Plaza on the Green 03/21/17 8800 Firethorn Lane Lincoln, Nebraska TCEP Project No.: 067-001-16 ADDENDUM NO. 2 ADD2-1 ADDENDUM NO. 2 The Architect/ Engineer issues this addendum, applicable to the above named project, to all known Contractors before receipt of proposal. This addendum includes Item Number 2-1 thru 2-32. This addendum item shall be fully incorporated into the Bidding/Contract Documents and have the same force and effect as though originally included. The Bidder shall acknowledge receipt of this Addendum No. 2 on the Bid Proposal Form in the place provided. GENERAL Item 2-1: Bidder Question: Site furnishings are not labeled on the drawings. Response: No site furnishings are included in this drawing package. Item 2-2: Bidder Question: We saw there are not bid bonds required. Are we to include costs for Performance and Payment bonds in our bid? Response: Refer to specification section 00 11 13, section 1.7.A. General Contractor to include costs in their bid amount associated with this requirement. Item 2-3: Bidder Question: In specifications and F0.0 plan that there are to be fabric hanging panels, custom upholstered items and Ripplefold drapery. However we are having a hard time confirming the locations and layout for these items on the plans. Are we missing it or can you provide clarification? Response: As noted on Finish Plans, see F1.00 for DF-1 and F1.02 for DF-2 and FHP. Custom upholstered bench shown in elevation #7, Sheet A6.60. Item 2-4: Bidder Question: The specs are listing some 3m window film to be installed on this project. Could you clarify the location for these installations? Response: The 3M film is not in this construction package, will be provided by Demountable Walls contractor. Item 2-5: Bidder Question: Corner guards (CG-1, CG-2 & CG-3), marker boards (MB-1 & MB-2) and fabric acoustical panels (FAP-1) are listed in the legend of the finish drawings, but locations and quantities are not shown. Please provide additional information. Response: No MB-1, MB-2 or FAP-2 are shown in drawings, remove reference from Finish Equipment List. Corner guards will be added to Finish Sheets in future addendum. Item 2-6: Pre-Bid Attendance Sign-In sheets for the March 17, 2017 pre-bid meeting are attached.

Transcript of 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door...

Page 1: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/21/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

ADDENDUM NO. 2 ADD2-1

ADDENDUM NO. 2 The Architect/ Engineer issues this addendum, applicable to the above named project, to all known Contractors before receipt of proposal. This addendum includes Item Number 2-1 thru 2-32. This addendum item shall be fully incorporated into the Bidding/Contract Documents and have the same force and effect as though originally included. The Bidder shall acknowledge receipt of this Addendum No. 2 on the Bid Proposal Form in the place provided.

GENERAL

Item 2-1: Bidder Question: Site furnishings are not labeled on the drawings.

Response: No site furnishings are included in this drawing package.

Item 2-2: Bidder Question: We saw there are not bid bonds required. Are we to include costs for Performance and Payment bonds in our bid?

Response: Refer to specification section 00 11 13, section 1.7.A. General Contractor to include costs in their bid amount associated with this requirement.

Item 2-3: Bidder Question: In specifications and F0.0 plan that there are to be fabric hanging panels, custom upholstered items and Ripplefold drapery. However we are having a hard time confirming the locations and layout for these items on the plans. Are we missing it or can you provide clarification?

Response: As noted on Finish Plans, see F1.00 for DF-1 and F1.02 for DF-2 and FHP. Custom upholstered bench shown in elevation #7, Sheet A6.60.

Item 2-4: Bidder Question: The specs are listing some 3m window film to be installed on this project. Could you clarify the location for these installations?

Response: The 3M film is not in this construction package, will be provided by Demountable Walls contractor.

Item 2-5: Bidder Question: Corner guards (CG-1, CG-2 & CG-3), marker boards (MB-1 & MB-2) and fabric acoustical panels (FAP-1) are listed in the legend of the finish drawings, but locations and quantities are not shown. Please provide additional information.

Response: No MB-1, MB-2 or FAP-2 are shown in drawings, remove reference from Finish Equipment List. Corner guards will be added to Finish Sheets in future addendum.

Item 2-6: Pre-Bid Attendance

Sign-In sheets for the March 17, 2017 pre-bid meeting are attached.

Page 2: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/21/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

ADDENDUM NO. 2 ADD2-2

Item 2-7: Building Permit

Drawings are currently submitted to the City for permitting. Owner is covering the cost of the building permit.

SITE

Drawings

Item 2-8: Sheet L2.01 Site Details

Sheet reissued in its entirety

Item 2-9: Sheet L6.05 Site Details

Sheet issued in its entirety

ARCHITECTURAL

Specification

Item 2-10: Section 08 71 00 Door Hardware

Door Hardware Schedule Added

Item 2-11: Section 09 51 13 – Acoustical Panel Ceilings

Substitution Request for WCS-1: Armstrong Wood Works Linear Solid Wood Panels in 3” plank widths approved as equal. Rulon Linear Open wood ceilings Rulon Cliprail in 3-3/4” board widths approved as equal.

Item 2-12: Section 10 22 39 – Folding Panel Partitions

Substitution Request: Modernfold Acousti-Seal 932 Hinged Pairs is approved as equal.

Item 2-13: Section 14 21 23 Machine Room-Less Elevators

a) Revise Part 1 General, 1.4 Performance Requirements, Section B. System

Performance to include: 8. Speed: 150 fpm

b) Revise Part 2 Products, 2.1 Manufacturers, Section A.1. to read: 2.1.A.1 Passenger Elevator Basis of Design: EcoSpace traction elevators by KONE, Inc.

a. Capacity: 3000 lb. b. Opening Type: SSP-CO c. Car Height: 8’ d. Entrance Height: 7’ e. Speed: 150 fpm

Page 3: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/21/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

ADDENDUM NO. 2 ADD2-3

c) Substitution Requests for Machine Room Less Elevator: Otis Elevator Company Gen 2 MRL traction elevator is approved as equal. ThyssenKrupp Synergy self-supported MRL traction elevator is not approved as equal.

Drawings

Item 2-14: Sheet A1.20 – Lower Level Reflected Ceiling Plan

West exterior soffit labeled as WSC-1 should read “Wood”, refer to specification section

06 20 13 “Exterior Finish Carpentry” for Hardwood Soffits.

Item 2-15: Sheet A1.21 – Main Level Reflected Ceiling Plan

North and South exterior soffits labeled as WSC-1 should read “Wood”, refer to

specification section 06 20 13 “Exterior Finish Carpentry” for Hardwood Soffits.

Item 2-16: Sheets A2.10 & A2.11 – Exterior Elevations

Added Precast notes, see attached drawings.

Item 2-17: Sheets A6.20 – Interior Elevations

Removed elevations not needed, added notations and section tags to elevations. See

attached drawing.

Item 2-18: Sheet A6.40 – Door Schedule

Hardware sets added to Door Schedule. Revise doors 114 & 115 to be Door Type ALD-1. See attached Sheets.

STRUCTURAL

Drawings

Item 2-19: Sheet S3.01 – Column & Footing Schedule & Baseplate Details

a) Schedule Grid J-6.7, add the following footing information:

7’-0”x7’-0”x1’-6” DEEP PAD FOOTING W/ 8-#6’s EACH WAY AT TOP & BOTTOM b) Schedule Grid P-11, Revise the following:

Main Level & Upper Level Size: Revise from 8x8x1/2” to 6x6x1/2” BasePlate: Revise from Type B to SEE 8/S3.03

Item 2-20: Sheet S3.03 – Foundation Plan Details

a) Sheet issued in its entirety.

Page 4: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/21/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

ADDENDUM NO. 2 ADD2-4

Item 2-21: Sheet S4.02 – Framing Details

a) Section Detail 19.

1. Revise concrete beam reinforcing note to read: “#3 CLOSED TIE (H=36”) @ 4” O.C. FOR 1’-4” BEYOND EACH END OF EACH OPENING (2 OPENINGS TOTAL) & 12” O.C. BETWEEN w/ 4 - #5 CONT. HORIZONTAL BARS @ TOP & BOTTOM (2 ROWS OF 2), TYPICAL WALL REINFORCING SHALL CONTINUE THROUGH BEAM.

2. Section Detail 19. Revise galvanized bent plate note to read: 3/8”x14 CONT. BENT PLATE w/ 1/4” FITTED STIFFENERS @ 24” O.C. (STIFFENERS SHALL NOT EXTEND INTO VENEER SPACE)

3. Weld at bent plate to embed plate. Delete weld spacing 4. Revise galvanized embed angle note to read: 8x6x5/8”x0’-8” LONG ANGLE

w/ 4-1/2” DIA. X 3” LONG HEADED ANCHOR STUDS SPACED AT 6” O.C. ON HORIZ LEG & 7” O.C. ON VERTICAL LEG, & 2-#4 x 2’-0’ VERT. REBAR WELDED TO VERT. LEG AT 6” O.C. (REBAR SHALL BE ANGLED TO PROVIDE APPROXIMATELY 1”+ COVER @ UPPER END), TYP @ 24” O.C.

MECHANICAL

Drawings

Item 2-22: Sheet M1.01 – Lower Level HVAC Plan

Note 2 shall be revised to the following:

AS PART OF DEDUCT ALTERNATE #1, PROVIDE A COST TO REMOVE ALL MECHANICAL EQUIPMENT BACK TO A SHELL SPACE. THE DUCTWORK SHALL TERMINATE ALONG THE SOUTH WALL OF CONFERNCE ROOM 114 & 115 AND THE EAST WALL OF KITCHEN 111. ANY DUCTWORK EXTENDING INTO CONFERENCE ROOM 114 AND 115 SHALL BE PROVIDED WITH A PAINT GRIP FINISH.

Item 2-23: Sheet M6.03 – Mechanical Details

Refer to detail 9, water service entrance detail. Irrigation tap shall be increased from a 1-

1/2” to 2”. This will also increase the sizes of BFP-4 & WM-2 to 2”.

Item 2-24: Sheet M7.01 – Mechanical Schedules

Refer to Roof Hood and Louver Schedule. Items shall be changed to or equivalent in lieu

of or Approved equivalent as currently listed in schedule.

Item 2-25: Sheet M7.02 – Mechanical Schedules

Refer to Heat Pump Schedule. COA CFM has been updated and electrical requirements

for MCA and MOCP have been added. Remark 11 has been added to HP-25. Sheet reissued to show changes. See attached sheet.

Page 5: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/21/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

ADDENDUM NO. 2 ADD2-5

Item 2-26: Sheet M7.03 – Mechanical Schedules

Refer to HVAC Hydronic and Plumbing Specialties. AS-2 shall have a tank volume equal

to 200 gallons.

Item 2-27: Sheet M7.04 – Mechanical Schedules

Refer Backflow Preventer & Plumbing Fixture Schedules. BFP-4 & WM-2 shall be

increased from 1-1/2” to 2” in size for larger irrigation line.

ELECTRICAL

Specification

Item 2-28: Section 28 31 11 – Fire Alarm System Honeywell shat be added to the list of approved manufacturers. All performances list in the specifications must be met.

Drawings

Item 2-29: Sheet E0.01 – Site Electrical Utilities Plan

Additional lighting has been added to the monument sign. See the attached sheet E0.01

for additional information.

Item 2-30: Sheet E5.01 – Light Fixture Schedule

Additional light fixtures have been added. See the attached sheet E5.01 for additional

information.

Item 2-31: Sheet E5.02 – Panelboard Schedule ‘BA’

An additional lighting circuit has been added. See the attached sheet E5.02 for additional

information.

Item 2-32: Sheet E6.01 – Lighting Contactor Schedule ‘c1’

An additional lighting circuit has been added to the contactor schedule. See the attached

sheet E6.01 for additional information.

END OF ADDENDUM NO. 2

Page 6: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified
Page 7: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified
Page 8: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 1

SECTION 08 71 00 – DOOR HARDWARE

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes commercial door hardware for the following:

1. Swinging doors. 2. Other doors to the extent indicated.

B. Door hardware includes, but is not necessarily limited to, the following:

1. Mechanical door hardware. 2. Electromechanical door hardware.

C. Related Sections:

1. Division 08 Section “Hollow Metal Doors and Frames”. 2. Division 08 Section “Interior Aluminum Doors and Frames”. 3. Division 08 Section “Flush Wood Doors”.

D. Codes and References: Comply with the version year adopted by the Authority Having Jurisdiction.

1. ANSI A117.1 - Accessible and Usable Buildings and Facilities. 2. ICC/IBC - International Building Code. 3. NFPA 70 - National Electrical Code. 4. NFPA 80 - Fire Doors and Windows. 5. NFPA 101 - Life Safety Code. 6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments.

E. Standards: All hardware specified herein shall comply with the following industry standards:

1. ANSI/BHMA Certified Product Standards - A156 Series 2. UL10C – Positive Pressure Fire Tests of Door Assemblies

1.2 SUBMITTALS

A. Product Data: Manufacturer's product data sheets including installation details, material descriptions, dimensions of individual components and profiles, operational descriptions and finishes.

Page 9: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 2

B. Door Hardware Schedule: Prepared by or under the supervision of supplier, detailing fabrication and assembly of door hardware, as well as procedures and diagrams. Coordinate the final Door Hardware Schedule with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of door hardware.

1. Format: Comply with scheduling sequence and vertical format in DHI's "Sequence and Format for the Hardware Schedule."

2. Organization: Organize the Door Hardware Schedule into door hardware sets indicating complete designations of every item required for each door or opening. Organize door hardware sets in same order as in the Door Hardware Sets at the end of Part 3. Submittals that do not follow the same format and order as the Door Hardware Sets will be rejected and subject to resubmission.

3. Content: Include the following information:

a. Type, style, function, size, label, hand, and finish of each door hardware item.

b. Manufacturer of each item.

c. Fastenings and other pertinent information.

d. Location of door hardware set, cross-referenced to Drawings, both on floor plans and in door and frame schedule.

e. Explanation of abbreviations, symbols, and codes contained in schedule.

f. Mounting locations for door hardware.

g. Door and frame sizes and materials.

h. Warranty information for each product.

4. Submittal Sequence: Submit the final Door Hardware Schedule at earliest possible date, particularly where approval of the Door Hardware Schedule must precede fabrication of other work that is critical in the Project construction schedule. Include Product Data, Samples, Shop Drawings of other work affected by door hardware, and other information essential to the coordinated review of the Door Hardware Schedule.

C. Shop Drawings: Details of electrified access control hardware indicating the following:

1. Wiring Diagrams: Upon receipt of approved schedules, submit detailed system wiring diagrams for power, signaling, monitoring, communication, and control of the access control system electrified hardware. Differentiate between manufacturer-installed and field-installed wiring. Include the following:

a. Elevation diagram of each unique access controlled opening showing location and interconnection of major system components with respect to their placement in the respective door openings.

b. Complete (risers, point-to-point) access control system block wiring diagrams.

c. Wiring instructions for each electronic component scheduled herein.

Page 10: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 3

2. Electrical Coordination: Coordinate with related sections the voltages and wiring details required at electrically controlled and operated hardware openings.

D. Keying Schedule: After a keying meeting with the owner has taken place prepare a separate keying schedule detailing final instructions. Submit the keying schedule in electronic format. Include keying system explanation, door numbers, key set symbols, hardware set numbers and special instructions. Owner must approve submitted keying schedule prior to the ordering of permanent cylinders/cores.

E. Operating and Maintenance Manuals: Provide manufacturers operating and maintenance manuals for each item comprising the complete door hardware installation in quantity as required in Division 01, Closeout Submittals.

1.3 QUALITY ASSURANCE

A. Manufacturers Qualifications: Engage qualified manufacturers with a minimum 5 years of documented experience in producing hardware and equipment similar to that indicated for this Project and that have a proven record of successful in-service performance.

B. Installer Qualifications: A minimum 3 years documented experience installing both standard and electrified door hardware similar in material, design, and extent to that indicated for this Project and whose work has resulted in construction with a record of successful in-service performance.

C. Door Hardware Supplier Qualifications: Experienced commercial door hardware distributors with a minimum 5 years documented experience supplying both mechanical and electromechanical hardware installations comparable in material, design, and extent to that indicated for this Project. Supplier recognized as a factory direct distributor by the manufacturers of the primary materials with a warehousing facility in Project's vicinity. Supplier to have on staff a certified Architectural Hardware Consultant (AHC) available during the course of the Work to consult with Contractor, Architect, and Owner concerning both standard and electromechanical door hardware and keying.

D. Each unit to bear third party permanent label demonstrating compliance with the referenced standards.

E. Keying Conference: Conduct conference to comply with requirements in Division 01 Section "Project Meetings." Keying conference to incorporate the following criteria into the final keying schedule document:

1. Function of building, purpose of each area and degree of security required. 2. Plans for existing and future key system expansion. 3. Requirements for key control storage and software. 4. Installation of permanent keys, cylinder cores and software. 5. Address and requirements for delivery of keys.

Page 11: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 4

F. Pre-Submittal Conference: Conduct coordination conference in compliance with requirements in Division 01 Section "Project Meetings" with attendance by representatives of Supplier(s), Installer(s), and Contractor(s) to review proper methods and the procedures for receiving, handling, and installing door hardware.

1. Prior to installation of door hardware, conduct a project specific training meeting to instruct the installing contractors' personnel on the proper installation and adjustment of their respective products. Product training to be attended by installers of door hardware (including electromechanical hardware) for aluminum, hollow metal and wood doors. Training will include the use of installation manuals, hardware schedules, templates and physical product samples as required.

2. Inspect and discuss electrical roughing-in, power supply connections, and other preparatory work performed by other trades.

3. Review sequence of operation narratives for each unique access controlled opening. 4. Review and finalize construction schedule and verify availability of materials. 5. Review the required inspecting, testing, commissioning, and demonstration procedures

G. At completion of installation, provide written documentation that components were applied to manufacturer's instructions and recommendations and according to approved schedule.

1.4 DELIVERY, STORAGE, AND HANDLING

A. Inventory door hardware on receipt and provide secure lock-up and shelving for door hardware delivered to Project site. Do not store electronic access control hardware, software or accessories at Project site without prior authorization.

B. Tag each item or package separately with identification related to the final Door Hardware Schedule, and include basic installation instructions with each item or package.

C. Deliver, as applicable, permanent keys, cylinders, cores, access control credentials, software and related accessories directly to Owner via registered mail or overnight package service. Instructions for delivery to the Owner shall be established at the "Keying Conference".

1.5 COORDINATION

A. Templates: Obtain and distribute to the parties involved templates for doors, frames, and other work specified to be factory prepared for installing standard and electrified hardware. Check Shop Drawings of other work to confirm that adequate provisions are made for locating and installing hardware to comply with indicated requirements.

B. Door Hardware and Electrical Connections: Coordinate the layout and installation of scheduled electrified door hardware and related access control equipment with required connections to source power junction boxes, low voltage power supplies, detection and monitoring hardware, and fire and detection alarm systems.

Page 12: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 5

C. Door and Frame Preparation: Doors and corresponding frames are to be prepared, reinforced and pre-wired (if applicable) to receive the installation of the specified electrified, monitoring, signaling and access control system hardware without additional in-field modifications.

1.6 WARRANTY

A. General Warranty: Reference Division 01, General Requirements. Special warranties specified in this Article shall not deprive Owner of other rights Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by Contractor under requirements of the Contract Documents.

B. Warranty Period: Written warranty, executed by manufacturer(s), agreeing to repair or replace components of standard and electrified door hardware that fails in materials or workmanship within specified warranty period after final acceptance by the Owner. Failures include, but are not limited to, the following:

1. Structural failures including excessive deflection, cracking, or breakage. 2. Faulty operation of the hardware. 3. Deterioration of metals, metal finishes, and other materials beyond normal weathering. 4. Electrical component defects and failures within the systems operation.

C. Standard Warranty Period: One year from date of Substantial Completion, unless otherwise indicated.

D. Special Warranty Periods:

1. Ten years for mortise locks and latches. 2. Seven years for heavy duty cylindrical (bored) locks and latches. 3. Five years for exit hardware. 4. Twenty five years for manual surface door closer bodies. 5. Two years for electromechanical door hardware.

1.7 MAINTENANCE SERVICE

A. Maintenance Tools and Instructions: Furnish a complete set of specialized tools and maintenance instructions as needed for Owner's continued adjustment, maintenance, and removal and replacement of door hardware.

PART 2 - PRODUCTS

2.1 SCHEDULED DOOR HARDWARE

A. General: Provide door hardware for each door to comply with requirements in Door Hardware Sets and each referenced section that products are to be supplied under.

Page 13: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 6

B. Designations: Requirements for quantity, item, size, finish or color, grade, function, and other distinctive qualities of each type of door hardware are indicated in the Door Hardware Sets at the end of Part 3. Products are identified by using door hardware designations, as follows:

C. Named Manufacturer's Products: Product designation and manufacturer are listed for each door hardware type required for the purpose of establishing requirements. Manufacturers' names are abbreviated in the Door Hardware Schedule.

D. Substitutions: Requests for substitution and product approval for inclusive mechanical and electromechanical door hardware in compliance with the specifications must be submitted in writing and in accordance with the procedures and time frames outlined in Division 01, Substitution Procedures. Approval of requests is at the discretion of the architect, owner, and their designated consultants.

2.2 HANGING DEVICES

A. Hinges: ANSI/BHMA A156.1 certified butt hinges with number of hinge knuckles as specified in the Door Hardware Sets.

1. Quantity: Provide the following hinge quantity, unless otherwise indicated:

a. Two Hinges: For doors with heights up to 60 inches.

b. Three Hinges: For doors with heights 61 to 90 inches.

c. Four Hinges: For doors with heights 91 to 120 inches.

d. For doors with heights more than 120 inches, provide 4 hinges, plus 1 hinge for every 30 inches of door height greater than 120 inches.

2. Hinge Size: Provide the following, unless otherwise indicated, with hinge widths sized for door thickness and clearances required:

a. Widths up to 3’0”: 4-1/2” standard or heavy weight as specified.

b. Sizes from 3’1” to 4’0”: 5” standard or heavy weight as specified.

3. Hinge Weight and Base Material: Unless otherwise indicated, provide the following:

a. Exterior Doors: Heavy weight, non-ferrous, ball bearing or oil impregnated bearing hinges unless Hardware Sets indicate standard weight.

b. Interior Doors: Standard weight, steel, ball bearing or oil impregnated bearing hinges unless Hardware Sets indicate heavy weight.

4. Hinge Options: Comply with the following where indicated in the Hardware Sets or on Drawings:

a. Non-removable Pins: Provide set screw in hinge barrel that, when tightened into a groove in hinge pin, prevents removal of pin while door is closed; for the all out-swinging lockable doors.

Page 14: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 7

5. Acceptable Manufacturers:

a. Bommer Industries (BO).

b. Hager Companies (HA).

c. McKinney Products (MK).

B. Continuous Geared Hinges: ANSI/BHMA A156.26 Grade 1-600 certified continuous geared hinge. with minimum 0.120-inch thick extruded 6060 T6 aluminum alloy hinge leaves and a minimum overall width of 4 inches. Hinges are non-handed, reversible and fabricated to template screw locations. Factory trim hinges to suit door height and prepare for electrical cut-outs.

1. Acceptable Manufacturers:

a. Bommer Industries (BO).

b. McKinney Products (MK).

c. Pemko Manufacturing (PE).

2.3 DOOR OPERATING TRIM

A. Door Push Plates and Pulls: ANSI/BHMA A156.6 certified door pushes and pulls of type and design specified in the Hardware Sets. Coordinate and provide proper width and height as required where conflicting hardware dictates.

1. Push/Pull Plates: Minimum .050 inch thick, size as indicated in hardware sets, with beveled edges, secured with exposed screws unless otherwise indicated.

2. Door Pull and Push Bar Design: Size, shape, and material as indicated in the hardware sets. Minimum clearance of 2 1/2-inches from face of door unless otherwise indicated.

3. Fasteners: Provide manufacturer's designated fastener type as indicated in Hardware Sets.

4. Acceptable Manufacturers:

a. Hiawatha, Inc. (HI).

b. Rockwood Manufacturing (RO).

c. Trimco (TC).

2.4 CYLINDERS AND KEYING

A. General: Cylinder manufacturer to have minimum (10) years experience designing secured master key systems and have on record a published security keying system policy.

B. Source Limitations: Obtain each type of keyed cylinder and keys from the same source manufacturer as locksets and exit devices, unless otherwise indicated.

Page 15: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 8

C. Cylinders: Original manufacturer cylinders complying with the following:

1. Mortise Type: Threaded cylinders with rings and cams to suit hardware application. 2. Rim Type: Cylinders with back plate, flat-type vertical or horizontal tailpiece, and raised

trim ring. 3. Bored-Lock Type: Cylinders with tailpieces to suit locks. 4. Mortise and rim cylinder collars to be solid and recessed to allow the cylinder face to be

flush and be free spinning with matching finishes. 5. Keyway: Manufacturer’s Standard.

D. Patented Cylinders: ANSI/BHMA A156.5, Grade 1, certified patented cylinders employing a utility patented and restricted keyway requiring the use of a patented key. Cylinders are to be protected from unauthorized manufacture and distribution by manufacturer’s United States patents. Cylinders are to be factory keyed with owner having the ability for on-site original key cutting.

1. Acceptable Manufacturers:

a. Medeco (MC) - X4 Series.

b. Sargent Manufacturing (SA) - XC Series.

E. Keying System: Each type of lock and cylinders to be factory keyed.

1. Conduct specified "Keying Conference" to define and document keying system instructions and requirements.

2. Furnish factory cut, nickel-silver large bow permanently inscribed with a visual key control number as directed by Owner.

3. New System: Key locks to a new key system as directed by the Owner.

F. Key Quantity: Provide the following minimum number of keys:

1. Change Keys per Cylinder: Two (2) Three (3). 2. Master Keys (per Master Key Level/Group): Five (5). 3. Construction Keys (where required): Ten (10).

G. Construction Keying: Provide construction master keyed cylinders.

H. Key Registration List (Bitting List):

1. Provide keying transcript list to Owner's representative in the proper format for importing into key control software.

2. Provide transcript list in writing or electronic file as directed by the Owner.

I. Key Control Software: Provide one network version of "Key Wizard" branded key management software package that includes one year of technical support and upgrades to software at no charge. Provide factory key system formatted for importing into “Key Wizard” software.

Page 16: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 9

2.5 MECHANICAL LOCKS AND LATCHING DEVICES

A. Mortise Locksets, Grade 1 (Heavy Duty): ANSI/BHMA A156.13, Series 1000, Operational Grade 1 certified. Locksets are to be manufactured with a corrosion resistant steel case and be field-reversible for handing without disassembly of the lock body.

1. Acceptable Manufacturers:

a. Corbin Russwin Hardware (RU) – ML2000 Series.

b. Sargent Manufacturing (SA) – 8200 Series.

c. Schlage (SC) – L9000 Series.

B. Cylindrical Locksets, Grade 1 (Heavy Duty): ANSI/BHMA A156.2, Series 4000, Grade 1 certified.

1. Furnish with solid cast levers, standard 2 3/4” backset, and 1/2" (3/4" at rated paired openings) throw brass or stainless steel latchbolt.

2. Locks are to be non-handed and fully field reversible.

3. Acceptable Manufacturers:

a. Corbin Russwin Hardware (RU) – CL3300 Series.

b. Sargent Manufacturing (SA) – 10 Line.

c. Schlage (SC) – ND Series.

2.6 LOCK AND LATCH STRIKES

A. Strikes: Provide manufacturer's standard strike with strike box for each latch or lock bolt, with curved lip extended to protect frame, finished to match door hardware set, unless otherwise indicated, and as follows:

1. Flat-Lip Strikes: For locks with three-piece antifriction latchbolts, as recommended by manufacturer.

2. Extra-Long-Lip Strikes: For locks used on frames with applied wood casing trim. 3. Aluminum-Frame Strike Box: Provide manufacturer's special strike box fabricated for

aluminum framing. 4. Double-lipped strikes: For locks at double acting doors. Furnish with retractable stop for

rescue hardware applications.

B. Standards: Comply with the following:

1. Strikes for Mortise Locks and Latches: BHMA A156.13. 2. Strikes for Bored Locks and Latches: BHMA A156.2. 3. Strikes for Auxiliary Deadlocks: BHMA A156.36. 4. Dustproof Strikes: BHMA A156.16.

Page 17: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 10

2.7 ELECTROMAGNETIC LOCKING DEVICES

A. Surface Electromagnetic Locks (Heavy Duty): Electromagnetic locks to be surface mounted type conforming to ANSI A156.23, Grade 1 with minimum holding force strength of 1,200 pounds. Locks to be capable of either 12 or 24 voltage and be UL listed for use on fire rated door assemblies. Electronics are to be fully sealed against tampering and allow exterior weatherproof applications. As indicated in Hardware Sets, provide specified mounting brackets and housings. Power supply to be by the same manufacturer as the lock with combined products having a lifetime replacement warranty.

1. Acceptable Manufacturers:

a. Securitron (SU) – M62 Series.

2.8 ELECTRIC STRIKES

A. Surface Mounted Rim Electric Strikes: Surface mounted rim exit device electric strikes conforming to ANSI/BHMA A156.31, Grade 1, and UL Listed for both Burglary Resistance and for use on fire rated door assemblies. Construction includes internally mounted solenoid with two heavy-duty, stainless steel locking mechanisms operating independently to provide tamper resistance. Strikes tested for a minimum of 500,000 operating cycles. Provide strikes with 12 or 24 VDC capability supplied standard as fail-secure unless otherwise specified. Option available for latchbolt and latchbolt strike monitoring indicating both the position of the latchbolt and locked condition of the strike. Strike requires no cutting to the jamb prior to installation.

1. Acceptable Manufacturers:

a. HES (HS) - 9500/9600 Series.

2.9 CONVENTIONAL EXIT DEVICES

A. General Requirements: All exit devices specified herein shall meet or exceed the following criteria:

1. At doors not requiring a fire rating, provide devices complying with NFPA 101 and listed and labeled for "Panic Hardware" according to UL305. Provide proper fasteners as required by manufacturer including sex nuts and bolts at openings specified in the Hardware Sets.

2. Where exit devices are required on fire rated doors, provide devices complying with NFPA 80 and with UL labeling indicating "Fire Exit Hardware". Provide devices with the proper fasteners for installation as tested and listed by UL. Consult manufacturer’s catalog and template book for specific requirements.

3. Except on fire rated doors, provide exit devices with hex key dogging device to hold the pushbar and latch in a retracted position. Provide optional keyed cylinder dogging on devices where specified in Hardware Sets.

Page 18: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 11

4. Devices must fit flat against the door face with no gap that permits unauthorized dogging of the push bar. The addition of filler strips is required in any case where the door light extends behind the device as in a full glass configuration.

5. Lever Operating Trim: Where exit devices require lever trim, furnish manufacturer's heavy duty escutcheon trim with threaded studs for thru-bolts.

a. Lock Trim Design: As indicated in Hardware Sets, provide finishes and designs to match that of the specified locksets.

b. Where function of exit device requires a cylinder, provide a cylinder (Rim or Mortise) as specified in Hardware Sets.

6. Vertical Rod Exit Devices: Where surface or concealed vertical rod exit devices are used at interior openings, provide as less bottom rod (LBR) unless otherwise indicated. Provide dust proof strikes where thermal pins are required to project into the floor.

7. Narrow Stile Applications: At doors constructed with narrow stiles, or as specified in Hardware Sets, provide devices designed for maximum 2” wide stiles.

8. Dummy Push Bar: Nonfunctioning push bar matching functional push bar.

9. Rail Sizing: Provide exit device rails factory sized for proper door width application.

10. Through Bolt Installation: For exit devices and trim as indicated in Door Hardware Sets.

B. Conventional Push Rail Exit Devices (Heavy Duty): ANSI/BHMA A156.3, Grade 1 certified panic and fire exit hardware devices furnished in the functions specified in the Hardware Sets. Exit device latch to be stainless steel, pullman type, with deadlock feature.

1. Acceptable Manufacturers:

a. Corbin Russwin Hardware (RU) - ED4000 / ED5000 Series.

b. Sargent Manufacturing (SA) - 80 Series.

2.10 DOOR CLOSERS

A. All door closers specified herein shall meet or exceed the following criteria:

1. General: Door closers to be from one manufacturer, matching in design and style, with the same type door preparations and templates regardless of application or spring size. Closers to be non-handed with full sized covers including installation and adjusting information on inside of cover.

2. Standards: Closers to comply with UL-10C for Positive Pressure Fire Test and be U.L. listed for use of fire rated doors.

3. Cycle Testing: Provide closers which have surpassed 15 million cycles in a test witnessed and verified by UL.

Page 19: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 12

4. Size of Units: Comply with manufacturer's written recommendations for sizing of door closers depending on size of door, exposure to weather, and anticipated frequency of use. Where closers are indicated for doors required to be accessible to the physically handicapped, provide units complying with ANSI ICC/A117.1.

5. Closer Arms: Provide heavy duty, forged steel closer arms unless otherwise indicated in Hardware Sets.

6. Closers shall not be installed on exterior or corridor side of doors; where possible install

closers on door for optimum aesthetics.

7. Closer Accessories: Provide door closer accessories including custom templates, special mounting brackets, spacers and drop plates as required for proper installation. Provide through-bolt and security type fasteners as specified in the hardware sets.

B. Door Closers, Surface Mounted (Large Body Cast Iron): ANSI/BHMA A156.4, Grade 1 surface mounted, heavy duty door closers with complete spring power adjustment, sizes 1 thru 6; and fully operational adjustable according to door size, frequency of use, and opening force. Closers to be rack and pinion type, one piece cast iron body construction, with adjustable backcheck and separate non-critical valves for closing sweep and latch speed control.

1. Acceptable Manufacturers:

a. LCN Closers (LC) - 4040XP Series.

b. Norton Door Controls (NO) – 9500 Series.

c. Sargent Manufacturing (SA) - 281 Series.

2.11 ARCHITECTURAL TRIM

A. Door Protective Trim

1. General: Door protective trim units to be of type and design as specified below or in the Hardware Sets.

Size: Fabricate protection plates (kick, armor, or mop) not more than 2" less than door width (LDW) on stop side of single doors and 1” LDW on stop side of pairs of doors, and not more than 1" less than door width on pull side. Coordinate and provide proper width and height as required where conflicting hardware dictates. Height to be as specified in the Hardware Sets.

2. Where plates are applied to fire rated doors with the top of the plate more than 16” above the bottom of the door, provide plates complying with NFPA 80. Consult manufacturer’s catalog and template book for specific requirements for size and applications.

3. Protection Plates: ANSI/BHMA A156.6 certified protection plates (kick, armor, or mop), fabricated from the following:

a. Stainless Steel: 300 grade, 050-inch thick.

Page 20: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 13

4. Options and fasteners: Provide manufacturer's designated fastener type as specified in the Hardware Sets. Provide countersunk screw holes.

5. Acceptable Manufacturers:

a. Hiawatha, Inc. (HI).

b. Rockwood Manufacturing (RO).

c. Trimco (TC).

2.12 DOOR STOPS AND HOLDERS

A. General: Door stops and holders to be of type and design as specified below or in the Hardware Sets.

B. Door Stops and Bumpers: ANSI/BHMA A156.16, Grade 1 certified door stops and wall bumpers. Provide wall bumpers, either convex or concave types with anchorage as indicated, unless floor or other types of door stops are specified in Hardware Sets. Do not mount floor stops where they will impede traffic. Where floor or wall bumpers are not appropriate, provide overhead type stops and holders.

1. Acceptable Manufacturers:

a. Hiawatha, Inc. (HI).

b. Rockwood Manufacturing (RO).

c. Trimco (TC).

C. Overhead Door Stops and Holders: ANSI/BHMA A156.6, Grade 1 certified overhead stops and holders to be surface or concealed types as indicated in Hardware Sets. Track, slide, arm and jamb bracket to be constructed of extruded bronze and shock absorber spring of heavy tempered steel. Provide non-handed design with mounting brackets as required for proper operation and function.

1. Acceptable Manufacturers:

a. Rixson Door Controls (RF).

b. Rockwood Manufacturing (RO).

c. Sargent Manufacturing (SA).

2.13 ARCHITECTURAL SEALS

A. General: Thresholds, weatherstripping, and gasket seals to be of type and design as specified below or in the Hardware Sets. Provide continuous weatherstrip gasketing on exterior doors and provide smoke, light, or sound gasketing on interior doors where indicated. At exterior applications provide non-corrosive fasteners and elsewhere where indicated.

Page 21: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 14

B. Smoke Labeled Gasketing: Assemblies complying with NFPA 105 that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction, for smoke control ratings indicated, based on testing according to UL 1784.

1. Provide smoke labeled perimeter gasketing at all smoke labeled openings.

C. Fire Labeled Gasketing: Assemblies complying with NFPA 80 that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction, for fire ratings indicated, based on testing according to UL-10C.

1. Provide intumescent seals as indicated to meet UL10C Standard for Positive Pressure Fire Tests of Door Assemblies, and NPFA 252, Standard Methods of Fire Tests of Door Assemblies.

D. Sound-Rated Gasketing: Assemblies that are listed and labeled by a testing and inspecting agency, for sound ratings indicated.

E. Replaceable Seal Strips: Provide only those units where resilient or flexible seal strips are easily replaceable and readily available from stocks maintained by manufacturer.

F. Acceptable Manufacturers:

1. National Guard Products (NG). 2. Pemko Manufacturing (PE). 3. Reese Enterprises, Inc. (RE).

2.14 ELECTRONIC ACCESSORIES

A. Push-Button Switches: Industrial grade momentary or alternate contact, back-lighted push buttons with stainless-steel switch enclosures. 12/24 VDC bi-color illumination suitable for either flush or surface mounting.

1. Acceptable Manufacturers:

a. Securitron (SU) - PB Series.

B. Request-to-Exit Motion Sensor: Request-to-Exit Sensors motion detectors specifically designed for detecting exiting through a door from the secure area to a non-secure area. Include built-in timers (up to 60 second adjustable timing), door monitor with sounder alert, internal vertical pointability coverage, 12VDC or 24VDC power and selectable relay trigger with fail safe/fail secure modes.

1. Acceptable Manufacturers:

a. Securitron (SU) - XMS Series.

Page 22: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 15

C. Door Position Switches: Door position magnetic reed contact switches specifically designed for use in commercial door applications. On recessed models the contact and magnetic housing snap-lock into a 1" diameter hole. Surface mounted models include wide gap distance design complete with armored flex cabling. Provide SPDT, N/O switches with optional Rare Earth Magnet installation on steel doors with flush top channels.

1. Acceptable Manufacturers:

a. Securitron (SU) - DPS Series.

2.15 FABRICATION

A. Fasteners: Provide door hardware manufactured to comply with published templates generally prepared for machine, wood, and sheet metal screws. Provide screws according to manufacturers recognized installation standards for application intended.

2.16 FINISHES

A. Standard: Designations used in the Hardware Sets and elsewhere indicate hardware finishes complying with ANSI/BHMA A156.18, including coordination with traditional U.S. finishes indicated by certain manufacturers for their products.

B. Provide quality of finish, including thickness of plating or coating (if any), composition, hardness, and other qualities complying with manufacturer's standards, but in no case less than specified by referenced standards for the applicable units of hardware

C. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine scheduled openings, with Installer present, for compliance with requirements for installation tolerances, labeled fire door assembly construction, wall and floor construction, and other conditions affecting performance.

B. Notify architect of any discrepancies or conflicts between the door schedule, door types, drawings and scheduled hardware. Proceed only after such discrepancies or conflicts have been resolved in writing.

Page 23: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 16

3.2 PREPARATION

A. Hollow Metal Doors and Frames: Comply with ANSI/DHI A115 series.

B. Wood Doors: Comply with ANSI/DHI A115-W series.

3.3 INSTALLATION

A. Install each item of mechanical and electromechanical hardware and access control equipment to comply with manufacturer's written instructions and according to specifications.

1. Installers are to be trained and certified by the manufacturer on the proper installation and adjustment of fire, life safety, and security products including: hanging devices; locking devices; closing devices; and seals.

B. Mounting Heights: Mount door hardware units at heights indicated in following applicable publications, unless specifically indicated or required to comply with governing regulations:

1. Standard Steel Doors and Frames: DHI's "Recommended Locations for Architectural Hardware for Standard Steel Doors and Frames."

2. Wood Doors: DHI WDHS.3, "Recommended Locations for Architectural Hardware for Wood Flush Doors."

3. Where indicated to comply with accessibility requirements, comply with ANSI A117.1 "Accessibility Guidelines for Buildings and Facilities."

4. Provide blocking in drywall partitions where wall stops or other wall mounted hardware is located.

C. Thresholds: Set thresholds for exterior and acoustical doors in full bed of sealant complying with requirements specified in Division 7 Section "Joint Sealants."

D. Storage: Provide a secure lock up for hardware delivered to the project but not yet installed. Control the handling and installation of hardware items so that the completion of the work will not be delayed by hardware losses before and after installation.

3.4 FIELD QUALITY CONTROL

A. Field Inspection: Supplier will perform a final inspection of installed door hardware and state in report whether work complies with or deviates from requirements, including whether door hardware is properly installed, operating and adjusted.

3.5 ADJUSTING

A. Initial Adjustment: Adjust and check each operating item of door hardware and each door to ensure proper operation or function of every unit. Replace units that cannot be adjusted to operate as intended. Adjust door control devices to compensate for final operation of heating and ventilating equipment and to comply with referenced accessibility requirements.

Page 24: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 17

3.6 CLEANING AND PROTECTION

A. Protect all hardware stored on construction site in a covered and dry place. Protect exposed hardware installed on doors during the construction phase. Install any and all hardware at the latest possible time frame.

B. Clean adjacent surfaces soiled by door hardware installation.

C. Clean operating items as necessary to restore proper finish. Provide final protection and maintain conditions that ensure door hardware is without damage or deterioration at time of owner occupancy.

3.7 DEMONSTRATION

A. Instruct Owner's maintenance personnel to adjust, operate, and maintain mechanical and electromechanical door hardware.

3.8 DOOR HARDWARE SETS

A. The hardware sets represent the design intent and direction of the owner and architect. They are a guideline only and should not be considered a detailed hardware schedule. Discrepancies, conflicting hardware and missing items should be brought to the attention of the architect with corrections made prior to the bidding process. Omitted items not included in a hardware set should be scheduled with the appropriate additional hardware required for proper application and functionality.

B. Manufacturer’s Abbreviations:

1. MK - McKinney 2. PE - Pemko 3. SA - Sargent 4. AD - Adams Rite 5. SU - Securitron 6. HS - HES 7. RO - Rockwood 8. RF - Rixson

Page 25: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 18

Hardware Schedule Set: 1.0 Doors: 200.1 2 Continuous Hinge KDFM83-HD1 PE 2 Magnetic Lock w/ REX M680BDX-313 313 SU 2 Pull (Maple wood finish) RM4030-10 Mtg-Type 12XHD US26 RO 2 Push Rail 47 US10BE RO 2 Door Closer 281 CPS 581-2 US10BE SA 2 Drop Plate 281D US10BE SA 1 Wall Stop 409 US10BE RO 1 Door Stop 463 EXP US32D RO 1 Threshold 2009DPK PE 1 Perimeter Weatherstrip/Stop By Door/Frame Supplier 1 Rain Guard 346D TKSP8 PE 2 Sweep 345DNB TKSP8 PE 2 Brush Astragal By Door System Supplier 1 Card Reader See Electrical Specification 1 Power Supply See Electrical Specification Notes: * Coordinate installation and connection of electrified and access control components. * Operation Narrative: - Doors are normally closed and secured. - Presentation of an authorized credential to card reader will unlock magnetic lock and allow access. - Magnetic locks will become powered after designated time by access control system and doors will become secure upon closing. - During designated hours magnetic locks may be unlocked by access control system for unimpeded access and egress. - After hours doors will be secured by magnetic locks as directed by access control system. - In the event of a loss of building power magnetic lock power will be provided by battery back up for doors to remain locked. - Free egress is available when doors are unsecured and by motion sensor/emergency override when doors are secured. Set: 2.0 Doors: 110.1 1 Continuous Hinge KDFM83-HD1 PE 1 Rim Exit Device (nightlatch, alum) 11 AD8504 862 CMK US10BE SA 1 Electric Strike 9400 313 HS 1 Door Closer 281 P10 581-2 US10BE SA 1 Drop Plate 281D US10BE SA 1 Wall Stop 409 US10BE RO 1 Perimeter Weatherstrip/Stop By Door/Frame Supplier 1 Rain Guard 346D TKSP8 PE 1 Sweep 345DNB TKSP8 PE 1 Card Reader See Electrical Specification 1 Power Supply See Electrical Specification

Page 26: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 19

Notes: * Coordinate supply, installation and connection of electrified and access control components. * Operation Narrative: - Door is normally closed and secured. - Presentation of authorized credential to card reader will unlock electric strike and allow access. - Electric strike to lock as directed by access control system after card is read and door becomes secure upon closing. - During designated hours, electric strike may be electrically unlocked by access control system to allow push/pull operation. - Access control system will lock strike to secure the opening on the designated schedule. - In the event of a loss of power door will have power removed and will become locked. - Key override is available for emergency access. - Free egress is always available from inside without alerting access control system. Set: 3.0 Doors: 318.1, 319.2 1 Continuous Hinge KDFM83-HD1 PE 1 Exit Device CPC AD8515 ETJ US10BE SA 1 Door Closer 281 OT US10BE SA 1 Threshold 171D PE 1 Perimeter Weatherstrip/Stop By Door/Frame Supplier 1 Rain Guard 346D TKSP8 PE 1 Sweep 345DNB TKSP8 PE 1 Door Bottom 4131CRL TKSP8 PE 1 Position Switch DPS-M-GY SU Notes: * Connect door position switch to access control system to monitor for unauthorized access. * Door position switch to be shunted during normal business hours. Set: 4.0 Doors: 205.1, 205.2, 205.3 1 Continuous Hinge KDFM83-HD1 PE 1 Mortise Deadlock x Thumbturn MS1850S x 4066 313 AD 2 Cylinder 11 41 US10BE SA 1 Push Bar & Pull BF15747 US10BE RO 1 Door Closer 281 CPS 581-2 US10BE SA 1 Drop Plate 281D US10BE SA 1 Threshold 2009DPK PE 1 Perimeter Weatherstrip/Stop By Door/Frame Supplier 1 Rain Guard 346D TKSP8 PE 1 Door Bottom 4131DRL TKSP8 PE 1 Sweep 57DV TKSP8 PE Notes: * Mount vinyl sweep inside and automatic door bottom outside.

Page 27: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 20

Set: 5.0 Doors: 401.3 1 Continuous Hinge KDFM83-HD1 PE 1 Mortise Deadlock x Thumbturn MS1850S x 4066 313 AD 1 Cylinder 11 41 US10BE SA 1 Push Bar & Pull BF15747 US10BE RO 1 Door Closer 281 CPS 581-2 US10BE SA 1 Drop Plate 281D US10BE SA 1 Threshold 2009DPK PE 1 Perimeter Weatherstrip/Stop By Door/Frame Supplier 1 Rain Guard 346D TKSP8 PE 1 Sweep 345DNB TKSP8 PE Set: 6.0 Doors: 114.2, 114.4, 115.2, 117.2 1 Continuous Hinge KDFM83-HD1 PE 1 Rim Exit Device (nightlatch, cyl. dog, alum) 11 16 AD8504 CMK US10BE SA 1 Door Closer 281 P10 581-2 US10BE SA 1 Drop Plate 281D US10BE SA 1 Wall Stop 409 US10BE RO 1 Threshold 2009DPK PE 1 Perimeter Weatherstrip/Stop By Door/Frame Supplier 1 Rain Guard 346D TKSP8 PE 1 Sweep 345DNB TKSP8 PE Set: 7.0 Doors: 101 1 Continuous Hinge KDFM83-HD1 PE 1 Rim Exit Device (nightlatch, alum) 11 AD8504 862 CMK US10BE SA 1 Door Closer 281 P10 581-2 US10BE SA 1 Drop Plate 281D US10BE SA 1 Wall Stop 409 US10BE RO 1 Threshold 2009DPK PE 1 Perimeter Weatherstrip/Stop By Door/Frame Supplier 1 Rain Guard 346D TKSP8 PE 1 Sweep 345DNB TKSP8 PE

Page 28: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 21

Set: 7.1 Doors: 203.1 1 Continuous Hinge KDFM83-HD1 PE 1 Rim Exit Device (nightlatch, alum) 11 AD8504 CMK US10BE SA 1 Door Closer 281 P10 581-2 US10BE SA 1 Drop Plate 281D US10BE SA 1 Wall Stop 409 US10BE RO 1 Threshold 2009DPK PE 1 Perimeter Weatherstrip/Stop By Door/Frame Supplier 1 Rain Guard 346D TKSP8 PE 1 Sweep 345DNB TKSP8 PE Set: 8.0 Doors: 122.2 1 Continuous Hinge DFM83SLI-HD1 PE 1 Rim Exit Device (nightlatch) 11 8504 862 CMK US10BE SA 1 Electric Strike 9400 313 HS 1 Door Closer 281 CPS US10BE SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US10BE RO 1 Threshold 2009DPK PE 1 Weatherstrip 294DV TKSP8 PE 1 Rain Guard 346D TKSP8 PE 1 Sweep 345DNB TKSP8 PE 1 Card Reader By Security Consultant 1 Power Supply By Security Consultant Notes: * Coordinate supply, installation and connection of electrified and access control components. * Operation Narrative: - Door is normally closed and secured. - Presentation of authorized credential to card reader will unlock electric strike and allow access. - Electric strike to lock as directed by access control system after card is read and door becomes secure upon closing. - During designated hours, electric strike may be electrically unlocked by access control system to allow push/pull operation. - Access control system will lock strike to secure the opening on the designated schedule. - In the event of a loss of power door will have power removed and will become locked. - Key override is available for emergency access. - Free egress is always available from inside without alerting access control system. Set: 9.0 Doors: 110.2 1 Continuous Hinge KDFM83-HD1 PE 1 Exit Device (dummy rail) 8893 US10BE SA 1 Pull 862 US10BE SA 1 Door Closer 281 P10 581-2 US10BE SA 1 Drop Plate 281D US10BE SA

Page 29: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 22

Set: 10.0 Doors: 200.2 2 Continuous Hinge KDFM83-HD1 PE 4 Pull (Maple wood finish) RM4030-36 Mtg-Type 12XHD US10BE RO 2 Door Closer 281 CPS 581-2 US10BE SA 2 Drop Plate 281D US10BE SA 1 Perimeter Stop By Door/Frame Supplier Set: 11.0 Doors: 303 3 Hinge (heavy weight) T4A3786 NRP 4-1/2" x 4-1/2" US26D MK 1 Exit Device 11 12 8504 862 CMK US26D SA 1 Electric Strike (fail secure) 9500 630 HS 1 Smart Pac Bridge Rectifier 2005M3 HS 1 Door Closer 281 P10 EN SA 1 Wall Stop 409 US10BE RO 1 Perimeter Seal S442D PE 1 Frame Wire Harness QC-C1500P MK 1 Card Reader See Electrical Specification. 1 Power Supply See Electrical Specification. Notes: * Coordinate supply, installation and connection of electrified and access control components. * Operation Narrative: - Door is normally closed and secured. - Presentation of authorized credential to card reader will unlock electric strike and allow access. - Electric strike to lock as directed by access control system after card is read and door becomes secure upon closing. - During designated hours, electric strike may be electrically unlocked by access control system to allow push/pull operation. - Access control system will lock strike to secure the opening on the designated schedule. - In the event of a fire alarm activation door will close, latch and become secure. - In the event of a loss of power door will have power removed and strike will become locked. - Key override is available for emergency access. - Free egress is always available from inside. Set: 12.0 Doors: 103, 203 3 Hinge (heavy weight) T4A3786 NRP 4-1/2" x 4-1/2" US26D MK 1 Passage Exit Device 12 8515 ETJ CMK US32D SA 1 Door Closer 281 O EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE

Page 30: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 23

Set: 13.0 Doors: 122.1 3 Hinge (heavy weight) T4A3786 4-1/2" x 4-1/2" US26D MK 1 Passage Set 28 10U15 LJ US26D SA 1 Door Closer 281 CPS EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Threshold 171A PE 1 Perimeter Seal S442D PE 1 Sweep 345ANB TKSP8 PE Set: 14.0 Doors: 201, 301, 401.1, 404 3 Hinge (heavy weight) T4A3786 NRP 4-1/2" x 4-1/2" US26D MK 1 Exit Device 11 12 8504 ETJ CMK US32D SA 1 Door Closer 281 O EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE Set: 15.0 Doors: 405.2, 406.1, 406.2 3 Hinge (heavy weight) T4A3786 NRP 4-1/2" x 4-1/2" US26D MK 1 Exit Device 11 12 8504 ETJ CMK US32D SA 1 Door Closer 281 P10 EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE Set: 16.0 Doors: 405.1 3 Hinge (heavy weight) T4A3786 4-1/2" x 8" US26D MK 1 Exit Device 11 12 8504 ETJ CMK US32D SA 1 Door Closer 281 P10 EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE

Page 31: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 24

Set: 17.0 Doors: 114, 115 1 Continuous Hinge KDFM83-HD1 PE 1 Rim Exit Device (classroom) 11 16 8513 CMK 10BE SA 1 Pull (Maple wood finish) RM4030-36 Mtg-Type 12XHD US32D RO 1 Door Closer 281 CPSH 581-2 ED SA 1 Drop Plate 281D US10BE SA 1 Perimeter Weatherstrip/Stop By Door/Frame Supplier Set: 18.0 Doors: 102 3 Hinge (heavy weight) T4A3786 NRP 4-1/2" x 4-1/2" US26D MK 1 Rim Exit Device (nightlatch) 11 8504 ETJ CMK US32D SA 1 Door Closer 281 P10 EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE Set: 19.0 Doors: 111 3 Hinge TA2714 NRP 4-1/2" x 4-1/2" US26D MK 1 Classroom Lock 11 28 10G37 LJ CMK US26D SA 1 Door Closer 281 O EN SA 1 Armor Plate K1050 36" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE Set: 20.0 Doors: 307, 353 3 Hinge TA2714 NRP 4-1/2" x 4-1/2" US26D MK 1 Storeroom Lock 11 28 10G04 LJ CMK US26D SA 1 Wall Stop 409 US32D RO Set: 21.0 Doors: 202, 302 3 Hinge TA2714 4-1/2" x 4-1/2" US26D MK 1 Storeroom Lock 11 28 10G04 LJ CMK US26D SA 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE

Page 32: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 25

Set: 22.0 Doors: 121, 123 3 Hinge TA2714 4-1/2" x 4-1/2" US26D MK 1 Storeroom Lock 11 28 10G04 LJ CMK US26D SA 1 Door Closer 281 O EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Threshold 171A PE 1 Perimeter Seal S442D PE 1 Door Bottom 420APKL TKSP8 PE Set: 23.0 Doors: 117.1, 205 3 Hinge (heavy weight) T4A3786 NRP 4-1/2" x 4-1/2" US26D MK 1 Classroom Lock 11 28 10G37 LJ CMK US26D SA 1 Wall Stop 409 US32D RO Set: 24.0 Doors: 210 3 Hinge TA2714 NRP 4-1/2" x 4-1/2" US26D MK 1 Storeroom Lock 11 28 10G04 LJ CMK US26D SA 1 Door Closer 281 CPS EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Perimeter Seal S442D PE Set: 24.1 Doors: 333 3 Hinge TA2714 NRP 4-1/2" x 4-1/2" US26D MK 1 Storeroom Lock 11 28 10G04 LJ CMK US26D SA 1 Surface Overhead Stop 9-X36 US26D RF 1 Perimeter Seal S442D PE Set: 25.0 Doors: 118 3 Hinge (heavy weight) T4A3786 NRP 4-1/2" x 4-1/2" US26D MK 1 Storeroom Lock 11 28 10G04 LJ CMK US26D SA 1 Door Closer 281 CPS EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Threshold 171A PE 1 Perimeter Seal S442D PE 1 Sweep 345ANB TKSP8 PE

Page 33: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 26

Set: 26.0 Doors: 112, 206, 310, 345, 352 3 Hinge TA2714 4-1/2" x 4-1/2" US26D MK 1 Storeroom Lock 11 28 10G04 LJ CMK US26D SA 1 Concealed Overhead Stop 1-X36 630 RF 1 Perimeter Seal S442D PE Set: 27.0 Doors: 119, 120 3 Hinge TA2714 4-1/2" x 4-1/2" US26D MK 1 Storeroom Lock 11 28 10G04 LJ CMK US26D SA 1 Concealed Overhead Stop 1-X36 630 RF 1 Threshold 171A PE 1 Perimeter Seal S442D PE 1 Door Bottom 420APKL TKSP8 PE Set: 28.0 Doors: 106 3 Hinge TA2714 NRP 4-1/2" x 4-1/2" US26D MK 1 Storeroom Lock 11 28 10G04 LJ CMK US26D SA 1 Concealed Overhead Stop 1-X36 630 RF Set: 29.0 Doors: 401.2 3 Hinge TA2714 NRP 4-1/2" x 4-1/2" US26D MK 1 Passage Set 28 10U15 LJ US26D SA 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE Set: 30.0 Not used – part of interior glass partitions spec. Set: 31.0 Doors: 354 3 Hinge TA2714 4-1/2" x 4-1/2" US26D MK 1 Privacy Set w/ Occ. Indicator 49 8265 LNJ US26D SA 1 Door Closer 281 O EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE

Page 34: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 27

Set: 32.0 Doors: 357, 358 3 Hinge TA2714 4-1/2" x 4-1/2" US26D MK 1 Privacy Set w/ Occ. Indicator 49 8265 LNJ US26D SA 1 Door Closer 281 P10 EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE Set: 33.0 Doors: 108, 306 3 Hinge (heavy weight) T4A3786 4-1/2" x 4-1/2" US26D MK 1 Pull Plate BF 110x70C US26D RO 1 Push Plate 70F US32D RO 1 Door Closer 281 P10 EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Wall Stop 409 US32D RO 1 Perimeter Seal S442D PE Set: 34.0 Doors: 107, 305 3 Hinge (heavy weight) T4A3786 4-1/2" x 4-1/2" US26D MK 1 Pull Plate BF 110x70C US26D RO 1 Push Plate 70F US32D RO 1 Door Closer 281 CPS EN SA 1 Kick Plate K1050 10" x 2" LDW 4BE CSK US32D RO 1 Perimeter Seal S442D PE

Mark Hardware

101 7.0

102 18.0

103 12.0

106 28.0

107 34.0

108 33.0

110.1 2.0

110.2 9.0

111 19.0

112 26.0

114 17.0

114.2 6.0

114.4 6.0

115 17.0

115.2 6.0

117.2 6.0

117.1 23.0

118 25.0

119 27.0

120 27.0

121 22.0

122.1 13.0

122.2 8.0

123 22.0

200.1 1.0

200.2 10.0

201 14.0

202 21.0

203 -12 203.1 7.1

205 23.0

205.1 4.0

205.2 4.0

205.3 4.0

206 26.0

210 24.0

301 14.0

302 21.0

303 11.0

305 34.0

306 33.0

307 20.0

Page 35: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Plaza on the Green 03/17

8800 Firethorn Lane

Lincoln, Nebraska

TCEP Project No.: 067-001-16

DOOR HARDWARE 08 71 00 - 28

310 26.0

318.1 3.0

319.2 3.0

333 24.1

345 26.0

352 26.0

353 20.0

354 31.0

357 32.0

358 32.0

401.1 14.0

401.2 29.0

401.3 5.0

404 14.0

405.1 16.0

405.2 15.0

406.1 15.0

406.2 15.0

END OF SECTION 08 71 00

Page 36: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

4" TH. CRUSHED ROCK PVMT.REF DETAIL 10

L6.01

WEATHERED LIMESTONESLABSREF DETAIL

2L6.02

CONC. CURB AND GUTTERREF DETAIL 4

L6.01 CONC. MOUNTABLE CURBREF DETAIL 5

L6.01

CONC. UNIT PAVERSREF DETAIL 6-8

L6.01

STONE WALL 'A' W/ HANDRAILREF DETAIL 1A,B

L6.03

WEATHERED LIMESTONE BANDINGREF DETAIL 5

L6.02

STONE WALL 'C'REF DETAIL 1

L6.04

CONC. UNIT PAVERSREF DETAIL 6-7

L6.01STONE WALL 'D'REF DETAIL 2A,B

L6.04

WEATHERED LIMESTONEBANDINGREF DETAIL

5L6.02

STONE WALL 'E'REF DETAIL 2A,B

L6.03

CONC. UNIT PAVERSREF DETAIL 6-7

L6.01

4" TH. CRUSHED ROCK PVMT.REF DETAIL 10

L6.01

4" TH. CRUSHED ROCK PVMT.REF DETAIL 10

L6.01

3BL6.02

4A

L6.02

4C

L6.02

3BL6

.02

3AL6

.02

7BL6.02

4B

L6.02

BIORETETNION CHECKDAMTYP OF 4REF DETAIL

13L6.01

MATCH LINEMATCH LINE MATCH LINEMATCH LINE

CURB OPENING TYP OF 3REF DETAIL 11

L6.01

BIORETENTION FOREBAYTYP OF 3REF DETAIL

12L6.01

STRIPE AS SHOWN, TYP.

STRIPE AS SHOWN, TYP.

14L6

.01

ACCO TRAFFIK TRENCH DRAIN.REF CIVIL SHTS

8.00

'8.

50'

8.00

'

8.00

'

5.00

'

8.00

'

5.00'

16.50'

18.0

0'

6" TH. CONC. PVMT.REF DETAIL 1-3

L6.01

CURB OPENINGREF DETAIL 11

L6.01

(10) 90° PARKING STALLS @ 9'x18'

9.00'

8L6.01

18.0

0'

9.00'

10.00'

(6) PARALLEL PARKING STALLS @ 9' X 20'

7AL6.02

(15) 90° PARKIN

G STALLS @

9'x18'

(24) 90° PARKING STALLS @ 9'x18'

(11) 90° PARKING STALLS @ 9'x17.5'

(10) 90° PARKING

STALLS @ 9'x18'

(10) 90° PARKING STALLS @ 9'x18'

18.05'

9.00'

18.0

0'

9.00'

18.0

0'

17.5

0'

9.00'

9.00'

10.50'

9.00'

MONUMENT SIGN,REF DETAIL

STONE WALL 'B'REF DETAIL

SAW CUT CLEAN EDGE ALONGEXISTING ASPHALT PVMT, TYP

3A,BL6.04

SCHNEIDER ELECTRIC NEMA 3R/12ELECTRIC POWER STATION,REF. ELEC SHTS, TYP

SEGMENTAL RETAINING WALL,REF DETAIL

CONC. UNIT PAVERS W/ SNOW MELT,REF DETAIL 8

L6.01

1L6.05

DEMO AND REMOVE POST ANDCABLE SYSTEM, TYP

SAW CUT CLEAN EDGE ALONGEXISTING ASPHALT PVMT, TYP

DEMO AND REMOVE POST ANDCABLE SYSTEM, TYP

16L6.01

25.00'

REINF CONC PVMTABOVE STORM PIPE INTHIS LOCATION.#4'S @12 O.C.

9.00

'

20.00'

LIGHT FIXTURE,REF. ELEC SHTS, TYP

LIGHT FIXTURE,REF. ELEC SHTS, TYP

LIGHT FIXTURE,REF. ELEC SHTS, TYP

LIGHT FIXTURE,REF. ELEC SHTS, TYP

LIGHT FIXTURE,REF. ELEC SHTS, TYP

2L6.02

1BL6.02

1AL6.02

ACCESSIBLE POLE SIGN,REF DETAIL 17

L6.01

6AL6.02

6B

L6.02

PRESERVE AND PROTECT,TREES, TYP.

PRESERVE AND PROTECT,TREES, TYP.

6" TH. CONC. PVMT.W/ SNOW MELT,REF DETAIL 1-3,9

L6.01

CONC. CURB AND GUTTER, TYP.REF DETAIL 4

L6.01

6" BOLLARD, TYP OF 7REF DETAIL 18

L6.01

WEATHERED LIMESTONEBANDINGREF DETAIL

5L6.02

395.98'

428.81'

424.55'

178.60'

50.4

0'

235.

62'

40' UTILITY EASEMENT20' UTILITY EASEMENT

60' UTILITY EASEM

ENT

20.0

0' S

ETBA

CK

15.00' SETBACK

40.00

' SET

BACK

20.0

0' SE

TBAC

K

A002

elec. vault

MATCH LINEMATCH LINE MATCH LINEMATCH LINE

PRESERVE AND PROTECT,UTILITIES, TYP.

PRESERVE AND PROTECT,TREES, TYP.

TREES TO BE SALVAGEDTYP OF 2, REPLANT IN SAMELOCATION, ADJUST TO NEWGRADES

183.7

3'

395.98'

60' UTILITY EASEM

ENT

15.00' SETBACK

40.00

' SET

BACK

Lincoln, NE 68508-2883

Kansas City, Missouri

402 477.9291 Fax 402 477.6542

www.clarkenersen.com

1010 Lincoln Mall, Suite 200

Landscape Architecture

Lincoln, Nebraska

InteriorsEngineering

Architecture

Fairway, Kansas

TCEP No.:

3 /

21 /

201

7 1

:14:

00 P

MPl

ot Ti

me

Stam

p:\\

Tcep

-ln-s

rv-0

04\0

00-0

99\0

67-0

01-1

6 Ru

nza

Cor

p HQ

\3) A

ctiv

e W

ork\

3) A

utoC

AD\

0670

01-L

201.

dwg

File

Loc

atio

n/N

ame:

Plaza on the Green8800 Firethorn LaneLincoln, Nebraska

067-001-16

ISSUED

#?

? - # SHEET HISTORY:

Site Materials Plan

L2.01

March 10, 2017

03/10/2017 AS PER CONSTR. DOCUMENTS

SITE MATERIALS PLANSCALE: 1"=20'-0"

PAVEMENT LEGEND:

LINENMODULINE(12" X24")

UNIT PAVEMENT SCHEDULE:

P-1

TYPE STYLE THICKNESS PATTERN COLOR

RUNNING BOND

MANUF. OR APPROVED

6" TH CONCRETE PAVEMENT

WEATHERED LIMESTONE SLABS

EQUAL:

STANDARD GRAY

BELGARD COMPANYOR APPROVED EQUAL

2 3/8"

UNIT PAVEMENT TYPE P-1

RUNNING BOND WITH WEATHERED LIMESTONE BAND

CRUSHED ROCK PAVEMENT

6" TH CONC. PAVEMENTW/ SNOW MELT SYSTEM

UNIT PAVEMENT TYPE P-1W/ SNOW MELT SYSTEM

-A 02 03/21/2017 AS PER ADDENDUM #002

AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
Page 37: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

Lincoln, NE 68508-2883

Kansas City, Missouri

402 477.9291 Fax 402 477.6542

www.clarkenersen.com

1010 Lincoln Mall, Suite 200

Landscape Architecture

Lincoln, Nebraska

InteriorsEngineering

Architecture

Fairway, Kansas

TCEP No.:

3 /

21 /

201

7 2

:31:

50 P

MPl

ot Ti

me

Stam

p:\\

Tcep

-ln-s

rv-0

04\0

00-0

99\0

67-0

01-1

6 Ru

nza

Cor

p HQ

\3) A

ctiv

e W

ork\

3) A

utoC

AD\

0670

01-L

605.

dwg

File

Loc

atio

n/N

ame:

Plaza on the Green8800 Firethorn LaneLincoln, Nebraska

067-001-16

ISSUED

#?

? - # SHEET HISTORY:

Site Details

L6.05

March 10, 2017

03/21/2017 AS PER ADDENDUM #2

SCALE: 3/4"=1'-0"

MONUMENT SIGN1

Plaza on the GreenTenant 1234567890

Tenant 1234567890Tenant 1234567890Tenant 1234567890

Tenant 1234567890

19'-0"

4'-4

"

3'-0"

2'-6"

2'-4

"

1'-8"#5 @12" O.C., EA. WAYY, EA. FACE,VERT. BARS SHALL HAVE 24"EMBEDMENT IN GRADE BEAM

CONT. 2X4 KEYWAY

#6 LONGITUDINAL, TYP. OF 3TOP & BTM.

#4 CLOSED TIE @24"O.C.

3'-6

"

2'-4"

4" ALUMINUM LETTER, 12" TH., STUD MOUNTED, PAINT AND PRIME.MATCH STOREFRONT COLOR: KAWNEER PERMADIZE DARK BRONZEASSUME 20 CHARACTERS PER TENANT LINE. OWNER TO VERIFYACTUAL TENANT TITLES.LIMESTONE VENEER TYPE S-1. MATCH BUILDING STONE PATTERN.

3" 12'-4"

GENERAL NOTE:OWNER TO VERIFY ALL FONTS, SIZES ANDTEXT PRIOR TO SIGN FABRICATION

88008820LIGHT FIXTURE, TYP.

1/4" TH. WEATHERED STEEL, TYP.

13" LETTERING VOID CUT FROM WEATHERED STEEL.7" LETTERING VOID CUT FROM WEATHERED STEEL.

LIMESTONE VENEER TYPE S-1.MATCH BUILDING STONE PATTERN.

1/4" TH. WEATHERED STEEL, TYP.

PROVIDE 34" DRAIN HOLE @ 36" O.C.LOCATED AT BTM OF OUSTIDEBTM. CORNER

SEE ENLARGEMENT FORCONNECTION DETAILS

3" X 12" GALVANIZED PLATE @ 24" O.C.11/2" X 11/2" X 14" GALVANIZED U CHANNEL,CONT. PROVIDE 14" DRAIN HOLE @ 36" O.C.

4" X12" X 38" EMBED PLATE W/ (6)1/2" ØX 4" LONG HEADED STUDS (3 ROWSOF 2 @ 2" O.C., QUALLY SPACED W/ 1"EDGE DISTANCE)

85°

3" X 12" GALVANIZED PLATE @ 24" O.C.

LIGHT FIXTURE, TYP.

1/4" TH. WEATHERED STEEL, TYP.

1/4" TH. WEATHERED STEEL, SHIM TOCREATE DRAINAGE AWAY FROM STONEANCHOR TO 12" PLATE BLOW WITHCONCEALED ANCHOR

LIMSTONE CAP, TH. VARIES TOMATCH STONE VENEEER PATTERN

RUBBER MEMBRANE FLASHING,INFILL BETWEEN STEEL PLATES TOPROVIDE UNIFORM SURFACE.

CONCEALED FASTENER, TYP OF 6 THIS FACE

1'-3"

ELEVATION

ELEC. ELEVATION

SECTION

END ELEVATION

ENLARGEMENT

GENERAL NOTE:DAMPPROOF WHEN STONE ISWITHIN 12" OF GRADE OR INCONTACT WITH CONCRETE, TYP.

LIGHT FIXTURE, SEE ELECTRICAL PLANS TYP.LIGHT FIXTURE, SEE ELECTRICAL PLANS TYP.

LOCATION OF LIGHT FIXTURE TRANSFORMER. SEE THEELECTRICAL PLANS FOR ADDITIONAL INFORMATION. EACHLIGHT FIXTURE TRANSFORMER IS TO BE INSTALLED INPLACE OF STONE COURSE.

12'-0"

1'-8

"1'

-101 2"

Page 38: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

EXTERIOR MATERIALS KEY

VETTER STONE - NORTHERN BUFF -SPLITFACE COURSED ASHLAR w/ RANDOM VERTICALS

CAST STONE

LIMESTONE 1

PACIFIC CAST STONE - COLOR & PATTERN TO MATCH LIMESTONE

FORMED METAL

PANEL

NOTE: MATERIALS LISTED ARE BASIS OF DESIGN, REFER SPEC. FOR APPROVED ALTERNATES

WEATHERED METAL PANEL -CONCEALED FASTENERSTANDARD PANELS: MORIN CF SERIES PANELS AS SHOWN BELOWCUSTOM PANELS: AS SHOWN BELOW

MAIN LEVEL100' - 0"

UPPER LEVEL115' - 0"

LOWER LEVEL85' - 0"

PENTHOUSE LEVEL130' - 7"

B.O. UPPER ROOF DECK144' - 8 1/2"

1

A5.13

1

A3.10

2

A3.10

1

A3.11

7 9 12 138 106 1143 51 2

3

A4.10

AL-402

AL-213 AL-215

AL-317 AL-318 AL-319

AL-220

AL-221

AL-

314

AL-

210

AL-403

B.O. LOWER ROOF DECK129' - 8"

F1.21

1

30' - 0"7' - 2"7' - 10"15' - 0"15' - 0"15' - 0"27' - 0 1/2"5' - 10"8' - 2 3/4"7' - 3 1/4"3' - 10 1/2"2' - 6 1/2"

METAL PANEL SYSTEM BEYOND

SPLITFACE COURSED ASHLAR LIMESTONE VENEER w/ RANDOM VERTICALS, TYP.

CAST STONE VENEER BASE, TYP. @ GRADE

LIMESTONE VENEER SITE WALL, REF. LANDSCAPE.

CAST STONE WALL CAP, TYP. @ LIMESTONE WALLS

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

CUSTOM CAST STONE STACKED VENEER THIS FACE

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

8" CAST STONE BAND

METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

METAL PANEL SYSTEM, PATTERN "A" REF. METAL PANEL TYPES, 3/A2.11

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM CURTAINWALL WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

AL-219

SPLITFACE LIMESTONE VENEER, TYP.

BUILDING SIGNAGE, REF. F1.21

PREFINISHED METAL GUARDRAIL SYSTEM

PRECAST A4 SILL

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

SPLITFACE LIMESTONE VENEER, TYP.

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

CAST STONE WALL CAP, TYP. @ LIMESTONE WALLS

METAL WALL COPING BEYOND

CUSTOM CAST STONE STACKED VENEER THIS FACE

3.00°

SLOPED WALL(3° FROM PLUMB)METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

PRECAST C8 LINTELPRECAST D8 LINTEL02A

02A

PRECAST B4 SILL

02A

PRECAST G4

8

A8.10

9

A8.10

PRECAST I4 SILL

MAIN LEVEL100' - 0"

UPPER LEVEL115' - 0"

LOWER LEVEL85' - 0"

PENTHOUSE LEVEL130' - 7"

B.O. UPPER ROOF DECK144' - 8 1/2"

2

A5.13

2

A3.111

A3.12

2

A3.12

5

A5.12

A C E J LDB KGF PM NH

2

A4.11

AL-313

AL-209

AL-212

AL-

109

AL-

108AL-107

B.O. LOWER ROOF DECK129' - 8"

4' - 2 1/2" 8' - 9 1/2" 9' - 0" 16' - 0" 11' - 4 3/4" 7' - 8" 20' - 2" 4' - 9 1/4" 7' - 5 1/2" 8' - 6 1/2" 9' - 7 1/2"9"

1' - 7 3/4"

METAL PANEL SYSTEM, PATTERN "A" REF. METAL PANEL TYPES, 3/A2.11

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

SPLITFACE LIMESTONE VENEER, TYP.

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

CAST STONE WALL CAP, TYP. @ LIMESTONE WALLS

SLOPED WALL(3° FROM PLUMB)METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

SPLITFACE LIMESTONE VENEER, TYP.

PREFINISHED METAL GUARDRAIL SYSTEM

PREFINISHED METAL GUARDRAIL SYSTEM

CAST STONE WALL CAP, TYP. @ LIMESTONE WALLS

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM CURTAINWALL WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

CAST STONE VENEER BASE, TYP. @ GRADE

LIMESTONE VENEER SITE WALL, REF. LANDSCAPE.

CAST STONE VENEER BASE, TYP. @ GRADE

PRECAST E8 CAST STONE VENEER BASE, TYP. @ GRADE

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZINGAL-211

5" WIDE SAWN VERTICAL LIMESTONE VENEER INSET 1"

5" WIDE SAWN VERTICAL LIMESTONE VENEER INSET 1"

SLOPED WALL(3° FROM PLUMB)METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

3.00°

PRECAST B4 SILL

PRECAST H4

PRECAST G402A

PRECAST E4 SILL

PRECAST B4 SILL 02A

PENTHOUSE LEVEL130' - 7"

B.O. UPPER ROOF DECK144' - 8 1/2"

AL-402AL-403

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

11

A6.60

5" N

OM

.10

" N

OM

.2"

NO

M.

8" N

OM

.

EQ EQ EQ

EQ EQ EQ

EQ EQ EQ

SPLITFACE COURSED ASHLAR w/ RANDOM VERTICALS

TYP. EA. ROW

TYP. EA. ROW

TYP. EA. ROW

#SHEET HISTORY:

?

? - #

Lincoln, Nebraska

1010 Lincoln Mall, Suite 200

Lincoln, NE 68508-2883

402 477.9291 Fax 402 477.6542

Kansas City, Missouri

Fairway, Kansas

Landscape Architecture

www.clarkenersen.com

Architecture

EngineeringInteriors

Plo

t Ti

me

Sta

mp

:

File

Lo

ca

tio

n/N

am

e:

ISSUED

3/2

1/2

01

7 1

:42

:58

PM

C:\

(1)

Re

vit

Pro

jec

ts\

20

17

\0

67

00

1-R

CH

Q-A

-17

_h

ea

the

r.k

ee

le@

cla

rke

ne

rse

n.c

om

.rv

t

Exterior Elevations

A2.10

TCEP No.: 067-001-16

8800 Firethorn LaneLincoln, Nebraska

Plaza on the Green

March 10, 2017

03/10/2017 AS PER CONSTRUCTION DOC.

SCALE: 1/8" = 1'-0"

SOUTH ELEVATION1

SCALE: 1/8" = 1'-0"

WEST ELEVATION3

SCALE: 1/8" = 1'-0"

SOUTH PENTHOUSE ELEVATION2

SCALE: 3/8" = 1'-0"

LIMESTONE PATTERN DETAIL4

A - 01 03/16/2017 AS PER ADDENDUM #01

A - 02 03/21/2017 AS PER ADDENDUM #02

Page 39: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

EXTERIOR MATERIALS KEY

VETTER STONE - NORTHERN BUFF -SPLITFACE COURSED ASHLAR w/ RANDOM VERTICALS

CAST STONE

LIMESTONE 1

PACIFIC CAST STONE - COLOR & PATTERN TO MATCH LIMESTONE

FORMED METAL

PANEL

NOTE: MATERIALS LISTED ARE BASIS OF DESIGN, REFER SPEC. FOR APPROVED ALTERNATES

WEATHERED METAL PANEL -CONCEALED FASTENERSTANDARD PANELS: MORIN CF SERIES PANELS AS SHOWN BELOWCUSTOM PANELS: AS SHOWN BELOW

MAIN LEVEL100' - 0"

UPPER LEVEL115' - 0"

LOWER LEVEL85' - 0"

PENTHOUSE LEVEL130' - 7"

B.O. UPPER ROOF DECK144' - 8 1/2"

1

A5.131

A3.10

2

A3.10

1

A3.11

791213 810 611 4 35 12

3

A4.10

AL-306AL-305 AL-307 AL-310 AL-311 AL-312

AL-208AL-207AL-206AL-205AL-204AL-203

AL-103 AL-104 AL-105 AL-106

B.O. LOWER ROOF DECK129' - 8"

AL-309AL-308

METAL PANEL SYSTEM, PATTERN "A" REF. METAL PANEL TYPES, 3/A2.11

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

SPLITFACE COURSED ASHLAR LIMESTONE VENEER w/ RANDOM VERTICALS, TYP.

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

CAST STONE WALL CAP, TYP. @ LIMESTONE WALLS

PREFINISHED METAL GUARDRAIL SYSTEM

30' - 0" 7' - 2" 7' - 10" 15' - 0" 15' - 0" 15' - 0" 27' - 0 1/2" 5' - 10" 8' - 2 3/4" 7' - 3 1/4" 3' - 10 1/2" 2' - 6 1/2"

PREFINISHED METAL GUARDRAIL SYSTEM

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

METAL PANEL SYSTEM, PATTERN "A" REF. METAL PANEL TYPES, 3/A2.11

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

PRECAST E4 CAST STONE VENEER BASE, TYP. @ GRADE

LIMESTONE VENEER SITE WALL BEYOND, REF. LANDSCAPE.

PRECAST E8 CAST STONE VENEER BASE, TYP. @ GRADE

SLOPED PARAPET WALL(3° FROM PLUMB)METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

SLOPED WALL(3° FROM PLUMB)METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

3.00°

8

A8.10

9

A8.10

PRECAST E4

PRECAST A4

PRECAST E8

PRECAST E4

PRECAST A4 02A

02A

02A

02A

MAIN LEVEL100' - 0"

UPPER LEVEL115' - 0"

LOWER LEVEL85' - 0"

PENTHOUSE LEVEL130' - 7"

B.O. UPPER ROOF DECK144' - 8 1/2"

2

A5.13

2

A3.11

1

A3.12

2

A3.12

5

A5.12

ACEJL D BK G FP MN H

2

A4.11

AL-

214

AL-301 AL-302 AL-303

AL-201

AL-304

AL-202

AL-102

AL-404

B.O. LOWER ROOF DECK129' - 8"

METAL PANEL SYSTEM, PATTERN "A" REF. METAL PANEL TYPES, 3/A2.11

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL PANEL SYSTEM, PATTERN "B" REF. METAL PANEL TYPES, 3/A2.11

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

CAST STONE VENEER BASE, TYP. @ GRADE

1' - 7 3/4" 9" 9' - 7 1/2" 8' - 6 1/2" 7' - 5 1/2" 4' - 9 1/4" 20' - 2" 7' - 8" 11' - 4 3/4" 16' - 0" 9' - 0" 8' - 9 1/2" 4' - 2 1/2"

OVERHEAD DOOR

HM DOOR & FRAME, PT TO MATCH OVERHEAD DOOR

PRECAST C8 LINTEL

PRECAST A4 SILL

SPLITFACE COURSED ASHLAR LIMESTONE VENEER w/ RANDOM VERTICALS, TYP.

CAST STONE WALL CAP, TYP. @ LIMESTONE WALLS

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

LIMESTONE VENEER SITE WALL BEYOND, REF. LANDSCAPE.

ALUMINUM CURTAINWALL WINDOW ASSEMBLY w/ 1" INSUL. GLAZING, BEYOND

ALUMINUM STOREFRONT WINDOW ASSEMBLY w/ 1" INSUL. GLAZING

METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

PREFINISHED METAL GUARDRAIL SYSTEM

METAL WALL COPING TO MATCH METAL PANEL SYSTEM

HARDCOAT PLASTER SYSTEM

METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

5" WIDE SAWN VERTICAL LIMESTONE VENEER INSET 1". CONT. UP FACADE 2" WIDE

5" WIDE SAWN VERTICAL LIMESTONE VENEER INSET 1". CONT. UP FACADE 2" WIDE

SLOPED WALL(3° FROM PLUMB)METAL PANEL SYSTEM, PATTERN "C" REF. METAL PANEL TYPES, 3/A2.11

3.00°

02APRECAST B4 SILL

PRECAST D8 LINTEL

02A

2" CAP

4'-8"

PANEL

10"

GUTTER

1' - 0" 1' - 0" 1' - 0" 1' - 5 1/2" 1' - 5 1/2" 1' - 0" 1' - 2 1/2" 1' - 0" 1' - 0" 1' - 0" 1' - 5 1/2" 1' - 0" 1' - 2 1/2" 1' - 0" 1' - 0" 1' - 0" 1' - 2 1/2" 1' - 0" 1' - 0" 1' - 0" 1' - 2 1/2" 1' - 0" 1' - 5 1/2" 1' - 2 1/2" 1' - 0" 1' - 0" 1' - 0"

PANEL

A-12

PANEL

W-12

PANEL

T-12

PANEL

TT-12

PANEL

C-14.5-S

PANEL

C-17.5-B

PANEL

C-17.5-F

PANEL

C-14.5-A

STANDARD:

BASIS OF DESIGN - MORIN CF SERIES METAL PANELS

CUSTOM PANEL TYPES:

PANEL

T-12

PANEL

W-12

PANEL

A-12

PANEL

C-17.5-B

PANEL

C-17.5-F

PANEL

C-14.5-A

PANEL

C-14.5-S

PANEL

C-17.5-F

PANEL

A-12

PANEL

W-12

PANEL

TT-12

PANEL

TT-12

PANEL

A-12

PANEL

T-12

PANEL

W-12

PANEL

C-14.5-A

PANEL

A-12

PANEL

T-12

PANEL

C-14.5-S

PANEL

TT-12

PANEL

C-17.5-B

PANEL

C-14.5-A

PANEL

TT-12

PANEL

W-12

29' - 10 1/2"

PANEL

A-12

PANEL

A-12

PANEL

A-12

2" CAP

6'-0"

PANEL

10"

GUTTER

1' - 0" 1' - 0" 1' - 0" 1' - 5 1/2" 1' - 5 1/2" 1' - 0" 1' - 2 1/2" 1' - 0" 1' - 0" 1' - 0" 1' - 5 1/2" 1' - 0" 1' - 2 1/2" 1' - 0" 1' - 0" 1' - 0" 1' - 2 1/2" 1' - 0" 1' - 0" 1' - 0" 1' - 2 1/2" 1' - 0" 1' - 5 1/2" 1' - 2 1/2" 1' - 0" 1' - 0" 1' - 0"

PANEL

T-12

PANEL

W-12

PANEL

A-12

PANEL

C-17.5-B

PANEL

C-17.5-F

PANEL

C-14.5-A

PANEL

C-14.5-S

PANEL

C-17.5-F

PANEL

A-12

PANEL

W-12

PANEL

TT-12

PANEL

TT-12

PANEL

A-12

PANEL

T-12

PANEL

W-12

PANEL

C-14.5-A

PANEL

A-12

PANEL

T-12

PANEL

C-14.5-S

PANEL

TT-12

PANEL

C-17.5-B

PANEL

C-14.5-A

PANEL

TT-12

PANEL

W-12

29' - 10 1/2"

PANEL

A-12

PANEL

A-12

PANEL

A-12

10"

GUTTER

PANEL

T-12

PANEL

W-12

PANEL

A-12

PANEL

W-12

PANEL

TT-12

PANEL

A-12

PANEL

T-12

PANEL

TT-12

PANEL

W-12

PANEL

TT-12

PANEL

A-12

PANEL

T-12

1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0"

12' - 0"

PANEL

LENGTH

VARIES

5' -

8"

7' -

0"

1' - 2 1/2" 1' - 2 1/2" 1' - 5 1/2" 1' - 5 1/2"

1' - 0" 1' - 0" 1' - 0" 1' - 0"

4"

4" 7"

4"

LEN

GT

H V

AR

IES

LEN

GT

H V

AR

IES

LEN

GT

H V

AR

IES

LEN

GT

H V

AR

IES

CUSTOM PATTERN "A"

CUSTOM PATTERN "B"

STANDARD PATTERN

7"

2 1/2"

7"

2 1/2"

#SHEET HISTORY:

?

? - #

Lincoln, Nebraska

1010 Lincoln Mall, Suite 200

Lincoln, NE 68508-2883

402 477.9291 Fax 402 477.6542

Kansas City, Missouri

Fairway, Kansas

Landscape Architecture

www.clarkenersen.com

Architecture

EngineeringInteriors

Plo

t Ti

me

Sta

mp

:

File

Lo

ca

tio

n/N

am

e:

ISSUED

3/2

1/2

01

7 1

:43

:13

PM

C:\

(1)

Re

vit

Pro

jec

ts\

20

17

\0

67

00

1-R

CH

Q-A

-17

_h

ea

the

r.k

ee

le@

cla

rke

ne

rse

n.c

om

.rv

t

Exterior Elevations

A2.11

TCEP No.: 067-001-16

8800 Firethorn LaneLincoln, Nebraska

Plaza on the Green

March 10, 2017

03/10/2017 AS PER CONSTRUCTION DOC.

SCALE: 1/8" = 1'-0"

NORTH ELEVATION1

SCALE: 1/8" = 1'-0"

EAST ELEVATION2 METAL PANEL TYPES

A - 01 03/16/2017 AS PER ADDENDUM #01

A - 02 03/21/2017 AS PER ADDENDUM #02

Page 40: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

LOWER LEVEL85' - 0"

GB-3

GB-1

GB-2

TTD-4

CT-2 AT FIXTURE WALL

CT-4

CT-2 AT INSET REAR WALL

PCT-1 BASE

SOLID SURFACE COUNTERTOP WITH INTEGRAL SINKS, SKIRT & APRON. (SSM-1)

TPTN-2

FRAMELESS MIRROR W/ POLISHED EDGE

3" 4' - 6" 3"3' -

0"

3' -

4"

11' - 2" 10 3/8" 5' - 0" 9 3/8" 02A

9

A6.60

Sim

LOWER LEVEL85' - 0"

GB-3

GB-1

GB-2

9 3/8" 5' - 0" 10 3/8" 11' - 2"

CT-1 AT FIXTURE WALL

CT-3

CT-1 AT INSET REAR WALL

PCT-2 BASE

SOLID SURFACE COUNTERTOP WITH INTEGRAL SINKS, SKIRT & APRON. (SSM-1)

TPTN-1

FRAMELESS MIRROR W/ POLISHED EDGE

9

A6.60

Sim 02A

UPPER LEVEL115' - 0"

M-1

GB-3

GB-1

GB-2

TTD1

1' - 6" 4' - 11 1/2"

2' -

10"

6"

TLT/SHOWER

357- 82 SFCH-1

6"

9

A6.60

SOLID SURFACE COUNTERTOP WITH INTEGRAL SINKS, SKIRT & APRON. (SSM-1)

02A

UPPER LEVEL115' - 0"

1' - 6" 5' - 6 1/8" 3' - 6 1/8"

2' -

11

3/8"

3 5/

8"

GB-3

GB-1

GB-2

4' - 6"

3' -

0"

6 1/

2"2'

- 9

1/2

"

5' - 0" 6 1/8" 3' - 0" 6 1/8" 3' - 0" 6 1/8"7 11/16" 5' - 0" 7 11/16"

CT-1 AT FIXTURE WALL

CT-3

CT-1 AT INSET REAR WALL

FRAMELESS MIRROR W/ POLISHED EDGE

HD-1

02A

UPPER LEVEL115' - 0"

3' - 6 1/8" 5' - 6 1/8"3

5/8"

2' -

11

3/8"

GB-3

GB-1

GB-2

2' -

9 1

/2"

6 1/

2"3'

- 0

"

4' - 6"

5' - 0" 1' - 1 13/16" 3' - 0" 6 1/8" 3' - 0" 6 1/8"CT-1 AT FIXTURE WALL

CT-3

CT-1 AT INSET REAR WALL

FRAMELESS MIRROR W/ POLISHED EDGE

HD-1

02A

#SHEET HISTORY:

?

? - #

Lincoln, Nebraska

1010 Lincoln Mall, Suite 200

Lincoln, NE 68508-2883

402 477.9291 Fax 402 477.6542

Kansas City, Missouri

Fairway, Kansas

Landscape Architecture

www.clarkenersen.com

Architecture

EngineeringInteriors

Plo

t Ti

me

Sta

mp

:

File

Lo

ca

tio

n/N

am

e:

ISSUED

3/2

1/2

01

7 1

:43

:18

PM

C:\

(1)

Re

vit

Pro

jec

ts\

20

17

\0

67

00

1-R

CH

Q-A

-17

_h

ea

the

r.k

ee

le@

cla

rke

ne

rse

n.c

om

.rv

t

Interior Elevations

A6.20

TCEP No.: 067-001-16

8800 Firethorn LaneLincoln, Nebraska

Plaza on the Green

March 10, 2017

03/10/2017 AS PER CONSTRUCTION DOC.

SCALE: 3/8" = 1'-0"

WOMENS LL RR1SCALE: 3/8" = 1'-0"

MEN'S LL RR2

SCALE: 3/8" = 1'-0"

UP - TLT/SHOWER5

SCALE: 3/8" = 1'-0"

WOMENS UP RR3

SCALE: 3/8" = 1'-0"

MEN'S UP RR4

A - 02 03/21/2017 AS PER ADDENDUM #02

02A

Page 41: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

FLOOR LINE

WD - 1

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

WD - 2 WD - 3, NOT USED

REF: SCHED.

DOOR WIDTH

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

REF: SCHED.

DOOR WIDTH

3" 8"

2' -

9"

MA

X.*

3' -

7"

T TEMPERED GLASS

L LAMINATED GLASS

T

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

REF: SCHED.

DOOR WIDTH

8" 8"

1' -

0"

4' -

0"

T

OD - 1

RE

F: S

HE

D.

DO

OR

HE

IGH

T

REF: SCHED.

DOOR WIDTH

RE

F: I

NT

. E

LE

V.

SIL

L H

EIG

HT

OD - 2

REF: SCHED.

DOOR WIDTH

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

FLOOR LINE

HMF - 1

2"

REF: SCHED.

DOOR WIDTH /

PAIR WIDTH 2"

2"

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

HMF - 3

2"

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

2"

1' -

4"

2"

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

2"

REF: SCHED.

DOOR WIDTH

2"

1' - 4" 2"

2"

REF: SCHED.

DOOR WIDTH 2"

4"

HMF - 5, NOT USED

T TEMPERED GLASS

L LAMINATED GLASS

T

T

HMF - 2

2"

REF: SCHED.

DOOR WIDTH /

PAIR WIDTH 2"

4"

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

2"

REF: SCHED.

DOOR WIDTH

2"

1' - 6" 2"

2"

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

T4"

HMF - 4

FLOOR LINE

HMD - 1

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

HMD - 2 HMD - 3, NOT USED

REF: SCHED.

DOOR WIDTH

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

REF: SCHED.

DOOR WIDTH

3" 8"

2' -

9"

MA

X.*

3' -

7"

T TEMPERED GLASS

L LAMINATED GLASS

T

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

REF: SCHED.

DOOR WIDTH

8" 8"

1' -

0"

4' -

0"

T

REF: SCHED.

DOOR WIDTH

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

5" 8"

6"

HMD - 4

T

T

FLOOR LINE

REF: SCHED.

DOOR WIDTH

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

5" 8"

6"

3' -

8"

10"

ALD -

1

T

T

T TEMPERED GLASS

L LAMINATED GLASS

REF: SCHED.

DOOR WIDTH

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

5" 8"

10"

ALD - 2, NOT USED

T

REF: SCHED.

DOOR WIDTH

RE

F: S

CH

ED

.

DO

OR

HE

IGH

T

3 1/2"

3 1

/2"

6 1

/2"

ALD -

4

T

REF: SCHED.

DOOR WIDTHR

EF

: S

CH

ED

.

DO

OR

HE

IGH

T

3 1/2"

3 1

/2"

3 1

/2"

3' -

7"

6 1

/2"

ALD - 3, NOT USED

T

T

DOOR & FRAME TYPE GENERAL NOTES

1. PROVIDE SAFETY GLAZING OR FIRE-PROTECTION-RATED GLAZING IN LOCATIONS REQUIRED BY

CURRENT LOCAL CODE. NOTIFY ARCHITECT OF CHANGES REQUIRED TO THE DRAWINGS. PROVIDE

OBSCURE GLAZING AS INDICATED.

2. PROVIDE AND INSTALL SAFETY GLAZING IN LOCATIONS AS PER SECTION 2406 & 2408 OF THE 2009

INTERNATIONAL BUILDING CODE.

3. ALL DIMENSIONS ARE NOMINAL. ACTUAL DIMENSIONS TO BE PROVIDED BY SUPPLIER W/

ADJUSTMENTS MADE FOR INSTALLATION TOLERANCES REQUIRED. VERIFY ALL EXISTING OPENINGS

PRIOR TO ORDER OF ALL NEW DOORS, DOOR FRAMES AND WINDOW FRAMES.

4. SEE FLOOR PLANS FOR DIRECTION OF DOOR SWINGS.

5. REFER TO WALL TYPE THICKNESS FOR THROAT DEPTHS OF HOLLOW METAL DOOR AND WINDOW

FRAMES INSTALLED IN STEEL STUD WALLS W/ GYPSUM. HOLLOW METAL DOOR AND WINDOW

FRAMES INSTALLED IN PRECAST, CAST-IN PLACE OR C.M.U. WALLS SHALL HAVE A STANDARD 6"

NOMINAL THROAT DEPTH AND SHALL BE CENTERED IN THE WALL, UNLESS NOTED OTHERWISE.

6. ALL INTERIOR HOLLOW METAL DOOR FRAMES SHALL BE GROUTED FULL. COORDINATE WITH

ELECTRICAL TRADES, FINISH HARDWARE AND ELECTRONIC EQUIPMENT.

7. ALL EXTERIOR ALUMINUM WINDOW FRAMING WERE DESIGNED TO EFCO SERIES 403 OR AS NOTED ON

THE

DRAWINGS WITH 1" INSULATED LOW 'E' GLAZING. INTERIOR HOLLOW METAL WINDOW FRAMING

DESIGNED

WITH INSULATED AND NON-INSULATED GLAZING AS NOTED ON THE DRAWINGS.

8. ALL INTERIOR DOOR FRAMES OF C.M.U. WALLS BEGIN 4" FROM THE FINISH FACE OF THE ADJACENT

WALLS, AND ALL INTERIOR DOOR FRAMES OF STUD WALLS W/ GYPSUM WALLS BEGIN 4" FROM THE

FINISH FACE OF THE ADJACENT WALLS UNLESS OTHERWISE NOTED.

9. CURTAIN WALL WINDLOADS AND DEADLOADS ENGINEERED BY WINDOW SUPPLIER. WINDLOAD

ANCHORS SUPPLIED BY WINDOW SUPPLIER. DEADLOADS TO TRANSFER TO FOUNDATION. SEE

STRUCTURAL DRAWINGS FOR WINDLOAD AND DEADLOAD REQUIREMENTS. PROVIDE EXPANSION

MULLIONS IN LONGER FRAMES AS REQUIRED.

10. VERIFY HOLLOW METAL FRAME FINISH WITH FINISH SCHEDULE.

11. MULLION LOCATIONS SHALL BE AS INDICATED ON THE DRAWINGS AND SHALL BE REFLECTED IN THE

SHOP DRAWINGS. NOTIFY ARCHITECT OF ANY CHANGES OR DEVIATIONS.

12. BORROWED LIGHT LOCATIONS SHALL BE AS INDICATED ON THE PLAN DRAWINGS AND SHALL BE

REFLECTED IN THE SHOP DRAWINGS. NOTIFY ARCHITECT OF ANY CHANGES OR DEVIATIONS.

PROVIDE GLAZING PANELS AS INDICATED.

INDICATES 1" INSULATED ALUMINUM PANEL.

INDICATES 1/4" FLOAT GLASS.

INDICATES 1/4" WIRE SAFETY GLASS.

INDICATES 1" CLEAR INSULATING VISION GLASS

INDICATES 1/4" LAMINATED SAFETY GLASS.

INDICATES 1" LAMINATED INSULATED SAFETY GLASS.

INDICATES 1/4" LAMINATED OPAQUE SPANDREL GLASS

A

F

FW

CIG

L

LIG

SP

#SHEET HISTORY:

?

? - #

Lincoln, Nebraska

1010 Lincoln Mall, Suite 200

Lincoln, NE 68508-2883

402 477.9291 Fax 402 477.6542

Kansas City, Missouri

Fairway, Kansas

Landscape Architecture

www.clarkenersen.com

Architecture

EngineeringInteriors

Plo

t Ti

me

Sta

mp

:

File

Lo

ca

tio

n/N

am

e:

ISSUED

3/2

1/2

01

7 1

:43

:19

PM

C:\

(1)

Re

vit

Pro

jec

ts\

20

17

\0

67

00

1-R

CH

Q-A

-17

_h

ea

the

r.k

ee

le@

cla

rke

ne

rse

n.c

om

.rv

t

Door Schedule, DoorTypes, Frame Types

A6.40

TCEP No.: 067-001-16

8800 Firethorn LaneLincoln, Nebraska

Plaza on the Green

March 10, 2017

03/10/2017 AS PER CONSTRUCTION DOC.

DOOR SCHEDULE

DOOR NO.

PAIR

WIDTH

DOOR FRAME

HARDWARE REMARKSWIDTH HEIGHT TYPE FINISH TYPE FINISH

101 3' - 3

1/2"

7' - 0" ALD-1 PRE-FIN AL-101 PRE-FIN 7.0

102 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 18.0 2, 5

103 3' - 0" 7' - 0" HMD-4 PT HMF-4 PT 12.0 2, 5

106 2' - 6" 7' - 0" HMD-1 PT HMF-1 PT 28.0 4

107 3' - 0" 7' - 0" WD-1 STN HMF-1 PT 34.0

108 3' - 0" 7' - 0" WD-1 STN HMF-1 PT 33.0

110.1 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-109 PRE-FIN 2.0

110.2 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-110 PRE-FIN 9.0

111 3' - 0" 7' - 0" HMD-2 PT HMF-1 PT 19.0 3, 5

111.1 5' - 0" 4' - 2" OD-2 PREFIN - PREFIN -

112 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 26.0 3, 5

114 3' - 0" 8' - 0" ALD-1 PREFIN AL-111 PREFIN 17.0 3, 5

114.2 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-108 PRE-FIN 6.0

114.3 4' - 0" 4' - 2" OD-2 PREFIN - PREFIN 6.0

114.4 3' - 2" 0" ALD-1 PRE-FIN AL-106 PRE-FIN 6.0

115 3' - 0" 8' - 0" ALD-1 PREFIN AL-112 PREFIN 17.0

115.2 3' - 2" 0" ALD-1 PRE-FIN AL-105 PRE-FIN 6.0

117.1 3' - 0" 7' - 0" WD-1 STN HMF-3 PT 23.0 3, 5

117.2 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-103 PRE-FIN 6.0

118 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 25.0 2, 5

119 3' - 0" 7' - 0" HMD-1 PT HMF-2 PT 27.0 2, 5

120 3' - 0" 7' - 0" HMD-1 PT HMF-2 PT 27.0 2, 5

121 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 22.0 2, 5

122.1 3' - 0" 7' - 0" HMD-2 PT HMF-1 PT 13.0 2, 5

122.2 3' - 6" 7' - 0" HMD-1 PT HMF-1 PT 8.0

123 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 22.0 2, 5

132 16' - 0" 10' - 8" OD-1 PT -

200.1 6' - 0" 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-219 PRE-FIN 1.0 6

200.2 6' - 0" 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-217 PRE-FIN 10.0

201 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 14.0 1, 5

202 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 21.0

203 3' - 0" 7' - 0" HMD-4 PT HMF-4 PT 12.0 2, 5

203.1 3' - 6" 7' - 3 3/4" ALD-1 PRE-FIN AL-212 PRE-FIN 7.1

205 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 23.0 3, 5

205.1 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-208 PRE-FIN 4.0

205.2 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-208 PRE-FIN 4.0

205.3 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-206 PRE-FIN 4.0

206 2' - 6" 7' - 0" HMD-1 PT HMF-1 PT 26.0 4

210 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 24.0

301 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 14.0 1, 5

302 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 21.0

303 3' - 0" 7' - 0" HMD-4 PT HMF-4 PT 11.0 2, 5

305 3' - 0" 7' - 0" WD-1 STN HMF-1 PT 34.0

306 3' - 0" 7' - 0" WD-1 STN HMF-1 PT 33.0

307 2' - 6" 7' - 0" HMD-1 PT HMF-1 PT 20.0 4

310 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 26.0 4

318.1 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-312 PRE-FIN 3.0

319.2 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-310 PRE-FIN 3.0

330 3' - 2" 0" ALD-1 PRE-FIN AL-109 PRE-FIN -

332 3' - 2" 0" ALD-1 PRE-FIN AL-110 PRE-FIN -

333 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 24.1

336 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-106 PRE-FIN -

337 3' - 0" 8' - 0" ALD-1 PRE-FIN AL-105 PRE-FIN -

345 3' - 0" 7' - 0" WD-1 STN HMF-1 PT 26.0

352 3' - 0" 7' - 0" WD-1 STN HMF-1 PT 26.0

353 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 20.0

354 3' - 0" 7' - 0" WD-1 STN HMF-1 PT 31.0

357 3' - 0" 7' - 0" WD-1 STN HMF-1 PT 32.0

358 3' - 0" 7' - 0" WD-1 STN HMF-1 PT 32.0

401.1 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 14.0 2, 5

401.2 3' - 0" 7' - 0" WD-2 STN HMF-1 PT 29.0

401.3 3' - 0" 8' - 0" HMD-1 PT HMF-1 PT 5.0

404 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 14.0 2, 5

405.1 3' - 6" 7' - 0" HMD-1 PT HMF-1 PT 16.0

405.2 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 15.0 1, 5

406.1 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 15.0 1, 5

406.2 3' - 0" 7' - 0" HMD-1 PT HMF-1 PT 15.0 1, 5

SCALE: 1/4" = 1'-0"

WOOD DOOR TYPESSCALE: 1/4" = 1'-0"

OVERHEAD COILING DOOR TYPE

SCALE: 1/4" = 1'-0"

HOLLOW METAL FRAME TYPES

SCALE: 1/4" = 1'-0"

HOLLOW METAL DOOR TYPESSCALE: 1/4" = 1'-0"

ALUMINUM DOOR TYPES

NO. REMARK

1 Fire Rating - 1hr

2 Fire Rating - 2hr

3 Fire rating - Smoke

4 Grill, See Mech.

5 Fire Rated glass to be clear, see spec.

6 Prep frame for future ADA operator

DOOR SCHEDULE REMARKS

*TO COMPLY WITH ADA REQUIREMENTS.

*TO COMPLY WITH ADA REQUIREMENTS.

A - 02 03/21/2017 AS PER ADDENDUM #02

02A

02A

02A

Page 42: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

J

6.7

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

6" 6" 8"

1' -

0 1

/4"

7 3/

4"8"

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

#5 CORNER BAR W/ 24" LEGS, TYP @ 12" O.C.

8 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT BAR W/ 50" VERT LEG & 16" HOOK

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C.

13

J

1' - 6"

1' -

0"

1' -

0"

STOOP GRADE BEAM, SEE #1/S3.04

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN ABOVE

LINE OF BASEPLATE ABOVE

11 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

ANCHOR BOLT LOCATION, TYP

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

1' - 4"

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C.

#4 TIE @ 8" O.C.

13

L

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C.

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN ABOVELINE OF BASEPLATE ABOVE

8 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

ANCHOR BOLT LOCATION, TYP

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

8" 8"

1' - 4"

1' -

0"

1' -

0"

2' -

0"

1' - 0"13

P

3 5/

8"1'

- 0

3/8

"

1' -

0 3

/8"

6 5/

8"5"

1' - 4"

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN ABOVE

LINE OF BASEPLATE ABOVE

ANCHOR BOLT LOCATION, TYP

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

STEM WALL, BELOW

2' - 0"

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C.

8 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

12

L

4" 8" 1' - 0"

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C. REINF. CIP CONCRETE WALL,

SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN ABOVE

LINE OF BASEPLATE ABOVE

8 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK ANCHOR BOLT LOCATION, TYP

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

1' -

0"

1' -

0"

2' -

0"

L

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

10"

1' -

4"

10" 8"

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

1' - 6"

8"8"

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

BETWEEN GRIDS 6.7 & 7

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 8" O.C.

#5 CORNER BAR W/ 24" LEGS, TYP @ 12" O.C.

2' -

2"

6 - #8's VERTICAL W/ #8 DOWEL @ EACH VERT BAR W/ 74" VERT LEG & 18" HOOK

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

7

L

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C.

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN ABOVE

LINE OF BASEPLATE ABOVE

6 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

ANCHOR BOLT LOCATION, TYP

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

8"

9" 9"

1' - 6"

1' -

0"

8"8"

8" 8"

#5 CORNER BAR W/ 24" LEGS @ 12" O.C., TYP

9

L

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C.

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN ABOVE

LINE OF BASEPLATE ABOVE

8 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

ANCHOR BOLT LOCATION, TYP

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

1' -

4"

8"8"

1' -

0"

9" 9"

1' - 6"

4.8

N

5

6"2' - 0"

6"

3' -

0"

1' - 10 3/4"7°

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN

LINE OF BASEPLATE BELOW

#6 DOWEL W/ 12" HOOK INTO PAD FOOTING, TYP OF 8 AS SHOWN

ANCHOR BOLT LOCATION, TYP

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

5/8"Ø x6" LONG HEADED STUD @ 8" O.C. EACH FACE

#4 'U' BAR W/ 24" LEGS @ 12" O.C.

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

L

6.3

11"11"8"

8"

1' -

4"

1' - 10"

8" 8" 6"

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C.

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN ABOVE

LINE OF BASEPLATE ABOVE

8 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

ANCHOR BOLT LOCATION, TYP

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

8" 8" 6"

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

P

11

8"

4 3/

8"3

5/8"

6"

60°

7 3/4" 8" 4"

8"

8"

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C.

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN ABOVE

LINE OF BASEPLATE ABOVE (SEE BASE PLATE DETAIL @ UPPER RIGHT)

6 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

ANCHOR BOLT LOCATION, TYP

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

8"6 7/8"

2" 1' - 0"

2"

2"

1"Ø DOUBLE NUT ANCHOR BOLTS W/ 12" EMBEDMENT AND 6" PROJECTION

11

1 1/

2"4

1/2"

4 1/

2"1

1/2"

1 1/2" 3" 6" 1 1/2"

HSS 6x6 COLUMN

12"x12"x3/4" BASE PLATE

P

#5 CORNER BAR W/ 24" LEGS @ 12" O.C., TYP

12

P

1' - 0" 1' - 0"

2' - 0"

8"4

3/8"

3 5/

8"8"

#3 CLOSED TIE, TYP OF 2 SETS AS SHOWN @ 10" O.C.

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

HSS COLUMN ABOVE

LINE OF BASEPLATE ABOVE

8 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

DASHED LINES & HATCH INDICATE CHANGE IN TOP OF WALL ELEVATION, SEE SHEET S1.02

ANCHOR BOLT LOCATION, TYP

EXTEND WALL HORIZONTALS THROUGH PIER, TYP

1' -

4"

13

8"

1' -

4"

1'-4" WIDE x 8" DEEP CIP CONCRETE COLUMN

3 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

#4 TIE @ 8" O.C. ALTERNATE HOOK DIRECTION

13

G6.8

REINF. CIP CONCRETE WALL, SEE SECTIONS FOR ADDITIONAL REQUIREMENTS

#4 TIE @ 8" O.C.

2' -

0"

8" 8"

3 - #6's VERTICAL W/ #6 DOWEL @ EACH VERT. BAR W/ 50" VERT. LEG & 16" HOOK

1' -

0"

1' -

0"

#SHEET HISTORY:

?

? - #

Lincoln, Nebraska

1010 Lincoln Mall, Suite 200

Lincoln, NE 68508-2883

402 477.9291 Fax 402 477.6542

Kansas City, Missouri

Fairway, Kansas

Landscape Architecture

www.clarkenersen.com

Architecture

EngineeringInteriors

ISSUED

Foundation Plan Details

S3.03

TCEP No.: 067-001-16

8800 Firethorn LaneLincoln, Nebraska

Plaza on the Green

Mach 10, 2017

03/10/2017 AS PER CONSTRUCTION DOC.

SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL11

SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL12

SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL7

SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL10

SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL6

SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL3SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL4SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL5SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL1SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL2

SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL8

SCALE: 3/4" = 1'-0"

FOUNDATION PLAN DETAIL9

SCALE: 1 1/2" = 1'-0"

CIP COLUMN PLAN DETAIL13

SCALE: 1 1/2" = 1'-0"

FOUNDATION PLAN DETAIL14

Page 43: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

HEAT PUMP SCHEDULE

COOLING PERFORMANCE HEATING PERFORMANCE COIL FAN PERFORMANCE ELECTRICAL

FULL LOAD FULL LOAD FULL LOAD PERFORMANCE MANUFACTURER

COA TOTAL SENSIBLE TOTAL SUPPLY FAN FAN OR APPROVED

MARK SERVES LOCATION CFM EDB/EWB EWT (MBH) (MBH) EER EAT EWT (MBH) COP GPM WPD (FT) CFM ESP MOTOR DISCHARGE RETURN VOLT -PH- Hz MCA MOCP REFRIGERANT EQUIVALENT MODEL REMARKS

CHP-1 1 1/2 TON CONSOLE MECHANICAL 123 MECHANICAL 123 0 75/62.54 77 16.3 13.9 14.8 70.0 45 17.8 3.7 5.0 5.0 520.0 0.50 ECM TOP BOTTOM/FRONT 208 1 60 10.1 15 R410A FLORIDA CA018 1,2,3,4,5,6,7,8,9

CHP-2 1 1/2 TON CONSOLE STAIR 103 STAIR 103 0 75/62.54 77 16.3 13.9 14.8 70.0 45 17.8 3.7 5.0 5.0 520.0 0.50 ECM TOP BOTTOM/FRONT 208 1 60 10.1 15 R410A FLORIDA CA018 1,2,3,4,5,6,7,8,9

CHP-3 1 1/2 TON CONSOLE STAIR 103 STAIR 103 0 75/62.54 77 16.3 13.9 14.8 70.0 45 17.8 3.7 5.0 5.0 520.0 0.50 ECM TOP BOTTOM/FRONT 208 1 60 10.1 15 R410A FLORIDA CA018 1,2,3,4,5,6,7,8,9

HP-01 3 TON VERTICAL CORRIDOR 113 MECHANICAL 112 100 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-02 2 TON VERTICAL KITCHEN 111 MECHANICAL 112 0 75/62.54 77 25.1 21.2 14.6 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM TOP SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1VTC 1,2,3,4,5,6,7,8

HP-03 3 TON VERTICAL CONFERENCE 114 MECHANICAL 112 250 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-04 3 TON VERTICAL CONFERENCE 115 MECHANICAL 112 250 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-05 2 TON VERTICAL LEASABLE 117 FUTURE MECHANICAL 118 75 75/62.54 77 25.1 21.2 14.6 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM TOP SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1VTC 1,2,3,4,5,6,7,8

HP-06 3 TON VERTICAL LEASABLE 117 FUTURE MECHANICAL 118 75 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-07 4 TON VERTICAL LEASABLE 117 FUTURE MECHANICAL 118 75 75/62.54 77 45.3 38.2 13.4 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM TOP SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1VTC 1,2,3,4,5,6,7,8

HP-08 4 TON VERTICAL LEASABLE 117 FUTURE MECHANICAL 118 75 75/62.54 77 45.3 38.2 13.4 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM TOP SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1VTC 1,2,3,4,5,6,7,8

HP-09 4 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 118 100 75/62.54 77 45.3 38.2 13.4 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM TOP SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1VTC 1,2,3,4,5,6,7,8

HP-10 3 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 118 100 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-11 3 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 118 100 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-12 3 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 118 100 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-13 2 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 118 100 75/62.54 77 25.1 21.2 14.6 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM TOP SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1VTC 1,2,3,4,5,6,7,8

HP-14 2 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 118 100 75/62.54 77 25.1 21.2 14.6 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM TOP SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1VTC 1,2,3,4,5,6,7,8

HP-15 3 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 121 75 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-16 2 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 121 100 75/62.54 77 25.1 21.2 14.6 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM TOP SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1VTC 1,2,3,4,5,6,7,8

HP-17 3 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 121 100 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-18 3 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 121 100 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-19 3 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 121 100 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-20 3 TON VERTICAL DATA/ELEC 202 MECHANICAL 121 0 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-21 3 TON VERTICAL ENTRY LOBBY 213 MECHANICAL 210 100 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-22 3 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 210 75 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-23 3 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 210 75 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-24 4 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 210 75 75/62.54 77 45.3 38.2 13.4 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM TOP SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1VTC 1,2,3,4,5,6,7,8

HP-25 4 TON VERTICAL LEASABLE 205 FUTURE MECHANICAL 210 0 75/62.54 77 45.3 38.2 13.4 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM TOP SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1VTC 1,2,3,4,5,6,7,8,11

HP-26 3 TON DOWNFLOW BREAKROOM 318 MECHANICAL 405 100 75/62.54 77 35.2 28.0 14.4 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM BOTTOM SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1CFC 1,2,3,4,5,6,7,8

HP-27 4TON DOWNFLOW BREAKROOM 318 MECHANICAL 405 100 75/62.54 77 45.2 35.2 13.3 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM BOTTOM SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1CFC 1,2,3,4,5,6,7,8

HP-28 5 TON DOWNFLOW OPEN OFFICE 319 MECHANICAL 405 100 75/62.54 77 59.8 47.0 15 70.0 45 59.5 3.9 14.0 10.3 1990.0 0.70 ECM BOTTOM SIDE 208 1 60 40.7 60 R410A FLORIDA ES061-1CFC 1,2,3,4,5,6,7,8

HP-29 2 TON DOWNFLOW OPEN OFFICE 319 MECHANICAL 405 100 75/62.54 77 25.0 19.5 14.5 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM BOTTOM SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1CFC 1,2,3,4,5,6,7,8

HP-30 3 TON DOWNFLOW OPEN OFFICE 319 MECHANICAL 405 100 75/62.54 77 35.2 28.0 14.4 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM BOTTOM SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1CFC 1,2,3,4,5,6,7,8

HP-31 2 TON DOWNFLOW OPEN OFFICE 319 MECHANICAL 405 100 75/62.54 77 25.0 19.5 14.5 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM BOTTOM SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1CFC 1,2,3,4,5,6,7,8

HP-32 2 TON DOWNFLOW OFFICE 339 MECHANICAL 405 50 75/62.54 77 25.0 19.5 14.5 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM BOTTOM SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1CFC 1,2,3,4,5,6,7,8

HP-33 4 TON DOWNFLOW OFFICE 341 MECHANICAL 405 70 75/62.54 77 45.2 35.2 13.3 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM BOTTOM SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1CFC 1,2,3,4,5,6,7,8

HP-34 2 TON DOWNFLOW OFFICE 331 MECHANICAL 405 70 75/62.54 77 25.0 19.5 14.5 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM BOTTOM SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1CFC 1,2,3,4,5,6,7,8

HP-35 2 TON DOWNFLOW TLT/SHOWER 357 MECHANICAL 405 70 75/62.54 77 25.0 19.5 14.5 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM BOTTOM SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1CFC 1,2,3,4,5,6,7,8

HP-36 4TON DOWNFLOW OPEN OFFICE 343 MECHANICAL 405 100 75/62.54 77 45.2 35.2 13.3 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM BOTTOM SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1CFC 1,2,3,4,5,6,7,8

HP-37 2 TON DOWNFLOW OFFICE 346 MECHANICAL 405 50 75/62.54 77 25.0 19.5 14.5 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM BOTTOM SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1CFC 1,2,3,4,5,6,7,8

HP-38 4TON DOWNFLOW OFFICE 348 MECHANICAL 405 70 75/62.54 77 45.2 35.2 13.3 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM BOTTOM SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1CFC 1,2,3,4,5,6,7,8

HP-39 2 TON DOWNFLOW WORKROOM 312 MECHANICAL 405 100 75/62.54 77 25.0 19.5 14.5 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM BOTTOM SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1CFC 1,2,3,4,5,6,7,8

HP-40 5 TON DOWNFLOW MEETING 314 MECHANICAL 405 250 75/62.54 77 59.8 47.0 15 70.0 45 59.5 3.9 14.0 10.3 1990.0 0.70 ECM BOTTOM SIDE 208 1 60 40.7 60 R410A FLORIDA ES061-1CFC 1,2,3,4,5,6,7,8

HP-41 3 TON DOWNFLOW ENTRY LOBBY 317 MECHANICAL 405 70 75/62.54 77 35.2 28.0 14.4 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM BOTTOM SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1CFC 1,2,3,4,5,6,7,8

HP-42 3 TON VERTICAL MEN 305 MECHANICAL 405 70 75/62.54 77 35.3 29.7 14.5 70.0 45 34.3 3.8 9.0 9.5 1200.0 0.70 ECM TOP SIDE 208 1 60 23.4 35 R410A FLORIDA ES035-1VTC 1,2,3,4,5,6,7,8

HP-43 6 TON VERTICAL STAIR 403 MECHANICAL 405 0 75/62.54 77 69.3 59.1 14 70.0 45 66.6 3.7 18.0 16.8 2200.0 0.70 ECM TOP SIDE 208 1 60 31.1 45 R410A FLORIDA ES071-1VTC 1,2,3,4,5,6,7,8, 10

HP-44 4 TON VERTICAL CONFERENCE 401 MECHANICAL 405 160 75/62.54 77 45.3 38.2 13.4 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM TOP SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1VTC 1,2,3,4,5,6,7,8

HP-45 4 TON VERTICAL LIVING ROOM 325 MECHANICAL 405 100 75/62.54 77 45.3 38.2 13.4 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM TOP SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1VTC 1,2,3,4,5,6,7,8

HP-46 4 TON VERTICAL MECHANICAL 405 MECHANICAL 405 0 75/62.54 77 45.3 38.2 13.4 70.0 45 44.4 3.7 12.0 11.1 1600.0 0.70 ECM TOP SIDE 208 1 60 33.3 50 R410A FLORIDA ES049-1VTC 1,2,3,4,5,6,7,8

HP-47 2 TON DOWNFLOW OFFICE 324 MECHANICAL 405 70 75/62.54 77 25.0 19.5 14.5 70.0 45 25.1 3.9 6.0 4.7 800.0 0.70 ECM BOTTOM SIDE 208 1 60 17.4 25 R410A FLORIDA ES025-1CFC 1,2,3,4,5,6,7,8

REMARKS:

1. PROVIDE EXTENDED FIVE YEAR PART WARRANTY ON ENTIRE UNIT INCLUDING COMPRESSOR, REFRIGERANT CIRCUIT AND CONTROL PANEL.

2. PROVIDE SINGLE POINT ELECTRICAL CONNECTION.

3. SEE PIPE KIT SCHEDULE FOR VALVE AND HOSE KIT ACCESSORIES.

4. APPROVED HEAT PUMP MANUFACTURERS ARE CLIMATE MASTER AND FLORIDA

5. EER AND COP PERFORMANCES TO BE AT AHRI ISO STANDARD 13256-1 FOR A CLOSED LOOP TYPE HEAT PUMP SYSTEM AS SCHEDULED WITH

OPERATING CONDITIONS OF COOLING EWT=77, EDB / EWB= 80 / 67 AND HEATING EAT / EWT = 70 / 32.

6. PROVIDE WITH EXTENDED TEMPERATURE RANGE OPTION.

7. PROVIDE WITH ULTRA QUIET CABINET OPTION.

8. PROVIDE WITH TWO STAGE COMPRESSOR AND STAGED FAN OPERATION WITH COMPRESSOR OR EQUAL.

9. PROVIDE COUNCIL HEAT PUMPS WITH INTEGRAL MANUFACTURER PROVIDED DISCONNECT AND MOTOR STARTER.

10. PROVIDE WITH SMOKE DETECTOR INSTALLED IN THE RETURN PLENUM OF HEAT PUMP, DISABLE (HP) UPON POSITIVE IDENTIFICATION AND SEND ALARM TO THE FIRE ALARM CONTROL PANEL.

11. HEAT PUMP IS SHOWN WITH 0 CFM OUTSIDE AIR. AT THE TIME THESE DOCUMENTS WERE PRODUCED, THIS WAS A SHELL SPACE AND OCCUPANCY WAS NOT YET DETERMINED. IF IN THE

FUTURE THIS HEAT PUMP IS DETERMINED TO SERVE AN OCCUPIED SPACE, IT SHALL BE REBALANCED TO BRING IN THE APPROPRIATE AMOUNT OF OUTSIDE AIR.

KITCHEN HOOD SCHEDULE

OPERATING CONDITIONS

EXHAUST DUCT SUPPLY DUCT MOUNTING HEIGHT DISCHARGE MANUFACTURER

MARK SERVES TYPE FITER TYPE MAKEUP AIR CFM SP CONNECTION LENGTH WIDTH HEIGHT CFM SP CONNECTION AFTER FINISH FLOOR CLG HEIGHT LOCATION ACCESSORIES OR EQUIVALENT MODEL REMARKS

KH-1 KITCHEN HOOD TYPE 1, GREASE HOOD BAFFLE FILTER SS PERFORATED PANEL 1,662 0.6 14" DIA 114" 60" 24" 1,500 0.2 8-10" DIA 6'-8" FIELD VERIFY TOP UL, SS1, LF, DC, GC, SSF, SW1, FP, UTL, SP CAPTIVE AIRE 6630 ND-2-PSP-F 1 , 2 ,3, 4, 5, 6, 7

ACCESSORIES

UL - UL LISTED WITHOUT FIRE DAMPER

SS1 - EXTERIOR SHALL BE CONSTURCTED OF MINIMUM 18 GAUGE TYPE 430 STAINLESS STEEL WITH #4 FINISH, INTEGRAL 3" AIR SPACE TO MEET NFPA 96 REQUIRMENTS AGAINST LIMITED COMUSTIBLE WALL

ALL SEAMS, JOITS AND PENETRATIONS OF THE HOOD ENCLOSURE SHALL BE WELDED AND LIQUID TIGHT, ALL UNEXPOSED INTERIOR SURFACES SHALL BE CONSTRUCTED OF MINIMUM

18 GAUGE CORROSION RESISTANT STEEL INCLUDING BUT NOT LIMITED TO DUCTS, PLENUMS AND BRACKETS

LF - LIGHT FIXTURE UL LISTED, LED

DC - DUCT COLLAR WITH 1" MOUNTING FLANGE

GC - GREASE CUP

SSF - STAINLESS STEEL FILTERS

SW1 - LIGHT AND EXHAUST FAN SWITCH MOUNTED ON FACE OF HOOD

FP - FILLER PANEL, COORDINATE WITH CEILING HEIGHT

FS - FACTORY PROVIDED AND PIPED NFPA APPROVED ANSUL FIRE SUPPRESSION SYSTEM WITH GAS SHUT OFF VALVE

UTL - 20" UTILITY CABINET EXTENSION ON LEFT END OF HOOD

SP - PERFORATED SUPPLY PLENUM

REMARKS:

1. EXHAUST FAN FOR FOR EACH HOOD SHALL BE PROVIDED BY THE SAME VENDOR AS THE KITCHEN HOOD SUPPLIER, EXHAUST FAN SHALL MATCH THE PERFORMANCE OF THE SUBMITTED HOOD

2. PRIOR TO ORDERING, THE CONTRACTOR SHALL VERIFY THE LOCATION OF THE EXHAUST HOOD DUCT CONNECTION IN COORDINATION WITH THE EXHAUST STACK.

3. NO CONDENSATE BAFFLE AND NO GUTTER SHALL BE PROVIDED WITH KITCHEN HOOD

4. PROVIDE LED LIGHT FIXTURES

5. PROVIDE FAN AND LIGHT SWITCH LOCATED ON HOOD.

6. PROVIDE WITH END UTILITY CABINET PREPPED FOR A FIRE SUPPRESSION SYSTEM BUT EXCLUDE THE FIRE SYSEM COMPONENTS.

7. PROVIDE WITH EMERGENCY GAS SHUT-OFF VALVE COORDINATE INSTALLATION WITH ELECTRICAL CONTRACTOR AND PLUMBING CONTRACTOR.

FINNED TUBE HEATER SCHEDULE

MANUFACTURER

MARK EWT (F) EAT (F) BTU/FT RATING NUMBER OF PANELS LENGTH MOUNTING STYLE ACCESSORIES OR EQUIVALENT MODEL REMARKS

R3F-2 120 65 541 2-FINNED ROWS SEE PLANS FOR LENGTH HORIZONTAL WALL REFER TO PLANS RUNTAL R3F-2 1,2,3,4

R3F-5 120 65 828 5-FINNED ROWS SEE PLANS FOR LENGTH HORIZONTAL WALL REFER TO PLANS RUNTAL R3F-5 1,2,3,4

R3F-6 120 65 1145 6-FINNED ROWS SEE PLANS FOR LENGTH HORIZONTAL WALL REFER TO PLANS RUNTAL R3F-6 1,2,3,4

REMARKS:

1. PROVIDE HIGH PRESSURE 128 PSI PANELS, TEST PRESSURE 184 PSI

2. PROVIDE A METAL COLOR CHIP CHART FROM THE MANUFACTURER TO FACILITATE ARCHITECT COLOR SELECTION

3. PROVIDE WITH APPROPRIATE WALL MOUNTING BRACKETS, AIR VENT, 3/4" PIPING CONNECTIONS

4. REFER TO THE PLANS FOR PIPING CONFIGURATION AND ACCESSORIES REQUIREMENTS

WATER -TO-WATER HEAT PUMP SCHEDULE

COOLING PERFORMANCE HEATING PERFORMANCE WATER FLOW ELECTRICAL MANUFACTURER

EVAP. COIL EVAP. COIL SYSTEM TOTAL EVAP. COIL EVAP. COIL SYSTEM LOAD SYSTEM COND OR

MARK AREA SERVED EWT LWT EWT (MBH) EWT LWT EWT (MBH) GPM WPD (FT) MEDIUM GPM MEDIUM REFIRGERANT V / P / HZ MCA MOCP COMP EQUIVALENT MODEL REMARKS

WWHP-1 PERIMETER HEATING 55 45.2 85 117.8 110.0 120 50 132.8 24 7.4 TREATED WATER 24 HEAT PUMP LOOP WATER (45F-85F) R410A 208 / 3 / 60 43.2 60 2 FLORIDA WW122 1,2,3,4,5

WWHP-2 PERIMETER HEATING 55 45.2 85 117.8 110.0 120 50 132.8 24 7.4 TREATED WATER 24 HEAT PUMP LOOP WATER (45F-85F) R410A 208 / 3 / 60 43.2 60 2 FLORIDA WW122 1,2,3,4,5

WWHP-3 PERIMETER HEATING 55 45.2 85 117.8 110.0 120 50 132.8 24 7.4 TREATED WATER 24 HEAT PUMP LOOP WATER (45F-85F) R410A 208 / 3 / 60 43.2 60 2 FLORIDA WW122 1,2,3,4,5

REMARKS:

1. PROVIDE FIVE YEAR COMPRESSOR WARRANTY

2. SEE HOSE KIT SCHEDULE FOR VALVE AND HOSE KIT ACCESSORIES

3. PROVIDE LOW TEMPERATURE FREEZE PROTECTION

4. PROVIDE CONTROL SYSTEM COMPATIBLE WITH BUILDING MANAGEMENT SYSTEM INTEGRATION TO INCLUDE A NETWORK CARD OR EQUAL.

5. THE WATER TO WATER HEAT PUMPS TO BE DISABLED AT A SET AMBIENT TEMPERATURE, SEE SEQUENCE OF OPERATIONS.

#SHEET HISTORY:

?

? - #

Lincoln, Nebraska

1010 Lincoln Mall, Suite 200

Lincoln, NE 68508-2883

402 477.9291 Fax 402 477.6542

Kansas City, Missouri

Fairway, Kansas

Landscape Architecture

www.clarkenersen.com

Architecture

EngineeringInteriors

Plo

t Ti

me

Sta

mp

:

File

Lo

ca

tio

n/N

am

e:

ISSUED

3/1

7/2

01

7 1

1:4

4:0

0 A

M

C:\

(1)

Re

vit

Pro

jec

ts\

20

17

\0

67

00

1-R

CH

Q-M

-17

_p

ete

.uh

ing

@c

lark

en

ers

en

.co

m.r

vt

Mechanical Schedules

M7.02

TCEP No.: 067-001-16

8800 Firethorn LaneLincoln, Nebraska

Plaza on the Green

March 10, 2017

03/10/2017 AS PER CONSTRUCTION DOC.A - 01 03/16/2017 ADDENDUM #01

A - 02 03/23/2017 ADDENDUM #02

02A

Page 44: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

F

MECH.

P1

S2

S3

S3

S3

S2

S5

S5

S5

S2

S2

S2A

S2A

S2

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

VIA 'C1'4

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

UGE

VIA 'C3'42

3

3

3

3

3

BA-10VIA 'C1'4

3

UGE

UGE

UGEUGE

UGE

UGE

5

5

5

BA-8

J61A-11,13

TUGE

7

UGEM

9

8

S1

S1

S1

S1

S1

S1

S1

S1

S1

S1

S1

S1

S1

S1 S1

S1

S1

M

10

10

UGT

UGT

UGT

11

12

13

13

UGE

J

J MM

MM

MM

MM

UGE

UGE

UGE

UGE

UGE

UGE

VIA 'C1'4 BA-33

A2

14

14

LL LL

Lincoln, NE 68508-2883

Kansas City, Missouri

402 477.9291 Fax 402 477.6542

www.clarkenersen.com

1010 Lincoln Mall, Suite 200

Landscape Architecture

Lincoln, Nebraska

InteriorsEngineering

Architecture

Fairway, Kansas

TCEP No.:

3 /

21 /

201

7 1

1:31

:21

AM

Plot

Tim

e St

amp:

\\Tc

ep-ln

-srv

-004

\000

-099

\067

-001

-16

Runz

a C

orp

HQ\3

) Act

ive

Wor

k\3)

Aut

oCA

D\06

7001

-E00

1.dw

gFi

le L

ocat

ion/

Nam

e:

Plaza on the Green8800 Firethorn LaneLincoln, Nebraska

067-001-16

ISSUED

#?

? - # SHEET HISTORY:

Electrical Site Utilities Plan

E0.01

March 10, 2017

03/10/2017 CONSTRUCTION DOCUMENTS

ELECTRICAL SITE UTILITIES PLANSCALE: 1"=20'-0"

ELECTRICAL SITE UTILITIES PLAN NOTES

KEY NOTE DESCRIPTION

POST-INDICATOR VALVE. COORDINATE FIRE ALARM CONNECTIONS TO THE PIV WITH THE MECHANICALCONTRACTOR.

1

2

3

4

ROUTE CIRCUIT VIA 20A, 1POLE, CIRCUIT BREAKER IN LIGHTING INVERTER (INV). SEE THE LOWER LEVEL LIGHTINGPLAN FOR ADDITIONAL INFORMATION.WALL MOUNT SO CENTER OF FIXTURE IS 6" BELOW WALL CAP.

ROUTE #10'S THROUGHOUT ENTIRE CIRCUIT.

5 INSTALL TRANSFORMER FOR LIGHT FIXTURES, IN WATERPROOF IN-GRADE BOX, NEAR THIS LOCATION.

6 ELECTRIC VEHICLE CHARGING STATION (SCHNEIDER ELECTRIC #EV230PDR). COORDINATE ALL INSTALLATIONDETAILS WITH THE CHARGING STATION MANUFACTURER. ROUTE (2) #8'S & (1) #10 GROUND IN A 3/4" CONDUIT.PROVIDE CONCRETE BASE.

APPROXIMATE LOCATION OF LOWER LEVEL ELECTRICAL ROOM AND SECONDARY ROUTING. SEE THE ELECTRICALONE LINE DIAGRAM FOR NUMBER OF CONDUIT/ CONDUCTORS. SEE THE TRANSFORMER PAD DETAIL FORADDITIONAL INFORMATION.

7

ROUTING OF PRIMARY CONDUIT/CONDUCTORS. COORDINATE WORK WITH ELECTRICAL UTILITY (LES).8

SECONDARIES TO RUN THROUGH METER/CT CABINET. SEE THE ELECTRICAL ONE LINE DIAGRAM FOR ADDITIONALINFORMATION.

9

INSTALL POLE BASE IN THIS LOCATION SO THAT THE TOP IF 12" ABOVE FINISH GRADE.10

STUB UP LOCATION OF THE INCOMING 4 - 4" TELECOM SERVICE ENTRANCE CONDUITS. SEE SHEET E0.02 FOREXACT LOCATION WITHIN THE BUILDING.

INSTALL A 24"X36" QUAZITE PULLBOX CATALOG NUMBER: PG2436BA42, PROVIDED WITH COVER: PG2436CG00, ORENGINEER APPROVED EQUAL. INSTALL THE 4 - 4" CONDUITS FROM THE BUILDING AND THE 4 -4" CONDUITSROUTED FROM THE SITE TO THIS LOCATION. BUSH CONDUIT ENDS AND PROVIDE PULLSTINGS IN ALL CONDUITS.

ROUTE 4 - 4" CONDUITS FROM THE QUAZITE PULLBOX OUT TO THE PROPERTY LINE, CAP AND MARK THISLOCATION. FOR USE BY THE TELECOM SERVICE PROVIDERS.

SEE THE LANDSCAPE PLANS (MONUMENT SIGN DETAIL) FOR EXACT FIXTURE QUANTITY AND MOUNTINGINFORMATION.

11

12

13

14

A2

-A 002 03/21/2017 AS PER ADDENDUM #002

AutoCAD SHX Text
T
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
T
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
T
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
AutoCAD SHX Text
P
AutoCAD SHX Text
C
Page 45: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

LIGHTING FIXTURE SCHEDULE

FixtureManufacturers Catalog Numbers Description

LampType

Volt VA Mounting RemarksType

A

FOCAL POINT FSM4BS-FLFL-375DN-1000UP-35K-120-LD1-C24-WH

4" PENDANTFIXTURE

LED 120 16W/FT PENDANT

PENDANT MOUNT FIXTURE 18"FROM BOTTOM OF CEILING

UNLESS OTHERWISE NOTED.PROVIDE FIXTURES IN LENGTHS

SHOWN ON DRAWINGS. PROVIDEFIXTURE TYPE 'A1' WITH

EMERGENCY BATTERY DRIVER.

B

FOCAL POINT FSM4L-FL-375-35K-120-LD1-SPEC-WH

4" RECESSEDFIXTURE

LED 120 4W/FT RECESSED

COORDINATE FIXTURE TRIM WITHTHE EXACT CEILING TYPE IT IS TO

BE INSTALLED IN. PROVIDEFIXTURE IN LENGTHS SHOWN ON

THE DRAWINGS. PROVIDECORNER DETAIL AS NEEDED.

PROVIDE FIXTURE TYPE 'B1' WITHEMERGENCY BATTERY DRIVER.

C

WILLIAMS L45-L30C-8-35-CS-M-DRV-120

4.5"DOWNLIGHT

LED 120 35 RECESSED

COORDINATE FIXTURE TRIM WITHTHE EXACT CEILING TYPE IT IS TO

BE INSTALLED IN. PROVIDEFIXTURE TYPE 'C1' WITH

EMERGENCY BATTERY DRIVER.PROVIDE FIXTURE TYPE 'C2' WET

LOCATION LISTED.

D

WILLIAMS GL-4-L150-835-DRV-120

4' INDUSTRIAL LED 120 121 PENDANT

PENDANT MOUNT FIXTURE 18"FROM BOTTOM OF STRUCTURE.

PROVIDE FIXTURE TYPE 'D1' WITHEMERGENCY BATTERY DRIVER.

EXIT

WILLIAMS EXIT/CA-R-WF-WHT-EM-SDT

EXIT FIXTURE LED 120 5 SURFACESEE THE DRAWINGS FOR EXACT

MOUNTING TYPE.

G

WILLIAMS 50-G-S-2-4-L35-835-S-AF12125-DRV-120

RECESSED 2X4FIXTURE

LED 120 34 RECESSED

COORDINATE FIXTURE TRIM WITHTHE EXACT CEILING TYPE IT IS TO

BE INSTALLED IN. PROVIDEFIXTURE TYPE 'G1' WITH

EMERGENCY BATTERY DRIVER.

H

BARTCO BSS840-45/68/90+35+7+CM48+SIN+SA

PENDANTMOUNTEDFIXTURE

LED 120 7.4W/FT PENDANT

PROVIDE FIXTURE TYPE 'H1' WITHEMERGENCY BATTERY DRIVER.COORDINATE EXACT FIXTUREPOSITIONING AND MOUNTING

HEIGHT WITH THEARCHITECT/ENGINEER.

K

DUALLITE EV4RIWCEILING

MOUNTEDEMERGENCY

FIXTURE

LED 120 5 RECESSEDCONNECT FIXTURE SO THAT ITILLUMINATES UNDER A POWER

LOSS ONLY.

L1

TECH LIGHTING 700-TD-CLOP-M-W-R-S-LED830

PENDANTMOUNTEDFIXTURE

LED 120 7.5 PENDANT

PENDANT MOUNT SO BOTTOM OFFIXTURE IS 2'-0" BELOW CEILING

UNLESS OTHERWISE NOTED.LEAVE EXTRA CORD ABOVE THECEILING TO FACILITATE A LOWER

INSTALLATION.

L2

TECH LIGHTING 700-TD-CLOP-G-W-R-S-LED830

PENDANTMOUNTEDFIXTURE

LED 120 15 PENDANT

PENDANT MOUNT SO BOTTOM OFFIXTURE IS 2'-6" BELOW CEILING

UNLESS OTHERWISE NOTED.LEAVE EXTRA CORD ABOVE THECEILING TO FACILITATE A LOWER

INSTALLATION.

M

MOOI LIGHTING SMALL RANDOM LIGHT

DECORATIVEPENDANTFIXTURE

LED 120 11.3 PENDANTPENDANT MOUNT SO BOTTOM OFFIXTURE IS 3'-0" BELOW CEILING

UNLESS OTHERWISE NOTED.

N

TECH LIGHTING 700MRAG-W-S-LED927

PENDANTMOUNTEDFIXTURE

LED 120 174 PENDANTPENDANT MOUNT SO BOTTOM OFFIXTURE IS 11'-0" FROM BOTTOM

OF CEILING.

P

WILLIAMS L60-L30C-8-35-CS-M-DIM-120

RECESSED 6"DOWNLIGHT

LED 120 36 RECESSEDPROVIDE FIXTURE TYPE 'P1' WITHEMERGENCY BATTERY DRIVER.

Q

WILLIAMS 50-G/F-S-2-4-L35-835-S-AF12125-DRV-120

RECESSED 2X4FIXTURE

LED 120 34 RECESSEDCOORDINATE FIXTURE WITH

EXACT CEILING TYPE.

R

FOCAL POINT FSM4BS-FLFL-625DN-1000UP-35K-120-LD1-C24-WH

4" PENDANTFIXTURE

LED 120 17W/FT PENDANT

PENDANT MOUNT FIXTURE 18"FROM BOTTOM OF STRUCTUREUNLESS OTHERWISE NOTED.

PROVIDE FIXTURES IN LENGTHSSHOWN ON DRAWINGS. PROVIDE

FIXTURE TYPE 'R1' WITHEMERGENCY BATTERY DRIVER.

S1

BK LIGHTING UL-F-MM-LED-E72-ASY-BSP-12-11

RECESSEDWALL

MOUNTEDFIXTURE

LED 120 3 RECESSED

OMIT IN GRADE STABILITY FLANGE.FIXTURE TO BE CORED IN SIDE OF

CAST IN PLACE WALL. SEE THELANSCAPE PLANS FOR

INSTALLATION DETAIL. WALLMOUNT 12" AFG. UNLESS

OTHERWISE NOTED.

S2

AAL SLVT-T2-56LED-4K-DB-HSS-4"

POLEMOUNTED SITE

FIXTURELED 120 83

POLEMOUNTED

PROVIDE METAL COLOR SAMPLEWITH POLE SHOP DRAWING

SUBMITTALSTRUCTURA POLE: SPAR-S-18-50-40-S4-C6-T4004-STD

LIGHTING FIXTURE SCHEDULE

FixtureManufacturers Catalog Numbers Description

LampType

Volt VA Mounting RemarksType

S2A

AAL SLVT-T2-56LED-4K-DB-HSS-4"

POLEMOUNTED SITE

FIXTURELED 120 83

POLEMOUNTED

PROVIDE METAL COLOR SAMPLEWITH POLE SHOP DRAWING

SUBMITTALSTRUCTURA POLE: SPAR-S-18-50-40-S4-C6-T4004-STD

S3

AAL SLVT-T3-56LED-4K-DB-HSS-4"

POLEMOUNTED SITE

FIXTURELED 120 83

POLEMOUNTED

PROVIDE METAL COLOR SAMPLEWITH POLE SHOP DRAWING

SUBMITTALSTRUCTURA POLE: SPAR-S-18-50-40-S4-C6-T4004-STD

S5

AAL SLVT-T5-56LED-4K-DB-4"

POLEMOUNTED SITE

FIXTURELED 120 83

POLEMOUNTED

PROVIDE METAL COLOR SAMPLEWITH POLE SHOP DRAWING

SUBMITTALSTRUCTURA POLE: SPAR-S-18-50-40-S4-C6-T4004-STD

T

FOCAL POINT FSM2LW-FL-250LF-35K-120-LD1-WM-EC-WH

4' WALL MOUNTFIXTURE

LED 120 13WALL

MOUNTPROVIDE FIXTURE WITH

EMERGENCY BATTER DRIVER.

U

ELLIPTIPAR S132-M424-S-02-8-V0-0-00

WALL MOUNTFIXTURE

LED 120 57WALL

MOUNT

WALL MOUNT FIXTURE 2'-0" FROMCEILING ON ARCHITECTURAL

EYEBROW.

V

LUMENWERX VIAWETR-TMG-LED-80-500-35-*-120-D-

RECESSEDEXTERIORFIXTURE

LED 120 5.5W/FT RECESSEDPROVIDE FIXTURE IN LENGTHS ASNECESSARY TO FILL RUN SHOWN

ON DRAWINGS.

W

TECH LIGHTING 700-MP-PEL-W-S-LEDS830

PENDANTMOUNTEDFIXTURE

LED 120 12 PENDANT

PROVIDE ALL NECESSARYCOMPONENETS FOR AN

OPERATIONAL LIGHT FIXTURE.PENDANT MOUNT FIXTURE 6'-0"

AFF.

Y

WILLIAMS 75-4-L30-835-DIM-120

SURFACEMOUNTED

COVE FIXTURELED 120 23 SURFACE

SURFACE MOUNT LIGHTINGFIXTURES ON TOP OF CLOUD. SEETHE ARCHITECTURAL PLANS FOR

ADDITIONAL INFORMATION.

Z

INSIGHT MA-3.535KASY-D-FMC-96"-INT1-BO-S-VSSURFACEMOUNTED

ASYMETRICFIXTURE

LED 120 28 SURFACEAIM FIXTURE SO THAT THE WALL

LETTERING IS ILLUMINATED.

AA

FOCALPOINT FSM4AL-FL-275-35-120-LD1-*-WH-4'

RECESSEDWALL WASH

FIXTURELED 120 14 RECESSED

COORDINATE FIXTURE TRIM WITHTHE EXACT CEILING TYPE IT IS TO

BE INSTALLED IN.

BB

MCGRAW EDISON TT-C3-LED-E1-WQ

PARKINGGARAGEFIXTURE

LED 120 45 PENDANT

PENDANT MOUNT FIXTURE SOTHAT THE BOTTOM OF FIXTURE ISFLUSH WITH THE BOTTOM OF THEADJACENT STRUCTURAL BEAMS.

PROVIDE FIXTURE TYPE 'BB1' WITHWATSTOPPER (FS-355)OCCUPANCY SENSOR.

CC

DELRAY UC2/4/5-S-W35-SR-BDIM-W1

PENDANTMOUNTEDFIXTURE

LED 120 41/82/102 PENDANT

REMOTE MOUNT FIXTURE DRIVERSABOVE THE ACCESSIBLE CEILING

IN THE ADJACENT MEETING ROOM.FIXTURES TO BE PENDANT

MOUNTED AT VARIOUS HEIGHTS.COORDINATE EXACT HEIGHTS ANDPLACEMENT WITH THE ARCHITECT/

ENGINNER PRIOR TOINSTALLATION AS INDICATED ON

DRAWINGS.

DD

WINONA WFP6160-30DIA-CARSTEN-LDP1A-35K-MVOLT-ID-OAE-BA

PEDNANTMOUNTEDFIXTURE

LED 120 64 PENDANTPENDANT MOUNT SO BOTTOM OFFIXTURE IS 2'-0" BELOW CEILING.

GG

LBL LIGHTING HPTEL-SC-LED830MPT

WALL MOUNTFIXTURE

LED 120 6WALL

MOUNTWALL MOUNT FIXTURE 8'-0" AFF.

HH

DUALLITE PG-Z-HTR

WALL MOUNTEMERGENCY

FIXTURELED 120 16

WALLMOUNT

WALL MOUNT FIXTURE 9'-0" AFF.UNLESSOTHERWISE NOTED.

KK

LUSIO LW-LUSIO-WD-2M-NW-LRFRAC-120

4' LED FIXTURE6,000

NOMINALLUMEN LED

120 60 SURFACE

WET LOCATION LISTED.COORDINATE EXACT MOUNTING

LOCATIONS WITH THE ELEVATORSUPPLIER/INSTALLER.

LL

ILIGHT T-24-W35-S-CL W L

LED ACCENTFIXTURE

LED 120 4 W/FT SURFACEFIXTURE TO BE MOUNTED BEHIND

SIGN PLATE.

MM

KIM EL218F5-8L3K-UV-FL-FH215-EP17

LEDFLOODLIGHT

LED 120 16 POST

MOUNT AND AIM FIXTURE TO LIGHTTENNENT AREA OF SIGN.

COORDINATE AIMING DETAILSWITH ENGINEER.

#SHEET HISTORY:

?

? - #

Lincoln, Nebraska

1010 Lincoln Mall, Suite 200

Lincoln, NE 68508-2883

402 477.9291 Fax 402 477.6542

Kansas City, Missouri

Fairway, Kansas

Landscape Architecture

www.clarkenersen.com

Architecture

EngineeringInteriors

Plo

t Ti

me

Sta

mp

:

File

Lo

ca

tio

n/N

am

e:

ISSUED

3/2

1/2

01

7 1

1:1

9:1

0 A

M

C:\

(1)

Re

vit

Pro

jec

ts\

20

17

\0

67

00

1-R

CH

Q-E

-17

_jk

rysl

.rv

t

Electrical Schedules

E5.01

TCEP No.: 067-001-16

8800 Firethorn LaneLincoln, Nebraska

Plaza on the Green

March 10, 2017

03/10/2017 CONSTRUCTION DOCUMENTS

A - 002 03/21/2017 ADDENDUM #002

002

A

Page 46: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

#SHEET HISTORY:

?

? - #

Lincoln, Nebraska

1010 Lincoln Mall, Suite 200

Lincoln, NE 68508-2883

402 477.9291 Fax 402 477.6542

Kansas City, Missouri

Fairway, Kansas

Landscape Architecture

www.clarkenersen.com

Architecture

EngineeringInteriors

Plo

t Ti

me

Sta

mp

:

File

Lo

ca

tio

n/N

am

e:

ISSUED

3/2

1/2

01

7 1

1:1

9:1

3 A

M

C:\

(1)

Re

vit

Pro

jec

ts\

20

17

\0

67

00

1-R

CH

Q-E

-17

_jk

rysl

.rv

t

Electrical Schedules

E5.02

TCEP No.: 067-001-16

8800 Firethorn LaneLincoln, Nebraska

Plaza on the Green

March 10, 2017

03/10/2017 CONSTRUCTION DOCUMENTS

Total Est. Demand: 79 A

MECH 8675 VA 100.00% 8675 VA Total Est. Demand: 28428 VA

LTG 6402 VA 125.00% 8003 VA Total Conn. Load: 24477 VA

RCPT 9400 VA 125.00% 11750 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 92 A 81 A

Total Load: 10426 VA 9085 VA

41 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 42

39 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 40

37 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 38

35 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 36

33 20 A 1 LTG SIGN LIGHTS 278 VA / 0 VA Spare 1 20 A 34

31 20 A 1 MECH UH-4 756 VA / 722 VA MECH UH-3 1 20 A 32

29 20 A 1 MECH UH-1 756 VA / 756 VA MECH UH-5 1 20 A 30

27 20 A 1 MECH UH-8 687 VA / 756 VA MECH UH-2 1 20 A 28

25 20 A 1 MECH UH-6 687 VA / 687 VA MECH UH-7 1 20 A 26

23 20 A 1 RCPT Room 123 400 VA / 687 VA MECH. 118 UH-9 1 20 A 24

21 -- -- -- 576 VA / 500 VA RCPT DATA / ELEC. 102 FACP 1 20 A 22

19 -- -- -- 576 VA / 200 VA RCPT MECH. 123 1 20 A 20

17 20 A 3 MECH MECH. 123 GEF-1 576 VA / 444 VA MECH MECH. 123 GEF-2 1 20 A 18

15 20 A 1 MECH. 123 SMP-2 2256 VA / 1768 VA -- -- -- 16

13 20 A 1 RCPT 200 VA / 1768 VA MECH. 123 SMP-1 2 35 A 14

11 20 A 1 LTG DATA / ELEC. 102 INVERTER 750 VA / 216 VA CUH-1 1 20 A 12

9 20 A 1 LTG DATA / ELEC. 102 C3 500 VA / 30 VA LTG BACK WALL 1 20 A 10

7 20 A 1 RCPT Room 117, 119, 102, 118 1400 VA / 1011 VA LTG PARKING LOT 1 20 A 8

5 20 A 1 RCPT GF-1 200 VA / 180 VA LTG C1 1 20 A 6

3 20 A 1 LTG Room 117 1234 VA / 500 VA RCPT LEASABLE AREA 117 CARD ACCESS 1 20 A 4

1 20 A 1 LTG Room 102, 101A, 117, 119 1204 VA / 1215 VA LTG Room 118, 117 1 20 A 2

CKT Rating Poles Load Name

A B C

Load Name Poles Rating CKT

Enclosure: LIGHTING &... MCB Rating: Main Lug Only (MLO)

Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: MDP Phases: 3

Location: DATA / ELEC. 102 Volts: 120/208 Wye A.I.C. Rating: 65,000

Branch Panel: BA

Total Est. Demand: 56 A

MECH 5812 VA 100.00% 5812 VA

LTG 2943 VA 125.00% 3679 VA Total Est. Demand: 20021 VA

RCPT 8400 VA 125.00% 10500 VA Total Conn. Load: 17185 VA

Other 30 VA 100.00% 30 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 54 A 49 A

Total Load: 6413 VA 5753 VA

41 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 42

39 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 40

37 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 38

35 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 36

33 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 34

31 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 32

29 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 30

27 -- -- -- 853 VA / 0 VA Spare 1 20 A 28

25 15 A 2 CHP-2 853 VA / 853 VA -- -- -- 26

23 20 A 1 RCPT ALCOVE 105 (GFI BREAKER) 600 VA / 853 VA CHP-3 2 15 A 24

21 20 A 1 MECH MEN 107 600 VA / 600 VA MECH MEN 107 1 20 A 22

19 20 A 1 MECH WOMEN 108 600 VA / 600 VA MECH WOMEN 108 1 20 A 20

17 20 A 1 RCPT 600 VA / 200 VA RCPT 1 20 A 18

15 20 A 1 RCPT 200 VA / 200 VA RCPT 1 20 A 16

13 20 A 1 LTG 180 VA / 1227 VA Room 113, 109, 105, 107, 108, 104 1 20 A 14

11 20 A 1 RCPT Room 108, 107 800 VA / 1166 VA LTG Room 111, 112 1 20 A 12

9 20 A 1 RCPT Room 113, 104, 117 1200 VA / 500 VA RCPT VEST. 110 CARD ACCESS 1 20 A 10

7 20 A 1 RCPT 600 VA / 500 VA RCPT CORRIDOR 113 CARD ACCESS 1 20 A 8

5 20 A 1 RCPT 400 VA / 400 VA RCPT 1 20 A 6

3 20 A 1 Power CONFERENCE ROOM 114 600 VA / 1000 VA RCPT Room 114 1 20 A 4

1 20 A 1 RCPT 500 VA / 500 VA RCPT 1 20 A 2

CKT Rating Poles Load Name

A B C

Load Name Poles Rating CKT

Enclosure: LIGHTING &... MCB Rating: Main Lug Only (MLO)

Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: MDP Phases: 3

Location: MECH. 112 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: BB

Total Est. Demand: 115 A

Total Est. Demand: 41318 VA

MECH 28609 VA 100.00% 28609 VA Total Conn. Load: 38943 VA

RCPT 10334 VA 122.98% 12709 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 112 A 111 A

Total Load: 13344 VA 13224 VA

41 -- -- Space 0 VA / 0 VA Space -- -- 42

39 -- -- Space 0 VA / 0 VA Space -- -- 40

37 -- -- Space 0 VA / 0 VA Space -- -- 38

35 -- -- Space 0 VA / 0 VA Space -- -- 36

33 -- -- Space 0 VA / 0 VA Space -- -- 34

31 -- -- Space 0 VA / 0 VA Space -- -- 32

29 -- -- Space 0 VA / 0 VA Space -- -- 30

27 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 28

25 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 26

23 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 24

21 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 22

19 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 20

17 20 A 1 RCPT KITCHEN 111 HEAT CAB 900 VA / 500 VA RCPT KITCHEN 111 HOOD LIGHTS 1 20 A 18

15 20 A 1 RCPT KITCHEN 111 REFRIGERATOR 1068 VA / 696 VA RCPT KITCHEN 111 PREP TABLE 1 20 A 16

13 20 A 1 RCPT KITCHEN 111 FREEZER 816 VA / 1068 VA RCPT KITCHEN 111 REFRIGERATOR 1 20 A 14

11 20 A 1 RCPT 1000 VA / 1000 VA RCPT 1 20 A 12

9 -- -- -- 5308 VA / 1643 VA -- -- -- 10

7 -- -- -- 5308 VA / 1643 VA RCPT KITCHEN 111 TOASTER 2 20 A 8

5 55 A 3 RCPT KITCHEN 111 FRYER 5308 VA / 3667 VA -- -- -- 6

3 -- -- -- 843 VA / 3667 VA -- -- -- 4

1 20 A 2 Power KITCHEN 111 843 VA / 3667 VA RCPT KITCHEN 111 OVEN 3 40 A 2

CKT Rating Poles Load Name

A B C

Load Name Poles Rating CKT

Enclosure: LIGHTING &... MCB Rating: Main Lug Only (MLO)

Mounting: RECESSED Wires: 4 Mains Rating: 225 A

Supply From: MDP Phases: 3

Location: KITCHEN 111 Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: K

Total Est. Demand: 41 A

MECH 216 VA 100.00% 216 VA Total Est. Demand: 14740 VA

RCPT 8340 VA 125.00% 10425 VA Total Conn. Load: 11835 VA

LTG 3279 VA 125.00% 4099 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 50 A 15 A

Total Load: 5612 VA 1794 VA

83 -- -- Space 0 VA / 0 VA Space -- -- 84

81 -- -- Space 0 VA / 0 VA Space -- -- 82

79 -- -- Space 0 VA / 0 VA Space -- -- 80

77 -- -- Space 0 VA / 0 VA Space -- -- 78

75 -- -- Space 0 VA / 0 VA Space -- -- 76

73 -- -- Space 0 VA / 0 VA Space -- -- 74

71 -- -- Space 0 VA / 0 VA Space -- -- 72

69 -- -- Space 0 VA / 0 VA Space -- -- 70

67 -- -- Space 0 VA / 0 VA Space -- -- 68

65 -- -- Space 0 VA / 0 VA Space -- -- 66

63 -- -- Space 0 VA / 0 VA Space -- -- 64

61 -- -- Space 0 VA / 0 VA Space -- -- 62

59 -- -- Space 0 VA / 0 VA Space -- -- 60

57 -- -- Space 0 VA / 0 VA Space -- -- 58

55 -- -- Space 0 VA / 0 VA Space -- -- 56

53 -- -- Space 0 VA / 0 VA Space -- -- 54

51 -- -- Space 0 VA / 0 VA Space -- -- 52

49 -- -- Space 0 VA / 0 VA Space -- -- 50

47 -- -- Space 0 VA / 0 VA Space -- -- 48

45 -- -- Space 0 VA / 0 VA Space -- -- 46

43 -- -- Space 0 VA / 0 VA Space -- -- 44

41 -- -- Space 0 VA / 0 VA Space -- -- 42

39 -- -- Space 0 VA / 0 VA Space -- -- 40

37 -- -- Space 0 VA / 0 VA Space -- -- 38

35 -- -- Space 0 VA / 0 VA Space -- -- 36

33 -- -- Space 0 VA / 0 VA Space -- -- 34

31 -- -- Space 0 VA / 0 VA Space -- -- 32

29 -- -- Space 0 VA / 0 VA Space -- -- 30

27 -- -- Space 0 VA / 0 VA Space -- -- 28

25 -- -- Space 0 VA / 0 VA Space -- -- 26

23 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 24

21 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 22

19 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 20

17 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 18

15 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 16

13 -- -- -- 3120 VA / 0 VA Spare 1 20 A 14

11 40 A 2 RCPT EV CHARGING STATION 3120 VA / 400... RCPT 1 20 A 12

9 20 A 1 RCPT DATA / ELEC. 202 200 VA / 216 VA CUH-2 1 20 A 10

7 20 A 1 RCPT Room 205, 210 600 VA / 400 VA RCPT 1 20 A 8

5 20 A 1 ELEV. LOBBY 204 409 VA / 500 VA RCPT FRONT DOOR CARD ACCESS 1 20 A 6

3 20 A 1 LTG Room 205, 210 983 VA / 395 VA LTG Room 202, 101B 1 20 A 4

1 20 A 1 LTG Room 205 625 VA / 867 VA LTG Room 205 1 20 A 2

CKT Rating Poles Load Name

A B C

Load Name Poles Rating CKT

Enclosure: LIGHTING &... MCB Rating: Main Lug Only (MLO)

Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: DP1 Phases: 3

Location: DATA / ELEC. 202 Volts: 120/208 Wye A.I.C. Rating: 42,000

Branch Panel: 1A

Total Est. Demand: 110 A

Total Est. Demand: 39586 VA

RCPT 37700 VA 79.08% 29813 VA Total Conn. Load: 45519 VA

LTG 7819 VA 125.00% 9774 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 131 A 126 A

Total Load: 15677 VA 15073 VA

83 -- -- Space 0 VA / 0 VA Space -- -- 84

81 -- -- Space 0 VA / 0 VA Space -- -- 82

79 -- -- Space 0 VA / 0 VA Space -- -- 80

77 -- -- Space 0 VA / 0 VA Space -- -- 78

75 -- -- Space 0 VA / 0 VA Space -- -- 76

73 -- -- Space 0 VA / 0 VA Space -- -- 74

71 -- -- Space 0 VA / 0 VA Space -- -- 72

69 -- -- Space 0 VA / 0 VA Space -- -- 70

67 -- -- Space 0 VA / 0 VA Space -- -- 68

65 -- -- Space 0 VA / 0 VA Space -- -- 66

63 -- -- Space 0 VA / 0 VA Space -- -- 64

61 -- -- Space 0 VA / 0 VA Space -- -- 62

59 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 60

57 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 58

55 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 56

53 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 54

51 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 52

49 20 A 1 RCPT 500 VA / 800 VA RCPT Room 352, 351 1 20 A 50

47 20 A 1 RCPT OPEN OFFICE 343 500 VA / 1700 VA RCPT Room 347 1 20 A 48

45 20 A 1 RCPT Room 348 1900 VA / 1200 VA RCPT OFFICE 348 1 20 A 46

43 20 A 1 RCPT OFFICE 346 1200 VA / 1200 VA RCPT 1 20 A 44

41 20 A 1 RCPT OPEN OFFICE 343 500 VA / 1000 VA RCPT SERVER 333 L5-20R 1 20 A 42

39 20 A 1 RCPT SERVER 333 L5-20R 1000 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 40

37 20 A 1 RCPT SERVER 333 600 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 38

35 30 A 1 RCPT SERVER 333 L5-30R 1000 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 36

33 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 34

31 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 32

29 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 30

27 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 1000 VA RCPT OPEN OFFICE 343 FLOOR BOX 1 20 A 28

25 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 1200 VA RCPT Room 344, 345 1 20 A 26

23 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 1000 VA RCPT Room 354, 353, 352 1 20 A 24

21 20 A 1 RCPT Room 342 1700 VA / 1200 VA RCPT OFFICE 340 1 20 A 22

19 20 A 1 RCPT 1200 VA / 1100 VA RCPT Room 340 1 20 A 20

17 20 A 1 RCPT OFFICE 332 1700 VA / 1200 VA RCPT OFFICE 341 1 20 A 18

15 20 A 1 RCPT OFFICE 330 1200 VA / 0 VA C2 1 20 A 16

13 20 A 1 RCPT MOTHER'S 354 1000 VA / 778 VA LTG 1 20 A 14

11 20 A 1 RCPT Room 343 1200 VA / 600 VA RCPT 1 20 A 12

9 20 A 1 RECEPT MEETING 314 180 VA / 1000 VA RCPT SERVER 333 L5-30R 1 20 A 10

7 20 A 1 LTG 1036 VA / 600 VA RCPT 1 20 A 8

5 20 A 1 OPEN OFFICE 319A 669 VA / 1700 VA RCPT Room 330, 332 1 20 A 6

3 20 A 1 LTG OPEN OFFICE 343 1669 VA / 1024 VA LTG Room 339, 340, 341, 342 1 20 A 4

1 20 A 1 LTG Room 350, 351, 355, 356, 344 1606 VA / 857 VA LTG Room 353, 352, 334, 354, 358, 357,... 1 20 A 2

CKT Rating Poles Load Name

A B C

Load Name Poles Rating CKT

Enclosure: LIGHTING &... MCB Rating: Main Lug Only (MLO)

Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: DP2 Phases: 3

Location: DATA / ELEC. 302 Volts: 120/208 Wye A.I.C. Rating: 42,000

Branch Panel: 2A

Total Est. Demand: 105 A

MECH 4236 VA 100.00% 4236 VA Total Est. Demand: 37814 VA

RCPT 30992 VA 82.67% 25620 VA Total Conn. Load: 41594 VA

LTG 6366 VA 125.00% 7958 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 148 A 94 A

Total Load: 17577 VA 11275 VA

83 -- -- Space 0 VA / 0 VA Space -- -- 84

81 -- -- Space 0 VA / 0 VA Space -- -- 82

79 -- -- Space 0 VA / 0 VA Space -- -- 80

77 -- -- Space 0 VA / 0 VA Space -- -- 78

75 -- -- Space 0 VA / 0 VA Space -- -- 76

73 -- -- Space 0 VA / 0 VA Space -- -- 74

71 -- -- Space 0 VA / 0 VA Space -- -- 72

69 -- -- Space 0 VA / 0 VA Space -- -- 70

67 -- -- Space 0 VA / 0 VA Space -- -- 68

65 -- -- Space 0 VA / 0 VA Space -- -- 66

63 -- -- Space 0 VA / 0 VA Space -- -- 64

61 -- -- Space 0 VA / 0 VA Space -- -- 62

59 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 60

57 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 58

55 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 56

53 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 54

51 20 A 1 Spare 0 VA / 0 VA Spare 1 20 A 52

49 20 A 1 MECH CUST. 307 180 VA / 500 VA RCPT MEETING 315 1 20 A 50

47 20 A 1 MECH WOMEN 306 600 VA / 600 VA MECH MEN 305 1 20 A 48

45 20 A 1 MECH MEN 305 600 VA / 600 VA MECH WOMEN 306 1 20 A 46

43 20 A 1 LTG Room 315, 314, 347, 346, 348, 349,... 1346 VA / 899 VA LTG Room 312, 322, 323, 324, 325 1 20 A 44

41 20 A 1 ELEV. LOBBY 304 1289 VA / 187 VA LTG STAIR 303A 1 20 A 42

39 20 A 1 LTG Room 309, 318, 308, 310 1037 VA / 538 VA LTG Room 306, 305 1 20 A 40

37 20 A 1 RCPT BREAKROOM 318 DISHWASHER 600 VA / 2856 VA RCPT BREAKROOM 318 DISPOSAL 1 20 A 38

35 20 A 1 RCPT BREAKROOM 318 200 VA / 200 VA RCPT 1 20 A 36

33 20 A 1 RCPT BREAKROOM 318 400 VA / 200 VA RCPT BREAKROOM 318 1 20 A 34

31 20 A 1 RCPT BREAKROOM 318 400 VA / 2496 VA -- -- -- 32

29 20 A 1 RCPT Room 318 600 VA / 2496 VA RCPT BREAKROOM 318 ESSPRESSO 2 30 A 30

27 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 28

25 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 26

23 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 24

21 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 22

19 20 A 1 RCPT OPEN OFFICE 319A FLOORBOX 500 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 20

17 20 A 1 RCPT OFFICE 322 1200 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 18

15 20 A 1 RCPT OFFICE 323 1200 VA / 500 VA RCPT OPEN OFFICE 319A FLOORBOX 1 20 A 16

13 20 A 1 RCPT Room 324 1700 VA / 1300 VA RCPT Room 323, 322 1 20 A 14

11 20 A 1 RCPT Room 312 1100 VA / 1200 VA RCPT 1 20 A 12

9 20 A 1 RCPT WORKROOM 312 1100 VA / 1200 VA RCPT 1 20 A 10

7 20 A 1 RCPT RECEPTION FLOOR BOX 500 VA / 1300 VA RCPT WORKROOM 312 1 20 A 8

5 20 A 1 LTG Room 319A, 325 1070 VA / 500 VA RCPT RECEPTION FLOOR BOX 1 20 A 6

3 20 A 1 RCPT MEETING 314 1200 VA / 700 VA RCPT Room 315, 314 1 20 A 4

1 20 A 1 RCPT Room 306, 305 1000 VA / 500 VA RCPT FRONT CARD ACCESS 1 20 A 2

CKT Rating Poles Load Name

A B C

Load Name Poles Rating CKT

Enclosure: LIGHTING &... MCB Rating: Main Lug Only (MLO)

Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: DP2 Phases: 3

ELECTRICAL 310 Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: 2B

A - 002 03/21/2017 ADDENDUM #002

002

A

Page 47: 8800 Firethorn Lane - clarkenersen.com No. 2 with...6. NFPA 105 - Installation of Smoke Door Assemblies. 7. State Building Codes, Local Amendments. E. Standards: All hardware specified

LOADS SHOWN ON THIS RISER ARE FOR REFERENCE ONLY

SEE LIGHTING PLANS AND FIXTURE SCHEDULE FOR ACTUAL LOADS

LIN

E V

OLT

AG

E S

WIT

CH

TE

RM

INA

LS

1-4

0-10V CURRENT SINK DIMMING TERMINALS

LIN

E V

OLT

AG

E S

WIT

CH

TE

RM

INA

LS

5-8

CRESNET CTRL SYS INPUT

CRESNET LOCAL NET OUTPUT OCCUPANCY SENSORS

PHOTOCELLS

RJ45NET

CONN.

SETUP CONTROLS

USBCONN.

GLPAC-DIMFLV4 (DIM1) & (DIM2)

TO BUILDING LAN (F.B.O)FOR INTERSYSTEM

ETHERNET COMMUNICATIONSREMOTE & LOCAL PROGRAM

UPLOADS

LIN

E V

OLT

AG

E S

WIT

CH

TE

RM

INA

LS

1-4

120 V

AC

120 V

AC

6 BUTTONSC2N-CBD-P-GRY-S

RS

C2N-CBD-P-GRY-S6 BUTTONS

RS

C2N-CBD-P-GRY-S6 BUTTONS

RS

C2N-CBD-P-GRY-S6 BUTTONS

RS

LOAD

SW H

-N

+

LOAD

SW H

-N

+

LOAD

SW H

-N

+

LOAD

SW H

-N

+

GLA-PWS50

120VPOWERFEED

GLS-PART-CN

PROVIDE NECESSARYWIRING AND CONNECTIONS

TO DIMMING SYSTEM.

OCCUPANCY SENSOR

OCCUPANCY SENSOR

PROVIDE ALL NECESSARYCONNECTIONS AND

COMPONENTS FOR A FULLYFUNCTIONING DIMMING

SYSTEM.

PROVIDE BUTTONS FORON/OFF CONTROL & DIM

UP/DOWN CONTROL OF EACHLIGHTING ZONE.

COORDINATE BUTTONLABELING WITH THE OWNERS

REPRESENTATIVE.

CRESTRON

NO. OF POLES

CONTACTOR SCHEDULE

DATA/ELEC. 102

DESIGNATION

C1

LOCATION SERVES CIRCUITS

4 20A

RATINGCONTACT

120

COILVOLTAGE

BA-7

CIRCUITCONTROL

P1/T1

CONTROLLEDBY

REMARKS

LIGHTING CONTROL DIAGRAM FOR ADDITIONAL

CONTINUOUS DUTY OPERATION. SEE EXTERIOR

PROVIDE CONTACTOR RATED FOR

INFORMATION

DATA/ELEC 302C2 4 20A 120 2A-16 P1/T2

LIGHTING CONTROL DIAGRAM FOR ADDITIONAL

CONTINUOUS DUTY OPERATION. SEE EXTERIOR

PROVIDE CONTACTOR RATED FOR

INFORMATION

PARKING LOT/LANDSCAPELIGHTING

EXTERIORBUILDINGLIGHTING

2A-132A-14

BA-8BA-10

DATA/ELEC 102C3 4 20A 120 BA-9 P1

LIGHTING CONTROL DIAGRAM FOR ADDITIONAL

CONTINUOUS DUTY OPERATION. SEE EXTERIOR

PROVIDE CONTACTOR RATED FOR

INFORMATION

EXTERIORBUILDINGLIGHTING

CIRCUIT VIA INVERTER.

BA-33

TIME CLOCK 'T1', INTERMATIC TYPE ET70115C,

CONTACTOR SCHEDULE FOROR EQUIVALENT. SEE

CIRCUIT. SEECONTACTOR SCHEDULE

120VAC LIGHTING

LIGHT FIXTURE,SEE LIGHTING PLANS

PHOTOCELL 'P1', INTERMATIC TYPEK4321C, OR EQUIVALENT. SEECONTACTOR SCHEDULE FOR

ADDITIONAL INFORMATION.

INFORMATIONFOR ADDITIONAL

LIGHTING CONTACTOR 'C 1' OR 'C2'SEE CONTACTOR SCHEDULE

SEE CONTACTORSCHEDULE

120VACCIRCUIT

ADDITIONAL INFORMATION.

C

BACKFILL SHALL NOT BE USED. MINIMUM OF 3500 PSI, 28 DAY TEST CONCRETE.

MINIMUM COMPACTION UNDER PAD SHALL BE 90% OF MAXIMUM DENSITY OF THEMATERIAL AS DETERMINED BY ASTM STANDARD METHOD D698-78. FROZEN

1

2

5

4

6

7

3

TRANSFORMER PAD DETAIL NOTES:

SEE THE SITE ELECTRICAL UTILITIES PLAN FOR ADDITIONAL INFORMATION.

LES.

AFTER CONCRETE HARDENS.

#5 REBAR REINFORCING RODS 8" ON CENTER

TWO 4" SCHEDULE 40 PVC 90° ELBOWS (48" RADIUS) SHALL BE STUBBED

OUT FROM THE PRIMARY COMPARTMENT AT A DEPTH OF 4'-0". LES WILL PROVIDETHE 90° ELBOWS, AND PLUGS. (ELBOW SAP MATERIAL 9710 PLUG SAP MATERIAL 9646,TO BE PICKED UP AT LES STOREROOM, 27TH AND FAIRFIELD ST.)STUB CONDUITS OUT OF TRANSFORMER PAD. COORDINATE EXACT DIRECTION WITH

LEAVE THIS AREA OPEN FOR CABLE ENTRANCE.

FINISH GRADE TO SLOPE AWAY FROM TRANSFORMER PAD.

TOP OF FOUNDATION TO BE SMOOTH, LEVEL AND CLEARED OF ALL FRAMING MATERIAL

SECONDARY CONDUITS, STUB 1" ABOVE PAD. SEE THE SITE ELECTRICAL UTILITIES PLAN

PROVIDE 1/4" BEVEL ON ALL EXPOSED EDGES.

AND ONE LINE DIAGRAM FOR EXACT NUMBER OF CONDUITS AND ADDITIONAL INFORMATION.

8

3"

1

60"

85"

PLUG ENDS2

12.5"

5 4

24" 12.5"

FINISHED GRADE

7 ,TYPICAL

3 6

COMPARTMENTPRIMARY SECONDARY

COMPARTMENT

7"18

"

78"

PLAN

ELEVATION

8

8"

85"

FRONT FACE OF TRANSFORMER PAD. SEE THE SITE ELECTRICAL UTILITIES PLAN FOR9

ADDITIONAL INFORMATION

9

TYPICAL BRANCHCIRCUIT CONDUIT

FEEDER CONDUIT

BONDING BUSHINGSOR GROUND WEDGESAS REQUIRED

EQUIPMENT BONDINGJUMPERS

METALLICCOLD WATER

PIPE

MAIN SERVICE GROUNDWIRE AND CONDUIT

INSULATEDNEUTRAL BUS

EQUIPMENTGROUND BUSGROUNDED TO

ENCLOSURE

ENCLOSURE FOR SAFETYSWITCH, CIRCUIT BREAKER,

PANELBOARD, SWITCHBOARDOR MOTOR CONTROL CENTER

DRIVEN GROUND RODS

10'-0" LONG, 3/4"~ COPPER CLADGROUND ROD EMBEDDED IN

MAINBONDING

JUMPER

MAIN SERVICE

ENTRANCEENCLOSURE

INSULATED

NEUTRAL BUS

EQUIPMENT

GROUND BUSBONDED TOENCLOSURE

DRIVEN GROUNDWIRE & CONDUIT

UTILITY CO.GROUND/NEUTRAL

MAIN SERVICECONDUIT

LEAVEACCESSIBLE

FOR GROUNDCONNECTION

(PHASE CONDUCTORS NOT SHOWN)

FLOOR SLAB

POLE BASE DETAIL NOTES:

1. FULLY COORDINATE INSTALLATION DETAILS WITH POLE MANUFACTURER.

6'-0

"

2'-0"

4"

42

" M

IN.

#3 TIES 12" O.C.

6 #4 EQUALLY SPACED

3000 PSI CONCRETE

FUSION WELD TO REBAR

RGS CONDUIT AND WIRE

PVC CONDUIT AND WIRE

CONDUIT ADAPTER

FINISH GRADE

RGS CONDUIT AND WIRE

1" CHAMFER ALL AROUND

GROUT AFTER LEVELING

HAZARD ZONE

CONDUIT PASSES THROUGH

SEAL-OFF EACH END IF

FIXTURE SCHEDULE)

SITE PLAN AND

LIGHT POLE (SEE

DRIVEN GROUND ROD

5/8" DIA. X 10'-0" LONG

POLE IF REQUIRED

CONDUIT TO NEXT

VERIFY W/POLE MAN

DOUBLE NUT LEVELING.

STEEL ANCHOR BOLTS.

4 EA., 1"X48" GALV.

PER MANUFACTURER

BOLTS SPACED

#10 AWG: BOND TO POLE

HANDHOLE

WEATHERPROOF

#SHEET HISTORY:

?

? - #

Lincoln, Nebraska

1010 Lincoln Mall, Suite 200

Lincoln, NE 68508-2883

402 477.9291 Fax 402 477.6542

Kansas City, Missouri

Fairway, Kansas

Landscape Architecture

www.clarkenersen.com

Architecture

EngineeringInteriors

Plo

t Ti

me

Sta

mp

:

File

Lo

ca

tio

n/N

am

e:

ISSUED

3/2

1/2

01

7 1

1:1

9:1

4 A

M

C:\

(1)

Re

vit

Pro

jec

ts\

20

17

\0

67

00

1-R

CH

Q-E

-17

_jk

rysl

.rv

t

Electrical Details

E6.01

TCEP No.: 067-001-16

8800 Firethorn LaneLincoln, Nebraska

Plaza on the Green

March 10, 2017

03/10/2017 CONSTRUCTION DOCUMENTS

DIMMING SYSTEM RISER DIAGRAM

EXTERIOR LIGHTING CONTROL DIAGRAM

TRANSFORMER PAD DETAIL

SERVICE ENTRANCE GROUND CONNECTIONS DETAIL

A - 002 03/21/2017 ADDENDUM #002

POLE BASE DETAIL

002A