Appendix e Space Requiremen

6
7/28/2019 Appendix e Space Requiremen http://slidepdf.com/reader/full/appendix-e-space-requiremen 1/6 Appendix E: Space Requirements 33 PART 33 HVAC EQUATIONS, DATA, AND RULES OF THUMB

Transcript of Appendix e Space Requiremen

Page 1: Appendix e Space Requiremen

7/28/2019 Appendix e Space Requiremen

http://slidepdf.com/reader/full/appendix-e-space-requiremen 1/6

Appendix E: Space

Requirements

33P A R T

33

H V A C E Q U AT I O N S , D A TA , A N D R U L E S O F T H U M B

Page 2: Appendix e Space Requiremen

7/28/2019 Appendix e Space Requiremen

http://slidepdf.com/reader/full/appendix-e-space-requiremen 2/6

720 PART 33

33.01 Space Requirements

Ceiling Plenum Space

Page 3: Appendix e Space Requiremen

7/28/2019 Appendix e Space Requiremen

http://slidepdf.com/reader/full/appendix-e-space-requiremen 3/6

 Appendix E: Space Requirements 721

Ceiling Plenum Space

 Notes for Ceiling Plenum Space Tables:1. Assumptions: 2″  fire proofing on beam, 6″  fluorescent light depth, 51 ⁄ 2″  floor slab thickness, 2″ 

suspended ceiling thickness.2. For depth from beam to ceiling, add 4″  to above figures.

3. For depth from underside of slab to light, add depth of beam plus 2″ .

4. * indicates beam protruding through ceiling.

Page 4: Appendix e Space Requiremen

7/28/2019 Appendix e Space Requiremen

http://slidepdf.com/reader/full/appendix-e-space-requiremen 4/6

722 PART 33

Pipe Spacing on Racks

 Notes for Pipe Spacing on Racks Tables:1. Table based on Schedule 40 pipe and includes the outside dimensions for flanges, fittings, etc.;

insulation over flanges, fittings, etc.; and space between fittings as follows:a. Pipe sizes: 2″  and smaller: 11 ⁄ 2″  Insulation.

Pipe sizes: 21 ⁄ 2″  and larger: 2″  Insulation. b. Space between two pipes 3″  and smaller: 1″ .c. Space between one pipe 3″  and smaller and one pipe 4″  and larger: 11 ⁄ 2″ .

d. Space between two pipes 4″  and larger: 2″ .2. For Schedule 80 and 160 pipe and 300 lb. fittings add the following:

a. Pipe sizes 4″  and smaller: 1″ . b. Pipe sizes 5″  to 12″ : 11 ⁄ 2″ .c. Pipe sizes 14″  and larger: 2″ .

3. Tables do not include space for valve handles and stems, expansion joints, expansion loops, andpipe guides.

Page 5: Appendix e Space Requiremen

7/28/2019 Appendix e Space Requiremen

http://slidepdf.com/reader/full/appendix-e-space-requiremen 5/6

 Appendix E: Space Requirements 723

 Notes for Pipe Spacing on Racks Tables:1. Table based on Schedule 40 pipe and includes the outside dimensions for flanges, fittings, etc.;

insulation over flanges, fittings, etc.; and space between fittings as follows:a. Pipe sizes: 2″  and smaller: 11 ⁄ 2″  Insulation.

Pipe sizes: 21 ⁄ 2″  and larger: 2″  Insulation. b. Space between two pipes 3″  and smaller: 1″ .c. Space between one pipe 3″  and smaller and one pipe 4″  and larger: 11 ⁄ 2″ .

d. Space between two pipes 4″  and larger: 2″ .2. For Schedule 80 and 160 pipe and 300 lb. fittings add the following:

a. Pipe sizes 4″  and smaller: 1″ . b. Pipe sizes 5″  to 12″ : 11 ⁄ 2″ .c. Pipe sizes 14″  and larger: 2″ .

3. Tables do not include space for valve handles and stems, expansion joints, expansion loops, andpipe guides.

Pipe Spacing on Racks

Page 6: Appendix e Space Requiremen

7/28/2019 Appendix e Space Requiremen

http://slidepdf.com/reader/full/appendix-e-space-requiremen 6/6

724 PART 33

Pipe Spacing on Racks

 Notes for Pipe Spacing on Racks Tables:1. Table based on Schedule 40 pipe and includes the outside dimensions for flanges, fittings, etc.;

insulation over flanges, fittings, etc.; and space between fittings as follows:a. Pipe sizes: 2″  and smaller: 11 ⁄ 2″  Insulation.

Pipe sizes: 21 ⁄ 2″  and larger: 2″  Insulation. b. Space between two pipes 3″  and smaller: 1″ .c. Space between one pipe 3″  and smaller and one pipe 4″  and larger: 11 ⁄ 2″ .

d. Space between two pipes 4″  and larger: 2″ .2. For Schedule 80 and 160 pipe and 300 lb. fittings add the following:

a. Pipe sizes 4″  and smaller: 1″ . b. Pipe sizes 5″  to 12″ : 11 ⁄ 2″ .c. Pipe sizes 14″  and larger: 2″ .

3. Tables do not include space for valve handles and stems, expansion joints, expansion loops, andpipe guides.