Use this manual for circuit board 4602-010 Revision A or higher.
WARNING
MOVINGGATECANCAUSE
Operate gateonly when gate area is in sight
and freeof people and obstructions.
Do notallow children to play in gate area
or operategate.Do notstand in gatepath orwalk through
path while gate ismoving.
Read ownersmanual and safety instructions.
SERIOUS INJURY OR DEATH
CLASS
CERTIFIED TO
CAN/CSA C22.2NO. 247
CONFORMSTO
ANSI/UL-325
VEHICULARGATE OPERATORHP
53382
MODELSERIALVOLTS
PHASE
AMPS
60Hz
MAXGATELOADDoorKing, Inc., Inglewood, CA
Installation/Owners Manual Series 9150Series 9150e r ie s 9 1 5
TM
Copyright 2013 DoorKing, Inc. All rights reserved.
Date Installed:
Installer/Company Name:
Phone Number:
Leave Manual with Owner
Vehicular Slide Gate Operator
UL 325 Compliant
Circuit BoardSerial Numberand Revision Letter:
Convenience Open Optional
9150-065-W-3-13
-
8/13/2019 9150-065-W-3-13.pdf
2/52
-
8/13/2019 9150-065-W-3-13.pdf
3/52
9150-065-W-3-13 1
WARNING
MOVINGGATECANCAUSE
Operategateonlywhengateareais insightandfreeofpeopleandobstructions.
Donotallowchildrentoplayingateareaoroperategate.
Donotstandingatepathorwalkthroughpathwhilegateismoving.
Readownersmanualandsafetyinstructions.
SERIOUSINJURYORDEATH
CLASS
CERTIFIED TOCAN/CSAC22.2NO. 247
CONFORMSTOANSI/UL-325
VEHICULARGATEOPERATOR
HP
53382
MODEL
SERIAL
VO LT S PHA SE
AMPS 60 Hz
MAXGATELOAD
DoorKing,Inc.,Inglewood,CA
15.2516.75
17.75
24.75
GateFrame
Class of Operation Model 9150 - UL 325 Class I, II, III, IV
Type of Gate Vehicular Slide Gates OnlyDrive Sprocket Size #40 Chain
Cycles Per Hour 60 Per Hour (Installed level).
Speed Approximately 1 Ft. per Second (Installed level).
Entrapment Protection Primary- Inherent entrapment sensing system (Type A)
Secondary- Provision for connection of a non-contact sensor (Type B1)and/or a contact sensor (Type B2).
SPECIFICATIONS
4 Minimum
1 Minimum
10.5
Use this manual for the Model 9150 operator with circuit board 4602-010 Rev A or higher ONLY.
Chain Height:Idler wheels intop position.
ConcretePad
ConcretePad
WITH Convenience OpenMax. Gate Weight
Installed Level
WITHOUT Convenience OpenMax. Gate Weight
Installed LevelAmpHorsepower - Voltage - PhaseMax Gate Length
Installed Level
1/2 HP - 115 VAC Single-Phase1 HP - 115 VAC Single-Phase
1,000 Lbs.1,500 Lbs.
800 Lbs.1,300 Lbs.
30 Ft.45 Ft.
5.49.7
Operator
SpecificationDecal
DoorKing, Inc. reserves the right to make changes in the products described in this manual without notice and without obligation of DoorKing, Inc. to notify any personsof any such revisions or changes. Additionally, DoorKing, Inc. makes no representations or warranties with respect to this manual. This manual is copyrighted, all rightsreserved. No portion of this manual may be copied, reproduced, translated, or reduced to any electronic medium without prior written consent from DoorKing, Inc.
Note:208/230/460/575 VAC input voltage can be connected to theoperator by installing an Optional High Voltage Kit (P/N 2600-266).
-
8/13/2019 9150-065-W-3-13.pdf
4/52
9150-065-W-3-12
SPECIFICATIONS 1
Slide Gate Requirements
Safety Information for Slide Gate OperatorsASTM 2200 Standard for Gate Construction
Important Safety Instructions
Instructions regarding intended installation:
Important Notices
UL325 Entrapment Protection
Glossary
4
56
6
6
7
8
9
SECTION 1 - INSTALLATION 10
10
10
11
12-15
15
16
17
18
19
1.1 Hardware for the Gate
1.2 Physical Stops for the Gate
1.3 Types of Gates
1.4 Operator Mounting Positions
1.5 Underground Conduit Requirements
1.6 Pad, Post or Ceiling Mount without / with J-Box Setup
1.7 Mounting Operator and Chain
1.8 Installation of Warning Signs
1.9 Chain Tray Kit
SECTION 2 - AC POWER TO OPERATOR(S) 20
20
21
2.1 High Voltage Wire Runs
2.2 High Voltage Terminal Connection
SECTION 3 - ADJUSTMENTS 22
3.1 4602 Circuit Board Description and Adjustments
3.2 DIP-Switch SW 1 and SW 2 Settings
3.3 Automatic Open / Close Limit Adjustment
3.4 Clutch Adjustment
3.5 Inherent Reverse Sensor Adjustment
22
23-24
25
26
26
TABLE OF CONTENTS
-
8/13/2019 9150-065-W-3-13.pdf
5/52
9150-065-W-3-13 3
SECTION 5 - WIRING 31
31
32
33
34
5.1 Main Terminal Description
5.2 Control Wiring for Single/Primary Operator
5.3 Auxiliary Device Wiring
5.4 Bi-Parting Gates Wiring - Dual Gate Operators
SECTION 8 - MAINTENANCE AND TROUBLESHOOTING 41
8.1 Maintenance
8.2 Troubleshooting
8.3 Accessory Items
Model 9150 Wiring Diagrams
41
42-43
44
45-48
SECTION 7 - OPTIONAL CONVENIENCE OPEN ADJUSTMENTS 39
7.1 Circuit Board (2340) Setup
7.2 DC System Description
7.3 DIP-Switch Settings
39
40
40
SECTION 6 - OPERATING INSTRUCTIONS 35
6.1 AC Power and Reset Switch
6.2 Shutdown ConditionsSoft Shutdown
Hard Shutdown
6.3 Manual Gate Operation
Fail-Safe Manual Release System
Fail-Secure Manual Release System
Emergency Vehicle Access Conditions
37-38
35
36-37
SECTION 4 - ENTRAPMENT AND SAFETY PROTECTION 27
4.1 UL 325 Terminal Description
4.2 Secondary Entrapment Protection Device Locations
4.3 Loop Detector Wiring
27
28-29
30
TABLE OF CONTENTS
-
8/13/2019 9150-065-W-3-13.pdf
6/52
9150-065-W-3-14
Slide Gate RequirementsThe operator is intended for installation only on gates used for vehicles.Pedestrians must be supplied with a separateaccess opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such thatpersons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.(ref. UL 325 56.8.4.b)
All openings of a horizontal slide gate areguarded or screened from the bottom of the gate to aminimum of six (6) feet (1.83 m) above the ground toprevent a 2 1/4 inch (57.2 mm) diameter sphere frompassing through the openings anywhere in the gateand in that portion of the adjacent fence that the gatecovers in the open position.(ref. ASTM F2200-11a, 6.1.2)
Note: A filler post or barriermay need to be installed in thegap area to reduce the distanceto 2 1/4 inches or less.A contact sensor should beinstalled in this area for
safety.(Seeon next page and page 28).
A gap, measured in the horizontal plane parallel tothe roadway, between a fixed stationary object
nearest the roadway (such as a gate support post)and the gate frame when the gate is in either the
fully open position or the fully closed position, shall
not exceed 2 1/4 inch (57.2 mm).(ref. ASTM F2200 6.1.4)
Closed Gate
21/4maximumgaparea
HighRiskofEntrapm
entArea
High Risk of Entrapment Area X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X
Adjacent fence that covers open gate position.
GateSupportPost
GateFrame
A
Note: Installscreened wiremesh to anon-compliantgate ANDnon-compliant
adjacent fencethat coversopen gateposition(See above).
X X XX X XX X XX X XX X X X XX X X
72(6ft)minimum
6ftminimum
Non-compliant openingswider than 2 1/4.
Less than 2 1/4Screened Wire Mesh
Compliant openingsless than 2 1/4.
Gate Frame and Adjacent Fence Area
Gate Frame and Adjacent Fence Area
Gates shall be designed, constructed andinstalled to not fall over more than 45
degrees from the vertical plane, when a gateis detatched from the supporting hardware.
Guide
Rollers
Fall Over Bracket
Illustrations not to scale.
-
8/13/2019 9150-065-W-3-13.pdf
7/52
9150-065-W-3-13 5
ReverseLoop
AutomaticExit Loop
Minimizes the potentialof the gate closingwhen a vehicle ispresent. Number andplacement of loops isdependent on theapplication.
ReverseLoop
Minimizes the potentialof the gate closingwhen a vehicle ispresent. Number andplacement of loops isdependent on theapplication.
(Optional) willprovide an opencommand to thegate operator(s)when a vehicle isexiting the property.
Warning Sign
Moving Gate Can CauseSerious Injury or Death
KEEP CLEAR! Gate may move at any timewithout prior warning.Do not let children operate the gate or play
in the gate area.This entrance is for vehicles only.Pedestrians must use separate entrance.
Moving Gate Can CauseSerious Injury or Death
KEEP CLEAR! Gate may move at any timewithout prior warning.Do not let children operate the gate or play
in the gate area.This entrance is for vehicles only.Pedestrians must use separate entrance.
11
A
B
C
ClosedGate
Sec
ure
Side
ofGate
Non-S
ecure
Side
ofGate
2
Safety Information for Slide Gate Operators
Physical Stop
Positive stops shall be requiredto limit travel to the designedfully open and fully closedpositions. These stops shall be
installed either at the top of thegate, or at the bottom of thegate where such stops shallhorizontally or vertically projectno more than is required toperform their intended function.
Physical Stops
Permanently mounted and easilyvisible from either side of the gate.
Warning Signs
Non-Contact Sensors (Photo Sensors)
1
2
Minimizes the potential of the gate closing on vehicular orother traffic that loops cannot sense. It can be installed on thesecure ORnon-secure side of gate.
Helps minimize the potential of entrapment during the backtravel of the gate.
Entrapment protection devices are required to reduce the risk of injury.Install sensors where the risk of entrapment or obstruction exists whilegate is moving. Individual requirements will vary. See pages 27-30 formore information on typical layout locations and setup.
Contact Sensor (Reversing Edges)
A
Minimizes the potential of the gate closing on vehicularor other traffic that loops cannot sense.
Installed on the fence to help minimize the potential ofentrapment between the gate and fence. A filler post orbarrier MAY need to be installed between fence and gate.
B
C
Helps minimize the potential of entrapment during theback travel of the gate.
Guide RollersSee previous page for more information.
SeparatePedestrian
WalkwayLocated so pedestrianscannot come in contactwith the vehicular gate.
HighRiskofEntrapmentArea
XXX
XXXXXXXXX
ScreenedWire MeshMay be necessary on partof fence ANDentire gate.See previous page for moreinformation.
Fence
Fence
Illustration not to scale.
-
8/13/2019 9150-065-W-3-13.pdf
8/52
9150-065-W-3-16
Instructions regarding intended installation:
Vehicular gates should be constructed and installed in accordance with ASTM F2200; Standard Specification for AutomatedVehicular Gate Construction. For a copy of this standard, contact ASTM directly at 610-832-9585; [email protected]; orwww.astm.org.
Important Safety InstructionsWARNING - To reduce the risk of injury or death:1. READ AND FOLLOW ALL INSTRUCTIONS.2. Never let children operate or play with gate controls. Keep the remote control away from children.3. Always keep people and objects away from gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.4. Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object
activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjustand retest the gate operator properly can increase the risk of injury or death.
5. Use the emergency release only when the gate is not moving.6. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate
hardware.7. The entrance is for vehicles only. Pedestrians must use separate entrance.
8. SAVE THESE INSTRUCTIONS!
Install the gate operator only if:
1. The operator is appropriate for the construction of the gate and the usage class of the gate.
2. All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 6 feet
(1.83 m) above the ground to prevent a 2 inch (57.2 mm) diameter sphere from passing through the openings
anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position.
3. All exposed pinch points are eliminated or guarded.
4. Guarding is supplied for exposed rollers.
The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate
access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such thatpersons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures
when opening and closing to reduce the risk of entrapment. Swinging gates should not open into public access areas.
The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not
over-tighten the operator clutch, pressure relief valve or reduce reversing sensitivity to compensate for a damaged gate.
For gate operators utilizing Type D protection:
1. The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving.
2. A warning placard shall be placed adjacent to the controls.
3. An automatic closing device (such as a timer, loop sensor, or similar device) shall not be employed.
4. No other activation device shall be connected.
Controls intended for user activation must be located at least ten feet (10) away from any moving part of the gate and
where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor oreasily accessible controls should have a security feature to prevent unauthorized use.
The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset control shall not
cause the operator to start.
A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.
For gate operators utilizing a non-contact sensor:
1. See the instructions on the placement of non-contact sensors for each type of application.
2. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate
is still moving in the opening direction.
3. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exist, such as the
perimeter reachable by a moving gate or barrier.
ASTM F2200 Standard for Gate Construction
-
8/13/2019 9150-065-W-3-13.pdf
9/52
-
8/13/2019 9150-065-W-3-13.pdf
10/52
9150-065-W-3-18
UL 325 Entrapment Protection
Class I
Class I and II
Class III
Class IV
Class II
Class III Class IV
A vehicular gate operator (or system) intended for use in ahome of one-to four single family dwelling, or a garage orparking area associated therewith.
A vehicular gate operator (or system) intended for use in acommercial location or building such as a multi-familyhousing unit (five or more single family units) hotel,garages, retail store or other building servicing the generalpublic.
A vehicular gate operator (or system) intended for use in a
industrial location or building such as a factory or loadingdock area or other locations not intended to service thegeneral public.
A vehicular gate operator (or system) intended for use in a
guarded industrial location or building such as an airportsecurity area or other restricted access locations notservicing the general public, in which unauthorized accessis prevented via supervision by security personnel.
This table illustrates the entrapment protection requirements for each of the four UL 325 classes.
A - Inherent entrapment protection system.
B1- Provision for connection of, or supplied with, a non-contact sensor (photoelectric sensor or the equivalent).When used as the PRIMARY device, must be monitored.
B2- Provision for connection of, or supplied with, a contact sensor (edge device or the equivalent).When used as the PRIMARY device, must be monitored.
C - Inherent adjustable clutch or pressure relief device.
D - Provision for connection of, or supplied with, an actuating device requiring continuous pressure to maintainopening or closing motion of the gate.
E - An inherent audio alarm.
STATEPRISON
UL 325Classifications
Horizontal Slide, Vertical Lift, Vertical Pivot Swing and Vertical Barrier (arm)
Primary Protection
A B1, B2 or D A, B1, B2, C or DA or C
A, B1 or B2 A, B1, B2, D or E A, B1, B2, C or DA, B1, B2 or C
A, B1, B2 or D A, B1, B2, D or E A, B1, B2, C, D or EA, B1, B2, C or D
Secondary Protection Primary Protection Secondary Protection
-
8/13/2019 9150-065-W-3-13.pdf
11/52
9150-065-W-3-13 9
GlossaryGATE- A moving barrier such as a swinging, sliding, raising, lowering, or the like, barrier, that is a stand-alone passagebarrier or is that portion of a wall or fence system that controls entrance and/or egress by persons or vehicles andcompletes the perimeter of a defined area.
RESIDENTIAL VEHICULAR GATE OPERATOR CLASS I- A vehicular gate operator (or system) intended for use in a home
of one-to four single family dwelling, or garage or parking area associated therewith.
COMMERCIAL / GENERAL ACCESS VEHICULAR GATE OPERATOR - CLASS II- A vehicular gate operator (or system)intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units),hotels, garages, retail store, or other building servicing the general public.
INDUSTRIAL / LIMITED ACCESS VEHICULAR GATE OPERATOR - CLASS III- A vehicular gate operator (or system)intended for use in an industrial location or building such as a factory or loading dock area or other locations not intendedto service the general public.
RESTRICTED ACCESS VEHICULAR GATE OPERATOR - CLASS IV- A vehicular gate operator (or system) intended for use ina guarded industrial location or building such as an airport security area or other restricted access locations not servicingthe general public, in which unauthorized access is prevented via supervision by security personnel.
VEHICULAR BARRIER (ARM) OPERATOR (OR SYSTEM)- An operator (or system) that controls a cantilever type device (orsystem), consisting of a mechanical arm or barrier that moves in a vertical arc, intended for vehicular traffic flow atentrances or exits to areas such as parking garages, lots or toll areas.
VEHICULAR HORIZONTAL SLIDE-GATE OPERATOR (OR SYSTEM)- A vehicular gate operator (or system) that controls agate which slides in a horizontal direction that is intended for use for vehicular entrance and exit to a drive, parking lot, orthe like.
VEHICULAR SWING-GATE OPERATOR (OR SYSTEM)- A vehicular gate operator (or system) that controls a gate whichmoves in an arc in a horizontal plane that is intended for use for vehicular entrance and exit to a drive, parking lot, or thelike.
SYSTEM- In the context of these requirements, a system refers to a group of interacting devices intended to perform acommon function.
WIRED CONTROL- A control implemented in a form of fixed physical interconnections between the control, the associateddevices, and an operator to perform predetermined functions in response to input signals.
WIRELESS CONTROL- A control implemented in means other than fixed physical interconnections (such as radio waves orinfrared beams) between the control, the associated devices, and an operator to perform predetermined functions inresponse to input signals.
INHERENT ENTRAPMENT PROTECTION SYSTEM- A system, examples being a motor current or speed sensing system,which provides protection against entrapment upon sensing an object and is incorporated as a permanent and integral part
of the operator.
EXTERNAL ENTRAPMENT PROTECTION DEVICE- A device, examples being an edge sensor, a photoelectric sensor, orsimilar entrapment protection device, which provides protection against entrapment when activated and is not incorporatedas a permanent part of an operator.
ENTRAPMENT- The condition when an object is caught or held in a position that increases the risk of injury.
-
8/13/2019 9150-065-W-3-13.pdf
12/52
9150-065-W-3-110
Gate End Retainer
EndPost
SECTION 1 - INSTALLATION
1.2 Physical Stops for the Gate
1.1 Hardware for the GateGood hardware is essential for proper operation of a sliding gate. DoorKing has a full line of gate hardware products that willensure safe, reliable and long lasting gate operation. The gate must be properly installed and roll smoothly in both directions.
Rubber bumper faces toward
operator. it will make contactwith the operator housing
during the initial automaticMultiple gate cyclingtoset the open and closegate position.
The 9150s automatic open/close gate limits must have a physical
stop on the open and close positions of the gate. This can be theuse of end posts with gate end retainers or chain stops, dependingon the mounting position of the operator. Note:Chain stops DONOT meet the ASTM F2200 requirements for physical gate stops.
Gate End Retainer - Helps stabilizethe end of the gate in the open orclosed position. Recommended forall slide gate applications.
Endless Idler Assembly withProtective Cover - Helps tominimize a pinch point for a180 chain return.
Guide Rollers withProtective Covers - Helpsto minimize a pinch pointon the gate.
Roller Bearing V-Wheelswith Protective Cover - Helpsto minimize a pinch point onthe gates wheel and V-rail.
Chain Stops
Gate
Prior to beginning the installation of the slide gate operator, we suggest that you become familiar with the
instructions, illustrations, and wiring guide-lines in this manual. This will help insure that your installation isperformed in an efficient and professional manner compliant with UL 325 safety and ASTM F2200 constructionstandards.
The proper installation of the vehicular slide gate operator is an extremely important and integral part of the
overall access control system. Check all local building ordinances and building codes prior to installingthis operator. Be sure your installation is in compliance with local codes.
-
8/13/2019 9150-065-W-3-13.pdf
13/52
9150-065-W-3-13 11
1.3 Typical Gate TypesThe Model 9150 operator is designed to be installed on these gate types.See the next 4 pages for specific operator mounting positions. Individualinstallations and physical stops can vary.
V-Rail
V-Whee
lOrnam
ental
Cantile
ver
1500 lb. max. weight per gate (1 HP).
Single Operator - 45 ft max. gate length (1 HP). Dual Operators - 90 ft max. total gate length (1 HP).
Chain tray recommended for gates longer than 20 ft using front or center post mount installations ONLY.
Frontp
osition
withc
oncrete
pads
hown.
Gatee
ndreta
inerso
nend
postsu
sedas
physic
alstop
sforgate
.
BoxFra
meRo
ller
WARNING
MO
VING
GATE
CAN
CAU
SE
Oper
ategateonly
whengate
ar eais in
s ight
andf ree
ofpeopl ea
ndobstr
uctions.
Dono
t allow
childr en
toplaying
atearea
or oper a
tegate .
Dono
t stand
ingat ep
at hor w
alkthro
ugh
pat hwhileg
ateism
oving.
Read
owner s
manual
andsafetyi
nstructio
ns.
SER
IO US
INJ U
RYO
RDE
ATH
CLASS
CERTI
FI EDTO
CAN
/ CSAC2
2. 2NO. 2
47
CONFORM
STO
ANSI/
UL-325
VEHI C
ULAR
GATE
OPER
ATORHP
533 82
MODEL
SERIAL
VOLTS
PHASE
AMPS
60Hz
MAX
GATELOADDo
or King
, Inc ., I
nglewo
od,CA
WARNING
MOVI
NGGAT
ECAN
CAUSE
Operate ga
te onlyw he
nga te area
is insigh t
andfree of
pe oplean d
obs tru ctio
ns .
Do not allo
w children
to pl ayi ng
ate area
orop erateg
at e.Do no
ts tandi ng
ate path or
walkthr ou
gh
pat hw
hilegat e is
m oving .
Rea do
wn ersm an
ua land sa
fetyi nstruc
tio ns.
SERI
OUSIN
J URYO
RDEA
TH
CLASS
CERTIFI
EDTO
CAN/ CS
AC22.2NO.247
CONFORM
STO
ANSI / UL
-325VEHIC
ULARGATE
OPERATORHP
5338 2
MODEL
SERI A
LVOLT
S
PHASE
AMPS
60Hz
MAXGATELO
ADD oorKing ,
Inc. ,Ingl
ew ood,C A
WARNING
MOVI
NGGAT
ECAN
CAUSE
Op erat eg a
te only whe
nga te are
ai sinsi ght
an dfre e of
pe ople and
obs tru cti o
ns .
Do nota llo
w chi ldr en
to playi n g
at earea
or opera teg
ate.Do no
ts tanding
at epath or
wa lkth rou
gh
pat hw
hi legate is
m ov ing .
Rea do
w nersm an
ual and sa
fet yinstru c
ti ons.
SERI
OUSI N
JURYO
RDEA
TH
CLASS
CERTIFI
EDTO
CAN/ CSAC22
.2NO.2
47
CONFORM
STO
ANSI/ UL
-325VEHIC
ULARGATE
OPERAT
ORHP
533 82
MODEL
SERIA
LVOLT
S
PHASE
AMPS
60Hz
MAXGAT
ELOADD oor
Ki ng,In c.,
Ing lew oo
d, CA
BoxFra
meCa
ntileve
r
WARNING
MOVIN
GGAT
ECAN
CAUSE
Op erate ga
te only w h
en gate ar
ea isin sig
ht
an dfree o
fp eople an
d obst ruc
tio ns.
Do not al l
ow child re
ntopla yi n
g atear ea
oro perat e
g ate.
Do not st
an ding ate
pat horw
alk thro ug
h
pat hwhi l
eg ateis m
ovin g.
Reado w n
er sma nu
alands afe
ty instruc t
io ns.
SERIO
USIN
J URYO
RDEA
TH
CLASS
CERTIFIED
TO
CAN/ C
SAC22. 2
NO.247
CONFORMS
TOANSI/ U
L-325
VEHI
CULAR
GATEOPER
ATOR
HP
5338 2
MODEL
SERIAL
VOLTS
PHASE
AMPS
60Hz
MAXGATEL
OADDoorKin
g,Inc .,In
glewood,
CA
Frontp
osition
withp
ostmo
untsh
own.
Chains
topsu
sedas
physic
alstop
sforga
te.
Frontp
osition
withp
ostmo
untan
dchai
ntray
shown
.
Chains
topsu
sedas
physica
lstops
forga
te.
Frontp
osition
withp
ostmo
untsh
own.
Chains
topsu
sedas
physic
alstop
sforga
te.
-
8/13/2019 9150-065-W-3-13.pdf
14/52
9150-065-W-3-112
1.4 Operator Mounting Positions
Operators chain idler wheels are factory setfor the front position.
Remove only the top chain knockouts fromeach side of the operator.
Chain stops or gate end retainer can beused as the physical stop for the gate
(Chain stops are shown).
Front Position with Concrete PadStandard method of installation.
ChainStop
Chain IdlerWheels
Chain IdlerWheels
ChainStop
Gate End Retainer
Gate EndRetainer
Gate End Retainer
Top View
Top View
Additional hardware required.Post base plate (P/N 2600-495) 6 x 6 steel posts not available from DoorKing.Base plate stop brackets (P/N 2600-970) bolts on post base plate when using chain stops.Optional chain tray kit (P/N 2601-270 10 ft section) and additional chain #40 (P/N 2600-442 - 20 ft. per box) may be needed.
Set operator chain idler wheels in thebottom position.
DO NOTremove chain knockouts.
Chain stops with base plate stopbrackets or gate end retainer can beused as the physical stop for the gate(Both are shown, only one type isneeded).
Base PlateStop Bracket
Chain Setup
Chain Setup
The Model 9150 operator is designed to be installed in the front, rear, center or ceiling mounting positions shown on this pageand the next 3 pages. V-wheel V-rail ornamental gates are shown as examples but other gate types on the previous page canuse the same mounting setups. Once the mounting position has been determined, the chain idler wheels may need to beadjusted BEFOREthe operator is mounted. Physical stops MUST be used in the open AND close positions for ANY gateinstallation (Chain stops, end posts with gate end retainers or a wall that the gate comes in contact with).
A filler post or barrier may need to beinstalled between the gate and wall area(See page 4 for more information).
A filler post or barrier may need to beinstalled between the gate and wall area(See page 4 for more information).
Front Position with Post MountRaises operator and allows different chain heights. Optional chain tray kit can be used and is recommended for gates over 20 ft,
supports the chains weight and helps prevent chain stretching.See page 19 for more information.
-
8/13/2019 9150-065-W-3-13.pdf
15/52
-
8/13/2019 9150-065-W-3-13.pdf
16/52
-
8/13/2019 9150-065-W-3-13.pdf
17/52
9150-065-W-3-13 15
1.5 Underground Conduit Requirements
Operators setup is the same as the front
position or rear position with concrete padshown on page 12 and 13.
(Front upside down position shown here).
Junction box connection is used for theceiling mount installation.
Front or Rear Position Upside DownCan be mounted on the ceiling to conserve floor space.
Note: There are NOfluids in theoperator that can leak out.
ChainStop
Ceiling
Chain IdlerWheels
OperatorBottom
Top View
Chain Setup
A filler post or barrier may need to beinstalled between the gate and wall area(See page 4 for more information).
Sweeps
ConcretePad
Primary
OperatorPosition
Secondary
OperatorPosition
The conduit requirements are for a typical slide gate operator installation (the secondary operator is shown for thoseapplications where a secondary operator may be used). The conduit requirements for your application may vary fromthis depending on your specific needs.
Use only sweeps for conduit bends. Do not use 90 elbows as this will make wire pulls very difficult and can causedamage to wire insulation.
DoorKing recommends using 3/4-inch conduit.
Be sure that all conduits are installed in accordance with local codes.
Neverrun low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
ElbowNO
SweepYES
Control and/or P.A.M.S. Wires (Low Voltage wire insulation)
DoorKings Primary/Secondary Interconnection Cable (Dual Operator Application Only)(Secondary Power and Communication wires)
Loop Lead-In Wires (Low Voltage wire insulation)
AC Input Power (High Voltage wire insulation)
AC Input Power (High Voltage wire insulation)
3/4 Inch Conduit Recommended
-
8/13/2019 9150-065-W-3-13.pdf
18/52
9150-065-W-3-116
2.5
1.6 Pad, Post or Ceiling Mount without/with J-Box Setup
Post Mount with Conduit
Pad Mount with Conduit
21.5
26Concrete Pad
Center
Concrete Pad
Concrete Foundation Conduit
4 min. above ground.
4 min. above ground.
Underground depth of theconcrete pad is determinedby soil conditions and localbuilding codes. Reinforced
concrete recommended.
Underground depth of theconcrete foundation is
determined by soilconditions and local
building codes. Reinforcedconcrete recommended.
Concrete padMUST be level.
Base PlateMUST be level.
Operator MUSTbe level.
Pad, Post or Ceiling Mount Connected with Junction Boxes
All wire connections can bemade on either sideof theoperator housing after ithas been installed.
Neverrun highvoltage and lowvoltage in thesame conduit.
Conduit Knock-Out SizesLowVolt
HighVolt
Note: Weld the posts to the base plate and mountassembly into concrete BEFOREattaching theoperator. Conduit runs up through 6 x 6 steel posts.
Note: Operator must be mounted1 min. away from gate.
LowVolt
HighVolt
Conduit Conduit
Pad, post orceiling mount
Conduit
14.5
Conduit Area
Electronic Box
8.5
1 minimum from operator housing to gate.
Conduit areainside 6 x 6
post.
Conduit areainside 6 x 6
post.
Base PlateP/N 2600-495
14Min.
ConcreteFoundation
24Min.6.5
1 minimum from operator housing to gate.
1.5
WARNING
MOVINGGATECANCAUSE
Operategateonlywhengateareaisinsightandfreeofpeopleandobstructions.Donotallowchildrentoplayingateareaoroperategate.Donotstandingatepathorwalkthroughpathwhilegateismoving.Readownersmanualandsafetyinstructions.
SERIOUSINJURYORDEATH
CLASS
CERTIFIED TOCAN/CSAC22.2NO.247
CONFORMSTOANSI/UL-325
VEHICULAR GATE OPERATOR
HP
53382
MODEL
SERIAL
VOLTS PHASE
AMPS 60 Hz
MAXGATELOAD
DoorKing,Inc.,Inglewood,CA
1/2
1/2
1/2
1/2
1/2
3/4 3/4
Fail SecureKey Lock
-
8/13/2019 9150-065-W-3-13.pdf
19/52
9150-065-W-3-13 17
1.7 Mounting Operator and ChainPrior to mounting the operator, be sure that the correct chain knockouts have been removed and chain idler wheels are in thecorrect position (top, center or bottom).
Fail-Secure Manual Release Kit Installation Note:It is easier to install the 2600-865 fail-secure manual release kit beforemounting the operator and attaching the chain. Refer to the instruction sheet supplied with the kit for installation.
Operator MUSTbeparallel to gate! Operator NOT
parallel to gate.
Chain bracketdoes NOTalign withidler wheels.
Chain bracket MUSTline up with chainidler wheels!
Chain brackets MUSTbemounted so the chainremains the same heightas it is on the idler wheels!
Positioning Operator and Chain Brackets
ChainBracketLines upwith IdlerWheels
CorrectChain
BracketHeight
CorrectChain
BracketHeight
Chain bracketspositionedtoo low.
NOO
NOO
Chain Idler Wheels
1 minimum from operator housing to gate.
YESS
Chain Idler Wheels
YES S
NOO
Chain bracketspositionedtoo high.
DoorKing recommends aminimum of four (4) 3/8 x 2sleeve anchors (not supplied).
Chain idlerwheels intop position.
Use six (6) 1/2-13 x 1 1/2bolts, lockwashers and nuts(not supplied).
Attaching Operator
to Concrete
Attaching Operator
to Post Base PlateLock
Washer
Washers
3/8
Connect Chain Bracket
to Gate. Weld completelyaround bracket. Chain nutand chain bolt MUST NOTprotrude past gate frame.
Connect chain to chain bolt withmaster link. Adjust the chain nuts totighten the chain. The chain should sag nomore than one (1) inch per 10 feet of travel.Do not over tighten the chain.
Connect Chain to Chain Bracket.
ChainNut
Chain Bolt
Chain Bracket
Option2
Master
Link
Option
1
Gate
Frame10.510.510.5
-
8/13/2019 9150-065-W-3-13.pdf
20/52
9150-065-W-3-118
Endless Idler Assembly (On Select Installations)
1.8 Installation of Warning SignsThis DoorKing Slide Gate Operator is shipped with two warning signs. The purpose of the warningsign is to alert uninformed persons, and to remind persons familiar with the gate system, that apossible hazard exists so that appropriate action can be taken to avoid the hazard or to reduceexposure to the hazard. See page 5 for suggested mounting positions of signs.
Permanently install the supplied warning signs in locations so that the signs are visible by persons on both sides of the gate.
Use appropriate hardware such as wood or sheet metal screws (not supplied) to install thewarning signs.
Lower chain does NOT align with upper chain.Note: Be sure that the chain is aligned andparallel to the gate. Installing the chain in anyother manner will cause excessive noise,chain idler wheel wear and chain stretching.
Lower chain MUSTalign with upper chain!
Upper and lower chainMUSTbe the sameheight as they are onthe operator idlerwheels.
NO
NO
NO
Gate Rail
Gate Rail
ChainBracket
EndlessIdler
Upper Chain
Lower Chain ChainBracket
ChainReturnOperator Idler Wheels
Operator Idler Wheel
OperatorIdler Wheel
Lower chainmounted Too High.
Lower chain mountedToo Low.
NO
NO
Lower chainmounted Too High.
Lower chain mountedToo Low.
DoorKing offers an endless idler assembly with a protective cover designed for the Model 9150 installations (P/N 2600-818).Make sure the endless idler assembly is securelyfastened to the wall or post (Depending on which type of installation will beused). Extreme force will be exerted on this assembly during gate cycling.
Lower chain MUSTbe1 inch lower than theendless idlers 180chain return.
Center and Rear Mount Positions (Top View)
Rear Mount Position (Side View)
Center Mount Position (Side View)
Gate Rail
ChainBracket
Chain Brackets
EndlessIdler
EndlessIdler
Upper Chain
Lower ChainChainBracket
ChainReturn
1
YES
YES
YES
-
8/13/2019 9150-065-W-3-13.pdf
21/52
9150-065-W-3-13 19
1.9 Chain Tray Kit
Tip:Chain tray supporting brackets can bemounted facing up (as shown on right),facing down or extended depending on thechain height and position. For furtherinformation, refer to instructions provided
with the chain tray kit.
Chain TraySupporting
Bracket
A chain tray is recommended for gates longer than 20 ft. to support the weight of the chain. DoorKing offers achain tray kit in sections to fit any length gate. (DoorKing P/N 2601-270 10 Ft. section)
Chain TraySupportingBracket(Facing down)
Chain TraySupportingBracket(Facing up)
Weep Hole
Carriage Bolts
Note: The chain should sag at leastone (1) inch per 10 feet of travel.
Post base plate (P/N 2600-495)
Base Plate Stop Brackets (P/N 2600-970) when using chain stops.
Note: All gate types can havethe chain tray installed onthem, V-rail V-wheelornamental is shown here.
10Ft.Segment
Chain TraySegmentsConnection
10Ft.Segmen
t
Installing the Chain Tray Kit
1
G
ate
-
8/13/2019 9150-065-W-3-13.pdf
22/52
9150-065-W-3-120
2.1 High Voltage Wire Runs
This table illustrates the high voltage AC power wire size and distance limitations.
Model - Motor Voltage - Motor HP - Motor AmpsWire Size / Max Distance in Feet
170 275 460 68585 135 230 340
12 AWG 10 AWG 8 AWG 6 AWG
Single 9150 - 115 VAC - 1/2 HP - 5.4 AmpsDual 9150s - 115 VAC - 1/2 HP - 5.4 Amps each, Single Power Source
Single 9150 - 115 VAC - 1 HP - 9.7 Amps
Dual 9150s - 115 VAC - 1 HP - 9.7 Amps each, Single Power Source
100 170 280 520
50 85 140 260
SECTION 2 - AC POWER TO OPERATOR(S)Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFFposition. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that alicensed electrical contractor perform this work.Since building codes vary from city to city, we highly recommend that you check with your local building department priorto installing any permanent wiring to be sure that all wiring to the operator (both high and low voltage) complies with local
code requirements.
THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!
If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When largegauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on strandedcopper wire. Wire run calculations are based on a AC power source with a 3% voltage drop on the power line, plus an additional10% reduction in distance to allow for other losses in the system.
Neverrun low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
Typical Grounding Sources
Ground to metallic cold water pipe.
GroundWire
GroundWire
Ground to existing electrical system.
Electrical
Panel
Grounding rod 10 feet in soil.
IMPORTANT:Ground wire shown withoutsafety protection for clarity. Make sureground wire is protected from beingtouched or electrical shock could occur!
Optional Heater Installation Note:When installing a heater, refer to the high voltage AC power wire sizeand distance limitationstable on the instruction sheet with the heater kit for AC power wire run limitations.
Optional High Voltage Kit Installation Note:When installing the high voltage kit for 208/230/460/575 VAC input power,
refer to the high voltage AC power wire size and distance limitations table on the instruction sheet with thehigh voltage kit (P/N 2600-266) for AC power wire run limitations.
-
8/13/2019 9150-065-W-3-13.pdf
23/52
9150-065-W-3-13 21
REVERSE
SENSITIVITY
REVERSE
LOOP
EXITLOOP
KEYSWITCH
DOORKING
4602-010
SW1
SW2
OPENTIMER
2.2 High Voltage Terminal Connection
Use the existing wire restrainersinside operator to keep wireaway from moving parts.
A separatepower disconnectswitch may be needed in your
area. Check local buildingcodes before installation.
Note:OptionalHigh Voltage Kitblack and white wiresconnect the same asshown above.
115 VACAC Power Terminal
ChassisGround
White - Neutral
Black - 115 VAC HotGreen - Chassis Ground
DANGER
HIGH VOLTAGE
Route incoming AC power wire through the high voltage conduit and run wire in the operator as shown.
Be sure wiring is installed in accordance with local codes. Be sure to color code all wiring.
It is recommended that a surge suppressor be installed on the high voltage power lines to help protect the operator
and circuit board from surges and power fluctuations. Dual operators (Primary/Secondary) require AC power to each operator.
Hot Neu
Loosenthe2nuts
undertheelectronicbox
toswingboxup.
DO NOTpower up and cycle theoperator until the Physical stopshave been installed. Damage couldoccur to the gate andoperator.
High VoltageAC Power Wire
External PowerDisconnect Switch
MOV- Helps protect operatorfrom power surges.
AC Power AC Power
Dual Operators
Every timethe 9150 is powered up, the Firstopen command will automatically run Multiplegate cyclesthat will locate and remember the gates open and close positions (See page 25).
AC POWER
ON
OFF
HighVoltageConduit
-
8/13/2019 9150-065-W-3-13.pdf
24/52
9150-065-W-3-122
ON
ON
REVERSESENSITIVITY
REVERSELOOP
EXITLOOP
KEY SWITCH
DOORKING4602-010
SW1 SW2
OPENTIMER
NC
1
23
4
5
NO18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
9410
9409
3.1 4602 Circuit Board Description and Adjustments
SECTION 3 - ADJUSTMENTSThe switch settings and adjustments in this chapter should be made after your installation and wiring to the operator(s) iscomplete. Whenever any of the programming switches on the circuit board are changed, power must be shut-off, and thenturned back on for the new setting to take effect. Every timethe 9150 is powered up, the Firstopen command will automati-cally run Multiple gate cyclesthat will locate and remember the gates open and close positions (See page 25).
Auto-close timer (whenturned on) SW 1, switch 2.
Adjust from 1 second(full counter clockwise) toapproximately 23 seconds(full clockwise).
Dry relay contacts(terminals 15-16) can beset for Normally Open(NO) or Normally Closed(NC) operation by placingthe relay shorting bar on theN.O. or N.C. pins respectively.SW 1, switches 4 and 5 mustbe set to control relay. Seenext page for descriptions.
1 23
Auto-Close Timer Dual Channel Loop Detector Single Channel Loop Detector
Dry Relay Contact
NC
NO
Set the DIP-switcheson the circuit boardto the desiredsetting. See switchsetting charts onnext 2 pages.
DIP-Switches
ON
1
2
3
4
5
6
7
8
SW 2
ON
1
2
3
4
5
6
7
8
SW 1
ON
1
2
3
4
5
6
7
8
SW 1
Cycles the operatorwhen pressed. Gateopens to full openposition ONLY.
Surface Mounted LEDsIndicates that low voltage power is applied to the circuit board.Input LEDsshould be OFF and will only illuminate when the input is activated. Pulse LEDswillblink as the operator is running. They can be either ON or OFF when the operator is stopped.
Key Switch
Adjust reversing sensitivity.Full counter clockwise forminimum sensitivity, fullclockwise for maximumsensitivity. See page 26.
Min MaxSensitivity
Inherent Reverse Sensor
Self-test (whenturned on) SW 1,switch 6.
CAUTIONDo notrun self-test with the operatorconnected to the gate. The drive chainmust be disconnected before runningthe self-test. This feature is designedfor bench testing ONLY.
Self-TestON
1
2
3
4
5
6
7
8
SW 1
UL 325Terminal
Power LED
Pulse LEDs
InputLEDs
Magnetic
SensorsSee page 26.
ON
1
2
3
4
5
6
7
8
SW 1
Typical Settings
Exit Loop Port Reverse Loop Port See page 30.See page 34.
-
8/13/2019 9150-065-W-3-13.pdf
25/52
9150-065-W-3-13 23
7-OFF
7-OFF
7-ON
7-ON
8-OFF
8-ON
8-OFF
8-ON
Gate OpenBack-OffPosition
Normal Setting. Gate fully opens.Gate stops short 1 from full open position. Used for a reversing edge device.
Gate stops short 2 from full open position. Used for a reversing edge device.
Gate stops short 3 from full open position. Used for a reversing edge device.
3.2 DIP-Switch SW 1 and SW 2 SettingsThe two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn onor off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and thenturned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.
SW 1 Switch 1Must OPENthe gate upon initial AC power up and open command. If the first open command begins to close thegate, turn AC power off and reverse this switch. Opening direction will vary depending on the type of installation (See above).
SW 1 Switch 2Turns the auto-close timer on or off. Can be adjusted from 1 to 23 seconds to close gate.
SW 1 Switch 3This switch should be left in the OFF position when the slide gate is running on a level track and the gate does notcoast after it has stopped. If the gate is on an incline, turning this switch on will apply a small DC voltage to the motor windingsafter the gate has stopped. This applies braking power to the motor to prevent the gate from coasting after it has stopped.
SW 1 Switches 4-5These work in conjunction with each other and determine when the relay on the board will be activated. Thisrelay can be used as a switch for various functions such as illuminating a warning light when the gate is moving, or turning on agreen light when the gate is full open. If a magnetic lock is used with the gate operator, these switches must be set for magneticlock operation which limits the relay to activate only when the gate is opening and full open.
SW 1 Switch 6This switch is a self-test feature that checks various functions of the circuit board and is used for bench test only.
Do not run this test with the operator connected to the gate.
SW 1 Switches 7-8These work in conjunction with each other and determine if the operator will stop the gate at the full openposition, or if the gate should stop 1, 2 or 3 inches short of the full open position. Needed only when using a reversing edgeentrapment protection device on the openingedge of the gate with an end post as the physical stop.
Switch Function Setting Description
SW 1 (Left 8 Switches)
OFF
ON
4-OFF
4-OFF
4-ON
4-ON
5-OFF
5-ON
5-OFF
5-ON
Auto-CloseTimer
Relay Activationand
LED IndicatorLight Activation
2
1
MotorHold
OFF
ON3
4 and 5
7 and 8
Normal Setting. No voltage to motor when gate is stopped (Level gate).
Voltage applied to motor always. Keeps inclined gate from coasting when stopped.
Auto-close timer is OFF. Manual input required to close gate.
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.
OFF
ONSelf-Test6
Normal Setting.
Runs self-test. Caution: Bench testing ONLY!
Relay activates and LED is ON when the gate is fully open.
Relay activates and LED is ON when the gate is not closed.
Relay activates and LED is ON when the gate is opening and open.
Relay activates and LED is ON when the gate is opening and closing.
Every timethe operator is powered up, the Firstopen command will automatically run Multiplegate cyclesthat will locate and remember the gates open and close positions (See page 25).
Changes the direction the operator will open/close the gate depending on the different chain configurations.
Openingdirection
using OFFsetting.
Openingdirectionusing ONsetting.
PostMounts
Center or
Openswith
ONsetting.
MountsRight
All Rear
Openswith
OFFsetting.
MountsLeft
All Rear
Openingdirection
using ONsetting.
Openingdirection
using OFFsetting.
Mount
Front
-
8/13/2019 9150-065-W-3-13.pdf
26/52
9150-065-W-3-124
3.2 Continued
OFF
ON
Operator ModelSelect
5
7-OFF
7-OFF
7-ON
7-ON
8-OFF
8-ON
8-OFF
8-ON
Gate CloseBack-OffPosition
Normal Setting. Gate fully closes.
Gate stops short 1 from full close position. Used for a reversing edge device.
Gate stops short 2 from full close position. Used for a reversing edge device.
Gate stops short 3 from full close position. Used for a reversing edge device.
Switch Function Setting Description
SW 2 (Right 8 Switches)
2
7 and 8
Built-inSolenoid
Lock
OFF
ON
4
Normal Setting. Fail-safe logic. Lock engages only if attempt is made to force gateopen (Factory setup).
Fail-secure logic. Lock engages after each gate cycle (2600-865 Lock kit required).Normal Setting. Switch must be OFF for Model 9150.
DO NOTuse ON setting for Model 9150.
OFF
ON
Partial Open(14 Ft)
3Normal Setting. Switch must be OFF for terminal #5 input to open gate 14 Ft.
DO NOTuse ON setting. NOTassociated with partial open feature for the 9150.
OFF
ON
OFF
ON
Normal Setting. Input to terminal #6 and/or reverse loops will reversegateduring closecycle.
Input to terminal #6 and/or reverse loops will stopgate during closecycle gatewill continue to close after input to terminal #6 and/or reverse loops are cleared(Helps prevent tailgating vehicles from unauthorized entry).
OFF
ON6Normal Setting. Timer will function normally.
Opening gate will stop and begin to close as soon as all reversing inputs (Reverseloops, photo sensors) are cleared regardless of the distance the gate has opened.
1
SW 2 Switch 1Switch 1 ON, plug-in exit loop detector is a normal full openinput. Switch 1 OFF, the normal exit loop portfunction is bypassed and a jumper wire is needed to open and close gate(s) for certain applications (Single operator automaticexit loop partialopen or dual operator application) depending on the type of loop detector used and position of jumper wire.SW 2 Switch 2Determines if an input to terminal #6 (Photo Sensors) AND/ORreverse loops will reverse ORstop a CLOSING gate.A tailgating vehicle can activateterminal #6 (Photo sensors) and/or reverse loops whilethe gate is in the closing cycle from theprevious vehicles authorized entry:Ifswitch 2 is turned OFF (Reverse), the closing gate that gets activated by a tailgating vehicle will reverse back to the openposition, possibly allowing the tailgating vehicle unauthorized entry while the gate is reversing back to the open position.Ifswitch 2 is turned ON (Stop), the closing gate that gets activated by a tailgating vehicle will stop, partially or completelyblocking the pathway, NOTallowing the tailgating vehicle to enter without proper authorization. The gate will not move until allsensors are clear, usually forcing the tailgating vehicle that activated the sensors to back away from the gate. The gate will thencontinue until closed, helping prevent the tailgating vehicle from unauthorized entry.SW 2 Switch 3Switch mustbe in the OFFposition. Inputs connected to terminal #5 will open and reverse the gate only 14 Ft.
SW 2 Switch 4This switch determines the operation of the built-in solenoid lock. The OFF setting is the factory setup. Caution:Do not set this switch to ON unless the 2600-865 fail-secure manual release kit has been installed in the operator.Changing this switch to the ON setting without installing the lock kit will damage the operator. See pages 37 and 38 for moreinformation about Fail-Safe vs. Fail-Secure release systems.SW 2 Switch 6Turning the quick-close feature on will cause the auto-close timer to close the gate after 1 second, regardless ofthe setting of the auto-close timer potentiometer. This will also cause an opening gateto stop and reverse when the reverseloops and/or photo sensors are cleared. This feature, along with turning SW 2, switch 2 ONabove, is useful to help preventtailgating vehicles from unauthorized entry.SW 2 Switches 7-8These work in conjunction with each other and determine if the operator will stop the gate at the full closeposition, or if the gate should stop 1, 2 or 3 inches short of the full close position. Needed only when using a reversing edgeentrapment protection device on the closingedge of the gate with an end post as the physical stop.
Quick-CloseTimer Override
Exit Loop Port
Output
JumperWire
Needed
Full Open Input
A plug-in exit loop detector plugged into the EXIT Loop port will partially open single
operator or fully open dual operators depending on type of loop detector used).Normal Setting. Plug-in exit loop detector will fully open gate (Single operator).
Reverses Gate
Stops Gate
-
8/13/2019 9150-065-W-3-13.pdf
27/52
9150-065-W-3-13 25
3.3 Automatic Open / Close Limit Adjustment
Gate MUSTopen until it contacts the physical open stop. (if gate starts to close, turn power off andchange the direction operator opens (SW 1, switch 1). Turn power back on and give open command again).
Auto-close timer will close the gate until it contacts the physical close stop. (Manual close commandrequired if timer is turned off).
Gate will automatically open until it gets approximately 12 inches away from the full open position andstop, then continue opening until it contacts the physical open stopagain.
Auto-close timer will close the gate until it gets approximately 12 inches away from the full close positionand stop, then continue closing until it contacts the physical close stopagain. (Manual close commandrequired if timer is turned off).
Sequence of Automatic Multiple Gate Cycles to Set Gate Limits
Open
Open
Close
Close
SequenceFinished
After the first open command is given to the operator (gate can be in any position):
Open and close gate positions are now set and will be remembered by the 9150 (until it loses AC power).Gate will function normally after automatic Multiple Gate Cycles sequence has finished.
The 9150s open/close limits DO NOThave to be physically adjusted. Every time the 9150 is powered up, the first opencommand will automatically run Multiple gate cycles that will locate and remember the gates open and close positions.These positions are determined by the physical stops that have been installed (See section 1.2, page 10).
Timer:The Auto-Close Timer should be turned ON (SW 1, switch 2) to allow the multiple gate cycles to run automatically,otherwise manual close commands will be required to complete this sequence.
Clutch:The clutchs factory setting will work correctly for most installations. The clutch must NOTslip while the gate is cyclingbetweenthe full open and full closed position or the gate limits will be incorrect. If the clutch slips during this period, it must betightened before running this sequence (See section 3.4 on the next page).
Safety Devices:Run this sequence beforetesting any safety features (primary inherent reverse sensor, secondary entrapmentprotection, entrapment alarm and reset features).
Reversing Edge mounted on the Gate using End Posts:When using a reversing edge on either end of the gate with an end
post as the physical stop, the reversing edge must be disconnected from the circuit board everytimethis sequence will be run(the UL 325 terminal can be unplugged from the circuit board).
CAUTION: Keep pedestrians and vehicles clear of the gate while this sequence is running!
Note: If gate encounters an obstruction during this sequencing,it will automatically continue after obstruction has been cleared.
MultipleGateCycles
-
8/13/2019 9150-065-W-3-13.pdf
28/52
9150-065-W-3-126
3.4 Clutch Adjustment
Test the operator clutch adjustment:
CAUTION: Keep pedestrians and vehicles clear of the gate whiletesting clutch!Place an immobile object along the gate path, allowing the gate to strikeit while in the openand closecycles. The clutch mustslip and the gatemustreverse direction after striking the object. If it does not, readjustthe clutch. Repeat this test until the correct clutch adjustment has beenachieved. The operator will assume a soft shutdown after striking andreversing the gate which will require a key switch command to cycleoperator again.
1
2
3
4
In addition to the inherent reverse sensor, this operator is equipped with a mechanical slip clutch (UL 325 Type C) to further reduce thepossibility of injury should an entrapment occur. DO NOTover tighten the clutch to compensate for a gate that is damaged, poorly constructedor too heavy. Over tightening the clutch would create a hazardwhich could result in serious injury or death to persons who may becomeentrapped.
Hex Bolt
MagneticSpring Assembly
To adjust clutch:
Hex nut is connected to black plastic magnet holder.
Important Note:2 magnetic sensorslocated on the bottom ofthe circuit board sense when the magnetic spring assembly isslipping during operation. Keep all high voltage wires away fromthe 2 sensors to avoid any electrical interference between thesensors and magnets.
Note:After power has been turned back on, the first open command willautomatically run the multiple gate cycles to locate and remember the openand close gate positions (See section 3.3 on previous page).
Make sure power to operator is OFF when adjusting clutch.
Hold large pulley to loosen the hex bolt counter clockwise.
Magnetic spring assembly can now be loosened (counter clockwise) or tightened(clockwise) to adjust the clutch.
Tighten the hex bolt to lock assembly after adjustment.
3.5 Inherent Reverse Sensor Adjustment
Test the operator reversing sensitivity:
Press the Key Switch button to cycle the gate.
While gate is cycling, slowly rotate reverse sensor clockwise until the gate reverses direction.Rotate reverse sensor back counter-clockwise approximately 1/8 turn.
Cycle the gate a few times to be sure that it cycles completely.
Place an immobile object along the gate path, allowing the gate to strike it while in the openand closecycles. The gate must reverse directionafter striking the object. If it does not, increase the reverse sensitivity (step ) and repeat this test until the correct sensitivity has been set. Theoperator will assume a soft shutdown after striking and reversing the gate which will require a key switch command to cycle operator again.
1
2
2
3
Min MaxSensitivityKey Switch
ReverseSensitivity
Note: Each operator must be individuallyadjusted if dual operators have been installed.
Ideal Clutch Adjustment:The operator will cycle the gate withoutthe clutch slipping. The clutch
willslip and the gate will reverse ONLYafter striking an obstruction with no more than 75 Lbs of force.This force can be measured with a gate scale, DoorKing P/N 2600-225.
This vehicular gate operator is equipped with an inherent adjustable reversing sensor (Type A) used as the primary entrapment protectionsystem according to UL 325 standards. The gate will reverse direction after physically encountering an obstruction in either theopening or closing gate cycle.
If the Auto-Close Timer (DIP-switch SW 1, switch 2) is ON and the gate physically encounters an obstruction during the CLOSING cycle, itwill reverse to the open position andHOLDthe gate at this position (Soft shutdown condition). Another input command is needed before thegate will reset and close again.
If the Partial Open Feature is being used and the gate physically encounters an obstruction during the CLOSING cycle, the gate will onlyreverse to the FULLopen position and NOTthe partial open position.
For the reverse system to function correctly, the gate must be properly installed and work freely in both directions. The clutch must beproperly adjusted before adjusting the reverse sensor.
-
8/13/2019 9150-065-W-3-13.pdf
29/52
9150-065-W-3-13 27
ON
ON
REVERSESENSITIVITY
REVERSELOOP
EXITLOOP
KEY SWITCH
DOORKING4602-010
SW1 SW2
OPENTIMER
NC
NO18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Note: The 5-pin terminal can be unpluggedfrom circuit board for easy wire connections.
All inputs are normally open (NO).
5-Pin UL 325 TerminalSecondary Entrapment Protection
Device Connection
115 VAC Convenience
Outlets
Secondary Entrapment Protection Devices:In addition to the inherent reversing sensor system, the Model 9150 has a 5-pin UL 325 terminal for the connection of photo sensors-Type B1and reversing edges-Type B2 secondary entrapment protection devices required by UL 325 standards. Entrapment protection devices mustbe installedto reduce the risk of injury. Install these devices where the risk of entrapment or obstruction exists while the gate is moving.The Model 9150 offers numerous options to meet your specific needs. The next 2 pages show wiring and typical positioning of the entrapment
protection devices but specific installations will vary.
OPEN Entrapment Sensor
CLOSE Entrapment Sensor
OPEN Contact Sensor
CLOSE Contact Sensor
Low Voltage Common
SECTION 4 - ENTRAPMENT AND SAFETY PROTECTION
4.1 UL 325 Terminal Description
Closed Gate
Wall / Fence
Opening-Direction Photo Beam
Wall / Fence
Filler Post if necessary
Gate Support Post if Installed
Closed Gate
Wall / FenceClosing-Direction Photo Beam
Closed Gate
Wall / Fence
CLOSE Entrapment Sensor (Photo Sensor):Obstructedclosing-direction photo beam will stop the gate during theclosing-direction only.Gate will resume the close cyclewhen the obstructed photo beam has been cleared.
Closed Gate
Low Voltage Common:Common terminal for all the secondary entrapment protection device inputs.
CLOSE Contact Sensor (Reversing Edge):Obstructed closing-direction reversing edge will stop, then reverse the gate to the open position, during theclosing-direction only.
After the gate reverses to the open position, the timer willautomatically close the gate (if it is turned on). If theclosing-direction reverse edge is activated a secondtime prior to the gate reaching theclose position, the operator will stopand enter a soft shutdown condition (See page 36).
When the closing-directionreversing edge gets obstructed and the gate is traveling back to the openposition and the opening-directionrevering edge gets obstructed, the gate will stopand enter a soft shutdown condition (See page 36).
1
2
3
4
5
OPEN Entrapment Sensor (Photo Sensor):Obstructedopening-direction photo beam will stop the gate during theopening-direction only.Gate will resume the open cyclewhen the obstructed photo beam has been cleared.
OPEN Contact Sensor (Reversing Edge(s)):Obstructed opening-direction reversing edge(s) will stop, then reverse the gate to the close position during theopening-direction only.
After the gate reverses to the full close position, anyopening input will cycle the gate again. Note: If the gate isopening by a time clock and an opening-direction reversingedge gets obstructed, the gate will return to the closedposition and another input (automatic exit loop, reverse loop. etc.) is needed to cycle the gate openagain.
When the opening-directionreversing edge(s) gets obstructed and the gate is traveling back to the close position andthe closing-direction reversing edge gets obstructed, the gate will stopand enter a soft shutdown condition (See page 36).
Opening-Direction Reversing Edges
Closing-Direction Reverse Edge
Entrapment Area
Entrapment Area
Entrapment Area
Entrapment Area
1
2
3
4
5
WARNING
MOVINGGATECANCAUSE
Operate gateonlywhen gate areai s insi ght
and free of people andobstructions.
Donot allowchi ldrentoplayin gate area
or operate gate.Do notstand ingate pathorwal kthrough
path while gate ismoving.
Readowners manual and safety instructions.
SERIOUS INJURY OR DEATH
CLASS
CERTIFIED
TO
CAN/CSAC22.2NO.247
CONFORMSTO
ANSI/UL-325
VEHICULARGATE OPERATORHP
53382
MODELSERIALVOLTS
PHASE
AMPS
60Hz
MAXGATELOADDoorKing, Inc., Inglewood, CA
ON
ON
REVERS
E
SENSITI
VITY
REVERSE
LOOP
EXITLOO
P
KEYSWIT
CH
DOORKI
NG
4602-0
10
SW1SW2
OPENTIME
R
NC
12345
NO
-
8/13/2019 9150-065-W-3-13.pdf
30/52
9150-065-W-3-128
ON
EXITLOOP
4602
SW1NC
NO18
17
16
15
14
13
12
11
10
9
8
76
5
4
3
2
1
1
2
34
5
GateFrame G
ateFrame
Non-Secure SideOutside Property
Secure SideInside Property
Filler Post or Barrier
Reversing Edge (Open Contact Sensor)
4.2 Secondary Entrapment Protection Device LocationsTypical UL Photo Sensor mounting heightand distance away from gate.
If the distance between the gateand wall is greater than 2 1/4.
Wall
ULsensormountedonpost.
ULsensormountedonwall.
A filler post or barrier may need to be installed between thegate and wall area to reduce the distance to 2 1/4 or less.A reversing edge should be installed on the post or barrierfor safety (See page 4 for more information).
Photo Sensors (With Filler Post and Reverse Edge) Sample Setup
Closed Gate
Wall
Normally Open
Normally Open
Normally Open
Common
Common
Normally Open
Photo Sensor Power Note:Photo sensors can be powered by the built-inconvenience outlets located on the operator (See previous page).
Closing-direction photo sensors wired to UL 325 terminal.
Closing-Direction Photo Beam
Opening-Direction Photo Beam
5-Pin UL 325 Terminal Wiring
Reverse Closing-Direction Option
Filler Post with Opening-Direction Reversing Edge (If necessary, see above)
OPEN Entrapment SensorCLOSE Entrapment Sensor
OPEN Contact Sensor
CLOSE Contact Sensor
Low Voltage Common
IFthe closing-direction photo sensor is wired to the UL 325 terminal, aclosing-direction photo beam that gets obstructed will STOPthe gate, thenresume closing the gate when the obstructed photo beam has been cleared.
IFthe closing-directionphoto sensor is wiredto the #6 main terminal,a closing-directionphoto beam that getsobstructed willREVERSEthe gate backto the open position.See pages 31 and 32for more information.
12
34
5
ON
1
2
3
4
5
6
7
8
SW 2
SW 2, switch 2must be OFF.
Main Terminal
Photo sensors may be installed on either side of gate frame, as close aspractical to the gate but no further away than 5.
No higher than27.5 above grade.
21 is typical formost installations.
Note: Additionalphoto sensors canbe added abovethe 27.5 height.
5
orLess
5
orLess
-
8/13/2019 9150-065-W-3-13.pdf
31/52
9150-065-W-3-13 29
ON
EXITLOOP
4602
SW1NC
NO18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
ON
EXITLOOP
4602
SW1NC
NO18
17
16
15
14
13
12
11
10
9
8
7
65
4
3
2
1
Wireless Reverse Edge Sample Setup - Single Receiver
Photo Sensor and Wireless Reverse Edge Sample Setup
Closed Gate
Wall
Normally Open
Common
Normally Open
Install Jumper Wire
Normally Open
Normally Open
Common
Filler Post Note:Install reversing edges on allthe gate support posts or filler post in this area(e.g. cantilever gate installations, See below).
Wireless Note:Refer to theinstruction sheet that comeswith the receiver/transmitterfor more specific wiring andmounting instructions.
Closing-DirectionReversingEdge
Closing-DirectionReversingEdge
Opening-Direction Reversing Edge
5-Pin UL 325 Terminal Wiring
Opening-Direction Reversing Edge (If filler post is used).
9 V battery operated transmitter mounted on gate.
Filler Post(If necessary)
EdgeTransmitter
Coax Antenna KitP/N 1514-073
Com
Com
Antenna mountedoutside operator cover.
24 VAC Receiver
Place receiver in operator.
5-Pin UL 325 Terminal Wiring
Normally Open
NormallyOpen
Common Com
Opening-Direction Photo Beam
Normally Open
Common
Wireless Note:Refer to theinstruction sheet that comeswith the receiver/transmitterfor more specific wiring andmounting instructions.
24 Volt
24 Volt
24 VAC Receiver
Place receiver in operator.
Photo Sensor Power Note:Photo sensors can be poweredby the built-in convenienceoutlets located on the operator(See page 27).
Install Opening-Directionreverse edges on the gate
support post(s) in this area.Cantilever Gate
Coax AntennaKitP/N 1514-073
Antenna mountedoutside operatorcover.
OPEN Entrapment Sensor
CLOSE Entrapment Sensor
OPEN Contact Sensor
CLOSE Contact Sensor
Low Voltage Common
OPEN Entrapment SensorCLOSE Entrapment Sensor
OPEN Contact Sensor
CLOSE Contact Sensor
Low Voltage Common
Power islimited to250 mamps.
Power is limitedto 250 mamps.
MainTerminal
MainTerminal
EdgeTransmitter
9 V battery operatedtransmitter mounted on gate.
1
2
3
4
5
12
3
4
5
When either direction reversingedge gets obstructed, the gate willSTOPand reverse direction.
When a reversing edge gets obstructed, thegate will STOPand reverse direction. Whena photo beam gets obstructed the gate willSTOP,then continue in the same directionafter obstructed photo beam has beencleared until the gate cycle is complete.
-
8/13/2019 9150-065-W-3-13.pdf
32/52
9150-065-W-3-130
9410
Reverse
4Ft.min.toavoi
dgate
movem
entinterference.
4Ft.min.toavoid
reverseloopinterference.
4Ft.min.toavoidgate
movem
entinterference.
Reverse
AutomaticExit
Note: Loop detector wiring is shown forDoorKing plug-in loop detector P/N 9410-010(Single Channel) only. If other loop detectorsare used, refer to the installation instructionssupplied with those detectors for wiring andseparate power instructions.
9410
Single Channel Single Channel
ON
ON
REVERSESENSITIVITY
REVERSELOOP
EXITLOOP
KEY SWITCH
DOORKING4602-010
SW1 SW2
OPENTIMER
NC
1
2
3
4
5
NO18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Loop
Lead
InWire
s
Loop
Lead
InWire
s
DoorKingPlug-in
Loop DetectorsAB
Note: The plug-in exit loop detector can
be wired to partially open gate 14-Ft. ifSW 2, switch 1 is turned OFF. A jumperwire must be connected from terminal#10 to terminal #5 (See next page formore information).
ON
1
2
3
4
5
6
7
8
SW 2
SW 2,switch 1must beONto fullyopen gate(Normalfunction).
B
LOOP1
PVC Conduit
Pa
rtialOpen
Automatic Exit LoopAutomatically opens the gate for exiting vehicleswithout having to use a transmitter or keypad. Theexit loop can be placed a minimum of 4 feet awayfrom the reverse loop or far enough away from thegate so the gate has started or completely opened
by the time you drive up to it (Free exit).
Exit loop lead-inwires are twistedapprox. 6 twistsper foot.
To help protect the operator from accidentally closing on vehicles in the gates path, DoorKing highly recommends that loopsand loop detectors be installed. Loops are laid underneath, cut into asphalt or concrete driveways or buried beneath gravel andearth driveways. A loop detection system will sense a vehicle like a metal detector and send a signal to the gate operatorpreventing the gate from automatically opening or closing on a vehicle when it is in the gates path. DoorKing recommends thata licensed installer perform this work.
DoorKing offers a free Loop andLoop-Detectors InformationManual PDF located atDoorkings web site for moreinformation. www.dkaccess.com
4.3 Loop Detector Wiring
Reverse LoopsReverse loops are placed on eachside of the gate to prevent the gate fromclosing on a vehicle in the gates path. They willreverse ORstop the cycling of the gate while avehicle is in or near the gates pathway.
ON
1
2
3
4
5
6
7
8
SW 2
Reverse looplead-in wires aretwisted approx.6 twists per footand are wired inseries.
A
LOOP1
PVC Conduit
Note: See page 24,SW 2, switch 2 forreverse loop
options.
-
8/13/2019 9150-065-W-3-13.pdf
33/52
9150-065-W-3-13 31
5.1 Main Terminal Description
15
10
6
5
Low Voltage Common
LED Indicator Output
Dry Relay Contact
Gate Tracker - Data
Gate Tracker - Busy
Entrapment Alarm
Alarm Reset
3-Button Close(DoorKing 3-Button station ONLY)
Exit Loop Logic Output(DoorKing Loop Detectors ONLY)
3-Button Full Open(DoorKing 3-Button station ONLY)
Dry Relay Contact
24 VAC - 250 mamp max.
Full Open
Partial Open
Standard Reverse or Stop
Not Used
Low Voltage Common
Full Open
KEY SWITCH
4602
NC
NO18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
When gate is closed, this input will fully opengate. When gate is open and auto close timer SW 1,switch 2 is turned ON, input will re-set and holdtimer.
When gate is open and auto close timer SW 1,switch 2 is turned OFF, input will close gate. When gate is closing, input will reverse gate.
ON
1
2
3
4
5
6
7
8
SW 1
17
Provides 24 VDC, 250 ma. maximum to powerLED. Operation of LED is dependent on setting ofSW 1, switches 4 and 5 (See page 23).
ON
1
2
3
4
5
6
7
8
SW 1
Operation of relay is dependent onsetting of SW 1, switches 4 and 5.Relay contacts can be set for Normally
Open (NO) or Normally Closed (NC)operation.Contact rating is 1 ampmaximum at 24-volts DC.
ON
1
2
3
4
5
6
7
8
SW 1NO
NC
4
This input ONLY fuctions when gate is fullyopenedor in the closing cycle.
When gate is open: auto close timerSW 1,switch 2 is turned ON, input will re-set and holdtimer.When gate is open: auto close timerSW 1,switch 2 is turned OFF, input will prevent gatefrom closing.
When gate is closing: input will stopgate whenSW 2, switch 2 is ON. When gate is closing: input will reversegatewhen SW 2, switch 2 is OFF.
ON
1
2
3
4
5
6
7
8
SW 2
ON
1
2
3
4
5
6
7
8
SW 1
JumperWireSW2,switch2OFF(DualOperators
only)
JumperWireSW2,switch2OFF(ExitLoopPartia
lOpen)
For long gate application. SW 2, switch 3must be OFF. Same operation as #4terminal above but will only open a closedgate 14-Ft. or reverse a closing gate to the14-Ft. open position.
ON
1
2
3
4
5
6
7
8
SW 2
ON
1
2
3
4
5
6
7
8
SW 2
-Terminal #10 connected to terminal #5 will PARTIALLYopenplug-in exit loop detector (Single channel) for a single operator.
-Terminal #10 connected to terminal #4 will FULLYopenbi-parting gates. Dual operators ONLY using DoorKingsplug-in DUAL channel loop detector.(Page 34).
lf SW 2, switch 1 is ON, the plug-in exit loop detector(Single channel) will FULLYopen the gate (Normal Setting).Single operator use ONLY.
lf SW 2, switch 1 is OFF, the normal exit loop portfunction is bypassed and a jumper wire is needed to openand close gate(s) for certain applications:
SECTION 5 - WIRING
-
8/13/2019 9150-065-W-3-13.pdf
34/52
9150-065-W-3-132
KEY SWITCH
4602
NC
NO18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Optional REVERSES GATE forClosing Direction Photo Sensors
Functions ONLYduring gate closing cycle.
SW 2, switch 2: After photo sensor beamgets obstructed:
OFF Setting - REVERSES GATE.
ON Setting -Stops gate then continuesclosing when gate is clear (Same functionas UL 325 terminal #2).
Note: The ONsetting is used to help prevent tailgatingbut the photo sensor should be wired to the UL 325terminal #2 when the stop gatefunction is desired,see page 28 for more information.
WARNING
MOVING GATECAN CAUSE
Operategateonlywhengatearea is insight
and freeofpeople andobstructions.
Donotallowchildren toplay ingatearea
or operategate.Donotstandingate pathor walkthrough
pathwhil egateismoving.
Readownersmanual andsafety instructions.
SERIOUS INJURY OR DEATH
CLASS
CERTIFIED TO
CAN/CSAC22.2 NO. 247
CONFORMSTO
ANSI/UL-325
VEHICULARGATEOPERATORHP
53382
MODELSERIALVOLTS
PHASE
AMPS
60Hz
MAXGATELOADDoorKing, Inc., Inglewood, CA
ON
ON
REVERS
E
SENSITI
VITY
REVERS
E
LOOP
EXITLOO
P
KEYSW
ITCH
DOORKIN
G
4602-01
0
SW1
SW2
OPEN
TIMER
NC
12345
NO
5.2 Control Wiring for Single/Primary Operator
ON
1
2
3
4
5
6
7
8
SW 2
Red Full Open
Green Close
White Com
Key Switch
Stand-AloneKeypad
Stand-AloneCard Reader
TelephoneEntry
Fire Box
3-Button Control StationDoorKing ONLY
Note:All stand-alone andtelephone entrydevices must use aseparate powersource.
#4-Connected device fully opens gate.#5-Connected device opens gate 14-feet.
#2-Full Open
Com
Com
Com
Relay - #2 - Full Open. #5 - Opens 14-feet.
Relay N.O. - #2 - Full Open. #5 - Opens gate 14-feet.
250 mamp.max.
3-Wire Radio Receiver
ON
1
2
3
4
5
6
7
8
SW 2
SW 2,switch 3must beOFF.
Relay Com
24 Volt Com
24 Volt - 250 mamp. max.
4-WireReceiver
#5 Terminal Note (Single Operator Only):Any opening device connected to terminal #5
will open the gate to the partial open 14-ft setting.Secondary entrapment protection devices will alsoopen the gate to the partial open setting. If theInherent Reverse Sensorgets activated during theclose cycle, it will always fullyopen the gate.
24 volt
Full Open
Full Open
Partial Open
Wiring opening device when usingManual Mode Operation forconvenience open operator(s):The opening device should be wired
to the 2340 circuit board whenusing the convenience opensystem to manually openthe gate(s) during a powerfailure. This will allow normaldaily operation as well as ACpower failure operation. Thisshould ONLY be wired thisway when operating in themanual mode withconvenience open operators(See page 39 for more info).
Important:Controls intended for user activation must be located at least six (6) feet away from any moving part of the gate and where the user is prevented fromreaching over, under, around or through the gate to operate the controls. Emergency access controls only accessible by authorized personnel (e.g., fire, police,
EMS) may be placed at any location in theline-of-sight of the gate.
-
8/13/2019 9150-065-W-3-13.pdf
35/52
9150-065-W-3-13 33
KEY SWITCH
4602
NC
NO18
17
16
15
1413
12
11
10
9
8
7
6
5
4
3
2
1
5.3 Auxiliary Device Wiring
Gate Tracker(Quad Box Shown)
Remote Alarm Reset Station(DoorKing P/N 1404-080 Only)
MUST be located in the line-of-sightof the gate and no further than 50 feetfrom the gate.
Red Alarm Output Terminal
Blue Alarm Reset Terminal
White Common Terminal
DoorKing Access Control System (Model 1833, 1835, 1837 or 1838)tracker system can be connected.This system can keep track of gateoperatorcycle count, shorted inputs, loop detector problems, any forced entry
attempts, if the gate has struck anything during the open or close cycle,power interruptions, etc.For more detailed information refer to the Tracker Installation and WiringManual, DoorKing P/N 2351-010.
Terminal #4 (Full open) or #5 (14-Ft. open) required only if the trackerboard will activate the gate operator. Refer to the manual 2351-065 fordetailed information.
-
8/13/2019 9150-065-W-3-13.pdf
36/52
9150-065-W-3-134
ON
EXITLOOP
KEY SWITCH
4602
SW1NC
NO18
17
16
15
14
13
12
1110
9
8
7
6
5
4
3
21
KEY SWITCH
4602
NC
NO18
17
16
15
14
13
12
1110
9
8
7
6
5
4
3
21
Open Photo
Close PhotoOpen EdgeClose Edge
Common
Open Photo
Close PhotoOpen EdgeClose Edge
Common
UL 325Terminal
UL 325Terminal
SecondaryOperator
PrimaryOperator
To Close Photo #2 To Close Photo #2
To Close Photo #2To Open Edge #3
To Open Edge #3
ToCommon#5
ToCommon#5
To Open Photo #1 To Open Photo #1
Fence
Gate
Opening Non-Contact Sensor
Closing Non-Contact Sensor
Opening Contact Sensor Opening Contact Sensor
Opening Non-Contact Sensor
Fence
Gate
Convenience Open Note:The gray wire is needed when using theconvenience open in the manual mode(See page 40 for wiringinformation about Wiring dual operators in manual mode).
5.4 Bi-Parting Gates Wiring - Dual Gate Operators
Secondary Entrapment Protection Devices for Bi-Parting Gates Separate power source for photo sensors (See page 27).
Interconnection CableSold separately from DoorKing.
6 wires used (8 - 18 AWG wires total).
Reverse loop lead-inwires are wired in series.
When using DualChannel plug-inloop detector.Connect #4 to #10:fully opens gates.
SW 2, switch 1must be OFF.
Plug into PrimaryOperator Exit Loop Port
Dual Channel9409