A Quick GuideTotal Cost of Ownership calculator tool (ver. 1.1)

ABB Transformers, 2015

Page 2: A Quick Guide Total Cost of Ownership calculator tool (ver. 1.1) ABB Transformers, 2015.

© ABB Group February 6, 2015 | Slide 2

TCO Tool / A Quick Guide

Page 3: A Quick Guide Total Cost of Ownership calculator tool (ver. 1.1) ABB Transformers, 2015.

© ABB Group February 6, 2015 | Slide 3

TCO Tool / A Quick GuidePre-word 1

Background of TCO and TCO tool

The use of Total Cost of Ownership –method (also known as Total Ownership Cost –method) allows manufacturers to tailor the design to the unique economic situation of each transformer user, and allows the user to evaluate multiple designs in order to find out the optimal solution for his need

The easy-to-use ABB Transformer TCO Tool supports customers to determine, based on their own situation and future scenario, the right loss capitalisation values to be used in their inquiry to be passed to the manufacturers

The tool also helps in comparing different alternative transformer offers, calculates the monetary savings and evaluates the environmental impact and therefore supports the related decision making and increases the awareness

Current version 1.1. supports in addition to English language also Chinese, German, French and Spanish languages

Page 4: A Quick Guide Total Cost of Ownership calculator tool (ver. 1.1) ABB Transformers, 2015.

© ABB Group February 6, 2015 | Slide 4

TCO Tool / A Quick GuidePre-word 2

TCO tool is an universal easy-to-use tool for

Determining the transformer loss capitalization values (”A” and ”B” factors)

Comparing transformers with different first cost and loss values from the following aspects

Total cost of ownership with payback time on marginal cost

Consumption of energy

CO2 emission impact (in kg of CO2) with analogue to the number of trees needed to compensate the extra emissions caused by the trafo with lower efficiency

Calculation formulas are based on IEC 60076-20 (current draft) on applicable parts (the results are fully applicable with ”IEEE” transformers as well)

Page 5: A Quick Guide Total Cost of Ownership calculator tool (ver. 1.1) ABB Transformers, 2015.

© ABB Group February 6, 2015 | Slide 5

TCO Tool / A Quick GuideInterface / inputs 1

i-buttons for help

Page 6: A Quick Guide Total Cost of Ownership calculator tool (ver. 1.1) ABB Transformers, 2015.

© ABB Group February 6, 2015 | Slide 6

TCO Tool / A Quick GuideInterface / inputs 2

i-buttons for help

Page 7: A Quick Guide Total Cost of Ownership calculator tool (ver. 1.1) ABB Transformers, 2015.

© ABB Group February 6, 2015 | Slide 7

TCO Tool / A Quick GuideInterface / comparison and results

Peak efficiency index (IEC) is the highest efficiency that the transformer can reach at an optima loading point. It is calculated based on the IEC definition of efficiency.

Total cost of ownership is the sum of the initial purchase cost and the net present value of the cost of losses during the lifetime. In this calculation, differences in other lifecycle cost components such as installation, maintenance, possible out-time and decommission costs are not included.

Total lifetime savings during the lifetime of the transformer in selected currency when comparing the “Lowest total cost” and the transformer x.

Payback time in years for the marginal investment on the higher efficiency when comparing the “Lowest total cost” and the transformer x. Simple payback calculation method.

Energy savings per year and total – The amount of energy saved when selecting the “Lowest total cost” instead of transformer x.

CO2 emission reduction per year – The amount of CO2 emission avoided in tons when selecting the “Lowest total cost” instead of transformer x. Calculated using the global average CO2 emission of 489 g per kWh generated.

CO2 absorption capability of trees – The number of trees needed to offset the higher CO2 emissions caused by a transformer with lower efficiency based on the average annual absorption capability of 22 kg of CO2 by a single tree.

Page 8: A Quick Guide Total Cost of Ownership calculator tool (ver. 1.1) ABB Transformers, 2015.

© ABB Group February 6, 2015 | Slide 8

TCO Tool / A Quick GuideTCO Tool / interface / basic reporting (pdf print)

Page 9: A Quick Guide Total Cost of Ownership calculator tool (ver. 1.1) ABB Transformers, 2015.

© ABB Group February 6, 2015 | Slide 9

TCO Tool / A Quick GuideNotes and remarks

Cooling losses

Cooling losses of a transformer equal the power consumption of the cooling equipment of the transformer. In case of cooling with natural oil and air flow (ONAN), the cooling losses are zero due to the fact that no additional power for pumps or fans is needed

With transformers with forced oil flow (OFAF, ODAF or OFWF) the pumps for oil are usually energised at no load condition of the unit. Therefore, for a typical case the cooling losses at no load () for those transformers equal the power consumption of the oil pumps

Page 10: A Quick Guide Total Cost of Ownership calculator tool (ver. 1.1) ABB Transformers, 2015.