B737-Center Tank Fuel Pumps

19
8/13/2019 B737-Center Tank Fuel Pumps http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 1/19 737.1 Center Tank Fuel Pumps Center Tank Fuel Pumps Terry Sheehan 737NG Procedures Manager Boeing Commercial Airplanes May 2004 Terry Sheehan 737NG Procedures Manager Boeing Commercial Airplanes May 2004

Transcript of B737-Center Tank Fuel Pumps

Page 1: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 1/19

737.1

Center Tank Fuel PumpsCenter Tank Fuel Pumps

Terry Sheehan737NG Procedures Manager 

Boeing Commercial Airplanes

May 2004

Terry Sheehan737NG Procedures Manager Boeing Commercial Airplanes

May 2004

Page 2: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 2/19

737.2The Boeing Company

Hydro-Aire Fuel PumpsHydro-Aire Fuel Pumps

• Two areas of concern were identified on Hydro-Aire

fuel pumps installed on 737-600/-700/-800/-900airplanes

 – Wire chafing

 – Localized overheating

• Two separate Airworthiness Directives issued

 – Both mandated similar operational restrictions

• Two areas of concern were identified on Hydro-Aire

fuel pumps installed on 737-600/-700/-800/-900airplanes

 – Wire chafing

 – Localized overheating

• Two separate Airworthiness Directives issued

 – Both mandated similar operational restrictions

 Background  Background 

Page 3: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 3/19

737.3The Boeing Company

BackgroundBackground

• In August 2002, teardown of several failed Hydro-

 Aire fuel pumps indicated the potential existed forwires to come in contact with the rotor as a result ofinstallation errors

• Evidence of arcing due to chafed wires wasdiscovered

• In August 2002, teardown of several failed Hydro-

 Aire fuel pumps indicated the potential existed forwires to come in contact with the rotor as a result ofinstallation errors

• Evidence of arcing due to chafed wires wasdiscovered

Wire Chafing Wire Chafing 

Page 4: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 4/19

737.4The Boeing Company

BackgroundBackground

Wire Chafing Wire Chafing 

Page 5: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 5/19

737.5The Boeing Company

BackgroundBackground

Wire Chafing Wire Chafing 

Page 6: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 6/19

737.6The Boeing Company

BackgroundBackground

• In response, the FAA released AD 2002-19-52

which mandated operational restrictions

• The AD provided terminating action

 – Inspection of pumps per Boeing or Hydro-Aire

Service Bulletin required prior to installation – Once center tank fuel pumps inspected and

found to be in compliance, the operationalrestrictions could be removed on an airplane-

by-airplane basis

• In response, the FAA released AD 2002-19-52

which mandated operational restrictions• The AD provided terminating action

 – Inspection of pumps per Boeing or Hydro-AireService Bulletin required prior to installation

 – Once center tank fuel pumps inspected andfound to be in compliance, the operationalrestrictions could be removed on an airplane-by-airplane basis

Wire Chafing Wire Chafing 

Page 7: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 7/19

737.7The Boeing Company

BackgroundBackground

• In October 2002, evidence of extreme localized

overheating in the area of the primer impeller wasfound on several in-service fuel pumps

• Further investigations indicated the potential forextreme over-temperature exposure outside the

explosion proof chamber of the fuel pump existed

• In October 2002, evidence of extreme localized

overheating in the area of the primer impeller wasfound on several in-service fuel pumps

• Further investigations indicated the potential forextreme over-temperature exposure outside the

explosion proof chamber of the fuel pump existed

 Localized Overheating  Localized Overheating 

Page 8: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 8/19

737.8The Boeing Company

BackgroundBackground Localized Overheating  Localized Overheating 

Page 9: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 9/19

737.9The Boeing Company

BackgroundBackground Localized Overheating  Localized Overheating 

Page 10: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 10/19

737.10The Boeing Company

BackgroundBackground

• The FAA released AD 2002-24-51 which reinstated

the requirement to maintain minimum fuel levels tokeep center fuel tank pump inlets covered

• No terminating action defined

• The FAA released AD 2002-24-51 which reinstated

the requirement to maintain minimum fuel levels tokeep center fuel tank pump inlets covered

• No terminating action defined

 Localized Overheating  Localized Overheating 

Page 11: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 11/19

737.11The Boeing Company

BackgroundBackground

• In June 2003, the FAA issued Approval Letter

140S-03-189 to allow a “staged shutoff” followingapproved X-ray inspection of center tank fuelpumps

 – Allows all fuel in the center tank to be used

• A Flight Crew Operations Manual Bulletin wasreleased to provide operating instructions

 – Either the AD procedures or the AMOCprocedures to be used at the discretion of theairline

• In June 2003, the FAA issued Approval Letter

140S-03-189 to allow a “staged shutoff” followingapproved X-ray inspection of center tank fuelpumps

 –  Allows all fuel in the center tank to be used

•  A Flight Crew Operations Manual Bulletin wasreleased to provide operating instructions

 – Either the AD procedures or the AMOCprocedures to be used at the discretion of theairline

 Alternative Method of Compliance (AMOC) Alternative Method of Compliance (AMOC)

Page 12: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 12/19

737.12The Boeing Company

Design ImprovementsDesign Improvements

• Original Master Caution system logic requires both

center tank fuel pumps to indicate low pressurebefore the Master Caution and FUEL annunciationilluminate

• With the new system logic, a low pressure condition

for either center tank fuel pump will illuminate theMaster Caution and FUEL annunciation

• Original Master Caution system logic requires both

center tank fuel pumps to indicate low pressurebefore the Master Caution and FUEL annunciationilluminate

• With the new system logic, a low pressure condition

for either center tank fuel pump will illuminate theMaster Caution and FUEL annunciation

 Master Caution System Master Caution System

Page 13: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 13/19

737.13The Boeing Company

Design ImprovementsDesign Improvements

• A center tank fuel pump is automatically shut off

after approximately 15 seconds of continuous lowpressure

 – No indication to the flight crew

• Considered a backup to normal flight crew actions

• If fuel remains in the center tank, the system can bereset by turning the fuel pump switch OFF, then ON

•  A center tank fuel pump is automatically shut off

after approximately 15 seconds of continuous lowpressure

 – No indication to the flight crew

• Considered a backup to normal flight crew actions

• If fuel remains in the center tank, the system can bereset by turning the fuel pump switch OFF, then ON

 Automatic Shutoff  Automatic Shutoff 

Page 14: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 14/19

737.14The Boeing Company

Design ImprovementsDesign Improvements

• In the original design, the alert is displayed if the

center fuel tank contains more than 1600pounds/726 kilograms of fuel and both center tankpumps are producing low or no pressure

• In the new design, the alert will be displayed if the

center tank contains more than 1600 pounds/726kilograms of fuel and both center tank pumps areOFF

• In the original design, the alert is displayed if the

center fuel tank contains more than 1600pounds/726 kilograms of fuel and both center tankpumps are producing low or no pressure

• In the new design, the alert will be displayed if the

center tank contains more than 1600 pounds/726kilograms of fuel and both center tank pumps areOFF

CONFIG Alert CONFIG Alert 

Page 15: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 15/19

737.15The Boeing Company

Revised Normal ProceduresRevised Normal Procedures

Page 16: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 16/19

737.16The Boeing Company

FAA ActionFAA Action

• Boeing has proposed the Master Caution system

logic change and center tank fuel pump automaticshutoff feature as terminating action for AD 2002-24-51

• Boeing believes the FAA will mandate these

changes and propose a 36-month compliance timeafter release of the Service Bulletin

• FAA decision is imminent

• Boeing has proposed the Master Caution system

logic change and center tank fuel pump automaticshutoff feature as terminating action for AD 2002-24-51

• Boeing believes the FAA will mandate these

changes and propose a 36-month compliance timeafter release of the Service Bulletin

• FAA decision is imminent

Page 17: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 17/19

737.17The Boeing Company

Design ImprovementsDesign Improvements

• All three design changes will be available in

production in May 2004 (Line Number 1494 and on)• Available via Service Bulletin in 4th Qtr 2004

•  All three design changes will be available in

production in May 2004 (Line Number 1494 and on)•  Available via Service Bulletin in 4th Qtr 2004

 Availability – 737 NG Availability – 737 NG

Page 18: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 18/19

737.18The Boeing Company

Design ImprovementsDesign Improvements

• Master Caution system logic change will be

available via Service Bulletin in 4th

Qtr 2004• Automatic shutoff feature will be available via

Service Bulletin in 3th Qtr 2005

• Master Caution system logic change will be

available via Service Bulletin in 4th

Qtr 2004•  Automatic shutoff feature will be available via

Service Bulletin in 3th Qtr 2005

 Availability – 737-200 through -500 Availability – 737-200 through -500

Page 19: B737-Center Tank Fuel Pumps

8/13/2019 B737-Center Tank Fuel Pumps

http://slidepdf.com/reader/full/b737-center-tank-fuel-pumps 19/19

737.19The Boeing Company

Design ImprovementsDesign Improvements

• Wire retention system

 – Prevents wires from contacting rotor due toinstallation errors

 – Scheduled to be available in 2nd Qtr 2005

 – Boeing is proposing this change as terminating

action for AD 2002-19-52

• Replacement fuel pump

 – Scheduled to be available in 24 to 36 months

• Wire retention system

 – Prevents wires from contacting rotor due toinstallation errors

 – Scheduled to be available in 2nd Qtr 2005

 – Boeing is proposing this change as terminating

action for AD 2002-19-52

• Replacement fuel pump

 – Scheduled to be available in 24 to 36 months

Future Design FeaturesFuture Design Features