Air sealing and ventilation improvements for multifamily
buildings
March 2, 2012
Jim FitzgeraldDave Bohac
Center for Energy and Environment
Better Buildings: Better Business Conference
![Page 2: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/2.jpg)
Better air quality through sealing leaks between units and ventilation improvements
What causes problems?
Air leakage & air flow rate measurements• 6 building CEE study
Air sealing and ventilation case studies
Maybe save energy too
![Page 3: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/3.jpg)
What causes problems?
Sometimes people smoke (and cook and ??)
![Page 4: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/4.jpg)
Convert to smoke-free building
Association of Nonsmokers - Minnesota
http://www.mnsmokefreehousing.org/
500+ smoke-free apartment buildings listed in Minnesota
![Page 5: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/5.jpg)
Owners – cooking odors are worst problem
What type of odor or contaminant is the most common source of objectionable air in buildings you manage?
0% 5% 10% 15% 20% 25% 30% 35% 40% 45% 50%
cooking odors
tobacco odors
other
none
don't know
![Page 6: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/6.jpg)
How big are air flows between units?
Pacific Northwest:• Building average – 13 to 26% air from other units
• Individual units – as high as 35%
NJ mid-rise: 4th floor – 22% from other units
West Coast: 4% air from adjoining units
Francisco & Palmiter (1994)
Harrje et al (1988)
Feustal & Diamond (1988)
Multizone tracer gas measurements
![Page 7: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/7.jpg)
How big are air leaks between units?
Minnesota: Modera et al. (1986)• 52% air leaks between units
• 1900’s low-rise masonry
Chicago: Diamond et al. (1986)• Similar results to Minnesota
• 1900’s low-rise
Sweden: Levin (1988)• 12 to 36% air leaks between units
• 3 Swedish apartment buildings
Blower door air leakage tests
![Page 8: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/8.jpg)
What are the driving forces to move air into and though
buildings?
![Page 9: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/9.jpg)
What are the driving forces?
WinterStack Effect
Taller Building => Bigger Effect
In at the bottom and out the top
![Page 10: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/10.jpg)
What are the driving forces?
Wind Effect
In on windward side and out on leeward side
Taller Building => Bigger Effect
![Page 11: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/11.jpg)
Mechanical ventilation is required by code: bathrooms, corridors & some kitchens
Exhaust ventilation => draws air into an apartment
Flow imbalances can also cause air to move from one apartment to another
What are the driving forces?
Mechanical System Effect
![Page 12: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/12.jpg)
Does it help for a smoker in a lower floor unit to open a window?
Not upstairs neighbor
Pressure in smoker’s unit will be about the same as outside, which increases pressure to upstairs and increases flow from smoker’s unit to upstairs
![Page 13: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/13.jpg)
In at the bottom and out the top
Anyway it can!
Gaps in walls, floors, mechanical chases
Some are accessible and others too diffuse or inaccessible for sealing
How does the air travel between units?
![Page 14: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/14.jpg)
Gaps around sink plumbing
Most openings are small and diffuse
![Page 15: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/15.jpg)
Baseboards and sprinkler heads
![Page 16: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/16.jpg)
Chemical smoke moves out of baseboard leakClear acrylic caulk required plus moving bookcases, etc
![Page 17: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/17.jpg)
Gaps along baseboard under carpet
![Page 18: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/18.jpg)
Gaps behind baseboard heaters
![Page 19: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/19.jpg)
Gaps around bath fan
Bathroom exhaust fans
![Page 20: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/20.jpg)
Leaky (2.5 si)
Tight (0.1 si)
Recessed Light Fixtures
![Page 21: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/21.jpg)
Hidden high rise chases = large uncontrolled flows
![Page 22: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/22.jpg)
![Page 23: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/23.jpg)
Can practical air sealing and ventilation treatments reduce
secondhand smoke (SHS) transfer?
6 dissimilar buildings common to local multifamily building types
This research project was funded in part by ClearWay Minnesota, … funded by proceeds from the Minnesota tobacco settlement. These findings are solely the responsibility of the authors and do not necessarily represent the official views of ClearWay Minnesota.
Study Objective
![Page 24: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/24.jpg)
General approach to reduce odor transport between apartments and improve air quality
Ventilate the source• Capture source before transported
Reduce transport between apartments• Seal building leaks
• Reduce driving force - pressure difference
Ventilate receiver’s apartment
![Page 25: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/25.jpg)
General approach to reduce odor transport between apartments and improve air quality
Ventilate
Seal
Ventilate
![Page 26: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/26.jpg)
Duplex 8-Plex
12-Plex
1930s
1970
1964
Minnesota SHS transfer study
![Page 27: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/27.jpg)
New 4 story
138 unit
11 story
1982
2001
1999
Minnesota SHS transfer study
![Page 28: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/28.jpg)
Page 28
Quantify – building tests Before and after fan pressurization tests
• Total “effective leakage area” of apartment
• Fraction of leakage area to outside and to other units
![Page 29: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/29.jpg)
Guarded Zone Multiple Fan Air Leakage Test
Up to 6 tests per unit
Test 1 Test 2
Unit A Unit B Unit C Unit A Unit B Unit C
QB1 QA2 QB2
Common Area Common Area
Q50B total = QB1 Q50
B to A = QB1 - QB2
Test 3 Test 4
Unit A Unit B Unit C Unit A Unit B Unit C
QB3 QC3 QB4
QComm4
Common Area Common Area
Q50B to C = QB1 - QB3 Q50
B exterior = QB4
Fan Fan Fan
Fan Fan Fan
Fan
Test 1 Test 2
Unit A Unit B Unit C Unit A Unit B Unit C
QB1 QA2 QB2
Common Area Common Area
Q50B total = QB1 Q50
B to A = QB1 - QB2
Test 3 Test 4
Unit A Unit B Unit C Unit A Unit B Unit C
QB3 QC3 QB4
QComm4
Common Area Common Area
Q50B to C = QB1 - QB3 Q50
B exterior = QB4
Fan Fan Fan
Fan Fan Fan
Fan
Test 1 Test 2
Unit A Unit B Unit C Unit A Unit B Unit C
QB1 QA2 QB2
Common Area Common Area
Q50B total = QB1 Q50
B to A = QB1 - QB2
Test 3 Test 4
Unit A Unit B Unit C Unit A Unit B Unit C
QB3 QC3 QB4
QComm4
Common Area Common Area
Q50B to C = QB1 - QB3 Q50
B exterior = QB4
Fan Fan Fan
Fan Fan Fan
Fan
Test 1 Test 2
Unit A Unit B Unit C Unit A Unit B Unit C
QB1 QA2 QB2
Common Area Common Area
Q50B total = QB1 Q50
B to A = QB1 - QB2
Test 3 Test 4
Unit A Unit B Unit C Unit A Unit B Unit C
QB3 QC3 QB4
QComm4
Common Area Common Area
Q50B to C = QB1 - QB3 Q50
B exterior = QB4
Fan Fan Fan
Fan Fan Fan
Fan
1: Total Leakage
2: 1 – 2= Leak to Right
3: 1 – 3= Leak to Left
4: 1 – 4= Leak to Out
![Page 30: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/30.jpg)
Page 30
Quantify – building tests Before and after fan pressurization tests
• Total “effective leakage area” of apartment
• Fraction of leakage area to outside and to other units Before and after tracer gas tests
• Week long average tests
• Passive perfluorocarbon tracers
• Nicotine
• Particles Measure exhaust ventilation flow Measure before/after treatments Up to 7 units per building
![Page 31: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/31.jpg)
Tracer gas tests show considerable air movement between apartments
Fraction of Air Coming From Adjoining Units Compared to Total Inflow
Building Min Median Max Min Median Max Min Median Max Min Median MaxDuplex 6% 35% 65% 19% 27% 34% -30% -9% 13%8-Plex 1% 3% 24% 3% 8% 42% -1% 5% 18%12-Plex 1% 12% 26% 9% 12% 17% -9% 1% 8%138 Unit 1% 11% 25% 1% 7% 22% 1% 1% 13% -12% -4% 0%11 Story 2% 5% 12% 1% 2% 9% 0% 1% 4% -11% -3% -1%4 Story 1% 2% 10% 0% 2% 7% -3% -1% 1%All Units 1% 5% 65% 0% 3% 22% 0% 8% 42% -30% -1% 18%
Pre-Treatment (%)
26%16%
26%
One-week tracer gas measurements
![Page 32: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/32.jpg)
Range Median
Top-floor units: 2 to 26% 16%
Mid-floor units: 1 to 20% 5%
Lowest-floor units: 1 to 4% 2%
How does the fraction vary by floor?
Fraction of Air Coming From Adjoining Units Compared to Total Inflow
One-week tracer gas measurements
![Page 33: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/33.jpg)
Total air leakage of individual units
Building Min Median Max Min Median Max Min Median Max < 1.25Duplex 2,101 2,368 2,636 115 130 145 3.16 3.56 3.97 0%8 Plex 837 1,008 1,031 46 55 57 1.93 2.04 2.46 0%12 Plex 731 917 1,318 40 50 72 1.61 2.02 2.90 0%138 Unit 390 665 754 21 37 41 0.86 1.01 2.06 88%11 Story 376 454 958 21 25 53 0.57 0.76 2.14 86%4 Story 921 1,156 1,559 51 63 86 1.05 1.85 2.30 14%
All Buildings 376 861 2,636 21 47 145 0.57 1.66 3.97 22%
NELA (si/100 sf)Ref. Flow Rate(cfm50) ELA (si)Building Min Median Max Min Median Max Min Median Max < 1.25Duplex 2,101 2,368 2,636 115 130 145 3.16 3.56 3.97 0%8 Plex 837 1,008 1,031 46 55 57 1.93 2.04 2.46 0%12 Plex 731 917 1,318 40 50 72 1.61 2.02 2.90 0%138 Unit 390 665 754 21 37 41 0.86 1.01 2.06 88%11 Story 376 454 958 21 25 53 0.57 0.76 2.14 86%4 Story 921 1,156 1,559 51 63 86 1.05 1.85 2.30 14%
All Buildings 376 861 2,636 21 47 145 0.57 1.66 3.97 22%
Ref. Flow Rate(cfm50)
LEED Green Building Rating system for MF SHS control requires ELA divided by wall & floor & ceiling area to be less than 1.25 si/100 sf
ELA – equivalent leakage area, reference 4Pa & coef. = 1
(1999)
(1982)
(2001)
Blower door air leakage tests
![Page 34: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/34.jpg)
Fraction of air leakage to adjacent units
TotalBuilding ELA (si) ELA (si) (%)Duplex 130 26 20%
8 Plex1
55 28 59%
12 Plex1
50 28 57%138 Unit 37 5 16%11 Story 25 8 26%4 Story 64
All Buildings 47 9 27%1 - leakage to adjacent units includes leakage to common area
To Adjacent Units
Blower door air leakage tests
![Page 35: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/35.jpg)
Leakage Area of Individual Units
712
341.8
612
281.1
514 512 510
28 1.3 24 0.5 332.5 1.1 4.4
414 412 410
34 2.4 22 0.1 531.0 2.3 4.2
314 312 310
21 3.0 25 1.3 331.2
212
23
Elevator
11 Story Building
![Page 36: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/36.jpg)
Air Sealing and VentilationTreatment Results
![Page 37: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/37.jpg)
General approach to reduce odor transport between apartments and improve air quality
Ventilate
Seal
Ventilate
![Page 38: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/38.jpg)
Air sealing treatments
Focus on leaks between units (not exterior)
Seal as much is practical – 3 to 8 hours/unit. Average cost of about $700/unit
Blower door test to monitor total leakage
Use visual/smoke puffer diagnostics sometimes aided by blower door. Tried IR in limited cases
![Page 39: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/39.jpg)
Total and shared leakage
CFM50/unit
Existing After TreatmentsTotal Shared Total Shared
Duplex 2409 466 1881 601
8-plex 1032 475 916 307
12-plex 918 507 769 247
138 unit 641 90 639 88
New 4 story 1150 25 900 20
11 story 556 120 417 108
Blower door air leakage tests
![Page 40: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/40.jpg)
Modest overall reductions in leakage between apartment units – but some were significant
Range Median
Duplex: small change
8-plex: 21 to 44% 35%
12-plex: 14 to 70% 55%
New 138-unit: 0 to 23% small change
New 4-story: 0 to 20%
11-story: 0 to 56% 23%
Blower door air leakage tests
![Page 41: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/41.jpg)
Mechanical ventilation observations
Often provided only by occupant-operated (highly intermittent-typically off) bath fans
Many bath fans are better noise-generators than air movers, even when new
Apartment bath fans are not maintained (corrosion, dirt)
Apartment exhaust flows are rarely balanced
![Page 42: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/42.jpg)
Continuous ventilation in code
“Old” Codes • Kitchens: 0 cfm OR 100+ cfm• Baths: 50 cfm
2012 International Mech. Code• Kitchens: 25 cfm• Bathrooms: 20 cfm
ASHRAE 62.1 -2010• 5 cfm per person + 0.06cfm/sq ft• Kitchens: 50 cfm• Kitchenettes: 0.30 cfm/sq ft• Toilets: 25cfm
![Page 43: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/43.jpg)
Corridor supply choices
Minimum 0.05 cfm/sq ft corridor area (IBC)
Minimum 0.06 cfm/sq ft corridor area ASHRAE 62.1-2010
Supply all ventilation to corridor & exhaust from units
Original design flow (typically higher)
Confirm with local code official
![Page 44: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/44.jpg)
Ventilation treatments – for study
Install effective (and quiet) exhaust fans with capacity of at least 30 to 45cfm
Convert intermittent exhaust to continuous exhaust
Balance exhaust air flows to reduce ventilation driving force between units
![Page 45: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/45.jpg)
Ventilation treatmentsQuiet, Continuous Ventilation
Constant Air Regulator
Quiet Ceiling ExhaustMulti-point
![Page 46: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/46.jpg)
Ventilation rate increased substantially
60% Increase*only one unit with added fan
Existing After Treatments
Duplex: 28 (12 to 43) 43 (35 to 50)
8-plex: 38 (19 to 58) 50 (26 to 79)
12-plex: 38 (23 to 75) 73 (57 to 157)
New 138-unit: 26 (15 to 47) 41 (31 to 53)
11-story: 28 (18 to 79) 69 (45 to 124)
4-story*: 45 (26 to 61) 48 (22 to 88)
Average 34 54
Median Ventilation Rate (cfm)
min to max
One-week tracer gas measurements
![Page 47: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/47.jpg)
Cleaner air, same transfer rate
Original ventilation system may be a direct path for smoke transfer (11 story, 138 unit, 4 story ducts)
More smoke is captured near source
Dilution reduces concentration in nonsmoker’s or receiver’s unit
![Page 48: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/48.jpg)
Effect of Treatments: Air Transfer
Fraction of Incoming Air From Adjoining Units
Existing After Treatments
Top-floor: 16% (2 to 26%) 13% (0 to 42%)
Mid-floor: 5% (1 to 20%) 2% (0 to 12%)
Lowest-floor: 2% (1 to 4%) 7% (1 to 19%)
One-week tracer gas measurements
![Page 49: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/49.jpg)
Effect of treatments
65% of the units had decreased air transfer
60% increase in ventilation rate
80% of tenants: SHS drift was less frequent and less severe
![Page 50: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/50.jpg)
Case Studies
![Page 51: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/51.jpg)
8-Plex: balance ventilation & air seal
Rooftop fan serves 4 units
![Page 52: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/52.jpg)
47 28 32 53
26 17 9 32
Uneven exhaust flow rates cause pressure difference & air flow between units
Before
Apartment exhaust flow rates
Powered roof ventilator
8 plex
![Page 53: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/53.jpg)
25 26 28 26
23 26 27 24
47 28 32 53
26 17 9 32
Uneven exhaust flow rates cause pressure difference & air flow between units
Before
After
66
3 2
Added
Powered roof ventilator
Apartment exhaust flow rates
Balanced exhaust flow rates reduces driving forces
![Page 54: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/54.jpg)
Page 54
Open between tubs
Neighbor’s bathtub
Why do our clothes smell like smoke?
![Page 55: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/55.jpg)
Easy air flow is possible through framing around pipes, etc
![Page 56: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/56.jpg)
Page 56
Is better good enough?
Unit #3 contaminants in unit #7 decreased by factor of five
Fraction of air from unit #3 to #7 reduced from 11% to 6%
Unit #3 ventilation rate increased 158%
Marked reduction of SHS odors per tenants
Will owners pay for it? Who can do the work?
![Page 57: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/57.jpg)
Page 57
Ongoing Success: 67 Buildings in Condo Complex of Tested 8-plex
Condo Maintenance team trained to respond to smoke complaints in additional buildings.
Smoker is back-charged for repair costs
20 additional units have been completed to date
15 more units are scheduled
Huge improvement in livability
Common areas air quality improved
![Page 58: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/58.jpg)
Page 58
Details of Ongoing work
Typical complaint has smoker on lower level with fan off and large bypasses venting smoke into chases.
Non-smoker on upper level often had higher exhaust fan flows which increased airflow from chase into unit. Stack effect enhances this flow in winter.
Seal major bypasses, 1-4 person hours Ventilation modifications
• Nonsmoker: replace fan damper with CAR• Smoker: remove fan damper and omit CAR for higher capture.• Typical flows are 25cfm in nonsmoker and 75cfm in smoker’s
unit.
Existing Conditions
Practical & Effective Work
![Page 59: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/59.jpg)
Page 59
High rise case study: seal hidden shafts & rooftop exhaust ventilation
![Page 60: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/60.jpg)
Hidden chase openings often difficult to access
![Page 61: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/61.jpg)
Add mineral wool fire-safing to high rise shaft openings
![Page 62: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/62.jpg)
Seal with listed fire barrier
![Page 63: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/63.jpg)
Page 63
PRV fan on roof – top of vent chase
Vent chase Operable register
![Page 64: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/64.jpg)
Page 64
FL
OO
R
0 1 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17
11 3 3 3 3 3 3 0 3 3 3 3 -1 3 3 0 3 3
10 3 3 3 3 3 3 3 3 3 3 3 -1 2 3 0 3 3
9 3 3 3 2 2 3 3 3 3 3 3 -1 2 3 0 0 2
8 2 3 3 0 2 3 2 3 3 3 -1 0 0 3 2 2 2
7 2 3 2 1 2 3 2 1 3 2 2 0 2 3 2 0 2
6 2 2 2 2 2 1 2 2 2 0 2 0 0 2 -1 0 2
5 2 2 2 3 -1 2 -1 2 2 0 0 2 2 2 -1 2 0
4 0 2 2 0 3 2 1 2 2 1 2 1 0 0 0 -1 0
3 1 -1 2 -1 2 2 2 1 2 1 0 2 1 0 0 0 0
2 2 0 2 -1 2 2 0 2 -1 2 0 0 2 2 0 2 0
1 2 2 2 2 2 2 0 0 2
Unit Number
Register flow “tissue” test
- good - weak - ? - blow back
Shaft number
Floor
![Page 65: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/65.jpg)
Page 65
Floor Press Flow Notes
11 -74 28
10 -45 27
9 -15 14
8 -10.8 14
7 -9.5 10
6 na
5 +1.2 + stinks
4 +0.1 + smoker
3 +0.3 + stinks
2 -2.8 4
1 -5.3 8
Flow box measurement
![Page 66: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/66.jpg)
Page 66
Obstructions: undersized floor cutout full-sized subduct
Concrete floor Bathroom vent sub duct
The 144 sq. in. shaft area only has 32 sq. in. for air flow.
c
Vent chase: 12” X 12” = 144 Sq. in.
8 x 8 cutout
![Page 67: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/67.jpg)
Page 67
Obstructions: undersized floor cutout full-sized subduct
Vent chase: 12” X 12” = 144 Sq. in.
Concrete floor Bathroom sub duct – replaced
with 3” for more flow.
The 144 in2 shaft only has 32 in2 for air flow
8 x 8 cutout
![Page 68: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/68.jpg)
Page 68
Drywall joints open
![Page 69: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/69.jpg)
Page 69
Total: 506 cfm
From units: 93 cfm
Leaks: 413 cfm No flow from lower 5 floors
Fan & register flow measurements
![Page 70: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/70.jpg)
Page 70
Ventilation system problems
Restrictions cause most air to be drawn from upper apartments
Duct leaks• Air drawn from unknown sources• Lower units no or reverse flow
Operable registers – occupant “balancing”• No flow when closed• Too high when open
![Page 71: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/71.jpg)
Page 71
Ventilation system solutionsReduce duct restrictions: 3” sub ducts to
upper 3 floors
Seal ductwork with Aeroseal technology
Install constant air regulators or designed orifice plates at registers
Test and adjust fan flow to required duct pressure
Thanks to Don Stevens for advising us of subduct code issue
Target: equal flow from all units
![Page 72: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/72.jpg)
Page 72
Remove restriction and provide 3” subducts for top 3 floors
Code: fire damper or sheet metal sub duct extending
22” above fan inlet
![Page 73: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/73.jpg)
Page 73
Aeroseal required for fan draw to reach lower units Before After
Total: 506 279 cfm
From units: 93 221 cfm
Leaks: 413 58 cfm
Targets leaks
![Page 74: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/74.jpg)
Page 74
Option used for test:3” opening sized to exact flow rate
Remove dampers, balance register flowFirst option : “self-adjusting” constant air regulator “CAR”
Production option: fixed orifices – more to come
![Page 75: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/75.jpg)
Page 75
FloorBefore After
Press Flow Press Flow
11 -74 28 -75 21
10 -45 27 -65 20
9 -15 14 -63 20
8 -10.8 14 -56 20
7 -9.5 10 -52 20
6 na -49 20
5 +1.2 + -42 20
4 +0.1 + -42 20
3 +0.3 + -42 20
2 -2.8 4 -42 20
1 -5.3 8 -44 20
TreatmentsSubductsAerosealOrifice platesFan adjustment
Even flow after upgrades
OutcomesRequired ventilation for allSave 227cfm ($250 - $500/year)Reduce unit/unit flow – smoke drift
17 fans ~ $4k - $8k
![Page 76: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/76.jpg)
Page 76
Keep control fans on
Aethelometer Measurement of ETS Particle Concentration in Nonsmoker's Apartment
-2
0
2
4
6
8
10
12
11/28 11/29 11/30 12/1 12/2 12/3 12/4 12/5 12/6
ET
S P
arti
cle
Con
cen
trat
ion
(mg/
m3 )
Instrument precision
ETS odors logged by resident
Kitchen shaft central exhaust fan turned off at midnight
SHS odor threshold
Secondhand smoke monitored in 11th floor unit
SHS logged by resident
![Page 77: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/77.jpg)
From research to production:
current options
Spray seal ducts with mastic & seal fan curbs
Orifice restrictors
Efficient fan
Clean or remove blockages
![Page 78: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/78.jpg)
Current options
Spray sealing with mastic
![Page 79: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/79.jpg)
Fan not connected - curb open
Current options: curb leakage
Total flow: 174 cfmFrom units: 30 cfm
Airflow from building shafts not exhaust grilles
![Page 80: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/80.jpg)
Current options: stop curb leakage
SealedTotal flow: 126 cfmFrom units: 120 cfm
![Page 81: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/81.jpg)
Current options
CARs failures: How soon? How often?After 9 years – 1 in 3 plugged
Dust buildup in 9 months
Adjustment holes
![Page 82: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/82.jpg)
Current options
Fixed orifices Not prone to foul
Can be cleaned
Durable
Sized for flow at target pressure
Mass - produced, low cost
Allow lower operating pressure (reduced duct leakage,
& fan power)
2
11/2
11/4
1
![Page 83: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/83.jpg)
Current options
Fixed orifices – flow rate guidelineInside Diameter
(in) Pressure, in wc (Pa)
Nominal Actual0.15(36)
0.2(50)
0.25(62)
0.36(90)
0.5(124)
0.75(186)
2 2.45 36 40 44 54
1.5 1.97 21 24 28 34 39 48
1.25 1.73 18 21 26 29 36
1 1.37 16 18 22
# stories* 3 to 7 5 to 10 6 to 12 9 to 18 12 to 25 to 25
*- building size for Minneapolis climate (20F average outside temp)
![Page 84: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/84.jpg)
Current options: efficient fan
384471 505
622710
25 42 50 86126
940
11431234
1508
1720
0
200
400
600
800
1000
1200
1400
1600
1800
2000
0 20 40 60 80 100 120
CFM
and
Watt
s
Static Pressure PA
CFM
Watts
RPM
Linear (CFM)
Linear (Watts)
EC style fan upgrade: lab test results
C 9" diam testStatic
Press (Pa)Flow (cfm)
Power (watts)
63.6 in2 inlet area 29 384 25(13 inlets 2.45 in) 44 471 42(21 inlets 1.97 in) 50 505 50(27 inlets 1.73 in) 78 622 86(43 inlets 1.37 in) 100 710 126
Orifice Area= 64 sq inFixed Orifice Area= 64 sq inVary fan speed
400w to 50w saves 3000kwh/yr each
![Page 85: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/85.jpg)
Exhaust grille on 12 story looks OK
Current options: blockages
![Page 86: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/86.jpg)
Current options: blockages
Exhaust fan runs but DP low/high
Fan intake 20.9Pa too low for flow needed
Fan outlet 221Pa to exterior grille (side with resistance)
Check pressures
![Page 87: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/87.jpg)
Current options: blockages
Access plugs from recent duct cleaning
Exhaust outlet plugged from inside
Hard to see
![Page 88: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/88.jpg)
Dirt obstructs flow: clean & adjust fan down
Current options: blockages
As found: 609 cfm After: 2,338cfm
Design flow: 1,780 cfm
![Page 89: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/89.jpg)
Fan stops damper from opening
Current options: blockages
![Page 90: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/90.jpg)
300 inspected – 1 in 4 plugged
Current options: supply blockages
![Page 91: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/91.jpg)
Exterior screen is clear. Hidden screen is forgotten
Current options: supply blockages
Pressure across grille 0.9 in wc (221Pa)
Inspection: 18 of 46 Corridor supply intakes obstructed
![Page 92: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/92.jpg)
Nobody can keep this clean:
remove hidden screens
Current options: supply blockages
![Page 93: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/93.jpg)
138 unit: little unit to unit leakage
![Page 94: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/94.jpg)
Meets LEED leakage guidelineOccupants still complain of smoke transfer
324 323 322 321
601 9 17 574 3 622+/-1 +/-13 +/-3
1 44
224 +/-7 223 222 +/-4 221
21 688 71 33 661 65 654+/-7 +/-4
28 -4 2 64
124 +/-14 Guest +/-12 123 +/-15 122 +/-12 121
609 35 390 37 606 51 664 93 683+/-8 +/-2 +/-8
Guarded-Zone Measured Air Leakage Rates
734
680
-13+/-11
Oaks: Pre-Treatmentunit #
total leakage
unit/unit leakage
leakage precision
(cfm50)
Smoker
Non- smoker
![Page 95: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/95.jpg)
Vent blocked: view inside smoker’s fan duct in attic
![Page 96: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/96.jpg)
Vent blocked: roof damper frozen shut on same fan
![Page 97: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/97.jpg)
CARs in fan duct in attic, smokers open for higher flow
![Page 98: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/98.jpg)
Post treatment fan flows
Unit Flow(cfm) Unit Flow
(cfm) Unit Flow(cfm)
323 24 322 25
224 21 223 20 222 22
Guest 26 123 28 122 20Smoker
![Page 99: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/99.jpg)
4 Story: duct leakage in ceiling joist space
![Page 100: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/100.jpg)
All leakage into joist space
![Page 101: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/101.jpg)
Aeroseal ducts in joist space
![Page 102: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/102.jpg)
Leaks into joist space: lights & sprinklers
![Page 103: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/103.jpg)
New continuous duty fan in kitchen: source of odor complaint
![Page 104: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/104.jpg)
Continuous at 40cfm. Installer sets high speed: 75, 160, or 390 cfm
Less than 20 watts at low speed
Continuous ventilation with kitchen hood
in 1 unit
![Page 105: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/105.jpg)
Duct seal side-benefit
Backdraft potential reduced by Aeroseal
-4.5 pa before -1.5pa after
80%-ID furnace both into B vent natural draft water heater
Door closed dryer+ AC fan on
in 1 unit
![Page 106: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/106.jpg)
Recommendations
Ventilate - source
Seal - between
Ventilate - receiver
![Page 107: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/107.jpg)
Recommendations: ventilation
Moderate/continuous/quiet – better than intermittent
Central exhaust: orifice, seal ducts, replace or adjust fan
Check for blockages and leaks
![Page 108: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/108.jpg)
Recommendations: air sealing
Seal between units
Large, accessible leaks (unoccupied or new is better)
Includes ducts and mechanical/plumbing chases
Improvement possible – can not eliminate transfer
![Page 109: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/109.jpg)
In at the bottom and out the top
Additional slides
![Page 110: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/110.jpg)
Additional Information
Canada Mortgage and Housing Corporation
Fact Sheet: Solving Odour Transfer Problems in Your Apartment
http://www.cmhc.ca/en/co/reho/reho_002.cfm
![Page 111: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/111.jpg)
Fan not connected - curb open
Current options: curb leakage
Total flow: 174 cfmFrom units: 30 cfm
Airflow from building shafts not unit exhaust grilles
![Page 112: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/112.jpg)
Current options: stop curb leakage
SealedTotal flow: 126 cfmFrom units: 120 cfm
![Page 113: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/113.jpg)
2-part Foam Seals Plumbing ChaseStop Vertical Air Transfer In Plumbing Wall
Patched, primed
Inject Foam Along Top of Wall
12-plex
Shared leakage reduced about 50% from 507 to 247 cfm50
![Page 114: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/114.jpg)
Kitchen option for cooking sourceIn different project after work
Cooking moisture was an issue in 15% of units
Continuous kitchen fan option needed
VenMar developed (UL) a quiet continuous range hood
![Page 115: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/115.jpg)
Page 115
Tobacco Smoke Research: Tobacco Smoke Research: Preliminary RecommendationsPreliminary RecommendationsSeal what is possible around pipes,
baseboards, etc. – start in smokers unit
Provide continuous ventilation
Balance ventilation between units –possibly higher exhaust in smokers unit
Consider more extensive air sealing when apartments turn over or during remodeling
Note – Improvements are possible. Managing expectations is important.
![Page 116: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/116.jpg)
Page 116
What does this cost, who pays, who can do it?
•Licensed mechanical contractor required for all duct alterations.•Aeroseal franchisee required for duct sealing. (Maint. prep ok)•Performance contractor/ consultant for design, balancing, QC
•$300 per unit or $3,200 for 1 shaft minimum, $5,000 for 2 shafts
•Changes to the building are an Association responsibility.
•Airsealing in unit is responsibility of individual condo owner
![Page 117: Air Sealing and Ventilation Improvements for Multifamily Buildings - Fitzgerald and Bohac](https://reader038.fdocuments.in/reader038/viewer/2022110121/558a1711d8b42ac1028b471a/html5/thumbnails/117.jpg)
Page 117
Individual supply and very low leakage required for best control
If an occupant opens a window to let smoke out air can come in and blow smoke into adjacent units. At 30F we measured a lower unit change pressure from from -0.7pa to hall to +24pa to hall by opening 1 window. Some flow still came in from under the kitchen kickboard @+2pa to hall. The occupant complained about intermittent smoke. Total air leakage down to 283cfm50 after work.
Some individuals may not tolerate any smoke transfer, a large improvement may not be enough.