COMMUNITY COLLEGE OF ALLEGHENY COUNTY PURCHASING DEPARTMENT
800 ALLEGHENY AVENUE, PITTSBURGH, PA 15233
ADDENDUM NO. 1 BID PROPOSAL NO. 1036
UPGRADE EMERGENCY GENERATOR AND UPS AT SOUTH CAMPUS DECEMBER 6, 2018
The following additional information is hereby made a part of this bid proposal: ***************************************************************************** Please include a $7,500 allowance with your bid for patching and painting. Completion date to be 3-20-19. See the attached, revised drawings E204 and E107. Liebert UPS and Cummins generator to be purchased separately by CCAC and provided for this project. See attached specifications for the UPS and Gen Set.
End of Addendum 1.
************************************************************************** Sign addendum and submit to the College with your original bid.
Company Name Bidder’s Signature
L473A
L473
EXISTING PANEL TR473B150A 120/208V., 3Ø, 4W.PROVIDE BREAKERS IN THISPANEL TO MEET PANELSCHEDULE REQUIREMENTS.
EXISTING PANEL TR473150A 120/208V., 3Ø, 4W.
EXISTING FIRE ALARMPANEL
PANEL TR473C175A 120/208V., 3Ø, 4W.
112.5 KVATRANSFORMER
60/2/30/3R
60/2/30/3R
1SBA-27,29
1SBA-31,33
J
J
AC05
AC06
CU06
CU05
LFC
ATS #1
ATS #2
150 KVA UPSBY CCAC
J
J
PANEL'1SBA'
PANEL'UPS1A'
200/3/175
ELECTRICAL CONTRACTOR TOPROVIDE INTERCONNECTIONWIRING BETWEEN OUTDOORCU AND INDOOR AC UNIT.
ELECTRICAL CONTRACTOR TOPROVIDE INTERCONNECTIONWIRING BETWEEN OUTDOORCU AND INDOOR AC UNIT.
A
S T
PROVIDE DIGITALTIMER SWITCH
A
A
A
ELECTRICAL CONTRACTOR SHALL INSTALLAND WIRE DISCONNECT SWITCHESPROVIDED UNDER MECHANICALCONTRACTOR'S SCOPE OF WORK
1SBA-24
SD
SD
PROVIDE (2)ADDRESSABLE SMOKEDETECTORS TO MATCHBASE BUILDINGSYSTEM AND PROVIDEALL REPROGRAMMINGINTO EXISTING FIREALARM SYSTEM.
ELECTRICALWIREWAY
ELECTRICAL CONTRACTOR TO PROVIDE 4"X 1/4" X 2'-0" COPPER GROUND BUS BARAND TIE BACK TO GROUND BAR LOCATEDIN ROOM L473 WITH #4/0 GREEN
GENERATORE-STOP WITHPLASTICENCLOSURE.
1SBA-10
1SBA-10
1SBA-10
THE ELECTRICAL CONTRACTOR SHALLUTILIZE THE EXISTING 120 VOLT BRANCHCIRCUITS MADE AVAILABLE FROMDEMOLITION OF EXISTING HALF HEIGHTWALL.
THE ELECTRICAL CONTRACTOR SHALLUTILIZE THE EXISTING 120 VOLT BRANCHCIRCUITS MADE AVAILABLE FROMDEMOLITION OF EXISTING HALF HEIGHTWALL.
THE ELECTRICAL CONTRACTOR SHALLPROVIDE A DOUBLE GANG JUNCTIONBOX WITH A SINGLE GANG FACEPLATEAT 18" AFF. PROVIDE A 1 1/4"C FROMJUNCTION BOX STUBBED UP TO ABOVECEILING SPACE OF COMPUTER LAB.TYPICAL AT (5) LOCATIONS.
1
DESIGNED:
DRAWN:
CHECKED:
DRAWING NUMBER
PROJECT NUMBER: 1841064
DRAWING TITLE
SEAL
NO. DATE REVISIONS/ADDENDUMS
DATE: 11-21-18
SCALE: AS SHOWN
PR
OJE
CT
N
AM
E
A
D
G
B
L
KEY PLAN
CC
AC
S
OU
TH
C
AM
PU
S - U
PS
A
ND
G
EN
ER
AT
OR
U
PG
RA
DE
800 A
llegheny A
venue P
ittsburgh P
A 15233
17
50
C
la
irto
n R
oa
d W
est M
ifflin
, P
A 1
51
22
-3
02
9
CC
AC
P
ro
je
ct #
13
-C
O-0
03
s5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
1 12.06.18 ADDENDUM #1
MWM
E204
MWM
DEB
BUILDING L
ELECTRICAL PLAN
1
E204BUILDING L ELECTRICAL PLAN - #L473 & L473A1/2" = 1'-0"
2
E204BUILDING L ELECTRICAL PLAN - UPS ROOM #L482B1/2" = 1'-0"
1E204
2E204
NORMAL FEEDERSRISE UP LOCATIONFROM KILN ROOMC306 BELOW.STUB OUT ANDFIRE SEAL ALLPENETRATIONS.
PANELTR473C
PARALLEL EMERGENCYFEEDERS RISE UPLOCATION FROM KILNROOM C306 BELOW.STUB OUT AND FIRE SEALALL PENETRATIONS.
PROVIDE AN ALLOWANCE OF$7,500.00 FOR PATCHING, REPAIRINGAND PAINTING OF WALL AREA TO BEDISTURBED FOR CONDUIT ROUTINGS.
1
DESIGNED:
DRAWN:
CHECKED:
DRAWING NUMBER
PROJECT NUMBER: 1841064
DRAWING TITLE
SEAL
NO. DATE REVISIONS/ADDENDUMS
DATE: 11-21-18
SCALE: AS SHOWN
PR
OJE
CT
N
AM
E
A
D
G
B
L
KEY PLAN
CC
AC
S
OU
TH
C
AM
PU
S - U
PS
A
ND
G
EN
ER
AT
OR
U
PG
RA
DE
800 A
llegheny A
venue P
ittsburgh P
A 15233
17
50
C
la
irto
n R
oa
d W
est M
ifflin
, P
A 1
51
22
-3
02
9
CC
AC
P
ro
je
ct #
13
-C
O-0
03
s5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
1 12.06.18 ADDENDUM #1
MWM
E107
MWM
DEB
FOURTH FLOOR BUILDING L
OVERALL ELECTRICAL PLAN
1
E107FOURTH FLOOR BUILDING L OVERALL ELECTRICAL PLAN1/8" = 1'-0"
12/6/2018 Vertiv-Proprietary Page 1 of 2
Liebert
c/o Donwil Company, 22 McCormick Road, McKees Rocks, PA 15136 FAX: (412) 787-1333 PH: (412) 787-1313
COMPANY: Allen & Shariff PROPOSAL #: Q02859030 ATTN: Mark Maydak PAGES: 2 FAX: DATE: Sep 17, 2018 FROM: Bob Wroblewski
PROJECT: CCAC - SOUTH CAMPUS - UPS
Liebert EXM Single Module UPS System each consisting of the following: One (1) 150 kVA/kW Nameplate Liebert EXM UPS, Model 51SA150EAA000C5, with the following features:
System Input Voltage of 480V, 60Hz, 3 Phase, 3 wire plus ground System Output Voltage of 208/120V, 3 Phase, 4 wire plus ground 100 kVA/kW Initial Capacity Scalable to 150 kVA/kW Ultimate Capacity UPS System Single Input Configuration Transformer-Free Architecture - Efficiency up to 96% in double conversion mode Unity Power Factor Rating - Delivers more usable power per kVA Load Power Factor Support - Supports loads 0.5 lagging to unity without derating Energy Optimization Mode (Eco-Mode) 65kAIC Rating - Provides interrupting rating and labeling of 65kA Active Power Factor Corrected IGBT Input Converter PWM transistorized (IGBT) inverter Continuous Duty Static Bypass Switch Input Contacts - Dry contacts are available for functions including monitoring external breakers,
on-generator signal, and other functions Output Contacts - Dry contacts are available for functions including a permissive signal to
maintenance bypass SKRU, to trip external breakers, and other functions Generator Load Control - Suppresses battery charging reducing power demand by an external
signal. Shifts unit from Eco Mode to double conversion (if applicable), and synchronizes the inverter output with the bypass
Automatic retransfer - Provides return to inverter power after an overload DSP based controls - Provides digital control of power conversion and system operation Backlit LCD display - Monitors power conversion, UPS operation and utility conditions. Deviations
are logged for troubleshooting One (1) IntelliSlot Unity Dual Protocol Card; P/N: IS-UNITY-DP; Monitoring and configuration of
Vertiv products and environmental sensors through stand-alone Web UI or integration with Trellis™, Liebert Nform, LIFE™ Services. Supports third-party management systems using SNMP, Modbus or BACnet.
Temperature-Compensated Charging/Battery Load Test Bottom cable entry to UPS, top cable entry through matching bypass or optional wiring cabinet Front only service access Local Emergency Power Off (EPO)
12/6/2018 Vertiv-Proprietary Page 2 of 2
LIFE™ Services for the 1st year IP 20 enclosure Casters and leveling feet UL and cUL Listed to UL Standard 1778 4th Edition
One (1) Liebert EXM Battery Cabinet System, Model 51BPHTAB1L, with the following features :
5 min @ 150 kVA,1 - 1200MM External Cabinet of East Penn HR3500 Batteries 10 min: Run Time at 100 kVA Cabinet Mounted Left Attached to Module The battery is provided with a 3 year full and 7 year prorated warranty
One (1) Maintenance Bypass Matching Cabinet, model 51MBH33AA0R10R6 with the following features:
3 Switching Devices (BIB,MBB,MIB) 300 Amp Breaker Trip Rating Key Interlock (SKRU) Cabinet Mounted Right Attached to Module with connecting cables factory supplied 300 MM - 11.8 inches Frame Size Front Access service design
One (1) Output Distribution Cabinet, Model 51X150BCJALA0F2 with the following features:
600 MM - 24 inches Frame Size K01 Output Transformer Included Input Voltage of 480V, 60Hz, 3 Phase, 3 wire plus ground Output Voltage of 208/120V, 3 Phase, 4 wire plus ground Cabinet Mounted Right Attached to Module with connecting cables factory supplied 600 Amp Output Distribution Load Breaker
o SNMP Communication Front Access service design
Above System Startup Services Startup includes one site trip by a LS customer engineer after the UPS has been installed. The site trip includes the following services for one UPS module: non-powered inspection, UPS electrical and operational checkout, full parts and labor for any remedial work required on the UPS or battery cabinets, and customer operation training. Startup also includes remedial onsite labor, parts, and travel for the full one-year warranty period.
Startup Plus 24x7 is scheduled at the customers designated time One preventive maintenance visit during the first year scheduled at customer’s convenience. The
PM will include the following services for one UPS module: consult with personnel responsible for the equipment, visually inspect internal sub-assemblies and major components, check all mechanical connections for tightness and heat discolorations, clean any foreign material and dust from internal compartments, check status of all alarm circuits, calibrate equipment to manufacturer's specifications, check the normal operation of the system, check battery transfer/discharge and perform a short duration battery run, perform any required engineering field changes, return unit to operational service with normal load then verify the output.
MBC/BDC/Wallmount Panel
LGS Site Services: o Site Acceptance Test with Load Bank