Adressable Intelligent Fire Alarm Panel Manual

download Adressable Intelligent Fire Alarm Panel Manual

of 31

Transcript of Adressable Intelligent Fire Alarm Panel Manual

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    1/31

    1

    ADDRESSABLEINTELLIGENTFIRE ALARM SYSTEM

    USER

    MANUAL

    NAVEEN ALARM SYSTEMS INDIA PVT LTD

    Office:1/10 Abilasha apartments, Gopalakrishna Street

    T.NagarChennai - 17. INDIA

    PH: +91 44 23457110 / 28157868

    email: [email protected]:www.naveenalarm.com

    Works:No.9 Lakshmi Vinayagar Koil Street

    Ambal nagar, EkadduthangalChennai - 97. INDIA

    Ph: +91 44 32557282/23457111

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    2/31

    2

    TABLE OF CONTENTS

    INTRODUCTION: .......................................................................................................................................................................3

    1.0 SYSTEM OVERVIEW: ............................................................................................................................................................4

    1.1 Description: .............................................................................................................................................................5

    1.2 Features: .................................................................................................................................................................5

    1.3 Technical Specifications: ........................................................................................................................................6

    2.0 FRONT PANEL CONTROLS AND INDICATION: ......................................................................................................................6

    2.1 Control Keys: ...........................................................................................................................................................7

    2.2 Front Panel LED Indication: ......................................................................................................................................7

    3.0 INSTALLATION: ....................................................................................................................................................................8

    4.0 BASIC SYSTEM MODULE: .....................................................................................................................................................8

    4.1 Power: .....................................................................................................................................................................9

    4.1.1 DC Input: ...........................................................................................................................................9

    4.1.2 Battery Connections:.........................................................................................................................9

    4.1.3 Loop Connections: .........................................................................................................................104.1.4 Conventional Sounder Connections: ..............................................................................................10

    4.1.5 Auxiliary Power Output Connections:...............................................................................................10

    4.1.6 Relay Connections:.........................................................................................................................10

    5.0 CONFIGURING THE PANEL:...............................................................................................................................................10

    6.0 PROGRAMMING/OPERATING: ..........................................................................................................................................19

    6.1 Level 1 Access Mode:...........................................................................................................................................19

    6.2 Level 2 Access Mode:...........................................................................................................................................20

    6.2.1 Set time & date:..............................................................................................................................21

    6.2.2 Enter zone area:..............................................................................................................................22

    6.2.3 Enter device point: ..........................................................................................................................22

    6.2.4 Zone config report: .........................................................................................................................22

    6.2.5 Erase data log report: .....................................................................................................................23

    6.2.6 Change password: .........................................................................................................................23

    6.2.7 Zone isolation: .................................................................................................................................24

    6.2.8 Assign devices:................................................................................................................................24

    6.2.9 Add / remove device manually: .....................................................................................................25

    6.3 Level 3 access mode (engineering mode): .........................................................................................................25

    6.3.1 Set serial no: ....................................................................................................................................26

    6.3.2 Set default value: ............................................................................................................................26

    6.3.3 Write bus data: ................................................................................................................................26

    7.0 TROUBLE SHOOTING:........................................................................................................................................................28

    8.0 MAINTENANCE:................................................................................................................................................................29

    9.0 WARNING AND CAUTION: ................................................................................................................................................29

    10.0 BLOCK DIAGRAM AND CIRCUIT CONNECTIONS OF ADDRESSABLE PANEL:......................................................................31

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    3/31

    3

    INTRODUCTION:

    Airlight addressable intelligent Fire Alarm System is a state-of-the-art system providing early warning

    of a fire so that people can be evacuated an d action can be taken to stop the fire at the earliest.

    The system can be integrated with AHU, AC supply, Access control, Fire Fighting system, BMS and so on.

    Intelligent Addressable Automatic Fire Detection and Alarm system consists of the following:

    1. Addressable Single Loop Fire Alarm panel2. Addressable photoelectric smoke detector3. Addressable heat detector4. Addressable Multisensor5. Addressable Manual Call Point6. Addressable Sounder beacon7. Control Module8. Isolator Module

    Fire Alarm Panel works on 230 Volt AC with backup supply of 24 Volt DC battery. Power supply is fed to other

    devices from the Fire Alarm panel through a two core cablewhich is also used for sending Fire signal from

    Detector to Panel and also from Panel to Sounder employing power-line communication technique. The

    Panel also sends fire alert signal to PC. Monitor screen pops up all the indications a s shown in the fire alarm

    panel along with mimic layout, fire affected zone, etc.

    Photoelectric smoke detectorsenses smoke and sends advance signals to the Fire Alarm Panel giving its

    ID.

    Heat detectoris a device that responds to changes in ambient temperature and sends advance signals to

    the Fire Alarm Panel giving its ID.

    Mul t i senso r i s a c omb in at io n o f s mok e & hea t det ect or th at senses heat / smoke and

    sends advance signals to the Fire Alarm Panel giving its ID.

    Manua l Ca l l Po in t provides additional facility to send fire signal to Fire Alarm panel by manually

    activating the signal from the fire affected zone.

    Sounder Beacon activates audio visual alarm on receipt of fire warning signal from Fire Alarm panel. This

    alerts everyone to arrange evacuation and fire fighting.

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    4/31

    4

    Cont ro l Modu le provides potential free contact for activating user designed external alarms.

    I so la to r modu le provides short circuit protection and isolates the devices beyond the short circuit point

    and allows normal communication up to the point where the short circuit occurred.

    1.0 SYSTEM OVERVIEW:The fire alarm panel, housed in a powder coated metal cabinet, consists of SMPS, Keypad and CPU card.

    The front panel is protected by a lid with a cam lock and also it houses a 2x40 LCD display, Navigation

    keys, Alpha numeric keypad, and Zonal Fire LED indicators.

    The panel provides power to other devices connected through two core cable. Fire alert signals are

    exchanged through the same cable.

    Fire alarm panel, through a two core cable, receives fire alarms from detectors and manual call points.

    On receipt of signal from Detectors/MCP along with ID, the panel sends out alarm signal to

    corresponding Sounder beacon for raising audio visual alarm to alert the people for evacuation. The

    Panel also sends out fire alert signal to PC. Monitor screen pops up all the indications as shown in the

    Fire Alarm Panel along with mimic layout, fire affected zone, etc.

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    5/31

    5

    1.1 Description:

    The analog addressable fire alarm control panel is designed for industrial, commercial and residential fire

    alarm applications. The control panel has facility to connect wireless devices where access is difficult or

    laying cable is impossible. The control panel supports to monitor and control sprinkler, hydrant, access

    control, guard tour, emergency security, shift bell, emergency light, public light, room temperature,

    equipment temperature, medical emergency, etc. Installer / user intelligence is the limit. It is suitable for thefollowing services:

    Automatic Fire Detector alarm Manual Fire alarm Automatic Smoke alarm Releasing Device service

    1.2 Features:

    1000 event history log Conventional device integration Wireless device integration Built-in battery charger Two level password protection Easy to read 80 character backlit display 16 zonal alarm LED Contamination level alert for maintenance Device missing PC MIMIC graphic software for alarm management & reporting Extensive networking capability Expandable loop cards Field programmable on front panel or PC High precision protocol Digital communication with high speed polling Detector sensitivity adjustments (from panel) Alarm verification feature Up to 127 devices per loop No shielded or twisted pair cable required. Standard 2x1.5sg. Mm cable can be used. ETDC approved Designed & manufactured to ISO9000 standards

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    6/31

    6

    1.3 Technical Specifications:

    Primary power supply 220V +/- 10% AC, 50Hz Standby power supply 24V DC (2nos of 12V, 7Ah SMF Battery) Battery charging voltage 27.5 +/- 1V Battery charging current 500 mA (max.) Programmable relay contact 3 sets Relay contact rating 2 Amps 30V DC Operating temperature 0 deg C to +50 deg C Wiring 2 Core Compatibility AL1X Protocol System

    2.0 FRONT PANEL CONTROLS AND INDICATION:The Front Panel contains controls for operating and programming the panel:

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    7/31

    7

    2.1 Control Keys:

    2.2 Front Panel LED Indication:

    Indicator Color Function

    SYSTEM ON GREENThe system is running OK with all the

    power supplies functioning.

    ZONE FIRE

    LEDs (1-16)

    REDThese LEDs illuminate to provide fire

    alarmcondition at corresponding Zone.

    LOW BATT YELLOWThis led illuminates when the battery

    voltage is low.

    MAINS FAIL YELLOWThis led illuminates when the AC power

    fails.

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    8/31

    8

    3.0 INSTALLATION:Check that you have all the components you require to install the system. Follow the field wiring

    diagrams and installation notes in this manual. Installation of the fire alarm panel should be carried out

    by qualified personnel only. Never insert or remove boards or components in the fire panel when the

    power is on.

    Mounting the panel

    The site chosen for the location of the panel should be clean, dry and not subjected to shock or

    vibration. The recommended temperature should be in the range 0C to +60C. The humidity should not

    exceed 95%.Open the door using the key provided. Screws or bolts of a minimum of 5mm diameter

    must be used to mount the enclosure in all four mounting positions.

    Do not over-tighten screw terminals. Over-tightening the cables may damage the thread, resulting in

    reducing the terminal contact pressure and difficulty with screw terminal removal. To prevent the spread

    of fire, use proper patching materials to areas where system wiring passes through fire-rated walls or

    floors.

    Before making modifications, verify that they will not interfere with battery, transformer and printed circuit

    board location.

    4.0 BASIC SYSTEM MODULE:

    FIELD WIRING CONNECTIONS

    Designation Description

    TB1-1 (+ 24) VDC Output terminal

    TB1-2 (-24) VDC Output terminal

    TB2-1 Relay Output(Common)

    TB2-2 Relay Output(Normally Closed)

    TB2-3 Relay Output(Normally Opened)

    TB2-4 Relay output(External Hooter (+) terminal)

    TB2-5 Relay output(External Hooter (-) terminal)

    TB3-1 Addressable Bus(+)

    TB3-2 Addressable Bus(-)

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    9/31

    9

    TB4-1 (+)28 VDC Input terminal

    TB4-2 (-)28 VDC Input terminal

    CON1-1 RS232 Output Transmit Terminal(To PC)

    CON1-2 RS232 Input Receive Terminal(From PC)

    CON1-3 Ground

    CON2-1 Power Transistor Terminal1(2N3055 Base )CON2-2 Power Transistor Terminal1(2N3055 Collector)

    CON2-3 Power Transistor Terminal1(2N3055 Emitter)

    CON3-1 Power Transistor Terminal2(2N3055 Base )

    CON3-2 Power Transistor Terminal2(2N3055 Collector)

    CON3-3 Power Transistor Terminal2(2N3055 Emitter )

    CON4-1 (+)5 VDC Output Terminal

    CON4-2 Ground

    CON5-1 NA

    CON5-2 NA

    CON5-3 NA

    CON5-4 NA

    CON5-5 NA

    CON5-6 NA

    CON5_7 NA

    CON5-8 NA

    CON6-1 Buzzer Output Terminal(+)

    CON6-2 Buzzer Output Terminal(-)CON 7 To Keypad

    CON 8 To LCD display

    CON9-1 (+)24 VDC Battery Terminal (+)

    CON9-2 Ground

    4.1 Power:

    4.1.1 DC Input:

    TB 4-1 is positive. (28 VDC)

    TB 4-2 is negative. (28 VDC)

    4.1.2 Battery Connections:

    CON 9-1 is positive

    CON 9-2 is negative

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    10/31

    10

    4.1.3 Loop Connections:

    Loop cable must always be segregated from the mains cable and brought into the enclosure.

    Before connecting the loop, check the circuit continuity of each conductor. If loop isolators are

    installed, it will not be possible to check the circuit continuity of the two loops unless the isolators

    are temporarily shorted out. The earth screen connections should also be continuous.

    TB3-1 is Positive

    TB3-2 is Negative

    4.1.4 Conventional Sounder Connections:

    CON 6-1 is Positive.

    CON 6-2 is Negative. See the above table.

    4.1.5 Auxiliary Power Output Connections:

    TB 1-1 is positive

    TB 1-2 is negative

    CON 4-1 is Positive.

    CON 4-2 is Ground.

    4.1.6 Relay Connections:

    TB 2-1 Common Normally Open

    TB 2-2 Normally Closed

    TB 2-3 Normally Open

    5.0 CONFIGURING THE PANEL:The front panel should be mounded in the wall by screw drivers and should not over tighten the

    terminals. Sometimes inbuilt switch in the main panel is switched OFF. Ensure that the inbuilt switch is ON.

    Check the panel without connecting buzzer, loops, bus and battery.

    Connect 230V AC Power supply to the panel and switch on the panel by pressing the button in the front

    panel. All the LEDs in the front panel will blink twice and the green LED will glow which indicates that the

    system is ON.

    Switch off the power and then connect the loops, bus and sounder circuit correctly. Connect the 12V

    batteries to the main panel and check the polarity of the battery connection before proceeding.

    Disconnect the AC supply from the panel and supply power to the panel through 12V batteries and

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    11/31

    11

    check the panel if it is working through battery.

    After checking the panel without any external device and with battery, restart the panel once again. All

    the LEDs in the front panel and external devices will blink for 2 seconds which indicates that all devices

    are connected to the panel. The green LED will glow in the front panel which indicates the system ON.

    The LCD window then display as:

    (Displays for one second)

    (Displays for one second)

    If the 230VAC supply is faulted or Power Off, the batteries will supply the power and the yellow LED will

    glow which indicates the mains fail. The LCD window is display as:

    If the 230V AC supply is failed or power off and the supply batteries also have low charge, the yellow LED

    in the front panel will glow which indicates the Low Battery. The LCD windows in the panel will display as:

    Configuration of panel from PC:

    The analogue addressable fire alarm control panel is a multiprocessor based configuration system. In order

    to allow configuration from a PC, it is necessary to have the AL GRAPH V X.X software installed in the

    computer.

    Naveen Fire Alarm

    India Pvt Ltd

    System ON 01 Jan 2009

    12:00

    Mains Fail 01 Jan 2009

    12:00

    Mains Fail Low Batt 01 Jan 2009

    12:00

    Addressable Intelligent Fire Alarm

    Software Version

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    12/31

    12

    Before starting the configuration, the fire alarm panel has to be previously switched ON, fully tested and

    execute a successful loop-learn. It is useless continuing if there is wiring faults or the fire alarm panel is not

    functioning correctly.

    Firstly, switch off the fire alarm panel and connect the Programming Lead to the RS232 connector in the

    panel. Then, connect the D-type connector into an available serial port on the computer. For computers that

    do not have a 9 pin serial port, a U187 USB converter will be needed.

    Program requirements:

    This segment describes hardware, software and memory requirements for using AL GRAPH V X.X for Windows.

    Hardware requirements:

    A processor speed of 90 MHz or better A Microsoft compatible mouse or pointing device supported by Windows An EGA, VGA or Super VGA graphics card An RS232 serial port One CD disk drive

    Software requirements:

    An installed copy of Microsoft Windows 2000, XP or windows 7

    Memory requirements:

    At least 2MB of free hard disk space RAM 16/32 megabytes

    Installation:

    Install the software onto the computer as follows:

    1. Insert the AL GRAPH V X.X software CD into the CD drive2. Copy the setup file and paste it in the PC3. Right click on setup.exe & click on open

    4. Click Next to continue

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    13/31

    13

    5. Enter your User information and click next to continue

    6. Install the software in the suitable place for you and click next to continue

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    14/31

    14

    7. Click Next to proceed with the installation

    8. AirLight NL 1.0 is installing. If needed, click cancel to abort the setup

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    15/31

    15

    9. Once the installation is complete, the following dialogue box will appear. Click on Finish to exit the installer

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    16/31

    16

    Configuring the panel via PC:

    Connect the panel to the computer through RS232 connector and switch on the Panel. After connecting

    the panel to the PC, double-click the software on the Computer desktop to open. The window in the PC

    will display as:

    1. Click Connect in the software for connecting PC to the panel. If it is connected, then the status in

    the Left corner shows connected. If it is not connected then status shows Not Connected. Default baud

    rate for this software is 9600.

    2. Click Zone Detail in the software for writing and loading the zones. The window in the PC will display

    as:

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    17/31

    17

    A group of devices and detectors connected in one area is a zone; for e.g.: kitchen, bedroom, shower-

    room, etc. In this option, we can enter Zone ID and Zone name in the box and click the Write option. If

    you have previous Zone detail files saved in the PC then clickLoad option which will load the files into the

    Zone details from PC. Up to 16 Zone names can be entered here.

    3. Click Device details in the software for writing and loading the device ID and Location name. Thewindow in the PC will display as:

    In this option we can enter device ID and Location name in the box and click the write Page options.

    You can write the location name from the previously saved file from PC by clicking the options Write

    from File. You can also load the data from the saved files in the PC by clicking the options Load

    You can also write individual device ID and Location name in the software by entering the ID and name

    in the bottom box and click the Write option. User can enter up to 999 Device IDs and names. User

    can view the location name by clicking Previous and Next buttons in the Left corner. User can save

    the entered Device ID and Location name by clicking the Save output to file options.

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    18/31

    18

    4. ClickOptions in the software, then the window will display as:

    5. User can view the reports and logging details by clicking Option and then click Reports in the

    software. Then the display window will show as:

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    19/31

    19

    6. By clicking the Import to Database, user can import the reports and logging records to the

    database. User can load the reports by clicking Load in the window.

    7. ClickOption and then clickReset system to reset the system in the software.

    8. ClickOption and then Silence in the software to silence the alarm at the panel.

    9. ClickOption and then Load Default in the software to load the default details.

    10. Clickoption and then Erase Zone to erase the Zone ID and Zone no.

    11. Clickoption and then Erase Report to erase reports and logging details in the system.

    6.0 PROGRAMMING/OPERATING:

    Normal conditions:

    In the normal condition, when there are no fire or fault conditions, system displays Current Time & Date.

    By pressing the ENTER key, the system will display as:

    Use Right /Left Navigation keys to switch between Alter and viewMode

    Selecting the view mode and Pressing the ENTER key grants access to Level 1

    Selecting the Alter mode and Pressing the ENTER key grants access to Level 2

    6.1 Level 1 Access Mode:

    This mode is the normal user level; in this level you can view fire condition report using navigation keys. The

    window in this level is displayed as:

    System ON 01 Jan 2009

    12:00

    ALTER VIEW

    Lt\Rt ENT\ESC

    VIEW MODE UP\DN ENT\ESC

    FIRE & Flt Report

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    20/31

    20

    By pressing the ENTER key, the window will display as:

    Use Up\Down keys to view the report. When there are no fire or fault conditions present, the window willdisplay as,

    Fire Condition:

    If the control panel initiates an alarm condition, the FIRE LED Indicators will be illuminated and, if appropriate,

    the relevant ZONE FIRE LED Indicators will illuminate. The internal buzzer will sound and the alphanumeric

    display will indicate the number of fires.

    In a fire alarm condition, the numerical address and a more detailed description of the device address of

    the detector / manual call point which is activated is displayed on the bottom line and the zone number and

    the address to which it is assigned is displayed on the top line (provided this information has been

    programmed into the panel).

    6.2 Level 2 Access Mode:This mode is the System administrator access level. The window will display as:

    By pressing the ENTER key, the window will display as,

    Authorization is granted by entering the four digit password. Default password is 1234. Use the numeric

    FIRE REP 001 OF 001 Zone-01 DEV-026

    10/05/09 12:31

    NO FAULT RECORD

    FIRE in ZONE 1 GENERATOR ROOM

    1/1 Dev 35 LEFT SIDE PANEL AREA

    ALTER VIEW

    Lt/Rt ENT/ESC

    Enter Password: xxxx

    (0-9) Lt/Rt ENT/ESC

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    21/31

    21

    keypad to input the password. By Pressing the EnterKey the window will display as:

    If the password entry is incorrect, then the window will display as:

    The functions available in the level 2 access mode are:

    1. Set time & date

    2. Enter Zone Area

    3. Enter Device Point

    4. Zone config Report

    5. Erase Data Log Report

    6. Change Password

    7. Zone Isolation

    8. Assign Devices

    9. Add/Remove Dev Manually

    10. Engineering mode

    6.2.1 Set time & date:You can change the time and date in this menu. The windows in the LCD shows:

    Use the numeric keypad to alter the time and date. When the correct value has been entered, Press ENTER

    key to move to the date field and repeat as required.

    ALTER MODE Up/Dn ENT/ESC

    1. Set Time & Date

    Invalid Password

    HH:MM:SS Set Time in 24 hrs

    00 : 00 : 00 (0-9) Ent / ESC

    DD:MM:YYYY Set Date

    01 / 01 / 2000 (0-9) Ent / ESC

    Setting Calendar

    Please wait

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    22/31

    22

    Press ESCAPE key to exit this menu. Use Up/Down keys to select other functions.

    6.2.2 Enter zone area:

    This menu allows you to enter the description of the zone location. Use Up/Down keys to select the zone

    number.

    Press ENTER key to confirm and use the numeric keypad to enter the text for the zone location.

    Press ENTER key to move to the next zone and repeat as required. Press ESCAPE key to exit this menu.

    6.2.3 Enter device point:

    This menu allows you to enter the description of the device location. Use up/down keys to select the Device

    number.

    Press ENTER key to confirm and use the numeric keypad to enter the text for the device location.

    Press ENTER key to move to the next Device and repeat as required. Press ESCAPE key to exit this menu. Use

    up/down keys to select the other functions.

    6.2.4 Zone config report:The reports of all the devices assigned to a particular zone are displayed in this menu. Use up and down keys

    to view the reports of other zones. The window wil l display as:

    ZONE 01 Up/Dn Edit/ Esc

    ZONE 01 (0-9) Rt/Lt Ent/Esc

    Generator Room sf-ab

    Device 001 Up/Dn Edit/ESC

    Device 001 (0-9) Rt / Lt Ent / Esc

    Right Corner Sf-ab

    ZONE 01 Up / Esc

    017 020 025 030

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    23/31

    23

    Press ESCAPE key to exit this menu. If no devices are configured for the zones, the window will display as,

    Use Up and Down keys to select the other functions.

    6.2.5 Erase data log report:

    In this we can erase all the fire event data. The window in this menu will display as:

    Press ENTER key to confirm the delete options.

    Press ENTER key to confirm the delete option and press ESCAPE key to exit this menu.

    6.2.6 Change password:In this menu, we can change the access level 2 password. The window in the LCD will display as:

    Password

    Input the 4-digit new password using the numeric keypad and Press ENTER key to confirm the changes.

    Press ESCAPE key to exit this menu.

    ZONE 01 Up / Esc

    No Devices Configured

    Confirm to Delete

    Ent / Esc

    Deleting

    ENTER NEW PASSWORD 1234

    (0-9) Rt/Lt Ent/Esc

    ENTER NEW PASSWORD 1234

    PASSWORD CHANGED (0-9) Rt/Lt Ent/Esc

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    24/31

    24

    6.2.7 Zone isolation:

    If a zone is programmed for non-fire conditions i.e. isolated and if a device is triggered on that zone, it will not

    be processed in the normal way, in which a fire condition will never be established, there will be no indication

    and hooters will not be activated. The window in the LCD will display as:

    Use Up and Down keys to switch between zone isolation on/off. Press ENTER key to confirm changes or press

    ESCAPE key to exit this menu.

    6.2.8 Assign devices:

    In this menu we can assign the no. of I/P devices (Detectors, MCPs) and O/P devices (Sounder beacon, short

    circuit isolators and control modules) to put into scanning mode.

    No. of i/p devices

    No. of o/p devices

    Starting address of i/p devices

    Ending address of i/p devices

    I/P devices: Smoke Detector, photo thermal Detector, Heat Detector, MCP

    O/P devices: Hooter, Control module

    By pressing the ENTER key, the following window will display as,

    Zone Isolation

    Zone-01 : Off Up / Esc

    Assign Devices for scan

    00 00 00 00 000 000 (0-9) Ent / Esc

    Devices assigned for scan

    Please restart the system

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    25/31

    25

    Press ESCAPE key to exit this menu. It is mandatory to do a panel reset after assigning devices for scanning.

    6.2.9 Add / remove device manually:

    In this menu we can add or remove device into or from a particular zone. The window in the LCD will display

    as:

    Press ENTER key to confirm the changes.

    Press ESCAPE key to exit this menu.

    6.3 Level 3 access mode (engineering mode):This level mode is the engineer level access mode. Authorization is granted by entering the four digit

    password. Default password is 4321. Use the numeric keypad to input the password. By pressing the ENTER

    key, the window will display as:

    If the password entered is incorrect, then the following window will display as:

    The functions available in the level 3 access mode are:

    1. Set Serial No

    2. Set Default Value

    Address Zone Manually Edit Device

    000 00 (0-9) Lt/Rt Ent/Esc

    Device Assigned

    Enter Password: xxxx

    (0-9) Lt/Rt Ent/Esc

    Engineering Mode Up/ Dn Ent/Esc

    1. Set Serial No.

    Invalid Password

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    26/31

    26

    3. Write Bus data

    4. Health check Up

    Use up and down keys to select the menu.

    6.3.1 Set serial no:

    Enter the four digit serial number using the numeric keypad. Press ENTER key to confirm the changes or press

    ESCAPE key to exit this menu.

    6.3.2 Set default value:

    With this we can load the EEPROM with default values of level 2 and level 3 passwords, panel serial number,

    zone/device location messages. By pressing the ENTER key following window will display as:

    This menu is used to assign the serial number to the panel. The window will display as:

    Press ESCAPE key to exit this menu.

    6.3.3 Write bus data:

    In this menu, we can write the data into the detectors, Sounder beacons, MCPs, Control Modules and Short

    circuit isolators.

    Set System SL No. 111

    (0-9) Lt/Rt Ent/Esc

    Confirm to set default value

    Ent / Esc

    Loading Default..63

    Loading device Loc

    Enter device ID No: 00 00 000 000

    (0-9) Lt/Rt Ent/Esc

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    27/31

    27

    Loop ID:

    The first two digit number is used to say to which device (I/p or o/p) the data is read/written into.

    Function:

    The second two digit number is used to say what function it is going to perform.

    Function Option

    RESET 1

    ISOLATOR 2

    IDCONFIRM 3

    READ_REF 4

    SILENCE 5

    SCAN 6

    SET_DEFAULT 7

    READ_ANALOG 8

    OUTPUT 9

    REF_ADJUST 10

    RENAME 11

    LED_BLINKON 12

    LED_BLINKOFF 13

    SET_REF 14

    Device Number:

    The third and fourth three digit number is used to say to which detector the data is written into and incase of

    sounder beacon/control modules, denotes zone number.

    Example:

    01 denote the rest of the detector and incase of hooters/control modules denotes zone number

    03 denote the device identification

    06 denote device scanning

    07 denote read EEPROM value

    08 denote writing smoke reference value to the detector

    09 denote writing temperature reference value to the detector

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    28/31

    28

    For example when you do a device scan of detector number 3 you have to write

    06 06 000 003

    The detector replies you with the following data:

    170 03 11 11 000 003 052 060

    7.0 TROUBLE SHOOTING:

    LCD:

    1. If there is no display in the LCD then the User has to check if the LCD Connecter cable is properly

    connected to the main board or not.

    2. If the LCD display becomes brighter then change the direction of the connector.

    KEYPAD:

    If the keypad in the Front panel is not working then check the connector. If the keypad is not working even after checking the connector, then check the Keypad IC

    PCF8574IC.

    Suppose keys in a single row are not working, and then change the Master IC.

    FUSE:

    If there is no input power supply to the panel, then check the SMPS fuse. If the System ON LED is in off condition even after the system is ON, then check the fuse F1

    and if it is the problem, replace it.

    If the System ON LED is glowing but the panel is not working means check the power transistorconnection.

    LOW BATTERY:

    If the voltage of the battery in the panel comes down the low voltage, then the yellow LED in the panel will

    glow which indicates the Low Battery. Then charge the Battery in the panel.

    Product

    ID

    Dev ID SL No.High

    SL No.Low

    0 Normal

    Non-Zero - Fire

    DevID

    SmokeValue Temperature

    value

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    29/31

    29

    TIME & DATE:

    If the time and date in the panel didnt work, check the RTC battery in PCB. If the time and date in the panel didnt change means check if the Timer IC is working or not.

    TONES:

    If the tones for Low battery, mains fail and Fire alarm doesnt work properly means check the transformerconnections in the PCB.

    8.0 MAINTENANCE:The device owner shall ensure that a periodic Inspection and Servicing Maintenance Schedule will be

    followed.

    The device owner shall appoint a single, named responsible person to oversee all aspects related to the fire

    alarm system, including record keeping and false alarm management.

    In accordance with best practice, responsible person should maintain a logbook to record all events from or

    affecting the system. The logbook should be kept in a place accessible to authorized persons.

    All events should be properly recorded (events include false fire alarms, temporary disconnections and

    service visits).

    No responsibility can be accepted by the manufacturer or distributors of this range of fire panels for any

    misinterpretation of an instruction or guidance note.

    9.0 WARNING AND CAUTION:

    This warning contains vital information. The system has been designed to be as effective as possible. Thereare situations, however involving fire, smoke or other types of emergencies where it may not provide

    protection. Any alarm systems of any type may fail to operate as expected for many reasons. Some but not

    all of these reasons may be:

    Inadequate installation:

    A security system must be installed properly in order to provide adequate protection. Every installation should

    be evaluated by a professional person to ensure that all access points and areas are covered. Windows,

    doors, walls, ceilings and other building materials must be of sufficient strength and construction to provide

    the level of protection expected. An evaluation by fire/police department is highly recommended if the

    service is available.

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    30/31

    30

    Power failure:

    Control panel, smoke detector, heat detector and many other security devices require an adequate power

    supply for a proper operation. If the device operates from batteries, it is possible for the batteries to fail. Even

    if the batteries have not failed, they must be charged, maintained in good condition and installed correctly.

    If a device operates only by AC power supply, any interruption will render that device inoperative while it doesnot have power. Power interruptions of any length are often accompanied by voltage fluctuations which may

    damage electronic equipment such as detectors, security systems, etc. After a power interruption conduct a

    complete system test to ensure that the system operates as intended.

    Smoke detector:

    Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot

    sense all types of smoke equally well. Smoke detectors may not provide timely warning of fires caused by

    carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of

    flammable materials, overload electrical circuits, etc.

    Warning device:

    Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping if

    there is an intervening wall or door. If the warning devices are located on a different level of the residence or

    premise. Then it is unlikely that the occupants will be alerted or awakened.

    Inadequate testing:

    Most problems that would prevent an alarm system from an operating as intended can be found by regular

    testing and maintenance. The testing should include all sensing devices, keypads, control panel, alarm

    indicating device and any other operational devices that are the part of the system.

    Security and insurance:

    Regardless of its capabilities and advantages, an alarm is not a substitute for property or life insurance. An

    alarm is also not a substitute for building owners, renter or other occupants to act quickly to prevent or to

    minimize harmful effects of an emergency situation.

  • 7/28/2019 Adressable Intelligent Fire Alarm Panel Manual

    31/31

    10.0 BLOCK DIAGRAM AND CIRCUIT CONNECTIONS OFADDRESSABLE PANEL: