    VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page

    Licenced to: Sevo Systems, Inc. Serial no: [dong

    File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results 6/16/2

    Project: Quipus

    Project-No: 9044_1_1

    Building: Kallutaca

    Object: Data Room

    Contractor: ISTC

    Owner: Telis S.R.L.

    Project engineer: mrg

    Date: 6/16/2015

    Regulation rule for calculation of FK-5-1-12 quantities: NFPA 2001, Edition 2012

    Altitude above sealevel: 3650 m

    Atmospheric correction factor: 0.660

    Project description:1 x 1.5" 180 Sidewall Nozzle 10108

    1 x 1.0" 180 Sidewall Nozzle 10110

    Pipe catalogue: schedule40.rkl

    Component catalogue: SEVOcomp_1_2.arm

    Nozzle catalogue: SEVO.noz

  • 7/25/2019 9044_1_1 Quipus - Telis S R L - ISTC (00000003)

    2/9

    VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page

    Licenced to: Sevo Systems, Inc. Serial no: [dong

    File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results 6/16/2

  • 7/25/2019 9044_1_1 Quipus - Telis S R L - ISTC (00000003)

    3/9

    VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page

    Licenced to: Sevo Systems, Inc. Serial no: [dong

    File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results 6/16/2

    Pipesystem data:

    Section- Starting- Endnode Length Height Pipetype Diameter Fitting Component Nb of containers

    No: node [m] [m] [mm] ** * code coefficient FK-5-1-12 quant

    1 0 3 0.953 0.953 10 5/4 C 165 1.600 1.0

    2 3 4 0.164 0.000 13 5/4 E - - 0.0

    3 4 5 2.347 2.347 13 3/2 E - - 0.0

    4 5 6 2.560 0.000 13 3/2 E - - 0.0

    5 6 7 0.200 0.000 13 3/2 T-0 - - 0.0

    6 7 10108 0.500 -0.500 13 3/2 E - - 0.0

    7 6 9 0.150 0.000 13 1 T-90 - - 0.0

    8 9 10110 0.100 -0.100 13 1 E - - 0.0

    * C=Component, B=Bend, T=T-Piece, E=Elbow

    ** If a pipe diameter is equal zero see the extra table of the calculated diameters

    Legend of pipetypesType Pipeclass Pipe roughness

    10 schedule 40 smooth

    13 schedule 40 black pipe

    Legend of componentsCode Type Resistance coefficient

    165 SEVO 164 LB/1 1/4" (CV14817) W/ 1 1/4" Flex Hose 1.600

    Nozzle data:

    No. Calculation zone Diameter [mm]

    10108 Main 15.3

    10110 False Ceiling 6.0

    Legend of nozzles:Type Number of C1 C2 C3 C4 C5 C6

    orifices

    1 Nozzle 1 1 0.10652 0.26900 0.23203 -0.20251 0.00000 0.00000

  • 7/25/2019 9044_1_1 Quipus - Telis S R L - ISTC (00000003)

    4/9

    VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page

    Licenced to: Sevo Systems, Inc. Serial no: [dong

    File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results 6/16/2

    Calculation zone data:

    Calculation of design quantity:

    Zone Total Volume of Calculated Total Max. Over- Design Extinguish- Design Design Designvolume building volume surface pressure temp. conc. factor conc. quantity[m3] parts [m3] [m3] [mbar] [C] [% Vol] [% Vol] [kg]

    1 Main 93.3 0.0 93.3 130.2 1.000 20.0 3.5 1.35 4.7 42.48

    2 False Ceiling 12.9 0.0 12.9 73.4 1.000 20.0 3.5 1.35 4.7 5.86

    Regulation rule for calculation of FK-5-1-12 quantities: NFPA 2001, Edition 2012

    Calczone no. 1: Class C Fire, NFPA 2001 (Edition 2012)

    Calczone no. 2: Class C Fire, NFPA 2001 (Edition 2012)

    Altitude above sealevel: 3650.0 m

    Atmospheric correction factor: 0.660

    FK-5-1-12 storage input data:

    Container volume: 62.0 l

    Maximum filling ratio of a container: 1.200 kg/l

    Filling pressure: 25.0 bar abs

    Storage temperature: 20.0 C

    Supplement factor: 1.01

    Minimum storage quantity: 48.39 kg

    Number of containers: 1

    Discharge time (input value): 10.0 s

    Further information:

    Design with included gas discharge time

    Design with predeterminated orifice diameters

  • 7/25/2019 9044_1_1 Quipus - Telis S R L - ISTC (00000003)

    5/9

    VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page

    Licenced to: Sevo Systems, Inc. Serial no: [dong

    File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results 6/16/2

    Calculation result s:

    FK-5-1-12 storage data:Design quantity: 48.3 kg

    Supplement factor: 1.01

    Minimum storage quantitiy: 48.8 kg

    Container volume: 62.0 l

    Filling ratio: 0.79 kg/l

    Filling pressure: 25.0 bar abs

    FK-5-1-12 -mass per container: 48.8 kg

    Number of containers: 1

    Actual storage quantity: 48.8 kg

    Storage temperature: 20.0 CStarting container pressure: 25.0 bar abs

    Discharge time:

    Discharge time air: 0.2 s

    Total gas discharge time: 0.4 s

    Two-phase discharge time: 8.7 s

    Total discharge time: 9.1 s

    System information:

    Container working pressure: 14.4 bar abs

    Container working temperature: 20.0 C

    Total network volume: 8.6 l

    Medium pipe content: 13.1 kg FK-5-1-12

    Filling portion in pipe system: 0.27 kg FK-5-1-12 /kg FK-5-1-12 -storage

  • 7/25/2019 9044_1_1 Quipus - Telis S R L - ISTC (00000003)

    6/9

    VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page

    Licenced to: Sevo Systems, Inc. Serial no: [dong

    File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results 6/16/2

    Pipe system:

    Section- Starting- Endnode Pressure Flowrate PipedimensionNo: node [bar abs] [kg/s] Di [mm] DN

    1 0 3 14.02 5.24 35.1 --

    2 3 4 13.80 5.26 35.1 --

    3 4 5 13.30 5.26 40.9 --

    4 5 6 13.14 5.26 40.9 --

    5 6 7 13.11 4.62 40.9 --

    6 7 10108 13.11 4.62 40.9 --

    7 6 9 13.05 0.65 26.6 --

    8 9 10110 13.04 0.65 26.6 --

    Tee split table

    T-Type Flow in 1th Flow out 2nd Flow out Regulatio

    Section Flow Section Flow Split Section Flow Split conform

    No. kg/s No. kg/s % No. kg/s %

    Side Tee 4 5.26 5 4.62 87.833 7 0.65 12.357 Yes

  • 7/25/2019 9044_1_1 Quipus - Telis S R L - ISTC (00000003)

    7/9

    VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page

    Licenced to: Sevo Systems, Inc. Serial no: [dong

    File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results 6/16/2

    Nozzle data:

    Calculation- Nozzle Nozzle Number of Pipeconnection Orifice FK-5-1-12 ozone no: no. type orifices Di [mm] DN [mm] put [kg]

    1 10108 1 1 40.9 -- 15.3 42.6

    2 10110 1 1 26.6 -- 6.0 6.0

    Two-phase discharge time: 8.7 s

    MAXIMUM TRANSPORT TIME DIFF. BETWEEN NOZZLES: 10110./ 10108. IS 0.14 S

    Calculation- Nozzle Outlet velocity Transport Jetdistance Evaporationzone no: no. [m/s] time [s] [m] distance [m]

    1 10108 15.5 2.49 5.6 4.9

    2 10110 24.9 2.35 3.1 1.7

  • 7/25/2019 9044_1_1 Quipus - Telis S R L - ISTC (00000003)

    8/9

    VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page

    Licenced to: Sevo Systems, Inc. Serial no: [dong

    File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results 6/16/2

    Concentrations:

    Calculation- Gascomposition after discharge [%]zone no: O2 FK-5-1-12 N2

    1 19.9 4.7 74.4

    2 19.9 4.8 74.4

    Pressure relief opening :

    Calculation- Recommended area against overpressurezone no: Area [m] Overpressure [mbar] Max. flow [kg/s]

    1 0.055 1.0 4.6

    2 0.008 1.0 0.6

  • 7/25/2019 9044_1_1 Quipus - Telis S R L - ISTC (00000003)

    9/9

    VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page

    Licenced to: Sevo Systems, Inc. Serial no: [dong

    File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results 6/16/2

    Component list:

    Component Number Code Coefficient

    SEVO 164 LB/1 1/4" ( 1 165 1.600

    Nozzle-type Number C1 C2 C3 C4 C5 C6

    1 2 0.10650 0.26900 0.23200 -0.20250 0.00000 0.00000

    Pipe-type Di [mm] DN Length [m]

    10 35.10 5/4 1.000

    13 35.10 5/4 0.20013 40.90 3/2 5.600

    13 26.60 1 0.200

    Number of bends (+) and elbows (-)

    Bend-type Di [mm] DN Number

    -90 35.10 5/4 1

    -90 40.90 3/2 3

    -90 26.60 1 1

    Number of T-distributors (in- and outdiameter)

    Number Input 90-out 90-out 0-out

    1 40.9 26.6 0.0 40.9