inflorescence odours and pollinators of arum and amorphophallus
Best Design Practices for Odour Management of High Profile ...€¦ · 6th IWA Conference on Odours...
Transcript of Best Design Practices for Odour Management of High Profile ...€¦ · 6th IWA Conference on Odours...
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 1
Best Design Practices for Odour Management of High
Profile, Waste Water Applications in an Urban
Environment
Derek S. Webb1* and Caleb Olesen1
1 Biorem Technologies, Guelph, Ontario, Canada N1H 6H9
*Corresponding author e-mail, [email protected]
ABSTRACT Three case studies are presented that demonstrate best design practices for
biological odour control systems to be aesthetically pleasing, quiet and provide
high levels of performance for total odour control. These biofilters feature
custom, site specific, below grade installations and engineered permanent
biofilter medias that allow low EBRT’s; energy efficiency and higher total odour
removal.
KEYWORDS: biofiltration, biofilter, biotrickling filter, odour control,
odour, wastewater, WWTP, pumping station, urban, H2S.
INTRODUCTION
New Challenges Facing Odour Control
Decades ago wastewater treatment plants were designed and built on the outskirts of the cities
that they service. Wastewater treatment plants and sewer infrastructure are increasingly having
to deal with the reality of urban encroachment. As a result, quality of life issues such as noise
(De Heyder, Ockier, Jansen, & Huiberts, 2001), odour (Lasaridi, et al., 2010) and aesthetics are
becoming very important for nearby residents. This recent increase of concern for efficient
odour control in urban areas has not only been observed in developed countries but also in
developing countries (Lazarova, Abed, Markovska, & Dezenclos, 2013).
Historically odour control at wastewater treatment plants has focused primarily or solely on the
reduction of hydrogen sulphide (H2S) or ammonia (NH3). The problem with this approach is
there are always other compounds that contribute to the overall odour (Lebrero, Bouchy, Stuetz,
& Muñoz, 2011). While there are situations where H2S is expected to be the primary contributor
to overall odor, there are also many situations where the contribution of H2S to overall odour is
minor compared to other compounds (McGinley & McGinley, 2008).
A Brief Review of Odour
Odour is a psychophysical phenomenon in which the sensed odour intensity is related through
a power law to the concentration of the chemical following the equation:
𝐼 = 𝑘𝐶𝑛 Equation 1
Where I is the sensed odour intensity, C is the concentration of the odorant and k and n are
constants specific to each odorant (McGinley, McGinley, & McGinley, 2000). Odour
concentration is similar to odour intensity, but the two measurements should not be confused
to be the same. Odour concentration is number of dilutions necessary to reduce the odour in the
sample to threshold of detection, while odour intensity is the perceived strength of the undiluted
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 2
sample. The concentration of individual odorants can be measured using analytical methods
such as gas chromatography, however the resulting perception of odour is more than just the
concentration of the odorant. A measurement of odour intensity or concentration necessitates
the use of a human testing panel.
Odour concentration measurements are typically measured by laboratory dilution of air
samples. The diluted samples are presented to panelists in an ascending concentration series
along with either one or two blank samples (binary or triangular forced choice). The panelist
has to choose which of the samples they think is the odorous sample, and indicate whether they
are guessing, have actually detected the odorous sample or if they can recognize what type of
odour they are smelling. The dilution factor at which 50% of the panelists can detect an odour
is reported as the odour concentration, with units of OU.
In addition to the odour concentration, there are other parameters of odorous samples that can
be measured by human panel including intensity, character and hedonic tone. Intensity is
measured by presenting panelists with suprathreshold dilutions and requiring them to be
evaluated by panelists in a 7-item Likert scale from “no odour” to “extremely strong odour”.
Character is measured by having panelists assign a number from 0 to 5 to eight different odor
descriptors: vegetable, fruity, floral, medicinal, chemical, fishy, offensive and earthy. Hedonic
tone is measured by having panelists rank the overall odour on a Likert scale from unpleasant
to pleasant. (McGinley, McGinley, & McGinley, 2000)
Wastewater Treatment Plant Odours
As has been briefly discussed, there are many more compounds than just H2S and NH3 that
contribute to overall odour from wastewater treatment plants. Table 1 shows the compounds
that commonly contribute to wastewater treatment plant odours. The relative amounts of these
compounds are present at varying levels throughout the wastewater treatment plant process.
The odours generated by wastewater treatment processes can be generally divided up according
to where they are generated: collection systems, liquid treatment and biosolids treatment.
Collection systems and liquid treatment systems typically produce high levels of H2S, and low
levels of volatile organic compounds (VOCs), organic sulphide compounds (OSCs) and NH3
whereas biosolids treatment processes typically produce lower levels of H2S, but higher levels
of VOCs, OSCs and NH3 (Tchobanoglous, Burton, & Stensel, 2003). Since the odour character
is expected to be different depending on the process that is producing the odours, there isn’t a
one-size-fits all solution to wastewater treatment plant odours. Any solution should be custom
designed based on the expected levels of H2S, OSCs, VOCs, NH3 and the expected overall
odour concentration.
In addition to the relative amounts of compounds that can be present, there are several factors
that influences the resulting concentration of these compounds that is emitted from the
wastewater. Wastewater that is subjected to higher temperatures, excessive turbulence and that
has high wastewater/air interface areas allows dissolved odorous compounds to more easily
transfer from the water phase into the air phase (Lebrero, Bouchy, Stuetz, & Muñoz, 2011).
Additionally, while ventilation rates don’t change the mass of odorants treated (increasing the
ventilation rate usually results in proportionately decreasing the odorant concentration),
ventilation rates are important in order to prevent fugitive emissions, and in the case of occupied
spaces, to reduce the odorant concentrations to levels that are safe for operators to work in.
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 3
Table 1: Common wastewater treatment plant odours
Odor descriptor Sensorial experience Chemical compound Fecal/Sewer-like Faecal
Manure
Sewery
Skatole
Indole
Earthy/Musty/Moldy Earthy/Musty
Moldy
Geosmin
2-Methylisoborneol
2,4,6 Trichloroanisole
Oxidant/Chlorinous Chlorinous Chlorine
Monochloramine
Dichoramine
Grassy/Woody Woody
Green/Grass
Cardboard
Hay
Cis 3-Hexen 1-ol
Sulfide/Cabbage/Garlic Decaying vegetation
Rotten eggs
Garlicky
Canned corn
Marshy/Swampy
Skunk
Burnt rubber
Coffee grounds
Hydrogen sulfide
Methyl mercaptan (OSC)
Dimethylsulfide (OSC)
Dimethyl trisulfide (OSC)
Fragrant/Fruity Soapy/Detergenty
Fruity
Citrusy
Green
1 Dodecanal
D-Limonene
Rancid/Putrid Yeasty
Sour mil
Rancid
Fatty/Oily
Sweaty
Sour cheese
Putrid
Decayed
Heptanal
Pyridine
Ammonia/Fishy Ammonia
Cat urine
Fishy
Ammonia
Trimethylamine
2,4 Decadienal
2,4 Heptadienal
Medicinal/Alcohol Medicinal
Alcohol
Chlorophenol
1-Butanol
Solventy/Hydrocarbon Burnt/Smoky
Tarry
Rubbery
Solventy
Glue
Gasoline
Paint
Mothballs
Shoe polish
Chemical
Methyl methacrylate
Toluene
Xylene
Styrene
Methyl isobutyl ketone
Dichlorobenzene
Cumene
Nose feel Pungent
Irritating
Metallic
Sharp
Ammonia
Ferrous sulfate
Reproduced from (Lebrero, Bouchy, Stuetz, & Muñoz, 2011)
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 4
Recent Advances in Biological Treatment of Odours
Biological treatment of wastewater treatment plant odours has been performed commercially
for around 50 years. It was developed primarily in Europe using open top soil biofilter beds.
The concept for treatment of odours was to use a substrate to immobilize beneficial bacteria
on the surface and allow them to produce enzymes which would oxidize the compounds of
concern. This is an example of a fixed-film bioreactor.
Up until the 1990’s most biofilter media were compost, woodchips, peat or soil (Leson &
Winer, 1991). Unfortunately, these conventional materials had many limitations from an
engineering perspective. Given the fact that most of these materials were natural, variations
from batch to batch made it difficult to accurately predict performance, which had the
unintended consequence of vendors and consultants over designing the size of the systems to
ensure a minimum threshold of performance was achieved. In addition, the organic nature of
these materials behaved as a carbon source, gradually being consumed by the microorganisms
over time and resulting in declining performance.
One of the often overlooked deficiencies of conventional media was the energy consumption
that such systems exerted on their facilities. Organic media systems often operate with 2000
to 3000 Pascals of differential pressure. For small air flows, this may not add up to a financial
burden for the facility, however, with larger air flows, the cost of air movement can be a
significant proportion of the operating costs.
From the early 2000’s to present, there has been a significant amount of research to address
the multitude of deficiencies with conventional approaches. Various Universities as well as
commercial entities have examined ways to develop a microbial immobilization matrix that
would improve energy efficiency, increase predictability and longevity, increase performance
and decrease overall footprints.
Through a recognition that a large number of municipal odour applications were a result of
hydrogen sulphide emissions, many vendors started improving biotrickling or biotower media
to use a variety of structured plastic packing. This helped to reduce the footprint and energy
consumption challenges, but fell short of resolving issues with Total Odour Reduction,
especially on the more recalcitrant compounds such as DMS and DMDS, which are often
associated with biosolids applications.
Other research programs focused efforts on developing engineered biofilter media with very
specific surface properties to help address the challenge of increasing overall destruction
efficiencies of the recalcitrant organic sulphur compound family. As a part of this
development work, process optimization became a focus to ensure the reactor operation was
properly paired with the intended performance objectives. For example, one of the process
improvements was the realization that the removal of hydrogen sulphide and methyl
mercaptan was best achieved by autotrophs operating in an acidic environment; while the
removal of volatile fatty acids and the other organic sulphur compounds were best achieved
by heterotrophs in a neutral environment.
One vendor in particular, Biorem Technologies Inc., was successful in developing a suite of
engineered media that are tailored for the particular uses that may arise in the treatment of
wastewater odours from the various sources. These media offer extended operational lives (to
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 5
20 years and beyond), high rates of organic sulphur compound destruction; and reduced
footprints. When combined with pre-treatment stages for the removal of elevated hydrogen
sulphide or ammonia, an engineered media solution allows for unique construction of reactors
for dense urban applications.
The remainder of this paper will present three case studies of advanced biological treatment
systems which feature the advanced designs that are necessary to meet the stringent odour
requirements that are being encountered more and more often.
CASE STUDIES
Case Study #1: Ville de Repentigny WWTP, Quebec
The “station de traitement des eaux usées à l’île Lebel” is the wastewater treatment plant that
serves the city of Repentigny. The WWTP serves a population of 63,000, treating 24,000
m3/day wastewater and producing 10,000 kg/day dewatered sludge for land application. The
plant was built in the mid 1990’s, and up until 2013, operated without treating their air with any
odour control equipment. Instead, odours were controlled by adding caustic soda and potassium
permanganate to the raw wastewater.
Figure 1: Map of the Ville de Repentigny WWTP
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 6
As can be seen in Figure 1, the WWTP is located within a 20 hectare park that features multi-
use trails just 40 metres from the main wastewater treatment plant building. The park is a very
high traffic area and frequently holds events such as Oktoberfest, fundraising events and other
group activities. In 2009, land 200 metres from the WWTP was being developed for 3 high
density residential buildings totaling 150 condominium units. The city conducted an odour
study and determined that odour control was required at the WWTP.
The City required a system that could be kept out of sight and out of mind of the nearby residents
and the multitude of tourists that visit the park each summer. The system needed to be robust
in terms of performance and able to address potentially elevated levels of hydrogen sulphide
without acidification of the media while still having high rates of removal for the other odour
causing compounds.
Given the high visibility of the WWTP and the limited space available for odour control,
Biorem worked with the city to design a biofiltration system that is inconspicuous, low footprint
and high efficiency. Table 2 gives an overview of the design parameters for the odour control
system.
Table 2: Repentigny biofilter design parameters
Parameter Value
Airflow 34 000 m3/h
Design H2S 5 ppm average, 30 ppm peak
Design OSC 1 ppm average, 3 ppm peak
Design Odour 3 000 OU average, 20 000 OU peak
BTF Media Polyurethane Random Packing
BTF EBRT 4 seconds
BF Media XLD (Biorem proprietary engineered media)
BF EBRT 20 seconds
Performance Guarantee 99% H2S, 95% Odour
As is shown in Figure 2, the biofilter was designed by Biorem to be completely below grade,
with the mechanical equipment room and a future ozone generator room located on top of the
biofilter roof at grade. The stack of the biofilter was also designed to be pleasing to the eye.
Figure 3 through Figure 5 show some pictures of the biofilter.
Figure 2: 3D Rendering of the Repentigny biofilter
Figure 3: Outside view of the Repentigny biofilter
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 7
Figure 4: Repentigny mechanical room on roof of
BTF
Figure 5: Repentigny future ozone generation room
on roof of BF
The biofilter system was commissioned in May 2013 and performance tested by Biorem in
October 2013 and again by an independent third party in November 2013. As can be seen in
Table 3, with only 25 seconds of total EBRT the system is achieving greater than 95% odour
removal.
Of particular note are the very low absolute odour levels witnessed on the discharge of the
system. Industry standard guidelines for estimating odour concentration from a well-designed
carbon polishing unit is typically set at 100-150 OU. The odour concentration released from
the second stage of this system far exceeds the performance expected from even carbon
polishing.
Table 3: Repentigny biofilter performance
Date Description Inlet to BTF Outlet from BF Odour Removal
October, 2013 Sample 1 3 509 OU 64 OU 98.2%
October, 2013 Sample 2 5 470 OU 231 OU 95.7%
November, 2013 Sample 3 1 136 OU 23 OU 97.9%
November, 2013 Sample 4 2 145 OU 45 OU 97.9%
Case Study #2: Morton Avenue Forced Main Outlet, Ontario
Georgina is one of the many small towns in Ontario that is experiencing very high growth. The
population is expected to double from 2011 to 2036. As a result of this projection the current
water and wastewater infrastructure was expanded by 55% in 2011. Part of this expansion
involved building the Joe Dales pumping station and an associated odour control facility at the
force main outlet on Morton Avenue (Forcemains in Quick Time, 2013).
As can be seen from Figure 6, the force main outlet and its associated odour control facility are
located extremely close to residential properties (3 metres from the closest property line, 20
metres from the closest house) and, due to the relatively long distance of 5.6 km to the pumping
station, the H2S levels were expected to be relatively high for a northern application (peaks of
185 ppm).
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 8
Figure 6: Satellite view of Morton Ave biofilter
Biorem worked with the Region of York to design a robust biofilter at the remote odour control
facility. In order to achieve the highest removal possible, two proprietary engineered inorganic
biofilter medias were used, the first to remove the majority of the H2S, and the second to polish
the remaining H2S and to remove trace organic sulphides and other VOC’s.
Table 4: Morton Ave biofilter design parameters
Parameter Value
Airflow 1 700 m3/h
Design H2S 17 ppm average, 185 ppm peak
Design OSC <1 ppm average
Design Odour 150 000 OU peak
BF Stage 1 Media Biosorbens (Biorem proprietary engineered media)
BF Stage 1 EBRT 25 seconds
BF Stage 2 Media XLD (Biorem proprietary engineered media)
BF Stage 2 EBRT 20 seconds
Performance Guarantee 99.9% H2S, <350 OU or <500 OU with positive hedonic tone
Given the residential location of this odour control facility, the system was designed with a
control room housing the exhaust fans, humidification system, control panel, instrumentation
and control valves. The biofilter itself was designed as a below grade concrete vessel beside the
control room. Figure 7 through Figure 10 show some drawings and pictures of this odour control
facility.
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 9
Figure 7: Section view of the Morton Ave biofilter
Figure 8: Outside view of the Morton Ave biofilter
Figure 9: Morton Ave control room
Figure 10: Morton Ave biofilter with access hatches
open
The biofilter system was commissioned in December 2010 and performance tested by an
independent third party in June 2012. As can be seen in Table 5 and Table 6, with 45 seconds
of total EBRT the system is achieving greater than 99.9% odour removal and greater than 99.9%
H2S removal.
Table 5: Morton Ave biofilter odour performance
Description Inlet to BF1 Outlet from BF2 Odour Removal
Sample 1 615 000 OU 120 OU 99.98%
Sample 2 298 750 OU 50 OU 99.98%
Sample 3 430 500 OU 40 OU 99.99%
Sample 4 664 500 OU 120 OU 99.98%
Table 6: Morton Ave biofilter H2S performance
Description Inlet to BF1 Outlet from BF2 Odour Removal
Sample 1 50 ppm 0.03 ppm 99.94%
Sample 2 17 ppm 0.02 ppm 99.88%
Sample 3 34 ppm 0.01 ppm 99.97%
Sample 4 50 ppm 0.03 ppm 99.94%
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 10
Case Study #3: Ankeny Pumping Station, Oregon
The Ankeny Pumping Station was built in 1929, with major remodels completed in 1952 and
in 2012. The pumping station was originally designed to protect downtown Portland from
flooding, pumping sewage and storm water directly into the Willamette River. In 1952 the city
connected the pumping station forced mains that sent sewage to the then newly built Columbia
Wastewater Treatment Plant. From 2011 to 2015 additional upgrades were completed to
upgrade the pumps and controls and to add odour control while maintaining the pumping
station’s historic exterior (The City of Portland Oregon, 2015).
Figure 11: Satellite view of Ankeny biofilter
As can be seen from Figure 11 the pumping station and associated odour control is located
within a 2.4 km long waterfront park, 50 metres away from an open-air arts and crafts market
and outdoor dining areas. There are also high pedestrian traffic multi-use trails that are only 1
metre away from the exhaust stack of the biofilter. Given the high visibility of the biofilter and
the limited space available for odour control, Biorem designed a biofiltration system that is
inconspicuous, with a small footprint and high efficiency. Table 7 gives an overview of the
design parameters for the odour control system.
Table 7: Ankeny biofilter design parameters
Parameter Value
Airflow 12 750 m3/h
Design H2S 1 ppm average, 20 ppm peak
BF Media XLD (Biorem proprietary engineered media)
BF EBRT 25 seconds
Performance Guarantee 99% H2S
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 11
The biofilter system was designed to be completely below grade with an underground vault for
the exhaust fan, humidification system, control panel, instrumentation and control valves. The
concrete vault and biofilter vessel were covered with top soil and grass seed such that the only
evidence that the odour control system is even there are access hatches and a brushed stainless
steel exhaust stack. Figure 7 through Figure 10 show some drawings and pictures of this odour
control facility.
Figure 12: 3D Rendering of the Ankeny biofilter
Figure 13: Outside view of the Ankeny biofilter
Figure 14: Plumbing and access hatch in the Ankeny
biofilter below grade mechanical room
Figure 15: Headspace above the Ankeny biofilter
media
CONCLUSIONS As was discussed in the introduction, public works engineers are more frequently having to
design wastewater treatment plants and collection systems with nearby residential and
commercial properties in mind. It is becoming very important that equipment be aesthetically
pleasing, quiet, and focused on total odour control, not just one or two odorous compounds.
The case studies presented have achieved these goals by incorporating the following elements:
Custom, site specific, below grade installations. While addressing aesthetics, these
design features also ensure that noise levels of operating equipment do not have a
negative impact on the surrounding communities.
Engineered biofilter media that allow lower EBRT’s and higher total odour removal.
Smaller footprints and the permanent nature of the engineered media allow for fully
enclosed, underground designs.
Multi-stage systems using different media types customize the process design to the
expected foul air makeup. This ensures long term, predictable performance.
Design emphasis on aesthetics, blending the biofilter installations into the surroundings.
This is increasingly important as urban growth rates necessitate integration with
municipal infrastructure.
6th IWA Conference on Odours & Air Emissions, November 16-18, 2015, Paris - France
Best Design Practices for Odour Management of High Profile, Waste Water Applications in an Urban Environment
Written by Derek S. Webb and Caleb Olesen 12
Integrated approach to design, customizing the layout to the specific site requirements
rather than providing off-the-shelf biofilter solutions. No single piece of equipment is
suited for every site and application. Understanding the application is paramount to
ensure the right solution selection.
Incorporating these elements in odour control design can improve the quality of life of
neighbors nearby wastewater treatment plants, virtually eliminating complaints and
maintaining property values.
REFERENCES De Heyder, B., Ockier, P., Jansen, R., & Huiberts, R. (2001). Predicting the sound power and
impact of a wastewater treatment plant. Water Science and Technology, 44(2-3), 231-
241.
Forcemains in Quick Time. (2013, July 4). Water Canada.
Giuliani, S., Zarra, T., Naddeo, V., & Belgiorno, V. (2013). A novel tool for odor emission
assessment in wastewater treatment plant. 13th International Conference on
Environmental Science and Technology. 55. Athens, Greece: Balaban Desalination
Publications.
Lasaridi, K., Katsabanis, G., Kyriacou, A., Maggos, T., Manios, T., Fountoulakis, M., . . .
Stentiford, E. I. (2010). Assessing odour nuisance from wastewater treatment and
composting facilities in Greece. Waste Management & Research, 28(11), 977-984.
Lazarova, V., Abed, B., Markovska, G., & Dezenclos, T. (2013). Control of odour nuisance in
urban areas: the efficiency and social acceptance of the application of masking agents.
Water Science & Technology, 68(3), 614-621.
Lebrero, R., Bouchy, L., Stuetz, R., & Muñoz, R. (2011). Odor Assessment and Management
in Wastewater Treatment Plants: A Review. Critical Reviews in Environmental Science
and Technology, 47(7), 915-950.
Leson, G., & Winer, A. (1991). Biofiltration: An Innovative Air Pollution Control Technology
for VOC Emissions. Journal of the Air & Waste Management Association, 41(8), 1045-
1054.
McGinley, C., McGinley, M., & McGinley, D. (2000). "Odor Basics", Understanding and
Using Odor Testing. The 22nd Annual Hawaii Water Environment Association
Conference. Honolulu, Hawaii.
McGinley, M., & McGinley, C. (2008). Odor Threshold Emission Factors for Common WWTP
Processes. Water Environment Federation / Air & Waste Management Association.
Phoenix, AZ.
Tchobanoglous, G., Burton, F., & Stensel, D. (2003). Wastewater Engineering, Treatment and
Reuse (4th ed.). New Delhi, India: McGraw Hill Education.
The City of Portland Oregon. (2015). Ankeny Pump Station Upgrade. Retrieved from The City
of Portland Oregon Website: https://www.portlandoregon.gov/bes/article/394265