Air-cooled & Water-cooled Scroll Chillers
-
7/25/2019 Air and Water Cooled Scroll Chillers
2/10
AIR-COOLED AND WATER-COOLED SCROLL CHILLERS
Voltas is the pioneer and a leading provider of integrated end-to-end solutions in the field of electro-mechanical and
refrigeration. We are committed to provide customers with technology that suits their needs. We have introduced a wide
variety of air-cooled and water-cooled scroll chillers with R22 and R407C refrigerant options.
With ISO:9001 cer tified factories, Voltas possesses total capability in the manufacture of scroll chill er s.
These chillers are available in a wide range of capacities from 12 TR to 111 TR. They are easy to in st al l
and commission, and can handle various cooling requirements, aided by multiple compressor con figurations.
Voltas scroll chillers are an ideal choice for various air-conditioning applications, including office spaces, banks,
hotels, hospitals, shopping malls, multiplexes, commercial complexes and process cooling.
MODEL NOMENCLATURE:
AC WC D S D M N 2044
AIR-COOLED
WATER-COOLED
DX CHILLER
SCROLL
COMPRESSOR
NOM. CAPACITY
048 = 48 TR
NO. OF COMPRESSORS PER CIRCUIT(FOR TANDEM MODEL)
NO. OF REF. CIRCUITS(FOR TANDEM MODEL)
N - STANDARD PANELA - ADVANCED BMS
MICROPROCESSOR-BASEDCONTROL PANEL
C - COPELAND COMPRESSOR
D - DANFOSS COMPRESSOR - R22
DP - DANFOSS COMPRESSOR - R407C
X 2
KEY FEATURES INCLUDE:
1) Scroll Compressor with R22 and R407C Refrigerant Options
2) Energy Efficiency
3) Modular Design
4) Application Flexibility
5) Low Noise and Compact Design
6) Easy-to-use Microprocessor Panel and Controls
-
7/25/2019 Air and Water Cooled Scroll Chillers
3/10
ACDS
077DPMN2X2
ACDS
096DPMN2X2
77 96
4 4
100/75/50/25 100/75/50/25
DX DX
1 1
205 256
5" nps 5" nps
2 3
4 6
2625 3710
2236 2236
2590 2615
2562 2872
ACDS
011DPMN1X1
UNIT MODEL
*Nominal Capacity - TR
ACDS
022DPMN2X1
ACDS
034DPMN3X1
ACDS
045DPMN2X2
CACDS
066DPMN3X2
11 22 34 45 66
Compressor Qty.
Unit Capacity ReductionSteps in %
1 2 3 4 6
100/50 100/50 100/66.7/33.3 100/75/50/25100/83.3/66.7/50/33.3/
16.7
Evaporator Type
Evaporator Qty.
Evap. Water Flow RateGPM (US)
Evap. Water NozzleSize**
DX DX DX DX DX
1 1 1 1 1
29 59 90 120 176
2-1/2" nps 3" nps 3" nps 4" nps 5" nps
Condenser Module Qty. 1 1 1 2 2
2 2 2 4 4
LENGTH (MM)
WIDTH (MM)
HEIGHT (MM)
Shipping Wt. Kg.
2500 2535 2535 2850 2625
650 1270 1270 2235 2236
1400 2310 2410 2590 2690
631 1033 1349 1961 2633
Note 1:* Capacity rated for evap. inlet water temp. 12 C leaving water temp. 7 C and at design ambient of 35 C Evap.
water side fouling factor of 0.000018 m2 C/W. Power and control supply voltage ranges are 360 -440 V and 210-240 V
respectively, and frequency 50Hz.
Note 2:** Siz ing of water piping to be done at site, based on operating tonnage and available pump head.
Note 3:For higher ambient applications, please contact us.
AIR-COOLED SCROLL CHILLERS R407C
TECHNICAL DATA
COMPRESSOR
EVAPORATOR
CONDENSER
No. of Fans
CHILLER PACKAGE PHYSICAL DATA
-
7/25/2019 Air and Water Cooled Scroll Chillers
4/10
OBEROI HOTEL, DELHIIISC, BANGALOREBHUSHAN STEEL LTD., KOLKATA
MICROPROCESSOR-BASED LCD CONTROLLER:
Three Modes of Operation:
Auto Mode: Auto start-and-stop, programmable for the entire year. Hence there is no need for any operator interface.
Auto Mode facilitates auto restart on power restoration after load shedding or grid supply failure.
Semi-auto Mode: Manual, single button start-and-stop, since further sequence is pr og rammed .
Manual (Test) Mode: Facilitates testing under supervision.
Equalization of Compressor Runtime
The Microprocessor Controller ensures equal running of compressors in multiple compressor units.
This ensures longer life of compressors.
All chillers are equipped with microprocessor controls that provide the following benefits:
-
7/25/2019 Air and Water Cooled Scroll Chillers
5/10
Controls and Interlocks
The chilled water pump is interlocked with compressors.
The safety controls are preset at factory while operating controls are field adjustable, depending on actual operating
requirements.
Optional Features
Communication port RS485 for remote connectivity, status and fault indication.
Advanced BMS with ASCII or RTU MODBUS protocol can be linked to Integrated Building
Management System (IBMS).
Limited hardware BMS for remote control operation.
Dual-mode chillers for thermal storage system.
Safety and Protection
Microcomputer Motor Protection Device (uMPD) and Microcomputer Voltage Protection Device (uVPD) protect chillers from phase
unbalance, phase loss, treversal, overload,under / over voltage and supply failure.
Programmed safety features available using sensitive and accurate temperature which protects the
system from:
Freezing Low Pressure Anti-recycle Low Chilled Water Temperature High Pressure
Inlet and Outlet Temperature for Chiller Sensor Error Low Water Flow in Condenser, Chiller
User-friendly Operation
Interface with keypad and 32 character LCD display.
Gives visual annunciation for safety trips.
Self-diagnosis Function
Digital display of all vital parameters such as:
Outlet temperature for Chillers Current Voltage Compressor run hours
Diagnose mode for easy trouble shooting shows alarm history for the last 5 trips with date, time and cause of failure.
EMAMI, KOLKATAHONDA R&D, DELHITATA POWER, MUMBAI
-
7/25/2019 Air and Water Cooled Scroll Chillers
6/10
R22
R407C
R407C
R410A
R410A
R22
EIGHT POWERFUL FEATURES:
Voltas chil lers are available in a wide range of models, with R407C and R22 re fr ig er an ts .
Higher Energy Efficiency - Tandem Compressor ModelsScroll chillers from 48 TR to 111 TR use compres sors operating in tandem. This improves the oper at in g
efficiency during part load period s, since the ent ire condenser area is utilized for hea t r ejec tion , e ven
though only one compressor may be in operation.
Capacity ModulationMultiple compressors are used in most of the models, with independent refrigerant circuits . The micropro cess or
contro l le r ensures that only the required number of compressors operate during part load conditions, thereby
saving power.
Operating ReliabilityThe compressor is a no-contact scroll design with the motor, cooled by the suction gas. Higher capaci ty sc ro ll
ch il le rs use tandem compressors with suction gas distribution restrictor, which allows balanced op er ati on of
compressor. The chillers are charged and tested in the factory prior to dispatch, thus enhancing operating
reliability.
Energy EfficiencyA range of sophisticated components such as highly energy-efficient, imported compressor, superior design of
wa te r- co ol ed condenser and chiller, internally grooved, cross-hatched copper tube coil with matched circuitry,
and a microprocessor controller, results in low power consumption.
Quiet Operation
The chillers use ultra-quiet, high efficiency scroll compressors. The condenser fans are designed for low noise levels.
Easy to Install
The chillers are pre-wired, fully charged and run-tested at the factory, saving installation and start-up time.
Voltas Countrywide After-Sales Service
A nationwide service network backs every unit. After the initial warranty period, Voltas offers annual se rv ic eschemes. More than 90% of the customers have opted for these schemes. You cannot get better insurance.
SCROLL CHILLERS
AIR-COOLED CHILLERS
WATER-COOLED CHILLERS
13 TR 26 TR 39 TR 52 TR 78 TR 111 TR
13 TR 26 TR 39 TR 52 TR 77 TR
Will be available shortly
11 TR 22 TR 34 TR 45 TR 66 TR 77 TR 96 TR
12 TR 24 TR 36 TR 48 TR 72 TR 83 TR 100 TR
Will be available shortly
-
7/25/2019 Air and Water Cooled Scroll Chillers
7/10
AIR-COOLED SCROLL CHILLERS R22
ACDS012DMN
UNIT MODEL
*Nominal Capacity - TR 12 24 36 48 72 83 100
COMPRESSOR
EVAPORATOR
CONDENSER
Compressor Qty.
Unit Capacity ReductionSteps in %
1 2 3 4 6 4 4
100/50 100/50 100/66.7/33.3 100/75/50/25100/83.3/66.7/50/33.3/
16.7100/75/50/25 100/75/50/25
Evaporator Type
Evaporator Qty.
Evap. Water Flow RateGPM (US)
Evap. Water NozzleSize**
DX DX DX DX DX DX DX
1 1 1 1 1 1 1
32 64 96 128 192 221 266
2-1/2" nps 3" nps 3" nps 4" nps 5" nps 5" nps 6" nps
Condenser Module Qty.
No. of Fans
1 1 1 2 2 2 3
2 2 2 4 4 4 6
UNIT DIMENSION & WEIGHTS
LENGTH (MM)
WIDTH (MM)
HEIGHT (MM)
Shipping Wt. Kg.
2500 2535 2535 2850 2625 2625 3900
650 1270 1270 2235 2236 2236 2236
1400 2310 2310 2690 2690 2690 2590
631 1034 1300 1961 2634 2515 2868
ACDS024DMN
ACDS036DMN
ACDS048DMN2X2
CACDS072DMN3X2
ACDS083DMN2X2
ACDS100DMN2X2
Note 1:* Capacity rated for evap. inlet water temp. 12 C leaving water temp. 7 C and at design ambient of 35 C Evap.
water side fouling factor of 0.000018 m2 C/W. Power and control supply voltage ranges a re 360-440 V and 210-240 V
respectively, and frequency 50Hz.
Note 2:** S izing o f water piping to be done at site, based on operating tonnage and available pump head.
Note 3:For higher ambient applications, please contact us.
-
7/25/2019 Air and Water Cooled Scroll Chillers
8/10
UNIT MODEL
*Nominal Capacity - TR
WATER-COOLED SCROLL CHILLERS R22
COMPRESSOR
Compressor Qty.
Unit Capacity ReductionSteps in %
Evaporator Type
Evaporator Qty / Unit
Evap. Water Flow RateGPM (US)
Evap. Water NozzleSize**
Condenser Qty / Unit
Condenser Water FlowRate GPM (US)
UNIT DIMENSION & WEIGHTS
WCDS013DMN
WCDS026DMN
WCDS039DMN
WCDS052DMN2X2
WCDS078DMN3X2
WCDS111DMN2X2
13 26 39 52 78 111
Cond. Water Nozzle
Size**
LENGTH (MM)
WIDTH (MM)
HEIGHT (MM)
Shipping Wt. Kg.
1 1/4" nps 1 1/4" nps 1 1/4" nps 2-1/2" nps
2000 2000 2500 2500 2500 3000
1300 1400
2100 19001700
950950
15351450
850850
1050
540 824 2345 267015451150
1 2 3 4
100 100/50 100/66.7/33.3 100/75/50/25
DX DX DX
1 1 1
35 69 104
2-1/2" nps 3" nps 3" nps
1 2 3 2
43 85 128 171
EVAPORATOR
DX DX
1 1
207 295
5" nps 6" nps
100/83.3/66.7/50/
33.3/16.7
100/83.3/66.7/50/
33.3/16.8
CONDENSER
DX
6 4
1
138
4" nps
2-1/2" nps 6" nps
3 1
256 365
Note 1:* Capacity rated for evap. inlet water temp. 12 C, leaving water temp. 7 C,Evap. water side fouling factor
of 0.000018 m2 C/W and condenser water side fouling factor of 0.000044 m2 C/W. Power and control supply vol tag e ra ng es ar e
360-440 V and 210-240 V respectively and frequency 50Hz.
Note 2:** Sizing o f water piping to be done at site, based on operating tonnage and availab le pump head.
-
7/25/2019 Air and Water Cooled Scroll Chillers
9/10
Note 1:* Capacity rated for evap. inlet water t emp . 12 C, leaving water temp. 7 C,Evap. water side fouling factor
of 0.000018 m2 C/W and condenser water side fouling factor of 0.000044 m2 C/W. Power and control supply volt ag e ra ng es ar e
360-440 V and 210-240 V respectively, and frequency 50Hz.
Note 2:** Siz ing of water piping to be done at site, based on operating tonnage and available pump head.
*Nominal Capacity - TR
Compressor Qty.
Unit Capacity ReductionSteps in %
Evaporator Type
Evaporator Qty.
Evap. Water Flow RateGPM (US)
Evap. Water NozzleSize**
Condenser Qty / Unit
Condenser Water FlowRate GPM (US)
ACWCDS013DPMN1X1
ACWCDS039DPMN3X1
ACWCDS052DPMN2X2
ACWCDS077DPMN3X2
13 26 39 52 77
Cond. Water Nozzle
Size**
LENGTH (MM)
WIDTH (MM)
HEIGHT (MM)
Shipping Wt. Kg.
1 1/4" nps 1 1/4" nps 1 1/4" nps 2" nps 2" nps
2350 2400 2500 2500 2500
1350
21501800
10001100
13001450
850850
1050
552 846 240415881196
1 2 3 4 6
100 100/50 100/66.7/33.3 100/75/50/25100/83.3/66.7/50/
33.3/16.7
DX DX DX DX DX
1 1 1 1 1
35 69 104 138 205
2-1/2" nps 3" nps 3" nps 4" nps 5" nps
1 2 3 2 3
43 86 128 171 253
UNIT MODELACWCDS
026DPMN2X1
COMPRESSOR
EVAPORATOR
CONDENSER
CHILLER PACKAGE PHYSICAL DATA
WATER-COOLED SCROLL CHILLERS R407C
-
7/25/2019 Air and Water Cooled Scroll Chillers
10/10
NORTH ZONE:DELHI(011) 66505550 / 66505657 / 66505680 / 66505683 / 66505684 CHANDIGARH(0172) 6610124 / 6610135
JAIPUR(0141) 6451756 / 6541011 LUCKNOW(0522) 237869 / 6546629 EAST ZONE: KOLKATA(033) 66266280
66266264 / 662 66 26 8 BHUBANESHWAR(0674) 6574044 JAMSHEDPUR(0657) 2427642 PATNA (0612) 2500786
WEST ZONE:MUMBAI(022) 66656754 / 66656756 / 66656757 / 66656760 GOA 09860976942 NAGPUR(0712) 64 64 69 2
PUNE(020) 66046607 / 6604 6447 AURANGABAD(020) 66046607 AHMEDABAD (079) 66301107 / 663 01 10 2
INDORE (0731) 2498616 SOUTH ZONE: HYDERABAD (040)66743007 / 66743033 VIJAYAWADA (0866) 2431507
VOLTAS LIMITED
EM&R Business Group Sales Headquarters
Voltas House 'B', 3rd Floor, T.B. Kadam Marg, Chinchpokli, Mumbai - 400 033
Tel: +91 22 66656666 / 66656552 Fax: +91 22 66656930
Email: [email protected] | www.voltas.com
ENERGY EFFICIENT
WATER-COOLED SCREW CHILLER
AIR-COOLED RECIPROCATING
CHILLER
WATER-COOLED RECIPROCATING
CHILLER
PRODUCT RANGE
VARIABLE REFRIGERANT FLOW (VRF)
SYSTEM
COGENERATION VAM
IAQ & ENERGY REDUCTION
SYSTEM
COILOTRON (UV FOR AHU COILS)
AIR-HANDLING UNIT
ENERGY EFFICIENT
AIR-COOLED SCREW CHILLER
DOUBLE EFFECT VAM
GERMITRON (DUCT MOUNTED UV)
KITCHEN EA DEODOURISATION SYSTEMSTP EA ODOUR / H2S REMOVAL SYSTEM
PACKAGED & DUCTABLE SPLIT UNIT