment

2 762X267UB197 72.313 14.146 comment

---------- ----------

135.330 23.457

== C O N D I T I O N N U M B E R ==

Maximum condition number: 2.493E+03 at node: 10 DOFN: 3

== A P P L I E D L O A D I N G ==

CASE 1: Transverse Wind Loads- ultimate

-- Member Loads --

Member Form T A S F1 X1 F2 X2

1 UNIF FZ LO 14.443

2 UNIF FZ LO 14.443

3 UNIF FZ LO 14.443

4 UNIF FZ LO 14.443

-- Sum of Applied Loads (Global Axes): --

FX: 101.245 FY: 0.000 FZ: 0.000

Moments about the global origin:

MX: 0.000 MY: 354.865 MZ: 0.000

CASE 2: Longitudinal Wind Loads - ultimate

-- Member Loads --

Member Form T A S F1 X1 F2 X2

5 UNIF FZ LO -6.490

10 UNIF FZ LO 6.490

-- Sum of Applied Loads (Global Axes): --

FX: 0.000 FY: 0.000 FZ: 148.361

Moments about the global origin:

MX: 0.000 MY: -1695.771 MZ: 0.000

CASE 3: Self-weight

-- Member Loads --

Member Form T A S F1 X1 F2 X2

5 UNIF FY LO 6.000

6 UNIF FY LO 11.050

7 UNIF FY LO -11.050

8 UNIF FY LO -11.050

9 UNIF FY LO -6.000

10 UNIF FY LO -6.000

11 UNIF FY LO -11.050

12 UNIF FY LO -11.050

13 UNIF FY LO -11.050

14 UNIF FY LO -6.000

-- Sum of Applied Loads (Global Axes): --

FX: 0.000 FY: -1032.129 FZ: 0.000

Moments about the global origin:

MX: 3502.425 MY: 0.000 MZ: -11797.235

CASE 4: Braking Loads - Multiple

-- Member Loads --

Member Form T A S F1 X1 F2 X2

6 UNIF FX LO 22.830

8 UNIF FX LO -22.830

11 UNIF FX LO 22.830

13 UNIF FX LO -22.830

-- Sum of Applied Loads (Global Axes): --

74

FX: 0.000 FY: 0.000 FZ: 0.000

Moments about the global origin:

MX: 0.000 MY: -1829.760 MZ: 0.000

CASE 5: Drag Force Due to Water Flow - flood level

-- Member Loads --

Member Form T A S F1 X1 F2 X2

5 UNIF FZ LO -0.342

10 UNIF FZ LO 0.342

-- Sum of Applied Loads (Global Axes): --

FX: 0.000 FY: 0.000 FZ: 7.818

Moments about the global origin:

MX: 0.000 MY: -89.361 MZ: 0.000

CASE 7: Vertical Wind Loads - ultimate

-- Member Loads --

Member Form T A S F1 X1 F2 X2

5 UNIF FY LO 5.000

6 UNIF FY LO 5.000

7 UNIF FY LO -5.000

8 UNIF FY LO -5.000

9 UNIF FY LO -5.000

10 UNIF FY LO -5.000

11 UNIF FY LO -5.000

12 UNIF FY LO -5.000

13 UNIF FY LO -5.000

14 UNIF FY LO -5.000

-- Sum of Applied Loads (Global Axes): --

FX: 0.000 FY: -571.500 FZ: 0.000

Moments about the global origin:

MX: 1950.987 MY: 0.000 MZ: -6532.245

CASE 8: Traffic Loads

-- Member Loads --

Member Form T A S F1 X1 F2 X2

5 UNIF FY LO 17.280

6 UNIF FY LO 34.500

7 UNIF FY LO -34.500

8 UNIF FY LO -34.500

9 UNIF FY LO -17.280

10 UNIF FY LO -17.280

11 UNIF FY LO -34.500

12 UNIF FY LO -34.500

13 UNIF FY LO -34.500

14 UNIF FY LO -17.280

-- Sum of Applied Loads (Global Axes): --

FX: 0.000 FY: -3156.052 FZ: 0.000

Moments about the global origin:

MX: 10702.328 MY: -0.001 MZ: -36073.672

CASE 11: Title of case 11

-- Load Combinations --

Case Factor

1 1.000 Transverse Wind Loads- ultimate

2 1.000 Longitudinal Wind Loads - ultimate

3 1.200 Self-weight

4 1.000 Braking Loads - Multiple

5 1.000 Drag Force Due to Water Flow - flood level

7 1.000 Vertical Wind Loads - ultimate

8 1.000 Traffic Loads

-- Sum of Applied Loads (Global Axes): --

FX: 101.245 FY: -4966.106 FZ: 156.180

Moments about the global origin:

MX: 16856.227 MY: -3260.029 MZ: -56762.602

== M E M B E R F O R C E S ==

CASE 11: Title of case 11

75

Member Node Axial Shear-y Shear-z Torque Moment-y Moment-z

kN kN kN kNm kNm kNm

1 1 0.000000 0.189913 94.043961 0.167305 98.884651 0.214752

2 0.000000 0.189913 70.386322 0.167305 -35.783749 -0.096326

2 2 0.000000 0.244824 25.746429 0.450331 4.960060 0.126394

3 0.000000 0.244824 2.074357 0.450331 -17.839075 -0.274873

3 3 0.000000 0.276777 40.333904 0.367040 32.733105 0.296132

4 0.000000 0.276777 13.368821 0.367040 -17.398392 -0.220610

4 4 0.000000 0.530643 57.430733 0.479516 36.416924 0.378449

5 0.000000 0.530643 30.480097 0.479516 -45.603893 -0.611731

5 1 0.000000 431.113068 -43.967751 -0.214752 -98.884651 0.167305

6 0.000000 94.156662 34.122009 -0.214752 -42.616238 -3.002E+03

6 2 130.473450 508.155640 -7.056072 -0.222720 -40.743809 0.283025

7-130.473450 -94.891174 -7.056072 -0.222720 39.907101 -2.362E+03

7 3 0.000000-589.510620 9.091908 -0.571005 50.572178 0.083290

8 0.000000 13.536164 9.091908 -0.571005 -53.3483353291.777832

8 4-130.473450-548.399658 9.516005 -0.599059 53.815311 -0.112479

9 130.473450 54.647141 9.516005 -0.599059 -54.9526142821.683594

9 5 0.000000-405.874237 8.443434 -0.611731 45.603893 0.479513

10 0.000000 -68.917816 8.443434 -0.611731 -50.9045492713.916260

10 6 0.000000 94.156662 34.174919 0.214752 42.7878193001.749512

11 0.000000 431.113068 -43.914841 0.214752 98.451454 -0.167305

11 7 130.473450 -94.891174 -7.069632 0.222720 -39.9479102361.523438

12-130.473450 508.155640 -7.069632 0.222720 40.857986 -0.283027

12 8 0.000000 -13.536164 -9.079210 0.571005 -53.3023453291.777832

13 0.000000 589.510620 -9.079210 0.571005 50.473022 0.083290

13 9-130.473450 -54.647141 -9.497896 0.599059 -54.9024282821.683594

14 130.473450 548.399658 -9.497896 0.599059 53.658527 -0.112479

14 10 0.000000 68.917816 -8.542773 0.611731 -51.2218362713.916260

15 0.000000 405.874237 -8.542773 0.611731 46.422054 0.479513

15 6 -68.296928 188.313324 0.122448 0.000000 0.171576 -0.429504

7 -68.296928 188.313324 0.122448 0.000000 -0.028994-308.886719

16 7 -54.171227 -1.469025 -0.058635 0.000000 -0.069876-309.332153

8 -54.171227 -1.469025 -0.058635 0.000000 0.026227-306.924438

17 8 -36.000107 -28.541355 0.104262 0.000000 0.072213-308.066467

9 -36.000107 -28.541355 0.104262 0.000000 -0.122445-254.779739

18 9 -16.986214-137.835632 -0.208756 0.000000 -0.072258-255.977875

10 -16.986214-137.835632 -0.208756 0.000000 0.317281 1.223463

19 11 0.000000 0.189933 -84.376183 -0.167305 -98.451454 0.214774

12 0.000000 0.189933 -84.376183 -0.167305 39.756733 -0.096335

20 12 0.000000 0.244827 -13.563260 -0.450331 -1.101251 0.126394

13 0.000000 0.244827 -13.563260 -0.450331 21.128933 -0.274878

21 13 0.000000 0.276783 -27.799545 -0.367040 -29.344091 0.296138

14 0.000000 0.276783 -27.799545 -0.367040 22.557661 -0.220615

22 14 0.000000 0.530653 -41.544968 -0.479516 -31.100866 0.378456

15 0.000000 0.530653 -41.544968 -0.479516 46.422054 -0.611742

Positive Forces (Member Axes):

Axial - Tension Shear - End A sagging

Torque - Right-hand twist Moment - Sagging

== S U P P O R T R E A C T I O N S ==

CASE 11: Title of case 11

Node Force-X Force-Y Force-Z Moment-X Moment-Y Moment-Z

kN kN kN kNm kNm kNm

1 -94.043961 431.302979 -43.967751 0.000000 0.000000 0.000000

2 -85.833557 508.210541 -7.056064 0.000000 0.000000 0.000000

3 -38.259548 589.542603 -9.091928 0.000000 0.000000 0.000000

4 86.411537 548.653564 -9.516032 0.000000 0.000000 0.000000

5 30.480097 405.343597 -8.443461 0.000000 0.000000 0.000000

6 -0.122427 0.000000 0.000000 0.000000 0.000000 0.000000

7-260.765839 0.000000 0.000000 0.000000 0.000000 0.000000

8 -0.162901 0.000000 0.000000 0.000000 0.000000 0.000000

9 261.259918 0.000000 0.000000 0.000000 0.000000 0.000000

10 -0.208741 0.000000 0.000000 0.000000 0.000000 0.000000

11 84.376183 431.302979 -43.914841 0.000000 0.000000 0.000000

12-201.286362 508.210541 -7.069640 0.000000 0.000000 0.000000

13 14.236283 589.542603 -9.079229 0.000000 0.000000 0.000000

14 144.218872 548.653564 -9.497924 0.000000 0.000000 0.000000

15 -41.544968 405.343597 -8.542801 0.000000 0.000000 0.000000

SUM: -101.2454224966.106445-156.179657 (all nodes)

(Reactions act on structure in positive global axis directions.)

76

Appendix C. SPECIFIED PROPERTIES OF 8.8/TF BOLTS

The following tables include the specified values for the properties of Grade 8.8 bolts in accordance

with AS4192.

Chemical Composition

Material Treatment Carbon Steel with additives (e.g.

B, Mn or Cr) quenched and

tempered

Carbon Steel quenched

and tempered

Check

Composition

Limits %

(m/m)

C min 0,15 0,25

max 0,40 0,55

P max 0,035 0,035

S max 0,035 0,035

B max 0,003 0,003

Tempering Temperature

°C min

425 425

Mechanical and Physical Properties d≤16mm d>16mm

Nominal Tensile Strength (Rm,nom) N/mm2 800 800

Minimum Tensile Strength (Rm, min)= de N/mm2 800 830

Vickers Hardness, HV (F≥98N)

min 250 255

max 320 335

Surface Hardness HV 0,3 max not more than 30 Vickers points

above core hardness

Stress at 0.2% non-proportional elongation

Rp0,2 N/mm2

nom 640 640

min 640 660

Stress under proof load, Sp

Sp/R p0,2 0,91 0,91

N/mm2 580 600

Breaking Torque Mb Nm min See ISO898-7

Percent elongation after fracture, A min 12 12

Reduction area after fracture, Z %min 52

Strength under wedge loading

not smaller than minimum tensile

strength

Impact strength, Ku J min 30 30

Head soundness No fracture

Minimum height of non-decarburized thread zone, E ½ H1

Minimum depth of complete

decarburization, G

mm 0,015

Hardness after tempering

Reduction of hardness, 20 HV

maximum

Surface Integrity

In accordance with ISO 6157-1 or

ISO 6157-3 as appropriate

77

Appendix D. BOLTS, NUTS AND WASHERS INVENTORY

The diagram below shows the naming convention used in the bolt groups in the tabulated inventory.

Note: Old Beam (1,2,3) – those constructed in 1968

New Beam (4,5)– those constructed in 1972

Abutment 1 refers to the in-bound side (closer to Stuart Highway)

Section 1 refers to diaphragm section between Old beams 1 and 2, etc.

Bridge Section (All from Brace+Bottom Flange)

M16 M22 Observations

Notes on Diaphragm bolts Bolts Nuts Washers Bolts Nuts Washers

Abutment 1 New Beam 4A 8 8 10 0 2 0 None of the M16 washers have tabs

Abutment 1 New Beam 5A 4 4 6 0 4 0

Abutment 1 Old Beam 1A 4 4 8 0 3 2

Abutment 1 Old Beam 2A 8 8 16 0 4 4 Only 2 of M16 washers have tabs

Abutment 1 Old Beam 3A 8 8 14 0 4 4

Abutment 2 New Beam 4E 8 8 16 0 3 0

Abutment 2 NewBeam 5E 4 4 8 0 4 0 M22 nuts are badly corroded

Abutment 2 Old Beam 1E 4 4 8 0 4 4

Abutment 2 Old Beam 2E 8 8 17 0 3 5

Abutment 2 Old Beam 3E 8 7 16 0 4 3 M22 washers have no tabs and are corroded

Diaphragm 1 Section 1 12 12 24 4 4 7 complete

Diaphragm 1 Section 2 12 11 21 2 2 2 missing 2 M22

Diaphragm 1 Section 3 11 10 10 2 3 1 2 M16 bolts have failed in fatigue

missing 1 M16 and 2 M22

Diaphragm 1 Section 4 11 11 16 3 4 2 5 of the M16 washers were on their own (spares)

missing 1 M16 and 1 M22

Diaphragm 2 Section 1 12 12 24 4 4 8 1 set of M16 connection was not painted and had a smaller tab (recently replaced)

Complete

Diaphragm 2 Section 2 11 11 22 4 3 7 Missing 1 M16

Diaphragm 2 Section 3 12 12 24 4 3 8 Complete

Diaphragm 2 Section 4 12 12 24 4 4 5 Complete

Diaphragm 3 Section 1 12 11 21 4 4 8 1 M22 bolt was cut to be removed Complete

Diaphragm 3 Section 2 12 12 24 4 1 8 Complete

Diaphragm 3 Section 3 12 13 25 3 3 6 Missing 1 M22

Diaphragm 4 Section 1 20 20 10 4 4 8

M22 bolts are corroded and some necking. 1 M16 bolt failed (fatigue).

Diaphragm 4 Section 2 11 11 22 3 3 6 Bolts have corroded on some parts of the threaded section

missing 1 M16 and 1 M22

Diaphragm 4 Section 3 7 11 7 4 2 8

1 set of M16 connection without washers have fatigued (where neck and threaded area meets) Missing 5 M16

Diaphragm 4 Section 4 12 12 23 4 3 8 M22 bolts are more corroded than M16 bolts complete

78

Bridge Section (All from Brace+Bottom Flange)

M16 M22 Observations

Notes on Diaphragm bolts Bolts Nuts Washers Bolts Nuts Washers

Diaphragm 5 Section 1 11 12 22 3 4 7 missing 1 M16 and 1 M22

Diaphragm 5 Section 2 13 13 25 3 3.5 8 1 M22 nut was cut in half and missing the other half Missing 1 M22

Diaphragm 5 Section 3 12 12 23 4 3 8 1 M16 bolt needed to be cut to be removed complete

Diaphragm 5 Section 4 12 10 23 4 4 8 complete

Headstock 2 New Beam 4C 6 6 12 0 5 1

Headstock Old Beam 1B 3 3 6 0 3 3 M22 washers have no tabs

Headstock 2 New Beam 4B 8 8 8 0 4 0

M16 washers have no tabs and bolts have dark finish and some corrosion noticeable on threads.

Headstock 2 New Beam5B 3 3 4 0 4 0 Minimal corrosion

Headstock 2 Old Beam 1C 4 4 8 0 5 4

Headstock 2 Old Beam 2C 8 8 16 0 4 4

Headstock 2 Old Beam 3B 8 8 9 0 4 6

M16 bolts have corrosion about the neck and nuts are corroded that some were broken from the outer surface through to the bolts

Headstock 2 Old Beam 3C 9 9 16 0 3 3

Headstock 3 ld Beam 3C 8 8 16 0 4 2

Headstock 3 New Bam 4D 8 8 15 0 4 0

Headstock 3 New Beam 4C 8 8 16 0 4 0

Headstock 3 New Beam 5D 4 4 8 0 4 0

Headstock 3 Old Beam 1C 4 7 4 0 4 4

Headstock 3 Old Beam 1D 4 4 8 0 4 4 M16 bolts are long and are corroded about the necks

Headstock 3 Old Beam 2C 8 8 16 0 4 4 M16 bolts are corroded about the thread

Headstock 3 Old Beam 2D 8 8 16 0 4 4 M22 washers have no tabs

Headstock 3 Old Beam 3D 8 8 16 0 3 3 Minimal corrosion

Headstock 4 New Beam 4D 10 10 20 0 4 0

Headstock 4 New Beam 5D 5 5 9 0 4 0 M16 connections all thoroughly corroded

Headstock 4 New Beam 5E 3 3 6 0 4 0 M22 nuts are badly corroded

Headstock 4 Old Beam 1D 2 2 4 0 2 2

Headstock 4 Old Beam 1E 5 5 10 0 6 6 Bolts are heavily corroded about the neck

Headstock 4 Old Beam 2D 7 7 14 0 4 4

Headstock 4 Old Beam 2E 8 8 18 0 3 3

Headstock 4 Old Beam 3D 8 8 16 0 4 0

Headstock 4 Old Beam 3E 8 8 16 0 4 2

M16 bolts of varying lengths, M22 nuts have corroded about the centre

Headstock New Beam 4A 6 6 0 0 4 7

Headstock New Beam 4B 11 11 12 0 4 0

Headstock New Beam 5A 4 4 4 0 4 0

Headstock New Beam 5B 3 3 3 0 4 0

Headstock New Beam 5C 5 3 8 0 4 0

Headstock Old Beam 1A 4 4 8 0 4 4

Headstock Old Beam 1B 4 4 8 0 4 4

Headstock Old Beam 2A 10 10 20 0 4 4 1 M16 bolt had a neck longer than the rest

Headstock Old Beam 2B 6 6 12 0 4 4

Headstock Old Beam 3A 7 7 11 0 4 4 M15 washers had varying sizes; some without tabs

Headstock Old Beam 3B 8 8 12 0 4 4 1 M16 bolt had a neck longer than the rest

79

Appendix E. EQUIPMENT USED FOR SAMPLE PREPARATION, BOLT ANALYSIS

AND BOLT TESTING

The above has been used for

metallographic preparation of test samples

as shown below.

Optical Microscope

Vickers Hardness Tester

sInstron machine and Actuator

80

Appendix F. VICKERS HARDNESS TESTING

Shown in this image is one of the results

from the Vickers Hardness Tests

conducted. The software is capable of

measuring the diagonals and

automatically calculating the hardness

number. The tensile strength (MPa) was

3.2x the Vickers Hardness.

Test Specimen Trial Diagonal Vickers Hardness Tensile Strength (Mpa) Average Tensile

Strength (Mpa)

1968 M22 Bolt

Thread 2 (Hv 1)

1 79.15 296 947.2

947.8

2 79.284 295 944.0

3 78.571 300 960.0

4 79.351 295 944.0

5 79.284 295 944.0

1972 M22 Bolt

Thread 1 (Hv

0,3)

1 45.974 263 841.6

891.5

2 43.636 292 934.4

3 45.455 269 860.8

4 44.156 285 912.0

5 44.286 284 908.8

1968 M22 Bolt

Cross-section 1

(Hv 0,3)

1 43.636 292 934.4

950.4

2 43.506 294 940.8

3 42.849 303 969.6

4 43.117 299 956.8

5 43.279 297 950.4

1972 M22 Bolt

Cross-section 2

(Hv 0,3)

1 79.15 296 947.2

947.8

2 79.284 295 944.0

3 78.571 300 960.0

4 79.351 295 944.0

5 79.284 295 944.0

81

Test

Specimen

Trial Diagonal Vickers Hardness Tensile Strength (Mpa) Average Tensile

Strength (Mpa)

1968 M16

Bolt 1

Cross-

section

1 44.104 286 915.2 935.7 2 43.352 296 947.2 3 43.799 290 928.0 4 43.279 297 950.4 5 43.574 293 937.6

1968 M16

Bolt 2

Cross-

section

1 44.654 279 892.8 923.5 2 43.723 291 931.2 3 43.45 288 921.6 4 43.723 291 931.2 5 43.5 294 940.8

1972 M16

Bolt 1

Cross-

Section

1 42.941 301 963.2 981.8 2 42.638 306 979.2 3 42.499 308 985.6 4 42.226 312 998.4 5 42.569 307 982.4

1972 M16

Bolt 2

Cross-

Section

1 42.708 305 976.0 988.8 2 41.958 316 1011.2 3 42.708 305 976.0 4 41.958 315 1008.0 5 42.778 304 972.8

1968 M16

Bolt Thread

1

1 40.935 332 1062.4 1029.3 2 42.778 304 972.8 3 41.121 329 1052.8

1968 M16

Bolt Thread

2

1 40.873 333 1065.6 1045.3 2 41.826 318 1017.6 3 41.121 329 1052.8

1972 M16

Bolt Thread

1

1 42.431 309 988.8 988.8 2 42.294 311 995.2 3 42.597 307 982.4

1972 M16

Bolt Thread

2

1 42.091 314 1004.8 996.3 2 42.849 303 969.6 3 41.892 317 1014.4

82

Appendix G. IMAGES FROM OPTICAL AND SCANNED ELECTRON MICROSCOPY

1968 5/8” Bolts Cross-Section

20x Magnification:

50x Magnification:

1968 5/8” Bolts Longitudinal Axis (Thread)

20x Magnification:

50x Magnification:

1972 M16 Bolts Cross Section

20x Magnification

50x Magnification

83

Appendix H. MECHANICAL TESTINGS

1. ONE SET OF SLIP LOAD GRAPH FROM THE SLIP TESTING EXPERIMENTS

2. FATIGUE TESTING EXPERIMENTAL DESIGN

M16 bolts (shear)

To determine the fatigue life of the M16 bolt group on the bridge diaphragm, a cyclic load experiment

is proposed to be conducted. Fatigue tests require the following parameters to be determined:

minimum load, maximum load and loading frequency.

Minimum and Maximum Load

The bolt group of 12 M16 bolts on the bridge diaphragms and the bolt group of 4 M16 on the gusset

plate connection at the inverse v-bracings are friction tightened and hence designed to resist slip at

load service and hence are designed to not be loaded over 70% of its slip load.

In conducting a fatigue test, the minimum and maximum loads in each cycle must be defined. In the

case of the M16 connections on the diaphragms, the minimum load is that of the dead loads and the

maximum is the 70% of the slip critical load. This 70% of the slip critical load is hence, for this

testing, assumed to be more than the dead load of the self-weight of the reinforced concrete deck and

the bridge railings together with the live loads of the traversing traffic causing the most adverse effect

on the structure. This is because the design factor only allow for bolted connections to not be loaded

more than 70% their capacity and as this connection is in shear, then that 70% is applied to its slip

critical load and not to its nominal shear capacity.

-10

0

10

20

30

40

50

60

70

80

90

-0.2 0 0.2 0.4 0.6 0.8 1 1.2 1.4

Load

(kN

)

Extension (mm)

First trials for M22 and 7/8" bolts

New

Old

84

The shear joints connecting the diaphragms and the main UB girders are subjected to the dead loads

due to the self-weight of the sections of the structure on top of the steel beams which include the

reinforced decking and the bridge railings which totalled up to 760kN per bridge span (total area of

168m2 and thus stress of 4.6MPa. The dead load due to 1/8 of the total area of the bridge span acts

on each set of bolted connection (21m2) thus total dead load each connection must resist is 4.6MPa x

21m2 = 96.6kN. There are 12 bolts in each of the diaphragm to girder bolted connection (6 on each

side) and hence each bolt is subjected to 8.05 kN each. However, it must be remembered that the total

strength of a bolt group of 12 bolts in one set of connection is not equal to 12 times the nominal

capacity of each bolt and that the stress concentration, shear and bending moment on each bolt in the

group varies depending on the bolt group centroid and the location of out-of-plain loading. For

simplicity, to carry out a cyclic loading test, it is important to use the maximum shear force on a bolt

in the group which in this case is that of the 8.05kN (as it would be acting on the bolts at the top or

closest to the location of the loading).

The maximum load is hence determined as the 70% of the slip critical load of the M16 friction

tightened bolts in double shear configuration. The slip resistance of an M16 bolt in a double shear

configuration was earlier calculated to be 29.47kN and as such its 70% is 20.6kN. From the slip tests

conducted on the new set of M16 bolts tightened such that the gap between the load indicating

washers and the plates was ensured to be at 0.25mm as specified for galvanized bolts, the average slip

load on 2 M16 bolts in a double shear configuration was 48kN implying that each bolt resisted 24kN

before slipping began, which is less than the 29kN as earlier calculated due to up to 20% inaccuracies

due to manual bolt tightening. As the average slip load from the earlier test is less than the determined

one from the calculated slip critical load, this will hence be the basis for the fatigue testing and as

such 70% of the 24kN will be used as the maximum load for the fatigue testing which is 16.8kN

From the above, the parameters for the fatigue testing of friction tightened bolt in an overlapped joint

is hence determined to have a minimum load of 8.05 kN and a maximum load of 16.8kN on each bolt.

However, as there are two bolts in the testing mechanism, for the fatigue testing, the loads will be at

minimum of 16.1kN and maximum of 33.6kN.

Loading Frequency and Expected Stress Cycle

From standards, service life of highways designed for Average Daily Truck Traffic (ADTT) of 2500

must be 2,000,000 cycles and those highways designed for ADTT of less than 2500 must have a

service life of 500,000 cycles.

Cyclic load testing requires for a pre-determined constant frequency for testing. For high-cycle

fatigue (HCF),20 to 50Hz is commonly used; however, this parameter is purely ideal and as such a

low-cycle fatigue (LCF) will instead be applied using a frequency of less than 10Hz,usually 0.01 to 5

Hz for a cycle of 10^4, however previous articles have conducted LCF testing in 5Hz and even up to

8-10Hz, which is usually indicated by the capacity of the testing machine or pre-determined based on

operation. As the lower frequency range in the LCF (0.01-5Hz) would imply stress cycles of less than

10^4, a loading frequency within the higher frequency range in the LCF (5-10Hz) would be chosen to

result in stress cycles in the 500,000 to 2,500,000 range.

85

Parameters:

Clamping force: Endure bolts are tightened such that the gap between the plate and the load indicating

washers is decreased down to 0.25mm

Minimum load: 16 kN

Maximum load: 33kN

Loading Frequency: 5-10 Hz (range can be smaller to ensure accuracy i.e. 5-6 or 8-10Hz depending

on machine)

Fatigue Testing for M22 bolts (tensile)

At the underside of each of the diaphragm-girder connections, there are 4 M22 bolts. For fatigue

testing, the amplitude for the cyclic loading would have a minimum of 0kN (as these connections are

not responsible for transfer of structural self-weight onto supports) and the maximum would be 1/4 of

the maximum horizontal braking forces (as there are 5 sets of this type of connection under each

diaphragm). The design horizontal braking force of the traffic condition with the highest vertical

loads on the structure was calculated to be 601.72kN which implies that each of the four bolt is

subjected to load of 150.4kN if only the braking force is considered. And as such for a cyclic tensile

testing of an M22 bolt the amplitude is 0kN and 150kN at 5-10Hz.

The maximum design axial tension of an M22 bolt with 0.8 factor (allowable maximum design load is

only 80% of nominal axial capacity) is 198kN. The 150.4kN due to horizontal braking forces is a lot

less than the design load which is still less than the axial capacity. However, if self-weight of the

structure and the other vertical loads on the bridge adds on to that load, the total applied load on the

M22 bolt at the diaphragm may very well be over the allowable maximum design load especially that

that location is where the maximum internal bending moment and maximum deflection of the bridge

occurs.