AccuFlex™ VRF Application Training - HVAC · PDF fileNote each column’s heading...

55
AccuFlex™ VRF Application Training May 2015

Transcript of AccuFlex™ VRF Application Training - HVAC · PDF fileNote each column’s heading...

AccuFlex™ VRF Application Training

May 2015

1

Pre‐Design Checklist

Accurate Room/Zone Load Calculation

Building Blueprint or Drawing with Scale

Jobsite Voltage

Block Load Method

Room/Zone Load Method

Peak Zone Load Method

Load Calculations

2

Front Offices

8 Tons

West Office

4 Tons

East Office

4 Tons

• Block load = Room/Zone Load

Room/Zone LoadBlock Load

4 Tons 4 Tons

4 Tons 4 Tons

Mini‐Split Application

3

West Office

4 Tons

East Office

2 Tons

West Office

2 Tons

East Office

4 Tons

• East Office Peak Zone Load = 4 Tons• West Office Peak Zone Load = 4 Tons

6 Tons

Peak Room/Zone Load

• Highest Block Load  =

4 Tons 4 Tons

6 Tons

AccuFlex™ VRF Application

Combination Ratio(Indoor / Outdoor)

8 Tons ÷ 6 Tons = 1.33

4

Highest Block Load occurring at hour 17…

236,067 Btu/h

Peak Zone Load regardless of thetime of day…

240,117 Btu/h

2249871080

2249871080

Size the outdoor unit to the highest block load

Size the indoor units to each peak zone load

• Total Peak Zone Load ÷ Highest Block Load = Combination Ratio

• 240,117 ÷ 236,067 = 1.02 Cooling Combination Ratio

5

Elevation Drawings

Floor Plans

Blueprints & Drawings

VRF Training Example 1

6

Always download all available “Updates”

Click “Sales” to begin

Click “New” to start the design

7

Enter the project name

Select the design state then the city

Enter the customer’s information

Enter your information as the designer

Click “OK”

Double‐click in a cell to change it 

①Add Floors to 

Building

②Add Rooms 

&Loads 

③Add Indoor 

Units

④Add Indoor Accessories

⑤ Add Outdoor Units

⑥Locate Units In Building

8

①Add Floors to 

Building

Click “Edit”

Note each column’s heading when entering new floors

Additional floors are entered at the bottom of each column

9

Click the blank cell at the bottom of the column and enter the  

quantity of floors in the Building

Floor Height

CeilingHeight

Press TAB twice then enter the floor height.

Press TAB then enter the ceiling height.

Press ENTER

Click any cell to change the data

Note the total number of floors have been added

When warned, click “OK” to confirm the need to redo all 

outdoor unit checks

10

To add a basement, enter ‐1 in the floor cell, press TAB to enter the heights, then press ENTER

After all floors are added or edited, click “Done”

To delete a floor, click to the the left of the floor on the arrow      then press DELETE

②Add Rooms 

&Loads 

11

Double‐click the blank cell under “Name” then enter the first room (zone) name

Press TAB then enter the total cooling load

Press TAB then enter the sensible cooling load

Press TAB then enter the total heating load

Double‐click the next  blank cell in the room column to enter the 

next room

Enter all of the remaining rooms and loads in the building

12

To delete a room, select the name then 

press DELETE Click “Yes” to confirm deleting the room

Double‐Click column line to see entire column content

③Add Indoor 

Units

13

VRF Training Example 1VRF Training Example 1

To start the process of selecting the indoor units, select the first room name

14

The available sizes of the style selected 

above are listed below

The different styles of indoor units are listed in the top section

“Qty” indicates the quantity of this model that are needed to satisfy the loads

Click the style of indoor unit you 

want for the room

Click the size of indoor unit with the quantity needed for the room

Click “Add”

If you select a model with a “Qty” of 2, then 2 units will be added 

to the room

To manually change the quantity, click the default number, then press BACKSPACEand then enter the 

new quantity

15

The indoor unit is now shown with the room

A yellow checkmark indicates an accessory has automatically been added, 

in this case a cassette 4 way panel

Click the next room

Click the styleof indoor unit

Click “Add”

Click the size &quantity of unit

16

Click the styleof indoor unit

Click “Add”

Click the size &quantity of unit Click the 

next room

Click the next room

Click the styleof indoor unit

Click “Add”

Click the size of unit with a quantity of 2

17

Note that 2 units were added to the room

Click the next room

Click the styleof indoor unit

18

Pause the mouse over the unit to see the 

entire model number 

For high wall indoor units, there appears to 

be 2 of each size

Models ending in “B” need an external EEV. Models ending in “C” come with a factory 

installed EEV

“High Wall” style has been selected

Click “Add”

Click the size of unit, with factory installed EEV and with a quantity of 2

19

Indoor units can be added without room or load information

You will need to manually confirm that units added without load information 

satisfy the required capacities

To delete an indoor unit, click the “Model Name” then press DELETE

Click “Yes” to confirm deleting the unit

20

Then click the indoor unit

To see the specifications of an indoor unit, click “Property” tab

To see all the indoor unitinformation click “Auto Hide” 

Click the “Building Management” tab to return to the building

21

Click any tab to see the information again

You can also “Auto Hide”     the “Add ID Units” section

Click “Auto Hide”      to unhide the section

22

④Add Indoor Accessories

VRF Training Example 1VRF Training Example 1

23

Select the unit you want to add accessories to manually

The yellow checkmarks indicate some accessories were automatically selected

Click the “Accessory” tab

Click the boxes to add accessories

… or click, hold and drag column line to move it

Double‐Click column line to see entire column content …

24

Click the next unit

Click the boxes  for the accessories

Add all of the additional accessories

Note “Auto Hide” applied

No controller was needed for second indoor unit in 

these rooms

25

⑤ Select Outdoor Units

Note “Auto Hide” was turned off

Note “Auto Hide” applied

26

Click the first unit to be connected to the outdoor unit

Press and hold CTRL then click the other indoor units 

connected to the outdoor unit

Pressing SHIFT in place of CTRL will select all units up to the second selection 

Once all the indoor units are selected, click the group and hold

Drag the group down to the “Outdoor List” and release 

the mouse button

27

Select “VRF” for 3 Phase units or “Mini‐VRF” for 1 Phase units

For 3 Phase units only, select “Heat Recovery” or “Heat Pump”

Change the outdoor unit name

Set the “Combination Ratio” to match your design

28

Size the outdoor unit to the highest block load

Size the indoor units to each peak zone load

Non‐Hourly Zone Load CalculationZone Load = Block Load

Combination Ratio = 1.00

To remove an indoor unit from this system, click the 

model then the – minus sign

Click “OK”

Click the outdoor model for the project

29

The outdoor unit is now shown

A green checkmark indicates the indoor unit is attached to the outdoor unit

Click “Yes” to confirm deleting the unit

To delete an outdoor unit, click the “Model Name” then press DELETE

30

⑥Locate Units In Building

Drag the room over to the floor where the unit it 

located and release the mouse button

Click a room and hold

31

Continue locating the rooms and units in the building

Also, the room and unit now appear on the floor

Note the room and unit are blue indicating they 

are located in the building

Never drag just the unit to the floor, always drag the room

Click the outdoor unit and hold

Drag the outdoor unit over to the 

roof or floor where the unit it located

32

Select the “Piping” tab to begin laying out the refrigerant piping

A green checkmark means the piping for the system can now be designed

Note the outdoor unit now appears

Note that “Auto” is checked

“Auto” will create a piping system automatically for 

heat pump systems

33

VRF Training Example 1

Empty boxes indicate a component can be located here

Select and drag a “Branch Joint” or “Header” to the empty box

Check “Manual” to lay out the piping according to the project

34

Magnifying glass features are also available

Use the mouse’s thumbwheel to increase ordecrease the drawing Size

Press & hold the mouse’s thumbwheel to move the drawing around the page

Right‐click in the empty box to see the available indoor units

Select the indoor unit for this location

35

Note that the unit now appears on the diagram

Select additional components until all the indoor units are in place

When designing a Heat Recovery system, a “Mode Change Unit” (MCU) will be available to select

When designing a Heat Recovery system, a “Mode Change Unit” (MCU) will be 

available to select

36

To see the specifications of any unit, click the unit

Click and hold the left border then drag it to enlarge the section

37

Right‐click on a component to remove it from the drawing

Click a section of pipe which then turns red

Click the “Actual Piping Length” box and enter the length

Click the “No. of Elbows” box and enter the quantity

Actual Length/Equivalent Length/Elbows(“Equivalent Length” & “Pipe Size” calculated during “System Check”

38

Click each section of pipe and enter the length and elbows

After all lengths and elbows are entered, click “System Check” to check the piping

Review all of the system piping checks. 

Note the additional refrigerant charge

Double‐click or drag the column line to expand it

39

An “[ERROR] System check failure” warning appears if the piping is incorrect

Review the “ERROR” that must be corrected 

Click the  to return to the piping diagram

40

After all corrections are made, click “System Check” 

to recheck the piping

After confirming a successful system check, click “Capacity Correction”

41

Note the outdoor unit “Simulated 

Capacity”

Click“Capacity Correction”

Note the indoor unit “Simulated 

Capacity”

Select “OK”

Click the “Indoor Unit” tab to review the simulated capacities

42

Note “Auto Hide” applied

Note “Auto Hide” applied

You may need to modify the indoor unit size if the simulated capacity does not satisfy the room Load

Click the “Model Name” of the unit you want to modify

Click the style of the unit

Click “Modify”

Click the size of the unit

43

Since the system capacity has changed, reselect the outdoor unit that meets the new load

Click “OK”

If you forget to reselect “Heat Pump” you will have to redo the piping layout

Note new indoor unit size

Click “Piping” to rerun “System Check”

44

Click “System Check” to recheck the piping

After confirming a successful system check, click “Capacity Correction”

To print the piping diagram, click “Print”

45

Note the updated outdoor unit “Simulated Capacity”

Click“Capacity Correction”

Note the updated indoor unit “Simulated Capacity”

Select “OK”

Confirm the updated simulated capacities satisfy the room loads

46

Note the amp draw and circuit protection is listed for each circuit

The amp draw of the field installed electric heat option in 4TVM air 

handlers are not included

Click the “Wiring” tab to view a simple system wiring diagram

Click the “Breaker Name” or “Breaker Size” box to edit the information

Click a fuse or breaker

47

Click an indoor unit to view the specifications or edit the addressing

Click the “TEXT” box to add text to indoor units or MCUs

Click an empty box to view optional components

Although outdoor units have a terminal block, click to add one with all central controllers

Click the “Controller” tab

48

Click the yellow dot to connect a controller to the R1/R2 control layer

Click a central controller to add it to the system

Note the yellow dot turns red indicating a pending connection

Right‐click on a component to 

remove or move it

49

Click “System Check” to check the control system

Click “OK”

Any controller errors will appear at the bottom

Select any tab to review or update the design

50

When the design is complete, click “Save As”

Save the project file to your choice of location

Click “Report” to save a complete project report

Rename the report to match the project, then click “Save”

51

Refrigerant Concentration Limit (RCL)  26 lbs./1,000 ft3 0.026 lbs./ft3

52

• Total System Charge = 39.308 lbs.

• 39.308 ÷ 0.026 = 1512 ft3 minimum volume

• 1512 ft3 x 12 ft. = 126 ft2 minimum square feet

• Smallest Room = 120 ft2

• Solutions?• Possibly louvers, transfer grilles, undercut doors –need engineer/inspector approval

• 2 Smaller Systems in Place of 1

Refrigerant Concentration Limit (RCL)  26 lbs./1,000 ft3 0.026 lbs./ft3

Thank You for AttendingAmerican Standard AccuFlex™

Application Training

AccuFlex™ VRF

Massachusetts Default Design Conditions

\

New Hampshire Default Design Conditions

Rhode Island Default Design Conditions