Addendum #01 - Springfield Public Schools › cms › lib › MO01909182 › Centricity...B. SSPC-SP...

17
3659 SOUTH AVE | SPRINGFIELD, MISSOURI 65807 | 417-708-7025 Addendum #01 Date: March 30, 2020 Project: Bissett Elementary HVAC Upgrades From: Jacob Nelson, PE MO# PE-2009018758 03-30-2020 Copy: File General: Refer to the attached Pre-Bid Conference Agenda, Sign-In Sheet, and Bid-Tab. Bid Tab shall be used for viewing of online bid opening. Specifications: Section 00 01 02 – Project Information: 1. Refer to Part 1.05 – F – Bid Opening: a. Revise bid opening to read as follows: Springfield Public Schools General Services Center (GSC) is closed to the public. No access will be permitted to attend the bid opening in person. The public bid opening shall be held virtually via Zoom on April 1, 2020 at 3:00pm. All bid packages must be delivered to GSC prior to the bid opening via parcel courier or bidders may hand deliver bids through the mail delivery slot located on the front lobby door of GSC. Zoom Link: https://zoom.us/j/633887549 Zoom Meeting 633 887 549 Please email Karsten Kargel at [email protected] with any questions. Section 01 21 00 – Allowances: 1. Add allowance for structural steel if needed per attached specifications section AD01 – 01 21 00. Section 09 91 23 – Interior Painting: 1. Revise painting spec per attached specification section AD01 – 09 91 23. Section 23 07 19 – HVAC Piping Insulation: 1. Refer to Part 3.02 – Schedule: a. Add part B to read, “Indoor Condensate Piping: Provide 0.75” insulation for indoor condensate piping shown on P-series sheets.

Transcript of Addendum #01 - Springfield Public Schools › cms › lib › MO01909182 › Centricity...B. SSPC-SP...

  • 3659 SOUTH AVE | SPRINGFIELD, MISSOURI 65807 | 417-708-7025

    Addendum #01

    Date: March 30, 2020

    Project: Bissett Elementary HVAC Upgrades

    From: Jacob Nelson, PE – MO# PE-2009018758 03-30-2020

    Copy: File

    General:

    Refer to the attached Pre-Bid Conference Agenda, Sign-In Sheet, and Bid-Tab. Bid Tab shall be used for viewing of online bid opening.

    Specifications:

    Section 00 01 02 – Project Information:1. Refer to Part 1.05 – F – Bid Opening:

    a. Revise bid opening to read as follows:

    Springfield Public Schools General Services Center (GSC) is closed to the public. No access will be permitted to attend the bid opening in person. The public bid opening shall be held virtually via Zoom on April 1, 2020 at 3:00pm. All bid packages must be delivered to GSC prior to the bid opening via parcel courier or bidders may hand deliver bids through the mail delivery slot located on the front lobby door of GSC. Zoom Link: https://zoom.us/j/633887549

    Zoom Meeting 633 887 549

    Please email Karsten Kargel at [email protected] with any questions.

    Section 01 21 00 – Allowances:1. Add allowance for structural steel if needed per attached specifications section AD01 – 01 21 00.

    Section 09 91 23 – Interior Painting:1. Revise painting spec per attached specification section AD01 – 09 91 23.

    Section 23 07 19 – HVAC Piping Insulation:1. Refer to Part 3.02 – Schedule:

    a. Add part B to read, “Indoor Condensate Piping: Provide 0.75” insulation for indoor condensate piping shown on P-series sheets.

    https://zoom.us/j/633887549

  • Section 23 09 23 – Direct-Digital Control System for HVAC:1. Refer to Part 3.02 – Wiring:

    a. Add part J to read, “The controls contractor is required to provide all new EMT conduit and junctions for new stat locations, wiring in exposed areas, controllers, etc to install wiring. Refer to division 26 specifications for additional requirements.”

    Section 23 09 93 – Sequence of Operations for HVAC Controls:1. Add section 1.08 – Dedicated Outdoor Air Units:

    a. The Dedicated outside air units shall be provided with a controller either factory provided or field installed to deliver neutral air at 72 degree F, 50% RH during occupied mode. While in unoccupied mode the unit shall be off.

    Section 23 23 00 – Refrigerant Piping1. Refer to Part 2.02 – Piping:

    a. Revise copper to be Type L.

    Section 23 74 13 – Packaged Outdoor Central Station Air Handling Units:1. Refer to Part 2.02 0 Manufactured Units:

    a. Add part C to read, “All base bid units for Lennox shall provide the notes listed on the schedule and in the specifications. The alternate Aaon units shall have the following additional notes and accessories:

    i. Double Wall constructionii. 25-year stainless steel heat exchanger warrantyiii. Heat pressure control

    Drawings:

    Sheet MEP200B – MEP Demo Plan – Area B:1. Refer to detail 1/MEP200B – Demo Mechanical Ductwork Plan – Area B:

    a. Revise keynote D23.19 to read, “REMOVE EXISTING CHILLER AND CORRESPONDING HYDRONIC PIPING BACK TO BOILER ROOM. REMOVE CONCRETE HOUSEKEEPING PAD AND RESEED EXISTING GRASS EFFECT BY THE REMOVAL.”

    b. Revise keynote D23.22 to read, “REMOVE EXISTING BOILER AND ASSOCIATED HYDRONIC PIPING, EXPANSION TANK, AIR SEPARATOR, ETC. IN BOILER ROOM. REMOVE EXISTING RAISED CONCRETE HOUSEKEEPING PAD AND LEVEL CONCRETE FLOOR EFFECTED BY THE REMOVAL.”

    Sheet M400 – Mechanical Schedules:1. Refer to Dedicated Outside Air Unit Schedule:

    a. Modify notes per attached sheet AD01-M400.2. Add air device schedule per attached sheet AD01-M400.

    Sheet E100A – Power Plan – Area A:1. Refer to detail 1/E100A, HVAC Power Plan – Area A:

    a. Add location of existing fire alarm panel per attached sheet AD01-E100A.b. Add location of existing IT closet per per attached sheet AD01-E100A.c. Remove BAS power and data locations per attached sheet AD01-E100A.d. Add tag to data devices and revise keynote 26.12 per attached sheet AD01-E100A.

    Sheet E200 – Electrical Details:1. Add sheet E200 to the Construction Document set per attached sheet AD01-E200.2. Add detail 1/E200, Reflected Ceiling Plan for Coordination per attached sheet AD01-E200.

  • 3. Add Communications Device Schedule per attached sheet AD01-E.

    Attachments:

    Pre-Bid Conference Agenda, Sign-in Sheet, Bid Tab Specifications:

    o Allowances – AD01 – 01 21 00.o Interior Painting – AD01 – 09 91 23.

    Sheets: o AD01-M400 – Mechanical Scheduleso AD01-E100A – Power Plan – Area Ao AD01-E200 – Electrical Details

  • 3659 SOUTH AVE. | SPRINGFIELD, MISSOURI 65807 | 417-708-7025

    Pre-Bid Conference

    Date: March 24, 2020

    Time: 1:00 pm

    Project: Bissett Elementary HVAC Upgrades

    Location: Bissett Elementary School

    Introductions:

    Representatives:o Owner: Springfield Public Schools

    Contact: Karsten Kargelo Engineer: True Engineering Group

    Jacob Nelson, PE Jon Kamies, EIT

    Online Plan Room: Visit www.erdigital.com Printed or digital plans and specifications are available for purchase. Contact

    Engineers Reprographics at 417-869-2222

    Project Description:

    Summary Project Description: The project is comprised of replacing and upgrading the existing HVAC system at Bissett Elementary School in Springfield, Missouri. The HVAC system scope

    includes replacement packaged rooftop units and new VRF systems. The building automation

    system will also be replaced.

    Bid Requirements and Procedures:

    Bid Submission Deadline and Public Bid Opening Date: Sealed proposals for the construction including the furnishing of all necessary materials, labor, and equipment for BISSETT ELEMENTARY HVAC UPGRADES FOR SPRINGFIELD PUBLIC SCHOOLS, SPRINGFIELD, MISSOURI shall be opened at the office of General Service Center, Springfield Public Schools, 1458 E. Chestnut Expressway, Springfield, MO 65802 at 3:00 p.m. (C.S.T.) April 1, 2020. Any proposal received subsequent to the time specified will be promptly returned to the bidder unopened. The sealed bid should be clearly marked on the outside of the envelope per the guidelines listed in the specifications.

    01 25 00 for substitutions. Substitution requests will be reviewed up until the end of the day on March 26, 2020. Any substitution requests after the deadline will not be reviewed.

    Bid Bond and Payment/Performance Bond are required.o Bid Bond of 5% of the bid is required to be enclosed with bids.

    http://www.erdigital.com/

  • 3659 SOUTH AVE. | SPRINGFIELD, MISSOURI 65807 | 417-708-7025

    o Bids may not be withdrawn for 30-day period.

    o Payment and Performance Bonds – 100% required at time of contract. The board is expected to approve contract negotiations with the successful bidder at the April 21, 2020 board meeting with a notice to proceed on April 22, 2020.

    Bid Form: Refer to specification section 00 41 00 for the bid form. Bid must be on the bid form provided in the specifications.

    Alternatives:o Alternative #1: Alternative HVAC Equipment Manufacturers: Substitute HVAC equipment

    manufacturers to be Aaon and LG.

    Product List: All bidders shall submit a list of all major equipment to the owner in a sealed envelope at the bid opening.

    Subcontractor Listing: All bidders shall submit a list of subcontractors to the owner in a sealed envelope at the bid opening.

    Project Administration:

    General Contract Conditions:o Standard contracts and procedures; will be reviewed in detail at the Pre-Construction

    meeting with the successful bidder once contracts are awarded. Wage Rates: Missouri Prevailing Wage Laws, Rates and Procedures are required, as applicable.

    The project is located in Greene County, Missouri. Tax Exempt: The project is tax exempt. Completion Date and Liquidated Damages:

    o July 24, 2020 - All major installations shall be completed including, but not limited to the new equipment, electrical modifications, and building automation systems.

    o August 7, 2020 - Date set for substantial completion. The entire project shall be complete with the air conditioning and heating operational. The project shall be ready for inspection and functional testing of the equipment. A punch list will be prepared. Liquidated damages for substantial completion will apply.

    o September 18, 2020 - Contract date for final completion. Liquidated damages for final completion will apply.

    True Engineering Group will be assisting the owner during construction and will be on-site for the installation of the majority of the HVAC equipment installation, start-up, and owner training.

    True Engineering Group will also be commissioning the project to insure the equipment is operating as intended. Pre-functional checklist will be distributed to the successful contractor prior to starting the replacement of the equipment.

    A clean, tobacco free site shall be maintained during construction and each contractor shall prevent debris from getting onto adjacent properties. Tobacco products will not be allowed in any of the buildings or on the roof. No alcoholic beverages or illegal substances of any kind will be allowed on site.

    Job Conditions and Special Issues:

    The project has a tight timeline to remove and install the new HVAC equipment and electrical equipment. The successful contractor will be required to coordinate with the owner for onsite equipment storage and access to the building.

    Questions/Clarifications:

  • PRE BID SIGN IN SHEET: Bissett HVAC Project

    Name: Company: Phone#: Email:

    1 Bill Wilson AAP 417.353.6498 [email protected]

    2 Larry Hunt AAP 417.763.9466 [email protected]

    3 Josh Camp Truestar Electric 479.657.0882 [email protected]

    4 Tony Kirkup Knight Heating and Air 417.725.2512 tony@knightheatingand ac.com

    5 Garry Martindale HG Butzer 573.616.6497 [email protected]

    6 Kyle Wenger MCC 417.521.7014 [email protected]

    7 Jacob Nelson True Engineering Group 417.708.7025 [email protected]

    8 David Goetz SPS 417.920.0418 [email protected]

    9 Adam Howie MSI 417.881.0903 [email protected]

    10 Shawn Dilday SPS - Director of Facilities 417.523.0418 [email protected]

    11 Karsten Kargel SPS - Project Coordinator 417.523.0478 [email protected]

    12 Jeff Acheson Ideal Comfort 417.920.8917 [email protected]

    13 John Beauchamp Gold Mechanical 417-873-9770 [email protected]

    14

    15

    16

    17

    18

    19

    20

    mailto:[email protected]:[email protected]:[email protected]:tony@knightheatingand ac.commailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:beauchamp@

  • Bissett Elementary HVAC UpgradesNumber Company Bid Form Bid Bond CashersCheck Base Bid Amount Alternate #01

  • BISSETT ELEMAMTARY SCHOOL HVAC UPGRADES

    SPRINGFIELD PUBLIC SCHOOLS

    SPRINGFIELD, MISSOURI

    Allowances 01 21 00 - 1

    SECTION 01 21 00

    ALLOWANCES

    PART 1 GENERAL

    1.01 SECTION INCLUDES

    A. Contingency allowance.

    1.02 CONTINGENCY ALLOWANCE

    A. Contractor's costs for products, delivery, installation, labor, insurance, payroll, taxes, bonding,

    equipment rental, overhead and profit will be included in Change Orders authorizing

    expenditure of funds from this Contingency Allowance.

    B. Funds will be drawn from the Contingency Allowance only by Change Order.

    C. At closeout of Contract, funds remaining in Contingency Allowance will be credited to Owner by

    Change Order.

    1.03 ALLOWANCES SCHEDULE

    A. Include the stipulated sum of forty thousand ($40,000) for structural modifications to support

    units if required under future direction from structural engineer.

    PART 2 PRODUCTS - NOT USED

    PART 3 EXECUTION - NOT USED

    END OF SECTION

  • BISSETT ELEMENTARY SCHOOL HVAC UPGRADES

    SPRINGFIELD PUBLIC SCHOOLS

    SPRINGFIELD, MISSOURI

    Interior Painting 09 91 23 - 1

    SECTION 09 91 23

    INTERIOR PAINTING

    PART 1 GENERAL

    1.01 SECTION INCLUDES

    A. Surface preparation.

    B. Scope: Finish interior surfaces exposed to view, unless fully factory-finished and unless

    otherwise indicated.

    1. Mechanical and Electrical:

    a. In finished areas, paint insulated and exposed ducts, unless otherwise indicated.

    C. Do Not Paint or Finish the Following Items:

    1. Items factory-finished unless otherwise indicated; materials and products having factory-

    applied primers are not considered factory finished.

    2. Items indicated to receive other finishes.

    3. Items indicated to remain unfinished.

    4. Fire rating labels, equipment serial number and capacity labels, bar code labels, and

    operating parts of equipment.

    5. Floors, unless specifically indicated.

    6. Glass.

    7. Concealed pipes, ducts, and conduits.

    1.02 REFERENCE STANDARDS

    A. MPI (APSM) - Master Painters Institute Architectural Painting Specification Manual Current

    Edition.

    B. SSPC-SP 1 - Solvent Cleaning 2015, with Editorial Revision (2016).

    C. SSPC-SP 6 - Commercial Blast Cleaning 2007.

    1.03 SUBMITTALS

    A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.

    B. Product Data: Provide complete list of products to be used, with the following information for

    each:

    1. Manufacturer's name, product name and/or catalog number, and general product category

    (e.g. "alkyd enamel").

    2. MPI product number (e.g. MPI #47).

    3. Cross-reference to specified paint system(s) product is to be used in; include description

    of each system.

    a. additional colors selected by Architect at no added cost to Owner.

  • BISSETT ELEMENTARY SCHOOL HVAC UPGRADES

    SPRINGFIELD PUBLIC SCHOOLS

    SPRINGFIELD, MISSOURI

    Interior Painting 09 91 23 - 2

    PART 2 - PRODUCTS

    2.1 MANUFACTURERS

    A. Basis-of-Design Product: Subject to compliance with requirements, provide Sherwin-Williams

    Company (The); or a comparable product by one of the following:

    1. Behr Process Corporation.

    2. Benjamin Moore & Co.

    3. PPG Paints.

    4. Valspar Corporation (The).

    5. Farrell-Calhoun

    B. Products: Subject to compliance with requirements, provide product listed in the Interior

    Painting Schedule for the paint category indicated.

    2.2 PAINT, GENERAL

    A. MPI Standards: Products shall comply with MPI standards indicated and shall be listed in its

    "MPI Approved Products Lists."

    B. Material Compatibility:

    1. Materials for use within each paint system shall be compatible with one another and

    substrates indicated, under conditions of service and application as demonstrated by

    manufacturer, based on testing and field experience.

    2. For each coat in a paint system, products shall be recommended in writing by topcoat

    manufacturers for use in paint system and on substrate indicated.

    C. Colors: As selected by Architect from manufacturer's full range.

    1. Thirty percent of surface area will be painted with deep tones.

    PART 3 - EXECUTION

    3.1 EXAMINATION

    A. Examine substrates and conditions, with Applicator present, for compliance with requirements

    for maximum moisture content and other conditions affecting performance of the Work.

    B. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter

    as follows:

    1. Concrete: 12 percent.

    2. Fiber-Cement Board: 12 percent.

    3. Masonry (Clay and CMUs): 12 percent.

    http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?uid=123457105303http://www.specagent.com/Lookup?uid=123457105283http://www.specagent.com/Lookup?uid=123457105297http://www.specagent.com/Lookup?uid=123457105307

  • BISSETT ELEMENTARY SCHOOL HVAC UPGRADES

    SPRINGFIELD PUBLIC SCHOOLS

    SPRINGFIELD, MISSOURI

    Interior Painting 09 91 23 - 3

    4. Wood: 15 percent.

    5. Gypsum Board: 12 percent.

    6. Plaster: 12 percent.

    C. Verify suitability of substrates, including surface conditions and compatibility with existing

    finishes and primers.

    D. Proceed with coating application only after unsatisfactory conditions have been corrected.

    1. Application of coating indicates acceptance of surfaces and conditions.

    3.2 PREPARATION

    A. Comply with manufacturer's written instructions and recommendations in "MPI Architectural

    Painting Specification Manual" applicable to substrates and paint systems indicated.

    B. Remove hardware, covers, plates, and similar items already in place that are removable and are

    not to be painted. If removal is impractical or impossible because of size or weight of item,

    provide surface-applied protection before surface preparation and painting.

    1. After completing painting operations, use workers skilled in the trades involved to

    reinstall items that were removed. Remove surface-applied protection if any.

    3.3 APPLICATION

    A. Apply paints according to manufacturer's written instructions and recommendations in "MPI

    Architectural Painting Specification Manual."

    B. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks,

    roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color

    breaks.

  • BISSETT ELEMENTARY SCHOOL HVAC UPGRADES

    SPRINGFIELD PUBLIC SCHOOLS

    SPRINGFIELD, MISSOURI

    Interior Painting 09 91 23 - 4

    3.4 INTERIOR PAINTING SCHEDULE

    A. Concrete Substrates, Nontraffic Surfaces:

    1. Epoxy, High Build, over Epoxy Primer System MPI INT 3.1P:

    a. Prime Coat: Primer, epoxy, high build, MPI #108.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Aquapon High Build Epoxy Primer or

    a comparable product approved by Architect and Owner.

    b. Intermediate Coat: Latex, interior, high performance architectural, matching

    topcoat.

    a. Topcoat: Epoxy, high build, MPI #108.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Aquapon High Build Epoxy Primer or

    a comparable product approved by Architect and Owner..

    B. Concrete Substrates, Traffic Surfaces:

    1. Water-Based Concrete Floor Sealer System MPI INT 3.2G:

    a. First Coat: Sealer, water based, for concrete floors, matching topcoat.

    b. Topcoat: Sealer, water based, for concrete floors, MPI #99 .

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); H&C Wet Look Sealer with Shark

    Grip additive or a comparable product approved by Architect and Owner..

    C. CMU Substrates:

    1. Alkyd, W.B. over Latex Sealer System MPI INT 4.2C:

    a. Block Filler: Block filler, latex, interior/exterior, MPI #4.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Loxon Acrylic Block Surfacer or a

    comparable product approved by Architect and Owner..

    b. Prime Coat: Primer, alkali resistant, water based, MPI #3.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Loxon Concrete & Masonry Primer

    or a comparable product approved by Architect and Owner.

    http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301

  • BISSETT ELEMENTARY SCHOOL HVAC UPGRADES

    SPRINGFIELD PUBLIC SCHOOLS

    SPRINGFIELD, MISSOURI

    Interior Painting 09 91 23 - 5

    c. Intermediate Coat 1: Latex, interior, high performance architectural, matching

    topcoat.

    d. Intermediate Coat 2: Latex, interior, high performance architectural, matching

    topcoat.

    a. Topcoat: Alkyd, interior (MPI Gloss Level 4), MPI #168.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Pro Industrial Water Based Alkyd

    Urethane or a comparable product approved by Architect and Owner..

    D. Gypsum Board Substrates - Ceilings:

    1. Alkyd, W.B. over Latex Sealer System MPI INT 9.2CC:

    a. Prime Coat: Primer sealer, latex, interior, MPI #50.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Harmony Interior Latex Primer for

    new construction only; all follow up interior painting by SPS will be

    Preprite Problock or a comparable product approved by Architect and

    Owner..

    b. Intermediate Coat: Alkyd, interior, matching topcoat.

    c. Topcoat: Alkyd, interior (MPI Gloss Level 4), MPI #168.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Pro Industrial Water Based Alkyd

    Urethane or a comparable product approved by Architect and Owner..

    A. Gypsum Board Substrates - Walls:

    1. Alkyd, W.B. over Latex Sealer System MPI INT 9.2CC:

    a. Prime Coat: Primer sealer, latex, interior, MPI #50.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Harmony Interior Latex Primer for

    new construction only; all follow up interior painting by SPS will be

    Preprite Problock or a comparable product approved by Architect and

    Owner..

    b. Intermediate Coat: Alkyd, interior, matching topcoat.

    c. Topcoat: Alkyd, interior (MPI Gloss Level 4), MPI #168.

    http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301

  • BISSETT ELEMENTARY SCHOOL HVAC UPGRADES

    SPRINGFIELD PUBLIC SCHOOLS

    SPRINGFIELD, MISSOURI

    Interior Painting 09 91 23 - 6

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Pro Industrial Water Based Alkyd

    Urethane or a comparable product approved by Architect and Owner..

    B. Steel Substrates:

    1. Alkyd System MPI INT 5.1S:

    a. Prime Coat: Primer, alkyd, quick dry, for metal, MPI #76.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Kem Bond HS Universal Alkyd

    Primer or a comparable product approved by Architect and Owner..

    b. Intermediate Coat: Alkyd, interior, matching prime coat.

    c. Intermediate Coat: Alkyd, interior, matching topcoat.

    d. Topcoat: Alkyd, interior (MPI Gloss Level 4), MPI #168.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Pro Industrial Water Based Alkyd

    Urethane or a comparable product approved by Architect and Owner..

    2. Alkyd Dry-Fall System MPI INT 5.1D:

    a. Prime Coat: Primer, alkyd, quick dry, for metal, MPI #76.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Kem Bond HS Universal Alkyd

    Primer (Protective & Marine) or a comparable product approved by

    Architect and Owner..

    b. Topcoat: Dry fall, alkyd, flat, MPI #55.

    1) Basis-of-Design Product: Subject to compliance with requirements, provide

    Sherwin-Williams Company (The); Dry Fall Flat (Protective & Marine)

    or a comparable product approved by Architect and Owner..

    3.5 PAINT SCHEDULE:

    C. Exposed double wall ductwork in Kitchen.

    D. Walls infilled from removed ductwork.

    E. Caps on existing air devices that are removed.

    F. Color determined by owner

    END OF SECTION

    http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301http://www.specagent.com/Lookup?ulid=11642http://www.specagent.com/Lookup?uid=123457105301

  • STA

    TEOF M ISS

    OURI

    P

    NUMBER

    ROF

    ESSIONAL E

    NG

    I NEER

    JACOB

    ADAM NELSON

    PE-2009018758

    In the event the client consents to, allows, authorizes or approves of

    changes to any plans, specifications or other construction documents,

    and these changes are not approved in writing by the design

    professional, the client recognizes that such changes and the results

    thereof are not the responsibility of the design professional. Therefore, the client agrees to release the design professional from any liability

    arising from the construction, use or result of such changes. In addition,

    the client agrees to the fullest extent permitted by law, to indemnify and

    hold the design professional harmless from any damage, liability or cost

    (including reasonable attorney's fees and costs of defense) arising from

    such changes.

    The personal seal of the registered Engineer shall be the legal equivalent

    of his signature whenever & wherever used, and the owner of the seal shall authenticate this sheet and the specification sections pertaining to

    this sheet. Responsibility shall be disclaimed for all other plans,

    specifications, estimates, reports or other documents or instruments

    relating to or intended to be used for any part or parts of the project.

    SPECIAL NOTICES

    DATE:

    PROJECT #:

    DRAWN:

    Drawing No.

    Missouri State Certificate of Authority #E-2016000752

    © Copyright 2020 - True Engineering Group LLC

    Engineer of RecordJacob Adam Nelson PE

    PE-2009018758

    True Engineering Group LLC

    3/3

    0/2

    02

    0 3

    :57:4

    6 P

    M

    Springfield

    Public

    Sch

    ools

    3014 W

    Calh

    oun S

    t.Springfield

    , M

    O 6

    5802

    Bis

    sett

    Ele

    menta

    ry H

    VAC U

    pgra

    des

    JK

    03/16/2020

    SPS-2001

    M400MECHANICAL SCHEDULES

    03/16/2020

    13. HINGED ACCESS DOORS.

    12. PROVIDE CURB ADAPTOR TO MATCH REMOVAL OF EXISTING UNITS.

    11. SINGLE ENTHALPY ECONOMIZER WITH HOOD.

    10. HUMIDITROL COIL FOR ACTICE DEHUMIDIFICATION.

    9. CONNECT TO BAS SYSTEM. COORDINATE REQUIREMENTS WITH BAS CONTRACTOR.

    8. FACTORY INSTALLED, FIELD POWERED GFCI RECEPTACLE.

    7. STAINLESS STEEL HEAT EXCHANGER.

    6. FACTORY MOUNTED DISCONNECTS.

    5. ECM MOTOR WITH TWO-STAGE FAN SPEED TO MATCH COMPRESSOR LOADING.

    4. CONDENSER COIL HAIL GUARDS.

    3. 5-YEAR COMPRESSOR AND 10-YEAR HEAT EXCHANGER WARRENTY.

    2. CRANKCASE HEATER.

    1. FILTER RACK. PROVIDE A MINMUM MERV 8 FILTER.

    NOTES:

    ROOFTOP UNIT SCHEDULE

    TYPEMARK

    MANUFACTURER MODEL NUMBER EER (SEER) TONNAGESUPPLY AIR

    (CFM)OUTSIDE

    AIR (CFM)FAN (BHP)

    EXTERNALSTATIC (WC)

    ENTERINGAIR DB

    ENTERINGAIR WB

    SENSIBLE(MBH)

    TOTAL(MBH)

    HEATINGENTERING

    AIR DB

    HEATINGINPUT

    (MBH)

    HEATINGOUTPUT

    (MBH)

    LEAVINGAIR DB

    MCA MOCP VOLTAGE NOTES

    RTU100 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.16 62.66 33.43 46.78 59.01 70 57 95 28 35 208/3 1 THRU 13

    RTU103 LENNOX LGH048H4E 12.8 4 1600 350 0.75 0.7" 79.72 62.82 34.55 48.07 58.22 70 57 95 28 35 208/3 1 THRU 13

    RTU104 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.32 62.72 32.90 46.34 59.01 70 57 95 28 35 208/3 1 THRU 13

    RTU105 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.28 62.68 33.25 46.19 59.01 70 57 95 28 35 208/3 1 THRU 13

    RTU106 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.31 62.71 33.14 46.57 59.01 70 57 95 28 35 208/3 1 THRU 13

    RTU107 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.28 62.68 33.26 46.20 59.01 70 57 95 28 35 208/3 1 THRU 13

    RTU108 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.36 62.66 33.40 46.84 59.84 70 57 95 28 35 208/3 1 THRU 13

    RTU114 LENNOX LGH180H4B 12.0 15 5250 750 3 0.7" 74.50 62.00 99.83 144.18 63.00 260 208 95 68 80 208/3 1 THRU 13

    RTU115 LENNOX LGH036H4E 12.8 3 1200 240 0.5 0.7" 78.76 62.66 21.28 30.76 59.40 70 57 95 22 30 208/3 1 THRU 13

    RTU119 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.16 62.66 28.86 41.80 59.01 70 57 95 28 35 208/3 1 THRU 13

    RTU121 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.27 62.67 29.83 42.77 59.01 70 57 95 28 35 208/3 1 THRU 13

    RTU122 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.29 62.69 34.10 47.07 59.01 70 57 95 28 35 208/3 1 THRU 13

    RTU123 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.20 62.70 29.46 42.40 59.01 70 57 95 28 35 208/3 1 THRU 13

    RTU124 LENNOX LGH048H4E 12.8 4 1600 330 0.75 0.7" 79.32 62.72 34.45 47.44 59.01 70 57 95 28 35 208/3 1 THRU 13

    5. DRAIN PAN WITH CONDENSATE SENSOR AND SHUTDOWN RELAY.

    4. CONDENSATE PUMP POWERED THROUGH UNIT.

    3. PROVIDE VRF SYSTEM MANUFACTURER'S PROGRAMMABLE WALL-MOUNTED 7 DAY PROGRAMABLE CONTROLLER/THERMOSTAT.

    2. SUSPEND FROM STRUCTURE PER MANUFACTURER'S RECOMMENDATIONS AND REQUIREMENTS. PROVIDE VIBRATION ISOLATION ACCESSORIES.

    1. PROVIDE MERV-8 FILTER AND FILTER RACK.

    NOTES:

    VRF - FAN COIL UNIT SCHEDULE

    TYPEMARK

    MANUFACTURER MODEL NUMBERSUPPLY AIR

    (CFM)OUTSIDE AIR

    (CFM)ESP (WC)

    COOLINGHEATING MBH VOLTAGE MCA MOCP NOTES

    SENSIBLE MBH TOTAL MBH

    FTU101 LENNOX V22B007H4-3P 240 30 - 4.1 4.6 4.9 208/1 0.38 15 1,2,3,4,5

    FTU102 LENNOX V22B015H4-3P 360 - - 11.1 13.0 7.2 208/1 0.53 15 1,2,3,4,5

    FTU103a LENNOX VMDB007H4-3P 220 - 0.1" 1.5 1.7 3.6 208/1 1.25 15 1,2,3,4,5

    FTU103b LENNOX V22B012H4-3P 265 - - 6.1 6.9 5.8 208/1 0.53 15 1,2,3,4,5

    FTU110 LENNOX VMDB030H4-3P 1100 350 0.1" 14.7 19.1 16.9 208/1 5 15 1,2,3,4,5

    FTU111 LENNOX VMDB030H4-3P 1100 350 0.1" 14.1 20.7 17.5 208/1 5 15 1,2,3,4,5

    FTU112a LENNOX VMDB015H4-3P 600 150 0.1" 7.3 10.3 9.2 208/1 3.2 15 1,2,3,4,5

    FTU112b LENNOX VMDB036H4-3P 1200 350 0.1" 18.5 26.7 23.9 208/1 5 15 1,2,3,4,5

    FTU112c LENNOX VMDB030H4-3P 1200 350 0.1" 15.9 23.5 24.9 208/1 5 15 1,2,3,4,5

    FTU113 LENNOX VMDB024H4-3P 800 350 0.1" 10.3 15.2 13.9 208/1 3.2 15 1,2,3,4,5

    FTU117 LENNOX V22B007H4-3P 240 - - 3.8 4.4 4.4 208/1 0.38 15 1,2,3,4,5

    FTU118 LENNOX V22B009H4-3P 240 - - 4.2 5.8 3.8 208/1 0.38 15 1,2,3,4,5

    FTU125 LENNOX VWMB009H4-3P 275 - - 5.1 5.6 4.6 208/1 0.24 15 1,2,3,4,5

    FTU126 LENNOX VWMB007H4-3P 230 - - 4.5 5.3 4.6 208/1 0.23 15 1,2,3,4,5

    FTU-BE LENNOX V22B007H4-3P 320 - - 3.5 3.5 3.5 208/1 0.38 15 1,2,3,4,5

    FTU-BS LENNOX V22B007H4-3P 100 - - 2.1 2.1 2.3 208/1 0.38 15 1,2,3,4,5

    FTU-BW LENNOX V22B007H4-3P 320 - - 4.0 4.0 3.7 208/1 0.38 15 1,2,3,4,5

    FTU-CN01 LENNOX V22B012H4-3P 265 - - 6.7 7.9 3.9 208/1 0.53 15 1,2,3,4,5

    FTU-CN02 LENNOX V22B012H4-3P 265 - - 6.7 7.9 3.9 208/1 0.53 15 1,2,3,4,5

    FTU-CN03 LENNOX V22B012H4-3P 265 - - 6.7 7.9 3.9 208/1 0.53 15 1,2,3,4,5

    FTU-CN04 LENNOX V22B012H4-3P 265 - - 6.0 7.0 3.5 208/1 0.53 15 1,2,3,4,5

    FTU-CN05 LENNOX V22B012H4-3P 265 - - 6.0 7.0 3.5 208/1 0.53 15 1,2,3,4,5

    FTU-CN06 LENNOX V22B012H4-3P 265 - - 6.0 7.0 3.5 208/1 0.53 15 1,2,3,4,5

    FTU-CS01 LENNOX V22B007H4-3P 240 50 - 4.3 5.2 2.8 208/1 0.38 15 1,2,3,4,5

    FTU-CS02 LENNOX V22B007H4-3P 240 50 4.3 5.2 2.8 208/1 0.38 15 1,2,3,4,5

    FTU-CW LENNOX VWMB009H4-3P 230 - - 5.5 6.0 3.5 208/1 0.24 15 1,2,3,4,5

    FTU-GE LENNOX V22B007H4-3P 240 - - 3.6 3.6 3.6 208/1 0.38 15 1,2,3,4,5

    FTU-GS LENNOX V22B007H4-3P 100 - - 2.2 2.2 2.4 208/1 0.38 15 1,2,3,4,5

    FTU-GW LENNOX V22B007H4-3P 240 - - 3.9 3.9 3.6 208/1 0.38 15 1,2,3,4,5

    FTU-KIT LENNOX VVCB024H4-3P 800 - 0.1" 12.4 14.4 4.9 208/1 3.75 15 1,2,3,4,5

    FTU-MS LENNOX V22B007H4-3P 50 - - 0.8 0.8 1.0 208/1 0.38 15 1,2,3,4,5

    FTU-PPL LENNOX V22B009H4-3P 240 30 - 4.8 5.4 5.9 208/1 0.38 15 1,2,3,4,5

    FTU-VE LENNOX V22B007H4-3P 240 - - 4.8 4.8 4.4 208/1 0.38 15 1,2,3,4,5

    FTU-VN LENNOX V22B009H4-3P 240 - - 4.7 4.7 6.9 208/1 0.38 15 1,2,3,4,5

    FTU-VS LENNOX V22B007H4-3P 240 - - 5.0 5.0 5.6 208/1 0.38 15 1,2,3,4,5

    FTU-VW LENNOX V22B009H4-3P 240 - - 5.3 5.3 9.3 208/1 0.38 15 1,2,3,4,5

    FTU-WS LENNOX V22B007H4-3P 50 - - 0.9 0.9 1.0 208/1 0.38 15 1,2,3,4,5

    5. PROVIDE EQUIPMENT SUPPORT SYSTEM BY BIG FOOT, QUICK-SLING, OR APPROVED EQUAL. EQUIPMENT SUPPORT SYSTEM SHALL BE SIZED PER MANUFACTURER'S REQUIREMENTS.

    4. PROVIDE ACCESSORIES FOR LOW AMBIENT OPERATION.

    3. PROVIDE REFRIGERANT TWINNING KIT.

    2. PROVIDE ALL REFRIGERATION SYSTEM ACCESSORIES REQUIRED BY MANUFACTURER FOR GIVEN LINE SET ROUTING.

    1. PROVIDE REFRIGERANT LINE SET(S) SIZED PER MANUFACTURER'S RECOMMENDATIONS.

    NOTES:

    VRF - HEAT RECOVERY UNIT SCHEDULE

    TYPEMARK

    MANUFACTURER MODEL NUMBERAMBIENT TEMPERATURE

    TOTAL MBH HEATING MBH VOLTAGE MCA MOCP NOTESSUMMER DB/WB WINTER DB/WB

    HRU01 LENNOX (1) VRB120H4M-3Y 92/74 9 68.0 45.3 208/3 54 60 1,2,3,4,5

    HRU02 LENNOX (1) VRB120H4M-3Y 92/74 9 75.9 67.7 208/3 54 60 1,2,3,4,5

    HRU03 LENNOX(1) VRB120H4M-3Y,(1) VRB096H4M-3Y

    92/74 9 137.8 128.2 208/3 54,39 60,45 1,2,3,4,5

    3. PROVIDE BALL VALVES AT LIQUID AND SUCTION LINE FOR EACH BRANCH.

    2. PROVIDE ALL REFRIGERATION SYSTEM ACCESSORIES REQUIRED BY MANUFACTURER FOR GIVEN LINE SET ROUTING.

    1. PROVIDE REFRIGERANT LINE SET(S) SIZED PER MANUFACTURER'S RECOMMENDATIONS.

    NOTES:

    VRF - HEAT RECOVERY BOX SCHEDULE

    TYPEMARK

    MANUFACTURER MODEL NUMBER VOLTAGE MCA MOCP NOTES

    HRB01 LENNOX V8MSBB10-3P 208/1 0.95 15 1,2,3

    HRB02a LENNOX V8MSBB06-3P 208/1 0.63 15 1,2,3

    HRB02b LENNOX V8MSBB10-3P 208/1 0.95 15 1,2,3

    HRB03a LENNOX V8MSBB10-3P 208/1 0.95 15 1,2,3

    HRB03b LENNOX V8MSBB08-3P 208/1 0.75 15 1,2,3

    7. WHITE PLASTIC GRILLE.

    6. 9.5" ROOF CURB WITH DAMPER TRAY.

    5. BIRDSCREEN.

    4. HINGED BASE KIT.

    3. FAN SPEED CONTROLLER.

    2. GRAVITY BACKDRAFT DAMPER.

    1. FACTORY MOUNTED DISCONNECTING MEANS.

    NOTES:

    EXHAUST FAN SCHEDULE

    TYPEMARK

    MANUFACTURER MODEL NUMBER CFMEXTERNAL

    STATIC (WC)MOUNTING FINISH VOLTAGE

    MOTOR HP(WATTS)

    NOTES EQUIVALENTS

    EF-102 COOK 70C17DEC 150 0.1" ROOF STANDARD 120/1 1/20 1,2,3,4,5,6 -

    EF-103 COOK 70C17DEC 150 0.1" ROOF STANDARD 120/1 1/20 1,2,3,4,5,6 -

    EF-BE COOK 101C15D 450 0.1" ROOF STANDARD 120/1 1/8 1,2,3,4,5,6 -

    EF-BW COOK 101C15D 675 0.1" ROOF STANDARD 120/1 1/8 1,2,3,4,5,6 -

    EF-GE COOK 90C10DH 375 0.1" ROOF STANDARD 120/1 1/25 1,2,3,4,5,6 -

    EF-GW COOK 90C10DH 300 0.1" ROOF STANDARD 120/1 1/25 1,2,3,4,5,6 -

    17. DOUBLE WALL HOUSING CONSTRUCTION.

    16. BID ALTERNATE: 5-YEAR COMPRESSOR AND 25-YEAR HEAT EXCHANGER WARRANTY.

    15. BASE BID: 5-YEAR COMPRESSOR AND 10-YEAR HEAT EXCHANGER WARRANTY.

    14. CONDENSER HAIL GUARDS.

    13. NON-POWER CONVENIENCE RECEPTACLE.

    12. MODULATING HOT GAS REHEAT COIL.

    11. MODULATING GAS VALVE.

    10. ECM MOTORS ON BOTH SUPPLY AND EXHAUST FANS.

    9. CONTROLLER PROVIDED BY BAS CONTRACTOR.

    8. VARIABLE SPEED OR DIGITAL SCROLL COMPRESSOR FOR MODULATING COOLING.

    7. INTAKE AND EXHAUST HOOD.

    6. TIMED EXHAUST FROST CONTROL.

    5. DIRTY FILTER SENSOR

    4. WHEEL ROTATION SENSOR.

    3. 2" MERV 8 FILTERS ON SUPPLY AND EXHAUST AIR STREAMS.

    2. MOTORIZED EXHAUST AND OUTSIDE AIR DAMPERS.

    1. FACTORY MOUNTED DISCONNECTING MEANS.

    NOTES:

    DEDICATED OUTSIDE AIR UNIT SCHEDULE

    TYPEMARK

    MANUFACTURER MODEL NUMBERSUPPLY

    AIR (CFM)EXHAUSTAIR (CFM)

    ENERGY RECOVERY SUPPLY FAN EXHAUST FAN COOLING HEATING

    VOLTAGE MCA MOCP WEIGHT NOTESCOOLING HEATINGESP (WC) HP ESP (WC) HP

    EAT(DB/WB)

    SENSIBLE(MBH)

    TOTAL(MBH)

    LAT(DB/WB)

    ETA(DB/WB)

    INPUT(MBH)

    OUTPUT(MBH)

    LAT(DB/WB)SA (DB/WB) RA (DB/WB) OA (DB/WB) SA (DB/WB) RA (DB/WB) OA (DB/WB)

    DOA-N LENNOX LGH048H4E 650 - - - - - - - 1" 0.75 - - 92/74 25.2 45.2 75/62 9/9 150 120 70/50 208/3 25 35 6111,2,3,5,7,8,9,10,11,12,13,14,15,

    16,17

    DOA-S MODINEMPR07BE1B1ALTA4

    D2GHD2000 1600 80/66 75/62 92/74 54/44 70/50 9/9 1" 3 0.75" 7.75 - 57.1 92.3 75/62 9/9 200 162 70/50 208/3 57.3 80.0 4567 1 THRU 17

    Revision No. Description Date

    1 Addendum #01 03-30-2020

    4. PROVIDE PLASTER FRAME ADAPTOR FOR LAYIN INTO GYPSUM CEILING.

    3. GRILLE/DIFFUSER SHALL BE FIELD PAINTABLE.

    2. DIFFUSER DISCHARGE AIR PATTERN SHALL BE 4-WAY UNLESS NOTED BY DIRECTION ON PLANS.

    1. GRILLE/DIFFUSER NECK SHALL BE SAME SIZE AS BRANCH DUCTWORK UNLESS NOTED OTHERWISE ON PLAN.

    NOTES:

    AIR DEVICE SCHEDULE

    TYPEMARK

    SYTEM TYPE MANUFACTURERMODEL

    NUMBERMODULE

    SIZEFRAME FINISH DAMPER

    MAX NCRATING

    THROW(FT)

    EXTERNALSTATIC (WC)

    NOTES EQUIVALENTS

    E01 EXHAUST KRUEGER 6690 SEE PLAN LAY-IN WHITE - 30 - 0.1" 1,3 TITUS

    E02 EXHAUST KRUEGER EGC5 SEE PLAN SURFACE WHITE - 30 - 0.1" 1,3 TITUS

    R01 RETURN KRUEGER 6690 SEE PLAN LAY-IN WHITE - 30 - 0.1" 1,3 TITUS

    S01 SUPPLY KRUEGER 5DMGDR SEE PLAN DUCT WHITE OBD 30 - 0.1" 1,3 TITUS

    S02 SUPPLY KRUEGER PLQ SEE PLAN LAY-IN WHITE - 30 - 0.1" 1,2,3 TITUS

    S03 SUPPLY KRUEGER 880 SEE PLAN SURFACE WHITE OBD 30 - 0.1" 1,3 TITUS

    1

    1

    1

  • F

    F

    T

    LP-A

    26.01

    MDP-1

    26.01

    LP-D

    26.01

    FTU-VW

    RTU123

    RTU124 RTU122

    RTU121FTU-CN01

    FTU-BW FTU-GW

    FTU-CW

    DP-1

    26.01

    26.01

    MEA

    EM-126.01

    MEB

    LP-B

    26.01

    26.01

    LP-C

    26.01

    LP-KIT

    26.01

    26.01

    LP-F

    26.03

    26.03

    26.03

    26.03

    RTU119

    26.03

    RTU115 DOA-N

    RTU100

    RTU104

    RTU114

    RTU106

    RTU105

    RTU103

    WPGF

    WPGF WP

    GF

    WPGF WP

    GF

    26.04

    26.04

    26.04

    26.04WPGF

    26.05

    26.04 26.04

    26.07

    26.06

    WPGF

    WPGF

    WPGF

    26.06

    WPGF

    WPGF

    WPGF

    26.04

    26.04

    26.04

    26.04

    26.04

    26.04

    26.09

    26.08

    Classroom

    123

    Classroom

    121

    Classroom

    119

    Classroom

    124

    Vestibule West

    Classroom

    122

    Custodial West

    007Multi-Purpose

    Room

    114

    Classroom

    115

    Principal

    Reception

    101

    Vestibule North

    Classroom

    100

    Workroom

    102

    Classroom

    104

    Kindergarden

    103

    CorridorKindergarden

    Classroom

    105

    Classroom

    106

    Boys East

    Office

    126

    26.10

    DD

    RT28.02

    28.01

    26.11

    EF-BW EF-GW

    26.12

    LP-VRF-N

    HRB01

    FTU-CN02

    1,3 LP-VRF-N

    DS01

    HRU01

    2,4,6LP-VRF-N

    5 LP-VRF-N

    26.13

    FTU-KIT

    7,9 LP-VRF-N

    FTU118 FTU117

    FTU-CN03

    FTU-PPL FTU101

    FTU-VN

    FTU-CN04

    C1

    8,10LP-VRF-N

    FTU102

    11,13,15LP-VRF-N

    DS02HRU02

    HRB02a

    HRB02b

    FTU-GEFTU-CN05FTU103b

    FTU103a

    FTU125

    EF-GE

    12,14LP-VRF-N

    16 LP-VRF-N

    26.15

    EF-103

    EF-BEFTU-BE

    FTU126

    26.15

    26.15

    3,5 LP-VRF-S

    26.11

    26.11

    26.11

    26.11

    26.02

    26.11

    26.11 26.11

    26.11

    26.11

    26.11 26.11

    26.11

    Health Room

    117

    ISS

    118

    C2

    17,19,21LP-VRF-N

    26.11

    26.11

    26.11

    26.11

    26.1126.11

    26.11

    26.11

    26.11

    26.11

    26.11

    EF-102

    18 LP-VRF-N

    A

    28.03

    1

    27.01

    1

    1

    1

    1

    GRADE

    EXISTING UTILTIY SERVICE SHALL REMAIN. NO MODIFICATIONS REQUIRED. SHOWN

    FOR REFERANCE ONLY

    1. JUNCTION BOX/CABINET(S) SHALL BE SIZED PER NEC REQUIREMENTS, AND BEAR NEMA ENCLOSURE RATING

    FOR APPLICABLE INSTALLATION ENVIRONMENT.

    2. EXISTING CONDITIONS INCLUDING BUT NOT LIMITED TO SIZES, RATINGS, LOCATIONS, AND DIMENSIONS SHALL

    BE FIELD VERIFIED.

    GENERAL NOTES:

    EXISTING UTILITY TRANSFORMER SHALL REMAIN. NO MODIFICATIONS REQUIRED.

    SHOWN FOR REFERANCE ONLY

    EXISTING ELECTRICAL METER SHALL REMAIN

    EXISTING 1200-AMP DISCONNECT TO REMAIN

    EXISTING 400-AMP DISCONNECT TO REMAIN

    MEBDS-1 DS-2

    EXISTING 400-AMP SQUARE D NQOD 3-PHASE,

    4-WIRE PANELBOARD

    MDP-1

    EXISTING 1200-AMP SQUARE D HCRU 3-PHASE,

    4-WIRE PANELBOARD

    DP-1LP-D

    EXISTING 800-AMP SQUARE D HCM 1-PHASE,

    3-WIRE PANELBOARD

    EXISTING 125-AMP FEED TO SQUARE D QO 1-PHASE, 3-

    WIRE PANELBOARD

    EXISTING 400-AMP SQUARE D NQOD 3-PHASE,

    4-WIRE PANELBOARD

    MEA EM-1

    EXISTING 150-AMP FEED TO SQUARE D NQOD 3-PHASE, 4-

    WIRE PANELBOARD

    LP-A LP-B LP-C

    EXISTING 150-AMP FEED TO SQUARE D NQOD 1-PHASE, 3-

    WIRE PANELBOARD

    EXISTING 150-AMP FEED TO SQUARE D QO 1-PHASE, 3-WIRE

    PANELBOARD

    EXISTING 150-AMP FEED TO SQUARE D QO 1-PHASE, 3-WIRE

    PANELBOARD

    PP1 LP1 LP1 LP-VRF-S

    EXISTING 150-AMP FEED TO SQUARE D NQ 3-PHASE, 4-WIRE

    PANELBOARD

    EXISTING 225-AMP FEED TO SQUARE D NQOD 1-PHASE, 3-

    WIRE PANELBOARD

    EXISTING 225-AMP FEED TO SQUARE D QO 1-PHASE, 3-WIRE

    PANELBOARD

    PROVIDE NEW 3-POLE 225-AMP CIRCUIT BREAKER

    (4) #4/0 AND (1) #4 GROUND IN 2.5" CONDUIT. CONFIRM ROUTING WITH

    ENGINEER PRIOR TO INSTALLING

    REFER TO SCHEDULE FOR REQUIREMENTS

    LP-VRF-N

    REFER TO SCHEDULE FOR REQUIREMENTS

    STA

    TEOF M ISS

    OURI

    P

    NUMBER

    ROF

    ESSIONAL E

    NG

    I NEER

    JACOB

    ADAM NELSON

    PE-2009018758

    In the event the client consents to, allows, authorizes or approves of

    changes to any plans, specifications or other construction documents,

    and these changes are not approved in writing by the design

    professional, the client recognizes that such changes and the results

    thereof are not the responsibility of the design professional. Therefore, the client agrees to release the design professional from any liability

    arising from the construction, use or result of such changes. In addition,

    the client agrees to the fullest extent permitted by law, to indemnify and

    hold the design professional harmless from any damage, liability or cost

    (including reasonable attorney's fees and costs of defense) arising from

    such changes.

    The personal seal of the registered Engineer shall be the legal equivalent

    of his signature whenever & wherever used, and the owner of the seal shall authenticate this sheet and the specification sections pertaining to

    this sheet. Responsibility shall be disclaimed for all other plans,

    specifications, estimates, reports or other documents or instruments

    relating to or intended to be used for any part or parts of the project.

    SPECIAL NOTICES

    DATE:

    PROJECT #:

    DRAWN:

    Drawing No.

    Missouri State Certificate of Authority #E-2016000752

    © Copyright 2020 - True Engineering Group LLC

    Engineer of RecordJacob Adam Nelson PE

    PE-2009018758

    True Engineering Group LLC

    3/3

    0/2

    02

    0 3

    :57:4

    6 P

    M

    Springfield

    Public

    Sch

    ools

    3014 W

    Calh

    oun S

    t.Springfield

    , M

    O 6

    5802

    Bis

    sett

    Ele

    menta

    ry H

    VAC U

    pgra

    des

    JK

    03/16/2020

    SPS-2001

    E100APOWER PLAN - AREA A

    03/16/2020

    KEYNOTE LEGENDKEY

    VALUEKEYNOTE TEXT

    26.01 EXISTING ELECTRICAL PANEL SHALL REMAIN.

    26.02 PROVIDE NEW ELECTRICAL PANEL. REFER TO ELECTRICAL RISER.

    26.03 RECONNECT TO EXISTING CONDUIT AND CONDUCTORS TO NEWROOFTOP UNIT. REVISE CIRCUIT BREAKER IN PANELBOARD MEA TOBE 35-AMP 3-POLE.

    26.04 PROVIDE ELECTRICAL CONNECTION TO NON-POWERED GFICRECEPTACLE PROVIDED WITH UNIT.

    26.05 CIRCUIT TO EXISTING ROOFTOP UNIT MAINTENANCE RECEPTACLE INPANELBOARD MEA.

    26.06 RECONNECT TO EXISTING CONDUIT AND CONDUCTORS TO NEWROOFTOP UNIT. REVISE CIRCUIT BREAKER IN PANELBOARD MEB TOBE 35-AMP 3-POLE.

    26.07 RECONNECT TO EXISTING CONDUIT AND CONDUCTORS TO NEWROOFTOP UNIT. REVISE CIRCUIT BREAKER IN PANELBOARD MEA TOBE 30-AMP 3-POLE.

    26.08 CIRCUIT TO EXISTING ROOFTOP UNIT MAINTENANCE RECEPTACLE INPANELBOARD MEB.

    26.09 CIRCUIT TO PANELBOARD MEB. PROVIDE NEW 1-POLE 20-AMPCIRCUIT BREAKER.

    26.10 RECONNECT TO EXISTING CONDUIT AND CONDUCTORS TO NEWROOFTOP UNIT. REVISE CIRCUIT BREAKER IN PANELBOARD MDP-1TO BE 80-AM 3-POLE CIRCUIT BREAKER.

    26.11 PROVIDE 2-POLE 20-AMP SWITCH FOR DISCONNECT TO VRFEQUIPMENT.

    26.12 PROVIDE POWER AND DATA FOR VRF CONTROLLER.

    26.13 CIRCUIT EXHAUST FANS THROUGH RELAY TO BE CONTROLLED BY BASCONTRACTOR. COORDINATE WITH CONTROLS CONTRACTOR.

    26.15 CIRCUIT NEW EXHAUST FAN TO EXISTING FAN CIRCUIT. PROVIDERELAY TO CONTROL EXHAUST FAN THROUGH BAS SYSTEM.COORDINATE WITH CONTROLS CONTRACTORS.

    27.01 LOCATION OF EXISTING IT RACK. ROUTE NETWORK CABLE FOR VRFCONTROLLER BACK TO PATCH PANEL. COORDINATE CONNECTIONWITH IT DEPARTMENT.

    28.01 PROVIDE DUCT SMOKE DETECTOR IN RETURN.

    28.02 PROVIDE REMOTE TEST STATION FOR DUCT SMOKE DETECTOR.

    28.03 LOCATION OF EXISTING SIMPLEX 4006 FIRE ALARM PANEL.

    3/32" = 1'-0"1HVAC POWER PLAN - AREA A

    NOT TO SCALE2 ELECTRICAL RISER

    CONDUIT AND CONDUCTORSKEY

    VALUESIZE AND QUANTITY

    C1 (3) #6 AND (1) #10 GROUND IN 1" CONDUIT.

    C2 (3) #8 AND (1) #10 GROUND IN 0.75" CONDUIT.

    KEY PLAN

    A

    Revision No. Description Date

    1 Addendum #01 03-30-2020

  • EXISTING AREA HAS LAY-IN CEILING AND TROFFER LIGHTS. REMOVE AND REINSTALL LIGHTS AND GRIDS AS REQUIRED FOR NEW

    INSTALLATION. FIELD VERIFY EXISTING CONDITIONS

    EXISTING LAYIN GRID SHALL REMAIN. REMOVE AS REQUIRED TO

    ROUTE REFRIGERANT AND CONDENSATE LINES

    AREAS NOT HATCHED IN GRAY ARE CONSIDERED EXPOSED FOR INSULATION

    AND ACCESSIBILITY

    STA

    TEOF M ISS

    OURI

    P

    NUMBER

    ROF

    ESSIONAL E

    NG

    I NEER

    JACOB

    ADAM NELSON

    PE-2009018758

    In the event the client consents to, allows, authorizes or approves of

    changes to any plans, specifications or other construction documents,

    and these changes are not approved in writing by the design

    professional, the client recognizes that such changes and the results

    thereof are not the responsibility of the design professional. Therefore, the client agrees to release the design professional from any liability

    arising from the construction, use or result of such changes. In addition,

    the client agrees to the fullest extent permitted by law, to indemnify and

    hold the design professional harmless from any damage, liability or cost

    (including reasonable attorney's fees and costs of defense) arising from

    such changes.

    The personal seal of the registered Engineer shall be the legal equivalent

    of his signature whenever & wherever used, and the owner of the seal shall authenticate this sheet and the specification sections pertaining to

    this sheet. Responsibility shall be disclaimed for all other plans,

    specifications, estimates, reports or other documents or instruments

    relating to or intended to be used for any part or parts of the project.

    SPECIAL NOTICES

    DATE:

    PROJECT #:

    DRAWN:

    Drawing No.

    Missouri State Certificate of Authority #E-2016000752

    © Copyright 2020 - True Engineering Group LLC

    Engineer of RecordJacob Adam Nelson PE

    PE-2009018758

    True Engineering Group LLC

    3/3

    0/2

    02

    0 3

    :57:4

    6 P

    M

    Springfield

    Public

    Sch

    ools

    3014 W

    Calh

    oun S

    t.Springfield

    , M

    O 6

    5802

    Bis

    sett

    Ele

    menta

    ry H

    VAC U

    pgra

    des

    Author

    03/16/2020

    SPS-2001

    E200ELECTRICAL DETAILS

    03/16/2020

    Revision No. Description Date

    1 Addendum #01 03-30-2020

    1" = 20'-0"1REFLECTED CEILING PLAN FOR COORDINATION

    2. COORDINATE INSTALLATION HEIGHTS WITH OWNER AND ELECTRICAL CONTRACTOR PRIOR TO INSTALLING.

    1. REFER TO SPECFICATIONS FOR ADDITIONAL REQUIREMENTS.

    NOTES:

    COMMUNICATIONS DEVICE SCHEDULE

    TYPEMARK

    DESCRIPTION FACEPLATE SIZEJACK

    HEIGHT CONDUIT SIZE CABLE NOTESQUANTITY MODEL NUMBER(S) COLOR

    A VRF CONTROLLER HUBBELL-ISB10WP 1 (1) HXJ6B BLUE - 1"(1) BERK-TEK

    101362261,2,3

    ADD FULL SIZE SHEET

    1

    01 - SPS - 2001 Biessett Elementary HVAC Upgrade AD01 2020-03-30_002 - SPS - 2001 - Bissett - Pre-Bid Conferance - 03-24-20_0Introductions:Project Description: Summary Project Description: The project is comprised of replacing and upgrading the existing HVAC system at Bissett Elementary School in Springfield, Missouri.  The HVAC system scope includes replacement packaged rooftop units and new VRF systems.  The building automation system will also be replaced.

    Bid Requirements and Procedures:Project Administration:Job Conditions and Special Issues:Questions/Clarifications:

    03 - Pre Bid Sign In Sheet_0WorksheetsSheet1

    04 - Bid Tab_0WorksheetsSheet1

    05 21 00-BSD-Allowances 3-30-2020 2-50-32 PM06 - 09 91 23-BSD-Interior Painting_0PART 1 GENERAL1.01 SECTION INCLUDESA. Surface preparation.B. Scope: Finish interior surfaces exposed to view, unless fully factory-finished and unless otherwise indicated.C. Do Not Paint or Finish the Following Items:

    1.02 REFERENCE STANDARDSA. MPI (APSM) - Master Painters Institute Architectural Painting Specification Manual Current Edition.B. SSPC-SP 1 - Solvent Cleaning 2015, with Editorial Revision (2016).C. SSPC-SP 6 - Commercial Blast Cleaning 2007.

    1.03 SUBMITTALSA. See Section 01 30 00 - Administrative Requirements, for submittal procedures.B. Product Data: Provide complete list of products to be used, with the following information for each:

    PART 2 - PRODUCTS2.1 MANUFACTURERSA. Basis-of-Design Product: Subject to compliance with requirements, provide Sherwin-Williams Company (The); or a comparable product by one of the following:B. Products: Subject to compliance with requirements, provide product listed in the Interior Painting Schedule for the paint category indicated.

    2.2 PAINT, GENERALA. MPI Standards: Products shall comply with MPI standards indicated and shall be listed in its "MPI Approved Products Lists."B. Material Compatibility:C. Colors: As selected by Architect from manufacturer's full range.

    PART 3 - EXECUTION3.1 EXAMINATIONA. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work.B. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows:C. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers.D. Proceed with coating application only after unsatisfactory conditions have been corrected.

    3.2 PREPARATIONA. Comply with manufacturer's written instructions and recommendations in "MPI Architectural Painting Specification Manual" applicable to substrates and paint systems indicated.B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and painting.

    3.3 APPLICATIONA. Apply paints according to manufacturer's written instructions and recommendations in "MPI Architectural Painting Specification Manual."B. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks.

    3.4 INTERIOR PAINTING SCHEDULEA. Concrete Substrates, Nontraffic Surfaces:B. Concrete Substrates, Traffic Surfaces:C. CMU Substrates:D. Gypsum Board Substrates - Ceilings:A. Gypsum Board Substrates - Walls:B. Steel Substrates:

    3.5 paint schedule:C. Exposed double wall ductwork in Kitchen.D. Walls infilled from removed ductwork.E. Caps on existing air devices that are removed.F. Color determined by owner

    END OF SECTION

    07 - M400 - MECHANICAL SCHEDULES - AD01SheetsE100A - POWER PLAN - AREA AE200 - ELECTRICAL DETAILSM400 - MECHANICAL SCHEDULES

    08 - E100A - POWER PLAN - AREA A - AD01SheetsE100A - POWER PLAN - AREA AE200 - ELECTRICAL DETAILSM400 - MECHANICAL SCHEDULES

    09 - E200 - ELECTRICAL DETAILS - AD01SheetsE100A - POWER PLAN - AREA AE200 - ELECTRICAL DETAILSM400 - MECHANICAL SCHEDULES