Air-Cooled Chillers
Embed Size (px)
Transcript of Air-Cooled Chillers

Copyright © Carrier Corp. 2005
COMMERCIAL HVACCHILLER EQUIPMENT
Air-Cooled Chillers
PRESENTED BY:
Omar Rojas
SalesEngineer
Technical Development Program

Copyright © Carrier Corp. 2005
Section 1 IntroductionSection 2 Basic Refrigeration CycleSection 3 Air-Cooled Chiller ComponentsSection 4 Chiller ControlsSection 5 Air-Cooled Chiller ConfigurationsSection 6 Application TopicsSection 7 Options and AccessoriesSection 8 Codes and Standards
Section 9 Summary
Menu

Copyright © Carrier Corp. 2005

Copyright © Carrier Corp. 2005
SECTION 1
Introduction
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
Objectives
• List the various types and tonnages ofair-cooled chillers and theiroperational characteristics
• Describe the correct applications forair-cooled chillers
• Identify the available options and accessories
Section 1 – Introduction

Copyright © Carrier Corp. 2005
Air-Cooled Chiller Package
Packaged Unit
=
Section 1 – Introduction
Air-CooledCondenser
Evaporator(cooler) Barrel
Compressor(s)
ExpansionDevice

Copyright © Carrier Corp. 2005
Design Air Inlet Temperature 95° F
Air Rise 15° F
Leaving Difference* 15° F
Refrigerant Condensing Temperature 125° F
* Difference betweencondensing temperatureand leaving air
125° FCondensingTemperature
Air-Cooled Condensing Temperature
Section 1 – Introduction

Copyright © Carrier Corp. 2005
Air-Cooled Chiller Advantages– Lower installed cost– Quicker availability– No cooling tower or condenser
pumps required– Less maintenance– No mechanical room required
Water-Cooled Chiller Advantages– Higher efficiency– Custom selections in larger sizes– Large tonnage capabilities– Indoor chiller location– Longer life
Air-Cooled vs. Water-Cooled Chillers
Section 1 – Introduction

Copyright © Carrier Corp. 2005
Cooling Tower
CondenserWater Pump
Water-Cooled Chiller System Requirements
Condenser Water Pipingand Chemical Treatment
Water-Cooled ChillerWater-Cooled Chiller
Section 1 – Introduction

Copyright © Carrier Corp. 2005
Condenser Water Pipingand Chemical Treatment
Cooling Tower
CondenserWater Pump
Air-Cooled Chiller System Requirements
Water-Cooled ChillerWater-Cooled Chiller
Air-CooledChiller
Air-CooledChiller
Section 1 – Introduction

Copyright © Carrier Corp. 2005
SECTION 2
Basic Refrigeration Cycle
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
Air-Cooled Refrigeration Cycle
*Flooded cooler, which has water in the tubes, is also used
Section 2 – Basic Refrigeration Cycle
WaterOutlet
WaterInlet
Water in Shell
Air-CooledCondenser
Compressor(s)• Scroll• Reciprocating• Screw
Evaporator
Thermal or ElectronicExpansion Device
Filter Drier
Condensed (liquid)Refrigerant
Heat Rejection to Atmosphere
Suction Line
Hot GasDischargeLine
Water-in-Shell

Copyright © Carrier Corp. 2005
SECTION 3
Air-Cooled Chiller Components
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
Air-Cooled Chiller Components• Cooler / Evaporator
– Refrigerant to water– Removes heat from chilled water loop
• Condenser– Refrigerant to air– Rejects heat to atmosphere
• Compressor– Transfers heat to condenser– Reciprocating, scroll, screw and centrifugal types
• Expansion Device– Maintains high-to-low side pressure differential– Provides proper superheat of the gas
to the compressor
Section 3 – Air-Cooled Chiller Components

Copyright © Carrier Corp. 2005
Three Types of Evaporators
DX Shell-and-Tube
FloodedShell-and-Tube
Brazed-Plate
Section 3 – Air-Cooled Chiller Components

Copyright © Carrier Corp. 2005
Brazed-Plate Evaporator
Return water in 54° FRefrigerant out
Chilled water out 44° FRefrigerant inNote: Brazed-Plate Heat Exchangers
are also used as condensers
Section 3 – Air-Cooled Chiller Components

Copyright © Carrier Corp. 2005
Direct Expansion Shell-and-Tube Evaporator
Water is in the shell
Internal bafflingdistributes waterover the tubes
Refrigerantflows throughthe tubes
Water ConnectionFlange
Section 3 – Air-Cooled Chiller Components

Copyright © Carrier Corp. 2005
Flooded Shell-and-Tube Evaporator
Section 3 – Air-Cooled Chiller Components
Refrigerant floodsthe tubes
Suction tocompressor inlet
Refrigerantvapor
Water in tubes
Refrigerant inthe shell
44° F
54° FChilled water out
Return water in

Copyright © Carrier Corp. 2005
Flooded Shell-and-Tube Pass Arrangements
One-Pass AREA = A
Two-Pass AREA = A/2
Three-Pass AREA = A/3
Low Pressure Drop,Low Rise
Medium Pressure Drop,Medium Rise
High Pressure Drop,High Rise
Section 3 – Air-Cooled Chiller Components

Copyright © Carrier Corp. 2005
Condenser
Air-Cooled Chiller
Vertical DischargePropeller Fans
Aerodynamically designedcondenser fan deck
Section 3 – Air-Cooled Chiller Components

Copyright © Carrier Corp. 2005
Four types of compressors used in air-cooled chillers:– Reciprocating (obsolete)– Scroll– Screw– Centrifugal
Compressor Types
Section 3 – Air-Cooled Chiller Components

Copyright © Carrier Corp. 2005
Horizontally Mounted TXV
SuperheatSensing Bulb
Section 3 – Air-Cooled Chiller Components
Mixed Phase toEvaporator
Liquid Line

Copyright © Carrier Corp. 2005
EXV Expansion Device
Mixed Phase toMixed Phase toEvaporator
Stepper MotorStepper Motor
Liquid LinesLiquid Lines
Section 3 – Air-Cooled Chiller Components

Copyright © Carrier Corp. 2005
SECTION 4
Chiller Controls
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
Chiller Controls and StartersStarter Types
• Across-the-Line (full voltage)• Part-Winding (soft start)• Wye-Delta (soft start)• VFD (soft start)
Capacity Control
Energy Management• Chilled-Water Reset• Demand Limit
Section 4 – Chiller Controls

Copyright © Carrier Corp. 2005
Control Panel
A060ALARM - @ 09:34 10-FEB-99COOLER LEAVING FLUIDTHERMISTR FAILURE7
Hand-held
Section 4 – Chiller Controls
Equipment-mounted

Copyright © Carrier Corp. 2005
Starter Summary Information
StartingMethod
Motor StartingCurrent as a % of
Locked RotorCurrent
Full LoadCurrent
Across-the-Line 100 600
Part Wind 65 390
Wye-Delta 33 200
Section 4 – Chiller Controls

Copyright © Carrier Corp. 2005
Capacity Control-Cycling CompressorsMultiple Scroll Chiller Design
Section 4 – Chiller Controls

Copyright © Carrier Corp. 2005
Capacity Control Hot Gas BypassAir-CooledCondenser
Evaporator (cooler) Barrel
Compressor
Hot GasSolenoid Valve
DischargeBypassValve
• Protects system inlow-load conditions
• Active at minimumstep of cooling only
Section 4 – Chiller Controls

Copyright © Carrier Corp. 2005
Capacity Control Slide-Valve and VFD’s

Copyright © Carrier Corp. 2005
SECTION 5
Air-Cooled Chiller Configurations
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
Packaged Single Piece ConfigurationGround or Roof-Mounted Chiller
Evaporator
Electricaland Controls
Air Inlet toCondenser Coil
CondenserFans
Multiple ScrollCompressors
Section 5 – Air-Cooled Chiller Configurations

Copyright © Carrier Corp. 2005
Remote Cooler BarrelConsult manufacturer’srecommendations for maximumseparation distance.
Outdoor packagedair-cooled chillerwith cooler removed
Field-installedrefrigerant piping
Liquid Line
Suction Line
Section 5 – Air-Cooled Chiller Configurations
WaterOutlet
WaterInlet
DX Evaporator
Outdoors
Indoors

Copyright © Carrier Corp. 2005
Outdoor Air-Cooled Condensers(1) Per Compressor Circuit
Condenserless Split-System Chiller
Outdoors
IndoorsHot Gas
Hot Gas Liquid
Liquid
IndoorCondenserless Chiller
Section 5 – Air-Cooled Chiller Configurations

Copyright © Carrier Corp. 2005
Condenserless Chiller
• Roof does not need to support the compressor(s)
• Lower electrical costs because the compressor iscloser to the indoor electrical panel
• More options for noise control
• Reduced freeze-up potential
Benefits of Condenserless Chiller Configurations
Section 5 – Air-Cooled Chiller Configurations

Copyright © Carrier Corp. 2005
Indoor Chiller & Indoor Air-Cooled Condenser
Section 5 – Air-Cooled Chiller Configurations
Hot Gas
Liquid
Indoor CondenserlessChiller
Indoor Centrifugal FanAir-Cooled Condenser
Ducted inlet
Ducted Outlet

Copyright © Carrier Corp. 2005
Indoor Chiller - Evaporative Condenser
Liquid
Hot Gas
Cold WaterBasin
Air In
Warm Air Out
Coil
Air In
Air Inlet Louvers
Spray PumpWet Deck Surface
Indoor Condenserless Chiller
Section 5 – Air-Cooled Chiller Configurations

Copyright © Carrier Corp. 2005
Work Session – Part 1
Work Session
AIR-COOLED CHILLERS
Work Session
1. What are the four major components to the air-cooled chiller refrigeration cycle?____________________________________________________________________________________________________________________________________________________________________
2. List the three types of compressors used in air-cooled chillers.___________________________________________________________________________________________________________________________
3. List the three types of coolers or evaporators used in air-cooled chillers.


Copyright © Carrier Corp. 2005

Copyright © Carrier Corp. 2005
SECTION 6
Application Topics
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
Application Topics• Typical operating limits• Effects of ambient air temperature• Effects of leaving chilled-water temperature• Variable flow minimum and maximum flow rates• Freeze protection methods• Refrigerants used in air-cooled chillers• Chiller sizing• Minimum chilled-water system volume• Parallel and series chillers• Clearances and installation
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Typical Operating Limits
• Minimum Outdoor Temperature-20° F(Standard unit 0° to 32° F)
• Maximum Outdoor Temperature125° F
• Minimum Leaving FluidTemperature 15° F(Standard unit 40° F)
• Maximum Leaving FluidTemperature 60° to 70° F
• Maximum Return WaterTemperature 85° F
Check with manufacturer for unit specifics
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Effects of Ambient Air Temperature
EnteringAir °F Tons kW/Ton % Change
Capacity% ChangeEfficiency
75° F 112.1 0.952 +15 +20
85° F 105.5 1.069 +8 +11
95° F 97.5 1.208 – –
105° F 89.5 1.384 -8 -15
115° F 81.2 1.621 -17 -35
125° F 73.1 1.923 -25 -60
Typical Air-Cooled Chiller Full Load
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Leaving Chilled WaterTemperature °F
kW /Ton
% ChangeEfficiency
per °F
% ChangeEfficiencyFrom 44° F
44 1.237 – –43 1.253 -1.1 -1.142 1.266 -1.0 -2.241 1.280 -1.1 -3.540 1.295 -1.2 -4.6
Typical Air-Cooled Chiller at 95° F Ambient
Effects of Leaving Chilled Water Temperature
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Variable Flow Minimum and Maximum Flow Rates
For variable flow, the maximum rate of changeper minute is 10% of the design flow rate.
• Flooded Cooler– Minimum flow is the gpm that corresponds to
3.0 fps water velocity in the tubes– Maximum flow results in an approximate 5° F DT in cooler– Maximum flow is approximately 5 gpm/ton
• DX Cooler– Minimum flow is the gpm that corresponds to
1.0 fps water velocity in the shell– Maximum flow results in an approximate 5° F DT in cooler– Maximum flow is approximately 5 gpm/ton
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Freeze Protection Methods
• Drain the chiller loop
• Use cooler heater
• Circulate the water continuously
• Use antifreeze solution
• Combinations of the above
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Freeze Damage
Burst Coil
Cracked Housing
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Evaporator Barrel Heater
• Refrigerant in tubes
• Water (glycol) in shell
• Heater cable wrapped aroundthe shell
• Factory or field-installed
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Freeze vs. Burst ProtectionPropylene Glycol
ProtectionTemperature (°F)
For FREEZEprotection
** % by weight
For BURSTprotection
** % by weight
+20 18 12
+10 29 20
0 35 25
-10 41 29
-20 45 30
-30 48 32
-40 52 34
**Confirm with the local glycol supplier
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
New refrigerants not scheduled for phase-out:
Refrigerants
R-22 phase-out:• 2010 new equipment• 2020 service
R – 410A Puron™R – 407C
R - 134a
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Chiller Sizing
• Do not oversize beyond 15%
• If future expansion, add a second chiller in parallel
• Use two small chillers versus one large chillerwhenever possible
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
Minimum Chilled-Water System Volume
• 3 gallons per ton of chiller fornormal air-conditioning duty
• 6 to 10 gallons per ton of chillerfor process duty or low ambientunit operation
• Mount tank on return line to chiller
Volume tank may be necessary
Suggested volumetank designs
Section 6 – Application Topics

Copyright © Carrier Corp. 2005
44° F64° F 54° F
Series – (Typically greater than 18° F drop)
54° F
44° F
44° F
44° F
Parallel – (Typically 18° F drop or less)
Section 6 – Application Topics
Parallel and Series Chillers

Copyright © Carrier Corp. 2005
Clearances
Section 6 – Application Topics
Unobstructed height isrequired for air dischargeabove fan deck
Approximately6 ft air inlet space
Approximately 6 ftminimum spacerequired for air inlet
Consult manufacturer’sliterature for exact
requirements
Require access toelectrical paneldoor swing

Copyright © Carrier Corp. 2005
Multiple Unit Separation
10 ft Minimum
Consult manufacturer’s literature for exact requirements
Section 6 – Application Topics
6 ft Minimum

Copyright © Carrier Corp. 2005
SECTION 7
Options and Accessories
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
Options and Accessories
• Low ambient operation
• Low chilled-water temperature
• Condenser coil corrosion protection
• Hydronics package
Section 7 – Options and Accessories

Copyright © Carrier Corp. 2005
Low Ambient OperationControl Section of Multi-Fan Air-Cooled Chiller
Fan Speed Controllers
required for operationFan speed control
required for operationto -20° F ambient
Section 7 – Options and Accessories

Copyright © Carrier Corp. 2005
Low Chilled Water Temperature
Brine Duty• From 40° F to 34° F leaving brine
requires field reset of chiller controls
• From 34° F to 15° F leaving brinerequires factory modification to chiller
Section 7 – Options and Accessories

Copyright © Carrier Corp. 2005
Chiller Coil Corrosion Protection
Standard Coil(majority of applications)
Plate fin coil options:• Pre-Coated Aluminum Fins
(moderate coastal protection)
• All Copper Coils(best coastal protection)
• Electro-Coated Aluminum Fins(best coastal and industrial protection)
Section 7 – Options and Accessories

Copyright © Carrier Corp. 2005
Copper-Fin CoilsCopper tube/copper fin coils are used for
corrosion resistance in coastal areas.
Section 7 – Options and Accessories

Copyright © Carrier Corp. 2005
Hydronics Packages
Brazed-PlateEvaporator
Strainer
Water Inlet
Water Outlet
Balancing Valve
Flow Switch
ExpansionTank
Water Pump
Air Vent
PressureGauges
Section 7 – Options and Accessories
Base Supportwith Heater
(Volume tank not shown)

Copyright © Carrier Corp. 2005
Pump in Hydronics Package
Section 7 – Options and Accessories
Pump assemblyfactory-supplied foran air-cooled chiller

Copyright © Carrier Corp. 2005
Expansion Tank in Hydronics Package
The change inwater systemvolume is about1% for chilled-water systems
Section 7 – Options and Accessories

Copyright © Carrier Corp. 2005
SECTION 8
Codes and Standards
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
Codes and Standards
Section 8 – Codes and Standards

Copyright © Carrier Corp. 2005
Codes and Standards• ARI
Air Conditioning and Refrigeration Institute– Chiller performance certification– Random testing of manufactured units for verification– ARI 550/590-98
• Latest standard for electric chillers
• ASHRAEAmerican Society of Heating, Refrigerating
and Air-Conditioning Engineers– ASHRAE 90.1
• Chiller minimum efficiency requirements– ASHRAE 15
• Safety of installations using refrigerants
• ASMEAmerican Society of Mechanical Engineers
– Pressure vessel specifications
Section 8 – Codes and Standards

Copyright © Carrier Corp. 2005
ARI Terms• Definitions
– EER: Measurement of a chiller’s efficiencyat full load capacity
– IPLV: Calculation of a chiller’s efficiency inaddition to full load using weightedaverages at various part load points
• ARI Conditions for Air-Cooled Chillers– Leaving chilled-water = 44° F– Chilled-water flow rate = 2.4 gpm/ton– Cooler fouling factor = 0.0001 hr °F ft²/Btu– Entering air temperature = 95° F
Section 8 – Codes and Standards

Copyright © Carrier Corp. 2005
ASHRAE Standard 15Locate reliefLocate reliefoutlets for
safe venting
Run floor drainsRun floor drainsper local code
Locate inlet ventsLocate inlet ventsaway from exhaust
outlets per code
Restrict mechanicalRestrict mechanicalroom access
SizeSizepressure
relief linesper
ASHRAE
Install tight fittingInstall tight fittingmechanical room
door
Secure chillerSecure chillerdrain valves
Minimize lowMinimize lowareas where
refrigerant mightcollect
Section 8 – Codes and Standards

Copyright © Carrier Corp. 2005
EquipmentType
SizeCategory
MinimumEfficiency
kW/Ton
Air-cooledwith
condenser
< 150 tons> 150 tons
9.562 EER /12.5 IPLV9.562 EER /12.75 IPLV
Air-cooledwithout
condenserAll
Must be ratedwith matchingcondensers andcomply withsame efficiencyrequirements.
Current Title 24 Minimum EfficienciesAir-Cooled Chillers
Section 8 – Codes and Standards

Copyright © Carrier Corp. 2005
Current Title 24
New central cooling plants and coolingplant expansions will be limited on the useof air-cooled chillers. For both the limit is300 tons per plant.

Copyright © Carrier Corp. 2005
Current Title 24Exceptions:1. Where the water quality at the building site
fails to meet manufacturer’s specifications forthe use of water-cooled chillers.
2. Chillers that are used to charge thermalenergy storage (TES) system with a designtemperature of less than 40°F.
3. Air cooled chillers with minimum efficienciesapproved by the Energy Commission pursuantto §10-109(d).

Copyright © Carrier Corp. 2005
SECTION 9
Selection Criteria
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
SECTION 9
Summary
AIR-COOLED CHILLERS

Copyright © Carrier Corp. 2005
Summary
• Listed the various types and tonnagesof air-cooled chillers and theiroperational characteristics
• Described the correct applications forair-cooled chillers
• Identified the availableoptions and accessories
Section 10 – Summary

Copyright © Carrier Corp. 2005

Copyright © Carrier Corp. 2005
Work Session – Part 2
Work Session
AIR-COOLED CHILLERS
Work Session
1. What are the four major components to the air-cooled chiller refrigeration cycle?____________________________________________________________________________________________________________________________________________________________________
2. List the three types of compressors used in air-cooled chillers.___________________________________________________________________________________________________________________________
3. List the three types of coolers or evaporators used in air-cooled chillers.

Copyright © Carrier Corp. 2005
Technical Development Program
Thank YouThis completes the presentation.
TDP-622 Air-Cooled ChillersArtwork from Symbol Library used by permission ofSoftware Toolboxwww.softwaretoolbox.com/symbols