BEST PRACTICE RECOMMENDATIONS - PHIUS · Intake and exhaust hoods min 6’ apart, above snow levels...
Transcript of BEST PRACTICE RECOMMENDATIONS - PHIUS · Intake and exhaust hoods min 6’ apart, above snow levels...
Second and Delaware, Kansas City, MO
BEST PRACTICE RECOMMENDATIONS
©2016 Passive House Institute US | PHIUS 1
OUTLINE
� VENTILATION & COMPONENT REQUIREMENTS UNDER PHIUS+
� COMPARISON TO OTHER VENTILATION STANDARDS:
� ASHRAE 62.2 2016 ERV/HRV� ASHRAE 62.2 2016 ERV/HRV
� IRC
� BSC Standard 01
� CONCLUSIONS & RECOMMENDATIONS
2©2016 Passive House Institute US | 2
LEARNING OBJECTIVES
� Understand the ventilation and system requirements for PHIUS+2015 certification as currently in place
� Understand components and layout requirements and best practices
� Understand how PHIUS+ ventilation system requirements differ from other ventilation requirements differ from other ventilation standards
� Understand tech committee to be working on issuing/confirming guidance on appropriate kitchen exhaust solution
3©2016 Passive House Institute US |
Definition &
Purpose
Controlled movement of air into
and out of a building, generally
using mechanical means,
through deliberately placed
holes in the building envelope
Provide the necessary
4
Provide the necessary
fresh(supply) air and remove
the necessary stale (exhaust)
air to maintain high indoor air
quality (control temperature,
humidity, odors, carbon
dioxide, airborne contaminants,
etc.) inside the building
©2016 Passive House Institute US |
Contaminants in Indoor Air
Molds
Pollens
Pets
From Outdoors From Indoors
People
Dust
Radon
Mold/Bacteria
Formaldehydes
VOC/PM-2.5 &10
Soil gases CO2 + Humidity
5
CO
©2016 Passive House Institute US |
Methods for Improving Indoor Air Quality
Pets, harmful cleaners,
bathroom/kitchen moisture &
odors, airborne contaminants, off-
gassing building materials, etc.
1: Source Control
Bring in “fresh” outside air, exhaust
“stale” inside air
2: Ventilation
Clean the inside air
3: Filtration
6©2016 Passive House Institute US |
Mechanical Ventilation Methods
•Neutral Pressure
•Air Inlet & Exhaust Controlled
Balanced
7
Heat Recovery Ventilation Heating Loss is equal to
0.6-2.2 kBTU/ft²yr for cool moderate climate.
This is 13-46% of the PH Heating Limit (4.75 kBTU/ft²yr)
Controlled
•VERY Efficient w/ Heat Recovery
Balanced
©2016 Passive House Institute US |
Mechanical Ventilation Methods
•Depressurizes Building
•Draws Air in Randomly
•Poor Efficiency
•May Hurt Building Durability
Exhaust Only
Exhaust Only
•Pressurizes Building
•Forces Air Out Randomly
•Poor Efficiency
•May Hurt Building Durability
Supply OnlySupply Only
8
Exhaust or Supply Only Ventilation Heating Loss is equal to
6.3-9.5 kBTU/ft²yr for Central Europe
This is 133-200% of the PH Heating Limit (4.75 kBTU/ft²yr)
©2016 Passive House Institute US |
Mechanical Ventilation Heat Recovery Efficiency
9
s. www.PHIUS.ORG /Tools/Resources for:
1. HVI-Winter-Ratings-modified-for-PHIUS-modeling
©2016 Passive House Institute US |
Ventilation System ConceptFor Excellent Distribution
ALL Ventilation Through HRV/ERV
Air Extracted
10©2016 Passive House Institute US |
Air Extracted from “Wet” Rooms
Supplied to Living/Sleeping Rooms
Ventilation Flow Criteria
11
Extract Air:Extract Air:
• Kitchen – 35 cfm
• Bathrooms – 24 cfm
• ½ Bath – 12 cfm
Max Design
Airflow =
Greater of
Supply/
Extract
PH delivered ventilation exceeds ASHRAE 62.2, because PH sizes
ventilation systems to meet actual loads, not assuming a leaky
envelope will provide any fresh air
Supply Air:Supply Air:
• 18 cfm/person (DIN1946)
• OR 0.3 AC/h
• Typ Home: 72 cfm
©2016 Passive House Institute US |
Ventilation System Layout -Recommendations
Keep Ambient (Outside) Air Ducts Short – place ventilator centrally located, close to envelope
Keep Ambient (Outside) Air Ducts Short – place ventilator centrally located, close to envelope
Well-Insulated w/ Vapor Impermeable InsulationWell-Insulated w/ Vapor Impermeable Insulation
12
Keep Conditioned (Inside) Air Ducts
Within the Thermal Envelope
Keep Conditioned (Inside) Air Ducts
Within the Thermal Envelope
Minimize Duct LossesMinimize Duct LossesSource:
www.proairservices.i.e.com
©2016 Passive House Institute US |
Ventilation System Layout -Best Practice
Smooth InteriorSmooth Interior
Minimize Bends/Kinks/ConstrictionsMinimize Bends/Kinks/Constrictions
Low Velocity (< 3 m/s | ~600fpm)Low Velocity (< 3 m/s | ~600fpm)
Tightly Sealed (< 3% Leakage)Tightly Sealed (< 3% Leakage)
Minimize Duct Losses
13
Size for Low & High Speed (Air Flow)Size for Low & High Speed (Air Flow)
Short & Centralized Duct LayoutShort & Centralized Duct Layout
(Use Far-Throwing Diffusers & Coanda Effect)(Use Far-Throwing Diffusers & Coanda Effect)
Intake away from pollutant sources Intake away from pollutant sources
Intake and exhaust hoods min 6’ apart, above snow levels with screened weather hoodsIntake and exhaust hoods min 6’ apart, above snow levels with screened weather hoods
Source:
www.proairservices.i.e.com
©2016 Passive House Institute US |
Ducts and Ventilator Noise
Sound Attenuation
• Vibration isolate ERV/HRV from floor joists
• Use flex duct or silencers
• to mitigate noise from rigid ducts
Sound Attenuation
• Vibration isolate ERV/HRV from floor joists
• Use flex duct or silencers
• to mitigate noise from rigid ducts
14
rigid ducts
• between bedrooms
• Consider sound attenuation in walls/ceiling/floor of mechanical room
rigid ducts
• between bedrooms
• Consider sound attenuation in walls/ceiling/floor of mechanical room
Source: Fantech
©2016 Passive House Institute US |
Ducts: Exhaust Placement
• in far corner of bathroom
• away from doorBathroomsBathrooms
15
• at least 6’ away from cooktop
•with grease filterKitchensKitchens
©2016 Passive House Institute US |
Ducts: Supply Placement
• Placed high in the room for coanda effect
• Typ. pointed towards windowsBedroomsBedrooms
• Placed high in the room for coanda effect
• Typ. pointed towards windows
Living/Family Rooms
Living/Family Rooms
16
• Dependent on occupancy
• For residences, treat as bedroomOfficesOffices
• Supply air similar to other floorsConditioned BasementsConditioned Basements
©2016 Passive House Institute US |
Duct Layout Single Unit Example
Layout Review:
� Find Exhaust Locations and Flow Rates
� Balance with Supply Locations
17
Supply Locations
� No Short Circuits
� Short runs with distribution towards perimeter
� Duct sized properly for flow
©2016 Passive House Institute US |
Effective Ventilation System Attributes
Ensure Even Distribution Throughout
•Use Adjustable Diffusers
•Set Each Register and Diffuser
•Balance Overall In & Out Flow
Balance the System
(< 10% Diff.)
Balance the System
(< 10% Diff.)
•Use Jump Ducts, Undercut Doors
Overflow Openings Between
Overflow Openings Between
18
Doors
•1 Pa Maximum Differential Between RoomsBetween Rooms
• No Recirculating Air StreamsAvoid “Short
Circuits”
Avoid “Short
Circuits”
• Simple Low, Medium or High
• Overrides in Kitchen & BathsControlsControls
©2016 Passive House Institute US |
Kitchen Ventilation Requirements
•Continuous
•Boost override in kitchen to max
35 cfmKitchen Exhaust
35 cfmKitchen Exhaust
•Good capture efficiency
RecircHoodRecircHood
19
efficiencyRecircHoodRecircHood
• Min 6’ from stoveExhaust
placement Exhaust
placement
•MERV 7 filter at kitchen
intakeFiltrationFiltration
©2016 Passive House Institute US |
IAQ Measured Results
Approx. continuous ventilation rate: 20+ cfm average
20©2016 Passive House Institute US |
VENTILATION STANDARDSVENTILATION STANDARDS
21©2016 Passive House Institute US |
Example: 1,800ft2 (gross), 3 beds
0.01* cfm+ 0.02 cfm * per 1ft2 (gross) + (7.5cfm x # of bedrooms +1)
ASHRAE 62.2-2016
22
*ASHRAE calls for 0.03cfm/ft2, but allows 0.02cfm/ft2
infiltration credit
(0.01cfm x 1800) + (0.02cfm x 1800) + (7.5cfm x 4) = 48cfm (mech.) + 36cfm (infiltration) = 84 cfm
©2016 Passive House Institute US |
ASHRAE 62.2-2016 – Local Exhaust
Kitchens – 100cfm intermittent / has to be directly vented if rate is less than 5 ACH continuous
Bathrooms - 50cfm intermittent / 20cfm continuous
23
Example – 10’Wx20’Lx9’H kitchen = 150cfm
This is a problem in medium to big and open kitchens!
©2016 Passive House Institute US |
ASHRAE 62.2-2016 – Kitchen Exhaust
Workaround 1 – design for intermittent (ERV/HRV on boost pulls 100cfm from kitchen)
Example A – 10’Wx20’Lx9’H kitchen = 1800 ft3 x5ACH/60min = 150cfm
Kitchens – 100cfm intermittent / 5 ACH continuous
24
Use booster switch and duct regulators to pull required from the kitchen
Example B: 10’Wx10’Lx9’H space around range = 900 ft3 x5ACH /60min = 75cfm
Workaround 2 – define volume as “reasonable” area surrounding range and design for continuous
kitchen)
©2016 Passive House Institute US |
ASHRAE 62.2-2016 – NEW
25
Combined intake/exhaust for direct kitchen vent if cross contamination is less than 10% as attested by manufacturer in writing.
NOT ALLOWED FOR BALANCED VENTILATION SYSTEMS
©2016 Passive House Institute US |
IRC 2012 and 2015
Based on square footage/bedrooms of home, s. table below
26
1,350ft2 (net), 3 bedrooms = 60cfm
©2016 Passive House Institute US |
Example: 1,800ft2 (gross), 3 beds
0.01 cfm* per 1ft2 (gross) + (7.5cfm x # of bedrooms +1)
BSC Standard 01(Balanced, intermittently balanced or unbalanced)
27
*0.75 credit for balanced distributed systems: 0.75x48cfm = 36cfm
(0.01cfm x 1800) + (7.5cfm x 4) = 48cfm
©2016 Passive House Institute US |
Example: 1,800ft2 (gross), 3 beds
100 cfm per kitchen+ (7.5cfm x # of bedrooms +1)
BSC Standard 01, additional kitchen exhaust, intermittent, directly exhausted, dampered
28
Total ventilation for balanced distributed systems:
= 36cfm + 100 cfm direct intermittent kitchen exhaust
100 cfm x 1= 100 cfm
©2016 Passive House Institute US |
Passive Buildings Ventilation Requirement, Continuous
Example: 1,800ft2 (gross)…~1,350ft2 iCFA
Minimum 0.30ACH (based on net enclosed volume)
29
10,800 x 0.30 / 60 = 54cfm
Approximate volume: 1,350 x 8 = 10,800ft3
©2016 Passive House Institute US |
Example: 1,800ft2 (gross), 3 beds, 1 kitchen, 2 baths, 1 powder room/laundry
(35cfm x # of kitchens) + (24cfm x # of bathrooms) + (12cfm x # powder room/laundry)
Passive Buildings Ventilation System Capacity Sizing Requirement for Max Extract Air Event
30
*Assumes no infiltration to help meet requirement
35cfm + (24cfm x 2) + 12 cfm = 95cfm
©2016 Passive House Institute US |
Summary System Components
� Air-tight envelope, no infiltration
� Very efficient balanced ventilation
system with heat recovery and filtration
� Duct system
� High quality recirculating range hood to
capture large particles
� Balanced ventilation Kitchen exhaust
31
� Balanced ventilation Kitchen exhaust
with boost override and filter at intake
� Overflow provisions at rooms
� If direct exhaust depressurizing
appliances provide make-up air
� If combustion appliances then direct-
vented
©2016 Passive House Institute US |
Standard Recommendation
� Passive building ventilation standard:
� Sizing requirements, ventilation flow
rates, required local exhaust
� Efficiency requirements by climate
� Testing and commissioning protocols
� Air-tightness and compartmentalization
protocols
32
protocols
� Rules for combustion and exhaust
appliances, make-up air
� Filtration requirements
� Duct system requirements, intake,
exhaust placement, insulation
� Specify indoor air quality limits for
VOC/CO2/PM 2.5-10
©2016 Passive House Institute US |
Thank You
Questions?
©2016 Passive House Institute US | 33
www.PHIUS.org | www.PHAUS.org