ATEXTREME TEMPERATUREeprints.utm.my/id/eprint/8344/1/BadriAbdulGhani1996_Experimental... · Jurnal...
Transcript of ATEXTREME TEMPERATUREeprints.utm.my/id/eprint/8344/1/BadriAbdulGhani1996_Experimental... · Jurnal...
Jurnal Mekanikal, Jilid II, 1996
EXPERIMENTAL VERIFICATION OF COLUMN
AT EXTREME TEMPERATURE
Badri Abdul Ghani
Mohamed El-Shayeb
Department of Mechanics ofMaterials
Faculty of Mechanical Engineering
Universiti Teknologi Malaysia
T.T.Lie
Division of Building Research
National Research Council, Canada
ABSTRACT
Experimental studies have been carried out to predict the fire
resistance of protected I-shaped steel insulated with ceramic
fibre. The steel section selected were W250-80 and W310-158.
The experimental results are compared with those obtained using
the mathematical models develop by the same authors. The
results indicate that the model is capable ofpredicting the fire.
1.0 INTRODUCTION
Over the .years, various specimens of protected steel columns, insulated with heat
retardant material such as gypsum board, cementitious material and material fibre
were tested. For the purpose of verification of the model given in the research paper
[1], the results of tests on five columns with different cross-section sizes and
insulation thickness will be used for comparison with calculated results. The
columns were made of structural steel section blanketed with ceramic fibres that
35
Jurnal Mekanikal, Jilid tt. 1996
follow its contour. All columns were 3,810 mm long from endplate to endplate The
thickness of the insulation were from 1 inch, 1-112 inch and 2 inches applied on steel
section W250-80 and W315-58. All steel endplates were 25 mm thick. A specimen
is illustrated in Fig. 1 and Fig. 2. The earlier figure shows the cross-section of the 1
shape steel section and location of the thermocouple and strain gauges. The latter
shows the whole length of the column from endplate to endplate.
The steel for the columns was cut to appropriate lengths and then the end
plates were weld to the steel at column extremities. The centering and
perpendicularity of the end plates were given special attention to ensure a high
degree of accuracy. After welding the end plates, twelve holes with diameter of 7/8
inch were drilled in each endplate. The holes were created for studs of the furnace
compressor piston at the bottom and support at the top.
The steel of the column had a specified yield strength of 300 MPa and the
insulation does not contribute to the strength of the column. Chromel-alurnel
thermocouples with a thickness of 0.91 mm were installed at the mid-height of the
column for measuring the temperatures of the steel section at different locations in
the cross section. The locations of the thermocouples are described in National
Standard of Canada CANIULC-SI01-M89.
2.0 TEST APPARATUS
The tests were done by exposing the columns to heat in a column test furnace. The
test furnace was designed to produce the conditions to which member might be
subjected during a fire. It consists of a steel framework supported by four steel
columns with the furnace chamber inside the frame characteristics and
instrumentation of the furnace which has a loading capacity of 1,000 tonnes, are
described in detail in Ref. 13.
36
Jurnal Meka nikal, lilid II, J996
"55 0... <. ,- '._ . ' . ' .... . .__. .... . . . . - -- - . . . . _~/ '/I sol t! a.t. u»II , O.J.5
/ 'jee!. \_. _-... - ... ..:-=.t-. t? 7'
... ff / A t ,2 'n_.
I ".- ',' ·. :f ·/ / / / .•- :»
I~
6 5 .tI '0
~ -~~. ,
1-
J~ . 7
'" ,h1l (gt=", j~25.4 - /- ~ -'_ .• . ._- ---. ..-
--- . .. 7 - ~--- ,--_ . _. '._-- --..~.._- -_....
--- u = ..JL4r "'--
-f-r · ·-'(! ~JJL- ..
H.. ..~..L .,
I 1 1 1:2TOt .' " .' /
.' / , . / ,. / ; / r> .:19 8
...-~3~f- --lf-+._ _ .L?..7- 5__._ _
C>
<0' 0<:\1
Fig, 1 W2S0-80 Steel Section with 1 Inch Ceramic
25.4 mm
.L
Endplate
I'\
I\I
I\
\
\
I
II
III
m II
\II
~ - - --- -54~ Sq -·_-- - ~
T1905 m
J
3810 mm
Fig, 2 The Column Length
37
Jurnal Mekanikal, Jilid II, J996
3.0 TEST CONDITIONS AND PROCEDURES
The tests were done with both ends of the columns fixed i.e. restrained against
rotation and horizontal translation. The columns were tested under a concentric load.
The applied loads were from 59% and 86% of the factored compressive resistance of
the columnstCi) as determined according to the Canadian Standards Association
CSA/CAN-S 16.1-M89 {"Limit States" 1989). The factored compressive resistances
of each column, as well as the applied loads, are given in Table 1. The effective
length factor K used in the calculation of the factored compressive resistance was
that recommended in CSA/CAN-S 16.1-M89 for the given end condition, i.e., 0.65.
The effective length of the columns, KL, was thus assumed to be 2.48 m. However
previous test had indicated a more accurate effective length of 2.0 m because the
extreme ends of the column were not exposed to the fire intensity as much as the
middle part of the column.
Table 1 Factored Compressive and Applied Loads
Resistances of Each Column
Section-Code Insulation Factored Max. Applied RatioColumn and Sizes: Thickness Strength Allowable Load
No. G40.21-M Load300W mm (inch) Cr (kN) (O+L) kN C (kN) CICr
FSI W250 x 80 25 ( 1 ) 2550 1908 1750 0.69
FS2 W250 x 80 38 (1-1/2 ) 2550 1908 1700 0.67
FS3 W310 x 158 25 ( I ) 5098 3856 3000 0.59
FS4 W250 x 80 25 ( 1 ) 2550 1908 2200 0.86
FS5 W310 x 158 50 (2 ) 5098 3856 3800 0.75
D - dead load, L - live load
During the test, the column was exposed to heating in a controlled way that
the average temperature in the furnace followed as closely as possible, the ASTM
E119-88 or CANIULC-S101 standard temperature-time curve.
38
Jurnal Mekanikal, Jilid II, 1996
4.0 RESULTS AND DISCUSSIONS
Using the mathematical model described ill Ref. 1, the temperatures axial
deformations, and strengths of the columns were calculated. In the calculations, the
thermal and mechanical properties of the steel, given in Ref. 4, were used. The
ceramic thermal properties was provided by the supplier Unifrax Corporation.
In the calculation of the time of fire resistance for calculated data, the graph
of load capacity of column against time is used, failure occurs when load carrying
capacity equal to the applied load. The strength decreases with time until it becomes
so low that the column can no longer support the load. The time to reach this point is
the fire resistance of the column. Fire resistance for measured data are determined
when the axial expansion stop. This is because the test only produce data for
temperatures and axial deformation but does not produce load capacity data. Hence
the time for fire resistance is obtained using the graph of axial deformation against
time where failure occurs when the column stop increasing in length.
In Figs. 3 to 7, the calculated average temperatures [1] are compared with the
average temperatures measured at the external surface of the steel section. With the
exception of the test conducted on the column FS3, there is good agreement between
calculated and measured column temperatures. The temperatures measured initially
showed a relatively cautious rise up to temperatures of approximately 50°C,
followed by a period of relatively faster rate of temperature rise. This temperature
behaviour may be the result of the steel section having reach some equilibrium for a
particular time step after the initial cold start. As a whole, which are important from
the point of view of predicting the fire resistance of the columns there is a good
agreement between calculated and measured temperatures [1].
39
Jurnal Mekanikal, Jilid II, 1996700
600
l/l::J'u 500(j)UOl~ 400
~.a 300l!!(\)c,
~ 200I-
100 .
20 30 40 50 60 70 80 89
Time, minutesAverage Temperature of Column FSl for Test and Calculated DataFig. 3
o .I---t---+----t----t----+----+----+----+----+----l
o 10
700
600
III 500 .:::)
'u~Cl 400~
€a 300e&.E~ 200'
100
l----· ·-------·~J--Test Celcius
-&- Calculated Celcius--------~~---~----_.._._._."----~
o 1----t--+--t--t-----.,i----I---+--+--+--+---+---+---+--_+_--I
o 10 20 30 40 50 60 70 80 90 100 110 120 129
Time, minutes
Fig. 4 Average Temperature of Column FS2 for Test and Calculated Data
40
Jurnal Mekanikal, Jilid II, 1996
700 -r------------------------I
600
III
·5 5004iog' 400"CI
€~ 300e8-E 200·Q)I-
100
0+=----+_-+-_+-----1--+---+--1----+--+--+----+---1-----1o 10 20 30 40 50 60 70 80 90 100 110 120
Time, minutes
Fig. 5 Average Temperature of Column FS3 for Test and Calculated Data
700.------------------------------.
600
...-fi 500GiUg' 400"CI
€::::J 300!8-E 200~
100[- _ ._ ._- _.__ .._~
--Test
-<>- Calculated----~._-
888070605040302010
O+----I---+--+_--I---_+~-+_--t__-_+--_+_----l
oTime, minutes
Fig. 6 Average Temperature of Column FS4 for Test and Calculated Data
41
Jurnal Mekanikal, Jilid II, 1996
700 ~.,...------------------------------,
--.._.._-----_._._-----~--~-
--Testl~~aJ~urate<l100
600
OI---+--+-l---+--+---l-+--+--+-l--+---+---+-+--+--+----t-+--+--+-----1
~
III~"u 500
~~ 4do't:I
~ 300eCI)
~ 200~
TIme, mInutesFig. 7 Average Temperature of Column FS5 for Test and Calculated Data
In Figs. 8 to 11, the calculated and measured axial deformations of the
columns during exposure to fire are shown. There is reasonably good agreement in
the trend of deformations between calculated and measured results [1]. There are
some differences, however, between the actual values of the calculated and measured
deformations.35.0 ,.----------------------------,
[--------------- ~- --]--Test (mm)
---<>- Calculated (mm)_._-_..._------_._----------_.-----------
30.0 -
25.0
~20.0
g15.0
iI§ 10.0
.emc 5.0-
iii~ 0.0 b--~:::::=..--t__-------+-------+--------t-- - ---t- -------+-- ... -----+----
10 20 30 40 50 60 70 80-5.0
-10.0
-15.0 _L- -----J
Time, minutesFig. 8 Test and Calculated Values for Axial Deformation of Column FSI
42
Jurnal Mekanikal, Ji/id 1I, J996
30.0 ·r-------------------------,
~---- _ ._---------~
- - Test (mm)
-0-- Calculated (mrn)_...--_. ~.._-- -_.---- .- ._----
0.0 O-"""""¥=- - -- ·-1-- ----\------ -+-- ·-- -/- -----\--- - -1-- -·- + ---- - -\----.+- - - ---t- --.
20 30 40 50 60 70 80 90 100 110
25.0
20.0
EE 15.0Co~ 10.0 .r
ioIi 5.0
~
-5.0
-10.0 .L- ---'
Time, minutes
Fig. 9 Test and Calculated Values for Axial Deformation of Column FS3
8070
[-- ---- -...-----.------.J- - Test (mm)
-0-- Calculated (mrn)-- - --.._- ,-- _ ...- -_.._--_ ..
6---.....'!-f-r:::- - -- --.--t-.- --- -.._- j-..-- --- ---(- - ·-- --- --t ····- - -- 1-··
10 20 30 40 50 60
30.0
25.0 -
20.0
E 15.0 · .EC
10.00
1iII)
\1 5.00Ii
~ 0.0
-5.0
-10.0
-15.0 ·
Time, minutes
Fig. 10 Test and Calculated Values for Axial Deformation of Column FS4
43
Jurnal Mekanikal, Jilid II, J996
30.0 .r-------------------------,
-+ ·!·_--+---I--+·····1--+--+-~t--+--+-+_·-+--t-·_--+·
b? re\:) co\:) ,,\:)\:) "rf> ~\:) "ro\:) "co\:)
[_ _---_ _._-----_._._~
--Test (rnrn)
-c>- Calculated (rnm)-_.,'"-,_..--._--_._. __ ._---~_._-_ .._.._~._ .....-20.0
25.0
-15.0
-10.0 .
E 15.0EC 10.0o=BCI) 5.0
~ 0.0 O-Oc""¥ii
~ -5:t[
-20.0 -'----------------------------'
Fig. 11
Time, minutes
Test and Calculated Values for Axial Deformation of Column FS5
It must be noted that the column deforms axially as a result of several factors
namely, load, thermal expansion, nding and creep. The last ones cannot be
completely taken into account in the calculations [1]. Since the axial deformations,
which are in the order of 20 mm, are for columns with a length of about 3800 mm,
small inaccuracies in these factors may cause noticeable differences between
calculated and measured axial deformations. A difference of 10% between the
theoretical and actual coefficients of thermal expansion of steels for example, will
cause a difference of approximately 5 mm in the axial deformations.
The effect of creep, which is more pronounced at the later stages of .fire
exposure, may be even greater. The model defines the failure point as the point at
which the column can no longer support the applied load and assumes that failure at
this point is instantaneous. During the tests, failure was not instantaneous but the
columns contracted considerably apparently as a result of continued loss of strength
and creep, before they were crushed.
44
Jurnal Mekanikal, Jilid II, 1996
In Figs. 12 to 16, the calculated column strengths, as a function of the fire
exposure time, are shown for the test loads given in Table 1. The results show that
the calculated fire resistance of column FS1, FS2 and FS5 are less than 5% off the
measured fire resistances. The specimens FS3 and FS4 showed a less accurate result
giving the value of 15% "and 20% respectively off the measured fire resistance. Lie
indicated that a 10% off the measure value is considered excellent validation but a
20% off in accuracy is still acceptable.
Coincidentally, the three column that produce the better results were the first
three specimens to be tested for its fire resistance in the furnace. There were
technical difficulties before the last two experiments that required rectification
which probably explained the less accurate results.
3200
3000
2800
2600 - Tim e v StrengthZJIl: -- TI m e v AvgTemp
:z: 2400I-C) 2200zwa:: 2000I-UJ
1800
1600
1400
1200
600
III
500~
'u'iio
400 u.ia::;:)I-
300 ~WD..
200 :IEwI-W
100C)
~W>
0 c(
o 20 40
TIME, min
60 80 100
Fig. 12 Column FSI
45
Jurnal Mekanikal, Jilid II. J996
3500 .,-------------------------"""T""
3000
Z 2500.:It:.
:E:I- ~ Tim e v Strength(!) 2000 -- Ti m e v AvgTempZW0:::I-U'J 1500
800
700 rn;:,'u
600Q)0u.i
500 0:::~I-
400 ~WQ.
300 :::EwI-
200 we
100 ~w>c(
0
o 20 40 60 80 100 120 140 160 180
TIME, min
Fig. 13 ColumnFS2
700
600III;:,"uQ)
500 0ui0:::
400 ~I-
~300 W
Q.
:::Ew
200 I-W(!)
100 ~W>
0 c(
~----;]- - Tim e v Strength-- T im e v AvgTemp
- - - - -
6000
7000 .....--- - - - - - - - - - - - - - - - - - - - - - - - ...
2000
:E:I-(!) 4000Zw0:::I-U'J 3000
Z 5000.:It:.
o 20 40 60 80 100 120 140 160
TIME, min
Fig. 14 Column FS3
46
Jurnal Mekanikal, Jilid II, 1996
600
III500 ~·u
QjU
400 W~
0::;:).I-
300 ~WQ.
.200 :EwI-W
100C)
~W>
0 ct
80 1006040
TIME, min
ColumnFS4
20
Fig. 15
o
3200
3000
2800
2600Z.lll:
::z::2400
I- -- Tim e v StrengthC) 2200 - TI mevAvgTempZW0: 2000I-en
1800
1600
1400
·1200
7000
6000
Z 5000.¥
Z - TI mevStrengthI-C) 4000 - TlmevAvgTempZW0:I-en 3000
2000
1000
0 50
Fig. 16
700
600 III~
U500
QjUu.i0:
400 :;:)I-
~300 w
Q.
:E
200wI-WC)
100 ~w>
0 ct
100 150 200 250
TlME, min
Column FS5
47Pt<.;.iU'USTAKAAN SULTANAH ZAN.AlUA.H
Universiti 'I'eknolozi Malavsis
Jurnal Mekanikal, Jilid II, /996
Other liable factor for the inaccuracy of the results is the considerable
contraction of the columns that the model can only partly take into account. In
addition, the properties of the materials applied in the model may not be the best
value to represent the specimens tested.
A factor that can severely affect the accuracy of the model is the mode of
fixing the column at each end to the furnace compressor and support. The actual
joints of the column during test is fixed end connection that could possibly give rise
to moment stress in the column but in the program, it is assumed to have pin-ended
joints and hence zero moment at both ends.
Another factor that can affect the accuracy of the program is that, the
instantaneous crushing of the column tend to occur about 10 minutes to an hour from
the theoretical failure. However, according to Lie, a definite standard on this type of
failure is not found in any code and the actual instantaneous failure is still arbitrarily
decided by the engineers concerned. Hence this mode of failure cannot be
considered for any program until clearly specified in the code. However if this mode
of failure is to be used as the failure criterion as most of the case in experimental
tests, then all the measured fire-resistance will show a higher value. This means that
the calculated fire resistance will indicate a conservative values which for practical
purposes mean that the calculated fire resistances lie on the safe side.
5.0 CONCLUSIONS
Based on the results of this study, the following conclusions can be drawn:
The mathematical model [1] employed in this study is capable of predicting
the fire resistance of protected steel columns, made of l-shape steel section insulated
with ceramic fibre with an accuracy that is adequate for practical purposes. The
results indicate that the model is conservative in its predictions.
48
Jurnal Mekanikal, Jilid II, 1996
The model will enable the expansion of data on the fire resistance of ceramic
protected steel columns which at present predominantly consists of data for concrete
columns.
By usmg the mathematical model, the fire resistance of protected steel
columns can be evaluated for any value of the significant parameters such as load,
column-section dimensions, and thickness of insulation of ceramic fibre without the
necessity of testing.
The model can also be used for the calculation of the fire resistance of
columns made with I-shaped steel section insulated with material other than those
investigated in this study - for examples cementitious or board that were not tested if
the relevant material properties are known.
6.0 ACKNOWLEDGMENTS
The test was carried out at the National Fire Laboratory of the Institute for Research
in Construction, National Research Council of Canada. The author would like to
thank all the staff of NRCC for their assistance with the experiments. Special
mention should be given to John Latour and Patrice for their commitment m
providing the author with the help while building the specimens and testing them.
49
Jurna/ Mekanikal, Ji/id II. /996
REFERENCES
1. Ghani, B. A. et. al, Heat Transfer and Strength Analysis of Column at Extreme
Temperature, University Technology of Malaysia, 199.6.
2. El-Shayeb, Mohamed, Fire-Resistance of Concrete-Filled and Reinforced
Concrete Columns, PhD. Thesis, University of New Hampshire, USA, May
1986.
3. Lie, T. T. ,Temperature of Protected Steel in Fire, Behaviour of Structural Steel
in Fire, Ministry of Technology and Fire Offices, Committee Joint Fire
Research Organisation Symposium No.2, H. M. S. 0., London, 1968.
4. Lie, T. T. Feasibility of Determining the Equilibrium Moisture Condition in Fire
ResistanceTest Specimens by Measuring their Electrical-resistance, Building
Research Note No. 75, Division of Building Research, NRC, Ottawa, 1971.
5. Dusinberre, G. M. Heat Transfer Calculations by Finite Differences,
International Textbook Company, Scranton, Pennsylvania, 1961.
6. Harmathy, T. Z. A Treatise on Theoretical Fire Endurance Rating, American
Society for Testing Materials, Special Technical Publication No. 301, 1961, pp.
10-40.
7. Harmathy T. Z. and Lie T. T., Experimental Verification of the Rule of
Moisture Moment, Fire Technology, Vol. 7, 1964 p. 17.
8. Bibliography Bardell, Kathleen. Spray-Applied Fire Resistive Coatings for Steel
Building Columns, Fire Resistive Coatings: The Need For Standards, ASTM
STP 826 Morris Lieff and F.M. Stumpf, eds., American Society for Testing and
Materials, 1983,40-55.
50
lurnal Mekanikal, Jilid ll, 1996
9. Standard Methods of Mire Tests of Building Construction and Materials, ASTM
Designation E119-69, 1969 Book of ASTM Standards, Part 14, pp. 436-452.
10. Brit, Iron Steel Res. Assoc., Physical Constants of Some Commercial Steels at
Elevated Temperature, Butterworths Sci. Publ., London, 1953.
11. Fujii, S. The Theoretical Calculation of Temperature-rise of Thermally Protected
Steel Column Exposed to the Fire, Building Research Institute Occasional
Report No. 10, Tokyo, 1963.
12. Emmons H. W., The Numerical Solution of Heat Conduction Problems,
Transactions of the American Society of Mechanical Engineers, Vol. 65, 1943,
pp.607-615.
13. Thrinks W. and Mawhinney M. W., Industrial Furnaces, John Wiley and Sons,
Inc., New York, 1986
14. Law, M., Structural Fire Protection in the Process Industry Building, Vol. 216,
No. 29, 1969, pp. 86-90.
15. Rains W.A., Evaluation on Existing Fire Protection Materials, Phase I Report,
Presented to the American Iron and steel Institute Fire Technology
Subcommittee, 1973.
16. Stumpf Frank M., Spray-Applied Fibrous Materials and Fire Resistive Coatings,
Presented to the ASTM, 1984.
51